Fujitsu AOU9RLS2H, AOU12RLS2H, AOU15RLS2H, ASU12RLS2, ASU15RLS2 Design & Technical Manual

Page 1
AIR CONDITIONER
Wall Mounted type
for Extra Cold Climate Area
INDOOR
OUTDOOR
ASU9RLS2 ASU12RLS2 ASU15RLS2
DESIGN & TECHNICAL MANUAL
Page 2
1. INDOOR UNIT
WALL MOUNTED TYPE :
ASU9RLS2 ASU12RLS2 ASU15RLS2
DTR_AS071E_01
2012.12.14
Page 3
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
CONTENTS
1. INDOOR UNIT
1. FEATURES
.............................................................................................................. 01 - 01
2. WIRELESS REMOTE CONTROLLER
............................................... 01 - 04
3. SPECIFICATIONS
.............................................................................................. 01 - 06
4. DIMENSIONS
........................................................................................................ 01 - 07
5. WIRING DIAGRAMS
........................................................................................ 01 - 09
6. CAPACITY TABLE
............................................................................................ 01 - 10
6-1. COOLING CAPACITY
...................................................................................... 01 - 10
6-2. HEATING CAPACITY
....................................................................................... 01 - 12
7. FAN PERFORMANCE
.................................................................................... 01 - 14
7-1. AIR VELOCITY DISTRIBUTION
..................................................................... 01 - 14
7-2. AIRFLOW
........................................................................................................... 01 - 16
8. OPERATION NOISE
......................................................................................... 01 - 18
8-1. NOISE LEVEL CURVE
.................................................................................... 01 - 18
8-2. SOUND LEVEL CHECK POINT
..................................................................... 01 - 19
9. ELECTRIC CHARACTERISTICS
........................................................... 01 - 20
10. SAFETY DEVICES
............................................................................................ 01 - 21
11. EXTERNAL INPUT & OUTPUT
............................................................... 01 - 22
11-1. EXTERNAL INPUT
........................................................................................... 01 - 22
11-2. EXTERNAL OUTPUT
....................................................................................... 01 - 24
12. FUNCTION SETTINGS
.................................................................................. 01 - 26
12-1. INDOOR UNIT (Setting by remote controller)
........................................... 01 - 26
13. OPTIONAL PARTS
........................................................................................... 01 - 30
13-1. CONTROLLER
.................................................................................................. 01 - 30
13-2. OTHERS
............................................................................................................. 01 - 30
Page 4
- (01 - 01) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
FEATURES1.
MODEL
ASU9RLS2 / AOU9RLS2H ASU12RLS2 / AOU12RLS2H ASU15RLS2 / AOU15RLS2H
FEATURES
Energy efciency
z
Extra Cold Climate Area Model
ASU9RLS2 ASU12RLS2 ASU15RLS2
Seasonal Energy Efciency Ratio (SEER) 27. 2 25.0 21.5 Heating Seasonal Performance Factor (HSPF) 8.8 9.3 10.3
MEASUREMENT CONDITIONS ANSI/ASHRAE STANDARD 37-1988
Thin & Slim design
z
Low outdoor air temperature correspondence
z
Corresponds to heating operation at -15°F (-26°C) outdoor air temperature (AOU9, 12, 15RLS2H)
Heating
-15 to 75°F
(-26 to 24°C)
Large fan
Open panel
Distributor 4-path
Refrigerant
Large intake
Big open panel and High density multi path heat
exchanger
Thin and slim design is realized by Ø3/16in. (Ø5mm) heat exchanger and high efficiency wind blower.
H11-3/32 × W34-1/4 × D7-9/32 in. (H282 × W870 × D185 mm)
7-9/32 in. (185mm)
Ø3/16in. (Ø5mm)
25/32 in. (20mm)
Specication improvement to allow operation
under extremely low outdoor temperature -15°F (-26°C) without trouble
Extra cold climate area model
Freezing
prevention of base
Structural
improvements
Improvement of cold­proof specications of
parts
32°F (0°C)
37°F (3°C)
OF F
ON
Heater operation
Outdoor temperature
Tim e
Freezing prevention
15 0 W He a te r
Base
Many drain holes
Page 5
- (01 - 02) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
Powerful operation
z
*Only ava ilable with W ireless RC.
20 minutes continuous operation by maximum airow and maximum compressor speed is possible. Rapid cooling and heating makes the room comfortable quickly.
Powerful
Setting temp.
Normal mode
Time
Temperature
Energy saving Program
z
Human sensor catches movements of people in a room, and operates with lower capacity when the room is empty. When people come back to the room, it automatically returns to previous operating mode.
Energy saving operation by detecting someone’s movement
Human sensor
MIN. HEAT Operation
z
*Only ava ilable with W ireless RC.
The room temperature can be set to go no lower than 50°F (10°C), thus ensuring that the room does not get too cold when not occupied
Caution)
When the room temperature is higher than 50°F (10°C), “ MIN. HE AT” operation will not start. Operation star ts and maintains the room temperature at 50°F (10°C) when the temperature drops below 50°F (10°C).
When “ MIN. HE AT” operation stops, the room set temperature quickly returns to the preset temperature.
Outdoor unit low noise
z
*Only ava ilable with W ireless RC.
When air-conditioner operates in large capacity, operation noise of outdoor unit will be suppressed. In case of room temperature being close to setting temperature, operation noise might not decrease.
Rated
noise level
3
dB
Down
Low noise
mode
Economy operation
z
Example : Cooling operation
Temp.
Economy operation
Shift
setting
temp
Control maximum current
Normal operation
Time
Set temperature
“MIN. HEAT”
Button ON
Indoor unit operation START
68
°F
(20°C)
50
°F
(10°C)
Economy operation is energy saving, as the set temperature of indoor unit is shifted by 2°F (1°C) and the maximum electric value of the outdoor unit is suppressed.
Page 6
- (01 - 03) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
3 Mode timer (Weekly/Program/Sleep)
z
*Only ava ilable with W ireless RC.
Weekly timer can be easily set by wireless remote controller. ON, OFF can be set up to 4 times in 1 day and up to 28 times in 1 week. For other modes, program timer and sleep timer can be also selected by one push.
Low outdoor air temperature correspondence
z
-15°F (-26°C)
Cooling
75°F (24°C)
Heating
115°F (46°C)
14°F (-10°C)
122 (50)
104 (40)
86 (30)
68 (20)
50 (10)
32 (0)
14 (-10)
-4 (-20)
-15 (-26)
Page 7
- (01 - 04) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
WIRELESS REMOTE CONTROLLER2.
FEATURES
3 Mode timer setup available (Weekly / Program / Sleep).
¾
Easy operation.
¾
Easy to change signal code (max. 4 units) by button operation.
¾
Simple function setting
z
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
z
Select from Three different timer programs (Weekly / Program / Sleep).
Weekly timer
z
Weekly timer can be easily set by wireless remote controller. ON, OFF can be set up to 4 times in 1 day and up to 28 times in 1 week.
Program timer
z
The program timer operates the on and off timer once within a 24 hour period.
Sleep timer
z
The sleep timer function automatically corrects the temperature thermostat setting according to the timer setting to prevent excessive cooling and heating while sleeping.
60min.
2°F (1°C)
4°F (2°C)
Timer setting
30min.
60min.
90min.
