A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5°C lower than a set temperature, the compressor
will be stopped.
* When the room temperature is between +2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
( Table 1 : Compressor Frequency Range )
minimum
frequency
maximum
frequency
AO* A72LALT
AO* A90LALT
28rps77rps
28rps86rps
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
When the room
temperature rises
Outdoor air
temperature
34°C
30°C
19°C
10°C
0°C
When the room
temperature drops
A zone
B zone
C zone
D zone
E zone
F zone
36°C
32°C
21°C
12°C
2°C
Fan speed mode
AO* A72LALT
AO* A90LALT
A zone
B zone
C zone
D-F zone
A zone
B zone
C zone
D-F zone
HiMeLo
77rps
77rps
60rps
51rps
86rps
86rps
77rps
66rps
56rps
56rps
51rps
48rps
71rps
71rps
66rps
56rps
51rps
51rps
48rps
48rps
66rps
66rps
56rps
53rps
01-01
1-2. HEATING OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower 3°C than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperature, the compressor
will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Fig. 2 based on
the outdoor temperature.
( Table 2 : Compressor Frequency Range )
minimum
frequency
maximum
frequency
AO* A72LALT
AO* A90LALT
30rps85rps
30rps100rps
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air
temperature
19°C
14°C
C zone
B zone
A zone
17°C
12°C
AO* A72LALT
AO* A90LALT
Fan speed mode
A zone
B zone
C zone
A zone
B zone
C zone
HiMeLo
90rps79rps70rps
100rps90rps79rps
01-02
1-3. DRY OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-3-1 INDOOR UNIT CONTROL
The compressor rotation speed shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Fig 3.
( Table 3 : Compressor Rotational Speed Range )
AO* A72LALT
AO* A90LALT
X zone
Y zone
X zone
Y zone
42rps
0
47rps
0
( Fig.3 : Compressor Control based on Room Temperature )
Room
temperature drops
Ts+0.5 °C
X zone
Compressor : ON
Ts+1.5 °C
Y zone
Compressor : OFF
Room
temperature rises
( Fig 4 : Indoor Fan Control )
ON
Compressor
OFF
Ts : Setting temperature
Indoor fan
DRY air flow
S-Lo
OFF
103060360120360120 1030
(sec)
01-03
1-4. AUTO CHANGEOVER OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING and MONITORING modes. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1 °C steps.
(1) When operation starts, only the indoor fan is operated for 2 minute. (Air flow mode: S-Lo)
After 2 minute, depends on the room temperature and outdoor unit's operation mode,
the operation mode is selected in accordance with the below. (During 3 minutes ST, Air flow mode : S-Lo)
( Fig 5 : Operation mode selection based on Outdoor Temperature )
C zone
Outdoor
temperature
( Table 4 : Operation mode selection table )
Room temperature :Tr
32°C
B zone
-10°C
A zone
Outdoor temperature zone
A zone
B zone
C zone
Tr > Ts +2 °C
Ts +2 °C > Tr > Ts -2 °C
Ts -2 °C > Tr
Ts : Setting temperatureTr : Room temperature
(2) When COOLING or HEATING was selected at (1), the air conditioner operates
in the room temperature correct coefficient value is 0°C.
(3) When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at (1) above,
operation is switched to MONITORING and the operation mode is selected again.
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig.6.
On the other hand, if switched in [Hi] ~ [Lo], the indoor motor will run at a constant airflow of [COOL]
operation modes Lo, Med, Hi, as shown in Table 5.
( Fig.6 : Airflow change - over ( COOLING : Auto ) )
Tr : Room temperature
Ts : Setting temperature
Tr-Ts > 2 °C
=
2 °C > Tr-Ts
When the room
temperature drops
Me
Lo
Tr-Ts > 2.5 °C
=
2.5 °C > Tr-Ts
When the room
temperature rises
4. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig.7.
On the other hand, if switched in [Hi] ~ [Lo], the indoor motor will run at a constant airflow
of [HEAT] operation modes Lo, Me, Hi, as shown in Table 5.
( Fig.7 : Airflow change - over ( HEATING : Auto ) )
Tr-Ts > - 2 °C
=
- 2 °C> Tr-Ts
When the room
temperature rises
Lo
Me
When the room
temperature drops
Tr-Ts > - 2.5 °C
=
- 2.5 °C> Tr-Ts
Tr: Room temperature
Ts : Setting temperature
5. COOL AIR PREVENTION CONTROL (HEATING mode)
Indoor fan motor operates in set fan mode when the indoor unit heat-exchanger temperature
becomes more than 27°C, and it operates until the compressor stops with a set mode maintained.
(The fan stops until the indoor unit heat-exchanger temperature reaches 27°C)
Pattern 1
.
When the Heating operation starts.
.
When thermo-OFF and fan stops after defrosting.
Indoor heat exchanger
temperature
Setting fan
mode
27°C
S-Lo
24°C
Stop
.
During thermo-OFF
Indoor heat exchanger
temperature
27°C
Pattern 2
Setting fan
mode
S-Lo
6. DRY OPERATION
Refer to the Fig.4 and Table 5.
During the DRY mode operation, the fan speed setting can not be changed.
01-06
1-6. OUTDOOR FAN CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1. Outdoor Fan Motor
.
The outdoor fan speed is decided depending on the operation mode and the outdoor temperature.
.
The compressor and the fan start-up at the same time,
and the fan stops after the compressor stops and 60 seconds has passed.
.
The fan doesn't operates for 5 seconds after the fan stops.
.
The fan operates at 500 rpm for 20 seconds after the start-up.
However, the fan operates at 300rpm for 20 seconds when the initial rotational speed is 300rpm or less.
Following table shows the fan speed of the outdoor unit.
When switched from normal fan step to intermittent fan step, always start from 300rpm /7sec.
When there was a change during intermittent step 1-6, switching is performed
at the time the current speed duration time reaches time-up.
Intermitten fan step
7 sec7 sec7 sec
[ T ] sec[ T ] sec
Time
01-07
1-7. COMPRESSOR CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1. OPERATION SPEED RANGE
The operation speed of the compressor is different based on the operation mode as
shown in Table 7.
(Table 7 : Compressor Operation Speed Range)
AO* A72LALT
AO* A90LALT
COOLING
Min
28rps
28rps
Max
77rps
86rps
Min
30rps
30rps
HEATING
Max
85rps
100rps
42rps
47rps
2. OPERATION SPEED CONTROL AT START UP (Common in all models)
The compressor speed soon after the start-up is controlled as shown in Fig.9.
(Fig.9 : Compressor Control at Start-up)
< Normal start-up >
Compressor
Upper Limit
Speed[ rps ]
65
55
43
33
60
180240
300
Time [ sec ]
DRY
< Cold start : Heating mode >
The compressor start-up by Cold start when corresponding to any of the following condition.
(1) First start-up after power-on
(2) Compressor temperature < 31°C
(3) 8 hours has passed after the compressor stop
Compressor
Upper Limit
Speed[ rps ]
65
55
43
33
60
150210
120
Time [ sec ]
01-08
1-8. TIMER OPERATION CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-9. TIMER OPERATION CONTROL1-9. TIMER OPERATION CONTROL
1-8-1 Wired Remote Controller
AR-WAE1E
ON / TIMER
OFF / TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Use this timer function to set operating time for each day of the week.
The weekly timer allows up to two ON and OFF time to set up per day.
Operation mode
Stop mode
Set time
The operating time can be set in 30 min increments only.
The OFF time can be carried over to next day.
The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
Operation mode
Stop mode
Set timeSet timeSet time
Operation mode
Stop mode
01-09
2-2. DAY OFF setting
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The DAY OFF setting is only available for days for which weekly settings already exist.
If the operating time carries over to the next day (during a next day setting), the effective
DAY OFF range will be set as shown below.
Normal
DAY OFF
Operation mode
Operation mode
Stop mode
Stop mode
Preceding dayNext day
Setting day
Stop mode
Next day setting
DAY OFF
Stop mode
Operation mode
Stop mode
Preceding dayNext daySetting day
Operation mode
Stop mode
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically
after the set day has passed.
3. TEMPERATURE SET BACK TIMER
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop
air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting
can be used.
During COOLING/DRY mode, the air conditioner will operate at a minimum of 18°C even if
the SET BACK temperature is set to 17°C or lower.
Case of SET BACK timer on the Cooling operation.
( Setting temperature :22°C, SET BACK temperature :26°C)
( Fig.10 : Detail of set back timer)
SET BACK setting
Operation
temperature
*1
Operation
temperature
*1: During the SET BACK function,
the setting temperature is changed.
26°C
22°C
26°C
24°C
22°C
ONOFFOFFON
Chenge the setting temperature:
22°C 24°C
01-10
1-9. ELECTRONIC EXPANSION VALVE CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor speed, the temperatures detected by the discharge temperature sensor, the
indoor heat exchanger sensor
(1) Pulse range of EEV
, the outdoor heat exchanger sensor
, and the outdoor temperature sensor.
Pulse range
70 ~ 500 pulse
60 ~ 500 pulse
All Models
Operation
COOLING / DRY
HEATING
(2) The EEV is set up at 500 pulses when the compressor is stopped.
(3) Initialization (Input of 528 pulses toward closing direction) is operated under
the following condition.
* When the power is turned on.
* 4 hours has passed since the last initialization, and 3 minutes has passed after
the compressor stop.
