Fujitsu ARYG72LHTA, ARYG90LHTA, AOYG72LRLA, AOYG90LRLA Design & Technical Manual

AIR CONDITIONER
Duct type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ARYG72LHTA ARYG90LHTA
AOYG72LRLA AOYG90LRLA
DR_AR012EF_05
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2017, 2018 Fujitsu General Limited. All rights reserved.
CONTENTS
Part 1. INDOOR UNIT...........................................................................1
1. Product features............................................................................................2
1-1. System outline .................................................................................................................2
2. Specifications................................................................................................3
3. Dimensions....................................................................................................4
3-1. Models: ARYG72LHTA and ARYG90LHTA..................................................................... 4
3-2. Installation space requirement ......................................................................................... 5
3-3. Maintenance space requirement...................................................................................... 6
4. Wiring diagrams ............................................................................................7
4-1. Model: ARYG72LHTA......................................................................................................7
4-2. Model: ARYG90LHTA......................................................................................................8
5. Capacity table................................................................................................9
5-1. Cooling capacity...............................................................................................................9
5-2. Heating capacity ............................................................................................................10
6. Fan performance .........................................................................................11
6-1. Fan performance curve.................................................................................................. 11
6-2. Airflow............................................................................................................................15
7. Operation noise (sound pressure).............................................................17
7-1. Noise level curve............................................................................................................17
7-2. Sound level check point.................................................................................................18
8. Electrical characteristics ............................................................................19
9. Safety devices .............................................................................................20
10. External input and output...........................................................................21
10-1.External input................................................................................................................22
10-2.External output..............................................................................................................23
10-3.Combination of external input and output......................................................................24
10-4.Details of function .........................................................................................................26
11. Remote controller .......................................................................................32
11-1.Wired remote controller.................................................................................................32
12. Function settings ........................................................................................35
12-1.Function settings on indoor unit .................................................................................... 35
12-2.Function settings by using remote controller.................................................................37
13. Accessories .................................................................................................48
14. Optional parts..............................................................................................49
14-1.Controllers ....................................................................................................................49
14-2.Others...........................................................................................................................51
CONTENTS (continued)
Part 2. OUTDOOR UNIT.....................................................................53
1. Specifications..............................................................................................54
2. Dimensions..................................................................................................55
2-1. Models: AOYG72LRLA and AOYG90LRLA................................................................... 55
3. Installation space ........................................................................................56
3-1. Models: AOYG72LRLA and AOYG90LRLA................................................................... 56
4. Refrigerant circuit .......................................................................................59
4-1. Models: AOYG72LRLA and AOYG90LRLA................................................................... 59
5. Wiring diagrams ..........................................................................................60
5-1. Models: AOYG72LRLA and AOYG90LRLA................................................................... 60
6. Capacity compensation rate for pipe length and height difference........61
6-1. Model: AOYG72LRLA.................................................................................................... 61
6-2. Model: AOYG90LRLA.................................................................................................... 62
7. Additional charge calculation ....................................................................63
7-1. Model: AOYG72LRLA.................................................................................................... 63
7-2. Model: AOYG90LRLA.................................................................................................... 63
8. Airflow..........................................................................................................64
8-1. Model: AOYG72LRLA.................................................................................................... 64
8-2. Model: AOYG90LRLA.................................................................................................... 64
9. Operation noise (sound pressure).............................................................65
9-1. Noise level curve............................................................................................................65
9-2. Sound level check point.................................................................................................66
10. Electrical characteristics ............................................................................67
11. Safety devices .............................................................................................68
12. External input and output ..........................................................................69
12-1.External input................................................................................................................69
12-2.External output..............................................................................................................71
13. Function settings .......................................................................................73
13-1.Local setting switch buttons .......................................................................................... 73
13-2.Local setting procedure.................................................................................................75
14. Check and test.............................................................................................77
14-1.Test run.........................................................................................................................77
14-2.Error code .....................................................................................................................79
14-3.Pump down...................................................................................................................80
15. Accessories .................................................................................................82
16. Optional parts..............................................................................................83

Part 1. INDOOR UNIT

DUCT TYPE: ARYG72LHTA ARYG90LHTA

1. Product features

3
4
1
: Power supply [Outdoor Unit] ( )
2
: Piping ( )
3
: Transmission line [O.U. - I.U] ( )
4
: Power supply [Indoor Unit] ( )
5
: Remote controller line [I.U. - R.C.] ( )
1
Earth leakage breaker
Power supply
Circuit breaker (over current)
5
Power supply
Earth leakage breaker
Circuit breaker (over current)
Outdoor unit
2
Indoor unit
φ3 400V~50Hz
φ1230V~50Hz
DUCT TYPE

1-1. System outline

ARYG72-90LHTA
DUCT TYPE
ARYG72-90LHTA
1-1. System outline 1. Product features
- 2 -

2. Specifications

Type
DUCT TYPE
Model name ARYG72LHTA ARYG90LHTA
ARYG72-90LHTA
Power supply 230 V ~ 50 Hz Available voltage range 198—264 V
Capacity
Input power
Current
Power factor
EER Cooling COP Heating 3.40 3.30 Moisture removal L/h (pints/h) 4.5 (7.92) 6.0 (10.56)
Maximum operating current *1
Fan
Static pressure range Pa 50 to 150 (Standard: 72) 50 to 200 (Standard: 72)
Sound pressure level *2
Sound power level
Heat exchanger type
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Drain hose
Operation range
Remote controller type Wired
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.).
• Protective function might work when using it outside the operation range.
• *1: Maximum current:
– The maximum value when operated within the operation range. – The total current of indoor unit and outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Duct
Inverter heat pump
Cooling
Heating
Cooling Heating 0.47 0.53
Fan
Cooling Heating 3.2 3.5 Cooling Heating 63.9 65.8
Airflow rate
Type × Q'ty Sirocco fan × 2 Motor output W 750 1,070
Net Gross 460 × 1,640 × 1,030 Net Gross 80 91
Size
Method Brazing Material PVC Size mm Ø 24.4 (I.D.), Ø 32 (O.D.) (VP25)
Rated
Min.—Max.
Rated
Min.—Max.
Rated kW
HIGH MED 450 470 LOW 320 350 QUIET 210 250
Rated A
Cooling Heating 4.6 6.0
Cooling
Heating
Cooling
Heating
Cooling Heating 80 80
Dimensions (H × W × D)
Fin pitch 1.3
Rows × Stages 3 × 26
Pipe type Copper Fin type Aluminium Material Steel Color
Liquid Gas Ø 25.40 (Ø 1)
Cooling
Heating °C 16 to 30
HIGH MED 3,900 3,900 LOW 3,450 3,450 QUIET 3,000 3,000 HIGH 4,300 4,300 MED 3,900 3,900 LOW 3,450 3,450 QUIET 3,000 3,000
HIGH MED 43 44 LOW 41 42 QUIET 39 40 HIGH 46 47 MED 43 44 LOW 41 42 QUIET 39 40
kW 19.0 22.0
Btu/h 64,800 75,000
kW 8.40 —20.90 10.30—24.20
Btu/h 28,600 —71,300 35,100 —82,500
kW 22.4 27.0
Btu/h 76,400 92,100
kW 7.20—24.60 8.50—29.70
Btu/h 24,500 —83,900 29,000—101,300
W
%
kW/kW
A
m3/h
dB (A)
dB (A)
mm
mm
kg
mm (in)
°C 18 to 32
%RH 80 or less
0.47 0.53
580 640
3.2 3.5
63.9 65.8
2.94 2.83
4.6 6.0
4,300 4,300
46 47
79 79
546 × 1,158 × 39.9
360 × 1,400 × 850
69 80
Ø 12.70 (Ø 1/2)
Sub: (252 × 1,158 × 13.3) × 2
Main: 546 × 1,158 × 39.9
Main: 1.3 Sub: 1.45
Main: 3 × 26
Sub: (1 × 12) × 2
DUCT TYPE
ARYG72-90LHTA
- 3 -
2. Specifications

3. Dimensions

Unit: mm
Gas pipe
Drain port
Control box
Liquid pipe
Air
Side view (R)Top viewSide view (L)
Front view
Rear view
90
88
DUCT TYPE

3-1. Models: ARYG72LHTA and ARYG90LHTA

ARYG72-90LHTA
DUCT TYPE
ARYG72-90LHTA
3-1. Models: ARYG72LHTA and ARYG90LHTA 3. Dimensions
- 4 -

3-2. Installation space requirement

Unit: mm
450 or more
500 or more
150 or
more
20 or more
2,500 or more
(When no ceiling)
Unit: mm
500 or more
150 or
more
20 or more
20 or more
2,500 or more
(When no ceiling)
DUCT TYPE
ARYG72-90LHTA
¢ Models: ARYG72LHTA and ARYG90LHTA
Provide sufficient installation space for product safety.
Installation by which service space is made on top of the unit (recommended):
Installation by which service is carried out from the bottom of the unit:
DUCT TYPE
ARYG72-90LHTA
3-2. Installation space requirement 3. Dimensions
- 5 -

3-3. Maintenance space requirement

AIR
Service access
700 or more
700 or more
500 or more
Control box
Bottom view
Unit: mm
Bottom view
Service access
2,000 or more
100
500 or more
500 or more
AIR
Unit: mm
For future maintenance and service access, provide sufficient maintenance space.
DUCT TYPE
ARYG72-90LHTA
¢ Models: ARYG72LHTA and ARYG90LHTA
NOTE:
Do not place any wiring or illumination in the maintenance space, as they will impede ser­vice.
DUCT TYPE
ARYG72-90LHTA
3-3. Maintenance space requirement 3. Dimensions
- 6 -

4. Wiring diagrams

I/O PCB, WLAN adapter, Converter etc.
DUCT TYPE

4-1. Model: ARYG72LHTA

ARYG72-90LHTA
DUCT TYPE
ARYG72-90LHTA
4-1. Model: ARYG72LHTA 4. Wiring diagrams
- 7 -

4-2. Model: ARYG90LHTA

I/O PCB, WLAN adapter, Converter etc.
DUCT TYPE
ARYG72-90LHTA
DUCT TYPE
ARYG72-90LHTA
4-2. Model: ARYG90LHTA 4. Wiring diagrams
- 8 -

