Fujitsu ASYG07LMCE, ASYG09LMCE, ASYG12LMCE, AOYG09LMCE, AOYG12LMCE Design & Technical Manual

...
AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE
OUTDOOR
AOYG07LMCE AOYG09LMCE AOYG12LMCE
AOYG14LMCE
2016.12.05
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2016 Fujitsu General Limited. All rights reserved.
CONTENTS
Part 1. INDOOR UNIT....................................................................... 1
1. Specifications............................................................................................2
2. Dimensions................................................................................................4
2-1. Models:ASYG07LMCE, ASYG09LMCE, ASYG12LMCE, and ASYG14LMCE ........... 4
3. Wiring diagrams ........................................................................................6
3-1. Models:ASYG07LMCE, ASYG09LMCE, ASYG12LMCE, and ASYG14LMCE ........... 6
4. Capacity table............................................................................................7
4-1. Cooling capacity.......................................................................................................... 7
4-2. Heating capacity .........................................................................................................8
5. Fan performance .......................................................................................9
5-1. Air velocity distributions............................................................................................... 9
5-2. Airflow....................................................................................................................... 11
6. Operation noise (sound pressure)......................................................... 13
6-1. Noise level curve....................................................................................................... 13
6-2. Sound level check point............................................................................................ 15
7. Safety devices ......................................................................................... 16
8. Remote controller ...................................................................................17
8-1. Wireless remote controller ........................................................................................ 17
9. External input and output.......................................................................19
9-1. External input............................................................................................................ 19
9-2. External output.......................................................................................................... 21
10. Function settings ....................................................................................23
10-1.Function settings by using remote controller............................................................ 23
10-2.Custom code setting for wireless remote controller.................................................. 28
11. Accessories.............................................................................................29
12. Optional parts..........................................................................................30
12-1.Controllers ............................................................................................................... 30
12-2.Others...................................................................................................................... 30
Part 2. OUTDOOR UNIT................................................................. 31
1. Specifications..........................................................................................32
2. Dimensions..............................................................................................33
2-1. Models:AOYG07LMCE, AOYG09LMCE, and AOYG12LMCE.................................. 33
2-2. Model:AOYG14LMCE............................................................................................... 34
3. Installation space ....................................................................................35
3-1. Models:AOYG07LMCE, AOYG09LMCE, AOYG12LMCE, and AOYG14LMCE ....... 35
4. Refrigerant circuit ...................................................................................38
4-1. Models:AOYG07LMCE, AOYG09LMCE, AOYG12LMCE, and AOYG14LMCE ....... 38
5. Wiring diagrams ......................................................................................39
5-1. Models:AOYG07LMCE and AOYG09LMCE............................................................. 39
5-2. Model:AOYG12LMCE............................................................................................... 40
5-3. Model:AOYG14LMCE............................................................................................... 41
6. Capacity compensation rate for pipe length and height difference....42
6-1. Models:AOYG07LMCE and AOYG09LMCE............................................................. 42
6-2. Model:AOYG12LMCE............................................................................................... 43
6-3. Model:AOYG14LMCE............................................................................................... 44
7. Additional charge calculation ................................................................45
7-1. Models:AOYG07LMCE and AOYG09LMCE............................................................. 45
7-2. Model:AOYG12LMCE............................................................................................... 45
7-3. Model:AOYG14LMCE............................................................................................... 45
8. Airflow......................................................................................................46
8-1. Models:AOYG07LMCE and AOYG09LMCE............................................................. 46
8-2. Model:AOYG12LMCE............................................................................................... 46
8-3. Model:AOYG14LMCE............................................................................................... 46
9. Operation noise (sound pressure)......................................................... 47
9-1. Noise level curve....................................................................................................... 47
9-2. Sound level check point............................................................................................ 49
10. Electrical characteristics........................................................................50
11. Safety devices ......................................................................................... 51
12. Accessories.............................................................................................52
CONTENTS (continued)
Part 1. INDOOR UNIT
WALL MOUNTED TYPE:
ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE
1. Specifications
Type
Wall mounted
Inverter heat pump
Model name ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE
Power supply 230 V ~ 50 Hz Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 2.00 2.50 3.40 4.00
Btu/h 6,800 8,500 11,600 13,600
Min.—Max.
kW 0.5—3.0 0.5—3.2 0.9—3.9 0.9—4.4
Btu/h 1,700—10,200 1,700—10,900 3,100—13,300 3,100—15,000
Heating
Rated
kW 3.00 3.20 4.00 5.00
Btu/h 10,200 10,900 13,600 17,000
Min.—Max.
