Fujitsu ARYG LHTA 1ph Installation Manual

Page 1
AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit (Duct type)
For authorized service personnel only.
INSTALLATIONSANLEITUNG
Nur für autorisiertes Fachpersonal.
MANUEL D'INSTALLATION
Unité intérieure (Type conduit)
Pour le personnel de service agrée uniquement.
MANUAL DE INSTALACIÓN
Unidad interior (Tipo ducto)
Únicamente para personal de servicio autorizado.
MANUALE D'INSTALLAZIONE
Unità interna (Tipo di condotto)
A uso esclusivo del personale tecnico autorizzato.
hsilgnE
hcstueDsiaçnarFloñapsEonailatIάkIvηλλEsêugutroP
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
Εσωτερική μονάδα (Τύπος αγωγού)
Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.
MANUAL DE INSTALAÇÃO
Unidade interior (Tipo conduta)
Somente para o pessoal do serviço técnico autorizado.
РУКОВОДСТВО ПО УСТАНОВКЕ
Внутренний модуль (Канального типа)
Только для авторизованного обслуживающего персонала.
KURULUM KILAVUZU
İç Ünite (Kanal tipi)
Yalnızca yetkili servis personeli için.
[Original instructions]
PART NO. 9379123143
йикссуР
eçkrüT
Page 2
INSTALLATION MANUAL
PART NO. 9379123143
Indoor Unit (Duct Type)
Contents
1. SAFETY PRECAUTIONS ..........................................................................................2
2. ABOUT THIS PRODUCT...........................................................................................2
2.1. Precautions for using the R410A refrigerant .......................................................2
2.2. Special tool for R410A refrigerant .......................................................................2
2.3. Accessories ........................................................................................................3
2.4. Optional parts .....................................................................................................3
3. GENERAL SPECIFICATION .....................................................................................3
3.1. Selecting the pipe material .................................................................................3
3.2. Pipe requirement ................................................................................................3
3.3. Electrical requirement .........................................................................................3
4. INSTALLATION WORK .............................................................................................4
4.1. Selecting an installation location ........................................................................4
4.2. Installation dimension .........................................................................................4
4.3. Installing the unit .................................................................................................4
4.4. Installing the drain hose ......................................................................................5
5. PIPE INSTALLATION ................................................................................................6
5.1. Flare connection (Pipe connection) ....................................................................6
5.2. Installing heat insulation .....................................................................................7
6. ELECTRICAL WIRING ..............................................................................................7
6.1. Wiring system diagram .......................................................................................8
6.2. Connection cable preparation .............................................................................8
6.3. Connection of wiring ...........................................................................................8
7. REMOTE CONTROLLER SETTING .........................................................................9
7.1. Installing the remote controller ...........................................................................9
7.2. Setting the dip switches ......................................................................................9
8. FUNCTION SETTING..............................................................................................10
8.1. Turning on the power ........................................................................................10
8.2. Function setting ................................................................................................10
8.3. Group control system .......................................................................................12
8.4. Dual remote controllers ....................................................................................12
9. OPTIONAL KIT INSTALLATION (OPTION) ............................................................. 13
10. CHECK LIST ............................................................................................................13
11. TEST RUN ...............................................................................................................13
12. CUSTOMER GUIDANCE ........................................................................................13
13. ERROR CODES ......................................................................................................14
Note: This manual describes how to install the air conditioner described above. Handling
and installation shall only be done by professionals as outlined in this manual.
CAUTION
Read carefully all safety information written in this manual before you install or use the air conditioner.
Install the product by following local codes and regulations in force at the place of instal­lation, and the instructions provided by the manufacturer.
This product is part of a set constituting an air conditioner. The product must not be installed alone or be installed with non-authorized device by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 3 mm for this product.
To protect the persons, earth (ground) the product correctly, and use the power cable combined with an Earth Leakage Circuit Breaker (ELCB).
The product is not explosion proof, and therefore should not be installed in explosive atmosphere.
To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 5 minutes or more before you touch the electrical components.
Do not touch the ns of the heat exchanger. Touching the heat exchanger ns could result in damage to the ns or personal injury such as skin rupture.
This product contains no user-serviceable parts. Always consult experienced service technicians for repairing.
When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the product.
Do not place any other electrical products or household belongings under the product. Condensation dripping from the product might get them wet, and may cause damage or malfunction of the property.
Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to property.
2. ABOUT THIS PRODUCT
2.1. Precautions for using the R410A refrigerant
WARNING
• Do not introduce any substanc e other than the prescribed refrige rant into the
refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become
abnormally high and cause the piping to rupture.
• If there is a refrigerant leakage, make sure that it does not exceed the concentration
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such
as oxygen starvation.
• Do not touch refrigerant that has leaked from the refrigerant pipe connections or
other area. Touching the refrigerant directly can cause frostbite.
• If a refrigerant leakage occurs during operation, immediately vacate the premises
and thoroughly ventilate the area.
If the refrigerant comes in contact with a ame, it produces a toxic gas.
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the Operating Manual to the customer.
