Fujitsu AS*G07LECA, AS*G12LECA, AS*G14LECA, AO*G07LEC, AO*G09LEC Design & Technical Manual

...
Page 1
AIR CONDITIONER
Wall Mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ASG07LECA ASG09LECA ASG12LECA
AOG07LEC AOG09LEC AOG12LEC
ASG14LECA
AOG14LEC
Page 2
1. INDOOR UNIT
WALL MOUNTED TYPE :
ASG07LECA ASG09LECA ASG12LECA ASG14LECA
DTR_AS049E_03
2011.03.23
Page 3
G07-14LE
WALL MOUNTED TYPE
AS
CONTENTS
G07-14LE
WALL MOUNTED TYPE
AS
1. INDOOR UNIT
1. FEATURE
.................................................................................................................. 01 - 01
2. WIRELESS REMOTE CONTROLLER
3. SPECIFICATIONS
4. DIMENSIONS
5. WIRING DIAGRAMS
6. CAPACITY TABLE
6-1. COOLING CAPACITY 6-2. HEATING CAPACITY
7. FAN PERFORMANCE
7-1. AIR VELOCITY DISTRIBUTION 7-2. AIR FLOW
.......................................................................................................... 01 - 15
8. OPERATION NOISE
8-1. NOISE LEVEL CURVE
.............................................................................................. 01 - 06
........................................................................................................ 01 - 07
........................................................................................ 01 - 10
.............................................................................................01 - 11
.......................................................................................01 - 11
....................................................................................... 01 - 12
.................................................................................... 01 - 13
..................................................................... 01 - 13
......................................................................................... 01 - 17
.................................................................................... 01 - 17
............................................... 01 - 04
8-2. SOUND LEVEL CHECK POINT
..................................................................... 01 - 19
9. ELECTRIC CHARACTERISTICS
10. SAFETY DEVICES
11. EXTERNAL INPUT & OUTPUT
11-1. EXTERNAL INPUT 11-2. EXTERNAL OUTPUT
12. FUNCTION SETTING
13. OPTIONAL PARTS
............................................................................................ 01 - 21
............................................................... 01 - 22
........................................................................................... 01 - 22
....................................................................................... 01 - 24
...................................................................................... 01 - 25
........................................................................................... 01 - 29
........................................................... 01 - 20
Page 4
FEATURE1.
MODEL
G07-14LE
WALL MOUNTED TYPE
AS
ASG07LECA / AOG07LEC ASG09LECA / AOG09LEC
G07-14LE
WALL MOUNTED TYPE
AS
ASG12LECA / AOG12LEC ASG14LECA / AOG14LEC
FEATURES
Energy-Efciency classication A
ASG07LECA ASG09LECA ASG12LECA
AOG07LEC AOG09LEC AOG12LEC
Europe Energy-Efciency classication A achieved
ALL DC
a
ASG14LECA
AOG14LEC
a
DC fan motor
b
compressor
DC
a
b
Front view
Quiet operation
INDOOR UNIT
Air ow mode can be set in 4 steps and more detailed air ow setting is possible.
Fan speed Noise level
Quiet 21
(ASG07/09/12LE)
OUTDOOR UNIT
Low noise mode Introduction of a low outdoor noise operation mode allow the outdoor unit to have quiet mode
operation setting.
* Performance may drop depending on the outside air temperature condition, etc.
Rated noise value -3dB
dB(A)
- (01 - 01) -
Page 5
G07-14LE
WALL MOUNTED TYPE
AS
10°C HEAT Operation
G07-14LE
WALL MOUNTED TYPE
AS
The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied
Caution)
When the room temperature is higher than 10°C, “10°C HE AT” operation does not start. Operation starts and maintains the room
temperature at 10°C when the temperature drops below 10°C.
“10°C HEAT”
Button ON
Indoor unit operation START
Powerful operation
20
°C
10
°C
20 minutes continuous operation by maximum airow and maximum compressor speed is possible. Rapid cooling and heating makes the room comfortable quickly.
Temperature
Powerful
Setting temp.
Low outdoor air temperature correspondence
Normal mode
Time
Corresponds to cooling operation at -10°C outdoor air temperature Corresponds to heating operation at -15°C outdoor air temperature
Cooling Heating
-10 to 43
Corresponds to maximum 20m long piping
°C
-15 to 24
°C
- (01 - 02) -
Page 6
G07-14LE
WALL MOUNTED TYPE
AS
Air conditioner lter features
G07-14LE
WALL MOUNTED TYPE
AS
Dirty Air
Ion Deodorization Filter
Apple-catechin Filter
Clean Air
Long-life Ion Deodorization Filter
Easy maintenance
Apple­catechin Filter
Easy maintenance and always clean. Troublesome maintenance has been made easy.
Since the front panel is easy to remove, maintenance is also easy.
- (01 - 03) -
Page 7
WIRELESS REMOTE CONTROLLER2.
60
C
°C
°C °C
FEATURES
G07-14LE
WALL MOUNTED TYPE
AS
Four kinds of timer setup
(On / Off / Program / Sleep) are possible.
Four kinds of timers. Easy operation.
Easy to change transmission code (4 patterns) by button operation.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
Select from four different timer programs (On / Off / Program / Sleep).
Program timer
G07-14LE
WALL MOUNTED TYPE
AS
The program timer operates the on and off timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the timer setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 1 °C every hour. The set temperature can rise up to a maximum of 2 °C.
Timer setting
min.
°
Switching remote controller signal code
After code change
Mixed-up
I.U. I.U. I.U. I.U.
AB CD
I.U. I.U. I.U. I.U.
2 °C
Heating operation
When the sleep timer is set, the set temperature automatically drops 1 °C every 30 minutes. The set temperature can drop to a maximum of 4 °C.
2
min.
min.
min.
Timer setting
4 °C
ABCD
Code selector switch eliminates unit
• being wrongly switched. (Up to 4 codes can be set.)
*I.U.=Indoor unit
- (01 - 04) -
Page 8
G07-14LE
WALL MOUNTED TYPE
AS
FUNCTIONS
2
3
4
5
6
7
8
10
11
12
13
14
15
16 17
18
1
Signal Transmitter
1
9
2
10 °C HEAT button
3
MODE button
4
ECONOMY button
5
OUTDOOR UNIT LOW NOISE button
6
ON TIMER button
7
OFF TIMER button
8
CLOCK ADJUST button
9
POWERFUL button
10
SET TEMP. button ( / )
11
START/STOP button
12
FAN button
13
SWING button
14
SET button
15
SLEEP TIMER button
16
CANCEL button
17
RESET button
18
TIMER SET button ( / )
G07-14LE
WALL MOUNTED TYPE
AS
Display panel
19
20
21
22
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current operation.