kW 0.5—3.4 0.5—4.0 0.9—5.3 0.9—6.0
Btu/h 1,700—11,600 1,700—13,600 3,100—18,000 3,100—20,400
Input power
Cooling
Rated
kW
0.465 0.65 0.97 1.135
Min.—Max. 0.25—1.29 0.25—1.29 0.25—1.40 0.25—1.98
Heating
Rated 0.685 0.730 1.02 1.365 Min.—Max. 0.25—1.63 0.25—1.63 0.25—1.98 0.25—2.32
Fan
HIGH
W
30 32 MED 20 23 LOW 10 12 QUIET 4 6
Current
Cooling
Rated A
2.5 3.2 4.6 5.3
Heating 3.3 3.5 4.8 6.3
EER Cooling
kW/kW
4.30 3.85 3.50 3.52 COP Heating 4.38 4.38 3.92 3.66 Sensible capacity Cooling kW 1.2 1.6 2.2 3.2
Power factor
Cooling
%
81 88 91 93
Heating 90 90 92 94
Moisture removal L/h (pints/h) 1.0 (1.8) 1.3 (2.3) 1.8 (3.2) 2.1 (3.7)
Maximum operating current *1
Cooling
A
6.0 6.0 6.5 9.0
Heating 7.5 7.5 9.0 10.5
Fan
Airflow rate
Cooling
HIGH
m3/h
750 770 MED 640 680 LOW 480 530 QUIET 310 360
Heating
HIGH 750 770 MED 640 680 LOW 520 560 QUIET 330 380
Type × Q'ty Cross flow fan × 1 Motor output W 30
Sound pressure level *2
Cooling
HIGH
dB (A)
43 44 MED 40 40 LOW 32 33 QUIET 21 25
Heating
HIGH 43 44 MED 38 40 LOW 33 35 QUIET 22 27
Heat exchanger type
Dimensions (H × W × D)
mm
Main: 320 × 630 × 20
Sub: 84 × 630 × 13.3 Fin pitch Man: 1.1, Sub: 1.4 Rows × Stages Main: 2 × 20, Sub: 1 × 4 Pipe type Copper tube Fin type Aluminum
Enclosure
Material Polystyrene
Color
White + Pearl white (painted)
Approximate color of Munsell N 9.25/
Dimensions (H × W × D)
Net
mm
270 × 870 × 204
Gross 270 × 925 × 336
Weight
Net
kg
8.5
Gross 11
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8) Ø 12.7 (Ø 1/2)
Method Flare
Drain hose
Material PP+LLDPE Size mm Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type Wireless (Wired [option])
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 2 -
WALL MOUNTED
ASYG07-14LMCE
Model name ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE
Energy efficiency class
Cooling
A
++
A
++
A
++
A
++
Heating (Average)
A
+
A
+
A
+
A
+
Pdesign
Cooling
kW
2.0 (35 °C) 2.5 (35 °C) 3.4 (35 °C) 4.0 (35 °C)
Heating (Average) 2.3 (-10 °C) 2.4 (-10 °C) 3.5 (-10 °C) 3.9 (-10 °C)
SEER Cooling
kWh/kWh
6.80 7.00 7.00 6.90
SCOP Heating (Average) 4.10 4.10 4.00 4.00
Annual energy consumption
QCE
kWh/a
103 125 170 203
QHE (Average) 786 820 1,225 1,365
Sound power level
Cooling
HIGH dB (A)
59 59 59 60
Heating 59 59 59 60
- 3 -
WALL MOUNTED
ASYG07-14LMCE
2. Dimensions
2-1. Models:ASYG07LMCE, ASYG09LMCE, ASYG12LMCE,
and ASYG14LMCE
Unit: mm
270
(270)
34218
209
74
870
204
(870)
426
310
444
165 144
178 233
321 315
295
Outline of unit
65 for pipe inlet
65 for pipe inlet
- 4 -
WALL MOUNTED
ASYG07-14LMCE
¢
Installation space requirement
Provide sufficient installation space for product safety.
Unit: mm
45 or more
1,800 or more
63 or more
Outline of unit
25 or more
52 or more
144 or more
1,500 or more
86 or more
- 5 -
WALL MOUNTED
ASYG07-14LMCE
3. Wiring diagrams
3-1. Models:ASYG07LMCE, ASYG09LMCE, ASYG12LMCE,
and ASYG14LMCE
- 6 -
WALL MOUNTED
ASYG07-14LMCE
4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢
Model:ASYG07LMCE
AFR
m3/h
750
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 20 1.87 1.32 0.33 2.09 1.33 0.33 2.16 1.45 0.33 2.30 1.45 0.34 2.37 1.57 0.34 2.51 1.56 0.34 2.65 1.66 0.35 25 1.78 1.26 0.37 1.98 1.26 0.37 2.05 1.37 0.37 2.18 1.38 0.38 2.25 1.49 0.38 2.39 1.48 0.38 2.52 1.58 0.39 30 1.68 1.19 0.41 1.87 1.19 0.41 1.94 1.30 0.42 2.06 1.30 0.42 2.13 1.41 0.42 2.25 1.40 0.43 2.38 1.49 0.43 35 1.58 1.12 0.45 1.76 1.12 0.46 1.82 1.22 0.46 1.94 1.23 0.46 2.00 1.32 0.47 2.12 1.32 0.47 2.24 1.40 0.47 40 1.41 1.00 0.45 1.57 1.00 0.46 1.62 1.09 0.46 1.73 1.09 0.46 1.78 1.18 0.46 1.89 1.17 0.47 2.00 1.25 0.47 43 1.31 0.92 0.45 1.45 0.93 0.45 1.50 1.01 0.46 1.60 1.01 0.46 1.65 1.09 0.46 1.75 1.09 0.47 1.85 1.16 0.47
¢
Model:ASYG09LMCE
AFR
m3/h
750
