Fujitsu ARXG-KLLAP Series Installation Manual

Page 1
AIR CONDITIONER Duct type
Contents
1. SAFETY PRECAUTIONS .................................................................. 1
1.1. Precautions for using R32 refrigerant ......................................... 2
2. PRODUCT SPECIFICATION ............................................................. 4
2.1. Installation tools .......................................................................... 4
2.2. Accessories ................................................................................ 4
2.3. Pipe requirement ........................................................................4
2.4. Electrical requirement ................................................................. 4
2.5. Optional parts .............................................................................5
3. INSTALLATION WORK ..................................................................... 5
3.1. Selecting an installation location ................................................ 5
3.2. Installation dimensions ...............................................................5
3.3. Installing the unit ......................................................................... 5
3.4. Drain installation ......................................................................... 7
3.5. Pipe installation .......................................................................... 9
3.6. Electrical wiring ......................................................................... 10
3.7. Remote controller setting .......................................................... 13
4. OPTIONAL INSTALLATION WORK ................................................ 13
4.1. Optional kit installation .............................................................. 13
4.2. External input and output .......................................................... 13
4.3. Remote sensor (Optional parts) ............................................... 14
4.4. IR receiver unit (Optional parts) ................................................ 14
4.5. Auto louver grille (Optional parts) ............................................. 14
4.6. Other optional parts .................................................................. 14
4.7. Optional parts cable binding ..................................................... 15
5. REMOTE CONTROL INSTALLATION ............................................. 15
5.1. Group control ............................................................................ 15
5.2. Multiple remote control .............................................................16
5.3. DIP switch 101 setting .............................................................. 16
5.4. Simultaneous multi-system operation ....................................... 17
6. FUNCTION SETTING...................................................................... 17
6.1. Function details ........................................................................ 17
7. TEST RUN ....................................................................................... 19
7.1. Check items .............................................................................. 19
7.2. Operation method ..................................................................... 19
8. FINISHING ...................................................................................... 19
9. CUSTOMER GUIDANCE ................................................................19
10. ERROR CODES .............................................................................. 19
NOTES:
This manual describes how to install the air conditioner described above. Handling
and installation shall only be done by professionals as outlined in this manual.
1. SAFETY PRECAUTIONS
• Be sure to read this manual thoroughly before installation.
• The warnings and precautions indicated in this manual contain important information pertaining to your safety. Be sure to observe them.
• Hand this manual, together with the operating manual, to the customer. Request the customer to keep them on hand for future use, such as for relocating or repairing the unit.
WARNING
Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.
INSTALLATION MANUAL
PART No. 9374342532
[Original instructions] For authorized service personnel only.
WARNING
• The appliance shall be installed, operated and stored in a room with a fl oor area larger than X m².
Amount of refrigerant charge
M (kg)
M 1.22
1.22 < M 1.23
1.23 < M 1.50 2.15
1.50 < M 1.75 2.92
1.75 < M 2.0 3.82
2.0 < M 2.5 5.96
2.5 < M 3.0 8.59
3.0 < M 3.5 11.68
3.5 < M 4.0 15.26
• Installation of this product must be done by experienced service technicians or profes­sional installers only in accordance with this manual. Installation by non-professional or improper installation of the product might cause serious accidents such as injury, water leakage, electric shock, or fi re. If the product is installed in disregard of the instructions in this manual, it will void the manufacturer’s warranty.
• Do not turn on the power until all work has been completed. Turning on the power be­fore the work is completed can cause serious accidents such as electric shock or fi re.
• If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant is exposed to a direct fl ame, it may produce a toxic gas.
• Installation must be performed in accordance with regulations, codes, or standards for electrical wiring and equipment in each country, region, or the installation place.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
• To avoid danger of suffocation, keep the plastic bag or thin fi lm used as the packaging material away from young children.
• The appliance shall be stored in a room without continuously operating ignition sources (for example: open fl ames, an operating gas appliance or an operating electric heater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odour.
CAUTION
• Read carefully all safety information written in this manual before you install or use the air conditioner.
• Install the product by following local codes and regulations in force at the place of installation, and the instructions provided by the manufacturer.
• This product is part of a set constituting an air conditioner. The product must not be installed alone or be installed with a device not authorized by the manufacturer.
• Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 3 mm for this product.
• To protect the persons, earth (ground) the product correctly, and use the power cable combined with an Earth Leakage Circuit Breaker (ELCB).
• This product is not explosion proof, and therefore should not be installed in an explo­sive atmosphere.
• To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 5 min­utes or more before you touch the electrical components.
• This product contains no user-serviceable parts. Always consult experienced service technicians for repairing.
• When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the product.
• Do not touch the aluminum fi ns of heat exchanger built-in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit.
• Do not place any other electrical products or household belongings under the product. Condensation dripping from the product might get them wet, and may cause damage or malfunction to the property.
• Be careful not to scratch the air conditioner when handling it.
Minimum room area
)
X (m
-
1.45
(IEC 60335-2-40)
EnglishDeutschFrançaisEspañolItalianoEλληvIkάPortuguêsРусский
Türkçe
Türkçe
CAUTION
Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to property.
En-1
Page 2
1.1. Precautions for using R32 refrigerant
The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of refrigerant R22 models, some of the piping and installation and service tools are special. (Refer to “2.1. Instal­lation tools”.) Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model, always replace the conventional piping and flare nuts with the R32 and R410A piping and are nuts on the outdoor unit side. For R32 and R410A, the same fl are nut on the outdoor unit side and pipe can be used.
Models that use refrigerant R32 and R410A have a different charging port thread diam­eter to prevent erroneous charging with refrigerant R22 and for safety. Therefore, check beforehand. [The charging port thread diameter for R32 and R410A is 1/2-20 UNF.]
Be more careful than R22 so that foreign matter (oil, water, etc.) does not enter the piping. Also, when storing the piping ,securely seal the opening by pinching, taping, etc. (Handling of R32 is similar to R410A.)
CAUTION
1-Installation (Space)
• That the installation of pipe-work shall be kept to a minimum.
• That pipe-work shall be protected from physical damage.
• The appliance shall not be installed in an unventilated space, if that space is smaller than X m².
Amount of refrigerant charge
M (kg)
M 1.22
1.22 < M 1.23
1.23 < M 1.50 2.15
1.50 < M 1.75 2.92
1.75 < M 2.0 3.82
2.0 < M 2.5 5.96
2.5 < M 3.0 8.59
3.0 < M 3.5 11.68
3.5 < M 4.0 15.26
• That compliance with national gas regulations shall be observed.
• That mechanical connections shall be accessible for maintenance purposes.
• In cases that require mechanical ventilation, ventilation openings shall be kept clear of obstruction.
• When disposing of the product is used, be based on national regulations, properly processed.
2-Servicing 2-1 Service personnel
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certifi cate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accor­dance with an industry recognised assessment specifi cation.
• Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of fl ammable refrigerants.
• Servicing shall be performed only as recommended by the manufacturer.
2-2 Work
• Prior to beginning work on systems containing fl ammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrig­erating system, the precautions in 2-2 to 2-8 shall be complied with prior to conduct­ing work on the system.
• Work shall be undertaken under a controlled procedure so as to minimize the risk of a fl ammable gas or vapour being present while the work is being performed.
• All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out.
• Work in confi ned spaces shall be avoided.
• The area around the workspace shall be sectioned off.
• Ensure that the conditions within the area have been made safe by control of fl am- mable material.
2-3 Checking for presence of refrigerant
• The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially fl ammable atmospheres.
• Ensure that the leak detection equipment being used is suitable for use with fl am- mable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.
2-4 Presence of fi re extinguisher
• If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fi re extinguishing equipment shall be available at hand.
• Have a dry powder or CO
fi re extinguisher adjacent to the charging area.
2
Minimum room area
)
X (m
-
1.45
(IEC 60335-2-40)
CAUTION
2-5 No ignition sources
• No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained fl ammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fi re or explosion.
• All possible ignition sources, including cigarette smoking, should be kept suffi ciently far away from the site of installation, repairing, removing and disposal, during which ammable refrigerant can possibly be released to the surrounding space.
• Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no fl ammable hazards or ignition risks. “No Smoking” signs shall be displayed.
