Fujitsu ARGA18FMTA, AOGA25FBTAH, ARGA25FMTA, AOGA18FBTAH Design & Technical Manual

Page 1
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AOGA25FBTAHAOGA18FBTAH
ARGA18FMTA ARGA25FMTA
AIR CONDITIONER
Duct type
Page 2
1. INDOOR UNIT
DTR_AR087E_02
2015.02.05
DUCT TYPE:
ARGA1 8FMTA
ARGA25FMTA
Page 3
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
CONTENTS
1. INDOOR UNIT
1. FEATURES
.............................................................................................................. 01 - 01
2. WIRED REMOTE CONTROLLER
......................................................... 01 - 03
3. SPECIFICATIONS
..............................................................................................01 - 05
4. DIMENSIONS
........................................................................................................01 - 06
5. WIRING DIAGRAMS
........................................................................................ 01 - 08
6. CAPACITY TABLE
............................................................................................01 - 10
6-1. COOLING CAPACITY
......................................................................................01 - 10
7. FAN PERFORMANCE AND CAPACITY
...........................................01 - 11
7-1. NORMAL MODE
................................................................................................01 - 11
7-2. STATIC PRESSURE MODE 1
......................................................................... 01 - 13
7-3. STATIC PRESSURE MODE 2
......................................................................... 01 - 15
7-4. STATIC PRESSURE MODE 3
......................................................................... 01 - 17
8. OPERATION NOISE (SOUND PRESSURE)
................................. 01 - 19
8-1. NOISE LEVEL CURVE
....................................................................................01 - 19
8-2. SOUND LEVEL CHECK POINT
..................................................................... 01 - 20
9. SAFETY DEVICES
............................................................................................ 01 - 21
10. EXTERNAL INPUT & OUTPUT
............................................................... 01 - 22
10-1. EXTERNAL INPUT
........................................................................................... 01 - 22
10-2. EXTERNAL OUTPUT
....................................................................................... 01 - 23
11. FUNCTION SETTINGS
.................................................................................. 01 - 25
11-1. INDOOR UNIT
................................................................................................... 01 - 25
11-2. INDOOR UNIT (Setting by remote controller)
........................................... 01 - 26
11-3. WIRED REMOTE CONTROLLER
.................................................................. 01 - 29
12. OPTIONAL PARTS
...........................................................................................01 - 31
Page 4
- (01 - 01) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
FEATURES1.
MODELS
ARGA18FMTA / AOGA18FBTAH ARGA25FMTA / AOGA25FBTAH
FEATURES
Installation styles
z
Slim & compact design
z
In the case of rear suction type, as seen from lower rear part.
Control Box united with main unit
One-touch operating and easy-to-install
long-life lter (optional)
In addition to the slim height of 270 mm, further compactication is attained by reducing 65 mm from the width with the anking control box embedded inside the chassis.
Easy maintenance
z
The fan and motor is easily accessible by the divided panel structure.
Structural improvement is attained by making the bottom panel in two pieces, front and rear.
The internal fan casing is also manufactured in two pieces, namely upper and lower. The maintenance
of the motor and fan can be easily carried out by removing the rear panel and the lower part of the casing while leaving the main chassis installed.
1
3
Bottom panel: 2 units
2
4
1. Control box
2. Fan casing
3. Fan
4. Motor
Embedded in Ceiling Hanging from Ceiling
AOGA25FBTAH
AOGA18FBTAH
Page 5
- (01 - 02) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
Quiet operation
z
Quiet operation at 25 dB (A) is possible in quiet mode.
Economy operation
z
The power consumption can be reduced.
Operation in high ambient temp
z
The operation is secured under the ambient temperature of up to 52 degrees celsius.
Cooling
21 to 52
°C
Page 6
- (01 - 03) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
WIRED REMOTE CONTROLLER2.
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
• Equipped with weekly timer as standard function.(Start/Stop function is
• twice per day for a week)
When setting up the timer, start/stop and a temperature setup can be
changed. When a failure occurs, the error code is displayed.
• Error history.(Last 16 error codes can be accessed.)
• Up to 16 indoor units can be simultaneously controlled.
• The room temperature can be controlled by being detective the
temperature accurately with Built-in thermo sensor.
Simple function setting
z
Setting of the air conditioner selection function is performed by remote controller.
High performance and compact size
z
Built-in timers
Weekly timer Setback timer
At "Weekly timer" + "Set back timer" setup
Easy-to-understand operation
z
[Variable timer control]
The operation/display sections are zoned
according to time and operation, enabling variable programming to match application.
Simple installation
z
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is
needed.
European
switch box
JIS box
SUMOTUWETH FR SA
7
3126 9
15 18 21
SUMOTUWETH FR SA
7
3126 9
15 18 21
SUMOTUWETH FR SA
3126 9
15 18 21
Possible to set ON/OFF time to operate twice each day of the week.
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
Screen after setup
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
Possible to set temperature for two time spans and for each day of the week.
Easy-to-understand time bar indicator
24°C
0 3 6 9 12 15 18 21 Time
28°C
0 3 6 9 12 15 18 21 Time
28°C
24°C
0 3 6 9 12 15 18 21 Time
24°C 28°C 24°C
Timer area
Operation area
Page 7
- (01 - 04) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
FUNCTIONS
Display panel
DIMENSION
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 18 WEIGHT ( g ) 160 CABLE LENGTH ( m ) 10 POWER ( V ) 12
WIRING SPECIFICATIONS
Use Size Wire type Remarks
Remote controller cable
0.33 mm
2
(22 AWG)
Polar 3 core
Use sheathed
PVC cable
15
11
10
9
8
2
1 3
5
14
4
12
13
6 7
17
16
18
19
20
21
120
120
120
18
Side ViewFront View
1
START/STOP button
Pressed to start and stop operation.
2
SET TEMP. button
Selects the setting temperature.
3
MODE button
Selects the operating mode (AUTO , COOL , DRY , FAN ).
4
FAN button
Selects the fan speed (AUTO , HIGH , MED , LOW , QUIET
).
5
ECONOMY button
Turns the economy efcient mode on and off.
6
TIMER MODE (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER). Set the current time.
7
DAY (DAY OFF) button
Temporarily cancels of one day timer.
8
SET BACK button
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
TIMER DELETE button
The schedule of a weekly timer is deleted.
11
TIMER SET button
Sets the date, hour, minute and on-off time.
12
 Verticalairowdirectionandswingbutton
Push for two seconds to change the swing mode.
13
 Horizontalairowdirectionandswingbutton
Push for two seconds to change the swing mode.
14
FILTER RESET button
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock indicator
17
Operation mode indicator
18
Fan speed indicator
19
Operation lock indicator
20
Temperature indicator
21
Function indicator
Defrost indicator Thermo sensor indicator Economy indicator Vertical swing indicator Horizontal swing indicator Filter indicator
NOTE:
Functions w ill be dif ferent due to type of indoor unit.
For details please see operation manual.
[ Unit: mm ]
Page 8
- (01 - 05) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
SPECIFICATIONS3. SPECIFICATIONS3.
NOTES :
Specicatio ns are based on the foll owing conditions:
Cooling (T1) : Indoor temperature of 27 °CDB / 19 °CWB, and outdoor temperature of 35 °CDB / 24 °CWB. Standard static pressure : 35 Pa Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit–Indoor unit)
The prote ctive fun ction mi ght work wh en using it in environm ent out of the temperature range mentioned above.
• Drain ho se should b e locall y purchas ed.
*1: The maximum current i s the maximum value wh en operated within t he operation rang e. *2: These a re the meas ured value s in the manu facture r’s anechoic chamb er.