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 20 2.34 1.62 0.46 2.61 1.63 0.46 2.70 1.77 0.47 2.87 1.78 0.47 2.96 1.92 0.47 3.14 1.91 0.48 3.32 2.04 0.48 25 2.22 1.54 0.51 2.48 1.55 0.52 2.56 1.68 0.52 2.73 1.69 0.53 2.81 1.82 0.53 2.98 1.82 0.54 3.15 1.93 0.54 30 2.10 1.45 0.57 2.34 1.46 0.58 2.42 1.59 0.58 2.58 1.60 0.59 2.66 1.72 0.59 2.82 1.72 0.60 2.98 1.83 0.60 35 1.98 1.37 0.63 2.20 1.38 0.64 2.28 1.50 0.64 2.43 1.50 0.65 2.50 1.62 0.65 2.65 1.61 0.66 2.80 1.72 0.66 40 1.76 1.22 0.63 1.96 1.23 0.64 2.03 1.33 0.64 2.16 1.34 0.65 2.23 1.44 0.65 2.36 1.44 0.66 2.50 1.53 0.66 43 1.63 1.13 0.62 1.82 1.14 0.63 1.88 1.24 0.64 2.00 1.24 0.64 2.07 1.34 0.65 2.19 1.33 0.65 2.31 1.42 0.66
¢
Model:ASYG12LMCE
AFR
m3/h
750
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 20 3.18 2.18 0.66 3.55 2.19 0.67 3.67 2.39 0.68 3.91 2.39 0.68 4.03 2.59 0.69 4.27 2.57 0.70 4.51 2.74 0.70 25 3.03 2.07 0.75 3.37 2.08 0.77 3.49 2.27 0.77 3.72 2.27 0.78 3.83 2.45 0.78 4.06 2.44 0.79 4.29 2.60 0.80 30 2.86 1.96 0.84 3.19 1.97 0.86 3.30 2.14 0.86 3.52 2.15 0.87 3.63 2.32 0.87 3.84 2.31 0.88 4.06 2.46 0.89 35 2.69 1.84 0.94 2.99 1.85 0.95 3.09 2.01 0.96 3.30 2.02 0.97 3.40 2.18 0.97 3.60 2.17 0.98 3.81 2.31 0.99 40 2.27 1.64 0.87 2.53 1.65 0.88 2.62 1.79 0.89 2.79 1.80 0.90 2.87 1.94 0.90 3.05 1.94 0.91 3.22 2.06 0.92 43 2.09 1.52 0.87 2.33 1.53 0.89 2.41 1.66 0.89 2.57 1.67 0.90 2.65 1.80 0.90 2.81 1.80 0.91 2.96 1.91 0.92
¢
Model:ASYG14LMCE
AFR
m3/h
770
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 20 3.72 2.44 0.77 4.15 2.46 0.78 4.29 2.67 0.79 4.57 2.68 0.80 4.71 2.90 0.80 4.99 2.89 0.81 5.28 3.07 0.82 25 3.54 2.34 0.88 3.94 2.36 0.89 4.08 2.56 0.90 4.34 2.57 0.91 4.48 2.78 0.91 4.75 2.77 0.92 5.02 2.95 0.93 30 3.36 2.31 0.99 3.74 2.32 1.00 3.87 2.52 1.01 4.12 2.53 1.02 4.25 2.73 1.02 4.50 2.72 1.03 4.76 2.90 1.04 35 3.16 2.19 1.10 3.52 2.21 1.11 3.64 2.40 1.12 3.88 2.41 1.13 4.00 2.60 1.14 4.24 2.59 1.15 4.48 2.76 1.16 40 2.30 1.87 0.75 2.56 1.88 0.76 2.65 2.04 0.77 2.83 2.05 0.78 2.91 2.21 0.78 3.09 2.20 0.79 3.26 2.35 0.80 43 2.20 1.84 0.80 2.45 1.85 0.81 2.53 2.01 0.81 2.70 2.02 0.82 2.78 2.18 0.83 2.95 2.17 0.83 3.12 2.31 0.84
- 7 -
WALL MOUNTED
ASYG07-14LMCE
4-2. Heating capacity
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
¢
Model:ASYG07LMCE
AFR
m3/h
750
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 1.72 0.71 1.68 0.73 1.64 0.74 1.60 0.75 1.56 0.77
-10 -11 2.38 0.86 2.33 0.88 2.27 0.90 2.21 0.92 2.16 0.94
-5 -7 2.90 0.97 2.83 0.99 2.76 1.01 2.69 1.03 2.62 1.05 0 -2 3.18 1.02 3.10 1.04 3.03 1.06 2.95 1.08 2.87 1.10 5 3 3.46 1.06 3.38 1.09 3.29 1.11 3.21 1.13 3.13 1.15 7 6 3.57 1.08 3.49 1.10 3.40 1.13 3.32 1.15 3.23 1.17
10 8 3.98 1.19 3.88 1.21 3.79 1.24 3.69 1.26 3.60 1.29 15 10 3.72 1.09 3.63 1.12 3.54 1.14 3.45 1.16 3.36 1.18
¢
Model:ASYG09LMCE
AFR
m3/h
750
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 1.72 0.71 1.68 0.73 1.64 0.74 1.60 0.75 1.56 0.77
-10 -11 2.38 0.86 2.33 0.88 2.27 0.90 2.21 0.92 2.16 0.94
-5 -7 2.99 0.97 2.91 0.99 2.84 1.01 2.77 1.03 2.70 1.05 0 -2 3.49 1.02 3.41 1.04 3.33 1.06 3.24 1.08 3.16 1.10 5 3 4.00 1.06 3.90 1.09 3.81 1.11 3.71 1.13 3.62 1.15 7 6 4.20 1.08 4.10 1.10 4.00 1.13 3.90 1.15 3.80 1.17
10 8 4.76 1.19 4.65 1.21 4.53 1.24 4.42 1.26 4.31 1.29 15 10 4.53 1.09 4.42 1.12 4.31 1.14 4.20 1.16 4.10 1.18
¢
Model:ASYG12LMCE
AFR
m3/h
750
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 2.94 1.54 2.87 1.57 2.80 1.60 2.73 1.63 2.66 1.66
-10 -11 3.73 1.60 3.64 1.63 3.55 1.67 3.46 1.70 3.37 1.73
-5 -7 4.40 1.62 4.29 1.65 4.19 1.69 4.08 1.72 3.98 1.75 0 -2 4.88 1.57 4.77 1.60 4.65 1.64 4.53 1.67 4.42 1.70 5 3 5.37 1.52 5.24 1.56 5.11 1.59 4.99 1.62 4.86 1.65 7 6 5.57 1.51 5.43 1.54 5.30 1.57 5.17 1.60 5.04 1.63
10 8 5.85 1.51 5.71 1.54 5.57 1.57 5.43 1.60 5.29 1.63 15 10 5.66 1.39 5.52 1.42 5.39 1.45 5.25 1.48 5.12 1.51
¢
Model:ASYG14LMCE
AFR
m3/h
770