4°F
(2°C)
6°F
(3°C)
8°F
(4°C)
Timer setting
2°F
(1°C)
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 2°F (1°C) every hour. The set temperature can rise up to a maximum of 4°F (2°C).
Heating operation
When the sleep timer is set, the set temperature automatically drops 2°F (1°C) every 30 minutes. The set temperature can drop to a maximum of 8°F (4°C).
Switching remote controller signal code
z
A B C D
A B
C
D
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
Code selector switch eliminates unit
• being wrongly switched. (Up to 4 codes can be set.)
*I.U.=Indoor unit
To change the temperature unit
z
Easy to change the temperature unit (°F ↔ °C) by button operation.
Page 8
- (01 - 05) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
FUNCTIONS
Signal
Transmitter
MIN. HEAT
button
TEMP.
button
POWERFUL
button
START/STOP
button
MODE button
SENSOR button
ECONOMY button
OUTDOOR UNIT
LOW NOISE button
SWING button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
SET button
WEEKLY button
ON/OFF button
SLEEP button
FAN button
RESET button
CLOCK ADJUST button
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current operation.
MODE Display
ENERGY SAVING
PROGRAM Display
LOW NOISE MODE
Display
Turns ON when the
¾
SENSOR button is operated.
CLOCK & TIMER Display
SEND Display
TEMPERATURE Display
Transmit Indicator Display
FAN Speed Display
SWING Display
SPECIFICATION
DIMENSIONS [H × W × D]: in. (mm) 8-1/16 (205) × 2-13/32 (61) × 21/32 (17)
WEIGHT oz. (g) 4.3 (122)
ACCESSORY Holder
Page 9
- (01 - 06) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
SPECIFICATIONS3.
Note :
Specications are based on the following conditions. Cooling : Indoor temperature of 80°F (26.67°C) DB / 67°F (19.44°C) WB, and outdoor temperature of 95°F (35°C) DB / 75°F (23.9°C) WB. Heating : Indoor temperature of 70°F (21.11°C) DB / 59°F (15°C) WB, and outdoor temperature of 47°F (8.33°C) DB / 43°F (6.11°C) WB. Pipe length : 24ft.7in (7.5m), Height difference:0 m. (Outdoor unit-Indoor unit) The protective function might work when using it outside the operation range. *: The maxi mum curr ent is the ma ximum value when op erated wi thin the o peratio n range.
Typ e
WALL MOU NTED
INVERT ER HEAT PUM P
Model na me ASU9RLS2 ASU12RLS2 ASU15RLS2
Power sour ce 208 / 230V ~ 6 0Hz
Available b oltage range 187 - 253V ~ 60H z
Capacity
Cooling
Rated
kW 2.64 3.52 4.25
Btu/h 9000 12000 1450 0
Min - Max
kW 0.90 - 3.6 0 0.90 - 4.0 0 0.90 - 5.4 0
Btu/h 3100 - 12000 3100 - 13600 3100 - 18400
Heating
Rated
kW 3.52 4.69 5.28
Btu/h 12000 16000 18000
Min - Max
kW 0.90 - 6. 45 0.90 - 6. 50 0.9 0 - 7.00
Btu/h 3100 - 2200 0 3100 - 22100 3100 - 2390 0
Input powe r
Cooling
Rated
kW
0.56 0.87 1. 21
Max 0.90 1.0 8 1.93
Heating
Rated 0.80 1.2 0 1.35
Max 1.99 2.00 2.26
Current
Cooling
Rated A
2.7 4.0 5.5
Heating 3.7 5.5 6.1
EER Cooling
kW/kW 4.71 4.05 3. 51
Btu/hW 16 .1 13. 8 12.0
COP Heating
kW/kW 4.40 3.91 3. 91
Btu/hW 15.0 13 .3 13.3
SEER Cooling Btu/hW 27.2 25.0 21. 5
HSPF Heating Btu/hW 8.8 9.3 10.3
Power fact or
Cooling
%
90 95 96
Heating 94 95 96
Moistur e removal pints/ h (l/h) 2.7 (1.3) 3.8 (1.8) 4.4 (2.1)
Maximum operating current *
Cooling
A
9.4 9.4 9.9
Heating 11.9 11.9 14 .9
Fan
Air ow rate
Cooling
High
CFM
(m
3
/h)
500 (85 0) 529 (90 0)
Med 394 (670) 435 (740)
Low 324 (550) 335 (570)
Quiet 194 (330) 2 29 (390)
Heating
High 500 (85 0) 559 (95 0)
Med 418 (710) 435 (740)
Low 324 (550) 3 53 (600)
Quiet 194 (330) 2 53 (430)
Type × Q'ty Cross o w fan × 1
Motor out put W 29
Sound pre ssure leve l
Cooling
High
dB (A)
43 45
Med 37 40
Low 32 33
Quiet 21 25
Heating
High 43 45
Med 38 40
Low 32 34
Quiet 21 27
Heat excha nger typ e
Dimensions
(H × W × D)
in. (mm)
Main : 12-19/32 × 27-5 /32 × 25/3 2 (320 × 690 × 2 0)
Sub : 3- 5/16 × 27-5/3 2 × 17/32 (84 × 690 × 13. 3)
Fin pitch FPI Main : 23 Sub : 18
Rows × Stag es Main : 2 × 20 Sub : 1 × 4
Pipe typ e Copper
Fin type Aluminum
Enclosure
Material Polystyrene
Color
White
Approx imate col or of MUN SELL N9. 3/
Dimensions
(H × W × D)
Net
inch 11 - 3/32 × 34 - 1/4 × 7 - 9/32
mm 282 × 8 70 × 185
Gross
inch 9 - 23/32 × 3 6 - 7/32 × 14 - 11/16
mm 247 × 92 0 × 373
Weight
Net
lbs. (kg)
21 (9.5)
Gross 27 (12)
Connec tion pip e
Size
Liquid
in. (mm)
Ø1/4 (Ø6.35)
Gas Ø3/8 (9.52) Ø1/2 (12.7)
Method Flare
Operat ion rang e
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 30)
Remote co ntrolle r type Wireless
Drain ho se
Material PE
Size in.( mm)
Ø17/32 (Ø13.8) (I.D.)
Ø5/8 to Ø21/3 2 (Ø15.8 to Ø16.7) (O.D.)
Page 10
- (01 - 07) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
DIMENSIONS4.
MODEL : ASU9RLS2, ASU12RLS2, ASU15RLS2
Unit : in. (mm)
ASU9RLS2 ASU12RLS2 ASU15LS2
Refrigerant pipe are
connection
Liquid Ø 1/4 in. (Ø 6.35 mm)
Gas Ø 3/8 in. (Ø 9.52 mm) Ø 1/2 in. (Ø 12.7 mm)
Drain hose connection Drain hose
(Ø 17/32 in. (I.D.), Ø 5/8 to Ø 21/32 in. (O.D.) [Ø 13.8 mm (I.D.), Ø 15.8 to 16.7 mm (O.D.)]
