Fujitsu AB*G36LRTE, AU*G36LRLE, AO*G30LETL, AR*G30LMLE, AB*G30LRTE Service Instruction

...
SPLIT TYPE ROOM AIR CONDITIONER
Models Indoor unit Outdoor unit
AO* G30LETL AO* G36LETL
SERVICE
INSTRUCTION
R410A
Cassette type Duct type Ceiling type
INVERTER
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION.............................................................................................
3. DRY OPERATION......................................................................................................
2. HEATING OPERATION..............................................................................................
5. INDOOR FAN CONTROL...........................................................................................
4. AUTO CHANGEOVER OPERATION.........................................................................
6. OUTDOOR FAN CONTROL.......................................................................................
8. TIMER OPERATION CONTROL................................................................................
7. COMPRESSOR CONTROL........................................................................................
10. TEST OPERATION CONTROL..................................................................................
9. ELECTRONIC EXPANSION VALVE CONTROL.......................................................
12. FOUR-WAY VALVE EXTENSION SELECT...............................................................
11. PREVENT TO RESTART FOR 3 MINUTES (3 MINUTES ST)..................................
18. ECONOMY OPERATION...........................................................................................
13. AUTO RESTART........................................................................................................
21. DEFROST OPERATION CONTROL..........................................................................
01-01 01-02 01-02 01-03 01-04 01-08
01-09 01-10 01-14 01-14
01-14 01-15
01-16
01-18
22. OFF DEFROST OPERATION CONTROL.................................................................. 01-20
23. VARIOUS PROTECTIONS......................................................................................... 01-21
15. FORCED COOLING OPERATION............................................................................. 01-15
24. COMPRESSOR STOP CONTROL............................................................................. 01-22
01-14
14. MANUAL AUTO OPERATION.................................................................................... 01-15
16. COMPRESSOR PREHEATING.................................................................................. 01-16
17. 10°C HEAT OPERATION........................................................................................... 01-16
19. FRESH AIR CONTROL.............................................................................................. 01-16
20. DRAIN PUMP OPERATION........................................................................................ 01-17
2-1-2 WIRED REMOTE CONTROLLER DISPLAY......................................................
2-1-1 INDOOR UNIT & WIRED REMOTE CONTROLLER DISPLAY..........................
2-1 ERROR DISPLAY......................................................................................................
2. TROUBLE SHOOTING
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
2-4 SERVICE PARTS INFORMATION............................................................................
02-01 02-01 02-02
02-26
02-03
02-31
3-1-2 PROCEDURES TO CHANGE THE FUNCTION SETTING................................
3-1-1 INDOOR UNIT....................................................................................................
3-1 FUNCTION SETTING................................................................................................
3. APPENDING DATA
03-01 03-01 03-04
3-2-2 OUTDOOR UNIT................................................................................................
3-2-1 INDOOR UNIT....................................................................................................
3-2 THERMISTOR RESISTANCE VALUES.................................................................... 03-07
03-07 03-07
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
Cassette/ Duct/ Ceiling type
INVERTER
( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 2°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
minimum frequency
maximum frequency
maximum frequency
AO* G30LETL
AO* G36LETL
16rps 72rps
56rps
61rps
Outside air Outside air temperature drops temperature rises
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi Me Lo Quiet
A zone 72rps
72rps
65rps
50rps
50rps
50rps
59rps
59rps
50rps
44rps
44rps
44rps
50rps
50rps
44rps
39rps
39rps
39rps
39rps
39rps
39rps
35rps
35rps
35rps
B zone
C zone
30LETL 36LETL
D zone
E zone
F zone
( Table 1 : Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +2°C to -2.5°C of the setting temperature, the compressor frequency is controlled within the range shown in Table 1. However, the maximum frequency is limited in the range shown in Fig. 1 based on the fan speed mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature, the compressor will be stopped.
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 3°C than a set temperature, the compressor operation frequency will attain to maximum performance. * If the room temperature is some degrees higher than a set temperature, the compressor will be stopped. * When the room temperature is between +2.5°C to -3°C of the setting temperature, the compressor frequency is controlled within the range shown in Table 2.
( Table 2 : Compressor Frequency Range )
01-02
minimum frequency
maximum frequency
AO* G30LETL AO* G36LETL
16rps 90rps
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 3. However, the frequency after the compressor start-up is 30rps for 60seconds.
Ts+0.5°C
Ts+1.5°C
( Table 3 : Compressor frequency )
( Fig. 2 : Compressor Control based on Room Temperature )
Operating frequency
39rps
0rps
30LETL 36LETL
X zone
Y zone
Room temperature drops
Room temperature rises
X zone
Y zone
4. AUTO CHANGEOVER OPERATION
01-03
Operation flow chart
START
Room temp.
Room temp.
>Ts+2°C ?
COOLING OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
NO
YES
YES
TS : Setting temperature
<Ts- 2°C ?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
YES
YES
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
5. INDOOR FAN CONTROL
01-04
1. Fan speed
( Table 4 : Indoor Fan Speed )
Operation mode
Air flow mode
Speed (rpm)
570 530 510 470 420 300 270
Cooling/ Fan
High
High
570 510 470 420 300 270
Med+
Med
Med
Heating
Low
Low Quiet
Quiet
Dry
S-Low
Cool air prevention
AU* G30LRLE
*Soft Quiet
*Soft Quiet
S-Low
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (High > Med, Med > Low, Low > Quiet, Quiet > Soft Quiet)
420
640 600 510 470 420 300 270 640 510 470 420 300 270
AU* G36LRLE
420
Operation mode
Air flow mode
Speed (rpm)
1270
---­ 980 790 630
---­ 420 420
Cooling
High
High
1130 980 790 630 420
Med+ Med
Med
Heating/ Fan
Low
Low Quiet
Quiet
Dry
S-Low
Cool air prevention
AR* G30LMLE
S-Lo
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (High > Med, Med > Low, Low > Quiet, Quiet > Soft Quiet)
630
AR* G36LMLE
Operation mode
Air flow mode
Speed (rpm)
1000 1000 910 750 650 500 250
Cooling/ Fan
High
High
1000 910 750 650 500 250
Med+ Med
Med
Heating
Low
Low Quiet
Quiet
Dry
S-Low
Cool air prevention
AB* G30LRTE
*Soft Quiet
S-Low
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (High > Med, Med > Low, Low > Quiet, Quiet > Soft Quiet)
650
1100 1100 910 750 650 500 250 1100 910 750 650 500 250
AB* G36LRTE
650
The airflow can be switched in 5 steps such as AUTO, Quiet, Low, Med, High, while the indoor fan only runs. When Fan mode is set at [AUTO], it operates on [Med] Fan Speed.
01-05
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Fig. 3. On the other hand, if switched in [High] ~ [Quiet], the indoor motor will run at a constant airflow of [COOL] operation modes Quiet, Low, Med, High, as shown in Table 4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C =
High mode
Med mode
Low mode
4. DRY OPERATION
Refer to the Table 4. During the dry mode operation, the fan speed setting can not be changed.
=
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Fig. 4. On the other hand, if switched in [High] ~ [Quiet], the indoor motor will run at a constant airflow of [HEAT] operation modes Quiet, Low, Med, High, as shown in Table 4.
