Fujitsu ASG07LLCC, ASG12LLCC, AOG07LLCC, AOG09LLCC, AOG12LLCC Design & Technical Manual

...
Page 1
AIR CONDITIONER
Wall Mounted type
INDOOR
OUTDOOR
ASG07LLCC ASG09LLCC ASG12LLCC
AOG07LLCC AOG09LLCC AOG12LLCC
DESIGN & TECHNICAL MANUAL
Page 2
1.INDOOR UNIT
WALL MOUNTED TYPE :
ASG07LLCC ASG09LLCC ASG12LLCC
DTR_AS087E_02
2014.02.10
Page 3
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
CONTENTS
1. INDOOR UNIT
1. FEATURES
.............................................................................................................. 01 - 01
2. WIRELESS REMOTE CONTROLLER
............................................... 01 - 03
3. SPECIFICATIONS
.............................................................................................. 01 - 05
4. DIMENSIONS
........................................................................................................ 01 - 07
5. WIRING DIAGRAMS
........................................................................................ 01 - 08
6. CAPACITY TABLE
............................................................................................ 01 - 09
6-1. COOLING CAPACITY
...................................................................................... 01 - 09
6-2. HEATING CAPACITY
....................................................................................... 01 - 10
7. FAN PERFORMANCE AND CAPACITY
...........................................01 - 11
7-1. AIR VELOCITY DISTRIBUTION
......................................................................01 - 11
7-2. AIRFLOW
........................................................................................................... 01 - 12
8. OPERATION NOISE (SOUND PRESSURE)
................................. 01 - 14
8-1. NOISE LEVEL CURVE
.................................................................................... 01 - 14
8-2. SOUND LEVEL CHECK POINT
..................................................................... 01 - 15
9. ELECTRICAL CHARACTERISTICS
................................................... 01 - 16
10. SAFETY DEVICES
............................................................................................ 01 - 17
11. FUNCTION SETTINGS
.................................................................................. 01 - 18
11-1. INDOOR UNIT (Setting by remote controller)
........................................... 01 - 18
12. OPTIONAL PARTS
........................................................................................... 01 - 22
Page 4
- (01 - 01) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
FEATURES1.
MODEL
ASG07LLCC / AOG07LLCC ASG09LLCC / AOG09LLCC ASG12LLCC / AOG12LLCC
FEATU RES
Energy efzciency class
MODEL
ASG07LLCC ASG09LLCC ASG12LLCC
Cooling A++ A++ A++
Heating(Average) A+ A+ A
Super quiet operation
z
Top class low noise operation by new airow construction. Our quiet operation makes the more comfortable environment in a bed room and a study room, etc.
Powerful operation
z
Reach the setting temperature quickly.
Powerful
Setting
Temp.
Normal mode
Temperature
Time
(Image)
Ex. : Cooling operation
Economy operation
z
Setting temp. is shifted by 1°C automatically.
Temp.
Economy operation
Shift setting temp
Normal operation
Ex. : Cooling operation
Time
Set temperature
Quiet
Fan speed
22dB(A)
Noise level
Page 5
- (01 - 02) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
Easy maintenance
z
Removable & washable panel
Corresponds to maximum 20m long piping
z
Page 6
- (01 - 03) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WIRELESS REMOTE CONTROLLER2.
FEATU RES
3 mode timer setup available (ON/OFF/SLEEP).
Easy operation.
Easy to change custom code (max. 4 custom codes) by button
operation.
Simple function setting
z
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
z
Select from three different timer programs (ON/OFF/SLEEP).
ON-OFF Programmable timer
z
You can set an integrated ON-OFF or OFF-ON timer suitable for your life style. (Setting time: 0.5, 1, 1.5, 2, 2.5, -----9.5, 10, 11, 12 hours)
Example of how to set the program timer.
OFF-ON timer
From sleep to wake up
ON-OFF timer
From wake up to go to work
OFF
10hours
ON 7hours
12
6
9
3
PM11:00 set
12
6
ON 9hours
OFF
2hours
9
3
PM9:00 set
Sleep timer
z
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling or heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 1 °C every hour. The set temperature can rise up to a maximum of 2 °C.
60min.
1 °C
2 °C
Timer setting
Heating operation
When the sleep timer is set, the set temperature automatically drops 1 °C every 30 minutes. The set temperature can drop to a maximum of 4 °C.
1 °C
30min.
60min.
90min.
2 °C
3 °C
4 °C
Timer setting
Switching remote controller custom code
z
A B C D
A B
C
D
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
Code selector switch eliminates unit
• being wrongly switched. (Up to 4 custom codes can be set.)