Request the customer to keep them on hand for future use, such as for relocating or
repairing the unit.
WARNING
Installation of this product must be done by experienced service technicians or profes­sional installers only in accordance with this manual. Installation by nonprofessional or improper installation of the product may cause serious accidents such as injury, water
leakage, electric shock, or re. If the product is installed in disregard of the instructions
in this manual, it will void the manufacturer’s warranty. Do not turn on the power until all work has been completed. Turning on the power
before the work is completed can cause serious accidents such as electric shock or
re.
If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant
is exposed to a direct ame it may produce a toxic gas. Do not use this equipment with air or any other unspecied refrigerant in the refriger-
ant lines. Excess pressure can cause a rupture. Installation must be performed in accordance with regulations, codes, or standards for
electrical wiring and equipment in each country, region, or the installation place. This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
To avoid danger of suffocation, keep the plastic bag or thin lm used as the packaging
material away from young children.
Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.
2.2. Special tool for R410A refrigerant
WARNING
• To install a unit that uses the R410A refrigerant, use dedicated tools and piping materials that have been manufactured specically for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than
the R22, failure to use dedicated piping material or improper installation can cause rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or
re.
Tool name Contents of change
• Pressure is huge and cannot be measured with a conventional
gauge. To prevent erroneous mixing of other refrigerants, the
Gauge manifold
Charging hose
Vacuum pump
Gas leakage
detector
diameter of each port has been changed.
It is recommended to use a gauge manifold with a high
pressure display range –0.1 to 5.3 MPa and a low pressure display range –0.1 to 3.8 MPa.
• To increase pressure resistance, the hose material and base
size were changed.
• A conventional vacuum pump can be used by installing a
vacuum pump adapter.
• Special gas leakage detector for HFC refrigerant R410A.
En-2
Page 3
2.3. Accessories
3. GENERAL SPECIFICATION
WARNING
• For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall,
water leakage, electric shock, or re.
• The following installation parts are furnished. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Do not discard any accessories needed for installation until the installation work has been completed.
Name and Shape Q’ty Application
Installation Manual
(Indoor unit)
Operating Manual
(Indoor unit)
Operating Manual (CD-ROM)
Special nut A
(Large flange)
Special nut B (Small flange)
Coupler heat insulation (Large)
(This manual)
1
1
1
For suspending the indoor unit from ceiling
4
4
For indoor side pipe joint (Gas pipe)
1
3.1. Selecting the pipe material
CAUTION
Do not use existing pipes.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion (es­pecially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A in­curs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials.
• Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than those indicated in the table even if they are available
on the market.
Pipe outside diameter [mm (in.)] Thickness [mm]
6.35 (1/4) 0.8
9.52 (3/8) 0.8
12.70 (1/2) 0.8
15.88 (5/8) 1.0
19.05 (3/4) 1.2
3.2. Pipe requirement
CAUTION
Refer to the installation manual of the outdoor unit for description of the length of con­necting pipe or for difference of its elevation.
Diameter [mm (in.)]
Liquid
Gas
9.52 (3/8)
15.88 (5/8)
Coupler heat insulation (Small)
Cable tie (Small)
Remote controller
Screw (M4 × 16)
Remote controller cable
For indoor side pipe joint (Liquid pipe)
1
For fixing the remote controller
1
cable
1
For installing indoor unit remote
2
controller
For connecting the remote controller
1
2.4. Optional parts
Parts name Model No. Application
Simple remote controller UTY-RSN*M For air conditioner operation
Wired remote controller UTY-RNN*M
Remote sensor unit UTY-XSZX Room temperature sensor
External connect kit UTD-ECS5A For control input/output port
Long life lter UTD-LF60KA
For air conditioner operation (3-wire type)
• Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks. Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only) In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70 %, install heat insulation around the refrigerant piping. If the expected humidity level is 70-80 %, use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. If heat insulation is used that is not as thick as specied, condensation may
form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
3.3. Electrical requirement
The indoor unit is powered from the outdoor unit. Do not power indoor unit from separate power source.
WARNING
Standard for electrical wiring and equipment differs in each country or region. Before you start electrical working, conrm related regulations, codes, or standards.
Cable
Connection
cable
Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 2% or more.
Cable
Remote controller cable (3-wire type)
Conductor size
(mm2)
1.5 (MIN.) Type 60245 IEC57
Conductor size
(mm2)
0.33
Type Remarks
Type Remarks
Use sheathed PVC cable.
(Accessories)
3Wire+Earth (Ground),
1φ 230V
Polar 3-wired
En-3
Page 4
4. INSTALLATION WORK
4.2. Installation dimension
WARNING
Do not turn on the power until all installation work is complete.
Carrying and installation of the unit should be performed by a sufcient number of people and with sufcient equipment that is adequate for the weight of the unit. Performing such work with an insufcient number of people or with inadequate equip-
ment could result in dropping of the unit or personal injury.
CAUTION
For installation details, refer to the technical data.
4.1. Selecting an installation location
Decide the mounting position together with the customer as follows.
