Fujitsu AOYG07KGCA, ASYG12KGTA, ASYG07KGTA, AOYG09KGCA, ASYG09KGTA Design & Technical Manual

...
Page 1
AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA
OUTDOOR
AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA
2017.12.15
Page 2
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Trademarks
FGLair™ is trademark of Fujitsu General Limited in the United States, other countries or both.
Google Play™ is trademark of Google Inc.
App Store® is a service mark of Apple Inc., registered in the U.S. and other countries.
Copyright © 2017 Fujitsu General Limited. All rights reserved.
Page 3
CONTENTS
Part 1. INDOOR UNIT....................................................................... 1
1. Specifications............................................................................................2
2. Dimensions................................................................................................4
2-1. Models: ASYG07KGTA, ASYG09KGTA, ASYG12KGTA, and ASYG14KGTA........... 4
3. Wiring diagrams ........................................................................................6
3-1. Models: ASYG07KGTA, ASYG09KGTA, ASYG12KGTA, and ASYG14KGTA........... 6
4. Capacity table............................................................................................7
4-1. Cooling capacity.......................................................................................................... 7
4-2. Heating capacity .........................................................................................................9
5. Fan performance .....................................................................................10
5-1. Air velocity distributions............................................................................................. 10
5-2. Airflow....................................................................................................................... 12
6. Operation noise (sound pressure)......................................................... 16
6-1. Noise level curve....................................................................................................... 16
6-2. Sound level check point............................................................................................ 18
7. Safety devices ......................................................................................... 19
8. External input and output.......................................................................20
8-1. External input............................................................................................................ 21
8-2. External output.......................................................................................................... 22
8-3. Combination of external input and output.................................................................. 23
8-4. Details of function .....................................................................................................25
9. Group connection ................................................................................... 30
10. Remote controller ...................................................................................31
10-1.Wireless remote controller ....................................................................................... 31
11. Function settings .................................................................................... 33
11-1.Function settings by using remote controller............................................................ 33
11-2.Custom code setting for wireless remote controller.................................................. 40
12. Accessories.............................................................................................41
12-1.Models: ASYG07KGTA, ASYG09KGTA, ASYG12KGTA, and ASYG14KGTA........ 41
13. Optional parts..........................................................................................42
13-1.Controllers ............................................................................................................... 42
13-2.Others...................................................................................................................... 42
Page 4
Part 2. OUTDOOR UNIT................................................................. 43
1. Specifications..........................................................................................44
2. Dimensions..............................................................................................45
2-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA, and AOYG14KGCA...... 45
3. Installation space ....................................................................................46
3-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA, and AOYG14KGCA...... 46
4. Refrigerant circuit ................................................................................... 49
4-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA, and AOYG14KGCA...... 49
5. Wiring diagrams ......................................................................................50
5-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA, and AOYG14KGCA...... 50
6. Capacity compensation rate for pipe length and height difference....51
6-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA, and AOYG14KGCA...... 51
7. Additional charge calculation ................................................................ 52
7-1. Models: AOYG07KGCA and AOYG09KGCA ........................................................... 52
7-2. Models: AOYG12KGCA and AOYG14KGCA ........................................................... 52
8. Airflow......................................................................................................53
8-1. Model: AOYG07KGCA.............................................................................................. 53
8-2. Model: AOYG09KGCA.............................................................................................. 53
8-3. Model: AOYG12KGCA.............................................................................................. 53
8-4. Model: AOYG14KGCA.............................................................................................. 54
9. Operation noise (sound pressure)......................................................... 55
9-1. Noise level curve....................................................................................................... 55
9-2. Sound level check point............................................................................................ 57
10. Electrical characteristics........................................................................58
11. Safety devices ......................................................................................... 59
12. Accessories.............................................................................................60
12-1.Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA, and AOYG14KGCA..... 60
CONTENTS (continued)
Page 5
Part 1. INDOOR UNIT
WALL MOUNTED TYPE:
ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA
Page 6
1. Specifications
Type
Wall mounted
Inverter heat pump
Model name ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA
Power supply 230 V ~ 50 Hz Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 2.00 2.50 3.40 4.20
Btu/h 6,800 8,500 11,600 14,300
Min.—Max.
kW 0.9—3.2 0.9—3.4 0.9—4.1 0.9—4.5
Btu/h 3,100—10,900 3,100—11,600 3,100—14,000 3,100—15,400
Heating
Rated
kW 2.50 2.80 4.00 5.40
Btu/h 8,500 9,500 13,600 18,400
Min.—Max.
kW 0.9—5.2 0.9—5.4 0.9—6.1 0.9—6.4
Btu/h 3,100—17,700 3,100—18,400 3,100—20,800 3,100—21,800
Input power
Cooling
Rated
kW
0.400 0.555 0.805 1.175
Min.—Max. 0.25—0.95 0.25—1.04 0.25—1.29 0.25—1.46
Heating
Rated 0.500 0.560 0.910 1.350 Min.—Max. 0.25—1.58 0.25—1.72 0.25—1.89 0.25—2.06
Fan
HIGH
W
22.9 26.9 26.6 32.5 MED 15.8 16.9 17.3 19.6 LOW 10.8 10.8 11.8 12.5 QUIET 7.6 7.6 9.0 9.1
Current
Cooling
Rated A
2.3 3.0 4.3 5.3
Heating 2.8 3.5 4.8 6.4
EER Cooling
kW/kW
5.00 4.50 4.22 3.57
COP Heating 5.00 5.00 4.40 4.00 Sensible capacity Cooling kW 1.2 1.6 2.2 3.2
Power factor
Cooling
%
76 80 81 96
Heating 78 70 82 92
Moisture removal L/h (pints/h) 1.0 (1.76) 1.3 (2.288) 1.8 (3.168) 2.1 (3.696)
Maximum operating current *1
Cooling
A
6.5 6.5 6.5 9.0
Heating 9.0 9.0 9.0 10.5
Fan
Airflow rate
Cooling
HIGH
m3/h
650 700 700 770 MED 540 560 560 600 LOW 430 430 430 450 QUIET 270 270 250 280
Heating
HIGH 720 750 770 800 MED 580 610 640 660 LOW 460 470 520 520 QUIET 330 330 310 340
Type × Q'ty Cross flow fan × 1 Motor output W 22 24 27 30
Sound pressure level *2
Cooling
HIGH
dB (A)
38 40 40 43 MED 33 34 35 36 LOW 29 29 30 30 QUIET 19 19 19 20
Heating
HIGH 41 42 42 44 MED 35 36 38 39 LOW 31 31 33 33 QUIET 21 21 21 24
Heat exchanger type
Dimensions (H × W × D)
mm
Main1: 210 × 670 × 26.6
Main2: 112 × 670 × 20
Main1: 210 × 670 × 26.6
Main2: 112 × 670 × 20
Sub: 84 × 670 × 13.3 Fin pitch Man1: 1.2, Main2: 1.1 Man1: 1.2, Main2: 1.1, Sub: 1.4 Rows × Stages Main1: 2 × 10, Main2: 2 × 7 Main1: 2 × 10, Main2: 2 × 7, Sub: 1 × 4 Pipe type Copper tube Fin type Aluminum
Enclosure
Material Polystyrene
Color
White + Pearl white (painted)
Approximate color of Munsell N 9.25/
Dimensions (H × W × D)
Net
mm
270 × 834 × 215
Gross 277 × 914 × 332
Weight
Net
kg
10.0
Gross 12.5 13.0
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8)
Method Flare
Drain hose
Material PP+LLDPE Size mm Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type
Wireless (Wired, Mobile app*3 [FGLair™] [option])
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play™ store or on App Store®. Optional WLAN adapter is also required. For details, refer to the setting manual.