(If 12 hours has passed since the last initialization, the compressor is compulsorily stopped.)
1-10 PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 3 minutes after the compressor is stopped,
even if any operation is given.
1-11. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
(Table 8 : Operation contents memorized when the power is interrupted)
Wired remote controller
(When Memory Backup : Disable)
Operation mode
Set temperature
Set air flow
Thermistor detected position
Timer mode
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller,
to enable the memory backup.
Refer to the installation manual of wired remote controller for details.
At the time when the air conditioner is switched from the Cooling mode to Heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.
1-13. TEST OPERATION CONTROL
With Wired Remote Controller
Under the condition where the air conditioner stops, press the MASTER CONTROL button and
the FAN CONTROL button simultaneously for 2 seconds or more, and the test operation control
mode will appear.
During test running, " " will display on the remote controller display.
Set the test operation mode, and the compressor will continue to run regardless of whatever
the room temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Outdoor Unit
(1) Turn on the power of the outdoor unit and enter
standby mode. POWER/MODE Lamp lights up.
(ERROR lamp is off.)
(2) Press the MODE/EXIT button (SW107) once.
LED105 LED104LED105 LED104
POWER/MODE
Lamp (LED101)
MODE/EXIT
button (SW107)
SELECT button
(SW108)
ENTER button (SW109)
POWER
MODE
LED101
(GREEN)
LED105 LED104
MODE
SELECT
/EXIT
SW108
SW107
ERROR
LED102
(RED)
PUMP
ENTER
DOWN
SW109 SW102
ERROR Lamp (LED102)
7 Segment LED Lamp
(LED105 and 104)
DIP switch
(Do not operate)
SW101
PUMP DOWN button (SW102)
(Do not operate in this chapter)
(3) Press the SELECT button (SW108), and display "F3" on the LED104.
(The display of the LED104 changes each time the SELECT button is pressed.)
*1: The "F1" and "F9" modes are used for maintenance, so do not set them in regular operation.
(Function mode)
(4) When "F3" appears on the LED104, press the ENTER button (SW109).
LED105 LED104LED105 LED104
A flashing display appears on the LED105, and the flashing display of • gF3• h on the LED104 go out.
01-12
(5) Press the SELECT button (SW108), and display the code number of the mode you want to get on the LED105.
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Cooling test operationHeating test operationTest operation stop
LED105 LED104LED105 LED104LED105 LED104
*2*2*2
*2: Numbers other than 00-02 are used during maintenance. Please do not use during normal operation.
(6) After confirming the operation mode you want to set, press ENTER button (SW109) for more than 3 seconds.
Ex.) To select the cooling test operation setting.
LED105 LED104LED105 LED104
Once "done" has displayed, operation will start after a few minutes. With this, setting is complete.
After operation has started, verify according to "9.3. Checklist" provided below.
If you want to stop during test operation, set to test operation stop described in (5) above and execute.
(7) After the completion of test operation, turn off the power, attach electrical components cover
and install front panel of outdoor unit.
Note
Test run will finish after about 60 minutes automatically.•
Test run may be stopped before operating for 60 minutes if an error occurs after a starting test run.•
Switching between heating and cooling is not possible during test operation.
•
If you want to change the operation mode, stop the test operation,
and change the operation mode once again with mode selection of step (5).
If switching between heating and cooling is done during test operation,
display as per the right figure will appear and settings will not change.
* After 5 seconds since the display of right figure, you can return to screen of step (5)
by holding the "Enter" switch.
LED105LED104
01-13
1-14. PUMP DOWN
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Confirm that the power is off, and the than (1)
open the service panel.
Turn the power on.(2)
Check that stop valves of liquid side and gas (3)
side are fully and properly open.
Hold PUMP DOWN button (SW102) for over 3 seconds.(4)
7 Segment LED of board on outdoor unit will fl ash, and
compressor will start the operation.
LED105
LED104
Fan of indoor unit will start the operation automatically.•
POWER/MODE
lamp
MODE/EXIT
button
(Do not operate
in this chapter.)
SELECT button
(Do not operate
in this chapter.)
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
MODE
/EXIT
SW107
SELECT
SW108
PUMP
ENTER
DOWN
SW109 SW102
SW101
PUMP DOWN button
ENTER button
(Do not operate in this chapter.)
Compressor and outdoor fan will start the operation automatically.•
It you want to stop pump down operation once it has started, hold •
PUMP DOWN button (SW102) again for over 3 seconds.
LED display of outdoor unit board will light-up with the display of “rUn” after around 5 minutes of the start of (5)
compressor operation. At this time, firmly close the three-way valve of liquid side immediately.
If the valve on liquid side is not closed at this stage, •
pump down will not be possible.
LED105
LED104
Step (5)
Step (6)
Closing direction
Closing direction
LED display of outdoor unit board will change as (6)
shown in the right fig ure after around 2-7 minutes
of the start of compress or operation. At this time,
fir mly close the three-way valve of gas side immediately.
LED105
LED104
Hexagon wrench
Liquid pipe
ERROR lamp
7 Segment
LED Lamp
DIP switch
(Do not operate.)
Gas pipe
If the valve on gas side is not closed at this stage, refrigerant
•
may runoff through pipes after the compressor is stopped.
After “End” displays, compressor and outdoor fan will automatically stop after around 1 minute.(7)
LED105
LED104
If pump down operation has ended normally (LED display figure •
outdoor unit will remain stopped until the power
supply is disconnected.
Turn the power off. PUMP DOWN is comoleted.(8)
Note
For performing pump down once again after pump down task has failed and compressor has automatically stopped; •
open the close three-way valve (both liquid and gas side), disconnect the power supply at once and restore it after
2-3 minutes, and then perform pump down operation.
For restarting the operation after the completion of pump down operation; open the close three-way valve (both •
liquid and gas side), disconnect the power supply at once and restore it after 2-3 minutes, and make sure to
perform test operation in “Cooling”.
If an error occurs during pump down operation; as shown in •
the right figure, “E.98.” (pump down error) will appear.
In such case, recover the refrigerant from service port.
POWER/MODE
lamp: OFF
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
ERROR
lamp: ON
7 Segment
LED Lamp
on the left),
01-14
1-15. COMPRESSOR PREHEATING
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When 30 minutes has passed after power-on or operation stop, the preheating is started according
to the outdoor unit heat exchanger (outlet) temperature as shown in Fig.11.
It applies the current to compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, the preheating ends.
(Fig 11 : Condition of the compressor preheating)
When outdoor unit
heat exchanger (outlet)
OFF
temperature rises
-3°C
-5°C
When outdoor unit
heat exchanger (outlet)
temperature drops
ON
1-16. FRESH AIR CONTROL
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation
as shown in Fig.12.
(Fig 12 : Fresh Air control)
Fan motor
(Indoor unit)
Control signal
(for Fresh Air)
ON
OFF
ON
OFF
12V
1-17. EXTERNAL ELECTRICAL HEATER CONTROL
The External Electrical Heater operates when it meets all the following conditions.
Model type : Heat pump
Operation mode : Heating mode
Compressor : ON
Indoor fan : ON
Room temperature zone : B zone
(Fig 13 : External Electrical Heater control)
Ts : Setting temperature
Heater : OFF ( A zone )
Ts -3°C
Heater : ON ( B zone )
Ts -12°C
Heater : OFF ( C zone )
When the room
temperature drops
When the room
temperature rises
Ts -1°C
Ts -10°C
Room temperature
zone in Heating
Control signal
(for
External Heater)
It operates only in Heating mode
and when the indoor fan operates.
(However, S-Lo is excluded)
B zone
A / C zone
ON
OFF
12V
01-15
1-18. DEFROST OPERATION CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects
the temperature lower than the values shown in Table 9.
(Table 9 : Condition of starting Defrost Operation)
Condition of 1st defrost operation
Compressor contiguous
operation time
Compressor integrating
operation time
Below 10min.Above 10min.
Less than 22min.
22 to 62min.62 to 105min.After 105min.
Operation temperature
Does not operate
Below - 9°C Below - 3°C Below - 1°C
Condition of 2nd defrost operation
Compressor contiguous
operation time
Compressor integrating
operation time
Operation temperature
Below 10min.Above 10min.
Less than 35min.
Does not operate
36 to 105min.After 105min.
Below - 5°C Below - 1°C
Condition of Integrating defrost operation)
Compressor contiguous
operation time
Compressor integrating
operation time
Operation temperature
Below 10min.Above 10min.
Less than 105min.
Does not operate
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
After 105min.
(For long continuous operation)
Below - 1°C
Less than 10min.
(For intermittent operation)
OFF count of the comp.
40 times
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions becomes as shown in Table 10.
( Table 10 : Condition of defrost release )
Release Condition
Compressor operation time has passed 15~20min.
or
High pressure sensor detects above 2.09MPaG.
01-16
3. Defrost Flow Chart
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The defrosting shall proceed by the integrating operation time
and outdoor heat exchanger emperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 10 minutes)
(In case of 1st defrost)
Compressor integrating
operation:
Over 22 minutes to
below 62 minutes
Compressor integrating
operation:
Over 105 minutes
Outdoor
heat exchanger
temperature:
Below - 1°C
Defrost start
Defrost Indicator.
is displayed
on the wired RC
Outdoor fan : OFF
Compressor speed : 0 rps
EEV :
AO*A72LALT : 480 or 500 pls
AO*A90LALT : 350 pls
4-way valve : OFF
Outdoor fan : OFF
Compressor speed
AO*A72LALT : 70~95rps
AO*A90LALT : 100rps
Compressor operation time has passed 15~20min.
or
High pressure sensor detects above 2.09MPaG.
