2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY.....................
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
01-13
01-14
01-14
01-14
01-16
01-17
01-20
01-20
01-21
01-21
01-22
01-23
02-01
02-01
02-03
02-29
2-4 SERVICE PARTS INFORMATION............................................................................
3. DISASSEMBLY PROCESS
02-34
DUCT type
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INVERTER
R410A
1 . DESCRIPTION OF EACH
CONTROL OPERATION
1. DESCRIPTION OF EACH CONTROL OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-1. COOLING OPERATION
1-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2°C lower than a set temperature, the compressor
will be stopped.
* When the room temperature is between +2°C to -2°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the
fan speed mode and the outdoor temperature.
( Table 1 : Compressor Frequency Range )
minimum
frequency
maximum
frequency
AO* G60LATT
15rps78rps
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
When the room
temperature rises
Outdoor air
temperature
34°C
30°C
19°C
10°C
0°C
When the room
temperature drops
A zone
B zone
C zone
D zone
E zone
F zone
36°C
32°C
21°C
12°C
2°C
Fan speed mode
AO* G60LATT
A zone
B zone
C zone
D-F zone
HiMeLo
78rps
78rps
67rps
59rps
67rps
67rps
59rps
55rps
59rps
59rps
52rps
47rps
01-01
1-2. HEATING OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower 3°C than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2°C than a set temperature, the compressor
will be stopped.
* When the room temperature is between +2°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
( Table 2 : Compressor Frequency Range )
minimum
frequency
maximum
frequency
AO* G60LATT
18rps85rps
01-02
1-3. DRY OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Table 3.
( Table 3 : Compressor frequency )
Operating
frequency
X zone
AO* G60LATT
J zone
Y zone
( Fig.2 : Compressor Control based on Room Temperature )
41rps
0rps
When the room
temperature drops
X zone
Ts+0.5°C
J zone
Ts-1.5°C
Y zone
( Fig.3 : Indoor Fan Control )
Compressor
ON
OFF
Setting air flow
Lo
S-Lo
When the room
temperature rises
Ts+1.5°C
Ts-0.5°C
Ts : Setting temperature
OFF
103060360120360120 1030(sec)
01-03
1-4. AUTO CHANGEOVER OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum
mode from among the Heating, Cooling, Dry and Monitoring mode. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1°C steps.
When operation starts, indoor fan is operated for around 2 minutes.
1
Room temperature and outdoor temperature are sensed, and the operation mode is selected
in accordance with the table below. <Monitoring mode>
( Table 4 : Operation mode selection table )
Room temperature (TR)
Operation mode
TR : Room temperature
Ts : Setting temperature
TR> Ts+2°C
Ts+2°C TR Ts -2°C
TR < Ts -2°CHeating
Cooling
(Automatic dry)
*Middle zone
*If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling, Dry, and Heating mode,
indoor unit will be operated by the same operation mode.
(2). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling, Dry, and Heating mode, indoor unit will be operated
according to the outdoor temperature as below.
( Fig. 4 : Outdoor temperature zone selection )
Cooling mode
25°C
Heating mode
2
When Cooling or Dry mode was selected at and air flow mode is Auto, the air conditioner operates as follow.
The same operation as COOLING OPERATION AND DRY OPERATION of page 01-01 is performed.
When the room temperature has remained at set temperature -1.5°C, operation is automatically
switched to Dry mode.
If the room temperature reaches set temperature +2°C during Dry mode, operation returns to Cooling.
1
( Fig.5 : Auto changeover : Cooling - Dry )
( Air flow mode : Auto )
Ts +1°C
Ts -1.5°C
Ts -2.5°C
When the room
temperature drops
3
When Heating was selected at , the same operation as HEATING OPERATION of page
01-02 is performed.
4
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the Cooling(Auto:Dry) or Heating mode was selected at above, operation is switched
to Monitoring and the operation mode is selected again.
The airflow can be switched in 4 steps such as Auto, Lo, Me, Hi, while the indoor fan only runs.
When [Auto] is selected, the indoor fan motor runs Me.
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 6.
On the other hand, if switched in [Hi] ~ [Lo], the indoor motor will run at a constant airflow of [Cool]
operation modes Lo, Me, Hi ,as shown in Table 5.
( Fig.6 : Airflow change - over ( Cooling : AUTO ) )
*1
When the room
temperature rises
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
=
2°C > TR-Ts > 1°C
=
1°C > TR-Ts
Hi mode
Me mode
Lo mode
When the room
temperature drops
TR-Ts > 2.5°C
=
2.5°C > TR-Ts > 1.5°C
1.5°C > TR-Ts
*1 : Contains a condition to the following
When the operation mode is set to Auto mode
at the start of operation.
When the setting temperature was changed.
When the operation mode was changed to Cooling mode.
When the airflow mode was changed to A
=
uto mode.
01-06
4. HEATING OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 7.
On the other hand, if switched in [Hi] ~ [Lo], the indoor motor will run at a constant airflow
of [Heat] operation modes Lo, Me, Hi, as shown in Table 5.
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
Indoor heat exchanger
temperature
TR-Ts > -1.0°C
=
1.0°C > TR-Ts > -2.0°C
=
-2.0°C > TR-Ts
Lo mode
Me mode
Hi mode
TR-Ts > -1.5°C
=
-1.5°C > TR-Ts > -2.5°C
-2.5°C > TR-Ts
=
5. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Fig. 8, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
( Fig.8 : Cool Air Prevention Control )
Indoor heat exchanger
temperature
Setting Fan mode
27°C
S-Lo mode
13 min. later
24°C
STOP
Indoor heat exchanger
temperature
Setting Fan mode
27°C
24°C
Lo
Lo
6. DRY OPERATION
Refer to the Fig. 3.
During the dry mode operation, the fan speed setting can not be changed.
7. DEFROST OPERATION
When the defrost operation starts, the indoor fan runs according to cool air preventtion control for 20 seconds.
And the fan is stopped if 20 seconds have passed.
When 60 seconds have passed after defrost operation is released,
the fan runs according to cool air preventtion control
01-07
1-6. OUTDOOR FAN CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
( Table 6 : Fan speed of the outdoor unit )
Cooling / DryHeating
AO* G60LATT
The outdoor fan speed changes in the range mentioned above depending on the compressor
*
frequency and outdoor temperature.
(When the compressor frequency and outdoor temperature increase, the outdoor fan speed
also changes to the higher speed.