- 2 -
WALL MOUNTED
ASYG07-14KGTA
Page 7
Model name ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA
Energy efficiency class
Cooling
A
+++
A
++
Heating (Average)
A
+++
A
+
Pdesign
Cooling
kW
2.0 (35 °C) 2.5 (35 °C) 3.4 (35 °C) 4.2 (35 °C)
Heating (Average) 2.3 (-10 °C) 2.4 (-10 °C) 2.5 (-10 °C) 4.0 (-10 °C)
SEER Cooling
kWh/kWh
8.52 8.52 8.51 7.11
SCOP Heating (Average) 5.12 5.11 5.10 4.31
Annual energy consumption
QCE
kWh/a
82 103 140 207
QHE (Average) 628 658 685 1,298
Sound power level
Cooling
HIGH dB (A)
54 55 56 57
Heating 56 57 58 59
- 3 -
WALL MOUNTED
ASYG07-14KGTA
Page 8
2. Dimensions
2-1. Models: ASYG07KGTA, ASYG09KGTA, ASYG12KGTA,
and ASYG14KGTA
Unit: mm
834
(834)
Outline of indoor unit
327
273
273 54
215
3.0
270(270)
43
43
9.5220
for pipe inlet Ø65 for pipe inlet Ø65
182 182
35634648 84
63 63
- 4 -
WALL MOUNTED
ASYG07-14KGTA
Page 9
¢
Installation space requirement
Provide sufficient installation space for product safety.
Unit: mm
Wall hook bracket
Outline of the indoor unit
50 or more
67 or more
The flare connection part should be installed outdoors.
40 or more
70 or more
107 or more
1,500 or more
1,800 or more
183 or more
- 5 -
WALL MOUNTED
ASYG07-14KGTA
Page 10
3. Wiring diagrams
3-1. Models: ASYG07KGTA, ASYG09KGTA, ASYG12KGTA,
and ASYG14KGTA
- 6 -
WALL MOUNTED
ASYG07-14KGTA
Page 11
4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢
Model: ASYG07KGTA
AFR
m3/h
650
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-10 2.29 2.01 0.13 2.48 2.11 0.14 2.72 2.26 0.14 2.85 2.28 0.14 2.95 2.34 0.14 3.17 2.39 0.15 3.37 2.48 0.14 0 2.25 2.07 0.24 2.43 2.13 0.23 2.57 2.21 0.23 2.68 2.22 0.23 2.79 2.27 0.22 2.96 2.31 0.22 3.18 2.43 0.21 5 2.29 2.08 0.14 2.47 2.14 0.13 2.61 2.23 0.13 2.73 2.23 0.13 2.84 2.28 0.13 3.01 2.33 0.13 3.23 2.45 0.12
10 2.25 2.01 0.19 2.43 2.07 0.19 2.57 2.15 0.19 2.68 2.16 0.18 2.79 2.21 0.18 2.96 2.25 0.18 3.18 2.36 0.17 15 2.21 2.05 0.25 2.38 2.11 0.25 2.51 2.19 0.25 2.63 2.20 0.24 2.73 2.25 0.24 2.90 2.30 0.23 3.11 2.41 0.23 20 2.20 2.04 0.31 2.38 2.10 0.30 2.51 2.18 0.30 2.62 2.18 0.29 2.72 2.23 0.28 2.89 2.28 0.28 3.10 2.39 0.27 25 2.08 2.01 0.37 2.25 2.07 0.36 2.37 2.15 0.36 2.48 2.16 0.35 2.58 2.21 0.34 2.73 2.25 0.34 2.93 2.36 0.33 30 2.00 1.97 0.43 2.16 2.03 0.41 2.28 2.11 0.41 2.39 2.12 0.40 2.48 2.18 0.40 2.63 2.23 0.39 2.82 2.34 0.38 35 1.95 1.92 0.48 2.10 1.98 0.47 2.22 2.05 0.47 2.31 2.06 0.46 2.35 2.19 0.45 2.55 2.24 0.44 2.74 2.35 0.43 40 1.82 1.77 0.54 1.96 1.82 0.52 2.07 1.89 0.53 2.16 1.90 0.51 2.25 2.13 0.50 2.39 2.18 0.50 2.56 2.28 0.48 46 1.69 1.67 0.57 1.83 1.80 0.56 1.95 1.93 0.57 2.03 2.02 0.57 2.14 2.09 0.56 2.24 2.12 0.55 2.42 2.17 0.54
¢
Model: ASYG09KGTA
AFR
m3/h
700
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-10 2.75 2.40 0.18 2.98 2.51 0.19 3.26 2.69 0.20 3.42 2.72 0.20 3.54 2.79 0.20 3.81 2.85 0.21 4.04 2.95 0.20 0 2.71 2.46 0.33 2.92 2.54 0.32 3.08 2.63 0.32 3.22 2.64 0.31 3.35 2.70 0.31 3.55 2.76 0.31 3.81 2.89 0.30 5 2.75 2.48 0.19 2.97 2.55 0.18 3.13 2.65 0.19 3.27 2.66 0.18 3.41 2.72 0.18 3.61 2.78 0.17 3.87 2.91 0.17
10 2.71 2.40 0.27 2.92 2.47 0.26 3.08 2.56 0.26 3.22 2.57 0.26 3.35 2.63 0.25 3.55 2.69 0.25 3.81 2.82 0.24 15 2.65 2.44 0.35 2.86 2.52 0.34 3.02 2.61 0.34 3.15 2.62 0.33 3.28 2.68 0.33 3.48 2.74 0.32 3.73 2.87 0.32 20 2.64 2.43 0.42 2.85 2.50 0.41 3.01 2.59 0.41 3.14 2.60 0.40 3.27 2.66 0.40 3.47 2.72 0.39 3.72 2.85 0.38 25 2.50 2.40 0.51 2.70 2.47 0.50 2.85 2.56 0.50 2.97 2.57 0.49 3.09 2.63 0.48 3.28 2.69 0.47 3.52 2.82 0.46 30 2.41 2.35 0.59 2.60 2.42 0.58 2.74 2.51 0.58 2.86 2.52 0.56 2.98 2.60 0.55 3.16 2.66 0.54 3.39 2.79 0.53 35 2.33 2.29 0.67 2.52 2.35 0.65 2.66 2.44 0.65 2.78 2.45 0.64 2.89 2.61 0.63 3.06 2.67 0.62 3.29 2.80 0.60 40 2.18 2.11 0.75 2.36 2.17 0.73 2.49 2.26 0.73 2.60 2.27 0.71 2.70 2.54 0.70 2.86 2.60 0.69 3.07 2.72 0.67 46 2.03 2.01 0.79 2.20 2.15 0.79 2.34 2.30 0.79 2.44 2.41 0.79 2.57 2.49 0.78 2.69 2.52 0.76 2.90 2.59 0.75
¢
Model: ASYG12KGTA
AFR
m3/h
700
