Thin and slim design is realized by Ø5mm heat
exchanger and high efficiency wind blower.
H282 X W870 X D185
185mm
Low outdoor air temperature correspondence
Big open panel and High density multi path heat
exchanger
Large intake
Open
panel
AOG09LTCN
Ø5mm
Large fan
20mm
AOG12LTCN
AOG14LTCN
Refrigerant
Distributor
4-path
Corresponds to heating operation at -25°C outdoor air temperature
Heating
-25 to 24
°C
Specification improvement that can be operated under
extreme low outdoor temperature (-25°C) without trouble
Improvement of cold-
Structural
improvements
New model
proof specifications
of parts
Expansion of
mechanical space
Freezing
prevention of bace
- (01 - 01) -
WALL MOUNTED TYPE
G09-14LT
AS
Powerful heating at low outdoor temperature
Keeping the high heating capacity at low outdoor temperature.
NEW modelCurrent model *
Heating capacity
(kW)
09 Class
13%up
15%up
3.0
2.6
-15°C-7°C2°C
3.6
3.2
Outdoor temperature
14%up
4.0
3.5
: ASYA09LEC (09 Class)
*
ASYA12LEC (12 Class)
WALL MOUNTED TYPE
G09-14LT
AS
Heating capacity
(kW)
12 Clas s
Heating capacity
(kW)
14 Class
38%up
4.3
4.0
3.5
2.9
-15°C-7°C2°C
Outdoor temperature
6.0
5.4
-15°C-7°C2°C
Outdoor temperature
4.6
6.1
23%up
12%up
4.1
Powerful operation
*Only ava ilable with Wire less RC.
Powerful operation is boosted with the
maximum full power and strong airflow.
Rapid cooling and heating makes the room
comfortable quickly.
Caution
Powerful mode operates for 6 minutes or more, and
stops automatically if reaching set temperature or 20
minutes pass.
Temperature
Normal mode
Powerful operation mode
Setting temp.
Time
- (01 - 02) -
Powerful heating capacity
Quick speed heating & Energy saving at low
ambient !
Quick speed
LE series
LE series
Energy saving
Set
temp.
High
Low
LT series
LT series
)
°C
(
Indoor
temperature
Compressor
Rotated speed
Time
WALL MOUNTED TYPE
G09-14LT
AS
High energy saving
High COP is realized by using Large heat exchanger, DC rotary compressor, and inverter
technology.
14%up!
4.85
5.0
4.0
3.0
2.0
1.0
Heatin g efficie ncy (COP)
0.0
Energy saving control
09
Class
4.27
Human sensor catches movements of people in a room, and operates with lower capacity when the room
is empty. When people come back to the room, it automatically returns to previous operating mode.
Energy saving operation by detecting someone’s movement
7%up!
4.40
12
Class
4.12
3.91
14
Class
LT series
LE series
Human
sensor
WALL MOUNTED TYPE
G09-14LT
AS
10°C HEAT Operation
*Only ava ilable with Wire less RC.
The room temperature can be set to go no lower than 10°C,
thus ensuring that the room does not get too cold when not occupied
Caution)
When the room temperature is higher than 10°C, “ •10°C HEAT” operation does not start. Operation starts and maintains the room
temperature at 10°C when the temperature drops below 10°C.
When “ •10°C HEAT” operation stops, the room set temperature quickly returns to the preset temperature.
“10°C HEAT”
20
°C
10
°C
Outdoor unit low noise
*Only ava ilable with Wire less RC.
When air-conditioner operates in large capacity, operation noise of outdoor unit will be suppressed. In case
of room temperature being close to setting temperature, operation noise might not decrease.
3
dB
Down
Rated
noise level
Economy operation
Example : Cooling operation
Low noise
mode
Button ON
Indoor unit
operation START
Temp.
Set temperature
Nomal operation
Control maxmum current
Economy operation
Time
Shift
setting
temp
Economy operation is energy saving, as the set •
temperature of indoor unit is shifted by 1°C and
the maximum electric value of the outdoor unit is
suppressed.
- (01 - 03) -
WALL MOUNTED TYPE
60
.