*I.U.=Indoor unit
Page 7
- (01 - 04) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
FUNCTIONS
Display panel
SPECIFICATION
2
3
5
6
7
12
13
14
8
9
10
11
15
4
1
16
19
18 17 22 20
21
SIZE (H x W x D mm) 139×56×18
WEIGHT ( g ) 70
1
Signal transmitter
2
MODE button
3
SET TEMP. button ( / )
4
POWERFUL button
5
ECONOMY button
6
START/STOP button
7
TEST RUN button
This button is used when installing the air conditioner, and
z
should not be used under normal conditions, as it will cause the indoor unit’s thermostat function to operate inc orrectly.
If this button is pressed during normal operation, the indoor
z
unit will switch to test operation mode, and the Indoor Unit’s OPERATION Indicator Lamp and TIMER Indicator Lamp will begin to ash simultaneously.
To stop the test operation mode, press the START/STOP button
z
to stop the air conditioner.
8
FAN button
9
SET button
10
SWING button
11
RESET button
TIMER
12
SLEEP TIMER button
13
OFF TIMER button
14
ON TIMER button
15
TIMER CANCEL button
16
Remote controller display
17
Transmit indicator
18
Operation mode indicator
19
Timer mode indicator SLEEP TIMER mark: OFF TIMER mark: OFF-ON TIMER mark: ON-OFF TIMER mark: ON TIMER Mark:
20
Fan speed indicator
21
Temperature and time indicator
It displays the temperature setting. However, when making the Timer setting, it will display the Timer time. (The temperature setting will reappear after nishing the timer setting)
22
Swing indicator
Page 8
- (01 - 05) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
SPECIFICATIONS3.
NOTES:
Specications are based on the following conditions Cooling:Indoor temperature of 27°C DB / 19°CWB and outdoor temperature of 35°C DB / 24°CW B. Heating:Indoor temperature of 20°C DB/15°CWB and outdoor temperature of 7 °C DB / 6°CW B. Pipe length: 5 m, Height difference: 0 m (Outdoor unit - Indoor unit)
The protective function might work when using it in environment out of the temperature range mentioned above.
*: The maximum current is the ma ximum value when operated within the operation range.
Type
WALL MOUNTED
INVERTER HEAT PUMP
Model name AS07LLCC ASG09LLCC ASG12LLCC
Power source 230V~ 50Hz
Available voltage range 198 - 264V~ 50Hz
Capacity
Cooling
Rated
kW 2.00 2.50 3.40
Btu/h 6,800 8,500 11,600
Min-Max
kW 0.9 - 2.8 0.9 - 3.0 0.9 - 3.8
Btu/h 3,100 - 9,500 3,100 - 10,200 3,100 -13,000
Heating
Rated
kW 2.70 3.0 4.00
Btu/h 9,200 10,200 13,600
Min-Max
kW 0.9 - 3.6 0.9 - 3.8 0.9 - 5.0
Btu/h 3,100 - 12,200 3,100 - 13,000 3,100 - 17,00 0
Input power
Cooling
Rated
kW
0.470 0.730 1.080
Min-Max 0.25 - 1.29 0.25 - 1.29 0.25 - 1.40
Heating
Rated 0.620 0.740 1.130
Min-Max 0.25 - 1.63 0.25 - 1.63 0.25 - 1.98
Current
Cooling
Rated A
2.6 3.5 5.2
Heating 3.0 3.5 5.4
EER Cooling
kW/kW
4.26 3.42 3.15
COP Heating 4.35 4.05 3.54
Sensible capacity Cooling kW 1.30 1.60 2.20
Power factor
Cooling
%
79 91 91
Heating 90 92 92
Moisture removal l/h (pints/h) 1.0 (1.8) 1.3 (2.3) 1.8 (3.2)
Maximum operating current *
Cooling
A
6.0 6.0 6.5
Heating 7.5 7.5 9.0
Fan
Air ow rate
Cooling
High
m3/h
720
Med 600
Low 420
Quiet 325
Heating
High 740
Med 600
Low 450
Quiet 325
Type × Q'ty Cross ow fan × 1
Motor output W 30
Sound pressure level
Cooling
High
dB (A)
43
Med 38
Low 33
Quiet 22
Heating
High 43
Med 38
Low 33
Quiet 22
Heat exchanger type
Dimensions
(H × W × D)
mm
256 × 630 × 20
Fin pitch 1.1
Rows Stages 2 × 16
Pipe type Copper
Fin type Aluminium
Enclosure
Material Polystyrene
Colour
White
(Approximate colour of MUNSELL N 9.25 /)
Dimensions
(H × W × D)
Net
mm
262 × 820 × 206
Gross 263 × 870 × 328
Weight
Net
kg
7.0
Gross 9.0
Connection pipe
Size
Liquid
mm
Ø 6.35 (Ø 1/4 in.)
