Fujitsu AS*G09LTCB, AS*G14LTCB, AO*G09LTCN, AO*G12LTCN, AS*G12LTCB Service Instructions Manual

...
SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
type
Models Indoor unit Outdoor unit
INVERTER
SERVICE
R410A
AS*G09LTCB AS*G12LTCB AS*G14LTCB
AO*G09LTCN AO*G12LTCN AO*G14LTCN
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION................................................................................................
3. DRY OPERATION.........................................................................................................
2. HEATING OPERATION.................................................................................................
5. INDOOR FAN CONTROL..............................................................................................
4. AUTO CHANGEOVER OPERATION............................................................................
7. LOUVER CONTROL.....................................................................................................
6. OUTDOOR FAN CONTROL..........................................................................................
9. TIMER OPERATION CONTROL...................................................................................
8. COMPRESSOR CONTROL..........................................................................................
11. TEST OPERATION CONTROL...................................................................................
10. ELECTRONIC EXPANSION VALVE CONTROL........................................................
13. FOUR-WAY VALVE EXTENSION SELECT................................................................
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST ).................................
15. MANUAL AUTO OPERATION ( Indoor unit body operation ).....................................
14. AUTO RESTART.........................................................................................................
16. FORCED COOLING OPERATION..............................................................................
17. COMPRESSOR PREHEATING..................................................................................
19. ECONOMY OPERATION............................................................................................
21. OUTDOOR UNIT LOW NOISE OPERATION..............................................................
20.
HUMAN SENSOR CONTROL.....................................................................................
01-01
01-02
01-02
01-03
01-04
01-06
01-07
01-08
01-09
01-12
01-12
01-12
01-13
01-13
01-13
01-14
01-14
18. 10°C HEAT OPERATION............................................................................................ 01-14
01-14
01-15
22. POWERFUL OPERATION.......................................................................................... 01-15
23. BASE HEATER OPERATION..................................................................................... 01-15
25. OFF DEFROST OPERATION CONTROL...................................................................
24.
DEFROST OPERATION CONTROL........................................................................... 01-16
01-18
26. VARIOUS PROTECTIONS.......................................................................................... 01-19
01-12
3. APPENDING DATA
3-1 FUNCTION SETTING.................................................................................................
3-1-1 INDOOR UNIT....................................................................................................
3-1-2 Procedures to change the Function Setting for wireless RC..............................
03-01
03-01
03-03
3-2 Thermistor Resistance Values.....................................................................................
3-2-1 INDOOR UNIT....................................................................................................
3-2-2 OUTDOOR UNIT................................................................................................
03-05
03-05
03-05
2. TROUBLE SHOOTING
2-1 ERROR DISPLAY.......................................................................................................
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY.....................
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION).....................................
2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE.....................................................
02-01
02-01
02-02
02-03
02-25
2-4 SERVICE PARTS INFORMATION.............................................................................. 02-30
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
WALL MOUNTED type
INVERTER
( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
Minimum frequency
Maximum frequency
Maximum frequency
AS*G09LTCB AS*G12LTCB AS*G14LTCB
18rps 15rps
76rps
12rps 63rps
57rps
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Indoor fan mode
Me Lo Quiet
A zone 96rps 61rps 51rps 33rps
B zone 96rps 61rps 51rps 33rps
C zone 96rps 61rps 51rps 33rps
AS*G09LTCB
D zone 57rps 42rps 36rps 27rps
E zone 57rps 42rps 36rps 27rps
F zone 57rps 42rps 36rps 27rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +2°C to -2.5°C of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature, the compressor will be stopped.
AS*G12LTCB
AS*G14LTCB
A zone 76rps 45rps 37rps 29rps
B zone 76rps 45rps 37rps 29rps
C zone 76rps 45rps 37rps 26rps
D zone 43rps 35rps 26rps 20rps
E zone 51rps 37rps 31rps 22rps
F zone 51rps 37rps 31rps 22rps
A zone 91rps 44rps 34rps 24rps
B zone 91rps 44rps 34rps 24rps
C zone 72rps 34rps 24rps
D zone 52rps 30rps 21rps 18rps
E zone 63rps 34rps 27rps 19rps
F zone 63rps 34rps 27rps 19rps
44rps
Outdoor temperature drops
Outdoor temperature rises
( Table 2 : Limit of maximum speed based on outdoor temperature )
96rps 76rps 91rps
Outdoor temp. zone
Hi
* If the room temperature is 2°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
* If the room temperature is lower by 3°C than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is some degrees higher than a set temperature, the compressor will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature, the compressor frequency is controlled within the range shown in Table 3. However, the maximum frequency is limited shown in Table 4 based on the fan mode.
( Table 3 : Compressor frequency range )
01-02
Minimum frequency
Maximum frequency
AS*G09LTCB 18rps 130rps
AS*G12LTCB
16rps
119rps
AS*G14LTCB
16rps 140rps
3. DRY OPERATION
The compressor frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 4. However, after the compressor is driven, the indoor unit shall run at operation frequency of 61rps (09LTCB), 51rps (12LTCB), 52rps (14LTCB) for 60 seconds.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table 4 : Compressor frequency in Dry mode)
( Fig.2 : Compressor control based on room temperature )
Operating frequency
33rps
25rps
0rps
09LTCB
X zone
J zone
Y zone
Operating frequency
J zone
Y zone
X zone 26rps
18rps
0rps
12LTCB
Operating frequency
J zone
Y zone
X zone 24rps
16rps
0rps
14LTCB
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
4. AUTO CHANGEOVER OPERATION
01-03
(Fig. 3 : Operation flow chart in Auto changeover)
START
Room temp.
Room temp.
>Ts+2°C ?
COOLING OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
NO
YES
YES
TS : Setting temperature
<Ts- 2°C ?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
YES
YES
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the Heating, Cooling, Dry and Monitoring modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs. When fan mode is set at [Auto], it operates on [Me] fan Speed.
01-04
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Figure4. On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool] operation modes Quiet, Lo, Me, Hi, as shown in Table 5.
( Fig.4 : Airflow change - over ( Cooling : Auto ) )
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C =
Hi mode
Me mode
Lo mode
1. Fan speed
( Table 5 : Indoor fan speed )
Operation mode Air flow mode
Speed (rpm)
Cooling/ Fan
Heating
Dry
X zone: 650
J zone: 610
X zone: 650
J zone: 610
X zone: 740
J zone: 710
AS*G09LTCB AS*G12LTCB AS*G14LTCB
4. DRY OPERATION
Refer to the Table 5. During the dry mode operation, the fan speed setting can not be changed.
Hi
Hi
Me+
Me
Me
Lo
Lo
Quiet
Quiet
S-Lo
Cool air prevention
Powerful
Powerful
1410 1300 1220 1120 960 650 610 570
1470 1370 1260 1180 960 650 610 570
1620 1510 1440 1220 1030 790 610
570 1410 1300 1080 960 650
1470 1370 1120 960 650
1550
1440
1220
980
740
The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected temperature by the indoor heat-exchanger sensor on heating mode.
( Fig.6 : Cool air prevension control )
01-05
5. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5 On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 6.
