Specifications are based on the following conditions:
•
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play™ store or on App Store®. Optional WLAN adapter is also required. For details, refer to the setting manual.
Rated
Min.—Max.
Rated
Min.—Max.
Rated
Min.—Max.0.09—1.660.24—3.15
Rated1.561.91
Min.—Max.0.09—2.860.14—3.00
HIGH
MED22.926.7
LOW13.313.3
QUIET8.28.2
RatedA
HIGH
MED810850
LOW640640
QUIET510510
HIGH1,0201,170
MED850850
LOW640640
QUIET510510
HIGH
MED4040
LOW3535
QUIET2929
HIGH4649
MED4040
LOW3535
QUIET2929
Liquid
GasØ 12.70 (Ø 1/2)
kW5.207.10
Btu/h17,70024,200
kW0.90—6.000.90—8.30
Btu/h3,100—20,5003,100—28,300
kW6.308.00
Btu/h21,50027,200
kW0.90—8.700.90—10.10
Btu/h3,100—29,6003,100—34,400
kW
W
kW/kW
%
A
m3/h
dB (A)
mm
mm
kg
mm (in)
°C18 to 32
%RH80 or less
Wireless remote controller (Option: Wired remote controller, Mobile app*3 [FGLair™])
2-1. Models: ASYG18KMTA and ASYG24KMTA2. Dimensions
- 4 -
¢
Unit: mm
Wall hook bracket
Outline of the indoor unit
50 or more
71 or more
40 or more
70 or more
117 or more
1,500 or more
1,800 or more
160 or more
The flare connection
part should be installed
outdoors.
Provide sufficient installation space for product safety.
WALL MOUNTED
ASYG18, 24KMTA
Installation space requirement
WALL MOUNTED
ASYG18, 24KMTA
2-1. Models: ASYG18KMTA and ASYG24KMTA2. Dimensions
- 5 -
3. Wiring diagrams
WALL MOUNTED
3-1. Models: ASYG18KMTA and ASYG24KMTA
ASYG18, 24KMTA
WALL MOUNTED
ASYG18, 24KMTA
3-1. Models: ASYG18KMTA and ASYG24KMTA3. Wiring diagrams
- 6 -
4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
WALL MOUNTED
ASYG18, 24KMTA
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
Circuit protection Current fuse (PCB*)250 V, 3.15 A
Fan motor
protection
*PCB: Printed Circuit Board
Type of
protection
Protection form
Thermal
protector
program
Activate
Reset
Model
ASYG18KMTAASYG24KMTA
125 ±24°C
Fan motor stop
100 ±25°C
Fan motor restart
WALL MOUNTED
ASYG18, 24KMTA
- 15 -
7. Safety devices
8. External input and output
Signal
Locally purchased
Indoor unit
control PCB
Communication kit
Optional parts
Connector
1
3
10 m*
Connected unit
Example: Switch
Operation
Stop
On
Off
Input signal
Indoor unit
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
WALL MOUNTED
ASYG18, 24KMTA
8-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
•
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
ConnectorInputOutputRemarks
CNA01Control input—
CNB01—Operation status output
CNB02—Error status output
See external input/output
settings for details.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
Control input (Operation/Stop or Forced stop)
WALL MOUNTED
ASYG18, 24KMTA
Unit operationInitial setting after power is onStarting mode other than initial setting
Operation modeAuto changeoverMode at previous operation
Set temperature24 °CTemperature at previous operation
Airflow modeAUTOMode at previous operation
Air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
• Circuit diagram example:
• Contact capacity: DC 24 V or more, 10
mA or more.
•
*: Make the distance from the PCB to
the connected unit within 10 m.
• Use non-polar relays and switches.