Gas Ø 9.52 (Ø 3/8 in.)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type Wireless
Drain hose
Material PP+LLDPE
Size mm Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Page 9
- (01 - 06) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
Model name AS07LLCC ASG09LLCC ASG12LL CC
Energy ef ciency class
Cooling A++ A++ A++ Heating (Average) A+ A+ A
Pdesign
Cooling
kW
2.0 (35°C) 2.5 (35°C) 3.4 (35°C)
Heating (Average) 2.2 (-10°C) 2.3 (-10°C) 3.2 (-10°C)
SEER Cooling
kWh/kWh
6.70 6.90 6.60
SCOP Heating (Average) 4.00 4.00 3.80
Annual energy consumption
QCE
kWh/a
104 127 180
QHE (Average) 770 805 1179
Sound power level
Cooling
High dB (A)
59 59 59
Heating 60 60 60
Page 10
- (01 - 07) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
DIMENSIONS4.
MODEL : ASG07LLCC, ASG09LLCC, ASG12LLCC
(Unit : mm)
262
206820
INSTALLATION PLACE
70 mm or more
1,500 mm or more
1,800 mm or more
(Wall cap)
63 mm or more
Wall hook bracket
100 mm or more
Page 11
- (01 - 08) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WIRING DIAGRAMS5.
MODEL : ASG07LLCC, ASG09LLCC, ASG12LLCC
Page 12
- (01 - 09) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
CAPACITY TABLE6.
COOLING CAPACITY6-1.
MODEL : ASG07LLCC
MODEL : ASG09LLCC
MODEL : ASG12LLCC
AFR: Air ow Rate (m³/min.) TC: Total Capaci ty (kW) SHC: Sens ible Hea t Capacit y (kW) IP: Input Po wer (kW)
AFR 12.0
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 1.87 1.32 0.33 2.09 1.33 0.34 2.16 1.45 0.34 2.30 1.45 0.34 2.37 1.57 0.34 2.51 1.56 0.35 2.65 1.66 0.35
25 1.78 1.26 0.37 1.98 1.26 0.38 2.05 1.37 0.38 2.18 1.38 0.38 2.25 1.49 0.38 2.39 1.48 0.39 2.52 1.58 0.39
30 1.68 1.19 0.41 1.87 1.19 0.42 1.94 1.30 0.42 2.06 1.30 0.42 2.13 1.41 0.43 2.25 1.40 0.43 2.38 1.49 0.44
35 1.58 1.12 0.45 1.76 1.12 0.46 1.82 1.22 0.46 1.94 1.23 0.47 2.00 1.32 0.47 2.12 1.32 0.47 2.24 1.40 0.48
40 1.41 1.00 0.45 1.57 1.00 0.46 1.62 1.09 0.46 1.73 1.09 0.47 1.78 1.18 0.47 1.89 1.17 0.47 2.00 1.25 0.48
43 1.31 0.92 0.45 1.45 0.93 0.46 1.50 1.01 0.46 1.60 1.01 0.47 1.65 1.09 0.47 1.75 1.09 0.47 1.85 1.16 0.48
AFR 12.0
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 2.34 1.62 0.51 2.61 1.63 0.52 2.70 1.77 0.52 2.87 1.78 0.53 2.96 1.92 0.53 3.14 1.91 0.54 3.32 2.04 0.54
25 2.22 1.54 0.58 2.48 1.55 0.58 2.56 1.68 0.59 2.73 1.69 0.59 2.81 1.82 0.60 2.98 1.82 0.60 3.15 1.93 0.61
30 2.10 1.45 0.64 2.34 1.46 0.65 2.42 1.59 0.65 2.58 1.60 0.66 2.66 1.72 0.66 2.82 1.72 0.67 2.98 1.83 0.68
35 1.98 1.37 0.70 2.20 1.38 0.72 2.28 1.50 0.72 2.43 1.50 0.73 2.50 1.62 0.73 2.65 1.61 0.74 2.80 1.72 0.74
40 1.76 1.22 0.70 1.96 1.23 0.71 2.03 1.33 0.72 2.16 1.34 0.73 2.23 1.44 0.73 2.36 1.44 0.74 2.50 1.53 0.74
43 1.63 1.13 0.70 1.82 1.14 0.71 1.88 1.24 0.72 2.00 1.24 0.72 2.07 1.34 0.73 2.19 1.33 0.73 2.31 1.42 0.74
AFR 12.0
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 3.18 2.18 0.76 3.55 2.19 0.77 3.67 2.39 0.77 3.91 2.39 0.78 4.03 2.59 0.79 4.27 2.57 0.79 4.51 2.74 0.80
25 3.02 2.07 0.85 3.37 2.08 0.87 3.48 2.27 0.87 3.71 2.27 0.88 3.83 2.45 0.88 4.06 2.44 0.89 4.28 2.60 0.90
30 2.86 1.96 0.95 3.18 1.97 0.96 3.29 2.14 0.97 3.51 2.15 0.98 3.62 2.32 0.98 3.83 2.31 0.99 4.05 2.46 1.00
35 2.69 1.84 1.04 2.99 1.85 1.06 3.09 2.01 1.06 3.30 2.02 1.07 3.40 2.18 1.08 3.60 2.17 1.09 3.81 2.31 1.10
40 2.39 1.64 1.04 2.67 1.65 1.06 2.76 1.79 1.06 2.94 1.80 1.07 3.03 1.94 1.08 3.21 1.94 1.09 3.39 2.06 1.10
43 2.22 1.52 1.04 2.47 1.53 1.05 2.56 1.66 1.06 2.73 1.67 1.07 2.81 1.80 1.08 2.98 1.80 1.09 3.15 1.91 1.10
Page 13
- (01 - 10) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
HEATING CAPACITY6-2.
