2-5. SERVICE PARTS INFORMATION.........................................................................
02-01
02-05
02-07
02-16
02-65
3. DISASSENBLLY PARTS
3-1. DISASSEMBLY PROCESS FOR OUTDOOR UNIT................................................
3-2. DISASSEMBLY PROCESS FOR BRANCH BOX....................................................
03-01
03-17
Hybrid Flex Inverter System
1 . DESCRIPTION OF EACH
CONTROL OPERATION
1-1. COOLING AND DRY OPERATION
1-1-1. COOLING AND DRY CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature,
and controls the operation speed of the compressor.
The outdoor unit operates according to the highest request capacity of indoor unit
to meet the demand capacity of all the indoor units.
The capacity control of the low request capacity indoor unit is controlled by Branch box EEV.
( Table 1 : Compressor speed range )
MinimumMaximum
AOU48RLXFZ
18rps
< Target high pressure control >
The outdoor fan speed is controlled to keep the high pressure to the constant range for stabilizing
the distribution performance.
90rps
High
pressure
478PSI
338PSI
275PSI
235PSI
( Fig. 1 : Target high pressure range)
Target high pressure
Outdoor
temperature
< Target low pressure control >
When the start-up control finished, the outdoor unit starts the target low pressure control.
The outdoor unit selects the target low pressure within the following range,
it is decided by the highest request capacity from indoor units.
( Fig. 2 : Target low pressure range)
184PSI
119PSI
Target low pressure
01-01
1-2. HEATING OPERATION
1-2-1. HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature,
and controls the operation speed of the compressor.
The outdoor unit operates according to the highest request capacity of indoor unit
to meet the demand capacity of all the indoor units.
The capacity control of the low request capacity indoor unit is controlled by Branch box EEV.
( Table 2 : Compressor speed range )
MinimumMaximum
AOU48RLXFZ
18rps
< Target high pressure control >
When the start-up control finished, the outdoor unit starts the target high pressure control.
The outdoor unit selects the target high pressure within the following range,
it is decided by the highest request capacity from indoor units.
96rps
( Fig. 3 : Target high pressure range
for NORMAL HEATING OPERATION)
451PSI
Target high pressure
328PSI
( Fig. 4 : Target high pressure range
for MIN. HEAT OPERATION)
272PSI
Target high pressure
190PSI
< Target low pressure control >
The outdoor fan speed is controlled to keep the low pressure to the constant range for the following reasons.
1. Frost prevention
2. Low pressure over rise prevention
( Fig. 5 : Target low pressure range)
123PSI
Target low pressure
109PSI
01-02
1-3. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum
mode from among the Heating, Cooling, Dry and Monitoring mode. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 64°F(18°C) and 88°F(30°C) in 2°F(1°C) steps.
When operation starts, indoor fan and outdoor fan are operated for around 3 minutes.
1
Room temperature and outdoor temperature are sensed, and the operation mode is selected
in accordance with the table below. <Monitoring mode>
( Table 3 : Operation mode selection table )
Room temperature (TR)
TR> Ts+4°F(+2°C)
Operation mode
Cooling
(Autmatic dry)
TR : Room temperature
Ts : Setting temperature
Ts+4°F(+2°C) TR Ts -4°F(-2°C)
TR < Ts -4°F(-2°C)Heating
*Middle zone
*If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling, Dry, and Heating mode,
indoor unit will be operated by the same operation mode.
(2). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling, Dry, and Heating mode,
indoor unit will be operated according to the outdoor temperature as below.
( Fig. 6 : Outdoor temperature zone selection )
Cooling mode
77°F (25°C)
Heating mode
2
When Cooling or Dry mode was selected at and air flow mode is Auto, the air conditioner operates as follow.
The same operation as COOLING OPERATION AND DRY OPERATION of page 01-01 is performed.
When the room temperature has remained at set temperature -3°F(-1.5°C), operation is automatically
switched to Dry mode.
If the room temperature reaches set temperature +4°F(+2°C) during Dry mode, operation returns to Cooling.
( Fig.7 : Auto changeover : Cooling - Dry )
( Air flow mode : Auto )
Ts +2°F(+1°C)
Cooling
Cooling
Ts -3°F(-1.5°C)
(J zone)
Ts -5°F(-2.5°C)
Compressor stop
When the room
temperature drops
3
When Heating was selected at , the same operation as HEATING OPERATION of page
1
01-02 is performed.
Dry
1
Dry
(X zone)
Ts +4°F(+2°C)
Ts -1°F(-0.5°C)
Ts -3°F(-1.5°C)
When the room
temperature rises
TR : Room temperature
Ts : Setting temperature
4
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the Cooling(Auto:Dry) or Heating mode was selected at above, operation is switched
1
to Monitoring and the operation mode is selected again.
01-03
AUTO CHANGEOVER operation flow chart
HEATING OPERATION
YES
START
Room temp.
Ts+4°F(+2
°C)?
NO
Room temp.
Ts -4°F(-2
°C)?
NO
Middle zone
Operation mode of
outdoor unit : Cooling or Dry?
NO
YES
TS : Setting temperature
YES
COOLING (AUTO:DRY)
OPERATION
YES
YES
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
System stops
or operation command other than
auto changeover operation?
NO
YES
YES
Operation mode of
outdoor unit : Heating?
NO
Outdoor temperature
77
°F(25°C)?
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
System stops
or operation command other than
auto changeover operation?
NO
YES
YES
01-04
1-4. INDOOR FAN CONTROL
1. Fan speed
( Table 4 : Indoor fan speed table)
ASU7RLF
ASU9RLF
Operation mode
Heating
Cooling / Fan
Dry
ASU12RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Fan Speed
1050
1000
950
850
720
600
480
1050
950
850
710
600
X, J zone:710
Fan Speed
1200
1130
1050
910
720
600
480
1200
1050
880
710
600
X, J zone:710
Operation mode
Heating
Cooling / Fan
Dry
ASU18RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Fan Speed
1100
1040
980
850
720
600
480
1100
980
850
710
600
X, J zone:710
Fan Speed
1260
1120
1020
900
790
680
480
1260
1020
900
770
680
X, J zone:770
ASU24RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Fan Speed
1430
1320
1220
1020
900
720
480
1480
1220
1020
900
720
X, J zone:900
AUU9RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Cool Air Prevention
*Soft Quiet
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Quiet > Soft Quiet)
01-05
Hi
Me+
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
Auto
Fan Speed
590
570
540
490
440
400
300
590
540
490
440
400
X, J zone:440
AUU12RLF
AUU18RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
ARU9RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Fan Speed
650
620
580
520
460
400
300
660
580
520
460
400
X, J zone:460
Fan Speed
1260
1160
1060
960
500
1260
1160
1060
960
500
X, J zone:960
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
ARU12RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Fan Speed
840
800
750
650
500
400
300
790
660
570
460
400
X, J zone:460
Fan Speed
1340
1240
1140
1030
500
1340
1240
1140
1030
500
X, J zone:1030
ARU18RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Fan Speed
1380
1300
1220
1140
600
1380
1300
1220
1140
600
X, J zone:1140
ARU24RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
01-06
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Fan Speed
1460
1360
1260
1180
600
1460
1360
1260
1180
600
X, J zone:1180
2. FAN OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on (Me) Fan Speed.
< All models >
3. COOLING OPERATION (Auto : Cooling)
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig 8.
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cooling]
operation modes Quiet, Lo, Me, Hi.
( Fig.8 : Airflow change - over )
TR-Ts > +4°F(+2°C)
=
+4
°F(+2°C) > TR-Ts > +2°F(+1°C)
=
+2
=
°F(+1°C) > TR-Ts
=
When the room
temperature drops
< All models >
Hi
Me
Lo
TR-Ts > +5
+5
°F(+2.5°C) > TR-Ts > +3°F(+1.5°C)
°F(+1.5°C) > TR-Ts
+3
When the room
temperature rises
=
TR : Room temperature
Ts : Setting temperature
°F(+2.5°C)
=
=
=
4. DRY OPERATION (Auto : Dry)
During the dry operation, the fan speed setting can not be changed,
it operates automatically as shown in Fig. 8
Room temperature variation which the room temperature sensor of the indoor unit body has detected.
( Fig. 9 : Indoor fan control )
< Compressor >
ON
OFF
< Indoor fan air flow mode >
Setting air flow
S-Lo
Fan OFF
1030601806018060 1030(sec)
< All models >
01-07
5. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig 10.
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow
of [Heat] operation modes Quiet, Lo, Me, Hi, as shown in Table 4.
( Fig.10 : Airflow change - over ( Heating : Auto ) )
< ASU7/9/12/18/24RLF >
When the room
temperature rises
TR-Ts > -2
°F(-1°C) > TR-Ts > -4°F(-2°C)
-2
°F(-1°C) > TR-Ts > -4°F(-2°C)
-2
=
°F(-2°C) > TR-Ts
-4
TR-Ts > -2
=
-4
°F(-2°C) > TR-Ts
°F(-1°C)
=
When the room
temperature rises
°F(-1°C)
=
When the room
Lo
Me
Me+
temperature drops
TR-Ts > -3°F(-1.5°C)
-3°F(-1.5°C) > TR-Ts > -5°F(-2.5°C)
-5
°F(-2.5°C) > TR-Ts
< AUU9/12/18RLF, ARU9/12/18/24RLF >
When the room
Lo
Me
Hi
temperature drops
TR-Ts > -3°F(-1.5°C)
-3°F(-1.5°C) > TR-Ts > -5°F(-2.5°C)
°F(-2.5°C) > TR-Ts
-5
=
=
TR : Room temperature
Ts : Setting temperature
=
=
6. COOL AIR PREVENTION CONTROL (For Heating and Min. Heat operation)
The maximum value of the indoor fan speed is set as shown in Fig 10, based on the detected
temperature by the indoor heat exchanger sensor in heating mode.
Field setting is necessary at AR and AU type as "Cool air prevention : effective"
( Fig.11 : Airflow change - over for cool air prevention)
During NORMAL HEATING OPERATION
< ASU7/9/12/18/24RLF, AUU9/12/18RLF >
When Indoor
heat exchanger
temperature rises
107.6°F
(42°C)
°F
102.2
(39°C)
°F
98.6
(37°C)
86
°F
(30°C)
Hi
*Me+ or setting
FAN mode
*Lo or setting
FAN mode
Cool air
prevention
S-Lo
When Indoor
heat exchanger
temperature drops
98.6
(37°C)
93.2
(34°C)
89.6
(32°C)
82.4
(28°C)
°F
°F
°F
°F
When Indoor
heat exchanger
temperature rises
98.6°F
(37°C)
84.2°F
(29°C)
< ARU9/12/18/24RLF >
*Hi or setting
FAN mode
*Lo or setting
FAN mode
S-Lo
*Lower speed is selected
*Lower speed is selected
During MIN. HEAT OPERATION
< ASU7/9/12/18/24RLF, AUU9/12/18RLF >
When Indoor
heat exchanger
temperature rises
102.2°F
(39°C)
Auto
Lo
When Indoor
heat exchanger
temperature drops
93.2°F
(34°C)
When Indoor
heat exchanger
temperature rises
98.6
(37°C)
< ARU9/12/18/24RLF >
Auto
°F
Lo
When Indoor
heat exchanger
temperature drops
°F
89.6
(32°C)
75.2
°F
(24°C)
When Indoor
heat exchanger
temperature drops
89.6°F
(32°C)
01-08
1-5. LOUVER CONTROL
For Compact Wall Mounted Type, Wall Mounted Type < ASU7/ 9/ 12/ 18/ 24RLF >
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range
will change as follow:
(Table9 : Recommended Operation Range)
Cooling / Heating / Dry mode / Fan mode
(Fig.12 : Virtical Air Direction Range)
<Wall Mounted Type><Compact Wall Mounted Type>
Vertical Louver
Power DiffuserVertical Louver
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
When the temperature of the air being blown out is low at the start of heating operation or during
defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
range ( ) for long period of time, since water vapor many condense near the outlet louvers and
drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow
Direction Louvers are left in the heating range for around 30 minutes, they will automatically
return to position .
2. HORIZONTAL LOUVER CONTROL (For ASU18/ 24RLF)
(Function Range)
Each time the button is pressed, the air direction
range will change as follows.
ASU7/9/12RLF changes by manual.
Cooling / Heating / Dry mode / Fan mode
3. SWING OPERATION
Vertical Airflow Swing Operation
When the swing signal is received from the remote controller, the vertical louver starts to swing.
When the swing signal is received from the remote controller, the horizontal louver starts to swing.
(Swinging Range)
All mode :
1
5
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted
and it stops at either upper end or bottom end.
Vertical and Horizontal Airflow Swing Operation
When the horizontal swing signal is input from remote control, the combination of the vertical
and horizontal swing operation is performed.
Power Diffuser doesn't swing in any swing operation.
01-09
For Compact Cassette Type < AUU9/ 12/ 18RLF >
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follows:
1234
(Operation Range)
During COOLING / HEATING / DRY / FAN mode :
1234
(Fig.14 : Air Direction Range)
3
4
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation
selected.