23
24
25
26
19
Remote Controller Display
20
Operation Mode Display
21
ENERGY SAVING MODE Display
22
LOW NOISE MODE Display
23
Temperature SET Display
24
FAN Speed Display
25
SWING Display
26
Clock & TIMER Display
SPECIFICATION
SIZE (H x W x D mm) 205 x 61 x 17
WEIGHT ( g ) 122
ACCESSORY Holder
- (01 - 05) -
Page 9
SPECIFIC ATIONS3.
G07-14LE
WALL MOUNTED TYPE
AS
Typ e
Model name ASG07LECA ASG09LECA ASG12LECA ASG14LECA Power source 230V~ 50Hz Available voltage range 198 -264V~ 50 Hz
European energy label
Cooling
Capacity
Heating
Input power
Current
EER Cooling COP Heating 4.38 4.27 4.04 3.83 SENSIBLE CAPACITY Cooling kW 1.2 1.6 2.2 2.6
POWER FACTOR
Moisture removal l/h(pints/h) 1.3 (2.3) 1.3 (2.3) 1.8 (3.2) 2.1 (3.7)
FAN
Sound pressure level
Heat exchanger type
Enclosure
Dimensions (H×W×D)
Weight
Connection pipe
Operation range
Remote controller type Wireless
Drain pipe
Cooling
Heating
Cooling
Heating
Cooling Heating 85 86 92 94
Airow rate
Type× Q’ty Cross ow fanx1 Motor output W 30
Net Gross 259x840x328 263x840x375 Net Gross 9.5(21) 10.5(23)
Size
Method Flare
Material PP+LLDPE Size mm Outer diameter:21/Outer diameter:13.6
Rated
Min-Max
Rated
Min-Max
Rated Min-Max 0.25~1.19 0.25~1.27 0.25~1.40 0.25~2.03 Rated 0.685 0.75 0.99 1.305 Min-Max 0.25~1.60 0.25~1.60 0.25~1.99 0.25~2.40 Rated Max 6.0 6.0 6.5 9.0 Rated 3.5 3.8 4.7 6.0 Max 7.5 7.5 9.0 10.5
High
Cooling
Heating
Cooling
Heating
Dimensions (H×W×D)
Fin pitch 1.1
Rows Stages 2x16
Pipe type Copper Fin type Aluminium Material Polystyrene
Colour
Liquid Gas Ø9.52(Ø3/8in) Ø12.7(Ø1/2in)
Cooling
Heating °C 30 or less
Med 610 680 Low 440 540 Quiet 300 410 High 710 770 Med 610 680 Low 480 580 Quiet 310 420
High Med 38 40 Low 31 33 Quiet 21 25 High 43 44 Med 38 40 Low 31 35 Quiet 21 27
CoolingAAAA HeatingAAAA
kW 2.10 2.50 3.40 4.00
BTU/h 7,200 8,500 11,600 13,600
kW 0.5~3.0 0.5~3.2 0.9~3.9 0.9~5.0
BTU/h 1,700~10,200 1,700~10,900 3,100~13,300 3,100~17,100
kW 3.00 3.20 4.00 5.00
BTU/h 10,200 10,900 13,600 17,100
kW 0.5~4.0 0.5~4.2 0.9~5.3 0.9~6.4
BTU/h 1,700~13,600 1,700~14,300 3,100~18,000 3,100~21,800
kW
A
kW/kW
%
3
/h
m
dB(A)
mm
mm
kg(lbs.)
mm
°C 18 to 32
%RH 80 or less
0.47 0.64 0.92 1.105
2.7 3.5 4.4 5.3
4.47 3.91 3.70 3.62
76 80 91 91
Approximate colour of MUNSELL N9.25/
WALL MOUNTED
INVERTER HEAT PUMP
690 770
43 44
256x630x20
White
260x790x198 260x790x203
7. 5(17) 8(1 8)
Ø6.35(Ø1/4in)
320x630x20
Sub:84x630x13.3
1.1
Sub:1.4
2x20
Sub:1x4
G07-14LE
WALL MOUNTED TYPE
AS
Note: Specications are based on the following conditions Cooling:Indoor temperature of 27°C CDB/19°CCWB.and outdoor temperature of 35°C CDB/24°CCWB. Heating:Indoor temperature of 20°C CDB/15°CCWB.and outdoor temperature of 7°C CDB/6°CCWB. Pipe length:5m,Height difference:0m(Outdoor unit-Indoor unit) The maximum current is the maximum value when the operated within the operation range(temperature).
- (01 - 06) -
Page 10
DIMENSIONS4.
G07-14LE
WALL MOUNTED TYPE
AS
MODEL  :ASG07LE, ASG09LE, ASG12LE
(Unit : mm)
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 07) -
Page 11
G07-14LE
WALL MOUNTED TYPE
AS
MODEL  :ASG14LE
(Unit : mm)
G07-14LE
WALL MOUNTED TYPE
AS
Outline of unit
18
47
62
ø2-65 for pipe inlet
209
94
18
52
78
ø2-65 for pipe inlet
215
184
47
450
82
323
237
327
353: Gas pipe
415: Liquid pipe
- (01 - 08) -
Page 12
G07-14LE
WALL MOUNTED TYPE
AS
INSTALLATION PLACE
G07-14LE
WALL MOUNTED TYPE
AS
(Unit : mm)
63 or more
45 or more
Outline of unit
52 or more
70 or more
48 or more
100 or more
1500 or more
- (01 - 09) -
1800 or more
Page 13
WIRING DIAGRAMS5.
G07-14LE
WALL MOUNTED TYPE
AS
MODEL  :ASG07LE, ASG09LE, ASG12LE, ASG14LE
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 10) -
Page 14
CAPACITY TABLE6.
G07-14LE
WALL MOUNTED TYPE
AS
COOLING CAPACITY6-1.