WARNING
Select installation locations that can properly support the weight of the indoor unit
and which will not amplify sound or vibration. If the installation location is not strong enough, the indoor unit may fall and cause injuries.
Install the units securely so that they do not topple or fall.
CAUTION
Do not install the indoor unit in the following areas:
Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fall or the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen. It will deteriorate plastic parts, causing the parts to fall or the unit to leak water.
Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon bers or ammable dust, or volatile inammables such as paint thinner or gasoline. If gas leaks and settles around the unit, it can cause a re.
Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing plants, or preserving precision devices or art objects. It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or ammable gas.
Install the unit where drainage does not cause any trouble. Install the indoor unit, outdoor unit, power supply cable, connection cable, and remote
control cable at least 1 m away from a television or radio receivers. The purpose of this is to prevent TV reception interference or radio noise. (Even if they are installed more than 1 m apart, you could still receive noise under some signal conditions.)
Install the unit where ambient temperature does not reach 60°C or more. Take a measure such as ventilation for an environment in which heat is retained.
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
(1) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room. (2) Leave the space required to service the air conditioner. (3) Install the unit where connection to the outdoor unit is easy. (4) Install the unit where the connection pipe can be easily installed. (5) Install the unit where the drain pipe can be easily installed.
(6) Install the unit where noise and vibrations are not amplied.
(7) Take servicing, etc., into consideration and leave the spaces. Also install the unit where
the lter can be removed. (8) Do not install the unit where it will be exposed to direct sunlight.
Correct initial installation location is important because it is difcult to move unit after it is
installed.
Install at least 20mm from the ceiling.
20
or more
450
2500 or more
(When no ceiling)
Floor
(For maintenance)
(1) Maintenance work of the control box is possible with the maintenance hole of the
measurement shown in the gure.
(2) If maintenance work is to be done from the bottom side, the maintenance hole needs
to be larger than the outside dimension of the indoor unit.
(3) If maintenance work is to be done from the top, keep the space of the more than
500 mm between the indoor unit and ceiling.
Control box
Maintenance hole
450
500
(Service space)
Unit : mm
500
Unit : mm
4.3. Installing the unit
WARNING
Carrying and installation of the unit should be performed by a sufcient number of people and with sufcient equipment that is adequate for the weight of the unit. Per­forming such work with an insufcient number of people or with inadequate equipment
could result in dropping of the unit or personal injury. If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care. When fastening the hangers, make the bolt positions uniform.
CAUTION
Conrm the directions of the air intake and outlet before installing the unit. The unit takes in air from the fan side, and expels it from the evaporator side.
Check that duct work does not exceed the range of external static pressure of equip­ment.
Make sure to insulate ducts to avoid the dew condensation.
Make sure to insulate between ducts and walls if metal ducts are used.
Please explain handling and washing methods of locally purchased materials to the customer.
To prevent people from touching the parts inside the unit, be sure to install grilles on the inlet and outlet ports. The grilles must be designed in such a way that cannot be removed without tools.
When connecting the duct to the outlet port of the indoor unit, be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port.
En-4
RECOMMENDED RANGE OF
EXTERNAL STATIC PRESSURE [Pa]
100 - 250
Page 5
4.3.1. Installing the hangers
Hanging bolt installation diagram
460
155
585
500
1,050 1,000
AIR
CAUTION
• If an intake duct is installed, take care not to damage the temperature sensor (the
85
temperature sensor is attached to the intake port ange).
• Be sure to install the air inlet grille and the air outlet grille for air circulation. The
correct temperature cannot be detected. Grills must be installed so that man cannot touch unit fan, and cannot be removed by only hand operation with tool.
Unit
AIR AIR
1,080
Hanging bolt M10
(Locally purchased) Washer
(Locally purchased)
CAUTION
• Fasten the unit securely with special nuts A and B.
Special nut A
(Accessories)
Special nut B
(Accessories)
4.3.2. Leveling
Use the procedure in the following gure to adjust the levelness.
Level meter
Unit : mm
Hanger
Air Outlet Grille
(Room)
• Be sure to install the air lter in the air inlet. If the air lter is not installed, the heat
exchanger may be clogged and its performance may decrease.
Air Inlet Grille
4.4. Installing the drain hose
CAUTION
Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enough to prevent condensation. Problems with the piping may lead to water leaks.
Be sure to properly insulate the drain hose so that the water will not drip from the con­nected parts.
The position of the installed drain hose should have a downward gradient of 1/100 or
more.
Do not connect the drain hose in which ammonia or other types of gas affecting the
unit is generated. Heat exchange erosion may occur.
To prevent excessive force on drain hose, avoid bends or twists. (To bend or twist may cause water leaks.)
Install the drain pipes according to the measurements given in the following gure.
Flange positions for connecting the drain pipes.
139
123
B
The side A of the unit with the drain port should be slightly lower than the opposite side
B of the unit. The height difference between sides A and B should be from 0 to 20mm.
A
4.3.3. Mounting the duct
Follow the procedure in the following gure to install the ducts.
325
14
27
Spacing between ange and drain pan.