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-10 3.09 2.54 0.32 3.45 2.78 0.38 3.82 2.96 0.44 4.00 3.01 0.45 4.13 3.09 0.40 4.41 3.14 0.45 4.62 3.21 0.44 0 3.30 2.76 0.52 3.57 2.87 0.54 3.76 2.93 0.51 3.94 3.01 0.52 4.04 3.05 0.53 4.37 3.15 0.52 4.68 3.23 0.54 5 3.27 2.75 0.29 3.54 2.85 0.30 3.72 2.91 0.29 3.91 2.99 0.29 4.00 3.03 0.30 4.33 3.13 0.29 4.64 3.22 0.30
10 3.23 2.72 0.38 3.49 2.83 0.40 3.68 2.89 0.37 3.86 2.97 0.38 3.95 3.01 0.39 4.28 3.10 0.38 4.58 3.19 0.39 15 3.17 2.69 0.46 3.43 2.80 0.48 3.61 2.86 0.46 3.79 2.93 0.47 3.88 2.98 0.47 4.20 3.07 0.47 4.50 3.15 0.48 20 3.10 2.65 0.54 3.35 2.76 0.57 3.53 2.81 0.54 3.71 2.89 0.55 3.79 2.93 0.56 4.11 3.02 0.55 4.40 3.11 0.56 25 3.01 2.61 0.62 3.26 2.71 0.65 3.43 2.76 0.61 3.60 2.84 0.62 3.69 2.88 0.63 3.99 2.97 0.62 4.27 3.05 0.64 30 2.91 2.55 0.69 3.15 2.65 0.72 3.31 2.70 0.68 3.48 2.78 0.69 3.56 2.82 0.71 3.85 2.90 0.69 4.13 2.98 0.72 35 2.79 2.48 0.76 3.02 2.58 0.79 3.18 2.63 0.75 3.34 2.71 0.76 3.42 2.75 0.77 3.70 2.83 0.76 3.96 2.91 0.79 40 2.66 2.41 0.82 2.88 2.51 0.86 3.03 2.56 0.81 3.18 2.63 0.82 3.25 2.66 0.84 3.52 2.75 0.82 3.77 2.82 0.85 46 2.45 2.40 0.91 2.62 2.51 0.88 2.77 2.60 0.91 2.85 2.62 0.88 2.90 2.59 0.90 3.10 2.72 0.92 3.32 2.75 0.92
- 7 -
WALL MOUNTED
ASYG07-14KGTA
Page 12
¢
Model: ASYG14KGTA
AFR
m3/h
770
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW
-10 3.35 2.71 0.35 3.74 2.97 0.42 4.14 3.16 0.48 4.34 3.22 0.49 4.48 3.30 0.44 4.78 3.35 0.49 5.01 3.43 0.49 0 3.57 2.95 0.57 3.87 3.06 0.60 4.07 3.13 0.56 4.27 3.21 0.57 4.37 3.26 0.58 4.73 3.36 0.57 5.07 3.45 0.59 5 3.54 2.93 0.32 3.84 3.05 0.33 4.04 3.11 0.31 4.24 3.20 0.32 4.34 3.24 0.32 4.70 3.34 0.32 5.03 3.43 0.33
10 3.50 2.91 0.42 3.79 3.02 0.43 3.98 3.09 0.41 4.18 3.17 0.42 4.28 3.21 0.42 4.63 3.31 0.42 4.96 3.41 0.43 15 3.44 2.88 0.51 3.72 2.99 0.53 3.91 3.05 0.50 4.11 3.13 0.51 4.21 3.18 0.52 4.55 3.28 0.51 4.88 3.37 0.53 20 3.36 2.83 0.60 3.63 2.94 0.62 3.82 3.01 0.59 4.02 3.09 0.60 4.11 3.13 0.61 4.45 3.23 0.60 4.77 3.32 0.62 25 3.26 2.78 0.68 3.53 2.89 0.71 3.72 2.95 0.67 3.90 3.03 0.68 3.99 3.07 0.69 4.32 3.17 0.68 4.63 3.26 0.71 30 3.15 2.72 0.76 3.41 2.83 0.79 3.59 2.89 0.75 3.77 2.97 0.76 3.86 3.01 0.77 4.18 3.10 0.76 4.47 3.19 0.79 35 3.02 2.65 0.83 3.27 2.76 0.87 3.44 2.81 0.82 3.62 2.89 0.84 3.70 2.93 0.85 4.01 3.02 0.84 4.29 3.11 0.86 40 2.88 2.58 0.90 3.12 2.68 0.94 3.28 2.73 0.89 3.45 2.81 0.90 3.53 2.85 0.92 3.82 2.93 0.91 4.09 3.01 0.94 46 2.65 2.56 1.00 2.84 2.68 0.96 3.01 2.78 1.00 3.08 2.80 0.97 3.15 2.76 0.98 3.36 2.90 1.01 3.59 2.94 1.01
- 8 -
WALL MOUNTED
ASYG07-14KGTA
Page 13
4-2. Heating capacity
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
¢
Model: ASYG07KGTA
AFR
m3/h
720
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.08 1.30 3.11 1.35 3.09 1.38 3.06 1.42 3.04 1.43
-10 -11 3.62 1.39 3.66 1.44 3.63 1.46 3.60 1.51 3.58 1.52
-5 -7 4.10 1.44 4.13 1.49 4.10 1.52 4.06 1.56 4.04 1.57 0 -2 4.50 1.48 4.54 1.53 4.43 1.53 4.36 1.56 4.35 1.59 5 3 4.86 1.45 4.94 1.51 4.82 1.51 4.74 1.55 4.73 1.57 7 6 5.24 1.48 5.33 1.58 5.20 1.58 5.12 1.62 5.11 1.64
10 8 5.39 1.51 5.49 1.61 5.28 1.59 5.27 1.65 5.26 1.67 15 10 5.29 1.31 5.38 1.40 5.16 1.40 5.17 1.43 5.16 1.45 20 15 5.54 1.25 5.54 1.23 5.38 1.24 5.26 1.23 5.11 1.25 24 18 5.69 1.18 5.69 1.17 5.53 1.17 5.40 1.16 5.26 1.18
¢
Model: ASYG09KGTA
AFR
m3/h
750
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.20 1.42 3.23 1.47 3.21 1.50 3.18 1.54 3.16 1.55
-10 -11 3.76 1.51 3.80 1.57 3.77 1.59 3.74 1.64 3.72 1.65
-5 -7 4.26 1.56 4.29 1.62 4.26 1.65 4.22 1.70 4.19 1.71 0 -2 4.67 1.61 4.72 1.67 4.61 1.66 4.53 1.70 4.52 1.73 5 3 5.04 1.58 5.13 1.65 5.01 1.65 4.93 1.68 4.92 1.71 7 6 5.44 1.61 5.53 1.72 5.40 1.72 5.31 1.76 5.30 1.79
10 8 5.60 1.64 5.70 1.76 5.48 1.73 5.47 1.79 5.46 1.82 15 10 5.49 1.42 5.59 1.52 5.36 1.52 5.37 1.55 5.35 1.58 20 15 5.75 1.36 5.75 1.34 5.58 1.35 5.46 1.34 5.31 1.36 24 18 5.91 1.29 5.91 1.27 5.74 1.28 5.61 1.27 5.46 1.29
¢
Model: ASYG12KGTA
AFR
m3/h
770
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.40 1.39 3.39 1.36 3.36 1.36 3.34 1.37 3.30 1.40
-10 -11 4.02 1.41 3.93 1.43 3.83 1.46 3.72 1.48 3.60 1.52
-5 -7 4.60 1.51 4.50 1.54 4.39 1.57 4.26 1.60 4.12 1.63 0 -2 5.29 1.63 5.17 1.66 5.04 1.69 4.89 1.72 4.73 1.76 5 3 6.06 1.77 5.93 1.79 5.78 1.83 5.61 1.87 5.43 1.91 7 6 6.40 1.82 6.26 1.85 6.10 1.89 5.92 1.93 5.73 1.97