• When function setting is “Operation/Stop” mode:
8-1. External input8. External input and output
- 16 -
• When function setting is “Forced stop” mode:
Remote controller
OnOnOn
Input signal
Indoor unit
Command
Remote control
operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
WALL MOUNTED
ASYG18, 24KMTA
• Optional part:
Part nameModel nameExterior
External input wire
External connect kitUTY-XWZXZ5
WALL MOUNTED
ASYG18, 24KMTA
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
8-1. External input8. External input and output
- 17 -
8-2. External output
Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kitConnected unit
Example: Relay unit
1
2
Signal
Relay
power supply
V
Connector
10 m*
DC 24 V
On
Off
Operation
Stop
Indoor unit
Output signal
With using external output function, operating status of this product can be transmitted to the external device, and also, this product can be inter-connected with the external device.
WALL MOUNTED
ASYG18, 24KMTA
¢
Air conditioner operation status signal can be output.
• Circuit diagram example:
Operation status output
WALL MOUNTED
ASYG18, 24KMTA
– *: Make the distance from the PCB to the connected unit within 10 m.
–
Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
• Optional part:
Part nameModel nameExterior
External output wire
External connect kitUTY-XWZXZ5
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
8-2. External output8. External input and output
- 18 -
¢
Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kitConnected unit
Example: Relay unit
1
2
Signal
Relay
power supply
V
Connector
10 m*
DC 24 V
On
Off
Error
Normal
Error status
Output signal
Air conditioner error status signal can be output.
• Circuit diagram example:
WALL MOUNTED
ASYG18, 24KMTA
Error status output
– *: Make the distance from the PCB to the connected unit within 10 m.
–
Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
WALL MOUNTED
ASYG18, 24KMTA
• Optional part:
Part nameModel nameExterior
External output wire
External connect kitUTY-XWZXZ5
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
8-2. External output8. External input and output
- 19 -
9. Group connection
A
BCDE
I.U.I.U.I.U.I.U.
Remote controller
Example of wiring method
12
R W
Remote
controller cable
Bus wire
Remote controller
Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4
RC AD
01
RC AD
02
RC AD
03
RC AD
04
Remote controller
Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4
Example of wiring method
NOTE: Group control cannot be used together with Wireless LAN adapter.
WALL MOUNTED
ASYG18, 24KMTA
Installation procedure for group control system:
A number of indoor units can be operated at the same time using a single remote controller.
NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette
type and duct type, or other combinations) are connected using group control system, some
functions may no longer be available.
1. Connect up to 16 indoor units in a system.
A, B, C, D, E: Remote controller cable
Wiring length limitationA + B + C + D + E ≤ 500 m
WALL MOUNTED
ASYG18, 24KMTA
2. Set the R.C. address. (Function setting)
Addresses will be automatically set when initially starting up this unit. In such a case, do not
•
change the remote controller address for the indoor unit, and keep it at the initial setting of
“00”.
• Only set addresses manually when using different numbers for addresses.
Set the R.C. address of each indoor unit using the function setting. (Refer to “Remote controller address setting” in "Contents of function setting" on page 24.)
NOTES:
– Do not use the same setting value.
– Setting is reflected after the power is turned on again.
Also set the R.C. address for the remote controller. For details, refer to the remote controller
installation manual.
NOTE: In manual setting, connect up to 15 indoor units in a system.
- 20 -
9. Group connection
10. Remote controller
Signal
transmitter
10°C HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
OUTDOOR UNIT
LOW NOISE button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
MODE button
FAN button
RESET button
CLOCK ADJUST button
TEST RUN button
ECONOMY button
Mode indicator
LOW NOISE mode
indicator
Clock and Timer indicator
SEND indicator
Temperature indicator
Fan speed indicator
Swing indicator
Transmit indicator
WALL MOUNTED
10-1. Wireless remote controller
ASYG18, 24KMTA
¢
Overview
WALL MOUNTED
ASYG18, 24KMTA
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators;
in actual operation, however, the display will only show those indicators appropriate to the current operation.
To adjust the functions of this product according to the installation environment, various types of
function settings are available.
WALL MOUNTED
ASYG18, 24KMTA
NOTE: Incorrect settings can cause a product malfunction.