14
26
295
865
Intake port ange
Outlet port ange
850
Unit : mm
108 41208
356
371
Main drain pipe
ø25.4 (O.D.)
Safety drain pipe
ø25.4 (O.D.)
Unit : mm
CAUTION
• This UNIT has drain ports in two locations. Follow the procedure in the figure to
connect drain pipes to each of them.
• Be sure to properly insulate the drain pipes.
Use general hard polyvinyl chloride pipe (VP25) and connect it with adhesive (polyvinyl
chloride) so that there is no leakage. Do not perform air bleeding.
(1) Main drain pipe
Provide one trap on the main drain pipe near the indoor unit.
= 100 mm (approx.)
H
Unit
1
= 50-100 mm
H
2
Drain pipe (main)
H1H2
Trap
En-5
Page 6
(2) Safety drain
There is no need to provide a trap for the safety drain pipe. If the safety drain pipe is connected to the main drain pipe, make the connection below the trap on the main drain pipe.
Unit
Drain pipe (main)
Drain pipe (safety)
Pipe outside diameter
[mm (in.)]
6.35 (1/4)
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional are tools to are R410A pipes, the dimension A should be approximately 0.5 mm more than indicated in the table (for aring with R410A are tools) to achieve the specied aring. Use a thickness gauge to measure the dimension A.
Dimension A [mm]
Flare tool for R410A,
clutch type
0 to 0.5
Dimension B
9.1
-00.4
[mm]
Once installation is complete, check the ow of the drain water.
5. PIPE INSTALLATION
WARNING
During installation, make sure that the refrigerant pipe is attached rmly before you
run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
When installing and relocating the air conditioner, do not mix gases other than the
specied refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a ame, it produces a toxic gas.
CAUTION
Be more careful so that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant R410A models. Also, when storing the piping, securely seal the open­ings by pinching, taping, etc.
While brazing the pipes, be sure to blow dry nitrogen gas through them.
Width across
ats
Pipe outside
diameter [mm (in.)]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
Width across flats
of Flare nut [mm]
5.1.2. Bending pipes
If pipes are shaped by hand, be careful not to collapse them.
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bend or stretched, the material will harden, making it
difcult to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
5.1.3. Pipe connection
CAUTION
Be sure to install the pipe against the port on the indoor unit correctly. If the centering is improper, the are nut cannot tighten smoothly. If the are nut is forced to turn, the
threads will be damaged.
• Do not remove the flare nut from the indoor unit pipe until immediately before
connecting the connection pipe.
5.1. Flare connection (Pipe connection)
WARNING
• Tighten the are nuts with a torque wrench using the specied tightening method. Otherwise, the are nuts could break after a prolonged period, causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a ame.
5.1.1. Flaring
• Use special pipe cutter and are tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter. (2) Hold the pipe downward so that cuttings will not enter the pipe and remove any
burrs.
(3) Insert the are nut (always use the are nut attached to the indoor and outdoor units
respectively) onto the pipe and perform the are processing with a are tool. Use the special R410A are tool, or the conventional are tool. Leakage of refrigerant may result if other are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Check if [L] is ared uniformly
B
Die
A
Pipe
and is not cracked or scratched.
/
• Do not use mineral oil on ared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.
(1) Detach the caps and plugs from the pipes. (2) Centering the pipe against port on the indoor unit, turn the are nut with your hand.
Flare nut
Connection pipe (small)
Flare nut
(3) When the are nut is tightened properly by your hand, hold the body side coupling
with a separate spanner, then tighten with a torque wrench. (See the table below for the are nut tightening torques.)
Connection pipe (large)
CAUTION
• Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to tighten the are nut correctly.
• Tighten the are nuts with a torque wrench using the specied tightening method. Otherwise, the are nuts could break after a prolonged period, causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a ame.
• Connect the piping so that the control box cover can easily be removed for servicing
when necessary.
• In order to prevent water from leaking into the control box, make sure that the piping
is well insulated.
En-6
Page 7
Tighten with 2 wrenches.
Holding wrench
Torque wrench
Indoor unit pipe (Body side)
Flare nut
Connection pipe
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
5.2. Installing heat insulation
After checking for gas leaks, insulate by wrapping insulation around the two parts (Gas and Liquid) of the indoor unit coupling, using the coupler heat insulation. After installing the coupler heat insulation, wrap both ends with vinyl tape so that there is no gap.
Secure both ends of the heat insulation material using nylon fasteners.
Coupler heat insulation (Small)
Indoor unit side
Coupler heat insulation (Large)
CAUTION
There should be no gaps between the insulation and the product.
CAUTION
After connecting the piping, check the all joints for gas leakage with gas leak detector. Once the pressure checking has been completed using nitrogen, please refer to the
outdoor unit installation manual to complete the evacuation process.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do so may cause water leaks.
6. ELECTRICAL WIRING
WARNING
• Electrical work must be performed in accordance with this Manual by a person certied under the national or regional regulations. Be sure to use a dedicated circuit
for the unit.
An insufcient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or re.
• Before starting work, check that power is not being supplied to the indoor unit and
outdoor unit.
