Easy setting by wireless or
wired remote controller
MODEL
CASSETTE TYPE
AUU9-18RLF
AUU9RLF / AOU9RLFC
CASSETTE TYPE
AUU9-18RLF
AUU12RLF / AOU12RLFC
AUU18RLF / AOU18RLFC
FEATUR ES
Energy saving
z
All DC design •
Heat exchange efciency increased and larger air ow by adoption of new type turbo fan •
Quiet quality
2-stage turbo fan
z
High efciency design by 2 stage structure
Wind
velocity
Fast
Slow
Previous turbo fan
In the case of a
conventional fan, the air
outlet range was narrow
as the air ow moved to
the motor side which
meant the velocit y of air
passing through the heat
exchanger was uneven.
2-stage turbo fan
A evenly spread air distribution across
the heat exchanger is possible due
to the new 2 stage turbo fan which
produces two separate airow
streams.
Heat exchange
efciency:
20%UP
1-stage
2-stage
z
Optimization of wing form (laminar
wing type) and wing number (7 blades
each)
Designed by CFD-analysis (uid) simulations
Laminar wing
Airow runs through smoothly
along the laminar wing
No airow separation
Quiet
Spin direction
Airow direction
Quiet
Adoption of laminar wing
Easy maintenance
z
Maintenance of fan motor and fan
Maintenance of the fan motor and fan can be done easily after taking off the panel as the bell mouth of the fan
can be removed easily.
A : Fan motor B : 2-stage turbo fan
C : Bell-mouth D : Panel
Long life lter
: standard equipment
Adaptation of transparent drainage parts
During installation, maintenance and operation, the drain pump and
kit can be checked easily.
Compact design
z
Easy installation by taking off ceiling panel of 23-5/8in. x 23-5/8in.(600mm x 600mm) size
High lift drain pump
z
Grille cover
Easy installation
z
- (01 - 01) -
MIN. HEAT Operation
68
°F
(20°C)
50
°F
(10°C)
“MIN. HEAT”
Button ON
Indoor unit
operation START
9ft.
(3m)
8ft.
(2.7m)
CASSETTE TYPE
AUU9-18RLF
z
CASSETTE TYPE
AUU9-18RLF
The room temperature can be set to go no lower than 50°F (10°C),
thus ensuring that the room does not get too cold when not occupied.
Caution)
When the room temperature is higher than 50°F (10°C), “ •MIN. HEAT” operation will not start. Operation starts and maintains the room
temperature at 50°F (10°C) when the temperature drops below 50°F (10°C).
When “ •MIN. HEAT” operation stops, the room set temperature quickly returns to the preset temperature.
Economy operation
z
The power consumption can be reduced.
FUNCTION SETTING
Outlet direction selection
z
Performs operation matched to the number of outlets when 4 directions are unnecessary and •
outlets are blocked when the ceiling cassette is installed in a corner, etc.
4-way direction3-way direction
Ceiling switching function
z
4-way direction mode: Set when there are 4 outlets
3-way direction mode: Set when there are 3 outlets.
(shipped state).
Air reaches sufciently up to 9ft. (3m) height, even it is compact cassette type.
Also delivers air to high ceilings by selecting the mode and raising the air ow according to the
height of the ceiling.
High ceiling (Mode 1)Standard ceiling (Standard)
Standard ...Operates at normal airow.
Mode 1 ...Airow becomes greater than normal.
Cooling room temperature correction
z
Heating room temperature correction
z
Auto restart
z
The unit will restart automatically when the current returns even when there is a power interruption
during operation.
- (01 - 02) -
REMOTE CONTROLLER2.
76°F (24°C)
0369 12 15 18 21
O'clock
12 369 12 369
time
AMPM
84°F (28°C)
0369 12 15 18 21
O'clock
12 369 12 369
time
AMPM
76°F 84°F 76°F
0 3 6 9 12 15 18 21
O'clock
12 3 6 9 12 3 6 9
time
AMPM
76°F (24°C)
84°F (28°C)
24°C 28° C 24°C
WIRED REMOTE CONTROLLER
CASSETTE TYPE
AUU9-18RLF
FEATUR ES
Various timer setup available (ON/OFF/WEEKLY). ●
Equipped with weekly timer as standard function. ●
(Start/Stop function is twice per day for a week)
When setting up the timer, start/stop and temperature setup can ●
be changed.