11-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting procedure and the content of each function setting, select appropriate functions for your installation environment.
¢
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller,
and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Cover for the electrical enclosure on the outdoor unit is in place.
• There is no wiring mistake.
• Piping air tight test and vacuuming have been performed firmly.
• All the necessary wiring work for outdoor unit has been finished.
Setting procedure by using wireless remote controller
WALL MOUNTED
ASYG18, 24KMTA
After reconfirming the items listed above, connect the power supply of the indoor unit.
NOTES:
• Settings will not be changed if invalid numbers or setting values are selected.
• When optional wired remote controller is used, refer to the installation manual enclosed with the
remote controller.
Entering function setting mode:
While pressing the
POWERFUL button and TEMP. (
) button simulta-
neously, press the RESET button to enter the function setting mode.
Selecting the function number and setting value:
1. Press the TEMP. () () buttons to select the function number.
To switch between the left and right digits, press the
10 °C HEAT
button.
2. Press the POWERFUL button to proceed to value setting. To return the function number selection, press the POWERFUL button
again.
3. Press the TEMP. (
switch between the left and right digits, press the
) () buttons to select the setting value. To
10 °C HEAT but-
ton.
4. Press the MODE button once. Confirm that you hear the beep
sound.
5. Press the START/STOP button to fix the function setting. Confirm
that you hear the beep sound.
6. Press the RESET button to end the function setting mode.
7. After completing the function setting, be sure to disconnect the
power supply and then reconnect it.
CAUTION
After disconnecting the power supply, wait
30 seconds or more before reconnecting it. The function
setting will not become active unless the power supply is disconnected and then reconnected.
11-1. Function settings by using remote controller11. Function settings
- 23 -
NOTES:
• The air conditioner custom code is set to prior to shipment.
•
WALL MOUNTED
ASYG18, 24KMTA
¢
Each function setting listed in this section is adjustable in accordance with the installation environment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
If you do not know the air conditioner custom code setting, try each of the custom codes (
→ → ) until you find the code that operates the air conditioner.
ontents of function setting
C
unction setting list
F
Function no.Functions
1)00Remote controller address setting
2)11Filter sign
3)30/31Room temperature control for indoor unit sensor
4)35/36Room temperature control for wired remote controller sensor
5)40Auto restart
6)42Room temperature sensor switching
7)44Remote controller custom code
8)46External input control
9)48Room temperature sensor switching (Aux.)
10)49Indoor unit fan control for energy saving for cooling
→
WALL MOUNTED
ASYG18, 24KMTA
1) Remote controller address setting
Multiple indoor units can be operated by using one wired remote controller.
Set the unit number of each indoor unit.
Function numberSetting valueSetting descriptionFactory setting
NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette
type and duct type, or other combinations) are connected using group control system, some
functions may no longer be available.
11-1. Function settings by using remote controller11. Function settings
- 24 -
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
WALL MOUNTED
ASYG18, 24KMTA
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufacturer’s recommended value).
Function numberSetting valueSetting descriptionFactory setting
00Standard setting♦
01No correction 0.0 °C
02-0.5 °C
03-1.0 °C
04-1.5 °C
05-2.0 °C
06-2.5 °C
07-3.0 °C
30
(For cooling)
31
(For heating)
08-3.5 °C
09-4.0 °C
10+0.5 °C
11+1.0 °C
12+1.5 °C
13+2.0 °C
14+2.5 °C
15+3.0 °C
16+3.5 °C
17+4.0 °C
Factory
setting
More cooling
Less heating
Less cooling
More heating
11-1. Function settings by using remote controller11. Function settings
- 25 -
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be
required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
WALL MOUNTED
ASYG18, 24KMTA
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
WALL MOUNTED
ASYG18, 24KMTA
Function numberSetting valueSetting description
00No correction♦
01No correction 0.0°C
02-0.5 °C
03-1.0 °C
04-1.5 °C
05-2.0 °C
06-2.5 °C
07-3.0 °C
35
(For cooling)
36
(For heating)
08-3.5 °C
09-4.0 °C
10+0.5 °C
11+1.0 °C
12+1.5 °C
13+2.0 °C
14+2.5 °C
15+3.0 °C
16+3.5 °C
17+4.0 °C
Factory
setting
More cooling
Less heating
Less cooling
More heating
5) Auto restart
Enables or disables automatic restart after a power interruption.
