Fujitsu AS*A09LKC, AS*A12LKC, AO*R12LKC, AO*R09LKC Service Instructions Manual

Page 1
SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
type
Models Indoor unit Outdoor unit
AS*A09LKC AS*A12LKC
AO*R09LKC AO*R12LKC
SERVICE
INSTRUCTION
R410A
Page 2
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION................................................................................................
3. DRY OPERATION.........................................................................................................
2. HEATING OPERATION.................................................................................................
5. INDOOR FAN CONTROL..............................................................................................
4. AUTO CHANGEOVER OPERATION............................................................................
7. LOUVER CONTROL.....................................................................................................
6. OUTDOOR FAN CONTROL..........................................................................................
9. TIMER OPERATION CONTROL...................................................................................
8. COMPRESSOR CONTROL..........................................................................................
11. TEST OPERATION CONTROL...................................................................................
10. ELECTRONIC EXPANSION VALVE CONTROL........................................................
13. FOUR-WAY VALVE EXTENSION SELECT................................................................
12. PREVENT TO RESTART FOR 3 MINUTES (3 MINUTES ST)...................................
15. MANUAL AUTO OPERATION (Indoor unit body operation).......................................
14. AUTO RESTART.........................................................................................................
16. FORCED COOLING OPERATION..............................................................................
18. COIL DRY OPEARTION CONTROL...........................................................................
17. COMPRESSOR PREHEATING..................................................................................
19. DEFROST OPERATION CONTROL...........................................................................
21. VARIOUS PROTECTIONS..........................................................................................
20. OFF DEFROST OPERATION CONTROL...................................................................
01-01
01-02
01-03
01-04
01-05
01-07
01-08
01-09
01-10
01-12
01-12
01-12
01-12
01-13
01-13
01-13
01-13
01-14
01-16
01-17
01-12
2. TROUBLE SHOOTING
2-1 ERROR DISPLAY.......................................................................................................
2-1-1 INDOOR UNIT AND WIRED RMOTE CONTROLLER DISPLAY (OPTION)......
3. APPENDING DATA
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION).....................................
2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE......................................................
1. Jumper setting of Indoor unit and Outdoor unit.............................................................
3. Thermistor Resistance Values.......................................................................................
2. Outdoor unit Pressure Value and Total Electric Current Curve.....................................
03-01
03-02
03-04
02-01
02-01
02-02
02-03
02-24
2-4 SERVICE PARTS INFORMATION.............................................................................. 02-29
Page 3
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
WALL MOUNTED type
INVERTER
Page 4
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 2°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
minimum frequency
maximum frequency
maximum frequency
AS*A09LKC 22Hz 76Hz 79Hz
AS*A12LKC 18Hz 80Hz 96Hz
Outside air Outside air temperature temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi Me Lo Quiet
A zone 79Hz 61Hz 52Hz 37Hz
B zone 79Hz 61Hz 52Hz 37Hz
C zone 79Hz 61Hz 52Hz 38Hz
09LKC
D zone 52Hz 43Hz 37Hz 28Hz
A zone 96Hz 61Hz 51Hz 33Hz
B zone 96Hz 61Hz 51Hz 33Hz
C zone 96Hz 61Hz 51Hz 33Hz
12LKC
D zone 57Hz 42Hz 36Hz 27Hz
( Table 1 : Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
01-01
* When the room temperature is between +2°C to -2.5°C of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be stopped.
Page 5
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 3°C than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature, the compressor frequency is controlled within the range shown in Table2. However, the maximum frequency is limited in the range shown in Figure 2 based on the fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
* The room temperature is controlled 2°C higher than the setting temperature for 60 minutes after starting the operation. After 60 minutes, it is controlled based on the normal setting temperature.
01-02
minimum frequency
maximum frequency
AS*A09LKC 22Hz 99Hz
AS*A12LKC
18Hz 130Hz
Hi Me+ Lo Quiet
AA zone
99Hz 99Hz 79Hz 67Hz
A zone
99Hz 99Hz 79Hz 67Hz
B zone
99Hz 99Hz 79Hz 56Hz
09LKC
C zone
AA zone
A zone
B zone
C zone
99Hz 99Hz 79Hz 46Hz
130Hz 130Hz 80Hz 68Hz
130Hz 130Hz 80Hz 68Hz
130Hz 130Hz 80Hz 54Hz
130Hz 130Hz
Me
96Hz
96Hz
96Hz
96Hz
96Hz
96Hz
96Hz
96Hz 80Hz 45Hz
12LKC
Outside air Outside air temperature temperature
19°C
C zone
B zone
A zone
AA zone
17°C
14°C
12°C
7°C
5°C
Page 6
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 3. However, after the compressor is driven, the indoor unit shall run at operation frequency of 70Hz (for AS*A09LKC) or 56Hz (for AS*A12LKC) , for a minute.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table 3 : Compressor frequency )
( Table 4 : Indoor fan speed )
( Fig.3 : Compressor Control based on Room Temperature )
( Fig.4 : Indoor Fan Control )
01-03
Operating frequency
37Hz
28Hz
0Hz
09LKC
X zone
J zone
Y zone
Operating frequency
J zone
Y zone
X zone
33Hz
25Hz
0Hz
12LKC
Room Room temperature temperature
X zone
J zone
Y zone
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 4)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(SEC)
X zone J, Y zone
AS*A09LKC 620rpm 600rpm
AS*A12LKC 620rpm 600rpm
Page 7
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute,
the room temperature and outside air temperature are sensed and the operation mode is selected in accordance with the table below.
C zone
32°C
B zone
-10°C A zone
( Table.5 Operation mode selection table)
Outside air temperature (TO)
Room temperature (TB)
A zone B zone C zone
TB > TS+2°C
Monitoring
Cooling
(automatic dry)
Cooling
(automatic dry)
TS+2°C TB TS - 2°C
Monitoring Monitoring Monitoring
TB TS- 2°C Heating Heating Monitoring
When COOLING was selected at , the air conditioner operates as follow:
The same operation as COOLING OPERATION of item 1 above is performed.
When the room temperature has remained at (set temperature -1°C) for 8 minutes, operation is
automatically switched to DRY and the same operation as DRY OPERATION of item 3 above is performed.
If the room temperature reaches (set temperature +2°C during DRY operation, operation returns to COOLING operation.
