Fujitsu ARYG45LHTBP, ARYG36LHTBP, ARYG18LHTBP, ARYG54LHTBP, ARYG30LHTBP Technical Manual

...
Page 1
DESIGN & TECHNICAL MANUAL
AIR CONDITIONER
Duct type
INDOOR
ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP
ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP
OUTDOOR
AOYG18LBCA AOYG24LBCA
AOYG45LBTA AOYG54LBTA
DR_AR006EF_01
2015.11.13
Page 2
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2015 Fujitsu General Limited. All rights reserved.
Page 3
CONTENTS
Part 1. INDOOR UNIT ........................................................................1
1. Product features ......................................................................................2
1-1. Model lineup ..............................................................................................................2
1-2. Features .....................................................................................................................2
2. Wired remote controller .........................................................................4
2-1. Features .....................................................................................................................4
2-2. Overview ....................................................................................................................8
2-3. Specifications .............................................................................................................9
2-4. Wiring specifications ..................................................................................................9
3. Specifications ........................................................................................10
3-1. Models: ARYG18LHTBP, ARYG24LHTBP, and ARYG30LHTBP ...........................10
3-2. Models: ARYG36LHTBP, ARYG45LHTBP, and ARYG54LHTBP ...........................12
4. Dimensions ............................................................................................14
4-1. Models: ARYG18LHTBP, ARYG24LHTBP, and ARYG30LHTBP ...........................14
4-2. Models: ARYG36LHTBP, ARYG45LHTBP, and ARYG54LHTBP ...........................15
4-3. Installation space requirement .................................................................................15
4-4. Maintenance space requirement .............................................................................16
5. Wiring diagrams .....................................................................................18
5-1. Models: ARYG18LHTBP and ARYG24LHTBP ........................................................ 18
5-2. Models: ARYG30LHTBP, ARYG36LHTBP, ARYG45LHTBP, and ARYG54LHTBP 19
6. Capacity table ........................................................................................20
6-1. Cooling capacity ......................................................................................................20
6-2. Heating capacity ......................................................................................................23
7. Fan performance ....................................................................................25
7-1. Fan performance curve ............................................................................................25
7-2. Airflow ......................................................................................................................35
8. Operation noise (sound pressure) .......................................................41
8-1. Noise level curve .....................................................................................................41
8-2. Sound level check point ...........................................................................................44
9. Safety devices ........................................................................................45
10. External input and output .....................................................................46
10-1.External input ..........................................................................................................46
10-2.External output ........................................................................................................48
10-3.Combination of external input and output ...............................................................49
10-4.Details of function ...................................................................................................51
11. Function settings ...................................................................................57
11-1.Function settings on indoor unit ..............................................................................57
11-2.Function settings by using remote controller ..........................................................59
Page 4
CONTENTS (continued)
12. Wired remote controller (Touch panel) ................................................66
12-1.Remote controller address setting .......................................................................... 66
12-2.Remote controller master/slave setting .................................................................. 68
13. Optional parts ........................................................................................69
13-1.Controllers .............................................................................................................. 69
13-2.Others ..................................................................................................................... 70
Page 5
CONTENTS (continued)
Part 2. OUTDOOR UNIT ..................................................................71
1. Specifications ........................................................................................72
1-1. Models: AOYG18LBCA and AOYG24LBCA ............................................................72
1-2. Models: AOYG30LBTA and AOYG36LBTA ............................................................73
1-3. Models: AOYG45LBTA and AOYG54LBTA ............................................................74
2. Dimensions ............................................................................................75
2-1. Models: AOYG18LBCA and AOYG24LBCA ............................................................75
2-2. Models: AOYG30LBTA and AOYG36LBTA ............................................................76
2-3. Models: AOYG45LBTA and AOYG54LBTA ............................................................77
2-4. Installation space requirement .................................................................................78
3. Refrigerant circuit ..................................................................................87
3-1. Models: AOYG18LBCA and AOYG24LBCA ............................................................87
3-2. Models: AOYG30LBTA and AOYG36LBTA ............................................................88
3-3. Models: AOYG45LBTA and AOYG54LBTA ............................................................89
4. Wiring diagrams .....................................................................................90
4-1. Models: AOYG18LBCA and AOYG24LBCA ............................................................90
4-2. Model: AOYG30LBTA ..............................................................................................91
4-3. Model: AOYG36LBTA ..............................................................................................92
4-4. Models: AOYG45LBTA and AOYG54LBTA ............................................................93
5. Capacity compensation rate for pipe length and height difference ..94
5-1. Models: AOYG18LBCA and AOYG24LBCA ............................................................94
5-2. Model: AOYG30LBTA ..............................................................................................95
5-3. Model: AOYG36LBTA ..............................................................................................96
5-4. Models: AOYG45LBTA and AOYG54LBTA ............................................................97
6. Additional charge calculation ...............................................................98
6-1. Models: AOYG18LBCA and AOYG24LBCA ............................................................98
6-2. Models: AOYG30LBTA and AOYG36LBTA ............................................................98
6-3. Models: AOYG45LBTA and AOYG54LBTA ............................................................98
7. Airflow .....................................................................................................99
7-1. Model: AOYG18LBCA .............................................................................................99
7-2. Model: AOYG24LBCA .............................................................................................99
7-3. Model: AOYG30LBTA ..............................................................................................99
7-4. Model: AOYG36LBTA ............................................................................................100
7-5. Model: AOYG45LBTA ............................................................................................100
7-6. Model: AOYG54LBTA ............................................................................................100
8. Operation noise (sound pressure) .....................................................101
8-1. Noise level curve ...................................................................................................101
8-2. Sound level check point .........................................................................................104
9. Electrical characteristics ....................................................................105
10. Safety devices ......................................................................................106
Page 6
CONTENTS (continued)
11. External input and output (AOYG45LBTA and AOYG54LBTA) .......109
11-1.External input ........................................................................................................ 109
11-2.External output ..................................................................................................... 111
12. Function settings ................................................................................. 113
12-1.Local setting switch buttons .................................................................................. 113
12-2.Local setting procedure ........................................................................................ 115
13. Optional parts ......................................................................................118
Page 7
Part 1. INDOOR UNIT
DUCT TYPE: ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP
Page 8
- 2 -
DUCT TYPE
ARYG18-54LHTBP
1. Product features
Implemented core technology provides easy-to-use product operations that realize a comfortable space.
1-1. Model lineup
1-2. Features
Automatic Airflow adjustment function
This unique and innovative function detects required air flow in each application case and auto­matically adjust the volume.
Improved installation flexibility
• The static pressure can be adjustable ranging from 30Pa to 200Pa in accordance with the desired applications.
• The built-in drain pump with lifting height up to 850 mm.
• The standardized depth and height in the unit dimensions are helpful in capacity selections for various ceiling spaces.
ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP
ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP
AOYG18LBCA AOYG24LBCA
AOYG30LBTA AOYG36LBTA
AOYG45LBTA AOYG54LBTA
Long duct with dumper
Short duct
200 Pa30 Pa
Drain hose is standard accessory
850 mm
Max.
(18/24/30)
1000mm
(36/45/54)
1400mm
300
mm
700mm
Page 9
- 3 -
DUCT TYPE
ARYG18-54LHTBP
High Efficiency and Energy Saving
The combination of the V-shaped heat exchanger, air stabiliser, and the high efficient DC fan motor allowed high efficiency despite of the small structual design.
Quiet operation
The low noise level is implemented by the equipment of the air stabilizer which equalises the air flow speed and the air flow volume passing through the heat exchanger.
Easy operation by touch panel controller
• Large LCD display
• Background light
• Built in thermo sensor
• Display room temperarture
• Set temperature limitation (High and Low)
• Weekly Timer , Set back Timer, Auto off timer
• Support 12 Languages
Improved service and maintenance
• Drain pump is easily detachable from the side
• Easy access to electrical box
• Error code can be checked more in detail from error history
V-shape h eat exchanger
Ecient airow design
High eci ent DC fan motor
Lower power consumption
At heating rated point
Air Stabilizer
Noise Level
33
dB(A)
ARYG18LHTBP
Page 10
- 4 -
DUCT TYPE
ARYG18-54LHTBP
2. Wired remote controller
2-1. Features
High performance and compact size
In addition to the individual control, various energy saving controls can be realized using 1 re­mote controller only.
Accurate and comfortable control
Indoor temperature can be detected accurately by the room temperature sensor built in the wired remote controller.
Various energy saving control
Auto-off timer
– The indoor unit automatically turns off after the set time has passed. – The time interval for which auto-off works can be set.
• Easy finger touch operation with LCD panel
• Built-in weekly/daily timer (on/off, temperature and mode)
• The backlit LCD enables easy operation in a dark room.
• Room temperature display
• Control up to 16 indoor units
• Corresponds to 12 different languages (English, Chinese French, German, Spanish, Russian, Polish, Italian, Portu­guese, Greek, Turkish, and Dutch)
Individual
control
Thermo
sensor
Weekly
timer
Auto off
timer
Room temperature sensor Room temperature display
Set interval time hour (17:00 to 24:00)
Set off time
(30 to 240 minutes)
17 4200 :00
On Auto-off
Off
Example: At interval time hour (17:00 to 24:00) to prevent forgetting to turn off.
Page 11
- 5 -
DUCT TYPE
ARYG18-54LHTBP
2 schedules weekly timer – 2 schedules such as for the summer and winter can be set. – 8 setting changeable per day of week (Setting items: on/off, temperature, mode, and time)
Set temperature auto return – The setting temperature automatically returns to the previous setting temperature. – The time range in which the set temperature can be changed is 10 to 120 minutes.
Set temperature upper and lower limit setting
The set temperature range can be set for each operation mode (COOL, HEAT, and AUTO).
Schedule 1 (Summer schedule) Schedule 2 (Winter schedule)
26 °C
24 °C
On
8:40 11:40 17:30 20:40
Off Off Off Off
Time
25 °C
23 °C
On
Setting temp.
Setting temp.
Setting example:
8:40 10:00 17:3015:30 20:40
Time
Setting temp.
Setting temp.
Cooling operation
24 °C
22 °C
Set temperature change Auto return
11:40 13:40
Time
Settable time range
10 to 120 minutes
Heating operation
25 °C
23 °C
Set temperature change Auto return
11:40 13:40
Time
Settable time range
10 to 120 minutes
Original temp.
setting range
Lower limit
setting
During cooling
30 °C
25 °C
18 °C
Original temp.
setting range
Upper limit
setting
During heating
30 °C
25 °C
16 °C
Page 12
- 6 -
DUCT TYPE
ARYG18-54LHTBP
Various convenient functions
Displays setting status and limitations
Summer time display
Child safety lock
Simplified installation
Easy maintenance
The remote controller settings can be easily checked.
Can be set easily from “Menu” screen.
Lock/unlock procedure: While touching the blank field on “Monitor” screen, push the on/off button for 4 seconds.
Use of non-polar 2-wire type
Faulty wiring can be prevented by using non-polar 2-wire.
Error history display
• Errors occur on the indoor unit or the remote controller are saved as a history.
• Maximum of 32-error incidents can be saved.
• Under Maintenance
• Forced Stop
• Mode Mismatch
Previous Page
Status
R.C. Prohibition
Special State
Page 2/ 4
Monitor
Next Page
• Op. Controlled
• Set Temp. Limited
• Energy Saving Operation
• Defrost
• Oil Recovery
Status
Special Srate
Page 3/ 4
Monitor
Previous Page
Next Page
• Human Sensor Setting
• Fan Control for Energy Saving
Status
Special Srate
Page 4/ 4
Monitor
Previous Page
Status
Air Flow Direction
VT
Off
1
Economy
Individual
Page 1/ 4
Monitor
Next Page
OK OK
non-polar 2-wire
Y1
Y2
Y1
Y2
I.U. I.U.
Y1Y2Y3 Y1Y2Y3
Page 13
- 7 -
DUCT TYPE
ARYG18-54LHTBP
Backlit LCD
System diagram
Multiple installation method described above is prohibited to combine with 2-wired type and 3­wired type.
Group control
With a single remote controller, up to 16 units can be simultaneously operated.