COOLING / DRY / FAN mode
HEATING mode
Horizontal flow
Downward flow
1
4
During AUTO mode operation, for the first minute after start-up, air-flow will be horizontal
; the air direction cannot be adjusted during this period.
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
The range of swing depends on the set airflow direction.
1
2
The type of operation
COOLING / HEATING / DRY / FAN
Range of swing
to
14
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted
and the louver stops at the memorized position.
( Stop mode means Operation stop.)
01-10
1-6. OUTDOOR FAN CONTROL
1. Fan speed table
Table 5 shows the fan speed of the outdoor unit.
( Table 5 : Outdoor fan speed table)
AOU48RLXFZ
Fan step
0
1
2
3
4
5
6
7
8
9
10
11
Fan speed
0
250
290
340
390
460
580
690
800
890
910
950
[rpm]
2. Limit of fan speed range
Fig.15 shows the limit of fan speed range changes by outdoor temperature.
( Fig.15 : Limit of fan speed range )
Outdoor
temperature
86°F(30°C)
68°F(20°C)
50°F(10°C)
< Cooling and Dry mode >
890rpm
580 ~ 890rpm
250 ~ 890rpm
0 ~ 890rpm
Outdoor
temperature
41°F(5°C)
< Heating mode >
460 ~ 910rpm
460 ~ 950rpm
3. Initial fan speed control
Initial fan speed is decided by outdoor temperature.
( Fig.16 : Initial fan speed range )
< Cooling and Dry mode >
Outdoor
temperature
690rpm
50°F(10°C)
390rpm
If the fan motor is running over than 400rpm, it start up process is stopped in all conditions. [ Prevent the big wind operation ]
*
When the fan motor is stopped, it can not restart for 10 seconds.
*
Even if during EEV initialization, outdoor unit fan starts.
*
01-11
< Heating mode >
Fixed at 690rpm
1-7. COMPRESSOR CONTROL
1. OPERATION SPEED RANGE
The operation speed of the compressor is different based on the operation mode as
shown in theTable 6.
( Table 6 : Compressor operation speed range )
Heating
MinimumMaximum
18rps96rps
AOU48RLXFZ
Dry / Cooling
MinimumMaximum
18rps
90rps
2. OPERATION SPEED CONTROL AT START-UP
The compressor speed soon after the start-up is controlled for
2-1 Cooling and Dry start-up procces
< Pattern 1 >
If it does not meet the condition of pattern 2, the compressor will start at pattern 1.
( Fig.17 : Pttern 1)
(rps)
70
limit
54
47
40
33
Upper
speed
90
180240
Elapsed time
< Pattern 2 >
If it meets one of the following conditions, the compressor will start at pattern 2.
Condition
1
2
3
Compressor control
before operation stops
Target pressure control
Start-up procces 2
Oil recovery / Defrost
Stop time of
compressor
Below 3 hours
Compressor
temperature
Over 32°C
( Fig.18 : Pattern 2)
(rps)
54
Upper
speed
limit
47
40
33
20
(sec)300330
90
180240
Elapsed time
01-12
(sec)30036070390
2-2 Heating start-up procces
< Pattern 1 >
If it does not meet the condition of pattern 2, the compressor will start at pattern 1.
( Fig.19 : Heating start-up pattern 1)
(rps)
70
limit
60
47
40
33
Upper
speed
90
Elapsed time
690 720
< Pattern 2 >
If it meets one of the following conditions, the compressor will start at pattern 2.
Condition
1
2
3
Compressor control
before operation stops
Target pressure control
Start-up procces 2
Oil recovery / Defrost
Stop time of
compressor
Below 3 hours
Compressor
temperature
Over 89.6°F
(32°C)
( Fig.20 : Heating start-up pattern 2)
(rps)
60
Upper
speed
limit
47
40
33
20
90
150210
Elapsed time
(sec)780840
(sec)27033070390
3. LIMIT OF THE COMPRESSOR SPEED RANGE
The compressor speed range is limited by outdoor temperature as shown in Fig.21
( Fig.21 : Limit of the compressor speed range )
< Cooling and Dry mode >
Outdoor
temperature
21 ~ 90rps
104°F(40°C)
18 ~ 90rps
50°F(10°C)
25 ~ 90rps
23°F(-5°C)
27 ~ 90rps
14°F(-10°C)
* 0rps
*Protection stop for low outdoor temperature.
It will be released when outdoor temperature
becomes over than 14°F(-10°C)
01-13
Outdoor
temperature
53.6°F(12°C)
41°F(5°C)
5°F(-15°C)
< Heating mode >
21 ~ 90rps
18 ~ 96rps
23 ~ 96rps
25 ~ 96rps
1-8. TIMER OPEARTION CONTROL
1-8-1 WIRELESS REMOTE CONTROLLER
The table 7 shows the available timer setting based on the product model.
( Table 7 : Timer setting )
ON TIMER / OFF TIMERPROGRAM TIMERSLEEP TIMER
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Stop mode
Set timeSet timeSet timeSet time
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest
to the clock's current timer setting.
The order of operations is indicated by the arrow in the remote control unit's display.
Operation mode
Operation mode
Stop mode
Stop mode
SLEEP timer operation cannot be combined with ON timer operation.
01-14
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically.
If the operation mode or the set temperature is change after the sleep timer is set, the operation is
continued according to the changed setting of the sleep timer from that time ON.
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 2 F(1 C).
It increases the setting temperature another 2 F(1 C) after 1 hour.
After that, the setting temperature is not changed and the operation is stopped at the time
of timer setting.
Set temperature rises
( Ts : Set temperature )
+4°F (+2°C)
+2°F (+1°C)
Ts
Stop of operation
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 2 F(1 C).
It decreases the setting temperature another 2 F(1 C) every 30 minutes.
Upon lowering 4deg C, the setting temperature is not changed and the operation stops at
the time of timer setting.
Set temperature lowers
( Ts : Set temperature )
Ts
-2 F(-1 C)
-4 F(-2 C)
-6 F(-3 C)
-8 F(-4 C)
Stop of operation
Set
30min
30min
30min
01-15
1-8-2 WIRED REMOTE CONTROLLER
The Table 8 shows the available timer setting based on the product model.
( Table 8 : Timer setting )
ON TIMER / OFF TIMERWEEKLY TIMERTEMPERATURE SET BACK TIMER
1. ON TIMER / OFF TIMER
Same to 1-8-1 ON / OFF TIMER and shown in those.
2. WEEKLY TIMER
This timer function can set operation times of the each day of the week.
All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
ONOFFONOFFONOFF
Setting daySetting daySetting day
Set timeSet time
3. TEMPERATURE SET BACK TIMER
This timer function can change setting temperature of setting operation times of the each day of the week.
This can be together with other timer setting.
Set back tmp.
Normal tmp.
ON
Set timeSet time
OFF
01-16
1-9. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor frequency, the temperatures detected by the discharge temperature sensor, the
indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature
sensor.
1. Pulse range
(Table 9 : Pulse range of outdoor unit EEV)
Outdoor unit
Main EEV
Subcool EEV
Operation mode
Dry / Cooling
Heating
During heating operation, lower limit is 0 pulse.
Pulse range
40 ~ 480
35 ~ 480
(Table 10 : Pulse range of branch box EEV)
Branch box
Main EEV
Bypass EEV
Operation mode
Dry / Cooling
Heating
There is a case that EEV is full close at 32 10 pulse.
Pulse range
32 ~ 480
0 ~ 480
+
-
2. Initialization
Initialization (Input of 528 pulses toward closing direction) is operated under the following conditions.
It apply to all of EEV.
< Initialization conditions >
.
Power-on.
.
4 hours has passed from the last initialization, and when the compressor starts.
.
If 12 hours has passed from the last initialization, the compressor is compulsorily stopped.
.
3 minutes has passed from the protection stop of outdoor unit.
01-17
1-10. TEST OPERATION CONTROL
< Pre-test run check items >
Before the test run, refer to the figure and check the following items.
1. Is check run performed? Test run doesn't operate if check run is not performed.
After checking that the above items are all in order, refer to Test run method "to test run the unit.
If there are problems, adjust immediately and recheck.
< Test run method >
Be sure to configure test run settings only when the outdoor unit has stopped operating.
Depending on the communication status between the indoor and outdoor units, it may take several minutes for •
the system to start operating after settings for the test run are complete.
After the test run settings are complete, all the outdoor units and the connected indoor units will start operating. •
Room temperature control will not activate during test run (continuous operation).
Test run set with the outdoor unit doesn't stop automatically. Be sure to stop the operation according to the •
operation method.
All indoor units will operate when test run is performed from the outdoor unit. At this time, the remote controller of •
the indoor unit is unavailable.
Operation mode cannot be changed during the test run. To change the operation mode, please stop the test run •
first, and then perform the test run again. At this time, the compressor cannot be restarted for three minutes after
it stops in order to protect the indoor unit. Please restarte it after three minutes.
With Wired Remote Controller
Under the condition where the air conditioner stops, press the MODE button and the FAN button
simultaneously for 2 seconds or more, and the test operation control mode will appear.
During test running, " " will display on the remote controller display.
Set the test operation mode, and the compressor will continue to run regardless of whatever
the room temperature sensor detects.
With Wireless Remote Controller
Under the condition where the air conditioner runs, press the TEST RUN button, and
the test operation control mode will appear.
During test running, the Operation LED and Timer LED of the air conditioner body blinks simultaneously.
Set the test operation mode, and the compressor will continue to run regardless of whether the room
temperature sensor detects.
With Outdoor Unit
All the indoor units connected to the outdoor unit can be test-operated by push button as next page.
01-18
Perform test run for refrigerant system.
You can set “cooling test run” or “heating test run” with the push-button switch on the outdoor unit print circuit board.
Test run setting method
Function settings
First 2 digits
(Blinking)
(Blinking)
(Blinking)
Last 2 digits
MODE/EXIT
(Blinking)
SELECT
(Blinking)
SELECT
ENTER
SELECT
For cooling operation, press the
SELECT button until
ENTER
Press the ENTER button for
more than 3 seconds.
This will be displayed when the
cooling test run starts.
(It takes approximately 30 seconds for
the outdoor unit to start its operation.)
This will be displayed
after 5 seconds.
MODE/EXIT
SELECT
ENTER
(When [F4] to [F9] are displayed, continue to press
the SELECT button until [F3] is displayed.)
SELECT
For heating operation, press the
is displayed.
“00”
(Blinking)
(Blinking)
SELECT button until
ENTER
Press the ENTER button for
more than 3 seconds.
This will be displayed when the
heating test run starts.
This will be displayed
after 5 seconds.
: Press the “MODE/EXIT” button.
: Press the “SELECT” button.
: Press the “ENTER” button.
Settings for starting
test run operation
is displayed.
“01”
(It takes approximately 30 seconds for
the outdoor unit to start its operation.)
SELECT
SELECT
Settings for stopping
test run operation
(Blinking)
(Blinking)
ENTER
Press the ENTER button for
more than 3 seconds.
This will be displayed when the
cooling operation mode is canceled.
(It takes approximately 30 seconds for
the outdoor unit to stop its operation.)
This will be displayed
after 5 seconds.
MODE/EXIT
(Blinking)
(Blinking)
ENTER
Press the ENTER button for
more than 3 seconds.
This will be displayed when the heating
operation mode is canceled.
(It takes approximately 30 seconds for
the outdoor unit to stop its operation.)
This will be displayed
after 5 seconds.
EXIT
After the test run is complete, turn off the power. Attach the cover of the electrical component box and the front panel
of the outdoor unit.
01-19
1-11. 4-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the Cooling mode to Heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.
1-12. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
(Table 11 : Operation contents memorized when the power is interrupted)
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup.
Refer to the installation manual of wired remote controller for details.
1-13. MANUAL AUTO OPERATION
If MANUAL / AUTO Button is pushed continuous from 3 seconds to 10 seconds,
manual auto operation will starts.
If the remote control is lost or battery power dissipated, this function will work without the remote
control.
(Table 12 : Manual auto operation control)
Functions
OPERATION MODE
SETTING TEMP.
FAN MODE
VERTICAL LOUVER
HORIZONTAL LOUVER
TIMER MODE
SWING OPERATION
ECONOMY
All models
Auto changeover
75.2°F(24°C)
Auto
NORMAL
NORMAL
Continuous
(No timer setting available)
OFF
OFF
01-20
1-14. FORCED COOLING OPERATION
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more.
During the forced cooling operation, it operates regardless of room temperature sensor.
Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON
and 1 second OFF on both operation LED and timer LED (same as test operation).
Forced cooling operation is released after 60 minutes of starting operation.
FORCED COOLING OPERATION will start as shown in Table12.
If any defrost operated, "compressor integrating operation time" and "compressor OFF count" are cleared.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions becomes as shown in Table 19.
( Table 19 : Condition of defrost release )
Release Condition
Outdoor heat exchanger temperature is higher than 53.6°F(12°C)
or
Compressor operation time has passed 15 minutes.