5. Capacity table

DUCT TYPE
ARYG72-90LHTA

5-1. Cooling capacity

¢ Model: ARYG72LHTA
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP)
DUCT TYPE
ARYG72-90LHTA
AFR
°CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
°CDB
-15 17.44 14.30 2.86 19.42 14.39 2.91 20.08 15.64 2.93 21.40 15.70 2.96 22.07 16.94 2.97 23.39 16.88 3.01 24.72 17.99 3.03
-10 17.26 14.16 2.87 19.23 14.25 2.92 19.88 15.49 2.93 21.20 15.53 2.96 21.85 16.78 2.98 23.16 16.71 3.01 24.48 17.80 3.03 0 17.10 14.03 3.06 19.05 14.11 3.10 19.69 15.34 3.12 20.99 15.39 3.15 21.64 16.61 3.17 22.95 16.55 3.20 24.24 17.63 3.23 5 17.06 13.99 3.19 19.01 14.07 3.24 19.65 15.30 3.26 20.94 15.34 3.29 21.60 16.58 3.31 22.89 16.51 3.35 24.19 17.59 3.38
10 16.88 13.97 3.59 18.81 14.05 3.65 19.44 15.27 3.67 20.72 15.33 3.70 21.37 16.55 3.72 22.65 16.49 3.76 23.94 17.56 3.80 15 16.40 13.80 3.71 18.25 14.03 3.77 18.89 15.25 3.79 20.12 15.30 3.83 20.74 16.53 3.85 21.99 16.46 3.88 23.23 17.52 3.93 20 16.62 13.93 4.13 18.50 14.17 4.20 19.14 15.40 4.21 20.40 15.45 4.26 21.03 16.69 4.28 22.29 16.62 4.33 23.56 17.70 4.36 25 16.78 13.94 4.90 18.69 14.18 4.98 19.33 15.41 5.00 20.61 15.46 5.05 21.24 16.71 5.08 22.52 16.64 5.13 23.79 17.72 5.18
Outdoor temperature
30 16.45 13.25 5.60 18.33 13.47 5.67 18.96 14.65 5.70 20.19 14.69 5.77 20.82 15.87 5.79 22.07 15.81 5.84 23.32 16.85 5.91 35 15.01 12.95 6.24 16.72 13.24 6.33 17.29 14.40 6.37 18.43 14.44 6.43 19.00 15.60 6.46 20.14 15.53 6.53 21.28 16.55 6.59 40 14.86 12.23 5.91 16.55 12.58 5.99 17.12 13.68 6.03 18.25 13.72 6.08 18.81 14.82 6.11 19.94 14.77 6.18 21.07 15.72 6.24 46 11.84 11.08 5.76 13.19 11.90 5.83 13.63 12.61 5.87 14.52 12.98 5.93 14.98 14.02 5.96 15.89 13.96 6.02 16.78 14.86 6.07
kW kW kW kW kW kW kW
m3/h
Indoor temperature
4,300
¢ Model: ARYG90LHTA
AFR
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
°CDB
-15 20.19 16.22 3.44 22.49 16.33 3.50 23.25 17.75 3.52 24.78 17.81 3.56 25.55 19.23 3.57 27.08 19.15 3.62 28.62 20.41 3.65
-10 19.98 16.06 3.46 22.27 16.16 3.51 23.02 17.58 3.52 24.55 17.63 3.56 25.30 19.04 3.58 26.82 18.96 3.62 28.34 20.20 3.65 0 19.80 15.91 3.68 22.05 16.01 3.73 22.80 17.40 3.76 24.30 17.46 3.79 25.05 18.85 3.82 26.57 18.77 3.85 28.07 20.00 3.89 5 19.75 15.88 3.84 22.01 15.96 3.90 22.75 17.36 3.93 24.25 17.41 3.96 25.01 18.81 3.99 26.51 18.73 4.02 28.01 19.95 4.06
10 19.55 15.85 4.32 21.78 15.94 4.38 22.51 17.33 4.41 24.00 17.39 4.45 24.74 18.77 4.48 26.23 18.71 4.52 27.71 19.92 4.57 15 18.99 15.66 4.47 21.14 15.92 4.53 21.87 17.31 4.56 23.30 17.35 4.60 24.02 18.75 4.63 25.47 18.68 4.67 26.90 19.88 4.72 20 19.24 15.81 4.97 21.42 16.08 5.05 22.17 17.48 5.07 23.62 17.53 5.12 24.35 18.94 5.15 25.81 18.86 5.20 27.28 20.09 5.25 25 19.42 15.82 5.90 21.64 16.08 5.99 22.39 17.49 6.02 23.86 17.54 6.08 24.60 18.96 6.11 26.07 18.88 6.17 27.55 20.11 6.23
Outdoor temperature
30 19.05 15.03 6.73 21.22 15.29 6.82 21.95 16.62 6.86 23.38 16.67 6.93 24.11 18.01 6.97 25.55 17.94 7.03 27.00 19.12 7.11 35 17.38 14.69 7.50 19.35 15.02 7.61 20.02 16.34 7.66 21.35 16.39 7.74 22.00 17.70 7.77 23.32 17.63 7.85 24.65 18.78 7.93 40 17.21 13.87 7.10 19.17 14.27 7.20 19.82 15.52 7.26 21.13 15.57 7.31 21.78 16.82 7.35 23.09 16.76 7.43 24.39 17.84 7.51 46 13.70 12.57 6.92 15.27 13.50 7.01 15.78 14.31 7.06 16.81 14.73 7.13 17.35 15.91 7.17 18.39 15.84 7.24 19.42 16.86 7.31
kW kW kW kW kW kW kW
m3/h
Indoor temperature
4,300
5-1. Cooling capacity 5. Capacity table
- 9 -

5-2. Heating capacity

DUCT TYPE
ARYG72-90LHTA
¢ Model: ARYG72LHTA
¢ Model: ARYG90LHTA
NOTE:
AFR
°CDB °CWB
Outdoor temperature
AFR
°CDB °CWB
Outdoor temperature
Values mentioned in the table are calculated based on the maximum capacity.
m3/h
Indoor temperature
°CDB 16 18 20 22 24
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-20 -21 10.58 5.57 10.32 5.68 10.07 5.80 9.82 5.91 9.57 6.02
-15 -16 16.21 6.42 15.83 6.56 15.44 6.69 15.06 6.82 14.68 6.96
-10 -11 18.89 6.82 18.44 6.96 18.00 7.10 17.55 7.25 17.10 7.39
-5 -7 20.98 7.11 20.48 7.26 19.98 7.41 19.48 7.56 18.99 7.70 0 -2 22.62 7.19 22.08 7.34 21.54 7.49 21.00 7.63 20.47 7.78 5 3 25.56 7.20 24.95 7.35 24.35 7.50 23.73 7.64 23.13 7.79 7 6 25.83 7.21 25.22 7.36 24.60 7.51 23.99 7.66 23.37 7.81
10 8 27.04 7.16 26.39 7.30 25.74 7.46 25.09 7.60 24.46 7.76 15 10 28.06 7.16 27.39 7.30 26.72 7.45 26.05 7.61 25.38 7.71 20 15 25.25 6.25 24.64 6.37 24.04 6.50 23.44 6.64 22.83 6.72 24 18 25.81 6.21 25.19 6.33 24.58 6.47 23.96 6.61 23.35 6.69
m3/h
Indoor temperature
°CDB 16 18 20 22 24
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-20 -21 12.77 6.65 12.47 6.79 12.16 6.93 11.86 7.07 11.56 7.19
-15 -16 19.57 7.68 19.11 7.84 18.64 8.00 18.18 8.16 17.72 8.31
-10 -11 22.81 8.16 22.27 8.32 21.73 8.49 21.19 8.66 20.65 8.83
-5 -7 25.33 8.50 24.73 8.68 24.12 8.86 23.52 9.03 22.92 9.21 0 -2 27.31 8.59 26.66 8.77 26.00 8.95 25.35 9.13 24.71 9.29 5 3 30.86 8.61 30.12 8.79 29.39 8.97 28.65 9.13 27.92 9.27 7 6 31.19 8.62 30.44 8.80 29.70 8.98 28.96 9.16 28.22 9.28
10 8 32.64 8.56 31.86 8.73 31.08 8.92 30.29 9.09 29.53 9.28 15 10 33.88 8.56 33.07 8.72 32.26 8.91 31.45 9.10 30.65 9.22 20 15 30.48 7.47 29.75 7.61 29.02 7.77 28.30 7.94 27.57 8.04 24 18 31.16 7.43 30.42 7.57 29.67 7.73 28.93 7.90 28.20 8.00
4,300
4,300
DUCT TYPE
ARYG72-90LHTA
5-2. Heating capacity 5. Capacity table
- 10 -

6. Fan performance

Airflow
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_1
Hi (SP mode15)
SP mode15
upper limit
Qu (SP mode15)
SP mode15
lower limit
Normal SP
upper limit
Normal SP lower limit
Hi (Normal SP)
Qu (Normal SP)
[l/s]
[m
3
/h]
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
[l/s]
[m
3
/h]
Airflow
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
Fan performance curve_2
(For function setting by remote controller)
Hi (SP mode13,14,15)
Hi (SP mode11)
Hi (SP mode09)
Hi (Normal SP)
Hi (SP mode07)
Hi (SP mode05)
Hi (SP mode12)
Hi (SP mode10)
Hi (SP mode08)
Hi (SP mode06)
DUCT TYPE

6-1. Fan performance curve

ARYG72-90LHTA
¢ Model: ARYG72LHTA
DUCT TYPE
ARYG72-90LHTA
NOTES:
• Setting of the external static pressure is switchable into modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static
• The default setting is set at "Normal SP".
6-1. Fan performance curve 6. Fan performance
pressure with referring “Fan performance curve_2” above.
- 11 -
[l/s]
[m
3
/h]
Airflow
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
100
105
95
Capacity [%]
DUCT TYPE
ARYG72-90LHTA
Characteristics of air volume and capacity
• Cooling
• Heating
DUCT TYPE
ARYG72-90LHTA
6-1. Fan performance curve 6. Fan performance
- 12 -
¢ Model: ARYG90LHTA
[l/s]
[m
3
/h]
Airflow
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
Fan performance curve_1
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
Hi (SP mode20)
Normal SP lower limit
Hi (Normal SP)
Qu (Normal SP)
Qu (SP mode20)
Normal SP
upper limit
SP mode20
lower limit
SP mode20 upper limit
[l/s]
[m
3
/h]
Airflow
0
280
300
260
240
220
200
180
160
140
120
100
80
60
40
20
External Static Pressure [Pa]
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
Fan performance curve_2
(For function setting by remote controller)
Hi (SP mode11)
Hi (SP mode09)
Hi (Normal SP)
Hi (SP mode07)
Hi (SP mode05)
Hi (SP mode12)
Hi (SP mode10)
Hi (SP mode08)
Hi (SP mode06)
Hi (SP mode20)
Hi (SP mode18)
Hi (SP mode16)
Hi (SP mode14)
Hi (SP mode19)
Hi (SP mode17)
Hi (SP mode15)
Hi (SP mode13)
DUCT TYPE
ARYG72-90LHTA
DUCT TYPE
ARYG72-90LHTA
NOTES:
• Setting of the external static pressure is switchable into modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pressure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal SP".
6-1. Fan performance curve 6. Fan performance
- 13 -
[l/s]
[m
3
/h]
Airflow
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
100
105
95
Capacity [%]
[l/s]
[m
3
/h]
Airflow
1,389556 695 833 972
1,111
1,250
2,000 2,500 3,000 3,500
4,000
4,500 5,000
100
105
95
Capacity [%]
DUCT TYPE
ARYG72-90LHTA
Characteristics of air volume and capacity
• Cooling
• Heating
DUCT TYPE
ARYG72-90LHTA
¢ Automatic airflow adjustment procedures
1. To start the auto setting, use No.32 of setting value in Function Number 26.
2. Run the air conditioner on fan mode (High). * For instructions on how to operate the air conditioner, refer to the operation manual of the remote controller.
During automatic airflow adjustment, the mode will be fixed at fan (High). When this function is active, do not operate the outdoor unit.
3. The air conditioner will run for about 1 to 8 min then stop automatically. * Do not change the throttles of the inlet and outlet ports during operation.
When used in a group control system, the setting will take about 10 min.
4. Turn the air conditioner off and on again.
5. Check the setting value of Function 26. * If the setting value has not changed, repeat the procedure from step 2.
CAUTION
When the duct or outlet installations are changed after the Automatic airflow adjustment is complet­ed, repeat the procedure from step 1.
6-1. Fan performance curve 6. Fan performance
- 14 -