When the compressor frequency and outdoor temperature decrease, the outdoor fan
speed also changes to the lower speed.)
The compressor and the fan start-up at the same time, and the fan stops after the compressor
*
stops and 60 seconds has passed.
The fan doesn't operates fan 10 seconds after the fan stops.
*
After operating the defrost control function on heating mode except economy operation,
*
its speed becomes 900rpm(Upper/ Lower) regardless of the compressor speed.
However, it returns to the normal speed control when the defrosting operation does not function
for 240 minutes after releasing the defrost operation or when the outdoor temperature sensor
detection value becomes higher than 5℃.
It runs at 500rpm for 20 seconds after starting up the outdoor fan.
*
However, the fan operates at 200rpm when the initial rotation speed is 300rpm or less.
The operation frequency of the compressor is different based on the operation mode as
shown in Table 7.
(Table 7 : Compressor Operation Frequency Range)
CoolingHeating
MinMaxMinMax
Dry
AO* G60LATT
15rps
78rps
18rps
85rps
41rps
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Fig. 9.
(Fig.9 : Compressor Control at Start-up)
< Normal start-up >
Immediate start-up after power-ON (cooling)
(rps)
70
limit
54
40
28
(rps)
90
180270360 (sec)
Elapsed time
Upper
speed
Immediate start-up after power-ON (Heating Ta < 10°C)
70
limit
limit
54
25
16
30120300650 (sec)
Elapsed time
=
(rps)
70
54
40
28
25
16
30270480560620 650 (sec)
Elapsed time
Upper
speed
Immediate start-up after power-ON (Heating Ta > 10°C)
Upper
speed
Ta : Outdoor temperature
01-09
1-8. TIMER OPERATION CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
AR-WAE1E
ON / TIMER
OFF / TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Use this timer function to set operating time for each day of the week.
The weekly timer allows up to two ON and OFF time to set up per day.
Operation mode
Stop mode
Set time
The operating time can be set in 30 min increments only.
The OFF time can be carried over to next day.
The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
Operation mode
Stop mode
Set timeSet timeSet time
Operation mode
Stop mode
01-10
2-2. DAY OFF setting
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The DAY OFF setting is only available for days for which weekly settings already exist.
If the operating time carries over to the next day (during a next day setting), the effective
DAY OFF range will be set as shown below.
Normal
DAY OFF
Operation mode
Operation mode
Stop mode
Stop mode
Preceding dayNext day
Setting day
Stop mode
Next day setting
DAY OFF
Stop mode
Operation mode
Stop mode
Preceding dayNext daySetting day
Operation mode
Stop mode
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically
after the set day has passed.
3. TEMPERATURE SET BACK TIMER
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop
air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting
can be used.
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if
the SET BACK temperature is set to 17°C or lower.
Case of SET BACK timer on the Cooling operation.
( Setting temperature :22°C, SET BACK temperature :26°C)
SET BACK setting
Operation
temperature
*1
Operation
temperature
*1: During the SET BACK function,
the setting temperature is changed.
ONOFFOFFON
26°C
22°C
26°C
24°C
22°C
Change the setting temperature:
22°C 24°C
01-11
1-9. ELECTRONIC EXPANSION VALVE CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor frequency, the temperatures detected by the discharge temperature sensor
and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is
50~ 480 pulses (Cooling), 40~ 480 pulses (Heating).
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (528 pulses are input to the closing direction).
1-10. TEST OPERATION CONTROL
With Wired Remote Controller
Under the condition where the air conditioner stops, press the MASTER CONTROL button and
the FAN CONTROL button simultaneously for 2 seconds or more, and the test operation control
mode will appear.
During test running, " " will display on the remote controller display.
Set the test operation mode, and the compressor will continue to run regardless of whatever
the room temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
1-11. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 3 minutes after the compressor is stopped,
even if any operation is given.
1-12. 4-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.
1-13. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, timer operation is canceled,
but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode
Set temperature
Set air flow
Timer mode and timer time (set by wireless remote controller)
ECONOMY operation
01-12
1-14. PUMP DOWN
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Operate [PUMP DOWN] switch on the display board.
< PUMP DOWN Procedure >
(1) Confirm that power is off, and open the service panel.
(2) Turn the power on.
: Light ON: Light OFF
TEST
POWER
ERROR
MODE
(3) Press [PUMP DOWN] switch for 3 seconds or more after 3 minutes after power on.
POWER
ERROR
MODE
LED display lights on as shown in the above figure, and the fans and the compressor start operating.
If the [PUMP DOWN] switch is pressed while the compressor is operating, the compressor will stop then
start again in about 3 minutes.
(4) LED display will change as shown as below about 3 minutes after the compressor starts.
Fully close the 3-way valve on the liquid pipe side at this stage.
POWER
ERROR
MODE
PUMP
RUN
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
TEST
RUN
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
TEST
RUN
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
LOW NOISEPEAK CUT
DOWN
PUMP
LOW NOISEPEAK CUT
DOWN
PUMP
LOW NOISEPEAK CUT
DOWN
(5) When LED display changes as shown in the below figure, close the 3-way valve on the gas pipe side tightly.
TEST
POWER
ERROR
MODE
Closing direction
PUMP
RUN
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
Step (4)
LOW NOISEPEAK CUT
DOWN
Step (5)
Closing direction
Hexagon wrench
Liquid pipe
Gas pipe
(6) LED display changes after 1 minute as shown in the figure below.
TEST
POWER
MODE
ERROR
PUMP
RUN
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
LOW NOISEPEAK CUT
DOWN
Fans and compressor stop automatically.
(7) Turn the power off.
TEST
POWER
MODE
ERROR
PUMP
RUN
(L1) (L2) (L3) (L4) (L5) (L6) (L7 )
LOW NOISEPEAK CUT
DOWN
PUMP DOWN is completed.
01-13
1-15. COMPRESSOR PREHEATING
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When the outdoor temperature is lower than 20°C and the all operation mode has been
stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started and when the outdoor temperature rises to 26°C or greater,
preheating is ended.
1-16. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
The ECONOMY operation is almost the same operation as below settings.
( Table9 )
Mode Cooling/ Dry Heating
Target temperature Setting temp.+1°C Setting temp.-1°C
1-17. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts as shown in the following Table 10, 11, and 12.