6. COOL AIR PREVENTION CONTROL (Heating mode)
( Fig.5 : Airflow change - over ( Heating : Auto ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C =
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C =
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
Lo mode
Me mode
Me+ mode
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Hi
Me+
Lo
Cool air prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
( Fig.7 : Indoor fan control )
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 6)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(sec)
( Table 6 : Indoor fan speed )
X zone J zone
AS*G09/12LTCB
650rpm 610rpm
Y zone
0 570rpm 650rpm
AS*G14LTCB 740rpm 710rpm 0 570rpm 740rpm
Dry
Cooling
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Powerful
Hi
Lo
Cool air prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
<Normal operation>
<Powerful operation>
6. OUTDOOR FAN CONTROL
( Table 8 : Outdoor fan speed )
*
The outdoor fan speed mentioned above depends on the compressor frequency. (When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequency decreases, the outdoor fan speed also changes to the lower speed.)
*
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table 9 without relating to the compressor frequency.
01-06
( Table 9 : Outdoor fan speed after the defrost )
1. Outdoor Fan Motor
2. Fan Speed
AC Motor DC Motor
AO*G09/ 12/ 14LTCN
Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table 7 : Type of Motor )
AO*G09LTCN 950rpm
Cooling Heating
AO*G09LTCN
AO*G12LTCN
AO*G14LTCN
Y Z
Zone
Refer to Fig.8
(rpm)
F G Y Z F G Y Z F G
Dry
250/ 200
330/ 300
300/ 250
850/ 750/ 670/ 500
1050/ 870/ 720/ 530
870/ 530/ 300
1050/ 870/ 720/ 590/ 530
870/530/300
950/ 850/ 750/ 670/ 550/ 450 760/ 470
1100/ 870/ 780/ 720/ 590/ 480 530
1100/ 1000/ 780/ 720/ 590/ 480 530
850/ 500/ 350
250/ 200
300
280/ 230
AO*G14LTCN
AO*G12LTCN
1100rpm 1100rpm
( Fig.8 : Outside air temperature zone selection )
21°C
10°C
Outside air temperature rises
Outside air temperature drops
Z zone
Y zone
F zone
G zone
12°C
C
19°C
C
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
2. SWING OPERATION
Each time the button is pressed, the air direction range will change as follow:
(Function Range)
01-07
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode
Horizontal flow
Heating mode Downward flow
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Table10 : Swinging Range)
Air Direction RangeFig.9 :
Cooling / Dry mode Fan mode ( )
Types of Air flow Direction Setting:
, , : During Cooling/Dry modes , , , : During Heating
The Remote Controller's display does not change.
Use the air direction adjustments within the ranges shown above.
During AUTO mode operation, for the first a few minutes after beginning operation, air-flow will be horizontal 1; the air direction cannot be adjusted during this period. The air flow direction setting will temporarily become 1 when the temperature of the air -flow is low at the start of the Heating mode.
Range
Heating mode Fan mode ( )
The SWING operation may stop temporarily when the air conditioner’s fan is not operating, or when operating at very low speeds.
1
2
3
4
5
6
7
2. ADJUST THE RIGHT-LEFT LOUVERS
Move the Right-Left louvers to adjust air flow in the direction you prefer.
Knob (2 places)
Right-Left Louvers
Knob
To select Vertical Airflow Swing Operation
To select Horizontal Airflow Swing Operation
(No function)
8. COMPRESSOR CONTROL
01-08
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the Table 11.
Cooling / Dry Heating
Minimum Maximum Minimum Maximum
AS*G09LTCB
AS*G12LTCB
18rps
15rps
96rps 18rps 130rps
16rps
119rps
76rps
AS*G14LTCB
91rps
16rps
12rps
140rps
AS*G09LTCB AS*G12LTCB AS*G14LTCB
AS*G09LTCB AS*G12LTCB AS*G14LTCB
AS*G09LTCB AS*G12LTCB AS*G14LTCB
AS*G09LTCB AS*G12LTCB
AS*G14LTCB
56rps 74rps 87rps 97rps
(Table 11 : Compressor frequency range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.10
(Fig.10 : Compressor control at start-up)
Time
Time Time Time
Time
(Frequency)
Frequency
Frequency
Frequency Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time Time Time
Time
80sec 140sec 200sec
(Time)
Frequency
Time
6
Frequency
Time
6
108rps
119rps
40rps 57rps 72rps 80rps
101rps
110rps
40rps 59rps 72rps 80rps
101rps
110rps
380sec
500sec440sec
80sec 110sec 140sec
200sec
410sec350sec
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.
Under Over Under Over Under Over
39rps 27rps 30rps18rps 35rps 18rps 15rps15rps 24rps 18rps 16rps12rps
(Table12 : Limitation of Compressor Frequency)
10°C 14°C 40°C
Under Over Under Over Under Over Under Over Under Over Under Over
35rps 35rps 35rps 27rps 18rps 30rps27rps 35rps 35rps 35rps 18rps 16rps 16rps29rps 24rps 24rps 24rps 18rps 16rps 16rps24rps
- 3°C
- 20°C - 15°C 7°C 14°C 40°C
[ Cooling/ Dry ]
[ Heating ]
9. TIMER OPEARTION CONTROL
1. OPEARTION FREQUENCY RANGE
The Table 13 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER
AS*G09/ 12/ 14LTCB
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
( Table 13 : Timer Setting )
2. PROGRAM TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time Set time Set time Set time
01-09
9-1 WIRELESS REMOTE CONTROLLER
WEEKLY TIMER
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1°C
+2°C
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not changed and the operation stops at the time of timer setting.
-4°C
-3°C
-2°C
-1°C
Set
30min
30min
30min
01-10
4. WEEKLY TIMER
This timer function can set operation times of the each day of the week. All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
Setting day Setting day Setting day
ON OFF ON OFF ON OFF
Set time Set time
01-11
9-2 WIRED REMOTE CONTROLLER (OPTION)
The Table14 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
( Table14 : Timer Setting )
1. ON TIMER / OFF TIMER
Same to 9-1 1.ON TIMER / OFF TIMER and shown in those.
2. WEEKLY TIMER
This timer function can set operation times of the each day of the week. All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
3. TEMPERATURE SET BACK TIMER
This timer function can change setting temperature of setting operation times of the each day of the week. This can be together with other timer setting.
Normal tmp.
ON
OFF
Setting day Setting day Setting day
ON OFF ON OFF ON OFF
Set time Set time
Set back tmp.
Set time Set time
AS*G09/ 12/ 14LTCB
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table15. The compressor frequency, the detected temperature by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
The expansion valve is set at 480 pulses 110seconds after the compressor had stopped.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).
01-12
( Table15 : The pulse range of the electronic expansion valve control )
AO*G09LTCN
AO*G12LTCN
AO*G14LTCN
Operation mode Pulse range
Between 60 to 480 pulses.
Between 60 to 480 pulses.
Cooling / Dry mode
Heating mode
Cooling / Dry mode
Heating mode
Cooling / Dry mode
Heating mode
between 60 to 480 pulses.
between 45 to 480 pulses.
Initialization will start after 24 hours pass from the last initialization, and the compressor stops
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is stopped, even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after the compressor stopped.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
13. FOUR-WAY VALVE EXTENSION SELECT
11. TEST OPERATION CONTROL
[ Operation method ]
The outdoor unit, may not operate, depending on the room temperature. In this case, keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds. The Operation lamp and Timer lamp will begin to flash simultaneously during cooling test run. Then, heating test run will begin in about 3 minutes when HEAT is selected by the remote control operation. (When the air conditioner is running by pressing the test run button, the Operation lamp and Timer lamp will simultaneously flash slowly.)