Function numberSetting valueSetting descriptionFactory setting
40
00Enable♦
01Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external device.
6)
Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function numberSetting valueSetting descriptionFactory setting
42
00Indoor unit♦
01Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
11-1. Function settings by using remote controller11. Function settings
- 26 -
7) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
WALL MOUNTED
ASYG18, 24KMTA
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
9) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting
Function numberSetting valueSetting descriptionFactory setting
00A♦
44
Function numberSetting valueSetting descriptionFactory setting
Function numberSetting valueSetting descriptionFactory setting
48
00Both♦
01Wired remote controller
10) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function numberSetting valueSetting descriptionFactory setting
00Disable
49
01Enable
02Remote controller♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
•
As the factory setting, this setting is initially activated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each remote
controller.
11-1. Function settings by using remote controller11. Function settings
- 27 -
11-2. Custom code setting for wireless remote controller
To interconnect the air conditioner and the wireless remote controller, assignment of the custom
code for the wireless remote controller is required.
WALL MOUNTED
ASYG18, 24KMTA
NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom
When 2 or more air conditioners are installed in a room, and the remote controller is operating an air
conditioner other than the one you wish to set, change the custom code of the remote controller to
operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not
match, the remote controller cannot be used to operate for the air conditioner.
code.
1. Press the START/STOP button until only the clock is displayed on
the remote controller display.
Press the MODE button for at least 5 seconds to display the cur-
2.
rent custom code. (Initially set to
.)
WALL MOUNTED
ASYG18, 24KMTA
3.
Press the TEMP. (
) () buttons to change the custom code between → → → . Match the code on the display to the air conditioner custom code. (Initially set to
4.
Press the MODE button again to return to the clock display. The
.)
custom code will be changed.
NOTES:
If no button is pressed within 30 seconds after the custom code is displayed, the system returns
•
to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to
prior to shipment. To change the custom code, con-
tact your retailer.
• If you do not know the assigned code for the air conditioner, try each of the custom code ( →
→ → ) until you find the code which operates the air conditioner.
11-2. Custom code setting for wireless remote controller11. Function settings
- 28 -
12. Accessories
WALL MOUNTED
12-1. Models: ASYG18KMTA and ASYG24KMTA
ASYG18, 24KMTA
Operating manual1Tapping screw (large)5
Installation manual1Tapping screw (small)2
Remote controller1Battery2
Remote controller
holder
Part nameExteriorQ’tyPart nameExteriorQ’ty
1Filter holder2
WALL MOUNTED
ASYG18, 24KMTA
Cloth tape
Wall hook bracket
1Air cleaning filters1
1
12-1. Models: ASYG18KMTA and ASYG24KMTA12. Accessories
operation in a dark room.
Wire type: Non-polar 2-wire
Optional communication kit is
necessary for installation.
High visibility and easy operation.
Room temperature can be accurately
controlled using the built-in thermo
sensor.
Wire type: Non-polar 2-wire
Optional communication kit is
necessary for installation.
Compact remote controller
concentrates on the basic functions
such as Start/Stop, fan control,
temperature setting, and operation
mode.
Wire type: Non-polar 2-wire
Optional communication kit is
necessary for installation.
WALL MOUNTED
ASYG18, 24KMTA
Compact remote controller
concentrates on the basic functions
such as Start/Stop, fan control, and
Simple remote
controller
UTY-RHRY
temperature setting.
Wire type: Non-polar 2-wire
Optional communication kit is
necessary for installation.
NOTES:
•
Available functions may differ by the remote controller. For details, refer to the operation manual.
• In this product, group controlling system of the wired remote controller is prohibited.