( Fig. 4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C =
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C =
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
Low mode
Med mode
High mode
The maximum value of the indoor fan speed is set as shown in Fig. 5, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig. 5 : Cool Air Prevention Control )
01-06
6. COOL AIR PREVENTION CONTROL (Heating mode)
[ AU* G30/ 36LRLE, AB* G30/ 36LRTE ]
[ AR* G30/ 36LMLE ]
*High or setting fan mode
*Low or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Cool air prevention
S-Low
S-Low
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
High
*Med+ or setting fan mode
*Low or setting fan mode
*Low or setting fan mode
*Low or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
High
*Med+ or setting fan mode
*Low or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
*Lower speed is selected.
High
*Low or setting fan mode
*Low or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
*Lower speed is selected.
13 min. later
13 min. later
01-07
The indoor fan motor will run as shown in Fig. 6.
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.6. It depends on the Function setting "Indoor unit fan control for energy saving".
8. INDOOR UNIT FAN (CONTROL FOR ENERGY SAVING (Cooling mode))
When the defrost operation starts, the indoor fan runs according to cool air prevention control for 20 seconds. And the fan is stopped if 20 seconds have passed. When 60 seconds have passed after defrost operation is released, the fan runs according to cool air prevention control
9. DEFROST OPERATION
( Fig. 6 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 5)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(SEC)
( Table 5 : Indoor fan speed )
AU*G30/ 36LRLE 420 rpm 420 rpm
AR*G30/ 36LMLE 630 rpm 630 rpm
AB*G30/ 36LRTE 650 rpm 650 rpm
Dry
Cooling
6. OUTDOOR FAN CONTROL
01-08
*
The outdoor fan speed mentioned above depends on the compressor frequency. (When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequency decreases, the outdoor fan speed also changes to the lower speed.)
*
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as Table8 without relating to the compressor frequency.
( Table8 : Outdoor fan speed after the defrost )
1. Outdoor Fan Motor
2. Fan Speed
AC Motor DC Motor
AO*G30/ 36LETL
The Table 6 shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table 6 : Type of Motor )
900rpm
( Fig.7 : Outside air temperature zone selection )
12°C
0°C
Outside air temperature
Outside air temperature
F zone
D zone
G zone
H zone
2°C
- 8°C
10°C
- 10°C
( Table 7 : Outdoor fan speed )
Cooling Heating
AO* G30LETL
AO* G36LETL
AO* G30LETL
AO* G36LETL
D
F
Zone
850/ 800/ 620/ 500/ 400
900/ 850/ 800/ 620/ 550/ 450
Refer to Fig. 7
(rpm)
500/ 320/ 250
G 300/ 250/ 200
H
D
F
G
H
300/ 250/ 200
Dry
550/ 450
500/ 320/ 250
300/ 250/ 200
300/ 250/ 200
900/ 800/ 620/ 500/ 400
900/ 800/ 620/ 550/ 450
500/ 320/ 250
300/ 250/ 200
300/ 250/ 200
550/ 450
500/ 320/ 250
300/ 250/ 200
300/ 250/ 200
7. COMPRESSOR CONTROL
01-09
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the Table 9.
Cooling Heating
Min Max Min Max Min Max
Dry
AO*G30/36LETL
AO*G30/36LETL
AO*G30/36LETL
16rps 72rps 16rps 90rps 39rps 39rps
30rps 47rps 60rps
(Table 9 : Compressor Operation Frequency Range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig. 8.
(Fig. 8 : Compressor Control at Start-up)
Time
Time Time
(Frequency)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time Time
60sec 120sec 180sec
(Time)
8. TIMER OPEARTION CONTROL
1. ON TIMER/ OFF TIMER
The Table 10 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER
PROGRAM TIMER SLEEP TIMER
AB* G30/ 36LRTE
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
( Table 10 : Timer Setting )
2. PROGRAM TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time Set time Set time Set time
01-10
8-1 WIRELESS REMOTE CONTROLLER
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1°C
+2°C
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not changed and the operation stops at the time of timer setting.
-4°C
-3°C
-2°C
-1°C
Set
30min
30min
30min
01-11
01-12
9-2 WIRED REMOTE CONTROLLER
The Table 11 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
AR* G30/ 36LMLE AU* G30/ 36LRLE
( Table11 : Timer Setting )
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The weekly timer allows up to two ON and OFF time to set up per day.
Use this timer function to set operating time for each day of the week.
Operation mode
The operating time can be set in 30 min increments only. The OFF time can be carried over to next day. The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
01-13
The DAY OFF setting is only available for days for which weekly settings already exist.
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
During COOLING/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower.
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
Normal
Next day setting
If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
2-2. DAY OFF setting
3. TEMPERATURE SET BACK TIMER
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
Preceding day Next day
DAY OFF
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
DAY OFF
Setting day
Preceding day Next daySetting day
Case of SET BACK timer on the Cooling operation. ( Setting temperature :22°C, SET BACK temperature :26°C)
SET BACK setting
Operation temperature
Operation temperature
26°C
22°C
26°C
22°C
24°C
*1
ON OFF OFFON
*1: During the SET BACK function, the setting temperature is changed.
Change the setting temperature: 22°C 24°C
9. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table 12. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
The expansion valve is set at 480 pulses after 120 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).
10. TEST OPERATION CONTROL
[ Wireless remote controller ]
Under the condition where the air conditioner runs, press the TEST RUN button of the remote control, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
[ Wired remote controller ]
If the operation lamp is on, press the START/STOP button to turn it off. Press the MODE and FAN buttons at the same time for more than two seconds to start the test operation. The operation lamp will light up and "o1" will be displayed on the set temperature display.
[ Release ]
Perform the test operation for 60 minutes. Pressing the START/STOP button will stop the test operation.
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 3 minutes later after the compressor stopped.
11. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
12. FOUR-WAY VALVE EXTENSION SELECT
01-14
( Table 12 : The pulse range of the electronic expansion valve control )
Cooling / Dry mode
Heating mode
AO*G30LETL AO*G36LETL
Operation mode Pulse range
between 53 to 480 pulses.
between 40 to 480 pulses.
14. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 13. If the remote control is lost or battery power dissipated, this function will work without the remote control.
OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous (No timer setting available) SETTING TEMP. 24°C SETTING LOUVER Standard SWING OFF
(Table 13)
01-15
15. FORCED COOLING OPERATION
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more. During the forced cooling operation, it operates regardless of room temperature sensor. Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON and 1 second OFF on both operation LED and timer LED (same as test operation). Forced cooling operation is released after 60 minutes of starting operation. The FORCED COOLING OPERATION will start as shown in Table 14.
Manual auto operation
OPERATION MODE FAN CONT. MODE TIMER MODE SETTING TEMP. SETTING LOUVER
SWING
( Table 14 )
Forced cooling operation Cooling Hi
Initial : Horizontal (It is changed follow as setting of remote controller)
OFF
Room Temp is not controlled
-
If cooling operation is set, the operation is controlled as shown in Table 14.