When HEATING was selected at , the same operation as HEATING OPERATION of item 2 above is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at above, operation is switched to MONITORING and the operation mode is selected again.
1
<
1
2
3
1
4
1
( Fig.5 : Outside air temperature zone selection )
01-04
Page 8
5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs. When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
01-05
1. Fan speed
2. FAN OPERATION
( Table 6 : Indoor Fan Speed )
AS*A09 / 12LKC
Operation mode Air flow mode Speed (rpm)
1440 1370 1200
980
Cooling
Hi
Hi
670 600 480
1400
Me+ Me
Me
Heating
Lo
Lo
1200
920
Quiet
Quiet
620
Dry
S-Lo
X zone: 620
J zone: 600
Cool air prevention
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 6. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH,as shown in Table 6.
( Fig.6 : Airflow change - over ( Cooling : AUTO ) )
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
TR-Ts > 2 degC
=
1 degC > TR-Ts
2 degC > TR-Ts > 1 degC
=
TR-Ts > 2.5 degC
=
1.5 degC > TR-Ts
2.5 degC > TR-Ts > 1.5 degC =
HIGH mode
MED mode
LOW mode
Page 9
Indoor heat exchanger Indoor heat exchanger temperature temperature
47°C
Hi
40°C
Me+
37°C
Lo
Cool air prevention
30°C
S-Lo
The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
(Fig.8 : Cool Air Prevention Control)
01-06
40°C
28°C
32°C
34°C
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 7.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 6.
6. COOL AIR PREVENTION CONTROL (Heating mode)
4. DRY OPERATION
Refer to the Table 6. During the dry mode operation, the fan speed setting can not be changed.
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > - 1.5 degC
=
- 2.5 degC > TR-Ts
- 1.5 degC > TR-Ts > - 2.5 degC =
TR-Ts > - 1 degC
=
- 2 degC > TR-Ts
- 1 degC > TR-Ts > - 2 degC =
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
LOW mode
MED mode
MED+ mode
42°C
Hi
39°C
Me+
37°C
Lo
Cool air prevention
30°C
S-Lo
35°C
28°C
31°C
33°C
AS*A09LKC
AS*A12LKC
Page 10
6. OUTDOOR FAN CONTROL
Cooling Dry Heating
AS*A09LKC
AS*A12LKC
730/ 650/ 470
860/ 760/ 470
860/ 470/ 330
730/ 470/ 230
( Table 8 : Outdoor fan speed )
*
The outdoor fan speed mentioned avobe depends on the compressor frequency. (When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequescy decreases, the outdoor fan speed also changes to the lower speed.)
*
It runs at 500(A-D ZONE)rpm for 20 seconds after starting up the outdoor fan.
*
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table 9 without relating to the compressor frequency.
01-07
A - C
D A - C
D
ZONE
730/ 470
760/ 470
650/ 470
760/ 680/ 470
Refer to Fig1.
(rpm)
( Table 9 : Outdoor fan speed after the defrost )
1. Outdoor Fan Motor
2. Fan Speed
AC Motor DC Motor
AS*A09/ 12LKC
Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table 7 : Type of Motor )
Min
AS*A09/ 12LKC 900rpm
Page 11
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
2. SWING OPERATION
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
range ( ) for long period of time, since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow Direction Louvers are left in the heating range for more than 30minutes, they will automatically return to position .
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically
becomes , and it cannot be adjusted.
Cooling mode / Dry mode / Fan mode( ) Heating mode / Fan mode( )
(Function Range)
(Fig 9: Air Direction Range)
(Operation Range)
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrrupted and the louver stops at the memorized position.
01-08
Page 12
8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the table 10.
Cooling Heating
Min Max Min Max Min Max
Dry
AS*A09LKC
AS*A12LKC
22Hz 79Hz 22Hz 99Hz 28Hz 37Hz
18Hz 96Hz 18Hz 130Hz 25Hz 33Hz
AS*A09LKC
AS*A12LKC
70Hz 82Hz 92Hz 96Hz 96Hz 96Hz
56Hz 74Hz 87Hz 97Hz 108Hz 119Hz
80sec 60sec 60sec 180sec 60sec 60sec
80sec 60sec 60sec 180sec 60sec 60sec
(Table 10 : Compressor Operation Frequency Range)
2. OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the figure 10.
(Fig.10 : Compressor Control at Start-up)
Time
Time Time Time
Time
Time
(Frequency)
(Time)
Frequency
Frequency
Frequency Frequency
Frequency
Frequency
Time Time
Time Time Time Time
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
01-09
AS*A09LKC
AS*A12LKC
Page 13
9. TIMER OPEARTION CONTROL
1. OPEARTION FREQUENCY RANGE
The table 11 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER SLEEP TIMER
AS*A09 / 12LKC
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
(Table 11 : Timer Setting)
01-10
Page 14
2. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1°C
+2°C
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not changed and the operation stops at the time of timer setting.
- 4°C
- 3°C
- 2°C
- 1°C
Set
30min
30min
30min
01-11
Page 15
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 60 to 480 pulses.
The expansion valve is set at 480 pulses after 110 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).
11. TEST OPERATION CONTROL
Under the condition where the air conditioner runs, press the test run button of the remote control, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is stopped, even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after the compressor stopped.
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature Set air flow Timer mode and timer time Set air flow Direction Swing
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
13. FOUR-WAY VALVE EXTENSION SELECT
14. AUTO RESTART
01-12
Econmy
Page 16
15. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 12. If the remote control is lost or battery power dissipated, this function will work without the remote control.
OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous SETTING TEMP. 24°C SETTING LOUVER Standard SWING OFF
When the outdoor heat exchanger temperature is lower than 5°C and the heating operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to 7°C or greater, preheating is ended.
AS*A09LKC
AS*A12LKC
780rpm 43Hz
780rpm 39Hz
(Table 12)
(No timer setting available)
17. COMPRESSOR PREHEATING
18. COIL DRY OPERATION CONTROL
The coil-dry operation functions by pressing COIL DRY button on the remote controller. The coil-dry operation is consisted of Fan operation 50 minutes, Heating operation 3 minutes, and Fan operates for 30 minutes at last before ending the air conditioner operation.