C
C
C
.
.
.
C
C
G09-14LT
AS
WIRELESS REMOTE CONTROLLER2.
FEATURES
3 Mode timer setup
(Weekly / Program / Sleep) are possible.
Easy operation.
Easy to change signal code (4 patterns) by button operation.
Built-in timers
Select from Three different timer programs (Weekly / Program / Sleep).
Weekly timer
Weekly timer can be easily set by wireless remote controller.
ON, OFF can be set up to 4 times in 1 day and up to 28 times in 1 week.
Program timer
The program timer operates the on and off timer once within a 24 hour period.
WALL MOUNTED TYPE
G09-14LT
AS
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to
the timer setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 1 °C every hour. The set
temperature can rise up to a maximum of 2 °C.
Timer setting
min
°
Simple function setting
2 °
Heating operation
When the sleep timer is set, the set temperature
automatically drops 1 °C every 30 minutes. The set
temperature can drop to a maximum of 4 °C.
°
°
°
4 °C
min
min
min
Timer setting
Setting of the air conditioner selection function is performed by remote controller.
Switching remote controller signal code
After code change
Mixed-up
I.U. I.U. I.U. I.U.
ABC D
I.U. I.U. I.U. I.U.
ABCD
Code selector switch eliminates unit
•
being wrongly switched.
(Up to 4 codes can be set.)
*I.U.=Indoor unit
- (01 - 04) -
WALL MOUNTED TYPE
G09-14LT
AS
FUNCTIONS
Signal
Transmitter
SENSOR button
WALL MOUNTED TYPE
G09-14LT
AS
10 °C HEAT
button
TEMP.
button
POWERFUL
button
START/STOP
button
MODE button
ECONOMY button
OUTDOOR UNIT
LOW NOISE button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
FAN button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
RESET button
CLOCK ADJUST button
Display panel
MODE Display
TEMPERATURE Display
ENERGY SAVING
MODE Display
Turns O N when the
SENSOR button is operated.
LOW NOISE MODE
Display
SEND Display
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation,
however, the display will only show those indicators appropriate to the current operation.
SPECIFICATION
Transmit Indicator
Display
FAN Speed Display
SWING Display
CLOCK & TIMER
Display
SIZE (H x W x D mm)205 x 61 x 17
WEIGHT ( g )122
ACCESSORYHolder
- (01 - 05) -
SPECIFICATIONS3.
WALL MOUNTED TYPE
G09-14LT
AS
Typ e
Model nameASG09LTCBASG12LTCBASG14LTCB
Power source230V~ 50Hz
Available voltage range198 -264V~ 50H z
Note:
Specifications are based on the following conditions
Cooling:Indoor temperature of 27 °CDB/19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CD B/15 °CWB.and outdoor temperature of 7° CDB/6 °CWB.
Pipe length:5m,Height difference:0m(Outdoor unit-Indoor unit)
The maximum current is the maximum value when the operated within the operation range(temperature).
The protective function might wor k when using it outside the operation range.
AFR : Air Fl ow Rate (m3/min)
TC : Total Capacit y (kW)
IP : Input Pow er (kW)
Indoor temperature
- (01 - 11) -
FAN PERFORMANCE7.
WALL MOUNTED TYPE
G09-14LT
AS
AIR VELOCITY DISTRIBUTION7-1.
