Air flow mode can be set in 4 steps and more detailed air flow setting is possible.
Fan speedNoise level
Quiet21
(ASG07/09/12LE)
OUTDOOR UNIT
Low noise mode
Introduction of a low outdoor noise operation mode allow the outdoor unit to have quiet mode
operation setting.
* Performance may drop depending on the outside air temperature condition, etc.
Rated noise value -3dB
dB(A)
- (01 - 01) -
Page 5
G07-14LE
WALL MOUNTED TYPE
AS
10°C HEAT Operation
G07-14LE
WALL MOUNTED TYPE
AS
The room temperature can be set to go no lower than 10°C,
thus ensuring that the room does not get too cold when not occupied
Caution)
When the room temperature is higher than 10°C, “10°C HE AT” operation does not start. Operation starts and maintains the room •
temperature at 10°C when the temperature drops below 10°C.
“10°C HEAT”
Button ON
Indoor unit
operation START
Powerful operation
20
°C
10
°C
20 minutes continuous operation by maximum airflow and maximum compressor speed is
possible. Rapid cooling and heating makes the room comfortable quickly.
Temperature
Powerful
Setting temp.
Low outdoor air temperature correspondence
Normal mode
Time
Corresponds to cooling operation at -10°C outdoor air temperature
Corresponds to heating operation at -15°C outdoor air temperature
CoolingHeating
-10 to 43
Corresponds to maximum 20m long piping
°C
-15 to 24
°C
- (01 - 02) -
Page 6
G07-14LE
WALL MOUNTED TYPE
AS
Air conditioner filter features
G07-14LE
WALL MOUNTED TYPE
AS
Dirty Air
Ion Deodorization Filter
Apple-catechin Filter
Clean Air
Long-life Ion
Deodorization Filter
Easy maintenance
Applecatechin Filter
Easy maintenance and always clean. Troublesome maintenance has been made easy.
Since the front panel is easy to remove, maintenance is also easy.
- (01 - 03) -
Page 7
WIRELESS REMOTE CONTROLLER2.
60
C
°C
°C °C
FEATURES
G07-14LE
WALL MOUNTED TYPE
AS
Four kinds of timer setup
(On / Off / Program / Sleep) are possible.
Four kinds of timers. Easy operation.
Easy to change transmission code (4 patterns) by button operation.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
Select from four different timer programs (On / Off / Program / Sleep).
Program timer
G07-14LE
WALL MOUNTED TYPE
AS
The program timer operates the on and off timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to
the timer setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 1 °C every hour. The set
temperature can rise up to a maximum of 2 °C.
Timer setting
min.
°
Switching remote controller signal code
After code change
Mixed-up
I.U. I.U. I.U. I.U.
AB CD
I.U. I.U. I.U. I.U.
2 °C
Heating operation
When the sleep timer is set, the set temperature
automatically drops 1 °C every 30 minutes. The set
temperature can drop to a maximum of 4 °C.
2
min.
min.
min.
Timer setting
4 °C
ABCD
Code selector switch eliminates unit
•
being wrongly switched.
(Up to 4 codes can be set.)
*I.U.=Indoor unit
- (01 - 04) -
Page 8
G07-14LE
WALL MOUNTED TYPE
AS
FUNCTIONS
2
3
4
5
6
7
8
10
11
12
13
14
15
16
17
18
1
Signal Transmitter
1
9
2
10 °C HEAT button
3
MODE button
4
ECONOMY button
5
OUTDOOR UNIT LOW NOISE button
6
ON TIMER button
7
OFF TIMER button
8
CLOCK ADJUST button
9
POWERFUL button
10
SET TEMP. button ( / )
11
START/STOP button
12
FAN button
13
SWING button
14
SET button
15
SLEEP TIMER button
16
CANCEL button
17
RESET button
18
TIMER SET button ( / )
G07-14LE
WALL MOUNTED TYPE
AS
Display panel
19
20
21
22
To facilitate explanation, the accompanying
illustration has been drawn to show all
possible indicators; in actual operation,
however, the display will only show those
indicators appropriate to the current
operation.
23
24
25
26
19
Remote Controller Display
20
Operation Mode Display
21
ENERGY SAVING MODE Display
22
LOW NOISE MODE Display
23
Temperature SET Display
24
FAN Speed Display
25
SWING Display
26
Clock & TIMER Display
SPECIFICATION
SIZE (H x W x D mm)205 x 61 x 17
WEIGHT ( g )122
ACCESSORYHolder
- (01 - 05) -
Page 9
SPECIFIC ATIONS3.