01-22
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
Outdoor unit operation mode : Heating mode
Compressor integrating
Outdoor
temperature [Ta]
Ta > 14°F(-10°C)
=
Outdoor
heat exchanger
temperature [Tn]
Tn < 1.4°F(-17°C)
=
operation time :
Over 35 minutes
Outdoor
heat exchanger
temperature [Tn]
Tn < Ta - 14°F(7°C)
=
Compressor continuous
operation time
Over 10 minutes
Outdoor
temperature [Ta]
Ta < 14°F(-10°C)
Outdoor
heat exchanger
temperature [Tn]
Tn < -4°F(-20°C)
=
Compressor
integrating
operation time
Over 240 minutes
Outdoor
heat exchanger
temperature [Ta]
Below 26.6°F(- 3°C)
Compressor
integrating
operation time
Over 210 minutes
Compressor
stop
Outdoor
temperature [Ta]
Ta < 35.6°F(2°C)
Compressor continuous
operation time
Less than 10 minutes
Outdoor
temperature [Ta]
Ta < 35.6°F(2°C)
Compressor
OFF count
40 times
Normal defrost
start
Outdoor heat exchanger temperature (Outlet): Over 53.6° F(12°C)
Compressor : 70rps
Outdoor fan motor : OFF
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Main EEV : 480Pulse
4-way valve : OFF
Solenoid valve : OFF
Indoor fan : OFF
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-23
Integrating defrost
start
1-18. OFF DEFROST OPERATION CONTROL
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, the outdoor unit will allow
the heat exchanger to defrost, and then stop.
1. OFF DEFROST OPERATION CONDITION
When heating operation stops, all of following conditions are met, OFF defrost operation starts.
1. Compressor operation integrating time lasts for more than 30 minutes.
2. Compressor countinuous operation time lasts for more than 10 minutes.
3. Outdoor unit heat exchenger temperature is less than 24.8°F(-4°C).
If the operation stops in defrost operation, defrost operation is kept untill the it is completed.
2. OFF DEFROST RELEASE CONDITION
OFF defrost operation is released when the conditions becomes as shown in Table 31
( Table 20 : OFF Defrost Release Condition )
Release Condition
Outdoor heat exchanger temperature is higher than 53.6°F(12°C)
or
Compressor operation time has passed 15 minutes.
OFF Defrost Flow Chart
Heating operation stop
Compressor integrating operation : Over 30 minutes
and
Compressor countinuous operation time : Over 10 minutes
and
Outdoor heat exchanger temperature : Below
Defrost start
Outdoor heat exchanger temperature : Over 53.6°F(12°C)
or
Compressor ON time : Maximum 15 minutes
24.8°F(-4°C)
Defrost end
01-24
1-19. OIL RECOVERY OPERATION
Outdoor unit operates by cooling refrigerant cycle for recover the refrigerant oil to the compressor
1. Cooling oil recovery operation
< Start condition >
It operates forcibly from the compressor integrating time in Cooling and Dry mode.
Condition of the oil recovery operates after 1 hour
(1). First time after power ON
(2). When the operation mode changes from Heating to Cooling. (only first time)
Condition of the oil recovery operates after 3 hour
Without condition
< Operation >
Compressor : Over 50rps
Outdoor fan : Normal operation
4 way valve : OFF
< Release condition >
*2~7 minutes has passed from the start of oil recovery operation.
2. Heating oil recovery operation
< Start condition >
It operates forcibly when the compressor integrating operation time becomes 12 hours.
< Operation >
Refrigerant cycle is changed to the cooling cycle temporarily.
Compressor : Fixed 50rps
Outdoor fan : Step2 (290rpm)
4 way valve : OFF
< Release condition >
*1~5 minutes has passed from the start of oil recovery operation.
During the oil recovery operation, appears on the display of wired and central remote controller,
and appears on the simple remote controller.
The operation indicators (LED) of the indoor units flash slowly.
*Operation time changes from the progress status of oil recovery.
01-25
1-20. FRESH AIR CONTROL( For AU / AR type)
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation
as shown in Figure 22.
(Fig. 22 : Fresh Air control)
Fan motor
(Indoor unit)
Fan motor
(for Fresh Air)
Operation
Stop
Operation
Stop
*It needs the external relay and power supply.
1-21. EXTERNAL ELECTRICAL HEATER CONTROL (For AR type)
The External Electrical Heater is operated as below.
< Heater : ON condition >
When all of the following conditions are met, external elecrtical heater will operate according to Figure 23.
System type
Operation mode
Compressor
Indoor fan
Heatpump
Heating
ON
ON (S-Lo is excluded)
< Heater : OFF condition >
1). When one of the ON conditions is not met.
2). When Defrost operation or Oil recovery operation starts
(Fig. 23 : External electrical heater control)
Heater : OFF
Ts -6°F(-3°C)
Ts -24°F(-12°C)
When the room
temperature drops
Heater : ON
Heater : OFF
When the room
temperature rises
Ts : Setting temperature
Ts -2°F(-1°C)
Ts -20°F(-10°C)
01-26
1-22. DRAIN PUMP OPERATION
During Cooling / Dry mode
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Anti- freezing protection", the drain pump is turned off
in 1 hour after the compressor stops.
4. When the water level in the drain pan rises up and then the float switch functions:
1
The compressor, indoor and outdoor fan motor operation are stopped.
2
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
3
The indoor unit fan motor operates after the float switch is turned off.
5. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
(It is necessary to turn off power for release it. )
6. When the float switch turns OFF less than 3 minutes, the unit starts Cooling operation.
( Fig. 24 : Detail of Drain Pump Operation in Cooling / Dry )
Compressor
Drain Pump
ON
OFF
ON
OFF
3 minutes
<Float Switch turns OFF less than 3 minutes>
Less than 3 minutes
Float Switch
Compressor
Indoor Fan
Drain Pump
ON
OFF
ON
OFF
3 minutes ST
ON
OFF
ON
OFF
3 minutes
During HEATING / FAN mode / Stop operation
1.When the water level in the drain pan rises up and then the float switch functions:
Drain pump operates continuously for 3 minutes after the float switch is turned off.
1
(Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
Thereafter, even if the float switch turns OFF, the "FAILURE INDICATION" is not released.
(It is necessary to turn off power for release it. )
( Fig. 25 : Detail of Drain Pump Operation in Heating )
Float Switch
Drain Pump
ON
OFF
ON
OFF
01-27
3 minutes
1-23. ECONOMY OPERATION
ECONOMY OPERATION functions by pressing ECONOMY button on the remote controller or
Home controller, it is almost the same operation as below settings.
( Table 20 : Detail of ECONOMY OPERATION)
Operation
mode
Cooling
Heating
Dry
Auto
Outdoor unit
limit current
value
*17.0A
Setting temperature
correction
Ts + 2°F(Ts+1°C)
Ts - 2°F(Ts-1°C)
Ts + 2°F (Ts+1°C)
Cooling : Ts + 2°F (Ts+1°C)
Heating : Ts -2°F (Ts-1°C)
Indoor fan
speed
Normal
operation
(When only fan mode,
air flow downs 1 step)
Indoor unit LED
OPERATION : Lighting
ECONOMY : Lighting
Ts : Setting temperature
Wired remote
controller display
: Lighting
ECO
During ECONOMY OPERATION,
*limit current value of outdoor unit is changed to 17.0A
When also "ENERGY SAVING PEAK CUT FUNCTION" mode is effective, the outdoor unit will operate
by lower current.
ECONOMY OPERATION does not operate in following conditions.
.
Compressor start-up process
.
Defrost operation
.
Oil recovery operation
.
Minimum heat operation
< Release conditions of ECONOMY OPERATION >
1, When the ECONOMY button on the remote controller is pressed.
2, When the indoor unit start-up by MANUAL AUTO button on the indoor unit.
(When the operation is stopped by MANUAL AUTO button, it is not released.)
01-28
1-24. ENERGY SAVING PEAK CUT FUNCTION
The current value is limited to reduce the power consumption by external input terminal 3(CN933).
When
and "LOW NOISE OPERATION" are effective, the
(Table 21 : Outline of ENERGY SAVING PEAK CUT FUNCTION)
this function, "CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION"
outdoor unit will operate by lowest current of them.
MODE1
0%
MODE2
50%
MODE3
75%
(Forced thermostat-OFF)
Cooling mode
Dry mode
Compressor stop
11.0A17.0A
Heating mode
*Percentage is rated electrical power ratio
ENERGY SAVING PEAK CUT OPERATION does not operate in following conditions.
.
Compressor start-up process
.
Defrost operation
.
Oil recovery operation
.
Check run
1-25. LOW NOISE MODE
The outdoor unit operation changes from the capacity priority to the low noise priority
by external input 1(CN931).
The compressor speed and outdoor fan speed are limited as following table.
MODE4
100%
(Rated)
22.5A
When "CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "PEAK CUT OPERATION"
are effective, the outdoor unit will operate by lowest current of them.
( Table 22 : Detail of LOW NOISE OPERATION)
MODE1MODE2MODE3
Cooling mode
Dry mode
Limit compressor speed
Limit fan speed
Limit compressor speed
52rps36rps
690rpm390rpm
55rps42rps
45rps
580rpm
49rps
Heating mode
Limit fan speed
690rpm
580rpm390rpm
(Relative to the rated sound pressure level)
*The performance drops when operating in the LOW NOISE OPERATION.
LOW NOISE OPERATION does not operate in following conditions.
.
Compressor start-up process
.
Defrost operation
.
Oil recovery operation
.
Check run
01-29
1-26. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
During the compressor in operation,
the discharge thermistior will detect discharge gas temperature.
The discharge gas temperature is controlled in the following protections.
Discharge temperature protection 1
<Start condition>
Discharge temperature becomes more than 221°F(105°C).
<Operation>
The compressor speed -20rps every 120 seconds.
If the compressor operates at minimum speed for 120 seconds,
and the release condition isn't met, it will be stopped.
<Release condition>
When the discharge temperature becomes lower than
212°F(100°C), the compressor returns to the normal operation.
If the compressor was stopped by protection, it will restart
after 3 minutes ST.
(Fig. 26 : Discharge temperature control)
Discharge
temperature
239°F
(115°C)
Comp. speed -20rps every 120 sec.
221°F
(105°C)
158°F
(70°C)
Comp. stop
Release protection 2
Hold
Discharge temperature protection 2
<Start condition>
Discharge temperature becomes more than 239°F(115°C).
<Operation>
The compressor is stopped, and it does not restart for 7 minutes.
<Release condition>
When the discharge temperature becomes lower than 158°F(70°C), the compressor restarts.
If the
Discharge temperature protection 2 operates 2 times within 24 hours,
discharge temperature error will occur. <Permanent stop>
An error code is displayed each controller, it is reset by only the main power supply reset.
2. COMPRESSOR TEMPERATURE PROTECTION CONTROL
<Start condition>
When the compressor temperature thermistor detects more than 233.6°F (112°C).
<Operation>
The compressor is stopped at once.
<Release condition>
The compressor temperature becomes lower than 176°F(80°C) after 3 minutes ST.
If the Compressor temperature protection operates 2 times within 24 hours,
discharge temperature error will occur. <Permanent stop>
An error code is displayed each controller, it is reset by only the main power supply reset.
01-30
3. HEAT SINK TEMPERATURE PROTECTION CONTROL
During the compressor in operation,
heat sink temperature thermistor (Built-in IPM) will detect heatsink temperature.
It is controlled in the following protections.
Heat sink protection 1 and 2 operates at the same time, if each conditions are met.
Heatsink temperature protection 1
<Start condition>
When the heat sink temperature becomes more than 185°F(85°C).
<Operation>
Outdoor unit fan +1 STEP (rise) every 30 seconds.
<Release condition>
When the h
eat sink temperature becomes lower than 176°F(80°C).
and the outdoor fan returns to the normal operation.
Heat sink
temperature
(100°C)
Heatsink temperature protection 2
<Start condition>
When the heat sink temperature becomes more than 194°F(90°C).
<Operation>
Compressor speed -10rps every 30 seconds.
If the compressor operates at minimum speed for 120 seconds,
and the release condition isn't met, it will be stopped.
<Release condition>
When the h
If the compressor was stopped by protection, it will restart after 3 minutes ST.
eat sink temperature becomes lower than 185°F(85°C), the outdoor fan to the normal operation.
(Fig. 27 : Heat sink temperature control)
Comp. stop
212°F
Comp. speed -10rps every 120 sec.
194°F
(90°C)
Outdoor unit fan +1 step every 30 sec.
185°F
(85°C)
Release protection 2,3
176°F
(80°C)
Release protection 1
Heatsink temperature protection 3
<Start condition>
When the heat sink temperature becomes more than 212°F(100°C).
<Operation>
Compressor is stopped
<Release condition>
When the h
the compressor restarts.
eat sink temperature becomes lower than 185°F(85°C) and after 3 minutes ST,
01-31
4. CURRENT RELEASE CONTROL
The compressor speed is controlled so that the outdoor unit input current does not exceeds
the current limit value is decided by the outdoor temperature.
When "ECONOMY OPERATION" or "PEAK CUT OPERATION" are effective,
the outdoor unit will operate by lowest current.
When the outdoor unit input current reaches to the control value, the compressor speed
-1rps every 1 second till the release value.
Then, if the compressor operates at minimum speed and the input current doesn't reach
to the release value, the compressor is stopped.