2-6 Ventilated area
• Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work.
• A degree of ventilation shall continue during the period that the work is carried out.
• The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
2-7 Checks to the refrigeration equipment
• Where electrical components are being changed, they shall be fi t for the purpose and to the correct specifi cation.
• At all times the manufacturer’s maintenance and service guidelines shall be followed.
• If in doubt consult the manufacturer’s technical department for assistance.
• The following checks shall be applied to installations using fl ammable refrigerants.
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed.
- The ventilation machinery and outlets are operating adequately and are not obstructed.
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing compo­nents, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
2-8 Checks to electrical devices
• Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures.
• If a fault exists that could compromise safety, then no electrical supply shall be con­nected to the circuit until it is satisfactorily dealt with.
• If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used.
• This shall be reported to the owner of the equipment so all parties are advised.
• Initial safety checks shall include.
- That capacitors are discharged: this shall be done in a safe manner to avoid pos­sibility of sparking.
- That there no live electrical components and wiring are exposed while charging, recovering or purging the system.
- That there is continuity of earth bonding.
3-Repairs to sealed components
• During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc.
• If it is absolutely necessary to have an electrical supply to equipment during servic­ing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
• Particular attention shall be paid to the following to ensure that by working on electri­cal components, the casing is not altered in such a way that the level of protection is affected.
• This shall include damage to cables, excessive number of connections, terminals not made to original specifi cation, damage to seals, incorrect fi tting of glands, etc.
• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of fl ammable atmospheres.
• Replacement parts shall be in accordance with the manufacturer’s specifi cations.
NOTES: The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
4-Repair to intrinsically safe components
• Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
• Intrinsically safe components are the only types that can be worked on while live in the presence of a fl ammable atmosphere.
• The test apparatus shall be at the correct rating.
• Replace components only with parts specifi ed by the manufacturer.
• Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
En-2
Page 3
CAUTION
5-Cabling
• Check that cabling will not be subject to wear, corrosion, excessive pressure, vibra­tion, sharp edges or any other adverse environmental effects.
• The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
6-Detection of fl ammable refrigerants
• Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks.
• A halide torch (or any other detector using a naked fl ame) shall not be used.
7-Leak detection methods
• Electronic leak detectors shall be used to detect fl ammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)
• Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
• Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confi rmed.
• Leak detection fl uids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
• If a leak is suspected, all naked fl ames shall be removed/extinguished.
• If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
8-Removal and evacuation
• When breaking into the refrigerant circuit to make repairs – or for any other purpose –conventional procedures shall be used. However, it is important that best practice is followed since fl ammability is a consid- eration. The following procedure shall be adhered to:
• remove refrigerant
• purge the circuit with inert gas
• evacuate
• purge again with inert gas
• open the circuit by cutting or brazing
• The refrigerant charge shall be recovered into the correct recovery cylinders.
• The system shall be “fl ushed” with OFN to render the unit safe.
• This process may need to be repeated several times.
• Compressed air or oxygen shall not be used for this task.
• Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fi ll until the working pressure is achieved, then venting to atmosphere, and fi nally pulling down to a vacuum.
• This process shall be repeated until no refrigerant is within the system.
• When the fi nal OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
• This operation is absolutely vital if brazing operations on the pipe work are to take place.
• Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
9-Charging procedures
• In addition to conventional charging procedures, the following requirements shall be followed.
- Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
- Cylinders shall be kept upright.
- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to overfi ll the refrigeration system.
• Prior to recharging the system it shall be pressure tested with OFN.
• The system shall be leak tested on completion of charging but prior to commission­ing.
• A follow up leak test shall be carried out prior to leaving the site.
CAUTION
10-Decommissioning
• Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.
• It is recommended good practice that all refrigerants are recovered safely.
• Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant.
• It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before attempting the procedure ensure that:
• mechanical handling equipment is available, if required, for handling refriger­ant cylinders;
• all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person;
• recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed
from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer’s
instructions. h) Do not overfi ll cylinders. (No more than 80 % volume liquid charge). i) Do not exceed the maximum working pressure of the cylinder, even temporarily. j) When the cylinders have been fi lled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and all
isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system un-
less it has been cleaned and checked.
11-Labelling
• Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
• The label shall be dated and signed.
• Ensure that there are labels on the equipment stating the equipment contains fl am- mable refrigerant.
12-Recovery
• When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
• When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
• Ensure that the correct number of cylinders for holding the total system charge are available.
• All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
• Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.
• Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
• The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of ammable refrigerants.
• In addition, a set of calibrated weighing scales shall be available and in good working order.
• Hoses shall be complete with leak-free disconnect couplings and in good condition.
• Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
• Do not mix refrigerants in recovery units and especially not in cylinders.
• If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that fl ammable refrigerant does not remain within the lubricant.
• The evacuation process shall be carried out prior to returning the compressor to the suppliers.
• Only electric heating to the compressor body shall be employed to accelerate this process.
• When oil is drained from a system, it shall be carried out safely.
Explanation of symbols displayed on the indoor unit or outdoor unit.
This symbol shows that this appliance uses a fl ammable
WARNING
CAUTION
CAUTION
CAUTION
refrigerant. If the refrigerant is leaked and exposed to an external igni­tion source, there is a risk of fi re.
This symbol shows that the operation manual should be read carefully.
This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.
This symbol shows that information is available such as the operating manual or installation manual.
En-3
Page 4
2. PRODUCT SPECIFICATION
2.1. Installation tools
Tool name Change from R22 to R32 (R410A)
Pressure is high and cannot be measured with a R22 gauge. To prevent erroneous mixing of other refrigerants,
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
■Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion value or capillary tube may become blocked with contaminants. As an air conditioner using R32 (R410A) incurs pressure higher than when using R22, it is necessary to choose adequate materials.
• Do not use the existing (for R22) piping and fl are nuts. If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause failure, injury, etc. (Use the special R32/R410A materials.)
• Use (refi ll or replace with) specifi ed refrigerant (R32) only. Use of unspecifi ed refriger-
ant can cause product malfunction, burst, or injury.
• Do not mix any gas or impurities except specifi ed refrigerant (R32). Infl ow of air or ap-
plication of unspecifi ed material makes the internal pressure of the refrigerant cycle too high, and may cause product malfunction, burst of piping, or injury.
• For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts. The use of non-prescribed parts can cause serious accidents such as the unit falling, water leakage, electric shock, or fi re.
• Do not turn on the power until all work has been completed.
This manual describes how to install the indoor unit only. To install the outdoor unit or branch box, (if any), refer to the installation manual included in each product.
2.2. Accessories
• For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts. The use of non-prescribed parts can cause serious accidents such as the unit to fall, water leakage, electric shock, or fi re.
• Keep the Installation manual in a safe place and do not discard any other accessories
until the installation work has been completed.
The following installation accessories are supplied. Use them as required.
Name and Shape
Operating manual
Operating manual (CD-ROM)
the diameter of each port has been changed. It is recommended to use gauge with seals -0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
To increase pressure resistance, the hose material and base size were changed. (R32/R410A)
A conventional vacuum pump can be used by installing a vacuum pump adapter. (Use of a vacuum pump with a series motor is prohibited.)
Special gas leakage detector for HFC refrigerant R410A or R32.
WARNING
CAUTION
WARNING
Q’ty
1
1
Name and Shape
Cable tie (large)
Cable tie (medium)
Q’ty
4
3
Coupler heat insulation (large)
Coupler heat insulation(small)
Insulation (for electrical wiring)
The following items are necessary to install this air conditioner. (The items are not includ­ed with the air conditioner and must be purchased separately.)
Hose band
1
Drain hose insulation B
1
2
1
1
Additional materials
Connection pipe assembly Wall cap Connection cable (4-conductor) Wall pipe Drain hose Decorative tape Tapping screws Vinyl tape Putty
Saddle
2.3. Pipe requirement
Model
07, 09, 12,14 Ø 9.52 (0.80) Ø 6.35 (0.80)
Refer to the installation manual for the outdoor unit for description of allowable pipe length and height difference.
• Use pipe with water-resistant heat insulation.
• Wrap heat insulation around both gas pipe and liquid pipe. No heat-insulation work or incorrect heat-insulation work may cause water leaks.