MODEL : ASG07LLCC
MODEL : ASG09LLCC
MODEL : ASG12LLCC
AFR: Air ow Rate (m³/min.) TC: Total Capaci ty (kW) IP: Input Po wer (kW)
AFR 12.3
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 2.42 1.22 2.36 1.24 2.30 1.27 2. 24 1.30 2.19 1.32
-10 -11 2.51 1.17 2.45 1.20 2.39 1.22 2.33 1.24 2. 27 1.27
-5 -7 2.75 1.15 2.68 1.18 2.61 1.20 2.55 1.23 2.48 1.25 0 -2 3.18 1.18 3.10 1.21 3.03 1.23 2.95 1.26 2.87 1.28 5 3 3.61 1.21 3.52 1.23 3.44 1.26 3.35 1.28 3.26 1.31 7 6 3.78 1.22 3.69 1.25 3.60 1.27 3.51 1.30 3.42 1.32
10 8 3.80 1.18 3.71 1.21 3.62 1.23 3.53 1.26 3.44 1.28 15 10 3.98 1.19 3.89 1.22 3.79 1.24 3.70 1.27 3.60 1.29
AFR 12.3
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 2.63 1.23 2.56 1.25 2.50 1.28 2.44 1.31 2.38 1.33
-10 -11 2.72 1.18 2.66 1.21 2.59 1.23 2.53 1.25 2.46 1.28
-5 -7 2.96 1.16 2.88 1.19 2.81 1.21 2.74 1.24 2.67 1.26 0 -2 3.39 1.20 3.31 1.22 3.23 1.25 3.14 1.27 3.06 1.30 5 3 3.82 1.23 3.73 1.25 3.64 1.28 3.54 1.30 3.45 1.33 7 6 3.99 1.24 3.90 1.27 3.80 1.29 3.71 1.32 3.61 1.34
10 8 3.94 1.18 3.84 1.21 3.75 1.23 3.66 1.26 3.56 1.28 15 10 4.11 1.19 4.01 1.22 3.91 1.24 3.81 1.27 3.71 1.29
AFR 12.3
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 3.17 1.39 3.10 1.42 3.02 1.45 2.94 1.48 2.87 1.51
-10 -11 3.35 1.44 3.27 1.47 3. 20 1.50 3.12 1.53 3.04 1.56
-5 -7 3.72 1.48 3.63 1.51 3.54 1.54 3.45 1.57 3.37 1.60 0 -2 4.36 1.51 4.25 1.54 4.15 1.57 4.05 1.60 3.94 1.63 5 3 5.00 1.53 4.88 1.57 4.76 1.60 4.64 1.63 4.52 1.66 7 6 5.25 1.55 5.13 1.58 5.00 1.61 4.88 1.64 4.75 1.67
10 8 4.90 1.38 4.78 1.41 4.66 1.44 4.55 1.47 4.43 1.50 15 10 5.15 1.39 5.02 1.42 4.90 1.45 4.78 1.48 4.66 1.51
Page 14
- (01 - 11) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
FAN PERFORMANCE AND CAPACITY7.
AIR VELOCITY DISTRIBUTION7-1.