• For wiring, use the prescribed type of cables, connect them securely, making sure
that there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as
overheating the terminals, electric shock, or re.
• Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious accidents such as
electric shock or re through exposure to dust or water.
WARNING
• Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
• Use the included connection cables and power cables or ones specified by the
man ufacturer. Improper connections , insufficient insulation, or exce eding the
allowable current can cause electric shock or re.
• Do not modify the power cables, use extension cables, or use any branches in the
wiring. Improper connections, insufficient insulation, or exceeding the allowable
current can cause electric shock or re.
• Match the terminal block numbers and connection cable colors with those of the
outdoor unit. Erroneous wiring may cause burning of the electric parts.
• Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends
of the wiring, can cause a malfunction, electric shock, or re.
Always fasten the outside covering of the connection cable with the cable clamp. (If
the insulator is chafed, electric leakage may occur.)
• Install a earth leakage breaker. In addition, install the earth leakage breaker so that
the entire AC main power supply is cut off at the same time. Otherwise, electric shock
or re could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
• Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
• Connect the connection cable rmly to the terminal board. Imperfect installation may cause a re.
CAUTION
• Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
• Do not connect power supply cables to the connection or remote controller terminals,
as this will damage the product.
• Never bundle the power supply cable and connection cable, remote controller cable
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.
• When handling PCB, static electricity charged in the body may cause malfunction of
the PCB. Follow the cautions below:
• Establish a ground for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor and outdoor units for more than 10 seconds to
discharge static electricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.
(1) Use ring terminals with insulating sleeves as shown in the gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the specied cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques. (7) Please do not x 2 power supply cables with 1 screw.
En-7
Page 8
6.2. Connection cable preparation
Strip 10 mm
Screw with
special washer
Ring terminal
Cable
Terminal block
Ring terminal
Cable
Sleeve
Screw with
special washer
Ring terminal
WARNING
• Use ring terminals and tighten the terminal screws to the specied torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the unit.
Tightening torque [N·m (kgf·cm)]
M4 screw
M5 screw
1.2 to 1.8 (12 to 18)
2.0 to 3.0 (20 to 30)
Keep the earth (ground) wire longer than the other wires.
30 mm
Earth (Ground) wire
40 mm or more
• Use a 4-core wire cable.
Power supply cable or connection cable
6.3. Connection of wiring
CAUTION
• Use care not to mistake the power supply cable and connection wires when installing.
• Install so that the wires for the remote controller will not come in contact with other
connection wires.
(1) Remove the control box cover and install each connection wire.
Control box cover
6.1. Wiring system diagram
Connection cable (to outdoor unit)
Earth (Ground) line
Power line
Control line
Wired remote controller cable
Red White
* Earth (Ground) the remote controller
Black
Indoor
unit side
CAUTION
Tighten the indoor unit connection cable and power supply indoor and outdoor unit,
terminal board connections rmly with the terminal board screws. Faulty connection may cause a re.
If the indoor unit connection cable and power supply are wired incorrectly, the air
conditioner may be damaged.
Connect the indoor unit connection cable by matching the numbers of the outdoor and
indoor units terminal board numbers as shown in terminal label.
Earth (Ground) both the indoor and outdoor units by attaching an earth (ground) cable.
Unit shall be grounded in compliance with the country or region's regulations.
CAUTION
Be sure to refer to the above diagram for do correct eld wiring. Wrong wiring causes
malfunction of the unit.
Check local electrical rules and also any specic wiring instructions or limitation.
(Please connect it when necessary.)
Loosen the screws (2 locations)
(2) After wiring is complete, secure the remote controller cable, connection cable, and
power supply cable with the cable clamps.
(3) Install the control box cover.
Cable clamp
Remote controller cable
Connection cable (to outdoor unit)
CAUTION
• Do not bundle the remote controller cable, or wire the remote controller cable in
parallel, with the indoor unit connection wire (to the outdoor unit) and the power supply cable. It may cause erroneous operation.
En-8
Page 9
7. REMOTE CONTROLLER SETTING
SET BACK
ON
ON
OFF
1 2 3 4 5 6
.
CAUTION
When detecting the room temperature using the remote con­troller, please set up the remote controller according to the following conditions. If the remote controller is not located prop­erly, the correct room temperature will not be detected, and thus abnormal conditions like “not cooled” or “not heated” will occur even if the air-conditioner is running normally.
• Locate where an average temperature for the room being air conditioned will be sensed.
• Do not locate directly exposed to the outlet air from the air-conditioner.
• Locate out of direct sunlight.
• Locate away from the inuence of other heat sources.
Do not touch the remote controller PC board and PC board parts directly with your hands
Do not wire the remote controller cable together with or parallel to the connection
cables, and power supply cable of the INDOOR UNIT and OUTDOOR UNIT. It may
cause erroneous operation.
When installing the bus wire near a source of electromagnetic waves, use shielded wire
Do not set the DIP switches, either on the air conditioner or the remote controller, in any way other than indicated in this manual that is supplied with the air conditioner. Doing so may result in improper operation.