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
[ Operation contents memorized when the power is interrupted ]
13. AUTO RESTART
Operation mode Set temperature Set air flow Set air flow direction Swing Economy operation 10°C Heat operation
Thermistor detected position
Timer mode
Wireless RC
Wired RC (Memory Backup : Disable)
Wired RC (Memory Backup : Enable)
OFF Timer ON Timer WEEKLY Timer Temperature SET BACK Timer
: Memorize : Not memorize
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup. Refer to the installation manual of wired remote controller for details.
01-16
When the outdoor heat exchanger temperature is lower than 0°C and the all operation mode has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started and when the outdoor heat exchanger temperature rises to 2°C or greater, preheating is ended.
16. COMPRESSOR PREHEATING
( Fig. 9 : Compressor Preheating )
ON
0°C
2°C
OFF
17 . 10°C HEAT OPERATION
The 10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller. The 10°C HEAT operation is almost the same operation as below settings.
Mode Heating
Setting temperature 10°C
Fan mode AUTO
( Table 15 )
18. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating
Target temperature Setting temp.+1°C Setting temp.-1°C
( Table 16 )
The fan motor for Fresh Air(Field supply) is operated in synchronization with the indoor fan operation as shown in Fig. 10.
19. FRESH AIR CONTROL
(Fig. 10 : Fresh Air control)
Operation
Stop
Operation
Stop
Fan motor (Indoor unit)
Fan motor (for Fresh Air)
01-17
20. DRAIN PUMP OPERATION
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Anti- freezing protection", the drain pump is turned off in 1 hour after the compressor stops.
4. When the water level in the drain pan rises up and then the float switch functions: The compressor, indoor and outdoor fan motor operation are stopped. Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
5. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates. (It is necessary to turn off power for release it. )
6. When the float switch turns OFF less than 3 minutes, the unit starts Cooling operation.
1 2
1.When the water level in the drain pan rises up and then the float switch functions: Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates. Thereafter, even if the float switch turns OFF, the "FAILURE INDICATION" is not released. (It is necessary to turn off power for release it. )
During Cooling / Dry mode
3 minutes
ON
OFF
ON
OFF
Compressor
Drain Pump
3 minutes
3 minutes ST
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Float Switch
Compressor
Indoor Fan
Drain Pump
3 minutes
ON
OFF
ON
OFF
Float Switch
Drain Pump
During Heating / Fan mode / Stop operation
<Float Switch turns OFF less than 3 minutes>
Less than 3 minutes
.
.
The indoor unit fan motor operates after the float switch is turned off.
3
(Fig. 11 : Detail of Drain Pump Operation)
01-18
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +13°C or Compressor operation time has passed 15 minutes.
21. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 17.
(Table 17 : Condition of starting Defrost Operation)
1st time defrosting after starting operation
Less than 22 min.
22 to 62 min.
62 min. to 4 hours
More than 4 hours
Does not operate
- 9°C
- 5°C
- 3°C
Compressor integrating operation time
Compressor contiguous operation time
Defrost operation is released when the conditions become as shown in Table 18.
(Table 18 : Defrost Release Condition)
Operation temperature
Below 10 min.
Above 10 min.
Less than 35 min.
35 min. to 215min
215 min. to 4 hours
Does not operate
- 6°C
- 5°C
More than 4 hours
- 3°C
Compressor integrating operation time
Compressor contiguous operation time
Operation temperature
Below 10 min.
Above 10 min.
Defrosting after 2nd time upon starting operation
Compressor integrating operation time
Operating condition
Integrating defrost for intermittent operation
Less than 10 min.
If the compressor continuous operation time is less than 10 minutes, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
OFF count of the compressor
40 times
More than 210 min.
Compressor OFF
(at outside air temp.< 2°C)
=
(Not defrosted for 10 minutes)
Outdoor fan : OFF Compressor : OFF EEV : 480pulse 4-way valve : OFF Compressor: ON (Frequency : 55rps)
Heating operation start : Compressor ON
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 13°C or Compressor ON time: Over 15 minutes
Defrost end
01-19
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger temperature as follows.
Compressor integrating operation: Over 22 minutes to below 62 minutes
Compressor integrating operation: Over 240 minutes
Compressor integrating operation: Over 62 minutes to below 240 minutes
Outdoor HEX temp.: Below - 9°C
Outdoor HEX temp.: Below - 5°C
Outdoor HEX temp.: Below - 3°C
In case of 1st defrost
In case of 2nd and later defrost
Outdoor temp ­Outdoor HEX temp. : Above 5 °C
Compressor integrating operation: Over 35 minutes to below 215 minutes
Outdoor HEX temp.: Below - 6°C
Compressor integrating operation: Over 215 minutes to below 240 minutes
Outdoor HEX temp.: Below - 5°C
Compressor integrating operation: Over 240 minutes
Outdoor HEX temp.: Below - 3°C
Compressor OFF: Outside air temp.< 2°C (More than 210 min.)
Compressor OFF count : 40 times (Less than 10min.)
In case of Integrating defrost for intermittent operation
Defrost start
=
*HEX : Heat EXchanger
22. OFF DEFROST OPERATION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than -4°C, compressor continuous operation more than 10 minutes, and compressor operation integrating time lasts for more than 30 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature : Below -4°C Compressor continuous operation : Over 10 minutes Compressor integrating operation : Over 30 minutes
Defrost start
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature :
Over +13°C
or
Compressor ON time : Over 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +13°C or Compressor operation time has passed 15 minutes.
01-20
23. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 10rps and it continues to decrease the frequency for 10rps every 120 seconds until the temperature becomes lower than Temperature . When the discharge temperature becomes lower than Temperature , the control of the compressor frequency is released. When the discharge temperature becomes higher than Temperature , the compressor is stopped and the indoor unit LED starts blinking.
AO* G30/ 36LETL
104°C 101°C 110°C
( Table 19 : Discharge Temperature Over Rise Prevention Control / Release Temperature )
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit value that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
( Table 20 : Current Release Operation Value / Release Value )
01-21
[ Heating ]
T0 : Outdoor Temperature
[ Cooling ]
AO* G30LETL AO* G30LETL
T0 (Control / Release)
9.0A / 8.5A
10.0A / 9.5A
12.5A / 12.0A
14.5A / 14.0A
50°C
46°C
40°C
T0 : Outdoor Temperature
T0 (Control / Release)
10.0A / 9.5A
11.5A / 11.0A
14.5A / 14.0A
14.5A / 14.0A
17°C
12°C
5°C
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature .
( Table 21 : Anti-freezing Protection Operation / Release Temperature )
Outdoor temperature
Over than 10°C *1 or 12°C *2
Less than 10°C *1 or 12°C *2
*1. When the temperature drops. *2. When the temperature rises.
4°C
7°C
13°C
Temperature Temperature
12°C
2°C
14.5A / 14.0A
14.5A / 14.0A
T0 : Outdoor Temperature
AO* G36LETL
T0 (Control / Release)
9.0A / 8.5A
10.0A / 9.5A
13.0A / 12.5A
16.5A / 16.0A
50°C
46°C
40°C
12°C
2°C
16.5A / 16.0A
16.5A / 16.0A
AO* G36LETL
T0 : Outdoor Temperature
T0 (Control / Release)
10.0A / 9.5A
11.5A / 11.0A
16.0A / 15.5A
18.0A / 17.5A
17°C
12°C
5°C
01-22
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C or greater, the compressor is stopped and trouble display is performed.
5. HIGH TEMPERATURE AND HIGH PRESSURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
Indoor heat exchange temperature rises
Indoor heat exchange temperature drops
[ Control System ]
It returns to the normal operation
Compressor is stopped
53°C
55°C
63°C
50°C
The compressor frequency is decreased 2rps every 120seconds.
The compressor frequency is decreased 15rps every 120seconds.
6. COMPRESSOR TEMPERATURE PROTECTION
When the compressor temperature sensor detects higher than 108°C, the compressor is stopped. The protection is released when the compressor temperature sensor detects 80°C after 3 minutes of compressor stop.
7. HIGH PRESSURE PROTECTION
When the pressure switch becomes OFF (Open : higher than 4.2 MPa), the compressor is stopped. It is released when the pressure switch becomes ON (Close : lower than 3.2 MPa) after 3 minutes of compressor stop.
24. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than Temp in the Table 22, the compressor is stopped.
( Table 22 : Operation temperature of compressor stop control )
Temperature
AO* G30/ 36LETL
Cooling Heating
-15°C
Stable zone
2 . TROUBLE SHOOTING
R410A
Cassette/ Duct/ Ceiling type
INVERTER
Manual Auto Switch Error
Indoor Room Thermistor Error
Indoor Unit Model Information Error EEPROM Access Abnormal
Wired Remote Controller Communication Error
Error Contents
Continuous
Continuous
4 times
Continuous2 times
3 times
3 times
5 times
Continuous2 times1 times
Continuous1 times1 times
Trouble shooting
Economy (Green)
Timer (Orange)
Operation (Green)
02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
1 times
Serial Communication Error
Indoor Unit Fan Motor Error
Indoor Heat Ex. Thermistor Error
Continuous4 times 2 times
Continuous1 times5 times
Continuous
Continuous3 times
7 times
5 times
1 times
Continuous
7 times 3 times
Continuous
7 times 4 times
Continuous
2 times
7 times
Drain Pump Error
Discharge Thermistor Error
Heat Ex. Liquid Outlet Thermistor Error
Outdoor Thermistor Error
Compressor Thermistor Error
Please refer the flashing pattern as follows. The OPERATION, TIMER, ECONOMY lamps operate as follows according to the error contents.
1,2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Continuous8 times 4 times
Current Sensor Error
Continuous8 times 6 times
High Pressure Switch Error
Continuous10 times 3 times
Compressor Temp. Error
Continuous
Continuous5 times
9 times
9 times
7 times
Compressor Control Error
Outdoor Unit Fan Motor Error
Continuous4 times9 times
Continuous9 times 9 times
4 Way Valve Error
Continuous1 times10 times
Discharge Temp. Error
Over Current Error
Continuous5 times6 times
IPM Error
Indoor Unit Display
Wired Remote Controller Display
11
12
32
35
41
42
51
53
64
65
71
72
73
74
84
86
94
95
97
99
A1
A3
Continuous4 times6 times
A. F. Voltage Error
[ ]
[ ]
[ ]
02-02
When " " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authorized service personnel.
2-1-2 WIRED REMOTE CONTROLLER DISPLAY
1. SELF - DIAGNOSIS
SU MOTUWETH FR SA
Unit number (usually 0)
Error code
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
3. Press the SET TEMPERATURE button to select the error history number.
SU MOTU WETH FR SA
Error code
Error history number
0 1 2 3 4 5 6 7 F E d c b A 9 8
Lower
Raise
Trouble shooting 1 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
Serial Communication Error (Serial Reverse Transfer Error)
Outdoor unit Main PCB Outdoor unit Fan motor
1. Connection failure 2. External cause 3. Main PCB failure 4. Outdoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC216V(AC240V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
When the indoor unit cannot receive the serial signal from Outdoor unit more than 2minutes after power ON, or the indoor unit cannot receive the serial signal more than 15seconds during normal operation.
02-03
2-2 TROUBLE SHOOTING WITH ERROR CODE
OK
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3. >> If it is abnormal, Check the parts as follows.
- Outdoor unit fan motor (PARTS INFORMATION 5) >> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB. >> If the parts are normal, replace Main PCB.
1
2
3
L
N
RED
WHITE
BLACK
BLACK
WHITE
+
-
Trouble shooting 2 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Serial Communication Error (Serial Forward Transfer Error)
Indoor unit Controller PCB Indoor unit Fan motor Outdoor unit Main PCB
1. Connection failure 2. External cause 3. Controller PCB failure 4. Indoor unit fan motor failure
5. Outdoor unit Main PCB
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC216V(AC240V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC30V and AC130V at outdoor unit terminal 2 - 3. >> If it is abnormal, replace Controller PCB. >> If it is abnormal, Check Indoor unit fan motor. (PARTS INFORMATION 4) >> If Indoor unit fan motor is abnormal, replace Indoor unit fan motor and Controller PCB. >> If it is abnormal, replace Outdoor unit Main PCB.
When the outdoor unit cannot properly receive the serial signal from indoor unit for 10 seconds or more.
02-04
1
2
3
L
N
RED
WHITE
BLACK
BLACK
WHITE
+
-
Trouble shooting 3 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Indicate or Display:
Wired Remote Controller Communication Error
Indoor unit Controller PCB Wired Remote Controller (Option)
1. Connection failure 2. Wired Remote Controller failure 3. Controller PCB failure
Check & correct the followings. Check the connection of terminal between Wired Remote Controller and indoor unit, and check if there is a disconnection of the cable.
When the indoor unit cannot properly receive the signal from Wired Remote Controller for 1 minute or more.
02-05
Refer to error code table.
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Check Voltage at CN14 (terminal 1-3) of Controller PCB. (Power supply to Remote Control)
02-06
Trouble shooting 4 INDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit Model Information Error EEPROM Access Abnormal
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 : Check Indoor unit electric components
YESYES
NO
Indoor unit Controller PCB
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
Trouble shooting 5 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Manual Auto Switch Error
Indoor Unit Controller PCB Indicator PCB Manual Auto Switch
When the Manual Auto Switch becomes ON for consecutive 60 or more seconds.
1. Manual Auto Switch failure 2. Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual Auto Switch
Check if Manual Auto Switch is kept pressed. Check ON/OFF switching operation by using a meter.
>> If Manual Auto Switch is disabled (on/off switching), replace it.
Check Point 2 : Replace Controller PCB and Indicator PCB
If Check Point 1 do not improve the symptom, replace Controller PCB and Indicator PCB and execute the check operation again.
02-07
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Room temperature thermistor
Detective details:
Room temperature thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failure
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
6.58.0
10.012.515.820.225.933.6
4.35.3Resistance value (k )
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB and execute the check operation again.
02-08
Trouble shooting 6 INDOOR UNIT Error Method:
Indicate or Display:
Indoor Room Thermistor Error
Refer to error code table.
Temperature (°C )
Temperature (°C )
0
40 45
5
44.0
-5 10
58.2
-10 15 20 25
30 35
Resistance value (k )
H/E (MID) Thermistor
Room Temp. Thermistor
AR*G30/ 36LMLE
BLACK BLACK
121
2
1 1 2 2
1 1 2 2
CN5
CN8
GRAY
GRAY
1 2
CN7
H/E (MID) Thermistor
Room Temp. Thermistor
AU*G30/ 36LRLE
RED RED
121
2
1 1 2 2
CN5
CN8
BLACK BLACK
1 2
CN7
121
2
121
2
1 2
H/E (MID) Thermistor
Room Temp. Thermistor
BLACK BLACK
CN5
CN8
GRAY GRAY
CN7
BLACK BLACK
AB*G30/ 36LRTE
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Detective Actuators:
Indoor unit Controller PCB Heat exchanger (MID) Thermistor
Detective details:
Heat exchanger (MID) thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB and execute the check operation again.
02-09
Trouble shooting 7 INDOOR UNIT Error Method:
Indicate or Display:
Indoor Heat Ex. Thermistor Error
Refer to error code table.
31.739.649.762.9
80.3103.3134.2176.0
17.120.825.6Resistance value (k )
Temperature (°C )
Temperature (°C )
0
40 45 50
14.1
55
5 10
1131.9
-30
804.5
-25
579.6
-20
422.9
-15
312.3
-10
233.2
-5 15
20 25 30 35
11.66010.4
63
Resistance value (k )
H/E (MID) Thermistor
Room Temp. Thermistor
AR*G30/ 36LMLE
BLACK BLACK
121
2
1 1 2 2
1 1 2 2
CN5
CN8
GRAY
GRAY
1 2
CN7
H/E (MID) Thermistor
Room Temp. Thermistor
AU*G30/ 36LRLE
RED RED
121
2
1 1 2 2
CN5
CN8
BLACK BLACK
1 2
CN7
121
2
121
2
1 2
H/E (MID) Thermistor
Room Temp. Thermistor
BLACK BLACK
CN5
CN8
GRAY GRAY
CN7
BLACK BLACK
AB*G30/ 36LRTE
02-10
Trouble shooting 8 INDOOR UNIT Error Method:
Indicate or Display:
Indoor unit Fan Motor Error
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
OK
Indoor unit Controller PCB Indoor unit fan motor
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is below 1/3 of target frequency is continued more than 56 seconds.
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Indicate or Display:
Refer to error code table.
Trouble shooting 9 INDOOR UNIT Error Method:
Drain Pump Error
Detective Actuators:
Indoor unit Controller PCB Float switch
Detective details:
When Float switch is ON for more than 3 minutes.
Check Point 1 : Check Float switch
Check operation of float switch. (any blocking by dust, etc.) Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is abnormal, replace it.
ON OFF
OK
Forecast of Cause :
1. Float switch failure 2. Shorted connector/wire 3. Controller PCB failure
4. Drain pump failure 5. Hose clogging
Check Point 2 : Check Connector (CN 9) / Wire
Check loose contact of CN9 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
Check Point 4 : Check Controller PCB
If Check Point 1 ~ 3 do not improve the symptom, change Controller PCB and execute the check operation again.
OK
OK
Check Point 3 : Check Drain hose
Check Drain hose .
>>If there is Hose clogging. Please clear the clog.
02-11
Trouble shooting 10 OUTDOOR UNIT Error Method:
A.F Voltage Error
02-12
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
Outdoor unit Main PCB
1. External cause 2. Connector connection failure 3. Main PCB failure
Check Point 2 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Replace Main PCB
If Check Point 1 - 2 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit. Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
When inverter input DC voltage is higher than 425V or lower than 80V. When a momentary power cut off occurred on low voltage
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Outdoor Fan
OK
OK
Check Point 5 : Replace Main PCB
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Outdoor unit Main PCB Compressor
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Compressor failure 5. Main PCB failure
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
Check Outdoor Fan Motor. (Refer to Trouble shooting 20)
>> If the Fan Motor is failure, replace it.
Check Point 4 : Check Compressor
(PARTS INFORMATION 2)
Check Compressor.
If Check Point 1 4 do not improve the symptom, change Main PCB.
When more than normal operating current to IPM in Main PCB flows, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
02-13
Trouble shooting 11 OUTDOOR UNIT Error Method:
IPM Error
Indicate or Display:
Refer to error code table.
OK
OK
Trouble shooting 12 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
17.826.3
20
40.0
62.579.1100.9129.8168.6Resistance value (k )
1510
1013.1
-30
531.6
-20
292.9
-10
221.1
-5 50Temperature (°C )
12.3
30 5040 60
2.03.44.66.38.7Resistance value (k )
120100908070Temperature (°C )
Discharge Thermistor Error
Outdoor unit Main PCB Discharge pipe temperature thermistor
When Discharge pipe temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-14
Refer to error code table.
BROWN
BROWN
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
CN64
BLUE
BLUE
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
Trouble shooting 13 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Compressor Thermistor Error
Outdoor unit Main PCB Compressor temperature thermistor
When Compressor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-15
Refer to error code table.
17.826.3
20
40.0
62.579.1100.9129.8168.6Resistance value (k )
1510
1013.1
-30
531.6
-20
292.9
-10
221.1
-5 50Temperature (°C )
12.3
30 5040 60
2.03.44.66.38.7Resistance value (k )
120100908070Temperature (°C )
OKOK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
BROWN
BROWN
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
CN64
BLUE
BLUE
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
Trouble shooting 14 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Heat Ex. Liquid Outlet Thermistor Error
Outdoor unit Main PCB Heat exchanger temperature thermistor
When Heat exchanger temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-16
Refer to error code table.
7.7
5
9.712.416.120.927.549.2Resistance value (k )
0-5-10-20
92.3
-30Temperature (°C ) 10 15
0.91.21.82.63.9Resistance value (k )
70
0.6
80
0.5
9060504030
6.1
20Temperature (°C )
OKOK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
BROWN
BROWN
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
CN64
BLUE
BLUE
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
Trouble shooting 15 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
16.1
5
20.726.935.246.662.3115.2Resistance value (k )
0-5-10-20
224.3
-30Temperature (°C ) 10 15
1.62.43.55.28.0Resistance value (k )
70
1.2
8060504030
12.6
20Temperature (°C )
Outdoor Thermistor Error
Outdoor unit Main PCB Outdoor temperature thermistor
When Outdoor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-17
Refer to error code table.
OKOK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
BROWN
BROWN
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
CN64
BLUE
BLUE
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
Trouble shooting 16 OUTDOOR UNIT Error Method:
Current Sensor Error
02-18
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Replace Main PCB
YES
NO
OK
Outdoor unit Main PCB
Check Point 2 : Check connections of Outdoor Unit Electrical Components
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
1. Defective connection of electric components 2. External cause 3. Main PCB failure
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
When Input Current Sensor has detected 0A, while Inverter Compressor is operating at higher than 56rps, after 1minute upon starting the Compressor. (Except during the defrost operation)
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Trouble shooting 17 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Indicate or Display:
02-19
Refer to error code table.
High Pressure Switch Error
Forecast of Cause :
Check Point 1 : Check the high pressure switch connection state
OK
Outdoor unit Main PCB High Pressure Switch
1. High pressure switch connector disconnection, open
2. High pressure switch characteristics failure
3. Main PCB failure
When pressure switch open is detected in 10 seconds after the power is turned on.
Connector and wiring connection state check Cable open check
Check Point 2 : Check the high pressure switch characteristics
Switch characteristics check * For the characteristics of high pressure switch, refer to below.
OK
Check Point 3 : Replace Main PCB
Change Main PCB, and execute the check operation again.
Type of contact
Characteristics of high pressure switch
C
H
Pressure
high pressure switch
4.2 0.1MPa
3.2 0.15MPa
Contact : Short Open
Contact : Open Short
(CN74)
02-20
Trouble shooting 18 OUTDOOR UNIT Error Method:
Indicate or Display:
Over Current Error
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
Check Point 2: Replace Main PCB
Outdoor unit Main PCB Compressor Transistor PCB (IPM)
If Check Point 1 do not improve the symptom, change Main PCB.
OKOK
Check Point 3: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
1. Outdoor unit fan operation defective, foreign matter on hear exchanger, excessive rise of ambient temperature
2. Main PCB
3. Inverter compressor failure (lock, winding short)
4. Transistor PCB (IPM) failure
"Protection stop by overcurrent generation after inverter compressor start processing completed'' generated consecutively 10 times. * The number of generations is reset if the start-up of the compressor succeeds.
No obstructions in air passages? Heat exchange fins clogged Outdoor unit fan motor check Ambient temperature not raised by the effect of other heat sources? Discharged air not sucked in?
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
Trouble shooting 19 OUTDOOR UNIT Error Method:
Compressor Control Error
02-21
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OKOK
Check Point 3: Replace Main PCB
Outdoor unit Main PCB Compressor
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1,2 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of phase with actual rotor location more than 90°, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
OKOK
Indicate or Display:
Refer to error code table.
02-22
Trouble shooting 20
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Check Outdoor unit fan motor
OK
OK
Outdoor Unit Fan Motor Error
Outdoor unit Main PCB Outdoor unit fan motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Outdoor unit fan motor. (PARTS INFORMATION 5) >>If Outdoor Fan Motor is abnormal, replace Outdoor fan motor and Main PCB.
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated 3 times in a row, compressor and fan motor stops. If and repeats 5 times in a row, compressor and fan motor stops permanently.
Check Point 2 : Check ambient temp. around motor
OK
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Indicate or Display:
Refer to error code table.
Read wire DC voltage
Red - Black
280V (AC220V-10%)~ 373V (AC240+10%)
White - Black
15 1.5V
CN800
1 2 3 4 5 6 7
1 2 3 4 5 6 7
BLACK WHITE YELLOW BROWN
RED
FM
FAN MOTOR
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
02-23
[ Solenoid coil ] Remove CN30 from PCB and check the resistance value of coil. Resistance value is about 1.4k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ] Check each piping temperature, and the location of the valve by the temperature difference. >> If the value location is not proper, replace 4-way valve.
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1- 3 do not improve the symptom, replace Main PCB.
Check Point 2 : Check thermistor of Indoor unit
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor, (Refer to Trouble shooting 6,7), If defective, replace the thermistor.
Indoor unit Controller PCB Heat exchanger temperature thermistor Room temperature thermistor 4-way valve
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops. Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 20degC Heating operation [indoor heat exchanger temp.] - [Room temp.] < -20degC If the same operation is repeated 5 times, the compressor stops permanently.
Trouble shooting 21 OUTDOOR UNIT Error Method:
4-Way Valve Error
Indicate or Display:
Refer to error code table.
<Cooling operation>
OK
OK
OK
OK
OK
OK
<Heating operation>
Discharge temperature thermistor Outdoor unit Main PCB
"Protection stop by "discharge temperature 110degC during compressor operation"" generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 12".
Check Point 4 : Check the discharge thermistor
EEV open?
Strainer clogging check (Refer to PARTS INFORMATION 3)
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (PARTS INFORMATION 5)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV open?
Strainer clogging check (Refer to PARTS INFORMATION 3)
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
02-24
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 22 OUTDOOR UNIT Error Method:
Discharge Temp. Error
Indicate or Display:
Refer to error code table.
Check Point 6 : Replace Main PCB
If Check Point 1- 5 do not improve the symptom, replace Main PCB.
<Cooling operation>
OK
OK
OK
OK
OK
OK
<Heating operation>
Compressor temperature thermistor Outdoor unit Main PCB
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 12".
Check Point 4 : Check the discharge thermistor
EEV open?
Strainer clogging check (Refer to PARTS INFORMATION 3)
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (PARTS INFORMATION 5)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV open?
Strainer clogging check (Refer to PARTS INFORMATION 3)
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
02-25
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 23 OUTDOOR UNIT Error Method:
Compressor Temp. Error
Indicate or Display:
Refer to error code table.
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Compressor temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
Check Point 6 : Replace Main PCB
If Check Point 1- 5 do not improve the symptom, replace Main PCB.
"Protection stop by "compressor temperature 108°C during compressor operation"" generated 2 times within 24 hours.
Trouble shooting 24
Forecast of Cause:
OKOK
Indoor Unit - No Power
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
02-26
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC216 - 264V appears at Outdoor Unit Terminal L - N.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
OK
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
OK
Trouble shooting 25
Forecast of Cause:
Check Point 3 : Check Electrical Components
OKOK
OKOK
OK
OK
Check Point 1 : Check Installation Condition
Outdoor Unit - No Power
1. Power Supply failure 2. External cause
3. Electrical Components defective
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check the voltage of power supply.
>> Check if AC216 - 264V appears at Outdoor Unit Terminal L - N.
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
If the symptom does not change by above Check 3, replace Main PCB.
02-27
Trouble shooting 26
Forecast of Cause:
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check Wired Remote Controller and Controller PCB
OK
OK
OKOK
No Operation (Power is ON)
1. Setting/ Connection failure 2. External cause
3. Electrical Component defective
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection. Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and Data & Technical Manual.
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
02-28
Check Voltage at CN14 (terminal 1-3) of Controller PCB. (Power supply to Remote Control)
Attention
Trouble shooting 27
Forecast of Cause:
Check Point 2 : Check Outdoor Unit Operation
Check Point 1 : Check Indoor Unit
Check Point 3 : Check Site Condition
Check Point 5 : Check Refrigeration cycle
Check Point 4 : Check Indoor/ Outdoor Installation Condition
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
OKOK
OKOK
OKOK
OKOK
MPa MPa
No Cooling / No Heating
1. Indoor Unit error 2. Outdoor Unit error
3. Effect by Surrounding environment
4. Connection Pipe / Connection Wire failure 5. Refrigeration cycle failure
Does Indoor unit FAN run on HIGH FAN?
Is Air Filter dirty? Is Heat Exchanger clogged?
Check if Energy save function is operated.
Check if Outdoor Unit is operating
Check any objects that obstruct the air flow route.
Check clogged Heat Exchanger.
Is the Valve open?
Is capacity of Indoor unit fitted to Room size?
Any windows open? Or direct sunlight ?
Check connection pipe (specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3)
Check Compressor (PARTS INFORMATION 1,2)
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-29
Trouble shooting 28
Forecast of Cause :
Trouble shooting 29
Forecast of Cause:
OK
OK
OK
OK
OKOK
OKOK
OKOK
MPa MPa
Abnormal Noise
1. Abnormal installation (Indoor/ Outdoor)
2. Fan failure (Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit. (Check and correct followings)
Abnormal noise is coming from Outdoor Unit. (Check and correct followings)
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is Main unit installed in stable condition? Is the installation of air suction grille and front panel normal?
Is Fan broken or deformed? Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Is Main Unit installed in stable condition? Is Fan Guard installed normally?
Check if vibration noise by loose bolt or contact noise of piping is happening.
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
Water Leaking
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water is spitting out.
Is the filter clogged?
Check Gas Pressure and correct it if there was a gas leak.
Diagnosis method when water leak occurs
Is Drain Hose connection loose? Is there a trap in Drain Hose?
Is Drain Hose clogged?
Is Main Unit installed in stable condition? Is Main Unit broken or deformed at the time of transportation or maintenance?
Is Fan rotating?
02-30
SERVICE PARTS INFORMATION 1
MPa MPa
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check Main PCB, connection of Compressor, and winding resistance. (Refer to the next page).
Check Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas Pipe Valve open? (Low Pressure is too low)
Check if Refrigerant is leaking. (Recharge Refrigerant)
Check if Strainer is clogged. (PARTS INFORMATION 3)
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
Abnormal noise
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Check if vibration noise by loose bolt or contact noise of piping is happening.
02-31
2-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 2
Inverter Compressor
02-32
Check Point 1 : Check connection
Check Point 2 : Check winding resistance
Check Point 3 : Replace Main PCB
U(R)
V(S)
W(T)
Check terminal connection of Compressor (Loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If Check Point 1, 2 do not improve the symptom, replace Main PCB.
U(R)
(RED)
V(S)
(WHITE)
W(T)
(BLACK)
Main PCB
Check connection of Transistor PCB(IPM). (Loose or incorrect wiring)
TM303TM304
TM305
RED
WHITE
BLACK
Compressor
Main PCB
Resistance Value :
0.642 8% at 20°C
SERVICE PARTS INFORMATION 3
Check Point 2 : Check Coil of EEV
Yellow - Red (Brown)
Orange - Red(Brown)
Blue - Red (Brown)
White - Red (Brown)
Read wire
46 4
Resistance value
Check Point 1 : Check Connections
Check Point 5 : Check Opening and Closing Operation of Valve
Check Point 4 : Check Voltage from Main PCB.
Check Point 3 : Check Noise at start up
Pipe (In)
Pipe (Out)
Pipe (In)
CLOSE Example : Hot Gas
OPEN Example : Hot Gas
Pipe (Out)
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
Check Point 6 : Check Strainer
DC
at 20°C
Outdoor unit Electronic Expansion Valve ( EEV )
Check connection of connector ( Loose connector or open cable )
Remove connector, check each winding resistance of Coil.
If Resistance value is abnormal, replace EEV.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
When Valve is closed, it has a temp. difference between Inlet and Outlet.
If it is open, it has no temp. difference between Inlet and Outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-33
CN700
EXPANSION VALVE COIL
RED BROWN BLUE ORANGE YELLOW WHITE
1 2 3 4 5 6
1 2 3 4 5 6
EV
CN700
RED BROWN BLUE ORANGE YELLOW WHITE
1 2 3 4 5 6
1 2 3 4 5 6
EV
12V
SERVICE PARTS INFORMATION 5
Check Point 1 : Check rotation of Fan
Outdoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Outdoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Red) 2 3 4 (Black) 5 (White) 6 (Yellow) 7 (Brown)
DC voltage (Vm) No function No function Earth terminal (GND) Control voltage (Vcc) Speed command (Vsp) Feed back (FG)
SERVICE PARTS INFORMATION 4
Check Point 1 : Check rotation of Fan
Indoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Indoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Brown) 2 (Yellow) 3 (White) 4 (Black) 5 6 (Red)
Feed back (FG) Speed command (Vsp) Control voltage (Vcc) Earth terminal (GND) No function DC voltage (Vm)
02-34
3 . APPENDING DATA
R410A
Cassette/ Duct/ Ceiling type
INVERTER
03-01
3-1. FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
3-1-1 INDOOR UNIT
( Factory setting)
1-2. Setting the Ceiling height (For AU, AB type)
Setting Description
Function Number Setting Value
Standard (Max 3.2m) High ceiling
(30:Max 3.6m, 36:Max 4.2m)
20
00
01
Low ceiling (Max 2.7m) 02 The ceiling height values are for the 4 way outlet.
Do not change this setting in the 3 way outlet mode.
Determine the wind volume in each mode.
Select the setting values in the table below according to the height of the ceiling.
( Factory setting)
Setting Description
Function Number Setting Value Standard (2,500 hours)
Long interval (4,400 hours)
Short interval (1,250 hours) No indication
11
00
01
02 03
1-1. Setting the Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the filter sign to be displayed, select the setting value for "No indication".
( Factory setting)
Setting Description
Function Number Setting Value Normal
High static pressure 1
High static pressure 1 High static pressure 1
21
00
01
02 03
1-3. Static pressure (For AR type)
Select appropriate static pressure according to the installation conditions.
[AU type]
( Factory setting)
Setting Description Function Number Setting Value
Standard (2.5~3.0m) High ceiling
(3.0m or more)
20
00
01
[AB type]
03-02
( Factory setting)
Setting Description
Function Number Setting Value
4-way
3-way
22
00
01
1-4. Outlet directions (For AU type)
Select the setting values in the table below for using a 3-way outlet.
( Factory setting)
Setting Description
Function Number Setting Value
Standard
Upward
23
00
01
1-5. Vertical direction adjusting scope (For AU type)
To prevent from draft, we recommend using "upward mode".
( Factory setting)
Setting Description
Function Number Setting Value
Standard Lower control
Slightly warmer control Warmer control
31
00 01
02 03
1-7. Setting the Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as shown in the table below.
1-6. Setting the Cooler room temperature correction
( Factory setting)
Setting Description
Function Number Setting Value
Standard
Slightly lower control
Lower control
Warmer control
30
00
01
02
03
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
1-8. Setting the Auto restart
Enable or disable automatic system restart after a power outage.
( Factory setting)
Setting Description
Function Number Setting Value
Yes No
40
00 01
Auto restart is an emergency function such as for power failure etc. Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
03-03
1-9. Setting the Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
( Factory setting)
Setting Description
Function Number Setting Value
No Yes
42
00 01
If setting value is “00”, room temperature is controlled by the indoor unit temperature sensor.
If setting value is “01”, room temperature is controlled by either indoor unit temperature sensor or remote control unit sensor.
1-10. Setting the Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
( Factory setting)
Setting Description
Function Number Setting Value
A
B
C
D
44
00
01
02
03
1-11. Setting the External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
( Factory setting)
Setting Description
Function Number Setting Value
Operation /Stop mode
(Setting forbidden)
Forced stop mode
46
00
01
02
1-12. Indoor unit fan control for energy saving
Enable or disable indoor unit fan control when the outdoor unit is stopped.
