Compressor frequency decides by capacity of an indoor unit, operation number of an indoor unit,
set temperature, room temperature and outside temperature.
2. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum
mode from among the Heating, Cooling, Dry and Monitoring mode.
During operation, the optimum mode is automatically switched in accordance with temperature changes.
The temperature can be set between 64°F(18°C) and 86°F(30°C) in 2°F(1°C) steps.
When operation starts, indoor fan and outdoor fan are operated for around 3 minutes.
ձ
Room temperature and outdoor temperature are sensed,
and the operation mode is selected in accordance with the table below. <Monitoring mode>
( Table 1 : Operation mode selection table )
Room temperature (TR)
TR> Ts+4°F(+2°C)
Operation mode
Cooling
(Autmatic dry)
TR : Room temperature
Ts : Setting temperature
Ts+4°F(+2°C) TR Ts -4°F(-2°C)
TR < Ts -4°F(-2°C)Heating
*Middle zone
*If it's Middle zone, operation mode of indoor unit is selected as below.
( 1 ). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling, Dry, and Heating mode,
indoor unit will be operated by the same operation mode.
( 2 ). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling, Dry, and Heating mode,
indoor unit will be operated according to the outdoor temperature as below.
( Fig. 1 : Outdoor temperature zone selection )
Cooling mode
77°F (25°C)
Heating mode
ղ
When Heating was selected at ձ, the same operation as HEATING OPERATION of
page 01-08 is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control
ճ
functionafter the Cooling(Auto:Dry) or Heating mode was selected at above,
operation is switchedto Monitoring and the operation mode is selected again.
01-01
AUTO CHANGEOVER operation flow chart
START
Ts : Setting temperature
HEATING OPERATION
YES
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
YES
YES
Room temp.
Ts+4°F(+2°C)?
NO
Room temp.
Ts -4°F(-2°C)?
NO
Middle zone
Operation mode
of outdoor unit : Cooling or Dry?
NO
Operation mode
of outdoor unit : Heating?
NO
YES
YES
COOLING (AUTO:DRY)
OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
YES
YES
System stops
or operation command other than
auto changeover operation?
NO
YES
Outdoor temp.
77°F(25°C)?
NO
01-02
System stops
or operation command other than
auto changeover operation?
NO
YES
3. INDOOR FAN CONTROL
1. Fan speed
( Table 2 : Indoor fan speed table )
ASU7RLF1
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Poweful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Poweful
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(rpm)
Fan Speed
1090
1050
1000
950
850
710
600
480
1090
1050
950
850
680
600
480
X, J zone : 680
ASU9RLF1(rpm)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Poweful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Poweful
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
Fan Speed
1140
1090
1040
980
850
710
600
480
1140
1090
980
850
680
600
480
X, J zone : 680
ASU12RLF1
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Poweful
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Poweful
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
X, J zone : 680
(rpm)
Fan Speed
1240
1190
1120
1050
910
710
600
480
1240
1190
1050
880
680
600
480
*Note, during Economy operation and operation mode is Fan,airflowis 1stepdowns.
(Hi > Me, Me > Lo, Quiet > Soft Quiet)
01-03
ASU18RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(rpm)
Fan Speed
1260
1120
1020
900
790
680
480
1260
1020
900
770
680
480
X, J zone : 770
ASU24RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
X, J zone : 900
(rpm)
Fan Speed
1430
1320
1220
1020
900
720
480
1480
1220
1020
900
720
480
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Quiet > Soft Quiet)
01-04
AGU9RLF
Operation modeAir flow mode
Heating
Cooling/ Fan
Dry
Powerful
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
Speed
Upper & Lower
air flow mode
1230/ 1040
1120/ 950
1000/ 850
860/ 730
660/ 560
660/ 560
660/ 560
1230/ 1040
1120/ 950
960/ 820
820/ 700
660/ 560
570/ 480
660/ 560
---- / ----
(rpm)
Upper
air flow mode
1300
1230
1090
940
750
680
680
1300
1230
1070
910
750
680
680
X, J zone : 750
AGU12RLF
Operation modeAir flow mode
Heating
Cooling/ Fan
Dry
Powerful
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
AGU15RLF
Operation modeAir flow mode
Heating
Cooling/ Fan
Dry
Powerful
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
Powerful
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
Speed
Upper & Lower
air flow mode
1350/ 1150
1240/ 1040
1080/ 920
910/ 770
660/ 560
660/ 560
660/ 560
1350/ 1150
1240/ 1040
1050/ 890
860/ 730
660/ 560
570/ 480
660/ 560
---- / ----
Speed
Upper & Lower
air flow mode
1440/ 1230
1330/ 1120
1140/ 970
940/ 800
660/ 560
660/ 560
660/ 560
1440/ 1230
1330/ 1120
1100/ 930
890/ 750
660/ 560
570/ 480
660/ 560
---- / ----
(rpm)
Upper
air flow mode
1370
1300
1140
980
750
680
680
1370
1300
1120
930
750
680
680
X, J zone : 750
(rpm)
Upper
air flow mode
1440
1370
1180
1020
750
680
680
1440
1370
1160
960
750
680
680
X, J zone : 750
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Quiet > Soft Quiet)
01-05
AUU7RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(rpm)
Fan Speed
590
570
540
490
440
400
300
590
540
490
440
400
300
X, J zone : 440
AUU9RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(rpm)
Fan Speed
590
570
540
490
440
400
300
590
540
490
440
400
300
X, J zone : 440
AUU12RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
X, J zone : 460
(rpm)
Fan Speed
650
620
580
520
460
400
300
660
580
520
460
400
300
AUU18RLF
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me+
Me
Lo
Quiet
Cool Air Prevention
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Quiet > Soft Quiet)
(rpm)
Fan Speed
840
800
750
650
500
400
300
790
660
570
460
400
300
X, J zone : 460
01-06
ARU7RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(rpm)
Fan Speed
1160
1000
940
880
500
1160
1000
940
880
500
500
X, J zone : 880
ARU9RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(rpm)
Fan Speed
1260
1160
1060
960
500
1260
1160
1060
960
500
500
X, J zone : 960
ARU12RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
ARU24RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo
Auto
(rpm)(rpm)
Fan Speed
1340
1240
1140
1030
500
1340
1240
1140
1030
500
500
X, J zone :1030
(rpm)
Fan Speed
1460
1360
1260
1180
600
1460
1360
1260
1180
600
600
X, J zone :1180
ARU18RLF (Static pressure:25Pa)
Operation mode
Heating
Cooling / Fan
Dry
Air flow mode
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
S-Lo600
Auto
Fan Speed
1380
1300
1220
1140
600
1380
1300
1220
1140
600
X, J zone :1140
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Quiet > Soft Quiet)
01-07
2. FAN OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on (Me) Fan Speed.< All models >
3. COOLING OPERATION (Auto : Cooling)
Switch the airflow [Auto], and the indoor fan will run according to a room temperature,
as shown in Fig. 2 .
On the other hand, if switched in [Hi]〜[Quiet], the indoor fan will run at a constant airflow of [Cooling]
operation modes Quiet, Lo, Me, Hi.
( Fig. 2 : Airflow change - over )
< All models >
When the room
temperature rises
TR-Ts > +5
+5
(+2.5°C)
(+1.5°C)
°F
=
(+2.5°C)
°F > TR-Ts > +3°F
=
°F > TR-Ts
+3
=
=
(+1.5°C)
TR : Room temperature
Ts : Setting temperature
TR-Ts > +4°F
°F > TR-Ts > +2°F
+4
=
(+2°C)
°F > TR-Ts
+2
(+1°C)
When the room
temperature drops
=
(+2°C)
=
(+1°C)
=
Hi
Me
Lo
4. DRY OPERATION (Auto : Dry)
During the dry operation, the fan speed setting can not be changed, it operates automatically as shown in Fig. 3 .
Room temperature variation which the room temperature sensor of the indoor unit body has detected.
( Fig. 3 : Indoor fan control )
< All models >
< Compressor >
ON
OFF
< Indoor fan air flow mode >
Setting air flow
S-Lo
Fan OFF
1030601806018060 1030(sec)
01-08
5. HEATING OPERATION (Auto : Heating)
Switch the airflow [Auto], and the indoor fan will run according to a room temperature,
as shown in Fig. 4 .
On the other hand, if switched in [Hi] [Quiet], the indoor fan will run at a constant airflow
of [Heat] operation modes Quiet, Lo, Me, Hi, as shown in Table 2 .
( Fig. 4 : Airflow change - over )
< ASU type >
When the room
temperature drops
TR-Ts > -3°F
-3
(-1.5°C)
-5
(-2.5°C)
When the room
temperature drops
TR-Ts > -3°F
-3
(-1.5°C)
(-2.5°C)
=
(-1.5°C)
°F > TR-Ts > -5°F
=
(-2.5°C)
°F > TR-Ts
=
(-1.5°C)
°F > TR-Ts > -5°F
-5
°F > TR-Ts
=
(-2.5°C)
TR-Ts > -2
°F > TR-Ts > -4°F
-2
=
(-1°C)(-2°C)
°F > TR-Ts
-4
=
(-1°C)
°F
(-2°C)
=
(-1°C)
(-2°C)
°F
TR-Ts > -2
°F > TR-Ts > -4°F
-2
=
(-1°C)
°F > TR-Ts
-4
(-2°C)
When the room
temperature rises
Lo
Me
Me+
< AGU/ AUU/ ARU type >
When the room
temperature rises
Lo
Me
Hi
TR : Room temperature
Ts : Setting temperature
6. COOL AIR PREVENTION CONTROL (For Heating and Minimum Heat operation)
The maximum value of the indoor fan speed is set as shown in Fig. 5 , based on the detected
temperature by the indoor heat exchanger sensor in heating mode.
Field setting is necessary at AU and AR type as "Cool air prevention : effective"
( Fig. 5 : Airflow change - over for cool air prevention )
During NORMAL HEATING OPERATION
< ASU type >
When Indoor heat exchanger
temperature rises
107.6°F
(42°C)
102.2
(39°C)
98.6
(37°C)
86
(30°C)
°F
°F
°F
*Me+ or setting
FAN mode
*Lo or setting
FAN mode
Cool air
prevention
S-Lo
*Lower speed is selected
When Indoor heat exchanger
temperature drops
Hi
98.6
(37°C)
93.2
(34°C)
89.6
(32°C)
82.4
(28°C)
°F
°F
°F
°F
When Indoor heat exchanger
temperature rises
107.6°F
(42°C)
102.2°F
(39°C)
98.6°F
(37°C)
86.0°F
(30°C)
< AGU type>
When Indoor heat exchanger
temperature drops
Hi
*Me or setting
FAN mode
*Lo or setting
FAN mode
Cool air
prevention
S-Lo
*Lower speed is selected
93.2°F
(34°C)
87.8°F
(31°C)
84.2°F
(29°C)
75.2°F
(24°C)
01-09
< AUU type >
< ARU type >
When Indoor heat exchanger
temperature rises
107.6°F
(42°C)
102.2°F
(39°C)
98.6°F
(37°C)
86.0°F
(30°C)
*Me+ or setting
FAN mode
*Lo or setting
FAN mode
When Indoor heat exchanger
temperature drops
Hi
Cool air
prevention
S-Lo
98.6°F
(37°C)
93.2°F
(34°C)
89.6°F
(32°C)
75.2°F
(24°C)
*Lower speed is selected
During MININIMUM HEAT OPERATION
< ASU / AUU type >
When Indoor heat exchanger
temperature rises
102.2°F
(39°C)
When Indoor heat exchanger
temperature drops
Auto
Lo
93.2°F
(34°C)
When Indoor heat exchanger
temperature rises
*Hi or setting
98.6°F
(37°C)
84.2°F
(29°C)
FAN mode
*Lo or setting
FAN mode
S-Lo
*Lower speed is selected
< AGU type >
When Indoor heat exchanger
temperature rises
102.2°F
(39°C)
Auto
Lo
When Indoor heat exchanger
temperature drops
89.6
°F
(32°C)
75.2
°F
(24°C)
When Indoor heat exchanger
temperature drops
87.8°F
(31°C)
< ARU type >
When Indoor heat exchanger
temperature rises
98.6°F
(37°C)
Auto
Lo
When Indoor heat exchanger
temperature drops
89.6°F
(32°C)
01-10
4. LOUVER CONTROL
For Compact Wall Mounted Type < ASU7/ 9/ 12RLF1 >
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow :
( Fig. 6 : Vertical air direction range )
ձ
ղ
ճ
մ
յ
ն
շ
Use the air direction adjustments within the ranges shown above.
The Remote Controller's display does not change.
If you set the angle to position
DRY mode, they automatically return to position
In COOL or DRY mode, if the angle is set to position
մ㹼շ for more than 30 minutes in COOL or
ճ.
մ㹼շ for many hours,
condensation may be formed, and the drips may wet your property.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode
Horizontal flow
Heating modeDownward flow
During AUTO or Heating mode operation, for the first a few minutes after beginning operation,
air flow will be horizontal
The air flow direction setting will temporarily become
ձ ; the air direction cannot be adjusted during this period.
ձ when the temperature of the air flow is
low at the start of the Heating mode.
2. SWING OPERATION
To select Vertical Airflow Swing Operation
When the swing signal is received from the remote controller, the vertical louver starts to swing.