G07-14LE
WALL MOUNTED TYPE
AS
Typ e
Model nameASG07LECAASG09LECAASG12LECAASG14LECA
Power source230V~ 50Hz
Available voltage range198 -264V~ 50 Hz
Note:
Specifications are based on the following conditions
Cooling:Indoor temperature of 27°C CDB/19°CCWB.and outdoor temperature of 35°C CDB/24°CCWB.
Heating:Indoor temperature of 20°C CDB/15°CCWB.and outdoor temperature of 7°C CDB/6°CCWB.
Pipe length:5m,Height difference:0m(Outdoor unit-Indoor unit)
The maximum current is the maximum value when the operated within the operation range(temperature).
AFR : Air flow rate (m3/min)
TC : Total capaci ty (kW)
IP :Input P ower (kW)
Indoor temperature
Indoor temperature
- (01 - 12) -
Page 16
FAN PERFORMANCE7.
G07-14LE
WALL MOUNTED TYPE
AS
AIR VELOCITY DISTRIBUTION7-1.
MODEL :ASG07LE, ASG09LE, ASG12LE
2
1
0
1
2
3
2
1
2.0
012345678
1.0
Unit : m/s(m)
0.5
Unit : m/s(m)
TOP VIEW
Vert ical fla p : Up
Horizontal flap : Ce nter
(m)
TOP VIEW
Vert ical fla p : Up
Horizontal flap : Ri ght & Left
Note:
Fan speed : High
Operation mode : FAN
G07-14LE
WALL MOUNTED TYPE
AS
0.5
1.0
0
2.0
1.0
1
0.5
2
3
012345678
3
2
2.0
1.0
1
0
012345678
3
2
1
2.0
1.0
Unit : m/s(m)
0.5
Unit : m/s(m)
0.5
(m)
SIDE VIEW
Vert ical fla p : Up
Horizontal flap : Ce nter
(m)
SIDE VIEW
Vert ical fla p : Down
Horizontal flap : Ce nter
0
012345678
- (01 - 13) -
(m)
Page 17
G07-14LE
WALL MOUNTED TYPE
AS
MODEL :ASG14LE
Note:
Fan speed : High
Operation mode : FAN
G07-14LE
WALL MOUNTED TYPE
AS
2
1
0
1
2
012345678
2
1
2.0
1.0
1.0
0
2.0
1.0
1
Unit : m/s(m)
0.5
Unit : m/s(m)
0.5
0.5
TOP VIEW
VERTIC AL FLAP : U pward
HORIZO NTAL FLAP : C enter
(m)
TOP VIEW
VERTIC AL FLAP : U pward
HORIZO NTAL FLAP : R ight & Left
2
012345678
3
Unit : m/s(m)
0.5
2
1
0
012345678
3
2
2.01.0
Unit : m/s(m)
2.0
1
0
012345678
1.0
0.5
(m)
SIDE VIEW
VERTIC AL FLAP : U pward
HORIZO NTAL FLAP : C enter
(m)
SIDE VIEW
VERTIC AL FLAP : D ownward
HORIZO NTAL FLAP : C enter
(m)
- (01 - 14) -
Page 18
G07-14LE
WALL MOUNTED TYPE
AS
AIR FLOW7-2.
MODEL :ASG07LE, ASG09LE, ASG12LE
Cooling
G07-14LE
WALL MOUNTED TYPE
AS
Fan speed
rotations
HIGH1400
MED1200
LOW920
QUIET620
Number of
(r.p.m.)
Air flow
690m
3
/h
191 l/s
406 CFM
3
610m
/h
169 l/s
359 CFM
3
440m
/h
122 l/s
259 CFM
3
300m
/h
83 l/s
176
CFM
Heating
Fan speed
HIGH1440
MED1200
LOW980
QUIET670
Number of
rotations
(r.p.m.)
Air flow
710m
3
/h
197 l/s
417 CFM
3
610m
/h
169 l/s
359 CFM
3
480m
/h
133 l/s
282 CFM
3
310m
/h
86 l/s
182
CFM
- (01 - 15) -
Page 19
G07-14LE
WALL MOUNTED TYPE
AS
MODEL :ASG14LE
Cooling
G07-14LE
WALL MOUNTED TYPE
AS
Fan speed
rotations
HIGH1400
MED1230
LOW1000
QUIET750
Number of
(r.p.m.)
Air flow
770m
3
/h
213 l/s
453 CFM
3
680m
/h
188 l/s
400 CFM
3
540m
/h
150 l/s
318 CFM
3
410m
/h
114 l / s
241
CFM
Heating
Fan speed
HIGH1400
MED1230
LOW1050
QUIET770
Number of
rotations
(r.p.m.)
