This product is not intended to be used by people (including children) with physical,
sensory or mental disability, or persons lacking experience or knowledge unless they
have been given by the through a person responsible for their safety, supervision or
instruction concerning the use of the device.
Do not touch the aluminum fi ns of heat exchanger built-in the indoor or outdoor unit to
avoid personal injury when you install or maintain the unit.
Do not place any other electrical products or household belongings under indoor unit
or outdoor unit. Dripping condensation from the unit might get them wet, and may
cause damage or malfunction of your property.
• Be careful not to scratch the air conditioner when handling it.
• After installation, explain correct operation to the customer, using the operating manual.
6. PUMP DOWN ............................................................................................................ 6
Notes:
• This manual describes how to install the outdoor unit only. To install the indoor unit,
refer to the installation manual included with the indoor unit.
• Be sure to read this manual thoroughly before the installation.
• Hand this manual, together with the operating manual, to the customer. Request the
customer to keep them on hand for future use, such as for relocating or repairing the
unit.
• After the installation, explain correct operation to the customer by using the operating
manual.
1. SAFETY PRECAUTIONS
The warnings and precautions indicated in this manual contain important information
pertaining to your safety. Be sure to observe them.
WARNING
CAUTION
For the air conditioner to operate satisfactorily, install it as outlined in this installation
manual.
The appliance shall be installed in accordance with national wiring regulations.
Never touch electrical components immediately after the power supply has been
turned off. Electrical shock may occur. After turning off the power, always wait
5 minutes or more before touching electrical components.
Do not turn ON the power until all work has been completed. Turning ON the power
before the work is completed can cause serious accidents such as electric shock or
fi re.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a fl ame, it produces a toxic gas.
Connect the indoor unit and outdoor unit with the air conditioner piping and cable
available standard parts.
This installation manual describes the correct connections using the installation set
available from our standard parts.
Do not use an extension cable.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the
installation.
There is not extra refrigerant in the outdoor unit for air purging.
If the supply cable is damaged, it must be replaced by the manufacture, its service
agent or similarly qualifi ed persons in order to avoid a hazard.
When installing pipes shorter than 5 m, sound of the outdoor unit will be transferred to
the indoor unit, which will cause large operating sound or some abnormal sound.
This unit must be installed by qualifi ed personnel with a capacity certifi cate for handling
refrigerant fl uids. Refer to regulation and laws in use on installation place.
The unit must be correctly grounded and the supply line must be equipped with a
differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
This unit contains no user-serviceable parts. Always consult authorized service
personnel to repairs.
Children should be monitored to ensure they do not play with the device.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
This mark indicates procedures which, if improperly
performed, might possibly result in personal harm to the user,
or damage to property.
WARNING
CAUTION
2. ABOUT THE UNIT
2.1. Precautions for using R410A refrigerant
The basic installation work procedures are the same as conventional refrigerant (R22)
models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant
(R22) models, some of the piping and installation and service tools are special. (See
the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant
R410A model, always replace the conventional piping and flare nuts with the R410A piping
and fl are nuts.
Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with conventional refrigerant (R22) and for safety. Therefore,
check beforehand. [The charging port thread diameter for R410A is 1/2 inch.]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by
pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of
the gas and liquid phases. And always charge from the liquid phase where refrigerant
composition is stable.
2.2. Special tools for R410A
Tool nameContents of change
Pressure is high and cannot be measured with a conven-
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detectorSpecial gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or
discolored portion (especially on the interior surface). Otherwise, the expansion value or
capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in table below. Never use
copper pipes thinner than 0.8mm even when it is available on the market.
Thicknesses of Annealed Copper Pipes
Pipe outside diameterThickness
6.35 mm (1/4 in.)0.80 mm
9.52 mm (3/8 in.)0.80 mm
12.70 mm (1/2 in.)0.80 mm
15.88 mm (5/8 in.)1.00 mm
19.05 mm (3/4 in.)1.20 mm
Do not use the existing (for R22) piping and fl are nuts.
If the existing materials are used, the pressure inside the refrigerant cycle will rise and
cause failure, injury, etc. (Use the special R410A materials.)
When installing and relocating the air conditioner, do not mix gases other than
the specifi ed refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to
an abnormally high value and cause failure, injury, etc.
tional (R22) gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals -0.1 to 5.3 MPa
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
To increase pressure resistance, the hose material and base
size were changed.
A conventional vacuum pump can be used by installing a
vacuum pump adapter.