( Table 23 : Current release operation value / Release value )
Outdoor
Cooling
Dry
Heating
temperature [ Ta ]
122°F(50°C) < Ta
116.6°F(47°C) < Ta < 122°F(50°C)
104°F(40°C) < Ta < 116.6°F(47°C)
104°F(35°C) < Ta < 104°F(40°C)
86°F(30°C) < Ta < 104°F(35°C)
20°F(30°C) < Ta < 86°F(30°C)
50°F(10°C) < Ta < 20°F(30°C)
23°F(-5°C) < Ta < 50°F(10°C)
75.2°F(24°C) < Ta
62.6°F(17°C) < Ta < 75.2°F(24°C)
53.6°F(12°C) < Ta < 62.6°F(17°C)
41°F(5°C) < Ta < 53.6°F(12°C)
30.2°F(-1°C) < Ta < 41°F(5°C)
5°F(-15°C) < Ta < 30.2°F(-1°C)
=
=
=
=
=
=
=
=
Ta < 23°F(-5°C)
=
=
=
=
=
=
Ta < 5°F(-15°C)
Normal
17.0 / 16.5
18.0 / 17.5
22.0 / 21.5
26.0 / 25.5
22.0 / 21.5
22.0 / 21.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
Current value [ A ]
(Conrtol / Release)
Low noise
mode 1
14.0 / 13.5
16.5 / 16.0
17.0 / 16.5
22.0 / 21.5
22.0 / 21.5
22.0 / 21.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
Ta : Outdoor temperature
Low noise
mode 2
13.0 / 12.5
15.0 / 14.5
15.5 / 15.0
17.0 / 16.5
17.0 / 16.5
19.0 / 18.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
Low noise
mode 3
10.5 / 10.0
12.5 / 12.0
13.0 / 12.5
14.0 / 13.5
14.0 / 13.5
16.0 / 15.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
*Current value(Control / Release) is different from the operating fan step of the outdoor unit.
(Above case is more than 4 STEP, refer to outdoor unit fan table.)
During the compressor in operation,
When the discharge high pressure sensor will detect the high pressure sensor.
The high pressure is controlled in the following protections.
HIGH PRESSURE PROTECTION 1
.
During Cooling / Dry mode
<Start and Release condition>
When the compressor speed meets following conditions.
The compressor speed -5rps every 60 seconds.
If the compressor operates at minimum speed for 60 seconds and the release condition isn't met,
it will be stopped.
.
During Heating mode
<Start and Release condition 1>
When the compressor speed meets following conditions.
( Table 25 : Heating high pressure protection control)
High pressure
Heating
Compressor speed [rps]
rps < 20
=
20 < rps < 90
90 < rps
=
Control
HP > 478PSI
=
HP > 507PSIHP < 530PSI
=
HP > 478PSI
=
HP < 451PSI
HP < 451PSI
<Operation>
The compressor speed -5rps every 60 seconds.
If the compressor operates at minimum speed for 60 seconds.
<Release condition 2>
If the compressor was stopped by protection, it will restart after 3 minutes ST
and high pressure is lower than 435PSI.
Release
=
=
=
01-33
HIGH PRESSURE PROTECTION 2
( Fig. 28 : High pressure protection 2 )
<Start condition>
High pressure sensor detects more than 594PSI.
<Operation>
High
pressure
594PSI
Compressor stop
Compressor is stopped.
<Release condition>
When the high pressure sensor detects lower than 435PSI
435PSI
Release of protection
and after 3 minutes ST, the compressor restarts.
HIGH PRESSURE PROTECTION 3
<Start condition>
When the pressure switch becomes OFF (Open : more than 609.2 PSI), the compressor is stopped.
<Operation>
Compressor is stopped.
<Release condition>
When the pressure switch becomes ON (Close : lower than 464.1 PSI) and after 3 minutes ST,
the compressor restarts.
6. LOW PRESSURE PROTECTION CONTROL
Hold
LOW PRESSURE PROTECTION 1 (For Cooling, Dry and Heating mode)
<Start condition>
After the compressor operates for 1 minute, and low pressure sensor
detects lower than 7.25PSI for 5 minutes.
<Operation>
Compressor is stopped.
<Release condition>
Compressor restarts after 3 minutes ST.
( Fig. 29 : Low pressure protection 1 )
Low
pressure
7.25PSI
(When continues for 5 minutes)
If the Low pressure protection 1 operates 5 times within 2 hours,
Low pressure error will occur. <Permanent stop>
An error code is displayed each controller, it is reset by only the main power supply reset.
LOW PRESSURE PROTECTION 2 (For Heating mode)
<Start condition>
The compressor operates for 10 minutes, and low pressure sensor
detects lower than 23.2PSI for 1 minute.
( Fig. 30: Low pressure protection 2 )
<Operation>
The compressor speed -5rps every 60 seconds till the
release condition.
If the compressor operates at minimum speed for 60 seconds,
and the release condition isn't met, the compressor is stopped.
<Release condition>
Low pressure sensor detects more than 26.0PSI,
and after 3 minutes ST.
During the compressor in operation, low pressure sensor detects
lower than 21.7PSI.
<Operation>
Main EEV of Branch Box opens untill the release condition.
<Release condition>
Low pressure sensor detects more than 24.6PSI.
If the compressor stopped, it restarts after 3 minutes ST.
7. ANTIFREEZING CONTROL (Cooling and Dry mode)
To prevent the indoor unit heat exchenger freezing.
<Start condition>
When the indoor heat exchanger temperature sensor detects lower than 37.4
<Operation>
Main EEV of branch box is closed.
<Release condition>
When indoor heat exchanger becomes more than 44.6
°F(7°C).
Low
pressure
24.6PSI
21.7PSI
(Fig. 31 : Low pressure protection 3)
Release protection 3
Hold
Main EEV of Branch Box opens
°F(3°C).
8. EEV FULL CLOSE PROTECTION CONTROL (Heating mode)
Operation condition of EEV is checked from the temperature difference
indoor heat exchanger and room temperature.
<Start condition>
When all the following conditions are met for the 2 times in a row.
1. During compressor in operation
2. After 20 minutes from compressor start-up.
3. Indoor unit heat exchanger temperature - Room temperature < 8°F( 4°C)
<Operation>
Outdoor unit is stopped and EEV is initialized.
<Release condition>
After 3 minutes ST, compressor will restart.
01-35
Hybrid Flex Inverter System
2. TROUBLE SHOOTING
2. TROUBLESHOOTING
2-1 Service maintenance for Hybrid Flex Inverter System
2-1-1 Features
Enhanced installability and maintenance.
<Product>
1) Multi-room --> Many pipes and lines
2) Branch box --> Pipes and line
3) Increased power supply points --> Outdoor units and branch boxes
<Functions>
- The conditions of each lines are automatically checked.
- Controller in outdoor units.
- 7-segment lamp in outdoor units.
Check operation
- Lines and pipes of branch boxes are automatically checked.
- Check result (Fault and right lines) is shown.
Controller in outdoor units
[Available]
- Cooling and heating test running
- Refrigerant recovery mode
- Local setteing function (Outdoor unit function)
Display in outdoor units
[Available]
- Cooling and heating running condition
- Detail and unit number of error
- Speed of compressor and outdoor fan
- Value detected from sensor
2-1-1 Error code
1) New error codes are adopted.
Lamp flashing, wired remote control, outdoor unit 7-segment (number).
Checked by alphabet.
Current "EE" --> New "Er"
Shown in wired remote control, temperature setting.
02-01
2) Hybrid Flex Inverter System, error codes
Error code displayDefective componentAppearanceObject person
Indoor unit
Indoor units lamps,
flashing of operation
and timer lamps.
and continuous
flashing of economy
lamp.
Wired remote
control
LCD, 7-segment
display
- Indoor unit error
- Abnormal units
except indoor units
OPERATION (Green)
TIMER (Orange)
ECONOMY (Green)
- End user
- Installer
- Service
engineer
Outdoor unit
Four 7-segment lamps
on PCB
- Outdoor unit error
- Abnormal units
except outdoor units
(Indoor
unit, Branch-
box)
Branch box
Four lamps on PCB
- Branch box error,
*No exception
2-1-3 Response procedure at error code display
Case1 : End user
Occurrence of an error
Indoor unit lamp is flashing.
Case2 : Service Engineer
Site visit
Check outdoor ‚7-seg
to find defectives
LED981
LED982
POWER
ERROR
/ MODE
LED961LED962
MODE /
SELECT
EXIT
SW932
SW931
ENTER
CHECK
SW933
SW934
LED401
LED402
LED403
LED404
LED405
Amount of errors
- Service
engineer
- Installer
Inform object person of
the number of flashing.
Indoor unit error
(7-seg : E5U1)
Branch box error
(7-seg : EJ2U)
Outdoor unit error
02-02
Check indoor unit,
Branch Box
Check indoor unit,
Branch Box
Case3 : Error at construction
After performing the below-described work, repairs, inspections etc., always carry out the Check operation. Normal
operation will not be possible without performing the Check operation.
1. Things to comfirm before starting the Check operation
To ensure safety, check that the following work, inspections and operations have been completed.
1 Check that all work on the piping connecting the outdoor unit , indoor units and branch box
has been completed
2 Check that all work on the wiring connecting the outdoor unit, indoor units and branch box
has been completed
3 Is there a gas leakge? (At pipe connections flang connections and brazed areas )
4 Is the system changed with the specifed volume of refrigera
5 Is a breaker installed at the power supply cable of outdoor unit and every branch boxes?
6 Are the wires connected to the terminals without looseness, and in accorodance with the specifications?
7 Is the 3-way valve of the outdoor unit open?(Gas pipe and liquid pipe)
8 Is power supplied to the crank case heater for more than 12 hours?
9 Has the power supply of the all indoor units turned of
2. Restrictions applicable when performing the Check operation
When the Check run starts, all indoor units connected to the outdoor unit will start to run automatically. During
the Check run, you cannot check the operation of the indoor units separately. After the Check run, check the
operation of the indoor units separately in normal operation.
The operable temperature ranges for the Check run are: external temperature -15 to 46ºC(5 to 115°F); room
rature for cooling 18 to 46ºC(64 to 114°F); room temperature for heating -15 to 37ºC(5 to 98°F).
tempe
In the check run, the conditioner will automatically switch between cooling and heating depending on the
external temperature and internal temperature.
If the external temperature or internal temperature is outside the above operable temperature range, wait until
the temperature is within the operab
The Check run can be completed within 1 hour, but may take several hours depending on the external and
internal temperature conditions etc.
Please do not conduct the Check run with all the windows in the room closed. Otherwise the room temperature
could get too low or too high.
Depending on the difference of the room temperature of each room, a judgment may be impossible.
3. Operating procedure for Check run
(1)
Turn power on to the outdoor unit, indoor units and branch boxes.
After the displayed number of “8888.” has been turned off, press
the “CHECK” button.(approximately 2 minutes)
{
}
nt?
f?(Remote controller)
le range and then perform the Check run.
7 seg.display
( : On, : Blinking, : Off)
POWER
ERROR
(LED982)
MODE
(LED981)
(2)
Press and hold the "CHECK" BUTTO for
more than 3 seconds.
(3)
The number of connected branch boxes and indoor units will be
displayed on the 7 seg. display. Check that the displayed number
matches the actual number of connected units. Do not perform the
Check run if the displayed number of units is in error. If the Check run
was performed with the number of units in error, check the state of the
units and then perform the Check run again.
If the displayed number of units matches the installed number,
1
go to (4)
If the displayed number does not match the installed number,
2
check the following.
Are all the Branch boxes tume
Branch boxes are turned on, and go to (4).
d on?
Check that the
Are connection cables connected to all of the indoor units?
Turn of the power, connect the
Connection cable and go to (1).
(4)
Press and hold the "CHECK" button again for more than 3 seconds.
The Check run will start.
In the Check run, the following items will be checked.
The wiring and piping between the indoor units and the Branch box
1
Valve opening
2
To make an enforced stop, press the "MOD
E/EXIT" button.
You cannot execute the stop operation using the remote control.
To prevent electric shock, close the service panel during the
Check run.
(5) The Check run will stop automatically after allitems are completed.
When an error occurs, consult the following error display items.
Correct the error, and carry out the Check run again.
When the error display disappear even the measures fo
*
are taken, switch on the power again after turning off the
r error
power. When the power is turned on again after turned off,
wait approx. 10 minutes and turn on the power again.
02-03
CHECK
(Press and hold for more
than 3 seconds.)
CHECK
(currently
operating)
(operation has finished
normally (without error))
MODE/EXIT
[Example of 7 seg. display]
Number of
indoor units
Number of
branch boxes
(Press and hold for more
than 3 seconds.)
(Press the MODE/EXIT button.
“END” has been turned off.)
4. Error display
Error displayError itemContents
7 seg. displayLED lamp
(blinking)
( : On, : Blinking, : Off)
IndeterminableThe external or room temperature is outside the oper-
ablerange. The air conditioner will temporarily permit
normal operation, but the Check run should be carried
out again at a later date when the temperatures are
within the operable ranges.
(example)
Wiring number
error
The number of wirings between indoor unit and branch
box is not correct. Turn off all the units, and check
number of connected wires. After correcting the error,
turn on the power and carry out the Check run again.
Pipe number
error
The number of wirings between indoor unit and branch
box is not correct. Turn off all the units, and check
number of connected wires. After correcting the error,
turn on the power and carry out the Check run again.