Air flow
770m
3
/h
213 l/s
453 CFM
3
680m
/h
188 l/s
400 CFM
3
580m
/h
161 l/s
341 CFM
3
420m
/h
116 l /s
247
CFM
- (01 - 16) -
Page 20
OPERATION NOISE8.
G07-14LE
WALL MOUNTED TYPE
AS
NOISE LEVEL CURVE8-1.
MODEL :ASG07LE
Cooling
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
G07-14LE
WALL MOUNTED TYPE
AS
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
MODEL :ASG09LE
Cooling
80
80
70
70
60
60
50
50
40
40
High
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Heating
80
80
70
70
60
60
50
50
40
40
High
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
- (01 - 17) -
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
Page 21
G07-14LE
WALL MOUNTED TYPE
AS
MODEL :ASG12LE
G07-14LE
WALL MOUNTED TYPE
AS
Cooling
80
70
60
50
High
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
High
Quiet
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL :ASG14LE
Cooling
80
80
70
70
60
60
50
50
40
40
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
80
70
70
60
60
50
50
40
40
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
- (01 - 18) -
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
Page 22
G07-14LE
WALL MOUNTED TYPE
AS
SOUND LEVEL CHECK POINT8-2.
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 19) -
Page 23
ELECTRIC CHARACTERISTICS9.
G07-14LE
WALL MOUNTED TYPE
AS
Model nameASG07LEASG09LEASG12LEASG14LE
Power supply
Max. operating currentA0.4
*1)Wiring Spec.
*1) Wiring Spec.
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
Volt ageV23 0~
FrequencyHz50
Connection cablemm
Limited wiring lengthm21
2
1.0 -1.51.5
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 20) -
Page 24
SAFETY DEVICES10.
G07-14LE
WALL MOUNTED TYPE
AS
Protection form
Model
ASG07LE
ASG09LE
G07-14LE
WALL MOUNTED TYPE
AS
ASG12LE
ASG14LE
Circuit protectionCurrent fuse (PCB)3.15A 250V
Terminal protectionCurrent (thermal) fuse3A 250V
+15
100
°C OFF
Fan motor protectionThermal protector program
95
+5
-10
-10
°C ON
- (01 - 21) -
Page 25
EXTERNAL INPUT & OUTPUT11.
G07-14LE
WALL MOUNTED TYPE
AS
Connector INPUTOUTPUT REMARKS
CN303Control input-See external
CN304-Operation status output
input/output settings
for details.
G07-14LE
WALL MOUNTED TYPE
AS
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Initial starting after power turned onStarting other than at the left
Operation modeAuto changeoverMode at previous operation
Set temperature24°CTemperature at previous operation
Air flow modeAUTOMode at previous operation
Up-down air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Left-right air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Circuit diagram example
Indoor
control PC boardCommunication kit
Connector
Connected unit
Ex.) Switch
1
3
*10 m
Signal
Optional parts
* Make the distance from the PC board to the connected unit within 10m.
Contact capacity : 24VDC or more, 10mA or more.
Please use the non-polar relays and switches.
When function setting is "Operation/Stop" mode
Input signal
Indoor unit
ON
OFF
Operation
Stop
Field supply
- (01 - 22) -
Page 26
G07-14LE
WALL MOUNTED TYPE
AS
When function setting is "Forced stop" mode
G07-14LE
WALL MOUNTED TYPE
AS
Input signal
Command
Indoor unit
Remote controller
Parts (Optional)
Parts name
On
Off
Forced stop
Normal
Operation
Stop
Model name
OnOnOn
Remote control
operation invalidity
External connect kitUTY-XWZX
Communication box kit
* For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to
the wire (UTY-XWZX).
UTY-XCBXE (for ASG07/09/12LE)
UTY-XCBXZ1 (for ASG14LE)
Wire (External input) : UTY-XWZX
- (01 - 23) -
Page 27
G07-14LE
WALL MOUNTED TYPE
AS
OPERATION STATUS OUTPUT
EXTERNAL OUTPUT11-2.
G07-14LE
WALL MOUNTED TYPE
AS
An air conditioner operation status signal can be output.
Circuit diagram example
Indoor
control PC boardCommunication kitConnected unit
Indoor unit
Output signal
Optional parts
Operation
Stop
ON
OFF
Connector
1
2
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Max.24VDC, 10mA to less than 500mA.
24V DC
V
*10 m
Ex.)Relay unit
Signal
Field supply
Ex.)Display
Relay
power
supply
Parts (Optional)
Parts name
Model name
External connect kitUTY-XWZX
Communication box kit
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(UTY-XWZX).