MODEL  :ASG07LE
AFR 11.5
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 1.97 1.22 0.33 2.19 1.23 0.34 2.26 1.33 0.34 2.41 1.34 0.34 2.49 1.45 0.34 2.64 1.44 0.35 2.79 1.53 0.35
25 1.87 1.16 0.37 2.08 1.17 0.38 2.15 1.27 0.38 2.29 1.27 0.38 2.36 1.37 0.38 2.50 1.37 0.39 2.65 1.46 0.39
30 1.76 1.10 0.41 1.97 1.10 0.42 2.03 1.20 0.42 2.17 1.20 0.42 2.23 1.30 0.43 2.37 1.29 0.43 2.50 1.38 0.44
35 1.66 1.03 0.45 1.85 1.04 0.46 1.91 1.13 0.46 2.04 1.13 0.47 2.10 1.22 0.47 2.23 1.22 0.47 2.35 1.29 0.48
40 1.48 0.92 0.45 1.65 0.92 0.46 1.70 1.00 0.46 1.82 1.01 0.47 1.87 1.09 0.47 1.98 1.08 0.47 2.10 1.15 0.48
Outdoor temperature
43 1.37 0.85 0.45 1.53 0.86 0.46 1.58 0.93 0.46 1.68 0.93 0.47 1.74 1.01 0.47 1.84 1.00 0.47 1.94 1.07 0.48
Indoor temperature
G07-14LE
WALL MOUNTED TYPE
AS
MODEL  :ASG09LE
AFR 11.5
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 2.34 1.62 0.45 2.61 1.63 0.46 2.70 1.77 0.46 2.87 1.78 0.46 2.96 1.92 0.47 3.14 1.91 0.47 3.32 2.04 0.48
25 2.22 1.54 0.50 2.48 1.55 0.51 2.56 1.68 0.52 2.73 1.69 0.52 2.81 1.82 0.52 2.98 1.82 0.53 3.15 1.93 0.53
30 2.10 1.45 0.56 2.34 1.46 0.57 2.42 1.59 0.57 2.58 1.60 0.58 2.66 1.72 0.58 2.82 1.72 0.59 2.98 1.83 0.59
35 1.98 1.37 0.62 2.20 1.38 0.63 2.28 1.50 0.63 2.43 1.50 0.64 2.50 1.62 0.64 2.65 1.61 0.65 2.80 1.72 0.65
40 1.76 1.22 0.62 1.96 1.23 0.63 2.03 1.33 0.63 2.16 1.34 0.64 2.23 1.44 0.64 2.36 1.44 0.65 2.50 1.53 0.65
Outdoor temperature
43 1.63 1.13 0.62 1.82 1.14 0.62 1.88 1.24 0.63 2.00 1.24 0.63 2.07 1.34 0.64 2.19 1.33 0.64 2.31 1.42 0.65
Indoor temperature
MODEL  :ASG12LE
AFR 11.5
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 3.18 2.18 0.63 3.55 2.19 0.64 3.67 2.38 0.64 3.91 2.39 0.65 4.03 2.58 0.65 4.27 2.57 0.66 4.51 2.74 0.67
25 3.03 2.08 0.72 3.37 2.09 0.73 3.49 2.27 0.73 3.72 2.28 0.74 3.83 2.46 0.74 4.06 2.45 0.75 4.29 2.61 0.76
30 2.86 1.96 0.80 3.19 1.97 0.81 3.30 2.15 0.82 3.52 2.15 0.82 3.63 2.32 0.83 3.84 2.32 0.84 4.06 2.47 0.85
35 2.69 1.84 0.89 2.99 1.85 0.90 3.09 2.01 0.91 3.30 2.02 0.92 3.40 2.18 0.92 3.60 2.17 0.93 3.81 2.31 0.94
40 2.27 1.56 0.83 2.53 1.57 0.84 2.62 1.70 0.84 2.79 1.71 0.85 2.87 1.84 0.86 3.05 1.84 0.86 3.22 1.96 0.87
Outdoor temperature
43 2.09 1.43 0.83 2.33 1.44 0.84 2.41 1.57 0.84 2.57 1.57 0.85 2.65 1.70 0.86 2.81 1.69 0.87 2.96 1.80 0.87
Indoor temperature
MODEL  :ASG14LE
AFR 12.8
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 3.72 2.58 0.77 4.14 2.60 0.78 4.29 2.83 0.79 4.57 2.83 0.79 4.71 3.06 0.80 4.99 3.05 0.81 5.28 3.25 0.81
25 3.55 2.46 0.87 3.95 2.48 0.88 4.08 2.69 0.89 4.35 2.70 0.89 4.49 2.92 0.90 4.76 2.91 0.91 5.03 3.10 0.92
30 3.36 2.34 0.97 3.75 2.35 0.98 3.87 2.55 0.99 4.13 2.56 1.00 4.26 2.77 1.00 4.51 2.76 1.01 4.77 2.94 1.02
35 3.16 2.19 1.07 3.52 2.21 1.08 3.64 2.40 1.09 3.88 2.41 1.10 4.00 2.60 1.11 4.24 2.59 1.12 4.48 2.76 1.13
40 2.78 1.93 1.05 3.09 1.94 1.07 3.20 2.11 1.07 3.41 2.12 1.08 3.51 2.28 1.09 3.73 2.28 1.10 3.94 2.42 1.11
Outdoor temperature
43 2.53 1.76 1.03 2.82 1.77 1.05 2.91 1.92 1.06 3.11 1.93 1.07 3.20 2.08 1.07 3.39 2.07 1.08 3.59 2.21 1.09
Indoor temperature
AFR : Air ow rate (m3/min) TC : Total capac ity (kW) SHC : Sens ible Heat c apacit y (kW) IP :Input P ower (kW)
- (01 - 11) -
Page 15
G07-14LE
WALL MOUNTED TYPE
AS
HEATING CAPACITY6-2.