13-1. Controllers13. Optional parts
- 30 -
13-2. Others
WALL MOUNTED
ASYG18, 24KMTA
ExteriorPart nameModel nameSummary
Required when external device is
connected.
External
connect kit
UTY-XWZXZ5
Optional communication kit is
necessary for installation.
WALL MOUNTED
ASYG18, 24KMTA
External input
and output PCB
Communication
kit
Wireless LAN
adapter
UTY-XCSXZ2
UTY-TWRXZ2
UTY-TFSXF2
Use to connect with external devices
and air conditioner PCB.
Use to connect Non-polar 2-core wired
remote controller.
Remotely manage an air conditioning
system using mobile devices such as
smartphones and tablets.
13-2. Others13. Optional parts
- 31 -
WALL MOUNTED
ASYG18, 24KMTA
WALL MOUNTED
ASYG18, 24KMTA
13-2. Others13. Optional parts
- 32 -
Part 2. OUTDOOR UNIT
SINGLE TYPE:
AOYG18KMTA
AOYG24KMTA
1. Specifications
OUTDOOR UNIT
AOYG18, 24KMTA
TypeInverter heat pump
Model nameAOYG18KMTAAOYG24KMTA
Power supply230 V ~ 50 Hz
Power supply intakeOutdoor unit
Available voltage range198—264 V
Starting currentA7.08.6
Fan
Sound pressure level *1
Sound power level
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions
(H × W × D)
Weight
Connection pipe
Operation range
Drain hose
NOTES:
Specifications are based on the following conditions:
•
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'tyPropeller fan × 1
Motor outputW49
TypeDC twin rotary
Motor outputW9001,060
Net
Gross692 × 940 × 375776 × 961 × 450
Net
Gross4046
Type (Global warming potential)R32 (675)
Chargeg1,0201,320
TypeFW68SRmM68AF
Amount
MaterialSteel sheet
Color
Liquid
GasØ 12.70 (Ø 1/2)
Cooling
Heating-15 to 24
MaterialPP
SizemmØ 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
m3/h
dB (A)
dB (A)
mm
Type (Material)Aluminum
Surface treatmentPC fin
3
cm
mm
kg
mm (in)
m
°C
2,3503,240
5054
6567
588 × 881 × 18.19
588 × 851 × 18.19
350400
632 × 799 × 290716 × 820 × 315
Approximate color of Munsell 10YR 7.5/1.0
3642
Beige
Ø 6.35 (Ø 1/4)
15
-10 to 46
672 × 881 × 18.19
672 × 851 × 18.19
OUTDOOR UNIT
AOYG18, 24KMTA
- 34 -
1. Specifications
2. Dimensions
Unit: mm
Side viewSide viewFront view
Bottom viewSide view (Valve part)
Top view
580
799196816290
3330
109
353
632
20
330
Pitch of bolts
for installation
Pitch of bolts for installation
4-
M1
0 hole
Airflow
Drain port Ø42
37
120
184
399180
2-1. Model: AOYG18KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
2-1. Model: AOYG18KMTA2. Dimensions
- 35 -
2-2. Model: AOYG24KMTA
Unit: mm
Side viewSide viewFront view
Top view
16315
2018
Airflow
600109
353
330
Pitch of bolts
for installation
Pitch of bolts for installation
4-
M1
0 hole
8201968
716
20
Drain port Ø42
37
410
Bottom viewSide view (Valve part)
119
184
194
OUTDOOR UNIT
AOYG18, 24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
2-2. Model: AOYG24KMTA2. Dimensions
- 36 -
3. Installation space
100 or more
250 or more
100 or more
100 or more
600 or more
600 or more
100 or more
100 or more
Max. 200
600 or more
250 or more
100 or more
Max. 200
100 or more
600 or more
3-1. Models: AOYG18KMTA and AOYG24KMTA
¢
Provide sufficient installation space for product safety.
Keep the space shown in the installation examples.