10 8 6.94 1.92 6.78 1.94 6.61 1.98 6.42 2.02 6.21 2.07 15 10 6.33 1.58 6.19 1.60 6.03 1.63 5.86 1.66 5.67 1.70 20 15 6.61 1.38 6.46 1.41 6.29 1.43 6.11 1.46 5.91 1.50 24 18 6.89 1.32 6.75 1.40 6.50 1.37 6.14 1.36 5.66 1.39
¢
Model: ASYG14KGTA
AFR
m3/h
800
Indoor temperature
16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.57 1.51 3.56 1.49 3.52 1.48 3.51 1.50 3.46 1.53
-10 -11 4.22 1.53 4.12 1.56 4.02 1.59 3.90 1.62 3.77 1.66
-5 -7 4.83 1.65 4.72 1.67 4.60 1.71 4.47 1.74 4.33 1.78 0 -2 5.55 1.78 5.42 1.81 5.29 1.84 5.13 1.88 4.97 1.92 5 3 6.36 1.93 6.22 1.96 6.06 1.99 5.89 2.03 5.70 2.08 7 6 6.72 1.99 6.57 2.02 6.40 2.06 6.21 2.10 6.01 2.15
10 8 7.28 2.09 7.11 2.12 6.93 2.16 6.73 2.20 6.52 2.26 15 10 6.64 1.72 6.49 1.74 6.33 1.78 6.15 1.81 5.95 1.86 20 15 6.93 1.51 6.77 1.53 6.60 1.56 6.41 1.59 6.20 1.63 24 18 7.22 1.44 7.08 1.53 6.82 1.50 6.44 1.48 5.94 1.52
- 9 -
WALL MOUNTED
ASYG07-14KGTA
Page 14
5. Fan performance
5-1. Air velocity distributions
¢
Models: ASYG07KGTA and ASYG09KGTA
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
(m)
-3
-2
-1
0
1
2
3
0.52.0 1.0
Unit: m/s
(m)
012345678910
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
2.0
2.0
1.0
1.0
0.5
0.5
Unit: m/s
(m)
(m)
-3
-2
-1
0
1
2
3
012345678910
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
(m)
(m)
3
2
1
0
012345678910
Unit: m/s
2.0
0.5
1.0
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
(m)
(m)
3
2
1
0
012345678910
0.50.5
2.0
1.0
Unit: m/s
- 10 -
WALL MOUNTED
ASYG07-14KGTA
Page 15
¢
Models: ASYG12KGTA and ASYG14KGTA
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Unit: m/s
(m)
(m)
-3
-2
-1
0
1
2
3
012345678910
0.52.0 1.0
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
1.0
1.0
0.5
0.5
2.0
2.0
Unit: m/s
(m)
(m)
-3
-2
-1
0
1
2
3
012345678910
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2.0
0.5
1.0
(m)
(m)
3
2
1
0
012345678910
Unit: m/s
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
0.50.5
2.0
1.0
(m)
(m)
3
2
1
0
012345678910
Unit: m/s
- 11 -
WALL MOUNTED
ASYG07-14KGTA
Page 16
5-2. Airflow
¢
Model: ASYG07KGTA
Cooling
Fan speed Airflow
HIGH
m3/h
650
l/s 181
CFM 383
MED
m3/h
540
l/s 150
CFM 318
LOW
m3/h
430
l/s 119
CFM 253
QUIET
m3/h
270
l/s 75
CFM 159
Heating
Fan speed Airflow
HIGH
m3/h
720
l/s 200
CFM 424
MED
m3/h
580
l/s 161
CFM 341
LOW
m3/h
460
l/s 128
CFM 271
QUIET
m3/h
330
l/s 92
CFM 194
- 12 -
WALL MOUNTED
ASYG07-14KGTA
Page 17
¢
Model: ASYG09KGTA
Cooling
Fan speed Airflow
HIGH
m3/h
700
l/s 194
CFM 412
MED
m3/h
560
l/s 156
CFM 330
LOW
m3/h
430
l/s 119
CFM 253
QUIET
m3/h
270
l/s 75
CFM 159
Heating
Fan speed Airflow
HIGH
m3/h
750
l/s 208
CFM 441
MED
m3/h
610
l/s 169
CFM 359
LOW
m3/h
470
l/s 131
CFM 277
QUIET
m3/h
330
l/s 92
CFM 194
- 13 -
WALL MOUNTED
ASYG07-14KGTA
Page 18
¢
Model: ASYG12KGTA
Cooling
Fan speed Airflow
HIGH
m3/h
700
l/s 194
CFM 412
MED
m3/h
560
l/s 156
CFM 330
LOW
m3/h
430
l/s 119
CFM 253
QUIET
m3/h
250
l/s 69
CFM 147
Heating
Fan speed Airflow
HIGH
m3/h
770
l/s 214
CFM 453
MED
m3/h
640
l/s 178
CFM 377
LOW
m3/h
520
l/s 144
CFM 306
QUIET
m3/h
310
l/s 86
CFM 182
- 14 -
WALL MOUNTED
ASYG07-14KGTA
Page 19
¢
Model: ASYG14KGTA
Cooling
Fan speed Airflow
HIGH
m3/h
770
l/s 214
CFM 453
MED
m3/h
600
l/s 167
CFM 353
LOW
m3/h
450
l/s 125
CFM 265
QUIET
m3/h
280
l/s 78
CFM 165
Heating
Fan speed Airflow
HIGH
m3/h
800
l/s 222
CFM 471
MED
m3/h
660
l/s 183
CFM 388
LOW
m3/h
520
l/s 144
CFM 306
QUIET
m3/h
340
l/s 94
CFM 200
- 15 -
WALL MOUNTED
ASYG07-14KGTA
Page 20
6. Operation noise (sound pressure)
6-1. Noise level curve
¢
Model: ASYG07KGTA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
¢
Model: ASYG09KGTA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
- 16 -
WALL MOUNTED
ASYG07-14KGTA
Page 21
¢
Model: ASYG12KGTA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
¢
Model: ASYG14KGTA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HIGH
QUIET
- 17 -
WALL MOUNTED
ASYG07-14KGTA
Page 22
6-2. Sound level check point
0.8 m
1 m
Microphone Microphone
NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated
above.
