Fujitsu ASYG18KMTA, ASYG24KMTA, AOYG18KMTA, AOYG24KMTA Design & Technical Manual

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ASYG18KMTA ASYG24KMTA
AOYG18KMTA AOYG24KMTA
DR_AS093EF_01
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Trademarks
FGLair™ is trademark of Fujitsu General Limited in the United States, other countries or both.
Google Play™
App Store® is a service mark of Apple Inc., registered in the U.S. and other countries.
is trademark of Google Inc.
Copyright © 2019 Fujitsu General Limited. All rights reserved.
CONTENTS
Part 1. INDOOR UNIT...........................................................................1
1. Specifications................................................................................................2
2. Dimensions....................................................................................................4
2-1. Models: ASYG18KMTA and ASYG24KMTA....................................................................4
3. Wiring diagrams ............................................................................................6
3-1. Models: ASYG18KMTA and ASYG24KMTA....................................................................6
4. Capacity table................................................................................................7
4-1. Cooling capacity...............................................................................................................7
4-2. Heating capacity ..............................................................................................................8
5. Fan performance ...........................................................................................9
5-1. Air velocity distributions....................................................................................................9
5-2. Airflow............................................................................................................................11
6. Operation noise (sound pressure).............................................................13
6-1. Noise level curve............................................................................................................13
6-2. Sound level check point.................................................................................................14
7. Safety devices .............................................................................................15
8. External input and output...........................................................................16
8-1. External input.................................................................................................................16
8-2. External output...............................................................................................................18
9. Group connection .......................................................................................20
10. Remote controller .......................................................................................21
10-1.Wireless remote controller ............................................................................................21
11. Function settings ........................................................................................23
11-1.Function settings by using remote controller................................................................. 23
11-2.Custom code setting for wireless remote controller.......................................................28
12. Accessories .................................................................................................29
12-1.Models: ASYG18KMTA and ASYG24KMTA.................................................................29
13. Optional parts .............................................................................................30
13-1.Controllers ....................................................................................................................30
13-2.Others...........................................................................................................................31
CONTENTS (continued)
Part 2. OUTDOOR UNIT.....................................................................33
1. Specifications..............................................................................................34
2. Dimensions..................................................................................................35
2-1. Model: AOYG18KMTA................................................................................................... 35
2-2. Model: AOYG24KMTA................................................................................................... 36
3. Installation space ........................................................................................37
3-1. Models: AOYG18KMTA and AOYG24KMTA................................................................. 37
4. Refrigerant circuit .......................................................................................40
4-1. Model: AOYG18KMTA................................................................................................... 40
4-2. Model: AOYG24KMTA................................................................................................... 41
5. Wiring diagrams ..........................................................................................42
5-1. Model: AOYG18KMTA................................................................................................... 42
5-2. Model: AOYG24KMTA................................................................................................... 42
6. Capacity compensation rate for pipe length and height difference........43
6-1. Model: AOYG18KMTA................................................................................................... 43
6-2. Model: AOYG24KMTA................................................................................................... 44
7. Additional charge calculation ....................................................................45
7-1. Model: AOYG18KMTA................................................................................................... 45
7-2. Model: AOYG24KMTA................................................................................................... 45
8. Airflow..........................................................................................................46
8-1. Model: AOYG18KMTA................................................................................................... 46
8-2. Model: AOYG24KMTA................................................................................................... 46
9. Operation noise (sound pressure).............................................................47
9-1. Noise level curve............................................................................................................47
9-2. Sound level check point.................................................................................................48
10. Electrical characteristics ............................................................................49
11. Safety devices .............................................................................................50
12. Accessories .................................................................................................51
12-1.Models: AOYG18KMTA and AOYG24KMTA................................................................ 51

Part 1. INDOOR UNIT

WALL MOUNTED TYPE:
ASYG18KMTA ASYG24KMTA

1. Specifications

Type
WALL MOUNTED
ASYG18, 24KMTA
Model name ASYG18KMTA ASYG24KMTA
Power supply 230 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V
Capacity
Input power
Current
EER Cooling COP Heating 4.04 4.19 Sensible capacity Cooling kW 4.05 5.30
Power factor
Moisture removal L/h (pints/h) 1.7 (3.0) 2.7 (4.8)
Maximum operating current *1
Fan
Sound pressure level *2
Heat exchanger type
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Drain hose
Operation range
Remote control
NOTES:
Wall mounted
Inverter heat pump
Cooling
Heating
Cooling
Heating
Fan
Cooling Heating 7.0 8.6
Cooling Heating 98 96
Cooling Heating 13.5 16.0
Cooling
Airflow rate
Heating
Type × Q'ty Cross flow fan × 1 Motor output W 59
Cooling
Heating
Dimensions (H × W × D)
Fin pitch
Rows × Stages
Pipe type Copper Fin type Aluminum Material Polystyrene
Color
Net Gross 322 × 1,078 × 346 Net Gross 18
Size
Method Flare Material PP + HDPE Size mm Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Cooling
Heating °C 16 to 30
Specifications are based on the following conditions:
• – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play™ store or on App Store®. Optional WLAN adapter is also required. For details, refer to the setting manual.
Rated
Min.—Max.
Rated
Min.—Max.
Rated Min.—Max. 0.09—1.66 0.24—3.15 Rated 1.56 1.91 Min.—Max. 0.09—2.86 0.14—3.00 HIGH MED 22.9 26.7 LOW 13.3 13.3 QUIET 8.2 8.2
Rated A
HIGH MED 810 850 LOW 640 640 QUIET 510 510 HIGH 1,020 1,170 MED 850 850 LOW 640 640 QUIET 510 510
HIGH MED 40 40 LOW 35 35 QUIET 29 29 HIGH 46 49 MED 40 40 LOW 35 35 QUIET 29 29
Liquid Gas Ø 12.70 (Ø 1/2)
kW 5.20 7.10
Btu/h 17,700 24,200
kW 0.90—6.00 0.90—8.30
Btu/h 3,100—20,500 3,100—28,300
kW 6.30 8.00
Btu/h 21,500 27,200
kW 0.90—8.70 0.90—10.10
Btu/h 3,100—29,600 3,100—34,400
kW
W
kW/kW
%
A
m3/h
dB (A)
mm
mm
kg
mm (in)
°C 18 to 32
%RH 80 or less
Wireless remote controller (Option: Wired remote controller, Mobile app*3 [FGLair™])
1.39 2.08
37.5 61.6
6.1 9.3
3.74 3.41
98 98
9.5 13.5
980 1,170
45 49
Main1: 210 × 798 × 26.6, Main2: 135 × 798 × 20
Sub1: 84 × 798 × 13.3, Sub2: 84 × 798 × 13.3
Main1: 1.2, Main2: 1.1
Sub1: 1.4, Sub2: 1.4
Main1: 2 × 10, Main2: 2 × 8
Sub1: 1 × 4, Sub2: 1 × 4
Approximate color of Munsell N 9.25/
White
280 × 980 × 240
12.5
Ø 6.35 (Ø 1/4)
WALL MOUNTED
ASYG18, 24KMTA
- 2 -
1. Specifications
Specifications for ErP Lot10
Model name ASYG18KMTA ASYG24KMTA
Energy efficiency class
WALL MOUNTED
ASYG18, 24KMTA
Pdesign
SEER Cooling SCOP Heating (Average) 4.56 4.18
Annual energy consumption
Sound power level
Cooling
Heating (Average) Cooling Heating (Average) 4.8 (-10°C) 7.1 (-10°C)
QCE QHE (Average) 1,472 2,372 Cooling Heating 61 65
HIGH dB (A)
kW
kWh/kWh
kWh/a
5.2 (35°C) 7.1 (35°C)
7.77 7.28
234 341
60 65
++
A
+
A
WALL MOUNTED
ASYG18, 24KMTA
- 3 -
1. Specifications