( Table 10 : Condition of 1st defrost operation)
Compressor integrating operation time
1st defrost
after
starting operation
( Table 11 : Condition of 2nd defrost operation)
From 2nd and later
defrost after
starting operation
( Table 12 : Condition of Integrating defrost operation)
Integratingdefrost
(Constant monitoring)
Less than 22 minutesMore than 22 minutesMore than 62 minutes
Does not operate
Compressor integrating operation time
Less than 35 minutesMore than 35 minutes
Does not operate
Compressor integrating operation time
More than 240 minutes
( For long continuous operation )
Outdoor heat exchanger temperature
Below -3°C
Outdoor heat exchanger temperature
Outdoor heat exchanger temperature
Below -9°C
Outdoor heat exchanger temperature
Below -10°C
Less than 10 minutes
( For intermittent operation )
OFF count of the compressor
40 times
Below -5°C
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions becomes as shown in Table 13.
( Table 13 : Condition of defrost release )
Outdoor heat exchanger temperature is higher than 10°C
or
Compressor operation time has passed 15 minutes.
Release Condition
01-14
3. Defrost Flow Chart
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 10 minutes)
1st defrost
Compressor
integrating
operation:
Over 22 minutes
Outdoor
heat exchanger
temperature:
Below - 9°C
Compressor
integrating
operation:
Over 62 minutes
Outdoor
heat exchanger
temperature:
Below - 5°C
2nd and later defrost
Compressor
integrating
operation:
Over 35 minutes
Outdoor
heat exchanger
temperature:
Below - 10°C
Defrost start
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Integrating defrost
(Constant monitoring)
Compressor
OFF count :
40 times
Compressor
integrating
operation:
Over 240 minutes
Outdoor
heat exchanger
temperature:
Below - 3°C
Compressor : OFF
Outdoor fan motor : OFF
30 sec later 4-way valve : OFF
36 sec later compressor : ON
Outdoor heat exchanger temperature: Over 10°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-15
1-18. OFF DEFROST OPEARTION CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
1. OFF DEFROST OPERATION CONDITION
In heating operation, the outdoor heat exchanger temperature is less than -4°C,
and compressor operation integrating time lasts for more than 30 minutes,
and and compressor operation contiguous time lasts for more than 10 minutes.
2. OFF DEFROST RELEASE CONDITION
OFF defrost operation is released when the conditions becomes as shown in Table 14.
( Table 14 : OFF Defrost Release Condition )
Release Condition
Outdoor heat exchanger temperature is higher than 10°C
or
Compressor operation time has passed 15 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature :
Below -4°C.
and
Compressor integrating operation :
Over 30 minutes.
and
Compressor contiguous operation:
Over 10 minutes.
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Defrost start
Outdoor heat exchanger temperature : Over 10°C
Compressor ON time : Maximum 15 minutes
or
Defrost end
01-16
1-19. VARIOUS PROTECTIONS
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 10rps, and it continues to decrease the frequency for 10rps every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of
the compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table15 : Discharge Temperature Over Rise Prevention Control / Release Temperature)
Temperature
105°C100°C 115°C
Temperature
Temperature
01-17
2. CURRENT RELEASE CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 16 : Current Release Operation Value / Release Value)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
*1. When the temperature rises.
*2. When the temperature drops.
4. COOLING PRESSURE OVER RISE PROTECTION
On cooling mode, the compressor frequency is controlled as following based on the
detection value of the outdoor heat exchanger temperature sensor.
(Fig.10 : Cooling Pressure Over Rise Protection Control)
Outdoor heat exchange
temperature
Compressor is OFF
68°C
The compressor frequency is
decreased 5rps every 120seconds.
63°C
Release of protection
5. LOW PRESSURE PROTECTION CONTROL (For Cooling mode)
5-1. Low Pressure Protection 1
<After the compressor start-up and 1 minute has passed>
(a).The detected value of pressure sensor is 0.02MPaG or less,
continues for 5 minutes, the compressor is stopped.
(b). When 7 minutes has passed and low pressure sensor detects
value is more than 0.05MPaG after the protection stop by (a),
the compressor restarts.
(c).When the protection (a) operates 5 times within 2 hours after the
restart by (b),
the error is displayed and the compressor stops. [Permanent stop]
(Fig 11 : Low pressure protection 1)
Pressure
0.05MPaG
0.02MPaG
Release of protection
Hold
Compressor stop
5-2. Low Pressure Protection 2
<After the compressor start-up and 10 minutes has passed>
(a).When the low pressure value becomes 0.68MPaG or less
continues for 1 minute, the compressor speed -8 rps.
(b). When the low pressure value becomes 0.68MPaG or less
after the protection (a), the compressor continues speed -8 rps
every 1 minute until the detected value becomes more than
0.68MPaG.
(c). When the low pressure value becomes more than 0.78MPaG,
this protection is released.
01-19
(Fig 12 : Anti freezing protection)
Pressure
0.78MPaG
0.68MPaG
Release of protection
Hold
-8 rps every 1 minute
6. HEATING OVERLOAD PROTECTION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
On heating mode, the compressor frequency is controlled as following based on the
detection value of the pressure sensor.
(Fig.13 : Heating Overload Protection Control)
Condensing pressure
(Indoor heat ex. temp.)
Compressor is OFF
4.1MPa
(65°C)
3.3MPa
(55°C)
3.0MPa
(50°C)
2.8MPa
(48°C)
The compressor frequency is
decreased 7rps every 60 seconds.
The compressor frequency is
decreased 1rps every 60 seconds.
Release
Release
Stable range
1-20. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than temperature
in the table below, the compressor is stopped.
(Table 18 : Operation temperature of compressor stop control)
Temperature
Operation
temperature
Cooling
- 20°C
Heating
1-21. FRESH AIR CONTROL
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation
as shown in Fig.14.
(Fig.14 : Fresh Air control)
Fan motor
(Indoor unit)
Control signal
(for Fresh Air)
ON
OFF
ON
OFF
12V
01-20
1-22. EXTERNAL ELECTRICAL HEATER CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The External Electrical Heater operates when it meets all the following conditions.
Model type : Heat pump
Operation mode : Heating mode
Compressor : ON
Indoor fan : ON
(Fig 15 : External Electrical Heater control)
When the room
temperature rises
Heater : OFF
Ts -3°C
Heater : ON
Ts -12°C
Heater : OFF
When the room
temperature drops
Ts -1°C
Ts -10°C
Ts : Setting temperature
1-23. LOW NOISE OPERATION
The compressor speed and the outdoor unit fan speed are limited to reduce the operation noise
by External Input.
During the LOW NOISE OPERATION,
"CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "PEAK CUT OPERATION"
are effective, and the outdoor unit operates by lowest current of them.