• In a reverse cycle model, use heat insulation with heat resistance above 120 °C.
• If expected humidity of the installation location of refrigerant pipes is higher than 70 %, wrap the heat insulation around the refrigerant pipes. If the expected humidity is between 70 % and 80 %, use heat insulation that has a thickness of 15 mm or more. If the expected humidity is higher than 80 %, use heat insulation that has a thickness of 20 mm or more.
• The use of thinner heat insulation than specifi ed above, may cause a condensation on the surface of the insulation.
• Use heat insulation with thermal conductivity of 0.045 W/(
Gas pipe size (thickness) [mm] Luquid pipe size (thickness) [mm]
18
Ø 12.70 (0.80) Ø 6.35 (0.80)
CAUTION
CAUTION
m•K
) or less, at 20 °C.
2.4. Electrical requirement
The indoor unit is powered from the outdoor unit. Do not power indoor unit from separate power source.
WARNING
Standard for electrical wiring and equipment differs in each country or region. Before you start electrical working, confi rm related regulations, codes, or standards.
2
Cable
Connection cable
Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is
Conductor size [
1.5 (Min) Type 60245 IEC 57
2% or more.
mm
] Type
Remarks
3 cable + Earth (Ground),
1 Ø 230 V
Installation manual (This manual)
Installation template
Washer
En-4
Filter (large) [18 model]
1
Filter (small) [07, 09,12,14 model]
1
Drain hose
8
2
2
1
Page 5
2.5. Optional parts
3.2. Installation dimensions
Refer to each installation manual for the method of installing optional parts.
Parts name Model No. Application
UTY-RNRZ
Wired remote controller
Simple remote controller
IR receiver unit UTY-LBTM For the wireless remote controller Remote sensor unit UTY-XSZX Room temperature sensor
Auto louver grille kit
External connect kit
W-LAN interface UTY-TFSXZ1 For wireless LAN control
UTY-RLR UTY-RVNM UTY-RNNM
UTY-RSR
UTY-RHR
UTY-RSNM
UTD-GXTA-W
UTD-GXTB-W
PCB terminal For control input port
UTY-XWZXZG For control output port
For air conditioner operation (2-wired type)
For air conditioner operation (3-wired type)
For air conditioner operation (2-wired type)
For air conditioner operation (3-wired type)
Air outlet grille with outo louver (07, 09,12,14 models)
Air outlet grille with outo louver (18 model)
3. INSTALLATION WORK
WARNING
Do not move the appliance by holding the indoor unit pipes. (The stress applied to the pipe joints may cause the fl ammable gas to leak during operation.)
3.1. Selecting an installation location
Especially, the installation place is very important for the split type air conditioner because it is very diffi cult to move from place to place after the fi rst installation.
Provide a Service access for inspection purposes. Do not place any wiring or illumination in the service space, as they will impede service.
Strong and durable ceiling
Indoor unit
Left side
150 mm or more
400 mm or more
Right side
300 mm or more
20 mm or more
240 mm or more
20 mm or more
Service access Ceiling
(When no ceiling)
2500 mm or more
Floor
Adjust the wind direction in the room depending on the shape of blow out opening.
Service access
WARNING
Select installation locations that can properly support the weight of the indoor. Install the units securely so that they do not topple or fall.
CAUTION
• Do not install the unit in the following areas:
- Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
- Area fi lled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
- Area where is close to heat sources.
- Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
- Area that can cause combustible gas to leak, contains suspended carbon fi bers or ammable dust, or volatile in fl ammables such as paint thinner or gasoline.
- If gas leaks and settles around the unit, it can cause a fi re.
- Area where animals may urinate on the unit or ammonia may be generated.
• Do not use the unit for special purposes, such as storing food, raising animals, grow­ing plants, or preserving precision devices or art objects. It can degrade the quality of the preserved or stored objects.
• Install the unit where drainage does not cause any trouble.
• Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote control cable at least 1 m away from a television or radio receivers. The purpose of this is to prevent TV reception interference or radio noise. (Even if they are installed more than 1 m apart, you could still receive noise under some signal conditions.)
• If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
• Decide the mounting position with the customer as follows:
(1) Install the indoor unit in a location having suffi cient strength to support the weight of
the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Locate where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibration is not amplifi ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the fi lter can be removed.
Unit
Control box
300 mm
or more
100 mm
or more
400 mm or more
Service space
3.3. Installing the unit
WARNING
• Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration. If the instal­lation location is not strong enough, the indoor unit may fall and cause injuries.
• If the work is done with the panel frame only, there is a risk that the unit will come loose. Please take care.
3.3.1. Unit installation example
■Connect the locally purchased duct:
(1) Inlet side
• Connect the duct to the locally purchased inlet fl ange.
• Connect the fl ange to the body with the locally purchased tapping screws.
• Wind the inlet fl ange connecting to the duct with the aluminum tape etc. to avoid the air discharge.
CAUTION
When the duct is connected to inlet side, remove contained fi lter and surely attach locally purchased fi lter at inlet opening.
(2) Outlet side
• Connect the duct with adjusting inside of outlet fl ange.
• Wind the outlet fl ange connecting to the duct with the aluminum tape etc. to avoid the air discharge.
• Insulate the duct to avoid the dew condensation.
En-5
Page 6
CAUTION
• Check that duct work does not exceed the range of external static pressure of equip­ment.
• Make sure to insulate ducts to avoid the dew condensation.
• Make sure to insulate between ducts and walls if metal ducts are used.
• Please explain handling and washing methods of locally purchased materials to the customer.
• To prevent people from touching the parts inside the unit, be sure to install grilles on the inlet and outlet ports. The grilles must be designed in such a way that cannot be removed without tools.
• When connecting the duct to the outlet port of the indoor unit, be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port.
• Set the static pressure outside the unit to 90 Pa or less (the allowable range is be­tween 0 and 90 Pa.)
■Replace the cover as follows:
• Remove the screws, and then remove cover and fan guard.
• Install the cover with the screws as shown in the illustration below. Model Screw
07, 09, 12, 14 9
18 11
Screw
Cover
Fan guard
Outlet side
Inlet side
A 650 mm 850 mm B P200×2=400 mm P200×3=600 mm
07, 09, 12,14 models 18 model
CAUTION
• Be sure to install the air inlet grille and the air outlet grille for air circulation. The cor­rect temperature cannot be detected.
• Grills must be fi xed so that man cannot touch indoor unit fan and exchanger, and cannot be removed by only hand operation without tool.
• Be sure to install the air fi lter in the air inlet.
If the air fi lter is not installed, the heat exchanger may be clogged and its perfor-
mance may decrease.
3.3.2. Install the fi lters
• Install the fi lters to the unit.
Side inlet - Side outlet
Insulation material (Locally purchased)
Aluminum tape
Flange (Locally purchased)
Air
Duct (Locally purchased)
Side inlet - Side outlet (Duct)
Insulation material (Locally purchased)
Aluminum tape
Flange (Locally purchased)
Air
Duct (Locally purchased)
Bottom inlet - Side outlet
Duct (Locally purchased)
Intake grille (Locally purchased)
(Locally purchased)
Intake grille
Air
Flange (Locally purchased)
Aluminum tape
Tapping screw for ange connection
(M4 x 10mm /
Air
purchased)
Locally
Filter (accessories)
Unit
Filter
3.3.3. Position the ceiling hole and hanging bolts
• Using the installation template, drill holes for bolts (4 holes).
Installation template (accessory)
Air
Drilling position for bolts
Air
Intake grille (Locally purchased)
En-6
377 mm
A
Air
A 734 mm 934 mm
07, 09, 12, 14 models 18 model
Page 7
3.3.4. Fix the unit
(1) Hang the unit
Nut A (Locally purchased)
Washer (accessories)
Nut B (Locally purchased)
Hanger bolt
Hanger bolt
Hanger
3.4. Drain installation
3.4.1. Installing drain pipes
WARNING
• Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat ex­change erosion may occur)
• Insulate the parts properly so that water will not drip from the connection parts.
• Check for proper drainage after the construction by using the visible portion of trans­parent drain port and the drain piping fi nal outlet on the body.
CAUTION
Do not apply adhesive agent on the drain port of the body.