( Table 3 : Swinging range )
The type of operation
Cooling / Dry / Fan mode
Heating / Fan mode
Range
ձ
մճշ
The SWING operation may stop temporarily when the air conditioner’s fan is not operating,
or when operating at very low speeds.
To select Horizontal Airflow Swing Operation
(No function)
01-11
For Wall Mounted Type < ASU18/ 24RLF >
1. VERTICAL LOUVER CONTROL
( Fig. 7 : Vertical air direction range )
(Function Range)
Each time the button is pressed, the air direction range will change as follow :
ձղճմյն
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown,
in accordance with the type of operation selected.
Cooling / Dry mode : Horizontal flow ձ
ձ
ղ
ճ
մ
յ
ն
Heating mode : Downward flow յ
When the temperature of the air being blown out is low at the start of heating operation or during
defrosting, the airflow direction temporarily becomes ձ to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
range ( մ㹼ն ) for long period of time, since water vapor many condense near the outlet louvers and
drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow
Direction Louvers are left in the heating range for around 20 minutes, they will automatically return to position ճ.
2. HORIZONTAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow :
ձ ղ ճմյ
( Fig. 8 : Horizontal air direction range )
3. SWING OPERATION
Vertical Airflow Swing Operation
When the swing signal is received from the remote controller,
the vertical louver starts to swing.
( Table 4 : Swinging range )
The type of operation
Cooling / Dry / Fan mode ( ձ㹼ճ )
Heating / Fan mode ( մ㹼շ )
Range
ձ
մ
ճն
ձ
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted
and it stops at either upper end or bottom end.
Horizontal Airflow Swing Operation
When the swing signal is received from the remote controller, the horizontal louver starts to swing.
( Table 5 : Swinging range )
RangeThe type of operation
Cooling / Dry / Heating / Fan mode
ձ
յ
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted
and it stops at either upper end or bottom end.
Vertical and Horizontal Airflow Swing Operation
When the horizontal swing signal is input from remote control, the combination of the vertical
and horizontal swing operation is performed.
Horizontal Louver
ղ
ճմ
յ
Power Diffuser doesn't swing in any swing operation.
01-12
For Floor Type < AGU9/ 12/ 15RLF >
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow :
The Remote Controller's display does not change.
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown,
in accordance with the type of operation selected.
( Fig. 9 : Air direction range )
Cooling / Dry / Fan mode
Heating mode
When the temperature of the air being blown out is low at the start of heating operation or during
defrosting, the airflow direction temporarily becomes
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically
becomes
䐟
, and it cannot be adjusted.
Horizontal flow
Downward flow
䐟㻌
to prevent cold air being blown onto the body.
2. ADJUST THE RIGHT-LEFT LOUVERS
Move the Right-Left louvers to adjust airfow in the direction you prefer.
( Fig. 10 : Air direction range )
3. SWING OPERATION
To select Vertical Airflow Swing Operation
When the swing signal is received from the remote controller, the vertical louver starts to swing .
( Table 6 : Swinging range )
Cooling / Dry / Heating / Fan mode
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrrupted
and it stops at either upper end or bottom end.
To select Horizontal Airflow Swing Operation
(No function)
RangeThe type of operation
ձ
01-13
յ
For Compact Cassette Type < AUU7/ 9/ 12/ 18RLF >
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow :
( Fig. 11 : Vertical air direction range )
1
2
3
4
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode : Horizontal flow ձ
Heating mode : Downward flow մ
During AUTO mode operation, for the first minute after start-up, air-flow will be horizontal ձ
the air direction cannot be adjusted during this period.
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
The range of swing depends on the set airflow direction.
( Table 7 : Swinging range )
RangeThe type of operation
Cooling / Dry / Heating / Fan mode
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted
and the louver stops at
the memorized position.
(Stop mode means Operation stop.)
ձ
մ
01-14
5. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
The Table 5 shows the fan speed of the outdoor unit.
( Table 8 : Fan speed of the outdoor unit )
Cooling
AOU36RLXFZH
AOU45RLXFZ
7. COMPRESSOR CONTROL
6. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 9 .
( Table 9 : Compressor operation frequency range )
AOU36RLXFZH
AOU45RLXFZ
2. OPERATION FREQUENCY CONTROL AT START UP
2.
The compressor frequency soon after the start-up is controlled as shown in the Fig. 12 .
The Table 10 shows the available timer setting based on the product model.
( Table 10 : Timer setting )
ON TIMER / OFF TIMERPROGRAM TIMERSLEEP TIMER
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Stop mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest
to the clock's current timer setting.
The order of operations is indicated by the arrow in the remote control unit's display.
Operation mode
Operation mode
Stop mode
Stop mode
Set timeSet timeSet timeSet time
SLEEP timer operation cannot be combined with ON timer operation.
01-16
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically.
If the operation mode or the set temperature is change after the sleep timer is set, the operation is
continued according to the changed setting of the sleep timer from that time ON.
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 2°F(1°C).
It increases the setting temperature another 2°F(1°C) after 1 hour.
After that, the setting temperature is not changed and the operation is stopped at the time
of timer setting.
Set temperature rises
( Ts : Set temperature )
+4°F (+2°C)
+2°F (+1°C)
Ts
Stop of operation
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 2°F(1°C).
It decreases the setting temperature another 2°F(1°C) every 30 minutes.
Upon lowering 8°F(4°C), the setting temperature is not changed and the operation stops at
the time of timer setting.
Set temperature lowers
( Ts : Set temperature )
Ts
-2 F(-1 C)
-4 F(-2 C)
-6 F(-3 C)
-8 F(-4 C)
Stop of operation
Set
30min
30min
30min
01-17
7-2 WIRED REMOTE CONTROLLER
The Table 11 shows the available timer setting based on the product model.
( Table 11 : Timer setting )
ON TIMER / OFF TIMERWEEKLY TIMERTEMPERATURE SET BACK TIMER
1. ON TIMER / OFF TIMER
Same to 6-1 ON / OFF TIMER and shown in those.
2. WEEKLY TIMER
This timer function can set operation times of the each day of the week.
All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
ONOFFONOFFONOFF
Setting daySetting daySetting day
Set timeSet time
3. TEMPERATURE SET BACK TIMER
This timer function can change setting temperature of setting operation times of the each day of the week.
s can be together with other timer setting.
Thi
Set back tmp.
Normal tmp.
ON
Set timeSet time
OFF
01-18
8. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the Table 13 .
The compressor frequency, the temperatures detected by the discharge temperature sensor
and the outdoor temperature sensor.
( Table 12 : The pulse range of the electronic expansion valve control )
Operation modePulse range
AOU36RLXFZH
AOU45RLXFZ
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (825 pulses are input to the closing direction).
Cooling /Dry mode
Heating mode
50 ~ 480
30 ~ 480
9. TEST OPERATION CONTROL
With Wireless Remote Controller ( with TEST RUN button )
Under the condition where the air conditioner runs, press the TEST RUN button, and
the test operation control mode will appear.
During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
Set the test operation mode, and the compressor will continue to run regardless of whether the room
temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller ( without TEST RUN button )
Under the condition where the air conditioner runs, press the MANUAL AUTO button of the
indoor unit for more than 10 seconds.
During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
Set the test operation mode, and the compressor will continue to run regardless of whether the room
temperature sensor detects.
The test operation mode is released, if 60 minutes have passed after setting up the test operation
or pressing the MANUAL AUTO button of the indoor unit for more than 3 seconds.
With Wired Remote Controller ( without TEST RUN button )
Under the condition where the air conditioner stops, press the MASTER CONTROL button and
the FAN CONTROL button simultaneously for 5 seconds or more, and the test operation control
mode will appear.
During test running, " " will display on the remote controller display.
Set the test operation mode, and the compressor will continue to run regardless of whatever
the room temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
Outdoor unit TEST RAN operation
It can carry out test run from the outdoor unit (Refer to 30.TEST RUN (For Outdoor unit)”)
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 3 minutes after the compressor is stopped,
even if any operation is given.
11. 4-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the Cooling mode to Heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.
01-19
12. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
( Table 13 : Operation contents memorized when the power is interrupted )
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup.
Refer to the installation manual of wired remote controller for details.
13. MANUAL AUTO OPERATION
If MANUAL / AUTO Button is pushed continuous from 3 seconds to 10 seconds,
manual auto operation will starts.
If the remote control is lost or battery power dissipated, this function will work without the remote control.
When the outdoor temperature is lower than 28.4°F(-2°C) and the all operation mode has been
stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started and when the outdoor temperature rises to 25°C or greater,
preheating is ended.
( Fig.13 : Compressor preheating )
OFF
32°F(0°C)
28.4°F(-2°C)
ON
15. POWERFUL OPERATION ( For ASU*RLF1/ AGU*RLF type )
The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller.
The indoor unit & outdoor unit will operate at maximum power as shown in Table 15 .
( Table 15 : Powerful operation)
COMPRESSOR FREQUENCYMaximum
FAN CONT. MODEPowerful
SETTING LOUVER
Cooling/ Dry : 3, Heating : 6 for ASU*RLF1
Cooling/ Dry : 4, Heating : 5 for AGU*RLF
Release Condition is as follows.
[Cooling / Dry]
- Room tenperature< Setting temperature -3.0°F(- 1.5°C) or Operation time has passed 20 minutes.
[Heating]
- Room tenperature> Setting temperature +3.0°F(+1.5°C) or Operation time has passed 20 minutes.
=
=
16. MINIMUM HEAT OPERATION
MINIMUM HEAT operation performs as below when pressing MIN. HEAT button or
Weekly timer setting on the remote controller.
( Table 16 : Minimum heat operation )
Mode Heating
Settingtemperature50°F(10°C)
FanmodeAuto
LEDdisplayEconomy
Defrost operationOperate as normal
17. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation
for cooling and heating.
The ECONOMY operation is almost the same operation as below settings.
. HEAT INSULATION CONDITION ( BUILDING INSULATION )
This setting can make the room temperature control more suitable for homes or buildings
with high insulation (Function Number 95).
When the thermo sensor is turned ON it controls the compressor frequency at
initial start to prevent overshoot in heating or cooling.
19
. THERMO CONTROL ( FOR INDOOR UNIT SENSOR )
When room temperature is controlled by the Indoor unit sensor, compressor operation
is as shown in Fig. 14 and 15.
But, adjustment is possible by the room temperature correction function setting.
(Function Number 30 or 31)
( Fig. 14 : For Cooling operation )
Compressor ON
Ts - 1°F
(Ts - 0.5°C)
Ts : Setting temperature
20
. THERMO CONTROL ( FOR WIRED REMOTE SENSOR )
Compressor OFF
Ts + 1°F
(Ts + 0.5°C)
( Fig. 15 : For Heating operation )
Compressor OFF
Ts + 1°F
(Ts + 0.5°C)
Compressor ON
When room temperature is controlled by the Wired remote sensor, compressor
operation is as shown in Fig. 16 and 17.
But, adjustment is possible by the room temperature correction function setting.
(Function Number 92 or 93)
( Fig. 16 : For Cooling operation )( Fig. 17 : For Heating operation )
Compressor ON
Compressor OFF
Ts - 1°F
(Ts - 0.5°C)
Ts- 1°F
(Ts - 0.5°C)
Ts : Setting temperature
Compressor OFF
Ts
Ts+ 1°F
(Ts + 0.5°C)
Ts
Compressor ON
01-22
21.BASE HEATER OPERATION ( For AOU36RLXFZH )
The base heater is operated as shown in Fig. 18 .
( Fig. 18 : Base heater control )
When outdoor
temperature drops
36°F
(2°C)
When the compressor stops, Base heater is OFF.
When the outdoor fan motor stops, Base heater is OFF.
In the cooling mode, Base heater is OFF.
In the defrost operation, Base heater maintains the same status as before the compressor stops.
When outdoor
temperature rises
OFF
41°F
(5°C)
ON
22. FRESH AIR CONTROL ( For AU type )
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as shown in Fig. 19 .
( Fig. 19 : Fresh air control )
Fan motor
(Indoor unit)
Fan motor
(for Fresh Air)
Operation
Stop
Operation
Stop
*It needs the external relay and power supply.
23. EXTERNAL ELECTRICAL HEATER CONTROL ( For AR type )
The External Electrical Heater is operated as below.
< Heater : O
When all of the following conditions are met, external elecrtical heater will operate according to Fig. 20 .
< Heater : OFF condition >
1). When one of the ON conditions is not met.
2). When Defrost operation or Oil recovery operation starts
N condition >
( Table 18 : External electrical heater control )
System type
Operation mode
Compressor
Indoor fan
Heatpump
Heating
ON
ON (S-Lo is excluded)
( Fig. 20 : External electrical heater control )
When the room
temperature drops
Ts -6°F(3°C)
Ts -22°F(12°C)
Heater : OFF
Heater : ON
Heater : OFF
When the room
temperature rises
Ts : Setting temperature
Ts -2°F(1°C)
Ts -18°F(10°C)
01-23
24. DRAIN PUMP OPERATION ( For AU / AR type )
During Cooling / Dry mode
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Anti- freezing protection", the drain pump is turned off
in 1 hour after the compressor stops.
4. When the water level in the drain pan rises up and then the float switch functi
1
The compressor, indoor and outdoor fan motor operation are stopped.