Temperature sensor
120
17
120
.
33.5
30
Hole
23
15.3
.
45.3
4.5
8
7.1. Installing the remote controller
Open the operation panel on the front of the remote controller, remove the 2 screws indi-
cated in the following gure, and then remove the front case of the remote controller.
When installing the remote controller, remove the connector from the front case. The wires may break if the connector is not removed and the front case hangs down.
When installing the front case, connect the connector to the front case.
Front case (back side)
Screws
Connector
When remote controller cable is concealed (1) Conceal the remote controller cable. (2) Pass the remote controller cable through the hole in the rear case and connect the
remote controller cable to the remote controller terminal board specied in gure.
(3) Clamp the remote controller cable sheath with the cable tie as shown in gure.
(4) Cut off the excess cable tie.
(5) Install the rear case to the wall, box, etc., with 2 screws gure.
1. Red
Hole
2. White
3. Black
Rear case
63.5
4.5
83.5
6
4.5 12.5
Hole × 2
Hole × 3
Unit: mm
CAUTION
Install the remote controller wires so as not to be direct touched with your hands.
Do not touch the remote controller PC board and PC board parts directly with your hands.
7.2. Setting the dip switches
Set the remote controller DIP switches.
[Example]
Front case (back side)
Cable tie
(Small)
[Example]
CAUTION
When connecting the remote controller wires, do not overtighten the screws.
Remote controller cable
Connector
Box
Rear case
Ground the remote controller if it has a ground wire.
Screws
Wrap the connector and remote controller wires with vinyl tape or some other type of insulation
as shown in the gure.
Remote controller
DIP­switch 1
NO.
1
2
3
4
5
SW state
OFF ON
6★ Invalidity Validity
DIP switch 1
Detail
Cannot be used. (Do not change)
Dual remote controller setting
* Refer to 8.4. Dual remote controllers
Cannot be used. (Do not change)
Cannot be used. (Do not change)
Cannot be used. (Do not change)
Memory backup setting * Set to ON to use batteries for the memory
backup. If batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
(★ Factory setting)
En-9
Page 10
8. FUNCTION SETTING
CAUTION
• Conrm whether the wiring work for outdoor unit has been nished.
• Conrm whether the cover for electric control box on the outdoor unit is close.
(4) Press the SET TEMP. buttons ( ) ( ) to select the setting value.
The display ashes as shown to the right during setting value selection.
8.1. Turning on the power
(1) Check the remote controller wiring and DIP switch settings.
(2) Install the front case.
When installing the front case, connect the connector to the front case.
(3) Check the indoor and outdoor unit wiring and circuit board switch settings, and then
turn on the indoor and outdoor units. After “9C” has ashed on the set temperature
display for several seconds, the clock display will appear in the center of the remote controller display. The clock display will appear in the center of the remote controller display.
SUMOTUWETH FR
8.2. Function setting
This procedure changes the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. This procedure should be performed by authorized installation or service personnel only.
Perform the “FUNCTION SETTING” according to the installation conditions using the remote
controller. (Refer to the indoor unit installation manual for details on the function numbers and setting values.)
(1) Press the SET TEMP. buttons (
5 seconds to enter the function setting mode.
SUMOTUWETH FR
(2) Press the SET BACK button to select the indoor unit number.
SET BACK
) ( ) and FAN button simultaneously for more than
SA
SA
SUMOTUWETH FR
(5) Press the TIMER SET button to conrm the setting.
Press the TIMER SET button for a few seconds until the setting value stops ashing. If the setting value display changes or if “- -” is displayed when the ashing stops, the
setting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings.
Press the SET TEMP. buttons (
more than 5 seconds to cancel the function setting mode. In addition, the func­tion setting mode will be automatically canceled after 1 minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
SA
Setting value
) ( ) and FAN button simultaneously again for
CAUTION
• After turning off the power, wait 30 seconds or more before turning on it again. The FUNCTION SETTING doesn’t become effective if it doesn’t do so.
Function Details
(1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the lter. Select the time setting for the lter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the lter sign to be displayed, select the
setting value for “No indication”.
(♦... Factory setting)
Function
Number
11
Setting
Value
00 Standard (2500 hours) 01 Long interval (5000 hours) 02 Short interval (1250 hours) 03 No indication
Setting Description
SUMOTUWETH FR
Unit number of INDOOR UNIT
(3) Press the SET TIME ( ) buttons to select the function number.
SUMOTUWETH FR
Function number
SA
SA
(2) Cooling room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
(♦... Factory setting)
Function
Number
30
Setting
Value
00 Standard ♦ 01 Warmer control 02 Slightly lower control 03 Lower control
Setting Description
(3) Heating room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as shown in the table below.
(♦... Factory setting)
Function
Number
31
Setting
Value
00 Standard ♦ 01 Warmer control 02 Slightly warmer control 03 Lower control
Setting Description
En-10
Page 11
(4) Auto restart
A
B
Enable or disable automatic system restart after a power outage.