Defrost end
01-17
1-19. OFF DEFROST OPERATION CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When operation stops in the HEATING mode, if frost is adhered to the outdoor unit
heat-exchanger, the defrost operation will proceed automatically.
In this time, if is displayed on the wired RC,
the outdoor unit will allow the heat-exchanger to defrost, and then stop.
1. OFF DEFROST OPERATION CONDITION
In heating operation, the outdoor heat exchanger temperature is less than - 4°C,
and compressor operation integrating time lasts for more than 30 minutes.
and compressor operation contiguous time lasts for more than 10 minutes.
2. OFF DEFROST END CONDITION
Release Condition
Compressor operation time has passed 15~20min. or
High pressure sensor detects above 2.09MPaG.
OFF Defrost Flow Chart
HEATING operation stops
Outdoor heat exchanger temperature:
Below - 4°C
and
Compressor integrating operation:
Over 30 minutes
and
Compressor contiguous operation:
Over 10 minutes
Defrost start
Defrost Indicator:
is displayed
on the wired RC
Compressor operation time has passed 15~20min.
or
High pressure sensor detects above 2.09MPaG.
Defrost end
01-18
1 -20. VARIOUS PROTECTIONS
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
1-1. Discharge Temperature Protection 1
(a). When the discharge temperature becomes more than 115°C, the compressor is stopped under all conditions.
(b). The compressor restarts after 7 minutes has passed from the protection stop by (a).
(c). The error is displayed and the compressor stops when the discharge temperature becomes more than 115°C
again within 24 hours after the restart by (b). [Permanent stop]
1-2. Discharge Temperature Protection 2
(a). When the discharge temperature becomes more than 105°C,
the compressor speed -10 rps, and it continues the speed -10 rps
every 2 minutes until the temperature becomes less than 105°C.
(b). When the discharge temperature becomes less than 100°C,
(Fig 14 : Discharge temperature control)
Discharge
temperature
115°C
Compressor stop
-10 rps every 2 minutes
105°C
the protection control of the compressor speed is released.
100°C
Release of protection
2. COMPRESSOR TEMPERATURE PROTECTION CONTROL
(a). When the compressor thermistor value becomes more than 112°C, the compressor is stopped
under all conditions.
(b). When 3 minutes has passed after the protection stop by (a), the compressor is restarted.
(c). When the compressor thermistor value becomes more than 112°C again within 24 hours
after the restart by (b), the error is displayed and the compressor is stopped. [Permanent stop]
3. LOW PRESSURE PROTECTION CONTROL
3-1. Low Pressure Protection 1 (For Cooling and Heating)
<After the compressor start-up and 1 minute has passed>
(a).The detected value of pressure sensor is 0.02MPaG or less,
continues for 5 minutes, the compressor is stopped.
(b). When 7 minutes has passed and low pressure sensor detects
value is more than 0.05MPaG after the protection stop by (a),
the compressor restarts.
(c).When the protection (a) operates 5 times within 2 hours after the restart by (b),
the error is displayed and the compressor stops. [Permanent stop]
(Fig 15 : Low pressure protection 1)
Pressure
0.05MPaG
0.02MPaG
Release of protection
Compressor stop
Hold
Hold
3-2. Low Pressure Protection 2
Anti Freezing Protection (For Cooling mode)
<After the compressor start-up and 10 minutes has passed>
(a).When the low pressure value becomes 0.68MPaG or less
continues for 1 minute, the compressor speed -8 rps.
(b). When the low pressure value becomes 0.68MPaG or less
after the protection (a), the compressor continues speed -8 rps
every 1 minute until the detected value becomes more than
0.68MPaG.
(c). When the low pressure value becomes more than 0.78MPaG,
this protection is released.
01-19
(Fig 16 : Anti freezing protection)
Pressure
0.78MPaG
Release of protection
Hold
0.68MPaG
-8 rps every 1 minute
4 . HIGH PRESSURE PROTECTION CONTROL
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
4-1. Abnormal Stop
<After the start-up and 1 minute has passed>
(a). When the high pressure value becomes more than 4.10 MPaG, the compressor is stopped
under all conditions.
(b). When 3 minutes has passed after the protection stop by (a), and high pressure value
becomes *[ A ] MPaG or less, the protection is released and the compressor is restarted.
Cooling
A
3.83.0
Heating
4-2. Cooling Pressure Over Rise Protection
(a). When the high pressure value becomes more than 4.00MPaG, the compressor speed
-5 rps every 2 minutes until it becomes 4.00MPaG or less.
(b). When the high pressure value becomes 3.80MPaG or less, the protection is released.
(Fig 17 : Cooling pressure over rise protection)
Pressure
4.10MPaG
4.00MPaG
3.80MPaG
*During protection : Compressor speed is holded, or when a lower speed is directed, it accedes it.
During release of protection : Compressor operates according to the direction speed.
Compressor stop
-5 rps every 2 minutes
*Hold
Release of protection
4-3. Limitation of the Compressor Upper Limit Speed
(a). The compressor upper limit speed is controlled by high pressure value as shown in Fig 18.
(b). The lowest upper limit speed is given to priority compared with other controls.
(Fig 18 : Limitation of the compressor upper limit speed)
High pressure
(Threshold value)
3.80MPaG
3.30MPaG
3.00MPaG
High pressure = 1.25 Low pressure + 2.125
80 rps
90 rps
95 rps
100 rps
+
Low pressure
01-20
6. HEATING OVERLOAD PROTECTION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
In Heating mode, the compressor speed is controlled as following based on the
detection value of the indoor heat-exchanger temperature sensor and pressure sensor.
6-1. High Temperature Release Control <Indoor unit control>
(Fig 19 : High temperature release control by indoor unit)
When Indoor unit
heat-exchanger
temperature rises
53°C
B zone
Refer to Table 11
When Indoor unit
heat-exchanger
temperature drops
50°C
Azone
(Table 11: Compressor Operation)
73 rps~ 70 rps
B zone
AO*A72LALT
B zone
AO*A90LALT
A zone
6-2. High Pressure Release Control <Outdoor unit control>
(a). When the high pressure value becomes more than 3.50MPaG, the compressor speed
-7 rps every 1 minute until it becomes 3.50MPaG or less.
(b). When the high pressure value becomes 3.00MPaG or less, the protection is released.
43~70 rps Speed down every 2 minutes
34~40 rps 32 rps for 2 minutes
28~32 rps Stop
82 rps~ 79 rps
45~79 rps Speed down every 2 minutes
34~42 rps 32 rps for 2 minutes
28~32 rps Stop
Normal Heating Control
(Fig 20 : High pressure release control)
Pressure
4.10MPaG
3.50MPaG
3.00MPaG
*During protection : Compressor speed is holded, or when a lower speed is directed, it accedes it.
During release of protection : Compressor operates according to the direction speed.
Compressor stop
-7 rps every 1 minute
*Hold
Release of protection
7 . CURRENT RELEASE CONTROL
The compressor speed is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature and outdoor fan speed.
The compressor speed returns to the designated speed of the indoor unit at the time
when the speed becomes lower than the release value.
01-21
4 . LOW VOLTAGE PROTECTION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When the temporary blackout, the load current is reduced to delay the switching power-off,
and reset of microcomputer is delayed.
A low voltage signal is detected every 1msec.
(Table 12 : Low voltage protection)
Operation
Compressor : stop
Fan : stop
Restart
Protection operate
Protection release
Condition
When level [ L ] is detected 3msec
more continuously
When level [ H ] is detected 2msec
more continuously
1-21. ECONOMY OPERATION
At the maximum output, ECONOMY OPERATION is approximately 70% of normal air conditioner
operation for Cooling and Heating.
When ECONOMY OPERATION is performed during the Cooling mode, dehumidification is improved.
This function is especially convenient when you want to remove the humidity in the room
without significantly lowering the room temperature.
If the room is not cooled (or heated) well during economy operation, select normal operation.
During the monitor period in the AUTO mode, the air conditioner operation will not change
to ECONOMY OPERATION even if ECONOMY OPERATION is selected by pressing the
ECONOMY button.
1-22. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than temperature
in the table below, the compressor is stopped.
(Table 13 : Operation temperature of compressor stop control)
Temperature
Operation
temperature
Release
temperature
COOLING
- 20°C
- 15°C
HEATING
01-22
1-23. DRAIN PUMP OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
.
During COOLING / DRY mode
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Anti- freezing protection", the drain pump is turned off
in 1 hour after the compressor stops.
4. When the water level in the drain pan rises up and then the float switch functions:
1
The compressor, indoor and outdoor fan motor operation are stopped.
2
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
3
The indoor unit fan motor operates after the float switch is turned off.
5. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
(It is necessary to turn off power for release it. )
6. When the float switch turns OFF less than 3 minutes, the unit starts Cooling operation.
(Fig 21 : Detail of Drain Pump Operation)
Compressor
Drain Pump
ON
OFF
ON
OFF
3 minutes
<Float Switch turns OFF less than 3 minutes>
Less than 3 minutes
Float Switch
Compressor
Indoor Fan
Drain Pump
.