OUTDOOR UNIT
AOYG18, 24KMTA
If the installation is not performed accordingly, it could cause a short circuit and result in a lack of
operating performance.
Single outdoor unit installation
Space requirement
CAUTION
• When the upper space is open:
Obstacles at rear onlyObstacles at rear and sides
Unit: mm
OUTDOOR UNIT
AOYG18, 24KMTA
Obstacles at frontObstacles at front and rear
• When there is an obstruction in the upper space:
Unit: mm
Obstacles at rear and aboveObstacles at rear, sides, and above
3-1. Models: AOYG18KMTA and AOYG24KMTA3. Installation space
- 37 -
Multiple outdoor unit installation
200 or more
250 or more
1,000 or more
250 or more
200 or more
1,000 or more
250 or more
1,500 or more
200 or more
250 or more
250 or more
Max. 300
1,500 or more
OUTDOOR UNIT
AOYG18, 24KMTA
• Provide at least 250 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following example “When an obstruction in the upper space:”.
• When the upper space is open:
Unit: mm
Obstacles at rear onlyObstacles at front only
OUTDOOR UNIT
AOYG18, 24KMTA
Obstacles at front and rear
• When an obstruction in the upper space:
Obstacles at rear and above.
Unit: mm
3-1. Models: AOYG18KMTA and AOYG24KMTA3. Installation space
- 38 -
Outdoor units installation in multi-row
100 or more
200 or more
500 or more
1,000 or more
200 or more
400 or more
1,000 or more
250 or more
2,000 or more
250 or more
1,000 or more
200 or more
250 or more
200 or more
OUTDOOR UNIT
AOYG18, 24KMTA
Single parallel unit arrangementMultiple parallel unit arrangement
Unit: mm
OUTDOOR UNIT
AOYG18, 24KMTA
NOTES:
If the space is larger than stated above, the condition will be the same as when there is no ob-
•
stacle.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the
drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain
cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely
cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it
might become difficult to get warm, and it is likely to cause product malfunction. Construct a
canopy and a pedestal, or place the unit on a high stand that is locally installed.
3-1. Models: AOYG18KMTA and AOYG24KMTA3. Installation space
supply
Max operating current *1A13.516.0
Starting currentA7.08.6
Wiring
spec.
OUTDOOR UNIT
*2
AOYG18, 24KMTA
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
VoltageV230 ~
FrequencyHz50
Circuit breaker currentA1620
Power cable
Connection
cable *3
Cross-sectional area
Limited wiring lengthm2631
mm
mm
2
2
2.5
1.5—2.5
OUTDOOR UNIT
AOYG18, 24KMTA
- 49 -
10. Electrical characteristics
11. Safety devices
OUTDOOR UNIT
AOYG18, 24KMTA
Type of
protection
Circuit
protection
Fan motor
protection
Compressor
protection
Protection form
Current fuse (PCB*)
Thermal protection program
Thermal protection program
(Discharge temp.)
Thermal protection program
(Outdoor temp.)
(Only in COOL or DRY mode)
Activate
Reset
Activate
Reset
Activate
Reset
Model
AOYG18KMTAAOYG24KMTA
250 V, 25 A
250 V 5 A
250 V, 3.15 A
100±15°C
Fan motor stop
95±10°C
Fan motor restart
110°C
Compressor stop
After 7 minutes
Compressor restart
-20 °C
Compressor stop
-15 °C
Compressor restart
-15 °C
Compressor stop
-10 °C
Compressor restart
OUTDOOR UNIT
AOYG18, 24KMTA
- 50 -
11. Safety devices
12. Accessories
12-1. Models: AOYG18KMTA and AOYG24KMTA
OUTDOOR UNIT
AOYG18, 24KMTA
Part nameExteriorQ’tyPart nameExteriorQ’ty
Installation manual1Drain pipe1
OUTDOOR UNIT
AOYG18, 24KMTA
12-1. Models: AOYG18KMTA and AOYG24KMTA12. Accessories
- 51 -