6-2. Airflow

¢ Model: ARYG72LHTA
DUCT TYPE
ARYG72-90LHTA
Cooling
Fan speed Airflow
Heating
HIGH
MED
LOW
QUIET
m3/h
l/s 1.195
CFM 2,531
m3/h
l/s 1,083
CFM 2,296
m3/h
l/s 958
CFM 2,031
m3/h
l/s 833
CFM 1,766
4,300
3,900
3,450
3,000
DUCT TYPE
ARYG72-90LHTA
Fan speed Airflow
m3/h
HIGH
MED
LOW
QUIET
l/s 1.195
CFM 2,531
m3/h
l/s 1,083
CFM 2,296
m3/h
l/s 958
CFM 2,031
m3/h
l/s 833
CFM 1,766
4,300
3,900
3,450
3,000
6-2. Airflow 6. Fan performance
- 15 -
¢ Model: ARYG90LHTA
DUCT TYPE
ARYG72-90LHTA
Cooling
Fan speed Airflow
Heating
Fan speed Airflow
HIGH
MED
LOW
QUIET
HIGH
MED
LOW
QUIET
m3/h
l/s 1.195
CFM 2,531
m3/h
l/s 1,083
CFM 2,296
m3/h
l/s 958
CFM 2,031
m3/h
l/s 833
CFM 1,766
m3/h
l/s 1.195
CFM 2,531
m3/h
l/s 1,083
CFM 2,296
m3/h
l/s 958
CFM 2,031
m3/h
l/s 833
CFM 1,766
4,300
3,900
3,450
3,000
4,300
3,900
3,450
3,000
DUCT TYPE
ARYG72-90LHTA
6-2. Airflow 6. Fan performance
- 16 -

7. Operation noise (sound pressure)

Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Quiet
High
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
High
Quiet
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Quiet
High
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Quiet
High
DUCT TYPE

7-1. Noise level curve

ARYG72-90LHTA
¢ Model: ARYG72LHTA
Cooling
Heating
DUCT TYPE
ARYG72-90LHTA
¢ Model: ARYG90LHTA
Cooling
7-1. Noise level curve 7. Operation noise (sound pressure)
Heating
- 17 -

7-2. Sound level check point

Front view
Microphone
Side view
Product
Air
1.5 m
2 m 1 m
Microphone
Measuring duct (Set the static pressure as rating in this area.)
Measuring duct
DUCT TYPE
ARYG72-90LHTA
DUCT TYPE
ARYG72-90LHTA
7-2. Sound level check point 7. Operation noise (sound pressure)
- 18 -

8. Electrical characteristics

DUCT TYPE
ARYG72-90LHTA
Model name ARYG72LHTA ARYG90LHTA
Power supply
Voltage V 230 ~ Frequency Hz 50
Max operating current A 4.6 6.0
Circuit breaker current A 15
2
mm
2
mm
m 101
1.5
1.5
Wiring spec. *1
Power cable
Connection cable *2
Limited wiring length
*1: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As the regulations of wire size and circuit breaker differ in each country or region, select appropriate de­vices complied to the regional standard.
*2: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
DUCT TYPE
ARYG72-90LHTA
- 19 -
8. Electrical characteristics

9. Safety devices

DUCT TYPE
ARYG72-90LHTA
Type of protection Protection form
Model
ARYG72LHTA ARYG90LHTA
Circuit protection Current fuse (PCB*)
250 V, 10 A 250 V, 20 A
250 V, 3.15 A
Fan motor protection Current protection 12.9 A 19.3 A
*: Printed Circuit Board
DUCT TYPE
ARYG72-90LHTA
- 20 -
9. Safety devices

10. External input and output

Y1 Y2 Y3 1 2Y1 Y2 Y3 1 2
Terminal
(External in)
CN71 (Drain pump)
CN9 (Float switch)
CN47 (External out)
CN65
(External in/out PCB)
CN8 (Remote sensor)
CN48 (IR receiver)
Rotary switch
SW2 SW1
Fig. External input and output PCB
Fig. Indoor unit PCB
DUCT TYPE
ARYG72-90LHTA
PCB External input External output Connector Input select
Operation/Stop Forced stop
- Terminal Dry contact Edge -
Operation status
Indoor unit
-
Error status Indoor unit fan
operation status
CN47 - - UTY-XWZXZG
External heater output
Input 1/
Input 2
Input 1 Edge
Dry contact/
Apply voltage
Output 1 Output 2 Output 3
External input
and output
(UTY-XCSX)
Operation/Stop
Forced thermostat off
-
-
Operation status Error status Indoor unit status External heater
output
External
Input
signal
connect kit
(Optional
parts)
Edge/
Pulse
- - -
DUCT TYPE
ARYG72-90LHTA
-
- 21 -
10. External input and output

10-1. External input

1
2

Terminal
1
2
C
Input 1 Input 2
PCB
Connected unit
 
+
+
-
1
2
C
Input 1 Input 2 Power supply
PCB
Connected unit
 

+-
DUCT TYPE
ARYG72-90LHTA
¢
¢
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
External input and output PCB
The indoor unit Operation/Stop can be set by using the input terminal on the PCB.
Input select
DUCT TYPE
ARYG72-90LHTA
Use either one of these types of terminals according to the application. (Both types of terminals cannot be used simultaneously.)
• Dry contact In case of internal power supply, set the slide switch of SW1 to "NON VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
• Apply voltage In case of external power supply, set the slide switch of SW1 to "VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA. *2: Make the power supply DC 12 V to 24 V 10 mA or more.
10-1. External input 10. External input and output
- 22 -

10-2. External output

1
2
CN47
LED
PCB
Resistor
Connected unit
+
-
1
2
Connected device
CN47
PCB
Connected unit Relay
(Operation status)
-
+
1
2
3
4
5
6
Power supply
Power supply
Power supply
PCB
Connected device 1
(Operation status)
Connected device 2 (Error status)
(Indoor unit fan
operation status)
Connected device 3
Example
DUCT TYPE
ARYG72-90LHTA
¢
Use an external output cable with appropriate external dimension, depending on the number of ca­bles to be installed.
Indoor unit
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 24.
When indicator, etc. are connected directly
DUCT TYPE
ARYG72-90LHTA
Example:
Function setting 60 is set to "00"
When connecting with a device equipped with a power supply
Example:
External input and output PCB
¢
Function setting 60 is set to "00"
• A twisted pair cable (22AWG) should be used.
• Permissible voltage and current: DC 5 V to 30 V / 3 A, AC 30 V to 250 V / 3 A
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 24.
10-2. External output 10. External input and output
- 23 -

10-3. Combination of external input and output

DUCT TYPE
ARYG72-90LHTA
By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
DUCT TYPE
ARYG72-90LHTA
External input
Mode
0-1 60-00 1 Operation/Stop
0-2 60-00 2 Operation/Stop
1—8
Mode
0-1 60-00 1 Operation/Stop Operation/Stop Error status
0-2 60-00 2 Operation/Stop Error status
1—8
Function
setting
60-01 to
60-08
9 60-09 B Operation/Stop
10 60-10 C Operation/Stop
11 60-11 D Operation/Stop
Function
setting
60-01 to
60-08
9 60-09 B Error status Operation/Stop
10 60-10 C
11 60-11 D
and output
PCB (Rotary
SW)
3 - 9, A (Setting prohibited)
External input
and output
PCB (Rotary
SW)
3 - 9, A (Setting prohibited)
Indoor unit
Input
Terminal Input 1 Input 2 Signal type
Operation/Stop Not available Edge
Operation Stop Pulse
Thermostat OFF
Thermostat OFF
Thermostat OFF
Thermostat OFF
Indoor unit
Output
CN47 Output 1 Output 2 Output 3
Indoor unit fan
operation status
External heater
output
Operation/Stop Error status
Operation/Stop
External input
External input and output PCB
Forced
Forced
Forced
Forced
External output
External input and output PCB
Not available Edge
Not available Edge
Not available Edge
Not available Edge
Indoor unit fan
operation status
Indoor unit fan
operation status
Indoor unit fan
operation status
Indoor unit fan
operation status
External heater
output
External heater
output
External heater
output
Error status
NOTE:
Input of Operation/Stop depends on the setting of function setting 46. 00: Operation/Stop mode 1 (R.C. enabled) 01: (Setting prohibited) 02: Forced stop 03: Operation/Stop mode 2 (R.C. disabled)
10-3. Combination of external input and output 10. External input and output
- 24 -
¢
Edge
Edge
Pulse
The width of pulse must be longer than 200 msec.
DUCT TYPE
ARYG72-90LHTA
Input signal type
• Indoor unit Input signal type is only "Edge".
• External input and output PCB The input signal type can be selected.
Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
DUCT TYPE
ARYG72-90LHTA
10-3. Combination of external input and output 10. External input and output
- 25 -