During HEATING / FAN mode / Stop operation
ON
OFF
ON
OFF
3 minutes ST
ON
OFF
ON
OFF
3 minutes
1.When the water level in the drain pan rises up and then the float switch functions:
Drain pump operates continuously for 3 minutes after the float switch is turned off.
1
(Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
Thereafter, even if the float switch turns OFF, the "FAILURE INDICATION" is not released.
(It is necessary to turn off power for release it. )
(Fig 22 : Stop operation on Heating and Fan mode)
Float Switch
Drain Pump
ON
OFF
ON
OFF
3 minutes
01-23
1-24. LOW NOISE OPERATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
The compressor speed and the outdoor unit fan speed are limited to reduce the operation noise
by External Input.
During the LOW NOISE OPERATION,
"CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "PEAK CUT OPERATION"
are effective, and the outdoor unit operates by lowest current of them.
However, during the DEFROST OPERATION, the compressor operates by the speed
for DEFROST OPERATION.
( Table 14 : Detail of Low Noise Operation )
Low Noise Mode
Cooling
Outdoor Fan
Upper Limit Speed
( rpm )
620
Compressor Speed ( rps )
AO* A72LALT AO* A90LALT
54
60
LEVEL 1
Heating
Cooling
600
500
69
46
70
54
LEVEL 2
Heating
Cooling
500
420
45
43
48
45
LEVEL 3
Heating
500
43
45
*The performance drops when operating in the LOW NOISE OPERATION.
1-25. PEAK CUT OPERATION
The Current Value is limited to reduce the power consumption by External Input.
During the PEAK CUT OPERATION,
"CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "LOW NOISE OPERATION"
are effective, and the outdoor unit operates by lowest current of them.
However, this function becomes invalid during DEFROST OPERATION.
(Table 15 : Outline of Peak Cut Operation )
PEAK CUT LEVEL
Peak Cut
For Rated Capacity
*Percentage is rated electrical power ratio.
LEVEL 1LEVEL 2LEVEL 3LEVEL 4
Forced
thermostat-OFF
01-24
75%50%
100%
1-26. DESCRIPTION OF DISPLAY UNIT
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1-26-1 Field setting switches
Remove the front panel of the outdoor unit and the cover of the electrical component box to access
the print circuit board of the outdoor unit.
Print circuit board switches for various settings and LED displays are shown in the figure.
POWER/MODE Lamp (LED101)
It lights up when power on.
LED105 LED104
MODE/EXIT button
(SW107)
SELECT button (SW108)
Outdoor unit printed circuit board
MODE
SELECT
/EXIT
SW108
SW107
ENTER button (SW109)
1-26-2 Normal operation mode
Operation status is displayed in 7 Segment LED Lamp (LED105 and LED104).
Mode
Operation
CODE
C L
H t
Cooling
Heating
d F During defrosting operation
P C During power saving operation
L n During low noise operation
Stopped
DESCRIPTION
POWER
MODE
LED101
(GREEN)
ENTER
SW109 SW102
ERROR Lamp (LED102)
It will flash rapidly in case of an error.
ERROR
LED102
(RED)
7 Segment LED Lamp
(LED105 and LED104)
Status of the unit will display.
DIP switch (SW101)
PUMP
DOWN
SW101
PUMP DOWN button (SW102)
1-26-3 Error display mode
10.2.1. Method for ascertaining the errors
(1) When an error has occurred, ERROR LED (LED102) will flash rapidly, and as shown in the figure below,
7 Segment LED will alternately display "Err" and number of errors.
Error display
LED105LED104LED105LED104
(2) Error contents will display if ENTER button (SW109) is pressed in the state of (1).
For error contents, refer to the list of error code described later.
LED105LED104
Display number of errors
Alternate display
Ex.) "E.0C" is displayed.
Discharge temperature
thermistor error.
01-25
(3) If SELECT button (SW108) is pressed in the state of (2), contents of all the errors will display.
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Error 1.Error 2.Error 3.
LED105LED104LED105LED104LED105LED104
(4) If ENTER button (SW109) is pressed, it will return to state of (1).
If no action is taken, it will return to the state of (1) after 60 seconds.
Note
•
In case the errors are resolved,
it will return to "Normal operation mode" described in 10.1. earlier.
Error code check table
CODEDESCRIPTION
E. 06. Outdoor heat exchanger temperature sensor (outlet) error
E. 0A. Outdoor temperature sensor error
E. 0C. Outdoor discharge pipe temperature sensor error
E. 0E. Heat sink thermistor (inverter) error
E. 0F. Discharge temperature error
E. 13. Indoor signal error
E. 15. Compressor temperature sensor error
E. 16. Pressure switch error, Pressure sensor error
E. 17. IPM protection
E. 1A. Compressor location error
E. 1b. Outdoor fan error
E. 24. Excessive high pressure protection
E. 2b. Compressor temperature error
E. 2E. Inverter error
E. 2F. Low pressure error
E. 98. Pump down error
E. 99. Indoor unit error condition
LED lamp :
0 1 2 3 4 5 6 7 8 9
Ab C dE FHiJL
n o PrStUvy-
01-26
1-26-6 Field Setting and Monitor Mode List
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Monitor mode
[ F1 ]
Setting mode
[ F2 ]
Classification
Operation of
each part
Time guard
Refrigerant
cycle data 1
Refrigerant
cycle data 3
Classification
Install
Correction
Change of30
function 2
Low noise
setting
ITEM
CODE No.
ITEM
CODE No.
Setting Mode
Rotational speed of outdoor unit fan motor
10
Rotational speed of INV compressor
11
Current value of INV compressor
12
14
Pulse of EEV1
INV compressor accumulated time
21
[ Cooling ]
22INV compressor accumulated time
[ Heating ]
Information on Thermistor 1
30
(Discharge Pipe Temperature Thermistor)
32Information on Thermistor 3
(Outdoor Temperature Thermistor)
34Information on Thermistor 5
(Heat Exchanger Temperature Thermistor)
39Information on Thermistor 10
(Compressor Temperature Thermistor)
50Information on pressure sensor 1 The value of the pressure sensor 1 is displayed
Information on pressure sensor 2
51
Setting Mode
Pipe length setting
00
Defrost setting shift 1
13
(Defrosting time)
Defrost setting shift 2
(Defrosting start time)
Energy saving level setting
41Low noise mode setting
Low noise mode operation
42
level setting
ITEM
CODE No.
The rotational speed of the outdoor unit fan motor is displayed
[ 0 ~ 999 ] rpm
The rotational speed of the compressor is displayed
[ 0 ~ 999 ] rps
Current value of INV compressor is displayed
[ 0.00 ~ 99.99 ] A
Pulse of EEV1 is displayed
[ 0 ~ 9999 ] pls
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 0 ~ 9999 ]
Accumulated time is displayed in the heating operation of the
INV compressor
[ 0 ~ 9999 ]
The value of the Thermistor 1 is displayed
[ -99.9 ~ 999.9 ]
The value of the Thermistor 3 is displayed
[ -99.9 ~ 999.9 ]
The value of the Thermistor 5 is displayed
[ -99.9 ~ 999.9 ]
The value of the Thermistor 10 is displayed
[ -99.9 ~ 999.9 ]
If unit is [MPa], it is displayed as [ 0.00 ~ 9.99 ]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
The value of the pressure sensor 2 is displayed
If unit is [MPa], it is displayed as [ 0.00 ~ 9.99 ]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
0040-65m
02
65-90m
00
End temperature:Normal
01
End temperature:Higher
02
End temperature:Lower
00
Start temperature:Normal
01
Start temperature:Higher
02
Start temperature:Lower
Level 1 (stop)
00
Level 2 (operated at 50% capacity)
01
Level 3 (operated at 75% capacity)
02
Level 4 (operated at 100% capacity)
03
00
Off (Normal operation)
01
On (Low noise mode operation is always done)
Level 1 (dB)
00
Level 2 (dB)
01
Level 3 (dB)
02
Information contents
10hour
10hour
°C or °F
°C or °F
°C or °F
°C or °F
Setting Function
End time:Normal
End time:Longer
End time:Shorter
Start time:Normal
Start time:Longer
Start time:Shorter
Default
ITEM
CODE No.
Function mode
Forced
operation
[ F3 ]
Clear
Error History
Error history
Display Mode
[ F9 ]
00Cooling test run
01Heating test runForced thermostat-ON in Heating
02Test run stopTest run is stopped
30Error history clearAll the abnormal code histories are cleared
33INV compressor accumulated time clearAccumulated time of the INV compressor becomes [ 0 ]
35Field setting all clearReturn to default the all set items
ITEM
CODE No.
00
01
02
03
Setting Mode
Meaning of Error History Number
1 time ago
(Newest)
2 times ago
3 times ago
4 times ago
Setting Function
Forced thermostat-ON in Cooling
Information contents
Refer to TROUBLE SHOOTING
01-27
DUCT type
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INVERTER
R410A
2 . TROUBLE SHOOTING
2. TROUBLE SHOOTING
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
2-1 ERROR DISPLAY
2-1-1 WIRED REMOTE CONTROLLER DISPLAY
The Error code operate as follows according to the error contents.