A, B, C, D, E : Remote controller cable. (Refer to Chapter 2-4. "Wiring specifications" on page 9.) A+B+C+D+E 500 m.
!
CAUTION
Group control is only possible between units with remote controllers of the same type. After confirming that the connected remote controllers have same model name by checking
the rear side of the remote controller or “Chapter 13-1. "Controllers" on page 69”, perform the group control.
• The backlit LCD enables easy operation in a dark room.
• Backlighting time can be selected from 30 or 60 seconds.
• The backlight is lit while the buttons are operated, and goes off 30 or 60 seconds after the operation stops.
1 remote controller 2 remote controllers
A, B, C: Remote controller cable
A 500 m; B+C 500 m
A
Indoor unit
Remote controller
Master
Slave
BC
Indoor unit
Remote controllers
A
BCDE
I.U. I.U. I.U. I.U.
Master
I.U.: Indoor Unit
Page 14
- 8 -
DUCT TYPE
ARYG18-54LHTBP
2-2. Overview
Display panel
a Remote temperature sensor (inside)
b On/off button
Operable only while displaying the “Monitor mode” screen.
c LED lamp (operation indicator)
d Touch panel display
e Set temperature
Operating temperature can be set.
f Remote controller group name
g Mode
Operation mode can be set.
h Status icons
i Clock
j Fan
Fan speed can be set.
k Room temperature
l Menu
Various settings can be set.
m Status
Status of the indoor unit and error can be checked.
NOTE: Functions may differ by type of the indoor unit.
For details, refer to the operation manual.
abcd
26.0
26.0
°C
°C
Cool
Auto
Office 01
Set Temp.
26.0°C
26.0°C
Mode
MenuStatus
Fan
Fri 10:00AM
Room Temp.
e
f
h
h
g
h
i
j
l
m
k
Page 15
- 9 -
DUCT TYPE
ARYG18-54LHTBP
2-3. Specifications
Dimensions and other specifications on the wired remote controller are as follows.
2-4. Wiring specifications
NOTE: Use shielded cable (locally purchased) in accordance with the regional cable standard.
Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) mm 120 × 120 × 20.4 Weight g 220 Input voltage V DC 12 Power consumption W Max. 0.3 Usage temperature range °C 0 to 40 Usage humidity range % 20 to 90 (no condensation) Storage temperature range °C -10 to 60 Storage humidity range % 20 to 90 (no condensation)
Use Cable size Wire type Remarks
Remote controller cable
0.33 to 1.25 mm
2
Non-polar 2-core Use sheathed PVC cable.
20.4120
120
[Unit:mm]
Page 16
- 10 -
DUCT TYPE
ARYG18-54LHTBP
3. Specifications
3-1. Models: ARYG18LHTBP, ARYG24LHTBP, and
ARYG30LHTBP
Typ e
Duct
Inverter heat pump
Model name
ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 5.2 6.8 8.5
Btu/h 17,700 23,200 29,000
Min.—Max.
kW 0.9 — 6.5 0.9 — 8.0 2.8—10.0
Btu/h 3,100 — 22,200 3,100 — 27,300 9,500 - 34,100
Heating
Rated
kW 6.0 8.0 10.0
Btu/h 20,500 27,300 34,100
Min.—Max.
kW 0.9 — 8.0 0.9 — 9.1 2.7—11.2
Btu/h 3,100 — 27,300 3,100 - 31,000 9,200 - 38,200
Input power
Cooling
Rated
kW
1.37 1.95 2.65
Max. 2.25 3.19 4.05
Heating
Rated 1.48 2.21 2.70
Max. 3.16 4.40 4.06
Fan
HIGH
W
50 70 150
MED 30 40 100
LOW 202575
QUIET 15 15 65
Current
Cooling
Rated A
6.1 8.6 11.6
Heating 6.6 9.7 11.8
Power factor
Cooling
%
97.6 98.6 99.3
Heating 97.5 99.1 99.5
EER Cooling
kW/kW
3.80 3.49 3.21
COP Heat ing 4.05 3.62 3.70
Moisture removal L/h (pints/h) 1.2 (2.1) 1.8 (3.2) 2.3 (4.0)
Maximum operating current *1
Cooling
A
10.0 13.5 17.0
Heating 13.5 18.5 17.0
Fan
Airflow rate
Cooling
HIGH
m3/h
1,050 1,360 1,700
MED 840 1,080 1,360
LOW 740 880 1,190
QUIET 630 680 1,070
Heating
HIGH 1,050 1,360 1,700
MED 840 1,080 1,360
LOW 740 880 1,190
QUIET 630 680 1,070
Type × Q'ty Sirocco fan × 2
Motor output W 197 375
Static pressure range Pa 30 to 200
Sound pressure level *2
Cooling
HIGH
dB(A)
28 32 36
MED 252833
LOW 222430
QUIET 20 21 29
Heating
HIGH 28 32 36
MED 252833
LOW 222430
QUIET 20 21 29
Sound power level
Cooling
dB(A)
54 57 63
Heating 545765
Heat exchanger type
Dimensions (H × W × D)
mm
420 × 758 × 39.9
Fin pitch 1.4
Rows × Stages 3 × 20
Pipe type Copper
Fin type
Aluminum
Hydrophilic coating
Enclosure
Material Stee l
Color
Dimensions (H × W × D)
Net
mm
300 × 1,000 × 700
Gross 400 × 1,238 × 875
Weight
Net
kg
36
Gross 43 44
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4) Ø 6.35 (Ø 1/4) Ø 9.52 (Ø 3/8)
Gas Ø 12.7 (Ø 1/2) Ø 15.88 (Ø 5/8) Ø 15.88 (Ø 5/8)
Method Flare
Drain hose
Material PVC
Size mm Ø 25 (I.D.), Ø 32 (O.D.) (VP25)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Page 17
- 11 -
DUCT TYPE
ARYG18-54LHTBP
Remote controller type Wired
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.), Standard static pressure; 18 type and 24 type: 35Pa, 30 type: 47Pa
Protective function might work when using it outside the operation range.*1: Maximum current:
– The maximum value when operated within the operation range. – The total current of indoor unit and outdoor unit.
*2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Model name
ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP
Energy efficiency class
Cooling
A
++
A
++
A
+
Heating (Average)
A
+
A
+
A
+
Pdesign
Cooling
kW
5.2 (35°C) 6.8 (35°C) 8.5 (35°C)
Heating (Average) 4.3 (-10°C) 6.0 (-10°C) 8.0 (-10°C)
SEER Cooling
kWh/
kWh
7.15 6.50 5.95
SCOP Heating (Average) 4.11 4.01 3.95
Annual energy consumption
QCE
kWh/a
255 366 500
QHE (Average) 1 ,462 2,092 2,833
Sound power level
Cooling
HIGH dB(A)
54 57 63
Heating 54 57 65
Typ e
Duct
Inverter heat pump
Model name
ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP
Page 18
- 12 -
DUCT TYPE
ARYG18-54LHTBP
3-2. Models: ARYG36LHTBP, ARYG45LHTBP, and
ARYG54LHTBP
Typ e
Duct
Inverter heat pump
Model name
ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 9.4 12.1 13.4
Btu/h 32,100 41,300 45,700
Min.—Max.
kW 2.8—11.2 4.0—14.0 4.5 - 14.5
Btu/h 9,500 - 38,200 13,700 - 47,800 15,400 - 49,500
Heating
Rated
kW 11.2 13.3 16.0
Btu/h 38,200 45,300 54,600
Min.—Max.
kW 2.7—12.7 4.2—16.2 4.7 - 16.5
Btu/h 9,200 - 43,300 14,300 - 55,300 16,000 - 56,300
Input power
Cooling
Rated
kW
2.83 3.59 4.42
Max. 4.76 5.37 5.59
Heating
Rated 3.07 3.44 4.62
Max. 4.78 5.35 5.61
Fan
HIGH
W
150 225 225
MED 90 135 135
LOW 60 90 90
QUIET 45 70 70
Current
Cooling
Rated A
12.4 15.7 19.4
Heating 13.4 15.1 20.2
Power factor
Cooling
%
99.2 99.4 99.1
Heating 99.6 99.0 99.4
EER Cooling
kW/kW
3.32 3.37 3.03
COP Heating 3.65 3. 87 3.46
Moisture removal L/h (pints/h) 2.0 (3.52) 2.6 (4.6) 3.7 (6.5)
Maximum operating current *1
Cooling
A
20.0 22.5 23.5
Heating 20.0 22.5 23.5
Fan
Airflow rate
Cooling
HIGH
m3/h
2,050 2,550 2,550
MED 1,640 2,040 2,040
LOW 1,330 1,650 1,650
QUIET 1,070 1,430 1,430
Heating
HIGH 1,850 2,550 2,550
MED 1,640 2,040 2,040
LOW 1,330 1,650 1,650
QUIET 1,070 1,430 1,430
Type × Q'ty Sirocco fan × 3
Motor output W 375
Static pressure range Pa 30 to 200
Sound pressure level *2
Cooling
HIGH
dB(A)
36 39 39
MED 31 35 35
LOW 28 31 31
QUIET 26 29 29
Heating
HIGH 33 39 39
MED 31 35 35
LOW 28 31 31
QUIET 26 29 29
Sound power level
Cooling
dB(A)
64 67 67
Heating 63 69 69
Heat exchanger type
Dimensions (H × W × D)
mm
420 × 1,158 × 39.9
Fin pitch 1.4
Rows × Stages 3 × 20
Pipe type Copper
Fin type
Aluminum
Hydrophilic coating
Enclosure
Material Steel
Color
Dimensions (H × W × D)
Net
mm
300 × 1,400 × 700
Gross 400 × 1,638 × 875
Weight
Net
kg
46
Gross 55
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Drain hose
Material PVC
Size mm Ø 25 (I.D.), Ø 32 (O.D.) (VP25)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Page 19
- 13 -
DUCT TYPE
ARYG18-54LHTBP
Remote controller type Wired
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.), Standard static pressure; 36 type: 47Pa, 45 type and 54 type: 60Pa
Protective function might work when using it outside the operation range.*1: Maximum current:
– The maximum value when operated within the operation range. – The total current of indoor unit and outdoor unit.
*2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Model name
ARYG36LHTBP
Energy efficiency class
Cooling
A
+
Heating (Average) A
Pdesign
Cooling
kW
9.4 (35°C)
Heating (Average) 8.7 (-10°C)
SEER Cooling
kWh/kWh
5.81
SCOP Heating (Average) 3.81
Annual energy consumption
QCE
kWh/a
566
QHE (Average) 3,194
Sound power level
Cooling
HIGH dB(A)
64
Heating 63
Typ e
Duct
Inverter heat pump
Model name
ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP
Page 20
- 14 -
DUCT TYPE
ARYG18-54LHTBP
4. Dimensions
4-1. Models: ARYG18LHTBP, ARYG24LHTBP, and
ARYG30LHTBP
Unit: mm
Air
Gas pipe
Drain port
Control box
Liquid pipe
Side view (L)
Side view (R)
Top view
Front view
Rear view
Page 21
- 15 -
DUCT TYPE
ARYG18-54LHTBP
4-2. Models: ARYG36LHTBP, ARYG45LHTBP, and
ARYG54LHTBP
4-3. Installation space requirement
Provide sufficient installation space for product safety.
Models: ARYG18LHTBP, ARYG24LHTBP, ARYG30LHTBP,
ARYG36LHTBP, ARYG45LHTBP, and ARYG54LHTBP
Unit: mm
Gas pipe
Drain port
Control box
Liquid pipe
Air
Side view (L)
Side view (R)
Top view
Front view
Rear view
Floor
300 or more
150 or
more
20 or more
2500 or more
(When no ceiling)
20 or more
Unit: mm
Page 22
- 16 -
DUCT TYPE
ARYG18-54LHTBP
4-4. Maintenance space requirement
For future maintenance and service access, provide sufficient maintenance space.
NOTE: Do not place any wiring or illumination in the maintenance space, as they will impede
service.
Models: ARYG18LHTBP, ARYG24LHTBP, and ARYG30LHTBP
• Provide a service access for maintenance purposes.