When a failure occurs, the error code is displayed. ●
Error history.(Last 16 error codes can be accessed.) ●
The room temperature can be controlled by detecting the ●
temperature accurately with Built-in thermo sensor.
High performance and compact size
z
CASSETTE TYPE
AUU9-18RLF
Individual
control
Accurate and comfortable
z
Thermo
sensor
Weekly
timer
Setback
timer
Indoor temperature can be detected accurately by the inclusion of a
thermo sensor in the body of the wired controller.
Our system can correspond to various scenes.
This wired remote controller and the optional remote sensor allows
exibility in sensor location, and suitable for all requirements.
Built-in timers
z
Weekly timerSetback timer
Possible to set ON/OFF time to operate twice each day of the
week.
Example : setup sc reen
(Set to Wedne sday: 8:0 0 to 20:0 0.)
Easy-to-un derst and time b ar displ ay
Screen
after setup
Possible to set temperature for two time spans and for each
day of the week.
Wired
remote
controller
Sensor part
Thermo sensor
display
Control part for
changing the
thermo sensor
Example : setup sc reen
(Set from S unday to Saturday: 12:0 0 to 15:00, 8 4°F (28°C).)
At "Weekly timer" + "Set back timer" setup
Easy-to-understand operation
z
[Variable timer control]
The operation/display sections are zoned according
to time and operation, enabling variable programming
to match application.
Timer
area
Operation
area
- (01 - 03) -
Simple installation
z
Components are compatible with standard switch
boxes. Flat back surface allows equipment to be
installed wherever it is needed.
European
switch b ox
JIS box
FUNCTIONS
15
11
10
9
8
2
1
3
5
14
4
12
13
6
7
17
16
18
19
20
21
4-23/32 (120)
4-23/32 (120)
4-23/32 (120)
23/32 (18)
Side ViewFront View
CASSETTE TYPE
AUU9-18RLF
Display panel
DIMENSION
SPECIFICATION
[Unit : in. (mm)]
1
START/STOP button
Pressed to start and stop operation.
2
SET TEMP. button
Selects the setting temperature.
3
MODE button
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY).
4
FAN button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
5
ECONOMY (THERMO SENSOR) button
Turns the economy efcient mode on and off.
6
TIMER MODE (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY
TIMER). Sets the current time.
7
DAY (DAY OFF) button
Temporarily cancels one day timer.
8
SET BACK button
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
TIMER DELETE button
Deletes the weekly timer schedule.
11
TIMER SET button
Sets the date, hour, minute and on-of f time.
12
Verticalairowdirectionandswingbutton
Push for two seconds to change the swing mode.
13
Horizontalairowdirectionandswingbutton
Push for two seconds to change the swing mode.
14
FILTER RESET button
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
Operation mode display
18
Fan speed display
19
Operation lock display
20
Temperature display
21
Function display
Defrost display
Thermo sensor display
Economy display
Vertical swing display
Horizontal swing display
Filter display
CASSETTE TYPE
AUU9-18RLF
SIZE [H x W x D]: in.(mm)
WEIGHT oz. (g)5.6 (160)
CABLE LENGTH ft. (m)33 (10)
POWER (V)12
WIRING SPECIFICATIONS
UseCable sizeWire typeRemarks
4-23/32 x 4-23/32 x 23/32
(120 x 120 x 18)
22AWG
Remote controller cable
(0.33 mm
2
)
- (01 - 04) -
Functions will be different due to type of indoor unit.
For details, please see operation manual.
Polar 3 coreUse sheathed PVC cable
SPECIFICATIONS3.