10-4. Details of function

Operation
Stop
Remote controller
On
Off
Indoor unit
On
Input
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
¢
DUCT TYPE
ARYG72-90LHTA
Control input function
When function setting is "Operation/Stop" mode 1
• In the case of "Edge" input
DUCT TYPE
ARYG72-90LHTA
Function
setting /
46-00
Rotary SW of
External input and
output PCB
- Input of indoor unit Terminal
60-00 / 1
• In the case of "Pulse" input
Function
setting /
46-00 60-00 / 1
Rotary SW of
External input and
output PCB
External input Input signal Command
External input and
output PCB
External input Input signal Command
External input and
output PCB
Off → On Operation On → Off Stop
Input 1
Input 1 Pulse Operation Input 2 Pulse Stop
Off → On Operation On → Off Stop
10-4. Details of function 10. External input and output
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
- 26 -
When function setting is "Forced stop" mode
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On On
Indoor unit
On
Input
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
Input 1
Input 2
On On On
Indoor unit
• In the case of "Edge" input
DUCT TYPE
ARYG72-90LHTA
Function
setting /
Rotary SW of
External input and
output PCB
- Input of indoor unit Terminal
46-02
60-00 / 1
• In the case of "Pulse" input
Function
setting /
46-02 60-00 / 1
Rotary SW of
External input and
output PCB
External input Input signal Command
External input and
output PCB
External input Input signal Command
External input and
output PCB
Off → On Forced stop On → Off Normal
Input 1
Off → On Forced stop On → Off Normal
Input 1 Pulse Forced stop Input 2 Pulse Normal
DUCT TYPE
ARYG72-90LHTA
10-4. Details of function 10. External input and output
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re­mote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
- 27 -
When function setting is "Operation/Stop" mode 2
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On OnOff
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
(R.C. disabled)
Off
On
• In the case of "Edge" input
DUCT TYPE
ARYG72-90LHTA
Function
setting /
Rotary SW of
External input and
output PCB
- Input of indoor unit Terminal
46-03
60-00 / 1
• In the case of "Pulse" input
External input Input signal Command
External input and
output PCB
Input 1
Off → On Operation
On → Off
Stop (R.C.
disabled)
Off → On Operation
On → Off
Stop (R.C.
disabled)
DUCT TYPE
ARYG72-90LHTA
Function
setting /
46-03 60-00 / 1
Rotary SW of
External input and
output PCB
External input Input signal Command
External input and
output PCB
Input 1 Pulse Operation
Input 2 Pulse
NOTES:
• When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
Stop (R.C.
disabled)
10-4. Details of function 10. External input and output
- 28 -
Forced thermostat off function
On Off
On
Off
Compressor
Room temp.
Set temp.
Input
Operation
Stop
High
Low
CN47
On
Off
Output 1
Indoor unit
¢
DUCT TYPE
ARYG72-90LHTA
¢
Function
setting /
Rotary SW of External
input and output PCB
60-00 / 2 60-09 / B 60-10 / C 60-11 / D
Control output function
Function
setting /
Rotary SW of External
input and output PCB
60-00 / 1, 2 Output of indoor unit CN47
60-00 / 1 60-09 / B 60-10 / C 60-11 / D
External input Input signal Command
External input and output
PCB
External output Output signal Command
External input and output
PCB
Input 1
Output 1
Off → On Thermostat off
On → Off
Normal
operation
Low → High Operation High → Low Stop
Off → On Operation
On → Off Stop
DUCT TYPE
ARYG72-90LHTA
The output is low when the unit is stopped.
10-4. Details of function 10. External input and output
- 29 -
Error status
Error
Normal
High
Low
CN47
On
Off
Output 1, 2, 3
Indoor unit
Fan run
Fan stop
High
Low
CN47
On
Off
Output 2, 3
Indoor unit
¢
DUCT TYPE
ARYG72-90LHTA
Function
setting /
Rotary SW of External
input and output PCB
External output Output signal Command
60-09 / B Output of indoor unit CN47
60-00 / 2
60-00 / 1 60-10 / C
External input and output
PCB
60-11 / D Output 3
The output is ON when an error is generated for the indoor unit.
Output 1
Output 2
Low → High Error High → Low Normal
Off → On Error On → Off Normal Off → On Error On → Off Normal Off → On Error On → Off Normal
DUCT TYPE
ARYG72-90LHTA
Indoor unit fan operation status
¢
Function
setting /
Rotary SW of External
input and output PCB
External output Output signal Command
60-10 / C Output of indoor unit CN47
60-00 / 2 60-09 / B 60-11 / D
External input and output
PCB
60-00 / 1 Output 3
Output signal Condition
On
Low → High
The indoor unit fan is operating.
Off The fan is stopped or during cold air prevention.
High → Low During thermostat off when in dry mode operation.
Output 2
Low → High Fan run High → Low Fan stop
Off → On Fan run
On → Off Fan stop
Off → On Fan run On → Off Fan stop
10-4. Details of function 10. External input and output
- 30 -
External heater output
Off
Off
On
Tr-Ts
Tr-Ts=-1 °C
Tr-Ts=-10 °C
Tr-Ts=-3 °C
Tr-Ts=-12 °C
¢
DUCT TYPE
ARYG72-90LHTA
Function
setting /
Output signal Condition
Low → High
Off → On
High → Low
On → Off • Error occurred
Rotary SW of External
input and output PCB
60-11 / D Output of indoor unit CN47
60-00 / 2 60-09 / B 60-10 / C
Heater turns on as shown in diagram of heating temperature
Heater turns off as shown in diagram of heating temperature
• Other than Heating mode
• Forced thermo off
• Fan stop protection
External input and output
External output Output signal Command
PCB
Output 3
Specifications of the signal output performance are as shown as follows:
Example:
When set temperature (Ts) is set at 22 °C;
• And room temperature (Tr) increase above 12 °C, signal output is on.
• And Tr increase above 21 °C, signal output is off.
• And Tr decrease below 19 °C, signal output is on.
• And Tr decrease below 10 °C, signal output is off.
Low → High Heater on High → Low Heater off
Off → On Heater on
On → Off Heater off
DUCT TYPE
ARYG72-90LHTA
The output also turns off in defrost operation.
10-4. Details of function 10. External input and output
- 31 -

11. Remote controller

a
b
c
d
ef
i
j
h
g
o
m
n
lk
Monitor mode screen
(Example: Airflow direction setting)
Setting screen
Auto
High
Med Low Quiet
Auto
Cool
Dry Fan Heat
DUCT TYPE

11-1. Wired remote controller

ARYG72-90LHTA
¢
Display panel
Overview
a LED lamp (Operation indicator)
Lights while the indoor unit is operating. Blinks when an error occurred.
b FAN button
Each time the button is pressed, fan speed switches as follows:
c +, - buttons (Set temperature buttons)
Used to adjust temperature in Monitor mode screen. + button: Raise
- button: Lower In Setting screen, used to select the setting items. NOTE: When the operation mode is set to FAN, the tem­perature cannot be adjusted.
d ENTER button
Used to enter setting items and settings.
e Room temperature sensor (inside)
Senses ambient temperature of unit.
f <, > buttons
Used to select setting items during the setting item selec­tion screen is displayed.
g MENU button
Used to display the setting item selection screen.
h MODE button
Each time the button is pressed, operation mode switches as follows:
DUCT TYPE
ARYG72-90LHTA
i On/Off button
Starts or stops the operation. NOTE: On/Off button cannot be operated at screens other than the Monitor mode screen.
NOTE:
For individual icons in Setting screen and related functions, refer to the oper­ation manual.
j Display panel
Displays Monitor mode screen or Setting screen. Monitor mode screen is home screen of this controller, and the basic operation is performed in this screen. In Setting screen, several settings are adjustable.
k Temperature indicator l Fan speed indicator m Clock indicator n Airflow direction indicator o Operation mode indicator
11-1. Wired remote controller 11. Remote controller
- 32 -
System diagram
A
Indoor unit
Remote controller
Primary
Secondary
BC
Indoor unit
Remote controllers
When there is a functional grounding
Remote controller
Indoor unit
Y1Y1Y2Y2Y3
When there is a functional grounding
Remote controller Remote controller
Y1
Y1Y2Y2
Y1 Y2
Y3
Indoor unit
When there is a functional grounding
Remote controller
Indoor units
Y2
Y2 Y2 Y2 Y2Y3 Y3 Y3 Y3
Y1
Y1 Y1 Y1 Y1
¢
DUCT TYPE
ARYG72-90LHTA
¢
1 remote controller:
Electrical wiring
1 remote controller:
2 remote controllers:
2 remote controllers:
A, B, C: Remote controller cable
A ≤ 500 m;B + C ≤ 500 m
DUCT TYPE
ARYG72-90LHTA
Group control:
NOTES:
• Group connection with simultaneous multi system is not allowed.
• Group control with Polar 3-wired remote controller is not allowed.
11-1. Wired remote controller 11. Remote controller
- 33 -
Specifications
Side view Rear viewFront view
Hole: 9 × 4.5
Hole: 6 × 4.5
Hole: 12.5 × 4.5
30 33
23
15.3
83.5
45.3
63.5
17
120
120
¢
Dimensions and other specifications on the wired remote controller are as follows.
DUCT TYPE
ARYG72-90LHTA
Size (H × W × D) mm 120 × 120 × 17 Weight g 170 Power V 12
Unit: mm
DUCT TYPE
ARYG72-90LHTA
Wiring specifications
Use Cable size Wire type Remarks
Remote controller cable
0.33 to 1.25 mm
2
Non-polar 2-core,
Twisted pair
Use sheathed PVC cable.
11-1. Wired remote controller 11. Remote controller
- 34 -

12. Function settings

SW100
1234
SW101
123
DUCT TYPE
ARYG72-90LHTA

12-1. Function settings on indoor unit

¢
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE:
Incorrect settings can cause a product malfunction.
Models: ARYG72LHTA and ARYG90LHTA
By using some components on the PCB, you can change the function settings.
Related components on the PCB and the applicable settings
Component Setting content
1
DIP switch100
DIP switch101
2 3 4 1 Setting change prohibited 2 Setting change prohibited 3 Fan delay setting
Remote controller address setting
DUCT TYPE
ARYG72-90LHTA
Component location
Components on the indoor unit main PCB used for the function settings are located as shown in the following figure.
12-1. Function settings on indoor unit 12. Function settings
- 35 -
00 01 02
Remote controller address
Indoor unit
Remote controller
DUCT TYPE
ARYG72-90LHTA
DIP switch setting
Remote controller address setting (SW100) When operating a number of indoor units by using a wired remote controller, DIP switch set­ting for assigning unit number to each indoor unit is required.
DIP switches are normally set to make the unit number 00.
DUCT TYPE
ARYG72-90LHTA
Remote
DIP switch number
controller
address
1 2 3 4
00 OFF OFF OFF OFF ♦ 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON
Factory setting
Switch 1: Setting change prohibited (SW101)
Switch 2: Setting change prohibited (SW101)
Switch 3: Fan delay setting (SW101) When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor unit fan operation will continue for 1 minute.
Switch 3 Fan delay Factory setting
ON Enabled
OFF Disabled
12-1. Function settings on indoor unit 12. Function settings
- 36 -