• The service access necessary for fan units and filter maintenance.
Bottom view
AIR
Unit: mm
Control box
300 or more
500 or more
500 or more
Service access
AIR
Service access
Fan unit side
300 or more
500 or more
1400 or more
100
Bottom view
Unit: mm
Page 23
- 17 -
DUCT TYPE
ARYG18-54LHTBP
Models: ARYG36LHTBP, ARYG45LHTBP, and ARYG54LHTBP
• Provide a service access for maintenance purposes.
• The service access necessary for fan units and filter maintenance.
300 or more
500 or more
Service access
500 or more
Control box
AIR
Bottom view
Unit: mm
AIR
300 or more
Service access
1800 or more
100
500 or more
Fan unit side
Bottom view
Unit: mm
Page 24
- 18 -
DUCT TYPE
ARYG18-54LHTBP
5. Wiring diagrams
5-1. Models: ARYG18LHTBP and ARYG24LHTBP
Page 25
- 19 -
DUCT TYPE
ARYG18-54LHTBP
5-2. Models: ARYG30LHTBP, ARYG36LHTBP, ARYG45LHTBP,
and ARYG54LHTBP
Page 26
- 20 -
DUCT TYPE
ARYG18-54LHTBP
6. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
6-1. Cooling capacity
Model: ARYG18LHTBP
Model: ARYG24LHTBP
AFR
m3/h
1,050
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 3.77 2.98 0.25 4.20 3.00 0.26 4.34 3.26 0.26 4.63 3.27 0.26 4.76 3.54 0.26 5.05 3.52 0.27 5.34 3.75 0.27
-10 3.65 2.93 0.31 4.07 2.95 0.32 4.21 3.20 0.32 4.49 3.21 0.32 4.62 3.47 0.32 4.90 3.45 0.33 5.18 3.68 0.33
0 3.59 2.90 0.34 4.00 2.92 0.35 4.14 3.17 0.35 4.41 3.18 0.35 4.55 3.44 0.35 4.82 3.42 0.36 5.09 3.64 0.36
5 3.47 2.85 0.41 3.86 2.86 0.42 4.00 3.11 0.42 4.26 3.12 0.42 4.39 3.37 0.43 4.65 3.35 0.43 4.92 3.58 0.43
10 3.33 2.78 0.48 3.71 2.79 0.49 3.84 3.04 0.49 4.09 3.04 0.50 4.22 3.29 0.50 4.47 3.28 0.50 4.73 3.49 0.51
15 3.41 2.81 0.40 3.80 2.83 0.41 3.93 3.08 0.41 4.19 3.09 0.41 4.32 3.33 0.41 4.58 3.32 0.42 4.84 3.54 0.42
20 4.41 3.30 0.84 4.91 3.32 0.86 5.08 3.61 0.86 5.41 3.63 0.87 5.58 3.92 0.87 5.91 3.90 0.88 6.25 4.15 0.89
25 4.19 3.19 0.95 4.67 3.21 0.96 4.83 3.49 0.97 5.15 3.51 0.98 5.30 3.78 0.98 5.62 3.77 0.99 5.94 4.02 1.00
30 3.97 3.09 1.05 4.42 3.11 1.07 4.57 3.37 1.07 4.88 3.39 1.08 5.02 3.66 1.09 5.32 3.64 1.10 5.62 3.88 1.11
35 4.11 3.16 1.32 4.58 3.18 1.34 4.73 3.45 1.35 5.04 3.46 1.36 5.20 3.74 1.37 5.51 3.73 1.39 5.82 3.97 1.40
40 3.33 2.78 1.07 3.71 2.80 1.09 3.84 3.04 1.09 4.10 3.04 1.10 4.22 3.29 1.11 4.47 3.28 1.12 4.73 3.49 1.13
46 2.38 2.31 0.82 2.65 2.35 0.83 2.74 2.55 0.83 2.93 2.55 0.84 3.02 2.76 0.84 3.19 2.75 0.85 3.37 2.93 0.86
AFR
m
3
/h
1,360
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 4.92 4.28 0.36 5.49 4.31 0.37 5.67 4.68 0.37 6.05 4.70 0.37 6.23 5.08 0.37 6.61 5.05 0.38 6.98 5.39 0.38
-10 4.78 4.20 0.45 5.32 4.23 0.45 5.50 4.60 0.46 5.87 4.61 0.46 6.04 4.99 0.46 6.41 4.96 0.47 6.77 5.29 0.48
0 4.70 4.17 0.48 5.24 4.19 0.49 5.41 4.55 0.49 5.77 4.57 0.50 5.95 4.93 0.50 6.31 4.91 0.51 6.66 5.23 0.51
5 4.54 4.09 0.59 5.05 4.10 0.60 5.23 4.47 0.60 5.57 4.48 0.60 5.74 4.84 0.61 6.09 4.81 0.61 6.43 5.13 0.62
10 4.36 3.99 0.68 4.85 4.00 0.69 5.02 4.36 0.70 5.35 4.37 0.71 5.52 4.72 0.71 5.85 4.71 0.71 6.18 5.01 0.72
15 4.46 4.04 0.57 4.97 4.07 0.58 5.14 4.42 0.58 5.48 4.43 0.59 5.65 4.79 0.59 5.99 4.77 0.60 6.33 5.08 0.60
20 5.76 4.74 1.20 6.42 4.77 1.22 6.64 5.19 1.23 7.07 5.21 1.24 7.29 5.62 1.24 7.73 5.60 1.26 8.17 5.96 1.27
25 5.48 4.59 1.35 6.10 4.61 1.37 6.32 5.02 1.38 6.73 5.03 1.39 6.94 5.43 1.40 7.35 5.42 1.41 7.77 5.77 1.42
30 5.19 4.43 1.50 5.78 4.46 1.52 5.98 4.84 1.53 6.38 4.86 1.54 6.57 5.25 1.55 6.96 5.22 1.56 7.35 5.57 1.58
35 5.37 4.53 1.88 5.98 4.56 1.91 6.19 4.96 1.92 6.60 4.97 1.94 6.80 5.37 1.95 7.21 5.35 1.97 7.62 5.70 1.99
40 4.36 3.99 1.53 4.85 4.01 1.55 5.02 4.36 1.56 5.36 4.37 1.57 5.52 4.72 1.58 5.85 4.71 1.59 6.18 5.02 1.61
46 3.11 3.32 1.16 3.47 3.37 1.18 3.59 3.66 1.18 3.83 3.67 1.19 3.94 3.97 1.20 4.17 3.95 1.21 4.41 4.20 1.22
Page 27
- 21 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG30LHTBP
Model: ARYG36LHTBP
Model: ARYG45LHTBP
AFR
m3/h
1,700
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 7.33 6.23 1.12 8.16 6.27 1.13 8.44 6.81 1.14 8.99 6.84 1.16 9.27 7.38 1.16 9.83 7.35 1.17 10.39 7.83 1.18
-10 7.21 6.00 1.41 8.02 6.03 1.43 8.30 6.57 1.43 8.85 6.58 1.45 9.12 7.12 1.46 9.66 7.08 1.47 10.22 7.54 1.49
0 6.87 5.95 1.78 7.65 5.98 1.81 7.91 6.51 1.82 8.43 6.53 1.84 8.69 7.05 1.84 9.21 7.02 1.87 9.73 7.48 1.88
5 6.78 5.81 1.79 7.56 5.84 1.82 7.81 6.35 1.83 8.33 6.37 1.85 8.59 6.88 1.86 9.10 6.85 1.87 9.61 7.30 1.90
10 6.75 5.89 1.81 7.51 5.93 1.84 7.77 6.45 1.84 8.29 6.47 1.86 8.54 6.98 1.87 9.05 6.96 1.89 9.56 7.41 1.91
15 7.34 6.10 1.98 8.17 6.15 2.02 8.45 6.68 2.03 9.01 6.71 2.05 9.28 7.24 2.06 9.84 7.21 2.08 10.40 7.68 2.10
20 8.19 6.40 2.36 9.13 6.44 2.40 9.44 6.99 2.42 10.06 7.02 2.44 10.38 7.58 2.45 11.00 7.55 2.47 11.62 8.04 2.50
25 8.05 6.41 2.55 8.97 6.45 2.58 9.27 7.01 2.60 9.89 7.04 2.62 10.19 7.60 2.64 10.80 7.57 2.66 11.42 8.06 2.69
30 7.46 6.25 2.58 8.31 6.29 2.63 8.59 6.84 2.64 9.16 6.85 2.66 9.44 7.40 2.68 10.01 7.38 2.71 10.58 7.86 2.73
35 6.72 5.81 2.56 7.48 5.84 2.60 7.74 6.35 2.61 8.25 6.37 2.64 8.50 6.88 2.65 9.01 6.85 2.68 9.52 7.30 2.71
40 5.10 4.83 2.23 5.68 4.87 2.25 5.87 5.28 2.27 6.26 5.30 2.29 6.46 5.73 2.31 6.84 5.70 2.33 7.23 6.08 2.35
46 4.56 4.17 2.20 5.07 4.20 2.23 5.24 4.56 2.24 5.59 4.58 2.26 5.76 4.94 2.28 6.11 4.92 2.30 6.45 5.24 2.32
AFR
m
3
/h
2,050
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 7.30 6.42 1.00 8.14 6.45 1.01 8.42 7.02 1.02 8.97 7.03 1.02 9.25 7.60 1.03 9.80 7.57 1.04 10.36 8.06 1.05
-10 7.18 6.27 1.23 8.00 6.31 1.25 8.27 6.86 1.26 8.81 6.89 1.27 9.09 7.43 1.28 9.64 7.40 1.29 10.18 7.88 1.30
0 6.78 6.30 1.56 7.55 6.33 1.58 7.81 6.89 1.59 8.33 6.90 1.60 8.59 7.46 1.61 9.11 7.43 1.63 9.62 7.91 1.65
5 6.77 6.20 1.58 7.55 6.24 1.60 7.80 6.78 1.61 8.31 6.80 1.63 8.57 7.35 1.63 9.08 7.32 1.65 9.60 7.80 1.67
10 6.74 6.31 1.58 7.50 6.34 1.61 7.76 6.90 1.62 8.27 6.92 1.63 8.53 7.48 1.64 9.04 7.44 1.65 9.55 7.93 1.67
15 7.24 6.46 1.74 8.07 6.50 1.76 8.34 7.06 1.77 8.90 7.09 1.79 9.17 7.65 1.80 9.72 7.62 1.82 10.27 8.12 1.84
20 8.14 6.79 2.07 9.07 6.83 2.10 9.37 7.43 2.11 10.00 7.45 2.13 10.31 8.05 2.14 10.93 8.02 2.16 11.54 8.54 2.18
25 8.02 6.81 2.29 8.93 6.85 2.32 9.23 7.45 2.33 9.84 7.48 2.36 10.15 8.07 2.37 10.75 8.04 2.39 11.36 8.56 2.42
30 7.84 6.75 2.72 8.74 6.78 2.76 9.03 7.38 2.77 9.63 7.40 2.80 9.93 7.99 2.82 10.52 7.96 2.84 11.12 8.48 2.87
35 7.43 6.66 2.73 8.28 6.70 2.77 8.55 7.29 2.79 9.11 7.31 2.82 9.40 7.90 2.83 9.96 7.86 2.86 10.52 8.38 2.89
40 5.51 5.01 2.12 6.14 5.04 2.15 6.35 5.48 2.16 6.76 5.49 2.18 6.97 5.93 2.19 7.39 5.91 2.21 7.81 6.30 2.24
46 4.95 4.87 2.04 5.51 4.90 2.07 5.70 5.33 2.07 6.08 5.34 2.09 6.26 5.77 2.11 6.64 5.75 2.12 7.02 6.12 2.15
AFR
m
3
/h
2,550
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 10.22 8.77 2.08 11.37 8.83 2.11 11.76 9.59 2.13 12.54 9.62 2.14 12.93 10.39 2.16 13.70 10.35 2.18 14.47 11.03 2.20
-10 10.30 8.91 2.00 11.47 8.96 2.03 11.86 9.74 2.04 12.65 9.78 2.06 13.04 10.56 2.07 13.82 10.51 2.10 14.60 11.20 2.11
0 10.47 9.02 1.82 11.67 9.08 1.85 12.06 9.87 1.85 12.86 9.90 1.88 13.26 10.69 1.88 14.06 10.65 1.90 14.85 11.34 1.92
5 10.24 8.91 1.88 11.41 8.96 1.91 11.80 9.74 1.92 12.58 9.77 1.93 12.96 10.55 1.95 13.75 10.51 1.96 14.52 11.19 1.98
10 10.01 8.71 2.03 11.14 8.76 2.06 11.53 9.53 2.06 12.28 9.56 2.09 12.66 10.32 2.10 13.42 10.28 2.12 14.18 10.95 2.14
15 9.76 8.64 2.17 10.87 8.69 2.21 11.24 9.45 2.22 11.99 9.48 2.24 12.35 10.24 2.25 13.10 10.20 2.28 13.84 10.86 2.30
20 10.11 8.69 2.54 11.25 8.74 2.58 11.64 9.50 2.59 12.41 9.54 2.62 12.79 10.30 2.64 13.56 10.25 2.66 14.32 10.92 2.68