Indoor Unit : AR* C72 / 90LHTA
Error Code
E00
E01
E02
E04
E06
E0A
E0C
E0E
E0F
E11
E12
E13
E15
E16
E17
Error Contents
Wired remote controller error
Serial error (Serial reverse transfer error)
Room temperature thermistor error
Indoor heat exchanger temperature thermistor (middle) error
Outdoor heat exchanger temperature thermistor (outlet) error
Outdoor temperature thermistor error
Outdoor discharge pipe temperature thermistor error
Heat sink thermistor (inverter) error
Discharge temperature error
Model distinction error (Indoor)
Indoor fan motor 1 lock error
Indoor fan motor 1 rev. error
Indoor signal error
Compressor temperature thermistor error
Pressure switch error, Pressure sensor error
IPM Protection
Trouble
Shooting
4
1
5
3
7
8
6
9
17
23
16
2
10
20
12
E1A
E1b
E24
E2A
E2b
E2c
E2E
E2F
E34
E37
E38
Compressor location error
Outdoor fan error
Excessive high pressure protection
Power supply frequency detection error
Compressor temperature error
4-way Valve Error, Solenoid Valve Error
Inverter error
Low pressure error
Indoor fan motor 2 lock error
Indoor fan motor 2 rev. error
Indoor fan motor 1 drivers circuit error
Indoor fan motor 2 drivers circuit error
13
14
18
11
21
19
15
22
16
24
02-01
2-1-2 OUTDOOR UNIT DISPLAY
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Please refer the blinking pattern as follows.
Outdoor Unit : AO* A72 / 90LALT
The Error LED operate as follows according to the error contents.
Error Code
E. 06. Outdoor heat exchanger temperature thermistor (outlet) error
E. 0A. Outdoor temperature thermistor error
E. 0C. Outdoor discharge pipe temperature thermistor error
E. 0E. Heat sink thermistor (inverter) error
E. 0F. Discharge temperature error
E. 13. Indoor signal error
E. 15. Compressor temperature thermistor error
E. 16. Pressure switch error, Pressure sensor error
E. 17. IPM protection
E. 1A. Compressor location error
E. 1b. Outdoor fan error
E. 24. Excessive high pressure protection
E. 2b. Compressor temperature error
E. 2E. Inverter error
E. 2F. Low pressure error
Error Contents
Trouble
Shooting
7
8
6
9
17
2
10
20
12
13
14
18
21
15
22
E. 99. Indoor unit error condition
---
02-02
2-2 TROUBLE SHOOTING WITH ERROR CODE
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Trouble shooting 1
Indicate or Display:
OUTDOOR UNIT Error Method:
Serial error
Refer to error code table.
(Serial reverse transfer error)
Detective Actuators:Detective details:
Outdoor unit Main PCB
When the indoor unit cannot properly receive the serial signal from
outdoor unit for 10 seconds or more.
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
NO
YESYES
Check Point 2 : Check connection
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears
at outdoor unit terminal L1 - N, L2 - N, L3 - N.
OK
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal 1 - 3.
>> If it is abnormal, replace Main PCB.
BLACK
WHITE
RED
1
2
3
+
-
02-03
Trouble shooting 2
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Indoor signal error
Refer to error code table.
Detective Actuators:Detective details:
Indoor unit controller PCB
Indoor unit filter PCB
When the indoor unit cannot properly receive the serial signal from
outdoor unit for 10 seconds or more.
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
Check Point 1-2 : Check external cause such as noise
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears
at outdoor unit terminal L1 - N, L2 - N, L3 - N.
OK
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal 2 - 3.
>> If it is abnormal, replace Controller PCB and Filter PCB.
BLACK
WHITE
RED
1
2
3
+
-
02-04
Trouble shooting 3
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Indoor heat exchanger temperature
Refer to error code table.
thermistor (middle) Error
Detective Actuators:Detective details:
Indoor unit controller PCB
Heat exchanger temperature
thermistor (middle)
When Heat exchanger temperature thermistor (middle) open or
short-circuit is detected at power ON.
Check & correct the followings.
Check the connection of terminal between Wired Remote Controller and indoor unit,
and check if there is a disconnection of the cable.
OKOK
Check Point 2 : Check Wired remote controller and Controller PCB
Check voltage at connector of Wired remote controller of Controller PCB. (Power supply to Wired remote controller)
>> CN140 : 1 - 3 pin
If it is DC12V, Wired remote controller is failure. (Controller PCB is normal)
>> Replace Wired remote controller.
If it is DC 0V, Controller PCB is failure.
>> Replace Controller PCB.
02-06
Trouble shooting 5
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Room temperature thermistor error
Refer to error code table.
Detective Actuators:Detective details:
Indoor unit controller PCB
Room temperature thermistor
When Room temperature thermistor open or short-circuit is
detected at power ON.
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
Temperature (°C )
Resistance value (k )
Temperature (°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
-30 -20 -10 0 10 20 30 40
1013.1 531.6 292.9 168.6 100.9 62.5 40.0 26.3
50 60 70 80 90 100 110 120
17.8 12.3 8.7 6.3 4.6 3.4 2.6 2.0
OKOK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
1 2
1 2
CN141
3 4 5 6
1 2 3 4
CN143
3 4
5 6
1 2 3 4
THERMISTOR
( DISCHARGE PIPE )
THERMISTOR
( COMPRESSOR TEMP. )
THERMISTOR
( HEAT EXCHANGER OUT )
CN144
1 2 3
1 2 3
If the voltage does not appear, replace Main PCB.
THERMISTOR
( OUTDOOR TEMP
. )
02-12
Trouble shooting 11
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Power supply frequency
Refer to error code table.
detection error
Detective Actuators:Detective details:
Indoor unit Controller PCB
When power frequency is not detected by 4 seconds after power-on.
Indoor unit Filter PCB
Forecast of Cause:
1. Connection failure 2. External cause 3. Controller PCB failure 4. Power PCB failure
Check Point 1-1 : Reset the power supply and operate
Does error indication reappear?
NO
YESYES
Check Point 2 : Check connection
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring.)
Check Point 1-2 : Check external cause such as noise
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears
at outdoor unit terminal, L1 - N, L2 - N, L3 - N.
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Check Point 4 : Replace Controller PCB and Power PCB
If Check Point 1 ~ 3 do not improve the symptom, replace Controller PCB and Filter PCB.
02-13
Trouble shooting 12
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
OUTDOOR UNIT Error Method:
IPM Protection
Refer to error code table.
Detective Actuators:Detective details:
Outdoor unit Inverter PCB
Compressor
When over current flows in Inverter PCB, the compressor stops.
After the compressor restarts, if the same error is repeated within
40sec, the compressor stops reappear.
If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Connection failure 2. Outdoor fan operation failure
Check Point 1 : Check connections condition in control unit
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Inverter PCB
Inverter PCB check is refer to SERVICE PARTS INFORMATION 4.
>> If it is abnormal, replace Inverter PCB.
OKOK
Check Point 3 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3-1: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
02-15
Trouble shooting 14
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Error
Refer to error code table.
Detective Actuators:Detective details:
Outdoor unit Main PCB
Outdoor fan motor
Main Filter PCB
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
consecutively 3 times, compressor and fan motor stops.
If repeats 5 times in a row,
permanently
.
Forecast of Cause:
1. Fan Motor failure 2. Motor protection by surrounding temperature rise
3. Main PCB failure 4. Main Filter PCB failure
Check Point 1 : Check rotation of Fan
Check if the fan motor is lock.
(Can the fan be rotated by hand when operation is off.)
Check the fan loosening.
(Lock-nut loosening, defective propeller fan)
>> If fan motor or bearing is abnormal, replace it.
compressor and fan motor stops
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>> Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Fuse of Main Filter PCB.
Check if F602 is open.
>> If F602 is open, replace Main Filter PCB.
OK
Check Point 4 : Check output voltage of Main PCB
Check outdoor unit circuit diagram and the voltage.
(Measure at Main PCB side connector)
When there is communication error between Main PCB
and Inverter PCB.
When "Inverter PCB cement resistor difference voltage between
both ends" detects 18V and above twice continuously.
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check resistance of Cement Resister
Remove connector, check each Cement Resister
Resistance value
5.65
If Resistance value is abnormal, replace Cement Resister.
OK
Check Point 3 : Replace Main PCB and Inverter PCB
If Check Point 1 and 2 do not improve the symptom, replace Main PCB and Inverter PCB.
02-17
Trouble shooting 16
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Indoor fan motor 1 lock error
Refer to error code table.
Indoor fan motor 1 rev. error
Detective Actuators:Detective details:
Indoor unit Controller PCB
Indoor unit Power PCB
When the condition that actual rev. of Indoor Fan is 1/3 or less.
Or the condition of fan speed is 0rpm is continued more than 56 seconds.
Indoor fan motor
Forecast of Cause:
1. Fan motor failure 2. Motor protection by surrounding temperature rise
3. Power PCB failure 4. Controller PCB failure
Check Point 1 : Check rotation of fan
Check if the fan motor is lock.
(Can the fan be rotated by hand when operation is off.)
Check the fan loosening.
(Lock-nut loosening, defective propeller fan)
>> If fan motor or bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>> Upon the temperature coming down, restart operation.
OK
Check Point 3 : Replace Power PCB and Controller PCB
If Check Point 1, 2 do not improve the symptom,
replace Power PCB and Controller PCB.
02-18
Trouble shooting 17
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
OUTDOOR UNIT Error Method:
Discharge temperature error
Refer to error code table.