7-7/8 (35)7-7/8 (200)
1-15/16 (49)
(3-5/16 (84)) 13-29/32 (353)
8-7/16 (214) 7 (178)
14-11/32 (364) 2-3/4 (70)
1-15/16 (49)
(11-3/32 (282))
25/32 (20)
12-1/4 (311)12-13/32 (315)
Outline of Unit
Ø2-9/16 (65) for pipe inlet
(34-1/4 (870))
Ø2-9/16 (65) for pipe inlet
11-3/32 (282)
7-9/32 (185)34-1/4 (870)
7-3/8(187) : Installed state
Page 11
- (01 - 08) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
INSTALLATION PLACE
Unit : in. (mm)
1-31/32 (50) or more
59-1/16 (1500) or more
9-23/32 (247)
2-5/32
(55)
5ft. 10-7/8 (1800) or more
13-9/32 (337)
6-5/16 (160) or more
1-31/32 (50) or more
6-5/16 (160) or more
3-15/16 (100) or more
4-23/32 (120) or more
Outline of Unit
Page 12
- (01 - 09) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
WIRING DIAGRAMS5.
MODEL : ASU9RLS2, ASU12RLS2, ASU15RLS2
Page 13
- (01 - 10) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
CAPACITY TABLE6.
COOLING CAPACITY6-1.
MODEL : ASU9RLS2
AFR : Air Fl ow Rate (CFM) TC : Total Capaci ty (kBtu /h) SHC : Sens ible Hea t Capacit y (kBtu/h) IP : Input Pow er (kW)
AFR : Air Fl ow Rate (m
3
/min)
TC : Total Capaci ty (kW) SHC : Sens ible Hea t Capacit y (kW) IP : Input Pow er (kW)
MODEL : ASU12RLS2
AFR : Air Fl ow Rate (CFM) TC : Total Capaci ty (kBtu /h) SHC : Sens ible Hea t Capacit y (kBtu/h) IP : Input Pow er (kW)
AFR : Air Fl ow Rate (m
3
/min)
TC : Total Capaci ty (kW) SHC : Sens ible Hea t Capacit y (kW) IP : Input Pow er (kW)
AFR 500
Indoor temperature
°FDB 64 70 75 80 85 90
°FWB 54 60 63 67 71 73
Outdoor temperature
°FDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
67 8.4 8.1 0.38 9.4 8.1 0.39 10.3 8.9 0.40 10.7 9.6 0.40 11.3 9.5 0.40 11.9 10.2 0.41
77 8.0 7.7 0.44 8.9 7.7 0.44 9.8 8.4 0.45 10.2 9.1 0.45 10.8 9.1 0.46 11.4 9.6 0.46
87 7.6 7.3 0.49 8.4 7.3 0.49 9.3 8.0 0.50 9.6 8.6 0.50 10.2 8.6 0.51 10.8 9.1 0.51
95 7.1 6.8 0.54 7.9 6.9 0.55 8.7 7.5 0.56 9.0 8.1 0.56 9.5 8.0 0.57 10.1 8.6 0.57
104 6.0 6.1 0.50 6.7 6.1 0.51 7.4 6.7 0.52 7.6 7.2 0.52 8.1 7.2 0.53 8.5 7.6 0.53
115 5.5 5.6 0.50 6.2 5.7 0.51 6.8 6.2 0.52 7.0 6.7 0.52 7.4 6.6 0.53 7.8 7.1 0.53
AFR 14.2
Indoor temperature
°CDB 17.8 21.1 23.9 26.7 29.4 32.2
°CWB 12.2 15.6 17.7 19.4 21.7 22.8
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
19.4 2.47 2.37 0.38 2.75 2.38 0.39 3.03 2.60 0.40 3.13 2.80 0.40 3.31 2.79 0.40 3.50 2.98 0.41
25.0 2.35 2.25 0.44 2.62 2.26 0.44 2.89 2.47 0.45 2.98 2.66 0.45 3.15 2.65 0.46 3.33 2.83 0.46
30.6 2.22 2.12 0.49 2.48 2.14 0.49 2.73 2.33 0.50 2.81 2.52 0.50 2.98 2.51 0.51 3.15 2.67 0.51
35.0 2.08 2.00 0.54 2.32 2.01 0.55 2.56 2.19 0.56 2.64 2.37 0.56 2.80 2.36 0.57 2.95 2.51 0.57
40.0 1.76 1.78 0.50 1.96 1.79 0.51 2.16 1.95 0.52 2.23 2.11 0.52 2.36 2.10 0.53 2.50 2.24 0.53
46.0 1.62 1.65 0.50 1.81 1.66 0.51 1.99 1.81 0.52 2.05 1.96 0.52 2.18 1.95 0.53 2.30 2.08 0.53
AFR 500
Indoor temperature
°FDB 64 70 75 80 85 90
°FWB 54 60 63 67 71 73
Outdoor temperature
°FDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
67 11.2 9.7 0.60 12.5 9.7 0.61 13.8 10.6 0.61 14.2 11.5 0.62 15.1 11.4 0.62 15.9 12.2 0.63
77 10.7 9.2 0.68 11.9 9.3 0.69 13.1 10.1 0.70 13.5 10.9 0.70 14.3 10.9 0.71 15.2 11.6 0.72
87 10.1 8.7 0.76 11.3 8.8 0.77 12.4 9.5 0.78 12.8 10.3 0.78 13.6 10.3 0.79 14.3 10.9 0.80
95 9.5 8.2 0.84 10.6 8.2 0.85 11.6 9.0 0.87 12.0 9.7 0.87 12.7 9.7 0.88 13.4 10.3 0.89
104 8.0 7.3 0.78 8.9 7.3 0.79 9.8 8.0 0.80 10.1 8.6 0.81 10.8 8.6 0.82 11.4 9.2 0.83
115 7.4 6.8 0.78 8.2 6.8 0.79 9.1 7.4 0.81 9.3 8.0 0.81 9.9 8.0 0.82 10.5 8.5 0.83
AFR 14.2
Indoor temperature
°CDB 17.8 21.1 23.9 26.7 29.4 32.2
°CWB 12.2 15.6 17.7 19.4 21.7 22.8
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
19.4 3.29 2.84 0.60 3.67 2.86 0.61 4.04 3.12 0.61 4.17 3.37 0.62 4.42 3.35 0.62 4.67 3.57 0.63
25.0 3.13 2.70 0.68 3.49 2.71 0.69 3.85 2.96 0.70 3.97 3.20 0.70 4.20 3.18 0.71 4.44 3.39 0.72
30.6 2.96 2.55 0.76 3.30 2.56 0.77 3.64 2.80 0.78 3.75 3.02 0.78 3.98 3.01 0.79 4.20 3.21 0.80
35.0 2.78 2.40 0.84 3.09 2.41 0.85 3.41 2.63 0.87 3.52 2.84 0.87 3.73 2.83 0.88 3.94 3.01 0.89
40.0 2.35 2.14 0.78 2.62 2.15 0.79 2.88 2.34 0.80 2.97 2.53 0.81 3.15 2.52 0.82 3.33 2.69 0.83
46.0 2.16 1.98 0.78 2.41 1.99 0.79 2.66 2.17 0.81 2.74 2.35 0.81 2.90 2.34 0.82 3.07 2.49 0.83
Page 14