MODEL : ASG07LLCC, ASG09LLCC, ASG12LLCC
Conditions:
Fan speed: HIGH
Operation mode: FAN
2.0
1.0
0.5
2
1
0
1
2
Unit : m/s(m)
(m)
TOP VIEW Vertic al air ow direction lou ver: Up Horizo ntal air ow direction l ouver: Ce nter
0 1 2 3 4 5 6 7 8
2.0
1.0
1.0
0.5
0.5
3
2
1
0
1
2
3
Unit : m/s(m)
TOP VIEW Vertic al air ow direction lou ver: Up Horizo ntal air ow direction l ouver: Ri ght & Left
(m)
0 1 2 3 4 5 6 7 8
2.0
1.0
0.5
3
2
1
0
Unit : m/s(m)
SIDE VIE W Vertic al air ow direction lou ver: Up Horizo ntal air ow direction l ouver: Ce nter
(m)
0 1 2 3 4 5 6 7 8
2.0
1.0
0.5
3
2
1
0
Unit : m/s(m)
SIDE VIE W Vertic al air ow direction lou ver: Down Horizo ntal air ow direction l ouver: Ce nter
(m)
0 1 2 3 4 5 6 7 8
Page 15
- (01 - 12) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
AIRFLOW7-2.
MODEL : ASG07LLCC, ASG09LLCC, ASG12LLCC
Cooling
z
z
Heating
Fan speed
Number of
rotations
(r.p.m)
Airow
HIGH 1320
m³/h 720
l/s 200
CFM 424
MED 112 0
m³/h 600
l/s 167
CFM 353
LOW 840
m³/h 420
l/s 117
CFM 247
QUIET 700
m³/h 325
l/s 90
CFM 191
Fan speed
Number of
rotations
(r.p.m)
Airow
HIGH 1360
m³/h 740
l/s 206
CFM 436
MED 112 0
m³/h 600
l/s 167
CFM 353
LOW 900
m³/h 450
l/s 125
CFM 265
QUIET 700
m³/h 325
l/s 90
CFM 191
Page 16
- (01 - 13) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
OPERATION NOISE (SOUND PRESSURE)8.
NOISE LEVEL CURVE8-1.
MODEL : ASG07LLCC, ASG09LLCC
High
Quiet
High
Quiet
High
Quiet
High
Quiet
Cooling
z
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 5 00 1,00 0 2,00 0 4,000 8 ,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 5 00 1,00 0 2,00 0 4,000 8 ,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 5 00 1,00 0 2,00 0 4,000 8 ,000
MODEL : ASG12LLCC
Cooling
z
Heating
z
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 5 00 1,00 0 2,00 0 4,000 8 ,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 17
- (01 - 14) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
SOUND LEVEL CHECK POINT8-2.
Page 18
- (01 - 15) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
ELECTRICAL CHARACTERISTICS9.
Model name ASG07LLCC ASG09LLCC ASG12LLCC
Power supply
Voltage V 230 ~
Frequency Hz 50
Max. operating current A 0.3
Wiring spec.
Connection cable mm
2
1.5
Limited wiring length m 21
Note : Wiring Spec.
1. Selected Sample (Selected based on Japan Electrotechnical Standards and Codes Committee E0 005)
2. Limited wiring length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 2% or more.
Page 19
- (01 - 16) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
SAFETY DEVICES10.
Protection form
Model
ASG07LLCC ASG09LLCC ASG12LLCC
Circuit protection Current fuse (PC board) 250V 3.15A
Fan motor protection Terminal protection program
OFF: 160 ± 25 °C
ON: 110 ± 25 °C
Page 20
- (01 - 17) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
FUNCTION SETTINGS11.
INDOOR UNIT (Setting by remote controller)11-1.
The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings may cause an indoor unit to malfunction.
After the power is turned on, perform the “Function Setting” according to the installation conditions using the remote controller.
The settings may be selected between the following two: Function Number and Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
PREPARATION
• Before turning on the power of the indoor unit:
- Conrm whether the piping air-tight test and vacuuming have been conducted.
- Reconrm whether there is no miswiring.
• Turn on the power of the indoor units.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP. (
) button simultaneously, press the RESET button to enter the
function setting mode.
STEP 1 Setting the Remote controller Custom Code
Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a custom code if the air conditioner has not been set for the custom code.) The custom code that is set through this process are applicable only during the Function Setting process. For details on how to set the custom code through the normal process, refer to the instructions under "REMOTE CONTROLLER CUSTOM CODE SETTING".
Press the SET TEMP. (1. ) ( ) button to change the custom code between → → → . Match the code on the display to the air conditioner custom code (initially set to ). (If the custom code does not need to be selected, press the MODE button and
proceed to
STEP 2
.)
Press the MODE button to accept the custom code, and proceed to 2.
STEP 2
.
*1
The air conditioner custom code is set to " " prior to shipment. Contact your retailer to change the custom code.