2. Dimensions

Unit: mm
980 240
280
Outline of indoor unit
for pipe inlet Ø65for pipe inlet Ø65
37
37
400 9041377
7341761 429
115
72
WALL MOUNTED

2-1. Models: ASYG18KMTA and ASYG24KMTA

ASYG18, 24KMTA
WALL MOUNTED
ASYG18, 24KMTA
2-1. Models: ASYG18KMTA and ASYG24KMTA 2. Dimensions
- 4 -
¢
Unit: mm
Wall hook bracket
Outline of the indoor unit
50 or more
71 or more
40 or more
70 or more
117 or more
1,500 or more
1,800 or more
160 or more
The flare connection part should be installed outdoors.
Provide sufficient installation space for product safety.
WALL MOUNTED
ASYG18, 24KMTA
Installation space requirement
WALL MOUNTED
ASYG18, 24KMTA
2-1. Models: ASYG18KMTA and ASYG24KMTA 2. Dimensions
- 5 -

3. Wiring diagrams

WALL MOUNTED

3-1. Models: ASYG18KMTA and ASYG24KMTA

ASYG18, 24KMTA
WALL MOUNTED
ASYG18, 24KMTA
3-1. Models: ASYG18KMTA and ASYG24KMTA 3. Wiring diagrams
- 6 -

4. Capacity table

Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
WALL MOUNTED
ASYG18, 24KMTA
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP)

4-1. Cooling capacity

¢
M
odel: ASYG18KMTA
WALL MOUNTED
ASYG18, 24KMTA
AFR
Outdoor temperature
M
¢
AFR
Outdoor temperature
m3/h
°CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
°CDB
-10 3.18 2.84 0.46 3.48 3.11 0.46 3.59 3.21 0.46 3.82 3.41 0.47 3.93 3.52 0.47 4.19 3.75 0.48 4.47 3.99 0.48
-5 2.98 2.76 0.55 3.26 3.02 0.55 3.36 3.11 0.56 3.58 3.31 0.56 3.69 3.41 0.57 3.93 3.63 0.58 4.19 3.87 0.58 0 2.78 2.68 0.64 3.05 2.93 0.65 3.14 3.02 0.65 3.34 3.21 0.66 3.44 3.31 0.67 3.67 3.52 0.67 3.91 3.76 0.68 5 3.12 2.81 0.44 3.41 3.07 0.44 3.52 3.17 0.45 3.74 3.37 0.45 3.86 3.47 0.45 4.11 3.70 0.46 4.38 3.94 0.46
10 2.95 2.74 0.52 3.23 3.00 0.53 3.33 3.09 0.53 3.54 3.29 0.54 3.65 3.39 0.54 3.88 3.61 0.55 4.14 3.85 0.55 15 3.83 3.11 0.57 4.19 3.40 0.57 4.32 3.51 0.58 4.60 3.73 0.58 4.74 3.84 0.59 5.05 4.09 0.60 5.38 4.37 0.60 20 4.61 3.45 0.93 5.05 3.77 0.94 5.20 3.89 0.95 5.53 4.13 0.96 5.70 4.26 0.97 6.07 4.54 0.98 6.48 4.84 0.99 25 4.49 3.40 1.05 4.92 3.72 1.06 5.07 3.83 1.07 5.39 4.08 1.08 5.56 4.20 1.09 5.92 4.48 1.10 6.31 4.77 1.11 30 4.35 3.34 1.19 4.76 3.65 1.20 4.91 3.76 1.21 5.22 4.00 1.23 5.38 4.13 1.24 5.73 4.40 1.25 6.11 4.69 1.26 35 4.21 3.28 1.33 4.60 3.59 1.35 4.74 3.69 1.36 5.04 3.93 1.38 5.20 4.05 1.39 5.54 4.32 1.40 5.91 4.60 1.42 40 3.92 3.14 1.42 4.29 3.44 1.44 4.42 3.54 1.45 4.70 3.77 1.47 4.85 3.88 1.48 5.17 4.14 1.50 5.51 4.41 1.51 46 3.45 2.91 1.47 3.78 3.18 1.48 3.90 3.28 1.50 4.14 3.48 1.51 4.27 3.59 1.53 4.55 3.83 1.55 4.85 4.08 1.56
kW kW kW kW kW kW kW
Indoor temperature
980
odel: ASYG24KMTA
m3/h
°CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
°CDB
-10 4.34 3.72 0.68 4.75 4.07 0.69 4.90 4.20 0.70 5.21 4.46 0.70 5.37 4.60 0.71 5.72 4.90 0.72 6.10 5.23 0.72
-5 4.07 3.61 0.82 4.46 3.95 0.83 4.59 4.07 0.84 4.88 4.33 0.84 5.03 4.46 0.85 5.36 4.76 0.86 5.72 5.07 0.87 0 3.80 3.50 0.96 4.16 3.83 0.97 4.28 3.95 0.98 4.56 4.20 0.99 4.70 4.33 1.00 5.01 4.61 1.01 5.34 4.92 1.02 5 4.26 3.68 0.65 4.66 4.02 0.66 4.80 4.14 0.67 5.11 4.41 0.67 5.27 4.54 0.68 5.61 4.84 0.69 5.98 5.16 0.69
10 4.03 3.59 0.78 4.41 3.92 0.79 4.54 4.04 0.80 4.83 4.30 0.81 4.98 4.43 0.81 5.30 4.72 0.82 5.65 5.04 0.83 15 5.23 4.07 0.85 5.73 4.45 0.85 5.90 4.59 0.86 6.27 4.88 0.87 6.47 5.03 0.88 6.89 5.36 0.89 7.35 5.71 0.90 20 6.29 4.51 1.39 6.89 4.94 1.41 7.10 5.09 1.42 7.55 5.41 1.44 7.78 5.58 1.45 8.29 5.95 1.46 8.84 6.34 1.48 25 6.14 4.45 1.56 6.71 4.87 1.58 6.92 5.02 1.60 7.36 5.34 1.61 7.59 5.50 1.63 8.08 5.86 1.65 8.62 6.25 1.66 30 5.94 4.37 1.78 6.50 4.78 1.80 6.70 4.93 1.82 7.12 5.24 1.84 7.34 5.40 1.86 7.82 5.75 1.87 8.34 6.13 1.89 35 5.74 4.29 2.00 6.28 4.69 2.02 6.48 4.83 2.04 6.89 5.14 2.06 7.10 5.30 2.08 7.57 5.65 2.10 8.07 6.02 2.12 40 5.36 4.11 2.13 5.86 4.50 2.15 6.04 4.63 2.18 6.42 4.93 2.20 6.62 5.08 2.22 7.05 5.41 2.24 7.52 5.77 2.26 46 4.72 3.80 2.20 5.16 4.16 2.22 5.32 4.29 2.24 5.66 4.56 2.27 5.83 4.70 2.29 6.21 5.01 2.31 6.62 5.34 2.34
kW kW kW kW kW kW kW
Indoor temperature
1,170
4-1. Cooling capacity 4. Capacity table
- 7 -