25 9.96 8.64 2.70 11.09 8.69 2.75 11.47 9.45 2.76 12.23 9.48 2.78 12.61 10.23 2.80 13.36 10.19 2.83 14.12 10.86 2.85
30 9.82 8.60 3.46 10.94 8.65 3.52 11.31 9.40 3.54 12.05 9.43 3.57 12.43 10.18 3.59 13.17 10.14 3.59 13.91 10.80 3.59
35 9.56 8.48 3.46 10.64 8.53 3.52 11.01 9.27 3.54 11.74 9.30 3.57 12.10 10.04 3.59 12.83 10.00 3.59 13.56 10.65 3.59
40 6.99 6.87 2.80 7.79 7.03 2.84 8.06 7.65 2.86 8.58 7.67 2.89 8.85 8.29 2.90 9.38 8.25 2.90 9.91 8.79 2.90
46 5.36 5.35 2.32 5.98 5.57 2.36 6.18 6.06 2.37 6.58 6.08 2.39 6.79 6.57 2.41 7.20 6.54 2.41 7.61 6.97 2.41
Page 28
- 22 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG54LHTBP
AFR
m3/h
2,550
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-15 12.48 10.05 2.84 13.91 10.12 2.89 14.38 11.00 2.90 15.32 11.03 2.93 15.80 11.91 2.94 16.75 11.86 2.97 17.70 12.64 3.00
-10 12.47 10.04 2.85 13.89 10.10 2.89 14.37 10.98 2.90 15.31 11.02 2.93 15.78 11.90 2.95 16.73 11.85 2.97 17.68 12.63 3.00
0 12.47 10.06 2.86 13.89 10.12 2.91 14.36 11.00 2.92 15.30 11.04 2.95 15.78 11.92 2.96 16.73 11.87 2.99 17.68 12.65 3.03
5 12.37 10.08 3.25 13.77 10.14 3.30 14.24 11.02 3.31 15.18 11.06 3.35 15.65 11.94 3.36 16.59 11.90 3.40 17.53 12.67 3.44
10 12.14 9.95 3.39 13.52 10.01 3.46 13.98 10.88 3.47 14.90 10.92 3.51 15.36 11.79 3.53 16.29 11.74 3.56 17.21 12.51 3.59
15 11.92 9.79 3.65 13.27 9.86 3.71 13.73 10.71 3.72 14.63 10.75 3.76 15.08 11.60 3.78 15.98 11.56 3.83 16.89 12.31 3.86
20 11.79 9.79 3.43 13.13 9.86 3.48 13.58 10.71 3.50 14.47 10.75 3.53 14.92 11.60 3.55 15.82 11.56 3.58 16.71 12.31 3.62
25 11.69 9.67 3.66 13.02 9.73 3.72 13.46 10.57 3.74 14.35 10.61 3.77 14.79 11.46 3.79 15.68 11.41 3.84 16.57 12.16 3.87
30 11.19 9.48 4.19 12.47 9.58 4.27 12.89 10.42 4.29 13.74 10.45 4.33 14.17 11.28 4.35 15.02 11.24 4.39 15.87 11.98 4.44
35 10.59 8.79 4.27 11.79 8.99 4.33 12.19 9.77 4.36 13.00 9.81 4.40 13.40 10.59 4.42 14.20 10.55 4.46 15.01 11.23 4.51
40 8.85 7.53 4.51 9.85 7.71 4.58 10.19 8.38 4.61 10.86 8.41 4.65 11.20 9.08 4.67 11.87 9.04 4.72 12.54 9.63 4.76
46 6.15 5.24 3.38 6.85 5.63 3.42 7.08 5.97 3.44 7.55 6.14 3.48 7.78 6.63 3.50 8.24 6.61 3.53 8.72 7.03 3.57
Page 29
- 23 -
DUCT TYPE
ARYG18-54LHTBP
6-2. Heating capacity
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Model: ARYG18LHTBP
Model: ARYG24LHTBP
Model: ARYG30LHTBP
AFR
m3/h
1,360
Indoor temperature
°CDB 16 18 20 22 27
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 5.17 1.96 5.04 2.00 4.92 2.04 4.80 2.09 4.67 2.12
-10 -11 5.85 2.11 5.71 2.16 5.57 2.21 5.44 2.25 5.30 2.29
-5 -7 6.54 2.22 6.39 2.26 6.23 2.31 6.07 2.36 5.92 2.41
0 -2 7.25 2.17 7.08 2.22 6.9 1 2.26 6.73 2.31 6.56 2.36
5 3 8.01 2.19 7.82 2.24 7.63 2.28 7.44 2.33 7.25 2.38
7 6 7.88 1.89 7.69 1.93 7.50 1.97 7.31 2.01 7.13 2.05
10 8 8.12 1.89 7.93 1.94 7.7 3 1.98 7.54 2.01 7.34 2.0 6
15 10 7.44 1.52 7.27 1.54 7.09 1.58 6.91 1.61 6.73 1.64
20 15 6.83 1.17 6.67 1.20 6.51 1.22 6.35 1.25 6.18 1.27
24 18 7.07 1.17 6.91 1.20 6.73 1.22 6.57 1.25 6.40 1.27
AFR
m3/h
1,360
Indoor temperature
°CDB 16 18 20 22 27
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 6.27 2.56 6.12 2.62 5.97 2.68 5.82 2.73 5.67 2.78
-10 -11 7.10 2.77 6.93 2.83 6.76 2.89 6.60 2.95 6.43 3.00
-5 -7 7.94 2.91 7.75 2.97 7.56 3.03 7.37 3.09 7.18 3.15
0 -2 8.80 2.84 8.59 2.91 8.3 8 2.97 8.17 3.03 7.96 3.0 9
5 3 9.72 2.87 9.49 2.93 9.26 2.99 9.03 3.05 8.80 3.11
7 6 9.56 2.48 9.33 2.53 9.10 2.58 8.87 2.64 8.65 2.69
10 8 9.85 2.48 9.62 2.54 9.3 8 2.59 9.15 2.64 8.91 2.7 0
15 10 9.03 1.99 8.82 2.02 8.60 2.07 8.39 2.11 8.17 2.15
20 15 8.29 1.54 8.09 1.58 7.90 1.60 7.70 1.64 7.50 1.67
24 18 8.58 1.54 8.38 1.57 8.17 1.60 7.97 1.63 7.77 1.67
AFR
m3/h
1,700
Indoor temperature
°CDB 16 18 20 22 27
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 8.26 3.03 8.07 3.09 7.87 3.16 7.67 3.22 7.48 3.28
-10 -11 8.75 3.04 8.54 3.11 8.33 3.18 8.12 3.24 7.91 3.30
-5 -7 9.56 3.10 9.34 3.16 9.11 3.22 8.88 3.29 8.65 3.35
0 -2 10.15 3.10 9.91 3.17 9.66 3.23 9.42 3.29 9.18 3.36
5 3 11.27 3.11 11.01 3.18 10.74 3.25 10.47 3.31 10.20 3.38
7 6 11.76 3.10 11.48 3.16 11.20 3.22 10.92 3.29 10.64 3.35
10 8 12.16 3.04 11.87 3.11 11.58 3.17 11.29 3.24 11.00 3.30
15 10 10.86 2.34 10.60 2.38 10.34 2.43 10.08 2.48 9.82 2.52
20 15 10.86 2.05 10.60 2.09 10.35 2.13 10.09 2.17 9.83 2.20
24 18 11.30 2.03 11.03 2.07 10.76 2.12 10.49 2.16 10.22 2.20
Page 30
- 24 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG36LHTBP
Model: ARYG45LHTBP
Model: ARYG54LHTBP
AFR
m3/h
1,850
Indoor temperature
°CDB 16 18 20 22 27
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 9.15 4.26 8.93 4.35 8.71 4.44 8.49 4.52 8.27 4.62
-10 -11 9.88 4.29 9.65 4.37 9.41 4.46 9.18 4.55 8.94 4.64
-5 -7 10.56 4.27 10.31 4.35 10.06 4.44 9.80 4.53 9.55 4.62
0 -2 11.79 4.23 11.51 4.32 11.23 4.41 10.95 4.49 10.67 4.58
5 3 12.91 4.16 12.60 4.26 12.29 4.34 11.98 4.43 11.68 4.51
7 6 13.34 3.72 13.02 3.79 12.70 3.88 12.38 3.95 12.07 4.03
10 8 13.65 3.59 13.32 3.66 13.00 3.73 12.67 3.80 12.35 3.89
15 10 12.13 2.74 11.84 2.81 11.55 2.86 11.26 2.92 10.98 2.96
20 15 12.07 2.41 11.79 2.46 11.50 2.51 11.21 2.56 10.92 2.60
24 18 12.69 2.40 12.38 2.45 12.08 2.50 11.78 2.54 11.48 2.58
AFR
m
3
/h
2,550
Indoor temperature
°CDB 16 18 20 22 27
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 11.38 3.93 11.11 4.02 10.84 4.10 10.58 4.19 10.31 4. 27
-10 -11 12.37 4.05 12.08 4.13 11.79 4.21 11.50 4.30 11.20 4.38
-5 -7 13.41 4.10 13.10 4.19 12.77 4.27 12.45 4.27 12.13 4.27
0 -2 14.39 4.10 14.05 4.19 13.71 4.27 13.37 4.27 13.02 4.27
5 3 15.74 4.10 15.36 4.19 14.99 4.27 14.61 4.27 14.24 4.27
7 6 17.02 4.10 16.61 4.19 16.20 4.27 15.79 4.27 15.40 4.27
10 8 17.54 4.10 17.12 4.19 16.70 4.27 16.28 4.27 15.87 4.27
15 10 17.30 3.68 16.89 3.76 16.48 3.83 16.06 3.83 15.66 3.83
20 15 16.50 3.26 16.12 3.33 15.72 3.39 15.32 3.39 14.94 3.39
24 18 17.38 3.26 16.96 3.33 16.56 3.39 16.14 3.39 15.72 3.39
AFR
m3/h
2,550
Indoor temperature
°CDB 16 18 20 22 27
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 13.19 5.20 12.87 5.31 12.56 5.41 12.25 5.52 11.93 5.63
-10 -11 14.66 5.20 14.31 5.31 13.96 5.41 13.61 5.52 13.26 5.63
-5 -7 16.25 5.21 15.87 5.32 15.48 5.42 15.09 5.53 14.71 5.64
0 -2 17.51 5.20 17.09 5.31 16.68 5.41 16.26 5.52 15.84 5.63
5 3 19.20 5.18 18.74 5.29 18.28 5.39 17.83 5.50 17.37 5.60
7 6 17.33 4.45 16.91 4.53 16.50 4.63 16.09 4.72 15.68 4.81
10 8 19.02 4.15 18.56 4.24 18.11 4.32 17.66 4.41 17.20 4.50
15 10 20.42 4.12 19.93 4.21 19.45 4.29 18.96 4.38 18.48 4.44
20 15 19.83 4.05 19.36 4.13 18.88 4.22 18.41 4.30 17.94 4.36
24 18 20.53 3.97 20.04 4.06 19.55 4.14 19.06 4.23 18.57 4.29
Page 31
- 25 -
DUCT TYPE
ARYG18-54LHTBP
7. Fan performance
7-1. Fan performance curve
Model: ARYG18LHTBP
NOTES:
• Setting of the external static pressure is switchable into modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
[l/s]
[m
3
/h]
Airflow
139 278 417 556
500
0
0100015002000
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_1
Hi (Normal SP)
Qu (Normal SP)
Hi (SP mode20)
SP mode20 upper limit
Normal SP upper limit
Normal SP lower limit
Qu(SP mode20)
SP mode20 lower limit
Fan performance curve_2
(For function setting by remote controller)
Hi (SP mode06)
Hi (SP mode04)
Hi (SP mode08)
Hi (SP mode10)
Hi (SP mode12)
Hi (SP mode14)
Hi (SP mode16)
Hi (SP mode18)
Hi (SP mode20)
Hi (SP mode07)
Hi (SP mode05)
Hi (Normal SP)
Hi (SP mode09)
Hi (SP mode11)
Hi (SP mode13)
Hi (SP mode15)
Hi (SP mode17)
Hi (SP mode19)
Hi (SP mode03)
[l/s]
[m
3
/h]
Airflow
139 278 417 556
500
0
0100015002000
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Page 32
- 26 -
DUCT TYPE
ARYG18-54LHTBP
• The default setting is set at "Normal SP".