(Use the attached drain hose and connect the drain piping)
Nut A
Hanger
(Locally purchased)
Washer (accessories)
Unit
Nut B (Locally purchased)
20mm length
Cover
* It might become diffi cult to open and shut the Cover /control box cover when the length
exceeds 20mm.
(2) Leveling
Base horizontal direction leveling on top of the unit.
Ceiling
Level
■When drain pump is used
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
• Do not perform a rise, trap and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.
GOOD
Locally arranged pipe
Max. 300 mm
Gap of 1.5 to 2 m
Supporter
VP25 [O.D 32 mm or more]
700 mm or less
Horizontal or upward gradient
PROHIBITED
Air bleeding
Trap
Rise
OK
PROHIBITED
10 mm or less
Level
Air
OK PROHIBITED
10 mm or less
CAUTION
• Leave a space of 100 mm or more between the inlet port and the ceiling.
• Fasten the unit securely with Special nuts A and B.
Observe the following procedures to construct centralized drain pipe fi ttings.
VP30 or more [O.D 38 mm or more]
Downward gradient 1/100 or more
700 mm or less
■When drain pump is not used (natural drainage)
CAUTION
Set “Drainage function setting (DIP switch 101-1)” in “5.3. DIP switch 101 setting”
If the drain pump is not used, please replace with the drain cap.
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
• Do not perform a rise, trap and air bleeding.
En-7
Page 8
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.
GOOD
D
ownward gradient
Gap of 1.5 to 2 m
2.5-5.0 mm
(2) Be sure to connect Drain pipe with adhesive (polyvinyl chloride) so that there is no
leakage.
Applying area of adhesive
Joint pipe (Locally purchased)
Drain pipe (VP25) (Locally purchased)
Supporter
100 mm or more
VP25 [O.D 32 mm or more]
PROHIBITED
Locally arranged pipe
Air bleeding
Trap
Rise
Observe the following procedures to construct centralized drain pipe fi ttings.
VP30 or more [O.D 38 mm or more]
Downward gradient 1/100 or more
3.4.2. Installing the drain hose (accsessory) and drain pipe (locally purchased)
(1) Be sure to use supplied Drain hose and Hose band
Hose band (accessory)
Drain hose (accessory)
4 mm or less
CAUTION
Do not connect to the Drain hole with adhesive. Using adhesive may cause damage and water leaks.
(3) After installing the Drain hose, check if the drainage is smooth.
CAUTION
To prevent excessive force on Drain hose, avoid bends or twists. (To bend or twist may cause water leaks.)
(4) After checking for drainage, attach the Drain hose insulation B to insulate, following
the instructions as in the fi gures. To avoid space with Drain hose and Hose band, press fi rmly the Drain hose insulation B.
Ensure there is no space.
• STEP 1 to STEP 3
Butt the insulation against the unit.
Drain hose insulation B (accessory)
Unit
Slit
Drain hole
Hard PVC side
Hose band
4 mm or less
20 mm
Drain hose
Hose band
Fasten the Hose band at the position where horizontal against ground. The Hose band must be positioned at the right side of the Drain hose as in the fi gure.
Press fi rmly
Press fi rmly
Roll the insulation over the joint.
STEP 1
Press fi rmly
Slit
Press fi rmly
STEP 2
Slit
Press fi rmly
STEP 3
En-8
• FINISH Check that there is no gap between the unit and the drain hose insulation.
Page 9
• When drain pump is used.
• When drain pump is not used. (Natural drainage)
Do not cover the panel window.
When using conventional fl are tools to fl are R32 pipes, the dimension A should be approx- imately 0.5 mm more than indicated in the table (for fl aring with R32 fl are tools) to achieve the specifi ed fl aring. Use a thickness gauge to measure the dimension A.
Width across
flats
NOTES: The fl are nut specifi cation is compliant with ISO14903.
Pipe outside diameter [mm (in.)]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
Width across flats of Flare
nut [mm]
■Bending pipes
Do not cover the control box cover.
NOTES: Check for drainage
Pour about 1 liter of water from the position shown in the diagram or from the airfl ow outlet to the dew tray. Check for any abnormalities such as strange noises and whether the drain pump functions normally.
CAUTION
Make sure the drain water is properly drained.
3.5. Pipe installation
3.5.1. Pipe connection
CAUTION
Tighten the flare nuts with a torque wrench using the specified tightening method. Otherwise, the fl are nuts could break after a prolonged period, causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a fl ame.
■Flaring
Use special pipe cutter and fl are tool designed for R410A or R32 pipework. (1) Cut the connection pipe to the necessary length with a pipe cutter. (2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs. (3) Insert the fl are nut (always use the fl are nut attached to the indoor unit(s) and outdoor
unit or branch box respectively) onto the pipe and perform the fl are processing with a are tool. Use the special R410A or R32 fl are tool, or the conventional fl are tool. Leak- age of refrigerant may result if other fl are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Check if [L] is flared uniformly
B
Die
A
Pipe
and is not cracked or scratched.
L
CAUTION
• To prevent breaking of the pipe, avoid sharp bends.
• If the pipe is bent repeatedly at the same place, it will break.
• The pipes are shaped by your hands. Be careful not to collapse them.
• Bend R70 mm or more with a pipe bender.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it diffi cult to bend or stretch them anymore.
• Do not bend or stretch the pipes more than 3 times.
• When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the insulating pipe with a sharp cutter as shown on the right, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insu­lating pipe back on the pipe, and secure it with tape.
Insulating pipe
Pipe
Cutter
Cut line
■Flare connection
CAUTION
• Be sure to install the pipe against the port on the indoor unit correctly. If the center-
ing is improper, the fl are nut cannot be tightened smoothly. If the fl are nut is forced to turn, the threads will be damaged.
• Do not remove the fl are nut from the indoor unit pipe until immediately before con-
necting the connection pipe.
• Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order
to tighten the fl are nut correctly.
• Tighten the fl are nuts with a torque wrench using the specifi ed tightening method.
Otherwise, the fl are nuts could break after a prolonged period, causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a fl ame.
• Connect the piping so that the control box cover can easily be removed for servic-
ing when necessary.
• In order to prevent water from leaking into the control box, make sure that the pip-
ing is well insulated.
When the flare nut is tightened properly by your hand, hold the body side coupling with a wrench, then tighten with a torque wrench. (Refer to the following table for the flare nut tightening torques.)
Tighten with 2 wrenches.
Holding wrench
Torque wrench
Indoor unit pipe (Body side)
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
Do not remove the cap from the connection pipe before connecting the pipe.
Flare nut
Connection pipe
Pipe outside diameter
[mm (in.)]
6.35 (1/4)
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
Dimension A [mm]
Flare tool for R32, clutch
type
0 to 0.5
Dimension B [mm]
9.1
En-9
Page 10
3.6. Electrical wiring
WARNING
• Electrical work must be performed in accordance with this Manual by a person certifi ed under the national or regional regulations. Be sure to use a dedicated circuit for the unit. An insuffi cient power supply circuit or improperly performed electrical work can cause serious accidents such as electric shock or fi re.
• Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
• For wiring, use the prescribed type of cables, connect them securely, making sure that there are no external forces of the cables applied to the terminal connections. Improperly connected or secured cables can cause serious accidents such as over­heating the terminals, electric shock, or fi re.
• Securely install the electrical box cover on the unit. An improperly installed electrical box cover can cause serious accidents such as electric shock or fi re through exposure to dust or water.
• Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit could result.
• Use the included connection cables and power cables or ones specifi ed by the manufacturer. Improper connections, insuffi cient insulation, or exceeding the allowable current can cause electric shock or fi re.
• Do not modify the power cables, use extension cables, or use any branches in the wiring. Improper connections, insuffi cient insulation, or exceeding the allowable current can cause electric shock or fi re.
• Match the terminal block numbers and connection cable colors with those of the outdoor unit or branch box. Erroneous wiring may cause burning of the electric parts.
• Securely connect the connection cables to the terminal board. In addition, secure the cables with wiring holders. Improper connections, either in the wiring or at the ends of the wiring, can cause a malfunction, electric shock, or fi re.