[ Release ]
Perform the test operation for 60 minutes. Pressing the MANUAL AUTO button of the indoor unit for more than 3 seconds.
[ Using the Wired remote control (Option) ]
If the Operation lamp is on, press the START/STOP button to turn it off. Press the MODE and the FAN buttons at the same time for more than two seconds to start the test operation. The operation lamp will light up and "o1" will be displayed on the set temperature display.
[ Release ]
Perform the test operation for 60 minutes. Pressing the START/STOP button will stop the test operation.
15. MANUAL AUTO OPERATION (Indoor unit body operation)
When the remote control is lost or battery power dissipated, this function will work without the remote control. When MANUAL AUTO button is set more than 3seconds and less than 10seconds, MANUAL AUTO OPERATION will be started as shown in Table16.To stop operation, press the MANUAL AUTO button for 3seconds.
(Table16 : MANUAL AUTO OPERATION)
01-13
16. FORCED COOLING OPERATION (TEST OPERATION)
Forced cooling operation is started when press MANUAL AUTO button for 10 seconds or more. During the forced cooling operation, it operates regardless of room temperature sensor. Operation LED and timer LED blink at the same time during the forced cooling operation. They blink for 1 second ON and 1 second OFF on both operation LED and timer LED (same as test operation). Forced cooling operation is released after 60 minutes of starting operation or pressing MANUAL AUTO button
for 3 seconds.
( Table17 : FORCED COOLING OPERATION )
When FORCED COOLING OPERATION is set, the operation is controlled as shown in Table17.
Press and hold MANUAL AUTO button for 3 ~ 10seconds
MANUAL AUTO button
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
[ Operation contents memorized when the power is interrupted ]
Operation mode Set temperature Set air flow Timer mode and set time (set by wireless remote controller) Set air flow Direction Swing ECONOMY operation 10°C HEAT operationOutdoor low noise operation
Human sensor
14. AUTO RESTART
OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous SETTING TEMP. 24°C SETTING LOUVER Standard SWING ECONOMY
OFF OFF
(No timer setting available)
Forced cooling operation Cooling Hi
Horizontal (It is changed follow as setting of remote controller)
OFF
Room Temp is not controlled
Manual auto operation
-
-
OPERATION MODE FAN CONT. MODE TIMER MODE SETTING TEMP. SETTING LOUVER
SWING ECONOMY
01-14
17. COMPRESSOR PREHEATING
18. 10°C HEAT OPERATION
10°C HEAT operation performs as below when pressing 10°C HEAT button or Weekly timer setting on the remote controller.
Mode Heating Setting temperature 10°C Fan mode Auto LED display Economy Defrost operation Operate as normal
( Table 18 : 10°C HEAT operation )
19. ECONOMY OPERATION
20 . HUMAN SENSOR CONTROL
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation for cooling and heating. The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating
Target temperature Setting temp.+1°C Setting temp.-1°C
( Table 19 )
Mode Cooling/ Dry Heating
Target temperature Setting temp.+2°C Setting temp.-4°C
( Table 20 )
The HUMAN SENSOR functions by pressing SENSOR button on the remote controller. When the sensor detects that there is no one in the room for 20 minutes or more, it automatically changes the operation as below settings.
When someone comes back into the room, the human sensor will detect this, and automatically revert to the original settings.
90°
6 m
6 m
50° 50°
Vertical angle 90°(Side view) Horizontal angle 100°(Top view)
( Application range )
The sensor unit should detect when the human body (estimate: 100cmX30cm) or the object which has more than 4 degreesC temp, difference from the background and are crossed with
1.0m/s speed in front of the sensor unit.
When the outdoor heat exchanger temperature is lower than 5°C and the all operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor heat exchanger temperature rises to 7°C or greater, preheating is ended.
01-15
21. OUTDOOR UNIT LOW NOISE OPERATION
The OUTDOOR UNIT LOW NOISE Operation functions by pressing OUTDOOR UNIT LOW NOISE button on the remote controller. This operation stops the PFC control, and changes the Current release operation/release value. OUTDOOR UNIT LOW NOISE Operation mode can be used during cooling, heating and automatic operation. It can not be used in Fan and Dry mode
Control / Release
Current release operation/release value
3.5A / 3.0A
( Table 21 )
22. POWERFUL OPERATION
The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller. The indoor unit & outdoor unit will operate at maximum power as shown in Table22.
Release Condition is as follows. [Cooling / Dry]
- Room tenperature < Setting temperature - 1.5°C or Operation time has passed 20 minutes.
COMPRESSOR FREQUENCY Maximum
FAN CONT. MODE Powerful
SETTING LOUVER Cooling/ Dry : 3, Heating : 5
(Table22)
Powerful operation
=
=
[Heating]
- Room tenperature > Setting temperature +1.5°C or Operation time has passed 20 minutes.
23. BASE HEATER OPERATION
The base heater is operated as shown in Figure 11.
( Fig.11 : Base heater control )
ON
2°C
5°C
OFF
When outdoor temperature drops
When outdoor temperature rises
When the compressor stops, Base heater is OFF. When the outdoor fan motor stops, Base heater is OFF. In the cooling mode, Base heater is OFF. In the defrost operation, Base heater maintains the same status as before the compressor stops.
01-16
24. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts as shown in the following Table 23.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +16°C or Compressor operation time has passed 15 minutes.
(Table 23 : Condition of starting Defrost Operation)
Defrost operation is released when the conditions become as shown in Table 24.
(Table 24 : Defrost Release Condition)
Integrating defrost
If the compressor continuous operation time is less than 10 minutes, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
Normal defrost
Compressor integrating operation time
Less than 25 minutes (09/ 12L) Less than 40 minutes (14L)
More than 25 minutes (09/ 12L) More than 40 minutes (14L)
Does not operate
Outdoor heat exchanger temp. < -17°C (at outside air temp. > -10°C)
Outdoor heat exchanger temp. < Outside air temp.- 7°C or Outdoor heat exchanger temp. < - 25°C (at outside air temp. < -10°C)
More than 240 minutes (For continuous operation)
Less than 10 minutes ( For
intermittent operation )
Compressor integrating operation time
Outdoor heat exchanger
temperature below -3°C
More than 213 minutes (For continuous operation)
Outdoor heat exchanger
temperature below -5°C
OFF count of the compressor
40 times
=
=
=
=
01-17
Outdoor fan : OFF Compressor speed : 0 rps EEV : 480pulse 4-way valve : OFF Compressor speed : 90rps (09L) 70rps (12L) 80rps (14L)
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
Heating operation start : Compressor ON
Outdoor HEX temp.: Over 16°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Outdoor HEX temp. Below - 17°C
Outdoor HEX temp.
- Outside air temp. Below - 7°C or Outdoor HEX temp. Below - 25°C
Integrating defrost
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Defrost start
Normal defrost
Outside air temp. > -10°C Outside air temp. < -10°C
=
Compressor OFF count : 40 times (Less than 10min.)
Compressor integrating operation: Over 240 min.
Outdoor heat exchanger temperature: Below - 3°C
Compressor integrating operation: Over 213 min.