(Table 13 : COIL-DRY Operating Functions)
Indoor Fan Speed
Compressor Frequency
Louver Position
01-13
Forced cooling operation
Cooling
16. FORCED COOLING OPERATION
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more. During the forced cooling operation, it operates regardless of room temperature sensor. Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON and 1 second OFF on both operation LED and timer LED (same as test operation). Forced cooling operation is released after 60 minutes of starting operation. The FORCED COOLING OPERATION will start as shown in Table12.
Hi
Horizontal OFF
Room Temp is not controlled
Manual auto operation
-
Page 17
19. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 14.
(Table 14 : Condition of starting Defrost Operation)
AS*A09 / 12LKC
Less than 25 minutes
25 minutes to 4 hours
Does not operate
Compressor operating time
After 4 hours
- 6°C - 3°C
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 15.
(Table 15 : Defrost Release Condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
01-14
AS*A09 / 12LKC
Page 18
Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
Compressor OFF Outdoor fan motor OFF 30 sec later 4 - way valve OFF 36 sec later compressor ON
Heating operation start : Compressor ON
Outdoor heat exchanger temperature: Over 16°C or Compressor ON time: Over 15 minutes
01-15
Compressor integrating operation: Over 25 minutes to below 240 minutes
Compressor integrating operation: Over 240 minutes
Outdoor heat exchanger temperature: Below - 6°C
Outdoor heat exchanger temperature: Below - 3°C
Defrost start
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Defrost end
Page 19
20. OFF DEFROST OPEARTION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than -4°C, and compressor operation integrating time lasts for more than 30 minutes.
AS*A09/ 12LKC
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature: Below -4°C and Compressor integrating operation: Over 30 minutes
Defrost start
Defrost Indicater: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 16°C or Compressor ON time: Over 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
01-16
Page 20
21. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
AS*A09 / 12LKC
104°C 101°C 110°C
When the discharge temperature becomes higher than Temperature ,the compressor frequency is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped and the indoor unit LED starts blinking.
(Table 16 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit velue that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
(Table 17 : Current Release Operation Value / Release Value)
01-17
[ Heating ]
OT (Control / Release)
5.0A/ 4.5A
5.0A/ 4.5A
5.0A/ 4.5A
5.0A/ 4.5A
5.5A/ 5.0A
7.0A/ 6.5A
7.5A/ 7.0A
8.5A/ 8.0A
17°C
12°C
OT : Outdoor Temperature
5°C
AS*A09LKC
OT (Control / Release)
17°C
12°C
OT : Outdoor Temperature
5°C
AS*A12LKC
OT (Control / Release)
3.5A/ 3.0A
4.0A/ 3.5A
5.0A/ 4.5A
4.0A/ 3.5A
5.0A/ 4.5A
6.0A/ 5.5A
46°C
42°C
OT : Outdoor Temperature
AS*A09LKC
OT (Control / Release)
46°C
42°C
OT : Outdoor Temperature
AS*A12LKC
[ Cooling ]
Page 21
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 18 : Anti-freezing Protection Operation / Release Temperature)
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C or greater, the compressor is stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
01-18
[ AS*A09LKC ]
[ AS*A12LKC ]
52Hz or greater 49Hz
48Hz or greater 45Hz
43 49Hz
45Hz
34 40Hz 28Hz
27 36Hz 18Hz
22 28Hz OFF
OFF
Indoor heat exchange temperature
[ Control System ]
Refer to below
It returns to the normal operation
Compressor Operation
25Hz
39
Frequency down every 120 sec
Frequency down every 120 sec
55°C
53°C
52°C
50°C
4°C
7°C
Temperature Temperature
The compressor frequency is decreased 3Hz every 60seconds.
Page 22
2 . TROUBLE SHOOTING
R410A
WALL MOUNTED type
INVERTER
Page 23
2. TROUBLE SHOOTING
02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED RMOTE CONTROLLER DISPLAY
1. ERROR DISPLAY Please refer the blinking pattern as follows.
Indoor Unit : AS*A09LKC, AS*A12LKC
The OPERATION, TIMER lamps operate as follows according to the error contents.
0.5s ON / 0.5s OFF (Flash) : OFF
Error contents
Indoor Unit display
Operation
(Green)
Timer
(Orange)
Trouble
shooting
Serial error (Serial reverse transfer error)
Serial error (Serial forward transfer error)
Wired remote controller error
2 times 3 times
4 times 5 times
1
2
3
4
5
Room temperature thermistor error 2 times
8 times
Indoor heat exchanger temperature thermistor (Middle) error
2 times
3 times
Outdoor discharge pipe temperature thermistor error 2 times
Outdoor heat exchanger temperature thermistor error 3 times
6
7
Outdoor temperature thermistor error 4 times
8
3 times
Manual auto switch error 2 times
10
4 times
11
Over current protection 2 times
12
CT error 3 times
13
Compressor location ditection error 5 times
14
Outdoor unit fan error
5 times
6 times
15
Indoor fan motor lock error
6 times
2 times
15
Indoor fan motor rev. error 3 times
16
Discharge temperature error 2 times
17
Exessive high pressure protection on cooling 3 times
18
7 times
8 times
Model distinction error (Indoor)
19
20
0.1s ON / 0.1s OFF (Flash)
Power supply frequency detection error 4 times
Active filter error
Wired Rmote
Controller
Display (option)
01
13
00
02
04
0C
06
0A
20
No Display
17
18
1A
1b
12
12
0F
24
19
11
2 times 3 times
4-way valve error
PFC circuit error
4 times
4 times
25
9
21
2C
Page 24
02-02
When "EE" in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed service personnel.
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION)
1. SELF - DIAGNOSIS
SU MOTUWETH FR SA
Unit number (usually 0)
Error code
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
3. Press the SET TEMPERATURE button to select the error history number.
SU MOTU WETH FR SA
Error code
Error history number
0 1 2 3 4 5 6 7 F E d c b A 9 8
Lower
Raise
Page 25
Trouble shooting 1 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Serial Error (Serial Reverse Transfer Error)
Outdoor Unit Inverter PCB
1. Connection failure 2. External cause 3. Inverter PCB failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal N - 3. >> If it is abnormal, replace Inverter PCB.
When the indoor unit cannot properly receive the serial signal from outdoor unit for 10 seconds or more.