WARNING
En-1
2.3. Power
2.6. Limitation of refrigerant piping length
WARNING
Always use a special branch circuit and install a special receptacle to supply power to
the room air conditioner.
Use a circuit breaker and receptacle matched to the capacity of the air conditioner.
Do not extend the power cable.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Install a leakage circuit breaker in accordance with the related laws and regulations
and electric company standards.
The circuit breaker is installed in the permanent wiring. Always use a circuit that can
trip all the poles of the wiring and has an isolation distance of at least 3 mm between
the contacts of each pole.
CAUTION
The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances. When the current contracted capacity is insuffi cient,
change the contracted capacity.
When the voltage is low and the air conditioner is diffi cult to start, contact the power
company the voltage raised.
2.4. Electric requirement
CAUTION
Be sure to install a breaker of the specifi ed capacity.
Regulation of cables and breaker differs from each locality, refer in accordance with
local rules.
Voltage rating1 ø 230 V (50 Hz)
Operating range198-264 V
1.5
*1
TypeRemarks
Type 60245
IEC66
Type 60245
IEC57
2cable + Earth
(Ground), 1ø230V
3cable + Earth
(Ground), 1ø230V
*2
*3
CableCable size [mm2]
Power supply cable4.0
Connection cable
*1
Selected sample: Select the correct cable type and size according to the country or
region’s regulations.
Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the
wire diameter when the wire length is long.
BreakerSpecifi cation
Circuit breaker (over current)Current : 25 (A)
Earth leakage breakerLeakage current : 30mA 0.1sec or less
*2
Select the appropriate breaker of the described specification according to the national
or regional standards.
*3
Select the breaker that enough load current can pass through it.
• Before starting work check that power is not being supplied to all poles of the indoor
unit and outdoor unit.
• Install all electrical works in accordance to the national standard.
• Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the
units. (Both indoor unit and outdoor unit)
• Install the circuit breaker nearby the units.
2.5. Accessories
Name and ShapeQ’tyApplication
Installation Manual
This manual
CAUTION
The total maximum pipe lengths and height difference of this product are shown in the
table.
If the units are further apart than this, correct operation cannot be guaranteed.
Pipe length
MAX.MIN.
25 m5 m15 m
Maximum height
(between indoor and outdoor)
2.7. Additional charge
Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.
Pipe length15 m20 m25 m
Additional amountNone100 g200 g
CAUTION
When adding refrigerant, add the refrigerant from the charging port at the completion
of work.
The maximum length of the piping is 25 m. The maximum height difference of the piping
is 15 m, if the units are further apart than these, correct operation cannot be guaranteed.
Between 15 m and 25 m, when using a connection pipe other than that in the table, charge
additional refrigerant with 20 g/1 m as the criteria.
2.8. Selecting pipe sizes
The diameters of the connection pipes differ according to the capacity of the indoor unit.
Refer to the following table for the proper diameters of the connection pipes between the
indoor and outdoor units.
Capacity of indoor unit
12ø9.52 (0.8)
14, 18
Gas pipe size
(thickness) [mm]
ø12.7 (0.8)
Liquid pipe size
(thickness) [mm]
ø6.35 (0.8)
ø6.35 (0.8)
CAUTION
Operation cannot be guaranteed if the correct combination of pipes, valves, etc., is not
used to connect the indoor and outdoor units.
2.9. Heat insulation around connection pipes
requirements
CAUTION
Install heat insulation around both the gas and liquid pipes.
Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70%, install heat insulation around the refrigerant piping. If the
expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if
the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specifi ed, condensation may form on
the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less
(at 20 °C).
Connect the connection pipes according to “5.3. Connecting the piping” in this installation
manual.
1
Drain pipe
Adapter assy
12.7mm → 9.52mm
For outdoor unit drain piping work
1
For use when connecting
[ 12 type only ]
1
En-2
3. SELECTING THE MOUNTING POSITION
With considering written conditions below, select an appropriate installing location in
consultation with the customer.
WARNING
Securely install the outdoor unit at a location that can withstand the weight of the unit.
Otherwise, the outdoor unit may fall and cause injury.
Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes
or strong winds. Improper installation can cause the unit to topple or fall, or other
accidents.
CAUTION
Do not install the outdoor unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts,
causing the parts to fail or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed oil or steam. It will
deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
• Area containing equipment that generates electromagnetic interference. It will cause
the control system to malfunction, preventing the unit from operating normally.