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.65 1.43 3.57 1.46 3.48 1.49 3.39 1.52 3.31 1.55
-10 -11 4.29 1.51 4.19 1.54 4.09 1.57 3.99 1.60 3.89 1.63
-5 -7 4.68 1.58 4.57 1.61 4.46 1.64 4.34 1.68 4.23 1.71 0 -2 5.31 1.69 5.19 1.72 5.06 1.76 4.93 1.79 4.81 1.83 5 3 5.73 1.79 5.59 1.83 5.46 1.86 5.32 1.90 5.18 1.94 7 6 6.30 1.86 6.15 1.89 6.00 1.93 5.85 1.97 5.70 2.01
10 8 6.64 1.90 6.49 1.94 6.33 1.98 6.17 2.02 6.01 2.06 15 10 6.44 1.65 6.28 1.69 6.13 1.72 5.98 1.76 5.82 1.79
- 8 -
WALL MOUNTED
ASYG07-14LMCE
5. Fan performance
5-1. Air velocity distributions
¢
Models:ASYG07LMCE, ASYG09LMCE, and ASYG12LMCE
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
2.0
1.0
0.5
2
1
0
1
2
Unit: m/s(m)
(m)
0123456789
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Left & Right
2.0
2.0
1.0
1.0
0.5
0.5
3
2
1
0
1
2
3
Unit: m/s(m)
(m)
0123456789
Side view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
2.0
1.0
0.5
3
2
1
0
Unit: m/s(m)
(m)
0123456789
Side view Vertical airflow direction louver: Down
Horizontal airflow direction louver: Center
2.0
1.0
0.5
3
2
1
0
Unit: m/s(m)
(m)
0123456789
- 9 -
WALL MOUNTED
ASYG07-14LMCE
¢
Model:ASYG14LMCE
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
2.0
1.0 0.5
2
1
0
1
2
Unit: m/s(m)
(m)
0123456789
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Left & Right
1.0
1.0
0.5
0.5
3
2
1
0
1
2
3
Unit: m/s(m)
(m)
0123456789
2.0
2.0
Side view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
2.0
1.0
0.5
3
2
1
0
Unit: m/s(m)
(m)
0123456789
Side view Vertical airflow direction louver: Down
Horizontal airflow direction louver: Center
2.0
1.0
0.5
3
2
1
0
Unit: m/s(m)
(m)
0123456789
- 10 -
WALL MOUNTED
ASYG07-14LMCE
5-2. Airflow
¢
Models:ASYG07LMCE, ASYG09LMCE, and ASYG12LMCE
Cooling
Fan speed Airflow
HIGH
m3/h
750
l/s 208
CFM 441
MED
m3/h
640
l/s 178
CFM 377
LOW
m3/h
480
l/s 133
CFM 283
QUIET
m3/h
310
l/s 86
CFM 182
Heating
Fan speed Airflow
HIGH
m3/h
750
l/s 208
CFM 441
MED
m3/h
640
l/s 178
CFM 377
LOW
m3/h
520
l/s 144
CFM 306
QUIET
m3/h
330
l/s 92
CFM 194
- 11 -
WALL MOUNTED
ASYG07-14LMCE
¢
Model:ASYG14LMCE
Cooling
Fan speed Airflow
HIGH
m3/h
770
l/s 214
CFM 453
MED
m3/h
680
l/s 189
CFM 400
LOW
m3/h
530
l/s 147
CFM 312
QUIET
m3/h
360
l/s 100
CFM 212
Heating
Fan speed Airflow
HIGH
m3/h
770
l/s 214
CFM 453
MED
m3/h
680
l/s 189
CFM 400
LOW
m3/h
560
l/s 156
CFM 330
QUIET
m3/h
380
l/s 106
CFM 224
- 12 -
WALL MOUNTED
ASYG07-14LMCE
6. Operation noise (sound pressure)
6-1. Noise level curve
¢
Model:ASYG07LMCE
Cooling
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,00 0 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
¢
Model:ASYG09LMCE
Cooling
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,00 0 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,00 0 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 13 -
WALL MOUNTED
ASYG07-14LMCE
¢
Model:ASYG12LMCE
Cooling
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,00 0 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,00 0 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
¢
Model:ASYG14LMCE
Cooling
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,00 0 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 50 0 1,00 0 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 14 -
WALL MOUNTED
ASYG07-14LMCE
6-2. Sound level check point
0.8 m
1 m
Microphone Microphone
- 15 -
WALL MOUNTED
ASYG07-14LMCE
7. Safety devices
Type of
protection
Protection form
Model
ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE
Circuit protection
Current fuse (PCB*) 250 V, 3.15 A
Fan motor protection
Thermal protector program
Activate
105±10°C
Fan motor stop
Reset
90±10°C
Fan motor restart
*PCB: Printed Circuit Board
- 16 -
WALL MOUNTED
ASYG07-14LMCE
8. Remote controller
8-1. Wireless remote controller
¢
Overview
Signal
transmitter
TEMP.