Characteristics of air volume and capacity
Cooling
Heating
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556
500
0
0100015002000
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556
500
0
0100015002000
Page 33
- 27 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG24LHTBP
NOTES:
• Setting of the external static pressure is switchable into modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal SP".
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_1
Hi (Normal SP)
Qu (Normal SP)
Hi (SP mode20)
SP mode20 upper limit
Normal SP upper limit
Normal SP lower limit
Qu(SP mode20)
SP mode20 lower limit
Fan performance curve_2
(For function setting by remote controller)
Hi (SP mode06)
Hi (SP mode04)
Hi (SP mode08)
Hi (SP mode10)
Hi (SP mode12)
Hi (SP mode14)
Hi (SP mode16)
Hi (SP mode18)
Hi (SP mode20)
Hi (SP mode07)
Hi (SP mode05)
Hi (Normal SP)
Hi (SP mode09)
Hi (SP mode11)
Hi (SP mode13)
Hi (SP mode15)
Hi (SP mode17)
Hi (SP mode19)
Hi (SP mode03)
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Page 34
- 28 -
DUCT TYPE
ARYG18-54LHTBP
Characteristics of air volume and capacity
Cooling
Heating
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
95
100
105
capacity(%)
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
Page 35
- 29 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG30LHTBP
NOTES:
• Setting of the external static pressure is switchable into modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal SP".
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_1
Hi (Normal SP)
Qu (Normal SP)
Hi (SP mode20)
SP mode20 upper limit
Normal SP upper limit
Normal SP lower limit
Qu(SP mode20)
SP mode20 lower limit
Fan performance curve_2
(For function setting by remote controller)
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Hi (SP mode06)
Hi (Normal SP)
Hi (SP mode08)
Hi (SP mode10)
Hi (SP mode12)
Hi (SP mode14)
Hi (SP mode16)
Hi (SP mode18)
Hi (SP mode20)
Hi (SP mode03)
Hi (SP mode07)
Hi (SP mode05)
Hi (SP mode04)
Hi (SP mode09)
Hi (SP mode11)
Hi (SP mode13)
Hi (SP mode15)
Hi (SP mode17)
Hi (SP mode19)
Page 36
- 30 -
DUCT TYPE
ARYG18-54LHTBP
Characteristics of air volume and capacity
Cooling
Heating
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556 695
500 1000 1500 2000 2500
Page 37
- 31 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG36LHTBP
NOTES:
• Setting of the external static pressure is switchable into modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal SP".
[l/s]
[m
3
/h]
Airflow
139 278 417 556 833
500 1000 1500 2000 3000
695
2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_1
Hi (Normal SP)
Qu (Normal SP)
Hi (SP mode20)
SP mode20 upper limit
Normal SP upper limit
Normal SP lower limit
Qu(SP mode20)
SP mode20 lower limit
[l/s]
[m
3
/h]
Airflow
139 278 417 556 833
500 1000 1500 2000 3000
695
2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_2
(For function setting by remote controller)
Hi (SP mode06)
Hi (Normal SP)
Hi (SP mode08)
Hi (SP mode10)
Hi (SP mode12)
Hi (SP mode14)
Hi (SP mode16)
Hi (SP mode18)
Hi (SP mode20)
Hi (SP mode03)
Hi (SP mode07)
Hi (SP mode05)
Hi (SP mode04)
Hi (SP mode09)
Hi (SP mode11)
Hi (SP mode13)
Hi (SP mode15)
Hi (SP mode17)
Hi (SP mode19)
Page 38
- 32 -
DUCT TYPE
ARYG18-54LHTBP
Characteristics of air volume and capacity
Cooling
Heating
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556 833
500 1000 1500 2000 3000
695
2500
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556 833
500 1000 1500 2000 3000
695
2500
Page 39
- 33 -
DUCT TYPE
ARYG18-54LHTBP
Models: ARYG45LHTBP and ARYG54LHTBP
NOTES:
• Setting of the external static pressure is switchable into modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal SP".
[l/s]
[m
3
/h]
Airflow
139 278 417 556 972
500 1000 1500 2000 3500
833
3000
695
2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_1
Hi (Normal SP)
Qu (Normal SP)
Hi (SP mode16)
SP mode16 upper limit
Normal SP upper limit
Normal SP lower limit
Qu(SP mode16)
SP mode16 lower limit
Fan performance curve_2
(For function setting by remote controller)
[l/s]
[m
3
/h]
Airflow
139 278 417 556 972
500 1000 1500 2000 3500
833
3000
695
2500
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Hi (Normal SP)
Hi (SP mode08)
Hi (SP mode04)
Hi (SP mode10)
Hi (SP mode12)
Hi (SP mode14)
Hi (SP mode16)
Hi (SP mode07)
Hi (SP mode09)
Hi (SP mode03)
Hi (SP mode05)
Hi (SP mode11)
Hi (SP mode13)
Hi (SP mode15)
Page 40
- 34 -
DUCT TYPE
ARYG18-54LHTBP
Characteristics of air volume and capacity
Cooling
Heating
Automatic airflow adjustment procedures
1. To start the auto setting, use No.32 of setting value in Function Number 26.
2. Run the air conditioner on fan mode (High). * For instructions on how to operate the air conditioner, refer to the operation manual of the re­mote controller. During automatic airflow adjustment, the mode will be fixed at fan (High). When this function is active, do not operate the outdoor unit.
3. The air conditioner will run for about 1 to 8 min then stop automatically. * Do not change the throttles of the inlet and outlet ports during operation. When used in a group control system, the setting will take about 10 min.
4. Turn the air conditioner off and on again.
5. Check the setting value of Function 26. * If the setting value has not changed, repeat the procedure from step 2.
!
CAUTION
When the duct or outlet installations are changed after the Automatic airflow adjustment is com­pleted, repeat the procedure from step 1.
[l/s]
[m
3
/h]
Airflow
139 278 417 556 972
500 1000 1500 2000 3500
833
3000
695
2500
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
139 278 417 556 972
500 1000 1500 2000 3500
833
3000
695
2500
100
105
95
Capacity [%]
Page 41
- 35 -
DUCT TYPE
ARYG18-54LHTBP
7-2. Airflow
Model: ARYG18LHTBP
Cooling
Heating
Fan speed Airflow
HIGH
m
3
/h
1,050
l/s 292
CFM 618
MED
m
3
/h
840
l/s 233
CFM 494
LOW
m
3
/h
740
l/s 206
CFM 436
QUIET
m
3
/h
630
l/s 175
CFM 371
Fan speed Airflow
HIGH
m
3
/h
1,050
l/s 292
CFM 618
MED
m
3
/h
840
l/s 233
CFM 494
LOW
m
3
/h
740
l/s 206
CFM 436
QUIET
m
3
/h
630
l/s 175
CFM 371
Page 42
- 36 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG24LHTBP
Cooling
Heating
Fan speed Airflow
HIGH
m
3
/h
1,360
l/s 378
CFM 800
MED
m
3
/h
1,080
l/s 300
CFM 800
LOW
m
3
/h
740
l/s 244
CFM 518
QUIET
m
3
/h
630
l/s 189
CFM 400
Fan speed Airflow
HIGH
m
3
/h
1,360
l/s 378
CFM 800
MED
m
3
/h
1,080
l/s 300
CFM 636
LOW
m
3
/h
880
l/s 244
CFM 518
QUIET
m
3
/h
680
l/s 189
CFM 400
Page 43
- 37 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG30LHTBP
Cooling
Heating
Fan speed Airflow
HIGH
m
3
/h
1,700
l/s 472
CFM 1,001
MED
m
3
/h
1,360
l/s 378
CFM 800
LOW
m
3
/h
1,190
l/s 331
CFM 700
QUIET
m
3
/h
1,070
l/s 297
CFM 630
Fan speed Airflow
HIGH
m
3
/h
1,700
l/s 472
CFM 1,001
MED
m
3
/h
1,360
l/s 378
CFM 800
LOW
m
3
/h
1,190
l/s 331
CFM 700
QUIET
m
3
/h
1,070
l/s 297
CFM 630
Page 44
- 38 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG36LHTBP
Cooling
Heating
Fan speed Airflow
HIGH
m
3
/h
2,050
l/s 569
CFM 1,207
MED
m
3
/h
1,640
l/s 456
CFM 965
LOW
m
3
/h
1,330
l/s 369
CFM 783
QUIET
m
3
/h
1,070
l/s 297
CFM 630
Fan speed Airflow
HIGH
m
3
/h
1,850
l/s 514
CFM 1,089
MED
m
3
/h
1,640
l/s 456
CFM 965
LOW
m
3
/h
1,330
l/s 369
CFM 783
QUIET
m
3
/h
1,070
l/s 297
CFM 630
Page 45
- 39 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG45LHTBP
Cooling
Heating
Fan speed Airflow
HIGH
m
3
/h
2,550
l/s 708
CFM 1,501
MED
m
3
/h
2,040
l/s 567
CFM 1,201
LOW
m
3
/h
1,650
l/s 458
CFM 971
QUIET
m
3
/h
1,430
l/s 397
CFM 842
Fan speed Airflow
HIGH
m
3
/h
2,550
l/s 708
CFM 1,501
MED
m
3
/h
2,040
l/s 567
CFM 1,201
LOW
m
3
/h
1,650
l/s 458
CFM 971
QUIET
m
3
/h
1,430
l/s 397
CFM 842
Page 46
- 40 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG54LHTBP
Cooling
Heating
Fan speed Airflow
HIGH
m
3
/h
2,550
l/s 708
CFM 1,501
MED
m
3
/h
2,040
l/s 567
CFM 1,201
LOW
m
3
/h
1,650
l/s 458
CFM 971
QUIET
m
3
/h
1,430
l/s 397
CFM 842
Fan speed Airflow
HIGH
m
3
/h
2,550
l/s 708
CFM 1,501
MED
m
3
/h
2,040
l/s 567
CFM 1,201
LOW
m
3
/h
1,650
l/s 458
CFM 971
QUIET
m
3
/h
1,430
l/s 397
CFM 842
Page 47
- 41 -
DUCT TYPE
ARYG18-54LHTBP
8. Operation noise (sound pressure)
8-1. Noise level curve
Model: ARYG18LHTBP
Cooling Heating
Model: ARYG24LHTBP
Cooling Heating
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
Page 48
- 42 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG30LHTBP
Cooling Heating
Model: ARYG36LHTBP
Cooling Heating
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
Page 49
- 43 -
DUCT TYPE
ARYG18-54LHTBP
Model: ARYG45LHTBP
Cooling Heating
Model: ARYG54LHTBP
Cooling Heating
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
High
Quiet
Page 50
- 44 -
DUCT TYPE
ARYG18-54LHTBP
8-2. Sound level check point
Center
Front view
Microphone
Center
Side view
Product
Air
1.5 m
2 m 1 m
Microphone
Measuring duct (Set the static pressure as rating in this area.)