4-2. Heating capacity

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
WALL MOUNTED
ASYG18, 24KMTA
¢
Model: ASYG18KMTA
WALL MOUNTED
ASYG18, 24KMTA
AFR
Outdoor temperature
M
¢
AFR
Outdoor temperature
m3/h
16 18 20 22 24 26 28
°CDB °CWB
-15 -16 5.17 1.92 5.04 1.96 4.90 2.00 4.76 2.04 4.63 2.08 4.49 2.12 4.36 2.16
-10 -11 6.23 1.89 6.06 1.93 5.90 1.98 5.74 2.01 5.57 2.04 5.41 2.09 5.25 2.13
-5 -7 7.31 2.11 7.12 2.15 6.93 2.07 6.74 2.24 6.55 2.28 6.36 2.33 6.17 2.37 0 -2 8.45 2.71 8.23 2.76 8.01 2.70 7.79 2.87 7.57 2.93 7.34 2.99 7.12 3.05 5 3 9.36 3.18 9.11 3.25 8.87 3.32 8.63 3.38 8.38 3.44 8.14 3.52 7.89 3.58 7 6 9.18 2.75 8.94 2.80 8.70 2.86 8.46 2.91 8.22 2.97 7.98 3.03 7.74 3.09
10 8 9.29 2.64 9.05 2.69 8.81 2.79 8.56 2.81 8.32 2.86 8.08 2.92 7.83 2.97 15 10 9.35 2.28 9.11 2.32 8.86 2.46 8.62 2.42 8.37 2.46 8.13 2.52 7.88 2.56 20 15 9.42 2.04 9.17 2.09 8.93 2.17 8.68 2.17 8.43 2.21 8.19 2.26 7.94 2.30 24 18 9.48 1.89 9.23 1.93 8.98 1.97 8.73 2.01 8.48 2.05 8.24 2.09 7.99 2.13
TC IP TC IP TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW kW kW
Indoor temperature
1,020
odel: ASYG24KMTA
m3/h
16 18 20 22 24 26 28
°CDB °CWB
-15 -16 7.29 2.76 7.10 2.81 6.91 2.87 6.72 2.93 6.53 2.98 6.34 3.05 6.15 3.10
-10 -11 8.23 2.83 8.01 2.89 7.80 2.94 7.58 3.01 7.37 3.07 7.15 3.13 6.94 3.19
-5 -7 9.17 2.96 8.93 3.02 8.69 3.04 8.45 3.15 8.21 3.21 7.97 3.27 7.73 3.33 0 -2 10.11 3.17 9.85 3.24 9.58 3.26 9.32 3.37 9.05 3.43 8.79 3.50 8.52 3.57 5 3 10.87 3.34 10.58 3.41 10.30 3.48 10.02 3.55 9.73 3.61 9.45 3.69 9.16 3.76 7 6 10.66 2.88 10.38 2.94 10.10 3.00 9.82 3.06 9.54 3.11 9.26 3.18 8.98 3.24
10 8 10.78 2.77 10.50 2.83 10.22 2.93 9.94 2.94 9.66 3.00 9.37 3.06 9.09 3.12 15 10 10.86 2.39 10.58 2.44 10.29 2.58 10.01 2.54 9.72 2.59 9.44 2.64 9.15 2.69 20 15 10.93 2.15 10.65 2.19 10.36 2.28 10.07 2.28 9.79 2.32 9.50 2.37 9.22 2.41 24 18 11.00 1.99 10.71 2.03 10.42 2.07 10.13 2.11 9.84 2.15 9.56 2.19 9.27 2.24
TC IP TC IP TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW kW kW
Indoor temperature
1,170
4-2. Heating capacity 4. Capacity table
- 8 -

5. Fan performance

2
1
0
1
2
Unit: m/s
(m)
(m)
0123456789
2.0
1.0
0.5
3
2
1
0
1
2
3
Unit: m/s
(m)
(m)
0123456789
0.5
0.5
1.0
1.0
2.0
2.0
3
2
1
0
Unit: m/s
(m)
(m)
0123456789
2.0
1.0
0.5
3
2
1
0
Unit: m/s
(m)
(m)
0123456789
0.51.02.0
WALL MOUNTED

5-1. Air velocity distributions

ASYG18, 24KMTA
¢
Measuring conditions
Model: ASYG18KMTA
Top view Vertical airflow direction louver
Horizontal airflow direction louver: Center
: Up
Fan speed Operation mode
HIGH FAN
WALL MOUNTED
ASYG18, 24KMTA
Top view Vertical airflow direction louver
Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver
Horizontal airflow direction louver: Center
: Up
: Up
Side view Vertical airflow direction louver
Horizontal airflow direction louver: Center
: Down
5-1. Air velocity distributions 5. Fan performance
- 9 -
Model: ASYG24KMTA
2
1
0
1
2
Unit: m/s
(m)
(m)
0123456789
2.0 1.0
0.5
3
2
1
0
1
2
3
Unit: m/s
(m)
(m)
0123456789
0.5
0.5
2.0
2.0
1.0
1.0
3
2
1
0
Unit: m/s
(m)
(m)
0123456789
2.0
1.0
0.5
3
2
1
0
Unit: m/s
(m)
(m)
0123456789
0.51.02.0
¢
Measuring conditions
WALL MOUNTED
ASYG18, 24KMTA
Top view Vertical airflow direction louver
Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver
Horizontal airflow direction louver: Left & Right
: Up
: Up
Fan speed Operation mode
HIGH FAN
WALL MOUNTED
ASYG18, 24KMTA
Side view Vertical airflow direction louver
Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver
Horizontal airflow direction louver: Center
: Up
: Down
5-1. Air velocity distributions 5. Fan performance
- 10 -

