Fujitsu aoyg30lat4 Installation Manual

Page 1
EnglishDeutschFrançaisEspañolItalianoEλληvIkάPortuguêsРусскийTϋrkçe
En-1
AIR CONDITIONER OUTDOOR UNIT
INSTALLATION MANUAL
INSTALLATIONSANLEITUNG
MANUAL DE INSTALACIÓN
MANUALE D'INSTALLAZIONE
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
MANUAL DE INSTALAÇÃO
РУКОВОДСТВО ПО УСТАНОВКЕ
MONTAJ KILAVUZU
For authorized personnel only.
PART NO. 9374872121-03
Nur für autorisiertes Personal.
Pour le personnel agréé uniquement.
Solo para personal autorizado.
Ad uso esclusivo del personale autorizzato.
Για εξουσιοδοτημένο προσωπικό σέρβις.
Apenas para técnicos autorizados.
Для уполномоченного персонала.
Yetkili servis personeli içindir.
Page 2
En-1
SAFETY PRECAUTIONS1.
Be sure to read this Manual thoroughly before installation. The warnings and precautions indicated in this Manual contain important information pertaining to your safety. Be sure to observe them. Hand this Manual, together with the Operating Manual, to the customer. Request the customer to keep them on hand for future use, such as for relocating or repairing the unit. After installation, explain correct operation to the customer, using the operating manual.
WARNING
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
Never touch electrical components immediately after the power supply has been turned off. Electrical shock may occur. After turning off the power, always wait 5 minutes or more before touching electrical components.
Request your dealer or a professional installer to install the indoor unit in accordance with this Installation Manual. An improperly installed unit can cause serious accidents
such as water leakage, electric shock, or re. If the indoor unit is installed in disregard
of the instructions in the Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning ON the power
before the work is completed can cause serious accidents such as electric shock or re.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a ame, it produces a toxic gas.
Installation work must be performed in accordance with national wiring standards by authorized personnel only.
Do not use this equipment with air or any other unspecied refrigerant in the refrigerant
lines. Excess pressure can cause a rupture.
During installation, make sure that the refrigerant pipe is attached rmly before you run
the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to rupture and even injury.
When installing and relocating the air conditioner, do not mix gases other than the
specied refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause rupture, injury, etc.
For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
Connect the indoor unit and outdoor unit with the air conditioner piping and cable available standards parts. This installation manual describes the correct connections using the installation set available from our standard parts.
Also, do not use an extension cable.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is not extra refrigerant in the outdoor unit for air purging.
Use a vacuum pump for R410A exclusively.
Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
Use a clean gauge manifold and charging hose for R410A exclusively.
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to rupture and even injury.
CAUTION
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by qualied personnel with a capacity certicate for handling refrigerant uids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 3mm for this unit.
The unit must be correctly grounded and the supply line must be equipped with a differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive atmosphere.
This unit contains no user-serviceable parts. Always consult authorized service personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation of the unit.
Children should be monitored to ensure they do not play with the device.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
ABOUT THE PRODUCT2.
Precautions for using R410A refrigerant2. 1.
WARNING
The basic installation work procedures are the same as conventional refrigerant models. However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant
(R22) models, some of the piping and installation and service tools are special. (See the table below.) Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional piping and are nuts with the R410A piping and are nuts. Models that use refrigerant R410A have a different charging port thread diameter • to prevent erroneous charging with conventional refrigerant (R22) and for safety.
Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.] Be careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when storing the piping, securely seal the openings by pinching, taping, etc. When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases. And always charge from the liquid phase where refrigerant composition is stable.
Contents
SAFETY PRECAUTIONS1. ……………………………………………………………… 1 ABOUT THE PRODUC2. T
Precautions for using R410A refrigerant2.1. ………………………………………… 1 Special tools for R410A2.2. ……………………………………………………………2 Accessories2.3. ………………………………………………………………………… 2 System conguration2.4. ……………………………………………………………… 2
INSTALLATION WOR3. K
Selecting an installation location3.1. ………………………………………………… 3 Drain installation3.2. …………………………………………………………………… 3 Installation dimensions3.3. …………………………………………………………… 3 Transportation of the unit3.4. ………………………………………………………… 4 Installation of the unit3.5. ……………………………………………………………… 4
PIPE INSTALLATION 4. I
Flare connection (pipe connection)4.1. ……………………………………………… 4
ELECTRICAL WIRIN5. G
The precautions of electrical wiring5.1. ……………………………………………… 5 Electrical requirement5.2. ……………………………………………………………… 6 Unit wiring5.3. …………………………………………………………………………… 6 Connection diagrams5.4. ……………………………………………………………… 6 Outdoor unit5.5. ………………………………………………………………………… 6
PIPE INSTALLATION I6. I
Vacuum6.1. ……………………………………………………………………………… 7
Additional charging6.2. ………………………………………………………………… 7 POWER7. …………………………………………………………………………………… 8 TEST RU8. N
Make a TEST RUN in accordance with the installation Manual 8.1.