(♦... Factory setting)
Function
Number
40
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
Setting
Value
00 Yes ♦ 01 No
Setting Description
(5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the Wired remote controller temperature sensor.
(♦... Factory setting)
Function
Number
42
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
Setting
Value
00 No ♦ 01 Yes
Setting Description
(6) External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(♦... Factory setting)
Function
Number
46
Setting
Value
00 Operation/Stop mode ♦ 01 (Setting forbidden) 02 Forced stop mode
Setting Description
(7) Room temperature control switching
• This setting is used to set the room temperature control method when the wired remote controller is selected by the Indoor Room Temperature Sensor Switching Function.
(♦... Factory setting)
Function
Number
48
Setting
Value
00
01
Setting Description
Control by the sensors of both the indoor unit and the wired remote controller.
Control only by the sensor of the wired remote controller
Setting record
Record any changes to the settings in the following table.
Setting Setting Value
(1) Filter sign (2) Cooling room temperature correction
(3) Heating room temperature correction
(4) Auto restart (5) Indoor room temperature sensor switching
function
(6) External input control
(7) Room temperature control switching
(8) Indoor unit fan control for energy saving for
cooling
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
SETTING THE ROOM TEMPERATURE DETECTION LOCATION
The detection location of the room temperature can be selected from the following 2 examples. Choose the detection location that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor
(1) When the THERMO SENSOR button is pressed, the lock display ashes because the
function is locked at the factory.
Indoor unit
.
B. Indoor unit/remote controller setting (room tempera-
ture sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect the room temperature.
(1) Enable the room temperature sensor selection in FUNCTION SETTING, which will be
“(5) Indoor room temperature sensor switching function”.
(2) Press the THERMO SENSOR button for 5 seconds or more to select the temperature
sensor of the indoor unit or the remote controller.
Indoor unit
(8) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
(♦... Factory setting)
Function
Number
49
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting. * As the factory setting, this setting is initially activated. * When connecting VRF system using network converter, this setting must be set to “00” or “01”.
Setting
Value
00 Disable 01 Enable 02 Remote controller
Setting Description
CAUTION
temperature sensor of the indoor unit temporarily.
As the temperature sensor of remote controller detects the temperature near
the wall, when there is a certain difference between the room temperature and the wall temperature, the sensor will not detect the room temperature correctly sometimes. Especially when the outer side of the wall on which the sensor is positioned is exposed to the open air, it is recommended to use the temperature sensor of the indoor unit to detect the room temperature when the indoor and outdoor
temperature difference is signicant.
The temperature sensor of the remote controller is not only used when there is a
problem in the detection of the temperature sensor of the indoor unit.
NOTES
If the function to change the temperature sensor is used as shown in examples A (other than example B), be sure to lock the detection location. If the function is locked, the lock
display
When select the “Remote controller setting”, if the detected temperat ure va lue between the temp erature sensor of the indoor unit and the temperature sensor of the remote controller
varies signicantly, it is likely to return to the control status of
will ash when the THERMO SENSOR button is pressed.
En-11
Page 12
8.3. Group control system
CAUTION
• When setting rotary switch, do not touch any other parts on the circuit board directly
with your bare hands.
• Be sure to turn off the main power.
A number of indoor units can be operated at the same time using a single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit 0 Indoor unit 1 Indoor unit 2 Indoor unit 3
Remote controller
Rotary switch setting (unit number)
Remote controller setting
Refrigerant circuit address
Primary/Secondary
Standard
Outdoor
unit
Indoor unit
pair
1
Simultaneous
twin
Outdoor
unit 2
Indoor
Indoor
unit
unit
Simultaneous
triple
Outdoor
unit
3
Indoor
Indoor
unit
unit
00 01 02 03 04 05
00 01 01 02 02 02
00 00 01 00 01 01
Indoor unit
1 2 3
1
2 3
R W B
Remote controller
When ground wire is necessary
(2) Rotary switch setting (indoor unit)
Set the unit number of each indoor unit using the rotary switch on the indoor unit circuit
board.
The rotary switch is normally set to 0.
1 2 3 1 2 3 1 2 3
Bus wire
Remote controller cable
Indoor unit
Rotary Switch
NOTE
Be sure to set the unit numbers sequentially.
(3) Remote controller setting
1. Turn on all of the indoor units.
* Turn on the indoor unit with the unit number 00 last. (Within 1 minute)
2. Set the refrigerant circuit address. (Assign the same number to all of the indoor units
connected to an outdoor unit.)
: Connection cable, Power supply cable : Power supply cable : Remote controller cable : Bus wire
* Make sure that the indoor unit with the unit number 00 is connected to the outdoor unit
using a connection cable.
8.4. Dual remote controllers
• Two separate remote controllers can be used to operate the indoor units.
• The timer and self-diagnosis functions cannot be used on the secondary units.