2
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
3
The indoor unit fan motor operates after the float switch is turned off.
5. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
(It is necessary to turn off power for release it. )
6. When the float switch turns OFF less than 3 minutes, the unit starts Cooling operation.
( Fig. 21 : Detail of drain pump operation in Cooling / Dry )
Compressor
Drain Pump
ON
OFF
ON
OFF
3 minutes
ons:
<Float Switch turns OFF less than 3 minutes>
Less than 3 minutes
Float Switch
Compressor
Indoor Fan
Drain Pump
ON
OFF
ON
OFF
3 minutes ST
ON
OFF
ON
OFF
3 minutes
During HEATING / FAN mode / Stop operation
1. When the water level in the drain pan rises up and then the float switch functions:
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
Thereafter, even if the float switch turns OFF, the "FAILURE INDICATION" is not released.
(It is necessary to turn off power for release it. )
( Fig. 22 : Detail of drain pump operation in Heating )
Float Switch
Drain Pump
ON
OFF
ON
OFF
3 minutes
01-24
25. AIR OUTLET SELECTION ( DAMPER CONTROL )( For AG type )
With this function , air come out simultaneously from the upper and lower air outlets so that
the room can be cooled or heated effectively.
This function is set using the switch behind the front grille of the Indoor unit.
(This function is available in cooling and heating operation.)
1. How to set to blow out air from the upper and lower air outlets
Set the air outlet selection switch to
Air blows out automatically from the upper and lower air outlets as shown in Table 19 below.
NOTE: Set the air outlet selection switch to the end.
Otherwise, air outlet cannot be selected as intended.
2. Description of operation
( Table 19 : Damper control )
OperationCOOLING ModeDRY ModeHEATING Mode
Air flow
Conditions
Upper and lower
air flow
Room temperature and set temperature are different.
Upper air flowUpper air flow
only
Room temperature is close to set
temperature,*1 or
the air conditioner
has operated for
1hour.
_
Upper and lower
air flow
Air flow temperature is high.
*1 : In Cooling mode*2 : In Heating mode
When the room
temperature drops
TR-Ts > 4°F
=
(2°C)
TR-Ts < 4°F
(2°C)
TR : Room temperature Ts : Setting temperature
Upper & Lower
air flow
Upper air flow
When the room
temperature rises
TR-Ts >14°F
TR-Ts < 14°F
=
(7°C)
(7°C)
When the room
temperature drops
84.2°F
(29°C)
Upper & Lower
air flow
Upper air flow
Upper air flow
Air flow temperature is low.*2
(During defrosting operation,
start of operation,
etc.)
When the room
temperature rises
98.6°F
(37°C)
3. How to set to blow out air from the upper air outlet only
Set the air outlet selection switch to
01-25
26. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects
the temperature lower than the values shown in Table 20, 21, 22 .
1-1 NORMAL DEFROST
( Table 20 : Condition of starting defrost operation )
Normal defrost
Tn
: Outdoor heat exchanger temp.
Ta
: Outside air temp.
: Before 5 minutes detected Tn
Tn-1
Less than 35 minutes
Does not operate
Sn
Sn-1
Compressor integrating operation time
More than 35minutes
Tn < 1.4°F(-17°C)
=
(at Ta > 14°F(-10°C)
Tn < 0.8 ×Ta - 11.6
=
(at 4°F(-20°C) < Ta < 14°F(-10°C))
Tn < 0.8 ×Ta - 11.6
=
(at Ta < 4°F(-20°C))
Tn - Tn-1 < 28.4°F(-2°C) and Sn = Sn-1
(Tn < 21.2°F(-6°C))
: Number of operation indoor units
: Before 5 minutes detected Sn
=
or Tn < -18.4°F(-28°C)
=
or Tn < -18.4°F(-28°C)
=
=
=
1-2. INTEGRATING DEFROST
( Table 21 : Condition of integrating defrost operation )
Integrating defrost
( OFF count defrost )
Tn < 26.6°F(-3°C)
(and after 30 minutes,
if the Tn < 26.6°F(-3°C)
Compressor integrating operation time
More than 210 minutes
( For continuous operation )
=
=
Tn < 23°F(-5°C)
(and after 3 minutes,
if the Tn < 23°F(-5°C)
1-3. INTEGRATING ( OFF COUNT ) DEFROST
( Table 22 : Condition of integrating ( OFF count ) defrost operation )
Integrating defrost
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
Compressor integrating operation time
Less than 10 minutes
( For intermittent operation )
OFF count of the compressor 40 times
( at outside air temp. < 35.6°F(2°C))
=
=
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 23 .
( Table 23 : Defrost release condition )
Outdoor heat exchanger temperature sensor value is higher than 59°F(15°C) or
Compressor operation time has passed 15 minutes.
Release Condition
01-26
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
Heating operation start : Compressor ON
Ta > 14°F(-10°C)
=
Tn < 1.4°F(-17°C)
=
Tn
: Outdoor heat exchanger temp.
Ta
: Outside air temp.
: Before 5 minutes detected Tn
Tn-1
: Number of operation indoor units
Sn
: Before 5 minutes detected Sn
Sn-1
4°F(-20°C) < Ta < 14°F(-10°C)
Tn < 0.8 ×Ta - 11.6
=
Tn < -18.4°F(-28°C)
=
Normal defrostIntegrating defrostIntegrating defrost
=
oror
Ta < 4°F(-20°C)
Tn < 0.8 ×Ta - 11.6
=
Tn < -18.4°F(-28°C)
=
Tn < 21.2°F(-6°C) More than 210 minutes
=
Tn - Tn-1 < 28.4°F(-2°C)
and Sn = Sn-1
( For continuous operation )
Tn < 26.6°F(-3°C)
(and after 30 minutes,
if the Tn < 26.6°F(-3°C)
or
Tn < 23°F(-5°C)
(and after 3 minutes,
if the Tn < 23°F(-5°C)
(Integrating OFF count defrost)
Compressor OFF count :
40 times
(Less than 10 minutes)
Defrost start
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec O FF
3 sec later Compressor : OFF
3 sec later Outdoor fan motor : OFF
35sec later 4WAY valve : OFF
41sec later Compressor : ON
Outdoor HEX temp. : Over 59°F(15°C)
or
Compressor ON time : Maximum 15 minutes
Defrost end
01-27
27. CHECK RUN OPERATION (AUTOMATIC WIRING CORRECTION)
If there is a mis-wiring after check operation, switch the indoor unit port automatically on the microcomputer.
(Check operating time)
-Cooling : 30min (Time of approximately)
-Heating : 60min (Time of approximately)
Operating procedure for check run
NOTE : Be sure that the power is turend ON before starting the check run.
(1) Press the “CHECK” swtich for 3 seconds or more.
CHECK
SW2
The positions of the swtiches on the outdoor unit
control board are shown in the right.
(2) The number of indoor units ( and the places ) connected through the communication lines is displayed.
・
If the displayed number of units ( places ) and the installed number of units ( places ) is the same,
proceed to step (3).
・
If the displayed number of units ( places ) and the installed number of units (places ) is not the same,
shut off the power and check whether the indoor and outdoor communication lines are properly connected.
・
If there is no operation for 1 minute, the LED will return to the original display.( POWER / MODE LED : ON )
(3) Press the “CHECK” switch for 3 seconds or more again. Check run is initiated.
When check run is initiated, all LEDs from A to F will flash. ( Preliminary operation )
The LED for each indoor unit will switch off in order as check for each unit is completed.
To interrupt the check run, press the “CHECK” switch.
Example) When 4 indoor units ( A to D ) are connected.Example) When 4 indoor units ( A to D ) are connected.
ERROR
POWER
/ MODE
ERROR
MONITOR
POWER
/ MODE
MONITOR
ACFEDB
(2-blink)
(2-blink)
(4) After the check run is complete, results will be displayed. Please fill the displayd result table accordingly.
NOTEAutomatic wiring correction will not be completed if the power is turned off while displaying the result.
・
To confirm the automatic wiring correction, be sure to carry out step (5).
If frost is formed on the outdoor unit while displaying the result, Automatic defrost function will operate.
・
Proceed to step (5) after the defrost function is finished.
01-28
If the connection is correct [(Example) When 4 indoor units are connected]
After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
POWER
/ MODE
ERROR
A
MONITOR
BC
(7 sec.)
(7 sec.)
(7 sec.)
(7 sec.)
D
EF
If the connection is incorrect [(Example) When connection of B and C of the 4 units are reversed]
After the number of connected units are displayed, B and C will light up in reverse.
POWER
/ MODE
ERROR
A
MONITOR
BC
(7 sec.)
D
EF
(7 sec.)
(7 sec.)
(7 sec.)
[How to record the contents]
Please fill the displayed result according to the following example.
Example 1
When piping A to D is connected bu the wires fo B and C are connected in reverse.
Displayed results
The LED will light up in 7 second interval in the following order.
POWER
/ MODE
ERROR
A
MONITOR
BC
(7 sec.)
(7 sec.)
D
EF
(7 sec.)
(7 sec.)
01-29
Example of result table
(a) Please wirte a where the LEDs light up in the order that they light up.
(b) Based on the results of step (a), please record as follows.
Please trace the dotted cicle woth a pen if multiple places liught up.
Please write the order from A to D in which the LEDs lit up inside the cicle.
(c) Select the correction method.
Correct the wiring manually.*2
Proceed to step (6).
/ MODE
ERROR
ACFEDB
MONITOR
POWER
Use the Automatic wiring correction function.*1
Proceed to step (5).
NOTE:
*1 : By using this function, the wiring is automatically corrected according to the piping.
*2 : When correcting the wiring manually, please disconnect the power supply or turn off the breaker during
results display, and then change the wiring manually according to the obtained test result.
For example, in Example 1, the wirings connected to the terminals B and C is to be exchanged manually.
Please write down the same results in the label on the reverse side of the service panel.
The results recorded are needed at the time of servicing.
(5) During results display, press the “CHECK” swtich for 3 seconds or more.
After LEDs A to F have lit in turn, all LEDs will light up indicating that the automatic wiring correction is completed.
(6) Disconnect the power supply or turn off the breaker and wait 10 minutes then turn the power back on and
perform test run.
NOTE: If you do not disconnect the power supply or turn off the breaker, normal operation is not possible.
Others
If an error occurs during check run it will be suspended. Please correct the error and start check run again.
・
After the check run, if automatic wiring correction is carried out, the indoor unit’s position will be modified
・
to match the piping. (Please note that the display of the optional remote controller changes.)
If you start check run again after the automatic wiring correction is finished, the modification will be reset.
・
01-30
Check run judgment failure display
If check run cannot be performed, the following is displayed. In this case, the check
run will stop. Please check by using the cooling test run of the indoor unit.
Temperature out of range judgment
ERROR
POWER
MODE
BA
MONITOR
FEDC
(2-blink)
blink
(High-speed)
Wiring / piping number difference
ERROR
POWER
MODE
(2-blink)
(2-blink)
blink
(High-speed)
(High-speed)
BA
blink
MONITOR
FEDC
OR
Re-display check run results
If you wish to check the automatic wiring correction contents, by briefly pressing the
"CHECK" switch, the check run results is displayed. Please check the check run
results by referring to the result table in step (4) of "8.3. Operating procedure for check run".
If the automatic wiring correction contents has not been done, the POWER/MODE
LED will blink twice and the MONITOR LED will turn off.
Automatic wiring correction memory reset
CAUTION
When relocating the unit, reset the memory beforehand, or the unit may not function
normally.
(1) Press the "CHECK" switch.
The LED will light as shown in “8.5 Re-display check run results”.
(2) Press the "CHECK" switch for more than 3 seconds when the LED is on.
(3) The LEDs from A to F will light in sequence, and then all LEDs will light to indicate
the completion of the Automatic wiring correction memory reset.
(4) Disconnect the power supply or turn off the breaker.
01-31
28. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
When the discharge temperature becomes higher than Temperature , the compressor frequency
is decreased 10rps, and it continues to decrease thefrequency for 10rps every 120 seconds until the
temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the compressor
frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor stops.
( Table 24 : Discharge temperature over rise prevension control / Release temperature )
Temperature
TemperatureTemperature
AOU36RLXFZH
AOU45RLXFZ
219°F (104°C)214°F (101°C)230°F (110°C)
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
3. COOLING PRESSURE OVER RISE PROTECTION
When the outdoor unit discharge pressure sensor rises to 580.2 psi (4 MPa) or greater,
the compressor is stopped and error display is indicated.
01-32
4. HIGH TEMPERATURE RELEASE CONTROL ( Heating mode )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the discharge pressure sensor.
( Fig. 23 : Heating overload protection control )
discharge pressure rises
Outdoor heat exchange
tempreture
8.6°F(-13°C) < Tn < 12.2°F(-11°C)
5°F(-15°C) < Tn < 8.6°F(-13°C)
-13°F(-25°C) < Tn < 5°F(-15°C)
-20.2°F(-29°C) < Tn < -13°F(-25°C)
=
=
=
=
Tn < -20.2°F(-29°C)
478.62 psi
(3.30 MPa)
464.12 psi
(3.20 MPa)
435.11 psi
(3.00 MPa)
377.10 psi
(2.60 MPa)
333.59 psi
(2.30 MPa)
A psi ( A MPa )
B psi ( B MPa )
C psi ( C MPa )
The compressor frequency is
decreased 15rps every 120 seconds.