5-2. Airflow

¢
WALL MOUNTED
ASYG18, 24KMTA
Cooling
Model: ASYG18KMTA
Fan speed Airflow
HIGH
MED
LOW
QUIET
m3/h
l/s 272
CFM 577
m3/h
l/s 225
CFM 477
m3/h
l/s 178
CFM 377
m3/h
l/s 142
CFM 300
980
810
640
510
WALL MOUNTED
ASYG18, 24KMTA
Heating
Fan speed Airflow
HIGH
MED
LOW
QUIET
m3/h
l/s 283
CFM 600
m3/h
l/s 236
CFM 500
m3/h
l/s 178
CFM 377
m3/h
l/s 142
CFM 300
1,020
850
640
510
5-2. Airflow 5. Fan performance
- 11 -
¢
Cooling
WALL MOUNTED
ASYG18, 24KMTA
Heating
Model: ASYG24KMTA
Fan speed Airflow
HIGH
MED
LOW
QUIET
m3/h
l/s 325
CFM 689
m3/h
l/s 236
CFM 500
m3/h
l/s 178
CFM 377
m3/h
l/s 142
CFM 300
1,170
850
640
510
WALL MOUNTED
ASYG18, 24KMTA
Fan speed Airflow
m3/h
HIGH
MED
LOW
QUIET
l/s 325
CFM 689
m3/h
l/s 236
CFM 500
m3/h
l/s 178
CFM 377
m3/h
l/s 142
CFM 300
1,170
850
640
510
5-2. Airflow 5. Fan performance
- 12 -

6. Operation noise (sound pressure)

Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
QUIET
HIGH
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
QUIET
HIGH
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
WALL MOUNTED

6-1. Noise level curve

ASYG18, 24KMTA
¢
Cooling
Model: ASYG18KMTA
Heating
WALL MOUNTED
ASYG18, 24KMTA
M
¢
odel: ASYG24KMTA
Cooling
Heating
6-1. Noise level curve 6. Operation noise (sound pressure)
- 13 -

6-2. Sound level check point

0.8 m
1 m
Microphone Microphone
WALL MOUNTED
ASYG18, 24KMTA
NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated
above.
WALL MOUNTED
ASYG18, 24KMTA
6-2. Sound level check point 6. Operation noise (sound pressure)
- 14 -

7. Safety devices

WALL MOUNTED
ASYG18, 24KMTA
Circuit protection Current fuse (PCB*) 250 V, 3.15 A
Fan motor protection
*PCB: Printed Circuit Board
Type of
protection
Protection form
Thermal protector program
Activate
Reset
Model
ASYG18KMTA ASYG24KMTA
125 ±24°C
Fan motor stop
100 ±25°C
Fan motor restart
WALL MOUNTED
ASYG18, 24KMTA
- 15 -
7. Safety devices

8. External input and output

Signal
Locally purchased
Indoor unit
control PCB
Communication kit
Optional parts
Connector
1
3
10 m*
Connected unit
Example: Switch
Operation
Stop
On Off
Input signal
Indoor unit
With using external input and output functions, this product can be operated inter-connectedly with an external device.
WALL MOUNTED
ASYG18, 24KMTA

8-1. External input

With using external input function, some functions on this product can be controlled from an external device.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢
The air conditioner can be remotely operated by means of the following on-site work. Unit operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
Connector Input Output Remarks
CNA01 Control input — CNB01 Operation status output CNB02 Error status output
See external input/output
settings for details.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
Control input (Operation/Stop or Forced stop)
WALL MOUNTED
ASYG18, 24KMTA
Unit operation Initial setting after power is on Starting mode other than initial setting
Operation mode Auto changeover Mode at previous operation Set temperature 24 °C Temperature at previous operation
Airflow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example:
• Contact capacity: DC 24 V or more, 10 mA or more.
*: Make the distance from the PCB to the connected unit within 10 m.
• Use non-polar relays and switches.
When function setting is “Operation/Stop” mode:
8-1. External input 8. External input and output
- 16 -
When function setting is “Forced stop” mode:
Remote controller
On On On
Input signal
Indoor unit
Command
Remote control operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
WALL MOUNTED
ASYG18, 24KMTA
Optional part:
Part name Model name Exterior
External input wire
External connect kit UTY-XWZXZ5
WALL MOUNTED
ASYG18, 24KMTA
* For operating the external function, the wall mounted type requires the communication kit in addi­tion to the wire (UTY-XWZXZ5).
8-1. External input 8. External input and output
- 17 -

8-2. External output

Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kit Connected unit
Example: Relay unit
1
2
Signal
Relay power supply
V
Connector
10 m*
DC 24 V
On
Off
Operation
Stop
Indoor unit
Output signal
With using external output function, operating status of this product can be transmitted to the exter­nal device, and also, this product can be inter-connected with the external device.
WALL MOUNTED
ASYG18, 24KMTA
¢
Air conditioner operation status signal can be output.
Circuit diagram example:
Operation status output
WALL MOUNTED
ASYG18, 24KMTA
– *: Make the distance from the PCB to the connected unit within 10 m. –
Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
Optional part:
Part name Model name Exterior
External output wire
External connect kit UTY-XWZXZ5
* For operating the external function, the wall mounted type requires the communication kit in addi­tion to the wire (UTY-XWZXZ5).
8-2. External output 8. External input and output
- 18 -
¢
Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kit Connected unit
Example: Relay unit
1
2
Signal
Relay power supply
V
Connector
10 m*
DC 24 V
On
Off
Error
Normal
Error status
Output signal
Air conditioner error status signal can be output.
Circuit diagram example:
WALL MOUNTED
ASYG18, 24KMTA
Error status output
– *: Make the distance from the PCB to the connected unit within 10 m. –
Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
WALL MOUNTED
ASYG18, 24KMTA
Optional part:
Part name Model name Exterior
External output wire
External connect kit UTY-XWZXZ5
* For operating the external function, the wall mounted type requires the communication kit in addi­tion to the wire (UTY-XWZXZ5).
8-2. External output 8. External input and output
- 19 -