- (01 - 11) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
MODEL : ASU15RLS2
AFR : Air Fl ow Rate (CFM) TC : Total Capaci ty (kBtu /h) SHC : Sens ible Hea t Capacit y (kBtu/h) IP : Input Pow er (kW)
AFR : Air Fl ow Rate (m
3
/min)
TC : Total Capaci ty (kW) SHC : Sens ible Hea t Capacit y (kW) IP : Input Pow er (kW)
AFR 529
Indoor temperature
°FDB 64 70 75 80 85 90
°FWB 54 60 63 67 71 73
Outdoor temperature
°FDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
67 13.5 10.7 0.84 15.0 10.8 0.86 16.6 11.8 0.87 17.1 12.7 0.87 18.1 12.7 0.88 19.1 13.5 0.89
77 12.9 10.2 0.95 14.3 10.3 0.96 15.8 11.2 0.98 16.3 12.1 0.98 17.2 12.1 0.99 18.2 12.9 1.00
87 12.2 9.7 1.06 13.6 9.8 1.07 15.0 10.6 1.09 15.4 11.5 1.10 16.4 11.5 1.11 17.3 12.2 1.12
95 11.5 9.1 1.17 12.8 9.2 1.19 14.1 10.0 1.20 14.5 10.8 1.21 15.4 10.8 1.22 16.2 11.5 1.23
104 10.1 8.0 1.15 11.2 8.1 1.17 12.4 8.8 1.19 12.7 9.5 1.19 13.5 9.5 1.20 14.3 10.1 1.22
115 9.2 7.3 1.13 10.2 7.3 1.15 11.3 8.0 1.17 11.6 8.6 1.17 12.3 8.6 1.19 13.0 9.2 1.20
AFR 15.0
Indoor temperature
°CDB 17.8 21.1 23.9 26.7 29.4 32.2
°CWB 12.2 15.6 17.7 19.4 21.7 22.8
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
19.4 3.95 3.15 0.84 4.40 3.17 0.86 4.85 3.45 0.87 5.00 3.73 0.87 5.30 3.71 0.88 5.60 3.96 0.89
25.0 3.77 3.00 0.95 4.20 3.02 0.96 4.63 3.29 0.98 4.77 3.55 0.98 5.05 3.54 0.99 5.34 3.77 1.00
30.6 3.57 2.84 1.06 3.98 2.86 1.07 4.39 3.12 1.09 4.52 3.37 1.10 4.79 3.36 1.11 5.07 3.58 1.12
35.0 3.36 2.67 1.17 3.74 2.69 1.19 4.12 2.93 1.20 4.25 3.17 1.21 4.50 3.15 1.22 4.76 3.36 1.23
40.0 2.95 2.35 1.15 3.29 2.36 1.17 3.62 2.58 1.19 3.73 2.78 1.19 3.96 2.77 1.20 4.18 2.95 1.22
46.0 2.69 2.14 1.13 2.99 2.15 1.15 3.30 2.35 1.17 3.40 2.53 1.17 3.61 2.52 1.19 3.81 2.69 1.20
Page 15
- (01 - 12) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
HEATING CAPACITY6-2.
MODEL : ASU9RLS2
AFR : Air Fl ow Rate (CFM) TC : Total Capaci ty (kBtu /h)
IP : Input Pow er (kW)
AFR : Air Fl ow Rate (m3/min) TC : Total Capaci ty (kW)
IP : Input Pow er (kW)
MODEL : ASU12RLS2
AFR : Air Fl ow Rate (CFM) TC : Total Capaci ty (kBtu /h)
IP : Input Pow er (kW)
AFR : Air Fl ow Rate (m3/min) TC : Total Capaci ty (kW)
IP : Input Pow er (kW)
AFR 500
Indoor t empera ture
°FDB 60 65 70 75
Outdoo r temper ature
°FDB °FWB TC IP TC IP TC IP TC IP
-15 -17 11. 6 2.10 11.4 2 .14 11.1 2.18 10.5 2 .26
-5 -7 14.7 2 .12 14.3 2.16 14.0 2.20 13.3 2.28 5 3 16.1 2.13 15.7 2.17 15.4 2 .21 14.6 2.3 0
14 12 16.8 2 .06 16.4 2.10 16.0 2.14 15. 2 2.22 23 19 18.3 1.99 17.9 2.03 1 7.5 2. 07 16.6 2 .15 32 28 18. 8 1.93 18.4 1.97 17.9 2.0 0 17.0 2.08 41 37 21.3 1.85 20.8 1.8 9 20.3 1.93 19. 3 2.00 47 43 23.1 1.91 22 .6 1.95 22.0 1.99 20.9 2. 07 50 47 25.5 1.94 24 .9 1.98 24. 3 2.02 23 .1 2.10 59 50 26.5 1.9 5 25.8 1.9 9 25.2 2.03 23 .9 2 .11
AFR 14. 2
Indoor t empera ture
°CDB 15 .6 18.3 21.1 23.9
Outdoo r temper ature
°CDB °CWB TC IP TC IP TC IP TC IP
-2 6.1 -2 7.0 3.41 2.10 3. 33 2.14 3. 25 2.18 3.09 2. 26
-20.6 -21.7 4.31 2 .12 4.20 2.16 4.10 2.20 3. 90 2.28
-15.0 -16.1 4.73 2.13 4.61 2.17 4.50 2.21 4. 28 2.30
-10.0 -11.1 4.91 2. 06 4.80 2.10 4. 68 2.14 4.4 5 2.22
-5.0 -7.2 5.3 8 1.99 5.2 5 2 .03 5 .12 2.07 4. 86 2 .15
0.0 -2.2 5.52 1.9 3 5.39 1.97 5.26 2.00 5.0 0 2.08
5.0 2.8 6. 25 1.85 6 .10 1.89 5.95 1.93 5 .65 2.00
8.3 6 .1 6.77 1.91 6.61 1.95 6.45 1.9 9 6.13 2.07
10.0 8. 3 7.48 1.9 4 7.30 1.98 7.13 2.02 6.77 2.10
15.0 10.0 7.75 1.95 7.57 1.9 9 7.38 2.03 7.02 2.11
AFR 14. 2
Indoor t empera ture
°CDB 15 .6 18.3 21.1 23.9
Outdoo r temper ature
°CDB °CWB TC IP TC IP TC IP TC IP
-26.1 -27.0 3.62 2 .15 3.54 2.19 3 .45 2.23 3. 28 2.31
-20.6 -21.7 4.63 2 .17 4. 52 2.21 4 .41 2.25 4 .19 2.3 3
-15.0 -16.1 5.16 2.17 5.03 2 .21 4.91 2. 25 4.66 2.3 4
-10.0 -11.1 5.36 2. 09 5.23 2.13 5.10 2.17 4.8 5 2 .25
-5.0 -7.2 5.8 6 2.02 5.72 2. 06 5.58 2.10 5.30 2 .17
0.0 -2.2 6.03 1.9 5 5.88 1.99 5.74 2.03 5.4 5 2.10
5.0 2.8 6.5 8 1.86 6.43 1.9 0 6.27 1.9 4 5 .96 2.02
8.3 6 .1 6 .80 1.92 6. 64 1.96 6.4 8 2.00 6 .15 2.0 8
10.0 8. 3 7.52 1.9 4 7.34 1.98 7.16 2.02 6.80 2.10
15.0 10.0 7.79 1.95 7.60 1.9 9 7.42 2.03 7.05 2.11
AFR 500
Indoor t empera ture
°FDB 60 65 70 75
Outdoo r temper ature
°FDB °FWB TC IP TC IP TC IP TC IP
-15 -17 12.4 2 .15 12 .1 2.19 11.8 2. 23 11.2 2. 31