Typ e
CASSETTE TYPE
AUU9-18RLF
Model na meAUU9RL FAUU12 RLFAUU18R LF
Power sour ce208 / 230 V ~ 60Hz
Availabl e boltag e range187 - 253V ~ 60 Hz
Cooling
Capacity
Heating
Input pow er
Current
EERCooling
COPHeating
SEERCoolingBtu/hW24.0 21. 9 20.1
HSPFHeatingBtu/hW13 .0 12.2 11.5
Power fac tor
Moistu re removalpints/ h (l/h)1.3 (0. 6)2.5 (1.2)4.6 (2.2)
Maximum operating current *
Fan
Sound pr essure l evel
Heat excha nger ty pe
Dimensions
(H × W × D)
Weight
Connec tion pi pe
Operat ion rang e
Remote co ntroll er typeWired [ Wirel ess(opti on)]
Note :
Specications are based on the following conditions.
Cooling : Indoor temperature of 80°F (26.67°C) DB / 67°F (19.44°C) WB, and outdoor temperature of 95°F (35°C) DB / 75°F (23.9°C) WB.
Heating : Indoor temperature of 70°F (21.11°C) DB / 59°F (15°C) WB, and outdoor temperature of 47°F (8.33°C) DB / 43°F (6.11°C) WB.
Pipe length : 24ft.7in (7.5m), Height difference:0 m. (Outdoor unit-Indoor unit)
The protective function may work when using it outside the operation range.
*: The max imum cur rent is the m aximum v alue when o perate d within t he opera tion ran ge.
- (01 - 05) -
DIMENSIONS4.
(Drain hose)
20-7/8 (530): Hanging bolt position
4-1/32 (102)
5-5/16
(135)
9-27/32 (250)
27-9/16 (700)
27-9/16 (700)
2-15/16 (75)
1-3/16 (30)
1-3/16 (30)
10-5/16 (262)
21-1/4 (540): Hanging bolt position
Ƒ,QGRRUXQLW
ƑWRWR
: Ceiling openings
&DVVHWWHJULOOHPRXQWLQJVWDWH
Top view
5-29/32 to 7-7/8 (150 to 200)Min. 17-23/32 (450)
Min. 17-23/32 (450)
Maintenance space
6LGHYLHZ
8-15/32 (215)
4-27/32 (123)
2-9/32 (58)
4-1/2 (114)
5-3/4 (146)
4-1/4
(108)
4-1/32 (102)
9-21/32 (245)
1-3/16 (30)
1-9/16 (40)
3-29/32 (99)
Drain port
Control box
Ceiling
Drain port
Be sXre to leave
maintenance space
for fXtXre service
at the GesignateG
position.
Bottom view
1-3/16 (30)
1-15/16 (49)
6LGHYLHZ
MODEL : AUU9RLF, AUU12RLF, AUU18RLF
CASSETTE TYPE
AUU9-18RLF
Unit : in.(mm)
CASSETTE TYPE
AUU9-18RLF
AUU9RLF, AUU12RLFAUU18RLF
Refrigerant pipe are
connection
Drain hose connectionDrain hoseI.D. Ø3/4 in. , O.D. Ø1-1/16 in.
LiquidØ1/4 in. (Ø6.35 mm)Ø1/4 in. (Ø6.35 mm)
GasØ3/8 in. (Ø9.52 mm)Ø1/2 in. (Ø12.70 mm)
- (01 - 06) -
CASSETTE TYPE
39-3/8 (1000)
or more
39-3/8 (1000)
or more
94-1/2 (2400)
or more
10-5/16 (262)
or more
Strong and durable ceiling
Obstruction
Floor
3-15/16 (100) or more
*
AUU9-18RLF
INSTALLATION PLACE
Unit : in. (mm)
CASSETTE TYPE
AUU9-18RLF
H
H (The maximum height from oor to
ceiling) Unit: in. (mm)
Model nameAUU9AUU12AUU18
Standard mode
106 -5/16
(2700)
High Ceiling mode-
106 -5/16
(2700)
118 -1/8
(3000)
106 -5/16
(2700)
118 -1/8
(3000)
3-way directions setting
z
To set “3-way directions”, the air outlet shutter plate (UTR-YDZB) sold separately must be
installed and “outlet-direction” switched to “3-way” by remote controller.
*When installing the indoor unit, be careful about the maintenance space.