02-03
L
N
3
WHITE
BLACK
+
-
2-2 TROUBLE SHOOTING WITH ERROR CODE
RED
Page 26
Trouble shooting 2 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Serial Error (Serial Forward Transfer Error)
Indoor Unit Controller PCB
1. Connection failure 2. External cause 3. Controller PCB failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal N - 3. >> If it is abnormal, replace Controller PCB .
When the indoor unit cannot properly receive the serial signal from outdoor unit for 10 seconds or more.
02-04
L
N
3
WHITE
BLACK
+
-
RED
Page 27
Trouble shooting 3 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Indicate or Display:
Wired Remote Controller Error
Indoor unit Controller PCB Wired Remote Controller(Option)
1. Connection failure 2. Wired Remote Controller failure 3. Controller PCB failure
Check & correct the followings. Check the connection of terminal between Wired Remote Controller and indoor unit, and check if there is a disconnection of the cable.
Check voltage at connector of Wired Remote Controller of Controller PCB. (Power supply to Wired Remote Controller) >> CN8, 1 - 3 pin
If it is DC12V, Wired Remote Controller is failure. (Controller PCB is normal)
>> Replace Wired Remote Controller (Option)
If it is DC 0V, Controller PCB is failure.
>> Replace Controller PCB.
When the indoor unit cannot properly receive the signal from Wired Remote Controller for 1 minute or more.
02-05
Refer to error code table.
Page 28
Trouble shooting 4 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 2 : Remove connector and check thermistor resistance value
Check Point 1 : Check connection of connector
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
OK
OK
6.51
35
8.04
30
10.012.515.820.225.933.6Resistance value (k )
2520151050
Temperature (°C )
3.594.355.30Resistance value (k )
504540Temperature (°C )
Room Temperature Thermistor Error
Indoor Unit Controller PCB Room Temperature Thermistor
When Room Temperature Thermistor open or short-circuit is detected at power ON.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Make sure circuit diagram of indoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-06
Refer to error code table.
CN4
THERMISTOR ( ROOM TEMP. )
THERMISTOR ( PIPE TEMP. )
1
4
2
3
1
4
2
3
BLACK
BLACK
BLACK
BLACK
Page 29
Trouble shooting 5 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 2 : Remove connector and check thermistor resistance value
Check Point 1 : Check connection of connector
OK
OK
31.7
35
39.6
30
49.762.980.3103134176
Resistance value (k )
2520151050
Temperature (°C )
17.120.825.6
Resistance value (k )
504540
Temperature (°C )
Indoor Heat Exchanger Temperature Thermistor (Middle) Error
Indoor Unit Controller PCB Heat Exchanger Temperature Thermistor (Middle)
When Heat Exchanger Temperature Thermistor (Middle) open or short-circuit is detected at power ON.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-07
Refer to error code table.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
CN4
THERMISTOR ( ROOM TEMP. )
THERMISTOR ( PIPE TEMP. )
1
4
2
3
1
4
2
3
BLACK
BLACK
BLACK
BLACK
Page 30
Trouble shooting 6 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
17.826.3
20
40.063.079.0101130168Resistance value (k )
151050Temperature (°C )
12.3
30 5040 60
2.03.44.66.38.7Resistance value (k )
120100908070Temperature (°C )
Outdoor Discharge Pipe Temperature Thermistor Error
Outdoor Unit Inverter PCB Discharge Pipe Temperature Thermistor
When Discharge Pipe Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Inverter PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Inverter PCB.
02-08
Refer to error code table.
CN61 CN62
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER )
THERMISTOR ( OUTDOOR TEMP. )
1
4
2
3
1
4
2
3
1 2 3
1 2 3
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
CN71 CN70
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER )
THERMISTOR ( OUTDOOR TEMP. )
1
4
2
3
1
4
2
3
1 2 3
1 2 3
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
AO*R09LKC AO*R12LKC
Page 31
Trouble shooting 7 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
3.844.77
15
5.987.569.6316.121.027.8Resistance value (k )
100-5-10Temperature (°C )
20
3025
Outdoor Heat Exchanger Temperature Thermistor Error
Outdoor Unit Inverter PCB Heat Exchanger Temperature Thermistor
When Heat Exchanger Temperature Thermistor (Out) open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Inverter PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-09
Refer to error code table.
3.11
35
12.4
5
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
CN61 CN62
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER )
THERMISTOR ( OUTDOOR TEMP. )
1
4
2
3
1
4
2
3
1 2 3
1 2 3
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
CN71 CN70
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER )
THERMISTOR ( OUTDOOR TEMP. )
1
4
2
3
1
4
2
3
1 2 3
1 2 3
BLACK
BLACK
BLACK
BLACK
AO*R09LKC AO*R12LKC
BLACK
BLACK
Page 32
Trouble shooting 8 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
12.616.1
5
20.726.935.246.662.3115Resistance value (k )
0-5-10-20Temperature (°C ) 10 2015
1.652.363.455.187.97Resistance value (k )
7060504030Temperature (°C )
Outdoor Temperature Thermistor Error
Outdoor Unit Inverter PCB Outdoor Temperature Thermistor
When Outdoor Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Inverter PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-10
Refer to error code table.
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Inverter PCB.
CN61 CN62
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER )
THERMISTOR ( OUTDOOR TEMP. )
1
4
2 3
1
4
2 3
1 2 3
1 2 3
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
CN71 CN70
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER )
THERMISTOR ( OUTDOOR TEMP. )
1
4
2 3
1
4
2 3
1 2 3
1 2 3
BLACK
BLACK
BLACK
BLACK
AO*R09LKC AO*R12LKC
BLACK
BLACK
Page 33
02-11
Trouble shooting 9 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Manual Auto Switch Error
Indoor Unit Inverter PCB Manual Auto Switch
When the Manual Auto Switch becomes ON for consecutive 30 or more seconds.
1. Manual Auto Switch failure 2. Inverter PCB failure
Check Point 1 : Check the Manual Auto Switch
Check if Manual Auto Switch is kept pressed. Check ON/OFF switching operation by using a meter.
>> If Manual Auto Switch is disabled (on/off switching), replace it.
Check Point 2 : Replace Inverter PCB
If Check Point 1 do not improve the symptom, replace Inverter PCB.
Refer to error code table.
Page 34
Trouble shooting 10 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Power Supply Frequency Detection Error
Indoor Unit Controller PCB
1. Connection failure 2. External cause 3. Controller PCB failure
Check Point 1-1 : Reset the power supply and operate
Does error indication reappear?