-5 -7 15.8 2.17 15.4 2.21 15.0 2.25 14.3 2.33 5 3 17.6 2.17 17.2 2.21 16.8 2. 25 15.9 2.3 4
14 12 18.3 2 .09 17.8 2.13 17.4 2 .17 16 .5 2.25 23 19 20.0 2.02 19. 5 2.06 19.0 2.10 18.1 2.17 32 28 20 .6 1.95 2 0.1 1.99 19.6 2. 03 18.6 2 .10 41 37 22. 5 1.86 21.9 1.9 0 21.4 1.94 20 .3 2.02 47 43 2 3.2 1.92 2 2.7 1.96 2 2.1 2 .00 21.0 2 .08 50 47 25.6 1.94 25 .0 1.98 24. 4 2.02 23. 2 2.10 59 50 26.6 1.9 5 25.9 1.9 9 25.3 2.03 24 .0 2 .11
Page 16
- (01 - 13) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
MODEL : ASU15RLS2
AFR : Air Fl ow Rate (CFM) TC : Total Capaci ty (kBtu /h)
IP : Input Pow er (kW)
AFR : Air Fl ow Rate (m3/min) TC : Total Capaci ty (kW)
IP : Input Pow er (kW)
AFR 559
Indoor t empera ture
°FDB 60 65 70 75
Outdoo r temper ature
°FDB °FWB TC IP TC IP TC IP TC IP
-15 -17 15.8 2.23 15.4 2. 28 15.0 2. 32 14.3 2. 41
-5 -7 17.6 2.26 17.1 2.31 16.7 2. 35 15.9 2.4 4 5 3 19.3 2.2 9 18.9 2.34 18. 4 2.38 17. 5 2.47
14 12 20.7 2 .33 20.2 2. 38 19.7 2.42 18.7 2.51 23 19 21.6 2.4 3 21 .1 2.48 20.5 2. 53 19.5 2.6 3 32 28 21.8 2.63 21.3 2. 68 20.7 2.73 19.7 2.83 41 37 23.8 2 .32 23.2 2. 37 22.7 2.42 21.5 2.52 47 43 25.1 2 .17 24 .5 2.21 23. 9 2 .26 22.7 2. 35 50 47 27.7 1.94 2 7.1 1.98 26. 4 2.02 25 .1 2.10 59 50 28.7 1.9 5 28.0 1.9 9 27.4 2.03 26.0 2 .11
AFR 15.8
Indoor t empera ture
°CDB 16 18 20 24
Outdoo r temper ature
°CDB °CWB TC IP TC IP TC IP TC IP
-2 6.1 -2 7.0 4.62 2.2 3 4.51 2.28 4. 40 2.32 4.18 2.41
-20.6 -21.7 5 .15 2.26 5.02 2 .31 4.90 2.3 5 4.66 2.44
-15.0 -16.1 5 .67 2.29 5.5 4 2.34 5.40 2. 38 5.13 2. 47
-10.0 -11.1 6.06 2. 33 5.92 2.3 8 5.78 2.42 5. 49 2.51
-5.0 -7.2 6. 32 2.43 6.17 2. 48 6.02 2.5 3 5.72 2.63
0.0 -2.2 6.38 2. 63 6.23 2.6 8 6 .08 2.73 5 .77 2.83
5.0 2.8 6. 97 2.32 6.81 2 .37 6.64 2. 42 6.31 2.52
8.3 6 .1 7.35 2.17 7.18 2.21 7.00 2. 26 6.65 2.3 5
10.0 8. 3 8.12 1.9 4 7.93 1.98 7.7 4 2.02 7.35 2.10
15.0 10.0 8.42 1.95 8.22 1.9 9 8.02 2.03 7.62 2.11
Page 17
- (01 - 14) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
FAN PERFORMANCE7.
AIR VELOCITY DISTRIBUTION7-1.
MODEL : ASU9RLS2, ASU12RLS2
Note:
Fan speed : High
Operation mode : FAN
5 (1.5)
3 (1.0)
2 (0.5)
2
1
0
1
2
Unit : ft./s (m/s)(m)
(m)
TOP VIEW
Vertic al ap : Up Horizo ntal ap : C enter
0 1 2 3 4 5 6 7 8
7
3
0
3
7
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
10
7
3
0
3
7
10
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
2 (0.5) 2 (0.5)
3 (1.0)
3 (1.0)
5 (1.5)
5 (1.5)
3
2
1
0
1
2
3
Unit : ft./s (m/s)(m)
TOP VIEW
Vertic al ap : Up Horizo ntal ap : R ight & Lef t
(m)
0 1 2 3 4 5 6 7 8
5 (1.5)
3 (1.0)
2 (0.5)
3
2
1
0
Unit : ft./s (m/s)(m)
SIDE VIE W
Vertic al ap : Up Horizo ntal ap : C enter
(m)
0 1 2 3 4 5 6 7 8
5 (1.5)
3 (1.0)
2 (0.5)
3
2
1
0
Unit : ft./s (m/s)(m)
SIDE VIE W
Vertic al ap : Dow n Horizo ntal ap : C enter
(m)
0 1 2 3 4 5 6 7 8
10
7
3
0
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
10
7
3
0
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
Page 18
- (01 - 15) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
MODEL : ASU15RLS2
Note:
Fan speed : High
Operation mode : FAN
5 (1.5)
3 (1.0)
2 (0.5)
2
1
0
1
2
(m)
(m)
TOP VIEW
Vertic al ap : Up Horizo ntal ap : C enter
0 1 2 3 4 5 6 7 8
2 (0.5) 2 (0.5)
3 (1.0)
3 (1.0)
5 (1.5)
5 (1.5)
3
2
1
0
1
2
3
(m)
TOP VIEW
Vertic al ap : Up Horizo ntal ap : R ight & Lef t
(m)
0 1 2 3 4 5 6 7 8
5 (1.5)
3 (1.0)
2 (0.5)
3
2
1
0
(m)
SIDE VIE W
Vertic al ap : Up Horizo ntal ap : C enter
(m)
0 1 2 3 4 5 6 7 8
5 (1.5)
3 (1.0)
2 (0.5)
3
2
1
0
(m)
SIDE VIE W
Vertic al ap : Dow n Horizo ntal ap : C enter
(m)
0 1 2 3 4 5 6 7 8
7
3
0
3
7
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
10
7
3
0
3
7
10
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
10
7
3
0
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
10
7
3
0
(f t.)
(f t.)
0 3 7 10 13 16 20 23 26
Unit : ft./s (m/s)
Unit : ft./s (m/s)
Unit : ft./s (m/s)
Unit : ft./s (m/s)
Page 19
- (01 - 16) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
AIRFLOW7-2.
MODEL : ASU9RLS2, ASU12RLS2
Cooling
z
Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Airow
HIGH 1370
850 m
3
/h
236 l/s
500 CFM
MED 112 0
670 m
3
/h
186 l/s
394 CFM
LOW 960
550 m
3
/h
153 l/s
324 CFM
QUIET 650
330 m
3
/h
92 l/s
194 CFM
Fan speed
Number of
rotations
(r.p.m.)