However, during the DEFROST OPERATION, the compressor operates by the speed
for DEFROST OPERATION.
( Table 19 : Detail of Low Noise Operation )
Low Noise mode
Cooling
Outdoor Fan
Upper Limit Speed
( rpm )
520
Compressor
Speed ( rps )
58
LEVEL 1
Heating
Cooling
520
520
58
37
LEVEL 2
Heating
Cooling
520
520
39
27
LEVEL 3
Heating
520
33
*The performance drops when operating in the LOW NOISE OPERATION.
01-21
1-24. PEAK CUT OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The Current Value is limited to reduce the power consumption by External Input.
During the PEAK CUT OPERATION,
"CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "LOW NOISE OPERATION"
are effective, and the outdoor unit operates by lowest current of them.
However, this function becomes invalid during DEFROST OPERATION.
(Table 20 : Outline of Peak Cut Operation )
PEAK CUT LEVEL
Peak Cut
For Rated Capacity
LEVEL 1LEVEL 2LEVEL 3LEVEL 4
Forced
thermostat-OFF
75%50%
*Percentage is rated electrical power ratio.
100%
01-22
1-25. DESCRIPTION OF DISPLAY UNIT
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-25-1 Layout of Display Unit
•
Various settings can be adjusted by changing Dip switches and Push switches on the board of the outdoor unit.
( Excerpt from the "INSTALATION MANUAL" )
LED DISPLAY
(1)(2)(3) (4)(5)(6)
SW1 (DIP-SW)SW2SW3SW4SW5SW6
PUSH SWITCH
Display lamp
(1) POWER / MODE
(2) ERROR
(3) TEST RUN (L1)OrangeLights on during test operation.
(4) PUMP DOWN (L2)
(5) LOW NOISE MODE
(L3, L4)
(6) PEAK CUT
(L5, L6, L7)
Switch
MODE
SELECT
Green
Red
Orange
Orange
Orange
SW1DIP-SWITCH
SW2To switch between “Local setting” and “Error code display”.
SW3
Function or operation method
Lights on while power on Local setting in outdoor unit
or error code is displayed with blink.
Blinks during abnormal air-conditioner operation.
Number of blinks indicates kind of error and error code is displayed.
Lights on during pump down operation.
Lights on during “Low noise” function when local setting is activated.
(Lighting pattern of L3 and L4 indicates low noise level)
Lights on during “Peak cut” function when local setting is activated.
(Lighting pattern of L5, L6 and L7 indicates peak cut level)
Function or operation method
For selecting COOLING or HEATING during test operation.
Positions 2 to 4 of Dip switch are not used.
To switch between the individual “Local settings” and the
“Error code displays”.
ENTER / TEST RUN
EXIT / INITIALIZE
PUMP DOWN
•
Dip switches 1 to 4 at shipment from the factory are set as follows.
1 2 3 4
COOLOFFOFFOFF
SW4
SW5
SW6To start the pump down operation.
DIP switch
To fix the individual “Local settings ” and the “Error code displays”.
EXIT
01-23
1-25-2 Display mode
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
•
In this mode, the "Operation Condition" and "Error Code" can be displayed by Push Switch on outdoor unit PCB
(Table :21 Display pattern)
NO.
1
2
Power / Mode
LED
Present Value
Of
Each Item
1
Error Code
2
Display Item
LED
L1L2L3L4
Compressor frequency
Upper fan speed (Outdoor unit)
Lower fan speed (Outdoor unit)
EEV pulse
Pressure sensor value (Low pressure range)
Pressure sensor value (High pressure range)
Outdoor air temperature sensor value
Discharge temperature sensor value
Heat-exchanger temperature sensor value (Middle)
Current value
Compressor accumulated time
Newest error code
Error code before 1 time
Error code before 2 times
(Table :22 Procedure for Present Value)
Procedure
1
2
3
4
During status display, press the MODE SWITCH 1 time.
(Status display : Outdoor unit is stopping and no error)
When the POWER / MODE LED blinking 1 time,
press the ENTER SWITCH.
Press the SELECT SWITCH and adjust to DISPLAY ITEM
(from L1 to L4) that you want to confirm. (Refer to Table 17)
Press the ENTER SWITCH.
(Data is displayed by lighting LED. Refer to Table : 19)
Selecting display items can be done by pressing
the SELECT SWITCH. (Return to Procedure 3)
Operation
5
When the EXIT SWITCH is pressed, this mode ends
and returns to the status display.
In this mode, the history of abnormality that occurred in the past can be confirmed.
(Table : 24 Procedure for History Mode )
ProcedureOperation
1
2
3
4
During status display, press the MODE SWITCH 2 times.
(Status display : Outdoor unit is stopping and no error)
When the POWER / MODE LED blinking 2 times,
press the ENTER SWITCH.
Press the SELECT SWITCH and adjust to DISPLAY ITEM
(from L1 to L4) that you want to confirm. (Refer to Table : 17)
Press the ENTER SWITCH, Error code is displayed by
lighting LED. (Refer to Table : 21)
Power
Mode
2
2
2
2
ErrorL1L2L3L7L6L5L4
n n
: Light ON: Light OFF
Note.
Selecting display items can be done by pressing the SELECT SWITCH. (Return to Procedure 3)
When the EXIT SWITCH is pressed, this mode ends and returns to the status display.
(Table : 25 Error Code)
TEST
POWER
MODE
2
ERROR
PUMP
RUN
DOWN
(L1)(L2)(L3)(L4)(L5)(L6)(L7)
1 1
2 2
5 15
6 1
7 1
8 4
9 4
10 1
LOW NOISEPEAK CUT
2
3
4
5
8
2
3
4
7
6
5
7
8
9
3
5
: Blinking2 : 2 Times Blinking
: Light ON
Serial forward transmission error immediately after operation
Serial forward transmission error during operation
Indoor unit capacity error
Indoor unit error
Over voltage
Power supply frequency error
Outdoor unit PCB model information error
PFC communication error
Inverter error
PFC AD detection error
PFC hardware error
IPM error (Trip terminal L error)
Rush current limiting resister temp rise protection
Discharge temp. sensor error
Compressor temp. sensor error
Heat Ex. middle temp. sensor error
Outdoor unit Heat Ex. liquid temp. sensor error
Outdoor temp. sensor error
Heat sink temp. sensor error
PFC heat sink temp. sensor error
Current sensor 1 error (stoppage permanently)
High pressure switch 1 error
Pressure sensor error
Trip detection (stoppage permanently)
Compressor motor control error (stoppage permanently)
Compressor motor loss of synchronization (stoppage permanently)
Outdoor unit fan motor 1 error (Duty error)
Outdoor unit fan motor 2 error (Duty error)
4-way valve error
Discharge temp. 1 error (stoppage permanently)
Compressor 1 temp. error (stoppage permanently)
Low pressure error
n : n Times Blinking
1 ~ : 1~ 15 Times Blinking 15
Description
01-27
1-25-4 ERROR CHECK MODE
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
•
In this mode, abnormality that is occurring now can be confirmed.