MODEL :ASG09LT
2
1
0
-1
-2
012345678
3
2
1.5
1
0
1.5
1.0
1.0
0.5
-1
1.5
-2
1.0
Unit : m/s(m)
0.5
Unit : m/s(m)
0.5
TOP VIEW
Vertic al flap : Up
Horizo ntal flap : Cen ter
(m)
TOP VIEW
Vertic al flap : Up
Horizo ntal flap : Rig ht & Left
Note:
Fan speed : High
Operation mode : FAN
WALL MOUNTED TYPE
G09-14LT
AS
-3
012345678
3
2
Unit : m/s(m)
1.5
1
1.0
0.5
0
012345678
3
2
1.5
1.0
1
0
012345678
0.5
Unit : m/s(m)
(m)
SIDE VIEW
Vertic al flap : Up
Horizo ntal flap : Cen ter
(m)
SIDE VIEW
Vertic al flap : Down
Horizo ntal flap : Cen ter
(m)
- (01 - 12) -
WALL MOUNTED TYPE
0.5
G09-14LT
AS
MODEL :ASG12LT
Note:
Fan speed : High
Operation mode : FAN
WALL MOUNTED TYPE
G09-14LT
AS
2
1
0
1.5
Unit : m/s(m)
1.00.5
-1
-2
012345678
3
2
1.0
Unit : m/s(m)
1.5
1
0.5
0
0.5
-1
TOP VIEW
Vertic al flap : Up
Horizo ntal flap : Cen ter
(m)
TOP VIEW
Vertic al flap : Up
Horizo ntal flap : Rig ht & Left
1.5
-2
-3
012345678
3
2
1
0
012345678
3
1.5
1.0
1.0
Unit : m/s(m)
0.5
Unit : m/s(m)
1.5
2
1.0
1
0
012345678
(m)
SIDE VIEW
Vertic al flap : Up
Horizo ntal flap : Cen ter
(m)
SIDE VIEW
Vertic al flap : Down
Horizo ntal flap : Cen ter
(m)
- (01 - 13) -
WALL MOUNTED TYPE
G09-14LT
AS
MODEL :ASG14LT
Note:
Fan speed : High
Operation mode : FAN
WALL MOUNTED TYPE
G09-14LT
AS
2
1
0
1.5
Unit : m/s(m)
1.00.5
-1
-2
012345678
3
2
1.0
Unit : m/s(m)
1.5
1
0.5
0
0.5
-1
TOP VIEW
Vertic al flap : Up
Horizo ntal flap : Cen ter
(m)
TOP VIEW
Vertic al flap : Up
Horizo ntal flap : Rig ht & Left
1.5
-2
-3
012345678
3
2
1
1.5
1.0
Unit : m/s(m)
1.0
0.5
0
012345678
3
Unit : m/s(m)
1.5
2
1.0
1
0
012345678
0.5
(m)
SIDE VIEW
Vertic al flap : Up
Horizo ntal flap : Cen ter
(m)
SIDE VIEW
Vertic al flap : Down
Horizo ntal flap : Cen ter
(m)
- (01 - 14) -
WALL MOUNTED TYPE
G09-14LT
AS
AIR FLOW7-2.
MODEL :ASG09LT
Cooling
WALL MOUNTED TYPE
G09-14LT
AS
Fan speed
HIGH1300
MED1080
LOW960
QUIET650
Heating
Number of
rotations
(r.p.m.)
Air flow
800 m
3
/h
222 l/s
471 CFM
3
640 m
/h
178 l/s
376 CFM
3
550 m
/h
153 l/s
324 CFM
3
330 m
/h
92 l/s
194 CFM
Fan speed
rotations
HIGH1300
MED1120
LOW960
QUIET650
Number of
(r.p.m.)
Air flow
800 m
3
/h
222 l/s
471 CFM
3
670 m
/h
186 l/s
394 CFM
3
550 m
/h
153 l/s
324CFM
3
330m
/h
92l/s
194
CFM
- (01 - 15) -
WALL MOUNTED TYPE
G09-14LT
AS
MODEL :ASG12LT
Cooling
WALL MOUNTED TYPE
G09-14LT
AS
Fan speed
HIGH1370
MED1120
LOW960
QUIET650
Heating
Number of
rotations
(r.p.m.)
Air flow
850 m
3
/h
236 l/s
500 CFM
3
670 m
/h
186 l/s
394 CFM
3
550 m
/h
153 l/s
324 CFM
3
330 m
/h
92 l/s
194 CFM
Fan speed
rotations
HIGH1370
MED1180
LOW960
QUIET650
Number of
(r.p.m.)
Air flow
850 m
3
/h
236 l/s
500 CFM
3
710 m
/h
197 l/s
418 CFM
3
550 m
/h
153 l/s
324 CFM
3
330 m
/h
92 l/s
194 CFM
- (01 - 16) -
WALL MOUNTED TYPE
G09-14LT
AS
MODEL :ASG14LT
Cooling
WALL MOUNTED TYPE
G09-14LT
AS
Fan speed
HIGH1440
MED1220
LOW980
QUIET740
Heating
Number of
rotations
(r.p.m.)