MODEL  :ASG07LE
AFR 11.8
G07-14LE
WALL MOUNTED TYPE
AS
(°CDB) 16 18 20 2 2 24
(°CDB) (°CWB) TC IP TC IP TC IP TC IP TC I P
-15 -16 2.2 5 0.9 9 2.19 1. 01 2.14 1.03 2.0 9 1.0 5 2. 03 1. 07
-10 -11 2.5 6 1.0 2 2.5 0 1.0 4 2.4 3 1.0 6 2.3 7 1.08 2.31 1.11
-5 -7 2 .93 1.05 2 .86 1.07 2 .79 1.10 2 .72 1.12 2. 65 1.14 0 -2 3.47 1. 09 3. 39 1.12 3.31 1.14 3 .23 1.16 3 .14 1.19 5 3 4.05 1.15 3.96 1.17 3.86 1.19 3.76 1.22 3.67 1.24 7 6 4.20 1.17 4.10 1. 20 4. 00 1. 22 3.90 1. 25 3 .80 1.27
10 8 4.4 2 1.19 4.31 1.21 4.21 1.2 4 4.10 1.26 4.00 1.29
Outdoo r temperature
15 10 4.58 1.18 4.47 1.20 4.36 1.23 4.25 1.25 4.14 1.27
MODEL  :ASG09LE
AFR 11.8
(°CDB) 16 18 20 2 2 24
(°CDB) (°CWB) TC IP TC IP TC IP TC IP TC I P
-15 -16 2.2 5 0.9 9 2.19 1. 01 2.14 1.03 2.0 9 1.0 5 2. 03 1. 07
-10 -11 2.5 6 1.0 2 2.5 0 1.0 4 2.4 3 1.0 6 2.3 7 1.08 2.31 1.11
-5 -7 2 .93 1.05 2 .86 1.07 2 .79 1.10 2 .72 1.12 2. 65 1.14 0 -2 3.47 1. 09 3. 39 1.12 3.31 1.14 3 .23 1.16 3 .14 1.19 5 3 4.05 1.15 3.96 1.17 3.86 1.19 3.76 1.22 3.67 1.24 7 6 4.41 1.17 4.31 1.20 4. 20 1.22 4.10 1.25 3.99 1.27
10 8 4.6 4 1.19 4 .53 1.21 4.42 1. 24 4. 31 1.2 6 4.2 0 1.29
Outdoo r temperature
15 10 4.81 1.18 4.69 1.20 4.58 1.23 4.46 1.25 4.35 1.27
MODEL  :ASG12LE
AFR 11.8
Indoor temperature
Indoor temperature
(°CDB) 16 18 20 2 2 24
(°CDB) (°CWB) TC IP TC IP TC IP TC IP TC I P
-15 -16 3.4 0 1.72 3 .32 1.76 3. 24 1.8 0 3.16 1.83 3.07 1. 87
-10 -11 3.7 6 1.72 3. 67 1.76 3 .58 1.7 9 3.49 1.83 3.4 0 1.86
-5 -7 4.18 1.72 4.08 1.76 3.9 8 1.79 3.88 1.8 3 3.78 1.87 0 -2 4.68 1.72 4.57 1.76 4.46 1.80 4.35 1.83 4.24 1.87 5 3 5.0 5 1.5 2 4.9 3 1.5 5 4.81 1.5 8 4.6 9 1.61 4.57 1.64 7 6 5.3 6 1.51 5 .23 1.54 5 .10 1.5 7 4.97 1.60 4. 85 1.63
10 8 5.5 5 1.51 5 .42 1. 54 5. 29 1.57 5.16 1. 60 5.02 1.6 3
Outdoo r temperature
15 10 5.5 4 1.41 5.41 1.4 4 5.28 1.47 5.15 1. 50 5. 01 1.5 3
MODEL  :ASG14LE
AFR 12.8
(°CDB) 16 18 20 2 2 24
(°CDB) (°CWB) TC IP TC IP TC IP TC IP TC I P
-15 -16 3.47 1.78 3.39 1.81 3. 30 1.8 5 3.22 1.89 3.14 1. 93
-10 -11 4.15 1. 87 4.05 1.91 3.95 1.95 3.85 1.99 3.7 6 2.03
-5 -7 4.78 1.97 4.67 2.01 4.55 2.06 4.44 2.10 4.33 2.14 0 -2 5.59 2.07 5.46 2.11 5.32 2.16 5.19 2.20 5.06 2.24 5 3 6.40 2.17 6.24 2.21 6.09 2.26 5.94 2.30 5.79 2.35 7 6 6.72 1.80 6.56 1.83 6.40 1.87 6.24 1.91 6.08 1.94
10 8 7.14 1.8 0 6. 97 1.8 4 6.80 1.8 8 6.63 1.9 2 6.46 1.9 6
Outdoo r temperature
15 10 7.46 1. 81 7.28 1.85 7.11 1.89 6. 93 1.93 6.75 1.97
AFR : Air ow rate (m3/min) TC : Total capaci ty (kW)
IP :Input P ower (kW)
Indoor temperature
Indoor temperature
- (01 - 12) -
Page 16
FAN PERFORMANCE7.
G07-14LE
WALL MOUNTED TYPE
AS
AIR VELOCITY DISTRIBUTION7-1.
MODEL  :ASG07LE, ASG09LE, ASG12LE
2
1
0
1
2
3
2
1
2.0
012345678
1.0
Unit : m/s(m)
0.5
Unit : m/s(m)
TOP VIEW Vert ical a p : Up Horizontal flap : Ce nter
(m)
TOP VIEW Vert ical a p : Up Horizontal flap : Ri ght & Left
Note:
Fan speed : High
Operation mode : FAN
G07-14LE
WALL MOUNTED TYPE
AS
0.5
1.0
0
2.0
1.0
1
0.5
2
3
012345678
3
2
2.0
1.0
1
0
012345678
3
2
1
2.0
1.0
Unit : m/s(m)
0.5
Unit : m/s(m)
0.5
(m)
SIDE VIEW Vert ical a p : Up Horizontal flap : Ce nter
(m)
SIDE VIEW Vert ical a p : Down Horizontal flap : Ce nter
0
012345678
- (01 - 13) -
(m)
Page 17
G07-14LE
WALL MOUNTED TYPE
AS
MODEL  :ASG14LE
Note:
Fan speed : High
Operation mode : FAN
G07-14LE
WALL MOUNTED TYPE
AS
2
1
0
1
2
012345678
2
1
2.0
1.0
1.0
0
2.0
1.0
1
Unit : m/s(m)
0.5
Unit : m/s(m)
0.5
0.5
TOP VIEW VERTIC AL FLAP : U pward HORIZO NTAL FLAP : C enter
(m)
TOP VIEW VERTIC AL FLAP : U pward HORIZO NTAL FLAP : R ight & Left
2
012345678
3
Unit : m/s(m)
0.5
2
1
0
012345678
3
2
2.0 1.0
Unit : m/s(m)
2.0
1
0
012345678
1.0
0.5
(m)
SIDE VIEW VERTIC AL FLAP : U pward HORIZO NTAL FLAP : C enter
(m)
SIDE VIEW VERTIC AL FLAP : D ownward HORIZO NTAL FLAP : C enter
(m)
- (01 - 14) -
Page 18
G07-14LE
WALL MOUNTED TYPE
AS
AIR FLOW7-2.
MODEL  :ASG07LE, ASG09LE, ASG12LE
Cooling
G07-14LE
WALL MOUNTED TYPE
AS
Fan speed
rotations
HIGH 1400
MED 1200
LOW 920
QUIET 620
Number of
(r.p.m.)