Outdoor heat exchanger temperature: Below - 5°C
Intermittent operation Continuous operation
25. OFF DEFROST OPEARTION CONTROL
01-18
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
OFF Defrost Flow Chart
Heating operation stop
Defrost start
Defrost Indicater: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 16°C or Compressor ON time: Over 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
In heating operation, the outdoor heat exchanger temperature is less than - 4°C, compressor continuous operation more than 10 minutes, and compressor operation integrating time lasts for more than 30 minutes.
Outdoor heat exchanger temperature : Below - 4°C Compressor continuous operation : Over 10 minutes Compressor integrating operation : Over 30 minutes
26. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the protection control of the compressor frequency will be released. When the discharge temperature becomes higher than Temperature , the compressor is stopped and the indoor unit LED starts blinking.
104°C 101°C 110°C
( Table 25 : Discharge temperature over rise prevension control / Release temperature )
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceed the current limit value that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
( Table 26 : Current release operation value / Release value )
01-19
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
OT (Control / Release)
4.0A / 3.5A
5.0A / 4.5A
6.0A / 5.5A
46°C
40°C
OT : Outdoor Temperature
AO*G09LTCN AO*G12LTCN AO*G14LTCN
AO*G09LTCN AO*G12LTCN AO*G14LTCN
OT (Control / Release)
5.5A / 5.0A
7.0A / 6.5A
7.5A / 7.0A
8.5A / 8.0A
17°C
12°C
5°C
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
OT (Control / Release)
4.5A / 4.0A
6.0A / 5.5A
8.5A / 8.0A
46°C
40°C
OT : Outdoor Temperature
OT (Control / Release)
7.0A / 6.5A
9.0A / 8.5A
10.0A / 9.5A
10.0A / 9.5A
17°C
12°C
5°C
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
OT (Control / Release)
4.5A / 4.0A
6.0A / 5.5A
9.0A / 8.5A
46°C
40°C
OT : Outdoor Temperature
OT (Control / Release)
7.0A / 6.5A
9.0A / 8.5A
11.0A / 10.5A
13.0A / 12.5A
17°C
12°C
5°C
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 27 : Anti-freezing Protection Operation / Release Temperature)
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C or greater, the compressor and the outdoor fan motor are stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
01-20
Outdoor temperature
Over than 10°C *1
or 12°C *2
Less than 10°C *1
or 12°C *2
*1. When the temperature rises. *2. When the temperature drops.
4°C
7°C
13°C
Temperature Temperature
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
[ Control System ]
Indoor heat exchange temperature rises
Indoor heat exchange temperature drops
It returns to the normal operation
Compressor is stopped
53°C
55°C
63°C
50°C
The compressor frequency is decreased 3rps every 60seconds.
The compressor frequency is decreased 25rps every 120seconds.
Stable zone
2 . TROUBLE SHOOTING
R410A
WALL MOUNTED type
INVERTER
2. TROUBLESHOOTING
02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
Please refer the flashing pattern as follows. Indoor Unit : AS*G09/ 12/ 14LTCB The OPERATION, TIMER and ECONOMY lamps operate as follows according to the error contents.
Manual auto switch error
Indoor room thermistor error
Indoor unit model information error EEPROM access abnormal
Wired remote controller communication error
Error Contents
Continuous
Continuous
4 times
Continuous2 times
3 times
3 times
5 times
Continuous2 times1 times
Continuous1 times1 times
Trouble shooting
(Green)
(Orange)
(Green)
1 times
Serial communication error
Indoor unit fan motor error
Indoor heat Ex. thermistor error
Continuous4 times 2 times
Continuous1 times5 times
Intake grille error
Continuous8 times5 times
Outdoor unit main PCB error
2 times6 times
Continuous
Continuous
4 times
7 times
6 times
1 times
Continuous
7 times 3 times
Continuous
7 times 4 times
Continuous
PFC circuit error (09/ 12L) Active filter error (14L)
Discharge thermistor error
Heat Ex. liquid outlet thermistor error
Outdoor thermistor error
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Continuous8 times 4 times
Current sensor error
Continuous
Continuous
Continuous
5 times
9 times
9 times
7 times
Compressor control error
Outdoor unit fan motor error
Continuous
4 times9 times
Continuous
9 times 9 times
4 Way valve error
1 times10 times
Discharge temp. error
Over current error
Continuous
5 times6 times
IPM error
Indoor Unit Display
Wired Remote Controller Display
11
12
32
35
41
42
51
58
62
64
65
71
73
74
84
94
95
97
99
A1
[ ]
[ ]
[ ]
OPERATION TIMER
ECONOMY
02-02
When " Er " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel.
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION)
1. SELF - DIAGNOSIS
SU MOTUWETH FR SA
Unit number (usually 0)
Error code
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
3. Press the SET TEMPERATURE button to select the error history number.
SU MOTU WETH FR SA
Error code
Error history number
01234 567
FEdcbA98
ı
ı
Lower
Raise
02-03
2-2 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1-1
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
YESYES
NO
RED
WHITE
BLACK
BLACK
WHITE
GREEN
+
-
OK
Serial communication error (Serial Reverse Transfer Error)
Outdoor unit Main PCB Outdoor unit fan motor
1. Connection failure 2. External cause 3. Main PCB failure 4. Outdoor unit fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2: Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC207V (AC230V -10%) - 253V (AC230V +10%) appears at Outdoor Unit Terminal L - N.
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3.
>> If it is abnormal, Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB.
>> If Outdoor fan motor is normal, replace Main PCB.
When the indoor unit cannot receive the serial signal from Outdoor unit more than 2minutes after power ON, or the indoor unit cannot receive the serial signal more than 15seconds during normal operation.
N
L
3
2
1
Indicate or Display:
Refer to error code table.
02-04
Trouble shooting 1-2
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
YESYES
NO
+
-
OK
Serial communication error (Serial Forward Transfer Error)
Indoor unit Controller PCB Indoor unit Fan motor
1. Connection failure 2. External cause 3. Controller PCB failure 4. Indoor unit fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2: Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC207V (AC230V -10%) - 253V (AC230V +10%) appears at Outdoor Unit Terminal L - N.
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Forward Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 2 - 3.
>> If it is abnormal, replace Controller PCB.
>> If it is abnormal, Check Indoor unit fan motor. (PARTS INFORMATION 4)
>> If Indoor unit fan motor is abnormal, replace Indoor unit fan motor and Controller PCB.
When the outdoor unit cannot receive the serial signal from Indoor unit more than 10seconds.
RED
WHITE
BLACK
BLACK
WHITE
GREEN
N
L
3
2
1
Indicate or Display:
Refer to error code table.
Trouble shooting 2
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check Remote Control and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Remote controller communication error
Indoor unit Controller PCB Wired remote control
1. Terminal connection abnormal 2. Wired remote control failure 3. Controller PCB failure
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit, and check if there is a disconnection of the cable.
Upon correcting the removed connector or mis-wiring, reset the power.
Check Voltage at CNC01 (terminal 1-3) of UTY-TWBXF(Communication kit). (Power supply to Remote Control)
>> If it is DC13V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
When the indoor unit cannot receive the signal from Wired Remote Control more than 1minute during normal operation.
02-05
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 : Check Indoor unit electric components
YESYES
NO
Trouble shooting 3 INDOOR UNIT Error Method:
Indoor unit main PCB error
Indoor unit Controller PCB
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
02-06
Indicate or Display:
Refer to error code table.