Airow
HIGH 1370
850 m
3
/h
236 l/s
500 CFM
MED 118 0
710 m
3
/h
197 l/s
418 CFM
LOW 960
550 m
3
/h
153 l/s
324 CFM
QUIET 650
330 m
3
/h
92 l/s
194 CFM
Page 20
- (01 - 17) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
MODEL : ASU15RLS2
Cooling
z
Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Airow
HIGH 1440
900 m
3
/h
250 l/s
529 CFM
MED 1220
740 m
3
/h
206 l/s
435 CFM
LOW 980
570 m
3
/h
158 l/s
335 CFM
QUIET 740
390 m
3
/h
108 l/s
229
CFM
Fan speed
Number of
rotations
(r.p.m.)
Airow
HIGH 1510
950 m
3
/h
264 l/s
559 CFM
MED 1220
740 m
3
/h
206 l/s
435 CFM
LOW 1030
600 m
3
/h
167 l/s
353 CFM
QUIET 790
430 m
3
/h
119 l/s
253
CFM
Page 21
- (01 - 18) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL : ASU9RLS2, ASU12RLS2
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
MODEL : ASU15RLS2
Cooling
z
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
High
Quiet
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
High
Quiet
High
Quiet
High
Quiet
Cooling
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
Page 22
- (01 - 19) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
SOUND LEVEL CHECK POINT8-2.
31-1/2in. (0.8m)
39-3/8in. (1m)
Page 23
- (01 - 20) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
ELECTRIC CHARACTERISTICS9.
Model name ASU9RLS2 ASU12R LS2 ASU15RLS2
Power supply
Volt ag e V 208 / 230 ~
Frequency Hz 60
Max. operating current A 0.4
*1) Wiring Spec.
Connection cable AWG 14 Limited wiring length ft. (m) 69 (21)
*1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
Page 24
- (01 - 21) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
SAFETY DEVICES10.
Protection form
Model
ASU9RLS2 ASU12RLS2 ASU15RLS2
Circuit protection Current fuse (PCB) 250V 3.15A
Terminal protection Current (thermal) fuse 250V 3A
Fan motor protection Thermal protector program
OFF: 320±45 °F (160±25 °C)
ON: 230±45 °F (110±25 °C)
Page 25
- (01 - 22) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
EXTERNAL INPUT & OUTPUT11.
Connector INPUT OUTPUT REMARKS
CNA01 Control input -
See external
input/output settings
for details.
CNB01 - Operation status output CNB02 - Error status output
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit. Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation Initial setting after power is ON Starting mode other than initial setting
Operation mode Auto changeover Mode at previous operation Set temperature 75°F (24°C) Temperature at previous operation
Air ow mode AUTO Mode at previous operation
Up-down air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Left-right air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
z
Signal
Field supply
Indoor unit
control PC board Communication kit
Optional parts
Connector
1
3
*33ft. (10m)
Connected unit
Ex.) Switch
* Make the distance from the PC board to the connected unit within 33ft.(10m). Contact capacity : 24VDC or more, 10mA or more. Please use non-polar relays and switches.
When function setting is in "Operation/Stop" mode
z
Operation
Stop
ON
OFF
Input signal
Indoor unit
Page 26
- (01 - 23) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
When function setting is in "Forced stop" mode
z
Remote controller
ON O N ON
Input signal
ON
OFF
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control operation invalidity
Parts (Optional)
z
Parts name
Model name
External connect kit UT Y-X W ZX Z 5
Communication kit UTY-T WBXF
* For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to
the wire (UTY-XWZXZ5).
Page 27
- (01 - 24) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
EXTERNAL OUTPUT11-2.
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
z
* Make the distance from the PC board to the connected unit within 33ft.(10m). Relay spec. : Max.24VDC, 10mA to less than 500mA.
Field supplyOptional parts
Ex.)Display
Indoor unit
control PC board Communication kit Connected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
*33ft. (10m)
24V DC
ON
OFF
Operation
Stop
Indoor unit
Output signal
Parts (Optional)
z
Parts name
Model name
External connect kit UT Y-X W ZX Z 5
Communication kit UTY-T WBXF
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(U T Y-XWZX Z5).
Page 28
- (01 - 25) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
ERROR STATUS OUTPUT
An air conditioner error status signal can be output.
Circuit diagram example
z
* Make the distance from the PC board to the connected unit within 33ft.(10m). Relay spec. : Max.24VDC, 10mA to less than 500mA.
Field supplyOptional parts
Ex.)Display
Indoor unit
control PC board Communication kit Connected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
24V DC
*33ft. (10m)
ON
OFF
Error
Normal
Error status
Output signal
Parts (Optional)
z
Parts name
Model name
External connect kit UT Y-X W ZX Z 5
Communication kit UTY-T WBXF
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(U T Y-XWZX Z5).
Page 29
- (01 - 26) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
FUNCTION SETTINGS12.
INDOOR UNIT (Setting by remote controller)12-1.
The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
PREPARATION
Turn on the power
¾
Before turning on the power of the indoor units, make sure the piping air-tight test and vacuuming have been
conducted.
¾
Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wireless remote controller)
Perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
CAUTION
Conrm whether the wiring work for Outdoor unit has been nished.
Conrm that the cover for the electrical enclosure on the outdoor unit is in place.
This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected. Refer to the installation manual enclosed with the remote control unit when the wired remote
control unit (option) is used. Adjust the signal code of the indoor unit and the signal code of the remote controller.
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP. (
) simultaneously, press the RESET button to enter the
function setting mode.
Selecting the Function Number and Setting Value
(1) Press the SET TEMP. (
/ ) buttons to select the function number.
(Press the 10°C HEAT button to switch between the left and right digits.)
(2) Press the POWERFUL button to proceed to setting the value.
(Press the POWERFUL button again to return to the function number selection.)
(3) Press the SET TEMP. (
/ ) buttons to select the setting value.
(Press the 10°C HEAT button to switch between the left and right digits.)
(4) Press the MODE button, in the order listed to conrm the settings.
Please conrm that the beep sounds.
(5) Next, please press START/STOP (
/ ) button. Please conrm that the beep sounds. (6) Press the RESET button to cancel the function setting mode. (7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
Function number
Setting value
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The Function Setting will not become active unless the power is turned off then on again.
Page 30
- (01 - 27) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
FUNCTION DETAILS
Functions
Compact wall
mounted
1) Filter sign
z
2) Cooler room temperature correction
z
3) Heater room temperature correction
z
4) Auto restart
z
5)
Indoor room temperature sensor switching function
z
6) Remote controller signal code
z
7) External input control
z
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the lter. Select the time setting for the lter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the lter sign to be displayed, select the setting value for "No indication".
(... Factory setting)
Setting description Function number Setting value
Standard
11
00
Long interval 01
Short interval 02
No indication 03
The lter sign interval time is different according to Indoor unit type as follows.
Setting description
Compact Wall
Mounted
Standard 400 hours
Long interval 1000 hours
Short interval 200 hours
2) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require correction. The settings may be selected as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
30
00
Slightly lower control 01
Lower control 02
Warmer control 03
3) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require correction. The settings may be changed as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
Page 31
- (01 - 28) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
4) Auto restart
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting description Function number Setting value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation. Be sure to operate using the remote controller, or external input device.
5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the control by Wired remote controller temperature sensor.