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring.)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
When power frequency is not detected by 4 seconds after power-on.
02-12
Check Point 4 : Replace Controller PCB
If Check Point 1 ~ 3 do not improve the symptom, replace Controller PCB.
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Page 35
Trouble shooting 11 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 4 : Check Compressor
OK
OK
Indicate or Display:
Check Point 5 : Replace Inverter PCB
OKOK
Check Point 1 : Check connections condition in control unit
Over Current Protection
Outdoor Unit Inverter PCB Compressor
1. Connection failure 2. Outdoor Fan operation failure 3.Outdoor Heat Exchanger clogged
4. Compressor failure 5. Inverter PCB failure
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
If Check Point 1 ~ 4 do not improve the symptom, replace Inverter PCB.
When over current flows in Inverter PCB, the compressor stops. After the compressor restarts, if the same error is repeated within 40sec, the compressor stops reappear. If and repeats 5 times, the compressor stops permanently.
02-13
Refer to error code table.
Compressor check is refer to SERVICE PARTS INFORMATION 2.
>> If it is abnormal, replace Compressor.
Check Point 2 : Check Outdoor Heat Exchanger
Is there any obstructing the air flow route? Is there any clogging of outdoor unit Heat Exchanger?
>> If clogged, clear the clog.
Check Point 3 : Check Outdoor Fan
OK
Check Outdoor Fan Motor. (Refer to Trouble shooting 15)
>> If the Fan Motor is failure, replace it.
Page 36
Trouble shooting 12 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 3 : Replace Inverter PCB
YES
NO
OK
Indicate or Display:
CT Error
Outdoor Unit Inverter PCB
Check Point 2 : Check connections condition in control unit
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connection failure 2. External cause 3. Inverter PCB failure
Check Point 1-1 : Reset power supply and operate
Does error indication reappear?
After compressor runs for 1 minute or more, and while it runs in 56Hz or more. When outdoor current value (A/D data) of Input Current Sensor has detected [00H].
02-14
Refer to error code table.
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
If Check Point 1 ~ 2 do not improve the symptom, replace Inverter PCB.
Page 37
Trouble shooting 13 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Compressor Location Detection Error
Outdoor Unit Inverter PCB
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connector connection failure 2.Inverter PCB failure
Check Point 1 : Check connections condition in control unit
When "compressor location detection error" is detected consecutively 5 times, within 40 seconds after start-up.
02-15
Refer to error code table.
Check Point 2 : Replace Inverter PCB
If Check Point 1 do not improve the symptom, replace or Inverter PCB.
Page 38
Trouble shooting 14 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check ambient temp. around motor
OK
OK
Indicate or Display:
Outdoor Unit Fan Error
Outdoor Unit Inverter PCB Outdoor Fan Motor
1. Fan Motor failure 2. Motor protection by surrounding temperature rise 3. Inverter PCB failure
Check Point 1 : Check rotation of Fan
Check if the Fan Motor is lock. (Can the Fan be rotated by hand when operation is off.) Check the Fan loosening. (Lock-nut loosening, defective propeller fan)
>> If Fan Motor or bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>> Upon the temperature coming down, restart operation.
Check Point 3 : Check output voltage of Inverter PCB
If the voltage is not correct, replace Inverter PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated consecutively 3 times, compressor and fan motor stops. If repeats 5 times in a row, compressor and fan motor stops permanently.
02-16
Refer to error code table.
BLACK
BROWN
RED
WHITE
YELLOW
CN800
1 2
3
4 5
6
1 2
3
4 5
6
FM
FAN MOTOR
Check outdoor unit circuit diagram and the voltage. (Measure at Inverter PCB side connector)
>>1 pin(Red) - 4 pin(Black) DC250V ~ 400V >>4 pin(Black) - 5 pin(White) DC15V 2V
7 7
Page 39
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
Indoor Unit Controller PCB Indoor Fan Motor
1. Fan Motor failure 2. Motor protection by surrounding temperature rise
3. Controller PCB failure
Check if the Fan Motor is lock. (Can the Fan be rotated by hand when operation is off.) Check the Fan loosening. (Lock-nut loosening, defective propeller fan)
>> If Fan Motor or bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>> Upon the temperature coming down, restart operation.
When the condition that actual rev. of Indoor Fan is 1/3 or less. Or the condition of fan speed is 0rpm is continued more than 56 seconds.
02-17
Check Point 3 : Replace Controller PCB
If Check Point 1, 2 do not improve the symptom, replace Controller PCB.
Trouble shooting 15 INDOOR UNIT Error Method:
Indicate or Display:
Indoor Fan Motor Lock Error Indoor Fan Motor Rev. Error
Refer to error code table.
Page 40
Trouble shooting 16 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Discharge Temperature Error
Outdoor Unit Inverter PCB Discharge Pipe Temperature Thermistor
02-18
When the discharge temperature becomes higher than 115°C. When detecting it 2 times within 24 hours, the compressor stops.
Check Point 1 : Check if gas valve is open
If it is not open, open it and check the operation.
Check Point 3 : Check if gas leak or less gas
Measure gas pressure, if there is a leak, correct it.
>> If recharging refrigerant, make sure to perform vacuuming and recharge the specified amount.
Check Point 5 : Check Outdoor Heat Exchanger
Is there any obstructing the air flow route? Is there any clogging of outdoor unit Heat Exchanger?
>> If clogged, clear the clog.
Check Point 4 : Check Discharge Pipe Thermistor
Is it on the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 6), If defective, replace the thermistor.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
OK
OK
OK
OK
OK
OK
MPa MPa
1. Valve is close 2. EEV failure 3. Gas leak, less 4. Discharge Thermistor failure
5. Outdoor Fan operation failure 6. Outdoor Heat Exchanger clogged
< Cooling mode >
< Heating mode >
Check Point 1 : Check if liquid valve is open
If it is not open, open it and check the operation.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
Refer to error code table.
Check Point 6 : Check Outdoor Fan
OK
Check Outdoor Fan Motor. (Refer to Trouble shooting 14)
>> If the Fan Motor is failure, replace it.