for the indoor unit ……………………………………………………………………8
Outdoor unit LEDS8.2. ………………………………………………………………… 8 PUMP DOWN9. ……………………………………………………………………………… 8
INSTALLATION MANUAL
PART NO. 9374872121-03
Page 3
En-2
Special tools for R410A2. 2.
Tool name
Contents of change
Gauge manifold
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals –0.1 to 5.3 MPa
(-1 to 53 bar) for high pressure. –0.1 to 3.8 MPa (-1 to 38 bar)
for low pressure.
Charge hose
To increase pressure resistance, the hose material and base size were changed.
Vacuum pump
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Gas leakage
detector
Special gas leakage detector for HFC refrigerant R410A.
Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or
discolored portion (especially on the interior surface). Otherwise, the expansion valve or
capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in the table. Never use copper pipes thinner than that in the table even when it is available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter Thickness
6.35 mm (1/4 in.) 0.80 mm
9.52 mm (3/8 in.) 0.80 mm
12.70 mm (1/2 in.) 0.80 mm
15.88 mm (5/8 in.) 1.00 mm
19.05 mm (3/4 in.) 1.20 mm
Accessories2. 3.
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts. The use of non-prescribed parts can cause serious accidents such as
the unit falling, water leakage, electric shock, or re.
Do not throw away the connecting parts until the installation has been complete.
Name and shape Q’ty Application
Installation manual
1
(This book)
Drain cap 2
For outdoor unit drain piping work
[Heat & Cool model (Reverse cycle)
only]
Drain pipe 1
Putty 1 For sealing
Adapter assy
12.7 mm / 9.52 mm
2
For use when connecting models 7–12 to outdoor port A or B
Adapter assy
12.7 mm / 15.88 mm
1 For use when connecting model 24
System conguration2. 4.
Layout example for the indoor units and outdoor unit.
Circuit breaker
INDOOR UNITS
UNIT D 7-12
UNIT C 7-12
UNIT B 7-18
UNIT A 7-24
OUTDOOR UNIT
Power source 230 V ~ 50 Hz
Power cable
Connection cable
Refrigerant pipe
d
c
H1
H1
H2
b
a
CONNECTABLE INDOOR UNIT CAPACITY TYPE2. 4. 1.
CAUTION
The total capacity of the indoor units connected must be between 27,000 and 49,000BTU.
Be sure to check the connecting pattern in technical manual when installed since
connection pattern is specied in it. Operation cannot be guaranteed if connected by a method not specied in it. It can cause the fault of the product.
At least three indoor units must be connected to the outdoor unit.
To install an indoor unit, refer to the installation Manual included with the indoor unit.
Outdoor port
Connectable model name
Standard port size
D 6.35/9.52 7 – 12
C 6.35/9.52 7 – 12
B 6.35/12.7 7 – 12
*1
/14 – 18
A 6.35/12.7 7 – 12
*1
/14 – 24
*2
*1
When connecting models 7–12 to the outdoor unit, the included adapter is necessary.
(For more information, refer to “4.1.3. HOW TO USE ADAPTER”.)
*2
When connecting model 24 to the outdoor unit, connect only two other indoor units to
the outdoor unit. (Max indoor unit capacity connection: 24,000 + 12,000 + 12,000 BTU)
In addition, the included adapter is necessary to connect the indoor unit to the outdoor
unit. (For more information, refer to “4.1.3. HOW TO USE ADAPTER”.)
UNIT D ø6.35, ø9.52
UNIT C ø6.35, ø9.52
UNIT B ø6.35, ø12.7
UNIT A ø6.35, ø12.7
LIMITATION OF REFRIGERANT PIPING LENGTH2. 4. 2.
CAUTION
The total maximum pipe lengths and height difference of this product are shown in the table. If the units are further apart than this, correct operation cannot be guaranteed.