- 18 -
WALL MOUNTED
ASYG07-14KGTA
Page 23
7. Safety devices
Type of protection Protection form
Model
ASYG07KGTA ASYG09KGTA
Circuit protection Current fuse (PCB*) 250 V, 3.15 A
Fan motor protection Thermistor protection
Activate
More than 85 °C
Fan motor speed down
Reset
85 °C or less
Fan motor speed recover
Type of protection Protection form
Model
ASYG12KGTA ASYG14KGTA
Circuit protection Current fuse (PCB*) 250 V, 3.15 A
Fan motor protection
Power IC thermal shutdown protection
Activate
125±25 °C
Fan motor stop
Reset
110
+25
-20
°C
Fan motor restart
*PCB: Printed Circuit Board
- 19 -
WALL MOUNTED
ASYG07-14KGTA
Page 24
8. External input and output
Indoor unit PCB
CN314
CN313
CN312
CN311
CN310
Rotary switchSW302SW301
CN308
External input and output PCB
CN6
PCB External input External output Connector Input select
Input
signal
External input
and output
(UTY-XCSXZ2)
Operation/Stop
-
CN313/
CN314
Dry contact/
Apply voltage
Edge/Pulse
Forced stop Forced thermostat off CN313 Edge
-
Operation status
CN310
- -
Error status CN311 Indoor unit fan
operation status
CN312
- 20 -
WALL MOUNTED
ASYG07-14KGTA
Page 25
8-1. External input
With using external input function, some functions on this product can be controlled from an exter­nal device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢
External input and output PCB
The indoor unit Operation/Stop can be set by using the input connector on the PCB.
Input select: Use either one of these types of connectors according to the application. (Both types of con­nectors cannot be used simultaneously.)
– Dry contact
In case of internal power supply, set the slide switch of SW301 to "NON VOL" side.
1
2
3
Input 1
PCB
Connected unit
*
+
-
1
2
3
Input 2
*
+
-
Connecto
r
(CN313)
Connecto
r
(CN314)
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
– Apply voltage
In case of external power supply, set the slide switch of SW301 to "VOL" side.
1
2
3
Input 1
Power supply
PCB
Connected unit
*
*
*2
+-
1
2
3
Input 2
Connector
(CN313)
Connector
(CN314)
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA. *2: Make the power supply DC 12 to 24 V, 10 mA or more.
- 21 -
WALL MOUNTED
ASYG07-14KGTA
Page 26
8-2. External output
Use an external output cable with appropriate external dimension, depending on the number of cables to be installed.
¢
External input and output PCB
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V±2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to "Combination of external input and output" on page 23.
When indicator or other components are connected directly: Example: Function setting 60 is set to "00".
1
2
Connecto
r
(CN310)
LED 1
(Operation status)
PCB
Resistor
Connected unit
+
-
1
2
Connecto
r
(CN311)
LED 2
(Error status)
Resistor
+
-
1
2
Connecto
r
(CN312)
LED 3
(Indoor unit fan
operation status)
Resistor
+
-
When connecting with a device equipped with a power supply: Example: Function setting 60 is set to "00".
1
2
Connected device 1
Connecto
r
(CN310)
PCBConnected unit Relay
(Operation status)
-
+
1
2
Connected device 2
Connecto
r
(CN311)
(Error status)
-
+
1
2
Connected device 3
Connecto
r
(CN312)
(Indoor unit fan
operation status)
-
+
- 22 -
WALL MOUNTED
ASYG07-14KGTA
Page 27
8-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
Mode
Function
setting
External input
and output PCB
(Rotary SW)
External input
External input and output PCB
CN313 CN314 Signal type
0-1 60-00 1
Operation/Stop Not available Edge
Operation Stop Pulse
0-2 60-00 2
Forced Thermostat
OFF
Not available Edge
1—8
60-01 to
60-08
3 - 9, A (Setting prohibited)
9 60-09 B
Forced Thermostat
OFF
Not available Edge
10 60-10 C
Forced Thermostat
OFF
Not available Edge
11 60-11 D
Forced Thermostat
OFF
Not available Edge
Mode
Function
setting
External input
and output PCB
(Rotary SW)
External output
External input and output PCB
CN310 CN311 CN312
0-1 60-00 1 Operation/Stop Error status
Indoor unit fan
operation status
0-2 60-00 2 Error status
Indoor unit fan
operation status
Not available
1—8
60-01 to
60-08
3 - 9, A (Setting prohibited)
9 60-09 B Operation/Stop
Indoor unit fan
operation status
Not available
10 60-10 C Operation/Stop Error status Not available
11 60-11 D Operation/Stop
Indoor unit fan
operation status
Error status
NOTE:
Input of Operation/Stop depends on the setting of function setting 46. 00: Operation/Stop mode 1 (R.C. enabled) 01: (Setting prohibited) 02: Forced stop 03: Operation/Stop mode 2 (R.C. disabled)
- 23 -
WALL MOUNTED
ASYG07-14KGTA
Page 28
¢
Input signal type
External input and output PCB:
The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and
output PCB.
Edge
Pulse
The width of pulse must be longer than 200 msec.