If the number of pipes is correct, the internal heat-exchanger thermistor or branch box piping thermistor may
have come out of its holder, or a coil may have come
out
of an expansion valve. In this case, please contact
Service personnel.
Wiring errorA wiring error has occurred.
The location at which the wiring error has been determined will be displayed 7 seg. display. If there are
multiple wiring error locations, the display will cycle
through the locations. switching every 2 seconds. After
performing the following operation, turn off the power
and correct the wiring.
Note down the content of the wiring error.
Note down the number of blinks of the green LED on
the PCB of the branch box.
(The number of blinks indicates the device number of
the Branch box)
After correcting the wiring, turn on the power and carry
out the Check run again.
unit error
(In the case of the diagram)
Connect the connection cable which is connected to the
terminal A of Branch box (Primary) to the terminal B on
Branch box (Secondary 2).
Example : Indoor Unit Main PCB Error (Operation LED : 3 times, Timer LED : 2 times)
1 cycle
ON
1.0s
Operation LED
Timer LED
Economy LED
OFF
ON
OFF
ON
OFF
0.5s 0.5s
0.1s / 0.1s
0.5s 0.5s 0.5s 0.5s
4.0s
02-08
1.0s
3.0s
0.5s 0.5s
0.5s 0.5s
1.0s
4.0s
2-3-2 Remote Controller Display
<< SIMPLE REMOTE CONTROLLER >>
ERROR CODE DISPLAY
If an error occurs, the following display will be shown.
““ will appear in the set room temperature display.)
(
““ is displayed, immediately contact authorized
If
service personnel.
<< WIRED REMOTE CONTROLLER >>
ERROR CODE DISPLAY
Error code
Faulty unit No.
(Remote controller address)
Ex. Error code display
If an error occurs, the following display will be shown.
““ will appear in the set room temperature display.)
(
“ is displayed, immediately contact authorized
“
If
service personnel.
<< HOME CONTROLLER >>
ERROR DISPLAY
To show which indoor unit is the error displayed.
indoor unit's name and "ERROR" are alternately shown.
(0.5s indoor unit's name / 0.5s "ERROR")
Unit number (usually 0)Error code
Ex. Error code display
Ex. Error display
02-09
2-3-3 Error Code List for Simple and Wired Remote Controller
Error
Code
1 1
1 2
1 5
2 1
2 2
2 3
2 4
3 2
3 5
4 1
4 2
5 1
5 3
6 2
Error Contents
Serial Communication Error
Wired Remote Controller
C
ommunication Error
Check Run Unfinished
Number of Wires and Pipes Error
Indoor Unit Capacity Error
Connected Combination Error
Number of Indoor Units Error
Number of Branch boxes Error
Indoor Unit Model Information Error
EEPROM Access Abnormal
Manual Auto Switch Error
Indoor Room Thermistor Error
Indoor Heat Ex. Thermistor Error
Indoor Unit Fan Motor Error
Drainage Error
Outdoor Unit Model Information Error
Suction Pressure Sensor Error
High Pressure Switch Error
9 4
9 5
9 7
9 9
A 1
A 3
A 5
J 2Branch Box Error
Over Current Error
Compressor Control Error
Outdoor Unit Fan Motor Error
4 Way Valve Error
Discharge Temp. Error
Compressor Temp. Error
Low Pressure Error
ex : discharge thermistor 1 abnormal ex : indoor unit abnormal
Press the "SELECT" button
display change
When there is more than one error, display is changed by
Press the "SELECT" button
If some error is newly occured or resolved
during transition, it is reflected after going
back to "Annunciation".
.
02-11
Indication type7 Segment LED Pattern
Idling(stop)
Blank
Description
Cooling mode
Heating mode
Oil recovery operation
Defrost operation
Power saving operation
Low noise operation
Error display mode
(Number of errors occured)
Error display mode
(Error code)
Running the vacuum/
pump down mode
End of the function
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" eak "C" ut
"L" OW "N" OISE
ex.
ex.
"RUN"
"DONE"
Alternating display
During Cooling mode
During Heating mode
During Oil recovery operation.
Refer to 01-25 page for operation.
During Defrost operation.
Refer to 01-22 page for operation.
During Power saving operation.
Refer to 01-29 page for o
peration.
During Low noise operation.
Refer to 01-29 page for operation.
Number of errors occured are displayed.
(Ex. Two error codes present.)
Refer to 02-11 page for details.
Error codes are displayed.
(Ex. Discharge thermistor error)
Refer to 02-11 page for details.
Vacuum/ Pump down mode running.
The function is finished normally.
(Function is "Test-run start/ stop"
and "EEPROM memory clear".)
Performing function failed
Power off
Preparation display
Connected units display
(Only for Check run)
Running Check.
End of Check run
Memory clear
Error display for Check run
(Wiring number error)
Error display for Check run
(Pipe number error)
Error display for Check run
(Wiring error)
Indeterminable
"FAIL"
"P" OWER "OFF"
ex.
Number of Branch boxes
"C" HECK "RUN"
"END"
"P" IPE ">" "L" INE
"P" IPE "<" "L" INE
ex.
1st Branch box & terminal
Number of Indoor units
Blinking
2nd Branch box & terminal
Blinking
The function can not be performed.
When "P.oFF" is displayed,
turn off the power supplies of all units.
Number of "8888" is displayed
for 2 minutes after power on.
Wiring check in Check run is performing.
Check run is finished.
Number "0000" is blinking for 1 minute
when the memory is cleared after Check run
is finished.
Number of wirings between indoor unit and
branch box is n
ot correct.
Number of pipes between indoor unit and
branch box is not correct.
Wiring error has occured.
(Ex. Connection of Terminal A on the primary BB
to Terminal B on secondary 2 BB is wrong.)
The external or room temperature is outside
the operating range of Check run.
02-12
2-3-5 Error Code List for Outdoor Unit Display
Error
Code
E. 1 1. 3
E. 1 1. 4
E. 1 5. 6
E. 2 1. 2
E. 2 2. 1
E. 2 4. 2
E. 2 4. 3
E. 5 U. 1
E. 6 2. 1
E. 6 3. 1
E. 6 4. 1
E. 7 1. 1
E. 7 2. 1
E. 7 3. 3
E. 7 4. 1
E. 7 5. 1
E. 7 7. 1
Error Contents
Serial communication error
Serial communication error
Check run unfinished
Number of wires and pipes error
Indoor unit capacity error
Number of indoor units error
Number of Branch boxes error
Indoor Unit error
Outdoor unit model information error
Inverter error
A.F. voltage error
Discharge thermistor error
Compressor thermistor error
Heat Ex. Liquid outlet thermistor error
Outdoor thermistor error
Suction gas thermistor error
Heat sink thermistor error
Trouble
shooting
1, 37 ~ 39
1, 37 ~ 39
3
4
6
7
8 ~ 13
14
15
16
17
18
19
20
21
22
Error
Code
E. 8 2. 1
E. 8 2. 2
E. 8 3. 1
E. 8 4. 1
E. 8 6. 1
E. 8 6. 3
E. 8 6. 4
E. 9 4. 1
E. 9 5. 1
E. 9 7. 3
E. 9 9. 1
E. A 1. 1
E. A 3. 1
E. A 5. 1
E. J 2. U
Error Contents
Sub cool heat EX. gas inlet thermistor error23
Sub cool heat EX. gas outlet thermistor error
Liquid pipe thermistor error
Current sensor error
Discharge pressure sensor error
Suction pressure sensor error
High pressure switch error
Over current error
Compressor control error
Outdoor unit fan motor error
4-way valve error
Discharge temp. error
Compressor temp. error
Low pressure error
Branch box error
Trouble
shooting
1,40 ~ 45
24
25
26
27
28
29
30
31
32
33
34
35
36
02-13
2-3-6 Error status for Branch Box Display
When an error occurs, an error description displays in the LED (No.401 - 405).
Lit
(n)
Flashing (number of flashing)
Unlit
GreenRed
LED401LED402LED403LED404LED405
(1)
(2)
Branch box
(3)
identifying
display
Primary
unit
(4)
(5)
: (1)
Secondary
unit1
(6)
: (2)
Secondary
(7)
unit2
: (3)
(8)
Comment
Connected combination error
Power frequency error
EEPROM access error
Model information error
Serial communication error between
Outdoor Unit and branch box
Serial communication error between
branch boxe
Serial communication error between
branch boxes
Serial communication error between
Indoor Unit A and branch box
Serial communication error between
Indoor Unit B and branch box
Serial communication error between
Indoor Unit C and branch box
Indoor Unit A, liquid pipe thermistor error
(CN309)
Indoor Unit B, liquid pipe thermistor error
(CN309)
Indoor Unit C, liquid pipe thermistor error
(CN310)
Indoor Unit A, gas pipe thermistor error
(CN309)
Indoor Unit B, gas pipe thermistor error
(CN309)
Indoor U
(CN310)
Indoor Unit A, EEV control error (CN305)
Indoor Unit B, EEV control error (CN306)
Indoor Unit C, EEV control error (CN307)
s
nit C, gas pipe thermistor error
Trouble
shooting
37
38
39
40
41
1
1
1
1
1
1
42
43
44
(9)
02-14
Remote controller communication error
45
Error Indication Flashing Pattern
Example : "Serial communication error between Indoor Unit B and branch box" at Secondary unit1
(LED401: 2times, LED402: 5times, LED403: Unlit, LED404: Lit, LED405: Unlit)
1 cycle
ON
LED401
OFF
ON
LED402
OFF
ON
LED403
OFF
ON
LED404
OFF
ON
LED405
OFF
0.5s + 1.0s0.5s0.5s0.5s
0.5s 0.5s
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s0.5s + 1.0s
0.5s + 1.0s
02-15
2-4 TROUBLE SHOOTING
Trouble shooting 1
ALL UNIT Error Method:
Serial Communication Error
(Serial Forward / Reverse Transfer Error)
Indicate or Display:
Outdoor Unit :
Indoor Unit : Refer to Connection line and Serial signal error list
(Page 13 )
Error Code :
Detective Actuators:Detective details:
Outdoor Unit
Indoor Unit
Branch Box
(Primary / secondary)
When the branch box cannot properly receive the serial signal from
Outdoor unit / Indoor unit / Branch Box.
When the Outdoor unit / Indoor unit cannot properly receive the
serial signal from Branch Box.
- When power is turn-on : 2 minutes.
- In operation : 15 seconds.
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB(Outdoor unit) failure
4. Controller PCB(Indoor unit / Branch Box) failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
NO
YESYES
Check Point 2 : Check connection
Check for loose or removed connection line of error.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Design&
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
OK
Check Point 3 : Check the error unit of indoor unit
Check the which case?
Case 1. When only one indoor unit error
Case 2. When more than one indoor unit error
Case 3. When all indoor unit error
Case 1. When only one indoor unit error
Check the error display of indoor unit
Replace Controller PCB of indoor unit of error.
NG
Check Point 1-2 : Check external cause such as noise
Check if the ground connection.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check the error display of each Branch Box(Primary / secondary)
Replace Controller PCB of Branch Box (Primary or Secondary) of error
and execute the check operation again.
02-16
Case 2. When more than one indoor unit error (2unit or 3 unit)
Check the error display of each Branch Box (Primary or Secondary)
Replace Controller PCB of Branch Box (Primary or Secondary) of error and execute the check operation again.
NG
Check the error display of Indoor unit
Replace Controller PCB of indoor unit of error
Case 3. When all indoor unit error
Replace Controller PCB
Replace Controller PCB of Branch Box(Primary) and execute the check operation again.
NG
Check the error of Branch Box(Primary)
Check the error of Branch Box(Secondary) or error of Outdoor unit
When Outdoor unit error
Check the error display of Outdoor unit
Replace Main PCB of Outdoor unit and
execute the check operation again.
When Branch Box(Secondary) error
Check the error display of each Branch Box(Secondary)
Replace Controller PCB of Branch Box(Secondary) of error
and execute the check operation again.
NG
Check Point 1 Check the Outdoor Unit Filter PCB
Check F502 Fuse in Outdoor Unit Filter PCB.
>> If Fuse is open, replace F502 Fuse and Main PCB.
When there is no LED display of outdoor unit
Check the LED display of outdoor unit
Check F380 Fuse in Outdoor Unit Inverter PCB.
>> If Fuse is open, replace F380 Fuse and Main PCB.
If does not improve the symptom,
>> Replace F380 Fuse and Main PCB.
>> Replace Inverter PCB and Protector P501 of Filter PCB.( If Destruction of IPM or DB)
>> Replace Inverter PCB , ACTPM and Protector P501 of Filter PCB.
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Economy LED Cont i nu o u s F l as h .
Error Code : 1 2
Detective Actuators:
Indoor unit controller PCB
Wired Remote Controller
Forecast of Cause : 1. Terminal connection abnormal 2. Wired Remote Controller failure 3. Controller PCB failure
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor
unit, but the same signal has not been received more than 1 minute.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote controller and Indoor unit,
and check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote controller and Controller PCB
Check terminal voltage of controller PCB Connector. (Power supply for Remote)
Cassette / Duct Type CN14 , Wall mount Type CN6 , Small size Wall mount Type CN305(UTY-XCBXZ14)
If DC12V, Remote Controller failure (C
If DC0V, Controller PCB failure (Remote is OK) >>> Replace
-In case of re-installation is done due to removed connector or incorrect wiring, turn on the power again
ontroller PCB is OK) >>> Replace Remote Controller
Controller PCB and execute the check operation again.