Total max. length (a+b+c+d) 70 m (230 ft)
*3
Max. length for each indoor unit (a, b, c, or d)
25 m (82 ft)
Max. height difference between outdoor unit and each indoor unit (H1)
15 m (49 ft)
Max. height difference between indoor units (H2)
10 m (33 ft)
Min. length for each indoor unit (a, b, c, or d)
5 m (16 ft)
Total min. length (a+b+c+d) 20 m (66 ft)
*3
If the total piping length is 51 m or longer, additional refrigerant charging is necessary.
(For more information, refer to “6.2. Additional charging”.)
SELECTING PIPE SIZES2. 4. 3.
The diameters of the connection pipes differ according to the capacity of the indoor unit. Refer to the following table for the proper diameters of the connection pipes between the indoor and outdoor units.
Capacity of indoor
unit
Gas pipe size
(thickness) [mm]
Liquid pipe size
(thickness) [mm]
7 – 12 ø9.52 (0.8) ø6.35 (0.8)
14 – 18 ø12.7 (0.8) ø6.35 (0.8)
24 ø15.88 (1.0) ø6.35 (0.8)
CAUTION
Operation cannot be guaranteed if the correct combination of pipes, valves, etc., is not used to connect the indoor and outdoor units.
Page 4
En-3
HEAT INSULATION AROUND CONNECTION PIPES REQUIREMENTS2. 4. 4.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specied, condensation may form on the
surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
Connect the connection pipes according to “4. PIPE INSTALLATION I” in this installation
Manual.
INSTALLATION WORK3.
Please obtain the approval of the customer when selecting the location of installation and installing the unit.
Selecting an installation location3. 1.
WARNING
Securely install the outdoor unit at a location that can withstand the weight of the unit. Otherwise, the outdoor unit may fall and cause injury.
Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes and typhoons or other strong winds. Improper installation can cause the unit to topple or fall, or other accidents.
Do not install the outdoor unit near the edge of a balcony. Otherwise, children may climb onto the outdoor unit and fall off of the balcony.
CAUTION
Do not install the outdoor unit in the following areas:
Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or the unit to leak water. Area lled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak water. Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage. Area containing equipment that generates electromagnetic interference. It will cause the control system to malfunction, preventing the unit from operating normally.
Area that can cause combustible gas to leak, contains suspended carbon bers or • ammable dust, or volatile inammables such as paint thinner or gasoline. If gas leaks and settles around the unit, it can cause a re. Area that has heat sources, vapors, or the risk of the leakage of ammable gas in
the vicinity. Area where small animals may live. It may cause failure, smoke or re if small animals enter and touch internal electrical parts. Area where animals may urinate on the unit or ammonia may be generated.
Please install the outdoor unit without slant.
Install the outdoor unit in a well-ventilated location away from rain or direct sunlight.
If the outdoor unit must be installed in an area within easy reach of the general public, install as necessary a protective fence or the like to prevent their access.
Install the outdoor unit in a location that would not inconvenience your neighbors, as
they could be affected by the airow coming out from the outlet, noise, or vibration. If it
must be installed in proximity to your neighbors, be sure to obtain their approval.
If the outdoor unit is installed in a cold region that is affected by snow accumulation, snow fall, or freezing, take appropriate measures to protect it from those elements. To ensure a stable operation, install inlet and outlet ducts.
Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor, soot, dust, or debris.
Install the indoor unit, outdoor unit, power supply cable, connection cable, and remote controller cable at least 1 m away from a television or radio receivers. The purpose of
this is to prevent TV reception interference or radio noise. (Even if they are installed more than 1 m apart, you could still receive noise under some signal conditions.)
Branch switch and circuit breaker
Branch switch and circuit breaker
1m or more
1 m or more
CAUTION
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
Keep the length of the piping of the indoor and outdoor units within the allowable range.
For maintenance purposes, do not bury the piping.
Drain installation3. 2.
CAUTION
Perform drain work in accordance with this Manual, and ensure that the drain water is properly drained. If the drain work is not carried out correctly, water may drip down from the unit, wetting the furniture.
When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may
freeze in extremely cold weather. (Reverse cycle model only)
Outdoor unit to be fasten with bolts at the four places indicated by the arrows without fail.
AIR
Bottom side
Drain cap mounting place
Drain pipe mounting place
Since the drain water ows out of the outdoor unit during heating operation, install the drain pipe and connect it to a commercial 16 mm hose. (Reverse cycle model only)
When installing the drain pipe, plug all the holes other than the drain pipe mounting hole
in the bottom of the outdoor unit with putty so there is no water leakage. (Reverse cycle model only)
Drain pipe mounting hole
Base
Drain pipe
Installation dimensions3. 3.