02-07
Trouble shooting 4
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
Manual auto switch error
Indoor unit Controller PCB Indicator PCB Manual auto switch
When the Manual Auto Switch becomes ON for consecutive 60 or more seconds.
1. Manual auto switch failure 2.Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual auto switch
Check if Manual auto switch is kept pressed.
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB and Indicator PCB.
Check ON/OFF switching operation by using a meter.
>>If Manual Auto Switch is disabled (on/off switching), replace it.
Indicate or Display:
Refer to error code table.
Trouble shooting 5
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 1 : Check connection of Connector
Check Point 3 : Check Point 3 : Check voltage of Controller PCB (DC5.0V)
10.012.515.820.225.933.644.058.2Resistance Value (k )
Temperature
OK
OK
5.36.58.0Resistance Value (k )
Temperature
Room temperature sensor error
Indoor unit Controller PCB Room temperature thermistor
When Room Temperature Thermistor open or short-circuit is detected.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-08
25°C 20°C15°C10°C5°C0°C-5°C-10°C
40°C
4.4
45°C35°C30°C
THERMISTOR (ROOM TEMP.)
THERMISTOR (PIPE)
BLACK
CN4
1 2 3 4
1 2 3 4
BLACK
BLACK
BLACK
Indicate or Display:
Refer to error code table.
Trouble shooting 6
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
62.9103.3134.2176.0233.2312.3579.61131.9Resistance Value (k )
Temperature
OKOK
OK
17.125.639.6Resistance Value (k )
Temperature
Indoor unit Heat Ex. sensor error
Indoor unit Controller PCB Heat Ex. temperature thermistor
When Heat Ex. Temperature Thermistor open or short-circuit is detected.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-09
20°C10°C5°C0°C-5°C-10°C-20°C-30°C
50°C
11.6
60°C
10.4
63°C40°C30°C
Indicate or Display:
Refer to error code table.
THERMISTOR (ROOM TEMP.)
THERMISTOR (PIPE)
BLACK
CN4
1 2 3 4
1 2 3 4
BLACK
BLACK
BLACK
Trouble shooting 7 INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
OK
Indoor unit fan motor error
Indoor unit Controller PCB Indoor unit Fan motor
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is below 1/3 of target frequency is continued more than 56 seconds.
02-10
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Indicate or Display:
Refer to error code table.
02-11
Trouble shooting 8
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Intake grille error
Indoor unit Controller PCB Micro switch
When the Micro switch is detected open while running the compressor.
1. Micro switch failure 2. Shorted connector/ wire 3.Controller PCB failure
Indicate or Display:
Refer to error code table.
Check Point 2 : Check Point 2 : Check Connector (CN11) / Wire
Check Point 1 : Check Limit switch
Check Point 3 : Replace Controller PCB
OKOK
Check operation of Micro switch. (any blocking by dust, etc.) Remove Micro switch and check ON/OFF switching operation by using a meter.
>>If Micro switch is detective, replace it.
Check loose contact of CN11 /shorted wire (pinched wire).
>>Replace Micro switch if the wire is abnormal
OKOK
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Replace Main PCB
YESYES
NO
Trouble shooting 9 OUTDOOR UNIT Error Method:
Outdoor unit main PCB error
Outdoor unit Main PCB
1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Change Main PCB.
Access to EEPROM failed due to some cause after outdoor unit started.
02-12
Indicate or Display:
Refer to error code table.
Trouble shooting 10-1
INDOOR UNIT
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
PFC circuit error
Outdoor unit Main PCB
1. External cause 2. Connector connection failure 3. Main PCB failure
Check Point 2 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
02-13
When inverter output DC voltage is higher than 415V for over 3 seconds, the compressor stops. If the same operation is repeated 5 times, the compressor stops permanently.
Indicate or Display:
Refer to error code table.
For AO*G09/ 12LTCN
Trouble shooting 10-2
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
Active filter error
Outdoor unit Main PCB Active filter module
1. External cause 2. Connector connection failure 3. Main PCB failure 4. Active filter module failure
Check Point 2 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 4 : Replace Main PCB
If Check Point 1 - 3 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
02-14
OKOK
Check Point 3 : Check Active filter module
For AO*G14LTCN
Check Active filter module. (PARTS INFORMATION 6) >>If Active filter module is abnormal, replace it.
When inverter input DC voltage is higher than 425V or lower than 80V. When a momentary power cut off occurred on low voltage
Refer to error code table.
Trouble shooting 11 OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Outdoor Fan
OK
OK
Check Point 6 : Replace Main PCB
OKOK
OKOK
Check Point 1 : Check connections of Outdoor Unit Electrical Components
IPM error
Outdoor unit Main PCB Outdoor unit Transistor PCB (14L) Compressor
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Compressor failure
5. Main PCB failure 6. Transistor PCB failure (For 14L)
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
Check Outdoor Fan Motor. (Refer to Trouble shooting 17)
>> If the Fan Motor is failure, replace it.
Check Point 4 : Check Compressor
(PARTS INFORMATION 2)
Check Compressor.
If Check Point 1 5 do not improve the symptom, change Main PCB.
When more than normal operating current to IPM in Main PCB flows, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
02-15
OKOK
Check Point 5 : Check Transistor PCB (For 14L)
(PARTS INFORMATION 7)
Check Transistor PCB.
Indicate or Display:
Refer to error code table.
Trouble shooting 12
INDOOR UNIT
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
62.5100.9129.8168.6221.1292.9531.61013.1Resistance Value (k )
Temperature
OKOK
OKOK
40.0
2.03.44.66.38.7Resistance Value (k )
Temperature
Discharge thermistor error
Outdoor unit Main PCB Discharge pipe temperature thermistor
When Discharge pipe temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-16
90°C80°C70°C
26.3
40°C
17.8
50°C
12.3
60°C
30°C
100°C
2.6
110°C
5°C0°C-5°C-10°C-20°C-30°C
20°C10°C
120°C
Indicate or Display:
Refer to error code table.
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK BLACK BLACK BLACK
BLACK
BLACK
1 2 3 4
1 2 3 4
1 2 3
1 2 3
CN61
CN62
AO*G14LTCN
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK
BLACK BROWN BROWN
BLACK
BLACK
1 2 3 4
1 2 3 4
1 2 3
1 2 3
CN71
CN70
AO*G09/ 12LTCN
Trouble shooting 13 OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
6.09.612.416.121.027.8Resistance Value (k )
Temperature
OKOK
OKOK
3.8
0.60.81.21.72.5Resistance Value (k )
Temperature
Outdoor unit Heat Ex. sensor error
Outdoor unit Main PCB Heat exchanger temperature thermistor
When Heat exchanger temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-17
-5°C-10°C
95.6
-30°C
50.3
-20°C
80°C70°C60°C
30°C20°C10°C5°C0°C
50°C40°C
Indicate or Display:
Refer to error code table.