9. Group connection

A
BCDE
I.U. I.U. I.U. I.U.
Remote controller
Example of wiring method
12
R W
Remote controller cable
Bus wire
Remote controller
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
RC AD
01
RC AD
02
RC AD
03
RC AD
04
Remote controller
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
Example of wiring method
NOTE: Group control cannot be used together with Wireless LAN adapter.
WALL MOUNTED
ASYG18, 24KMTA
Installation procedure for group control system:
A number of indoor units can be operated at the same time using a single remote controller.
NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette
type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
1. Connect up to 16 indoor units in a system.
A, B, C, D, E: Remote controller cable
Wiring length limitation A + B + C + D + E ≤ 500 m
WALL MOUNTED
ASYG18, 24KMTA
2. Set the R.C. address. (Function setting) Addresses will be automatically set when initially starting up this unit. In such a case, do not
• change the remote controller address for the indoor unit, and keep it at the initial setting of “00”.
• Only set addresses manually when using different numbers for addresses. Set the R.C. address of each indoor unit using the function setting. (Refer to “Remote con­troller address setting” in "Contents of function setting" on page 24.)
NOTES:
– Do not use the same setting value. – Setting is reflected after the power is turned on again.
Also set the R.C. address for the remote controller. For details, refer to the remote controller installation manual.
NOTE: In manual setting, connect up to 15 indoor units in a system.
- 20 -
9. Group connection

10. Remote controller

Signal
transmitter
10°C HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
OUTDOOR UNIT
LOW NOISE button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
MODE button
FAN button
RESET button
CLOCK ADJUST button
TEST RUN button
ECONOMY button
Mode indicator
LOW NOISE mode
indicator
Clock and Timer indicator
SEND indicator
Temperature indicator
Fan speed indicator
Swing indicator
Transmit indicator
WALL MOUNTED

10-1. Wireless remote controller

ASYG18, 24KMTA
¢
Overview
WALL MOUNTED
ASYG18, 24KMTA
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current op­eration.
10-1. Wireless remote controller 10. Remote controller
- 21 -
¢
Top view
Front view Side view
205
1761
48.5
5.5
26.2
69.3
6.5
Front View Side View
Bottom View
Ø 3.5 (Hole)
150
106.8
Hole
3.5
2-R
Controller
WALL MOUNTED
ASYG18, 24KMTA
Specifications
Unit: mm
WALL MOUNTED
ASYG18, 24KMTA
Size (H × W × D) mm 205 × 61 × 17 Weight g 125 (without batteries)
Holder
Unit: mm
Size (H × W × D) mm 150 × 69.3 × 26.2 Weight g 27
10-1. Wireless remote controller 10. Remote controller
- 22 -

11. Function settings

Function number
Setting value
To adjust the functions of this product according to the installation environment, various types of function settings are available.
WALL MOUNTED
ASYG18, 24KMTA
NOTE: Incorrect settings can cause a product malfunction.

11-1. Function settings by using remote controller

Some function settings can be changed on the remote controller. After confirming the setting proce­dure and the content of each function setting, select appropriate functions for your installation envi­ronment.
¢
The function number and the associated setting value are displayed on the LCD of the remote con­troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Cover for the electrical enclosure on the outdoor unit is in place.
• There is no wiring mistake.
• Piping air tight test and vacuuming have been performed firmly.
• All the necessary wiring work for outdoor unit has been finished.
Setting procedure by using wireless remote controller
WALL MOUNTED
ASYG18, 24KMTA
After reconfirming the items listed above, connect the power supply of the indoor unit.
NOTES:
• Settings will not be changed if invalid numbers or setting values are selected.
• When optional wired remote controller is used, refer to the installation manual enclosed with the remote controller.
Entering function setting mode:
While pressing the
POWERFUL button and TEMP. (
) button simulta-
neously, press the RESET button to enter the function setting mode.
Selecting the function number and setting value:
1. Press the TEMP. ( ) ( ) buttons to select the function number. To switch between the left and right digits, press the
10 °C HEAT
button.
2. Press the POWERFUL button to proceed to value setting. To re­turn the function number selection, press the POWERFUL button again.
3. Press the TEMP. ( switch between the left and right digits, press the
) ( ) buttons to select the setting value. To
10 °C HEAT but-
ton.
4. Press the MODE button once. Confirm that you hear the beep sound.
5. Press the START/STOP button to fix the function setting. Confirm that you hear the beep sound.
6. Press the RESET button to end the function setting mode.
7. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
CAUTION
After disconnecting the power supply, wait
30 seconds or more before reconnecting it. The function
setting will not become active unless the power supply is disconnected and then reconnected.
11-1. Function settings by using remote controller 11. Function settings
- 23 -
NOTES:
• The air conditioner custom code is set to prior to shipment.
WALL MOUNTED
ASYG18, 24KMTA
¢
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
If you do not know the air conditioner custom code setting, try each of the custom codes ( → → ) until you find the code that operates the air conditioner.
ontents of function setting
C
unction setting list
F
Function no. Functions
1) 00 Remote controller address setting
2) 11 Filter sign
3) 30/31 Room temperature control for indoor unit sensor
4) 35/36 Room temperature control for wired remote controller sensor
5) 40 Auto restart
6) 42 Room temperature sensor switching
7) 44 Remote controller custom code
8) 46 External input control
9) 48 Room temperature sensor switching (Aux.)
10) 49 Indoor unit fan control for energy saving for cooling
WALL MOUNTED
ASYG18, 24KMTA
1) Remote controller address setting
Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit.
Function number Setting value Setting description Factory setting
00 Unit no. 0 ♦ 01 Unit no. 1 02 Unit no. 2 03 Unit no. 3 04 Unit no. 4 05 Unit no. 5 06 Unit no. 6
00
07 Unit no. 7 08 Unit no. 8 09 Unit no. 9 10 Unit no. 10 11 Unit no. 11 12 Unit no. 12 13 Unit no. 13 14 Unit no. 14 15 Unit no. 15
NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette
type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
11-1. Function settings by using remote controller 11. Function settings
- 24 -
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
WALL MOUNTED
ASYG18, 24KMTA
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur­er’s recommended value).
Function number Setting value Setting description Factory setting
00 Standard (400 hours)
11
01 Long interval (1,000 hours) 02 Short interval (200 hours) 03 No indication
WALL MOUNTED
ASYG18, 24KMTA
Function number Setting value Setting description
00 Standard setting ♦ 01 No correction 0.0 °C 02 -0.5 °C 03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C
30
(For cooling)
31
(For heating)
08 -3.5 °C 09 -4.0 °C 10 +0.5 °C 11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
Factory
setting
More cooling Less heating
Less cooling
More heating
11-1. Function settings by using remote controller 11. Function settings
- 25 -
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
WALL MOUNTED
ASYG18, 24KMTA
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
WALL MOUNTED
ASYG18, 24KMTA
Function number Setting value Setting description
00 No correction ♦ 01 No correction 0.0°C 02 -0.5 °C 03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C
35
(For cooling)
36
(For heating)
08 -3.5 °C 09 -4.0 °C 10 +0.5 °C 11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
Factory
setting
More cooling Less heating
Less cooling
More heating
5) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable ♦ 01 Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter­nal device.
6)
Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number Setting value Setting description Factory setting
42
00 Indoor unit ♦ 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
11-1. Function settings by using remote controller 11. Function settings
- 26 -
7) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
WALL MOUNTED
ASYG18, 24KMTA
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
9) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re­mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01). When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting
Function number Setting value Setting description Factory setting
00 A
44
Function number Setting value Setting description Factory setting
46
01 B 02 C 03 D
00 Operation/Stop mode 1 ♦ 01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2
30 and 31 too.
WALL MOUNTED
ASYG18, 24KMTA
Function number Setting value Setting description Factory setting
48
00 Both ♦ 01 Wired remote controller
10) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
00 Disable
49
01 Enable 02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller. 01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed. 02: Enable or disable this function by remote controller setting.
NOTES:
As the factory setting, this setting is initially activated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for ener­gy saving function or connecting a network converter. To confirm if the remote controller has this setting, refer to the operating manual of each remote controller.
11-1. Function settings by using remote controller 11. Function settings
- 27 -