CAUTION
Select installation locations that can properly support the weight of the indoor and outdoor units. Install the units securely so that they do not topple or fall.
WARNING
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near heat source of heat, steam, or ammable gas.
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
CAUTION
Install the unit where it will not be tilted by more than 3˚. However, do not install the unit
with it tilted towards the side containing the compressor.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
Decide the mounting position with the customer as follows:
(1) Install the outdoor unit in a location which can withstand the weight of the unit and
vibration, and which can install horizontally.
(2) Provide the indicated space to ensure good airow. (3) If possible, do not install the unit where it will be exposed to direct sunlight. (If necessary, install a blind that does not interfere with the airow.) (4) Do not install the unit near a source of heat, steam, or ammable gas. (5) During heating operation, drain water ows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water ow will not be
obstructed. (Reverse cycle model only) (6) Do not install the unit where strong wind blows or where it is very dusty. (7) Do not install the unit where people pass. (8) Install the outdoor unit in a place where it will be free from being dirty or getting wet by
rain as much as possible.
(9) Install the unit where connection to the indoor unit is easy.
Page 5
En-4
Single outdoor unit installation 3. 3. 1.
When the upward area is open
When there are obstacles at the back side.
100 mm
or more
AIR
When there are obstacles at the back and front sides.
100 mm
or more
600 mm
or more
AIR
When an obstruction is present also in the upward area
When there are obstacles at the
back, side(s), and
top
100-300 mm*
250 mm or more
(Service space)
300 mm
or more
600-1000 mm*
AIR
If the space is larger than that is stated, the condition will be the same as that there are no obstacles.
Multiple outdoor unit installation3. 3. 2.
Provide at least 250 mm of space between the outdoor units if multiple units are installed. When routing the piping from the side of an outdoor unit, provide space for the piping. No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following example when an obstruction is present also in the upward area.
When there are obstacles at the back side with the installation of more than one unit.
250 mm
or more
250 mm
or more
300 mm
or more
AIR
Transportation of the unit3. 4.
WARNING
Do not touch the ns. Otherwise, personal injury could result.
CAUTION
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or ngers may be pinched.
Be sure to hold the handles on the sides of the unit. Otherwise, holding the suction grille on the sides of the unit may cause deformation.
Handle
Installation of the unit3. 5.
Install 4 anchor bolts at the locations indicated with arrows in the gure. To reduce vibration, do not install the unit directly on the ground. Install it on a secure
base (such as concrete blocks).
The foundation shall support the legs of the unit and have a width of 50mm or more. Depending on the installation conditions, the outdoor unit may spread its vibration during operation, which may cause noise and vibration. Therefore, attach damping materials
(such as damping pads) to the outdoor unit during installation.
Install the foundation, making sure that there is enough space for installing the connection pipes.
Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially • available M10 bolts, nuts, and washers.) The bolts should protrude 20mm. (Refer to the gure.)
If overturning prevention is required, purchase the necessary commercially available items.
650mm
Bottom side
4-ø12 hole
370mm
AIR
Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, nut and washer.)
Bolt
Nut
Block
PIPE INSTALLATION I4.
Flare connection (pipe connection)4. 1.
CAUTION
Do not use mineral oil on a ared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.
While welding the pipes, be sure to blow dry nitrogen gas through them.
The maximum lengths of this product are shown in the table. If the units are further apart than this, correct operation cannot be guaranteed.
Flaring
Use special pipe cutter and are tool exclusive for R410A.
Cut the connection pipe to the necessary length with a pipe cutter.(1) Hold the pipe downward so that the cuttings will not enter the pipe and remove any (2) burrs.
Insert the are nut (always use the are nut attached to the indoor and outdoor units (3) respectively) onto the pipe and perform the are processing with a are tool. Leakage of refrigerant may result if other are nuts are used.
Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from (4) entering the pipes.
L
Check if [L] is ared uniformly
and is not cracked or scratched.
Pipe
A
B
Die
Page 6
En-5
Pipe outside
diameter [mm (in.)]
Dimension A (mm)
Dimension B
0
- 0.4
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional are tools to are R410A pipes, the dimension A should be • approximately 0.5mm more than indicated in the table (for aring with R410A are tools) to achieve the specied aring. Use a thickness gauge to measure the dimension A.
Pipe outside diameter
[mm (in.)]
Width across atsof Flare nut
[mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
Width across ats
Bending pipes4. 1. 1.
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curvature of 100mm or more.
If the pipe is bent repeatedly at the same place, it will break.