Page 41
Trouble shooting 17 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 3 : Check Outdoor Fan
OK
OK
Indicate or Display:
OKOK
OKOK
Check Point 1 : Check connections condition in control unit
Excessive High Pressure Protection On Cooling
1. Connection failure 2. Outdoor Fan operation failure
3. Outdoor Heat Exchanger clogged 4. Thermistor failure 5. EEV failure 6. Inverter PCB failure
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor Heat Exchanger
Is there any obstructing the air flow route? Is there any clogging of outdoor unit Heat Exchanger? >> If clogged, clear the cloge it.
Check Outdoor Fan Motor. (Refer to Trouble shooting 14)
>> If the Fan Motor is failure, replace it.
Check Thermistor. (Refer to Trouble shooting 7) >> If the Thermistor is failure, replace it.
Check Point 5 : Check EEV
Check Point 4 : Check Thermistor
Check EEV. (PARTS INFORMATION 3)
>> If the EEV is failure, replace it.
In cooling operation, after 1 minute or more compressor starts, when outdoor heat exchanger temperature is 68 °C and above.
02-19
Check Point 6 : Replace Inverter PCB
OKOK
If Check Point 1 ~ 5 do not improve the symptom, replace Inverter PCB.
Outdoor Unit Inverter PCB Outdoor Fan Motor Heat Exchanger Temp. Thermistor Outdoor unit EEV
Refer to error code table.
Page 42
Forecast of Cause :
OKOK
OKOK
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops.
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Inverter PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
Remove CN501(AO*R09LKC)/CN30(AO*R12LKC) from PCB and check the resistance value of coil.Resistance value is about 1.4k
>>If it is Open or abnormal resistance value, replace Solenoid Coil.
02-20
Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 10degC
Heating operation [indoor heat exchanger temp.] - [room temp.] < -10degC
If the same operation is repeated 5 times, the compressor stops permanently.
[ Solenoid coil ]
Check each piping temperature, and the location of the valve by the temperature difference.
>>If the value location is not proper, replace 4-way valve.
[ 4-way valve ]
OKOK
Check Point 4 : Replace Inverter PCB
If Check Point 1- 3 do not improve the symptom, replace Inverter PCB.
Check Point 2 : Check each thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor, If defective, replace the thermistor
Trouble shooting 18 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Indicate or Display:
4-way valve error
Outdoor Unit Inverter PCB Circuit 4-way valve
Refer to error code table.
Page 43
Trouble shooting 19 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Active Filter Error
Outdoor Unit Inverter PCB
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connector connection failure 2. lnverter PCB failure
Check Point 1 : Check connections condition in control unit
Inverter low voltage protection Inverter overvoltage protection
02-21
Refer to error code table.
Check Point 2 : Check Inverter PCB
If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power voltage and replace Inverter PCB.
Check Varistor(VA1 - VA2).
Page 44
Forecast of Cause :
OKOK
OKOK
1. External cause 2. Connector connection failure 3. Inverter PCB failure
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Replace Inverter PCB
If Check Point 1, 2 do not improve the symptom, replace Inverter PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit. Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
02-22
When inverter output DC voltage is higher than 415V for over 3 seconds, the compressor stops. If the same operation is repeated 5 times, the compressor stops permanently.
Trouble shooting 20 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Indicate or Display:
PFC circuit error
Outdoor Unit Inverter PCB Circuit
Refer to error code table.
Page 45
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 : Check connections condition in control unit
YESYES
NO
Trouble shooting 21 INDOOR UNIT Error Method:
Indicate or Display:
Model Distinction Error (Indoor)
Indoor Unit Controller PCB
1. External cause 2. Defective for connection in controller unit 3. Controller PCB failure
Check Point 1-1 : Reset power supply and operate
Does error indication show reappear?
Check all connectors. (loose connector or incorrect wiring) Check any shortage or corrosion on PCB.
If Check Point 1, 2 do not improve the symptom, replace Controller PCB.
When power is on and there is some below case.
1. When model information of EEPROM is incorrect
2. When the access to EEPROM failed
02-23
Refer to error code table.
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
OK
Page 46
Trouble shooting 22
Forecast of Cause:
NO
OK
OK
OKOK
Indoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical components defective
Check Point 1 : Check installation condition
Isn’t the breaker down? Check loose or removed connection cable.
>> If abnormal condition is found, correct it by referring to manual.
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Instant voltage drop of ----- Check if there is abnormally large load in the same power supply power supply system. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply system. Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check whether the ground connection is proper.
Check Point 3 : Check electrical components
02-24
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Check the voltage of power supply.
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at indoor unit Terminal L - N(Power supply).
Check Fuse on Controller PCB (F1).
>> If Fuse is open, check loose terminal, and replace Fuse.
Check Varistor on Inverter PCB (VA1).
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power voltage.
OK
If Check Point 1 3 do not improve the symptom, replace Controller PCB.
Page 47
Trouble shooting 23
Forecast of Cause:
NO
OK
OK
OKOK
Outdoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical components defective
Check Point 1 : Check installation condition
Isn’t the breaker down? Check loose or removed connection cable.
>> If abnormal condition is found, correct it by referring to manual.
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Instant voltage drop of ----- Check if there is a abnomally large load in the same power supply power supply system. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply system. Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check whether the ground connection is proper.
Check Point 3 : Check electrical components
If Check Point 1 ~ 3 do not improve the symptom, replace Inverter PCB,
02-25
Check the voltage of power supply.
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
Check Fuse(F201) on terminal board.
>> If Fuse is open, check loose terminal, and replace Fuse.
Check Varistor on Filter PCB (VA1 - 2).
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power voltage.
OK
Page 48
Trouble shooting 24
Forecast of Cause:
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check electrical components at indoor unit and outdoor unit
OK
OK
OK
No Operation (Power is ON)
1. Setting / Connection failure 2. External cause
3. Electrical component defective
Indoor unit - Check incorrect wiring between indoor unit - remote controller, or terminals between indoor units. Or, check if there is an open cable connection. Are these indoor unit, outdoor unit, and remote controller suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to manual.
Is there loose or removed serial communication line of between indoor unit and outdoor unit?
Instant voltage drop of power supply ----- Check if there is abnormally large load in the same power supply system. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply system. Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check whether the ground connection is proper.
Check voltage at CN8 on Controller PCB.