UTY-XCBXE (for ASG07/09/12LE)
UTY-XCBXZ1 (for ASG14LE)
Wire (External output) : UTY-XWZX
- (01 - 24) -
Page 28
FUNCTION SETTING12.
G07-14LE
WALL MOUNTED TYPE
AS
INDOOR UNIT (Setting by remote controller)12-1.
The function settings of the control of the indoor unit can be changed by this procedure according •
G07-14LE
WALL MOUNTED TYPE
AS
to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation •
conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. •
Settings will not be changed if invalid numbers or setting values are selected. •
PREPARATION
Turn o n t he p o w e r •
* By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have been conducted
before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP. (
•
function setting mode.
STEP 1
Setting the Remote controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note
that the air conditioner cannot receive a signal code if the air conditioner has not
been set for the signal code.) The signal codes that are set through this process are
applicable only to the signals in the FUNCTION SETTING. For details on how to set
the signal codes through the normal process, refer to SELECTING THE REMOTE
CONTROLLER SIGNAL CODE.
Press the SET TEMP. (1.
→
→ Match the code on the display to the air conditioner signal code. (initially
set to
(If the signal code does not need to be selected, press the 10°C Heat button and
proceed to STEP 2.)
Press the MODE button and check that the indoor unit can receive signals at the 2.
displayed signal code.
Press the 10°C Heat button to accept the signal code, and proceed to STEP 2.3.
)
) ( ) button to change the signal code between →
) simultaneously, press the RESET button to enter the
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a
signal code other than signal code A, reset the signal code after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes (
find the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
Press the SET TEMP. (1.
(Press the 10°C Heat button to switch between the left and right
digits.)
Press the POWERFUL button to proceed to setting the value. 2.
Press the POWERFUL button again to return to the function number
selection.)
Press the SET TEMP. (3.
(Press the 10°C Heat button to switch between the left and right
digits.)
Press the MODE button, and START/STOP button, in the order listed 4.
to confirm the settings.
Press the RESET button to cancel the function setting mode.5.
After completing the FUNCTION SETTING, be sure to turn off the 6.
power and turn it on again.
After turning off the power, wait 10 seconds or more before turning on it again.
The FUNCTION SETTING doesn’t become effective if it doesn’t do so.
) ( ) buttons to select the function number.
) ( ) buttons to select the setting value.
CAUTION
F unction numbe r
→→→ ) until you
Setting
value
- (01 - 25) -
Page 29
G07-14LE
WALL MOUNTED TYPE
AS
FUNCTION DETAILS
G07-14LE
WALL MOUNTED TYPE
AS
Functions
1) Filt er sign
2) Cooler room temperature correction
3) Heater room temperature correction
4) Auto restart
Indoor room temperature sensor
5)
switching function
6) Remote controller signal code
7) External input control
Compact wall
mounted
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time
setting for the filter sign display interval in the table below according to the amount of dust or
debris in the room. If you do not wish the filter sign to be displayed, select the setting value for
"No indication".
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Long interval01
Short interval02
No indication03
11
00
The filter sign interval time is different according to Indoor unit type as follows.
Setting description
Standard 400 hours
Long interval1000 hours
Short interval200 hours
Compact Wall
Mounted
2) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below.
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Slightly lower control01
Lower control02
Warmer control03
30
00
3) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below.
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Lower control01
Slightly warmer control02
Warmer control03
31
00
- (01 - 26) -
Page 30
G07-14LE
WALL MOUNTED TYPE
AS
4) Auto restart
G07-14LE
WALL MOUNTED TYPE
AS
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting descriptionFunction numberSetting value
Yes
No01
40
00
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.
5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller
temperature sensor.
(... Factory setting)
Setting descriptionFunction numberSetting value
No
Yes01
42
00
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller
unit sensor.
6) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(... Factory setting)
Setting descriptionFunction numberSetting value
A
B01
C02
D03
44
00
7) External inpu t control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(... Factory setting)
Setting descriptionFunction numberSetting value
Operation/Stop mode
(Setting forbidden)01
Forced stop mode02
46
00
- (01 - 27) -
Page 31
G07-14LE
WALL MOUNTED TYPE
AS
REMOTE CONTROLLER SIGNAL CODE SETTING
Use the following steps to select the signal code of the remote controller.
(Note that the air conditioner cannot receive a signal code if the air conditioner has
not been set for the signal code.)
Press the START/STOP button until only the clock is displayed on the remote 1.
controller display.
Press the MODE button for at least five seconds to display the current signal code 2.
(initially set to
Press the SET TEMP. (3.
→
→ .
Match the code on the display to the air conditioner signal code.