The compressor frequency is
decreased 2rps every 120 seconds.
Release
Release
Stable range
5. HIGH PRESSURE PROTECTION
During the compressor operation, when detect the condition of the following table value,
the protection function will be worked.
The operation condition varies according to the compressor speed.
The protection function is, the compressor speed is descreased 7 rps every 60 seconds.
( Table 26 : Cooling operation )
Release value [ psi (MPa) ]
Hp < 471.37 psi (3.25 MPa)
=
Hp < 522.14 psi (3.60 MPa)
=
Hp < 449.62 psi (3.10 MPa)
=
rps < 20
=
20 < rps < 90
90 < rps < 100
=
=
Operation value [ psi (MPa) ]Compressor frequency [ rps ]
Hp > 500.38 psi (3.45 MPa)
=
Hp > 551.14 psi (3.80 MPa)
=
Hp > 478.62 psi (3.30 MPa)
=
Dsicharge pressure [ psi (MPa) ]
AB
449.62 psi
(3.10 MPa)
478.62 psi
(3.00 MPa)
406.11 psi
(2.80 MPa)
362.59 psi
(2.50 MPa)
319.08 psi
(2.20 MPa)
C
406.11 psi
(2.80 MPa)
391.60 psi
(2.70 MPa)
377.10 psi
(2.60 MPa)
333.59 psi
(2.30 MPa)
290.08 psi
(2.00 MPa)
( Table 27 : Heating operation )
Compressor frequency [ rps ]
rps < 20
=
20 < rps < 90
90 < rps < 100
=
=
100 < rps
Operation value [ psi (MPa) ]Release value [ psi (MPa) ]
Hp > 500.38 psi (3.45 MPa)
=
Hp > 507.63 psi (3.50 MPa)
=
Hp > 478.62 psi (3.30 MPa)
=
Hp > 449.62 psi (3.10 MPa)
=
Hp < 471.37 psi (3.25 MPa)
=
Hp < 478.62 psi (3.30 MPa)
=
Hp < 449.62 psi (3.10 MPa)
=
Hp < 420.61 psi (2.90 MPa)
=
Hp : detected discharge pressure sensor value
rps : detected compressor frequency
6. COMPRESSOR TEMPERATURE PROTECTION
Compressor temperature sensor is monitoring the compressor Temperature
When the compressor temperature sensor detects higher than Temperature , the compressor is stopped.
When 3 minutes has passed from the compressor stop and the compressor temperature sensor detects
lower than Temperature , protection is released and the compressor will restart.
( Table 28 : Operation value )
Temperature
176°F
(80°C)
AOU36RLXFZH
AOU45RLXFZ
Temperature
226°F
(108°C)
01-33
29. PUMP DOWN OPERATION
When moving or discarding the air conditioner, in order to consider the environment and
avoid the discharge of refrigerant to the atmosphere, please pump down according to the following procedure.
(1) Connect the pressure gauge to the charging port.
(2) Change the DIP switch on the board (SET1-2) to ON*1
SET1
ON
1 2 3 4
*Be sure the power supply is
disconnected on the breaker
is turned off when changing
the DIP switch.
During the pump down operation, make sure that compressor is off before you remove
the refrigerant piping. Do not remove the connection pipe while the compressor is in
operation with valve open. This may cause abnormal pressure in the refrigeration cycle
that leads to breakage and even injury.
*1: DIP switch
(SET1-2)
(3) To start operation, press the [PUMP DOWN] switch*2 for 3 seconds or press after the
power has been on for 3 min.
TEST RUN
1WS
PUMP DOWN
During pump down, the LED (POWER/MODE) will ash 3 times consecutively.
ERROR
POWER
MODE
(3-blink)
NOTE:
If the [PUMP DOWN] switch is pressed during compressor operation, the compressor
will stop, and the operation will start after about 3 min.
(4) Close the liquid pipe valve.
(5) When 7.3 psi ~ 0 psi (0.05 MPa ~ 0 MPa) is shown, close the gas pipe valve.
(6) Stop pump down by pressing the [PUMP DOWN] switch for 3 seconds.
The LED will light as follows.
*2: Push switch (SW1)
MONITOR
BA
FEDC
WARNING
ERROR
POWER
MODE
MONITOR
BA
(3-blink)
(7) Disconnect the power supply or turn off the breaker.
NOTE:
If the pump down is not stopped by pressing the switch as in step (6), it will stop
automatically after 15 min. and the LED will light as follows. If the pump down is
complete, disconnect the power supply or turn off the breaker. If not completed open
the liquid pipe valve, and then start again from step (3).
ERROR
POWER
MODE
MONITOR
BA
(3-blink)
In order to interrupt the pump down operation, press the [PUMP DOWN] switch
The pump down may stop before completion due to error. To complete the pump
blink
(High-speed)
again. The LED will return to the original display before starting pump down.
(POWER/MODE LED: On)
down, correct the error, open the liquid pipe valve and then start from step (1) again.
Otherwise, the refrigerant can be recovered from the service port.
FEDC
FEDC
01-34
30. TEST RUN ( For Outdoor unit )
CAUTION
Always turn on the power 12 hours prior to the start of the operation in order to protect
the compressor.
(1) Indoor unit
Is the drain normal?
1
Is there any abnormal noise and vibration during operation?
2
(2) Outdoor unit
Is there any abnormal noise and vibration during operation?
1
Will noise, wind, or drain water from the unit disturb the neighbors?
In the fiUVWWHVWUXQEHVXUHWRVHWWKHRSHUDWLRQPRGHWR³&22/´
7KHRSHUDWLRQPRGHFDQQRWEHVZLWFKHGEHWZHHQ³&22/´DQG³+($7´GXULQJWKHWHVW
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
Please refer the flashing pattern as follows.
The Operation, Timer, Economy lamps operate as follows according to the error contents.
Error Contents
Serial Communication Error
Wired Remote Controller
Communication Error
Indoor Unit Capacity Error
Indoor Unit Model Information Error
EEPROM Access Abnormal
Manual Auto Switch Error
Operation
(Green)
3 times
3 times
Indoor Unit Display
Timer
(Orange)
5 times
Economy
(Green)
Continuous1 times1 times
Continuous2 times1 times
Continuous2 times2 times
Continuous2 times
Continuous
Wired Remote
Controller
Display
11
12
22
32
35
Trouble
shooting
1,2
3
5
6
7
Indoor Room Thermistor Error
Indoor Heat Ex. Thermistor Error
Indoor Unit Fan Motor Error
Drain Pump Error
Damper Error
Intake Grille Error
Outdoor Unit Model Information Error
Inverter Error
Active Filter Error
IPM Error
Discharge Thermistor Error
Compressor Thermistor Error
Heat Ex. Thermistor Error (OUT)
Outdoor Thermistor Error
1 times
3 times5 times
7 times5 times
8 times5 times
2 times6 times
3 times6 times
6 times
7 times
7 times
7 times3 times
7 times4 times
4 times
5 times6 times
1 times
2 times
Continuous4 times
Continuous4 times2 times
Continuous1 times5 times
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
41
42
51
53
57
58
62
63
64
65
71
72
73
74
8
9
10
11
12-1,12-2
13
14
17
18
19
20
21
22
23
2-Way Valve Thermistor Error
3-Way Valve Thermistor Error
CT Error
Discharge Pressure Sensor Error
Over Current Error
Compressor Control Error
Outdoor Unit Fan Motor Error
4-Way Valve Error
Coil (expansion valve) Error
Discharge Temp. Error
Compressure Temp. Error
7 times6 times
7 times6 times
4 times8 times
6 times8 times
4 times9 times
9 times
9 times
9 times9 times
9 times10 times
10 times3 times
5 times
7 times
1 times10 times
02-01
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
76
76
84
86
94
95
97
99
9A
A1
A3
24
25
26
27
28
29
30
31
32
33
34
1. SELF - DIAGNOSIS
When " Er " in Temperature Display is displayed, inspection of the air conditioning system is necessary.
Please consult authorized service personnel.
Unit number (usually 0)
Error code
SUMOTU WETH FR SA
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds
or more to start the self-diagnosis.
Error code
Error history number
SU MO TU WETH FR SA
3. Press the SET TEMPERATURE button to select the error history number.
Lower
01234567
FEdcbA98
Raise
Õ
Õ
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more
or there is no key input for 60 seconds to stop the display.
02-02
2-1-2 SIMPLE REMOTE CONTROLLER DISPLAY
If an error occurs, the following display will be shown.
“ will appear in the set room temperature display.)
(
“
“ is displayed, immediately contact authorized service personnel.
If
“
Error code
Faulty unit No.
(Remote controller address)
Ex. Error code display
2-1-3 CENTRAL REMOTE CONTROLLER DISPLAY
To show which indoor unit is the error displayed.
indoor unit's name and "ERROR" are alternately shown.
(0.5s indoor unit's name / 0.5s "ERROR")
Ex. Error display
2-1-4 OUTDOOR UNIT DISPLAY
If an error occurs, the LED will light up to display the error location and the error code.
In the event of an error
The error LED frashes quickly.
ERROR
POWER
MODE
blink
(High-speed)
Error location display
LEDs A to F of MONITOR light up and display the error location. In the case of an
overall error, LEDs A to F of MONITOR do not light up.
Example) Coil error in indoor unit B
ERROR
POWER
MODE
BA
BA
MONITOR
FEDC
MONITOR
FEDC
blink
(High-speed)
02-03
Error code display
While the error is occurring, please briefly press SW1.
The error code is displayed.
Ex.) Serial communication error ( Error cord = 11.3 )
3
(1-blink)
(1-blink)
Blink
(High-speed)
Display mode
LED on :
LED off :
Blink :
(0.5s Light on / 0.5s Light off)
For MONITOR
(A and B)
A : 10 - Blink
C : 11 - Blink
F : 12 - Blink
J : 13 - Blink
P : 14 - Blink
U : 15 - Blink
CDEF
1
2
3
4
5
6
7
8
9
A
C
F
J
P
U
02-03-1
Error codeError contents
11. 3
11. 4
16. 5
22. 1
22. 1
Serial communication error
Serial communication error
during operation
Communication error between
controller and outdoor unit
Indoor unit capacity error
Outdoor unit LED display part
A
1
1
BC
1
1
16
22
Monitor
DEF
Trouble
shooting
1
2
4
5
5U. 1
62. 8
63. 1
65. 3
71. 1
72. 1
73. 3
74. 1
76. 1
76. 2
84. 1
86. 1
94. 1
95. 1
Indoor unit error
PCB model information error62. 1
EEPROM access error62. 3
EEPROM data corruption error
Inverter error
IPM error (Trip terminal L error)
Dsicharge temp. sensor error
Compressor temp. sensor error
Heat ex. liquid temp. sensor error
Outdoor temp. sensor error
valve sensor error
Current sensor 1 error
(stoppage permanently)
Discharge pressure sensor error
Trip detection
Compressor motor control error
515
62
62
62
63
65
71
72
73
74
76
76
84
86
94
95
-
14
15
16
17
19
20
21
22
23
24
25
26
27
28
29
97. 3
99. 1
9A. 1
A1. 1
Fan motor 1 error(Duty error)
4-way valve error
Coil 1 (expansion valve 1) error
Discharge temperature 1 error
(stoppage permanently)
Compressor 1 temperature errorA3. 1
: Flashing: No indication
1 - 15 : Outdoor LED Blink ( 1 to 15 times ) 0.5s Light on / 0.5s Light off
NOTE
Error code 16.5 : Occur when using the Home remote controller.
Error code 5U.1 : Indoor unit all error
97
99
910
101
101
This Error code list is excerpt by instalation manual.
02-04
30
31
32
33
34
2-2 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1
OUTDOOR UNIT Error Method:
Serial Communication Error
(Serial Reverse Transfer Error)
Detective Actuators:
Outdoor unit main PCB
Outdoor unit fan motor
Indicate of Display:
Indoor Unit
Operation lamp : 1 time Flash
Timer lamp: 1 time Flash
ERROR CODE : [E : 11]
Outdoor Unit
ABCDEF
11
1
111
: Light ON: Light OFFn : n time blinking
Detective details:
When the indoor unit cannot receive the serial signal from outdoor unit
more than 2 minutes after power ON, or the indoor unit cannnot receive
the serial signal more than 15 seconds during normal operation.
Forecast of Cause:
1. Connection failure2. External cause3. Main PCB failure4. Active filter module failure
5. Transistor PCB (IPM) failure 6. Filter PCB failure7. Outdoor unit Fan motor failure
Test 1-1 : Reset the power and operate
Does error indication reappear?
NO
YES
Test 2 : Check connection
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or miss-wiring)
Test 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Monitor
OK
Test 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC187V(AC208V-10%) - 253V(AC230V+10%) appears
at outdoor unit terminal L1 - L2.
OK
Test 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3.
>> If it is abnormal, Check the parts as follows.
- Outdoor unit fan motor (SERVICE PARTS INFORMATION 6)
- Active filter module (SERVICE PARTS INFORMATION 8)
- Filter PCB (Check the wire of CN201)
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB.
(SERVICE PARTS INFORMATION 10)
>> If Active filter module or IPM is abnormal, replace it.