(Table : 26 Procedure for Error Check Mode )
: Light ON: Light OFF2 : 2 Times Blinking
ProcedureOperation
1
2
3
Note.
When the EXIT SWITCH is pressed, this mode ends and returns to the status display.
Check that the "ERROR" LED blinking (Hi-speed),
and then short press the ENTER SWITCH 1 time.
Error code is displayed by lighting LED.
(Refer to Table : 21)
When the MODE SWITCH is pressed for more than
3 seconds, the Error history is cleared.
Power
Mode
ErrorL1L2L3L7L6L5L4
Blinking
Hi-speed
2
2 2 2 2 2 2 2 2 2
Confirm Chapter 2 " TROUBLE SHOOTING" in detail.
n : n Times Blinking
n n
01-28
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
DUCT type
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INVERTER
R410A
2 . TROUBLE SHOOTING
2-1 ERROR DISPLAY
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
1. SELF - DIAGNOSIS
When "Er" in Temperature Display is displayed, inspection of the air conditioning system is necessary.
Please consult authoilzed service personnel.
Unit number (usually 0)
Error code
SUMOTUWETH FR
ex. Self-diagnosis check
SA
Error Contents
Serial Communication Error
Wired Remote Controller
Communication Error
Fan Motor Driving Circuit Error
Indoor Room Thermistor Error
Indoor Heat Ex. Thermistor Error
Indoor Unit Fan Motor1 Error
Drainage Error
Indoor Unit Fan Motor2 Error
Indoor Unit Error
Inverter Error
Error
Code
11
12
39
41
42
51
53
59
5U
63
Trouble
shooting
1,2
3
4
5
6
7
8
9
1- 9
10
Error Contents
Current sensor Error
Pressure sensor Error
Over Current Error
Compressor Control Error
Outdoor Unit Fan Motor 1 Error
Outdoor Unit Fan Motor 2 Error
4-way Valve Error
Discharge Temp. Error
Compressor Temp. Error
Low Pressure Error
Error
Code
84
86
94
95
97
98
99
A1
A3
A5
Trouble
shooting
17
18
19
20
21
22
23
24
25
26
IPM Error
Discharge Thermistor Error
Compressor Thermistor Error
Heat Ex. Liquid Temp.
Thermistor Error
Outdoor Thermistor Error
Heat Sink Thermistor Error
65
71
72
73
74
77
11
12
13
14
15
16
02-01
2. ERROR CODE HISTORY DISPLAY
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds
or more to start the self-diagnosis.
Error code
Error history number
SU MOTU WE TH FR SA
3. Press the SET TEMPERATURE button to select the error history number.
Lower
01234567
Raise
FEdcbA98
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more
or there is no key input for 60 seconds to stop the display.
02-02
2-2 TROUBLE SHOOTING WITH ERROR CODE
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Trouble shooting 1
Indicate or Display:
OUTDOOR UNIT Error Method:
Serial Communication Error
Refer to error code table.
(Serial Reverse Transfer Error)
Detective Actuators:Detective details:
Outdoor unit Main PCB
Outdoor unit Fan motor
When the indoor unit cannot receive the serial signal from Outdoor unit
more than 2minutes after power ON, or the indoor unit cannot receive
the serial signal more than 15seconds during normal operation.
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB failure 4. Inverter PCB (IPM) failure
5. Filter PCB failure 6. Outdoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
NO
YESYES
Check Point 2 : Check connection
Check Point 1-2 : Check external cause such as noise
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V(AC220V-10%) - 264V(AC240V+10%) appears
at outdoor unit terminal L - N.
OK
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3.
>> If it is abnormal, Check the parts as follows.
- Outdoor unit fan motor (PARTS INFORMATION 5)
- Inverter PCB (IPM) (PARTS INFORMATION 6)
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB.
>> If IPM is abnormal, replace it.
>> If the parts are normal, replace Main PCB.
BLACK
WHITE
RED
BLACK
WHITE
1
2
3
L
N
+
-
02-03
Trouble shooting 2
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Serial Communication Error
Refer to error code table.
(Serial Forward Transfer Error)
Detective Actuators:Detective details:
Indoor unit Controller PCB
When the outdoor unit cannot properly receive the serial signal from
indoor unit for 10 seconds or more.
Forecast of Cause:
1. Connection failure 2. External cause 3. Controller PCB failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
NO
YESYES
Check Point 2 : Check connection
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V(AC220V-10%) - 268V(AC240V+10%) appears
at outdoor unit terminal L - N.
OK
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC30V and AC130V at outdoor unit terminal 2 - 3.
>> If it is abnormal, replace Controller PCB.
BLACK
WHITE
RED
BLACK
WHITE
1
2
3
L
N
+
-
02-04
Trouble shooting 3
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Wired Remote Controller
Refer to error code table.
Communication Error
Detective Actuators:Detective details:
Indoor unit Controller PCB
Wired Remote Controller (Option)
When the indoor unit cannot properly receive the signal from
Wired Remote Controller for 1 minute or more.
Check & correct the followings.
Check the connection of terminal between Wired Remote Controller and indoor unit,
and check if there is a disconnection of the cable.
OKOK
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Voltage at CN140 of Controller PCB. (terminal 1-3)
(Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
02-05
Trouble shooting 4
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Refer to error code table.
Fan Motor Drive Circuit Error
Detective Actuators:Detective details:
Indoor Unit Power Supply PCB
When a momentary power cut off.
When do not start fan motor.
Forecast of Cause :
1. External cause 2. Connection of connector failure 3. Power Supply PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Replace Power supply PCB
If Check Point 1, 2 do not improve the symptom, replace Power supply PCB.
02-06
Trouble shooting 5
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INDOOR UNIT Error Method:
Indoor Room Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Temperature Thermistor
If Thermistor is either open or shorted, replace it and reset the power.