Detective Actuators:Detective details:
Outdoor unit Main PCB
Discharge pipe temperature thermistor
Forecast of Cause :
1. Valve is close 2. EEV failure 3. Gas leak, less 4. Discharge thermistor failure
5. Outdoor fan operation failure 6. Outdoor heat exchanger clogged
< Cooling mode >
Check Point 1 : Check if gas valve is open
If it is not open, open it and check the operation.
OKOK
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
OK
When the discharge temperature becomes higher than 115°C.
When detecting it 2 times within 24 hours, the compressor stops.
< Heating mode >
Check Point 1 : Check if liquid valve is open
If it is not open, open it and check the operation.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
MPa MPa
OK
Check Point 3 : Check if gas leak or less gas
Measure gas pressure, if there is a leak, correct it.
>> If recharging refrigerant, make sure to perform
vacuuming and recharge the specified amount.
OK
Check Point 4 : Check Discharge pipe thermistor
Is it on the holder?
Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 6),
If defective, replace the thermistor
OK
Check Point 5 : Check Outdoor heat exchanger
Is there any obstructing the air flow route?
Is there any clogging of outdoor unit heat exchanger?
>> If clogged, clear the clog.
OK
Check Point 6 : Check Outdoor fan
Check outdoor fan motor. (Refer to Trouble shooting 14)
>> If the fan motor is failure, replace it.
02-19
Trouble shooting 18
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
OUTDOOR UNIT Error Method:
Excessive high pressure protection
Refer to error code table.
Detective Actuators:Detective details:
Outdoor unit Main PCB
Outdoor fan motor
In cooling operation, after 1 minute or more compressor starts,
when outdoor heat exchanger temperature is 68 °C and above.
Heat exchanger temp. thermistor (Out)
Outdoor unit EEV
4. Thermistor failure 5. EEV failure 6. Main PCB failure
Check Point 1 : Check connections condition in control unit
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor heat exchanger
Is there any obstructing the air flow route?
Is there any clogging of outdoor unit heat exchanger?
>> If clogged, clear the cloge it.
OK
Check Point 3 : Check Outdoor fan
Check Outdoor fan motor. (Refer to Trouble shooting 14)
>> If the fan motor is failure, replace it.
OKOK
Check Point 4 : Check Thermistor
Check Thermistor. (Refer to Trouble shooting 7)
>> If the thermistor is failure, replace it.
OKOK
Check Point 5 : Check EEV
Check EEV. (PARTS INFORMATION 3)
>> If the EEV is failure, replace it.
OKOK
Check Point 6 : Replace Main PCB
If Check Point 1 ~ 5 do not improve the symptom, replace Main PCB.
02-20
Trouble shooting 19
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
OUTDOOR UNIT Error Method:
4-way Valve Error,
Solenoid Valve Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB
Heat exchanger temperature thermistor
Room temperature thermistor
4-way valve
Detective details:
When the indoor heat exchanger temperature is compared with
the room temperature, and either following condition is detected
continuously two times, the compressor stops.
Cooling or Dry operation
[Indoor heat exchanger (middle) temp.] - [Room temp.] > 20degC
Heating operation
[indoor heat exchanger (middle) temp.] - [Room temp.] < -14degC
If the same operation is repeated 5 times, the compressor stops permanently.
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Check thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor, If defective, replace the thermistor.
OKOK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN105 from PCB and check the resistance value of coil.
Resistance value is about 1.5k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature, and confirm the
location of the valve by the temperature difference.
>> If the value location is not proper,
replace 4-way valve.
Heating OperationCooling Operation
4WAY VALVE
ON
SOLENOID COIL
HOT GAS
AC
Resistance Value
1.5K
4WAY VALVE
OFF
SOLENOID COIL
HOT GASHOT GAS
HOT GAS
AC
OKOK
Check Point 4: Check Voltage of Solenoid Coil
If CN105 of Control PCB dose not Show 220V + 20 V during Heating operation (Compressor is in operation),
replace Control PCB.
Outdoor unit Main PCB
Pressure sensor
Pressure switch
30 seconds or more after power-on, when pressure sensor detection
value detects the condition below continuously for 30 seconds or more.
High pressure : Ps < 0.3 or Ps > 5.0 MPa
Low pressire : Ps < 0.06 or Ps > 5.0 MPa
When pressure switch detectes more than 4.2 MPa
Check Point 1 : Check connection of the Pressure Sensor
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check output voltage of Main PCB
Check voltage of Main PCB.
(Measure at Main PCB side connector)
>>1 pin(Red) - 3 pin(Black) DC5V 5%
If the voltage is not correct, replace Main PCB.
CN118(HP)
CN119(LP)
OK
Check Point 3 : Check output voltage of Pressure Sensor
Check voltage of Main PCB.
(Measure at Main PCB side connector)
>>2 pin(White) - 3 pIn(Black) Voltage is refer to the following graph.
[High pressure][Low pressure]
4.5
Voltage [V]
0.5
05
Pressure [MPa]
If the voltage is not correct, replace Presure Sensor.
3.5
Voltage [V]
0.5
01.7
Pressure [MPa]
RED
1
1
WHITE
2
2
BLACK
3
3
PRESSURE SENSOR
OK
Check Point 3 : Continuity check of Pressure Switch
Continuity check of Pressure Switch
Pressure Switch characteristics
OFF : 4.2 0.1 MPa
ON : 3.2 0.15 MPa
If it is not correct, replace pressure switch.
CN120
02-22
BLUE
1
1
2
2
BLUE
3
3
PRESSURE SWITCH
Trouble shooting 21
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
OUTDOOR UNIT Error Method:
Compressor temperature error
Refer to error code table.
Detective Actuators:Detective details:
Outdoor unit Main PCB
Compressor temperature thermistor
Forecast of Cause :
1. Valve is close 2. EEV failure 3. Gas leak, less 4. Compressor thermistor failure
5. Outdoor fan failure 6. Outdoor heat exchanger clogged
< Cooling mode >
Check Point 1 : Check if gas valve is open
If it is not open, open it and check the operation.
OK
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
OK
Check Point 3 : Check if gas leak or less gas
When the compressor temperature becomes 112°C or more.
< Heating mode >
Check Point 1 : Check if liquid valve is open
If it is not open, open it and check the operation.
OK
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
MPa MPa
OK
Measure Gas pressure, if there is a leak, correct it.
>> If recharging refrigerant, make sure to perform
vacuuming and recharge the specified amount.
OK
Check Point 4 : Check Compressor temperature thermistor
Is it on the holder?
Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 10),
If defective, replace the Compressor temperature thermistor.
OK
Check Point 5 : Check Outdoor heat exchanger
Is there any obstructing the air flow route?
Is there any clogging of outdoor unit heat exchanger?
>> If clogged, clear the clog.
OK
Check Point 6 : Check Outdoor fan
OK
Check Outdoor fan motor. (Refer to Trouble shooting 14)
>> If the Fan Motor is failure, replace it.
Check Point 7 : Replace Main PCB
If Check Point 1 ~ 6 do not improve
the symptom, replace Main PCB.
02-23
Trouble shooting 22
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
OUTDOOR UNIT Error Method:
Low pressure error
Refer to error code table.
Detective Actuators:Detective details:
Outdoor unit Main PCB
Pressure sensor
In cooling operation, 1 minute or more after compressor's start-up,
when pressure sensor detects 0.12 MPa or less for consecutive
5 minutes.
Forecast of Cause :
1. Connector connection failure 2. Pressure sensor failure 3. Main PCB failure 4. Gas leak, less
Check Point 1 : Check connections of the Pressure sensor
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check output voltage of Main PCB
Check voltage of Main PCB.
(Measure at Main PCB side connector)
>>1 pin(Red) - 3 pin(Black) DC5V 5%
RED
1
1
CN119
If the voltage is not correct, replace Main PCB.
WHITE
2
2
BLACK
3
3
PRESSURE SENSOR
PS
OK
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>> If recharging refrigerant, make sure to perform
vacuuming and recharge the specified amount.
OK
Check Point 4 : Replace Pressure sensor
If Check Point 1 ~ 3 do not improve the symptom, replace Pressure sensor.
MPa MPa
02-24
Trouble shooting 23
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Model distinction error (Indoor)
Refer to error code table.
Detective Actuators:Detective details:
When power is on and there is some below case.
Indoor unit Controller PCB
1. When model information of EEPROM is incorrect
2. When the access to EEPROM failed
Forecast of Cause:
1. External cause 2. Defective for connection in controller unit 3. Controller PCB failure
Check Point 1-1 : Reset power supply and operate
Does error indication show reappear?
YESYES
Check Point 2 :
Check connections condition in control unit
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
If Check Point 1, 2 do not improve the symptom,
replace Controller PCB.
NO
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
02-25
Trouble shooting 24
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indicate or Display:
INDOOR UNIT Error Method:
Indoor fan motor 1 drivers circuit error
Refer to error code table.
Indoor fan motor 2 drivers circuit error
Detective Actuators:Detective details:
Indoor unit Power PCB
When a momentary power cut off.
When do not start fan motor.
Forecast of Cause :
1. External cause 2. Connection of connector failure 3. Power PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Replace Power supply PCB
If Check Point 1, 2 do not improve the symptom, replace Power PCB.
02-26
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Trouble shooting 25
Indoor unit - No Power
Forecast of Cause:
1. Power supply failure
2. External cause
3. Electrical components defective
Check Point 1 : Check installation condition
Isn’t the breaker down?