- 24 -
WALL MOUNTED
ASYG07-14KGTA
Page 29
8-4. Details of function
¢
Control input function
When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input:
Function
setting /
Rotary SW on
External input and
output PCB
External input Input signal Command
46-00 60-00 / 1
External input and
output PCB
CN313
Off → On Operation On → Off Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
CN313
– In the case of "Pulse" input:
Function
setting /
Rotary SW on
External input and
output PCB
External input Input signal Command
46-00 60-00 / 1
External input and
output PCB
CN313 Pulse Operation CN314 Pulse Stop
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
- 25 -
WALL MOUNTED
ASYG07-14KGTA
Page 30
When function setting is "Forced stop" mode – In the case of "Edge" input:
Function
setting /
Rotary SW on
External input and
output PCB
External input Input signal Command
46-02 60-00 / 1
External input and
output PCB
CN313
Off → On Forced stop On → Off Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On On
Indoor unit
On
CN313
– In the case of "Pulse" input:
Function
setting /
Rotary SW on
External input and
output PCB
External input Input signal Command
46-02 60-00 / 1
External input and
output PCB
CN313 Pulse Forced stop CN314 Pulse Normal
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
CN313
CN314
On On On
Indoorunit
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
- 26 -
WALL MOUNTED
ASYG07-14KGTA
Page 31
When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input:
Function
setting /
Rotary SW on
External input and
output PCB
External input Input signal Command
46-03 60-00 / 1
External input and
output PCB
CN313
Off → On Operation
On → Off
Stop (R.C.
disabled)
On
CN313
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote contoller
On OnOff
– In the case of "Pulse" input:
Function
setting /
Rotary SW on
External input and
output PCB
External input Input signal Command
46-03 60-00 / 1
External input and
output PCB
CN313 Pulse Operation
CN314 Pulse
Stop (R.C.
disabled)
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
(R.C. disabled)
Off
On
NOTE:
When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
- 27 -
WALL MOUNTED
ASYG07-14KGTA
Page 32
Forced thermostat off function
Function
setting /
Rotary SW on
External input and
output PCB
External input Input signal Command
60-00 / 2 60-09 / B
60-10 / C
External input and output
PCB
CN313
Off → On
Thermostat
off
On → Off
Normal
operation
On Off
On
Off
Compressor
Room temp.
Set temp.
Input
- 28 -
WALL MOUNTED
ASYG07-14KGTA
Page 33
¢
Control output function
Operation/Stop status
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
60-00 / 1
External input and output
PCB
CN310
Off → On Operation On → Off Stop
The output is low when the unit is stopped.
Operation
Stop
On
Off
CN310
Indoor unit
Error status
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
60-00 / 1
External input and output
PCB
CN311
Off → On Error On → Off Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
On
Off
CN310―312
Indoor unit
Indoor unit fan operation status
Function
setting /
Rotary SW on External
input and output PCB
External output
Output
signal
Command
60-00 / 1
External input and output
PCB
CN312
Off → On Fan run On → Off Fan stop
Output signal Condition
On
The indoor unit fan is operating.
Low → High
Off The fan is stopped or during cold air prevention.
High → Low During thermostat off when in dry mode operation.
Fan run
Fan stop
On
Off
CN311―312
Indoor unit
- 29 -
WALL MOUNTED
ASYG07-14KGTA
Page 34
9. Group connection
Installation procedure for group control system:
A number of indoor units can be operated at the same time using a single remote controller.
NOTE:
When different type of indoor units (such as wall mounted type and cassette type, cas­sette type and duct type, or other combinations) are connected using group control sys­tem, some functions may no longer be available.
1. Connect up to 16 indoor units in a system.
A
BCDE
I.U. I.U. I.U. I.U.
Remote controller
A
, B, C, D, E: Remote controller cable
A
+ B + C + D + E ≤ 500 m
Example of wiring method
12
R W
Remote controller cable
Bus wire
Remote controller
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
2. Set the R.C. address. (Function setting)
• Addresses will be automatically set when initially starting up this unit. In such a case, do not change the remote controller address for the indoor unit, and keep it at the initial set­ting of “00”.
• Only set addresses manually when using different numbers for addresses. Set the R.C. address of each indoor unit using the function setting. (Refer to “Remote con­troller address setting” in "Contents of function setting" on page 35.)
NOTES:
– Do not use the same setting value. – Setting is reflected after the power is turned on again.
Also set the R.C. address for the remote controller. For details, refer to the remote con­troller installation manual.
NOTE: In manual setting, connect up to 15 indoor units in a system.
RC AD
01
RC AD
02
RC AD
03
RC AD
04
Remote controller
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
Example of wiring method
- 30 -
WALL MOUNTED
ASYG07-14KGTA
Page 35
10. Remote controller
10-1. Wireless remote controller
¢
Overview
Signal
transmitter
10°C HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
OUTDOOR UNIT
LOW NOISE button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
MODE button
SENSOR button
FAN button
RESET button
CLOCK ADJUST button
TEST RUN button
ECONOMY button
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
Mode indicator
ENERGY SAVING mode
indicator
LOW NOISE mode
indicator
Turns on when the SENSOR button is operated.
Clock and Timer indicator
SEND indicator
Temperature indicator
Fan speed indicator
Swing indicator
Transmit indicator
To facilitate explanation, the accompanying illustration has been drawn to show all possible indica­tors; in actual operation, however, the display will only show those indicators appropriate to the cur­rent operation.
- 31 -
WALL MOUNTED
ASYG07-14KGTA
Page 36
¢
Specifications
Controller
Unit: mm
Top view
Front view Side view
205
1761
Size (H × W × D) mm 205 × 61 × 17 Weight g 122 (without batteries)
Holder
Unit: mm
48.5
5.5
26.2
69.3
6.5
Front View Side View
Bottom View
Ø 3.5 (Hole)
150
106.8
Hole
3.5
2-R
Size (H × W × D) mm 150 × 69.3 × 26.2 Weight g 27
- 32 -
WALL MOUNTED
ASYG07-14KGTA
Page 37
11. Function settings
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE:
Incorrect settings can cause a product malfunction.
11-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting pro­cedure and the content of each function setting, select appropriate functions for your installation environment.
NOTE: Incorrect settings can cause a product malfunction.
¢
Setting procedure by using wireless remote controller
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Cover for the electrical enclosure on the outdoor unit is in place.
• There is no wiring mistake.
• Piping air tight test and vacuuming have been performed firmly.
• All the necessary wiring work for outdoor unit has been finished.
After reconfirming the items listed above, connect the power supply of the indoor unit.
NOTES:
• Settings will not be changed if invalid numbers or setting values are selected.
• When optional wired remote controller is used, refer to the installation manual enclosed with the remote controller.
Entering function setting mode:
While pressing the POWERFUL button and TEMP. ( ) button simul­taneously, press the RESET button to enter the function setting mode.
Function number
Setting value
Selecting the function number and setting value:
1. Press the TEMP. ( ) ( ) buttons to select the function number. To switch between the left and right digits, press the 10 °C HEAT button.
2. Press the POWERFUL button to proceed to value setting. To re­turn the function number selection, press the POWERFUL button again.
3. Press the TEMP. ( ) ( ) buttons to select the setting value. To switch between the left and right digits, press the 10 °C HEAT but­ton.