• Area that can cause combustible gas to leak, contains suspended carbon fi bers or fl ammable dust, or volatile infl ammables such as paint thinner or gasoline. If gas leaks
and settles around the unit, it can cause a fi re.
• Area that has heat sources, vapors, or the risk of the leakage of fl ammable gas in the
vicinity.
• Area where small animals may live. It may cause failure, smoke or fi re if small ani-
mals enter and touch internal electrical parts.
• Area where animals may urinate on the unit or ammonia may be generated.
(1) If possible, do not install the unit where it will be exposed to direct sunlight.
(If necessary, Install a blind that does not interfere with the air fl ow.)
(2) Do not install the unit where a strong wind blows or where it is very dusty.
(3) Do not install the unit where people pass.
(4) Take you neighbors into consideration so that they are not disturbed by air blowing
into their windows or by noise.
(5) Provide the space shown in fi gure so that the air fl ow is not blocked. Also for ef-
fi cient operation, leave open three of the four directions front, rear, and both sides.
(6) Install the unit where keep away more than 3m from the antenna of TV set and
Radio.
(7) Outdoor unit should be set to a place where both drainage and itself will not be af-
fected when heating.
• When there are obstacles at the back side.
600mm or more
100-300 mm*
AIR
250 mm or more
(Service space)
* If the space is larger than that is stated, the condition will be the same as that there are
no obstacles.
• When there are obstacles at the back side with the installation of more than one unit.
300 mm
or more
AIR
250 mm
or more
250 mm
or more
300 mm
or more
4. INSTALLATION DIAGRAM
INDOOR UNIT
AIR
• When there are obstacles at the back and front sides.
AIR
600 mm
or more
• When there are obstacles at the back, side(s), and top.
100 mm
or more
100 mm
or more
[OUTDOOR UNIT]
Bolt
Nut
Outdoor unit
bottom
5 cm or over
• Fix securely with bolts on a solid
block. (Use 4 sets of commercially
Block
available M10 bolt, nut and washer.)
• Do not directly install it on the ground,
otherwise it will cause failure.
54 cm
Power
supply
cable
32 cm
En-3
Drain hose
CAUTION
When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may
freeze in extreme cold weather. (Reverse cycle model only)
In the area with heavy snowfall, if the intake and outlet of outdoor units blocked with
snow, it might become diffi cult to get warm and it is likely to cause of the breakdown.
Please construct a canopy and a pedestal or place the unit on a high stand (local
confi gured).
Do not tighten the terminal screws too much, otherwise, the screws may break.(5)
See the table below for the terminal screw tightening torques.(6)
Screw with special washer
Wire
Strip : 10mm
Crimp-type terminal
Crimp-type
terminal
Sleeve
Screw with
special washer
Crimp-type
terminal
5. INSTALLATION
5.1.
Outdoor unit installation
Connector cover removal
Remove the tapping screw.
Installing the connector cover
Tapping screw
Front hooks
Rear hooks
Connector cover
(1) After inserting the four hooks, then
slide the cover.
(2) Tighten the tapping screw.
WARNING
Install the unit where it will not be tilted by more than 5°.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
5.2.
Outdoor unit wiring
1. CONNECTION DIAGRAMS
3
Control line
Power line
Power supply
(GROUND)
N
L
3
EARTH
22
1
EARTH (GROUND)
Indoor unit
side terminal
2. CABLE PREPARATION
• When stripping off the coating of a lead wire, always use a special tool such as a wire
stripper. If there is no special tool available, carefully strip the coating with a knife etc.
Keep the earth (ground) wire longer than the other wires.
Earth (Ground)
wire
Earth (Ground) line
40 mm
45 mm or more
1
EARTH
(GROUND)
Outdoor unit
side terminal
Connection cable
and power cable
Terminal blocks
Wire
Tightening torque [N·m (kgf·cm)]
M4 screw1.2 to 1.8 (12 to 18)
3. OUTDOOR UNIT
(1) Remove the outdoor unit connector cover.
(2) Bend the end of the cable as shown in the fi gure.
(3) Connect the end of the connection cable fully into the terminal block.
(4) Fasten the sheath with a cable clamp.
(5) Install the connector cover.
Control box
Cable clamp
Connection cable
Earth (Ground)
screw
Earth (Ground)
screw
Connection cable
Cable clamp
Power supply cable
Connection cable wiring
Run the connection cable to the rear of the outdoor unit within the A range of the arrows
shown in the figure.