Measuring duct
Page 51
- 45 -
DUCT TYPE
ARYG18-54LHTBP
9. Safety devices
*: Printed Circuit Board
Type of protection Protection form
Model
ARYG18LHTBP ARYG24LHTBP
ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP
Circuit protection Current fuse (PCB*) 250 V, 5A 250 V, 10A
Fan motor protection
Thermal protection program
Activate
115 ± 15 °C
Fan motor stop
-
Reset
70 °C
Fan motor restart
-
Current protection Activate - 7.58A
Page 52
- 46 -
DUCT TYPE
ARYG18-54LHTBP
10. External input and output
10-1. External input
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
PCB External input External output Connector Input select
Input
signal
External
connect kit
(Optional parts)
Indoor unit
Operation/Stop Forced stop
- Terminal Dry contact Edge -
-
Operation status
CN47 - - UTY-XWZXZG
Error status Indoor unit fan
operation status External heater
output
External
input and
output
(UTY-XCSX)
Operation/Stop
-
Input 1/
Input 2
Dry contact/
Apply voltage
Edge/ Pulse
-
Forced thermostat off
Input 1 Edge
-
Operation status
Output 1 Output 2 Output 3
-- -
Error status Indoor unit
status External heater
output
Terminal
(Ext.in)
CN65
(Ext.in/out PCB)
CN47
(Ext.out)
Rotary switch
SW2
SW1
Fig. External input and output PCBFig. Indoor unit PCB
1
2

Terminal
PCB
Page 53
- 47 -
DUCT TYPE
ARYG18-54LHTBP
External input and output PCB
The indoor unit Operation/Stop can be set by using the input terminal on the PCB.
Input select
Use either one of these types of terminals according to the application. (Both types of terminals cannot be used simultaneously.)
• Dry contact In case of internal power supply, set the slide switch of SW1 to "NON VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
• Apply voltage In case of external power supply, set the slide switch of SW1 to "VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA. *2: Make the power supply DC 12 V to 24 V 10 mA or more.
1
2
C
Input 1 Input 2
PCB
Connected unit
 
+
+
-
1
2
C
Input 1 Input 2 Power supply
PCB
Connected unit
 

+-
Page 54
- 48 -
DUCT TYPE
ARYG18-54LHTBP
10-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca­bles to be installed.
Indoor unit
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 49.
When indicator, etc. are connected directly
Example: Function setting 60 is set to "00"
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
External input and output PCB
• A twisted pair cable (22AWG) should be used.
• Permissible voltage and current: DC 5 V to 30 V / 3 A, AC 30 V to 250 V / 3 A
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 49.
1
2
CN47
LED
PCB
Resistor
Connected unit
+
-
1
2
Connected device
CN47
PCB
Connected unit Relay
(Operation status)
-
+
1
2
3
4
5
6
Power supply
Power supply
Power supply
PCB
Connected device 1
(Operation status)
Connected device 2 (Error status)
(Indoor unit fan
operation status)
Connected device 3
Example
Page 55
- 49 -
DUCT TYPE
ARYG18-54LHTBP
10-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
NOTE: Input of Operation/Stop depends on the setting of function setting 46. 00: Operation/Stop mode 1 (R.C. enabled) 01: (Setting prohibited) 02: Forced stop 03: Operation/Stop mode 2 (R.C. disabled)
Mode
Function
setting
External
input and
output PCB
(Rotary SW)
External input
Indoor unit
Input
External input and output PCB
Terminal Input 1 Input 2 Signal type
0-1 60-00 1 Operation/Stop
Operation/Stop Not available Edge
Operation Stop Pulse
0-2 60-00 2 Operation/Stop
Forced
Thermostat OFF
Not available Edge
1—8
60-01 to
60-08
3 - 9, A (Setting prohibited)
9 60-09 B Operation/Stop
Forced
Thermostat OFF
Not available Edge
10 60-10 C Operation/Stop
Forced
Thermostat OFF
Not available Edge
11 60-11 D Operation/Stop
Forced
Thermostat OFF
Not available Edge
Mode
Function
setting
External
input and
output PCB
(Rotary SW)
External output
Indoor unit
Output
External input and output PCB
CN47 Output 1 Output 2 Output 3
0-1 60-00 1 Operation/Stop Operation/Stop Error status
Indoor unit fan
operation status
0-2 60-00 2 Operation/Stop Error status
Indoor unit fan
operation status
External heater
output
1—8
60-01 to
60-08
3 - 9, A (Setting prohibited)
9 60-09 B Error status Operation/Stop
Indoor unit fan
operation status
External heater
output
10 60-10 C
Indoor unit fan
operation status
Operation/Stop Error status
External heater
output
11 60- 11 D
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
Page 56
- 50 -
DUCT TYPE
ARYG18-54LHTBP
Input signal type
• Indoor unit Input signal type is only "Edge".
• External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
Edge
Edge
Pulse
The width of pulse must be longer than 200 msec.
Page 57
- 51 -
DUCT TYPE
ARYG18-54LHTBP
10-4. Details of function
Control input function
When function setting is "Operation/Stop" mode 1
• In the case of "Edge" input
• In the case of "Pulse" input
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-00
- Input of indoor unit Terminal
Off On Operation On Off Stop
60-00 / 1
External input and
output PCB
Input 1
Off On Operation On Off Stop
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-00 60-00 / 1
External input and
output PCB
Input 1 Pulse Operation Input 2 Pulse Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
Input
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
Page 58
- 52 -
DUCT TYPE
ARYG18-54LHTBP
When function setting is "Forced stop" mode
• In the case of "Edge" input
• In the case of "Pulse" input
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-02
- Input of indoor unit Terminal
Off On Forced stop On Off Normal
60-00 / 1
External input and
output PCB
Input 1
Off On Forced stop On Off Normal
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-02 60-00 / 1
External input and
output PCB
Input 1 Pulse Forced stop Input 2 Pulse Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On On
Indoor unit
On
Input
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
Input 1
Input 2
On On On
Indoor unit
Page 59
- 53 -
DUCT TYPE
ARYG18-54LHTBP
When function setting is "Operation/Stop" mode 2
• In the case of "Edge" input
• In the case of "Pulse" input
NOTES:
• When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-03
- Input of indoor unit Terminal
Off On Operation
On Off
Stop (R.C.
disabled)
60-00 / 1
External input and
output PCB
Input 1
Off On Operation
On Off
Stop (R.C.
disabled)
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-03 60-00 / 1
External input and
output PCB
Input 1 Pulse Operation
Input 2 Pulse
Stop (R.C.
disabled)
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On OnOff
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
(R.C. disabled)
Off
On
Page 60
- 54 -
DUCT TYPE
ARYG18-54LHTBP
Forced thermostat off function
Control output function
The output is low when the unit is stopped.
Function
setting /
Rotary SW of External
input and output PCB
External input Input signal Command
60-00 / 2
External input and output
PCB
Input 1
Off On
Thermostat
off
60-09 / B 60-10 / C
On Off
Normal
operation
60-11 / D
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-00 / 1, 2 Output of indoor unit CN47
Low High Operation High Low Stop
60-00 / 1
External input and output
PCB
Output 1
Off On Operation
60-09 / B 60-10 / C
On Off Stop
60-11 / D
On Off
On
Off
Compressor
Room temp.
Set temp.
Input
Operation
Stop
High
Low
CN47
On
Off
Output 1
Indoor unit
Page 61
- 55 -
DUCT TYPE
ARYG18-54LHTBP
Error status
The output is ON when an error is generated for the indoor unit.
Indoor unit fan operation status
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-09 / B Output of indoor unit CN47
Low High Error High Low Normal
60-00 / 2
External input and output
PCB
Output 1
Off On Error On Off Normal
60-00 / 1
Output 2
Off On Error
60-10 / C On Off Normal
60-11 / D Output 3
Off On Error On Off Normal
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-10 / C Output of indoor unit CN47
Low High Fan run High Low Fan stop
60-00 / 2
External input and output
PCB
Output 2
Off On Fan run
60-09 / B
On Off Fan stop
60-11 / D
60-00 / 1 Output 3
Off On Fan run On Off Fan stop
Output signal Condition
On
The indoor unit fan is operating.
Low High
Off The fan is stopped or during cold air prevention.
High Low During thermostat off when in dry mode operation.
Error
Normal
High
Low
CN47
On
Off
Output 1, 2, 3
Indoor unit
Fan run
Fan stop
High
Low
CN47
On
Off
Output 2, 3
Indoor unit
Page 62
- 56 -
DUCT TYPE
ARYG18-54LHTBP
External heater output
Specifications of the signal output performance are as shown as follows:
Example: When set temperature (Ts) is set at 22 °C;
• And room temperature (Tr) increase above 12 °C, signal output is on.
• And Tr increase above 21 °C, signal output is off.
• And Tr decrease below 19 °C, signal output is on.
• And Tr decrease below 10 °C, signal output is off.
The output also turns off in defrost operation.
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-11 / D Output of indoor unit CN47
Low High Heater on High Low Heater off
60-00 / 2
External input and output
PCB
Output 3
Off On Heater on
60-09 / B 60-10 / C On Off Heater off
Output signal Condition
Low High
Heater turns on as shown in diagram of heating temperature
Off On
High Low
Heater turns off as shown in diagram of heating temperature
• Other than Heating mode
On Off
• Error occurred
• Forced thermo off
• Fan stop protection
Off
Off
On
Tr-Ts
Tr-Ts=-1°C
Tr-Ts=-10°C
Tr-Ts=-3°C
Tr-Ts=-12°C
Page 63
- 57 -
DUCT TYPE
ARYG18-54LHTBP
11. Function settings
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE: Incorrect settings can cause a product malfunction.
11-1. Function settings on indoor unit
Models: ARYG18LHTBP, ARYG24LHTBP, ARYG30LHTBP,
ARYG36LHTBP, ARYG45LHTBP, and ARYG54LHTBP
By using some components on the PCB, you can change the function settings.
Related components on the PCB and the applicable settings
Component location
Components on the indoor unit main PCB used for the function settings are located as shown in the following figure.
Component Setting content
DIP switch100
1
Remote controller address setting
2 3 4
DIP switch101
1 Setting change prohibited 2 Setting change prohibited 3 Fan delay setting
SW100
1234
SW101
123
Page 64
- 58 -
DUCT TYPE
ARYG18-54LHTBP
DIP switch setting
Remote controller address setting (SW100) When operating a number of indoor units by using a wired remote controller, DIP switch setting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00.
Switch 1: Setting change prohibited (SW101)
Switch 2: Setting change prohibited (SW101)
Switch 3: Fan delay setting (SW101) When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor unit fan operation will continue for 1 minute.
Remote
controller
address
DIP switch number
Factory
setting
1 2 3 4
00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON
Switch 3 Fan delay Factory setting
ON Enabled
OFF Disabled
00 01 02
Remote controller address
Indoor unit
Remote controller
Page 65
- 59 -
DUCT TYPE
ARYG18-54LHTBP
11-2. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce­dure and the content of each function setting, select appropriate functions for your installation envi­ronment.
NOTE: Incorrect settings can cause a product malfunction.
Setting procedure by using wired remote controller
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before turning on the power of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
1. Turn on the power.
2. Touch the “Function Setting” on the “Maintenance” screen. The “Function Setting” screen is displayed. Then touch the “Address” on the “Function Setting” screen.
3. “Address” screen is displayed. Select the address of the indoor unit whose function number is to be set by touching or . When setting at all the indoor units, touch “All”.
NOTE: Perform this step only when the remote controller address setting is required. Otherwise,
skip this step.
4. Touch the “Function No.” on the “Function Setting” screen.
5. “Function No.” screen is displayed. Set the function number “11” by touching or . When the “OK” is touched, the display returns to the “Function Setting” screen.
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back Setting
002–01
Address
Cancel OK
All
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back Setting
11
Function No.