The remote controller resets to custom code when the batteries in the remote controller are replaced. If you use a custom code other than custom code , reset the custom code after replacing the batteries. If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you nd the code which operates the air conditioner.
STEP 2 Selecting the Function Number and Setting Value
Press the SET TEMP. (1. ) ( ) buttons to select the function number. (Press the MODE button to switch between the left and right digits.)
Press the FAN button to proceed to setting the value. 2. (Press the FAN button again to return to the function number
selection.)
Press the SET TEMP. (3. ) ( ) buttons to select the setting value. (Press the MODE button to switch between the left and right digits.)
Press the SLEEP button, then after you hear the beep emitted from 4. the indoor unit, the START/STOP button in order to x the settings.
Press the RESET button to end the function setting mode.5.
After completing the Function Setting, be sure to turn off the power 6. and turn it on again.
Function number
Setting value
*1
*1
CAUTION
After turning off the power, wait 30 seconds or more before turning on it again. The Function Setting will not become active unless the power is turned off then on again.
Note : *1) Small "A" is displayed on the right of the custom code during the FUNCTION SETTING.
Page 21
- (01 - 18) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
FUNCTION DETAILS
Functions
1) Filter sign
2) Room temperature control for cooling
3) Room temperature control for heating
4) Auto restart
5) Remote controller custom code
6) Indoor unit fan control for energy saving for cooling
1) Filter sign
Select appropriate intervals for displaying the lter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03).
(... Factory setting)
Setting description Function number Setting value
Standard (400 hours)
11
00
Long interval (1000 hours) 01
Short interval (200 hours) 02
No indication 03
2) Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
(... Factory setting)
Setting description Function number Setting value
Standard
30
00
Slightly lower control 01
Lower control 02
Higher control 03
3) Room temperature control for heating
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
(... Factory setting)
Setting description Function number Setting value
Standard
31
00
Lower control 01
Slightly higher control 02
Higher control 03
Page 22
- (01 - 19) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
4) Auto restart
Enable or disable automatic restart after a power interruption.
(... Factory setting)
Setting description Function number Setting value
Enable
40
00
Disable 01
* Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external input device.
5) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
(... Factory setting)
Setting description Function number Setting value
A
44
00
B 01 C 02 D 03
6) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
(
... Factory setting)
Setting description Function number Setting value
Disable
49
00
Enable 01
*00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the
setting on the remote controller.
*01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low
speed.
Page 23
- (01 - 20) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
REMOTE CONTROLLER CUSTOM CODE SETTING
Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a signal if the right signal code has not
been set.)
Press the MODE button for at least ve seconds to display the current custom 1. code (initially set to ).
Press the SET TEMP. (2. ) ( ) button to change the custom code between → → → . Match the code on the display to the air conditioner custom code.
Press the MODE button again. The custom code will be changed.3.
If no buttons are pressed within 30 seconds after the custom code is displayed, the display returns to the original status. In this case, start again from step 1.
The air conditioner custom code is set to A prior to shipment.
The remote controller resets to custom code A when the batteries in the remote controller are replaced. If you use a custom code other than custom code A, reset the custom code after replacing the batteries. If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you nd the code which operates the air conditioner.
Page 24
- (01 - 21) -
WALL MOUNTED TYPE
AS
G0 7-12L LC C
WALL MOUNTED TYPE
AS
G0 7-12L LC C
OPTIONAL PARTS12.
Exterior Parts name Model No. Summary
Remote
controller
holder
UT Z- RXLA
Wall or pillar mountable, and holds the remote controller.
Page 25
2.OUTDOOR UNIT
SINGLE TYPE :
AOG07LLCC
AOG09LLCC
AOG12LLCC
DTR_AO154E_01
2013.11.07
Page 26
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
CONTENTS
2. OUTDOOR UNIT
1. SPECIFICATIONS
.............................................................................................. 02 - 01
2. DIMENSIONS
........................................................................................................ 02 - 02
3. REFRIGERANT CIRCUIT
............................................................................ 02 - 03
4. WIRING DIAGRAMS
........................................................................................ 02 - 04
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
..................................................................... 02 - 05
6. ADDITIONAL CHARGE CALCULATION
......................................... 02 - 07
7. AIRFLOW
................................................................................................................. 02 - 08
8. OPERATION NOISE (SOUND PRESSURE)
................................. 02 - 09
8-1. NOISE LEVEL CURVE
.................................................................................... 02 - 09
8-2. SOUND LEVEL CHECK POINT
......................................................................02 - 11
9. ELECTRICAL CHARACTERISTICS
................................................... 02 - 12
10. SAFETY DEVICES
............................................................................................ 02 - 13
Page 27
- (02 - 01) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
SPECIFICATIONS1.