Becaus e of the surr ounding s ound envir onment, t he sound levels measured in actua l installation conditions might be higher than the specied values here.
Type
DUCTED MODEL
COOLING ONLY Model name ARGA18FMTA ARGA25FMTA Power source 220 / 240 V ~ 50 Hz Available voltage ra nge 198 to 264 V COOLING (T1 condition)
Capacity
kW 5.20 / 5.20 6.45 / 6.45
Btu/h 17,800 / 17,800 22,000 / 22,000 Input power kW 1.51 / 1.53 1.88 / 1.91 Current A 7.0 / 6.5 8.8 / 8.5 EER Btu/hW 11.79 / 11.63 11.70 / 11.52 Sensibl e capaci ty kW 4.10 / 4.10 5.08 / 5.08 Power factor % 98.1 / 98.1 97.1 / 93.6
Moisture removal
l/h
(pints/h)
1.6 (2.8) 1.9 (3.3)
Maximum operating current *1 Cooling A 13.5 16.7
Fan
Airow
rate
Cooling
High
m
3
/h
1,050 1,200
Med 860 960
Low 740 820
Quiet 670 750 Type × Q'ty Sirocco × 2 Motor output W 106
Recommended static pressure Pa 30 to 150
Sound pressure leve l *2 Cooling
High
dB(A)
29 31
Med 27 29
Low 26 27
Quiet 25 25
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 1000 × 39.9 Fin pitch 1.4 Rows x Stages 3 × 14 Pipe type Copper Fin type Aluminium
Enclosure
Material Steel Colour -
Dimensions ( H×W ×D )
Net
mm
270 × 1,135 × 700
Gross
300 × 1,320 × 790
Weight
Net
kg
38
Gross
45
Connection pipe
Size
Liquid
mm
Ø 6.35 (Ø 1/4 in.)
Gas
Ø 15.88 (Ø 5/8 in.)
Method
Flare
Operation range Cooling
°C
18 to 32
%RH
80 or less
Remote controller type
Wired
Drain port
Material
Steel
Size mm
Ø 36.0 (I.D.), Ø 38.0 (O.D.)
Page 9
- (01 - 06) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
DIMENSIONS4.
MODEL : ARGA18FMTA, ARGA25FMTA
(Unit: mm)
Refrigerant piping are connection (Gas)
Refrigerant piping are connection (Liquid)
Drain piping connection
Drain piping connection with cap.
Knock out hole for fresh air.
Front view
Top view
Side view (L)
Side view (R)
Rear view
Page 10
- (01 - 07) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
INSTALLATION PLACE
(Unit: mm)
MAINTENANCE HOLE
WHEN USING A SQUARE DUCT
BOTTOM AIR INTAKE HOLE
It shall be possible to install and remove the control box.
It shall be possible to install and remove the control box, fan units and lter.
Page 11
- (01 - 08) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
WIRING DIAGRAMS5.
MODEL : ARGA18FMTA
Page 12
- (01 - 09) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
MODEL : ARGA25FMTA
Page 13
- (01 - 10) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
CAPACITY TABLE6.
COOLING CAPACITY6-1.
This table is created using the maximum capacity.
MODEL : ARGA18FMTA
MODEL
: ARGA25FMTA
AFR : Airow Ra te (m3/min) TC : Total Capacit y (kW) SHC : S ensible Heat Capa city (kW ) IP : I nput Power (k W)
AFR 17.5
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
21 4.48 3.84 1.15 4.99 3.86 1.17 5.16 4.20 1.17 5.50 4.21 1.19 5.67 4.54 1.19 6.01 4.53 1.21 6.35 4.82 1.21
25 4.45 3.79 1.24 4.95 3.81 1.27 5.12 4.14 1.27 5.45 4.16 1.29 5.62 4.49 1.29 5.96 4.47 1.31 6.29 4.76 1.32 30 4.32 3.67 1.37 4.82 3.69 1.39 4.98 4.01 1.39 5.30 4.03 1.41 5.47 4.35 1.42 5.80 4.33 1.43 6.12 4.62 1.44 35 4.11 3.46 1.47 4.58 3.48 1.50 4.73 3.78 1.51 5.04 3.80 1.52 5.20 4.10 1.53 5.51 4.08 1.54 5.82 4.35 1.56 40 3.89 3.26 1.98 4.33 3.28 2.01 4.48 3.56 2.02 4.78 3.58 2.04 4.93 3.86 2.05 5.22 3.84 2.07 5.52 4.10 2.09 45 3.57 3.09 2.11 3.98 3.11 2.15 4.12 3.38 2.15 4.39 3.39 2.18 4.59 3.66 2.19 4.79 3.65 2.21 5.07 3.88 2.23 52 3.06 2.86 2.33 3.41 2.87 2.37 3.52 3.13 2.38 3.76 3.13 2.40 3.87 3.39 2.42 4.11 3.37 2.44 4.34 3.59 2.46
AFR 20.0
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
21 5.55 4.76 1.43 6.18 4.78 1.46 6.39 5.20 1.47 6.82 5.22 1.48 7.03 5.63 1.49 7.45 5.61 1.50 7.87 5.98 1.51
25 5.51 4.70 1.55 6.14 4.73 1.58 6.35 5.13 1.59 6.76 5.15 1.61 6.97 5.56 1.61 7.40 5.54 1.63 7.81 5.90 1.64 30 5.36 4.55 1.71 5.97 4.58 1.73 6.17 4.97 1.74 6.58 4.99 1.76 6.78 5.39 1.77 7.19 5.37 1.79 7.60 5.72 1.80 35 5.09 4.29 1.84 5.68 4.31 1.87 5.87 4.69 1.88 6.26 4.71 1.90 6.45 5.08 1.91 6.84 5.06 1.93 7.22 5.40 1.95 40 4.83 4.04 2.47 5.37 4.06 2.51 5.56 4.41 2.52 5.93 4.43 2.55 6.11 4.78 2.56 6.48 4.76 2.59 6.85 5.08 2.61 45 4.43 3.82 2.64 4.94 3.85 2.68 5.11 4.19 2.69 5.45 4.20 2.72 5.69 4.53 2.73 5.94 4.52 2.76 6.29 4.81 2.79 52 3.80 3.54 2.91 4.23 3.56 2.96 4.37 3.87 2.97 4.66 3.88 3.00 4.80 4.20 3.02 5.10 4.18 3.05 5.38 4.45 3.08
Page 14
- (01 - 11) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
FAN PERFORMANCE AND CAPACITY7.
NORMAL MODE7-1.
MODEL : ARGA18FMTA
Static pressure (Pa)
13 16 20 22 25 28 30 34 35 38
FAN SPEED
Hi
m
3
/h
- - - - - 1150 1120 1070 1050 950
l/s
- - - - - 319 311 297 292 264
CFM
- - - - - 677 659 630 618 559
Med
m
3
/h
- - - 860 795 - - - - -
l/s
- - - 239 221 - - - - -
CFM
- - - 506 468 - - - - -
Low
m
3
/h
- 820 740 690 - - - - - -
l/s
- 228 206 192 - - - - - -
CFM
- 483 436 406 - - - - - -
Quiet
m
3
/h
740 600 - - - - - - - -
l/s
206 167 - - - - - - - -
CFM
436 353 - - - - - - - -
Hi Med Low Quiet
Q-h Characteristic curve
Static pressure (Pa)
50
40
30
20
10
0
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
104
102
100
98
96
94
92
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Capacity
Page 15
- (01 - 12) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
MODEL : ARGA25FMTA
Static pressure (Pa)
6 11 14 21 25 30 35 40
FAN SPEED
Hi
m
3
/h
- - - - - 1300 1200 1100
l/s
- - - - - 361 333 306
CFM
- - - - - 765 706 647
Med
m
3
/h
- - - 980 910 830 - -
l/s
- - - 272 254 231 - -
CFM
- - - 577 539 489 - -
Low
m
3
/h
- - 825 690 - - - -
l/s
- - 229 192 - - - -
CFM
- - 486 406 - - - -
Quiet
m
3
/h
630 525 - - - - - -
l/s
175 146 - - - - - -
CFM
371 309 - - - - - -
Hi Med Low Quiet
Q-h Characteristic curve
Static pressure (Pa)
50
40
30
20
10
0
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
104
102
100
98
96
94
92
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Capacity
Page 16
- (01 - 13) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
STATIC PRESSURE MODE 17-2.