DC
02-19
Trouble shooting 3
INDOOR UNIT Error Method:
Check run unfinished
Indicate or Display:
Outdoor Unit : E. 15. 6
Indoor Unit : Operation LED 1 times Flash, Timer LED 5 Times Flash,
Economy LED Cont i nu o u s F l as h .
Error Code : 15
Detective Actuators:Detective details:
Outdoor unit
Branch BOX
When the operation command is input by remote controller without
check operation completion.
Forecast of Cause :
1. Check operation not complete 2. Outdoor Main PCB changed 3. Branch BOX PCB changed
Check Point 1 : Check the indoor unit number connection
Check the number of indoor unit connected.
>> If the check operation not complete, execute it by referring to Installation Manual
or Design & Technical Manual.
>> Upon correcting incorrect setting, reset the power.
OK
Check Point 2 : Replace Main PCB
Replace Main PCB, and execute the check operation again.
INDOOR UNIT Error Method:
Number of Wires and Pipes Error
Indicate or Display:
Outdoor Unit : E.2 1.2
Indoor Unit : Operation LED 2 times Flash, Timer LED 1 Times Flash,
Economy LED Cont i nu o u s F l as h .
Error Code : 2 1
Detective Actuators:Detective details:
Indoor unit
When the operation command is input by remote controller without
check operation completion.
When a PCB has been replaced.
Check Point 1 : Check the indoor unit number connection
Check the number of indoor unit connected.
>> If the check operation not complete, execute it by referring to Installation Manual
or Design & Technical Manual.
>> Upon correcting incorrect setting, reset the power.
OK
Check Point 2 : Replace Controller PCB
Replace Controller PCB, and execute the check operation again.
02-20
Trouble shooting 4
INDOOR UNIT Error Method:
Indoor Unit Capacity Error
Indicate or Display:
Outdoor Unit : E. 22. 1
Indoor Unit : Operation LED 2 times Flash, Timer LED 2 Times Flash,
Economy LED Continuous Flash.
Error Code : 22
Detective Actuators:Detective details:
All indoor unit
When the total capacity of indoor units is outside of range
between 38,000BTU and 63,000BTU.
Forecast of Cause :
1. The selection of indoor units is incorrect 2. Main PCB(Outdoor unit) failure
Check Point 1 : Check the total capacity of indoor unit
Check the total capacity of the connected indoor units.
>> If abnormal condition is found, correct it by referring
to Installation Manual or Design & Technical Manual.
OKOK
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB(Outdoor unit),
and execute the check operation again.
02-21
Trouble shooting 5
INDOOR UNIT Error Method:
Connected Combination Error
Indicate or Display:
Outdoor Unit : E.5 U.1 or E.J 2.U
Indoor Unit : Operation LED 2 times Flash, Timer LED 3 Times Flash,
Economy LED Cont i nu o u s F l as h .
Error Code : 2 3
Detective Actuators:Detective details:
Indoor Unit
Branch Box
When power is on and one of the below occurs.
1. When the wirring is mistake
2. When the connection outdoor unit different.
3. When the connection indoor unit of unsupported multi.
Forecast of Cause:
1. connections condition in Controller PCB(Indoor unit / Branch Box)
Check Point 1 : Check the Indoor unit / Branch Box
Check the Indoor unit / Branch Box
>> If there is abnormal connect, correct it by referring to Installation Manual
or Design & Technical Manual.
>> Upon correcting incorrect setting, and execute the check operation again.
02-22
Trouble shooting 6
INDOOR UNIT Error Method:
Number of Indoor Units Error
Indicate or Display:
Outdoor Unit : E. 24. 2
Indoor Unit : Operation LED 2 times Flash, Timer LED 4 Times Flash,
Economy LED Continuous Flash.
Error Code : 24
Detective Actuators:Detective details:
Indoor Unit
When the total connection number of indoor units is outside of range
between 2 and 8.
Forecast of Cause :
1. Indoor unit connection failure
Check Point 1 : Check the indoor unit number connection
Check the indoor unit number connection.
>> If there is an abnormal condition, correct it by referring to Installation Manual
or Design & Technical Manual.
>> Upon correcting incorrect setting, reset the power.
02-23
Trouble shooting 7
Branch Box Error Method:
Number of Branch Boxes Error
Indicate or Display:
Outdoor Unit : E. 24. 3
Indoor Unit : Operation LED 2 times Flash, Timer LED 4 Times Flash,
Economy LED Continuous Flash.
Error Code : 24
Detective Actuators:Detective details:
Branch Box
When the number of branch boxes and are different,
and the operation command is input to the outdoor unit.
Memorized number at the check operation.
Number of Serial forward signal.
Forecast of Cause :
1. Branch box power failure
2. Branch box connection failure
Check Point 1 : Check the Branch box power
Check the Branch Box power
>> If there is an abnormal condition, power turned on.
OK
Check Point 2 : Check the Branch box connection
Check the Branch Box connection.
>> If there is an abnormal condition, correct it by referring to Installation Manual
or Design & Technical Manual.
>> Upon correcting incorrect setting, reset the power.
02-24
Trouble shooting 8
INDOOR UNIT Error Method:
Indoor Unit Model Information Error
EEPROM Access Abnormal
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 3 2
Detective Actuators:
Indoor Unit
Forecast of Cause : 1. External cause 2. connections condition in Controller PCB 3. Controller PCB failure
Check Point 1-1 : Reset power supply and operate
Does error indication show reappear?
3 continuous failure of read test of EEPROM at power on, or apparent model
information error from EEPROM. Also, error on model information upon model
information test of EEPROM, or Model information of EEPROM not possible to
recover.
NO
YES
Detective details:
Check Point 2 :
Check connections condition in Controller PCB
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Check Point 3 : Replace Controller PCB
Change Controller PCB and execute the
check operation again.
02-25
Trouble shooting 9
INDOOR UNIT Error Method:
Manual Auto Switch Error
Indicate or Display:
Outdoor Unit : No Display
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash,
Economy LED Continuous Flash.
Error Code : 3 5
Detective Actuators:Detective details:
Indoor Unit Controller PCB
Indicator PCB
When the Manual Auto Switch becomes ON for consecutive 30 or
more seconds.
Manual Auto Switch
Forecast of Cause :
1. Manual Auto Switch failure 2. Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual Auto Switch
Check if Manual Auto Switch is kept pressed.
Check ON/OFF switching operation by using a meter.
>> If Manual Auto Switch is disabled (on/off switching), replace it.
OKOK
Check Point 2 : Replace Controller PCB and Indicator PCB
If Check Point 1 do not improve the symptom, replace Controller PCB and Indicator PCB
and execute the check operation again.
02-26
Trouble shooting 10
INDOOR UNIT Error Method:
Indoor Room Thermistor Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Temperature Thermistor
Indoor unit thermistor is open or short is detected always.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermisto r cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (° F )
776859504132
10.012.515.820.125.233.6Resistance Value ( )
Temperature (° F )
122113104
3.54.35.3Resistance Value ( )
86
8.0
95
6.5
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct circuit diagram (Connector connection)
CN5
CN7
CN8
121
2
1
2
11
22
GRAY
BLACK
BLACK
H/E (MID) Thermistor
Room Temp. Thermistor
GRAY
Cassette circuit diagram (Connector connection)
GRAY
CN5
CN8
121
2
11
22
GRAY
BLACK
BLACK
H/E (MID) Thermistor
Room Temp. Thermistor
Small size Wall mount circuit diagram(Connector connection)
BLACK
1
1
BLACK
2
CN4
2
BLACK
3
3
BLACK
4
4
Wall mount Scircuit diagram (Direct soldering to PCB)
RED
1
CN3
CN1
WHITE
2
BLACK
1
BLACK
2
DC
H/E Thermistor
Room Temp. Thermistor
BLACK
1
1
2
2
BLACK
3
3
H/E Thermistor
Room Temp. Thermistor
If the voltage does not appear, replace Controller PCB and execute the check operation again.
02-27
Trouble shooting 11
INDOOR UNIT Error Method:
Indoor Heat Ex. Thermistor Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB
Detective details:
Indoor unit thermistor is open or short is detected always.
Check if connector is loose or removed
Check erroneous connection
Check if thermisto r cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (° F )
Resistance Value ( )
Temperature (° F )
122113104
776859504132
49.862.579.1100.9129.8168.6
86
40.0
95
32.4
Resistance Value ( )
17.821.226.3
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct circuit diagram (Connector connection)
CN5
CN7
CN8
121
2
1
2
11
22
GRAY
BLACK
BLACK
H/E (MID) Thermistor
Room Temp. Thermistor
GRAY
Cassette circuit diagram (Connector connection)
GRAY
CN5
CN8
121
2
11
22
GRAY
BLACK
BLACK
H/E (MID) Thermistor
Room Temp. Thermistor
Small size Wall mount circuit diagram(Connector connection)
BLACK
1
1
BLACK
2
CN4
2
BLACK
3
3
BLACK
4
4
Wall mount circuit diagram (Direct soldering to PCB)
RED
1
CN3
CN1
WHITE
2
BLACK
1
BLACK
2
DC
H/E Thermistor
Room Temp. Thermistor
BLACK
1
1
2
2
BLACK
3
3
H/E Thermistor
Room Temp. Thermistor
If the voltage does not appear, replace Controller PCB and execute the check operation again.
02-28
Trouble shooting 12
INDOOR UNIT Error Method:
Indoor Unit Fan Motor Error
Detective Actuators:
Indoor Unit Controller PCB
Indoor Fan Motor
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 5 times Flash, Timer LED 1 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 5 1
Detective details:
When Indoor fan control is either phase control or DC control and rotation feed
back control is ON, the feed back rotation value becomes 0 and lasts for more
than 1 minute at motor operation condition. Or, the feed back rotation value
continues at 1/3 of target value for more than 1 minute.
Forecast of Cause : 1. Fan MOTOR failure 2. Fan motor winding open 3. Motor protection by surrounding temp. increase
4. Controller PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check Motor winding
Check Indoor Fan motor
>>If Fan motor is abnormal, replace it.
OK
Check Point 3 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation..
OK
Check Point 4 : Replace Controller PCB
Change Controller PCB and execute the check operation again.
02-29
Trouble shooting 13
INDOOR UNIT Error Method:
Drainage Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 5 times Flash, Timer LED 3 Times Flash,
Economy LED Continuous Flash.
Error Code : 5 3
Detective Actuators:
Indoor Unit Controller PCB Circuit
Float Switch
Forecast of Cause : 1. Float switch failure 2. Shorted connector/wire 3. Controller PCB failure
4. Drain pump failure 5. Hose clogging
Detective details:
When Float switch is ON for more than 3 minutes.
Check Point 1 : Check Float Switch
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is abnormal, replace it.
ONOFF
OK
Check Point 2 : Check Connector (CN 9) / Wire
Check loose contact of CN9 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
OK
Check Point 3 : Check Drain Hose
Check Drain Hose .
>>If there is Hose clogging. Please clear the clog.
OK
Check Point 4 : Check Controller PCB
If Check Point 1 ~ 3 do not improve the symptom, change
Controller PCB and execute the check operation again.
Attention!!
Wall mount / Small size wall mount type
does not have a float switch.
In this case, replace Controller PCB
and set up the original address.
Please refer to.
02-30
Trouble shooting 14
OUTDOOR UNIT Error Method:
Outdoor Unit Model Information Error
Indicate or Display:
Outdoor Unit : E. 62. 1
Indoor Unit : Operation LED 6 times Flash, Timer LED 2 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 62
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure
Check Point 1-1 : Turn the power
on agaun.
Error displayed again?
NO
Detective details:
Access to EEPROM failed due to some cause after outdoor unit started.
Check Point 1-2 : External cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connected correctly or there are no related cables near the
power line.
YES
Check Point 2 : Replace Main PCB
Change Main PCB, and execute the check operation again.
02-31
Trouble shooting 15
OUTDOOR UNIT Error Method:
Inverter Error
Indicate or Display:
Outdoor Unit : E. 63. 1
Indoor Unit : Operation LED 6 times Flash, Timer LED 3 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 63
Detective Actuators:
Inverter PCB
Main PCB
Filter PCB
Forecast of Cause :
1. External cause
2. Power supply line & Communication line to Filter PCB to Inverter PCB wiring disconnection, open
3. Inverter PCB failure
4. Main PCB failure
5. Filter PCB failure
Check Point 1-1 :
Turn the power on again.
Error displayed again?
Detective details:
Error information received from Inverter PCB
NO
Check Point 1-2 : External cause
Check if temporary voltage drop was not generated.
Check if temporary open was not generated.
Check if ground is connected correctly or there are no related cables near the
power line.
OK
Check Point 2 : Check the wiring
(Inverter PCB to Main PCB, Inverter PCB to Filter PCB)
Connector and wiring connection state check
Cable open check
OK
Check Point 3 : Replace Inverter PCB
If Check Point 1,2 do not improve the symptom, replace Inverter PCB(Outdoor unit),
and execute the check operation again.