Press the MODE button again to return to the clock display. The signal code will 4.
be changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original
clock display. In this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use
a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the
air conditioner signal code setting, try each of the signal codes (
operates the air conditioner.
).
) ( ) button to change the signal code between →
→→→ ) until you find the code which
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 28) -
Page 32
OPTIONAL PARTS13.
G07-14LE
WALL MOUNTED TYPE
AS
ExteriorParts nameModel No.Summary
Unit control is performed by
Wired remote
controller
Simple remote
controller
Communication
box kit
UTY-RNNYM
UTY-RSNYM
UTY-XCBXE
wired remote controller.
*Optional communication kit is
necessary for the installation.
Unit control is performed by
simple remote controller.
*Optional communication kit is
necessary for the installation.
Use to connect with optional
devices and air conditioner
PC board.
(for ASG07/09/12LE)
G07-14LE
WALL MOUNTED TYPE
AS
Communication
kit
External
connect kit
Apple-catechin
filter
UTY-XCBXZ1
UTY-XWZX
UTR-FA16
Use to connect with optional
devices and air conditioner
PC board.
(for ASG14LE)
Required when external device
is connected.
*Optional communication kit is
necessary for the installation.
Fine dust, invisible mold
spores, and harmful
microorganisms are absorbed
onto the fi lter by static
electricity, and further growth
is inhibited and deactivated
by the polyphenol ingredient
extracted from apples.
Ion
deodorisation
filter
- (01 - 29) -
UTR-FA16-2
The filter deodorizes by
powerfully decomposing
absorbed odors using the
oxidizing and reducing effects
of ions generated by the ultra
fine-particle ceramic.
TypeINVERTER HEAT PUMP
Model nameAOG07LECAOG09LECAOG12LECAOG14LEC
Power sourse230V~ 50Hz
Available voltage range198-264V ~ 50Hz
Starting currentA3.53.84.76.0
Fan
Airflow rate
Cooling
Heati ng1,510 1,600 1,66 0
Type×Q'tyPropeller fan×1
3
m
/h
Motor outputW40
Sound pressure level
Heat exchanger type
Cooling
Heating45 50 50
Dimensions(H×W×D)
dB(A)
mm
Fin pitch1.31.41.3
Rows×Stages1 × 242× 24
Pipe typeCopper
Fin TypeAluminium
Compressor
Refrigerant
Type×Q'tyRotary×1
Motor outputW500 750
TypeR410A
Chargeg650 800 1050
Refrigerant oilTypePOE(VG74)
MaterialSteel
Enclosure
Dimensions
(H×W×D)
Weight
Netmm540 × 660 ×290
Grossmm611 × 797 × 401
Net
Gross26(57)32(71)38(84)
Colour
kg (lbs.)
Liquid
Connenction pipe
Size
GasØ9.52 (Ø3/8in.)
MethodFlare
mm
Pre-charge length
Max.length20
m
Max.height difference15
Operation range
Cooling
Heating-15 to 24
°C
1,720 1,830 1,800
4550 49
650 × 504 × 18.2
642 × 504 ×
36.4
896 × 504 ×
36.4
Beige
Approximate colour of MUNSELL 10YR7.5/1.0
540 × 790 ×
290
648 × 938 ×
400
23(51)29(64)34(75)
Ø6.35 (Ø1/4 in.)
Ø12.7
(Ø1/2in.)
15
-10 to 43
G07-14LE
OUTDOOR UNIT
AO
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
The maximum current is the maximum value when the operated within the operation range(temperature).
- (02 - 01) -
Page 36
DIMENSIONS2.
MODEL :AOG07LE, AOG09LE, AOG12LE
(Unit : mm)
G07-14LE
OUTDOOR UNIT
AO
G07-14LE
OUTDOOR UNIT
AO
INSTALLATION PLACE
When there are obstacles at
the back or front sides.
100 mm
or more
600 mm
or more
When there are obstacles at
the back, side(s), and top.
600 mm or more
100 mm
or more
300 mm or more
(Service space)
- (02 - 02) -
300 mm
or more
When there are obstacles at the
back, side with the installation of
more than one unit.
300 mm
or more
300 mm
or more
300 mm
or more
Page 37
MODEL :AOG14LE
(Unit : mm)
G07-14LE
OUTDOOR UNIT
AO
G07-14LE
OUTDOOR UNIT
AO
INSTALLATION PLACE
When there are obstacles at
the back or front sides.
100 mm
or more
600 mm
or more
When there are obstacles at
the back, side(s), and top.
600 mm or more
100 mm
or more
250 mm or more
(Service space)
- (02 - 03) -
300 mm
or more
When there are obstacles at the
back, side with the installation of
more than one unit.