MODEL : ARGA18FMTA
Static pressure (Pa)
18 22 29 33 41 47 56 64
FAN SPEED
Hi
m
3
/h - - - - - - 1150 950
l/s - - - - - - 319 26 4
CFM - - - - - - 677 559
Med
m
3
/h - - - - 995 810 - -
l/s - - - - 276 225 - -
CFM - - - - 586 477 - -
Low
m
3
/h - - 805 685 - - - -
l/s - - 224 190 - - - -
CFM - - 474 403 - - - -
Quiet
m
3
/h 645 550 - - - - - -
l/s 181 153 - - - - - -
CFM 383 324 - - - - - -
Q-h Characteristic curve
Static pressure(Pa)
70
60
50
40
30
20
10
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
104
102
100
98
96
94
92
Capacity
Page 17
- (01 - 14) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
MODEL : ARGA25FMTA
Static pressure (Pa)
20 23 30 35 40 47 55 65
FAN SPEED
Hi
m
3
/h - - - - - - 1200 1000
l/s - - - - - - 333 278
CFM - - - - - - 706 589
Med
m
3
/h - - - - 1000 815 - -
l/s - - - - 278 226 - -
CFM - - - - 589 480 - -
Low
m
3
/h - - 830 680 - - - -
l/s - - 231 189 - - - -
CFM - - 489 400 - - - -
Quiet
m
3
/h 650 540 - - - - - -
l/s 181 150 - - - - - -
CFM 383 318 - - - - - -
Q-h Characteristic curve
Static pressure(Pa)
70
60
50
40
30
20
10
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
104
102
100
98
96
94
92
Capacity
Page 18
- (01 - 15) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
STATIC PRESSURE MODE 27-3.
MODEL : ARGA18FMTA
Static pressure (Pa)
33 36 49 54 69 73 90 97
FAN SPEED
Hi
m
3
/h - - - - - - 1135
950
l/s - - - - - - 315
264
CFM - - - - - - 668
559
Med
m
3
/h - - - - 990 825 - -
l/s - - - - 275 229 - -
CFM - - - - 583 486 - -
Low
m3/h - - 820 710 - - - -
l/s - - 228 197 - - - -
CFM - - 483 418 - - - -
Quiet
m
3
/h 685 585 - - - - - -
l/s 190 163 - - - - - -
CFM 403 344 - - - - - -
Q-h Characteristic curve
Static pressure(Pa)
110
100
90
80
70
60
50
40
30
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
104
102
100
98
96
94
92
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Capacity
Page 19
- (01 - 16) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
MODEL : ARGA25FMTA
Static pressure (Pa)
35 37 50 55 68 75 93 100
FAN SPEED
Hi
m
3
/h - - - - - - 1160 930
l/s - - - - - - 322 258
CFM - - - - - - 683 547
Med
m3/h - - - - 1020 800 - -
l/s - - - - 283 222 - -
CFM - - - - 600 471 - -
Low
m3/h - - 835 670 - - - -
l/s - - 232 186 - - - -
CFM - - 491 394 - - - -
Quiet
m
3
/h 660 530 - - - - - -
l/s 183 147 - - - - - -
CFM 388 312 - - - - - -
Q-h Characteristic curve
Static pressure(Pa)
110
100
90
80
70
60
50
40
30
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
104
102
100
98
96
94
92
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Capacity
Page 20
- (01 - 17) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
STATIC PRESSURE MODE 37-4.
MODEL : ARGA18FMTA
Static pressure (Pa)
54 56 83 87 113 118 142 150
FAN SPEED
Hi
m
3
/h
- - - - - - 1140 1050
l/s
- - - - - - 317 292
CFM
- - - - - - 671 618
Med
m
3
/h
- - - - 1030 920 - -
l/s
- - - - 286 256 - -
CFM
- - - - 606 542 - -
Low
m
3
/h
- - 880 790 - - - -
l/s
- - 244 219 - - - -
CFM
- - 518 465 - - - -
Quiet
m
3
/h
710 650 - - - - - -
l/s
197 181 - - - - - -
CFM
418 383 - - - - - -
Q-h Characteristic curve
Static pressure(Pa)
150 140 130 120 110 100
90 80 70 60 50
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
104
102
100
98
96
94
92
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Capacity
Page 21
- (01 - 18) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
MODEL : ARGA25FMTA
Static pressure (Pa)
55 58 85 90 115 122 142 150
FAN SPEED
Hi
m
3
/h
- - - - - - 1100 880
l/s
- - - - - - 306 244
CFM
- - - - - - 647 518
Med
m
3
/h
- - - - 1000 810 - -
l/s
- - - - 278 225 - -
CFM
- - - - 589 477 - -
Low
m
3
/h
- - 840 680 - - - -
l/s
- - 233 189 - - - -
CFM
- - 494 400 - - - -
Quiet
m
3
/h
660 525 - - - - - -
l/s
183 146 - - - - - -
CFM
388 309 - - - - - -
Q-h Characteristic curve
Static pressure(Pa)
150 140 130 120 110 100
90 80 70 60 50
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Cooling
z
Cooling capacity (%)
104
102
100
98
96
94
92
500 600 700 800 900 1,000 1,100 1,200 1,300
Airow (m
3
/h)
Capacity
Page 22
- (01 - 19) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
OPERATION NOISE (SOUND PRESSURE)8.
NOISE LEVEL CURVE8-1.
MODEL : ARGA18FMTA
Conditions: Static pressure: 35 Pa Static pressure mode: NORMAL
QUIET
HIGH
COOLING
z
Octave ba nd sound p ressure l evel, dB:(0d B=0.0 002µb ar)
Octave ba nd cente r frequen cy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : ARGA25FMTA
HIGH
QUIET
COOLING
z
Octave ba nd sound p ressure l evel, dB:(0d B=0.0 002µb ar)
Octave ba nd cente r frequen cy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Page 23
- (01 - 20) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
SOUND LEVEL CHECK POINT8-2.
Microphone
Measuring duct
Measuring duct
Set the static pressure
as rating in this area
2 m 1 m
1.5 m
AIR
Microphone
Page 24
- (01 - 21) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
SAFETY DEVICES9.
Protection form
Models
ARGA18FMTA
ARGA25FMTA
Circuit protection Current fuse (PC board) 250 V 3.15 A
Fan motor protection Thermal protection
OFF: 135 ± 15 °C
ON: 115 ± 15 °C
Page 25
- (01 - 22) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
EXTERNAL INPUT & OUTPUT10.
EXTERNAL INPUT10-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit. Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation InitialsettingafterpowerisON Starting mode other than initial setting
Operation mode Auto changeover Mode at previous operation Set temperature 24°C Temperature at previous operation
Airow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
z
Indoor unit
control PC board Connected unit
Ex.) Switch
Connector
1 3
Signal
Locally purchased
*: Make the distance from the PC board to the connected unit within 10 m. Contact capacity: DC 24 V or more, 10 mA or more. Please use non-polar relays and switches.