12-2. Function settings by using remote controller

” is displayed:
Address automatically
Remote controller address
allocated
Not displayed: Address manually allocated
01 to 32
DUCT TYPE
ARYG72-90LHTA
¢
Some function settings can be changed on the remote controller. After confirming the setting proce­dure and the content of each function setting, select appropriate functions for your installation envi­ronment.
Remote controller address setting
Remote controller address confirmation
DUCT TYPE
ARYG72-90LHTA
NOTE:
The address of this remote controller is set automatically. Do not change the indoor unit remote controller address from the factory setting "0". (Verify that the address is "0".)
1. To activate the address setting mode, hold down the three buttons of “MENU”, “<“, and “EN­TER” at the same time for 2 seconds or longer. Menu 2 setting screen is displayed.
2. Select the “15” in Menu 2 settings. Then press the “ENTER” button.
3. The address of this unit is displayed on the screen.
12-2. Function settings by using remote controller 12. Function settings
Press the “ENTER” button to return to the Menu 2 item selection screen.
- 37 -
” is displayed:
Address automatically
Remote controller address
allocated
Not displayed: Address manually allocated
01 to 32
DUCT TYPE
ARYG72-90LHTA
Setting the remote controller address manually
NOTES:
• Perform manual address setting only when setting the address with an arbitrary number. Indoor unit remote controller address setting is necessary. Set the remote controller address of indoor units connected by the same remote controller cable within a range of 1 to 9 and A (10) to F (15) so that there is no duplication. (Do not set to "0".)
• The address of this unit is set within a range of 1 to 32, but set it so that it does not duplicate the remote controller address of an indoor unit connected by the same remote controller cable.
1. To activate the address setting mode, hold down the three buttons of “MENU”, “<“, and “EN­TER” at the same time for 2 seconds or longer. Menu 2 setting screen is displayed.
DUCT TYPE
ARYG72-90LHTA
2. Select the “15” in Menu 2 settings. Then press the “ENTER” button.
3. The address of this unit is displayed on the screen. Set the unit number with the “+” or “-” but­tons. System number cannot be changed.
Press the “ENTER” button to return to the Menu 2 item selection screen.
12-2. Function settings by using remote controller 12. Function settings
- 38 -
” is displayed:
Address automatically allocated
Not displayed: Address manually allocated
: Not reset
: Reset
DUCT TYPE
ARYG72-90LHTA
Resetting the manual address setting number
1. To activate the address setting mode, hold down the three buttons of “MENU”, “<“, and “EN­TER” at the same time for 2 seconds or longer. Menu 2 setting screen is displayed.
2. Select the “14” in Menu 2 settings. Then press the “ENTER” button.
DUCT TYPE
ARYG72-90LHTA
3. To reset address, select “1: Reset” with the “+” or “-” buttons. If not resetting, press the “MENU” button to the Menu 2 item selection screen.
Press the “ENTER” button to return to the Menu 2 item selection screen.
12-2. Function settings by using remote controller 12. Function settings
- 39 -
Remote controller master/slave setting
: Master : Slave
Number of Master units
¢
DUCT TYPE
ARYG72-90LHTA
NOTE:
Set only one Master remote controller.
1. To activate the address setting mode, hold down the three buttons of “MENU”, “<“, and “EN­TER” at the same time for 2 seconds or longer. Menu 2 setting screen is displayed.
2. Select the “06” in Menu 2 settings. Then press the “ENTER” button.
DUCT TYPE
ARYG72-90LHTA
3. Select the “0: Master” or the “1: Slave” with the “+” or “-” buttons.
4. Press the "ENTER" button. If there is no problem, return to Menu 2 items selection screen. In the case of settings at initial booting, "Monitor mode screen" is displayed.
• There's 0 or more than 2 "Master" units: The number will be displayed.
• "Master" is 0: Press the "ENTER" button to return to the Menu 2 item selection screen.
• "Master" is more than 2: Press the "ENTER" button to return to the screen of step 2.
• "Master" is 0 or more than 2: Press the "MENU" button to return to the Menu 2 item selection
screen.
12-2. Function settings by using remote controller 12. Function settings
- 40 -
¢
Remote controller address
Example: When remote controller address “01” is selected.
Function number
DUCT TYPE
ARYG72-90LHTA
Setting procedure by using wired remote controller
The function number and the associated setting value are displayed on the LCD of the remote con­troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
1. Connect the power supply.
2. To activate the address setting mode, hold down the three buttons of “MENU”, “<“, and “EN­TER” at the same time for 2 seconds or longer. Menu 2 setting screen is displayed.
DUCT TYPE
ARYG72-90LHTA
3. Select the “13” in Menu 2 settings. Then press the “ENTER” button.
4. Pressing the "+" or "-" button, select a remote controller address (select the indoor unit you want to operate). Then press the "ENTER" button.
5. Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button.
12-2. Function settings by using remote controller 12. Function settings
- 41 -
Setting number
Example: Function number 30
Setting number 01
GoodError
When the data was not set up on the indoor unit
Set up the data again.
When the data was normally set up on the indoor unit.
(” --” is displayed.)
DUCT TYPE
ARYG72-90LHTA
6. Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button.
Pressing the "ENTER" button to return to the address selection screen. If setting has been completed, pressing the "MENU" button to return to the Menu 2 item selec-
tion screen.
DUCT TYPE
ARYG72-90LHTA
12-2. Function settings by using remote controller 12. Function settings
- 42 -
¢
DUCT TYPE
ARYG72-90LHTA
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE:
10) 48 Room temperature sensor switching (Aux.)
11) 49 Indoor unit fan control for energy saving for cooling
12) 60 Switching functions for external output terminal
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 11 Filter sign
2) 26 Static pressure
3) 30/31 Room temperature control for indoor unit sensor
4) 35/36 Room temperature control for wired remote controller sensor
5) 40 Auto restart
6) 42 Room temperature sensor switching
7) 43 Cold air prevention
8) 44 Remote controller custom code
9) 46 External input control
DUCT TYPE
ARYG72-90LHTA
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
00 Standard (2,500 hours)
11
01 Long interval (4,400 hours) 02 Short interval (1,250 hours) 03 No indication
12-2. Function settings by using remote controller 12. Function settings
- 43 -
DUCT TYPE
ARYG72-90LHTA
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number Setting value Setting description Factory setting
05 50 Pa 06 60 Pa 07 70 Pa 08 80 Pa 09 90 Pa 10 100 Pa 11 110 Pa 12 120 Pa
26
13 130 Pa 14 140 Pa 15 150 Pa 16 160 Pa 17 170 Pa 18 180 Pa 19 190 Pa 20 200 Pa 31 Standard (72 Pa) ♦ 32 Automatic airflow adjustment
DUCT TYPE
ARYG72-90LHTA
NOTE:
Range of static pressure is different by model.
Type name Setting of static pressure range
72 type 50 to 150 Pa 90 type 50 to 200 Pa
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur­er’s recommended value).
Function number Setting value Setting description
00 Standard setting ♦ 01 No correction 0.0 °C 02 -0.5 °C 03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C
30
(For cooling)
31
(For heating)
08 -3.5 °C 09 -4.0 °C 10 +0.5 °C 11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
More cooling Less heating
Less cooling
More heating
Factory
setting
12-2. Function settings by using remote controller 12. Function settings
- 44 -
DUCT TYPE
ARYG72-90LHTA
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
DUCT TYPE
ARYG72-90LHTA
Function number Setting value Setting description
00 No correction ♦ 01 No correction 0.0°C 02 -0.5 °C 03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C
35
(For cooling)
36
(For heating)
08 -3.5 °C 09 -4.0 °C 10 +0.5 °C 11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
Factory
setting
More cooling Less heating
Less cooling
More heating
5) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
00 Enable ♦ 01 Disable
NOTE:
40
Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or exter­nal device.
6) Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number Setting value Setting description Factory setting
42
00 Indoor unit ♦ 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE:
12-2. Function settings by using remote controller 12. Function settings
Remote controller sensor must be turned on by using the remote controller.
- 45 -
DUCT TYPE
ARYG72-90LHTA
7) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled, the fan setting will always follow the setting on the remote controller. (Excluding defrost mode)
Function number Setting value Setting description Factory setting
43
00 Enable ♦ 01 Disable
8) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
00 A
44
01 B 02 C 03 D
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
DUCT TYPE
ARYG72-90LHTA
Function number Setting value Setting description Factory setting
00 Operation/Stop mode 1
46
01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2
10) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re­mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01). When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
48
00 Both ♦ 01 Wired remote controller
12-2. Function settings by using remote controller 12. Function settings
- 46 -
DUCT TYPE
ARYG72-90LHTA
11) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
00 Disable
49
01 Enable 02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller. 01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed. 02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially inactivated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for ener­gy saving function or connecting a network converter. To confirm if the remote controller has this setting, refer to the operating manual of each remote controller.
DUCT TYPE
ARYG72-90LHTA
12) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and output”.
Function number Setting value Setting description Factory setting
00 Operation status
01—08 (Setting prohibited)
60
09 Error status 10 Indoor unit fan operation status 11 External heater
12-2. Function settings by using remote controller 12. Function settings
- 47 -

13. Accessories

DUCT TYPE
ARYG72-90LHTA
Part name Exterior Q’ty Part name Exterior Q’ty
Operating manual (For indoor unit)
Coupler heat insulation
1
(small)
DUCT TYPE
ARYG72-90LHTA
1
Operating manual (CD-ROM)
Operating manual (For remote controller)
Installation manual (For indoor unit)
Installation manual (For remote controller)
Special nut A (large flange)
Special nut B (small flange)
Cable tie
1
(large)
Cable tie
1
(medium)
Cable tie
1
(small)
1 Remote controller 1
Remote controller
4
accessories
1 set
4 Drain hose insulation 1
4
1
1
Washer 8 Drain hose 1
Coupler heat insulation (large)
1 Hose band 1
- 48 -
13. Accessories

14. Optional parts

DUCT TYPE

14-1. Controllers

ARYG72-90LHTA
Exterior Part name Model name Summary
Easy finger touch operation with LCD
Wired remote
controller
Wired remote
controller
Wired remote
controller
UTY-RNRYZ*
UTY-RLRY
UTY-RVNYM
panel. Backlit LCD enables easy operation in a dark room. Wire type: Non-polar 2-wire
High visibility and easy operation. Room temperature can be accurately controlled using the built-in thermo sensor.
Wire type: Non-polar 2-wire
Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wire type: Polar 3-wire
DUCT TYPE
ARYG72-90LHTA
Wired remote
controller
Simple remote
controller
Simple remote
controller
UTY-RNNYM
UTY-RSRY
UTY-RHRY
Room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor. Wire type: Polar 3-wire
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Non-polar 2-wire
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, and temperature setting. Wire type: Non-polar 2-wire
Compact remote controller concentrates on the basic functions
Simple remote
controller
14-1. Controllers 14. Optional parts
UTY-RSNYM
- 49 -
such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Polar 3-wire
Exterior Part name Model name Summary
DUCT TYPE
ARYG72-90LHTA
NOTE:
IR receiver kit
with wireless
remote
UTY-LBTYM
Unit control is performed by wireless remote controller.
controller
Available functions may differ by the remote controller. For details, refer to the operation manual.
DUCT TYPE
ARYG72-90LHTA
14-1. Controllers 14. Optional parts
- 50 -

14-2. Others

DUCT TYPE
ARYG72-90LHTA
Exterior Part name Model name Summary
Remote sensor
unit
UTY-XSZX
Thermo-sensor for sensing the temperature of arbitrary place in the room.
DUCT TYPE
ARYG72-90LHTA
Long-life filter UTD-LFKA
Drain pump unit UTZ-PX1NAB
External
connect kit
External input
and output PCB
UTY-XWZXZG
UTY-XCSX
Long-life filter can be mounted to the indoor unit.
Optional drain lift up mechanism allows more flexible installation.
Use to connect with various peripheral devices and air conditioner PCB.
For control output port.
Use to connect with external devices and air conditioner PCB.
Wireless LAN
adapter
Modbus
converter
UTY-TFSXZ1
UTY-VMSX
KNX converter UTY-VKSX
Split system
converter
UTY-VTGX
Remotely manage an air conditioning system using mobile devices such as smartphones and tablets.
For connection between an air conditioner and a Modbus open network.
For connection between an air conditioner and a KNX network.
This converter is required when connecting single split system to VRF network system.
14-2. Others 14. Optional parts
- 51 -
Exterior Part name Model name Summary
DUCT TYPE
ARYG72-90LHTA
NOTE:
Split system
converter
(AC power
supply)
External switch
controller
UTY-VTGXV
UTY-TERX
This converter is required when connecting single split system to VRF network system.
Air conditioner switching can be controlled by connecting other external sensor switches.
Combined use of External input and output PCB,Modbus converter, KNX converter, , and Wireless LAN adapter is not allowed.
DUCT TYPE
ARYG72-90LHTA
14-2. Others 14. Optional parts
- 52 -