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK BLACK BLACK BLACK
BLACK
BLACK
1 2 3 4
1 2 3 4
1 2 3
1 2 3
CN61
CN62
AO*G14LTCN
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK
BLACK BROWN BROWN
BLACK
BLACK
1 2 3 4
1 2 3 4
1 2 3
1 2 3
CN71
CN70
AO*G09/ 12LTCN
Trouble shooting 14 OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
26.935.246.662.384.2115.2Resistance Value (k )
Temperature
OKOK
OKOK
20.7
6.48.010.012.616.1Resistance Value (k )
Temperature
Outdoor thermistor error
Outdoor unit Main PCB Outdoor temperature thermistor
When Outdoor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-18
-15°C-20°C
224.3
-30°C
159.7
-25°C
35°C
5.2
40°C
4.2
45°C
3.5
50°C
2.8
55°C30°C25°C
10°C5°C0°C-5°C-10°C
20°C15°C
Indicate or Display:
Refer to error code table.
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK BLACK BLACK BLACK
BLACK
BLACK
1 2 3 4
1 2 3 4
1 2 3
1 2 3
CN61
CN62
AO*G14LTCN
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK
BLACK BROWN BROWN
BLACK
BLACK
1 2 3 4
1 2 3 4
1 2 3
1 2 3
CN71
CN70
AO*G09/ 12LTCN
Trouble shooting 15
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 4 : Replace Main PCB
YES
NO
OK
Current sensor error
Outdoor unit Main PCB
Check Point 2 : Check connections of Outdoor Unit Electrical Components
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
1. Defective connection of electric components 2. External cause 3. Main PCB failure
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
When Input Current Sensor has detected 0A, while Inverter Compressor is operating at higher than 56rps, after 1minute upon starting the Compressor. (Except during the defrost operation)
02-19
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Indicate or Display:
Refer to error code table.
Trouble shooting 16 OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
Check Point 2: Replace Main PCB
Outdoor unit Main PCB Compressor
Trip detection
If Check Point 1 do not improve the symptom, change Main PCB.
02-20
OKOK
Check Point 3: Replace Compressor
If Check Point 2 do not improve the symptom, change Compressor.
1. Outdoor unit fan operation defective, foreign matter on hear exchanger, excessive rise of ambient temperature
2. Inverter PCB failure
3. Inverter compressor failure (lock, winding short)
"Protection stop by overcurrent generation after inverter compressor start processing completed'' generated consecutively 10 times. * The number of generations is reset if the start-up of the compressor succeeds.
No obstructions in air passages? Heat exchange fins clogged Outdoor unit fan motor check Ambient temperature not raised by the effect of other heat sources? Discharged air not sucked in?
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
Indicate or Display:
Refer to error code table.
Trouble shooting 17 OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OKOK
OKOK
Check Point 3: Replace Main PCB
Outdoor unit Main PCB Compressor
Compressor motor control error
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1,2 do not improve the symptom, change Main PCB.
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
If the detected rotor location is out of phase with actual rotor location more than 90°, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
02-21
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
Indicate or Display:
Refer to error code table.
Trouble shooting 18
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Check Outdoor unit fan motor
OK
OK
Outdoor unit fan motor error
Outdoor unit Main PCB Outdoor unit Fan motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Outdoor unit fan motor. (PARTS INFORMATION 5) >>If Outdoor unit fan motor is abnormal, replace Outdoor unit fan motor.
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated 3 times in a row, compressor and fan motor stops. If and repeats 5 times in a row, compressor and fan motor stops permanently.
Read wire DC voltage
Red - Black (Vm)
240 - 400V (12/ 14L)
280 28V (09L)
White - Black (Vcc)
15 1.5V
02-22
CN800 [09/12L]
CN801 [14L]
1 2 3 4 5 6 7
BLACK WHITE YELLOW
RED
FM
FAN MOTOR
Check Point 2 : Check ambient temp. around motor
OK
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Indicate or Display:
Refer to error code table.
BROWN
Trouble shooting 19 INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
4-way valve error
Indoor unit Controller PCB Heat Ex. temperature thermistor Room temperature thermistor 4-way valve
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops.
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
Remove CN30 (For 9/12L) and CN500 (For 14L) from PCB and check the resistance value of coil. Resistance value is 1.88k 2.29k (at 20°C).
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
02-23
Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 10degC
Heating operation [Indoor heat exchanger temp.] - [room temp.] < - 10degC
If the same operation is repeated 5 times, the compressor stops permanently.
[ Solenoid coil ]
Check each piping temperature, and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
[ 4-way valve ]
OKOK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 2 : Check each thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 5, 6), If defective, replace the thermistor
Indicate or Display:
Refer to error code table.
Trouble shooting 20
INDOOR UNIT
OUTDOOR UNIT Error Method:
Discharge temperature error
02-24
Indicate or Display:
Refer to error code table.
<Cooling operation>
OK
OK
OK
OK
OK
<Heating operation>
Outdoor unit Main PCB Discharge temperature thermistor
"Protection stop by "discharge temperature 110degC during compressor operation"" generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check. (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 12".
Check Point 4 : Check the discharge thermistor
EEV (EEV2, indoor unit EEV) open?
Strainer clogging check (before and after EEV, ACM oil return)
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger Check if fan can be rotated by hand.
Motor check (PARTS INFORMATION 5)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV (EEV1, EEV2) open?
Strainer clogging check (before and after EEV, ACM oil return)
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
Detective Actuators:
Detective details:
Forecast of Cause :
Refer to "Service Parts Information 3".
Refer to "Service Parts Information 3".
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
Trouble shooting 21
Forecast of Cause:
OKOK
Indoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
02-25
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Check Point 3 : Check Electrical Components
YESYES
NO
Check the voltage of power supply.
>> Check if AC207 - 253V appears at Outdoor Unit Terminal L - N.
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
OK
Trouble shooting 22
Forecast of Cause:
Check Point 3 : Check Electrical Components
OKOK
OKOK
YESYES
OK
NO
Check Point 1 : Check Installation Condition
Outdoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical Components defective
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check the voltage of power supply.
>> Check if AC207 - 253V appears at Outdoor Unit Terminal L - N.
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
If the symptom does not change by above Check 3, replace Main PCB.
02-26
Trouble shooting 23
Forecast of Cause:
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check Electrical Components at Indoor and Outdoor
OK
OK
OKOK
No Operation (Power is ON)
1. Setting/ Connection failure 2. External cause
3. Electrical component defective
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection. Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and Data & Technical Manual.
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
>> If it is DC13V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Check Indoor unit fan motor. (PARTS INFORMATION 4) If it is normal, replace Controller PCB. If it is abnormal, replace Indoor unit fan motor and Controller PCB.
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
02-27
Check Voltage at CNC01 (terminal 1-3) of UTY-TWBXF(Communication kit). (Power supply to Remote Control)
Attention
Trouble shooting 24
Forecast of Cause:
Check Point 2 : Check Outdoor unit operation
Check Point 1 : Check Indoor unit
Check Point 3 : Check Site condition
Check Point 5 : Check Refrigeration cycle
Check Point 4 : Check Indoor/ Outdoor installation condition
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
OKOK
OKOK
OKOK
OKOK
MPa MPa
No Cooling / No Heating
1. Indoor Unit error 2. Outdoor Unit error
3. Effect by surrounding environment
4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure
Does Indoor unit Fan run on High fan?
Is Air filter dirty? Is Heat exchanger clogged?
Check if Energy save function is operated.
Check if Outdoor unit is operating
Check any objects that obstruct the air flow route.
Check clogged Heat Exchanger.
Is the Valve open?
Is capacity of Indoor unit fitted to room size?