*10 m
When function setting is in "Operation/Stop" mode
Operation
Stop
ON
OFF
Input signal
Indoor unit
When function setting is in "Forced stop" mode
Remote controller
ON ON ON
Input signal
ON
OFF
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control operation invalidity
Parts (Optional)
z
Model name
UTD-ECS5A
Wire (External input)
Connector INPUT OUTPUT REMARKS
CN102 Control input
See external
input/output settings for
details.
CN103 Operation status output
CN6 Fresh air control output
Page 26
- (01 - 23) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
EXTERNAL OUTPUT10-2.
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
z
Locally purchased
Ex.)Display
Indoor
control PC board
Connected unit
Ex.)Relay unit
1
2
Signal
Relay power supply
V
Connector
*: Make the distance from the PC board to the connected unit within 10 m. Relay spec.: Max. DC 24 V, 10 mA to less than 500 mA.
*10 m
DC 24 V
ON
OFF
Operation
Stop
Indoor unit
Output signal
Parts (Optional)
z
Model name
UTD-ECS5A
Wire (External output)
Page 27
- (01 - 24) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
FRESH AIR CONTROL OUTPUT
A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation.
Circuit diagram example
z
Locally purchased
Indoor
control PC board
Connector
1
12 V
on/off
2
Signal
Relay power supply
*: Make the distance from the PC board to the connected unit within 10 m. Relay spec.: Rated DC 12 V, 50 mA or less.
Ex.) Fan
Connected unit
Ex.) Relay unit
*10 m
ON OFF
Operation
Stop
Indoor fan
Output signal
Parts (Optional)
z
Model name
UTD-ECS5A
Wire (Fresh air output)
Page 28
- (01 - 25) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
FUNCTION SETTINGS11.
INDOOR UNIT11-1.
SWITCH POSITION
DIP-SW SETTING
Unit number setting
z
A number of indoor units can be operated at the same time using a wired remote controller. Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board. (See the following table.) The DIP switches are normally set to make the unit number 00.
(
. . .Factory setting)
Unit number
DIPswitchNo.
1 2 3 4
00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON
INDOOR UNIT
DIP SW
1
Remote controller address setting
2 3 4
Jumper Wire
JM1
Setting change prohibitedJM2
JM3
JM3
JM2
JM1
Indoor unit Printed circuit board
MAIN PCB
Page 29
- (01 - 26) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
INDOOR UNIT (Setting by remote controller)11-2.
The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.
After the power is turned on, perform the Function Setting according to the installation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Number.
Settings will not be changed if disable numbers or setting values are selected.
PREPARATION
Turn on the power.
* Before turning on the power of the indoor units, make sure the piping air-tight test and vacuuming
have been conducted.
* Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wired remote controller)
Setting method
z
(1) Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously for more than 5 seconds to enter the function setting mode.
SU
MO
TU
WE
TH FR
SA
(2) Press the SET BACK button to select the indoor unit number.
SET BACK
SUMOTUWETH FR
SA
Unit number of INDO OR UNIT
(3) Press the Set time buttons to select the function number.
Function number
SUMOTUWETH FR
SA
(4) Press the SET TEMP. buttons ( ) ( ) to select the setting value. The indicator ashes during setting value selection.
Settin g value
SUMOTUWETH FR
SA
Page 30
- (01 - 27) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
(5) Press the TIMER SET button to conrm the setting. Press the TIMER SET button for a few seconds until the setting value stops
ashing. If the setting value indicator changes or if “- -” is displayed when the ashing stops, the setting value has not been set correctly. (A disable setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings. Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously again for
more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1
minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
!
CAUTION
• After turning off the power, wait 30 seconds or more before turning on it again. The Function Setting will not become active
unless the power is turned off then on again.
CONTENTS OF FUNCTION SETTING
• Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed
condition. After the power is turned on, perform the Function Setting on the remote control.
• The settings may be selected between the following t wo: Function Number or Setting Value.
• Settings will not be changed if inenable numbers or setting values are selected.
1) Filter sign
2) Static pressure
3) Room temperature sensor control for cooling
4) Auto restart
5) Room temperature sensor switching
6) External input control
7) Room temperature sensor switching (Aux.)
1) Filter sign
Select appropriate intervals for displaying the lter sign on the indoor unit according to the estimated amount of dust in the air of the
room.
If the indication is not required, select "No indication" (03).
(
. . .Factory setting)
Function Number Setting Value Setting Description
11
00 Standard (2500 hours) 01 Long inter val (4400 hours) 02 Short interval (1250 hours) 03 No indication
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
(
. . .Factory setting)
Function Number Setting Value Setting Description
21
00 Normal
01 High static pressure 1 02 High static pressure 2 03 High static pressure 3
Refer to "7. FAN PERFORMANCE AND CAPACITY".
3) Room temperature sensor control for cooling
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
(
. . .Factory setting)
Function Number Setting Value Setting Description
30
00 Standard
01 Lower control 02 Slightly higher control 03 Higher control
Page 31
- (01 - 28) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
4) Auto restart
Enable or disable automatic restart after a power interruption.
(
. . .Factory setting)
Function Number Setting Value Setting Description
40
00 Enable
01 Disable
* Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
5)Roomtemperaturesensorswitching
(Only for wired remote controller) When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
(
. . .Factory setting)
Function Number Setting Value Setting Description
42
00 Indoor unit
01 Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*Remote controller sensor must be turned on by using the remote controller.
6) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
. . .Factory setting)
Function Number Setting Value Setting Description
46
00 Operation/Stop mode
01 (Setting prohibited) 02 Forced stop mode
7)Roomtemperaturesensorswitching(Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01). This function
will only work if the function setting 42 is set at "Both" (01).
(
. . .Factory setting)
Function Number Setting Value Setting Description
48
00 Both
01 Wired remote controller
Page 32
- (01 - 29) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
WIRED REMOTE CONTROLLER11-3.
DIP
Switch 1
SW1
Setting change prohibited
SW2
Setting change prohibited
SW3
Setting change prohibited
SW4
Setting change prohibited
SW5
Setting change prohibited
SW6
Memory backup setting
* Do not use DIP Switch 2
SWITCH POSITION
Wired remote controller
z
1 2 3 4 5 6
Front case (back side)
DIP Switch 2 (All switches
xed at OFF)
DIP Switch 1
ON
ONOFF
Page 33
- (01 - 30) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
DIP SWITCH 1 SETTING
SW6 setting
z
Memory backup setting
Set to ON to use batteries for the memory backup.
If batteries are not used, all of settings stored in memory will be deleted if there is a power
failure.
(u...Factory setting)
SW6 Memory backup
u
OFF Disable
ON Enable
Page 34
- (01 - 31) -
DUCT TYPE
ARGA18-25FMTA
DUCT TYPE
ARGA18-25FMTA
OPTIONAL PARTS12.
Exterior Parts name Model No. Summary
Square ange UTD-SF045T
Both the
Squareange
and
the
Roundange
can be selected.
Roundange
is also used when the fresh air duct is installed.
Round ange UTD-RF204
507mm
Long-life lter UTD-LF25NA
Long-lifelter
can be
mounted to the indoor unit.
Remote sensor UTY-XSZX
New amenity space can be offered
by installing the
Remote sensor in the remote controller.
External
control set
UTD-ECS5A
Use to connect with various peripheral devices and air conditioner PC board.