11-2. Custom code setting for wireless remote controller

To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required.
WALL MOUNTED
ASYG18, 24KMTA
NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom
When 2 or more air conditioners are installed in a room, and the remote controller is operating an air conditioner other than the one you wish to set, change the custom code of the remote controller to operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not match, the remote controller cannot be used to operate for the air conditioner.
code.
1. Press the START/STOP button until only the clock is displayed on the remote controller display.
Press the MODE button for at least 5 seconds to display the cur-
2. rent custom code. (Initially set to
.)
WALL MOUNTED
ASYG18, 24KMTA
3.
Press the TEMP. (
) ( ) buttons to change the custom code be­tween → → → . Match the code on the display to the air con­ditioner custom code. (Initially set to
4.
Press the MODE button again to return to the clock display. The
.)
custom code will be changed.
NOTES:
If no button is pressed within 30 seconds after the custom code is displayed, the system returns
• to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to
prior to shipment. To change the custom code, con-
tact your retailer.
• If you do not know the assigned code for the air conditioner, try each of the custom code ( → → → ) until you find the code which operates the air conditioner.
11-2. Custom code setting for wireless remote controller 11. Function settings
- 28 -

12. Accessories

WALL MOUNTED

12-1. Models: ASYG18KMTA and ASYG24KMTA

ASYG18, 24KMTA
Operating manual 1 Tapping screw (large) 5
Installation manual 1 Tapping screw (small) 2
Remote controller 1 Battery 2
Remote controller holder
Part name Exterior Q’ty Part name Exterior Q’ty
1 Filter holder 2
WALL MOUNTED
ASYG18, 24KMTA
Cloth tape
Wall hook bracket
1 Air cleaning filters 1
1
12-1. Models: ASYG18KMTA and ASYG24KMTA 12. Accessories
- 29 -

13. Optional parts

WALL MOUNTED

13-1. Controllers

ASYG18, 24KMTA
Exterior Part name Model name Summary
Easy finger touch operation with LCD panel. Backlit LCD enables easy
Wired remote
controller
Wired remote
controller
Simple remote
controller
UTY-RNRYZ*
UTY-RLRY
UTY-RSRY
operation in a dark room. Wire type: Non-polar 2-wire
Optional communication kit is necessary for installation.
High visibility and easy operation. Room temperature can be accurately controlled using the built-in thermo sensor.
Wire type: Non-polar 2-wire Optional communication kit is
necessary for installation. Compact remote controller
concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Non-polar 2-wire
Optional communication kit is necessary for installation.
WALL MOUNTED
ASYG18, 24KMTA
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, and
Simple remote
controller
UTY-RHRY
temperature setting. Wire type: Non-polar 2-wire
Optional communication kit is necessary for installation.
NOTES:
Available functions may differ by the remote controller. For details, refer to the operation manu­al.
• In this product, group controlling system of the wired remote controller is prohibited.
13-1. Controllers 13. Optional parts
- 30 -

13-2. Others

WALL MOUNTED
ASYG18, 24KMTA
Exterior Part name Model name Summary
Required when external device is connected.
External
connect kit
UTY-XWZXZ5
Optional communication kit is necessary for installation.
WALL MOUNTED
ASYG18, 24KMTA
External input
and output PCB
Communication
kit
Wireless LAN
adapter
UTY-XCSXZ2
UTY-TWRXZ2
UTY-TFSXF2
Use to connect with external devices and air conditioner PCB.
Use to connect Non-polar 2-core wired remote controller.
Remotely manage an air conditioning system using mobile devices such as smartphones and tablets.
13-2. Others 13. Optional parts
- 31 -
WALL MOUNTED
ASYG18, 24KMTA
WALL MOUNTED
ASYG18, 24KMTA
13-2. Others 13. Optional parts
- 32 -

Part 2. OUTDOOR UNIT

SINGLE TYPE:
AOYG18KMTA AOYG24KMTA

1. Specifications

OUTDOOR UNIT
AOYG18, 24KMTA
Type Inverter heat pump
Model name AOYG18KMTA AOYG24KMTA
Power supply 230 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current A 7.0 8.6
Fan
Sound pressure level *1
Sound power level
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Operation range
Drain hose
NOTES:
Specifications are based on the following conditions:
• – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'ty Propeller fan × 1 Motor output W 49
Type DC twin rotary Motor output W 900 1,060
Net Gross 692 × 940 × 375 776 × 961 × 450 Net Gross 40 46
Size
Method Flare Pre-charge length Max. length 25 30 Max. height difference 20 25
Cooling Heating 2,100 2,820
Cooling Heating 50 52 Cooling Heating 65 66 Dimensions (H × W × D) Fin pitch 1.3 Rows × Stages 1 × 28 1 × 32 Pipe type Copper tube
Fin type
Type (Global warming potential) R32 (675) Charge g 1,020 1,320 Type FW68S RmM68AF Amount Material Steel sheet
Color
Liquid Gas Ø 12.70 (Ø 1/2)
Cooling Heating -15 to 24 Material PP Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
m3/h
dB (A)
dB (A)
mm
Type (Material) Aluminum Surface treatment PC fin
3
cm
mm
kg
mm (in)
m
°C
2,350 3,240
50 54
65 67
588 × 881 × 18.19 588 × 851 × 18.19
350 400
632 × 799 × 290 716 × 820 × 315
Approximate color of Munsell 10YR 7.5/1.0
36 42
Beige
Ø 6.35 (Ø 1/4)
15
-10 to 46
672 × 881 × 18.19 672 × 851 × 18.19
OUTDOOR UNIT
AOYG18, 24KMTA
- 34 -
1. Specifications