Air ow
690 m
3
/h
191 l/s
406 CFM
3
610 m
/h
169 l/s
359 CFM
3
440 m
/h
122 l/s
259 CFM
3
300 m
/h
83 l/s
176
CFM
Heating
Fan speed
HIGH 1440
MED 1200
LOW 980
QUIET 670
Number of
rotations
(r.p.m.)
Air ow
710 m
3
/h
197 l/s
417 CFM
3
610 m
/h
169 l/s
359 CFM
3
480 m
/h
133 l/s
282 CFM
3
310 m
/h
86 l/s
182
CFM
- (01 - 15) -
Page 19
G07-14LE
WALL MOUNTED TYPE
AS
MODEL  :ASG14LE
Cooling
G07-14LE
WALL MOUNTED TYPE
AS
Fan speed
rotations
HIGH 1400
MED 1230
LOW 1000
QUIET 750
Number of
(r.p.m.)
Air ow
770 m
3
/h
213 l/s
453 CFM
3
680 m
/h
188 l/s
400 CFM
3
540 m
/h
150 l/s
318 CFM
3
410 m
/h
114 l / s
241
CFM
Heating
Fan speed
HIGH 1400
MED 1230
LOW 1050
QUIET 770
Number of
rotations
(r.p.m.)
Air ow
770 m
3
/h
213 l/s
453 CFM
3
680 m
/h
188 l/s
400 CFM
3
580 m
/h
161 l/s
341 CFM
3
420 m
/h
116 l /s
247
CFM
- (01 - 16) -
Page 20
OPERATION NOISE8.
G07-14LE
WALL MOUNTED TYPE
AS
NOISE LEVEL CURVE8-1.
MODEL  :ASG07LE
Cooling
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
G07-14LE
WALL MOUNTED TYPE
AS
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
MODEL  :ASG09LE
Cooling
80
80
70
70
60
60
50
50
40
40
High
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Heating
80
80
70
70
60
60
50
50
40
40
High
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
- (01 - 17) -
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
Page 21
G07-14LE
WALL MOUNTED TYPE
AS
MODEL  :ASG12LE
G07-14LE
WALL MOUNTED TYPE
AS
Cooling
80
70
60
50
High
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μ bar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
High
Quiet
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL  :ASG14LE
Cooling
80
80
70
70
60
60
50
50
40
40
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
80
70
70
60
60
50
50
40
40
30
30
20
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
10
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
- (01 - 18) -
0
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Octave band center frequency,Hz
Page 22
G07-14LE
WALL MOUNTED TYPE
AS
SOUND LEVEL CHECK POINT8-2.
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 19) -
Page 23
ELECTRIC CHARACTERISTICS9.
G07-14LE
WALL MOUNTED TYPE
AS
Model name ASG07LE ASG09LE ASG12LE ASG14LE
Power supply
Max. operating current A 0.4
*1)Wiring Spec.
*1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
Volt age V 23 0~ Frequency Hz 50
Connection cable mm Limited wiring length m 21
2
1.0 -1.5 1.5
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 20) -
Page 24
SAFETY DEVICES10.
G07-14LE
WALL MOUNTED TYPE
AS
Protection form
Model
ASG07LE ASG09LE
G07-14LE
WALL MOUNTED TYPE
AS
ASG12LE ASG14LE
Circuit protection Current fuse (PCB) 3.15A 250V
Terminal protection Current (thermal) fuse 3A 250V
+15
100
°C OFF
Fan motor protection Thermal protector program
95
+5
-10
-10
°C ON
- (01 - 21) -
Page 25
EXTERNAL INPUT & OUTPUT11.
G07-14LE
WALL MOUNTED TYPE
AS
Connector INPUT OUTPUT REMARKS
CN303 Control input - See external
CN304 - Operation status output
input/output settings
for details.
G07-14LE
WALL MOUNTED TYPE
AS
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit. Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Initial starting after power turned on Starting other than at the left
Operation mode Auto changeover Mode at previous operation Set temperature 24°C Temperature at previous operation
Air ow mode AUTO Mode at previous operation Up-down air direction (swing) Standard air direction (swing OFF) Air direction at previous operation Left-right air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
Indoor
control PC board Communication kit
Connector
Connected unit
Ex.) Switch
1
3
*10 m
Signal
Optional parts
* Make the distance from the PC board to the connected unit within 10m. Contact capacity : 24VDC or more, 10mA or more. Please use the non-polar relays and switches.
When function setting is "Operation/Stop" mode
Input signal
Indoor unit
ON
OFF
Operation
Stop
Field supply
- (01 - 22) -
Page 26
G07-14LE
WALL MOUNTED TYPE
AS
When function setting is "Forced stop" mode
G07-14LE
WALL MOUNTED TYPE
AS
Input signal
Command
Indoor unit
Remote controller
Parts (Optional)
Parts name
On Off
Forced stop
Normal
Operation
Stop
Model name
On On On
Remote control operation invalidity
External connect kit UTY-XWZX
Communication box kit
* For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to
the wire (UTY-XWZX).
UTY-XCBXE (for ASG07/09/12LE)
UTY-XCBXZ1 (for ASG14LE)
Wire (External input) : UTY-XWZX
- (01 - 23) -
Page 27
G07-14LE
WALL MOUNTED TYPE
AS
OPERATION STATUS OUTPUT
EXTERNAL OUTPUT11-2.
G07-14LE
WALL MOUNTED TYPE
AS
An air conditioner operation status signal can be output.
Circuit diagram example
Indoor
control PC board Communication kit Connected unit
Indoor unit
Output signal
Optional parts
Operation
Stop
ON
OFF
Connector
1
2
* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Max.24VDC, 10mA to less than 500mA.
24V DC
V
*10 m
Ex.)Relay unit
Signal
Field supply
Ex.)Display
Relay
power
supply
Parts (Optional)
Parts name
Model name
External connect kit UTY-XWZX
Communication box kit
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(UTY-XWZX).
UTY-XCBXE (for ASG07/09/12LE)
UTY-XCBXZ1 (for ASG14LE)
Wire (External output) : UTY-XWZX
- (01 - 24) -
Page 28
FUNCTION SETTING12.
G07-14LE
WALL MOUNTED TYPE
AS
INDOOR UNIT (Setting by remote controller)12-1.
The function settings of the control of the indoor unit can be changed by this procedure according
G07-14LE
WALL MOUNTED TYPE
AS
to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the “FUNCTION SETTING” according to the installation
conditions using the remote controller. The settings may be selected between the following two: Function Number or Setting Value. • Settings will not be changed if invalid numbers or setting values are selected.