Page 35
DTR_AO202E_01
2015.01.19
SINGLE TYPE:
AOGA18FBTAH
AOGA25FBTAH
2. OUTDOOR UNIT
Page 36
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
CONTENTS
2. OUTDOOR UNIT
1. SPECIFICATIONS
.............................................................................................. 02 - 01
2. DIMENSIONS
........................................................................................................02 - 02
3. REFRIGERANT CIRCUIT
............................................................................ 02 - 04
4. WIRING DIAGRAMS
........................................................................................ 02 - 06
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
..................................................................... 02 - 08
6. ADDITIONAL CHARGE CALCULATION
......................................... 02 - 10
7. AIRFLOW
..................................................................................................................02 - 11
8. OPERATION NOISE (SOUND PRESSURE)
................................. 02 - 12
8-1. NOISE LEVEL CURVE
....................................................................................02 - 12
8-2. SOUND LEVEL CHECK POINT
..................................................................... 02 - 13
9. ELECTRIC CHARACTERISTICS
........................................................... 02 - 14
10. SAFETY DEVICES
............................................................................................ 02 - 15
Page 37
- (02 - 01) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
SPECIFICATIONS1.
NOTES:
Specicatio ns are based on the foll owing conditions. Coolin g: Indoor te mperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/ 24 °CWB. Pipe leng th: 7.5 m, Height dif ferenc e: 0 m.(Outdoor unit - Indoor unit) The prote ctive fun ction may work when using it outside the op eration r ange. *: These are t he measured values in t he manufacturer ’s anechoic chamber.
Becaus e of the surr ounding s ound envir onment, t he sound levels measur ed in actua l installation condition s might be higher than the specied values here.
Type COOLING ONLY
Model name AOGA18FBTAH AOGA25FBTAH
Power source 220 / 240 V ~ 50 Hz
Available voltage range 198 to 264 V
Starting current A 42 55
Fan
Airow rate m
3
/h 3,200 3,300
Type × Q'ty Propeller × 1
Motor output W 75 59
Sound pressure level * Cooling dB(A) 54 54
Heat exchanger type
Dimensions (H × W × D)
mm
630 x 901 x 36.4 798 × 900 × 36.4
Fin pitch 1.45 1.30
Rows x Stages 2 × 30 2 × 38
Pipe type Copper
Fin type (Surface treatment) Aluminium (Blue n)
Compressor
Type × Q'ty Rotary × 1
Motor output W 1,330 1,670
Refrigerant
Type R410A
Charge g 1,500 1,800
Refrigerant oil Type RB75EA (POE)
Enclosure
Material Steel sheet
Colour
BEIGE
Approximate colour of MUNSELL 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
650 × 830 × 320 830 × 900 × 330
Gross 743 × 984 × 413 970 × 1050 × 445
Weight
Net
kg
50 63
Gross 54 70
Connection
pipe
Size
Liquid
mm
Ø 6.35 (Ø 1/4 in.)
Gas Ø 15.88 (Ø 5/8 in.)
Method Flare
Pre-charge length
m
7.5
Max. length 20 25 Max. height difference 8 15
Operation range Cooling ˚C 21 to 52
Page 38
- (02 - 02) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
DIMENSIONS2.
MODEL : AOGA18FBTAH
(Unit : mm)
INSTALLATION PLACE
(Unit : mm)
350
830
650
12
101
154
343
320
58
603
Air flow
Bottom
90
Top view
Front view
Side view
Bottom view
* If the space is larger than stated, the condition will be the same as those without any obstacles.
Height above the oor level should be 50 mm or more.
When there are obstacles at the back and front sides.
When there are obstacles at the back, side(s), and top.
When there are obstacles at the back side with the installation of more than one unit.
600
or more
300
or more
300 or more
300 or more
*600-1000
300 or more
300 or more
300 or more
300
or more
(Service space)
Page 39
- (02 - 03) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
MODEL : AOGA25FBTAH
(Unit : mm)
INSTALLATION PLACE
(Unit : mm)
When there are obstacles at the back, side(s), and top.
When there are obstacles at the back side with the installation of more than one unit.
When there are obstacles at the back and front sides.
600
or more
250
or more
250
or more
300
or more
*600 - 1000
100
or more
300
or more
*100 - 300
250 or more
(Service space)
* If the space is larger than stated, the condition will be the same as those without any obstacles.
Height above the oor level should be 50 mm or more.
Air flow
900
650
830
370
99
196
21
9
77
31 330
400
170
147
12
Top view
Front view
Side view
Bottom view
Page 40
- (02 - 04) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
REFRIGERANT CIRCUIT3.
MODEL : AOGA18FBTAH
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 5/8" (15.88 mm)
Page 41
- (02 - 05) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
MODEL : AOGA25FBTAH
Sub-accumulator
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 5/8" (15.88 mm)
Page 42
- (02 - 06) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
WIRING DIAGRAMS4.
MODEL : AOSA18FBTAH
Page 43
- (02 - 07) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
MODEL : AOGA25FBTAH
Page 44
- (02 - 08) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL : AOGA18FBTAH
Outdoor unit
Indoor unit
Connec tion pip e
2 Indoor unit is lower than outdoor unit.
H
Indoor unit
Outdoor unit
Connec tion pip e
1 Indoor unit is higher than outdoor unit.
H
Height difference H
COOLING
Pipe length (m)
5 7.5 10 15 20
Height
difference H
(m)
1
Indoor unit is higher
than outdoor unit
8 - - 0.983 0.979 0.977 5 0.997 0.992 0.988 0.984 0.982 0 1.005 1.000 0.996 0.992 0.990
2
Indoor unit is lower
than outdoor unit
-5 1.005 1.000 0.996 0.992 0.990
-8 - - 0.996 0.992 0.990
Page 45
- (02 - 09) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
This table is created using the maximum capacity.
MODEL : AOGA25FBTAH
Outdoor unit
Indoor unit
Connec tion pip e
2 Indoor unit is lower than outdoor unit.
H
Indoor unit
Outdoor unit
Connec tion pip e
1 Indoor unit is higher than outdoor unit.
H
Height difference H
COOLING
Pipe length (m)
5 7.5 10 15 20 25
Height
difference H
(m)
1
Indoor unit is higher
than outdoor unit
15 - - - 0.972 0.970 0.968 10 - - 0.979 0.975 0.973 0.971
7.5 - 0.987 0.983 0.979 0.977 0.975 5 0.997 0.992 0.988 0.984 0.982 0.980 0 1.005 1.000 0.996 0.992 0.990 0.988
2
Indoor unit is lower
than outdoor unit
-5 1.005 1.000 0.996 0.992 0.990 0.988
-7.5 - 1.000 0.996 0.992 0.990 0.988
-10 - - 0.996 0.992 0.990 0.988
-15 - - - 0.992 0.990 0.988
Page 46
- (02 - 10) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
ADDITIONAL CHARGE CALCULATION6.
MODEL : AOGA18FBTAH
Refrigerant Charge
z
MODEL : AOGA25FBTAH
Refrigerant Charge
z
Refrigerant type R410A
Refrigerant amount g 1,500
Total pipe length m 7.5 or less 15 20(Max.)
20 g/m
Additional charge g 0 150 250
Refrigerant type R410A
Refrigerant amount g 1,800
Total pipe length m 7.5 or less 10 15 20 25 (Max.)
20g/m
Additional charge g 0 50 150 250 350
Page 47
- (02 - 11) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
AIRFLOW7.
MODEL : AOGA18FBTAH
MODEL
: AOGA25FBTAH
Airow
m
3
/h 3,200
l/s 889
CFM 1,884
Airow
m
3
/h 3,300
l/s 917
CFM 1,942
Page 48
- (02 - 12) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
OPERATION NOISE (SOUND PRESSURE)8.
NOISE LEVEL CURVE8-1.