4. Press the MODE button once to send the function setting informa­tion. Confirm that you hear the beep sound.
5. Press the START/STOP button to fix the function setting. Confirm that you hear the beep sound.
6. Press the RESET button to end the function setting mode.
7. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
- 33 -
WALL MOUNTED
ASYG07-14KGTA
Page 38
CAUTION
After disconnecting the power supply, wait 30 seconds or more before reconnecting it. The func­tion setting will not become active unless the power supply is disconnected and then reconnect­ed.
NOTES:
• The air conditioner custom code is set to prior to shipment.
• If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner.
- 34 -
WALL MOUNTED
ASYG07-14KGTA
Page 39
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 00 Remote controller address setting
2) 11 Filter sign
3) 30/31 Room temperature control for indoor unit sensor
4) 35/36 Room temperature control for wired remote controller sensor
5) 40 Auto restart
6) 42 Room temperature sensor switching
7) 44 Remote controller custom code
8) 46 External input control
9) 48 Room temperature sensor switching (Aux.)
10) 49 Indoor unit fan control for energy saving for cooling
11) 60 Switching functions for external output terminal
1) Remote controller address setting
NOTE: Because this setting is normally done automatically when 2-wire-type wired remote con-
troller is installed, setting is unnecessary.
Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit.
Function number Setting value Setting description Factory setting
00
00 Unit no. 0 ♦ 01 Unit no. 1 02 Unit no. 2 03 Unit no. 3 04 Unit no. 4 05 Unit no. 5 06 Unit no. 6 07 Unit no. 7 08 Unit no. 8 09 Unit no. 9 10 Unit no. 10 11 Unit no. 11 12 Unit no. 12 13 Unit no. 13 14 Unit no. 14 15 Unit no. 15
NOTE:
When different type of indoor units (such as wall mounted type and cassette type, cas­sette type and duct type, or other combinations) are connected using group control sys­tem, some functions may no longer be available.
- 35 -
WALL MOUNTED
ASYG07-14KGTA
Page 40
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti­mated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard (400 hours) 01 Long interval (1,000 hours) 02 Short interval (200 hours) 03 No indication
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufac­turer’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting ♦ 01 No correction 0.0 °C 02 -0.5 °C
More cooling Less heating
03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C 08 -3.5 °C 09 -4.0 °C 10 +0.5 °C
Less cooling
More heating
11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
- 36 -
WALL MOUNTED
ASYG07-14KGTA
Page 41
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Function number Setting value Setting description
Factory
setting
35
(For cooling)
36
(For heating)
00 No correction ♦ 01 No correction 0.0°C 02 -0.5 °C
More cooling Less heating
03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C 08 -3.5 °C 09 -4.0 °C 10 +0.5 °C
Less cooling
More heating
11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
5) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable ♦ 01 Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or external device.
6) Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number Setting value Setting description Factory setting
42
00 Indoor unit ♦ 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
- 37 -
WALL MOUNTED
ASYG07-14KGTA
Page 42
7) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
44
00 A ♦ 01 B 02 C 03 D
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode 1 ♦ 01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2
9) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01). When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
48
00 Both ♦ 01 Wired remote controller
10) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable 01 Enable 02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the set-
ting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low
speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially activated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy saving function or connecting a network converter. To confirm if the remote controller has this setting, refer to the operating manual of each re­mote controller.
- 38 -
WALL MOUNTED
ASYG07-14KGTA
Page 43
11) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and output”.
Function number Setting value Setting description Factory setting
60
00 Operation status ♦ 09 Error status 10 Indoor unit fan operation status
- 39 -
WALL MOUNTED
ASYG07-14KGTA
Page 44
11-2. Custom code setting for wireless remote controller
To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required.
NOTE:
Air conditioner cannot receive a signal if the air conditioner has not been set for the cus­tom code.
When 2 or more air conditioners are installed in a room, and the remote controller is operating an air conditioner other than the one you wish to set, change the custom code of the remote con­troller to operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not match, the remote controller cannot be used to operate for the air conditioner.
1. Press the START/STOP button until only the clock is displayed on the remote controller display.
2. Press the MODE button for at least 5 seconds to display the cur­rent custom code. (Initially set to
.)
3. Press the TEMP. ( ) ( ) buttons to change the custom code be­tween → → → . Match the code on the display to the air conditioner custom code. (Initially set to .)
4. Press the MODE button again to return to the clock display. The custom code will be changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system re­turns to the original clock indicator. In this case, start again from step 1.
The air conditioner custom code is set to
prior to shipment. To change the custom code,
contact your retailer.
If you do not know the assigned code for the air conditioner, try each of the custom code ( → → → ) until you find the code which operates the air conditioner.
- 40 -
WALL MOUNTED
ASYG07-14KGTA
Page 45
12. Accessories
12-1. Models: ASYG07KGTA, ASYG09KGTA, ASYG12KGTA,
and ASYG14KGTA
Part name Exterior Q’ty Part name Exterior Q’ty
Operating manual 1 Cloth tape 1
Installation manual 1 Tapping screw (Large) 5
Operating manual (CD ROM)
1 Tapping screw (Small) 2
Remote controller 1 Wall hook bracket 1
Battery 2
Remote controller holder
1
- 41 -
WALL MOUNTED
ASYG07-14KGTA
Page 46
13. Optional parts
13-1. Controllers
Exterior Part name Model name Summary
Wired remote
controller
UTY-RNRYZ*
Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wire type: Non-polar 2-wire
Optional communication kit is necessary for installation.
Wired remote
controller
UTY-RLRY
High visibility and easy operation. Room temperature can be accurately controlled using the built-in thermo sensor.
Wire type: Non-polar 2-wire Optional communication kit is
necessary for installation.
NOTE:
Available functions may differ by the remote controller. For details, refer to the operation manual.
13-2. Others
Exterior Part name Model name Summary
External
connect kit
UTY-XWZX
Use to connect with various peripheral devices and air conditioner PCB.
External input
and output PCB
UTY-XCSXZ2
Use to connect with external devices and air conditioner PCB.
Communication
kit
UTY-TWRXZ2
Use to connect Non-polar 2-core wired remote controller.
Wireless LAN
adapter
UTY-TFSXW1
Remotely manage an air conditioning system using mobile devices such as smartphones and tablets.