Air flow
900 m
3
/h
250 l/s
529 CFM
3
740 m
/h
206 l/s
435 CFM
3
570 m
/h
158 l/s
335 CFM
3
390 m
/h
108 l/s
229
CFM
Fan speed
rotations
HIGH1510
MED1220
LOW1030
QUIET790
Number of
(r.p.m.)
Air flow
950 m
3
/h
264 l/s
559 CFM
3
740 m
/h
206 l/s
435 CFM
3
600 m
/h
167 l/s
353 CFM
3
430 m
/h
119 l/s
253
CFM
- (01 - 17) -
OPERATION NOISE8.
WALL MOUNTED TYPE
G09-14LT
AS
NOISE LEVEL CURVE8-1.
MODEL :ASG09LT
Cooling
Cooling
80
80
70
70
60
60
50
50
㪟㫀㪾㪿
40
40
30
30
20
20
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
10
10
㪨㫌㫀㪼㫋
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Heating
80
80
70
70
60
60
50
50
40
40
30
30
20
20
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
10
10
㪨㫌㫀㪼㫋
㪟㫀㪾㪿
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
WALL MOUNTED TYPE
G09-14LT
AS
0
0
63 125 250 500 1,000 2,000 4,000 8,000
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
Octave band center frequency,Hz
MODEL :ASG12LT
Cooling
80
80
70
70
60
60
50
50
㪟㫀㪾㪿
40
40
30
30
20
20
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
10
10
㪨㫌㫀㪼㫋
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
0
63 125 250 500 1,000 2,000 4,000 8,000
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
Octave band center frequency,Hz
Heating
80
80
70
70
60
60
50
50
㪟㫀㪾㪿
40
40
30
30
20
20
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
10
10
㪨㫌㫀㪼㫋
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
0
63 125 250 500 1,000 2,000 4,000 8,000
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
Octave band center frequency,Hz
- (01 - 18) -
0
0
63 125 250 500 1,000 2,000 4,000 8,000
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
Octave band center frequency,Hz
WALL MOUNTED TYPE
G09-14LT
AS
MODEL :ASG14LT
WALL MOUNTED TYPE
G09-14LT
AS
Cooling
80
70
60
50
High
40
30
20
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
10
0
63 125 250 500 1,000 2,000 4,000 8,000
Quiet
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
80
70
60
50
40
30
20
Octave ba nd sound pre ssure level , dB:(0dB= 0.0002 μbar)
10
0
63 125 250 500 1,000 2,000 4,000 8,000
High
Quiet
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- (01 - 19) -
WALL MOUNTED TYPE
G09-14LT
AS
SOUND LEVEL CHECK POINT8-2.
WALL MOUNTED TYPE
G09-14LT
AS
- (01 - 20) -
ELECTRIC CHARACTERISTICS9.
WALL MOUNTED TYPE
G09-14LT
AS
Model nameASG09LTASG12LTASG14LT
Power supply
Max. operating currentA0.4
*1)Wiring Spec.
*1) Wiring Spec.
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
Volt ageV230 ~
FrequencyHz50
Connection cablemm
Limited wiring lengthm21
2
1.5
WALL MOUNTED TYPE
G09-14LT
AS
- (01 - 21) -
SAFETY DEVICES10.
WALL MOUNTED TYPE
G09-14LT
AS
Model
Protection form
ASG09LT
ASG12LT
ASG14LT
Circuit protectionCurrent fuse (PCB)3.15A 250V
Terminal protectionCurrent (thermal) fuse3A 250V
+15
100
°C OFF
Fan motor protectionThermal protector program
95
+5
-10
-10
°C ON
WALL MOUNTED TYPE
G09-14LT
AS
- (01 - 22) -
EXTERNAL INPUT & OUTPUT11.
WALL MOUNTED TYPE
G09-14LT
AS
Connector INPUTOUTPUTREMARKS
CNA01Control inputCNB01-Operation status output
CNB02-Error status output
See external
input/output settings
for details.