Cancel OK
Page 66
- 60 -
DUCT TYPE
ARYG18-54LHTBP
6. Touch the “Setting” on the “Function Setting” screen.
7. Setting screen of “Setting No.” is displayed. Set the setting number by touching or . (The setting range is from 00 to 99.) When the “OK” is touched, the “Function Setting” verification screen is displayed.
8. When the “Back” on the “Function Setting” screen is touched, the display returns to the “Main­tenance” screen.
9. After completing the function setting, be sure to turn off the power and turn it on again.
!
CAUTION
After turning off the power, wait 30 seconds or more before turning on the power again. The function setting will not become active unless the power is turned off then on again.
[002–01]
[11]
[00]
Address
Function No.
Setting No.
Function Setting
Back Setting
00
[002–01]
[11]
Function Setting
Cancel OK
Address Function No.
Setting No.
Example: When configuring the setting number of filter sign.
[002–01]
[11]
[00]
Address
Function No.
Setting No.
Function Setting
Back Setting
Page 67
- 61 -
DUCT TYPE
ARYG18-54LHTBP
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function no. Functions
1)
11
Filter sign
2)
26
Static pressure
3)
30/31
Room temperature control for indoor unit sensor
4)
35/36
Room temperature control for wired remote controller sensor
5)
40
Auto restart
6)
42
Room temperature sensor switching
7)
43
Cold air prevention
8)
44
Remote controller custom code
9)
46
External input control
10)
48
Room temperature sensor switching (Aux.)
11)
49
Indoor unit fan control for energy saving for cooling
12)
60
Switching functions for external output terminal
Function number Setting value Setting description Factory setting
11
00 Standard (2,500 hours) 01 Long interval (4,400 hours) 02 Short interval (1,250 hours) 03 No indication
Function number Setting value Setting description Factory setting
26
03 30 Pa 04 40 Pa 05 50 Pa 06 60 Pa 07 70 Pa 08 80 Pa 09 90 Pa 10 100 Pa 11 110 Pa 12 120 Pa 13 130 Pa 14 140 Pa 15 150 Pa 16 160 Pa 17 170 Pa 18 180 Pa 19 190 Pa 20 200 Pa
31
Standard (35 Pa: 18, 24 type) Standard (47 Pa: 30, 36 type) Standard (60 Pa: 45, 54 type)
32 Automatic airflow adjustment
Page 68
- 62 -
DUCT TYPE
ARYG18-54LHTBP
NOTE: Range of static pressure is different by model.
If the static pressure is set above maximum range, the setting will be the same as the maximum.
Example:
For 45, 54 type models, setting "170 Pa" (17) to "200 Pa" (20) will be the same as "160 Pa" (16). For details, refer to Chapter 7. "Fan performance curve" on page 25.
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur­er’s recommended value).
Type name Setting of static pressure range
18 type, 24 type, 30 type, and 36 type 30 to 200 Pa
45 type or 54 type 30 to 160 Pa
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting 01 No correction 0.0 °C 02 -0.5 °C
More cooling Less heating
03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C 08 -3.5 °C 09 -4.0 °C 10 +0.5 °C
Less cooling
More heating
11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
Page 69
- 63 -
DUCT TYPE
ARYG18-54LHTBP
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
5) Auto restart
Enables or disables automatic restart after a power interruption.
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external device.
6) Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
7) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled, the fan setting will always follow the setting on the remote controller. (Excluding defrost mode)
Function number Setting value Setting description
Factory
setting
35
(For cooling)
36
(For heating)
00 No correction 01 No correction 0.0°C 02 -0.5 °C
More cooling Less heating
03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C 08 -3.5 °C 09 -4.0 °C 10 +0.5 °C
Less cooling
More heating
11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
Function number Setting value Setting description Factory setting
40
00 Enable 01 Disable
Function number Setting value Setting description Factory setting
42
00 Indoor unit 01 Both
Function number Setting value Setting description Factory setting
43
00 Enable 01 Disable
Page 70
- 64 -
DUCT TYPE
ARYG18-54LHTBP
8) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
10) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
11) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially activated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy saving function or connecting a network converter. To confirm if the remote controller has this setting, refer to the operating manual of each remote controller.
Function number Setting value Setting description Factory setting
44
00 A 01 B 02 C 03 D
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode 1 01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2
Function number Setting value Setting description Factory setting
48
00 Both 01 Wired remote controller
Function number Setting value Setting description Factory setting
49
00 Disable 01 Enable 02 Remote controller
Page 71
- 65 -
DUCT TYPE
ARYG18-54LHTBP
12) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and output”.
Function number Setting value Setting description Factory setting
60
00 Operation status 09 Error status 10 Indoor unit fan operation status 11 External heater
Page 72
- 66 -
DUCT TYPE
ARYG18-54LHTBP
12. Wired remote controller (Touch panel)
12-1. Remote controller address setting
How to confirm the remote controller address
NOTE: The address of this remote controller is set automatically. Do not change the indoor unit
remote controller address from the factory setting "0". (Verify that the address is "0".)
1. When the [RC Address Setting] on the “Maintenance” screen is touched, the “Installer Pass­word Verification” screen is displayed.
2. Enter the installer password, and touch the [OK]. “R.C. Address Setting” screen is displayed. The address of this unit is displayed on the “R.C. Address Setting” screen.
3. When the [Back] is touched, the display returns to the “Maintenance” screen.
How to set the remote controller address manually
NOTE: Perform manual address setting only when setting the address with an arbitrary number.
Indoor unit remote controller address setting is necessary.
1. Touch the [Manual Addressing] on the “R.C. Address Setting” screen.
2. “Manual Addressing” screen is displayed. Set the address with [] or []. When the [OK] is touched, a verification screen is displayed.
Previous Page
Back
Next Page
Page 2/ 3
Maintenance
Test Run
R.C. Address Setting
Function Setting
I.U. Address Setting
[001–01]
R.C. Address Setting
Current Address
Back
Manual Addressing
Address Reset
R.C. address (Unit number)
When the address is set manually, this mark is displayed.
[001–01]
R.C. Address Setting
Current Address
Back
Manual Addressing
Address Reset
01001
Manual Addressing
Cancel OK
System Unit
Page 73
- 67 -
DUCT TYPE
ARYG18-54LHTBP
3. When the [Yes] on the verification screen is touched, a message screen is displayed.
4. When the [Close] on the message screen is touched, the display returns to the “R.C. Address Setting” screen. Turn on the power again.
NOTES:
• Indoor unit remote controller address setting is necessary.
• Set the remote controller address of indoor units connected by the same remote controller cable within a range of 1 to 9 and A (10) to F(15) so that there is no duplication. (Do not set to "0".)
• The address of remote controller is set within a range of 1 to 32, but set it so that it does not duplicate the remote controller address of an indoor unit connected by the same remote controller cable.
How to reset the manual address setting number
1. Touch the [Address Reset] on the “R.C. Address Setting” screen.
2. A verification screen is displayed. When the [Yes] is touched, a verification screen is displayed.
3. When the [Close] on the message screen is touched, the display returns to the “R.C. Address Setting” screen. Turn on the power again.
No Yes
Manual Addressing
Manual address setting will be started. OK?
Setting is reflected after the power is turned on again.
Manual Addressing
Close
[001–05]
R.C. Address Setting
Current Address
Back
Manual Addressing
Address Reset
No Yes
R.C. Address Setting
The address will be returned to factory setting. OK?
Setting is reflected after the power is turned on again.
R.C. Address Setting
Close
Page 74
- 68 -
DUCT TYPE
ARYG18-54LHTBP
12-2. Remote controller master/slave setting
1. Touch the [RC Master/Slave Setting] on the “Initial Setting” screen.
2. “RC Master/Slave Setting” screen is displayed. Select the [Master] or [Slave].
NOTES:
• Set only one Master remote controller. Units specified other than [Master] are set to [Slave] auto­matically.
• Do not perform “RC Mater/Slave Setting” during setting or operating from the Master remote controller.
Back
Previous Page
Page 3/ 3
Initial Setting
RC Master/ Slave Setting
R.C. Master / Slave Setting
Cancel OK
Master
Slave
Page 75
- 69 -
DUCT TYPE
ARYG18-54LHTBP
13. Optional parts
13-1. Controllers
NOTE: Available functions may differ by the remote controller. For details, refer to the operation
manual.
Exterior Part name Model name Summary
Wired remote
controller
UTY-RNRYZ1
Easy finger touch operation with LCD panel. Backlight enables easy operation in a darkened room. Wire type: Non-polar 2-wire
Wired remote
controller
UTY-RLRY
High visibility and easy operation. Room temperature can be accurately controlled using the built-in thermo sensor. Wire type: Non-polar 2-wire
Wired remote
controller
UTY-RVNYM
Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wire type: Polar 3-wire
Wired remote
controller
UTY-RNNYM
Room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor. Wire type: Polar 3-wire
Simple remote
controller
UTY-RSNYM
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Polar 3-wire
IR receiver unit UTY-LBTYM
Unit control is performed by wireless remote controller.
Page 76
- 70 -
DUCT TYPE
ARYG18-54LHTBP
13-2. Others
Exterior Part name Model name Summary
Remote sensor
unit
UTY-XSZX
New amenity space can be offered by installing Remote sensor unit in the remote controller.
Long-life filter UTD-LFNB
Long-life filter can be mounted to the indoor unit. (For 24, 30 models)
Long-life filter UTD-LFNA
Long-life filter can be mounted to the indoor unit. (For 36, 45, and 54 models)
External
connect kit
UTY-XWZXZG
Use to connect with various peripheral devices and air conditioner PCB. For control output port.
External input
and output PCB
UTY-XCSX
Use to connect with external devices and air conditioner PCB.
External input
and output PCB
bracket
UTZ-GXNA
For installing the External input and output PCB.
Page 77
Part 2. OUTDOOR UNIT
SINGLE TYPE:
AOYG18LBCA AOYG24LBCA
AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA
Page 78
- 72 -
OUTDOOR UNIT
AOYG18-54LB
1. Specifications
1-1. Models: AOYG18LBCA and AOYG24LBCA
Typ e
Inverter heat pump
Model name
AOYG18LBCA AOYG24LBCA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A6.69.7
Fan
Airflow rate
Cooling
m3/h
1,900 2,460
Heating 1,700 2,340
Type × Q'ty Propeller × 1
Motor output W 49
Sound pressure level *1
Cooling
dB(A)
50 55
Heating 51 56
Sound power level
Cooling
dB(A)
63 68
Heating 62 68
Heat exchanger type
Dimensions (H × W × D)
mm
Main:588 × 881 × 36.4
Sub:546 × 580 × 18.2
Fin pitch 1.45
Rows × Stages Main:2 × 28 Sub:1 × 26
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminum)
Surface treatment Hydrophilic coating (Blue fin)
Compressor
Type × Q'ty Twin rotary × 1
Motor output W 1,100
Refrigerant
Type R410A
Factory charge g 1,800
Refrigerant oil
Type POE (RB68)
Amount
cm
3
600
Enclosure
Material Stee l
Color
Beige
Approximate color of MUNSELL 10YR7. 5/1.0
Dimensions (H × W × D)
Net
mm
620 × 790 × 290
Gross 713 × 945 × 395
Weight
Net
kg
41
Gross 45
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4) Ø 6.35 (Ø 1/4)
Gas Ø 12.7 (Ø 1/2) Ø 15.88 (Ø 5/8)
Method Flare
Pre-charge length
m
15
Max. length 30
Max. height difference 20
Operation range
Cooling
°C
-15 to 46
Heating -15 to 24
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 79
- 73 -
OUTDOOR UNIT
AOYG18-54LB
1-2. Models: AOYG30LBTA and AOYG36LBTA
Typ e
Inverter heat pump
Model name
AOYG30LBTA AOYG36LBTA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A11.813.4
Fan
Airflow rate
Cooling
m3/h
3,600 3,800
Heating 3,600 3,800
Type × Q'ty Propeller × 1
Motor output W 100
Sound pressure level *1
Cooling
dB(A)
53 54
Heating 55 55
Sound power level
Cooling
dB(A)
68 69
Heating 69 70
Heat exchanger type
Dimensions (H × W × D)
mm
798 × 900 × 36.4
Fin pitch 1.3
Rows × Stages 2 × 38
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminum)
Surface treatment Hydrophilic coating (Blue fin)
Compressor
Type × Q'ty Twin rotary × 1
Motor output W 2,100
Refrigerant
Typ e R410A
Factory charge g 2,100
Refrigerant oil
Typ e POE (RB68)
Amount
cm
3
800
Enclosure
Material St eel
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions (H × W × D)
Net
mm
830 × 900 × 330
Gross 970 × 1,050 × 445
Weight
Net
kg
61
Gross 68
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Pre-charge length
m
20
Max. length 50
Max. height difference 30
Operation range
Cooling
°C
-15 to 46
Heating -15 to 24
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measure d in actual installation conditions might be higher than the specified values here.