>> If it is DC12V, Wired Remote Controller is failure. >> Replace Wired Remote Controller(Option) >> If it is DC 0V, Controller PCB is fallure. >> Replace Controller PCB
>> If Check Point 1 - 3 do not improve the symptom, replace control parts of outdoor unit.
02-26
Page 49
Attention
Trouble shooting 25
Forecast of Cause:
Check Point 2 : Check outdoor unit operation
Check Point 1 : Check indoor unit
Check Point 3 : Check site condition
Check Point 5 : Check refrigeration cycle
Check Point 4 : Check indoor unit / outdoor unit installation condition
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
OKOK
OKOK
OKOK
OKOK
No Cooling / No Heating
1. Indoor unit error 2. Outdoor unit error
3. Effect by surrounding environment
4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure
Does indoor unit Fan run on high fan? Is Air Filter dirty? Is Heat Exchanger clogged? Check if energy save function is operated.
Is outdoor unit is operating? (If not, refer to Trouble shooting 23) Is there any obstructing the air flow route? Is there any clogging on outdoor unit Hert Exchanger? Is the valve open?
Is capacity of indoor unit fitted to room size? Any windows open? Or direct sunlight?
Check connection pipe. (Specified pipe length and pipe diameter?) Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check if Strainer is clogged (Refer to the figure at right). Measure gas pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV Check Compressor
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-27
MPa MPa
Page 50
Trouble shooting 26
Forecast of Cause :
Trouble shooting 27
Forecast of Cause:
OK
OK
OK
OK
OK
OK
OK
Abnormal Noise
1. Abnormal installation(Indoor unit / outdoor unit)
2. Fan failure(Indoor unit / outdoor unit)
3. Compressor failure (Outdoor unit)
Diagnosis method when abnormal noise is occurred
Abnormal noise is coming from indoor unit. (Check and correct followings)
Abnormal noise is coming from outdoor unit. (Check and correct followings)
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is main unit installed in stable condition? Is the installation of air suction grille and front panel normal?
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is main unit installed in stable condition? Is Fan Guard installed normally?
Check if vibration noise by loose bolt or contact noise of piping is happening.
Is Compressor locked? >> Check Compressor
Water Leaking
Diagnosis method when water is spitting out.
Is the filter clogged?
Check gas pressure and correct it if there was a gas leak.
Diagnosis method when water leak occurs
Is Drain Hose connection loose? Is there a trap in Drain Hose? Is Drain Hose clogged?
Is main unit installed in stable condition? Is main unit broken or deformed at the time of transportation or maintenance?
Is Fan rotating? >> Check Fan Motor
02-28
1. Erroneous installation 2. Drain hose failure
MPa MPa
Page 51
SERVICE PARTS INFORMATION 1
MPa
Compressor
Diagnosis method of Compressor (If outdoor unit LED displays error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check connection of Compressor,and winding resistance. (Refer to the next page).
Check Inverter PCB connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.)
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas Pipe Valve open? (Low Pressure is too low)
Check if Refrigerant is leaking. (Recharge Refrigerant)
Check if Strainer is clogged. (PARTS INFORMATION 3)
Abnormal noise
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Check if vibration noise by loose bolt or contact noise of piping is happening.
02-29
2-4 SERVICE PARTS INFORMATION
MPa
Page 52
SERVICE PARTS INFORMATION 2
Inverter Compressor
02-30
Check Point 1 : Check connection
Check Point 2 : Check winding resistance
Check Point 3 : Replace Inverter PCB
U
V
W
Check terminal connection of Compressor (Loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If Check Point 1, 2 do not improve the symptom, replace lnverter PCB.
Resistance value : 0.71 (at 20°C)
U
(RED)
V
(WHITE)
W
(BLACK)
Inverter PCB
Check connection of Inverter PCB (Loose or incorrect wiring)
W9W8
W7
RED
WHITE
BLACK
Compressor
Inverter PCB
Page 53
SERVICE PARTS INFORMATION 3
Check Point 2 : Check coil of EEV
Check Point 1 : Check Connections
Check Point 3 : Check voltage from Inverter PCB.
Check Point 4 : Check Noise at start up
Outdoor Unit Electronic Expansion Valve (EEV)
Check connection of connector ( Loose connector or open cable )
Remove connector, check each winding resistance of Coil.
If Resistance value is abnormal, replace EEV.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Controller PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Inverter PCB.
02-31
CN600
EXPANSION VALVE COIL
Red - Orange
Red - Yellow
Red - White
Red - Green
Read wire
46 4
Resistance value
at 20°C
DC
1 2 3 4 5
1 2 3 4 5
PMV
Red
Orange
Green
Yellow
White
CN40
EXPANSION VALVE COIL
1 2 3 4 5
1 2 3 4 5
PMV
Red
Orange
Brown
Yellow
White
AO*R09LKC AO*R12LKC
Red - Orange
Red - Yellow
Red - White
Red - Brown
Read wire
46 4
Resistance value
at 20°C
AO*R09LKC AO*R12LKC
Page 54
Check Point 5 : Check opening and closing operation of valve
Pipe (In) Hi TEMP.
OPEN Example : Hot gas
Pipe (Out) Hi TEMP.
Check Point 6 : Check Strainer
Pipe (In) Hi TEMP.
Pipe (Out) Normal TEMP.
CLOSE Example : Hot gas
When valve is closed, it has a temp. difference between Inlet and outlet.
If it is open, it has no temp. difference between inlet and outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
02-32
Page 55
3 . APPENDING DATA
R410A
WALL MOUNTED type
INVERTER
1. Jumper setting of Outdoor unit
2. Outdoor unit Pressure Value and Total Electric Current Curve
3. Thermistor Resistance Values
Page 56
03-01
[Outdoor Unit]
JP
JM2 JM103 JM102 JM101
Normal Preheat
12LKC
Higher Preheat
- it is possible to select the higher or standard level of preheating function.
- When it is set up at the higher level of preheat, the magnetic noise of the compressor becomes higher.