MODEL : AOGA18FBTAH
Cooling
z
Octave ba nd sound p ressure l evel, dB:(0d B=0.0 002µb ar)
Octave ba nd cente r frequen cy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2, 000 4, 000 8, 000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
MODEL : AOGA25FBTAH
Cooling
z
Octave ba nd sound p ressure l evel, dB:(0d B=0.0 002µb ar)
Octave ba nd cente r frequen cy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,0 00 2, 000 4, 000 8, 000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 49
- (02 - 13) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
SOUND LEVEL CHECK POINT8-2.
Page 50
- (02 - 14) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
ELECTRIC CHARACTERISTICS9.
NOTES :
*1: The maximum current is the total current of indoor unit and outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
*3: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
Model name AOGA18FBTAH AOGA25FBTAH
Power supply
Voltage V 220 /240 ~
Frequency Hz 50
Max. operating current
*1
A 13.5 16.7
Starting current A 42 55
Wiring spec.
*2
Circuit breaker current A 20 30
Power cable mm
2
2.5 - 3.0 2.5 - 3.5
Connection cable
*3
mm
2
1.5 - 2.5
Limited wiring length m 21 26
Page 51
- (02 - 15) -
OUTDOOR UNIT
AOGA18-25FBTAH
OUTDOOR UNIT
AOGA18-25FBTAH
SAFETY DEVICES10.
Protection form
Models
AOGA18FBTAH AOGA25FBTAH
Fan motor protection Thermal protection
OFF: 150 ± 5 °C
ON: 96 ± 15 °C
High pressure protection Pressure switch
OFF: 4.9 ± 0.1 MPa ON: 3.8 ± 0.15 MPa
Compressor protection Over Load Protector
OFF: 160 - 165 °C
ON: 90 ± 10 °C
Page 52
DESIGN & TECHNICAL MANUAL
AIR CONDITIONER
Duct type
INDOOR
ARGA30FMTA ARGA36FMTA
ARGA45FMTA
ARGA60FHTA
OUTDOOR
AOGA30FBTAS
AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS
DR_AR003EG_04
2015.10.02
Page 53
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2015 Fujitsu General Limited. All rights reserved.
Page 54
CONTENTS
Part 1. INDOOR UNIT........................................................................1
1. Product features ......................................................................................2
1-1. Model lineup ..............................................................................................................2
1-2. Features .....................................................................................................................2
2. Wired remote controller .........................................................................4
2-1. Features .....................................................................................................................4
2-2. Overview ....................................................................................................................6
2-3. Specifications .............................................................................................................7
2-4. Wring specifications ...................................................................................................7
3. Specifications ..........................................................................................8
4. Dimensions ............................................................................................10
4-1. Model: ARGA30FMTA ............................................................................................. 10
4-2. Models: ARGA36FMTA and ARGA45FMTA ...........................................................11
4-3. Model: ARGA60FHTA .............................................................................................12
4-4. Installation space requirement .................................................................................13
4-5. Maintenance space requirement .............................................................................14
5. Wiring diagrams .....................................................................................17
5-1. Model: ARGA30FMTA ............................................................................................. 17
5-2. Models: ARGA36FMTA and ARGA45FMTA ...........................................................18
5-3. Model: ARGA60FHTA .............................................................................................19
6. Capacity table ........................................................................................20
6-1. Cooling capacity ......................................................................................................20
7. Fan performance ....................................................................................22
7-1. Fan performance curve ............................................................................................22
8. Operation noise (sound pressure) .......................................................30
8-1. Noise level curve .....................................................................................................30
8-2. Sound level check point ...........................................................................................32
9. Safety devices ........................................................................................33
10. External input and output .....................................................................34
10-1.Control input (Operation/Stop or Forced stop) ........................................................34
10-2.External output ........................................................................................................36
11. Function settings ...................................................................................39
11-1.Function settings on indoor unit ..............................................................................39
11-2.Function settings by using remote controller ..........................................................43
11-3.Function settings on wired remote controller ..........................................................48
12. Optional parts ........................................................................................49
12-1.Others .....................................................................................................................49
Page 55
CONTENTS
Part 2. OUTDOOR UNIT..................................................................50
1. Specifications ........................................................................................ 51
2. Dimensions ............................................................................................ 53
2-1. Model: AOGA30FBTAS .......................................................................................... 53
2-2. Models: AOGA36FRTAS, AOGA45FRTAS, and AOGA60FRTAS ......................... 54
2-3. Installation space requirement ................................................................................ 55
3. Refrigerant circuit ................................................................................. 61
3-1. Model: AOGA30FBTAS .......................................................................................... 61
3-2. Models: AOGA36FRTAS, AOGA45FRTAS, and AOGA60FRTAS ......................... 62
4. Wiring diagrams .................................................................................... 63
4-1. Model: AOGA30FBTAS .......................................................................................... 63
4-2. Models: AOGA36FRTAS, AOGA45FRTAS, and AOGA60FRTAS ......................... 64
5. Capacity compensation rate for pipe length and height difference . 65
5-1. Model: AOGA30FBTAS .......................................................................................... 65
5-2. Models: AOGA36FRTAS, AOGA45FRTAS, and AOGA60FRTAS ......................... 66
6. Additional charge calculation ..............................................................67
6-1. Model: AOGA30FBTAS .......................................................................................... 67
6-2. Models: AOGA36FRTAS and AOGA45FRTAS ...................................................... 67
6-3. Model: AOGA60FRTAS .......................................................................................... 67
7. Airflow .................................................................................................... 68
7-1. Model: AOGA30FBTAS .......................................................................................... 68
7-2. Models: AOGA36FRTAS, AOGA45FRTAS, and AOGA60FRTAS ......................... 68
8. Operation noise (sound pressure) .......................................................69
8-1. Noise level curve ..................................................................................................... 69
8-2. Sound level check point .......................................................................................... 71
9. Electrical characteristics ...................................................................... 72
10. Safety devices ....................................................................................... 73
Page 56
Part 1. INDOOR UNIT
DUCT TYPE: ARGA30FMTA ARGA36FMTA ARGA45FMTA
ARGA60FHTA
Page 57
- 2 -
DUCT TYPE
ARGA30-60F
1. Product features
Implemented core technology provides easy-to-use product operations that realize a comfortable space.
1-1. Model lineup
1-2. Features
High efficiency technology
ARGA30FMTA AOGA30FBTAS
ARGA36FMTA ARGA45FMTA
ARGA60FHTA AOGA36FRTAS
AOGA45FRTAS AOGA60FRTAS
DC fan motor
V-Shape Heat-exchanger
High efficient
Large diameter
sirocco fan
Optimized
casing design
Optimization of airflow
speed distribution
Page 58
- 3 -
DUCT TYPE
ARGA30-60F
Powerful air flow
Low noise
Top class operating sound level in cooling operation is provided among the major competitors.
High install ability long piping correspondence (AR36,45,60)
Separated indoor unit (AR60 only)
The indoor unit can be moved into the ceiling space through the designated opening.
Top class
(BTU)
2,000
2,500
36,000
1,600
30,000
45,000
3,350
(Hi:㎥/h)
60,000
35
dB*(A)
(cooling operation)
* At rated point (30 model)
50 m
20 m
Ceiling
Inspection hole
Integration in the ceiling
Separation
Page 59
- 4 -
DUCT TYPE
ARGA30-60F
2. Wired remote controller
2-1. Features
High performance and compact size
Simple function setting
Setting for selecting function of the air conditioner is performed by remote controller.
Accurate and comfortable
Indoor temperature can be detected accurately by the inclusion of a thermo sensor in the body of the wired controller.
Our system can correspond to various scenes. This wired remote controller and the optional remote sensor allows flexibility in sensor location,
and suitable for all requirements.
• Various timer setup available (on, off, and weekly).
• Equipped with weekly timer as standard function. (Start/ stop function is twice per day for a week.)
• When setting up the timer, operation mode and tempera­ture setup can be changed.