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operationInitial starting after turned power onOther than initial starting
Operation modeAuto changeoverMode at previous operation
Set temperature24°CTemperature at previous operation
Air flow modeAUTOMode at previous operation
Up-down air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Left-right air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Circuit diagram example
Indoor
control PC boardCommunication kit
Connector
1
Connected unit
Ex.) Switch
WALL MOUNTED TYPE
G09-14LT
AS
3
*10 m
Signal
Optional parts
* Make the distance from the PC board to the connected unit within 10m.
Contact capacity : 24VDC or more, 10mA or more.
Please use the non-polar relays and switches.
When function setting is "Operation/Stop" mode
Input signal
Indoor unit
ON
OFF
Operation
Stop
Field supply
- (01 - 23) -
WALL MOUNTED TYPE
G09-14LT
AS
When function setting is "Forced stop" mode
WALL MOUNTED TYPE
G09-14LT
AS
Input signal
Command
Indoor unit
Remote controller
Parts (Optional)
Parts name
On
Off
Forced stop
Normal
Operation
Stop
Model name
OnOnOn
Remote control
operation invalidity
External connect kitUTY-XWZXZ5
Communication kitUTY-TWBXF
* For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to
the wire (UTY-XWZXZ5).
Wire (External input) : UTY-XWZXZ5
- (01 - 24) -
WALL MOUNTED TYPE
G09-14LT
AS
EXTERNAL OUTPUT11-2.
OPER ATIO N STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
Indoor
control PC boardCommunication kitConnected unit
Connector
1
2
24V DC
V
*10 m
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Max.24VDC, 10mA to less than 500mA.
Ex.)Relay unit
Signal
Field supplyOptional parts
Ex.)Display
Relay
power
supply
WALL MOUNTED TYPE
G09-14LT
AS
Indoor unit
Output signal
Parts (Optional)
Operation
Stop
ON
OFF
Parts name
Model name
External connect kitUTY-XWZXZ5
Communication kitUTY-TWBXF
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(UTY-XWZXZ5).
Wire (External output) : UTY-XWZXZ5
- (01 - 25) -
WALL MOUNTED TYPE
G09-14LT
AS
ERROR STATUS OUTPUT
An air conditioner error status signal can be output.
Circuit diagram example
Indoor
control PC boardCommunication kitConnected unit
Connector
1
2
24V DC
V
*10 m
Ex.)Relay unit
Signal
Field supplyOptional parts
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Max.24VDC, 10mA to less than 500mA.
Ex.)Display
Relay
power
supply
WALL MOUNTED TYPE
G09-14LT
AS
Error status
Error
Normal
ON
Output signal
OFF
Parts (Optional)
Parts name
Model name
External connect kitUTY-XWZXZ5
Communication kitUTY-TWBXF
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(UTY-XWZXZ5).
Wire (External output) : UTY-XWZXZ5
- (01 - 26) -
FUNCTION SETTING12.
WALL MOUNTED TYPE
G09-14LT
AS
INDOOR UNIT (Setting by remote controller)12-1.
The function settings of the control of the indoor unit can be changed by this procedure according •
to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation •
conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. •
Settings will not be changed if invalid numbers or setting values are selected. •
PREPARATION
Turn on the power •
By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have been conducted
before turning on the power.
Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wireless remote controller)
Perform the “FUNCTION SETTING” according to the installation conditions using the remote
controller.
CAUTION
Confirm whether the wiring work for Outdoor unit has been finished.
Confirm that the cover for the electrical enclosure on the outdoor unit is in place.
This procedure changes to the function settings used to control the indoor unit according to the •
installation conditions. Incorrect settings can cause the indoor unit to malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation •
conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. •
Settings will not be changed if invalid numbers or setting values are selected. •
Refer to the installation manual enclosed with the remote control unit when the wired remote •
control unit (option) is used.
Adjust the signal code of the indoor unit and the signal code of the remote controller. •
WALL MOUNTED TYPE
G09-14LT
AS
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP. (
function setting mode.