Part 2. OUTDOOR UNIT

SINGLE TYPE:
AOYG72LRLA AOYG90LRLA

1. Specifications

Type Inverter heat pump
Model name AOYG72LRLA AOYG90LRLA
Power supply 3N 400 V ~ 50 Hz Available voltage range 342—456 V Starting current A 11.5 14.1
Input power
Current
Power factor
OUTDOOR UNIT
AOYG72-90LRLA
Fan
Sound pressure level *1
Sound power level
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Operation range
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 7.5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Cooling Heating 6.12 7.65
Cooling
Heating
Cooling Heating 76.8 78.3
Airflow rate
Type × Q'ty Propeller × 2 Motor output W 111 × 2
Type × Q'ty Scroll × 1 Motor output W 4,700
Net Gross 1,557 × 1,174 × 600 Net Gross 181 190
Size
Method Brazing Pre-charge length Max. length 100 Max. height difference 30
Rated kW
Rated Max. 13.3 14.6 Rated 11.5 14.1 Max. 13.3 14.6
Rated %
Cooling Heating 8,400 9,000
Cooling Heating 55 57 Cooling Heating 70 71 Dimensions (H × W
× D) Fin pitch 1.45 Rows × Stages 2 × 66 2.6 × 66 Pipe type Copper
Fin
Type R410A Factory charge g 5,600 7,100 Type FVC68D Amount Material Painted galvanized steel
Color
Liquid Gas Ø 25.40 (Ø 1)
Cooling Heating -20 to 24
A
m3/h
dB (A)
dB (A)
mm
Type (Material) Corrugate (Aluminum) Surface treatment Blue fin
3
cm
mm
kg
mm (in)
m
°C
5.99 7.24
11.2 13.5
77.2 77.4
8,400 8,400
55 55
68 68
1,386 × 1,293 × 36.38
2,300
Beige
Approximate color of MUNSELL 10YR 7.5/1.0
1,428 × 1,080 × 480
163 172
Ø 12.70 (Ø 1/2)
30
-15 to 46
Main: 1,386 × 1,293 × 36.38
Sub: 1,386 × 773 × 18.19
OUTDOOR UNIT
AOYG72-90LRLA
- 54 -
1. Specifications

2. Dimensions

Unit: mm
Top view
Front view Rear viewSide view
Bottom view
196 688
515.5
40.5
39
196
1,080
1,428
23.5
A
1,017
1,102
40 480 12
B
C
447
479
Terminal blocks (Power)

2-1. Models: AOYG72LRLA and AOYG90LRLA

OUTDOOR UNIT
AOYG72-90LRLA
OUTDOOR UNIT
AOYG72-90LRLA
2-1. Models: AOYG72LRLA and AOYG90LRLA 2. Dimensions
- 55 -

3. Installation space

100 or more
100 or more
300 or more
80 or more
1,000 or more
1,000 or more
100 or more
100 or more
Max. 500
1,000 or more
1,500 or more
80 or more
100 or more
300 or more

3-1. Models: AOYG72LRLA and AOYG90LRLA

¢
Provide sufficient installation space for product safety.
Single outdoor unit installation
OUTDOOR UNIT
AOYG72-90LRLA
Space requirement
When the upper space is open:
When there are obstacles at the rear only. When there are obstacles at the rear and
sides.
Unit: mm
OUTDOOR UNIT
AOYG72-90LRLA
When there are obstacles at the front only. When there are obstacles at the front and
rear.
When there is an obstruction in the upper space:
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
Unit: mm
3-1. Models: AOYG72LRLA and AOYG90LRLA 3. Installation space
- 56 -
Multiple outdoor unit installation
300 or more
1,500 or more
500 or more
1,500 or more
1,500 or more
1,500 or more
500 or more
Max. 300
OUTDOOR UNIT
AOYG72-90LRLA
NOTES:
• Provide at least 100 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
• No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following ex­ample when an obstruction is present also in the upward area.
When the upper space is open:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
OUTDOOR UNIT
AOYG72-90LRLA
When there are obstacles at the front and rear.
When there is an obstruction in the upper space:
When there are obstacles at the rear and above.
Unit: mm
3-1. Models: AOYG72LRLA and AOYG90LRLA 3. Installation space
- 57 -
Outdoor unit installation in multi-row
1,000 or more
2,000 or more
600 or more
100 or more
3,000 or more
600 or more
1,500 or more
500 or more
OUTDOOR UNIT
AOYG72-90LRLA
NOTES:
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
• If the space is larger than stated above, the condition will be the same as when there is no ob­stacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
OUTDOOR UNIT
AOYG72-90LRLA
CAUTION
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
3-1. Models: AOYG72LRLA and AOYG90LRLA 3. Installation space
- 58 -

4. Refrigerant circuit

Pressure sensor
(High)
Pressure switch
Strainer
Pressure sensor
(Low)
25.4mm (1in)
12.7mm (1/2in)
Muffler
Expansion Valve
3-WAY Valve
4-WAY Valve
Pressure Check Valve
3-WAY Valve

4-1. Models: AOYG72LRLA and AOYG90LRLA

OUTDOOR UNIT
AOYG72-90LRLA
OUTDOOR UNIT
AOYG72-90LRLA
4-1. Models: AOYG72LRLA and AOYG90LRLA 4. Refrigerant circuit
- 59 -

5. Wiring diagrams

5-1. Models: AOYG72LRLA and AOYG90LRLA

OUTDOOR UNIT
AOYG72-90LRLA
OUTDOOR UNIT
AOYG72-90LRLA
5-1. Models: AOYG72LRLA and AOYG90LRLA 5. Wiring diagrams
- 60 -
6. Capacity compensation rate for pipe length and height
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
difference
OUTDOOR UNIT
AOYG72-90LRLA

6-1. Model: AOYG72LRLA

OUTDOOR UNIT
AOYG72-90LRLA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor
unit is
higher
than
outdoor
unit *1
30 0.898 0.874 0.850 0.826 0.803 0.780 0.756 0.732 20 0.938 0.913 0.889 0.864 0.840 0.817 0.793 0.769 0.744 10 0.978 0.953 0.928 0.903 0.879 0.854 0.830 0.806 0.781 0.757
7.5 0.988 0.982 0.957 0.932 0.907 0.882 0.858 0.834 0.809 0.784 0.760
5 0.992 0.992 0.986 0.961 0.935 0.911 0.886 0.861 0.837 0.812 0.788 0.763
5 7.5 10 20 30 40 50 60 70 80 90 100
0 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
Indoor
unit is
lower
Height difference H (m)
than
outdoor
unit *2
HEATING
Indoor
unit is
higher
than
outdoor
unit *1
-5 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-7.5 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-10 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-20 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-30 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
5 7.5 10 20 30 40 50 60 70 80 90 100 30 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908 20 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908 10 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
7.5 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
5 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
0 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
Indoor
unit is
lower
Height difference H (m)
than
outdoor
unit *2
-5 0.995 0.995 0.992 0.982 0.972 0.961 0.951 0.941 0.933 0.923 0.913 0.903
-7.5 0.993 0.990 0.980 0.970 0.959 0.949 0.939 0.931 0.921 0.911 0.901
-10 0.987 0.977 0.967 0.956 0.946 0.937 0.928 0.918 0.908 0.898
-20 0.967 0.957 0.947 0.937 0.927 0.919 0.909 0.899 0.889
-30 0.948 0.937 0.927 0.918 0.909 0.900 0.890 0.880
Pipe length (m)
Pipe length (m)

6-1. Model: AOYG72LRLA 6. Capacity compensation rate for pipe length and height difference

- 61 -

6-2. Model: AOYG90LRLA

NOTE:
OUTDOOR UNIT
AOYG72-90LRLA
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor
unit is
higher
than
outdoor
unit *1
30 0.898 0.874 0.850 0.826 0.803 0.780 0.756 0.732 20 0.938 0.913 0.889 0.864 0.840 0.817 0.793 0.769 0.744 10 0.978 0.953 0.928 0.903 0.879 0.854 0.830 0.806 0.781 0.757
7.5 0.988 0.982 0.957 0.932 0.907 0.882 0.858 0.834 0.809 0.784 0.760
5 0.992 0.992 0.986 0.961 0.935 0.911 0.886 0.861 0.837 0.812 0.788 0.763
5 7.5 10 20 30 40 50 60 70 80 90 100
0 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
Indoor
unit is
lower
Height difference H (m)
than
outdoor
unit *2
HEATING
Indoor
unit is
higher
than
outdoor
unit *1
-5 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-7.5 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-10 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-20 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-30 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
5 7.5 10 20 30 40 50 60 70 80 90 100 30 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908 20 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908 10 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
7.5 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
5 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
0 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
Indoor
unit is
lower
Height difference H (m)
than
outdoor
unit *2
-5 0.995 0.995 0.992 0.982 0.972 0.961 0.951 0.941 0.933 0.923 0.913 0.903
-7.5 0.993 0.990 0.980 0.970 0.959 0.949 0.939 0.931 0.921 0.911 0.901
-10 0.987 0.977 0.967 0.956 0.946 0.937 0.928 0.918 0.908 0.898
-20 0.967 0.957 0.947 0.937 0.927 0.919 0.909 0.899 0.889
-30 0.948 0.937 0.927 0.918 0.909 0.900 0.890 0.880
Pipe length (m)
Pipe length (m)
OUTDOOR UNIT
AOYG72-90LRLA
6-2. Model: AOYG90LRLA 6. Capacity compensation rate for pipe length and height difference
- 62 -

7. Additional charge calculation

7-1. Model: AOYG72LRLA

Refrigerant type R410A Factory charge amount g 5,600
¢ Refrigerant charge
OUTDOOR UNIT
AOYG72-90LRLA

7-2. Model: AOYG90LRLA

¢ Refrigerant charge
Total pipe length m
Additional charge amount
Refrigerant type R410A Factory charge amount g 7,100
Total pipe length m
Additional charge amount
30 or
less
g 0 1,100 2,200 3,300 4,400 5,500 6,600 7,700
30 or
less
g 0 1,100 2,200 3,300 4,400 5,500 6,600 7,700
40 50 60 70 80 90
40 50 60 70 80 90
100
(Max.)
100
(Max.)
110 g/m
110 g/m
OUTDOOR UNIT
AOYG72-90LRLA
7-1. Model: AOYG72LRLA 7. Additional charge calculation
- 63 -

8. Airflow

8-1. Model: AOYG72LRLA

Cooling
OUTDOOR UNIT
AOYG72-90LRLA
Heating
Airflow
m3/h
l/s 2,334
CFM 4,944
Airflow
m3/h
l/s 2,334
CFM 4,944
8,400
8,400
OUTDOOR UNIT
AOYG72-90LRLA

8-2. Model: AOYG90LRLA

Cooling
m3/h
l/s 2,334
CFM 4,944
Heating
m3/h
l/s 2,500
CFM 5,297
Airflow
8,400
Airflow
9,000
8-1. Model: AOYG72LRLA 8. Airflow
- 64 -

9. Operation noise (sound pressure)

Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15

9-1. Noise level curve

Model: AOYG72LRLA
¢
Cooling
OUTDOOR UNIT
AOYG72-90LRLA
Heating
OUTDOOR UNIT
AOYG72-90LRLA
Model: AOYG90LRLA
¢
Cooling
9-1. Noise level curve 9. Operation noise (sound pressure)
Heating
- 65 -