NOTES:
Speci cations are base d on the foll owing conditio ns. Coolin g: Indoor te mperature of 27 °CD B / 19 °CWB and ou tdoor tem peratur e of 35 °CDB / 2 4 °CWB. Heating : Indoor te mperatu re of 20 °CD B / 15 °CWB and ou tdoor tem peratur e of 7 °CDB / 6 °C WB. Pipe leng th: 5 m, Heig ht diffe rence: 0 m. (Ou tdoor uni t - Indoor u nit)
The prote ctive fu nction m ight work w hen usin g it out the op eratio n range.
Typ e INVERT ER COOLI NG & HEATING
Model na me AOÛG07LLCC AOÛG09L LCC AOÛG12LLC C
Power sour ce 230 V~ 50 H z
Available v oltage r ange 198-26 4 V
Start ing current A 3.0 3.5 5.4
Fan
Air ow ra te
Cooling
m3/h
1,670 1,83 0
Heating 1,470 1,60 0
Type × Q'ty Pr opelle r fan × 1
Motor out put W 23
Sound pre ssure leve l
Cooling
dB (A)
47 50
Heating 48 51
Sound pow er level
Cooling
dB (A)
61 65
Heating 61 65
Heat excha nger typ e
Dimensi ons (H × W × D)
mm
650 × 50 4 × 18.2
642 × 504 × 18 .2 612 × 504 × 18.2
Fin pitch 1.3 1.4
Rows × Stag es 1 × 24 2 × 24
Pipe typ e Copper
Fin type Alumi nium
Compressor
Type × Q'ty Rotar y × 1
Motor out put W 610 670
Refrigerant
Type (Global War ming Poten tial) R410A (1975)
Charge g 650 850
Refrig erant oil Typ e POE (VG74)
Enclosu re
Material Steel
Colour
BEIGE
(Approx imate co lour of MU NSELL 10YR 7.5/1.0)
Dimensions (H × W × D)
Net
mm
535 × 66 3 × 293
Gross 595 × 790 × 3 95
Weight
Net
kg
24 26
Gross 27 29
Connec tion pip e
Size
Liquid
mm
Ø 6.35 (Ø 1/4 in.)
Gas Ø 9.52 (Ø 3/8 in.)
Method Flare
Pre- charge l ength
m
15
Max. len gth 20
Max. hei ght dif ferenc e 15
Operat ion rang e
Cooling
°C
-10 to 43
Heating -15 to 24
Page 28
- (02 - 02) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
INSTALLATION PLACE
If the space is larger than stated, the condition will be the same as those without any obstacles.
600 mm or more
100 mm or more
200 mm or more
100 mm or more
250 mm or more
(Service space)
CAUTION
When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold weather. (Reverse cycle model only) In areas with heavy snowfall, if the intake and outlet of outdoor unit is blocked with snow, it might become difficult to get warm and it is likely to cause breakdown. Please construct a canopy and a pedestal or place the unit on a high stand (local configured).
DIMENSIONS2.
MODELS : AOG07LLCC, AOG09LLCC, AOG12LLCC
(Unit : mm)
Page 29
- (02 - 03) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
REFRIGERANT CIRCUIT3.
MODELS : AOG07LLCC, AOG09LLCC, AOG12LLCC
Refrigerant pipe diameter Liquid: 1/4" (6.35mm) Gas:
3/8" (9.52 mm)
: Cooling : Heating
Page 30
- (02 - 04) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
WIRING DIAGRAMS4.
MODEL :
AOG07LLCC, AOG09LLCC,
AOG12LLCC
Page 31
- (02 - 05) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
MODEL: AO
G07LLCC, AOG09LLCC
H H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5 7. 5 10 15 20
Height difference H
(m)
Û
1
Indoor unit is higher
than outdoor unit.
15
- - -
0.832
0.822
10 - - 0.917 0.832 0.822
7. 5 - 0.961 0.917 0.832 0.822
5 1.000 0.961 0.917 0.832 0.822
0 1.000 0.961 0.917 0.832 0.822
Û
2
Indoor unit is lower
than outdoor unit.
-5 0.995 0.956 0.912 0.828 0.818
-7. 5 - 0.954 0.910 0.826 0.816
-10 - - 0.908 0.824 0.814
-15 - - - 0.815 0.805
COOLING
Pipe length (m)
5 7. 5 10 15 20
Height difference H
(m)
Û
1
Indoor unit is higher
than outdoor unit.
15 - -
-
0.872
0.910
10 - - 0.961 0.886 0.925
7. 5 - 0.979 0.965 0.890 0.929
5 0.992 0.983 0.969 0.893 0.933
0 1.000 0.991 0.976 0.901 0.940
Û
2
Indoor unit is lower
than outdoor unit.