>> If the parts are normal, replace Main PCB. (SERVICE PARTS INFORMATION 10)
BLACK
WHITE
RED
1
2
3
+
-
02-05
Trouble shooting 2
INDOOR UNIT Error Method:
Serial Communication Error
(Serial Forward Transfer Error)
Indicate of Display:
Indoor Unit
Operation lamp : 1 time Flash
Timer lamp: 1 time Flash
ERROR CODE : [E : 11]
Outdoor Unit
ABCDEF
111
111
: Light ON: Light OFFn : n time blinking
Monitor
Detective Actuators:
Indoor unit controller PCB
Detective details:
When the outdoor unit cannot properly receive the serial signal from
indoor unit for 15 seconds or more.
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or miss-wiring)
Test 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
OK
Test 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC187V(AC208V-10%) - 253V(AC230V+10%) appears
at outdoor unit terminal L1 - L2.
OK
Test 4 : Check serial signal (Forward transfer signal)
Check Serial Signal (Forward Transfer Signal)
>> Check if Indicated value swings between AC30V and AC130V at Outdoor Unit Terminal 2 - 3.
>> If it is abnormal, replace Controller PCB.
>> If it is abnormal, Check Indoor unit fan motor. (SERVICE PARTS INFORMATION 5)
>> If Indoor unit fan motor is abnormal, replace Indoor unit fan motor and Controller PCB.
BLACK
WHITE
RED
1
2
3
+
-
02-06
Trouble shooting 3
INDOOR UNIT Error Method:
Wired Remote Controller
Communication Error
Indicate of Display:
Indoor Unit
Operation lamp : 1 time Flash
Timer lamp: 2 time Flash
ERROR CODE : [E : 12]
Outdoor Unit
ABCDEF
: Light ON: Light OFFn : n time blinking
Monitor
Detective Actuators:
Indoor unit controller PCB
Wired remote controller
Detective details:
When the indoor unit cannot properly receive the signal from
Wired Remote Controller for 1 minutes or more.
Check & correct the followings.
Check the connection of terminal between Wired Remote Controller and indoor unit,
and check if there is a disconnection of the cable.
OKOK
Test 2 : Check Wired Remote Controller and Controller PCB
Check Voltage at terminal 1-3 of Controller PCB or Communication PCB.
(Power supply to Remote Control)
Compact Cassette, SlimDuct Type : CN14
Wall Mount , Floor Type : CN16
Compact Wall Mount Type : CNC01 (UTY-XCBXZ2)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
02-07
Trouble shooting 4
OUTDOOR UNIT Error Method:
Communication Error Between
Controller And Outdoor Unit
Indicate of Display:
Indoor Unit
Operation lamp : - time Flash
Timer lamp: - time Flash
ERROR CODE : [E : --]
Outdoor Unit
ABCDEF
1
: Light ON: Light OFFn : n time blinking
Monitor
6
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When the home controller cannot 60sec receive the signal from
Home Controller
Forecast of Cause:
1. Connection failure 2. Home Controller failure 3. Main PCB failure
Test 1 : Check the connection of terminal
Check & correct the followings.
Check the connection of terminal between Wired Remote Controller and indoor unit,
and check if there is a disconnection of the cable.
OKOK
Test 2 : Check Home Controller and Main PCB
Check Voltage at terminal 1-3 (CN93) of Main PCB.
(Power supply to Remote Control)
>> If it is DC12V, Home Controller is failure. (Main PCB is normal) >> Replace Home Controller
>> If it is DC 0V, Main PCB is failure. (Check Home Controller once again) >> Replace Main PCB
(SERVICE PARTS INFORMATION 10)
02-08
Trouble shooting 5
INDOOR UNIT Error Method:
Indoor Unit Capacity Error
Indicate of Display:
Indoor Unit
Operation lamp : 2 time Flash
Timer lamp: 2 time Flash
ERROR CODE : [E : 22]
Outdoor Unit
ABCDEF
2
: Light ON: Light OFFn : n time blinking
Monitor
2
Detective Actuators:
All indoor unit
Detective details:
The total capacity of the indoor unit if it is install beyond.
Forecast of Cause:
1. The selection of indoor units is incorrect 2. Main PCB(Outdoor unit) failure
Test 1 : Check the total capacity of indoor unit
Check the total capacity of the connected indoor units.
>> If abnormal condition is found, correct it by referring
to Installation Manual or Design & Technical Manual.
OKOK
Test 2 : Replace Main PCB
If Test 1 do not improve the symptom, replace Main PCB of Outdoor unit.
(SERVICE PARTS INFORMATION 10)
02-09
Trouble shooting 6
INDOOR UNIT Error Method:
Indoor Unit Model Information Error
EEPROM Access Abnormal
Indicate of Display:
Indoor Unit
Operation lamp : 3 time Flash
Timer lamp: 2 time Flash
ERROR CODE : [E : 32]
Detective Actuators:Detective details:
Indoor unit controller PCB
When power is on and there is some below case.
When model information of EEPROM is oncorrect.
When the access to EEPROM failed.
Forecast of Cause:
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Outdoor Unit
ABCDEF
515
: Light ON: Light OFFn : n time blinking
Monitor
Test 1-1 : Reset Power Supply and operate
Does Error indication show again?
YESYES
Test 2 : Check Indoor unit electric components
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
Test 3 : Replace Controller PCB
Change Controller PCB.
NO
Test 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a nonvolatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
02-10
Trouble shooting 7
INDOOR UNIT Error Method:
Manual Auto Switch Error
Indicate of Display:
Indoor Unit
Operation lamp : 3 time Flash
Timer lamp: 5 time Flash
ERROR CODE : [E : 35]
Outdoor Unit
ABCDEF
: Light ON: Light OFFn : n time blinking
Monitor
Detective Actuators:
Indoor unit controller PCB
Indicator PCB
Manual auto switch
Detective details:
When the Manual Auto Switch becomes ON for consecutive
60 seconds or more.
Forecast of Cause:
1. Manual Auto Switch failure 2. Controller PCB and Indicator PCB failure
Test 1 : Check the Manual Auto Switch
Check if Manual Auto Switch is kept pressed.
Check ON/OFF switching operation by using a meter.
>> If Manual Auto Switch is disabled (on/off switching), replace it.
OKOK
Test 2 : Replace Controller PCB and Indicator PCB
If Test 1 do not improve the symptom, replace Controller PCB and Indicator PCB.
02-11
Trouble shooting 8
INDOOR UNIT Error Method:
Indoor Room Thermistor Error
Indicate of Display:
Indoor Unit
Operation lamp : 4 time Flash
Timer lamp: 1 time Flash
ERROR CODE : [E : 41]
Outdoor Unit
ABCDEF
: Light ON: Light OFFn : n time blinking
Monitor
Detective Actuators:
Indoor unit controller PCB circuit
Room temperature thermistor
Detective details:
Room temperature thermistor is open or short is detected always.
Forecast of Cause:
1. Connector failure connection
2. Thermistor failure
3. Controller PCB failure
Test 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
32
0
104866850
5.308.0412.5420.1733.6258.25
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
-10
14
If Thermistor is either open or shorted, replace it and reset the power.
OK
4540302010
113
4.35
Test 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Compact wall mount circuit diagram(Connector connection)
BLACK
1
1
BLACK
2
2
CN4
Wall mount circuit diagram (Direct soldering to PCB)
CN3
CN1
Floor circuit diagram (Connector connection and Direct soldering to PCB)
CN3
CN1
3
4
1
2
1
2
121
1
2
3
4
2
BLACK
BLACK
RED
WHITE
BLACK
BLACK
GRAY
GRAY
BLACK
BLACK
1
2
3
BLACK
1
2
BLACK
3
H/E Thermistor
Room Temp. Thermistor
H/E Thermistor
Room Temp. Thermistor
H/E (MID) Thermistor
Room Temp. Thermistor
If the voltage does not appear, replace Controller PCB and execute the check operation again.
Indoor Unit
Operation lamp : 5 time Flash
Timer lamp: 7 time Flash
ERROR CODE : [E : 57]
Outdoor Unit
ABCDEF
: Light ON: Light OFFn : n time blinking
Monitor
Detective Actuators:
Indoor unit controller PCB
Limit switch
Damper
Detective details:
When limit switch were not able to detect the close though the damper close.
(Upper air flow)
When limit switch were not able to detect the close though the damper open.
(Upper and lower air flow)
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
>>If Micro switch is detective, replace it.
OK
Test 2 : Check Connector (CN11) / Wire
Check loose contact of CN11 /shorted wire (pinched wire).
>>Replace Micro switch if the wire is abnormal
OK
Test 3 : Replace Controller PCB
If Test 1 - 2 do not improve the symptom, change Controller PCB.
02-18
Trouble shooting 14
INDOOR UNIT Error Method:
Outdoor Unit Model Information Error
Indicate of Display:
Indoor Unit
Operation lamp : 6 time Flash
Timer lamp: 2 time Flash
ERROR CODE : [E : 62]
Detective Actuators:Detective details:
Outdoor unit main PCB
When power is on and there is some below case.
When model information of EEPROM is incorrect.
When the access to EEPROM failed.
Forecast of Cause:
1. External cause2. Defective connection of electric components 3. Main PCB failure
Outdoor Unit
ABCDEF
6
: Light ON: Light OFFn : n time blinking
Monitor
2
Test 1-1 : Reset Power Supply and operate
Does Error indication show again?
YES
Test 2 : Check Indoor unit electric components
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Test 3 : Replace Main PCB
If Test 1 - 2 do not improve the symptom, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
NO
Test 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a nonvolatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
02-19
Trouble shooting 15
OUTDOOR UNIT Error Method:
EEPROM Access Error
Indicate of Display:
Indoor Unit
Operation lamp : - time Flash
Timer lamp: - time Flash
ERROR CODE : [E : --]
Detective Actuators:Detective details:
Outdoor unit Main PCB
When the check run if can not write data to the EEPROM.
Forecast of Cause:
1. External cause 2. Main PCB defective
Outdoor Unit
ABCDEF
6
: Light ON: Light OFFn : n time blinking
Monitor
2
Test 1-1 : Turn the power on again?
NO
Error displayed again?
・
YES
Test 2 : Replace Main PCB
If Test 1 do not improve the symptom, replace Main PCB(Outdoor unit).
(SERVICE PARTS INFORMATION 10)
Test 1-2 : External cause
Check if temporary voltage drop was not generated.
Check if temporary open was not generated.
Check if ground is connected correctly or
there are no related cables near the power line.
02-20
Trouble shooting 16
OUTDOOR UNIT Error Method:
EEPROM Data Corruption Error
Indicate of Display:
Indoor Unit
Operation lamp : - time Flash
Timer lamp: - time Flash
ERROR CODE : [E : --]
Detective Actuators:Detective details:
Outdoor unit Main PCB
When the power is turned on and
When the data of the automatic correction was damaged
Forecast of Cause:
1. External cause 2. Main PCB defective
Outdoor Unit
ABCDEF
6
: Light ON: Light OFFn : n time blinking
Monitor
2
Test 1-1 : Turn the power on again?
NO
・
Error displayed again?
YES
Test 2 : Replace Main PCB
If Test 1 do not improve the symptom, replace Main PCB(Outdoor unit).
(SERVICE PARTS INFORMATION 10)
Test 1-2 : External cause
Check if temporary voltage drop was not generated.
Check if temporary open was not generated.
Check if ground is connected correctly or
there are no related cables near the power line.
02-21
Trouble shooting 17
OUTDOOR UNIT Error Method:
Inverter Error
Indicate of Display:
Indoor Unit
Operation lamp : 6 time Flash
Timer lamp: 3 time Flash
ERROR CODE : [E : 63]
Detective Actuators:Detective details:
Outdoor Unit
ABCDEF
6
: Light ON: Light OFFn : n time blinking
Monitor
3
Inverter PCB
Error information received from Inverter PCB
Forecast of Cause:
1. External cause2. Power supply to Filter PCB to Inverter PCB wiring disconnection, open
3. Filter PCB failure 4. Inverter PCB failure
Test 1-1 : Turn the power on again?
Error displayed again?
・
NO
Test 1-2 : External cause
Check if temporary voltage drop was not generated.
Check if temporary open was not generated.
Check if ground is connected correctly or
there are no related cables near the power line.
YES
Test 2 : Check the wiring (Power supply to Filter PCB to Inverter PCB)
Connector and wiring connection state check
Cable open check
OK
Test 3 : Replace Inverter PCB
If Test 1,2 do not improve the symptom, replace Inverter PCB(Outdoor unit),
and execute the check operation again.
OK
Test 4 : Replace Main PCB
If Test 3 do not improve the symptom, replace Main PCB(Outdoor unit),
and execute the check operation again.
OK
Test 5 : Replace Filter PCB
If Test 4 do not improve the symptom, replace Filter PCB(Outdoor unit).
(SERVICE PARTS INFORMATION 10)
02-22
Trouble shooting 18
OUTDOOR UNIT Error Method:
Active Filter Error
Indicate of Display:
Indoor Unit
Operation lamp : 6 time Flash
Timer lamp: 4 time Flash
ERROR CODE : [E : 64]
Outdoor Unit
No Display
Detective Actuators:
Outdoor unit main PCB
Active filter module
Detective details:
When inverter input DC voltage is higher than 430V or lower than 110V.
When a momentary power cut off occurred on low voltage.
Forecast of Cause:
1. External cause 2. Connector connection failure 3. Main PCB failure 4. Active filter module failure
Test 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Test 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or miss-swiring, reset the power.