If pipes are shaped by hand, be careful not to collapse them. Do not bend the pipes at an angle of more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difcult to bend or stretch them any more. Do not bend or stretch the pipes more than 3 times.
Pipe connection4. 1. 2.
CAUTION
Be sure to install the pipe against the port on the indoor unit and the outdoor unit
correctly. If the centering is improper, the are nut cannot be tightened smoothly. If the are nut is forced to turn, the threads will be damaged.
Do not remove the are nut from the outdoor unit pipe until immediately before
connecting the connection pipe.
After installing the piping, make sure that the connection pipes do not touch the compressor or outer panel. If the pipes touch the compressor or outer panel, they will vibrate and produce noise.
Detach the caps and plugs from the pipes.(1)
Center the pipe against the port on the outdoor unit, and then turn the are nut by hand.(2)
To prevent gas leakage, coat the are surface with alkylbenzene oil (HAB).
Do not use mineral oil.
Attach the connection (3) pipe.
Flare nut
Connection
pipe (Liquid)
Connection pipe (Gas)
Flare nut
3-way valve (Gas)
2-way valve
(Liquid)
When the are nut is (4)
tightened properly by your hand, use a torque wrench
to nally tighten it.
Holding spanner
Torque wrench
Body side
CAUTION
Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to
tighten the are nut correctly.
Outer panel may be distorted if fastened only with a wrench. Be sure to x the elementary • part with a holding wrench (spanner) and fasten with a torque wrench (refer to below diagram). Do not apply force to the blank cap of the valve or hang a wrench, etc., on the
cap. If blank cap is broken, it may cause leakage of refrig
erant.
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1100)
HOW TO USE ADAPTER (Connection ports of outdoor unit)4. 1. 3.
When using the ADAPTER, be careful not to overtighten the nut, or the smaller pipe may be damaged. Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where
the are nut comes in. Use appropriate wrenches to avoid damaging the connection thread by overtightening the • are nut. Apply wrenches on both of are nut (local part), and ADAPTER to tighten them.
Adapter type [mm] Tightening torque [N·m (kgf·cm)]
ø12.7 → ø9.52 49 to 61 (490 to 610)
ø12.7 → ø15.88 49 to 61 (490 to 610)
ELECTRICAL WIRING5.
The precautions of electrical wiring5. 1.
WARNING
Wiring connections must be performed by a qualied person in accordance with specications.
The rated supply of this product is 50Hz, 230V. Use a voltage within the range of 198-264V.
Before connecting the wires, make sure the power supply is OFF.
Be sure to install a breaker of the specied capacity. When selecting breaker, please
comply with the laws and the regulations of each country. One breaker must be installed on the power supply of the outdoor unit. Wrong selection and setup of the breaker will
cause electric shock or re.
Be sure to install an earth leakage breaker. Otherwise, it will cause electric shock or
re.
Do not connect AC power supply to the transmission line terminal board. Improper wiring can damage the entire system.
Connect the connector cable securely to the terminal.
Faulty installation can cause a re.
Make sure to secure the insulation portion of the connector cable with the cable clamp. A damaged insulation can cause a short circuit.
Never install a power factor improvement condenser. Instead of improving the power factor, the condenser may overheat.
Before servicing the unit, turn the power supply switch OFF. Then, do not touch electric parts for 5 minutes due to the risk of electric shock.
Make sure to perform grounding work. Improper grounding work can cause electric shocks.
CAUTION
The primary power supply capacity is for the air conditioner itself, and does not include the concurrent use of other devices.
Do not use crossover power supply wiring for the outdoor unit.
If the electrical power is inadequate, contact your electric power company.
Install a breaker in a location that is not exposed to high temperatures. If the temperature surrounding the breaker is too high, the amperage at which the breaker cuts out may decrease.
This system uses an inverter which means that it must be used an earth leakage breaker that can handle harmonics in order to prevent malfunctioning of the earth leakage breaker itself.
When the electrical switchboard is installed outdoors, place it under lock and key so that it is not easily accessible.
Do not fasten the power supply cable and connection cable together.
Always keep to the maximum length of the connection cable. Exceeding the maximum length may lead to erroneous operation.
Page 7
En-6
CAUTION
The static electricity that is charged to the human body can damage the control PC Board when handling the control PC Board for address setting, etc. Please keep caution to the following points. Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
Cut off the power supply (breaker). Touch the metal section (such as the unpainted control box section) of the indoor or
outdoor unit for more than 10 seconds. Discharge the static electricity in your body. Never touch the component terminal or pattern on the PC Board.