Any windows open? or direct sunlight ?
Check connection pipe (specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3)
Check Compressor (PARTS INFORMATION 1,2) Check Heater Unit (PARTS INFORMATION 8)
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-28
Trouble shooting 25
Forecast of Cause :
Trouble shooting 26
Forecast of Cause:
OK
OK
OK
OK
OKOK
OKOK
OKOK
MPa MPa
Abnormal Noise
1. Abnormal installation (Indoor/ Outdoor)
2. Fan failure (Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when abnormal noise is occurred
Abnormal noise is coming from Indoor unit. (Check and correct followings)
Abnormal noise is coming from Outdoor unit. (Check and correct followings)
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is Main unit installed in stable condition? Is the installation of air suction grille and front panel normal?
Is Fan broken or deformed? Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Is Main unit installed in stable condition? Is Fan guard installed normally?
Check if vibration noise by loose bolt or contact noise of piping is happening.
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
Water Leaking
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water is spitting out.
Is the filter clogged?
Check Gas pressure and correct it if there was a gas leak.
Diagnosis method when water leak occurs
Is Drain hose connection loose? Is there a trap in Drain hose? Is Drain hose clogged?
Is Main unit installed in stable condition? Is Main unit broken or deformed at the time of transportation or maintenance?
Is Fan rotating?
02-29
SERVICE PARTS INFORMATION 1
MPa MPa
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check Main PCB, connection of Compressor, and winding resistance. (Refer to the next page).
Check Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas pipe valve open? (Low pressure is too low)
Check if Refrigerant is leaking. (Recharge Refrigerant)
Check if strainer is clogged. (PARTS INFORMATION 3)
>> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.)
Abnormal noise
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Check if vibration noise by loose bolt or contact noise of piping is happening.
02-30
2-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 2
Check Point 1 : Check Connection
Check Point 2 : Check Winding Resistance
Check Point 3 : Replace Main PCB
C
S
R
Inverter Compressor
Check terminal connection of Compressor (loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If the symptom does not change with above Check 1, 2, replace Main PCB.
02-31
R
S
(WHITE)
C
(BLACK)
Terminal cover opened
(RED)
S(V)
R(U)
(RED)
C(W)
(BLACK)
Terminal cover opened
(WHITE)
AO*G12/ 14L
AO*G09L
Resistance Value :
0.7 at 20°C
AO*G09L
Resistance Value :
1.4 at 25°C
AO*G12L
Resistance Value :
0.7 at 25°C
AO*G14L
SERVICE PARTS INFORMATION 3
Check Point 2 : Check Coil of EEV
Yellow - Red
Orange - Red
Blue - Red
White - Red
Read wire
46
4
Resistance value
Check Point 1 : Check Connections
Check Point 5 : Check Opening and Closing Operation of Valve
Check Point 3 : Check Voltage from Main PCB.
Check Point 4 : Check Noise at start up
Pipe (In)
Pipe (Out)
Hi TEMP.
Pipe (In)
Hi TEMP.
Normal TEMP.
CLOSE Example : Hot Gas
OPEN Example : Hot Gas
Pipe (Out)
Hi TEMP.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
Check Point 6 : Check Strainer
DC
EXPANSION VALVE COIL
EV
RED BLUE ORANGE YELLOW WHITE
1 2 3 4 5
at 20°C
Outdoor unit Electronic Expansion Valve ( EEV )
Check connection of connector (CN40) ( Loose connector or open cable )
Remove connector, check each winding resistance of Coil.
If Resistance value is abnormal, replace EEV.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
When Valve is closed, it has a temp. difference between Inlet and Outlet.
If it is open, it has no temp. difference between Inlet and Outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-32
1 2 3 4 5
CN40 [09/12L]
CN700 [14L]
SERVICE PARTS INFORMATION 5
Check Point 1 : Check rotation of Fan
Outdoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Outdoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Red)
2
3
4 (Black)
5 (White)
6 (Yellow)
7 (Brown or Blue)
DC voltage (Vm)
No function
No function
Earth terminal (GND)
Control voltage (Vcc)
Speed command (Vsp)
Feed back (FG)
SERVICE PARTS INFORMATION 4
Check Point 1 : Check rotation of Fan
Indoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Indoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Blue)
2 (Yellow)
3 (White)
4 (Black)
5
6 (Red)
Feed back (FG)
Speed command (Vsp)
Control voltage (Vcc)
Earth terminal (GND)
No function
DC voltage (Vm)
02-33
SERVICE PARTS INFORMATION 6
Active filter module
02-34
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Check Point 2 : Check the Output DC voltage (between P and N)
L2L1
P
N
+IN
Check the Output DC voltage (between P and N) of compressor stopping and operating.
If it is abnormal,replace ACTIVE FILTER MODULE
Remove connector, check the open or short-circuit and the diode in the module
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping, Active Filter Module is detective. >> Replace Active Filter Module
Terminal
Resistance value
L2
L1
L1,L2
P
P
Control Box
N
N
(+IN)
(+IN)
( IN)
( IN)
Tester(+) Tester(-)
Check the open or short-circuit
L2
P
P
N
L2
L2
Check the diode
0
360k
720k
1.69M /
20%
+
-
360k
20%
+
-
20%
+
-
(Ref. value 1)
1.88M
(Ref. value 2)
1.40M /
(Ref. value 1)
2.28M
(Ref. value 2)
Terminal
Resistance value
Tester(+) Tester(-)
1.32M /
(Ref. value 1)
1.50M
(Ref. value 2)
1.40M /
(Ref. value 1)
1.51M
(Ref. value 2)
Ref. value 1 Specifications for Multimeter Manufacturer : HIOKI Model name : 3804 Power source : DC9V.
Ref. value 2 Specifications for Multimeter Manufacturer : YOKOGAWA Model name : 7534 Power source : DC3V.
-IN
For AO*G14LTCN
SERVICE PARTS INFORMATION 7
IPM (
Mounted on Transistor PCB)
02-35
Check Point 1
Check Point 2
Terminal
Resistance value
Tester(+) Tester(-)
 Disconnect the connection wires between the Transistor PCB - Capacitor PCB and Transistor PCB - Inverter Compressor.
 Set the tester to the "Resistance" mode, and measure the resistance between the following terminals.
Set the tester to the "Diode" mode, and measure the voltage value between the following terminals.
 Judge the result of as follows:
Judge the result of as follows:
TM301 (P) - TM305(U) / TM304(V) / TM303(W) TM302 (N) - TM305(U) / TM304(V) / TM303(W)
P
P
P
U
V
W
N
N
N
U
V
W
U
V
W
P
P
P
U
V
W
N
N
N
Over 2k (Including )
Over 2k (Including )
Over 20k (Including )
Terminal
Tester display
Tester(+) Tester(-)
P
P
P
U
V
W
N
N
N
U
V
W
U
V
W
P
P
P
U
V
W
N
N
N
0.3V 0.7V
For AO*G14LTCN
SERVICE PARTS INFORMATION 8
Check Point 3 : Check Heater wire.
Black - White
Read wire Resistance value
Check Point 1 : Check Connections
Heater Unit
Check connection of connector ( Loose connector or open cable )
Remove connector, check resistance of Heater wire.
If Resistance value is abnormal, replace Heater Unit.
02-36
Check Point 2 : Check electrical components
Check Check Fuses.