2. Dimensions

Unit: mm
Side viewSide view Front view
Bottom view Side view (Valve part)
Top view
580
79919 68 16 290
33 30
109
353
632
20
330
Pitch of bolts
for installation
Pitch of bolts for installation
4-
M1
0 hole
Airflow
Drain port Ø42
37
120
184
399 180

2-1. Model: AOYG18KMTA

OUTDOOR UNIT
AOYG18, 24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
2-1. Model: AOYG18KMTA 2. Dimensions
- 35 -

2-2. Model: AOYG24KMTA

Unit: mm
Side viewSide view Front view
Top view
16 315
20 18
Airflow
600 109
353
330
Pitch of bolts
for installation
Pitch of bolts for installation
4-
M1
0 hole
82019 68
716
20
Drain port Ø42
37
410
Bottom view Side view (Valve part)
119
184
194
OUTDOOR UNIT
AOYG18, 24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
2-2. Model: AOYG24KMTA 2. Dimensions
- 36 -

3. Installation space

100 or more
250 or more
100 or more
100 or more
600 or more
600 or more
100 or more
100 or more
Max. 200
600 or more
250 or more
100 or more
Max. 200
100 or more
600 or more

3-1. Models: AOYG18KMTA and AOYG24KMTA

¢
Provide sufficient installation space for product safety.
Keep the space shown in the installation examples.
OUTDOOR UNIT
AOYG18, 24KMTA
If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Single outdoor unit installation
Space requirement
CAUTION
When the upper space is open:
Obstacles at rear only Obstacles at rear and sides
Unit: mm
OUTDOOR UNIT
AOYG18, 24KMTA
Obstacles at front Obstacles at front and rear
When there is an obstruction in the upper space:
Unit: mm
Obstacles at rear and above Obstacles at rear, sides, and above
3-1. Models: AOYG18KMTA and AOYG24KMTA 3. Installation space
- 37 -
Multiple outdoor unit installation
200 or more
250 or more
1,000 or more
250 or more
200 or more
1,000 or more
250 or more
1,500 or more
200 or more
250 or more
250 or more
Max. 300
1,500 or more
OUTDOOR UNIT
AOYG18, 24KMTA
• Provide at least 250 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following ex­ample “When an obstruction in the upper space:”.
When the upper space is open:
Unit: mm
Obstacles at rear only Obstacles at front only
OUTDOOR UNIT
AOYG18, 24KMTA
Obstacles at front and rear
When an obstruction in the upper space:
Obstacles at rear and above.
Unit: mm
3-1. Models: AOYG18KMTA and AOYG24KMTA 3. Installation space
- 38 -
Outdoor units installation in multi-row
100 or more
200 or more
500 or more
1,000 or more
200 or more
400 or more
1,000 or more
250 or more
2,000 or more
250 or more
1,000 or more
200 or more
250 or more
200 or more
OUTDOOR UNIT
AOYG18, 24KMTA
Single parallel unit arrangement Multiple parallel unit arrangement
Unit: mm
OUTDOOR UNIT
AOYG18, 24KMTA
NOTES:
If the space is larger than stated above, the condition will be the same as when there is no ob-
• stacle.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
3-1. Models: AOYG18KMTA and AOYG24KMTA 3. Installation space
- 39 -

4. Refrigerant circuit

2-way
valve
Strainer
Strainer
3-way
valve
MufflerMuffler
Acccumlator
4-way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Compressor
Cooling Heating
Th
D
Th
R
Th
PI
Th
HO
Th
O
Th
R
Th
PI
Th
D
Th
O
Th
HO
:Thermistor (Room temperature)
:Thermistor (Pipe temperature)
:Thermistor (Discharge temperature) :Thermistor (Outdoor temperature)
:Thermistor (Heat exchanger out temperature)

4-1. Model: AOYG18KMTA

OUTDOOR UNIT
AOYG18, 24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
4-1. Model: AOYG18KMTA 4. Refrigerant circuit
- 40 -

4-2. Model: AOYG24KMTA

Strainer
Strainer
3-way
valve
2-way
valve
Muffler
4-way valve
Expansion valve
Heat exchanger
Heat exchanger
(INDOOR)
(OUTDOOR)
Compressor
Cooling Heating
Muffler
Th
D
Th
R
Th
O
Th
HO
Muffler
Pressure switch
Accumulator
Th
PI
Th
C
: Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature)
Th
D
: Thermistor (Compressor temperature)
Th
C
Th
O
Th
HO
: Thermistor (Room temperature) : Thermistor (Pipe temperature)
Th
R
Th
PI
OUTDOOR UNIT
AOYG18, 24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
4-2. Model: AOYG24KMTA 4. Refrigerant circuit
- 41 -

5. Wiring diagrams

5-1. Model: AOYG18KMTA

OUTDOOR UNIT
AOYG18, 24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA

5-2. Model: AOYG24KMTA

5-1. Model: AOYG18KMTA 5. Wiring diagrams
- 42 -
6. Capacity compensation rate for pipe length and height
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
d
OUTDOOR UNIT
AOYG18, 24KMTA

6-1. Model: AOYG18KMTA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
ifference
OUTDOOR UNIT
AOYG18, 24KMTA
COOLING
Indoor unit is higher than
outdoor unit *
Indoor unit is lower than
outdoor unit *
Height difference H (m)
HEATING
Indoor unit is higher than
outdoor unit *
Indoor unit is lower than
outdoor unit *
Height difference H (m)
Pipe length (m)
5 7.5 10 15 20 25 20 0.917 0.900 10 0.966 0.947 0.932 0.914
1
7.5 0.979 0.970 0.951 0.936 0.918 5 0.992 0.983 0.974 0.955 0.939 0.922 0 1.000 0.991 0.981 0.963 0.946 0.930
-5 1.000 0.991 0.981 0.963 0.946 0.930
-7.5 0.991 0.981 0.963 0.946 0.930
2
-10 0.981 0.963 0.946 0.930
-20 0.946 0.930
Pipe length (m)
5 7.5 10 15 20 25 20 0.887 0.871 10 0.952 0.903 0.887 0.871
1
7.5 0.976 0.952 0.903 0.887 0.871 5 1.000 0.976 0.952 0.903 0.887 0.871 0 1.000 0.976 0.952 0.903 0.887 0.871
-5 0.995 0.971 0.947 0.899 0.883 0.866
-7.5 0.969 0.945 0.897 0.881 0.865
2
-10 0.942 0.894 0.879 0.863
-20 0.869 0.854