(... Factory setting)
Setting description Function number Setting value
No
42
00
Yes 01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
6) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(... Factory setting)
Setting description Function number Setting value
A
44
00 B 01 C 02 D 03
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(... Factory setting)
Setting description Function number Setting value
Operation/Stop mode
46
00
(Setting forbidden) 01
Forced stop mode 02
Page 32
- (01 - 29) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
REMOTE CONTROLLER SIGNAL CODE SETTING
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
(1) Press the START/STOP (
/ ) button until only the clock is displayed on the
remote controller display.
(2) Press the MODE button for at least 5 seconds to display the current signal code
(initially set to
).
(3) Press the SET TEMP. (
/ ) buttons to change the signal code between
→ → → .
Match the code on the display to the air conditioner signal code.
(4) Press the MODE button again to return to the clock display. The signal code will
be changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original
• clock display. In this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment.
REMOTE CONTROLLER TEMPERATURE UNIT
To change the temperature unit: (1) Press the TEMP. (Up) button (
) for at least 5 seconds to display the current temperature unit. (Factory setting: °F)
(2) Press the TEMP. buttons (
/ ) to switch the temperature unit. (°F ↔ °C)
(3) With either of pressing the START/STOP button or no additional button operation for 30 seconds in step 2., the
temperature unit currently selected will be set.
Page 33
- (01 - 30) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
OPTIONAL PARTS13.
CONTROLLER13-1.
OTHERS13-2.
Exterior Parts name Model No. Summary
Mode
Menu
Cool
Monitor
Set temp.
Fan
High
°
F
80
Mo
10:00
AM
Icon check:
Wired remote
controller
UTY- RVNUM
Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. *Optional communication kit is
necessary for installation
Wired remote
controller
UTY-RNNUM
The room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor. *Optional communication kit is
necessary for installation.
Simple remote
controller
UTY- RSNUM
Compact remote controller concentrates on the basic functions such as Start/Stop, Fan Control, Temperature
Setting and Operation mode.
*Optional communication kit is
necessary for installation.
Exterior Parts name Model No. Summary
Communication
kit
UTY-T WBXF
Use to connect with optional devices and air conditioner
PC board.
( x 1 )
( x 2 )
External
connect kit
UTY-X W ZX Z5
Required when external device is connected.
*Optional communication kit
is necessary for installation.
Page 34
2. OUTDOOR UNIT
SINGLE TYPE :
AOU9RLS2H AOU12RLS2H AOU15RLS2H
DTR_AO123E_01
2012.12.14
Page 35
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
CONTENTS
2. OUTDOOR UNIT
1. SPECIFICATIONS
.............................................................................................. 02 - 01
2. DIMENSIONS
........................................................................................................ 02 - 02
3. REFRIGERANT CIRCUIT
............................................................................ 02 - 03
4. WIRING DIAGRAMS
........................................................................................ 02 - 04
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
.................................................................................. 02 - 06
6. ADDITIONAL CHARGE CALCULATION
......................................... 02 - 08
7. AIRFLOW
................................................................................................................. 02 - 09
8. OPERATION NOISE
......................................................................................... 02 - 10
8-1. NOISE LEVEL CURVE
.................................................................................... 02 - 10
8-2. SOUND LEVEL CHECK POINT
..................................................................... 02 - 12
9. ELECTRIC CHARACTERISTICS
........................................................... 02 - 13
10. SAFETY DEVICES
............................................................................................ 02 - 14
Page 36
- (02 - 01) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
SPECIFICATIONS1.
Typ e INVERTER HEAT PUMP Model name AOU9RLS2H AOU12RLS2H AOU15R LS2H Power source 208 / 230V
~
60Hz
Available voltage range 187 - 253V
~
60Hz
Starting current A 3.7 5.5 6 .1
Fan
Airow rate
Cooling
CFM
(m
3
/h)
1082 (1840) 1206 (2050)
Heating 1082 (1840) Type × Q'ty Propeller fan × 1 Motor output W 115
Sound pressure level
Cooling
dB (A)
48 49 51
Heating 49 50 51
Heat exchanger type
Dimensions
(H × W × D)
in. 23-5/32 × 34-11/16 × 1-7/16
mm 588 × 881 × 36.4 Fin pitch FPI 20 Rows × Stages 2 × 28 Pipe type Copper Fin Type Aluminum
Compressor
Type × Q'ty Rotary × 1 Motor output W 850 1000
Refrigerant
Type (Global Warming Potential) R410A (1975)
Charge
lbs.oz. 2lbs.10oz. 2lbs.12oz.
kg 1.20 1.25
Refrigerant oil Type FREOL α68SZ
Enclosure
Material Steel
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions (H × W × D)
Net
in. 24 - 1/2 × 31 - 3/32 × 11 - 11/32
mm 620 × 790 × 290
Gross
in. 28 - 1/16 × 37-7/32 × 15 - 9/16
mm 713 × 945 × 395
Weight
Net
lbs.( kg)
86 (39) 88 (40)
Gross 93 (42) 95 (43)
Connenction pipe
Size
Liquid
in. (mm)
Ø 1/4 (Ø 6.35)
Gas Ø 3/8 (Ø 9.52) Ø 1/2 (Ø 12.7)
Method Flare Pre - charge length
ft. (m)
49 (15) Max. length 66 (20) Max. height difference 49 (15)
Operation range
Cooling
°F (°C)
14 to 115 (-10 to 46)
Heating -15 to 75 (-26 to 24)
Note :
Specications are based on the following conditions.
Cooling : Indoor temperature of 80°F (26.67°C) DB / 67°F (19.44°C) WB, and outdoor temperature of 95°F (35°C) DB / 75° F (23.9°C) WB. Heating : Indoor temperature of 70°F (21.11°C) DB / 59°F (15°C) WB, and outdoor temperature of 47°F (8.33°C) DB / 4 3°F (6.11°C) WB. Pipe length : 24ft.7in ( 7.5m), Height difference:0 m. (Outdoor unit - Indoor unit) The protective function may work when using it outside the operation range.
Page 37
- (02 - 02) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
DIMENSIONS2.
MODEL : AOU9RLS2H, AOU12RLS2H, AOU15RLS2H
Unit : in. (mm)
INSTALLATION PLACE
4-11/32
(110)
8-7/32 (209)
6-7/8 (175)
12-19/32 (320)
4-ø7/16 (11.3) hole
21-1/4 (540)
Air flow
ø25/32 (20) hole
Bottom view
31/32 (25)
2-5/32 (55)
31/32(10)
hole
31/32(25)
13/32 (10) 13/32 (10)
hole
4-1/32 (102)
23-5/8 (600)
or more
3-15/16 (100) or more
7-7/8 (200) or more
3-15/16 (100)
or more
9-27/32 (250) or more
(Service space)
CAUTION
In areas with heavy snowfall, if the intake and outlet of the outdoor unit is blocked with snow, it may be difficult to warm up and likely to cause breakdown. In such condition, be sure to construct a canopy or baffle board stand.
If the space is larger than is stated, the condition will be the same as those without any no obstacles.
Page 38
- (02 - 03) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
REFRIGERANT CIRCUIT3.
MODEL : AOU9RLS2H, AOU12RLS2H, AOU15RLS2H
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger ( OUTDOOR )
Compressor
Cooling Heating
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm) : 9/12RLS2H
1/2" (12.70 mm) : 15RLS2H
Th
D
Th
R
Th
PI
Th
HO
Th
O
: Thermistor (Discharge Temp.)