CN10
1 2 3 4 5
3 2 1
3 2 1
1 2 3 4 5
BLACK
BLACK
WHITE
WHITE
BLACK
BLACK
WHITE
FUSE 250V5A
FUSE 250V5A
HEATER
THERMOSTAT (55°C)
>> If Fuse is open, check connection, and replace Fuse.
321 ~ 368
AO*G14LTCN
AO*G09/ 12LTCN
CN112
1 2
1 2 3
1 2 3
1 2
BLACK
WHITE
WHITE
BLACK
BLACK
WHITE
FUSE 250V5A
HEATER
THERMOSTAT (55°C)
(at 25°C)
3 . APPENDING DATA
R410A
WALL MOUNTED type
INVERTER
03-01
3-1. FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
3-1-1 INDOOR UNIT
( Factory setting)
Setting Description
Function Number Setting Value
Standard (400 hours)
Long interval (1000 hours)
Short interval ( 200 hours)
No indication
11
00
01
02
03
1-1. Setting the Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the filter sign to be displayed, select the setting value for "No indication".
( Factory setting)
Setting Description
Function Number Setting Value
Standard
Slightly lower control
Lower control
Warmer control
30
00
01
02
03
1-2. Cooling Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
( Factory setting)
Setting Description
Function Number Setting Value
Standard
Lower control
Slightly warmer control
Warmer control
31
00
01
02
03
1-3. Heating Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
03-02
( Factory setting)
Setting Description
Function Number Setting Value
Yes
No
40
00
01
( Factory setting)
Setting Description
Function Number Setting Value
No
Yes
42
00
01
1-4. Setting the Auto Restart
Enable or disable automatic system restart after a power outage.
1-5. Indoor room temperature sensor switching function (Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
( Factory setting)
Setting Description
Function Number Setting Value
A
B
C
D
44
00
01
02
03
1-6. Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
( Factory setting)
Setting Description
Function Number Setting Value
Operation/Stop mode
(Setting forbidden)
Forced stop mode
46
00
01
02
1-7. External input control
"Operation/Stop" mode or "Forced stop" mode can be elected.
* If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor. * If setting value is "01" : Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
03-03
Settings will not be changed if invalid numbers or setting values are selected.
After the power is turned on, perform the "FUNCTION SETTING" according to the installation conditions using the remote controller.
This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP.( ) button simultaneously, press the RESET button to enter the function setting mode.
3-1-2 Procedures to change the Function Setting for wireless RC
(2) Press the POWERFUL button to proceed to setting the value. (Press the POWERFUL button again to return to the function number selection.)
Selecting the Function Number and Setting Value
(5) Next, please press the START/STOP( ) button. Please confirm that the beep sounds.
(6) Press the RESET button to cancel the function setting mode.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The FUNCTION SETTING doesn't become active unless the power is turned off then on again.
(3) Press the SET TEMP.( ) ( ) buttons to select the setting value. (Press the 10°C HEAT button to switch between the left and right digits.)
Function Number
(1) Press the SET TEMP.( ) ( ) buttons to select the function number. (Press the 10°C HEAT button to switch between the left and right digits.)
(4) Press the MODE button, in the order listed to confirm the setting. Please confirm that the beep sounds.
Setting Value
03-04
(2) Press the MODE button for at least 5 seconds to display the current signal code. (initially set to ).
(4) Press the MODE button again to return to the clock display. The signal code will be changed.
Selecting the Remote Controller Signal Code
(3) Press the SET TEMP.( ) ( ) buttons to change the signal code between . Match the code on the display to the air conditioner signal code.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original clock display. In this case, start again from step 1. The air conditioner signal code is set to A prior to shipment.
CAUTION
(1) Press the START/STOP( ) button until only the clock is displayed on the remote controller display.
-10.0 58.2 0.73
-30.0 1131.9 0.21
-5.0 44.0 0.93 -25.0 804.5 0.29
0.0 33.6 1.15 -20.0 579.6 0.40
5.0 25.9 1.39 -15.0 422.9 0.53
10.0 20.2 1.66 -10.0 312.3 0.69
15.0 15.8 1.94 -5.0 233.2 0.88
20.0 12.5 2.22 0.0 176.0 1.10
25.0 10.0 2.50 5.0 134.2 1.36
30.0 8.0 2.77 10.0 103.3 1.63
35.0 6.5 3.03 15.0 80.3 1.92
40.0 5.3 3.27 20.0 62.9 2.21
45.0 4.4 3.49 25.0 49.7 2.51
30.0 39.6 2.79
35.0 31.7 3.06
40.0 25.6 3.30
45.0 20.8 3.53
50.0 17.1 3.73
55.0 14.1 3.90
60.0 11.6 4.05
63.0 10.4 4.14
Room temperature thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Indoor heat exchanger thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Discharge thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
03-05
3-2. Thermistor Resistance Values
3-2-1 INDOOR UNIT
3-2-2 OUTDOOR UNIT
-30.0 1013.1 0.06
-25.0 729.1 0.09
-20.0 531.6 0.12
-15.0 392.3 0.16
-10.0 292.9 0.21
-5.0 221.1 0.28
0.0 168.6 0.36
5.0 129.8 0.46
10.0 100.9 0.57
15.0 79.1 0.71
20.0 62.5 0.86
25.0 49.8 1.03
30.0 40.0 1.23
35.0 32.4 1.43
40.0 26.3 1.65
45.0 21.6 1.88
50.0 17.8 2.11
55.0 14.8 2.34
60.0 12.3 2.57
65.0 10.3 2.79
70.0 8.7 3.00
75.0 7.4 3.19
80.0 6.3 3.37
85.0 5.4 3.54
90.0 4.6 3.69
95.0 4.0 3.83
100.0 3.4 3.96
105.0 3.0 4.07
110.0 2.6 4.17
115.0 2.3 4.26
120.0 2.0 4.33
Temp ( C)
Resistance(k )
Voltage(V)
-30.0 95.6 0.24
-25.0 68.9 0.32
-20.0 50.3 0.43
-15.0 37.2 0.57
-10.0 27.8 0.73
-5.0 21.0 0.92
0.0 16.1 1.14
5.0 12.4 1.39
10.0 9.6 1.65
15.0 7.6 1.93
20.0 6.0 2.21
25.0 4.8 2.49
30.0 3.8 2.77
35.0 3.1 3.02
40.0 2.5 3.26
45.0 2.1 3.48
50.0 1.7 3.68
55.0 1.4 3.85
60.0 1.2 4.00
65.0 1.0 4.13
70.0 0.8 4.25
75.0 0.7 4.35
80.0 0.6 4.43
Temp ( C)
Resistance(k )
Voltage(V)
-30.0 224.3 0.73
-25.0 159.7 0.97
-20.0 115.2 1.25
-15.0 84.2 1.56
-10.0 62.3 1.90
-5.0 46.6 2.26
0.0 35.2 2.61
5.0 26.9 2.94
10.0 20.7 3.25
15.0 16.1 3.52
20.0 12.6 3.76
25.0 10.0 3.97
30.0 8.0 4.14
35.0 6.4 4.28
40.0 5.2 4.41
45.0 4.2 4.51
50.0 3.5 4.59
55.0 2.8 4.65
Temp ( C)
Resistance(k )
Voltage(V)
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
September 2011 Printed in Japan
Loading...