Check loose or removed connection cable.
>> If abnormal condition is found, correct it by referring to manual.
OK
Check Point 2 :
Instant voltage drop of ----- Check if there is abnormally large load in the same
power supply power supply system.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply system.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check whether the ground connection is proper.
Check external cause at indoor unit and outdoor unit (Voltage drop or noise)
OK
OK
Check Point 3 : Check electrical components
Check the voltage of power supply.
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at indoor unit
Terminal 1 - 2 (Power supply).
OK
Check Fuse(F600) on Power PCB and 20A Fuse .
>> If Fuse is open, check loose terminal, and replace Fuse.
Check Varistor on Filter PCB (VA301, VA302).
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power voltage and replace Filter PCB.
OK
If Check Point 1 ~ 3 do not improve the symptom, replace Filter PCB, Power PCB
and controller PCB.
NO
02-27
Trouble shooting 26
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Outdoor unit - No Power
Forecast of Cause:
1. Power supply failure
2. External cause
3. Electrical components defective
Check Point 1 : Check installation condition
Isn’t the breaker down?
Check loose or removed connection cable.
>> If abnormal condition is found, correct it by referring to manual.
OK
Check Point 2 :
Instant voltage drop of ----- Check if there is a abnomally large load in the same
power supply power supply system.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply system.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check whether the ground connection is proper.
Check external cause at indoor unit and outdoor unit (Voltage drop or noise)
OK
Check Point 3 : Check electrical components
Check the voltage of power supply.
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears
at outdoor unit terminal , L1 - N, L2 - N, L3 - N.
OK
Check Fuse F50 and F100 on Main PCB.
>> If Fuse is open, check loose terminal, and replace Fuse.
Check Fuse F602 on Main Filter PCB.
>> If Fuse is open, check loose terminal, and replace Fuse.
NO
Check Varistor VA50 and VA51 on Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power voltage and replace Main PCB.
Check Varistor VA601, and VA604 on Main Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power voltage and replace Main Filter PCB.
OK
If Check Point 1 ~ 3 do not improve the symptom, replace Main Filter PCB,
Inverter Filter PCB Main PCB, and Inverter PCB .
02-28
Trouble shooting 27
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
No Operation (Power is ON)
Forecast of Cause:
1. Setting / Connection failure
2. External cause
3. Electrical component defective
Check Point 1 : Check indoor and outdoor installation condition
Indoor unit - Check incorrect wiring between indoor unit - remote controller, or terminals between indoor units.
Or, check if there is an open cable connection.
Are these indoor unit, outdoor unit, and remote controller suitable model to connect?
>> If there is some abnormal condition, correct it by referring to manual.
OK
Is there loose or removed serial communication line of between indoor unit and outdoor unit?
OK
Check Point 2 : Check external cause at indoor unit and outdoor unit (Voltage drop or noise)
Instant voltage drop of power supply ----- Check if there is abnormally large load in the same power supply system.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply system.
Noise ------------------------------ Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check whether the ground connection is proper.
OK
Check Point 3 : Check electrical components at indoor unit and outdoor unit
Check voltage at CN140
>> If it is DC12V, Wired Remote Controller is failure. >> Replace Wired Remote Controller.
>> If it is DC 0V, Controller PCB is fallure. >> Replace Controller PCB.
>> If Check Point 1, 2 do not improve the symptom, replace control parts of outdoor unit.
Does indoor unit fan run on high fan?
Is Air filter dirty?
Is Heat exchanger clogged?
Check if energy save function is operated.
OK
Check Point 2 : Check outdoor unit operation
Is outdoor unit is operating?
(If not, refer to Trouble shooting 25)
Is there any obstructing the air flow route?
Is there any clogging on outdoor unit heat exchanger?
Is the valve open?
OK
Check Point 3 : Check site condition
Is capacity of indoor unit fitted to room size?
Any windows open? or direct sunlight?
OK
Check Point 4 :
Check indoor unit / outdoor unit installation condition
Check connection pipe.
(Specified pipe length and pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data & Technical
Manual.
OK
Check Point 5 : Check refrigeration cycle
Check if Strainer is clogged (Refer to the figure at right).
Measure gas pressure and if there is a leakage, correct it.
>>
When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV
Check Compressor
MPa MPa
Attention
Strainer normally does not have temperature difference
between inlet and outlet as shown in , but if there is a
difference like shown in , there is a possibility of inside
clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
Pipe (In)Pipe (Out)
02-30
Trouble shooting 29
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Forecast of Cause :
1. Abnormal installation (Indoor unit / outdoor unit)
Abnormal Noise
2. Fan failure (Indoor unit / outdoor unit)
3. Compressor failure (Outdoor unit)
Diagnosis method when abnormal noise is occurred
Abnormal noise is coming from indoor unit.
(Check and correct followings)
Abnormal noise is coming from outdoor unit.
(Check and correct followings)
Is main unit installed in stable condition?
Is the installation of air suction grille and
front panel normal?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Trouble shooting 30
Forecast of Cause:
Water leaking
Is main unit installed in stable condition?
Is Fan guard installed normally?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
OK
Check if vibration noise by loose bolt or contact noise
of piping is happening.
OK
Is Compressor locked?
>> Check Compressor
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water leak occurs
Is main unit installed in stable condition?
Is main unit broken or deformed at the time of
transportation or maintenance?
OK
Is Drain hose connection loose?
Is there a trap in Drain hose?
Is Drain hose clogged?
OK
Is Fan rotating?
>> Check Fan motor
Diagnosis method when water is spitting out.
Is the filter clogged?
OK
Check gas pressure and correct it
if there was a gas leak.
MPa MPa
02-31
2-4 SERVICE PARTS INFORMATION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
SERVICE PARTS INFORMATION 1
Compressor
Diagnosis method of Compressor (If outdoor unit LED displays error, refer to Trouble shooting )
Does not start up
Is there open or loose connection
cable?
Check
connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered.
(Locked compressor due to
clogged dirt or less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection
cable?
Is Gas pipe valve open?
(Low pressure is too low)
MPa
MPa
Check if Refrigerant is leaking.
(Recharge refrigerant)
Check if Strainer is clogged.
(PARTS INFORMATION 3)
Check Inverter PCB
connection of Compressor,and winding resistance.
(Refer to the next page).
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
Abnormal noise
Check if vibration noise by
loose bolt or contact noise
of piping is happening.
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Replace Compressor
Replace Compressor
02-32
SERVICE PARTS INFORMATION 2
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Inverter Compressor
Check Point 1 : Check connection
Check terminal connection of Compressor
(Loose or incorrect wiring)
RED
BLACK
Inverter PCB
WHITE
Check Point 2 : Check winding resistance
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
Check connection of Inverter PCB
(Loose or incorrect wiring)
TM806
Inverter PCB
TM807
RED
TM808
Compressor
Compressor
BLACK
WHITE
R(U)
Resistance value : 0.553
(at 25°C)
T(W)
S(V)
Check Point 3 : Check Inverter PCB
If Check Point 1, 2 do not improve the symptom, refer to SERVICE PARTS INFORMATION 4.
>> If it is abnormal, replace Inverter PCB.
02-33
SERVICE PARTS INFORMATION 3
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Outdoor Unit Electronic Expansion Valve (EEV)
Check Point 1 : Check Connections
Check connection of connector (Loose connector or open cable)
1 2
1 2
CN70
3
4 5
6
3
4 5
6
RED
BLUE
ORANGE
YELLOW
WHITE
EXPANSION VALVE COIL
EV
Check Point 2 : Check coil of EEV
Remove connector, check each winding resistance of Coil.
Read wire
Red - Blue
Red - Orange
Red - Yellow
Red - White
If Resistance value is abnormal, replace EEV.
Resistance value
464
at 20°C
Check Point 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
Check Point 3 : Check voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 5 : Check opening and closing operation of valve
When valve is closed,
it has a temp. difference between Inlet and outlet.
CLOSE
Example : Hot gas
Pipe (In)
If it is open,
it has no temp. difference between inlet and outlet.
OPEN
Example : Hot gas
DC
Pipe (In)
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in ,
but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
Pipe (Out)
Pipe (Out)
Pipe (In)Pipe (Out)
02-34
SERVICE PARTS INFORMATION 4
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
IPM
(Mounted on Inverter PCB)
Check Point 1
Disconnect the connection wires between the Inverter
PCB - electrolytic capacitor and Inverter PCB - Inverter
Compressor.
Set the tester to the "Resistance" mode, and measure
the resistance between the following terminals.
Red wire (P) - screw terminals U/V/W
White wire (N) - screw terminals U/V/W
Judge the result of as follows:
All 6 points several M or greater : Normal
1 or more points several k to short : Defective
Terminal
W
U
V
P
N
Inverter PCB
Check Point 2
Set the tester to the "Diode" mode, and measure the voltage value between the following terminals.
Tester display
Tester display
Tester display
Tester display
Tester display
Tester +side
(red)
Terminal U
Terminal V
Terminal W
White wire
(N)
Tester - side
(black)
Red wire
(P)
Terminal U
Terminal V
Terminal W
Tester display
[V]
[V]
[V]
[V]
[V]
[V]
Judge the result of as follows:
All 6 points several 0.3V to 0.7V : Normal
1 or more points under 0.1V or over load : Defective
02-35
04-103
DUCT type
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
INVERTER
R410A
3 . APPENDING DATA
3-1. FUNCTION SETTING
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
3-1-1 INDOOR UNIT
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
1-1. Setting the Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter.