OK
Check Point 4 : Replace Main PCB
If Check Point 3 do not improve the symptom, replace Main PCB(Outdoor unit),
and execute the check operation again.
OK
Check Point 5 : Replace Filter PCB
If Check Point 4 do not improve the symptom, replace Filter PCB(Outdoor unit),
and execute the check operation again.
02-32
Trouble shooting 16
OUTDOOR UNIT Error Method:
A.F Voltage Error
Indicate or Display:
Outdoor Unit : E. 64. 1
Indoor Unit : Operation LED 6 times Flash, Timer LED 4 Times Flash
Economy LED Cont i nu o u s F l a sh .
Error Code : 64
Check Point 1 : Check connections condition in control unit
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check ACTPM
Check ACTPM (PARTS INFORMATION 8).
If ACTPM is abnormal, replace it.
Check Point 3 : Replace Inverter PCB
If Check Point 1,2 do not improve the symptom,
replace Inverter PCB, and
execute the check operation again.
02-33
Trouble shooting 17
OUTDOOR UNIT Error Method:
Discharge Thermistor Error
Indicate or Display:
Outdo
or Unit : E. 71. 1
Indoor Unit : Operation LED 7 times Flash, Timer LED Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 71
Detective Actuators:
Discharge temperature thermistor
Forecast of Cause :
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Discharge temperature thermistor short detected
Discharge thermistor open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN62:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(COMP SHELL)
THERMISTOR
(DIS.TEMP.)
BLACK
BLACK
BLACK
BLACK
1234
1234
CN62
Discharge temperature thermistor (CN62:1-2)
If the voltage does not appear, replace Main PCB,
and execute the check operation again.
DC
02-34
Trouble shooting 18
OUTDOOR UNIT Error Method:
Compressor Thermistor Error
Indicate or Display:
Outdoor Unit : E. 72. 1
Indoor Unit : Operation LED 7 times Flash, Timer LED 2 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 72
Detective Actuators:
Compressor temperature thermistor
Forecast of Cause :
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Compressor temperature thermistor short detected
Compressor thermistor open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 14".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN62:3-4) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(COMP SHELL1)
THERMISTOR
(DIS.TEMP.1)
BLACK
BLACK
BLACK
BLACK
1234
1234
CN62
Compressor temperature thermistor (CN62:3-4)
If the voltage does not appear, replace Main PCB
the check operation again.
DC
, and execute
02-35
Trouble shooting 19
OUTDOOR UNIT Error Method:
Heat Ex. Liquid Outlet Temp.
Thermistor Error
Indicate or Display:
Outdoor Unit : E. 73. 3
Indoor Unit : Operation LED 7 times Flash, Timer LED 3 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 73
Detective Actuators:
Heat exchanger liquid temperature
thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Heat exchanger outlet temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN63:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
BLACK
123
123
SC (LP OUT)
THERMISTOR
(HEX. PIPE. OUT.)
BLACK
BLACK
BLACK
5
4
4
5
CN63
Heat exchanger outlet temperature thermistor (CN63:1-2)
If the voltage does not appear, replace Main PCB
If the voltage does not appear,
the check operation again.
DC
, and execute
02-36
Trouble shooting 20
OUTDOOR UNIT Error Method:
Outdoor Thermistor Error
Indicate or Display:
Outdoor Unit : E. 74. 1
Indoor Unit : Operation LED 7 times Flash, Timer LED 4 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 74
Detective Actuators:
Outdoor temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Outdoor temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2: Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN61:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
(OUT TEMP.)
THERMISTOR
BLACK
BLACK
123
123
CN61
Outdoor temperature thermistor (CN61:1-3)
If the voltage does not appear, replace Main PCB
If the voltage does not appear, replace Main PCB
the check operation again.
DC
, and execute
02-37
Trouble shooting 21
OUTDOOR UNIT Error Method:
Suction Gas Thermistor Error
Indicate or Display:
Outdoor Unit : E. 75. 1
Indoor Unit : Operation LED 7 times Flash, Timer LED 5 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 75
Detective Actuators:
Suction gas temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor failure3. Main PCB failure
Detective details:
Suction gas temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN66:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(SUC. TEMP)
BLACK
BLACK
1 2 3
1 2 3
CN66
Suction gas temperature thermistor (CN66:1-3)
If the voltage does not appear, replace Main PCB, and execute
the check operation.
DC
02-38
Trouble shooting 22
OUTDOOR UNIT Error Method:
Heat Sink Thermistor Error
Indicate or Display:
Outdoor Unit : E. 77. 1
Indoor Unit : Operation LED 7 times Flash, Timer LED 7 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 77
Detective Actuators:
Inverter PCB
Forecast of Cause :
Detective details:
Heat sink temperature thermistor (Built-in IPM) open/short detected
1. Inverter PCB failure
If this error is displayed, replace Inverter PCB
02-39
Trouble shooting 23
OUTDOOR UNIT Error Method:
Sub-cool Heat EX. Gas Inlet
Thermistor Error
Indicate or Display:
Outdoor Unit : E. 82. 1
Indoor Unit : Operation LED 8 times Flash, Timer LED 2 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 82
Detective Actuators:
Sub-cooling heat exchanger gas inlet
temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor failure3. Main PCB failure
Detective details:
Sub-cooling heat exchanger gas inlet temperature thermistor short or
open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN65:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(SC.OUT.LIQ)
THERMISTOR
(SC.INT.GAS)
BLACK
BLACK
BLACK
BLACK
1234
1
2 34
CN65
Sub-cooling heat exchanger gas inlet thermistor (CN65:1-2)
If the voltage does not appear, replace Main PCB
and execute the check operation again.
DC
,
02-40
Trouble shooting 24
OUTDOOR UNIT Error Method:
Sub-cool Heat Ex. Gas Outlet
Thermistor Error
Indicate or Display:
Outdoor Unit : E. 82. 2
Indoor Unit : Operation LED 8 times Flash, Timer LED 2 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 82
Detective Actuators:
Sub-cooling heat exchanger gas outlet
temperture thermistor
Forecast of Cause :
1. Connector connection failur, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Sub-cooling heat exchanger gas outlet temperture thermistor short or
open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN63:4-5) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Outdoor Unit : E. 83. 1
Indoor Unit : Operation LED 8 times Flash, Timer LED 3 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 83
Detective Actuators:
Heat exchanger liquid outlet thermistor
Forecast of Cause :
1. Connector connection failur, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Heat exchanger liquid pipe thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN63:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Outdoor Unit : E. 84. 1
Indoor Unit : Operation LED 8 times Flash, Timer LED 4 Times Flash,
Economy LED Cont i n uo u s F l a sh .
Error Code : 84
Detective Actuators:
Judgment from value sensed by current
sensor (current sensor for inverter)
* Current sensor is mounted on
Filter PCB
Forecast of Cause :
1. Filter PCB to Inverter PCB CT system wiring connector disconnection, open
2. Filter PCB failure (Power supply section, current sensor section)
3. Inverter PCB failure
Detective details:
When the compressor stops and 30seconds has passed,
and the current value from INVERTER is over than 15A,
outdoor unit is stopped permanently by protection.
Check Point 1 : Filter PCB to Inverter PCB CT system wiring connection state
Connector and wiring connection state check
Cable open check
OK
Check Point 2 : Check Filter PCB and Inverter PCB
If Check Point 1 do not improve the symptom, replace Filter PCB
.
NG
Check Point 3 : Check Filter PCB and Inverter PCB
If Check Point 2 do not improve the symptom, replace Inverter PCB.
02-43
Trouble shooting 27
OUTDOOR UNIT Error Method:
Discharge Pressure Sensor Error
Indicate or Display:
Outdoor Unit : E. 86. 1
Indoor Unit : Operation LED 8 times Flash, Timer LED 6 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 86
Detective Actuators:
Discharge pressure sensor
Forecast of Cause :
1. Discharge pressure sensor connector disconnection, open
2. Discharge pressure sensor failure3. Main PCB failure
Detective details:
When any of the following conditions is satisfied, a discharge pressure
sensor error is generated.
1. 30 seconds or more have elapsed since the outdoor unit power was turned
on and pressure sensor detected value 0.3V continued for 30 seconds
or more
2. 30 seconds or more have elapsed since the outdoor unit power was turned
on and pressure sensor detected value 5.
Check Point 1 : Check the discharge pressure sensor connection state
Connector connection state check
Cable open check
OK
Check Point 2 : Check the discharge pressure sensor
Sensor characteristics check
* For the characteristics of the discharge pressure sensor,
refer to the "Service Parts Information 6".
0V was detected.
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN91:1-4) voltage value = 5V
Remove the thermistor from Main PCB, check the volt
PRESSURE
SENSOR
(HIGH)
PS
WHITE
BLACK
RED
4
23
1
123
4
age.
CN91
Discharge pressure sensor (CN91:1-4)
If the voltage does not appear, replace Main PCB
the check operation again.
DC
, and execute
02-44
Trouble shooting 28
OUTDOOR UNIT Error Method:
Suction Pressure Sensor Error
Indicate or Display:
Outdoor Unit : E. 86. 3
Indoor Unit : Operation LED 8 times Flash, Timer LED 6 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 86
Detective Actuators:
Suction pressure sensor
Forecast of Cause :
1. Suction pressure sensor connector disconnection, open
2. Suction pressure sensor failure3. Main PCB failure
Detective details:
When any of the following conditions is satisfied, a suction pressure
sensor error is generated.
1. 30 seconds or more have elapsed since the outdoor unit power was turned
on and pressure sensor detected value 0.06V continued for 30
seconds or more.
2. 30 seconds or more have elapsed since the outdoor unit power was turned
on and pressure sensor detected v
Check Point 1 : Check the suction pressure sensor connection state
Connector connection state check
Cable open check
OK
Check Point 2 : Check the suction pressure sensor
Sensor characteristics check
* For the characteristics of the suction pressure
refer to the "Service Parts Information 6".
sensor,
alue 5.0V was detected.
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN92:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
PRESSURE
SENSOR
(LOW)
PS
WHITE
RED
BLACK
123
123
CN92
Suction pressure sensor (CN92:1-3)
If the voltage does not appear, replace Main PCB
the check operation again.
DC
, and execute
02-45
Trouble shooting 29
OUTDOOR UNIT Error Method:
High Pressure Switch Error
Indicate or Display:
Outdoor Unit : E. 86. 4
Indoor Unit : Operation LED 8 times Flash, Timer LED 6 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 86
Detective Actuators:
High pressure switch
Forecast of Cause :
1. High pressure switch connector disconnection, open
2. High pressure switch characteristics failure3. Main PCB failure
Detective details:
When the power was turned on, "high pressure switch : open" was detected.
Check Point 1 : Check the high pressure switch connection state
Connector and wiring connection state check
Cable open check
OK
Check Point 2 : Check the high pressure switch characteristics
Switch characteristics check
* For the characteristics of high pressure switch, refer to below.
OK
Check Point 3 : Replace Main PCB
Change Main PCB, and execute the check operation again.
Type of contact
C
Pressure
Characteristics of pressure switch
Contact : Short Open
Contact : Open Short
H
(CN101)
Pressure switch 1
608.7 14.5 PSI
463.8 21.7 PSI
02-46
Trouble shooting 30
OUTDOOR UNIT Error Method:
Over Current Error
Indicate or Display:
Outdoor Unit : E. 94. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 4 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : 94
Detective Actuators:
Inverter PCB
Forecast of Cause :
1. Outdoor unit fan operation defective, foreign matter on hear exchanger, excessive rise of ambient
temperature
"Protection stop by "overcurrent generation after inverter compressor start
processing completed'''' generated consecutively 10 times.
* The number of generations is reset if the start-up of the compre
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
OK
ssor succeeds.
Check Point 2 : Check the Inverter PCB
Inverter PCB check
OK
Check Point 3 : Replace the Inverter compressor
Inverter compressor replacement
02-47
Trouble shooting 31
OUTDOOR UNIT Error Method:
Compressor Control Error
Indicate or Display:
Outdoor Unit : E. 95. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 5 Times Flash
Economy LED Continuous Flash.
Error Code : 95
Detective Actuators:Detective details:
Outdoor Unit Inverter PCBCompressor
When "compressor location detection error" is detected consecutively
5 times, within 40 seconds after start-up.
(Compressor location detection becomes over than 90°)
If the voltage is not correct, replace Main PCB, and execute the check operation again.
3456
3456
CN243
YELLOW
BLUE
7
7
02-49
Trouble shooting 33
OUTDOOR UNIT Error Method:
4-way valve error
Indicate or Display:
Outdoor Unit : E. 99. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 9 Times Flash
Economy LED Cont i nu o u s F l as h .
Error Code : 99
Detective Actuators:
Indoor Unit Controller PCB Circuit
Heat Exchanger Temperature Thermistor
Room Temperature Thermistor
4-way valve
Detective details:
When the indoor heat exchanger temperature is compared with
the room temperature, and either following condition is detected
continuously two times, the compressor stops.
Cooling or Dry operation
[Indoor heat exchanger temp.] - [Room temp.] > 50degF
Heating operation
[indoor
If the same operation is repeated 2 times,
the compressor stops permanently.