button
POWERFUL
button
10°C HEAT
button
Start/Stop
button
FAN button
SWING button
SET button
MODE button
RESET button
CLOCK ADJUST button
ECONOMY button
OUTDOOR UNIT
LOW NOISE button
ON TIMER button
OFF TIMER button
TIMER SELECT button
SLEEP TIMER button
TIMER CANCEL button
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
Mode indicator
Clock and Timer indicator
LOW NOISE mode
indicator
Transmit indicator
Temperature indicator
Fan speed indicator
Swing indicator
To facilitate explanation, the accompanying illustration has been drawn to show all possible indica­tors; in actual operation, however, the display will only show those indicators appropriate to the cur­rent operation.
- 17 -
WALL MOUNTED
ASYG07-14LMCE
¢
Specifications
Controller
Unit: mm
Top view
Front view Side view
205
1761
Size (H × W × D) mm 205 × 61 × 17 Weight g 122 (without batteries)
Holder
Unit: mm
48.5
5.5
26.2
69.3
6.5
Front View Side View
Bottom View
Ø 3.5 (Hole)
150
106.8
Hole
3.5
2-R
Size (H × W × D) mm 150 × 69.3 × 26.2 Weight g 27
- 18 -
WALL MOUNTED
ASYG07-14LMCE
9. External input and output
With using external input and output functions, this product can be operated inter-connectedly with an external device.
Connector Input Output Remarks
CNA01 Control input
See external input/output
settings for details.
CNB01 Operation status output CNB02 Error status output
9-1. External input
With using external input function, some functions on this product can be controlled from an exter­nal device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢
Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
Unit operation Initial setting after power is on
Starting mode other than initial
setting
Operation mode Auto changeover Mode at previous operation Set temperature 24 °C Temperature at previous operation
Airflow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
Signal
Locally purchased
Indoor unit
control PCB
Communication kit
Optional parts
Connector
1
3
10 m*
Connected unit
Example: Switch
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit within 10 m.
• Use non-polar relays and switches.
When function setting is "Operation/Stop" mode
Operation
Stop
On
Off
Input signal
Indoor unit
- 19 -
WALL MOUNTED
ASYG07-14LMCE
When function setting is "Forced stop" mode
Remote controller
On On On
Input signal
Indoor unit
Command
Remote control operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ5
External input wire
Communication kit UTY-XCBXZ2
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
- 20 -
WALL MOUNTED
ASYG07-14LMCE
9-2. External output
With using external output function, operating status of this product can be transmitted to the ex­ternal device, and also, this product can be inter-connected with the external device.
¢
Operation status output
Air conditioner operation status signal can be output.
Circuit diagram example
Locally purchasedOptional parts
Example: Display
Indoor unit control PCB
Communication kit Connected unit
Example: Relay unit
1
2
Signal
Relay power supply
V
Connector
10 m*
DC 24 V
• *: Make the distance from the PCB to the connected unit within 10 m.
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
On
Off
Operation
Stop
Indoor unit
Output signal
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ5
External output wire
Communication kit UTY-XCBXZ2
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
- 21 -
WALL MOUNTED
ASYG07-14LMCE
¢
Error status output
Air conditioner error status signal can be output.
Circuit diagram example
Locally purchasedOptional parts
Example: Display
Indoor unit control PCB
Communication kit Connected unit
Example: Relay unit
1
2
Signal
Relay power supply
V
Connector
10 m*
DC 24 V
• *: Make the distance from the PCB to the connected unit within 10 m.
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
On
Off
Error
Normal
Error status
Output signal
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ5
External output wire
Communication kit UTY-XCBXZ2
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
- 22 -
WALL MOUNTED
ASYG07-14LMCE
10. Function settings
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE:
Incorrect settings can cause a product malfunction.
10-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting pro­cedure and the content of each function setting, select appropriate functions for your installation environment.
NOTE:
Incorrect settings can cause a product malfunction.
¢
Setting procedure by using wireless remote controller
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
Then, connect the power supply of the indoor unit.
Entering function setting mode:
While pressing the POWERFUL button and TEMP. (
) button simultaneously, press the RESET
button to enter the function setting mode.
STEP 1: Setting the remote controller custom code
Use the following steps to select the custom code of the remote controller. (Note that the air con­ditioner cannot receive a custom code if the air conditioner has not been set for the custom code.)
The custom codes that are set through this process are applicable only to the signal in the func­tion setting.
For details on how to set the custom codes through the normal process, refer to "Custom code
setting for wireless remote controller" on page 28.
1. Press the TEMP. ( ) ( ) buttons to change the custom code be­tween → → → . Match the code on the display to the air conditioner custom code. (Initially set to
.) If the custom code does not need to be selected, press the 10 °C HEAT button, and proceed to STEP 2.