: Thermistor (Outdoor Temp.)
: Thermistor (Heat Exchanger Out Temp.)
Th
D
Th
O
Th
HO
: Thermistor (Room Temp.)
: Thermistor (Pipe Temp.)
Th
R
Th
PI
Page 39
- (02 - 04) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
WIRING DIAGRAMS4.
MODEL : AOU9RLS2H, AOU12RLS2H
Page 40
- (02 - 05) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
MODEL : AOU15RLS2H
Page 41
- (02 - 06) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
MODEL : AOU9RLS2H, AOU12RLS2H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5m 7. 5m 10m 15m 20m
17f t. 25ft. 33ft. 50ft. 67ft.
Height
difference H
Û
1
Indoor unit is
higher than
outdoor unit.
15m 50ft. - - - 0.933 0.925
10m 33ft. - - 0.981 0.933 0.925
7. 5m 25ft. - 1.000 0.981 0.933 0.925
5m 17ft. 1.017 1.000 0.9 81 0.933 0.925
0m 0ft. 1.017 1.000 0.981 0.933 0.925
Û
2
Indoor unit is
lower than
outdoor unit
-5m -17f t. 1.012 0.995 0.976 0.928 0.920
-7. 5 m -25ft. - 0.993 0.974 0.926 0.918
-10m -33ft. - - 0.971 0.923 0.916
-15m -50ft. - - - 0.914 0.906
COOLING
Pipe length (m)
5m 7. 5m 10m 15m 20m
17f t. 25ft. 33ft. 50ft. 67ft.
Height
difference H
Û
1
Indoor unit is
higher than
outdoor unit.
15m 50ft. - - - 0.877 0.874
10m 33ft. - - 0.956 0.891 0.888
7. 5m 25ft. - 0.988 0.960 0.895 0.892
5m 17ft. 1.017 0.992 0.964 0.899 0.895
0m 0ft. 1.025 1.000 0.971 0.906 0.902
Û
2
Indoor unit is
lower than
outdoor unit
-5m -17f t. 1.025 1.000 0.971 0.906 0.902
-7. 5 m -25ft. - 1.000 0.971 0.906 0.902
-10m -33ft. - - 0.971 0.906 0.902
-15m -50ft. - - - 0.906 0.902
H H
Page 42
- (02 - 07) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
MODEL : AOU15RLS2H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5m 7. 5m 10m 15m 20m
17f t. 25ft. 33ft. 50ft. 67ft.
Height
difference H
Û
1
Indoor unit is
higher than
outdoor unit.
15m 50ft. - - - 0.994 0.979
10m 33ft. - - 1.012 0.994 0.979
7. 5m 25ft. - 1.000 1.012 0.994 0.979
5m 17ft. 0.969 1.000 1.012 0.994 0.979
0m 0ft. 0.969 1.000 1.012 0.994 0.979
Û
2
Indoor unit is
lower than
outdoor unit
-5m -17f t. 0.964 0.995 1.007 0.989 0.974
-7. 5 m -25ft. - 0.993 1.004 0.986 0.972
-10m -33ft. - - 1.002 0.984 0.969
-15m -50ft. - - - 0. 974 0.959
COOLING
Pipe length (m)
5m 7. 5m 10m 15m 20m
17f t. 25ft. 33ft. 50ft. 67ft.
Height
difference H
Û
1
Indoor unit is
higher than
outdoor unit.
15m 50ft. - - - 0.951 0.950
10m 33ft. - - 0.979 0.967 0.966
7. 5m 25ft. - 0.988 0.983 0.971 0.970
5m 17ft. 0.994 0.992 0.987 0.975 0 .974
0m 0ft. 1.002 1.000 0.995 0.983 0.982
Û
2
Indoor unit is
lower than
outdoor unit
-5m -17f t. 1.002 1.000 0.995 0.983 0.982
-7. 5 m -25ft. - 1.000 0.995 0.983 0.982
-10m -33ft. - - 0.995 0.983 0.982
-15m -50ft. - - - 0.983 0.982
H H
Page 43
- (02 - 08) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
ADDITIONAL CHARGE CALCULATION6.
MODEL : AOU9RLS2H, AOU12RLS2H
REFRIGERANT CHARGE
z
MODEL : AOU15RLS2H
REFRIGERANT CHARGE
z
Refrigerant type R410A
Refrigerant amount
lbs. oz. 2lbs.10oz.
g 1200
Pipe length
ft. 49 or less 66 (MAX)
0.22oz./ft. (20 g /m)
m 15 or less 20 (MAX)
Additional charge
oz. 0 3.5
g 0 100
Refrigerant type R410A
Refrigerant amount
lbs. oz. 2lbs.12oz.
g 1250
Pipe length
ft. 49 or less 66 (MAX)
0.22oz./ft. (20 g /m)
m 15 or less 20 (MAX)
Additional charge
oz.
0
3.5
g 0 100
Page 44
- (02 - 09) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
AIRFLOW7.
MODEL : AOU9RLS2H
Cooling
z
Heating
z
MODEL : AOU12RLS2H, AOU15RLS2H
Cooling
z
Heating
z
Number of
rotations
(r.p.m.)
Airow
780
1840 m
3
/h
510 l/s
1082 CFM
Number of
rotations
(r.p.m.)
Airow
780
1840 m
3
/h
510 l/s
1082 CFM
Number of
rotations
(r.p.m.)
Airow
870
2050 m
3
/h
569 l/s
1206 CFM
Number of
rotations
(r.p.m.)
Airow
780
1840 m
3
/h
510 l/s
1082 CFM
Page 45
- (02 - 10) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL : AOU9RLS2H
Cooling
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
MODEL : AOU12RLS2H
Cooling
z
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 46
- (02 - 11) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
MODEL : AOU15RLS2H
Cooling
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2 ,000 4,0 00 8,0 00
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 47
- (02 - 12) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
SOUND LEVEL CHECK POINT8-2.
39-3/8in. (1m)
Page 48
- (02 - 13) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
ELECTRIC CHARACTERISTICS9.
Model name AOU9RLS2H AOU12RLS2H AOU15RLS2H
Power supply
Voltage V 208 / 230 ~ Frequency Hz 60
MCA A
14.5 18.2
Starting Current A 3.7 5.5 6 .1
*1) Wiring Spec.:
MAX. CKT. BKR A 15 20 Power Cable AWG 14 12 *2) Limited wiring length : ft. (m) 60 (18) 75 (22)
*1) Wiring Spec.: Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
MCA : Min Circuit Amp (Calculation based on UL1995) MAX. CKT. BKR : Maximum Circuit Breaker
Page 49
- (02 - 14) -
OUTDOOR UNIT
AOU9-15RLS2 H
OUTDOOR UNIT
AOU9-15RLS2 H
SAFETY DEVICES10.
Protection form
Model
AOU9RLS2H AOU12RLS2H AOU15RLS2H
Circuit protection
Current fuse (Near the terminal)
250V 20A
250V 25A
250V 5A
Current fuse (Main printed circuit board)
250V 15A 250V 10A
250V 3.15A 250V 3.15A
Fan motor protection
Thermal protection program
OFF : 212±27 °F (100±15 °C)
ON : 203±18 °F (95±10 °C)
Compressor protection
Thermal protection program (Discharge temp.)
OFF : 230 °F (110 °C)
ON : After 7 minutes