Page 80
- 74 -
OUTDOOR UNIT
AOYG18-54LB
1-3. Models: AOYG45LBTA and AOYG54LBTA
Typ e
Inverter heat pump
Model name
AOYG45LBTA AOYG54LBTA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A15.720.2
Fan
Airflow rate
Cooling
m3/h
6,750 6,750
Heating 6,200 6,850
Type × Q'ty Propeller × 2
Motor output W 100 × 2
Sound pressure level *1
Cooling
dB(A)
55 55
Heating 55 57
Sound power level
Cooling
dB(A)
68 69
Heating 68 71
Heat exchanger type
Dimensions (H × W × D)
mm
1,260 × 900 × 36.4
Fin pitch 1.3
Rows × Stages 2 × 60
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminum)
Surface treatment Hydrophilic coating (Blue fin)
Compressor
Type × Q'ty Twin rotary × 1
Motor output W 2,100
Refrigerant
Type R410A
Factory charge g 3,350
Refrigerant oil
Type POE (RB68)
Amount
cm
3
800
Enclosure
Material Stee l
Color
Beige
Approximate color of MUNSELL 10YR7. 5/1.0
Dimensions (H × W × D)
Net
mm
1,290 × 900 × 330
Gross 1,430 × 1,050 × 445
Weight
Net
kg
86
Gross 94
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Pre-charge length
m
20
Max. length 50
Max. height difference 30
Operation range
Cooling
°C
-15 to 46
Heating -15 to 24
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 81
- 75 -
OUTDOOR UNIT
AOYG18-54LB
2. Dimensions
2-1. Models: AOYG18LBCA and AOYG24LBCA
Unit : mm
Top view
Front view
Side viewSide view
Bottom view
790
62
20
20
9
110
620
209
175
100
35
328
28
Drain port Ø20 (Drain pipe)Drain port 3-Ø20 (Drain cap)
28
Airflow
352
23
290
26
Page 82
- 76 -
OUTDOOR UNIT
AOYG18-54LB
2-2. Models: AOYG30LBTA and AOYG36LBTA
Unit : mm
Airflow
900
650
830
370
99
196
21
9
77
31 330
400
170
147
12
Top view
Front view
Side view
Bottom view
Page 83
- 77 -
OUTDOOR UNIT
AOYG18-54LB
2-3. Models: AOYG45LBTA and AOYG54LBTA
330
31
650 119132
(
370
)
38
(Liquid)
45
66
46
(
Gas
)
1290
900
21
9
89 21
95
25
50
543
(
Gas valve
)
540
(Liquid valve)
992
21
330
31
12
55
50 120
50
95
167
156
112
21
67
188
265
302
400
51.5 440
625
Ø28
(Cable port)
Ø28
(Cable port)
Ø28
(Cable port)
Ø28
(Cable port)
Ø28 (Cable port)
Ø28 (Cable port)
Pipe port
A
Pipe port
Pipe port
Top view
Front view
Bottom view
Side view
Detail A
Rear view
40
3-way valve
(
Gas
)
3-way valve
(Liquid)
Terminal blocks
1446
1654
87
131
Pipe & cable port
Unit: mm
Page 84
- 78 -
OUTDOOR UNIT
AOYG18-54LB
2-4. Installation space requirement
Provide sufficient installation space for product safety.
Model: Models: AOYG18LBCA and AOYG24LBCA
Single outdoor unit installation
When the upper space is open:
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the rear and sides.
When there are obstacles at the front only. When there are obstacles at the front and rear.
Unit: mm
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
100 or more
250 or more
100 or more
100 or more
600 or more
600 or more
100 or more
100 or more
Max. 200
600 or more
600 or more
100 or more
250 or more
100 or more
Max. 200
Page 85
- 79 -
OUTDOOR UNIT
AOYG18-54LB
Multiple outdoor unit installation
When the upper space is open:
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
When there are obstacles at the front and rear.
Unit: mm
When there are obstacles at the rear and above.
200
or more
1,000 or more
200 or more
1,000 or more
1,500 or more
200 or more
Max. 300
Page 86
- 80 -
OUTDOOR UNIT
AOYG18-54LB
Outdoor unit installation in multi-row
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
!
CAUTION
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
100 or more
200 or more
500 or more
1,000 or more
200 or more
400 or more
1,000 or more
2,000 or more
200 or more
Page 87
- 81 -
OUTDOOR UNIT
AOYG18-54LB
Models: AOYG30LBTA and AOYG36LBTA
Single outdoor unit installation
When the upper space is open:
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the rear and sides.
When there are obstacles at the front only. When there are obstacles at the front and rear.
Unit: mm
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
100 or more
250 or more
300 or more
100 or more
600 or more
600 or more
100 or more
300 or more
Max. 500
600 or more
1,000 or more
100 or more
250 or more
500 or more
Max. 500
Page 88
- 82 -
OUTDOOR UNIT
AOYG18-54LB
Multiple outdoor unit installation
When the upper space is open:
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
When there are obstacles at the front and rear.
Unit: mm
When there are obstacles at the rear and above.
300
250 or more
or more
1,500 or more
250 or more
500 or more
1,500 or more
250 or more
1,500 or more
500 or more
250 or more
250 or more
Max. 300
1,500 or more
Page 89
- 83 -
OUTDOOR UNIT
AOYG18-54LB
Outdoor unit installation in multi-row
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
!
CAUTION
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
150 or more
600 or more
1,000 or more
2,000 or more
500 or more
600 or more
1,500 or more
250 or more
3,000 or more
250 or more
150
1,500 or more
500 or more
250 or more
Page 90
- 84 -
OUTDOOR UNIT
AOYG18-54LB
Models: AOYG45LBTA and AOYG54LBTA
Single outdoor unit installation
When the upper space is open:
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the rear and sides.
When there are obstacles at the front only. When there are obstacles at the front and rear.
Unit: mm
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
150 or more
200 or more
200 or more
300 or more
1000 or more
1000 or more
150 or more
300 or more
Max. 500
1,000 or more
Max. 500
500 or more
250 or more
250 or more
1,500 or more
Page 91
- 85 -
OUTDOOR UNIT
AOYG18-54LB
Multiple outdoor unit installation
When the upper space is open:
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
When there are obstacles at the front and rear.
Unit: mm
When there are obstacles at the rear and above.
300 or more
1,500 or more
500 or more
1,500 or more
1,500 or more
1,500 or more
500 or more
Max. 300
Page 92
- 86 -
OUTDOOR UNIT
AOYG18-54LB
Outdoor unit installation in multi-row
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
!
CAUTION
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
1,000 or more
2,000 or more
600 or more
150 or more
3,000 or more
600 or more
1,500 or more
500 or more
Page 93
- 87 -
OUTDOOR UNIT
AOYG18-54LB
3. Refrigerant circuit
3-1. Models: AOYG18LBCA and AOYG24LBCA
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Compressor
: Cooling : Heating
Muffler
Pressure switch
Sub-accumulator
Th
C
Th
R
Th
D
Th
PI
Th
O
Th
HO
Th
C
: Thermistor (Compressor Temp.)
: Thermistor (Discharge Temp.)
: Thermistor (Outdoor Temp.)
: Thermistor (Heat Exchanger Out Temp.)
Th
D
Th
O
Th
HO
: Thermistor (Room Temp.)
: Thermistor (Pipe Temp.)
Th
R
Th
PI
Page 94
- 88 -
OUTDOOR UNIT
AOYG18-54LB
3-2. Models: AOYG30LBTA and AOYG36LBTA
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Compressor
: Cooling : Heating
Muffler
Pressure switch
Sub-accumulator
Th
C
Th
R
Th
D
Th
PI
Th
O
Th
HO
Th
C
: Thermistor (Compressor Temp.)
: Thermistor (Discharge Temp.)
: Thermistor (Outdoor Temp.)
: Thermistor (Heat Exchanger Out Temp.)
Th
D
Th
O
Th
HO
: Thermistor (Room Temp.)
: Thermistor (Pipe Temp.)
Th
R
Th
PI
Page 95
- 89 -
OUTDOOR UNIT
AOYG18-54LB
3-3. Models: AOYG45LBTA and AOYG54LBTA
㻿㼁㻮 㻭㻯㻹
㻲㻭㻺
㻠㼃㼂
㻯㻹㻼
㻭㻯
㻻㼁㼀㻱㻾
㻴㻱㼄
㻵㻺㻺㻱㻾
㻴㻱㼄
㻲㻭㻺
㻿㼀㻾㻭㻵㻺㻱㻾
㻟㼃㼂
㻟㼃㼂
㻿㼀㻾㻭㻵㻺㻱㻾
㻹㼁㻲㻲㼁㻸㻱㻾
㻱㻱㼂
㻿㻱㻾㼂㻵㻯㻱
㻼㻻㻾㼀
㻼㻾㻱㻿㻿㼁㻾㻱
㻿㻱㻺㻿㻻㻾
㻼㻾㻱㻿㻿㼁㻾㻱
㻿㼃㻵㼀㻯㻴
㻯㻴㻱㻯㻷 㼂㻭㻸㼂㻱
㻹㼁㻲㻲㼁㻸㻱㻾
Page 96
- 90 -
OUTDOOR UNIT
AOYG18-54LB
4. Wiring diagrams
4-1. Models: AOYG18LBCA and AOYG24LBCA
Page 97
- 91 -
OUTDOOR UNIT
AOYG18-54LB
4-2. Model: AOYG30LBTA
Page 98
- 92 -
OUTDOOR UNIT
AOYG18-54LB
4-3. Model: AOYG36LBTA
Page 99
- 93 -
OUTDOOR UNIT
AOYG18-54LB
4-4. Models: AOYG45LBTA and AOYG54LBTA
Page 100
- 94 -
OUTDOOR UNIT
AOYG18-54LB
5. Capacity compensation rate for pipe length and height difference
5-1. Models: AOYG18LBCA and AOYG24LBCA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher than outdoor unit *1
20 - - - - 0.952 0.951 0.951 10 - - 0.980 0.966 0.968 0.967 0.966
7.5 - 0.988 0.984 0.970 0.972 0.971 0.970 5 0.995 0.992 0.988 0.974 0.976 0.975 0.974 0 1.003 1.000 0.996 0.982 0.983 0.983 0.982
Indoor unit is lower
than outdoor unit *2
-5 1.003 1.000 0.996 0.982 0.983 0.983 0.982
-7.5 - 1.000 0.996 0.982 0.983 0.983 0.982
-10 - - 0.996 0.982 0.983 0.983 0.982
-20 - - - - 0.983 0.983 0.982
HEATING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher than outdoor unit *1
20 - - - - 0.954 0.932 0.908 10 - - 0.998 0.975 0.954 0.932 0.908
7.5 - 1.000 0.998 0.975 0.954 0.932 0.908 5 0.989 1.000 0.998 0.975 0.954 0.932 0.908 0 0.989 1.000 0.998 0.975 0.954 0.932 0.908
Indoor unit is lower
than outdoor unit *2
-5 0.984 0.995 0.993 0.970 0.950 0.927 0.903
-7.5 - 0.993 0.991 0.968 0.947 0.925 0.901
-10 - - 0.988 0.965 0.945 0.923 0.899
-20 - - - - 0.935 0.914 0.890
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH