Fujitsu AR*G12LL, AU*G07LVLA, AR*G14LL, AR*G18LL, AU*G09LVLA Service Instructions Manual

...
SPLIT TYPE ROOM AIR CONDITIONER
Models Indoor unit Outdoor unit
AO*G18LAT3 AO*G24LAT3 AO*G30LAT4
INVERTER MULTI
SERVICE
INSTRUCTION
Universal Floor / Ceiling Slim Duct / Compact Cassette Compact Wall Mounted /
Wall Mounted / Floor
AB*G14LVTA AB*G18LVT *
AR*G07LLTA AR*G09LLTA AR*G12LL* * AR*G14LL* * AR*G18LL* *
AU*G07LVLA AU*G09LVLA AU*G12LVL * AU*G14LVL * AU*G18LVL *
AS*G07LJCA AS*G09LJCA AS*G12LJCA AS*G18LFCA AS*G24LFC *
AS*G07LUCA AS*G09LUCA AS*G12LUCA AS*G14LUCA
AG*G09LVCA AG*G12LVCA AG*G14LVCA
AS*G07LMCA AS*G09LMCA AS*G12LMCA AS*G14LMCA
Refer to the combination in the catalogue
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. CAPACITY CONTROL................................................................................................
3. INDOOR FAN CONTROL...........................................................................................
2. AUTO CHANGEOVER OPERATION..........................................................................
5. OUTDOOR FAN CONTROL.......................................................................................
4. LOUVER CONTROL...................................................................................................
7. COMPRESSOR CONTROL.......................................................................................
6. TIMER OPERATION CONTROL................................................................................
9. TEST OPERATION CONTROL..................................................................................
8. ELECTRONIC EXPANSION VALVE CONTROL........................................................
11. 4-WAY VALVE EXTENSION SELECT.......................................................................
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )................................
13. MANUAL AUTO OPERATION...................................................................................
12. AUTO RESTART........................................................................................................
18. FRESH AIR CONTROL..............................................................................................
14. COMPRESSOR PREHEATING..................................................................................
21.
DEFROST OPERATION CONTROL..........................................................................
19. EXTERNAL ELECTRICAL HEATER CONTROL........................................................
22. VARIOUS PROTECTIONS.........................................................................................
01-01 01-01 01-03 01-11 01-17 01-18 01-21 01-22 01-22 01-22 01-23
01-23 01-24
01-25 01-25
01-27
20.
DRAIN PUMP OPERATION....................................................................................... 01-26
01-30
01-23
2-1-2 WIRED REMOTE CONTROLLER DISPLAY......................................................
2-1-1 INDOOR UNIT DISPLAY....................................................................................
2-1 ERROR DISPLAY......................................................................................................
2. TROUBLE SHOOTING
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
2-4 SERVICE PARTS INFORMATION............................................................................
02-01 02-01 02-02
2-1-3 OUTDOOR UNIT DISPLAY.................................................................................
02-03
02-34
02-04
02-39
3. REPLACEMENT PARTS
15. POWERFUL OPERATION......................................................................................... 01-24
16. 10°C HEAT OPERATION........................................................................................... 01-24
17. ECONOMY OPERATION........................................................................................... 01-24
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
INVERTER (MULTI )
Universal Floor / Celling Slim Duct / Compact Cassette Compact Wall Mounted / Wall Mounted / Floor type
2. AUTO CHANGEOVER OPERATION
01-01
1. CAPACITY CONTROL
Compressor frequency decides by capacity of an indoor unit, operation number of an indoor unit, set temperature, room temperature and outside temperature.
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum mode from among the Heating, Cooling, Dry and Monitoring mode. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
When operation starts, indoor fan and outdoor fan are operated for around 3 minutes. Room temperature and outdoor temperature are sensed, and the operation mode is selected in accordance with the table below. <Monitoring mode>
Cooling mode
25°C
Heating mode
( Table 1 : Operation mode selection table )
Room temperature (TR)
TR> Ts + 2°C
Ts + 2°C TR Ts - 2°C
*Middle zone
TR < Ts - 2°C Heating
When Cooling or Dry mode was selected at and air flow mode is Auto, the air conditioner operates as follow.
The same operation as COOLING OPERATION AND DRY OPERATION. When the room temperature has remained at set temperature -1.5°C, operation is automatically switched to Dry mode. If the room temperature reaches set temperature +2°C during Dry mode, operation returns to Cooling.
1
1
2
( Fig. 1 : Outdoor temperature zone selection )
Cooling
(Autmatic dry)
Operation mode
*If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling, Dry, and Heating mode, indoor unit will be operated by the same operation mode.
(2). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling, Dry, and Heating mode, indoor unit will be operated according to the outdoor temperature as below.
Cooling
Cooling
Dry(X zone)
Dry(J zone)
Compressor stop
When the room temperature drops
When the room temperature rises
Ts + 2°C
Ts - 0.5°C
Ts - 1.5°C
Ts + 1°C
Ts - 1.5°C
Ts - 2.5°C
( Fig.2 : Auto changeover : Cooling - Dry )
TR : Room temperature Ts : Setting temperature
TR : Room temperature Ts : Setting temperature
( Air flow mode : Auto )
01-02
START
Room temp.
Ts + 2
°C?
COOLING (AUTO:DRY)
OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
AUTO CHANGEOVER operation flow chart
TS : Setting temperature
Room temp.
Ts - 2
°C?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
Middle zone
NO
Operation mode
of outdoor unit : Cooling or Dry?
YES
NO
Operation mode
of outdoor unit : Heating?
YES
NO
YES
Outdoor temperature
25°C?
NO
YES
YES
NO
YES
YES
When Heating was selected at , the same operation as HEATING OPERATION of page 01-02 is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the Cooling(Auto:Dry) or Heating mode was selected at above, operation is switched to Monitoring and the operation mode is selected again.
3
1
4
1
3. INDOOR FAN CONTROL
01-03
1. Fan speed
(Table 2 : Indoor fan speed table)
AS*G07LJCA AS*G09LJCA
AS*G12LJCA
AS*G18LFCA
AS*G24LFC*
AU*G07LVLA
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Quiet > Soft Quiet)
(rpm)
(rpm)
(rpm) (rpm)
(rpm)
(rpm)
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1050 1000
950 850 710 600 480
1050
950 850 680 600
X, J zone:680
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1100 1040
980 850 710 600 480
1100
980 850 680 600
X, J zone:680
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1200 1130 1050
910 710 600
480 1200 1050
880
680
600
X, J zone:680
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1220 1120 1020
900 710 660
480 1220 1020
900
710
660
X, J zone:710
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1430 1320 1220 1020
900 720
480 1480 1220 1020
900
720
X, J zone:900
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
590 570 540 490 440 400 300 590 540 490 440 400
X, J zone:440
AR*G09LL*A (Static pressure:25Pa)
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:960
1260 1160 1060
960
500 1260 1160 1060
960
500
AU*G12LVL*
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
650 620 580 520 460 400 300 660 580 520 460 400
X, J zone:460
01-04
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
AU*G09LVLA
590 570 540 490 440 400 300 590 540 490 440 400
X, J zone:440
AU*G14LVLA
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:460
740 700 670 600 480 400 300 730 630 540 460 400
AU*G18LVLA
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:460
840 800 750 650 500 400 300 790 660 570 460 400
AR*G07LL*A (Static pressure:25Pa)
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:880
1160 1000
940 880
500 1160 1000
940
880
500
(rpm)
(rpm)
(rpm)
(rpm)
(rpm)(rpm)
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Quiet > Soft Quiet)
AR*G12LL** (Static pressure:25Pa)
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:1030
1340 1240 1140 1030
500 1340 1240 1140 1030
500
AR*G18LL** (Static pressure:25Pa)
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1380 1300 1220 1140
600 1380 1300 1220 1140
600
X, J zone:1140
01-05
AR*G14LL** (Static pressure:25Pa)
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:1030
1560 1400 1240 1030
500 1560 1400 1240 1030
500
AB*G14LVTA
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:670
850 850 800 740 670 500 300 850 800 740 670 500
AB*G18LVTA
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
X, J zone:740
1040
1000
950 800 740 500 300
1040
950 800 740 500
(rpm) (rpm)
(rpm)
(rpm)
(rpm)
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Quiet > Soft Quiet)
01-06
AG*G09LVCA
Hi
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1120/950 1000/850
860/730 660/560 660/560 660/560
1120/950
960/820 820/700 660/560 570/480
-
Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower
1230 1090
940 750 680
680 1230 1070
910
750
680
X, J zone:750
Upper & Lower
air flow mode
Upper
air flow mode
AG*G12LVCA
Hi
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1240/1040
1080/920
910/770 660/560 660/560 660/560
1240/1040
1050/890
860/730 660/560 570/480
-
Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower
1300 1140
980
750
680
680 1300 1120
930
750
680
X, J zone:750
Upper & Lower
air flow mode
Upper
air flow mode
AG*G14LVCA
Hi
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1330/1120
1140/970
940/800 660/560 660/560 660/560
1330/1120
1100/930
890/750 660/560 570/480
-
Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower Upper / Lower
1370 1180 1020
750
680
680 1370 1160
960
750
680
X, J zone:750
Upper & Lower
air flow mode
Upper
air flow mode
(rpm)
(rpm)
(rpm)
01-07
AS*G07LUCA AS*G09LUCA
AS*G12LUCA
AS*G14LUCA
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Quiet > Soft Quiet)
(rpm)
(rpm)
(rpm) (rpm)
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1030
980 980 910 850 650 610 570
1030
980 910 850 650 610
X, J zone:650
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1050 1030 1030
950 850 650 610
570 1080 1030
950
850
650
610
X, J zone:650
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1160 1110 1110 1030
930 650 610
570 1160 1110 1030
930
650
610
X, J zone:650
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1230 1180 1180 1080 1010
790 610
570 1230 1180 1080
980
740
710
X, J zone:740
01-07+1
AS*G07LMCA AS*G09LMCA
AS*G12LMCA
AS*G14LMCA
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Quiet > Soft Quiet)
(rpm)
(rpm)
(rpm) (rpm)
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1090 1050 1000
950 850 710 600
480 1090 1050
950
850
680
600
X, J zone:680
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1140 1090 1040
980 850 710 600
480 1140 1090
980
850
680
600
X, J zone:680
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1240 1190 1120 1050
910 710 600
480 1240 1190 1050
880
680
600
X, J zone:680
Powerful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Fan Speed
1240 1190 1120 1050
910 710 600
480 1240 1190 1050
880
680
600
X, J zone:680
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs. When Fan mode is set at (Auto), it operates on (Me) Fan Speed.
2. FAN OPERATION
3. COOLING OPERATION (Auto : Cooling)
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig 3. On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cooling] operation modes Quiet, Lo, Me, Hi.
( Fig.3 : Airflow change - over (Cooling : Auto) )
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
TR-Ts > +2°C
=
+1°C > TR-Ts
+2°C > TR-Ts > +1°C
=
TR-Ts >
+2.5°C
=
+1.5°C > TR-Ts
+2.5°C) > TR-Ts > +1.5°C
=
Hi
Me
Lo
=
=
=
=
4. DRY OPERATION (Auto : Dry)
During the dry operation, the fan speed setting can not be changed,it operates automatically as shown in Fig. 4. Room temperature variation which the room temperature sensor of the indoor unit body has detected.
( Fig. 4 : Indoor fan control )
10 30 60 180 60 180 60 10 30 (sec)
Fan OFF
OFF
< Compressor >
ON
Setting air flow
S-Lo
< Indoor fan air flow mode >
< All models >
< All models >
01-08
3-1 INDOOR UNIT FAN CONTROL FOR ENERGY SAVING (Cooling mode)
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.4.
It depends on the Function setting "Indoor unit fan control for energy saving."
The maximum value of the indoor fan speed is set as shown in Fig 6, based on the detected temperature by the indoor heat exchanger sensor in heating mode. Field setting is necessary at AR and AU type as "Cool air prevention : effective".
< AS*G type >
01-09
5. HEATING OPERATION (Auto : Heating)
Switch the airflow [Auto], and the indoor fan will run according to a room temperature, as shown in Fig 5. On the other hand, if switched in [Hi] [Quiet], the indoor fan will run at a constant airflow of [Heat] operation modes Quiet, Lo, Me, Hi, as shown in Table 2.
6. COOL AIR PREVENTION CONTROL (For Heating and 10°C heat operation)
( Fig.5 : Airflow change - over (Heating : Auto) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
Lo
Me
Me+
42°C
30°C
34°C
When Indoor heat exchanger temperature rises
When Indoor heat exchanger temperature drops
Hi
*Me+ or setting
FAN mode
Cool air prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
*Lo or setting
FAN mode
29°C
When Indoor heat exchanger temperature rises
When Indoor heat exchanger temperature drops
*Lo or setting
FAN mode
37°C
32°C
24°C
*Hi or setting
FAN mode
S-Lo
During NORMAL HEATING OPERATION
< AR*G type >
*Lower speed is selected
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C> TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room temperature rises
When the room temperature drops
Lo
Me
Hi
< AU*G / AR*G / AB*G / AG*G type >
< AS*G type >
( Fig.6 : Airflow change - over for cool air prevention)
*Lower speed is selected
01-10
34°C
When Indoor heat exchanger temperature rises
When Indoor heat exchanger temperature drops
Lo
39°C
Auto
When Indoor heat exchanger temperature rises
When Indoor heat exchanger temperature drops
Lo
Auto
32°C
37°C
During 10°C HEAT OPERATION
< AS*G / AU*G / AB*G type >
< AR*G type >
< AB*G / AU*G type >
42°C
30°C
34°C
When Indoor heat exchanger temperature rises
When Indoor heat exchanger temperature drops
Hi
*Me+ or setting
FAN mode
Cool air prevention
39°C
37°C
37°C
32°C
24°C
S-Lo
*Lo or setting
FAN mode
< AG*G type >
*Lower speed is selected
42°C
30°C
31°C
When Indoor heat exchanger temperature rises
When Indoor heat exchanger temperature drops
Hi
*Me or setting
FAN mode
Cool air prevention
39°C
37°C
34°C
29°C
24°C
S-Lo
*Lo or setting
FAN mode
*Lower speed is selected
31°C
When Indoor heat exchanger temperature rises
When Indoor heat exchanger temperature drops
Lo
39°C
Auto
< AG*G type >
4. LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
(Function Range)
(Table9 : Recommended Operation Range)
01-11
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode : Horizontal flow Heating mode : Downward flow AS*G07/09/12LJCA : , AS*G18/24LFCA :
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating range ( ) for long period of time, since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow Direction Louvers are left in the heating range for around 30 minutes, they will automatically return to position .
(Fig.7 : Virtical Air Direction Range)
Cooling / Heating / Dry mode / Fan mode
Cooling / Dry / Fan mode( ) : Heating / Fan mode( ) : AS*G07/09/12LJCA [ ], AS*G18/24LFCA [ ]
3. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
1 3
1
4
4
6
6
Vertical Airflow Swing Operation
Horizontal Airflow Swing Operation ( For AS*G18/24LFCA )
When the swing signal is received from the remote controller, the horizontal louver starts to swing.
Cooling / Heating / Dry / Fan mode :
(Swinging Range)
5
1
Vertical and Horizontal Airflow Swing Operation
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted and it stops at either upper end or bottom end.
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted and it stops at either upper end or bottom end.
When the horizontal swing signal is input from remote control, the combination of the vertical and horizontal swing operation is performed.
1
2
3
4
5
2. HORIZONTAL LOUVER CONTROL ( For AS*G18/24LFCA )
Horizontal Louver
Each time the button is pressed, the air directionrange will change as follows.
(Function Range)
Cooling / Heating / Dry / Fan mode
(Fig.8 : Horizontal Air Direction Range)
Power Diffuser doesn't swing in any swing operation.
For Compact Wall Mounted Type, Wall Mounted Type < AS*G07/09/12LJCA,18/24LFCA >
1. VERTICAL LOUVER CONTROL
Power DiffuserVertical Louver
Vertical Louver
<Wall Mounted Type><Compact Wall Mounted Type>
36
4
1. VERTICAL LOUVER CONTROL
3. SWING OPERATION
Each time the button is pressed, the air direction range will change as follow:
(Function Range)
01-12
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode
Horizontal flow
Heating mode Downward flow
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Table9 : Swinging Range)
(Fig.9 : Air Direction Range)
Cooling / Dry mode Fan mode ( )
Types of Air flow Direction Setting:
, , : During Cooling/Dry modes , , , : During Heating
The Remote Controller's display does not change.
Use the air direction adjustments within the ranges shown above.
During AUTO mode operation, for the first a few minutes after beginning operation, air-flow will be horizontal 1; the air direction cannot be adjusted during this period. The air flow direction setting will temporarily become 1 when the temperature of the air -flow is low at the start of the Heating mode.
Range
Heating mode Fan
m
ode ( )
The SWING operation may stop temporarily when the air conditioner’s fan is not operating, or when operating at very low speeds.
1 2 3 4 5 6 7
2. ADJUST THE RIGHT-LEFT LOUVERS
Move the Right-Left louvers to adjust air flow in the direction you prefer.
Knob (2 places)
Right-Left Louvers
Knob
To select Vertical Airflow Swing Operation
To select Horizontal Airflow Swing Operation
(No function)
For Wall Mounted Type < AS*G07/09/12/14LUCA >
1. VERTICAL LOUVER CONTROL
2. SWING OPERATION
Each time the button is pressed, the air direction range will change as follow:
(Function Range)
01-12+1
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode
Horizontal flow
Heating mode Downward flow
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Table11 : Swinging Range)
Air Direction RangeFig.9 :
Cooling / Dry mode Fan mode ( )
The Remote Controller's display does not change.
Use the air direction adjustments within the ranges shown above.
If you set the angle to position 4.7 for more than 30 minutes in COOL or DRY mode, they automatically return to position 3. In COOL or DRY mode, if the angle is set to position 4.7 for many hours, condensation may be formed, and the drips may wet your property.
During AUTO or Heating mode operation, for the first a few minutes after beginning operation, air-flow will be horizontal 1; the air direction cannot be adjusted during this period. The air flow direction setting will temporarily become 1 when the temperature of the air -flow is low at the start of the Heating mode.
Range
Heating mode Fan mode ( )
The SWING operation may stop temporarily when the air conditioner’s fan is not operating, or when operating at very low speeds.
2. ADJUST THE RIGHT-LEFT LOUVER S
Move the Right-Left louvers to adjust air flow in the direction you prefer.
To select Vertical Airflow Swing Operation
To select Horizontal Airflow Swing Operation
(No function)
Right-Left Louvers
1
2
3
4
5
6
7
Knob
For Wall Mounted Type < AS*G07/09/12/14LMCA >
01-13
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
(Function Range)
(Fig.10 : Air Direction Range)
(Operation Range)
Cooling / Heating / Dry / Fan mode :
Cooling / Dry / Fan mode
Horizontal flow
Heating mode
Downward flow
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and it stops at either upper end or bottom end. ( Stop mode means Operation stop.)
During AUTO mode operation, for the first minute after start-up, air-flow will be horizontal ; the air direction cannot be adjusted during this period.
For Compact Cassette Type < AU*G07/09/12/14/18 >
1234
1234
1
14
4
1
2
3
4
(Swinging Range)
Cooling / Heating / Dry / Fan mode :
01-14
( Fig.11 : Air Direction Range : Ceiling installation)
For Floor / Ceiling Type < AB*G14/18 >
1-1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above. The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode
Horizontal flow
Heating mode
Downward flow
(Function Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and it stops at either upper end or bottom end.
The indoor fan motor starts after the louver reaches to the setting position.
( Stop mode means Operation stop.)
1
4
5
6
7
3
2
1234567
1234567
1 7
(Swinging Range)
7
Cooling / Dry / Fan mode Heating mode
6
7
( Fig.12 : Air Direction Range : Floor installation)
Cooling / Heating / Dry / Fan mode :
2-1. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Heating / Dry / Fan mode :
Use the air direction adjustments within the ranges shown above.
(Function Range)
(
Fig.13 : Air Direction Range : Ceiling installation)
(Operation Range)
2-2. SWING OPERATION
When the swing signal is received from the remote controller, the horizontal louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and it stops at either upper end or bottom end.
01-15
( Stop mode means Operation stop.)
12345
12345
1
3
4
5
2
(Swinging Range)
Cooling / Heating / Dry / Fan mode
5
12 3 45
( Fig.14 : Air Direction Range : Floor installation)
01-16
For Floor Type < AG*G09/12/14 >
1. VERTICAL LOUVER CONTROL
2. SWING OPERATION
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode
Horizontal flow
Heating mode
Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes , and it cannot be adjusted.
(Function and Operation Range)
When the swing signal is received from the remote controller, the vertical louver starts to swing .
(Swinging Range)
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrrupted
and it stops at either upper end or bottom end.
( Fig.15 : Air Direction Range)
Cooling / Heating / Dry / Fan mode :
5. OUTDOOR FAN CONTROL
Following table 3 shows the fan speed of the outdoor unit.
01-17
1. Outdoor Fan Motor
*
It runs at 500rpm for 20 seconds after starting up the outdoor fan.
When the outdoor heat exchanger temperature is lower than 1°C, the fan speed switches to 780rpm on heating mode.
When the outdoor heat exchanger temperature is lower than 2°C, the fan speed switches to 850rpm on heating mode.
( Table 3 : Fan speed of the outdoor unit )
780/ 730/ 400/ 300/ 250/ 200 rpm
780/ 730/ 660/ 400/ 300/ 250/ 200 rpm
Cooling
Heating
AO*G18LAT3
AO*G18/ 24LAT3
AO*G30LAT4
AO*G30LAT4
850/ 820/ 780/ 400/ 300/ 200 rpm
850/ 780/ 400/ 300/ 200 rpm
AO*G24LAT3
6. TIMER OPEARTION CONTROL
1. ON / OFF TIMER
The table 4 shows the available timer setting based on the product model.
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
2. PROGRAM TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time Set time Set time Set time
01-18
6-1 WIRELESS REMOTE CONTROLLER
( Table 4 : Timer setting )
ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER
*WEEKLY TIMER
* For AS*G07/ 09/ 12/ 14LUCA Type
3. SLEEP TIMER
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Stop of operation
Ts
+1°C
+2°C
Set
60min
Set
30min
30min
30min
01-19
Ts
-1
°C
-2°C
-3°C
-4°C
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4deg C, the setting temperature is not changed and the operation stops at the time of timer setting.
4. WEEKLY TIMER (For AS*G07/ 09/ 12/ 14LUCA Type )
This timer function can set operation times of the each day of the week. All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
Setting day Setting day Setting day
ON OFF ON OFF ON OFF
Set time Set time
01-20
6-2 WIRED REMOTE CONTROLLER
The Table 5 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
( Table 5 : Timer setting )
1. ON TIMER / OFF TIMER
Same to 6-1 ON / OFF TIMER and shown in those.
2. WEEKLY TIMER
This timer function can set operation times of the each day of the week. All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
3. TEMPERATURE SET BACK TIMER
This timer function can change setting temperature of setting operation times of the each day of the week. This can be together with other timer setting.
Normal tmp.
ON
OFF
Setting day Setting day Setting day
ON OFF ON OFF ON OFF
Set time Set time
Set back tmp.
Set time Set time
7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the table 6.
Cooling Heating
Min Max Min Max
AO*G18LAT3
20rps 100rps 24rps 110rps
AO*G30LAT4 20rps 90rps 20rps 95rps
(Table 6 : Compressor Operation Frequency Range)
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the figure 16.
(Fig.16 : Compressor Control at Start-up)
01-21
40rps
120sec
120sec
60 - 780sec
180 - 900sec 300 - 1020sec
56rps
85rps
For AO*G18/ 24LAT3
For AO*G30LAT4
The compressor frequency soon after the start-up is controlled as shown in Figure 17. (Fig.17 : Compressor Control at Start-up)
40rps
180sec
120sec
60 - 720sec
240 - 900sec 360 - 1020sec
40rps
56rps
AO*G24LAT3
8. ELECTRONIC EXPANSION VALVE CONTROL
9. TEST OPERATION CONTROL
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
01-22
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table7. The compressor frequency, the temperatures detected by the discharge temperature sensor and the outdoor temperature sensor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (1000 pulses are input to the closing direction).
Under the condition where the air conditioner stops, press the MASTER CONTROL button and the FAN CONTROL button simultaneously for 5 seconds or more, and the test operation control mode will appear. During test running, " " will display on the remote controller display. Set the test operation mode, and the compressor will continue to run regardless of whatever the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wired Remote Controller ( without TEST RUN button )
Under the condition where the air conditioner runs, press the TEST RUN button, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller ( with TEST RUN button )
Cooling /Dry mode
Heating mode
AO*G18/ 24LAT3 AO*G30LAT4
Operation mode Pulse range
50 ~ 480 30 ~ 480
(Table7 : The pulse range of the electronic expansion valve control)
At the time when the air conditioner is switched from the Cooling mode to Heating mode, the compressor is stopped, and the 4-way valve is switched in 3 minutes later after the compressor stopped.
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically resumed with the memorized operation contents.
(Table 8 : Operation contents memorized when the power is interrupted)
Operation mode
Set temperature
Set air flow
Thermistor detected position
11. 4-WAY VALVE EXTENSION SELECT
12. AUTO RESTART
01-23
13. MANUAL AUTO OPERATION
If MANUAL / AUTO Button is pushed continuous from 3 seconds to 10 seconds, manual auto operation will starts. If the remote control is lost or battery power dissipated, this function will work without the remote control.
OPERATION MODE
Auto changeover
Auto
Continuous (No timer setting available)
24°C
(Table 9 : Manual auto operation control)
SETTING TEMP. FAN MODE
TIMER MODE
Timer mode
Wireless remote controller
Wired remote controller (When Memory Backup : Disable)
Wired remote controller (When Memory Backup : Enable)
OFF Timer ON Timer WEEKLY Timer Temperature
: Memorize : Not memorize
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup. Refer to the installation manual of wired remote controller for details.
SWING OPERATION ECONOMY
OFF OFF
VERTICAL LOUVER
NORMAL NORMAL
HORIZONTAL LOUVER
All models
Functions
SET BACK Timer
14. COMPRESSOR PREHEATING
01-24
When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 10) and the heating operation has
been stopped for 3 hours, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to Release temperature or greater, preheating
is over.
(Table 10 : Preheating Operation / Release Temperature)
Before 24 hour After 24 hour
Operation temperature
Operation temperature
Release temperature
Release temperature
3°C 7°C 0°C 4°C
15. POWERFUL OPERATION
The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller. The indoor unit & outdoor unit will operate at maximum power as shown in Table11.
Release Condition is as follows. [Cooling / Dry]
- Room tenperature < Setting temperature - 1.5°C or Operation time has passed 20 minutes.
COMPRESSOR FREQUENCY Maximum FAN CONT. MODE Powerful SETTING LOUVER Cooling/ Dry : 3, Heating : 5
(Table11)
Powerful operation
=
=
[Heating]
- Room tenperature > Setting temperature +1.5°C or Operation time has passed 20 minutes.
16. 10°C HEAT OPERATION
10°C HEAT operation performs as below when pressing 10°C HEAT button or Weekly timer setting on the remote controller.
Mode Heating Setting temperature 10°C Fan mode Auto LED display Economy Defrost operation Operate as normal
(Table 12 : 10°C HEAT operation )
17. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation for cooling and heating. The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating Target temperature Setting temp.+1°C Setting temp.-1°C
(Table 13 )
01-25
The External Electrical Heater is operated as below.
19. EXTERNAL ELECTRICAL HEATER CONTROL (For AR type)
(Fig. 19 : External electrical heater control)
When the room temperature rises
When the room temperature drops
Ts : Setting temperature
Heater : OFF
Heater : ON
Heater : OFF
Ts - 10°C
Ts - 1°C
Ts - 3°C
Ts - 12°C
When all of the following conditions are met, external elecrtical heater will operate according to Figure 19.
1). When one of the ON conditions is not met.
2). When Defrost operation or Oil recovery operation starts
< Heater : ON condition >
< Heater : OFF condition >
System type Operation mode Compressor Indoor fan
Heatpump Heating ON ON (S-Lo is excluded)
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as shown in Figure 18.
18. FRESH AIR CONTROL( For AU / AR type)
(Fig. 18 : Fresh Air control)
Operation Stop
Operation Stop
Fan motor (Indoor unit)
Fan motor (for Fresh Air)
*It needs the external relay and power supply.
01-26
20. DRAIN PUMP OPERATION( For AU / AR type)
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Anti- freezing protection", the drain pump is turned off in 1 hour after the compressor stops.
4. When the water level in the drain pan rises up and then the float switch functions: The compressor, indoor and outdoor fan motor operation are stopped. Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
5. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
(It is necessary to turn off power for release it. )
6. When the float switch turns OFF less than 3 minutes, the unit starts Cooling operation.
1
2
1.When the water level in the drain pan rises up and then the float switch functions: Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates. Thereafter, even if the float switch turns OFF, the "FAILURE INDICATION" is not released. (It is necessary to turn off power for release it. )
1
During Cooling / Dry mode
3 minutes
ON OFF
ON OFF
Compressor
Drain Pump
3 minutes
3 minutes ST
ON OFF
ON OFF
ON OFF
ON OFF
Float Switch
Compressor
Indoor Fan
Drain Pump
3 minutes
ON OFF
ON OFF
Float Switch
Drain Pump
During HEATING / FAN mode / Stop operation
<Float Switch turns OFF less than 3 minutes>
Less than 3 minutes
The indoor unit fan motor operates after the float switch is turned off.
3
( Fig. 20 : Detail of Drain Pump Operation in Cooling / Dry )
( Fig. 21 : Detail of Drain Pump Operation in Heating )
21. DEFROST OPERATION CONTROL
01-27
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 15-1, 15-2.
(Table 15-1 : Defrost release condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 10°C or Compressor operation time has passed 15 minutes.
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 14-1, 14-2, 14-3.
(Table 14-1 : Condition of starting defrost operation)
Less than 6 min. *1
or 10min. *2
*2. Compressor stop time:
Below 20min. Select 6min. Above 20min. Select 10min.
After 6 min. *1
or 10min. *2
Compressor integrating operation :Less than 45min.
Compressor integrating operation :45min and over
-8°C *3
-12°C *4
-14°C *5
-16°C *6
Does not operate
*1. It means contiguous operation time.
1-1 NORMAL DEFROST
(Table 15-2 : Defrost release condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 12°C or Compressor operation time has passed 15 minutes.
(Table 14-2 : Condition of starting defrost operation)
Less than 6 min. *1
or 10min. *2
*3. Outdoor temp. > -1°C *4. Outdoor temp. < -1°C
*2. Compressor stop time:
Below 20min. Select 6min. Above 20min. Select 10min.
After 6 min. *1
or 10min. *2
Compressor integrating operation :Less than 45min.
Compressor integrating operation :45min and over
-10°C *3
-12°C *4
Does not operate
=
*1. It means contiguous operation time.
*3. Outdoor temp. > 3°C *4. Outdoor temp. > -1°C *5. Outdoor temp. > -5°C *6. Outdoor temp. < -5°C
Normal defrost
Normal defrost
Integrating defrost
If the compressor continuous operation time is less than 10 minutes, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
More than 210 minutes (For continuous operation)
Less than 10 minutes ( For intermittent operation )
Compressor integrating operation time
When the compressor is
stopped, If detected
outside air temp. at 2°C
OFF count of the compressor
40 times
( at outside air temp. < 2°C )
1-2. INTEGRATING DEFROST
(Table 14-3 : Condition of starting defrost operation)
For AO*G18/ 24LAT3
For AO*G30LAT4
For AO*G18/ 24LAT3, AOG30LAT4
For AO*G18/ 24LAT3
For AO*G30LAT4
=
01-28
3 sec later Compressor : OFF 3 sec later Outdoor fan motor : OFF 28sec later 4WAY valve : OFF 34sec later Compressor : ON
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.
(Not defrosted for 6 or 10 minutes)
Heating operation start : Compressor ON
Outdoor HEX temp. : Over 10°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Outdoor HEX temp.Below
-8°C
Integrating defrost
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec O FF
Defrost start
Normal defrost
Outside air temp.
> 3°C
Compressor integrating operation: Over 210 min.
Intermittent operation
Compressor OFF count : 40 times (Less than 10min.)
Continuous operation
Outdoor HEX temp.Below
-12°C
Outside air temp.
> -1°C
Outdoor HEX temp.Below
-14°C
Outside air temp.
> -5°C
Outdoor HEX temp.Below
-16°C
Outside air temp.
< -5°C
For AO*G18/ 24LAT3
When the compressor is
stopped, If detected outside air temp. at 2°C
=
01-29
3 sec later Compressor : OFF 3 sec later Outdoor fan motor : OFF 28sec later 4WAY valve : OFF 34sec later Compressor : ON
(Not defrosted for 6 or 10 minutes)
Heating operation start : Compressor ON
Outdoor HEX temp.: Over 12°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Integrating defrost
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec O FF
Defrost start
Normal defrost
Compressor integrating operation: Over 210 min.
When the
compressor is
stopped,
If detected outside
air temp. at 2°C.
Intermittent operation
Compressor OFF count : 40 times (Less than 10min.)
Continuous operation
Outdoor HEX temp.Below
-10°C
Outside air temp.
> -1°C
Outdoor HEX temp.Below
-12°C
Outside air temp.
< -1°C
For AO*G30LAT4
=
22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
When the discharge temperature becomes higher than ,the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until the temperature becomes lower than . When the discharge temperature becomes lower than ,the control of the compressor frequency is released.
When the discharge temperature becomes higher than ,the compressor stops. When the discharge temperature becomes lower than 80°C ,the compressor operates.
2. CURRENT RELEASE CONTROL
01-30
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit value that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
3. ANTI-FREEZING CONTROL (Cooling mode)
When the indoor unit heat exchanger and 2-way valve temperature becomes lower than ,the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until the temperature becomes higher than .
This operation is not released until both the temperature of the indoor unit heat exchanger and 2-way valve temperature exceed the release temperature.
(Table 17 : Anti-freezing Protection Operation / Release Temperature)
AO*G18/ 24LAT3
105°C 95°C 110°C
Tenperrature
AO*G30LAT4
Tenperrature Tenperrature
110°C 100°C 115°C
(Table 16 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
12°C
3°C 2°C 6°C
Temperature Temperature
3°C 2°C 13°C
Outside air Temperature
Indoor Heat Ex. Temperature
2-way valve Temperature
Indoor Heat Ex. Temperature
2-way valve Temperature
12°C
5°C
12°C
=
>
<
01-31
4. COOLING PRESSURE OVER RISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 70.5 3°C) or greater, the compressor is stopped and error display is indicated.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
(Fig 22 : Heating Overload Protection Control)
7. COMPRESSOR TEMPERATURE PROTECTION
Compressor temperature sensor is monitoring the compressor temperature. When the compressor temperature sensor detects higher than Temperature , the compressor is stopped.
6. HIGH PRESSURE PROTECTION
(1) When the pressure switch becomes OFF (Open : higher than 4.2 MPa),
the compressor is stopped. It is released when the pressure switch becomes ON (Close : lower than 3.2 MPa) after 3 minutes of compressor stop.
(2) When the pressure switch is opened for 10 seconds from power on, all of outdoor unit operation is stopped.
The outdoor unit will start up if the pressure switch is returned to ON after 10 seconds has passed.
When 10 minutes (Cooling) or 3 minutes (Heating) has passed from the compressor stop and pressure switch becomes ON, protection is released and the compressor will restart.
110°C
125°C
80°C
+
AO*G30LAT4
Temperature
Temperature
When 3 minutes has passed from the compressor stop and the compressor temperature sensor detects lower than Temperature , protection is released and the compressor will restart.
+
-
AO*G18/ 24LAT3
Indoor heat exchange temperature
63°C
Compressor is OFF
The compressor frequency is decreased 10rps every 20 seconds.
56°C
54°C
A°C
B°C
Outdoor heat exchange tempreture
-9°C
Stable range
Release
=
<
Th
-11°C
=
<
Th
< -9°C
-13°C
=
<
Th
< -11°C
-15°C
=
<
Th
< -13°C
Th
< -15°C
In one operation of the indoor unit : Qu air than
All indoor unit opeate, : Qu air
52°C 52°C 52°C 50°C 48°C
50°C 50°C 48°C 46°C 44°C
48°C
48°C 48°C 48°C 48°C
46°C
46°C 46°C 46°C 46°C
A°C A°CB°C B°C
The compressor frequency is decreased 6rps every 60 seconds.
The compressor frequency is decreased 2rps every 60 seconds.
Release
2 . TROUBLE SHOOTING
R410A
INVERTER (MULTI )
Universal Floor / Celling Slim Duct / Compact Cassette Compact Wall Mounted / Wall Mounted / Floor type
02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
Please refer the flashing pattern as follows. The Operation, Timer, Economy lamps operate as follows according to the error contents.
Manual auto switch error
Indoor room thermistor error
Indoor unit model information error EEPROM access abnormal
Wired remote controller
communication error
Error Contents
Continuous
Continuous
4 times
Continuous2 times
3 times
3 times
5 times
Continuous2 times1 times
Continuous1 times1 times
Trouble shooting
Economy
(Green)
Timer
(Orange)
Operation
(Green)
1 times
Serial communication error
Indoor unit fan motor error
Indoor heat ex. thermistor error
Continuous4 times 2 times
Continuous1 times5 times
Continuous
Continuous4 times
7 times
6 times
1 times
Continuous
7 times 3 times
Continuous
7 times 4 times
Continuous
2 times
7 times
Active filter error
Discharge thermistor error
Heat ex. thermistor error
Outdoor thermistor error
Compressor thermistor error
1,2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
3
0
Continuous
7 times 7 times
Heat sink thermistor error
Continuous8 times 6 times
High pressure switch error
Continuous10 times 3 times
Compressure temp. error
Continuous
Continuous5 times
9 times
9 times
7 times
Compressor control error
Outdoor unit fan motor error
Continuous4 times9 times
Continuous9 times 9 times4-way valve error
Continuous1 times10 times
Discharge temp. error
Over current error
Continuous5 times6 times
IPM error
Indoor Unit Display
Wired Remote
Controller
Display
11
12
22
32
35
41
42
51
53
57
57
58
62
64
65
71
72
73
74
76
76
77
86
94
95
97
99
A1
A3
Indoor unit capacity error
Continuous2 times2 times
Continuous2 times6 times
Outdoor unit model information error
Intake grille error
Continuous7 times 6 times
2-way valve thermistor error
Continuous7 times 6 times
3-way valve thermistor error
Continuous5 times 7 times
Damper (Open/Close) detection limit switch error
Continuous3 times5 times
Drain pump error
Continuous5 times 7 times
Continuous5 times 8 times
Damper (Open/Close) simultaneous detection limit switch error
02-02
When " Er " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authorized service personnel.
2-1-2 WIRED REMOTE CONTROLLER DISPLAY
1. SELF - DIAGNOSIS
SUMOTU WETH FR SA
Unit number (usually 0)
Error code
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more
or there is no key input for 60 seconds to stop the display.
3. Press the SET TEMPERATURE button to select the error history number.
SU MO TU WETH FR SA
Error code
Error history number
01234567 FEdcbA98
ı
ı
Lower
Raise
02-03
0.5sec 0.5sec 2sec
ON
OFF
1. ERROR DISPLAY
2. ERROR DISPLAY METHOD
Outdoor LED Blink (1 to 22 times) 0.5sec ON / 0.5sec OFF blinking
2-1-3 OUTDOOR UNIT DISPLAY
2-way Valve Thermistor Error
(for Indoor unit A)
Serial Communication Error (Outdoor unit to Indoor unit C)
Serial Communication Error (Outdoor unit to Indoor unit D)
Serial Communication Error (Outdoor unit to Indoor unit B)
17
Error Contents
٨ 1 time
٨ 1 time
٨ 1 time
٨ 1 time
٨ 2 times
OFF OFF OFF
OFF OFF
OFFOFF
OFF
OFF
OFF OFF
OFF OFFOFF
OFF
19
٨ 3 times
OFFOFF
OFF
٨ 4 times
OFFOFF
OFF
٨ 5 times
OFFOFF
OFF
٨ 7 times
OFF
OFF
٨ 8 times
OFF
OFF
٨ 9 times
OFF
OFF
٨ 10 times
OFF
OFF
٨ 11 times
OFF
OFF
٨ 12 times
OFF
OFF
٨ 13 times
OFF
OFF
٨ 14 times
OFF
OFF OFF
OFF OFF OFF OFF
OFF OFF
OFF
٨ 15 times
OFFOFF
OFF
٨ 17 times
OFFOFF
OFF
2
Trouble shooting
LED1 LED2 LED3 LED4
Serial Communication Error (Outdoor unit to Indoor unit A)
Indoor Unit Capactiy Error
Outdoor Unit PCB Microcomputer
Communication Error
Outdoor Unit fan motor Error
Over Current Error Compressor Control Error
Compressor Thermistor Error
Heat Sink Thermistor Error High Pressure switch 1 Error High Pressure switch 2 Error
Discharge Thermistor Error
Heat Ex. Thermistor Error
Outdoor Thermistor Error
2-way Valve Thermistor Error
(for Indoor unit B)
2-way Valve Thermistor Error
(for Indoor unit C)
2-way Valve Thermistor Error
(for Indoor unit D)
٨ 5 times
٨ 5 times
٨ 5 times
OFF OFF OFF OFF OFF
OFF
OFF OFF
OFF
3-way Valve Thermistor Error
(for Indoor unit A)
3-way Valve Thermistor Error
(for Indoor unit B)
3-way Valve Thermistor Error
(for Indoor unit C)
3-way Valve Thermistor Error
(for Indoor unit D)
٨ 6 times
OFFOFF
OFF
٨ 6 times
٨ 6 times
٨ 6 times
OFF OFF OFF OFF OFF
OFF
OFF OFF
OFF
IPM Error
Discharge Temp. Error
٨ 18 times
OFFOFF
OFF
Compressor Temp. Error
٨ 19 times
OFFOFF
OFF
4-way Valve Error
٨ 20 times
OFFOFF
OFF
Outdoor Unit PCB Model Information
Error Active Filter Error
٨ 21 times
OFFOFF
OFF
٨ 22 times
OFFOFF
OFF
٨ : Flashing
20
21
22
18 23
24
4
25 26 16
27 14 29
30 28
14 15
Trouble shooting 1 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
Serial communication error (Serial reverse transfer error)
Outdoor unit Main PCB Outdoor unit fan motor
1. Connection failure 2. External cause 3. Main PCB failure 4. Active filter module failure
5. Filter PCB failure 6. Outdoor unit fan motor failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V(AC220V-10%) - 264V(AC240V+10%) appears
at outdoor unit terminal L - N.
When the indoor unit cannot receive the serial signal from Outdoor unit more than 2minutes after power ON, or the indoor unit cannot receive the serial signal more than 15seconds during normal operation.
02-04
2-2 TROUBLE SHOOTING WITH ERROR CODE
OK
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal 1 - 3. >> If it is abnormal, Check the parts as follows.
- Outdoor unit fan motor (PARTS INFORMATION 5)
- Active filter module (PARTS INFORMATION 6)
- Filter PCB (Check the wire of CN34) >> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB. >> If Active filter module or IPM is abnormal, replace it. >> If the parts are normal, replace Main PCB.
1 2
3
RED
WHITE
BLACK
+
-
Trouble shooting 2 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Serial communication error (Serial forward transfer error)
Indoor unit Controller PCB
1. Connection failure 2. External cause 3. Controller PCB failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal 2 - 3. >> If it is abnormal, replace Controller PCB.
When the outdoor unit cannot properly receive the serial signal from indoor unit for 10 seconds or more.
02-05
1 2
3
RED
WHITE
BLACK
+
-
Trouble shooting 3 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Indicate or Display:
Wired remote controller communication error
Indoor unit Controller PCB Wired remote controller (Option)
1. Connection failure 2. Wired remote controller failure 3. Controller PCB failure
Check & correct the followings. Check the connection of terminal between Wired Remote Controller and indoor unit, and check if there is a disconnection of the cable.
When the indoor unit cannot properly receive the signal from Wired Remote Controller for 1 minute or more.
02-06
Refer to error code table.
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Check Voltage at terminal 1-3 of Controller PCB or Communication PCB. (Power supply to Remote control) Cassette, Duct, Universal Floor/Ceiling Type : CN14 Wall mount ,Floor Type : CN6 Compact Wall mount Type : CN305 (UTY-XCBXZ1)
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
All indoor unit
The total capacity of the indoor unit if it is install beyond.
1. The selection of indoor units is incorrect 2. Main PCB (Outdoor unit) failure
Check Point 1 : Check the total capacity of indoor unit
Check the total capacity of the connected indoor units.
>> If abnormal condition is found, correct it by referring to Installation Manual or Design & Technical Manual.
02-07
Trouble shooting 4 INDOOR UNIT Error Method:
Indicate or Display:
Indoor unit capacity error
Refer to error code table.
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB of Outdoor unit.
02-08
Trouble shooting 5 INDOOR UNIT Error Method:
Indicate or Display:
Indoor unit model information error EEPROM access abnormal
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 : Check Indoor unit electric components
YESYES
NO
Indoor unit Controller PCB
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When power is on and there is some below case. When model information of EEPROM is incorrect. When the access to EEPROM failed.
Trouble shooting 6 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Manual auto switch error
Indoor unit Controller PCB Indicator PCB Manual auto switch
When the Manual auto switch becomes ON for consecutive 60 or more seconds.
1. Manual auto switch failure 2. Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual auto switch
Check if Manual auto switch is kept pressed. Check ON/OFF switching operation by using a meter.
>> If Manual auto switch is disabled (on/off switching), replace it.
Check Point 2 : Replace Controller PCB and Indicator PCB
If Check Point 1 do not improve the symptom, replace Controller PCB and Indicator PCB.
02-09
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Room temperature thermistor
Detective details:
Room temperature thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failure
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
OK
Trouble shooting 7 INDOOR UNIT Error Method:
Indicate or Display:
Indoor room thermistor error
Refer to error code table.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Small size Wall mount circuit diagram(Connector connection)
If the voltage does not appear, replace Controller PCB.
H/E (MID) Thermistor
Room Temp. Thermistor
Room Temp. Thermistor
H/E Thermistor
Cassette circuit diagram (Connector connection)
Wall mount Scircuit diagram (Direct soldering to PCB)
Duct circuit diagram (Connector connection)
BLACK BLACK
3 4
CN4
1 2
3 4
1 2
BLACK BLACK
BLACK
BLACK
BLACK BLACK
1 2
1 2
CN3
CN1
121 2 33
RED WHITE
H/E Thermistor
Room Temp. Thermistor
BLACK BLACK
121
2
11 22
11 22
CN5
CN8
GRAY GRAY
1 2
CN7
BLACK BLACK
121
2
121
2
121
2
11 2
1 2
2
CN5
CN8
GRAY GRAY
H/E (MID) Thermistor
Room Temp. Thermistor
02-10
H/E (MID) Thermistor
Room Temp. Thermistor
BLACK BLACK
CN5
CN8
GRAY GRAY
CN7
BLACK BLACK
Universal floor / ceiling circuit diagram (Connector connection) Floor circuit diagram (Connector connection and Direct soldering to PCB)
BLACK BLACK
121
2
1 2
CN3
CN1
GRAY GRAY
H/E (MID) Thermistor
Room Temp. Thermistor
DC
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
6.5
35
8.0
30
10.012.515.820.225.233.6
Resistance Value ( )
2520151050
58.2
-10
44.0
-5
Temperature (°C)
Resistance Value ( )
4.35.3
4540
Temperature (°C)
Detective Actuators:
Indoor unit Controller PCB Heat exchanger (MID) thermistor
Detective details:
Heat exchanger (MID) thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
02-11
Trouble shooting 8 INDOOR UNIT Error Method:
Indicate or Display:
Indoor heat ex. thermistor error
Refer to error code table.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Small size Wall mount circuit diagram(Connector connection)
If the voltage does not appear, replace Controller PCB.
H/E (MID) Thermistor
Room Temp. Thermistor
Room Temp. Thermistor
H/E Thermistor
Cassette circuit diagram (Connector connection)
Wall mount Scircuit diagram (Direct soldering to PCB)
Duct circuit diagram (Connector connection)
BLACK BLACK
3 4
CN4
1 2
3 4
1 2
BLACK BLACK
BLACK
BLACK
BLACK BLACK
1 2
1 2
CN3
CN1
121 2 33
RED WHITE
H/E Thermistor
Room Temp. Thermistor
BLACK BLACK
121
2
11 22
11 22
CN5
CN8
GRAY GRAY
1 2
CN7
BLACK BLACK
121
2
121
2
121
2
11 2
1 2
2
CN5
CN8
GRAY GRAY
H/E (MID) Thermistor
Room Temp. Thermistor
H/E (MID) Thermistor
Room Temp. Thermistor
BLACK BLACK
CN5
CN8
GRAY GRAY
CN7
BLACK BLACK
Universal floor / ceiling circuit diagram (Connector connection) Floor circuit diagram (Connector connection and Direct soldering to PCB)
BLACK BLACK
121
2
1 2
CN3
CN1
GRAY GRAY
H/E (MID) Thermistor
Room Temp. Thermistor
DC
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Resistance Value ( )
Temperature (°C)
Resistance Value ( )
Temperature (°C)
1131.9 579.6 312.3 233.2 176.0 134.2 103.3 80.3 62.9
49.7 39.6 31.7 25.6 20.8 17.1 14.1 11.6 10.4
-30 -20 -10 -5 0 5 10 15 20
25 30 35 40 45 50 55 60 63
02-12
Trouble shooting 9 INDOOR UNIT Error Method:
Indicate or Display:
Indoor unit fan motor error
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
OK
Indoor unit Controller PCB Indoor unit fan motor
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is below 1/3 of target frequency is continued more than 56 seconds.
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Indicate or Display:
Refer to error code table.
Trouble shooting 10 INDOOR UNIT Error Method:
Drain pump error
Detective Actuators:
Indoor unit Controller PCB Float switch
Detective details:
When Float switch is ON for more than 3 minutes.
Check Point 1 : Check Float switch
Check operation of float switch. (any blocking by dust, etc.) Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is abnormal, replace it.
ON OFF
OK
Forecast of Cause :
1. Float switch failure 2. Shorted connector/wire 3. Controller PCB failure
4. Drain pump failure 5. Hose clogging
Check Point 2 : Check Connector (CN 9) / Wire
Check loose contact of CN9 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
Check Point 4 : Check Controller PCB
If Check Point 1 ~ 3 do not improve the symptom, change Controller PCB and execute the check operation again.
Attention!!
Wall mount / Small size wall mount type does not have a float switch. In this case, replace
Controller PCB
and set up the original address. Please refer to.
OK
OK
Check Point 3 : Check Drain hose
Check Drain hose .
>>If there is Hose clogging. Please clear the clog.
02-13
Indicate or Display:
Refer to error code table.
02-14
Detective Actuators:
Detective details:
Forecast of Cause :
Indoor unit Controller PCB Limit switch Damper
When limit switch were not able to detect the close though the damper close. (Upper air flow) When limit switch were not able to detect the open though the damper open. (Upper & Lower air flow)
1. Limit switch failure 2. Shorted connector/ wire 3. Damper faulure
4. Controller PCB failure
Check Point 2 : Check Point 2 : Check Connector (CN18) / Wire
Check Point 1 : Check Limit switch
Check Point 4 : Replace Controller PCB
OKOK
OKOK
Check operation of limit switch. (any blocking by dust, etc.) Remove Limit switch and check ON/OFF switching operation by using a meter.
>>If Limit switch is detective, replace it.
Check loose contact of CN18 /shorted wire (pinched wire).
>>Replace Limit switch if the wire is abnormal
Check Point 2 : Check Point 3 : Check Damper
OKOK
>>Replace Damper if the damper is abnormal
If Check Point 1 3 do not improve the symptom, change Controller PCB.
Check the obstruction of damper movement. Check the damper movement.
Trouble shooting 11 INDOOR UNIT Error Method:
Damper(Open/Close) detection limit switch error
Indicate or Display:
Refer to error code table.
02-15
Detective Actuators:
Detective details:
Forecast of Cause :
Indoor unit Controller PCB Limit switch
When the limit switch detects open and close at the simultaneous.
1. Limit switch failure 2. Shorted connector/ wire 3. Controller PCB failure
Check Point 2 : Check Point 2 : Check Connector (CN18) / Wire
Check Point 1 : Check Limit switch
Check Point 3 : Replace Controller PCB
OKOK
Check operation of limit switch. (any blocking by dust, etc.) Remove Limit switch and check ON/OFF switching operation by using a meter.
>>If Limit switch is detective, replace it.
Check loose contact of CN18 /shorted wire (pinched wire).
>>Replace Limit switch if the wire is abnormal
OKOK
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
Trouble shooting 12 INDOOR UNIT Error Method:
Damper(Open/Close) simultaneous detection limit switch error
02-16
Trouble shooting 13
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Intake grille error
Indoor unit Controller PCB Micro switch
When the Micro switch is detected open while running the compressor.
1. Micro switch failure 2. Shorted connector/ wire 3.Controller PCB failure
Indicate or Display:
Refer to error code table.
Check Point 2 : Check Point 2 : Check Connector (CN11) / Wire
Check Point 1 : Check Limit switch
Check Point 3 : Replace Controller PCB
OKOK
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
>>If Micro switch is detective, replace it.
Check loose contact of CN11 /shorted wire (pinched wire).
>>Replace Micro switch if the wire is abnormal
OKOK
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
02-17
Trouble shooting 14 INDOOR UNIT Error Method:
Indicate or Display:
Outdoor unit model information error
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Main PCB
Check Point 2 : Check Indoor unit electric components
YESYES
NO
Outdoor unit Main PCB
1. External cause 2. Defective connection of electric components 3. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
If Check Point 1,2 do not improve the symptom, replace Main PCB.
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When power is on and there is some below case. When model information of EEPROM is incorrect. When the access to EEPROM failed.
OK
Trouble shooting 15 OUTDOOR UNIT Error Method:
Active filter error
02-18
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
Outdoor unit Main PCB Active filter module
1. External cause 2. Connector connection failure 3. Main PCB failure 4. Active filter module failure
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 4 : Replace Main PCB
If Check Point 1 - 3 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit. Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit. Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Active filter module
Check Active filter module. (PARTS INFORMATION 6)
>>If Active filter module is abnormal, replace it.
When inverter input DC voltage is higher than 425V or lower than 80V. When a momentary power cut off occurred on low voltage
02-19
Trouble shooting 16 OUTDOOR UNIT Error Method:
IPM error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 1 : Replace Main PCB
Outdoor unit Main PCB
1. Main PCB failure
Change Main PCB.
When the signal from FO terminal of IPM in Main PCB is "L"(=0V) while the compressor stops.
Trouble shooting 17 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
Outdoor discharge thermistor error
Outdoor unit Main PCB Discharge pipe temperature thermistor
When the discharge pipe temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-20
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN26 CN23 CN22 CN21
1 21 21 21 2
Refer to error code table.
THERMISTOR
(COMPRESSOR)
BROWN
1 2
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
Temperature(°C)
-30 -20 -10 0 10 20 30 40 50
60 70 80 90 100 110 120
1013.1 531.6 292.9 168.6 100.9 62.5 40.0 26.3 17.8
12.3 8.7 6.3 4.6 3.4 2.6 2.0
Trouble shooting 18 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
Compressor thermistor error
Outdoor unit Main PCB Compressor temperature thermistor
When the compressor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-21
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(COMPRESSOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
BROWN
CN25 CN26 CN23 CN22 CN21
1 21 21 21 21 2
Refer to error code table.
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
Temperature(°C)
-30 -20 -10 0 10 20 30 40 50
60 70 80 90 100 110 120
1013.1 531.6 292.9 168.6 100.9 62.5 40.0 26.3 17.8
12.3 8.7 6.3 4.6 3.4 2.6 2.0
Trouble shooting 19 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
DC
Heat ex. thermistor error
Outdoor unit Main PCB Heat exchanger temperature thermistor
When the heat exchanger temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-22
Refer to error code table.
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN26 CN23 CN22 CN21
1 21 21 21 2
THERMISTOR
(COMPRESSOR)
BROWN
1 2
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
Temperature(°C)
-30 -20 -10 0 10 20 30 40 50
60 70 80
95.6 50.3 27.8 16.1 9.6 6.0 3.8 2.5 1.7
1.2 0.8 0.6
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Trouble shooting 20 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
Outdoor thermistor error
Outdoor unit Main PCB Outdoor temperature thermistor
When the outdoor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-23
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN26 CN23 CN22 CN21
1 21 21 21 2
Refer to error code table.
THERMISTOR
(COMPRESSOR)
BROWN
1 2
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
50
Resistance Value (k )
403020100-30 -20 -10Temperature(°C)
Resistance Value (k )
70 8060Temperature(°C)
224.3 115.2 62.3 35.2 20.7 12.6 8.0 5.2
3.5 2.4 1.6 1.2
Trouble shooting 21
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
2-way valve thermistor error
Outdoor unit Main PCB 2-way valve temperature thermistor
When the 2-way valve temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-24
BLACK RED RED RED RED RED RED RED
GRAY
BROWN
BLACK
BLUE
YELLOW
RED
BLACK WHITE WHITE WHITE WHITE WHITE WHITE WHITE
RED
WHITE
1 2 3 4 5 6 7 8
1
2
3
4
5 6 7 8
1 2 3 4 5 6 7 8
1
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9
1 4
5 6 7 8 9
CN40
CN39
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
VALVE THERMISTOR D (For AOG30LAT4)
2-WAY VALVE C
3-WAY VALVE C
ORANGE
GREEN
2-WAY VALVE D
3-WAY VALVE D
Refer to error code table.
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
40
Resistance Value (k )
3020100-10-30 -20Temperature(°C)
Resistance Value (k )
60
70 80
50
Temperature(°C)
1131.9 579.6 312.3 176.0 103.3 62.9 39.6 25.6
17.1 11.6 8.1 5.8
Trouble shooting 22
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
3-way valve thermistor error
Outdoor unit Main PCB 3-way valve temperature thermistor
When the 3-way valve temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-25
BLACK RED RED RED RED RED RED RED
GRAY
BROWN
BLACK
BLUE
YELLOW
RED
BLACK WHITE WHITE WHITE WHITE WHITE WHITE
WHITE
RED
WHITE
1 2 3 4 5 6 7 8
1
2
3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9
1 4
5 6 7 8 9
CN40
CN39
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
VALVE THERMISTOR D (For AOG30LAT4)
2-WAY VALVE C
3-WAY VALVE C
ORANGE
GREEN
2-WAY VALVE C
3-WAY VALVE C
Refer to error code table.
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
40
Resistance Value (k )
3020100-10-30 -20Temperature(°C)
Resistance Value (k )
60
70 80
50
Temperature(°C)
1131.9 579.6 312.3 176.0 103.3 62.9 39.6 25.6
17.1 11.6 8.1 5.8
Trouble shooting 23
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
Heat sink thermistor error
Outdoor unit Main PCB Heat sink temperature thermistor
When the heat sink temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-26
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN26 CN23 CN22 CN21
1 21 21 21 2
Refer to error code table.
THERMISTOR
(COMPRESSOR)
BROWN
1 2
40
Resistance Value (k )
3020100-10-30 -20Temperature(°C)
Resistance Value (k )
60
70 80 90 100
50
Temperature(°C)
92.3 49.2 27.5 16.1 9.7 6.1 3.9 2.6
1.8 1.2 0.9 0.6 0.5 0.4
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Trouble shooting 24
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Point 2 : Check voltage of Main PCB (DC5.0V)
PRESSURE SWITCH 1
RED RED
CN37
1 2
PRESSURE SWITCH 2
WHITE WHITE
CN36
1 2
Check Point 1 : Reset power supply and operate
Check Point 3 : Check Pressure switch
YESYES
NONO
High pressure switch error
Outdoor unit Main PCB Pressure switch
1. Connector connection failure 2. Pressure switch failure 3. Main PCB failure
When the pressure switch open is detected in 10 seconds after the power is turned on.
Does abnormal LED indication show again?
Make sure circuit diagram of outdoor unit and check terminal voltage at Pressure switch. (DC5.0V)
If the voltage does not appear, replace Main PCB.
Check if connector is loose or cable is open.
>> If no abnormal connection is found,
replace Pressure Switch. After replacing Pressure switch, check operating
condition and pressure in operation.
02-27
Refer to error code table.
OK
PRESSURE SWITCH 1 (CN37)
Pressure switch 1
4.2 0.1MPa
3.2 0.15MPa
Contact : Short Open Contact : Open Short
Characteristics of pressure switch
PRESSURE SWITCH 2 (CN36)
Pressure switch 2
3.7 MPa
2.9 0.2MPa
Contact : Short Open Contact : Open Short
+0
0.2
-
02-28
Trouble shooting 25 OUTDOOR UNIT Error Method:
Indicate or Display:
Over current error
Refer to error code table.
Detective Actuators:
Detective details:
Outdoor unit Main PCB Compressor
When more than normal operating current to IPM in Main PCB flows, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
Check Point 3 : Check Outdoor fan
OK
OK
Check Point 5 : Replace Main PCB
OK
OK
Check Point 1 : Check connections of Outdoor unit electrical components
1. Defective connection of electric components 2. Outdoor fan operation failure
3. Outdoor heat exchanger clogged 4. Compressor failure 5. Main PCB failure
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor fan, Heat exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the fan motor is locked, replace it.
Check Outdoor fan motor. (Refer to Trouble shooting 27)
>> If the fan motor is failure, replace it.
Check Point 4 : Check Compressor
Check Compressor. (PARTS INFORMATION 2)
If Check Point 1 ~ 4 do not improve the symptom, change Main PCB.
Trouble shooting 26 OUTDOOR UNIT Error Method:
Compressor control error
02-29
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 1 : Check connection of around the Compressor components
Check Point 2: Replace Main PCB
Outdoor unit Main PCB Compressor
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1 do not improve the symptom, change Main PCB.
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of phase with actual rotor location more than 90°, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
OKOK
Check Point 3: Replace Compressor
If Check Point 2 do not improve the symptom, change Compressor.
OKOK
Indicate or Display:
Refer to error code table.
02-30
Trouble shooting 27
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Check Outdoor unit fan motor
OK
OK
Outdoor unit fan motor error
Outdoor unit Main PCB Outdoor unit fan motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Outdoor unit fan motor. (PARTS INFORMATION 5) >>If Outdoor Fan Motor is abnormal, replace Outdoor fan motor and Main PCB.
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated 3 times in a row, compressor and fan motor stops. If and repeats 5 times in a row, compressor and fan motor stops permanently.
Read wire DC voltage Red - Black
White - Black
15 1.5V
CN800
1 2 3 4 5 6 7
BLACK WHITE YELLOW BROWN
RED
FM
FAN MOTOR
Check Point 2 : Check ambient temp. around motor
OK
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Indicate or Display:
Refer to error code table.
280V (AC220V-10%) ~ 373V (AC240+10%)
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Main PCB failure 6. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
02-31
[ Solenoid coil ] Remove CN30 from PCB and check the resistance value of coil. Resistance value is about 1.4k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ] Check each piping temperature, and the location of the valve by the temperature difference. >> If the value location is not proper, replace 4-way valve.
Check Point 5 : Replace Controller PCB
If Check Point 1- 4 do not improve the symptom, replace Controller PCB of Indoor unit .
Check Point 2 : Check thermistor of Indoor unit
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor, (Refer to Trouble shooting 7,8), If defective, replace the thermistor.
Indoor unit Controller PCB Heat exchanger temperature thermistor Room temperature thermistor 4-way valve
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops. Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 10
°C
Heating operation [indoor heat exchanger temp.] - [Room temp.] < -10
°C
If the same operation is repeated 5 times, the compressor stops permanently.
Trouble shooting 28 OUTDOOR UNIT Error Method:
4-way valve error
Indicate or Display:
Refer to error code table.
Check Point 4 : Check the voltage of 4-way valve
Check the CN 30 voltage of Main PCB
Check if AC198V(AC220V-10%) - 264V(AC240V+10%) appears at CN 30 of Main PCB.
[ Heating operation ]
>> If it is not voltage, Replace Main PCB.
[ Cooling operation ]
>> If it is voltage, Replace Main PCB.
OKOK
OKOK
OKOK
<Cooling operation>
OK
OK
OK
OK
OK
<Heating operation>
Outdoor unit Main PCB Discharge temperature thermistor
"Protection stop by "discharge temperature 110°C (18,24type) / 115°C (30type) during compressor operation"" generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check. (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 17".
Check Point 4 : Check the discharge thermistor
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger Check if fan can be rotated by hand. Motor check (PARTS INFORMATION 5)
Check Point 5 : Check the refrigerant amount
Leak check
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
02-32
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 29 OUTDOOR UNIT Error Method:
Discharge temp. error
Indicate or Display:
Refer to error code table.
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 2 : Check the EEV, strainer
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 2 : Check the EEV, strainer
<Cooling operation>
OK
OK
OK
OK
OK
<Heating operation>
Compressor temperature thermistor
"Protection stop by "compressor temperature 110°C (18,24type)/ 125°C (30type) during compressor operation"" generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 17".
Check Point 4 : Check the discharge thermistor
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger Check if fan can be rotated by hand. Motor check (PARTS INFORMATION 5)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
02-33
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 30 OUTDOOR UNIT Error Method:
Compressor temp. error
Indicate or Display:
Refer to error code table.
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Compressor temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
Trouble shooting 31
Forecast of Cause:
OKOK
Indoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical components defective
Check Point 1 : Check Installation condition
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical manual.
02-34
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Check Point 3 : Check Electrical components
YESYES
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
Check Varistor in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
OK
Check Fuse of between of Terminal and Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB is loose, and replace Fuse.
Check Point 4 : Replace Filter PCB
If Check Point 1- 3 do not improve the symptom, replace Filter PCB.
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit. Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Trouble shooting 32
Forecast of Cause:
Check Point 3 : Check Electrical components
OKOK
OKOK
YESYES
YESYES
OK
Check Point 1 : Check Installation Condition
Outdoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical components defective
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit. Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
Check Active filter module. (PARTS INFORMATION 6)
>> If Active filter module is abnormal, replace it.
02-35
Check Point 4 : Replace Main PCB
If Check Point 1- 3 do not improve the symptom, replace Main PCB.
Trouble shooting 33
Forecast of Cause:
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check Wired Remote Controller and Controller PCB
OK
OK
OKOK
No Operation (Power is ON)
1. Setting/ Connection failure 2. External cause
3. Electrical Component defective
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection. Are these Indoor unit, Outdoor unit, and Remote control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and Data & Technical manual.
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor unit and Outdoor unit?
Instant drop ----- Check if there is a large load electric apparatus in the same circuit. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit. Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Check Indoor unit fan motor. (PARTS INFORMATION 4) If it is normal, replace Controller PCB. If it is abnormal, replace Indoor unit fan motor and Controller PCB.
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
02-36
Check Voltage at terminal 1-3 of Controller PCB or Communication PCB. (Power supply to Remote Control) Cassette, Duct, Universal Floor/Ceiling Type : CN14 Wall mount, Floor Type : CN6 Conpact Wall mount Type : CN305 (UTY-XCBXZ1)
Attention
Trouble shooting 34
Forecast of Cause:
Check Point 2 : Check Outdoor unit operation
Check Point 1 : Check Indoor unit
Check Point 3 : Check Site condition
Check Point 5 : Check Refrigeration cycle
Check Point 4 : Check Indoor/ Outdoor installation condition
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
OKOK
OKOK
OKOK
OKOK
MPa MPa
No Cooling / No Heating
1. Indoor unit error 2. Outdoor unit error
3. Effect by Surrounding environment
4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure
Does indoor unit fan run on high fan?
Is air filter dirty?
Is heat exchanger clogged? Check if energy save function is operated.
Check if outdoor unit is operating Check any objects that obstruct the air flow route. Check clogged Heat exchanger. Is the valve open?
Is capacity of Indoor unit fitted to room size?
Any windows open? Or direct sunlight ?
Check connection pipe (specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical manual.
Check if strainer is clogged (Refer to the figure at right).
Measure gas pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3)
Check Compressor (PARTS INFORMATION 1,2)
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-37
Trouble shooting 35
Forecast of Cause :
Trouble shooting 36
Forecast of Cause:
OK
OK
OK
OK
OKOK
OKOK
OKOK
MPa MPa
Abnormal noise
1. Abnormal installation (Indoor/ Outdoor)
2. Fan failure (Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal noise is occurred
Abnormal noise is coming from Indoor unit. (Check and correct followings)
Abnormal noise is coming from outdoor unit. (Check and correct followings)
Is fan broken or deformed? Is the screw of fan loose? Is there any object which obstruct the fan rotation?
Is Main unit installed in stable condition? Is the installation of air suction grille and front panel normal?
Is fan broken or deformed? Is the screw of Fan loose?
Is there any object which obstruct the fan rotation?
Is Main unit installed in stable condition? Is fan guard installed normally?
Check if vibration noise by loose bolt or contact noise of piping is happening.
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
Water leaking
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water is spitting out.
Is the filter clogged?
Check gas pressure and correct it if there was a gas leak.
Diagnosis method when water leak occurs
Is Drain hose connection loose?
Is there a trap in drain hose?
Is drain hose clogged?
Is Main unit installed in stable condition?
Is Main unit broken or deformed at the time of
transportation or maintenance?
Is fan rotating?
02-38
SERVICE PARTS INFORMATION 1
MPa MPa
Compressor
Diagnosis method of Compressor ( If outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check Filter PCB, Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
Check Filter PCB, Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is gas pipe valve open? (Low pressure is too low)
Check if refrigerant is leaking. (Recharge refrigerant)
Check if strainer is clogged. (PARTS INFORMATION 3)
>> If there is no failure, the defect of Compressor can be considered. (Compressor part broken or valve defective.)
Abnormal noise
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Check if vibration noise by loose bolt or contact noise of piping is happening.
02-39
2-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 2
Check Point 1 : Check Connection
Check Point 2 : Check Winding Resistance
Check Point 3 : Replace Main PCB
U(R)
V(S)
W (T)
Inverter Compressor
Check terminal connection of Compressor (loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If the symptom does not change with above Check 1, 2, replace Main PCB.
02-40
U(R)
(RED)
V(S)
(WHITE)
W (T)
(BLACK)
Main PCB
Resistance Value : 0.97 at 20°C
Resistance Value : 0.88 at 20°C
For AO*G18/ 24LAT3
For AO*G30LAT4
SERVICE PARTS INFORMATION 3
Check Point 1 : Check Connections
Outdoor unit Electronic Expansion Valve ( EEV )
Check connection of connector
( Loose connector or open cable )
02-41
EXPANSION VALVE COIL A
EXPANSION VALVE COIL B
EXPANSION VALVE COIL C
CN27
CN50
CN51
RED
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
BLACK WHITE WHITE WHITE
WHITE WHITE
BROWN BLUE ORANGE
YELLOW
WHITE
WHITE
GREEN
BLACK
GREEN GREEN GREEN GREEN
RED BROWN BLUE ORANGE
YELLOW
WHITE
GREEN
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1
2 3 4 5 6
1 2 3 4 5 6
2
1
1 3
4 5 6 7
4 5
6 7
E V
E V
E V
For AO*G18/ 24LAT3
EXPANSION VALVE COIL A
EXPANSION VALVE COIL B
EXPANSION VALVE COIL C
EXPANSION VALVE COIL D
CN27
CN50
CN51
RED
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
BLACK WHITE WHITE WHITE WHITE WHITE
BROWN BLUE ORANGE YELLOW WHITE
WHITE
GREEN
BLACK
GREEN GREEN GREEN GREEN
RED BROWN BLUE ORANGE YELLOW WHITE
GREEN
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1
2 3 4 5 6
2
1
1
3
4
5
6 7
4
5
6
7
E V
E V
E V
CN52
BLUE BLUE BLUE BLUE BLUE
BLACK
RED BROWN BLUE ORANGE YELLOW WHITE
GREEN
1 2 3 4 5 6
1 2 3 4 5 6
1
3
4
5
6
7
E V
For AO*G30LAT4
Check Point 5 : Check Opening and Closing operation of valve
Pipe (In)
Pipe (Out)
Pipe (In)
CLOSE Example : Hot gas
OPEN Example : Hot gas
Pipe (Out)
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
Check Point 6 : Check strainer
When Valve is closed, it has a temp. difference between Inlet and Outlet.
If it is open, it has no temp. difference between Inlet and Outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-42
Check Point 2 : Check Coil of EEV
Yellow - Brown Orange - Red Blue - Brown
White - Red
Read wire
46
4
Resistance value
Check Point 3 : Check voltage from Main PCB.
Check Point 4 : Check noise at start up
DC
at 20°C
Remove connector, check each winding resistance of Coil.
If resistance value is abnormal, replace EEV.
Remove connector and check voltage (DC12V)
If it does not appear, replace Main PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
SERVICE PARTS INFORMATION 5
Check Point 1 : Check rotation of fan
Outdoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of outdoor fan motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Red) 2 3 4 (Black) 5 (White) 6 (Yellow) 7 (Brown)
DC voltage (Vm) No function No function Ground terminal (GND) Control voltage (Vcc) Speed command (Vsp) Feed back (FG)
SERVICE PARTS INFORMATION 4
Check Point 1 : Check rotation of fan
Indoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If fan or bearing is abnormal, replace it.
Check Point 2 : Check resistance of indoor fan motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Blue) 2 (Yellow) 3 (White) 4 (Black) 5 6 (Red)
Feed back (FG) Speed command (Vsp) Control voltage (Vcc) Ground terminal (GND) No function DC voltage (Vm)
02-43
Pin number (wire color)
Terminal function (symbol)
1 (Brown) 2 (Yellow) 3 (White) 4 (Black) 5 6 (Red)
Feed back (FG) Speed command (Vsp) Control voltage (Vcc) Ground terminal (GND) No function DC voltage (Vm)
For Cassette, Duct, Universal Floor/Ceiling TypeFor Wall Mount, Conpact Wall Mount,Floor Type
SERVICE PARTS INFORMATION 6
Active filter module
02-44
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Check Point 2 : Check the Output DC voltage (between P and N)
L2L1
P
N
+IN
Check the output DC voltage (between P and N) of compressor stopping and operating.
If it is abnormal,replace Active filter module.
Remove connector, check the open or short-circuit and the diode in the module
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping, Active filter module is detective. >> Replace Active filter module.
Terminal
Resistance value
L2
L1
L1,L2
P
P
Control box
N
N
(+IN)
(+IN)
( IN)
( IN)
Tester(+) Tester(-)
Check the open or short-circuit
L2
P
P
N
L2
L2
Check the diode
0
360k
720k
1.69M /
20%
+
-
20%
+
-
360k
20%
+
-
(Ref. value 1)
1.88M
(Ref. value 2)
1.40M /
(Ref. value 1)
2.28M
(Ref. value 2)
Terminal
Resistance value
Tester(+) Tester(-)
1.32M /
(Ref. value 1)
1.50M
(Ref. value 2)
1.40M /
(Ref. value 1)
1.51M
(Ref. value 2)
Ref. value 1 Specifications for Multimeter Manufacturer : HIOKI Model name : 3804 Power source : DC9V.
Ref. value 2 Specifications for Multimeter Manufacturer : YOKOGAWA Model name : 7534 Power source : DC3V.
-IN
By kind of tester, the value may change significantly.
3 . REPLACEMENT PARTS
R410A
INVERTER (MULTI )
Universal Floor / Celling Slim Duct / Compact Cassette Compact Wall Mounted / Wall Mounted / Floor type
ACTPM
Compressor
4-way valve
3-1 AO*G18/ 24LAT3
3-1-1 PARTS LAYOUT DRAWING
03-01
Motor DC Brushless
Propeller Fan assy
Condenser A assy
Coil (Expansion valve)& Expansion valve
Solenoid
Pressure SW
Choke Coil
Accumulator
Main PCB
Filter PCB
Thermistor (Heat exchanger temp.)
2-way valve assy (Liquid)
3-way valve assy (Gas)
03-02
Thermo Holder& Thermistor (Outdoor Temp.)
1. Service Panel sub assy removal
Remove the 2 mounting screws. Remove the Service Panel sub assy by sliding downward.
2. Top Panel sub assy removal
Remove the 7 mounting screws. Remove the Top Panel sub assy upward.
FRONT VIEW REAR VIEW
3-1-2 DISASSEMBLY PROCESS (AO*G18/ 24LAT3)
03-03
Replaceable Component
Compressor Accumulator 4-way valve Solenoid Thermistor (Compressor temp.) Thermistor (Discharge temp.) Thermistor (Outdoor temp.) Thermistor (Heat exchanger temp.) Thermistor (2/3-way valve temp.) Pressure SW Coil (Expansion valve)
Hook (3 places)
Service Panel sub assy
Top Panel sub assy
3. Inverter Box removal
Remove the 6 mounting screws. Remove the power supply & connection cord. Remove the connectors connected to Main PCB. (Thermistor, EEV, and so on) Remove the Inverter Box upward.
03-04
Inverter Box
REAR VIEW
FRONT VIEW
03-05
Remove the 1 mounting screw. Remove the Inverter Box Cover upward.
Hook (2 places)
Inverter Box Cover
4. Inverter Box Cover removal
5. Main PCB removal
03-06
A
D
B
C
Remove the 4 mounting screws. (Refer to VIEW -A) Remove the wires from terminal. (Refer to VIEW -B) Remove the wires. (Refer to VIEW -C, -D) Remove the Main PCB.
Hook
Screw
Screw
(IPM)
Screw
(Diode Bridge)
VIEW - A
VIEW - B
Red Yellow Pink
Main PCB
03-07
VIEW - C
VIEW - D
CN34(Yellow)
TM101(Black) TM102(White)
CN1(White)
Main PCB
Filter PCB
03-08
VIEW - E
Spread the heat dissipation compound on the other side of IPM and Diode Bridge, when you exchange Main PCB by the repair.
IPM
Diode Bridge
E
Precautions for exchange of Main PCB
6. Filter PCB removal
03-09
Remove the 2 mounting screws. (Refer to VIEW -A) Remove the wires from terminal and fuse holder. (Refer to VIEW -B) Remove the Filter PCB.
Hook
Screw
VIEW - A
VIEW - B
White
Black
Black
Black
Filter PCB
A
B
7. ACTPM removal
03-10
Remove the connectors and cords. (Refer to VIEW -F) Remove the 2 mounting screws. (Refer to VIEW -F) Remove the ACTPM (Active Filter Module).
VIEW - F
CN407
" P " (Yellow)
" N1 " (Blue)
" - " (Black)
" + " (Red)
" L1 " (White)
Twist 4 times or more 2 turn the Wire this way
" L2 " (Brown)
Thermistor (Heat sink)
Screw
Spread the heat dissipation compound on the other side of ACTPM, when you exchange ACTPM by the repair.
F
8. Valve Cover sub assy removal
Remove the 3 mounting screws. Remove the Valve Cover sub assy.
9. Thermo Holder removal
Remove the 1 mounting screw. Remove the Thermo Holder by sliding upward.
03-11
Valve Cover sub assy
Thermo Holder
Hook
10. Right Panel sub assy removal
Remove the 13 mounting screws.
Remove the Right Panel sub assy by sliding upward.
03-12
Right Panel sub assy
Hook
3-2 AO*G30LAT4
3-2-1 PARTS LAYOUT DRAWING
03-13
Main PCB
Filter PCB
Active Filter Module
Thermistor (Heat sink)
Fan motor
Fan
Heat Exchanger
Accumulator
Compressor
4-way valve
Solenoid
Thermistor (Compressor temp.)
Coil(Expansion valve)& Expansion valve
Choke coil
Receiver tank
03-14
Thermistor (Heat exchanger temp.)
Pressure SW
2-way valve (Liquid)
3-way valve (Gas)
Thermo Holder& Thermistor (Outdoor Temp.)
1. Service Panel sub assy removal
2. Top Panel sub assy removal
3-2-2 DISASSEMBLY PROCESS (AO*G30LAT4)
03-15
Remove the 2 mounting screws. Remove the SERVICE PANEL by sliding downward.
Replaceable Component
Compressor Accumulator 4-way valve Solenoid Thermistor (Compressor temp.) Thermistor (Discharge temp.) Thermistor (Outdoor temp.) Thermistor (Heat exchanger temp.) Thermistor (2/3-way valve temp.) Pressure SW Coil (Expansion valve)
Hook (3 places)
Remove the 7 mounting screws. Remove the TOP PANEL upward.
FRONT VIEW REAR VIEW
3. Inverter Box removal
Remove the 6 mounting screws. Remove the power supply & connection cord. Remove the connectors connected to Main PCB. (Thermistor, EEV, and so on) Remove the Inverter Box upward.
03-16
REAR VIEW
FRONT VIEW
INVERTER BOX
03-17
Remove the 1 mounting screw. Remove the Inverter Box Cover upward.
4. Inverter Box Cover removal
Hook (2 places)
Inverter Box Cover
Loading...