(1) Wiring method (indoor unit to remote controller)
Indoor unit
Remote controller cable
1 2 3
When ground wire is necessary
R W B R W B
Primary unit
Remote controller
(2) Remote controller DIP switch 1 setting
Set the remote controller DIP switch 1 No. 2 according to the following table. (Refer to 7.2. Setting the dip switches)
Number of remote
controllers
1 (Normal) OFF
2 (Dual) OFF ON
Primary unit Secondary unit
DIP SW 1 No. 2 DIP SW 1 No. 2
1 2 31 2 3
Secondary
unit
Refrigerant circuit
address
3. Set the “primary” and “secondary” settings. (Set the indoor unit that is connected to
the outdoor unit using a connection cable as the “primary”.)
Primary
Secondary 01
4. After completing the function settings, turn off all of the indoor units, and then turn
them back on.
* If error code 21, 22, 24, or 27 is displayed, there may be an incorrect setting.
NOTE
• When different indoor unit models are connected using the group control system, some
• If the group control system contains multiple units that are operated simultaneously, con-
• Auto-changeover operates under the same mode with model unit number 00.
• It should not be connected to any other Gr that is not of the same series (A**G only).
Perform the remote controller setting again.
functions may no longer be available.
nect and set the units as shown below.
Function Number Setting Value
02 00~15
Function Number Setting Value
51
00
En-12
Page 13
9. OPTIONAL KIT INSTALLATION (OPTION)
11. TEST RUN
WARNING
Regulation of cable differs from each locality, refer in accordance with local rules.
This air conditioner can be connected with the following optional kits.
Option type Connector No.
UTY-XSZX (Remote sensor unit) CN8
UTD-ECS5A (External input) CN114
UTD-ECS5A (External output) CN115
UTD-ECS5A (Preparation) CN5, CN106
(CN115)(CN114)
(CN106)
(CN8)
(CN5)
Remote controller cable
Connection cable (to outdoor unit)
CHECK ITEMS
(1) Is operation of each button on the remote controller normal? (2) Is the drain normal?
Is there any abnormal noise and vibration during operation?
(3)
• Do not operate the air conditioner in test run for a long time.
[OPERATION METHOD]
• For the operation method, refer to the operating manual. (1) Stop the air conditioner operation.
Press the MODE button and the FAN button simultaneously for 2 seconds or more to
(2)
start the test run.
Test run display
(3) Press the START/STOP button to stop the test run. If “C0” appears in the unit number display, there is a remote controller error. Refer to the
installation manual included with the remote controller.
Unit number Error code Content
Incompatible indoor unit is connected
Indoor unit ↔ remote controller communication error
12. CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air
ow switching, and other remote controller operations.
2) Air lter removal and cleaning, and how to use the air louvers.
(
(3) Give the operating and installation manuals to the customer.
10. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After installation is complete, be sure to check the following check items again.
CHECK ITEMS If not performed correctly CHECK BOX
Has the indoor unit been
installed correctly?
Has there been a check for
gas leaks (refrigerant pipes)?
Has heat insulation work been completed?
Does water drain easily from the indoor units?
Are the wires and pipes all connected completely?
Is the connection cable the
specied thickness?
Are the inlets and outlets free of any obstacles?
After installation is completed, has the proper operation and handling been explained to the user?
Vibration, noise, indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn damage
No operation, heat or burn damage
No cooling, No heating
En-13
Page 14
13. ERROR CODES
[Troubleshooting at the remote controller LCD]
This is possible only on the wired remote controller.
[Self-diagnosis]
If an error occurs, the following display will be shown.(“Er” will appear in the set room temperature display.)
Error codeUnit number of indoor unit
EX. Self-diagnosis
2-way valve temp. sensor error
3-way valve temp. sensor error Heat sink temp. sensor error
• Sub-cool Heat Ex. gas inlet temp. sensor error
• Sub-cool Heat Ex. gas outlet temp. sensor error
Liquid pipe temp. sensor error
Current sensor error
Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
Trip detection
Wired remote
controller
Error code
Description
Serial communication error
Wired remote controller communication error
Check run unnished
Unit number or Refrigerant circuit address setting error [Simultaneous Multi]
Indoor unit capacity error
Combination error
Connection unit number error (indoor secondary unit) [Simultaneous Multi]
Connection unit number error (indoor unit or branch unit) [Flexible Multi]
Primary unit, secondary unit set-up error [Simultaneous Multi]
Power supply interruption error
Indoor unit PCB model information error
Manual auto switch error
Room temp. sensor error
Compressor rotor position detection error (permanent stop)
Outdoor unit fan motor 1 error
Outdoor unit fan motor 2 error
4-way valve error
Coil (expansion valve) error
Discharge temp. error
Compressor temp. error
High pressure error
Low pressure error
Branch boxes error
[Flexible Multi]
Indoor unit Heat Ex. Middle temp. sensor error
Indoor unit fan motor error
Drain pump error
Damper error
Indoor unit error
Outdoor unit main PCB model information error or communication error
Inverter error
Active lter error, PFC circuit error
Trip terminal L error
Display PCB microcomputers communication error
Discharge temp. sensor error
Compressor temp. sensor error
Outdoor unit Heat Ex. liquid temp. sensor error
Outdoor temp. sensor error
Suction Gas temp. sensor error
En-14
Page 15
Loading...