Electrical requirement5. 2.
CAUTION
Be sure to install a breaker of the specied capacity.
Regulation of cables and breaker differs from each locality, refer in accordance with local rules.
Voltage rating
1Φ 230V (50Hz)
Operating range
198-264V
Cable Cable size (mm2) *1Type Remarks
Power supply cable 4.0
Type 60245 IEC 66
2 cable + Earth (Ground),
1 Ø 230V
Connection cable 1.5
Type 60245 IEC 57
3 cable + Earth (Ground),
1 Ø 230V
*1
Selected sample: Select the correct cable type and size according to the country or
region’s regulations. Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the
wire diameter when the wire length is long.
Breaker Specication
*2
Circuit breaker (over current) Current : 25 (A)
Earth leakage breaker Leakage current : 30mA 0.1sec or less
*3
*2
Select the appropriate breaker of the described specication according to the national
or regional standards.
*3
Select the breaker that enough load current can pass through it.
Before starting work check that power is not being supplied to all poles of the indoor unit and outdoor unit. Install all electrical works in accordance to standard. Install the disconnect device with a contact gap of at least 3mm in all poles nearby the
units. (Both indoor unit and outdoor unit) Wiring size must comply with the applicable local and national code.
Unit wiring5. 3.
When stripping off the coating of a lead wire, always use a special tool such as a wire stripper. If there is no special tool available, carefully strip the coating with a knife etc.
Earth (Ground) wire
30 mm
100 mm or more
Power supply cable
Earth (Ground) wire
15 mm
60 mm or more
Connection cable
How to connect wiring to the terminal Caution when wiring cable
Use crimp-type terminals with insulating sleeves as shown in the gure to (1) connect to the terminal block.
Securely clamp the crimp-type terminals to the wires using an appropriate tool (2) so that the wires do not come loose.
Use the specied wires, connect them securely, and fasten them so that there is (3)
no stress placed on the terminals.
Use an appropriate screwdriver to tighten the terminal screws. Do not use a (4) screwdriver that is too small, otherwise, the screw heads may be damaged and prevent the screws from being properly tightened. Do not tighten the terminal screws too much, otherwise, the screws may break.(5)
See the table below for the terminal screw tightening torques.(6)
Strip : 10mm
Wire
Terminal blocks
Crimp-type terminal
Sleeve
Wire
Crimp-type terminal
Screw with special washer
Screw with special washer
Crimp-type terminal
Tightening torque [N·m (kgf·cm)]
M4 screw 1.2 to 1.8 (12 to 18)
Connection diagrams5. 4.
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
OUTDOOR UNIT
Power cable
EARTH
(GROUND)
D D
C
C
B
B
A
L N
A
POWER
230V
50 Hz · 1ø
INDOOR UNIT
Connection cable
Connection cable
Connection cable
Connection cable
Outdoor unit5. 5.
Service panel removal(1) Remove the two mounting screws. Remove the service panel by pushing downwards.
Hook
(3 places)
Service panel
Direction of the service panel removal
Connect the power supply (2)
cable and the connection
cable to terminal.
Power cable
UNIT D connection cable
UNIT C connection cable
UNIT B connection cable
UNIT A connection cable
Fasten the power supply (3)
cable and connection
cable with cable clamp.
UNIT A UNIT B UNIT C UNIT D
Page 8
En-7
Be sure to seal the holes (4) when applying the putty. Place the cables side by
side. (Do not overlap the cables.)
Putty
Put the service panel and (5) valve cover back after completion of the work.
PIPE INSTALLATION II6.
Vacuum6. 1.
CAUTION
Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the outdoor unit at the factory.
Refrigerant must not be discharged into atmosphere.
Use a vacuum pump, gauge manifold and charge hose for R410A exclusively. Using the same vacuum for different refrigerants may damage the vacuum pump or the unit.
After connecting the piping, check the joints for gas leakage with gas leak detector or soapy water.
CHECKING GAS LEAKAGE AND PURGING AIR6. 1. 1.
Gas leak checks are performed using either vacuum or nitrogen gas, so select the proper one depending on the situation. Checking gas leaks with vacuum:
Check if the piping connections are secure.(1) Remove the cap of 3-way valve, and connect the gauge manifold charge hoses to the (2) charging port of the 3-way valve. Open the valve of the gauge manifold fully.(3) Operate the vacuum pump and start pump down.(4) Check that the compound pressure gauge reads -0.1 MPa (76 cmHg), operate the (5) vacuum pump for 30 minutes or more in each valve. At the end of pump down, close the valve of the gauge manifold fully and stop the (6) vacuum pump.