(The connector cover becomes difficult to install.)
10 cm 5 cm
Connection cable
CAUTION
Before starting work, check that power is not being supplied to the indoor unit and
outdoor unit.
Match the terminal block numbers and connection cable colors with those of the indoor
unit.
Erroneous wiring may cause burning of the electric parts.
Connect the connection cable fi rmly to the terminal block. Imperfect installation may
cause a fi re.
Always fasten the outside covering of the connection cable with the cord clamp. (If the
insulator is chafed, electric leakage may occur.)
Securely earth (ground) the power cable.
Do not use the earth (ground) screw for an external connector. Only use for interconnection between two units.
How to connect wiring to the terminal
Caution when wiring cable
Use crimp-type terminals with insulating sleeves as shown in the fi gure to (1)
connect to the terminal block.
Securely clamp the crimp-type terminals to the wires using an appropriate tool (2)
so that the wires do not come loose.
Use the specifi ed wires, connect them securely, and fasten them so that there is (3)
no stress placed on the terminals.
Use an appropriate screwdriver to tighten the terminal screws. Do not use a (4)
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
En-4
5.3. Connecting the piping
BENDING PIPES
(1) When bending the pipe, be careful not to crush it.
(2) To prevent breaking of the pipe, avoid sharp
bends.
Bend the pipe with a radius of curvature of
150 mm or over.
(3) If the copper pipe is bend the pipe or pulled
to often, it will become stiff. Do not bend the
pipes more than three times at one place.
FLARING
(1) Cut the connection pipe to the necessary
length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will
not enter the pipe and remove the burrs.
(3) Insert the flare nut onto the pipe and flare
the pipe with a fl aring tool.
Insert the flare nut (always use the flare nut
attached to the indoor and outdoor units respectively) onto the pipe and perform the fl are
processing with a fl are tool.
Use the special R410A fl are tool, or the conventional (for R22) fl are tool.
When using the conventional fl are tool, always use an allowance adjustment gauge and
secure the A dimension shown in Table 2.
ADAPTER
Connection ports of outdoor unit
• When using the ADAPTER, be careful not to overtighten the nut, or the smaller pipe
may be damaged.
• Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit
where the fl are nut comes in.
• Use appropriate wrenches to avoid damaging the connection thread by overtightening
the fl are nut.
• Apply wrenches on both of fl are nut (local part), and ADAPTER to tighten them.
12 type only
Adapter tightening torque
Adapter type [mm]Tightening torque
ø12.7 → ø9.5249 to 61 [N·m] (490 to 610 kgf·cm)
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation set or pro-
cured at the site) to the wall pipe.
(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the fl are surface and tightening the nut hand tight,
tighten the nut to the specifi ed tightening torque with a torque wrench. (Table 1)
Fasten a fl are nut with a torque wrench as instructed in this manual. If fastened too
tight, the fl are nut may be broken after a long period of time and cause a leakage of
refrigerant.
During installation, make sure that the refrigerant pipe is attached fi rmly before you run
the compressor. Do not operate the compressor under the condition of refrigerant piping
not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
Check if [L] is fl ared uniformly and
is not cracked or scratched.
Die
A
Pipe
To prevent gas leakage, coat the fl are
surface with refrigerator oil.
Dimension A [mm]
Flare tool for R410A, clutch type
0 to 0.5
5.4. Air purge
Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the outdoor unit at the factory.
Close the high pressure side valve of the gauge manifold fully and do not operate it during
the following work.
CAUTION
Refrigerant must not be discharged into atmosphere.
After connecting the piping, check the joints for gas leakage with gas leak detector.
Gas leak checks are performed using either vacuum or nitrogen gas, so select the proper
one depending on the situation.
Checking gas leaks with vacuum:
(1) Check if the piping connections are secure.
(2) Remove the cap of 3-way valve, and connect the gauge manifold charge hoses to the
charging port of the 3-way valve.
(3) Open the valve of the gauge manifold fully.
(4) Operate the vacuum pump and start pump down.
(5) Check that the compound pressure gauge reads -0.1 MPa (76 cmHg), operate the
vacuum pump for at least 1 hour.
(6) At the end of pump down, close the valve of the gauge manifold fully and stop the
vacuum pump.
(It checks that leave as it is for about 10 minutes, and a needle does not return.)
(7) Disconnect the charge hose from the 3-way valve charging port.