Select the time setting for the filter sign display interval in the table below according to
the amount of dust or debris in the room.
If you do not wish the filter sign to be displayed, select the setting value for "No indication".
( Factory setting)
Setting Description
Standard (2,500 hours)
Long interval (5,000 hours)
Short interval (1,250 hours)
No indication
Function NumberSetting Value
00
01
11
02
03
1-2. Setting the Static Pressure
Select appropriate static pressure according to the installation conditions.
Refer to the technical manual for details or follow the instructions of the duct designer.
( Factory setting)
Setting DescriptionFunction NumberSetting Value
Normal (72Pa)
Low static pressure (50Pa)
High static pressure 1 (150Pa)
High static pressure 2 (200Pa)
21
00
02
03
04
High static pressure 3 (250Pa)05
1-3. Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room temperature sensor may
require a correction. The settings may be selected as shown in the table below.
Setting DescriptionFunction NumberSetting Value
Standard (No correction)
Warmer control (+1.0°C)
Slightly warmer control (+0.5°C)
Slightly lower control (-0.5°C)
Low control (-1.0°C)04
03-01
30
( Factory setting)
00
01
02
03
1-4. Setting the Heater Room Temperature Correction
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Depending on the installed environment, the room temperature sensor may
require a correction. The settings may be selected as shown in the table below.
( Factory setting)
Setting DescriptionFunction NumberSetting Value
Standard (No correction)
Warmer control (+1.0°C)
Slightly warmer control (+0.5°C)
Slightly lower control (-0.5°C)
31
00
01
02
03
Low control (-1.0°C)04
1-5. Setting the Auto restart
Enable or disable automatic system restart after a power outage.
( Factory setting)
Setting Description
Yes
No
Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.
1-6. Setting the Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
Function NumberSetting Value
00
40
01
( Factory setting)
Setting Description
No
Yes
If setting value is “00”,
room temperature is controlled by the indoor unit temperature sensor.
If setting value is “01”,
room temperature is controlled by either indoor unit temperature sensor or remote control unit sensor.
Function NumberSetting Value
00
42
01
03-02
1-7. Cool Air Prevention
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
This setting is used to set the fan speed when the compressor stops once
the room temperature has reached the set temperature during heating operation.
( Factory setting)
Setting DescriptionFunction NumberSetting Value
Super low
Follow the setting on
the remote controller
43
00
01
(corresponding to ventilation)
1-8. Room Temperature Control Switching
This setting is used to set the room temperature control method when the wired
remote controller is selected by the Indoor Room Temperature Sensor Switching Function.
( Factory setting)
Setting DescriptionFunction NumberSetting Value
Control by the sensors of
both the indoor unit and the
wired remote controller.
Control only by the sensor of
the wired remote controller
48
00
01
03-03
3-1-3 Procedures to change the Function Setting
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
This procedure changes the function settings used to control the indoor unit
according to the installation conditions.
Incorrect settings can cause the indoor unit to malfunction.
This procedure should be performed by authorized installation or service personnel only.
Perform the "FUNCTION SETTING"
according to the installation conditions using the remote controller.
(1) Press the set temperature buttons ( ) ( )
and fan control button simultaneously for more than
5 seconds to enter the function setting mode.
(2) Press the SET BACK button to select the indoor unit number.
(3) Press the set time buttons to select the function number.
SUMOTUWETH FR
SET BACK
SUMOTUWETH FR
SA
SA
Unit number of INDOOR UNIT
SUMOTUWETH FR
SA
Function number
(4) Press set temperature buttons ( ) ( ) to select the setting value.
The display flashes as shown to the right during setting value selection.
(5) Press the SET button to confirm the setting.
Press the SET button for a few seconds until the setting
value stops flashing.
If the setting value display changes or if "- -" is displayed
when the flashing stops, the setting value has not been
SUMOTUWETH FR
SA
set correctly.
(An invalid setting value may have been selected for
the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings.
Setting value
Press the set temperature buttons ( ) ( ) and fan
control button simultaneously again for more than 5 secondsto cancel the function setting mode.
In addition, the function setting mode will be automatically canceled after 1 minute
if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
03-04
3-1-4 WIRED REMOTE CONTROLLER
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Wired remote controller
Can be used. ( Do not change.)
1
Dual remote controller setting
2
Filter reset operation and filter display
3
DIP SW
( Duct model is nonfunctional.)
Can be used. ( Do not change.)
4
Can be used. ( Do not change.)
5
Memory backup setting
6
SWITCH POSITION
Wired remote controller
Front case (back side)
OFF
ON
1
2
3
4
5
6
Do not use
this DIP Switch 2
DIP Switch 1
ON
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch 1 No.2 according to the following table.
(Factory setting)
Number of
remote
controller
1 (Normal)
Master unitSlave unit
DIP-SW 1
No.2
OFF
DIP-SW 1
No.2
2 (Dual)
1-2 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
(Factory setting)
DIP-SW
No.6
OFF
ONValidity
Memory backup
OFF
Invalidity
ON
03-05
3-2. THERMISTOR RESISTANCE VALUES
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
3-2-1 Indoor unit
Room temperature thermistor
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
58.25
44.03
33.62
25.92
20.17
15.84
12.54
10.00
8.04
6.51
5.30
4.35
Voltage(V)Resistance(K )Tempe C
1.15
1.39
1.66
1.94
2.22
2.50
2.77
3.03
3.27
3.48
3.68
3.85
Indoor heat exchanger thermistor
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
312.27
233.21
176.03
134.23
103.34
80.28
62.91
49.70
39.57
31.74
25.64
20.85
17.06
14.05
11.64
9.69
8.12
6.83
5.78
4.91
4.19
3.59
3.09
2.67
2.32
2.02
1.76
Voltage(V)Resistance(K )Tempe C
0.69
0.88
1.10
1.36
1.63
1.92
2.21
2.51
2.79
3.06
3.30
3.53
3.73
3.90
4.05
4.19
4.30
4.40
4.48
4.55
4.61
4.66
4.71
4.75
4.78
4.81
4.83
3-2-2 Outdoor unit
Discharge thermistor
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
1013.11
729.09
531.56
392.31
292.91
221.09
168.60
129.84
100.91
79.12
62.55
49.84
40.01
32.35
26.34
21.58
17.79
14.75
12.30
10.32
8.69
7.36
6.27
5.36
4.60
3.96
3.43
2.98
2.60
2.27
2.00
Voltage(V)Resistance(K )Tempe C
0.06
0.09
0.12
0.16
0.21
0.28
0.36
0.46
0.57
0.71
0.86
1.03
1.23
1.43
1.65
1.88
2.11
2.34
2.57
2.79
3.00
3.19
3.37
3.54
3.69
3.83
3.96
4.07
4.17
4.26
4.33
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
1013.11
729.09
531.56
392.31
292.91
221.09
168.60
129.84
100.91
79.12
62.55
49.84
40.01
32.35
26.34
21.58
17.79
14.75
12.30
10.32
8.69
7.36
6.27
5.36
4.60
3.96
3.43
2.98
2.60
2.27
2.00
Voltage(V)Resistance(K )Tempe C
0.06
0.09
0.12
0.16
0.21
0.28
0.36
0.46
0.57
0.71
0.86
1.03
1.23
1.43
1.65
1.88
2.11
2.34
2.57
2.79
3.00
3.19
3.37
3.54
3.69
3.83
3.96
4.07
4.17
4.26
4.33
Compressor temperature thermistor
03-06
Outdoor heat exchanger thermistor
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
95.57
68.89
50.31
37.19
27.81
21.02
16.05
12.38
9.63
7.56
5.98
4.77
3.84
3.11
2.53
2.08
1.71
1.42
1.19
1.00
0.84
0.71
0.61
Voltage(V)Resistance(K )Tempe C
0.24
0.32
0.43
0.57
0.73
0.92
1.14
1.39
1.65
1.93
2.21
2.49
2.77
3.02
3.26
3.48
3.67
3.85
4.00
4.13
4.25
4.35
4.43
Outdoor Temprature thermistor
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
200.20
144.32
105.38
77.90
58.25
44.03
33.62
25.92
20.17
15.84
12.54
10.00
8.04
6.51
5.30
4.35
3.59
2.98
2.49
2.09
1.76
1.49
1.27
Voltage(V)Resistance(K )Tempe C
0.80
1.05
1.33
1.65
1.98
2.33
2.66
2.98
3.27
3.54
3.77
3.96
4.13
4.27
4.39
4.49
4.57
4.64
4.70
4.74
4.78
4.81
4.84
Heat sink thermistor
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
94.26
67.95
49.62
36.68
27.42
20.73
15.83
12.21
9.50
7.46
5.90
4.71
3.78
3.06
2.50
2.05
1.69
1.40
1.17
0.98
0.83
0.70
0.60
0.51
0.44
Voltage(V)Resistance(K )Tempe C
0.08
0.11
0.15
0.20
0.26
0.34
0.43
0.55
0.68
0.84
1.01
1.21
1.42
1.64
1.88
2.11
2.35
2.58
2.81
3.02
3.22
3.41
3.57
3.73
3.87
03-07
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
February. 2014 Printed in Japan
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.