• Always fasten the outside covering of the connection cable with the cable clamp. (If the insulator is chafed, electric leakage may occur.)
• Install an earth leakage breaker. In addition, install the earth leakage breaker so that the entire AC main power supply is cut off at the same time. Otherwise, electric shock or fi re could result.
• Always connect the earth (ground) cable. Improper earthing (grounding) work can cause electric shocks.
• Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
• Connect the connection cable fi rmly to the terminal board. Imperfect installation may cause a fi re.
• Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating may be produced and possibly cause heavy damage inside the unit.
CAUTION
• Be careful not to generate a spark as follows for using a fl ammable refrigerant.
- Do not remove the fuse while the power is on.
- Do not disconnect the wiring while the power is on.
- It is recommended to position the outlet connection in a high position. Place the cords so that they do not get tangled.
• Earth (Ground) the unit. Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a telephone earth (ground) cable. Improper earthing (ground­ing) may cause electric shock.
• Install the remote controller cables so as not to be direct touched with your hand.
• Do not connect power supply cables to the transmission or remote controller termi­nals, as this will damage the product.
• Never bundle the power supply cable and transmission cable, remote controller cable together. Separate these cable by 50 mm or more. Bundling these cables together will cause miss operation or breakdown.
• When handling PCB, static electricity charged in the body may cause malfunction of the PCB. Follow the cautions below:
- Establish an earth (a ground) for the indoor and outdoor units and peripheral devices.
- Cut power (breaker) off.
- Touch metal part of the indoor and outdoor units for more than 10 seconds to discharge static electricity charged in the body.
- Do not touch terminals of parts and patterns implemented on PCB.
• Be sure to refer to the above diagram for do correct fi eld wiring. Wrong wiring causes malfunction of the unit.
• Check local electrical rules and also any specifi c wiring instructions or limitation.
3.6.1. Wiring system diagram
■Standard pair
Connection cable
Indoor unit
Wired remote controller cable 2-wire type
Indoor unit
Earth (Ground) line
Y1 Y2
Power line
Control line
Red
White
Outdoor unit
Wired remote controller
R
W
Y3
1 2
3-wire type
Indoor unit
Y1 Y2 Y3
1 2
*Earth (Ground) the remote controller if it has a earth (ground) line.
■Flexible multi
Connection cable
Indoor unit Outdoor unit
Indoor unit
Wired remote controller cable
2-wire type
Indoor unit
3-wire type
Indoor unit
Remote controller cable
Red
White
Black
Remote controller cable
Earth (Ground) line
Power line
Control line
Red White
Remote controller cable
Wired remote controller
R
W
B
UNIT A
UNIT B
Wired remote controller
Wired remote controller
En-10
Red White Black
Remote controller cable
*Earth (Ground) the remote controller if it has a earth ground) line.
Page 11
■Simultaneous twin (18 model only)
Connection cable
Indoor unit
(Primary)
Junction box (Locally purchased)
Earth (Ground) line
Outdoor unit
■Simultaneous triple (18 model only)
Connection cable
Indoor unit
(Primary)
Junction box (Locally purchased)
Earth (Ground) line
Outdoor unit
Indoor unit
(Secondary)
Wired remote controller cable 3-wire type only
Indoor unit
(Primary)
Red White Black
Remote controller cable
Indoor unit
(Secondary)
*Earth (Ground) the remote controller if it has a earth (ground) line.
• Connect the remote controller wires to the primary unit.
Bus wire (Locally purchased, remote controller cable) Max length: 500 m
Earth (Ground) line
Control line
Power line
Wired remote controller
Indoor unit
(Secondary)
Indoor unit
(Secondary)
Wired remote controller cable 3-wire type only
Indoor unit
(Primary)
Indoor unit
(Secondary)
Earth (Ground) line
Control line
Power line
Wired remote controller
Red White
Black
Remote controller cable
Bus wire (Locally purchased, remote controller cable) Max length: 500 m
Indoor unit
(Secondary)
*Earth (Ground) the remote controller if it has a earth (ground) line.
• Connect the remote controller wires to the primary unit. Wired remote controller is recommended using simultaneous twin or triple connection.
En-11
Page 12
3.6.2. Connection cable preparation
■Connection cable
Keep the earth (ground) wire longer than the other wires.
20 mm
Earth (Ground) wire
30mm or more
• Use a 4-core wire cable.
■Remote controller cable
For 2-wire type
30 mm 30 mm
For 3-wire type
Connection cable
■Connection cable
■Remote controller cable
Earth (ground)
DIP switch
12 3
Outdoor unit
Control line
Power line
Connection cable (power supply)
Print circuit board
(PCB)
3.6.3. How to connect wiring to the terminals
■Caution when wiring cable
To strip off the insulation of a lead wire, always use a special tool such as a wire stripper. If there is no special tool, carefully strip off the insulation by using a knife or other utensil.
(1) Use ring terminals with insulating sleeves as shown in the fi gure to connect to the
terminal block.
(2) Securely clamp the ring terminals to the wires by using an appropriate tool so that the
wires do not come loose.
Strip : 10 mm
Ring terminal
Sleeve
(3) Connect specifi ed wires securely, and fasten them so that there is no stress applied on
the terminals.
(4) Use a screwdriver with an appropriate bit size to tighten the terminal screws. Using of
screwdriver with inappropriate bit size will damage the screw heads, and the screws will not be tightened properly.
(5) Do not overtighten the terminal screws. Otherwise, the screws may break.
Screw with special washer
Wire
Ring terminal
Screw with special washer
Ring terminal
Terminal blocks
Wire (6) Refer to the table for the terminal screw tightening torques. (7) Please do not fi x 2 power supply cables with 1 screw.
Tightening torque [N·m (kgf·cm)]
M4 screw 1.2 to 1.8 (12 to 18)
3.6.4. Connection wiring
CAUTION
• Be careful not to mistake the power supply cable and connection wires when install­ing.
• Install so that the wires for the remote controller will not come in contact with other connection wires.
(1) Remove the control box cover (2) Connect the connection cable.
Cover
3-wire type
Y1 Y2
Y3 1 2 Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
Black
White
2-wire type
Y3 1 2
TO REMOTE CONTROL UNIT Ex IN
White
Red
Red
EarthEarth
Remote controller
Remote controller cable
Factory setting “2 WIRE”
Remote controller
Connecting the Optional parts
Remote controller cable
Set to “3 WIRE”
*Earth (Ground) the remote controller if it has a earth (ground) wire.
NOTES: Be sure to change the DIP SW to the corresponding remote controller.
When a 2-wire remote controller is connected to a “3WIRE” setting, power will
not be supplied.
When a 3-wire remote controller is connected to a “2WIRE” setting, a
communication error will be detected.
(3) After wiring is complete, secure the remote controller cable, connection cable with
the cable clamps.
Y3 1 2
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
Remote controller cable
Connection cable
12 3
(power supply)
Cable clamp
En-12
Screw
Connection cable (power supply)
Avoid touching the ceiling with the wiring
Ceiling
Do not bind the power supply cable and other cables together.
Cable tie (medium, accessories)
Avoid covering the air inlet with the wiring.
Page 13
(4) Seal the cable outlet or other gaps with putty to prevent dew condensation or insect
from entering the electric control box.
(5) Replace the control box cover.
CAUTION
Do not bundle the remote controller cable, or wire the remote controller cable in par­allel, with the indoor unit connection wire (to the outdoor unit) and the power supply cable. It may cause erroneous operation.
Ter min al
Y1 Y2
Y3 1 2
TO REMOTE CONTROL UNIT Ex IN
3.7. Remote controller setting
To install and set the remote controller, refer to the installation manual of the remote controller.
4. OPTIONAL INSTALLATION WORK
4.1. Optional kit installation
WARNING
Regulation of cable differs from each locality, refer in accordance with local rules.
CN65
CN11
Y3 1 2
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
12 3
This air conditioner can be connected with the following optional kits. For details on how to install optional parts, refer to the installation manual included in each item.
Connector No. Option type
CN47*1 Connect wire (UTY-XWZXZG)
CN8 Remote sensor (UTY-XSZX) CN48 IR Receiver (UTY-LBTM) CN11 Auto louver grille (UTD-GXT-W)
CN65*2 Other optional parts
*1: For external output terminal setting, refer to Function No.60 in “6. FUNCTION SET-
TING”.