2. Press the MODE button and check that the indoor unit can receive signals at the displayed custom code.
3. Press the 10 °C HEAT button to accept the custom code, and pro­ceed to STEP 2.
4. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
- 23 -
WALL MOUNTED
ASYG07-14LMCE
NOTES:
• The air conditioner custom code is set to
prior to shipment.
• The remote controller resets to custom code when the batteries on the remote controller are replaced. If you use a custom code other than code , reset the custom code after replacing
the batteries.
• If you do not know the air conditioner custom code setting, try each of the custom codes ( →
→ → ) until you find the code that operates the air conditioner.
STEP 2: Selecting the function number and setting value
1. Press the TEMP. ( ) ( ) buttons to select the function number.
To switch between the left and right digits, press the 10 °C HEAT button.
2. Press the POWERFUL button to proceed the setting value. To re-
turn the function number selection, press the POWERFUL button again.
3. Press the TEMP. (
) ( ) buttons to select the setting value. To switch between the left and right digits, press the 10 °C HEAT but­ton.
4. Press the MODE button, and START/STOP button, in the order listed to confirm the settings.
5. Press the RESET button to cancel the function setting mode.
6. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
Function number
Setting value
CAUTION
After disconnecting the power supply, wait 30 seconds or more before reconnecting it. The func­tion setting will not become active unless the power supply is disconnected and then reconnect­ed.
- 24 -
WALL MOUNTED
ASYG07-14LMCE
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 11 Filter sign
2) 30 Room temperature sensor control for cooling
3) 31 Room temperature sensor control for heating
4) 40 Auto restart
5) 42 Room temperature sensor switching
6) 44 Remote controller custom code
7) 46 External input control
8) 48 Room temperature sensor switching (Aux.)
9) 49 Indoor unit fan control for energy saving for cooling
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti­mated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard (400 hours) 01 Long interval (1,000 hours) 02 Short interval (200 hours) 03 No indication
2) Room temperature sensor control for cooling
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
Function number Setting value Setting description Factory setting
30
00 Standard ♦ 01 Slightly lower control 02 Lower control 03 Higher control
3) Room temperature sensor control for heating
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
Function number Setting value Setting description Factory setting
00 Standard ♦ 01 Lower control
31 02 Slightly higher control
03 Higher control
- 25 -
WALL MOUNTED
ASYG07-14LMCE
4) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable ♦ 01 Disable
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device.
5) Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number Setting value Setting description Factory setting
42
00 Indoor unit ♦ 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE:
Remote controller sensor must be turned on by using the remote controller.
6) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
44
00 A ♦ 01 B 02 C 03 D
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode ♦ 01 (Setting prohibited) 02 Forced stop mode
8) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01). When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
48
00 Both ♦ 01 Wired remote controller
- 26 -
WALL MOUNTED
ASYG07-14LMCE
9) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable 01 Enable
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the set-
ting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low
speed.
- 27 -
WALL MOUNTED
ASYG07-14LMCE
10-2. Custom code setting for wireless remote controller
To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required.
NOTE:
Air conditioner cannot receive a signal if the air conditioner has not been set for the cus­tom code.
When 2 or more air conditioners are installed in a room, and the remote controller is operating an air conditioner other than the one you wish to set, change the custom code of the remote con­troller to operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not match, the remote controller cannot be used to operate for the air conditioner.
1. Press the START/STOP button until only the clock is displayed on the remote controller display.
2. Press the MODE button for at least 5 seconds to display the cur­rent custom code. (Initially set to
.)
3. Press the TEMP. ( ) ( ) buttons to change the custom code be­tween
→ → → . Match the code on the display to the air
conditioner custom code. (Initially set to .)
4. Press the MODE button again to return to the clock display. The custom code will be changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system re­turns to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to
prior to shipment. To change the custom code,
contact your retailer.
• If you do not know the assigned code for the air conditioner, try each of the custom code ( → → → ) until you find the code which operates the air conditioner.
- 28 -
WALL MOUNTED
ASYG07-14LMCE
11. Accessories
Part name Exterior Q’ty Part name Exterior Q’ty
Operating manual 1 Cloth tape 1
Installation manual 1
Tapping screw (large), M4 × 25 mm
5
Wall hook bracket 1
Tapping screw (small), M3 × 12 mm
2
Remote controller 1 Air cleaning filter 2
Battery 2 Filter holder 2
Remote controller holder
1
Seal A (for 15 model)
1
- 29 -
WALL MOUNTED
ASYG07-14LMCE
12. Optional parts
12-1. Controllers
Exterior Part name Model name Summary
Wired remote
controller
UTY-RVNYM
Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wire type: Polar 3-wire
Wired remote
controller
UTY-RNNYM
Room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor. Wire type: Polar 3-wire
Simple remote
controller
UTY-RSNYM
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Polar 3-wire
NOTE:
Available functions may differ by the remote controller. For details, refer to the operation manual.
12-2. Others
Exterior Part name Model name Summary
External
connect kit
UTY-XWZXZ5
Required when external device is connected.
Communication
kit
UTY-XCBXZ2
Use to connect with optional devices and air conditioner PCB.