Selecting the Function Number and Setting Value
(1) Press the SET TEMP. (
(Press the 10°C HEAT button to switch between the left and right digits.)
(2) Press the POWERFUL button to proceed to setting the value.
(Press the POWERFUL button again to return to the function number selection.)
(3) Press the SET TEMP. (
(Press the 10°C HEAT button to switch between the left and right digits.)
(4) Press the MODE button, in the order listed to confirm the settings.
Please confirm that the beep sounds.
(5) Next, please press START/STOP (
(6) Press the RESET button to cancel the function setting mode.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
After turning off the power, wait 10 seconds or more before turning on it again.
The Function Setting does not become active unless the power is turned off then on again.
/ ) buttons to select the function number.
/ ) buttons to select the setting value.
/ ) button. Please confirm that the beep sounds.
) simultaneously, press the RESET button to enter the
CAUTION
Function number
Setting
value
- (01 - 27) -
WALL MOUNTED TYPE
G09-14LT
AS
FUNCTION DETAILS
WALL MOUNTED TYPE
G09-14LT
AS
Functions
1) Filter sign
2) Cooler room temperature correction
3) Heater room temperature correction
4) Auto restart
Indoor room temperature sensor
5)
switching function
6) Remote controller signal code
7) External input control
Compact wall
mounted
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time
setting for the filter sign display interval in the table below according to the amount of dust or
debris in the room. If you do not wish the filter sign to be displayed, select the setting value for
"No indication".
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Long interval01
Short interval02
No indication03
11
00
The filter sign interval time is different according to Indoor unit type as follows.
Setting description
Standard 400 hours
Long interval1000 hours
Short interval200 hours
Compact Wall
Mounted
2) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below.
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Slightly lower control01
Lower control02
Warmer control03
30
00
3) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below.
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Lower control01
Slightly warmer control02
Warmer control03
31
00
- (01 - 28) -
WALL MOUNTED TYPE
G09-14LT
AS
4) Auto restart
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting descriptionFunction numberSetting value
Yes
No01
40
00
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.
5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller
temperature sensor.
(... Factory setting)
Setting descriptionFunction numberSetting value
No
Yes01
42
00
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller
unit sensor.
WALL MOUNTED TYPE
G09-14LT
AS
6) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(... Factory setting)
Setting descriptionFunction numberSetting value
A
B01
C02
D03
44
00
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(... Factory setting)
Setting descriptionFunction numberSetting value
Operation/Stop mode
(Setting forbidden)01
Forced stop mode02
46
00
- (01 - 29) -
WALL MOUNTED TYPE
G09-14LT
AS
REMOTE CONTROLLER SIGNAL CODE SETTING
Use the following steps to select the signal code of the remote controller. (Note that
the air conditioner cannot receive a signal code if the air conditioner has not been set
for the signal code.)
(1) Press the START/STOP (
remote controller display.
(2) Press the MODE button for at least 5 seconds to display the current signal code
(initially set to
(3) Press the SET TEMP. (
→ → → .
Match the code on the display to the air conditioner signal code.
(4) Press the MODE button again to return to the clock display. The signal code will
be changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original
•
clock display. In this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment.
•
).
/ ) button until only the clock is displayed on the
/ ) buttons to change the signal code between
WALL MOUNTED TYPE
G09-14LT
AS
- (01 - 30) -
OPTIONAL PARTS13.
WALL MOUNTED TYPE
G09-14LT
AS
ExteriorParts nameModel No.Summary
Unit control is performed by
Wired remote
controller
Simple remote
controller
Communication
kit
UTY-RNNYM
UTY-RSNYM
UTY-TWBXF
wired remote controller.
*Optional communication kit is
necessary for the installation.
Unit control is performed by
simple remote controller.
*Optional communication kit is
necessary for the installation.
Use to connect with optional
devices and air conditioner
PC board.
WALL MOUNTED TYPE
G09-14LT
AS
( x 1 )
( x 2 )
External
connect kit
Apple-catechin
filter
Ion
deodorisation
filter
UTY-XWZXZ5
UTR-FA16
UTR-FA16-2
Required when external device
is connected.