(8) Remove the blank caps, and fully open the spindles of the 2-way and 3-way valves
with a hexagon wrench.
[torque: 6 to 7 N·m (60 to 70 kgf·cm)].
(9) Tighten the blank caps and charging port cap of the 2-way valve and 3-way valve to
the specifi ed torque.
Checking gas leaks with nitrogen gas:
(1) Check if the piping connections are secure.
(2) Remove the cap of 3-way valve, and connect the gauge manifold charge hoses to
the charging port of the 3-way valve.
(3) Pressurize with nitrogen gas using the 3-way valve charging port.
(4) Do not pressurize up to the specifi ed pressure all at once but do so gradually.
Increase the pressure up to 0.5 MPa (5 kgf/cm
1
and then check for any decrease in pressure.
Increase the pressure up to 1.5 MPa (15 kgf/cm
2
and then check for any decrease in pressure.
Increase the pressure up to the specifi ed pressure (the pressure designed for the
3
product) and then make a note of it.
(5) Let it sit at the specifi ed pressure and if there is no decrease in pressure then it is
satisfactory. If a pressure decrease is confi rmed, there is a leak, so it is necessary to
specify the leak location and make minor adjustments.
(6) Discharge the nitrogen gas and starting removing the gas with a vacuum pump.
(7) Open the valve of the gauge manifold fully.
(8) Operate the vacuum pump and start pump down.
(9) Check that the compound pressure gauge reads -0.1 MPa (76 cmHg), operate the
vacuum pump for at least 1 hour.
(10) At the end of pump down, close the valve of the gauge manifold fully and stop the
vacuum pump.
(11) Disconnect the charge hose from the 3-way valve charging port.
(12) Remove the blank caps, and fully open the spindles of the 2-way and 3-way valves
with a hexagon wrench.
[torque: 6 to 7 N·m (60 to 70 kgf·cm)].
(13) Tighten the blank caps and charging port cap of the 2-way valve and 3-way valve to
the specifi ed torque.
Compound pressure gauge
2
way valve
3-way valve
-
Flare nut
Valve stem
Blank cap
port
Charging
Charging
port cap
6.35 mm (1/4 in)20 to 25 N·m (200 to 250 kgf·cm)
9.52 mm (3/8 in.) 20 to 25 N·m (200 to 250 kgf·cm)
Blank cap
12.70 mm (1/2 in.)28 to 32 N·m (280 to 320 kgf·cm)
15.88 mm (5/8 in.)30 to 35 N·m (300 to 350 kgf·cm)
19.05 mm (3/4 in.)35 to 40 N·m (350 to 400 kgf·cm)
Charging port cap12.5 to 16 N·m (125 to 160 kgf·cm)
2
), let it sit for about fi ve minutes
2
), let it sit for about fi ve minutes
Gauge manifold
-0.1 MPa
(-76 cmHg
-1 bar)
Low
pressure
side valve
Charge hose
Tightening torque
Pressure gauge
Vacuum pump
High
pressure
side valve
(closed)
Charge
hose
En-5
5.5. Test run
1. Make a TEST RUN in accordance with installation instruction sheet for the
indoor unit.
CHECK ITEMS
INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?
OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
• Do not operate the air conditioner in the test running state for a long time.
• For the operation method, refer to the operating manual and perform operation check.
6. PUMP DOWN
6.1. Pump down
PUMP DOWN OPERATION (FORCED COOLING OPERATION)
To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal,
recover refrigerant by doing the cooling operation or forced cooling operation according
to the following procedure. (When the cooling operation cannot start in winter, and so on,
start the forced cooling operation.).
(1) Do the air purging of the charge hose by connecting the charging hose of gauge mani-
fold to the charging port of 3 way valve and opening the low-pressure valve slightly.
(2) Close the valve stem of 2 way valve completely.
(3) Start the cooling operation or following forced cooling operation. Keep on pressing the
MANUAL AUTO button of the indoor unit for more than 10 seconds. The operation in-
dicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on
pressing for more than 10 seconds.)
(4) Close the valve stem of 3 way valve when the reading on the compound pressure
gage becomes 0.05~0 Mpa (0.5~0 kg/cm
(5) Stop the operation.
• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side. (It
is not necessary to press on keeping for more than 10 seconds.)
2
).
CAUTION
During the pump-down operation, make sure that the compressor is turned off before
you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2 way or
3 way valve open. This may cause abnormal pressure in the refrigeration cycle that
leads to breakage and even injury.
En-6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.