- 30 -
WALL MOUNTED
ASYG07-14LMCE
Part 2. OUTDOOR UNIT
SINGLE TYPE: AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE
1. Specifications
Type Inverter heat pump
Model name AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE
Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current A 3.3 3.5 4.8 6.3
Fan
Airflow rate
Cooling
m3/h
1,670 1,830 1,940
Heating 1,470 1,600 1,700 Type × Q'ty Propeller fan × 1 Motor output W 23 37
Sound pressure level *1
Cooling
dB (A)
45 50
Heating 45 50
Sound power level
Cooling
dB (A)
58 61 65
Heating 56 61 65
Heat exchanger type
Dimensions
(H × W × D)
mm
650 × 504 × 18.2 642 × 504 × 36.4 896 × 504 × 36.4
Fin pitch 1.3 1.4 1.3
Rows × Stages 1 × 24 2 × 24
Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum) Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty Rotary × 1 Motor output W 500 610 750
Refrigerant
Type (Global warming potential) R410A (1975)
Charge g 700 850 1,050
Refrigerant oil
Type POE (VG74)
Amount
cm
3
280
Enclosure
Material Steel sheet
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0 Dimensions
(H × W × D)
Net
mm
535 × 663 × 293 540 × 790 × 290
Gross 595 × 790 × 395 648 × 938 × 400
Weight
Net
kg
21 26 34
Gross 25 30 37
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8) Ø 12.7 (Ø 1/2) Method Flare Pre-charge length
m
15 Max. length 20 Max. height difference 15
Operation range
Cooling
°C
-10 to 43
Heating -15 to 24
Drain hose
Material PP+LLDPE LDPE
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.8 (O. D.)
Ø 13.0 (I. D.),
Ø 16.0 to Ø 16.7 (O.
D.)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 32 -
OUTDOOR UNIT
AOYG07-14LMCE
2. Dimensions
2-1. Models:AOYG07LMCE, AOYG09LMCE, and
AOYG12LMCE
Top view
Unit: mm
Front view Side view
20 663 68 293
Drain hole 30
330
454
(Pitch of bolt)
103
535
15
48
352
330
- 33 -
OUTDOOR UNIT
AOYG07-14LMCE
2-2. Model:AOYG14LMCE
790
290
352
6820 10 18
Top view
540
320
209
Side view
Front view
Airflow
175
110
9
20
540
Drain pipe mounting place (ø20)
4-ø11.3mm hole
Bottom view
Unit: mm
- 34 -
OUTDOOR UNIT
AOYG07-14LMCE
3. Installation space
3-1. Models:AOYG07LMCE, AOYG09LMCE, AOYG12LMCE,
and AOYG14LMCE
¢
Space requirement
Provide sufficient installation space for product safety.
Single outdoor unit installation
When the upper space is open:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the rear and
sides.
100 or more
250 or more
100 or more
100 or more
When there are obstacles at the front only. When there are obstacles at the front and
rear.
600 or more
600 or more
100 or more
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
100 or more
Max. 200
600 or more
600 or more
100 or more
250 or more
100 or more
Max. 200
- 35 -
OUTDOOR UNIT
AOYG07-14LMCE
Multiple outdoor unit installation
When the upper space is open:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
200
or more
1,000 or more
When there are obstacles at the front and rear.
200 or more
1,000 or more
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear and above.
1,500 or more
200 or more
Max. 300
- 36 -
OUTDOOR UNIT
AOYG07-14LMCE
Outdoor unit installation in multi-row
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
100 or more
200 or more
500 or more
1,000 or more
200 or more
400 or more
1,000 or more
2,000 or more
200 or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better opera­tion efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in ex­tremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
- 37 -
OUTDOOR UNIT
AOYG07-14LMCE
4. Refrigerant circuit
4-1. Models:AOYG07LMCE, AOYG09LMCE, AOYG12LMCE,
and AOYG14LMCE
Heat exchanger
(INDOOR)
Th
D
Th
D
Th
P
Th
P
Th
R
Th
R
Th
HO
Th
HO
Th
O
Th
O
3-way
valve
Muffler
: Cooling : Heating
: Thermistor (Discharge temperature)
: Thermistor (Outdoor temperature)
: Thermistor (Heat exchanger out temperature)
: Thermistor (Room temperature)
: Thermistor (Pipe temperature)
Compressor
4-way valve
Strainer
Expansion valve
Strainer
2-way
valve
- 38 -
OUTDOOR UNIT
AOYG07-14LMCE
5. Wiring diagrams
5-1. Models:AOYG07LMCE and AOYG09LMCE
- 39 -
OUTDOOR UNIT
AOYG07-14LMCE
5-2. Model:AOYG12LMCE
- 40 -
OUTDOOR UNIT
AOYG07-14LMCE
5-3. Model:AOYG14LMCE
- 41 -
OUTDOOR UNIT
AOYG07-14LMCE
6. Capacity compensation rate for pipe length and height difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Models:AOYG07LMCE and AOYG09LMCE
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.872 0.910 10 - - 0.961 0.886 0.925
7.5 - 0.979 0.965 0.890 0.929 5 0.992 0.983 0.969 0.893 0.933 0 1.000 0.991 0.976 0.901 0.940
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.991 0.976 0.901 0.940
-7.5 - 0.991 0.976 0.901 0.940
-10 - - 0.976 0.901 0.940
-15 - - - 0.901 0.940
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.832 0.822 10 - - 0.917 0.832 0.822