(It checks that leave as it is for about 10 minutes, and a needle does not return.)
Disconnect the charge hose from the 3-way valve charging port.(7) Remove the blank caps, and fully open the spindles of the 2-way and 3-way valves (8) with a hexagon wrench.
[torque: 6 to 7 N·m (60 to 70 kgf·cm)]. Tighten the blank caps and charging port cap of the 2-way valve and 3-way valve to (9) the specied torque.
Checking gas leaks with nitrogen gas:
Check if the piping connections are secure.(1) Remove the cap of 3-way valve, and connect the gauge manifold charge hoses to the (2) charging port of the 3-way valve. Pressurize with nitrogen gas using the 3-way valve charging port.(3) Do not pressurize up to the specied pressure all at once but do so gradually. (4)
Increase the pressure up to 0.5 Mpa (5 kgf/cm
2
), let it sit for about ve minutes
and then check for any decrease in pressure.
Increase the pressure up to 1.5 Mpa (15 kgf/cm
2
), let it sit for about ve minutes
and then check for any decrease in pressure.
Increase the pressure up to the specied pressure (the pressure designed for the product) and then make a note of it. Let it sit at the specied pressure and if there is no decrease in pressure then it is (5) satisfactory. If a pressure decrease is conrmed, there is a leak, so it is necessary to
specify the leak location and make minor adjustments. Discharge the nitrogen gas and starting removing the gas with a vacuum pump.(6) Open the valve of the gauge manifold fully.(7) Operate the vacuum pump and start pump down.(8) Check that the compound pressure gauge reads -0.1 MPa (76 cmHg), operate the (9) vacuum pump for 30 minutes or more in each valve. At the end of pump down, close the valve of the gauge manifold fully and stop the (10) vacuum pump. Disconnect the charge hose from the 3-way valve charging port.(11) Remove the blank caps, and fully open the spindles of the 2-way and 3-way valves (12) with a hexagon wrench.
[torque: 6 to 7 N·m (60 to 70 kgf·cm)]. Tighten the blank caps and charging port cap of the 2-way valve and 3-way valve to (13) the specied torque.
Tightening torque
Blank cap
6.35 mm (1/4 in.) 20 to 25 N·m (200 to 250 kgf·cm)
9.52 mm (3/8 in.) 20 to 25 N·m (200 to 250 kgf·cm)
12.70 mm (1/2 in.) 28 to 32 N·m (280 to 320 kgf·cm)
15.88 mm (5/8 in.) 30 to 35 N·m (300 to 350 kgf·cm)
19.05 mm (3/4 in.) 35 to 40 N·m (350 to 400 kgf·cm)
Charging port cap
10 to 12 N·m (100 to 120 kgf·cm)
Hexagon wrench
Charging port
Service hose with valve core
Service hose with valve core
Service hose with valve core
Service hose with valve core
Blank cap
Spindle
Cap
Lo
Hi
Gauge manifold
Vacuum pump
Service hose
CAUTION
Do not purge the air with refrigerants, but use a vacuum pump to vacuum the installation! There is no extra refrigerant in the outdoor unit for air purging!
Use a vacuum pump and gauge manifold and charging hose for R410A exclusively. Using the same vacuum for different refrigerants may damage the vacuum pump or the unit.
Additional charging6. 2.
Refrigerant suitable for a total piping length of 50 m is charged in the outdoor unit at the factory. When the piping is longer than 50 m, additional charging is necessary. For the additional amount, see the table below.
Total piping
length
50m
(164 ft)
60m
(197 ft)
70m
(230 ft)
Additional refrigerant
None
250g
(8.8 oz)
500g
(17.6 oz)
25g/m
(0.27 oz/ft)
CAUTION
When moving and installing the air conditioner, do not mix gas other than the specied refrigerant (R410A) inside the refrigerant cycle.
When charging the refrigerant R410A, always use an electronic balance for refrigerant
charging (to measure the refrigerant by weight).
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and always charge from the liquid phase side whose composition is stable.
Gas
Liquid
R410A
Add refrigerant from the charging valve after the completion of the work.
If the units are further apart than the maximum pipe length, correct operation can not be guaranteed.
Page 9
En-8
POWER7.
WARNING
Always use a special branch circuit and install a special receptacle to supply power to the air conditioner.
Use a special branch circuit breaker and receptacle matched to the capacity of the air
conditioner. (Install in accordance with standard.)
Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
Install a leakage special branch circuit breaker in accordance with the related laws and regulations and electric company standards.
CAUTION
When the voltage is low and the air conditioner is difcult to start, contact the power
company the voltage raised.
TEST RUN8.
The test run method may be different for each indoor unit that is connected. Refer to the installation Manual included with each indoor unit.
CAUTION
Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection.
Make a TEST RUN in accordance with the installation Manual 8. 1. for the indoor unit
CHECK ITEMS8. 1. 1.
(1) INDOOR UNIT
Is operation of each button on the remote controller normal?(1) Does each lamp light normally?(2) Do the air ow-direction louver operate normally?(3) Is the drain normal?(4) Is there any abnormal noise and vibration during operation?(5)
(2) OUTDOOR UNIT
Is there any abnormal noise and vibration during operation?(1) Will noise, wind, or drain water from the unit disturb the neighbors?(2)
Is there any gas leakage?(3) Do not operate the air conditioner in the test running state for a long time. For the operation method, refer to the operating manual and perform operation check.
Outdoor unit LEDS8. 2.
When a malfunction occurs in the outdoor unit, the LED on the circuit board lights to indicate the error. Refer to the following table for the description of each error according to the LED.
Error contents LED 1 LED 2 LED 3 LED 4
Communication error
(outdoor unit to indoor unit A)
●1 time - - -
Communication error
(outdoor unit to indoor unit B)
- ●1 time - -
Communication error
(outdoor unit to indoor unit C)
- - ●1 time -
Communication error
(outdoor unit to indoor unit D)
- - - ●1 time
Discharge temp. sensor error ●2 times - - -
Outdoor unit Heat Ex. middle temp. sensor error
●3 times - - -
Outdoor temp. sensor error ●4 times - - -
2 way valve temp. sensor error(for Indoor unit A)
●5 times - - -
2 way valve temp. sensor error(for Indoor unit B)
- ●5 times - -
2 way valve temp. sensor error(for Indoor unit C)
- - ●5 times -
2 way valve temp. sensor error(for Indoor unit D)
- - - ●5 times
3 way valve temp. sensor error(for Indoor unit A)
●6 times - - -
3 way valve temp. sensor error(for Indoor unit B)
- ●6 times - -
3 way valve temp. sensor error(for Indoor unit C)
- - ●6 times -
3 way valve temp. sensor error(for Indoor unit D)
- - - ●6 times
Compressor temp. sensor error ●7 times - - -
Heat sink temp. sensor error ●8 times - - -
High pressure switch 1 error ●9 times - - -
High pressure switch 2 error ●10 times - - -
Indoor unit capacity error ●11 times - - -
Trip detection ●12 times - - -
Compressor rotor position detection error ●13 times - - -
Error contents LED 1 LED 2 LED 3 LED 4
Trip terminal L error ●14 times - - -
Outdoor unit fan motor error ●15 times - - -
Outdoor unit PCB microcomputer communication error
●17 times - - -
Discharge temperature error ●18 times - - -
Compressor temperatuer error ●19 times - - -
4 way valve error ●20 times - - -
Outdoor unit PCB model information error ●21times - - -
Active lter error, PFC circuit error ●22 times - - -
● : ashing - : Off
LED is on a reverse
side of the board.
Hole
LED4
LED3
LED2
LED1
PUMP DOWN9.
PUMP DOWN OPERATION To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or forced cooling operation according to
the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced cooling operation.)
Do the air purging of the charge hose by connecting the charging hose of gauge (1) manifold to the charging port of 3 way valve (At lease one unit of connected units) and
opening the low pressure valve slightly.
Close the valve stem of 2 way valve (All connected units) completely.(2) Start the cooling operation or following forced cooling operation. (All connected units) (3)
When using the remote controller Press the TEST RUN button after starting the cooling operation by the remote controller. The operation indicator lamp and timer indicator
lamp will begin to ash simultaneously during test run. When using the MANUAL AUTO button of the indoor unit (The remote controller is lost, and so on.) Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds. (The forced
cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for
more than 10 seconds.) Close the valve stem of 3 way valve (All connected units) when the reading on the (4) compound pressure gauge becomes 0.05~0 Mpa (0.5~0 kg/cm
2
).
Stop the operation. (All connected units) Press the START/STOP button of the remote (5)
controller to stop the operation. Press the MANUAL AUTO button when stopping the
operation from indoor unit side. (It is not necessary to press on keeping for more than 10 seconds.)
Loading...