• When a failure occurs, the error code is displayed.
• Error history. (Last 16 error codes can be accessed.)
• The room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor.
Sensor part
Thermo sensor indicator
Control part for changing the thermo sensor
Page 60
- 5 -
DUCT TYPE
ARGA30-60F
Built-in timers
Easy-to-understand operation
[Variable timer control]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
Simple installation
Components are compatible with standard switch boxes. Flat-back surface allows equipment to be installed wherever it is needed.
System diagram
Weekly timer Setback timer
Possible to set on/off time to operate twic e each day of the week.
Possible to set temperature for two time spans and for each day of the week.
At “Weekly timer” + “Set back timer” setup
1 remote controller
A: Remote controller cable A500 m
SUMOTUWETH FR SA
7
31269
15 18 21
SUMOTUWETH FR SA
7
31269
15 18 21
Easy-to-understand time bar display
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
Screen after setup
24°C
036912151821Time
SUMOTUWETH FR SA
31269
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 䉝.)
28°C
036912151821Time
28 °C
24 °C
036912151821Time
24 °C 28 °C 24 °C
Timer area
Operation area
European switch box
JIS box
A
Indoor unit
Remote controller
Page 61
- 6 -
DUCT TYPE
ARGA30-60F
2-2. Overview
Display panel
a START/STOP button
Starts and stops operation.
b SET TEMP. button
Selects the setting temperature.
c MODE button
Selects the operating mode (AUTO , , FAN , COOL , and DRY ).
d FAN button
Selects the fan speed AUTO ,QUIET , LOW , MED , and HIGH ).
e ECONOMY (THERMO SENSOR) button
Turns the economy-efficient mode on and off.
f TIMER MODE (CLOCK ADJUST) button
Selects the timer mode (off timer, on timer, and weekly timer). Sets the current time.
g DAY (DAY OFF) button
Temporarily cancels one day timer.
h SET BACK button
Selects the set back timer.
i Set time button
Pressed to set time.
j TIMER DELETE button
Deletes the weekly timer schedule.
k TIMER SET button
Sets the date, hour, minute, and on-off time.
l Vertical airflow direction and swing button
Push for 2 seconds to change the swing mode.
m Horizontal airflow direction and swing
button
Push for 2 seconds to change the swing mode.
n FILTER RESET button o Operation lamp
Lights during operation and when the timer is on.
p Timer and clock indicator q Operation mode indicator r Fan speed indicator s Operation lock indicator t Temperature indicator u Function indicators
Defrost indicator Thermo sensor indicator Economy indicator Vertical swing indicator Horizontal swing indicator Filter indicator
NOTE: Functions may differ by type of the indoor unit.
For details, refer to the operation manua l.
b f g h i
j k
a c d
e
l
m
n
o
pqrst
u
Page 62
- 7 -
DUCT TYPE
ARGA30-60F
2-3. Specifications
Dimensions and other specifications on the wired remote controller are as follows.
2-4. Wring specifications
Unit: mm
Size (H × W × D) mm 120 × 120 × 18 Weight g 160 Cable length (accessory) m 10 Power V 12
Use Cable size Wire type Remarks
Remote controller cable
0.33 mm
2
(22 AWG)
Polar 3-core Use sheathed PVC cable.
120
120
120
18
Side ViewFront View
Page 63
- 8 -
DUCT TYPE
ARGA30-60F
3. Specifications
Type
Duct
Cooling only
Model name ARGA30FMTA
Power supply 220—240 V ~ 50 Hz Available voltage range 198—264 V Cooling (T1 condition)
Capacity
kW 8.3—8.3
Btu/h 28400—28400 Input power kW 2.40—2.46 Current A 11.3—1 1.1 EER Btu/hW 11.83—11.54 Sensible capacity kW 6.68—6.68 Power factor % 96.5—92.3 Moisture removal L/h (pints/h) 2.3—2.3 (4.0—4.0)
Maximum operating current *1 Cooling A 23.0
Fan
Airflow rate Cooling
HIGH
m3/h
1600 MED 1500 LOW 1400 QUIET 1250
Type × Q'ty Sirocco fan × 2 Motor output W 197
Recommended static pressure Pa 30 to 120
Sound pressure level *2 Cooling
HIGH
dB(A)
35 MED 34 LOW 32 QUIET 29
Heat exchanger type
Dimensions (H × W × D)
mm
420 × 758 × 39.9 Fin pitch 1.4 Rows × Stages 3 × 20 Pipe type Copper Fin type Aluminum
Enclosure
Material Steel Color
Dimensions (H × W × D)
Net
mm
300 × 1000 × 700
Gross 400 × 1238 × 875
Weight
Net
kg
35
Gross 43
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Operation range Cooling
°C 18 to 32
%RH 80 or less
Remote controller type Wired Drain hose
Material PVC Size mm Ø 25 (I.D.), Ø 32 (O.D.)
NOTES:
Specifications are based on the following conditions:
– Cooling (T1): Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Standard static pressure: 47 Pa – Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.*1: Maximum current is the maximum value when operated within the operation range.*2: Sound pressure level: Measured after a 2-m duct to the outlet port and a 1-m duct to the suction port are installed.
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 64
- 9 -
DUCT TYPE
ARGA30-60F
Type
Duct
Cooling only
Model name ARGA36FMTA ARGA45FMTA ARGA60FHTA
Power supply 3N 380—415 V ~ 50 Hz Available voltage range 342—457 V Cooling (T1 condition)
Capacity
kW 10.3—10.3 13.5—13.5 15.2 —15.2
Btu/h 35000—35000 46000—46000 52000—52000 Input power kW 3.01—3.01 4.00—4.00 4.47—4.47 Current A 5.2—5.0 6.9—6.5 7.8—7.5 EER Btu/hW 11.63—11.63 11.50—11.50 11.63—11.63 Sensible capacity kW 8.54—8.54 10.8—10.8 12.92—12.92 Power factor % 87.9—83.8 88.1—85.6 87.1—82.9 Moisture removal L/h (pints/h) 3.0—3.0 (5.3—5.3) 3.3 —3.3 (5.8—5.8) 3.4—3.4 (6.0—6.0)
Maximum operating current *1 Cooling A 10.5 14.0 15.5
Fan
Airflow rate Cooling
HIGH
m3/h
2000 2500 3350 MED 1850 2350 3150 LOW 1650 2200 2950 QUIET 1500 2000 2650
Type × Q'ty Sirocco fan × 3 Sirocco fan × 2 Motor output W 197 375
Recommended static pressure Pa 30 to 120 60 to 160
Sound pressure level *2 Cooling
HIGH
dB(A)
37 40 41 MED 35 38 40 LOW 34 37 39 QUIET 32 35 38
Heat exchanger type
Dimensions (H × W × D)
mm
420 × 1158 × 39.9 546 × 1158 × 39.9 Fin pitch 1.4 1.3 Rows × Stages 3 × 20 3 × 26 Pipe type Copper Fin type Aluminum
Enclosure
Material Steel Color
Dimensions (H × W × D)
Net
mm
300 × 1400 × 700 360 × 1400 × 850
Gross 400 × 1638 × 875 460 × 1640 × 1030
Weight
Net
kg
44 67
Gross 53 77
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 19.05 (Ø 3/4)
Method Flare
Operation range Cooling
°C 18 to 32
%RH 80 or less
Remote controller type Wired Drain hose
Material PVC Size mm Ø 25 (I.D.), Ø 32 (O.D.)
NOTES:
Specifications are based on the following conditions:
– Cooling (T1): Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 ° CWB. – Standard static pressure: 60 Pa – Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.*1: Maximum current is the maximum value when operated within the operation range.*2: Sound pressure level: Measured after a 2-m duct to the outlet port and a 1-m duct to the suction port are installed.