62.9 49.7 39.6 31.7 25.6 20.8 17.1 14.1 11.6 10.4
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
CN110
CN114
If the voltage does not appear, replace Controller PCB and execute the check operation again.
1
BLACK
2
2
BLACK
1
1
BLACK
2
2
H/E Thermistor
Room Temp. Thermistor
02-08
Trouble shooting 7
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INDOOR UNIT Error Method:
Indoor Unit Fan Motor1 Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Power Supply PCB
Indoor unit fan motor
Detective details:
When the condition that actual frequency of Indoor Fan is
below 1/3 of target frequency is continued more than 56 seconds.
Forecast of Cause:
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Power Supply PCB failure 5. Indoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
OK
Check Point 4 : Replace Power Supply PCB
If Check Point 1- 3 do not improve the symptom, replace Power Supply PCB.
02-09
Trouble shooting 8
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INDOOR UNIT Error Method:
Drainage Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor Unit Controller PCB Circuit
Float Switch
Forecast of Cause : 1. Float switch failure 2. Shorted connector/wire 3. Controller PCB failure
4. Drain pump failure 5. Hose clogging
Detective details:
When Float switch is ON for more than 3 minutes.
Check Point 1 : Check Float Switch
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is abnormal, replace it.
ONOFF
OK
Check Point 2 : Check Connector and Wire
Check loose contact of CN120 and shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
OK
Check Point 3 : Check Drain Hose
Check Drain Hose .
>>If there is Hose clogging. Please clear the clog.
OK
Check Point 4 : Check Controller PCB
If Check Point 1 ~ 3 do not improve the symptom, change
Controller PCB and execute the check operation again.
02-10
Trouble shooting 9
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INDOOR UNIT Error Method:
Indoor Unit Fan Motor2 Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Power Supply PCB
Indoor unit fan motor
Detective details:
When the condition that actual frequency of Indoor Fan is
below 1/3 of target frequency is continued more than 56 seconds.
Forecast of Cause:
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Power Supply PCB failure 5. Indoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
OK
Check Point 4 : Replace Power Supply PCB
If Check Point 1- 3 do not improve the symptom, replace Power Supply PCB.
02-11
Trouble shooting 10
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Inverter Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Inverter PCB
Forecast of Cause :
1. External cause. 2. Power supply to Filter PCB to Inverter PCB wiring disconnection, open
3. Filter PCB failure 4. Inverter PCB failure
Check Point 1-1 :
Turn the power on again.
Error displayed again?
NO
Detective details:
Error information received from Inverter PCB
Check Point 1-2 : External cause
Check if temporary voltage drop was not generated.
Check if temporary open was not generated.
Check if ground is connected correctly or there are no related cables near the
power line.
YES
Check Point 2 : Check the wiring (Power supply to Filter PCB to Inverter PCB)
Connector and wiring connection state check
Cable open check
OK
Check Point 3 : Replace Filter PCB (INV) and Inverter PCB
Replace Filter PCB and Inverter PCB.
02-12
Trouble shooting 11
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
IPM Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Compressor
Detective details:
When more than normal operating current to IPM in Main PCB flows,
the compressor stops.
After the compressor restarts, if the same operation is repeated within 40sec,
the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Outdoor Fan Operation failure
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
OK
Check Point 3 : Check Outdoor Fan
Check Outdoor Fan Motor. (Refer to Trouble shooting 21,22)
>> If the Fan Motor is failure, replace it.
OKOK
Check Point 4 : Check Compressor
Check Compressor.
(PARTS INFORMATION 2)
OKOK
Check Point 5 : Replace Main PCB
If Check Point 1 ~ 4 do not improve the symptom, change Main PCB.
02-13
Trouble shooting 12
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Discharge Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Discharge temperature thermistor
Forecast of Cause :
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Discharge temperature thermistor short detected
Discharge thermistor open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 7".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN24:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(DIS.TEMP.)
BROWN
BROWN
1 2 3
1 2 3
CN24
Discharge temperature thermistor (CN24:1-3)
If the voltage does not appear, replace Main PCB,
and execute the check operation again.
02-14
Trouble shooting 13
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Compressor Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Compressor temperature thermistor
Forecast of Cause :
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Compressor temperature thermistor short detected
Compressor thermistor open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 7".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN27:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
(COMP SHELL)
THERMISTOR
BROWN
BROWN
1 2 3
1 2 3
CN27
Compressor temperature thermistor (CN27:1-3)
If the voltage does not appear, replace Main PCB, and execute
the check operation again.
02-15
Trouble shooting 14
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Heat Ex. Liquid Temp.
Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Heat exchanger outlet temp. thermistor
Detective details:
Heat exchanger liquid temperature thermistor short or open detected
Heat exchanger middle temp. thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor failure
3. Main PCB failure
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 7".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN25:1-3, CN22:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(HEX. PIPE. MID.)
BLACK
BLACK
1 2
1 2
CN22
THERMISTOR
(HEX. PIPE. OUT.)
BLACK
BLACK
1 2 3
1 2 3
CN25
Heat exchanger outlet/ middle temperature thermistor (CN25:1-3/ CN22:1-2)
If the voltage does not appear, replace Main PCB, and execute
If the voltage does not appear,
the check operation again.
02-16
Trouble shooting 15
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Outdoor Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor failure
3. Main PCB failure
Detective details:
Outdoor temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2: Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information7".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN26:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
(OUT TEMP.)
THERMISTOR
BLUE
BLUE
1 2 3
1 2 3
CN26
Outdoor temperature thermistor (CN26:1-3)
If the voltage does not appear, replace Main PCB, and execute
If the voltage does not appear, replace Main PCB
the check operation again.
02-17
Trouble shooting 16
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Heat Sink Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Heat Sink temperature thermistor (INV)
Detective details:
Heat sink temperature thermistor short or open detected
Heat Sink temperature thermistor (PFC)
Forecast of Cause :
1. Connector connection defective, open 2. Thermistor failure
3. Main PCB failure 4. Inverter PCB failure
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2: Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information8".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN23:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Inverter PCB (CN803:1-2) voltage value = 5V
Remove the thermistor from Inverter PCB, check the voltage.
(HEATSINK PFC)
THERMISTOR
BLACK
BLACK
1 2
1 2
CN23
Heat sink temp. thermistor
(CN23:1-2)
If the voltage does not appear, replace Main PCB, and execute
If the voltage does not appear, replace Main PCB
Heat sink temp. thermistor
(CN803:1-2)
(HEATSINK INV)
THERMISTOR
BLACK
BLACK
1 2
1 2
CN803
the check operation again.