*2: Other options (WLAN adapter, converters, etc.) may be connectable. Please refer to
the technical data for details.
NOTES:
Options connecting to CN65 cannot be used at the same time.
4.2. External input and output
4.2.1. External input
• Indoor unit functions such as Operation/Stop or Forced stop can be done by using indoor unit terminals.
• “Operation/Stop” mode or “Forced stop” mode can be selected with function setting of indoor unit.
A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m (492 ft.).
• Use an external input and output cable with appropriate external dimension, depending on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
CN47
CN48
CN8
Connected device
Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry contact terminal.
*1
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
Ter minal (External in)
■Operation behavior
Input signal type
ON
Edge
OFF
When function setting is “Operation/Stop” mode 1.
Input signal Command
OFF ON Operation ON OFF Stop
When function setting is “Forced stop” mode.
Input signal Command
OFF ON Forced stop ON OFF Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
When function setting is “Operation/Stop” mode 2.
Input signal Command
OFF ON Operation ON OFF Stop (R.C. disabled)
4.2.2. External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m (82 ft.).
• Use an external input and output cable with appropriate external dimension, depending on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
■Output select
When interlocking with external device
Connected
device
Relay (locally purchased)
PCB
CN47
or
When displaying “Operation/Stop”
Resistor
LED
PCB
CN47
Connected device
En-13
Page 14
Operation behavior
*If function setting “60” is set to “00”
Function setting Status Output voltage
00
09
60
10
11
Stop 0V
Operation DC 12 V
Normal 0V
Error DC 12 V
Indoor unit fan stop 0V
Indoor unit fan operation DC 12 V
External heater OFF 0 V
External heater ON DC 12V
4.2.3. Connection methods
■Wire modifi cation
• Remove insulation from wire attached to wire kit connector.
• Remove insulation from locally purchased cable. Use crimp type insulated butt connector to join fi eld cable and wire kit wire.
• Connect the wire with connecting wire with solder.
IMPORTANT:
Be sure to insulate the connection between the wires.
Locally purchased
Option parts External output wire
Solder and insulate the connected parts.
• Connecting wires to the terminals.
Use ring terminals with insulating sleeves to connect to the terminal block.
• Connection terminals and wiring arrangement (Refer to “4.6. Other optional parts”)
4.3. Remote sensor (Optional parts)
4.3.1. Connection method
• Remove the existing connector and replace it with the remote sensor connector (ensure that the correct connector is used).
• The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry.
• Connection terminals and wiring arrangement. (Refer to “4.6. Other optional parts”)
4.3.2. Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated below.
• Function Number “30”:
Set the Setting Number to “00”. (Default)
• Function Number “31”:
Set the Setting Number to “02”.
* Refer to “6. FUNCTION SETTING” for details about Function number and Setting
value
4.4. IR receiver unit (Optional parts)
• For the installation method, please refer to the installation manual of IR receiver unit.
4.4.1. Connection method
• Use 7 pins for receiver unit cable.
• At fi rst, connect the receiver unit cable to the controller PCB.
• Attach the core that comes between controller PCB and the clamp.
• Connection terminals and wiring arrangement. (Refer to “4.6. Other optional parts”).
4.5. Auto louver grille (Optional parts)
4.5.1. Connection method
• Wiring arrangement
Controller PCB
Y3 1 2
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
CN11
DIP SW 101 ( " 2 " : ON)
CAUTION
To protect the cable insulation after opening a knockout hole, remove any burrs from the edge of the hole.
12 3
(c) Block gaps with insulation
(a) Opening this
knockout hole
Auto louver grille cable
(accessories)
(b) Bushing
(accessories of optional parts)
Cable tie (medium, accessories)
4.6. Other optional parts
4.6.1. Connection method
• Connection terminals and wiring arrangement
In following fi gure, all the possible connections are done for description. In actual installation, connections will differ according to each installation requirements.
Controller PCB
CN65
CN47
CN48
Y3 1 2
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
External output
External input
En-14
CN8
Core
12 3
Page 15
4.7. Optional parts cable binding
Bushing**
Insulation
Other optional parts cables
(2) Set the R.C. address (DIP switch setting) Set the R.C. address of each indoor unit using the DIP switch on the indoor unit
circuit board.
Air inlet
Remote controller cable
Cable tie
(medium,
accessories)
Auto louver grille cable
Power supply cable
Avoid touching the ceiling with the wirings.
* Use an accessory of indoor unit or optional parts for cable tie. ** Use an accessory of optional parts for bushing.
• Do not bind the power supply cable and other cables together.
Avoid covering the air
inlet with the wirings.
Ceiling
CAUTION
To protect the cable insulation after opening a knockout hole, remove any burrs from the edge of the hole.
5. REMOTE CONTROL INSTALLATION
5.1. Group control
NOTES: Group control cannot be used together with W-LAN adapter.
A number of indoor units can be operated at the same time using a single remote controller. *When different types of indoor units (such as wall mounted type and cassette type, cas-
sette type and duct type, or other combinations) are connected using group control sys­tem, some functions may no longer be available.
(1) Connect up to 16 indoor units in a system.
I.U. I.U. I.U. I.U.
Y3 1 2
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
12 3
SW100
(a) 2-wire type
DIP switch (RC AD SW)...Factory setting “00” Since the remote controller address settings are automatically confi gured, you do not need to confi gure them. If confi guring manually, it is necessary to confi gure both the indoor unit and the remote controller. For details, please refer to the remote controller installation manual.
(b) 3-wire type
DIP switch (RC AD SW)...Factory setting “00”
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from “00”.
Setting
Remote controller address
Example
If 4 indoor units are connected.
Indoor unit 1
RC AD SW
00
Setting
range
00 to 15
Indoor unit 2 Indoor unit 3 Indoor unit 4
RC AD SW
01
Setting example 00
RC AD SW
02
Switch 100
ON
1234
RC AD
RC AD SW
03
BCDE
A
Remote controller
A, B, C, D, E : Remote controller cable. A+B+C+D+E 500 m.
Example of wiring method (2-wire type)
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
123 123 123 123
123
Y
1 Y2
Remote controller
Remote con­troller cable
Remote controller cable
Remote controller
Set the R.C. address in accordance with the table below.
Indoor unit
NOTES:
Be sure to set consecutive R.C. address. The indoor units cannot be operated if a number is skipped.
R.C. address
1 00 OFF OFF OFF OFF 2 01 ON OFF OFF OFF 3 02 OFF ON OFF OFF 4 03 ON ON OFF OFF 5 04 OFF OFF ON OFF 6 05 ON OFF ON OFF 7 06 OFF ON ON OFF 8 07 ON ON ON OFF
9 08 OFF OFF OFF ON 10 09 ON OFF OFF ON 11 10 OFF ON OFF ON 12 11 ON ON OFF ON 13 12 OFF OFF ON ON 14 13 ON OFF ON ON 15 14 OFF ON ON ON 16 15 ON ON ON ON
1234
Outdoor unit 1
Outdoor unit 2
DIP SWITCH No.
Outdoor unit 3
Outdoor unit 4
Remote controller
R.C. address
(DIP switch setting)
Indoor unit 1
Indoor unit 2
00 01 02 03
: Transmission cable, Power supply cable : Remote controller cable
Indoor unit 3
Indoor unit 4
: Connection cable
En-15
Page 16
■Settings when simultaneous Multi is included
(3) Set the refrigerant circuit address (Remote controller setting)
1. Turn on all of the indoor units. * Turn on the indoor unit with the R.C. address 00 last.
(Within 1 minute)
2. Set the refrigerant circuit address. Assign the same number to all of the indoor units connected to an outdoor unit. (The unit is factory-set to “00”)
Refrigerant circuit address
Function
Number
Setting Value
00 01
02 00 to 15 14 15
(4) Set the “primary” and “secondary” settings. (Remote controller setting) (Set the indoor unit that is connected to the outdoor unit using a transmission cable as the
“primary”.)
Function Number
Primary
Secondary 01
After completing the function settings, turn off all of the indoor units, and then turn them back on. * If error code 21, 22, 24, or 27 is displayed, there may be an incorrect
setting. Perform the remote controller setting again.