OK
Test 3 : Check Active filter module
Check Active filter module. (SERVICE PARTS INFORMATION 8)
>>If Active filter module is abnormal, replace it.
OK
Test 4 : Replace Main PCB
If Test 1 - 3 do not improve the symptom, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
02-23
Trouble shooting 19
OUTDOOR UNIT Error Method:
IPM Error
Indicate of Display:
Indoor Unit
Operation lamp : 6 time Flash
Timer lamp: 5 time Flash
ERROR CODE : [E : 65]
Outdoor Unit
ABCDEF
6
: Light ON: Light OFFn : n time blinking
Monitor
5
Detective Actuators:
Outdoor unit main PCB
Compressor
Detective details:
When more than normal operating current to IPM in Main PCB flows,
the compresor stops.
After the compressor restarts, if the same operation is repeated
within 40 sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Forecast of Cause:
1. Defective connection of electric components2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged4. Compressor failure5. Main PCB failure
Test 1 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off?
>> If the Fan Motor is locked, replace it.
OK
Test 3 : Check Outdoor Fan
Check Outdoor Fan Motor. (Refer to Trouble shooting 30)
>> If the Fan Motor is failure, replace it.
OK
Test 4 : Check Compressor
Check Compressor.(SERVICE PARTS INFORMATION 9)
OK
Test 5 : Replace Main PCB
If Test 1 - 4 do not improve the symptom, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
02-24
Trouble shooting 20
OUTDOOR UNIT Error Method:
Discharge Thermister Error
Indicate of Display:
Indoor Unit
Operation lamp : 7 time Flash
Timer lamp: 1 time Flash
ERROR CODE : [E : 71]
Outdoor Unit
ABCDEF
7
: Light ON: Light OFFn : n time blinking
Monitor
1
Detective Actuators:
Outdoor unit main PCB circuit
Discharge pipe temperature thermistor
Detective details:
When Discharge pipe temperarture thermistor open or short-circuit is detected
at power ON or while running the compressor.
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
-30
-22
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
140
12.30
If Thermistor is either open or shorted, replace it and reset the power.
-20
-4
158
8.70
292.91531.561013.11
-10
14
807060
176
6.27
0
32
194
10
50
100110
212230
3.434.60
2.60
12090
248
2.00
40
1048668
26.3440.0162.55100.91168.60
503020
122
17.79
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
121
CN61
CN62
CN63
2
33
121
2
33
121
2
33
44
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
If the voltage does not appear, replace Main PCB.
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( HEX OUT TEMP. )
THERMISTOR
( DISCHARGE TEMP. )
THERMISTOR
( COMP TEMP. )
02-25
Trouble shooting 21
OUTDOOR UNIT Error Method:
Compressor Thermister Error
Indicate of Display:
Indoor Unit
Operation lamp : 7 time Flash
Timer lamp: 2 time Flash
ERROR CODE : [E : 72]
Outdoor Unit
ABCDEF
7
: Light ON: Light OFFn : n time blinking
Monitor
2
Detective Actuators:
Outdoor unit main PCB circuit
Compressor temperature thermistor
Detective details:
When Compressor temperarture thermistor open or short-circuit is detected
at power ON or while running the compressor.
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
-30
-22
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
140
12.30
If Thermistor is either open or shorted, replace it and reset the power.
-20
-4
158
8.70
292.91531.561013.11
-10
14
807060
176
6.27
0
32
194
10
50
100110
212230
3.434.60
2.60
12090
248
2.00
40
1048668
26.3440.0162.55100.91168.60
503020
122
17.79
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
121
CN61
CN62
CN63
2
33
121
2
33
121
2
33
44
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
If the voltage does not appear, replace Main PCB.
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( HEX OUT TEMP. )
THERMISTOR
( DISCHARGE TEMP. )
THERMISTOR
( COMP TEMP. )
02-26
Trouble shooting 22
OUTDOOR UNIT Error Method:
Heat Ex. OUT Thermister Error
Indicate of Display:
Indoor Unit
Operation lamp : 7 time Flash
Timer lamp: 3 time Flash
ERROR CODE : [E : 73]
Outdoor Unit
ABCDEF
7
: Light ON: Light OFFn : n time blinking
Monitor
3
Detective Actuators:
Outdoor unit main PCB circuit
Heat Ex. temperature thermistor
Detective details:
When Heat Ex. temperarture thermistor open or short-circuit is detected
at power ON or while running the compressor.
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
-30
-22
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
140
1.19
If Thermistor is either open or shorted, replace it and reset the power.
-20
-4
158
0.84
-10
27.8150.3195.58
176
0.61
14
807060
32
0
10
50
40
1048668
2.533.845.989.6316.05
503020
122
1.71
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
121
CN61
CN62
CN63
2
33
121
2
33
121
2
33
44
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
If the voltage does not appear, replace Main PCB.
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( HEX OUT TEMP. )
THERMISTOR
( DISCHARGE TEMP. )
THERMISTOR
( COMP TEMP. )
02-27
Trouble shooting 23
OUTDOOR UNIT Error Method:
Outdoor Thermister Error
Indicate of Display:
Indoor Unit
Operation lamp : 7 time Flash
Timer lamp: 4 time Flash
ERROR CODE : [E : 74]
Outdoor Unit
ABCDEF
7
: Light ON: Light OFFn : n time blinking
Monitor
4
Detective Actuators:
Outdoor unit main PCB circuit
Outdoor temperature thermistor
Detective details:
When Outdoor temperarture thermistor open or short-circuit is detected
at power ON or while running the compressor.
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
-30
-22
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
140
2.36
If Thermistor is either open or shorted, replace it and reset the power.
-20
-4
158
1.65
-10
62.28115.24224.33
176
1.18
14
807060
32
0
10
50
40
1048668
5.187.9712.6420.7235.21
503020
122
3.45
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
121
CN61
CN62
CN63
2
33
121
2
33
121
2
33
44
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
If the voltage does not appear, replace Main PCB.
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( HEX OUT TEMP. )
THERMISTOR
( DISCHARGE TEMP. )
THERMISTOR
( COMP TEMP. )
02-28
Trouble shooting 24
OUTDOOR UNIT Error Method:
2-Way Valve Thermistor Error
Indicate of Display:
Indoor Unit
Operation lamp : 7 time Flash
Timer lamp: 6 time Flash
ERROR CODE : [E : 76]
Outdoor Unit
ABCDEF
7
: Light ON: Light OFFn : n time blinking
Monitor
6
Detective Actuators:
Outdoor unit main PCB circuit
2 Way valve temperature thermistor
Detective details:
When 2 Way valve temperarture thermistor open or short-circuit is detected
at power ON or while running the compressor.
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
-30
-22
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
140
12.30
If Thermistor is either open or shorted, replace it and reset the power.
-20
-4
158
8.70
292.91531.561013.11
-10
14
807060
176
6.27
32
0
10
50
40
1048668
26.3440.0162.55100.91168.60
503020
122
17.79
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AOU36RLXFZHFor AOU45RLXFZ
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
CN64
11
22
33
44
55
66
77
88
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
VALVE THERMISTOR C, D
BLACK
CN65
11
22
33
44
55
66
77
88
99
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
2-WAY VALVE C
3-WAY VALVE C
2-WAY VALVE D
3-WAY VALVE D
If the voltage does not appear, replace Main PCB.
CN64
CN65
CN66
BLACK
1
1
BLACK
2
2
BLACK
3
3
BLACK
4
4
BLACK
5
5
BLACK
6
6
BLACK
7
7
BLACK
8
8
BLACK
1
1
BLACK
2
2
3
3
BLACK
4
4
BLACK
5
5
BLACK
6
6
BLACK
7
7
BLACK
8
8
BLACK
9
9
BLACK
1
1
BLACK
2
2
3
3
BLACK
4
4
BLACK
5
5
6
6
7
7
8
8
9
9
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
VALVE THERMISTOR C, D
2-WAY VALVE C
3-WAY VALVE C
2-WAY VALVE D
3-WAY VALVE D
VALVE THERMISTOR E
2-WAY VALVE E
3-WAY VALVE E
02-29
Trouble shooting 25
OUTDOOR UNIT Error Method:
3-Way Valve Thermistor Error
Indicate of Display:
Indoor Unit
Operation lamp : 7 time Flash
Timer lamp: 6 time Flash
ERROR CODE : [E : 76]
Outdoor Unit
ABCDEF
7
: Light ON: Light OFFn : n time blinking
Monitor
6
Detective Actuators:
Outdoor unit main PCB circuit
3 Way valve temperature thermistor
Detective details:
When 3 Way valve temperarture thermistor open or short-circuit is detected
at power ON or while running the compressor.
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
-30
-22
Temperature (°C)
Temperature (°F)
Resistance Value
(k )
140
12.30
If Thermistor is either open or shorted, replace it and reset the power.
-20
-4
158
8.70
292.91531.561013.11
-10
14
807060
176
6.27
32
0
10
50
40
1048668
26.3440.0162.55100.91168.60
503020
122
17.79
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AOU36RLXFZHFor AOU45RLXFZ
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
CN64
11
22
33
44
55
66
77
88
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
VALVE THERMISTOR C, D
BLACK
CN65
11
22
33
44
55
66
77
88
99
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
2-WAY VALVE C
3-WAY VALVE C
2-WAY VALVE D
3-WAY VALVE D
If the voltage does not appear, replace Main PCB.
CN64
CN65
CN66
BLACK
1
1
BLACK
2
2
BLACK
3
3
BLACK
4
4
BLACK
5
5
BLACK
6
6
BLACK
7
7
BLACK
8
8
BLACK
1
1
BLACK
2
2
3
3
BLACK
4
4
BLACK
5
5
BLACK
6
6
BLACK
7
7
BLACK
8
8
BLACK
9
9
BLACK
1
1
BLACK
2
2
3
3
BLACK
4
4
BLACK
5
5
6
6
7
7
8
8
9
9
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
VALVE THERMISTOR C, D
2-WAY VALVE C
3-WAY VALVE C
2-WAY VALVE D
3-WAY VALVE D
VALVE THERMISTOR E
2-WAY VALVE E
3-WAY VALVE E
02-30
Trouble shooting 26
OUTDOOR UNIT Error Method:
CT Error
Indicate of Display:
Indoor Unit
Operation lamp : 8 time Flash
Timer lamp: 4 time Flash
ERROR CODE : [E : 84]
Outdoor Unit
ABCDEF
8
: Light ON: Light OFFn : n time blinking
Monitor
4
Detective Actuators:Detective details:
Outdoor unit main PCB When Input Current Sensor has detected 0A, while Inverter Compressor is
operating at higher than 60 rps, after 1 minutes upon starting the Compressor.
( Except during the defrost operation )
Forecast of Cause:
1. Defective connection of electric components 2. External cause 3. Main PCB failure
Test 1-1 : Reset Power Supply and operate
NO
Does Error indication show again?
YES
Test 2 : Check connections of Outdoor Unit
Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring,
reset the power.
OK
Test 4 : Replace Main PCB
If Test 1, 2 do not improve the symptom, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
Test 1-2 :
Check external cause at Indoor and Outdoor
( Voltage drop or Noise )
Instant drop : Check if there is a large load electric
apparatus in the same circuit.
Momentary power failure : Check if there is a defective
contact or leak current in the
power supply circuit.
Noise : Check if there is any equipment causing harmonic
wave near electric line.(Neon bulb or electric
equipment that may cause harmonic wave)
Check the complete insulation of grounding.
02-31
Trouble shooting 27
OUTDOOR UNIT Error Method:
Discharge Pressure Sensor Error
Indicate of Display:
Indoor Unit
Operation lamp : 8 time Flash
Timer lamp: 6 time Flash
ERROR CODE : [E : 86]
Detective Actuators:Detective details:
Discharge pressure sensor
When any of the following conditions is satisfied, a discharge pressure
・
sensor error is generated.
30 seconds or more have elapsed since the outdoor unit power was
turned on and pressure sensor detected value < 0.3V continued
for 30 seconds or more
30 seconds or more have elapsed since the outdoor unit power was
turned on and pressure sensor detected value > 5.0V was detected.
Test 1 : Check ambient temp. around motor,Heat Exchanger
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
>>Upon the temperature coming down, restart operation.
OK
ABCDEF
9
: Light ON: Light OFFn : n time blinking
Monitor
4
Test 2 : Check Outdoor Fan
Is the Fan rotating by hand when operation is off?
>> If the Fan Motor is locked, replace it.
OK
Test 3 : Replace Main PCB
If Test 1 - 2 do not improve the symptom, change Main PCB.
OK
Test 4 : Replace Compressor
If Test 3 do not improve the symptom, change Compressor.
02-33
Trouble shooting 29
OUTDOOR UNIT Error Method:
Compresor Control Error
Indicate of Display:
Indoor Unit
Operation lamp : 9 time Flash
Timer lamp: 5 time Flash
ERROR CODE : [E : 95]
Outdoor Unit
ABCDEF
9
: Light ON: Light OFFn : n time blinking
Monitor
5
Detective Actuators:
Outdoor unit main PCB
Compressor
Detective details:
While running the compressor, if the detected rotor location is out of phase
with actual rotor location more than 105°, the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40 sec,the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Forecast of Cause:
1. Defective connection of electric components2. Main PCB failure 3. Compressor failure
Test 1 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(SERVICE PARTS INFORMATION 2)
>>Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Replace Main PCB
If Test 1 do not improve the symptom, change Main PCB.