PREPARATION
Turn o n t he p o w e r
* By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have been conducted
before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP. (
• function setting mode.
STEP 1 Setting the Remote controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) The signal codes that are set through this process are applicable only to the signals in the FUNCTION SETTING. For details on how to set the signal codes through the normal process, refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE.
Press the SET TEMP. (1.
Match the code on the display to the air conditioner signal code. (initially set to (If the signal code does not need to be selected, press the 10°C Heat button and proceed to STEP 2.)
Press the MODE button and check that the indoor unit can receive signals at the 2. displayed signal code.
Press the 10°C Heat button to accept the signal code, and proceed to STEP 2.3.
)
) ( ) button to change the signal code between
) simultaneously, press the RESET button to enter the
The air conditioner signal code is set to A prior to shipment. Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes ( nd the code which operates the air conditioner.
STEP 2 Selecting the Function Number and Setting Value
Press the SET TEMP. (1. (Press the 10°C Heat button to switch between the left and right digits.)
Press the POWERFUL button to proceed to setting the value. 2. Press the POWERFUL button again to return to the function number selection.)
Press the SET TEMP. (3. (Press the 10°C Heat button to switch between the left and right digits.)
Press the MODE button, and START/STOP button, in the order listed 4. to conrm the settings.
Press the RESET button to cancel the function setting mode.5.
After completing the FUNCTION SETTING, be sure to turn off the 6. power and turn it on again.
After turning off the power, wait 10 seconds or more before turning on it again. The FUNCTION SETTING doesn’t become effective if it doesn’t do so.
) ( ) buttons to select the function number.
) ( ) buttons to select the setting value.
CAUTION
F unction numbe r
) until you
Setting value
- (01 - 25) -
Page 29
G07-14LE
WALL MOUNTED TYPE
AS
FUNCTION DETAILS
G07-14LE
WALL MOUNTED TYPE
AS
Functions
1) Filt er sign
2) Cooler room temperature correction
3) Heater room temperature correction
4) Auto restart
Indoor room temperature sensor
5) switching function
6) Remote controller signal code
7) External input control
Compact wall
mounted
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the lter. Select the time setting for the lter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the lter sign to be displayed, select the setting value for "No indication".
(... Factory setting)
Setting description Function number Setting value
Standard
Long interval 01
Short interval 02
No indication 03
11
00
The lter sign interval time is different according to Indoor unit type as follows.
Setting description
Standard 400 hours
Long interval 1000 hours
Short interval 200 hours
Compact Wall
Mounted
2) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
Slightly lower control 01
Lower control 02
Warmer control 03
30
00
3) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
Lower control 01
Slightly warmer control 02
Warmer control 03
31
00
- (01 - 26) -
Page 30
G07-14LE
WALL MOUNTED TYPE
AS
4) Auto restart
G07-14LE
WALL MOUNTED TYPE
AS
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting description Function number Setting value
Yes
No 01
40
00
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
(... Factory setting)
Setting description Function number Setting value
No
Yes 01
42
00
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
6) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(... Factory setting)
Setting description Function number Setting value
A B01 C02 D03
44
00
7) External inpu t control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(... Factory setting)
Setting description Function number Setting value
Operation/Stop mode
(Setting forbidden) 01
Forced stop mode 02
46
00
- (01 - 27) -
Page 31
G07-14LE
WALL MOUNTED TYPE
AS
REMOTE CONTROLLER SIGNAL CODE SETTING
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has
not been set for the signal code.)
Press the START/STOP button until only the clock is displayed on the remote 1. controller display.
Press the MODE button for at least ve seconds to display the current signal code 2. (initially set to
Press the SET TEMP. (3.
.
Match the code on the display to the air conditioner signal code.
Press the MODE button again to return to the clock display. The signal code will 4. be changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original clock display. In this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment. Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes ( operates the air conditioner.
).
) ( ) button to change the signal code between
) until you nd the code which
G07-14LE
WALL MOUNTED TYPE
AS
- (01 - 28) -
Page 32
OPTIONAL PARTS13.
G07-14LE
WALL MOUNTED TYPE
AS
Exterior Parts name Model No. Summary
Unit control is performed by
Wired remote
controller
Simple remote
controller
Communication
box kit
UTY-RNNYM
UTY-RSNYM
UTY-XCBXE
wired remote controller.
*Optional communication kit is
necessary for the installation.
Unit control is performed by simple remote controller.
*Optional communication kit is
necessary for the installation.
Use to connect with optional devices and air conditioner PC board. (for ASG07/09/12LE)
G07-14LE
WALL MOUNTED TYPE
AS
Communication
kit
External
connect kit
Apple-catechin
lter
UTY-XCBXZ1
UTY-XWZX
UTR-FA16
Use to connect with optional devices and air conditioner PC board. (for ASG14LE)
Required when external device is connected.
*Optional communication kit is
necessary for the installation.
Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the lter by static electricity, and further growth is inhibited and deactivated by the polyphenol ingredient extracted from apples.
Ion
deodorisation
lter
- (01 - 29) -
UTR-FA16-2
The lter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra ne-particle ceramic.
Page 33
2. OUTDOOR UNIT
SINGLE TYPE :
AOG07LEC AOG09LEC
AOG12LEC AOG14LEC
DTR_AO072E_02
2011.03.03
Page 34
2. OUTDOOR UNIT
CONTENTS
G07-14LE
OUTDOOR UNIT
AO
1. SPECIFICATIONS
2. DIMENSIONS
3. REFRIGERANT CIRCUIT
4. WIRING DIAGRAMS
.............................................................................................. 02 - 01
........................................................................................................ 02 - 02
............................................................................ 02 - 04
........................................................................................ 02 - 05
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
6. ADDITIONAL CHARGE CALCULATION
7. AIR FLOW
8. OPERATION NOISE
8-1. NOISE LEVEL CURVE 8-2. SOUND LEVEL CHECK POINT
.................................................................................................................02 - 11
......................................................................................... 02 - 13
.................................................................................... 02 - 13
..................................................................... 02 - 07
......................................... 02 - 10
..................................................................... 02 - 15
G07-14LE
OUTDOOR UNIT
AO
9. ELECTRIC CHARACTERISTICS
10. SAFETY DEVICES
............................................................................................ 02 - 17
........................................................... 02 - 16
Page 35
G07-14LE
OUTDOOR UNIT
AO
SPECIFIC ATIONS1.