51
Setting Value
00
NOTES:
• When different indoor unit models are connected using the group control system, some functions may no longer be available.
• If the group control system contains multiple units that are operated simultaneously, con­nect and set the units as shown below.
• Auto-changeover operates under the same mode with model R.C. address 00.
• It should not be connected to any other Gr that is not of the same series (A**G only).
Standard
Outdoor unit 1
Remote controller
R.C. address
(DIP switch setting)
Refrigerant circuit address setting
(Function number 02)
Primary/Secondary setting
(Function number 51)
: Transmission cable, Power supply cable : Remote controller cable
pair
Indoor unit 1
Standard
pair
Outdoor unit 2
Indoor unit 2
Simultaneous
twin
Outdoor unit 3
Indoor
Indoor
unit 3
unit 4
Simultaneous
triple
Outdoor unit 4
Indoor
Indoor
unit 5
unit 6
: Power supply cable : Connection cable
Indoor unit 7
5.2. Multiple remote control
Up to 2 remote controllers can be used to operate one indoor unit
CAUTION
Multiple installation method described above is prohibited to combine 3 Wired type with 2 Wired Type.
I.U.
A
Primary Primary Secondary
A, B : Remote controller cable. (Refer to “2.4. Electrical requirement”) A ≤ 500 m, A+B ≤ 500 m
The timer and self-diagnosis functions cannot be used on the secondary units.
(1) Wiring method (indoor unit to remote controller)
Indoor unit
Primary unit
Remote controller
(2) Remote controller DIP switch 1 setting Set the remote controller DIP switch 1 No. 2 according to the following table.
DIP SW 1-No. 2
Primary unit
OFF
Secondary unit
ON
I.U.
AB
Remote con­troller cable
Secondary unit
5.3. DIP switch 101 setting
If contained drain pump is not used, set the drainage function to “Disable” in the drainage function switching.
The auto louver grille setting (optional parts) can be used when the it is mounted. For the setting method, refer to “4.5. Auto louver grille (Optional parts)”.
The fan delay setting can be used when the auxiliary heater is mounted. When the operation is stopped when the indoor unit is operating with an auxiliary heater, the operation continues 1 minutes.
Change the following settings by using the DIP switch.
(... Factory setting)
DIP switch 101
1 Disable Enable Drainage function setting 2 Enable Disable ♦ Auto louver grille setting 3 Enable Disable ♦ Fan delay setting
Switching position
DIP SW state
ON OFF
Details
En-16
DIP SW 101
Y3 1 2
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
12 3
Page 17
5.4. Simultaneous multi-system operation
CAUTION
• When setting DIP switches, do not touch any other parts on the circuit board directly with your bare hands.
• Be sure to turn off the main power.
• Ensure to use a 3-wire type wired remote controller. (Set the DIP switch to 3-wire type.)
• When using a simultaneous multi system, a WLAN adapter cannot be used.
• If connected to an indoor unit that supports R410A, an error message is displayed. Check the machine type of the indoor unit to connect, and ensure to use an indoor unit support­ing R32.
• By combining with an outdoor unit, 2 units for twin and 3 units for triple indoor units, can be switched on/off simultaneously.
(1) Wiring method
• Refer to “3.6. Electrical wiring” for wiring procedure and wiring method.
• The indoor unit is connected the outdoor unit using a transmission cable is “primary”.
• Connect the remote controller wire to the primary unit.
■Twin type ( 18 model only )
Outdoor
unit
3. After completing the function settings, turn off all of the indoor units, and then turn them back on.
* If error code 21, 22, 24 or 27 is displayed, there may be an incorrect setting.
Perform the remote controller setting again.
■Twin type ( 18 model only )
Outdoor
unit
Remote controller
R.C. address
(DIP switch setting)
Primary/Secondary setting
(Function number 51)
Indoor unit 1
[Primary]
Indoor unit 2
[Secondary]
■Triple type ( 18 model only )
Outdoor
unit
Remote controller
Indoor unit 1
[Primary]
Indoor unit 2
[Secondary]
■Triple type ( 18 model only )
Outdoor
unit
Remote controller
: Transmission cable, Power supply cable
(2) Set the R.C. address (DIP switch setting )
Set the R.C. address of each indoor unit using the DIP switches on the indoor unit circuit board. (Refer to the following table and fi gure.) The DIP switches are normally set to make the R.C. address 00.
Indoor unit 1
[Primary]
Indoor unit 2
[Secondary]
Indoor unit 3
[Secondary]
: Power supply cable : connection cable: Remote controller cable
Indoor unit R.C. address DIP SWITCH No.
1234
1 00 OFF OFF OFF OFF
2 01 ON OFF OFF OFF
3 02 OFF ON OFF OFF
Y3 1 2
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
12 3
Be sure to set the R.C. address sequentially.
NOTES:
(3) Set the primary and secondary (Remote controller setting)
1. Turn on all of the indoor units.
2. Set the “primary” and “secondary” settings. (Set the indoor unit that is connected to the outdoor unit using a transmission cable as the “primary”.)
Function Number
Primary
Secondary 01
51
SW100
Setting Value
00
Remote controller
R.C. address
(DIP switch setting)
Primary/Secondary setting
(Function number 51)
: Transmission cable, Power supply cable : Remote controller cable
Indoor unit 1
[Primary]
Indoor unit 2
[Secondary]
Indoor unit 3
[Secondary]
: Power supply cable : Connection cable
6. FUNCTION SETTING
6.1. Function details
■Filter sign
Select appropriate intervals for displaying the fi lter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select “No indication” (03).
Function
number
11
Setting
value
00 Standard (400 hours) 01 Long interval (1000 hours) 02 Short interval (200 hours) 03 No indication
Setting description
■Static pressure
Select appropriate static pressure according to the installation conditions.
Function
number
26
Range of static pressure is different from 1 model to other.
Range of static pressure 0 to 90 Pa
Setting
value
00 0 Pa
01 10 Pa
02 20 Pa
03 30 Pa
04 40 Pa
05 50 Pa
06 60 Pa
07 70 Pa
08 80 Pa
09 90 Pa
31 ♦ 25 Pa [Standard]
Setting description
(... Factory setting)
(... Factory setting
)
En-17
Page 18
■Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the “Standard setting” (00) (manufacturer’s recommended value).
Function number
30
(For cooling)31(For heating)
Setting
value
00 Standard setting 01 No correction 0.0 °C (0 °F) 02 -0.5 °C (-1 °F) 03 -1.0 °C (-2 °F) 04 -1.5 °C (-3 °F) 05 -2.0 °C (-4 °F) 06 -2.5 °C (-5 °F) 07 -3.0 °C (-6 °F) 08 -3.5 °C (-7 °F) 09 -4.0 °C (-8 °F) 10 +0.5 °C (+1 °F) 11 +1.0 °C (+2 °F) 12 +1.5 °C (+3 °F) 13 +2.0 °C (+4 °F) 14 +2.5 °C (+5 °F) 15 +3.0 °C (+6 °F) 16 +3.5 °C (+7 °F) 17 +4.0 °C (+8 °F)
Setting description
(... Factory setting)
More
Cooling
Less
Heating
Less
Cooling
More
Heating
■Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to “Both” (01). Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Function number
35
(For cooling)36(For heating)
Setting
value
00 No correction 01 No correction 0.0 °C (0 °F) 02 -0.5 °C (-1 °F) 03 -1.0 °C (-2 °F) 04 -1.5 °C (-3 °F) 05 -2.0 °C (-4 °F) 06 -2.5 °C (-5 °F) 07 -3.0 °C (-6 °F) 08 -3.5 °C (-7 °F) 09 -4.0 °C (-8 °F) 10 +0.5 °C (+1 °F) 11 +1.0 °C (+2 °F) 12 +1.5 °C (+3 °F) 13 +2.0 °C (+4 °F) 14 +2.5 °C (+5 °F) 15 +3.0 °C (+6 °F) 16 +3.5 °C (+7 °F) 17 +4.0 °C (+8 °F)
Setting description
(... Factory setting)
More
Cooling
Less
Heating
Less
Cooling
More
Heating
■Auto restart
Enable or disable automatic restart after a power interruption.