7.5 - 0.961 0.917 0.832 0.822 5 1.000 0.961 0.917 0.832 0.822 0 1.000 0.961 0.917 0.832 0.822
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.956 0.912 0.828 0.818
-7.5 - 0.954 0.910 0.826 0.816
-10 - - 0.908 0.824 0.814
-15 - - - 0.815 0.805
- 42 -
OUTDOOR UNIT
AOYG07-14LMCE
6-2. Model:AOYG12LMCE
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.858 0.868 10 - - 0.929 0.872 0.882
7.5 - 0.960 0.933 0.876 0.885 5 0.992 0.964 0.937 0.879 0.889 0 1.000 0.972 0.944 0.887 0.896
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.972 0.944 0.887 0.896
-7.5 - 0.972 0.944 0.887 0.896
-10 - - 0.944 0.887 0.896
-15 - - - 0.887 0.896
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.896 0.879 10 - - 0.968 0.890 0.879
7.5 - 0.994 0.968 0.896 0.879 5 1.000 0.994 0.968 0.896 0.879 0 1.000 0.994 0.968 0.896 0.879
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.989 0.963 0.891 0.875
-7.5 - 0.987 0.961 0.889 0.873
-10 - - 0.959 0.887 0.871
-15 - - - 0.878 0.862
- 43 -
OUTDOOR UNIT
AOYG07-14LMCE
6-3. Model:AOYG14LMCE
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.893 0.909 10 - - 0.955 0.908 0.924
7.5 - 0.975 0.959 0.912 0.928 5 0.992 0.979 0.963 0.916 0.931 0 1.000 0.987 0.970 0.923 0.939
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.987 0.970 0.923 0.939
-7.5 - 0.987 0.970 0.923 0.939
-10 - - 0.970 0.923 0.939
-15 - - - 0.923 0.939
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 - - - 0.956 0.938 10 - - 1.004 0.956 0.938
7.5 - 1.013 1.004 0.956 0.938 5 1.000 1.013 1.004 0.956 0.938 0 1.000 1.013 1.004 0.956 0.938
Indoor unit is lower than
outdoor unit *2
-5 0.995 1.008 0.999 0.951 0.938
-7.5 - 1.005 0.997 0.948 0.931
-10 - - 0.994 0.946 0.929
-15 - - - 0.937 0.919
- 44 -
OUTDOOR UNIT
AOYG07-14LMCE
7. Additional charge calculation
7-1. Models:AOYG07LMCE and AOYG09LMCE
Refrigerant type R410A Refrigerant amount g 700
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-2. Model:AOYG12LMCE
Refrigerant type R410A Refrigerant amount g 850
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-3. Model:AOYG14LMCE
Refrigerant type R410A Refrigerant amount g 1,050
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
- 45 -
OUTDOOR UNIT
AOYG07-14LMCE
8. Airflow
8-1. Models:AOYG07LMCE and AOYG09LMCE
Cooling
m3/h
1,670
l/s 464
CFM 983
Heating
m3/h
1,470
l/s 408
CFM 865
8-2. Model:AOYG12LMCE
Cooling
m3/h
1,830
l/s 508
CFM 1,077
Heating
m3/h
1,600
l/s 444
CFM 942
8-3. Model:AOYG14LMCE
Cooling
m
3
/h
1,940
l/s 539
CFM 1,142
Heating
m
3
/h
1,700
l/s 472
CFM 1,001
- 46 -
OUTDOOR UNIT
AOYG07-14LMCE
9. Operation noise (sound pressure)
9-1. Noise level curve
¢
Model:AOYG07LMCE
Cooling
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
Heating
-
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
¢
Model:AOYG09LMCE
Cooling
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
Heating
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
- 47 -
OUTDOOR UNIT
AOYG07-14LMCE
¢
Model:AOYG12LMCE
Cooling
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
Heating
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
¢
Model:AOYG14LMCE
Cooling
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
Heating
80
70
60
50
40
30
20
10
0
63 125 25 0 500 1,000 2,0 00 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency,Hz
- 48 -
OUTDOOR UNIT
AOYG07-14LMCE
9-2. Sound level check point
1 m
MicrophoneMicrophone
Rear
A
irflow
Rear view
Side view
NOTE:
Detailed shape of the actual outdoor unit might be slightly different from the one illustrat­ed above.
- 49 -
OUTDOOR UNIT
AOYG07-14LMCE
10. Electrical characteristics
Model name AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE Power
supply
Voltage V 230 ~
Frequency Hz 50 Max operating current *1 A 7.5 7.5 9.0 10.5 Starting current A 3.3 3.5 4.8 6.3
Wiring spec. *2
Circuit breaker current A 15
Power cable
mm
2
1.5
Connection cable *3
mm
2
1.5
Limited wiring length m 21
*1: Maximum current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri­ate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 50 -
OUTDOOR UNIT
AOYG07-14LMCE
11. Safety devices
Type of
protection
Protection form
Model
AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE
Circuit protection
Current fuse (PCB*)
250 V, 20 A
250 V, 3.15 A 250 V, 5 A
Fan motor protection
Terminal protection program
Activate
100±15°C
Fan motor stop
150±15°C
Fan motor stop
Reset
95±10°C
Fan motor restart
120±15°C Fan motor
restart
Compressor protection
Terminal protection program (Discharge temp.)
Activate
110°C
Compressor stop
Reset
After 7 minutes
Compressor restart
- 51 -
OUTDOOR UNIT
AOYG07-14LMCE
12. Accessories
Part name Exterior Q’ty Part name Exterior Q’ty
Installation manual 1 Drain pipe 1
- 52 -
OUTDOOR UNIT
AOYG07-14LMCE