6-1. Model: AOYG18KMTA 6. Capacity compensation rate for pipe length and height difference

- 43 -

6-2. Model: AOYG24KMTA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
OUTDOOR UNIT
AOYG18, 24KMTA
Height difference H (m)
Height difference H (m)
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
Pipe length (m)
5 7.5 10 15 20 25 30 25 0.893 0.877 20 0.917 0.900 0.885 10 0.966 0.947 0.932 0.914 0.899
7.5 0.979 0.970 0.951 0.936 0.918 0.903 5 0.992 0.983 0.974 0.955 0.939 0.922 0.906 0 1.000 0.991 0.981 0.963 0.946 0.930 0.914
-5 1.000 0.991 0.981 0.963 0.946 0.930 0.914
-7.5 0.991 0.981 0.963 0.946 0.930 0.914
-10 0.981 0.963 0.946 0.930 0.914
-20 0.946 0.930 0.914
-25 0.930 0.914
Pipe length (m)
5 7.5 10 15 20 25 30 25 0.871 0.855 20 0.887 0.871 0.855 10 0.952 0.903 0.887 0.871 0.855
7.5 0.976 0.952 0.903 0.887 0.871 0.855 5 1.000 0.976 0.952 0.903 0.887 0.871 0.855 0 1.000 0.976 0.952 0.903 0.887 0.871 0.855
-5 0.995 0.971 0.947 0.899 0.883 0.866 0.850
-7.5 0.969 0.945 0.897 0.881 0.865 0.849
-10 0.942 0.894 0.879 0.863 0.847
-20 0.869 0.854 0.838
-25 0.850 0.834
OUTDOOR UNIT
AOYG18, 24KMTA
6-2. Model: AOYG24KMTA 6. Capacity compensation rate for pipe length and height difference
- 44 -

7. Additional charge calculation

7-1. Model: AOYG18KMTA

¢ Refrigerant charge
OUTDOOR UNIT
AOYG18, 24KMTA

7-2. Model: AOYG24KMTA

¢ Refrigerant charge
Refrigerant type R32 Refrigerant amount g 1,020
Total pipe length m 15 or less 20 25 (Max.) Additional charge g 0 100 200
Refrigerant type R32 Refrigerant amount g 1,320
20 g/m
OUTDOOR UNIT
AOYG18, 24KMTA
Total pipe length m 15 or less 20 25 30 (Max.) Additional charge g 0 100 200 300
20 g/m
7-1. Model: AOYG18KMTA 7. Additional charge calculation
- 45 -

8. Airflow

8-1. Model: AOYG18KMTA

Cooling
OUTDOOR UNIT
AOYG18, 24KMTA
Heating

8-2. Model: AOYG24KMTA

Cooling
m3/h
l/s 653
CFM 1,383
m3/h
l/s 583
CFM 1,236
m3/h
l/s 900
CFM 1,907
2,350
2,100
3,240
OUTDOOR UNIT
AOYG18, 24KMTA
Heating
m3/h
l/s 783
CFM 1,660
2,820
8-1. Model: AOYG18KMTA 8. Airflow
- 46 -

9. Operation noise (sound pressure)

Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,000 2,000 4,000 8,000
NC-65 NC-60 NC-55
NC-50
NC-45 NC-40
NC-35 NC-30 NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,000 2,000 4,000 8,000
NC-65 NC-60 NC-55
NC-50
NC-45 NC-40
NC-35
NC-25
NC-20
NC-15
NC-30
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,000 2,000 4,000 8,000
NC-65 NC-60 NC-55
NC-50
NC-45 NC-40
NC-35 NC-30 NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,000 2,000 4,000 8,000
NC-65 NC-60 NC-55
NC-50
NC-45 NC-40
NC-35
NC-25
NC-20
NC-15
NC-30

9-1. Noise level curve

Model: AOYG18KMTA
¢
Cooling
OUTDOOR UNIT
AOYG18, 24KMTA
Heating
OUTDOOR UNIT
AOYG18, 24KMTA
odel: AOYG24KMTA
M
¢
Cooling
Heating
9-1. Noise level curve 9. Operation noise (sound pressure)
- 47 -

9-2. Sound level check point

1 m
MicrophoneMicrophone
Rear
A
irflow
Rear view
Side view
OUTDOOR UNIT
AOYG18, 24KMTA
NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated
above.
OUTDOOR UNIT
AOYG18, 24KMTA
9-2. Sound level check point 9. Operation noise (sound pressure)
- 48 -

10. Electrical characteristics

Model name AOYG18KMTA AOYG24KMTA Power
supply Max operating current *1 A 13.5 16.0 Starting current A 7.0 8.6
Wiring spec.
OUTDOOR UNIT
*2
AOYG18, 24KMTA
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de­vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
Voltage V 230 ~ Frequency Hz 50
Circuit breaker current A 16 20 Power cable
Connection cable *3
Cross-sectional area Limited wiring length m 26 31
mm
mm
2
2
2.5
1.5—2.5
OUTDOOR UNIT
AOYG18, 24KMTA
- 49 -
10. Electrical characteristics

11. Safety devices

OUTDOOR UNIT
AOYG18, 24KMTA
Type of
protection
Circuit protection
Fan motor protection
Compressor protection
Protection form
Current fuse (PCB*)
Thermal protection program
Thermal protection program (Discharge temp.)
Thermal protection program (Outdoor temp.) (Only in COOL or DRY mode)
Activate
Reset
Activate
Reset
Activate
Reset
Model
AOYG18KMTA AOYG24KMTA
250 V, 25 A
250 V 5 A
250 V, 3.15 A
100±15°C
Fan motor stop
95±10°C
Fan motor restart
110°C
Compressor stop
After 7 minutes
Compressor restart
-20 °C
Compressor stop
-15 °C
Compressor restart
-15 °C
Compressor stop
-10 °C
Compressor restart
OUTDOOR UNIT
AOYG18, 24KMTA
- 50 -
11. Safety devices

12. Accessories

12-1. Models: AOYG18KMTA and AOYG24KMTA

OUTDOOR UNIT
AOYG18, 24KMTA
Part name Exterior Q’ty Part name Exterior Q’ty
Installation manual 1 Drain pipe 1
OUTDOOR UNIT
AOYG18, 24KMTA
12-1. Models: AOYG18KMTA and AOYG24KMTA 12. Accessories
- 51 -