-5 1.000 0.991 0.976 0.901 0.940
-7. 5 - 0.991 0.976 0.901 0.940
-10 - - 0.976 0.901 0.940
-15 - - - 0.901 0.940
Page 32
- (02 - 06) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
MODEL : AOG12LLCC
H H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
COOLING
Pipe length (m)
5 7. 5 10 15 20
Height difference H
(m)
Û
1
Indoor unit is higher
than outdoor unit.
15
- - - 0.858 0.868
10
- - 0.929 0.872 0.882
7. 5
- 0.960 0.933 0.876 0.885
5
0.992 0.964 0.937 0.879 0.889
0
1.000 0.972 0.944 0.887 0.896
Û
2
Indoor unit is lower
than outdoor unit.
-5
1.000 0.972 0.944 0.887 0.896
-7. 5
- 0.972 0.944 0.887 0.896
-10
- - 0.944 0.887 0.896
-15
- - - 0.887 0.896
HEATING
Pipe length (m)
5 7. 5 10 15 20
Height difference H
(m)
Û
1
Indoor unit is higher
than outdoor unit.
15
- - - 0.896 0.879
10
- - 0.968 0.890 0.879
7. 5
- 0.994 0.968 0.896 0.879
5
1.000 0.994 0.968 0.896 0.879
0
1.000 0.994 0.968 0.896 0.879
Û
2
Indoor unit is lower
than outdoor unit.
-5
0.995 0.989 0.963 0.891 0.875
-7. 5
- 0.987 0.961 0.889 0.873
-10
- - 0.959 0.887 0 .871
-15
- - - 0.878 0.862
Page 33
- (02 - 07) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
ADDITIONAL CHARGE CALCULATION6.
MODELS : AOG07LLCC, AOG09LLCC
Refrigerant charge
z
MODEL : AOG12LLCC
Refrigerant charge
z
Refrigerant type R410A
Refrigerant amount g 650
Total pipe length m 15 or less 20 (Max.)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 850
Total pipe length m 15 or less 20 (Max.)
20g/m
Additional charge g 0 100
Page 34
- (02 - 08) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
AIRFLOW7.
MODELS : AOG07LLCC, AOG09LLCC
Cooling
z
Heating
z
MODEL : AOG12LLCC
Cooling
z
Heating
z
Number of
rotations
(r.p.m.)
Airow
730
m
3
/h 1670
l/s 464
CFM 984
Number of
rotations
(r.p.m.)
Airow
650
m
3
/h 1470
l/s 408
CFM 866
Number of
rotations
(r.p.m.)
Airow
860
m
3
/h 1830
l/s 508
CFM 1078
Number of
rotations
(r.p.m.)
Airow
760
m
3
/h 1600
l/s 444
CFM 942
Page 35
- (02 - 09) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
OPERATION NOISE (SOUND PRESSURE)8.
NOISE LEVEL CURVE8-1.
MODEL : AOG07LLCC
MODEL : AOG09LLCC
Heating
z
Cooling
z
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2,0 00 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2,0 00 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Cooling
z
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2,0 00 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2,0 00 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 36
- (02 - 10) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
MODEL : AOG12LLCC
Cooling
z
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2,0 00 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB: (0 d B=0. 0002 µ bar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2,0 00 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 37
- (02 - 11) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
SOUND LEVEL CHECK POINT8-2.
Airflow
1 m
Page 38
- (02 - 12) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
ELECTRICAL CHARACTERISTICS9.
Model name
AOÛG07LLCC AOÛG09 LLCC AOÛG12LLCC
Power supply
Voltage V
230 ~
Frequency Hz
50
Max. operating current *1 A
7. 5 7. 5 9.0
Starting current A
3.0 3.5 5.4
Wiring spec. *2
Circuit breaker current A
15
Power cable mm
2
1.5
*1: The maximum current is the total current of indoor unit and outdoor unit.
*2: Wiring spec.: Selected sample
(Selected based on Japan Electrotechnical Standards and Codes Committee E0005)
Page 39
- (02 - 13) -
OUTDOOR UNIT
AO
G07-12LLCC
OUTDOOR UNIT
AO
G07-12LLCC
SAFETY DEVICES10.
Protection form
Model
AOÛG07LLCC
AOÛG09LLCC
AOÛG12LLCC
Circuit protection
Current fuse (Main printed circuit board)
250V 25A
250V 5A
Fan motor protection Terminal protection program
OFF: 100 ± 15 °C
ON: 95 ± 10 °C
Compressor protection
Terminal protection program (Discharge temp.)
OFF: 110°C
ON: After 7 minutes