(SERVICE PARTS INFORMATION 10)
OK
Test 3 : Replace Compressor
If Test 2 do not improve the symptom, change Compressor.
02-34
Trouble shooting 30
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Motor Error
Indicate of Display:
Indoor Unit
Operation lamp : 9 time Flash
Timer lamp: 7 time Flash
ERROR CODE : [E : 97]
Detective Actuators:Detective details:
Outdoor unit main PCB circuit
Outdoor unit fan motor
When outdoor unit fan rotation speed is less than 100 rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60 sec is repeated
3 times in a row, compressor and fan motor stops.
If and repeats 5 times in a row, compressor and fan motor stops
permanently.
Forecast of Cause:
1. Fan rotation failure2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor failure
Test 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Outdoor Unit
ABCDEF
9
: Light ON: Light OFFn : n time blinking
Monitor
7
Test 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Test 3 : Check Outdoor unit fan motor
Check Outdoor unit fan motor. (PARTS INFORMATION 6)
>>If Outdoor Fan Motor is abnormal, replace Outdoor fan motor and Main PCB.
OK
Test 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
RED
1
CN243
2
3
4
5
6
7
1
2
3
BLACK
4
WHITE
5
YELLOW
6
BROWN
7
FAN MOTOR
FM
If the voltage is not correct, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
Read wireDC voltage
Red - Black
White - Black
260 - 400V
15 1.5V
02-35
Trouble shooting 31
OUTDOOR UNIT Error Method:
4-Way Valve Error
Indicate of Display:
Indoor Unit
Operation lamp : 9 time Flash
Timer lamp: 9 time Flash
ERROR CODE : [E : 99]
Outdoor Unit
ABCDEF
9
: Light ON: Light OFFn : n time blinking
Monitor
9
Detective Actuators:
Indoor unit main PCB
Heat Ex. temperature thermistor
Room temperature thermistor
4-Way valve
Detective details:
When the indoor unit Heat Ex. temperatrure is compared with the
room temperature, and either following condition is detected
continuously 2 times, compressor stops.
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or miss-wiring, reset the power.
OK
Test 2 : Check thermistor of Indoor unit
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor, (Refer to Trouble shooting 7,8),
If defective, replace the thermistor.
OK
Test 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN202 from PCB and check the resistance value of coil.
Resistance value is about 2085 +10% (68°F(20°C))
>> If it is Open or abnormalresistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
OK
Test 4 : Check the voltage of 4-way valve
Check the CN202 voltage of Main PCB
Check if AC187V(AC208V-10%) - 253V(AC230V+10%) appears at CN 202 of Main PCB.
[ Heating operation ]
>> If it is not voltage, Replace Main PCB.
[ Cooling operation ]
>> If it is voltage, Replace Main PCB.
OKOK
Test 5 : Replace Controller PCB
If Test 1- 4 do not improve the symptom, replace Controller PCB of Indoor unit .
-
(SERVICE PARTS INFORMATION 10)
(SERVICE PARTS INFORMATION 10)
02-36
Trouble shooting 32
OUTDOOR UNIT Error Method:
Coil (expansion valve ) Error
Indicate of Display:
Indoor Unit
Operation lamp : 9 time Flash
Timer lamp
ERROR CODE : [E : 9A]
: 10 time Flash
Outdoor Unit
ABCDEF
9
: Light ON: Light OFFn : n time blinking
Monitor
10
Detective Actuators:
EEV Coil
Detective details:
Coil (Expansion valve) driver circuit open detected.
3. Defective EEV coil 4. Main PCB (DC12V) output abnormal
Test 1 : Check the connection of EEV connector
Check if the connector is loose connection or not.
OK
Test 2 : Check the EEV wire
Check if the wire of EEV has damage or not.
(Slash, Braking of wire, Pinching, etc.)
OK
Test 3 : Check the EEV Coil
Check if the circuit of EEV coil winding is good or not.
(Refer to the service parts information 3)
Replace EEV Coil
NG
Replace EEV Coil
NG
OK
Test 4 : Check the output of EEV on the Main PCB
Check if the DC12V is on between the Pin No.1 of CN111-115 and GND Pin.
(Disconnect the wire of EEV when you check the output of EEV)
OK
Replace Main PCB
(SERVICE PARTS INFORMATION 10)
Test 5 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
NG
02-37
Trouble shooting 33
OUTDOOR UNIT Error Method:
Discharge Temperature Error
Indicate of Display:
Indoor Unit
Operation lamp : 10 time Flash
Timer lamp: 1 time Flash
ERROR CODE : [E : A1]
Outdoor Unit
ABCDEF
110
: Light ON: Light OFFn : n time blinking
Monitor
1
Detective Actuators:
Outdoor unit main PCB
Discharge pipe temperature thermistor
Forecast of Cause:
1. 3-way valve not opened2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger4. Discharge temperature thermistor failure
5. Insufficient refrigerant6. Main PCB failure
<Cooling operation>
Test 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Test 2 : Check the EEV, strainer
EEV open?
Strainer clogging check
(SERVICE PARTS INFORMATION 3)
OK
Detective details:
Protection stop by Discharge pipe temperature thermistor > 230°F(110°C)
during compressor operation generated 2 times within 24 hours.
<Heating operation>
=
Test 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Test 2 : Check the EEV, strainer
EEV open?
Strainer clogging check
(SERVICE PARTS INFORMATION 3)
Test 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (SERVICE PARTS INFORMATION 6)
OK
Test 4 : Check the discharge thermistor
Discharger thermistor characteristics check.
(Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 20".
OK
Test 5 : Check the refrigerant amount
Leak check
OK
02-38
Trouble shooting 34
OUTDOOR UNIT Error Method:
Compressor Temperature Error
Indicate of Display:
Indoor Unit
Operation lamp : 10 time Flash
Timer lamp: 3 time Flash
ERROR CODE : [E : A3]
Outdoor Unit
ABCDEF
110
: Light ON: Light OFFn : n time blinking
Monitor
3
Detective Actuators:
Compressor temperature thermistor
Forecast of Cause:
1. 3-way valve not opened2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger4. Compressor temperature thermistor failure
5. Insufficient refrigerant6. Main PCB failure
<Cooling operation>
Test 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Test 2 : Check the EEV, strainer
EEV open?
Strainer clogging check
(SERVICE PARTS INFORMATION 3)
OK
Detective details:
Protection stop by Compressor temperature thermistor > 226.4°F(108°C)
during compressor operation generated 2 times within 24 hours.
<Heating operation>
=
Test 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Test 2 : Check the EEV, strainer
EEV open?
Strainer clogging check
(SERVICE PARTS INFORMATION 3)
Test 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (SERVICE PARTS INFORMATION 6)
OK
Test 4 : Check the compressor thermistor
Compressor thermistor characteristics check.
(Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 21".
OK
Test 5 : Check the refrigerant amount
Leak check
OK
02-38
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Trouble shooting 35
Indoor unit - No Power
Forecast of Cause :
1. Power supply failure.
2. External cause.
3. Electrical components defective.
Test 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OK
Test 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Test 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC187 - 253V appears at Outdoor Unit Terminal L1 - L2.
YES
Check Fuse of between of Terminal and Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB
is loose, and replace Fuse.
Check Varistor in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
Upon checking the normal power supply, replace Varistor.
OK
Test 4 : Replace Filter PCB
If Test 1- 3 do not improve the symptom, replace Filter PCB.
02-40
Trouble shooting 36
Outdoor unit - No Power
Forecast of Cause :
1. Power supply failure.
2. External cause.
3. Electrical components defective.
Test 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OK
Test 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Test 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC187 - 253V appears at Outdoor Unit Terminal L1 - L2.
YES
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose,
and replace Fuse.
YES
Check Active Filter Module. (PARTS INFORMATION 8)
>> If Active Filter Module is abnormal, replace it.
OK
Test 4 : Replace Main PCB
If Test 1- 3 do not improve the symptom, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
02-41
Trouble shooting 37
No Operation (Power is ON)
Forecast of Cause :
1. Setting / Connection failure.
2. External cause.
3. Electrical components defective.
Test 1 : Check indoor and outdoor installation condition
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control.
Or, check if there is an open cable connection.
Are these Indoor unit, Outdoor unit, and Remote control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
OK
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor unit and Outdoor unit?
OK
Test 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Test 3 : Check Wired Remote Controller and Controller PCB
Check Voltage at terminal 1-3 of Controller PCB or Communication PCB.
(Power supply to Remote Control)
Compact Cassette, Slim Duct Type : CN14
Wall Mount , Floor Type : CN16
Compact Wall Mount Type : CNC01(UTY-XCBXZ2)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again)
>> Check Indoor unit fan motor. (SERVICE PARTS INFORMATION 5)
If it is normal, replace Controller PCB.
If it is abnormal, replace Indoor unit fan motor and Controller PCB.
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
(SERVICE PARTS INFORMATION 10)
02-42
Trouble shooting 38
Forecast of Cause :
No Cooling / No Heating
Test 1 : Check Indoor Unit
Does Indoor unit FAN run on HIGH FAN?
Is Air filter dirty?
Is Heat exchanger clogged?
Check if Energy save function is operated.
OKOK
Test 2 : Check Outdoor Unit Operation
Check if Outdoor unit is operating
Check any objects that obstruct the air flow route.
Check clogged Heat exchanger.
Is the Valve open?
OK
1. Indoor / Outdoor unit error.
2. Effect by surroudingding environment.
3. Connection pipe / Connection wire failure
4. Refrigeration cycle failure.
Test 3 : Check Site Condition
Is capacity of Indoor unit fitted to Room size?
Any windows open? Or direct sunlight ?
OK
Test 4 : Check Indoor/ Outdoor Installation Condition
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data & Technical
Manual.
OK
PSI
Test 5 : Check Refrigeration Cycle
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV (SERVICE PARTS INFORMATION 3)
Check Compressor (SERVICE PARTS INFORMATION 1,2)
Check Heater unit (SERVICE PARTS INFORMATION 7)
Attention
Strainer normally does not have temperature difference
between inlet and outlet as shown in , but if there is a
difference like shown in , there is a possibility of inside
clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
PSI
Pipe (In)Pipe (Out)
䐠
䐟
02-43
Trouble shooting 39
Abnormal Noise
Forecast of Cause :
1. Abnormal installation (Indoor / Outdoor unit).
2. Fan failure (Indoor / Outdoor unit).
3. Compressor failure (Ourdoor unit).
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor unit.
(Check and correct followings)
Abnormal noise is coming from Outdoor unit.
(Check and correct followings)
Is Main Unit installed in stable condition?
Is the installation of Air suction grille and
front panel normal?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Trouble shooting 40
Forecast of Cause :
Water Leaking
Is Main Unit installed in stable condition?
Is Fan Guard installed normally?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
OK
Check if vibration noise by loose bolt or contact noise
of piping is happening.
OK
Is Compressor locked?
>> Check Compressor
(SERVICE PARTS INFORMATION 1,2)
1. Erroneous installation.
2. Drain hose failure.
Diagnosis method when water leak occurs
Is Main unit installed in stable condition?
Is Main unit broken or deformed at the time of
transportation or maintenance?
OK
Is Drain hose connection loose?
Is there a trap in Drain hose?
Is Drain Hose clogged?
OK
Is Fan rotating?
02-44
Diagnosis method when water is spitting out.
Is the filter clogged?
OK
PSI
Check Gas pressure and correct it
if there was a gas leak.
PSI
Trouble shooting 41
Too Warm
Forecast of Cause :
1. House insulation setting has not been changed.
2. Temperature sensing location has not been changed.
3. Installation location of the wired remote.
4. Function settings have not been changed.
Test 1 : Check insulation level of structure of house
Is insulation level greater than R-13.
NO
Too warm
Test 2 : Verity room temperature sensing location
Do you want room temperature sensed at
the wired remote controller (Wired remote sensor)
or by they build in sensor inside the unit
(Indoor unit sensor).
“Indoor unit sensor”
Test3 : Check the remote controller display
Test 1-1 : Check Function Setting
YES
If insulation level is greater than R-13
set function
95 to 01.
Ref.)
Setting Value
95
※
Please reference the APPENDING DATA
00
01
Setting DescriptionFunction Number
Standard insulation
High insulation
OK
Test 1-2 : Check effects of Function Setting change
Is the space still too warm in relation to set point.
“Wired remote sensor”
TO NEXT PAGE
Test 3-1 : Check the remote controller
Is the "Thermo Sensor Icon" displayed
on the screen?
NO
Test 4 : Check Function Settings
Using the table on the right adjust function 31.
(Room Temperature Control for indoor unit sensor)
※
Please reference the APPENDING DATA
Hold down the THERMO SENSOR button until the
thermo sensor icon is turned off.
YES
Too warm
Setting Value
00
01
02
03
04
05
06
07
08
09
No correction 0.0°F (0.0°C)
02-45
Ref.)
31
(For heating)
Setting DescriptionFunction Number
Standard setting
-1°F (-0.5°C)
-2°F (-1.0°C)
-3°F (-1.5°C)
-4°F (-2.0°C)
-5°F (-2.5°C)
-6°F (-3.0°C)
-7°F (-3.5°C)
-8°F (-4.0°C)
Less
Heating
“Wired remote sensor”
Test 3 : Check the remote controller display
Is the "Thermo Sensor Icon" displayed on the screen?