02-18
Trouble shooting 17
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Current Sensor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When Input Current Sensor has detected 0A, while Inverter Compressor is
operating at higher than 56rps, after 1minute upon starting the Compressor.
(Except during the defrost operation)
Forecast of Cause :
1. Defective connection of electric components 2. External cause 3. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
NO
YES
Check Point 2 :
Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring,
reset the power.
OK
Check Point 1-2 :
Check external cause at Indoor and Outdoor
(Voltage drop or Noise)
Instant drop : Check if there is a large load electric
apparatus in the same circuit.
Momentary power failure : Check if there is a defective
contact or leak current in the
power supply circuit.
Noise : Check if there is any equipment causing harmonic
wave near electric line.(Neon bulb or electric
equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
02-19
Trouble shooting 18
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
OUTDOOR UNIT Error Method:
Pressure sensor error
Refer to error code table.
Detective Actuators:Detective details:
Outdoor unit Main PCB
Pressure sensor
30 seconds or more after power-on, when pressure sensor detection
value detects the condition below continuously for 30 seconds or more.
Check Point 1 : Check connection of the Pressure sensor
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check output voltage of Main PCB
Check voltage of Main PCB.
(Measure at Main PCB side connector)
>>1 pin(Red) - 3 pin(Black) DC5V 5%
RED
1
1
CN16
WHITE
2
2
BLACK
3
3
PRESSURE SENSOR
PS
If the voltage is not correct, replace Main PCB.
OK
Check Point 3 : Check output voltage of Pressure Sensor
Check voltage of Main PCB.
(Measure at Main PCB side connector)
>>2 pin(White) - 3 pIn(Black) Voltage is refer to the following graph.
4.5
Voltage [V]
2.5
0.5
02.55
Pressure [MPa]
If the voltage is not correct, replace Presure Sensor.
02-20
Trouble shooting 19
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INDOOR UNIT Error Method:
Over Current Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Compressor
Inverter PCB
Forecast of Cause :
1. Outdoor unit fan operation defective, foreign matter on heat exchanger,
Detective details:
"Protection stop by overcurrent generation after inverter compressor start
processing completed'' generated consecutively 10 times.
* The number of generations is reset if the start-up of
the compressor succeeds.
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
OKOK
Check Point 2: Check Transistor PCB (IPM)
Check IPM. (PARTS INFORMATION 6)
>> If IPM is abnormal, replace Inverter PCB.
OKOK
Check Point 3: Replace Main PCB
If Check Point 1 or 1,2 do not improve the symptom, change Main PCB.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
02-21
Trouble shooting 20
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Compressor Control Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Compressor
Inverter PCB
Detective details:
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 90°,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
4. Inverter PCB (IPM) failure
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 2 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3: Check Inverter PCB (IPM)
Check IPM. (PARTS INFORMATION 6)
>> If IPM is abnormal, replace Inverter PCB.
OKOK
Check Point 4: Replace Main PCB
If Check Point 1,2 or 1 3 do not improve the symptom, change Main PCB.
OKOK
Check Point 5: Replace Compressor
If Check Point 4 do not improve the symptom, change Compressor.
02-22
Trouble shooting 21
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Motor 1 Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit fan motor
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
If and repeats 5 times in a row
permanently
Forecast of Cause:
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
, compressor and fan motor stops
.
OK
Check Point 3 : Check Outdoor unit fan motor
Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>>If Outdoor Fan Motor is abnormal, replace Outdoor fan motor and Main PCB.
OK
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
RED
1
1
2
2
BLACK
3
4
5
6
3
WHITE
4
YELLOW
5
BROWN
6
CN81
If the voltage is not correct, replace Main PCB.
FAN MOTOR
(UPPER)
FM
Read wire DC voltage
Red - Black
White - Black
280V (AC220V-10%)
~ 373V (AC240V+10%)
15 1.5V
02-23
Trouble shooting 22
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Motor 2 Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit fan motor
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
If and repeats 5 times in a row
permanently
Forecast of Cause:
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
, compressor and fan motor stops
.
OK
Check Point 3 : Check Outdoor unit fan motor
Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>>If Outdoor Fan Motor is abnormal, replace Outdoor fan motor and Main PCB.
OK
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
RED
1
1
2
2
BLACK
3
4
5
6
3
WHITE
4
YELLOW
5
BROWN
6
CN82
If the voltage is not correct, replace Main PCB.
FAN MOTOR
(LOWER)
FM
Read wire DC voltage
Red - Black
White - Black
280V (AC220V-10%)
~ 373V (AC240V+10%)
15 1.5V
02-24
Trouble shooting 23
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
4-Way Valve Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor Unit Controller PCB Circuit
Heat Exchanger Temperature Thermistor
Room Temperature Thermistor
4-way valve
Detective details:
When the indoor heat exchanger temperature is compared with
the room temperature, and either following condition is detected
continuously two times, the compressor stops.
Cooling or Dry operation
[Indoor heat exchanger temp.] - [Room temp.] > 20degC
Heating operation
[indoor heat exchanger temp.] - [Room temp.] < -14degC
If the same operation is repeated 5 times,
the compressor stops permanently.
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Check thermistor of Indoor unit
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor, (Refer to Trouble shooting 5,6),
If defective, replace the thermistor.
OKOK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN111 from PCB and check the resistance value of coil.
Resistance value is about 1.4k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1- 3 do not improve the symptom, replace Main PCB.
02-25
Trouble shooting 24
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Discharge Temp. Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Discharge temperature thermistor
Forecast of Cause :
1. 3-way valve not opened
2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure
5. Insufficient refrigerant
<Cooling operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3, 4 "
"Protection stop by "discharge temperature 115°C during compressor
operation'''' generated 2 times within 24 hours.
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3, 4"
OK
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check(PARTS INFORMATION 5)
OK
Check Point 4 : Check the discharge thermistor
Discharger thermistor characteristics check
(Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor,
refer to the "Service Parts Information 7".
OK
Check Point 5 : Check the refrigerant amount
Leak check
OK
02-26
Trouble shooting 25
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Compressor Temp. Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Compressor temperature thermistor
Forecast of Cause :
1. 3-way valve not opened
2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Compressor temperature thermistor failure
5. Insufficient refrigerant
<Cooling operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
"Protection stop by "compressor temperature" 110°C during compressor
operation""generated 2 times within 24 hours
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV open?