Type INVERTER HEAT PUMP Model name AOG07LEC AOG09LEC AOG12LEC AOG14LEC Power sourse 230V~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current A 3.5 3.8 4.7 6.0
Fan
Airow rate
Cooling Heati ng 1,510 1,600 1,66 0
Type×Q'ty Propeller fan×1
3
m
/h
Motor output W 40
Sound pressure level
Heat exchanger type
Cooling Heating 45 50 50
Dimensions(H×W×D)
dB(A)
mm Fin pitch 1.3 1.4 1.3 Rows×Stages 1 × 24 2× 24 Pipe type Copper Fin Type Aluminium
Compressor
Refrigerant
Type×Q'ty Rotary×1 Motor output W 500 750
Type R410A Charge g 650 800 1050
Refrigerant oil Type POE(VG74)
Material Steel
Enclosure
Dimensions (H×W×D)
Weight
Net mm 540 × 660 ×290
Gross mm 611 × 797 × 401
Net Gross 26(57) 32(71) 38(84)
Colour
kg (lbs.)
Liquid
Connenction pipe
Size
Gas Ø9.52 (Ø3/8in.)
Method Flare
mm
Pre-charge length Max.length 20
m
Max.height difference 15
Operation range
Cooling Heating -15 to 24
°C
1,720 1,830 1,800
45 50 49
650 × 504 × 18.2
642 × 504 ×
36.4
896 × 504 ×
36.4
Beige
Approximate colour of MUNSELL 10YR7.5/1.0
540 × 790 ×
290
648 × 938 ×
400
23(51) 29(64) 34(75)
Ø6.35 (Ø1/4 in.)
Ø12.7
(Ø1/2in.)
15
-10 to 43
G07-14LE
OUTDOOR UNIT
AO
Note : Specications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB. Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) The maximum current is the maximum value when the operated within the operation range(temperature).
- (02 - 01) -
Page 36
DIMENSIONS2.
MODEL  :AOG07LE, AOG09LE, AOG12LE
(Unit : mm)
G07-14LE
OUTDOOR UNIT
AO
G07-14LE
OUTDOOR UNIT
AO
INSTALLATION PLACE
When there are obstacles at the back or front sides.
100 mm or more
600 mm or more
When there are obstacles at the back, side(s), and top.
600 mm or more
100 mm or more
300 mm or more
(Service space)
- (02 - 02) -
300 mm
or more
When there are obstacles at the back, side with the installation of more than one unit.
300 mm or more
300 mm
or more
300 mm or more
Page 37
MODEL  :AOG14LE
(Unit : mm)
G07-14LE
OUTDOOR UNIT
AO
G07-14LE
OUTDOOR UNIT
AO
INSTALLATION PLACE
When there are obstacles at the back or front sides.
100 mm or more
600 mm or more
When there are obstacles at the back, side(s), and top.
600 mm or more
100 mm or more
250 mm or more
(Service space)
- (02 - 03) -
300 mm
or more
When there are obstacles at the back, side with the installation of more than one unit.
250 mm or more
250 mm
or more
300 mm or more
Page 38
REFRIGERANT CIRCUIT3.
MODEL  :AOG07LE, AOG09LE, AOG12LE, AOG14LE
G07-14LE
OUTDOOR UNIT
AO
Compressor
3-Way
valve
Muffler
4-Way valve
Heat exchanger
( INDOOR )
Heat exchanger ( OUTDOOR )
2-Way
valve
Strainer
Expansion valve
Strainer
G07-14LE
OUTDOOR UNIT
AO
Cooling Heating
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm) :07/09/12LE
1/2" (12.7 mm) :14LE
- (02 - 04) -
Page 39
WIRING DIAGRAMS4.
MODEL  :AOG07LE, AOG09LE
G07-14LE
OUTDOOR UNIT
AO
G07-14LE
OUTDOOR UNIT
AO
- (02 - 05) -
Page 40
MODEL  :AOG12LE, AOG14LE
G07-14LE
OUTDOOR UNIT
AO
G07-14LE
OUTDOOR UNIT
AO
- (02 - 06) -
Page 41
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
MODEL  :AOG07LE, AOG09LE
G07-14LE
OUTDOOR UNIT
AO
Height
difference H
(m)
Height
difference H
(m)
COOLING
1
Indoor unit is
upper than
outdoor unit.
2
Indoor unit is
under than
outdoor unit
HEATING
1
Indoor unit is
upper than
outdoor unit.
2
Indoor unit is
under than
outdoor unit
Pipe length (m)
57.5101520
15 - - - 0.872 0.910
10 - - 0.961 0.886 0.925
7.5 - 0.979 0.965 0.890 0.929
5 0.992 0.983 0.969 0.893 0.933
0 1.000 0.991 0.976 0.901 0.940
-5 1.000 0.991 0.976 0.901 0.940
-7.5 - 0.991 0.976 0.901 0.940
-10 - - 0.976 0.901 0.940
-15 - - - 0.901 0.940
Pipe length (m)
57.5101520
15 - - - 0.832 0.822
10 - - 0.917 0.832 0.822
7.5 - 0.961 0.917 0.832 0.822
5 1.000 0.961 0.917 0.832 0.822
0 1.000 0.961 0.917 0.832 0.822
-5 0.995 0.956 0.912 0.828 0.818
-7.5 - 0.954 0.910 0.826 0.816
-10 - - 0.908 0.824 0.814
-15 - - - 0.815 0.805
G07-14LE
OUTDOOR UNIT
AO
Height difference H
Indoor unit
Outdoor unit
Connection pipe
1 Indoor unit is upper than outdoor unit.
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is under than outdoor unit.
- (02 - 07) -
Page 42
MODEL  :AOG12LE
G07-14LE
OUTDOOR UNIT
AO
Height
difference H
(m)
Height
difference H
(m)
COOLING
1
Indoor unit is
upper than
outdoor unit.
2
Indoor unit is
under than
outdoor unit
HEATING
1
Indoor unit is
upper than
outdoor unit.