* If setting value is "00" : When the outdoor unit is stopped, the indoor unit fan operates following the setting on the remote controller continuously. * If setting value is "01" : When the outdoor unit is stopped, the indoor unit fan operates at very low speed intermittently.
( Factory setting)
Setting Description
Function Number Setting Value
No
Yes
49
00
01
03-04
3-1-2 PROCEDURES TO CHANGE THE FUNCTION SETTING
SET BACK
SUMOTUWETH FR
SA
SUMOTUWETH FR
SA
SUMOTUWETH FR
SA
(1) Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously for more than 5 seconds to enter the function setting mode.
(2) Press the SET BACK button to select the indoor unit number.
(3) Press the Set time buttons to select the function number.
(4) Press SET TEMP. buttons ( ) ( ) to select the setting value. The display flashes as shown to the right during setting value selection.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops flashing. If the setting value display changes or if "- -" is displayed when the flashing stops, the setting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings. Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1 minute if no operation is performed.
Unit number of Indoor unit
Function number
SUMOTUWETH FR
SA
Setting value
Settings will not be changed if invalid numbers or setting values are selected.
The settings may be selected between the following two: Function Number or Setting Value.
After the power is turned on, perform the "FUNCTION SETTING" according to the installation conditions using the remote controller.
The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
PREPARATION
FUNCTION SETTING METHOD (for Wired remote controller)
Turn on the power.
* By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have been conducted before turning on the power. * Also check again to make sure no wiring mistakes were made before turning on the power.
CAUTION
After turning off the power, wait 30 seconds or more before turning on it again. The FUNCTION SETTING doesn't become effective if it doesn't do so.
03-05
FUNCTION SETTING METHOD (for Wireless remote controller)
The remote controller resets to signal code when the batteries in the remote controller are replaced. If you use a signal code other than signal code , reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes ( ) until you find the code which operates the air conditioner.
The air conditioner signal code is set to prior to shipment. Contact your retailer to change the signal code.
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP.( ) button simultaneously, press the RESET button to enter the function setting mode.
STEP 1. Setting the Remote controller Signal Code
(1) Press the SET TEMP.( ) ( ) button to change the signal code between . Match the code on the display to the air conditioner signal code. (initially set to ) (If the signal code does not need to be selected, press the MODE button and proceed to STEP 2.)
(2) Press the MODE button to accept the signal code, and proceed to STEP 2.
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) The signal code that is set through this process are applicable only to the signal in the FUNCTION SETTING. For details on how to set the signal code through the normal process, refer to REMOTE CONTROLLER SIGNAL CODE SETTING.
Function Number
Setting Value
(2) Press the FAN button to proceed to setting the value. (Press the FAN button again to return to the function number selection.)
STEP 2. Selecting the Function Number and Setting Value
(5) Press the RESET button to cancel the function setting mode.
(6) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The FUNCTION SETTING doesn't become effective if it doesn't do so.
(3) Press the SET TEMP.( ) ( ) buttons to select the setting value. (Press the MODE button to switch between the left and right digits.)
(1) Press the SET TEMP.( ) ( ) buttons to select the function number. (Press the MODE button to switch between the left and right digits.)
(4) Press the TIMER MODE button, then after you hear the beep emitted from the indoor unit, press the START/STOP button to confirm the settings.
03-06
(2) Press the MODE button for at least 5 seconds to display the current signal code. (initially set to ).
(4) Press the MODE button again. The signal code will be changed.
(3) Press the SET TEMP.( ) ( ) button to change the signal code between . Match the code on the display to the air conditioner signal code.
(1) Press the START/STOP button until only the clock is displayed on the remote controller display.
If no buttons are pressed within 30 seconds after the signal code is displayed, the display returns to the original status. In this case, start again from step 1.
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
REMOTE CONTROLLER SIGNAL CODE SETTING
The remote controller resets to signal code when the batteries in the remote controller are replaced. If you use a signal code other than signal code , reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes ( ) until you find the code which operates the air conditioner.
The air conditioner signal code is set to prior to shipment. Contact your retailer to change the signal code.
Room temperature thermistor
Temp (°C)
Resistance(k )
Voltage(V)
Temp (°C)
Resistance(k )
Voltage(V)
Temp (°C)
Resistance(k )
Voltage(V)
Temp (°C)
Resistance(k )
Voltage(V)
Temp (°C)
Resistance(k )
Voltage(V)
Indoor heat exchanger thermistor
Discharge thermistor Comp. temperature thermistor
Outdoor heat ex. thermistor
Outdoor temperature thermistor
03-07
3-2. THEMISTOR RESISTANCE VALUES
3-2-1 INDOOR UNIT
3-2-2 OUTDOOR UNIT
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
58.2
44.0
33.6
25.9
20.2
15.8
12.5
10.0
8.0
6.5
5.3
4.3
0.73
0.93
1.15
1.39
1.66
1.94
2.22
2.50
2.77
3.03
3.27
3.48
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
63.0
1131.9
804.5
579.6
422.9
312.3
233.2
176.0
134.2
103.3
80.3
62.9
49.7
39.6
31.7
25.6
20.8
17.1
14.1
11.6
10.4
0.21
0.29
0.40
0.53
0.69
0.88
1.10
1.36
1.63
1.92
2.21
2.51
2.79
3.06
3.30
3.53
3.73
3.90
4.05
4.14
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
1013.1
729.1
531.6
392.3
292.9
221.1
168.6
129.8
100.9
79.1
62.5
49.8
40.0
32.4
26.3
21.6
17.8
14.8
12.3
10.3
8.7
7.4
6.3
5.4
4.6
4.0
3.4
3.0
2.6
2.3
2.0
0.06
0.09
0.12
0.16
0.21
0.28
0.36
0.46
0.57
0.71
0.86
1.03
1.23
1.43
1.65
1.88
2.11
2.34
2.57
2.79
3.00
3.19
3.37
3.54
3.69
3.83
3.96
4.07
4.17
4.26
4.33
92.3
67.0
49.2
36.6
27.5
20.9
16.1
12.4
9.7
7.7
6.1
4.9
3.9
3.2
2.6
2.2
1.8
1.5
1.2
1.1
0.9
0.8
0.6
0.6
0.5
0.24
0.33
0.44
0.57
0.74
0.93
1.14
1.38
1.64
1.91
2.19
2.46
2.73
2.98
3.22
3.44
3.63
3.81
3.96
4.09
4.21
4.31
4.40
4.48
4.54
224.3
159.7
115.2
84.2
62.3
46.6
35.2
26.9
20.7
16.1
12.6
10.0
8.0
6.4
5.2
4.2
3.5
2.8
2.4
2.0
1.6
1.4
1.2
0.73
0.97
1.25
1.56
1.90
2.26
2.61
2.94
3.24
3.52
3.76
3.96
4.14
4.28
4.40
4.50
4.59
4.65
4.71
4.76
4.79
4.83
4.85
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
Apr. 2013 Printed in Japan
Loading...