YES
Too warm
Test 4 : Check the Function Setting
Is function 48 (Room temperature sensor switching)
set to 01?
YES
Too warm
NO
NO
Test 3-1 : Check Function Setting
Is function 42 (Indoor room temperature sensor
switching function) set to 01?
Ref.)
Setting DescriptionFunction Number Setting Value
42
※
Please reference the APPENDING DATA
00
01
Indoor unit
Both
OK
Test 3-2 : Check the remote controller
Press and hold down the THERMO SENSOR
button to turn on the icon.
Test 4-1 : Check the Function Setting
Change setting of function 48
(Room temperature sensor switching) to 01.
Ref.)
Setting DescriptionFunction Number Setting Value
48
※
Please reference the APPENDING DATA
00
01
Both
Wired remote controller
OK
Test 4-2 : Check the effects of Function
Setting change
Did this function setting improve temperature control?
Test 5 : Location of the remote controller
Is the mounting location of the wired remote
controller affecting the temperature sensing?
(Sunlight on the remote, heat source next to the remote)
NO
Test 6 : Check Function Setting
Using the table on the right adjust temperature correction
by changing function setting 93.
(Room Temperature control for wired remote controller sensor)
※
Please reference the APPENDING DATA
YES
02-46
Test 5-1 : Location of the remote controller
Move the remote controller.
Too war m
Ref.)
Setting DescriptionFunction Number Setting Value
00
No correction 0.0°F (0.0°C)
No correction 0.0°F (0.0°C)
2. Temperature sensing location has not been changed.
3. Installation location of the wired remote.
4. Function settings have not been changed.
Test 1 : Check insulation level of structure of house
Is insulation level greater than R-13.
NO
Too cool
Test 2 : Verity room temperature sensing location
Do you want room temperature sensed at
the wired remote controller (Wired remote sensor)
or by they build in sensor inside the unit
(Indoor unit sensor).
“Indoor unit sensor”
Test3 : Check the remote controller display
Test 1-1 : Check Function Setting
YES
If insulation level is greater than R-13
set function
95 to 01.
Ref.)
Setting Value
95
※
Please reference the APPENDING DATA
00
01
Setting DescriptionFunction Number
Standard insulation
High insulation
OK
Test 1-2 : Check effects of Function Setting change
Is the space still too warm in relation to set point.
“Wired remote sensor”
TO NEXT PAGE
Test 3-1 : Check the remote controller
Is the "Thermo Sensor Icon" displayed
on the screen?
NO
Test 4 : Check Function Settings
Using the table on the right adjust function 30.
(Room Temperature Control for indoor unit sensor)
※
Please reference the APPENDING DATA
Hold down the THERMO SENSOR button until the
thermo sensor icon is turned off.
Is the "Thermo Sensor Icon" displayed on the screen?
YES
Too cool
Test 4 : Check the Function Setting
Is function 48 (Room temperature sensor switching)
set to 01?
YES
Too cool
NO
NO
Test 3-1 : Check Function Setting
Is function 42 (Indoor room temperature sensor
switching function) set to 01?
Ref.)
Setting DescriptionFunction Number Setting Value
42
※
Please reference the APPENDING DATA
00
01
Indoor unit
Both
OK
Test 3-2 : Check the remote controller
Press and hold down the THERMO SENSOR
button to turn on the icon.
Test 4-1 : Check the Function Setting
Change setting of function 48
(Room temperature sensor switching) to 01.
Ref.)
Setting DescriptionFunction Number Setting Value
48
※
Please reference the APPENDING DATA
00
01
Both
Wired remote controller
OK
Test 4-2 : Check the effects of Function
Setting change
Did this function setting improve temperature control?
Test 5 : Location of the remote controller
Is the mounting location of the wired remote
controller affecting the temperature sensing?
(Sunlight on the remote, heat source next to the remote)
NO
Test 6 : Check Function Setting
Using the table on the right adjust temperature correction
by changing function setting 92.
(Room Temperature control for wired remote controller sensor)
※
Please reference the APPENDING DATA
YES
02-48
Test 5-1 : Location of the remote controller
Move the remote controller.
Too cool
Ref.)
Setting DescriptionFunction Number Setting Value
00
No correction 0.0°F (0.0°C)
No correction 0.0°F (0.0°C)
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection
cable?
Check Filter PCB, Main PCB,
connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection
cable?
Is Gas Pipe Valve open?
(Low Pressure is too low)
Check if Refrigerant is leaking.
(Recharge Refrigerant)
PSI
PSI
Abnormal noise
Check if vibration noise by
loose bolt or contact noise
of piping is happening.
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Replace Compressor
Check if Strainer is clogged.
(
PARTS INFORMATION 3)
Check Filter PCB, Main PCB,
connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
Replace Compressor
02-49
SERVICE PARTS INFORMATION 2
Compressor
Test 1 : Check Connection
Check terminal connection of Compressor
(loose or incorrect wiring)
V(S)
(WHITE)
Main PCB
W (T)
(BLACK)
U(R)
(RED)
Test 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
U(R)
Check terminal connection of Main PCB
(loose or incorrect wiring)
Main PCB
RED
TM403
TM404
Compressor
TM405
BLACK
WHITE
W (T)
V(S)
Test 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
Resistance Value : 0.642 + 8% (68°F(20°C))
02-50
-
SERVICE PARTS INFORMATION 3
Outdoor unit electronic expansion valve
(EEV)
Test 1 : Check Connections
Check connection of connector
( Loose connector or open cable )
For AOU36RLXFZHFor AOU45RLXFZ
CN111
CN112
CN113
CN114
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
66
1
2
3
4
5
66
RED
1
BLUE
2
ORANGE
3
YELLOW
4
WHITE
5
RED
1
BLUE
2
ORANGE
3
YELLOW
4
WHITE
5
RED
1
2
BLUE
3
ORANGE
4
YELLOW
5
WHITE
RED
1
2
BLUE
3
ORANGE
4
YELLOW
5
WHITE
EXPANSION
EV
VALVE COIL A
EXPANSION
EV
VALVE COIL B
EXPANSION
EV
VALVE COIL C
EXPANSION
EV
VALVE COIL D
CN111
CN112
CN113
CN114
CN115
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
66
1
2
3
4
5
66
1
2
3
4
5
66
77
RED
1
BLUE
2
ORANGE
3
YELLOW
4
WHITE
5
RED
1
BLUE
2
ORANGE
3
YELLOW
4
WHITE
5
RED
1
2
BLUE
3
ORANGE
4
YELLOW
5
WHITE
RED
1
2
BLUE
3
ORANGE
4
YELLOW
5
WHITE
RED
1
2
3
BLUE
4
ORANGE
5
YELLOW
WHITE
EXPANSION
EV
VALVE COIL A
EXPANSION
EV
VALVE COIL B
EXPANSION
EV
VALVE COIL C
EXPANSION
EV
VALVE COIL D
EXPANSION
EV
VALVE COIL E
02-51
Test 2 : Check Coil of EEV
Remove connector, check each winding resistance of Coil.
Read wire
Resistance value
White - Red
Yellow - Blue
Orange - Red
46
at 68°F(20°C)
4
Blue - Orange
If Resistance value is abnormal, replace EEV.
Test 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Test 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
(SERVICE PARTS INFORMATION 10)
Test 5 : Check Opening and Closing Operation of Valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot Gas
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot Gas
Pipe (In)
Hi TEMP.
Test 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in ,
but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (Out)
Normal TEMP.
)tuO( epiP)nI( epiP
Pipe (In)
Hi TEMP.
Pipe (Out)
Hi TEMP.
)tuO( epiP)nI( epiP
02-52
SERVICE PARTS INFORMATION 4
Discharge pressure sensor
Test 1 : Check the voltage from Main PCB
With the connector connected to the Main PCB,
measure the voltage between CN 92 : 1 - 2 of the Main PCB
CN92
+
-
Characteristics of pressure sensor
4.5
Output [DCV]
0.5
0
Pressure [MPa]
5.0
1
2
3
RED
WHITE
BLACK
PSDischarge pressure sensor
02-53
SERVICE PARTS INFORMATION 5
Indoor unit fan motor
Test 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Test 2 : Check resistance of Indoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
For Compact Wall Mount, Wall Mount Type
Pin number
(wire color)
1 (Blue)
2 (Yellow)
3 (White)
4 (Black)
5
6 (Red)
Terminal function
(symbol)
Feed back (FG)
Speed command (Vsp)
Control voltage (Vcc)
Ground terminal (GND)
No function
DC voltage (Vm)
For Compact Cassette Type
Pin number
(wire color)
1 (Red)
2
3 (White)
4 (Black)
5No function
6
7 (Yellow)
8 (Brown)Feed back (FG)
Terminal function
(symbol)
DC voltage (Vm)
No function
Control voltage (Vcc)
Ground terminal (GND)
Feed back (FG)
Speed command (Vsp)
Control voltage (Vcc)
Ground terminal (GND)
No function
DC voltage (Vm)
For Slim Duct Type
Pin number
(wire color)
1 (Blue)
2 (Yellow)
3 (White)
4 (Black)
5
6 (Red)
Feed back (FG)
Speed command (Vsp)
Control voltage (Vcc)
Ground terminal (GND)
No function
DC voltage (Vm)
Terminal function
(symbol)
Terminal function
(symbol)
02-54
SERVICE PARTS INFORMATION 6
Outdoor unit fan motor
Test 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Test 2 : Check resistance of Outdoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
(SERVICE PARTS INFORMATION 10)
Pin number
(wire color)
1 (Red)
2
3No function
4 (Black)
5 (White)
6 (Yellow)
7 (Brown)
Terminal function
(symbol)
DC voltage (Vm)
No function
Ground terminal (GND)
Control voltage (Vcc)
Speed command (Vsp)
Feed back (FG)
02-55
For AOU36RLXFZH
S
ERVICE PARTS INFORMATION 7
Heater unit
Test 1 : Check Connections
Check connection of connector
( Loose connector or open cable )
WHITE
BLACK
1234
1234
HEATER
THERMOSTAT
CN206
Test 2 : Check electrical components
Check Check Fuses.
>> If Fuse is open, check connection, and replace Fuse.
Test 3 : Check Heater wire.
Remove connector, check resistance of Heater wire.
eulav ecnatsiseR eriw daeR
Black - White
If Resistance value is abnormal, replace Heater Unit.
320.7 - 367.3
at 77°F (25°C)
02-56
SERVICE PARTS INFORMATION 8
Active filter module
Test 1 : Check Open or Short-circuit and Diode (D1)
Remove connector, check the open or short-circuit and the diode in the module
Check the open or short-circuit
Table.1 Each type standard value
Terminal
multimeter
(+)
multimeter
(-)
Type AType B
SACT32010 [ HITACHI ]
LACT33020 [ HITACHI ]
PM-601 [ FGEL ]
LOT No. - 1302931395
Resistance value
PM-604 [ FGEL ]
PM-703 [ FGEL ]
PM-601 [ FGEL ]
LOT No. 1302931396 -
LOT No. of PM-601 [ FGEL ] type
Label position
※
※
+ (+IN)*
- ( -IN)*
P
L1
P
L1 , L2
L2
- ( -IN)*
N1 (N)
*
+ (+IN)*
L2
N1 (N)*
Control Box
N1 (N)*
360k
0
720k
1.01M /
(Ref. value 1)
360k
1.65M /
(Ref. value 1)
+
20%
-
+
20%
-
0.76M
(Ref. value 2)
+
20%
-
1.14M
(Ref. value 2)
1.01M /
(Ref. value 1)
* ( ) is FGEL terminal name.
Table.2 Standard value is changed by the tool specification
(Type A and B are the same value)
Terminal
L2
multimeter
(-)
P
P
L2
multimeter
(+)
※
※
By kind of multimeter , the value may change significantly.
※
Ref. value 1
Specifications for Multimeter
Manufacturer : FLUKE
Model name : FLUKE11
Power source : DC9V.
Resistance value
1.32M /
(Ref. value 1)
1.01M /
(Ref. value 1)
0.66M
(Ref. value 2)
0.76M
(Ref. value 2)
Ref. value 2
Specifications for Multimeter
Manufacturer : SANWA
Model name : PM3
Power source : DC3V.
360k
900k
540k
1.65M /
(Ref. value 1)
+
20%
-
0
+
20%
-
0.76M
(Ref. value 2)
+
20%
-
1.14M
(Ref. value 2)
Label
Model name
+ (+IN)*
- ( -IN)*
Lot No.(10 figures)
L2L1
P
N1 (N)*
If it is abnormal,replace ACTIVE FILTER MODULE
Test 2 : Check the Output DC voltage (between P and N)
Check the Output DC voltage (between P and N) of compressor stopping and operating.
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping,
Active Filter Module is detective. >> Replace Active Filter Module
02-57
SERVICE PARTS INFORMATION 9
IPM
(Mounted on Transistor PCB)
Test 1 : Check the Transistor of PCB ( for Resistance )
Disconnect the connection wires between the Transistor
PCB - Capacitor PCB and Transistor PCB - Inverter
Compressor.
Set the tester to the "Resistance" mode, and measure
the resistance between the following terminals.