- 42 -
WALL MOUNTED
ASYG07-14KGTA
Page 47
Part 2. OUTDOOR UNIT
SINGLE TYPE: AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA
Page 48
1. Specifications
Type Inverter heat pump
Model name AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA
Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current A 2.8 3.5 4.8 6.4
Fan
Airflow rate
Cooling
m3/h
1,610 1,610 1,680 1,680
Heating 1,560 1,610 1,580 1,580 Type × Q'ty Propeller fan × 1 Motor output W 21
Sound pressure level *1
Cooling
dB (A)
46 50
Heating 46 48 50
Sound power level
Cooling
dB (A)
61 65
Heating 62 63 66
Heat exchanger type
Dimensions
(H × W × D)
mm
504 × 688 × 249
Fin pitch 1.3
Rows × Stages 1.5 × 24 2 × 24
Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum) Surface treatment Corrosion resistance
Compressor
Type × Q'ty Rotary × 1 Motor output W 900
Refrigerant
Type (Global warming potential) R32 (675)
Charge g 750 850
Refrigerant oil
Type RB68A
Amount
cm
3
340
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0 Dimensions (H × W × D)
Net
mm
542 × 799 × 290
Gross 602 × 940 × 375
Weight
Net
kg
30 31 32
Gross 34 35 36
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8) Method Flare Pre-charge length
m
15 Max. length 20 Max. height difference 15
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Drain hose
Material PP+LLDPE Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.8 (O. D.)
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 44 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 49
2. Dimensions
2-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
Unit: mm
Airflow
184
120
37
179399
Bottom view Side view (Bulb part)
580 109
799 68 29016
33 30
19
330
542
20
Pitch of bolts
for installation
Pitch of bolts for installation
Top view
Side viewSide view
Front view
Drain port Ø42
4-M10 hole
- 45 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 50
3. Installation space
3-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
¢
Space requirement
Provide sufficient installation space for product safety.
CAUTION
Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of
operating performance.
Single outdoor unit installation
When the upper space is open:
Unit: mm
Obstacles at rear only Obstacles at rear and sides
100 or more
250 or more
100 or more
100 or more
Obstacles at front Obstacles at front and rear
600 or more
600 or more
100 or more
When there is an obstruction in the upper space:
Unit: mm
Obstacles at rear and above Obstacles at rear, sides, and above
100 or more
Max. 200
600 or more
250 or more
100 or more
Max. 200
100 or more
600 or more
- 46 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 51
Multiple outdoor unit installation
• Provide at least 250 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following example “When an obstruction in the upper space:”.
When the upper space is open:
Unit: mm
Obstacles at rear only Obstacles at front only
200 or more
250 or more
1,000 or more
250 or more
Obstacles at front and rear
200 or more
1,000 or more
250 or more
When an obstruction in the upper space:
Unit: mm
Obstacles at rear and above.
1,500 or more
200 or more
250 or more
250 or more
Max. 300
1,500 or more
- 47 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 52
Outdoor units installation in multi-row
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
100 or more
200 or more
500 or more
1,000 or more
200 or more
400 or more
1,000 or more
250 or more
2,000 or more
250 or more
1,000 or more
200 or more
250 or more
200 or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• When installing the outdoor unit, be sure to open the front and left side to obtain better opera­tion efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in ex­tremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
- 48 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 53
4. Refrigerant circuit
4-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
Strainer
Strainer
3-way
valve
2-way
valve
Muffler
4-way valve
Expansion valve
Heat exchanger
Heat exchanger
(INDOOR)
(OUTDOOR)
Compressor
Cooling
Heating
Th
D
Th
R
Th
PI
Th
O
Th
HO
: Thermistor (Discharge temperature)
: Thermistor (Outdoor temperature)
: Thermistor (Heat exchanger out temperature)
Th
D
Th
O
Th
HO
: Thermistor (Room temperature)
: Thermistor (Pipe temperature)
Th
R
Th
PI
Muffler
- 49 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 54
5. Wiring diagrams
5-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
- 50 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 55
6. Capacity compensation rate for pipe length and height difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.858 0.868 10 0.929 0.872 0.882
7.5 0.960 0.933 0.876 0.885 5 0.992 0.964 0.937 0.879 0.889 0 1.000 0.972 0.944 0.887 0.896
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.972 0.944 0.887 0.896
-7.5 0.972 0.944 0.887 0.896
-10 0.944 0.887 0.896
-15 0.887 0.896
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.896 0.879 10 0.968 0.890 0.879
7.5 0.994 0.968 0.896 0.879 5 1.000 0.994 0.968 0.896 0.879 0 1.000 0.994 0.968 0.896 0.879
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.989 0.963 0.891 0.875
-7.5 0.987 0.961 0.889 0.873
-10 0.959 0.887 0.871
-15 0.878 0.862
- 51 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 56
7. Additional charge calculation
7-1. Models: AOYG07KGCA and AOYG09KGCA
Refrigerant type R32 Refrigerant amount g 750
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-2. Models: AOYG12KGCA and AOYG14KGCA
Refrigerant type R32 Refrigerant amount g 850
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
- 52 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 57
8. Airflow
8-1. Model: AOYG07KGCA
Cooling
m3/h
1,610
l/s 447
CFM 948
Heating
m3/h
1,560
l/s 433
CFM 918
8-2. Model: AOYG09KGCA
Cooling
m3/h
1,610
l/s 447
CFM 948
Heating
m3/h
1,610
l/s 447
CFM 948
8-3. Model: AOYG12KGCA
Cooling
m
3
/h
1,680
l/s 467
CFM 989
Heating
m
3
/h
1,580
l/s 439
CFM 930
- 53 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 58
8-4. Model: AOYG14KGCA
Cooling
m3/h
1,680
l/s 467
CFM 989
Heating
m3/h
1,580
l/s 439
CFM 930
- 54 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 59
9. Operation noise (sound pressure)
9-1. Noise level curve
¢
Model: AOYG07KGCA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
¢
Model: AOYG09KGCA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 55 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 60
¢
Model: AOYG12KGCA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
¢
Model: AOYG14KGCA
Cooling
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave band sound pressure level, dB: (0 dB=0.0 002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 56 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 61
9-2. Sound level check point
1 m
MicrophoneMicrophone
Rear
A
irflow
Rear view
Side view
NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrat-
ed above.
- 57 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 62
10. Electrical characteristics
Model name AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA Power
supply
Voltage V 230 ~
Frequency Hz 50 Max operating current *1 A 9.0 10.5 Starting current A 2.8 3.5 4.8 6.4
Wiring spec. *2
Circuit breaker current A 15
Power cable
mm
2
1.5
Connection cable *3
mm
2
1.5
Limited wiring length m 21
*1: Maximum current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri­ate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 58 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 63
11. Safety devices
Type of
protection
Protection form
Model
AOYG07KGCA AOYG09KGCA
Circuit protection Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor protection
Terminal protection program
Activate
125±25 °C
Fan motor stop
Reset
100±25 °C
Fan motor restart
Compressor protection
Terminal protection program (Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Type of
protection
Protection form
Model
AOYG12KGCA AOYG14KGCA
Circuit protection Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor protection
Terminal protection program
Activate
125±25 °C
Fan motor stop
Reset
100±25 °C
Fan motor restart
Compressor protection
Terminal protection program (Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
- 59 -
OUTDOOR UNIT
AOYG07-14KGCA
Page 64
12. Accessories
12-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
Part name Exterior Q’ty Part name Exterior Q’ty
Installation manual 1 Drain pipe 1
- 60 -
OUTDOOR UNIT
AOYG07-14KGCA