2
Indoor unit is
under than
outdoor unit
Pipe length (m)
57.5101520
15 - - - 0.858 0.868
10 - - 0.929 0.872 0.882
7.5 - 0.960 0.933 0.876 0.885
5 0.992 0.964 0.937 0.879 0.889
0 1.000 0.972 0.944 0.887 0.896
-5 1.000 0.972 0.944 0.887 0.896
-7.5 - 0.972 0.944 0.887 0.896
-10 - - 0.944 0.887 0.896
-15 - - - 0.887 0.896
Pipe length (m)
57.5101520
15 - - - 0.896 0.879
10 - - 0.968 0.890 0.879
7.5 - 0.994 0.968 0.896 0.879
5 1.000 0.994 0.968 0.896 0.879
0 1.000 0.994 0.968 0.896 0.879
-5 0.995 0.989 0.963 0.891 0.875
-7.5 - 0.987 0.961 0.889 0.873
-10 - - 0.959 0.887 0.871
-15 - - - 0.878 0.862
G07-14LE
OUTDOOR UNIT
AO
Height difference H
Indoor unit
Outdoor unit
Connection pipe
1 Indoor unit is upper than outdoor unit.
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is under than outdoor unit.
- (02 - 08) -
Page 43
MODEL  :AOG14LE
G07-14LE
OUTDOOR UNIT
AO
Height
difference H
(m)
Height
difference H
(m)
COOLING
1
Indoor unit is
upper than
outdoor unit.
2
Indoor unit is
under than
outdoor unit
HEATING
1
Indoor unit is
upper than
outdoor unit.
2
Indoor unit is
under than
outdoor unit
Pipe length (m)
57.5101520
15 ---0.893 0.909
10 - - 0.955 0.908 0.924
7. 5 - 0.975 0.959 0.912 0.928
5 0.992 0.979 0.963 0.916 0.931
0
-5 1.000 0.987 0.970 0.923 0.939
-7.5
-10 - - 0.970 0.923 0.939
-15 - - - 0.923 0.939
15 - - - 0.956 0.938
10 - - 1.004 0.956 0.938
7. 5
5 1.000 1.013 1.004 0.956 0.938
0 1.000 1.013 1.004 0.956 0.938
-5 0.995 1.008 0.999 0.951 0.933
-7.5 - 1.005 0.997 0.948 0.931
-10 - - 0.994 0.946 0.929
-15 ---0.937 0.919
1.000 0.987 0.970 0.923 0.939
- 0.987 0.970 0.923 0.939
Pipe length (m)
57.5101520
- 1.013 1.004 0.956 0.938
G07-14LE
OUTDOOR UNIT
AO
Height difference H
Indoor unit
Outdoor unit
Connection pipe
1 Indoor unit is upper than outdoor unit.
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is under than outdoor unit.
- (02 - 09) -
Page 44
G07-14LE
OUTDOOR UNIT
AO
ADDITIONAL CHARGE CALCULATION6.
MODEL  :AOG07LE, AOG09LE
Refrigerant type R410A
Refrigerant amount g 650
Refrigerant charge
Total pipe length m 15 or less 20 (MAX)
Additional charge g 0 100
MODEL  :AOG12LE
Refrigerant type R410A
Refrigerant amount g 800
Refrigerant charge
20g/m
G07-14LE
OUTDOOR UNIT
AO
Total pipe length m 15 or less 20 (MAX)
Additional charge g 0 100
MODEL  :AOG14LE
Refrigerant type R410A
Refrigerant amount g 1050
Refrigerant charge
Total pipe length m 15 or less 20 (MAX)
Additional charge g 0 100
20g/m
20g/m
- (02 - 10) -
Page 45
G07-14LE
OUTDOOR UNIT
AO
AIR FLOW7.
MODEL  :AOG07LE, AOG09LE
Cooling
Number of
rotations
(r.p.m.)
730
Heating
Number of
rotations
(r.p.m.)
1720 m
476 l/s
1011 CFM
1510 m
Air ow
Air ow
3
/h
3
/h
G07-14LE
OUTDOOR UNIT
AO
650
418 l/s
888 CFM
MODEL  :AOG12LE
Cooling
Number of
rotations
(r.p.m.)
1830 m
860
Heating
Number of
rotations
(r.p.m.)
507 l/s
1076 CFM
1600 m
Air ow
Air ow
3
/h
3
/h
760
443 l/s
941 CFM
- (02 - 11) -
Page 46
G07-14LE
OUTDOOR UNIT
AO
MODEL  :AOG14LE
Cooling
Number of
rotations
(r.p.m.)
1800 m
800
Heating
Number of
rotations
(r.p.m.)
499 l/s
1058 CFM
1660 m
Air ow
Air ow
3
/h
3
/h
G07-14LE
OUTDOOR UNIT
AO
750
460 l/s
976 CFM
- (02 - 12) -
Page 47
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL  :AOG07LE
G07-14LE
OUTDOOR UNIT
AO
Cooling
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
G07-14LE
OUTDOOR UNIT
AO
MODEL  :AOG09LE
Cooling
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
- (02 - 13) -
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Page 48
MODEL  :AOG12LE
G07-14LE
OUTDOOR UNIT
AO
Cooling
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
G07-14LE
OUTDOOR UNIT
AO
MODEL  :AOG14LE
Cooling
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002μbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
- (02 - 14) -
0
63 125 250 500 1,000 2,0 00 4,00 0 8,00 0
Octave band center frequency,Hz
Page 49
SOUND LEVEL CHECK POINT8-2.
G07-14LE
OUTDOOR UNIT
AO
G07-14LE
OUTDOOR UNIT
AO
- (02 - 15) -
Page 50
G07-14LE
OUTDOOR UNIT
AO
ELECTRIC CHARACTERISTICS9.
Model name AOG07LE AOG09LE AOG12LE AOG14LE
Power supply
*1) Max operating current A 7.5 7.5 9.0 10.5 Starting Current A 3.5 3.8 4.7 6.0
*2) Wiring Spec.:
*1) The maximum current is the total current of indoor unit and outdoor unit.
*2) Wiring Spec.: Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*3) Limited wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Voltage V 230 ~ Frequency Hz 50
Main Fuse (Circuit breaker) Current Power Cable mm
A20
2
1.5
*3) Limited wiring length : m 21
G07-14LE
OUTDOOR UNIT
AO
- (02 - 16) -
Page 51
SAFETY DEVICES10.
Model
Protection form
AOG07LE AOG09LE AOG12LE AOG14LE
G07-14LE
OUTDOOR UNIT
AO
Circuit protection
Fan motor protection
High Pressure Protection
Current fuse (MAIN PRINTED CIRCUIT BOARD)
Thermal protection program
Terminal protection program COMPRESSOR TEMP.
20A/250V
5A/250V
OFF : 100
ON : 95
+10
+10
°C
-10
°C
-10
OFF:110°C
ON:After 7 minutes
G07-14LE
OUTDOOR UNIT
AO
- (02 - 17) -