9-2. Sound level check point

1 m
A
irflow
MicrophoneMicrophone
Rear
Rear viewSide view
OUTDOOR UNIT
AOYG72-90LRLA
OUTDOOR UNIT
AOYG72-90LRLA
NOTE:
Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above.
9-2. Sound level check point 9. Operation noise (sound pressure)
- 66 -

10. Electrical characteristics

OUTDOOR UNIT
AOYG72-90LRLA
*1: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As the regulations of wire size and circuit breaker differ in each country or region, select appropriate de­vices complied to the regional standard.
*2: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
Model name AOYG72LRLA AOYG90LRLA
Power supply
Voltage V 3N 400 ~ Frequency Hz 50
Max operating current A 13.3 14.6
Circuit breaker current A 30
2
mm
2
mm
m 101
6.0
1.5
Wiring spec. *1
Power cable
Connection cable *2
Cross-sectional area
Limited wiring length
OUTDOOR UNIT
AOYG72-90LRLA
- 67 -
10. Electrical characteristics

11. Safety devices

OUTDOOR UNIT
AOYG72-90LRLA
Type of
protection
Circuit protection
Fan motor protection
Compressor protection
High pressure protection
Low pressure protection
Protection form
Model
AOYG72LRLA AOYG90LRLA
Current protector (Filter PCB) 500 V, 45 A × 3 Current fuse (Main PCB) 250 V, 10 A Current fuse (Terminal) 250 V, 20 A
115±15 °C
Fan motor stop
70 °C
Fan motor restart
130 °C
Compressor stop
80 °C
Compressor restart
115 °C
Compressor stop
After 7 minutes
Compressor restart
+0
4.2
-0.15
MPa
Compressor stop
3.2±0.15 MPa
Compressor restart
4.1 MPa
Compressor stop
After 3 minutes
Compressor restart
Compressor stop
0.15 MPa
Compressor restart
Thermal protection program
Terminal protection program (Compressor temp.)
Thermal protection program (Discharge temp.)
Pressure switch
Pressure sensor
Pressure sensor Cooling
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
0.12 MPa or less (for 5 minutes)
OUTDOOR UNIT
AOYG72-90LRLA
- 68 -
11. Safety devices

12. External input and output

Outdoor unit
control PCB
Connected unit
Example: Switch
Signal
*10 m
Connector
Locally purchased
CN131
On
Off
On
Off
Input signal
Low noise mode
With using external input and output functions, this product can be operated inter-connectedly with an external device.
OUTDOOR UNIT
AOYG72-90LRLA

12-1. External input

With using external input function, on/off status of “Low noise mode” and “Peak cut mode” can be specified by the external signal.
¢
In following condition, the operating noise of the outdoor unit reduces comparing from the one in nor­mal operating condition:
The air conditioner is set to the “Low noise mode” when closing the contact input of a commercial timer or on/off switch to a connector on the control PCB of the outdoor unit.
Connector Input Output Remarks
CN131 Low noise mode — CN132 Peak cut mode — CN136 Error status CN137 Compressor status
See external input/output settings
for details.
Low noise mode
OUTDOOR UNIT
AOYG72-90LRLA
NOTE:
Product performance may drop depending on some conditions such as the outdoor temper­ature.
Circuit diagram example (CN131)
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit within 10 m.
• Construct a circuit as shown in this figure with using optional parts mentioned below.
• Input signal: On in “Low noise mode”
• Input signal: Off in normal operation
• To set the level of “Low noise mode”, refer to "Low
noise mode" on page 75.
12-1. External input 12. External input and output
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 69 -
¢
Outdoor unit
control PCB
Connected unit
Example: Switch
Signal
*10 m
Connector
Locally purchased
CN132
On
Off
On
Off
Input signal
Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled: The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
Circuit diagram example (CN132)
OUTDOOR UNIT
AOYG72-90LRLA
Peak cut mode
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit within 10 m.
• Construct a circuit as shown in this figure with using optional parts mentioned below.
• Input signal: On in “Peak cut mode”
• Input signal: Off in normal operation
• To set the level of “Peak cut mode”, refer to "Peak cut
mode" on page 76.
OUTDOOR UNIT
AOYG72-90LRLA
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
12-1. External input 12. External input and output
- 70 -

12-2. External output

Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*10 m
Vcc
+
+
-
Load
Vcc
Power supply
CN136
Error
Normal
On
Off
Error status
Output signal
With using external output function, some status signals are transmitted to the control PCB, and the related LED lamp indicates the status of this product.
Error status output
¢
Signal on air conditioner error status is generated when a malfunction occurs.
Circuit diagram example (CN136)
OUTDOOR UNIT
AOYG72-90LRLA
Optional part
• 1: Power supply Voltage (Vcc): DC 24 V or less
• 2: Load DC 500 mA or less
• *: Make the distance from the PCB to the con­nected unit within 10 m.
OUTDOOR UNIT
AOYG72-90LRLA
Part name Model name Exterior
External connect kit UTY-XWZXZ3
12-2. External output 12. External input and output
- 71 -
¢
Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*10 m
Vcc
+
+
-
Load
Vcc
Power supply
CN137
Operation
Stop
On
Off
Compressor status
Output signal
Signal on compressor operation status is generated when the compressor is running.
Circuit diagram example (CN137)
OUTDOOR UNIT
AOYG72-90LRLA
Compressor status output
• 1: Power supply Voltage (Vcc): DC 24 V or less
• 2: Load DC 500 mA or less
• *: Make the distance from the PCB to the con­nected unit within 10 m.
OUTDOOR UNIT
AOYG72-90LRLA
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
12-2. External output 12. External input and output
- 72 -

13. Function settings

LED display and button
/
SW107
SW108 SW109 SW112 SW110
LED display part
Button part
Perform appropriate function setting locally according to the installation environment.
NOTE:
• Before setting up the switch buttons, discharge the static electricity from your body.
• Never touch the terminals or the patterns on the parts that are mounted on the PCB.
OUTDOOR UNIT
AOYG72-90LRLA

13-1. Local setting switch buttons

¢
Control PCB of the outdoor unit is located as shown in the following figure.
Incorrect settings can cause a product malfunction.
CAUTION
Control PCB and switch buttons location
OUTDOOR UNIT
AOYG72-90LRLA
¢
Switch buttons and the functions
13-1. Local setting switch buttons 13. Function settings
- 73 -
OUTDOOR UNIT
AOYG72-90LRLA
¢
LED lamp Function or operation method
(1) POWER/MODE Green
(2) ERROR Red Blinks during error operation. (3) PUMP DOWN (L1) Orange Lights on during pump down operation.
LOW NOISE MODE
(4)
(L2 and L3) PEAK CUT MODE
(5)
(L4, L5, and L6)
Switch button Function or operation method
SW107 MODE Switches between “Local setting” and “Error code display”. SW108 SELECT Switches between the individual “Local settings” and the “Error code displays”. SW109 ENTER Switches between the individual “Local settings” and the “Error code displays”. SW112 EXIT Returns to “Operation status display”. SW110 PUMP DOWN Starts the pump down operation.
Orange
Orange
Lights on while power on. Local setting in outdoor unit or error code is displayed with blink.
Lights on during “Low noise mode” when local setting is activated. (Lighting pattern of L2 and L3 indicates low noise level.)
Lights on during “Peak cut mode” when local setting is activated. (Lighting pattern of L4, L5, and L6 indicates peak cut level.)
Function setting table
LED display
OUTDOOR UNIT
AOYG72-90LRLA
No. Setting item
Low noise
1
mode setting
Peak cut mode
2
setting
Level 1 Level 2 ○ Level 1 ● Level 2 ○ Level 3 ● Level 4
POWER
MODE
Blink
(9 times)
ERROR
PUMP
DOWN
(L1) (L2) (L3) (L4) (L5) (L6)
LOW NOISE PEAK CUT
Sign "○": Lights off, "●": Lights on
No. Setting item Content
By using the "Low noise mode", the limit of the noise level will be set to decrease the noise level. The mode comes in 2 levels which can be set accordingly.
1 Low noise mode setting
2 Peak cut mode setting
To turn on the mode, use the external input terminal (CN131).
• By using this mode, the cooling/heating performance may decrease.
• Depending on the operating condition, the noise level may not decrease even if the Low noise mode is on.
The capacity limit can be selected when operating with the “Peak Cut mode.” The operation selection can be done by external input terminal (CN132). The lower the level, the more the effect of energy saving, but the cooling/heating performance decreases.
Factory
setting
Noise level as low noise mode setting
Unit: dB (A)
AOYG72LRLA AOYG90LRLA
Cooling Heating Cooling Heating
Level1 53 53 53 55 Level2 51 51 51 53
13-1. Local setting switch buttons 13. Function settings
- 74 -

13-2. Local setting procedure

POWER
MODE
ERROR
(L1) (L2) (L3) (L4) (L5) (L6)
PUMP
DOWN
LOW NOISE PEAK CUT
Blinks
(9 times
)
Sign “ ”: Lights off
(L2)
(L3)
LOW NOISE
Blink
LOW NOISE
MODE
(L2) (L3)
LOW NOISE
LOW NOISE
MOD
E
Sign “ ”: Lights on
PEAK CUT
Level 1
Level 2
Blink
Blink
(L4) (L5) (L6)
Low
Lower
PEAK CUT
Level 1
Level 2
(L4) (L5) (L6)
Low
Lower
NOTE:
¢
1. Press the MODE switch button (SW107) for 3 seconds or more to switch to “Local setting
2. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch but-
OUTDOOR UNIT
AOYG72-90LRLA
3. Press the SELECT switch button (SW108), and adjust the LED lamp as shown below. Then the
Before performing the function setting, be sure to stop the operation of the air conditioner.
Low noise mode
mode”.
ton (SW109).
LED lamp indicates the current setting.
OUTDOOR UNIT
AOYG72-90LRLA
4. Press the ENTER switch button (SW109).
5. Press the SELECT switch button (SW108), and adjust the LED lamps as shown below.
6. Press the ENTER switch button (SW109) and fix it.
7. To return to “Operating status display (Normal operation)”, press the EXIT switch button
In case of missing how many times you pressed the SELECT and ENTER switch buttons:
1. To return to “Operation status display (Normal operation)”, press the EXIT switch button once.
2. Restart from the beginning of setting procedure.
NOTE:
13-2. Local setting procedure 13. Function settings
(SW112).
In case of missing how many times you pressed the SELECT and ENTER switch buttons, you must redo the setting procedure. Return to “Operation status display (Normal opera­tion)” by pressing the EXIT switch button once, and restart from the beginning of the setting procedure.
- 75 -
¢
POWER
MODE
ERROR
(L1) (L2) (L3) (L4) (L5) (L6)
PUMP
DOWN
LOW NOISE PEAK CUT
Blinks
(9 times
)
Sign “ ”: Lights off
(L2)
(L3)
LOW NOISE
Blink
PEAK CUT
MOD
E
(L2) (L3)
LOW NOISE
PEAK CUT
MODE
Sign “ ”: Lights on
PEAK CUT
(L4) (L5) (L6)
0% of rated input ratio
○○Blink
50% of rated input ratio
Blink
75% of rated input ratio
Blink Blink
100% of rated input ratio
Blink
○○
Sign “○”: Lights off
Level 1
Level 2
Level 3
Level 4
PEAK CUT
(L4) (L5) (L6)
○○ ○○ ○
○○
Sign “○”: Lights off, “●”: Lights on
0% of rated input ratio
50% of rated input ratio
75% of rated input ratio
100% of rated input ratio
Level 1
Level 2
Level 3
Level 4
1. Press the MODE switch button (SW107) for 3 seconds or more to switch to “Local setting
2. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch but-
OUTDOOR UNIT
AOYG72-90LRLA
3. Press the SELECT switch button (SW108), and adjust the LED lamp as shown below. Then the
4. Press the ENTER switch button (SW109).
Peak cut mode
mode”.
ton (SW109).
LED lamp indicates the current setting.
OUTDOOR UNIT
AOYG72-90LRLA
5. Press the SELECT switch button (SW108), and adjust the LED lamps as shown below.
6. Press the ENTER switch button (SW109) and fix it.
7. To return to “Operating status display (Normal operation)”, press the EXIT switch button
NOTE:
13-2. Local setting procedure 13. Function settings
(SW112).
When pressed number is lost during setting, you must redo the setting procedure. Return to “Operation status display (Normal operation)” by pressing the EXIT switch button once, and restart from the beginning of the setting procedure.
- 76 -