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Check thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor, If defective, replace the thermistor.
OKOK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN30 from PCB and check the resistance value of coil.
Resistance value is about 1.4k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1- 3 do not improve the symptom, replace Main PCB,
and execute the check operation again.
02-50
Trouble shooting 34
OUTDOOR UNIT Error Method:
Discharge Temp. Error
Indicate or Display:
Outdoor Unit : E. A1. 1
Indoor Unit : Operation LED 10 times Flash, Timer LED 1 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : A1
Detective Actuators:
Detective details:
Discharge temperature thermistor
Forecast of Cause :
1. 3-way valve not opened
2. EEV defective, strainer clogged
3. Outdoor unit operation
4. Discharge temperature thermistor
5. Insufficient refrigerant
<Cooling operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV (EEV2, indoor unit EEV) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3, 4 "
"Protection stop by "discharge temperature 239degF during compressor
operation'''' generated 2 times within 24 hours.
failure, foreign matter on heat exchanger
failure
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV (EEV1, EEV2) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3, 4"
OK
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check(PARTS INFORMATION 7)
OK
Check Point 4 : Check the discharge thermistor
Discharger thermistor characteristics check
(Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Service Parts Information 5".
:
OK
Check Point 5 : Check the refrigerant amount
Leak check
OK
02-51
Trouble shooting 35
OUTDOOR UNIT Error Method:
Compressor Temp. Error
Indicate or Display:
Outdoor Unit : E. A3. 1
Indoor Unit : Operation LED 10 times Flash, Timer LED 3 Times Flash,
Econom
y LED Continuous Flash.
Error Code : A3
Detective Actuators:
Detective details:
Compressor temperature thermistor
Forecast of Cause :
1. 3-way valve not opened
2. EEV defective, strainer clogged
3. Outdoor unit operation
4. Compressor temperature thermistor
5. Insufficient refrigerant
<Cooling operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV (EEV2, indoor unit EEV) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3, 4".
"Protection stop by "compressor tempreture" 233degF during compressor
operation""generated 2 times within 24 hours
failure, foreign matter on heat exchanger
failure
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV (EEV1, EEV2) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3,4 ".
OK
Check Point 3 : Outdoor unit fan, heat exchanger chek
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check(PARTS INFORMATION 7)
OK
Check Point 4 : Check the compressor temperature thermistor
Compressor temperature thermistor characteristics check
(Check by disconnecting thermistor from PCB)
* For the characteristics of the thermistor, refer to the "Service Par
OK
Check Point 5 : Check the refrigerant amount
Leak check
OK
ts Information 5.
02-52
Trouble shooting 36
OUTDOOR UNIT Error Method:
Low Pressure Error
Indicate or Display:
Outdoor Unit : E. A5. 1
Indoor Unit : Operation LED 10 times Flash, Timer LED 5 Times Flash,
Economy LED Cont i nu o u s F l a sh .
Error Code : A5
Detective Actuators:
Detective details:
Suction pressure sensor
Forecast of Cause :
1. 3-way valve not opened 2. Outdoor unit ambient temperature too low
3. Outdoor unit fan operation defective, foreign matter at heat exchanger
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
"Protection stop by suction pressure 7.35PSI continued for 5 minutes"
repeats 5 times w
ithin 2 hours.
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Check Point 2 : Check the outdoor unit ambient temperature
Outdoor ambient temperature lower than operating range?
OK
OK
strainer clogging
Indoor unit EEV operation check
Strainer not clogged?
OK
Check Point 5 : Check the solenoid valve (SV1)
Solenoid valve operation check
OK
Check Point 6 : Check the suction pressure sensor
Suction pressure sensor characteristics check
* For the characteristics of the suction pressure sensor
(PARTS INFORMATION 5)
OK
Check Point 3 : Check the outdoor unit fan operation,
heat exchanger
No foreign oblect in air passage?
Heat exchange fins clogged
Fan rotates?
Outdoor unit fan motor check
OK
Check Point 4 : Check the outdoor unit EEV, strainer clogging
Outdoor unit EEV1 operation check
Strainer not clogged?
Refer to "Sevice Parts Information 3"
Check Point 7 : Check the refrigerant amount
Leak check
02-53
Trouble shooting 37
Branch Box Error Method:
Connected combination error
Indicate or Display:
Outdoor Unit : E. 11. 3
Branch Box : LED401/ 402/ 403/ 404/ 405 Lit
Indoor Unit : Operation LED 1times Flash, Timer LED 1times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
Error Code : 11
Detective Actuators:
Outdoor unit
Forecast of Cause :
1. Connected outdoor unit
Detective details:
When another outdoor unit in the future is connected to
the terminal "Outdoor unit" of Primary branch box.
Check Point 1 : Check the outdoor unit
Check the outdoor unit
>> If there is another outdoor unit, correct it by referring to Installation Manual
or Design & Technical Manual.
>> Upon correcting incorrect setting, reset the power.
02-54
Trouble shooting 38
Branch Box Error Method:
Power frequency error 1
Indicate or Display:
Outdoor Unit : E. 11. 3 or E. 11. 4
Branch Box : LED401/ 402/ 403/ 404 Lit, LED405 Unlit
Indoor Unit : Operation LED 1times Flash, Timer LED 1times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
Error Code : 11
Detective Actuators:
Branch Box Controller PCB
Forecast of Cause :
1. Connection failure 2. External cause 3. Controller PCB failure
Detective details:
When 4 continuous failures occurred at Power frequency test.
(Power supply of Branch Box)
Check Point 1-1 : Reset the power supply and operate
Does error indication reappear?
YES
Check Point 2 : Check connection
Check Cable/Breaker.
Check loose or removed connection.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Design &
Technical Manual.
OK
NO
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC187V(AC208V-10%) - 253V(AC230V+10%) appears
at Branch Box terminal "Power" L1 - L2.
OK
Check Point 4 : Replace Controller PCB.
If Check Point 1 ~ 3 do not improve the symptom,
replace Controller PCB.
AC
02-55
Trouble shooting 39
Branch Box Error Method:
Power frequency error 2
Indicate or Display:
Outdoor Unit : E. 11. 3 or E. 11. 4
Branch Box : LED401/ 402/ 403 Lit, LED404 Unlit, LED405 Lit
Indoor Unit : Operation LED 1times Flash, Timer LED 1times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
Error Code : 11
Detective Actuators:
Branch Box Controller PCB
Outdoor unit Main PCB
Outdoor Filter PCB
Forecast of Cause :
1. Connection failure 2. External cause 3. Controller PCB failure 4. Outdoor Main PCB failure
5. Outdoor Filter PCB failure
Detective details:
When 4 continuous failures occurred at Power frequency test.
( Branch Box (Primary) : Power supply for communication to outdoor unit.
Branch Box (Secondary) : Power supply for communication to
Check Point 1-1 : Reset the power supply and operate
Does error indication reappear?
YES
Check Point 2 : Check connection
Check Cable/Breaker.
Check loose or removed connection.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Design &
Technical Manual.
OK
primary branch box.)
NO
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment whic
h causes harmonic wave).
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
[Primary branch box]
>> Check if AC187V(AC208V-10%) - 253V(AC230V+10%) appears
at Branch box terminal "Outdoor unit" 1 - 2 (CN105).
If the voltage does not appear, replace Outdoor Filter PCB.
[Secondary branch box]
>> Check if AC187V(AC208V-10%) - 253V(AC230V+10%) appears
at Branch box terminal "Branch box" 1 - 2 (CN105).
If the voltage does not appear, replace Branch box controller PCB
AC
02-56
Trouble shooting 40
Branch Box Error Method:
EEPROM access error
Indicate or Display:
Outdoor Unit : E. J2. U
Branch Box : LED402 1time Flash, LED403/ 404/ 405 Unlit
Indoor Unit : Operation LED 13times Flash, Timer LED 2times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
Error Code : J2
Detective Actuators:
Branch Box Controller PCB
Forecast of Cause :
1. External cause 2. Defective for connection in controller unit 3. Controller PCB failure
Detective details:
When power is on and the access to EEPROM failed.
Check Point 1-1 : Reset power supply and operate
Does error indication show reappear?
YES
Check Point 2 : Check connections condition.
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
If Check Point 1, 2 do not improve the symptom,
replace Controller PCB.
NO
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
02-57
Trouble shooting 41
Branch Box Error Method:
Model information error
Indicate or Display:
Outdoor Unit : E. J2. U
Branch Box : LED402 2times Flash, LED403/ 404/ 405 Unlit
Indoor Unit : Operation LED 13times Flash, Timer LED 2times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
Error Code : J2
Detective Actuators:
Branch Box Controller PCB
Forecast of Cause :
1. External cause 2. Defective for connection in controller unit 3. Controller PCB failure
Detective details:
When power is on and model information of EEPROM is incorrect.
Check Point 1-1 : Reset power supply and operate
Does error indication show reappear?
YES
Check Point 2 : Check connections condition.
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
If Check Point 1, 2 do not improve the symptom,
replace Controller PCB.
NO
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
02-58
Trouble shooting 42
Branch Box Error Method:
Indoor Unit A, B, C, liquid pipe
thermistor error (CN309 / 310)
Indicate or Display:
Outdoor Unit : E. J2. U
Branch Box : LED402 6times Flash
(Indoor unit A): LED403 Lit, LED404/ 405 Unlit
(Indoor unit B): LED403 Unlit, LED404 Lit, LED405 Unlit
(Indoor unit C):
Indoor Unit : Operation LED 13times Flash, Timer LED 2times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
Error Code : J2
LED403/ 404 Unlit, LED405 Lit
Detective Actuators:
Branch Box Controller PCB
Indoor unit A,B,C Liquid pipe Thermistor
When open or shorted Liquid pipe Thermistor is detected.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°F)
Resistance Value (k )
Temperature (°F)
122113104
776859504132
49.862.579.1100.9129.8168.6
86
40.0
95
32.4
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
17.821.226.3
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Schematic Diagram (Connector connection)
Liquid pipe Thermistor (Unit A) (CN309 Wire:Black)
Liquid pipe Thermistor (Unit B) (CN309 Wire:Black)
Gas pipe Thermistor (Unit A) (CN309 Wire:Black)
Gas pipe Thermistor (Unit B) (CN309 Wire:Black)
Liquid pipe Thermistor (Unit C) (CN310 Wire:Black)
Gas pipe Thermistor (Unit C) (CN310 Wire:Black)
If the voltage does not appear, replace Controller PCB .
02-59
DC
Trouble shooting 43
Branch Box Error Method:
Indoor Unit A, B, C, gas pipe
thermistor error (CN309 / 310)
Indicate or Display:
Outdoor Unit : E. J2. U
Branch Box : LED402 7times Flash
(Indoor unit A): LED403 Lit, LED404/ 405 Unlit
(Indoor unit B): LED403 Unlit, LED404 Lit, LED405 Unlit
(Indoor unit C):
Indoor Unit : Operation LED 13times Flash, Timer LED 2times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
Error Code : J2
LED403/ 404 Unlit, LED405 Lit
Detective Actuators:
Branch Box Controller PCB Circuit
Indoor unit A,B,C Gas pipe Thermistor
When open or shorted Liquid pipe Thermistor is detected.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°F)
Resistance Value (k )
Temperature (°F)
122113104
776859504132
49.862.579.1100.9129.8168.6
86
40.0
95
32.4
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
17.821.226.3
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Schematic Diagram (Connector connection)
Liquid pipe Thermistor (Unit A) (CN309 Wire:Black)
Liquid pipe Thermistor (Unit B) (CN309 Wire:Black)
Gas pipe Thermistor (Unit A) (CN309 Wire:Black)
Gas pipe Thermistor (Unit B) (CN309 Wire:Black)
Liquid pipe Thermistor (Unit C) (CN310 Wire:Black)
Gas pipe Thermistor (Unit C) (CN310 Wire:Black)
If the voltage does not appear, replace Controller PCB .
02-60
DC
Trouble shooting 44
Branch Box Error Method:
Indoor Unit A, B, C, EEV control error
(CN305 / 306 / 307)
Indicate or Display:
Outdoor Unit : E. J2. U
Branch Box : LED402 8times Flash
(Indoor unit A): LED403 Lit, LED404/ 405 Unlit
(Indoor unit B): LED403 Unlit, LED404 Lit, LED405 Unlit
Indoor Unit : Operation LED 13times Flash, Timer LED 2times Flash,
Economy LED Flashing (0.1s ON / 0.1s OFF)
In cooling or dry operation, when the Indoor unit heat exchanger temperature
becomes lower than 3degC for 5minutes,the compressor stops and
EEV is initialized.
After the compressor restarts, if the same protection is repeated within
1hr, the compressor stops permanently.
OK
Check Point 2 : Check Coil of EEV
Remove connector, check each winding resistance of Coil.
Read wire
White - Red
Yellow - Red
Orange - Red
Blue - Red
If Resistance value is abnormal, replace EEV.
Resistance value (68°F)
46
± 4
OK
Check Point 3 : Check Voltage from Controller PCB
Remove Connector and check Voltage (DC12V).
>> If it does not appear, replace Controller PCB.
OK
DC
02-61
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.