*Optional communication kit is
necessary for the installation.
Fine dust, invisible mold
spores, and harmful
microorganisms are absorbed
onto the fi lter by static
electricity, and further growth
is inhibited and deactivated
by the polyphenol ingredient
extracted from apples.
The filter deodorizes by
powerfully decomposing
absorbed odors using the
oxidizing and reducing effects
of ions generated by the ultra
fine-particle ceramic.
Typ eINVERTER HEAT PUMP
Model nameAOG09LTCNAOG12LTCNAOG14LTCN
Power sourse230V ~ 50Hz
Available voltage range198-264V ~ 50Hz
Starting currentA3.34.36.1
Fan
Airflow rate
Cooling
Heating1,700 2,000
Type×Q'tyPropeller fan×1
3
m
/h
Motor outputW50 115
Sound pressure level
Heat exchanger type
Cooling
Heating49 50
Dimensions(H×W×D)
Fin pitch1.31.3
dB(A)
mm
Rows×Stages2 × 242 × 28
Pipe typeCopper
Fin TypeAluminium
Compressor
Refrigerant
Type×Q'tyRotary × 1
Motor outputW8501,000
Typ eR410A
Chargeg1,050 1,200 1,250
Refrigerant oilTypePOE(VG74)
MaterialSteel
Enclosure
Dimensions
(H×W×D)
Weight
Connenction pipe
Net
Gross633 × 945 × 395713 × 945 × 395
Net
Gross4043
Size
MethodFlare
Pre-charge length
Max. length20
Colour
mm
kg
Liquid
GasØ9.52 (Ø3/8 in.)Ø12.70 (Ø1/2 in.)
mm
m
Max. height difference15
Operation range
Cooling
Heating-25 to 24
°C
1,700 2,050
48 50
504 × 896 × 36.4588 × 881 × 36.4
Beige
Approximate colour of MUNSELL 10YR7.5/1.0
540 × 790 × 290620 × 790 × 290
3640
Ø6.35 (Ø1/4 in.)
15
10 to 43
G09-14LT
OUTDOOR UNIT
AO
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
The maximum current is the maximum value when the operated within the operation range (temperature).
The protective function might wor k when using it outside the operation range.
- (02 - 01) -
DIMENSIONS2.
MODEL :AOG09LT
(Unit : mm)
G09-14LT
OUTDOOR UNIT
AO
320
540
102
17.5
25
hole
G09-14LT
Top view
790
68201018
290
OUTDOOR UNIT
AO
20
9
352
Side viewFront view
540
Air flow
1010
(10)
25
ø20 hole
(10)
23
(6x20=120)(6x20=120)
(10)
20
20
55
55
25
23
hole
4-ø11.3mm hole
209
175
110
Bottom view
INSTALLATION PLACE
CAUTION
In the area with heavy snowfall, if the intake and outlet
of outdoor unit is blocked with snow, it might become
difficult to get warm and it is likely to cause of the breakdown. Construct a canopy or baffle board stand.
600 mm or more
100 mm or more
250 mm or more
(Service space)
100 mm or more
200 mm or more
If the space is larger that is stated, the condition will be the same as that are no obstacles.
- (02 - 02) -
MODEL :AOG12LT, AOG14LT
(Unit : mm)
G09-14LT
OUTDOOR UNIT
AO
320
620
102
17.5
G09-14LT
OUTDOOR UNIT
AO
20
Top view
790
62
18
290
18
20
9
Front view
352
Side view
540
Air flow
25
hole
1010
175
110
(10)
25
ø20 hole
(10)
23
(6x20=120)(6x20=120)
(10)
20
55
55
23
20
hole
25
4-ø11.3mm hole
209
INSTALLATION PLACE
100 mm or more
250 mm or more
(Service space)
If the space is larger that is stated, the condition will be the same as that are no obstacles.
600 mm or more
100 mm or more
200 mm or more
Bottom view
- (02 - 03) -
CAUTION
In the area with heavy snowfall, if the intake and outlet
of outdoor unit is blocked with snow, it might become
difficult to get warm and it is likely to cause of the breakdown. Construct a canopy or baffle board stand.