14. Check and test

POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
○ ○ ○○○○○

14-1. Test run

¢
OUTDOOR UNIT
AOYG72-90LRLA
Pre-test run check items
Check column Check item
Is the outdoor unit securely installed? Have you performed gas leakage inspection?
(Connection joints of various pipes (flange connection, brazing)) Is the heat insulation done completely?
(Gas pipe, liquid pipe, drain hose extension on indoor unit side etc) Is the water discharging from drain without any problems? Are the cables connected correctly? Are the cables as per specifications? Is the earth wire connected accurately? Are there any obstacles blocking the suction gate, and outlet of the indoor/outdoor units? Have you filled the specified amount of refrigerant? Are the stop valves of gas pipe and liquid pipe fully open? Has the power been supplied to crankcase heater for more than 6 hours?
OUTDOOR UNIT
AOYG72-90LRLA
Test operation method
¢
Be sure to configure test run settings only when the outdoor unit has stopped operating.
Notices:
• Depending on the communication status between the indoor and outdoor units, it may take sev­eral minutes for the system to start operating after settings for the test run are complete.
• After the test run settings are complete, the outdoor units and the connected indoor units will start operating. Room temperature control will not activate during test operation (continuous op­eration).
• If a knocking sound can be heard in the liquid compression of the compressor, stop the unit im­mediately and then energize the crank case heater for a sufficient length of time before restart­ing the operation.
Test operation setting method (It can be performed in the following two ways)
• Set with test operation setting (refer to installation instructions manual of indoor unit for further de­tails) available in the remote controller.
• "Cooling operation" and "Heating operation" can be set using SELECT button and ENTER button available on the board of display unit. (*Make sure to perform the first test operation with cooling operation.)
Set as per the procedure given below.
Symbols in the following table indicate LED status. "○": Lights off, "●": Lights on
1. Turn on the power of the outdoor unit and enter standby mode. “POWER/MODE” Lamp lights up.
14-1. Test run 14. Check and test
- 77 -
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
○○○
Blink
○○○
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
○○○
Blink
○○○
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
○○
Blink
○○○○
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
○○○
○○○
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
○○
○○○○
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
○ ○ ○○○○○
OUTDOOR UNIT
AOYG72-90LRLA
2. Press the ENTER button for more than 3 seconds.
3. Press the SELECT button, LED of the test run mode Switched between "COOL " and "HEAT".
• Cooling test mode
• Heating test mode
4. After confirming the operation mode, Press ENTER button.The display changes as follows, and Air conditioner starts operation.
• Cooling test mode
OUTDOOR UNIT
AOYG72-90LRLA
• Heating test mode
5. Press [ENTER] button. Air conditioner stopped operation.
Checklist
¢
Check items during test operation.
Check column Check item
Is the outdoor unit making any abnormal noise or vibrating significantly? Is the cold air or hot air blowing from indoor unit according to the operation mode? Check that the “ERROR” LED blinks.
If, it has displayed, check the error content refer to Error code check table. Operate the unit according to the operating manual provided with the indoor unit, and check
that it is operating normally.
14-1. Test run 14. Check and test
- 78 -

14-2. Error code

POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
(Hi speed)
○ ○○○○○
Sign “○”: Lights off, “●”: Lights on
LED display
RemarkDescription
POWER/
MODE
ERROR
PUMP DOWN LOW NOISE PEAK CUT
(L1) (L2) (L3) (L4) (L5) (L6)
(2)
(1) (1)
○○
Serial communication error
Serial forward transmission error immediately after operation
(2)
(1) (1)
○○
Serial forward transmission error during operation
(2)
(2) (2)
○○○
Indoor unit capacity error Indoor unit capacity error
(2)
(5) (15)
○○○
Indoor unit error Indoor unit error
(2)
(6) (2)
○○○
Outdoor unit main PCB error Outdoor unit PCB model information error
(2)
(6) (3)
○○○
Inverter PCB error Inverter error
(2)
(6) (5)
○○
rorre L lanimret pirTrorre MPI
(2)
(7) (1)
○○○
Discharge temp. sensor error Discharge temp. sensor 1 error
(2)
(7) (2)
○○○
Compressor temp. sensor error Compressor temp. sensor 1 error
(2)
(7) (3)
○○
Outdoor unit Heat Ex. sensor error
Heat Ex. middle temp. sensor error
(2)
(7) (3)
○○
Outdoor unit Heat Ex. liquid temp. sensor error
(2)
(7) (4)
○○○
Outdoor temp. sensor error Outdoor temp. sensor error
(2)
(7) (7)
○○○
Heat sink temp. sensor error Heat sink temp. sensor error
(2)
(8) (4)
○○○
Current sensor error Current sensor 1 error (stoppage permanently)
(2)
(8) (6)
○○
Pressure sensor error
High pressure switch 1 error
(2)
(8) (6)
○○○
Outdoor unit discharge pressure sensor error
(2)
(8) (6)
○○
Outdoor unit suction pressure sensor error
(2)
(9) (4)
○○○
noitceted pirTnoitceted pirT
(2)
(9) (5)
○○○
Compressor motor control error Rotor position detection error (stoppage permanently)
(2)
(9) (7)
○○
Outdoor unit fan motor 1 error Duty error
(2)
(9) (8)
○○
Outdoor unit fan motor 2 error Duty error
(2)
(9) (9)
○○○
4-way valve error 4-way valve error
(2)
(10) (1)
○○○
Discharge temp. 1 error Discharge temp. 1 error
(2)
(10) (3)
○○○
Compressor temp. error Compressor 1 temp. error
(2)
(10) (5)
○○○
Pressure error 2 Low pressure error
Display mode
: Lights on : Lights off
: Blink (0.5s Lights on / 0.5s Lights off)
( ) : Number of  ashing
If an error occurs, the LED will light up to display the error location and the error code.
¢
Display when an error occurs.
OUTDOOR UNIT
AOYG72-90LRLA
Error display mode
OUTDOOR UNIT
AOYG72-90LRLA
NOTE:
Error code check table
¢
14-2. Error code 14. Check and test
Check that the “ERROR” LED blinks, then press the [ENTER] button once.
- 79 -

14-3. Pump down

POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
● ○ ○ ○○○○○
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
● ○ ● ○○●●●
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
● ○ ● ○○○●●
OUTDOOR UNIT
AOYG72-90LRLA
WARNING
• Never touch electrical components such as the terminal blocks except the button on the display board. It may cause a serious accident such as electric shock.
• During the pump-down operation, make sure that the compressor is turned off before you re­move the refrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2-way or g. 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
CAUTION
• Perform the pump down operation before disconnecting any refrigerant pipe or electric cable.
• Collect refrigerant from the service port or the 3-way valve if pump down cannot be performed.
• In case of a group control system installation, do not turn the power off until pump down is com­pleted in all outdoor units. (Group control system installation described in “SPECIAL INSTALLATION METHODS” in the in­stallation manual of the indoor unit.)
OUTDOOR UNIT
AOYG72-90LRLA
Pump down procedure
¢
Confirm that the power is off, and then open the service panel.
Symbols in the following table indicate LED status. "○": Lights off, "●": Lights on
1. Check the 3-way valves (both the liquid side and gas side) are opened.
2. Turn the power on.
3. Press [PUMP DOWN] button for 3 seconds or more after 3 minutes after power on.
LED display lights on as shown in the above figure, and the fans and the compressor start op­erating.
NOTE:
If the [PUMP DOWN] button is pressed during compressor operation, the compres­sor will stop, and the operation will start after about 3 min.
4. LED display will change as shown below about 3 minutes after the compressor starts. Fully close the 3-way valve on the liquid pipe side at this stage.
NOTE:
If the valve on the liquid pipe side is not closed, the pump down cannot be per­formed.
14-3. Pump down 14. Check and test
- 80 -
5. When LED display changes as shown in the below figure, close the 3-way valve on the gas
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
● ○ ● ○○○○●
Step (5)
Closing direction
Step (4)
Hexagon wrench
Liquid pipe
Gas pipe
Closing direction
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
● ○ ● ○○○○○
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
○ ○ ○ ○○○○○
pipe side tightly.
OUTDOOR UNIT
AOYG72-90LRLA
NOTE:
If the valve on the gas pipe side is not closed, refrigerant may flow into the piping after the compressor stops.
6. LED display changes after 1 minute as shown in the figure below. The LED will light as follows.
Fans and compressor stop automatically.
NOTE:
If the pump down is successfully completed (the above LED display is shown), the outdoor unit remains stopped until the power is turned off.
7. Turn the power off.
OUTDOOR UNIT
AOYG72-90LRLA
Pump down is completed.
Notices:
• To stop pump down, press the [PUMP DOWN] button again.
• To start the pump down again after the compressor is automatically stopped due to an error, disconnect the power supply and open the 3-way valves. Wait 3 minutes, reconnect the power supply and start the pump down again.
• When starting the operation after completion of the pump down, disconnect the power supply, and then open the 3-way valves. Wait 3 minutes, reconnect the power supply and perform a test run in the “COOL” operation mode.
• If an error occurs, recover the refrigerant from service port.
14-3. Pump down 14. Check and test
- 81 -

15. Accessories

OUTDOOR UNIT
AOYG72-90LRLA
Part name Exterior Q’ty Part name Exterior Q’ty
Installation manual 1 Joint pipe B 1
Drain pipe 1 Push mount cable tie 2
Drain cap 9 Grommet edging 2
Joint pipe A 1
OUTDOOR UNIT
AOYG72-90LRLA
- 82 -
15. Accessories

16. Optional parts

OUTDOOR UNIT
AOYG72-90LRLA
Exterior Part name Model name Summary
External
connect kit
UTY-XWZXZ3
Use to operate the external input and output functions of outdoor unit.
OUTDOOR UNIT
AOYG72-90LRLA
- 83 -
16. Optional parts
Loading...