Strainer clogging check (before and after EEV, ACM)
Refer to "Service Parts Information 3, 4".
OK
Check Point 3 : Outdoor unit fan, heat exchanger check
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check(PARTS INFORMATION 5)
OK
Check Point 4 : Check the compressor temp. thermistor
Compressor temperature thermistor characteristics check
(Check by disconnecting thermistor from PCB)
* For the characteristics of the thermistor,
refer to the "Service Parts Information 7.
OK
Check Point 5 : Check the refrigerant amount
EEV open?
Strainer clogging check (before and after EEV, ACM)
Refer to "Service Parts Information 3,4 ".
OK
Leak check
02-27
Trouble shooting 26
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
Low Pressure Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Suction pressure sensor
Forecast of Cause :
1. 3-way valve not opened 2. Outdoor unit ambient temperature too low
3. Outdoor unit fan operation defective, foreign matter at heat exchanger
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Check Point 2 : Check the EEV, strainer clogging
Indoor unit EEV operation check
Strainer not clogged?
"Protection stop by suction pressure 0.02MPaG continued for 5 minutes"
repeats 5 times within 2 hours.
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Check Point 2 : Check the outdoor unit ambient temperature
Outdoor ambient temperature lower than operating range?
OK
Check Point 5 : Check the solenoid valve (SV1)
Solenoid valve operation check
OK
Check Point 6 : Check the suction pressure sensor
Suction pressure sensor characteristics check
* For the characteristics of the suction pressure sensor
(PARTS INFORMATION 8)
OK
OK
Check Point 3 :
Check the outdoor unit fan operation, heat exchanger
No foreign object in air passage?
Heat exchange fins clogged
Fan rotates?
Outdoor unit fan motor check
OK
Check Point 4 : Check the outdoor unit EEV, strainer clogging
Outdoor unit EEV operation check
Strainer not clogged?
Refer to "Service Parts Information 3"
Check Point 7 : Check the refrigerant amount
Leak check
02-28
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Trouble shooting 27
Forecast of Cause:
1. Power Supply failure 2. External cause
Indoor Unit - No Power
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
YESYES
Check Fuse in Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB
is loose, and replace Fuse.
Check Varistor in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
Upon checking the normal power supply, replace Varistor.
OK
If the symptom does not change by above Check 3, replace Main PCB.
NO
02-29
Trouble shooting 28
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Outdoor Unit - No Power
Forecast of Cause:
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
YESYES
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose,
and replace Fuse.
YESYES
Check IPM. (PARTS INFORMATION 6)
>> If IPM is abnormal, replace Inverter PCB.
OK
If the symptom does not change by above Check 3, replace Main PCB.
NO
02-30
Trouble shooting 29
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Forecast of Cause:
1. Setting/ Connection failure 2. External cause
No Operation (Power is ON)
3. Electrical Component defective
Check Point 1 : Check indoor and outdoor installation condition
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control.
Or, check if there is an open cable connection.
Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
OK
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Wired Remote Controller and Controller PCB
Check Voltage at CN140 of Controller PCB. (terminal 1-3)
(Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data & Technical
Manual.
OKOK
MPa MPa
Check Point 5 : Check Refrigeration Cycle
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3)
Check Compressor (PARTS INFORMATION 1,2)
Attention
Strainer normally does not have temperature difference
between inlet and outlet as shown in , but if there is a
difference like shown in , there is a possibility of inside
clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
Pipe (In)Pipe (Out)
02-32
Trouble shooting 31
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Forecast of Cause :
1. Abnormal installation (Indoor/ Outdoor)
Abnormal Noise
2. Fan failure (Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit.
(Check and correct followings)
Abnormal noise is coming from Outdoor Unit.
(Check and correct followings)
Is Main Unit installed in stable condition?
Is the installation of Air suction grille and
front panel normal?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Trouble shooting 32
Forecast of Cause:
Water Leaking
Is Main Unit installed in stable condition?
Is Fan Guard installed normally?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
OK
Check if vibration noise by loose bolt or contact noise
of piping is happening.
OK
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water leak occurs
Is Main Unit installed in stable condition?
Is Main Unit broken or deformed at the time of
transportation or maintenance?
OKOK
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
OKOK
Is Fan rotating?
Diagnosis method when water is spitting out.
Is the filter clogged?
OKOK
Check Gas Pressure and correct it
if there was a gas leak.
MPa MPa
02-33
2-4 SERVICE PARTS INFORMATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
SERVICE PARTS INFORMATION 1
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection
cable?
Check Main PCB, connection of
Compressor, and winding resistance.
(Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection
cable?
Is Gas Pipe Valve open?
(Low Pressure is too low)
MPa MPa
Check if Refrigerant is leaking.
(Recharge Refrigerant)
Abnormal noise
Check if vibration noise by
loose bolt or contact noise
of piping is happening.
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Replace Compressor
Check if Strainer is clogged.
(PARTS INFORMATION 3)
Check Main PCB, connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
Replace Compressor
02-34
SERVICE PARTS INFORMATION 2
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Inverter Compressor
Check Point 1 : Check Connection
Check terminal connection of Compressor
(loose or incorrect wiring)
(WHITE)
S(V)
Inverter PCB
R(U)
C(W)
(RED)
(BLACK)
Check Point 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
R
Resistance Value :
0.79 at 20°C
RED
INVERTER PCB
TM804
Compressor
TM806TM805
BLACK
WHITE
C
S
Check Point 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
02-35
SERVICE PARTS INFORMATION 3
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Outdoor unit Electronic Expansion Valve
( EEV )
Check Point 1 : Check Connections
Check connection of connector
( Loose connector or open cable )
EXPANSION
VALVE COIL
EV
CN17
1
2
3
4
5
6
RED
1
BROWN
2
BLUE
3
ORANGE
4
YELLOW
5
WHITE
6
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Read wire
Resistance value
Check Point 3 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show,
replace Main PCB.
White - Red
Check Point 4 : Check Voltage from Main PCB.
Yellow - Brown
Orange - Red
464
at 20°C
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Blue - Brown
If Resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot Gas
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot Gas
12V
CN17
1
2
3
4
5
6
1
2
3
4
5
6
RED
BROWN
BLUE
ORANGE
YELLOW
WHITE
DC
EV
Pipe (In)
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in ,
but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
Pipe (Out)
Pipe (In)
Pipe (Out)
Pipe (In)Pipe (Out)
02-36
SERVICE PARTS INFORMATION 4
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Indoor Fan Motor 1 or 2
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.