Normal Preheat
09LKC
Higher Preheat
1. Jumper setting of Outdoor unit
JM100JM3JM1
Page 57
Model Name : AS*A09 / 12LKC
[Condition] Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
5.0m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*A09LKC
AS*A12LKC
AS*A09LKC
AS*A12LKC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
In/outdoor ambient temparature [degC] In/outdoor ambient temparature [degC]
Low-pressure of outdoor unit [MPa]
Low-pressure of outdoor unit [MPa]
In/outdoor ambient temparature [degC] In/outdoor ambient temparature [degC]
Outdoor total electric current [A]
Outdoor total electric current [A]
03-02
[50Hz-230V]
0.8
0.9
1.0
1.1
1.2
1.3
1.4
16 18 20 22 24 26 28 30 32
RH50% RH60% RH70%
[50Hz-230V]
0.6
0.7
0.8
0.9
1.0
1.1
1.2
16 18 20 22 24 26 28 30 32
RH50%
RH60%
RH70%
[50Hz-230V]
2.6
2.8
3.0
3.2
3.4
3.6
16 18 20 22 24 26 28 30 32
RH50% RH60% RH70%
[50Hz-230V]
3.4
3.6
3.8
4.0
4.2
4.4
4.6
4.8
16 18 20 22 24 26 28 30 32
RH50%
RH60%
RH70%
2. Outdoor unit Pressure Value and Total Electric Current Curve
2-1 Cooling operation
Page 58
Model Name : AS*A09 / 12LKC
[Condition] Ambient
temperature
IIndoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping 5.0m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*A09LKC
AS*A09LKC
AS*A12LKC
AS*A12LKC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
Outdoor ambient temparature [degC] Outdoor ambient temparature [degC]
High-pressure of outdoor unit [MPa]
High-pressure of outdoor unit [MPa]
Outdoor ambient temparature [degC]
Outdoor ambient temparature [degC]
Outdoor total electric current [A]
length
03-03
Measure the high pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
2-2 Heating operation
[50Hz-230V]
2.0
2.2
2.4
2.6
2.8
3.0
0 2 4 6 8 10 12 14
15 degC 20 degC (Indoor ambient temp.) 23 degC
[50Hz-230V]
2.6
2.8
3.0
3.2
3.4
3.6
3.8
0 2 4 6 8 10 12 14
[50Hz-230V]
5.6
6.0
6.4
6.8
7.2
7.6
0 2 4 6 8 10 12 14
15 degC 20 degC (Indoor ambient temp.) 23 degC
15 degC 20 degC (Indoor ambient temp.) 23 degC
Outdoor total electric current [A]
[50Hz-230V]
3.8
4.2
4.6
5.0
5.4
5.8
0 2 4 6 8 10 12 14
15 degC 20 degC (Indoor ambient temp.) 23 degC
Page 59
0.00 33.62 1.15 0.00 176.03 1.10
5.00 25.93 1.39 5.00 134.23 1.36
10.00 20.18 1.66 10.00 103.34 1.63
15.00 15.84 1.94 15.00 80.28 1.92
20.00 12.54 2.22 20.00 62.91 2.21
25.00 10.00 2.50 25.00 49.70 2.51
30.00 8.04 2.77 30.00 39.57 2.79
35.00 6.51 3.03 35.00 31.74 3.06
40.00 5.30 3.27 40.00 25.64 3.30
45.00 4.35 3.48 45.00 20.85 3.53
50.00 3.59 3.68 50.00 17.06 3.73
55.00 2.98 3.85 55.00 14.10 3.90
60.00 2.47 4.00 60.00 11.64 4.55
65.00 2.09 4.14 65.00 9.69 4.19
70.00 1.76 4.25 70.00 8.12 4.30
75.00 1.49 4.35 75.00 6.83 4.40
80.00 1.27 4.44 80.00 5.78 4.48
85.00 1.09 4.51 85.00 4.91 4.55
90.00 0.93 4.57 90.00 4.19 4.61
95.00 0.81 4.63 95.00 3.59 4.66
100.00
0.70
4.67
100.00
3.09
4.71
0.00 168.6 0.36 -20.00 48.13 0.45 -20.00 101.7 1.37
5.00 130.7 0.45 -15.00 36.07 0.58 -15.00 76.31 1.67
10.00 102.2 0.56 -10.00 27.29 0.74 -10.00 57.73 1.99
15.00 80.51 0.70 -5.00 20.84 0.93 -5.00 44.01 2.33
20.00 63.89 0.85 0.00 16.05 1.14 0.00 33.80 2.66
25.00 51.05 1.01 5.00 12.45 1.38 5.00 26.14 2.97
30.00 41.07 1.20 10.00 9.736 1.64 10.00 20.35 3.27
35.00 33.26 1.41 15.00 7.672 1.91 15.00 15.96 3.53
40.00 27.09 1.62 20.00 6.090 2.19 20.00 12.59 3.76
45.00 22.20 1.85 25.00 4.869 2.47 25.00 10.00 3.96
50.00 18.29 2.08 30.00 3.918 2.74 30.00 7.990 4.14
55.00 15.15 2.31 35.00 3.173 3.00 35.00 6.423 4.28
60.00 12.62 2.54 40.00 2.586 3.24 40.00 5.192 4.40
65.00 10.56 2.76 45.00 2.120 3.46 45.00 4.222 4.50
70.00 8.878 2.97 50.00 1.747 3.66 50.00 3.451 4.59
75.00 7.498 3.17 55.00 1.448 3.83 55.00 2.836 4.66
80.00 6.361 3.36 60.00 1.206 3.99 60.00 2.343 4.71
85.00 5.419 3.53 65.00 1.009 4.12 65.00 1.945 4.76
90.00 4.635 3.69 70.00 0.849 4.24 70.00 1.623 4.80
95.00 3.980 3.83 75.00 0.717 4.34 75.00 1.361 4.83
100.00 3.430 3.96 80.00 0.608 4.43 80.00 1.146 4.85
105.00 2.967 4.07 85.00 0.518 4.51 85.00 0.970 4.88
110.00 2.575 4.17 90.00 0.444 4.57 90.00 0.824 4.89
115.00 2.243 4.26 95.00 0.381 4.63 95.00 0.703 4.91
120.00
1.960
4.34
100.00
0.328
4.68
100.00
0.602 4.92
Room temperature thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Indoor heat exchanger thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Discharge thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Outdoor heat exchanger thermistor
Temp ( C)
Resistance(k )
Voltage(V)
Temp ( C)
Resistance(k )
Voltage(V)
Outdoor temperature thermistor
03-04
3. Thermistor Resistance Values
3-1 INDOOR UNIT
3-2 OUTDOOR UNIT
Page 60
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
MAR. 2010 Printed in Japan
Loading...