Function
number
40
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or external device.
Setting
value
00 Enable
01 Disable
Setting description
(... Factory setting)
■Room temperature sensor switching
(Only for wireless remote controller) When using the Wired remote controller temperature sensor, change the setting to “Both” (01).
Function
number
42
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active. *
Remote controller sensor must be turned on by using the remote controller
Setting
value
00 Indoor unit
01 Both
Setting description
(... Factory setting)
En-18
■Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
Function
number
44
Setting
value
00 A 01 B 02 C 03 D
Setting description
(... Factory setting)
■External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
Function
number
46
Setting
value
00 Operation/Stop mode 1 01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2
Setting description
(... Factory setting)
■Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to “Wired remote controller” (01). This function will only work if the function setting 42 is set at “Both” (01)
Function
number
48
Setting
value
00 Both 01 Wired remote controller
Setting description
(... Factory setting)
■Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function
number
49
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting.
*When using a wired remote controller without Indoor unit fan control for energy saving for
cooling function, or when connecting a single split converter, the setting cannot be made by using the remote controller. Set to (00) or (01).
To confi rm if the remote controller has this function, refer to the operating manual of each
remote controller.
Setting
value
00 Disable 01 Enable 02 Remote controller
Setting description
(... Factory setting)
■Switching functions for external output terminal
Functions of the external output terminal can be switched.
Function
number
60
Setting
value
00 Operation status
01 to 08 (Setting prohibited)
09 Error status 10 Fresh air control
11 Auxiliary heater
Setting description
(... Factory setting)
■Setting record
Record any changes to the settings in the following table.
Setting description Setting value
Filter sign Static pressure Room temperature control for indoor
unit sensor Room temperature control for
wired remote controller sensor Auto restart Room temperature sensor switching Remote controller custom code External input control Room temperature sensor switching (Aux.) Indoor unit fan control for energy saving for cooling Switching functions for external output terminal
After completing the Function Setting, be sure to turn off the power and turn it on again.
Cooling Heating Cooling Heating
Page 19
7. TEST RUN
7.1. Check items
Is operation of each button on the remote controller normal? Does each lamp light normally? Is the drain normal? Do not have an abnormal noise and vibration during operation?
Do not operate the air conditioner in test run for a long time.
7.2. Operation method
Depending on your installation, choose from the following:
■By the wireless remote controller (with [TEST RUN] button)
(1) To start test run, press [START/STOP] and [TEST RUN] on the remote controller. (2) To end test run, press [START/STOP] on the remote controller.
■By the indoor unit or IR receiver unit
(1) To start test run, press [MANUAL AUTO] of the unit for more than 10 seconds (forced
cooling).
(2) T
o end test run, press [MANUAL AUTO] for more than 3 seconds or press [START/STOP]
on the remote controller.
The Operation indicator lamp and Timer indicator lamp will simultaneously fl ash during
the test run mode.
■By the wired remote controller
(1) For the operation method, refer to the installation manual and the operating manual of
the wired remote controller.
Heating test run will begin in a few minutes when HEAT is selected by the remote control­ler [reverse cycle model only].
8. FINISHING
Install the heat insulation material after performing a refrigerant leak check (Refer to the Installation manual for the outdoor unit for details).
■Coupler heat insulation
CAUTION
• After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform this section.
• Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do so may cause water leaks.
• Insulate with the coupler heat insulation (accessories) around the gas pipe and liquid
pipe at indoor unit.
• After installing the coupler heat insulation, wrap both ends with vinyl tape so that
there is no gap.
• After affi xing the coupler heat insulation, secure it with 2 cable tie (large,
accessories), one on each end of the insulation.
• Make sure that the cable tie overlap the heat insulation pipe.
Coupler heat insulation (accessories)
Cable tie (large, accessories)
Cover this portion with heat insulation.
Heat insulation
9. CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual: (1) Starting and stopping method, operation switching, temperature adjustment, timer, air
ow switching, and other remote controller operations.
(2) Cleaning and maintenance of the product, and other items such as air fi lters and air
louvers if applicable. (3) Give the operating and installation manuals to the customer. (4) If the indoor unit custom code is changed, and the installation includes a wireless
remote controller, inform the customer the changed code. (On some wireless remote
controllers, the custom code may return to A when batteries are replaced.)
10. ERROR CODES
If you use a wireless remote controller, the lamp on the photo detector unit will output error codes by way of blinking patterns. If you use a wired remote controller, error codes will ap­pear on the remote control display. Refer to the lamp blinking patterns and error codes in the table. An error display is displayed only during operation.
Error display
OPERATION
lamp
(green)
TIMER
ECONOMY
lamp
(orange)
(1)
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(3)
(3)
(3)
(3)
(3)
(3)
(4)
(4)
(4)
(5)
(5)
(5)
(10)
lamp
(green)
(1)
(2)
(5)
(6)
(8)
(1)
(2)
(3)
(4)
(6)
(7)
(9)
(1)
(2)
(3)
(5)
(9)
(1)
(2)
(4)
(1)
(3)
(4)
Error code Description
Serial communication error
• Wired remote controller com­munication error
• Server room control communica­tion error
Check run unfinished Automatic airflow adjustment error
Peripheral unit transmission PCB connection error
External communication error
Unit number or Refrigerant circuit address setting error [Simultaneous Multi]
Indoor unit capacity error
Combination error
• Connection unit number error (indoor secondary unit) [Simultaneous Multi]
• Connection unit number error (indoor unit or branch unit) [Flexible Multi]
Indoor unit address setting error
Primary unit, secondary unit setup error [Simultaneous Multi]
Connection unit number error in wired remote controller system
Power supply interruption error
Indoor unit PCB model information error
Indoor unit motor electricity consumption detection error
Manual auto switch error
Indoor unit power supply error for fan motor
Indoor unit communication circuit (wired remote controller) error
Room temp. sensor error
Indoor unit heat ex. middle temp. sensor error
Human sensor error
Indoor unit fan motor error
Drain pump error
Electric air cleaner reverse VDD error
En-19
Page 20
OPERATION
lamp
(green)
(5)
(5)
(5)
(5)
(5)
(5)
(6)
(6)
(6)
(6)
(6)
(6)
(6)
(7)
(7)
(7)
(7)
(7)
(7)
(7)
(8)
(8)
(8)
(8)
(9)
Error display
TIMER
lamp
(orange)
(5)
(7)
(8)
(9)
(10)
(15)
(1)
(2)
(3)
(4)
(5)
(8)
(10)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(2)
(3)
(4)
(6)
(4)
ECONOMY
lamp
(green)
Error code Description
Filter set error
Damper error
Intake grille error
Indoor unit fan motor 2 error (Left side fan)
Indoor unit fan motor 3 error (Right side fan)
Indoor unit error
Outdoor unit reverse/missing phase and wiring error
Outdoor unit main PCB model information error or communication error
Inverter error
Active filter error, PFC circuit error
Trip terminal L error
Outdoor unit rush current limiting resister temp. rise error
Display PCB microcomputers communication error
Discharge temp. sensor error
Compressor temp. sensor error
Outdoor unit Heat Ex. liquid temp. sensor error
Outdoor temp. sensor error
Suction Gas temp. sensor error
• 2-way valve temp. sensor error
• 3-way valve temp. sensor error Heat sink temp. sensor error
• Sub-cool Heat Ex. gas inlet temp. sensor error
• Sub-cool Heat Ex. gas outlet temp. sensor error
Liquid pipe temp. sensor error
Current sensor error
• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
Trip detection
OPERATION
lamp
(green)
(9)
(9)
(9)
(9)
(9)
(10)
(10)
(10)
(10)
(13)
Display mode
Error display
TIMER
(orange)
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
lamp
(10)
ECONOMY
lamp
(green)
(5)
(7)
(8)
(9)
(1)
(3)
(4)
(5)
(2)
Error code Description
Compressor rotor position detection error (permanent stop)
Outdoor unit fan motor 1 error
Outdoor unit fan motor 2 error
4-way valve error
Coil (expansion valve) error
Discharge temp. error
Compressor temp. error
High pressure error
Low pressure error
Branch boxes error [Flexible Multi]
En-20