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 65
- 10 -
DUCT TYPE
ARGA30-60F
4. Dimensions
4-1. Model: ARGA30FMTA
Unit: mm
Air
Gas pipe
Drain port
Control box
Liquid pipe
Side view (L)
Side view (R)
Top view
Front view
Rear view
Page 66
- 11 -
DUCT TYPE
ARGA30-60F
4-2. Models: ARGA36FMTA and ARGA45FMTA
Unit: mm
Gas pipe
Drain port
Control box
Liquid pipe
Air
Side view (L)
Side view (R)
Top view
Front view
Rear view
Page 67
- 12 -
DUCT TYPE
ARGA30-60F
4-3. Model: ARGA60FHTA
Unit: mm
Gas pipe
Drain port
Control box
Liquid pipe
Air
Side view (R)Top viewSide view (L)
Front view
Rear view
Page 68
- 13 -
DUCT TYPE
ARGA30-60F
4-4. Installation space requirement
Provide sufficient installation space for product safety.
Models: ARGA30FMTA, ARGA36FMTA, and ARGA45FMTA
Model: ARGA60FHTA
Installation by which service space is made on top of the unit (recommended):
Installation by which service is carried out from the bottom of the unit:
Floor
300 or more
150 or
more
20 or more
2500 or more
(When no ceiling)
20 or more
Unit: mm
Unit: mm
450 or more
500 or more
150 or
more
20 or more
2500 or more
(When no ceiling)
Unit: mm
500 or more
150 or
more
20 or more
20 or more
2500 or more
(When no ceiling)
Page 69
- 14 -
DUCT TYPE
ARGA30-60F
4-5. Maintenance space requirement
For future maintenance and service access, provide sufficient maintenance space. NOTE: Do not place any wiring or illumination in the maintenance space, as they will impede
service.
Model: ARGA30FMTA
• Provide a service access for maintenance purposes.
• The service access necessary for fan units and filter maintenance.
Bottom view
AIR
Unit: mm
Control box
300 or more
500 or more
500 or more
Service access
AIR
Service access
Fan unit side
300 or more
500 or more
1400 or more
100
Bottom view
Unit: mm
Page 70
- 15 -
DUCT TYPE
ARGA30-60F
Models: ARGA36FMTA and ARGA45FMTA
• Provide a service access for maintenance purposes.
• The service access necessary for fan units and filter maintenance.
300 or more
500 or more
Service access
500 or more
Control box
AIR
Bottom view
Unit: mm
AIR
300 or more
Service access
1800 or more
100
500 or more
Fan unit side
Bottom view
Unit: mm
Page 71
- 16 -
DUCT TYPE
ARGA30-60F
Model: ARGA60FHTA
AIR
Service access
700 or more
700 or more
500 or more
Control box
Bottom view
Unit: mm
Bottom view
Service access
2000 or more
100
500 or more
500 or more
AIR
Unit: mm
Page 72
- 17 -
DUCT TYPE
ARGA30-60F
5. Wiring diagrams
5-1. Model: ARGA30FMTA
Page 73
- 18 -
DUCT TYPE
ARGA30-60F
5-2. Models: ARGA36FMTA and ARGA45FMTA
Page 74
- 19 -
DUCT TYPE
ARGA30-60F
5-3. Model: ARGA60FHTA
Page 75
- 20 -
DUCT TYPE
ARGA30-60F
6. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) 1 kW = 3412 Btu/h
6-1. Cooling capacity
Model: ARGA30FMTA
Model: ARGA36FMTA
Model: ARGA45FMTA
AFR
m3/h
1600
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 21 6.92 5.87 1.84 7.85 6.41 1.84 8.13 6.54 1.84 8.66 6.75 1.85 8.89 6.83 1.87 9.34 6.91 1.86 9.73 6.92 1.87 25 6.85 5.86 2.00 7.77 6.39 2.00 8.05 6.52 2.00 8.57 6.73 2.01 8.80 6.81 2.03 9.25 6.89 2.02 9.64 6.90 2.03 30 6.70 5.80 2.18 7.60 6.32 2.18 7.87 6.46 2.19 8.38 6.66 2.19 8.61 6.74 2.22 9.05 6.82 2.21 9.42 6.82 2.22 35 6.46 5.75 2.39 7.33 6.27 2.39 7.59 6.40 2.40 8.08 6.61 2.40 8.30 6.68 2.43 8.72 6.76 2.42 9.09 6.77 2.43 40 6.07 5.59 2.54 6.88 6.10 2.54 7.13 6.23 2.55 7.59 6.43 2.55 7.80 6.50 2.58 8.20 6.58 2.57 8.54 6.59 2.58 46 5.56 5.35 2.85 6.31 5.83 2.86 6.54 5.96 2.86 6.96 6.15 2.87 7.15 6.22 2.90 7.51 6.29 2.89 7.83 6.30 2.90 50 5.16 5.15 3.08 5.85 5.62 3.09 6.06 5.74 3.09 6.45 5.92 3.10 6.63 5.99 3.14 6.96 6.06 3.12 7.25 6.06 3.14 52 4.93 5.04 3.21 5.60 5.50 3.21 5.80 5.61 3.21 6.17 5.79 3.22 6.34 5.86 3.26 6.66 5.93 3.24 6.94 5.93 3.26
AFR
m3/h
2000
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 21 10.31 8.47 2.60 10.54 8.50 2.64 10.79 8.55 2.67 11.21 9.05 2.72 11.38 9.03 2.75 11.71 8.95 2.80 12.02 9.35 2.84 25 10.72 8.72 2.43 10.99 8.76 2.46 11.23 8.81 2.48 11.65 9.30 2.52 11.83 9.26 2.53 12.15 9.17 2.57 12.44 9.55 2.59 30 10.03 8.31 2.66 10.32 8.37 2.69 10.56 8.47 2.72 10.96 8.96 2.76 11.13 8.94 2.77 11.45 8.85 2.81 11.76 9.26 2.84 35 9.34 7.97 2.91 9.52 8.03 2.92 9.76 8.08 2.95 10.12 8.57 2.99 10.30 8.54 3.01 10.63 8.49 3.05 10.95 8.93 3.09 40 8.36 6.02 3.08 8.73 6.73 3.16 9.00 7.36 3.22 9.53 8.03 3.29 9.76 8.23 3.30 10.19 8.58 3.34 10.96 8.71 3.37 46 7.96 6.02 3.47 8.35 6.77 3.57 8.63 7.27 3.64 9.17 7.92 3.69 9.20 8.17 3.73 9.82 8.50 3.78 10.56 8.93 3.80 50 6.87 5.93 3.68 7.45 6.47 3.80 7.68 6.83 3.89 8.21 7.42 3.98 8.13 7.63 3.97 8.77 8.04 4.04 9.49 8.71 4.04 52 6.41 5.89 3.78 7.07 6.35 3.90 7.28 6.63 3.99 7.80 7.18 4.09 7.64 7.39 4.09 8.33 7.81 4.16 9.02 8.62 4.15
AFR
m3/h
2500
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 21 13.51 10.69 3.45 13.81 10.74 3.51 14.14 10.80 3.55 14.69 11.45 3.62 14.92 11.41 3.65 15.35 11.31 3.72 15.74 11.81 3.77 25 14.05 11.02 3.24 14.39 11.07 3.27 14.72 11.14 3.30 15.28 11.75 3.35 15.51 11.70 3.36 15.93 11.58 3.41 16.31 12.07 3.45 30 13.16 10.52 3.55 13.53 10.58 3.58 13.84 10.70 3.60 14.36 11.32 3.65 14.60 11.29 3.68 15.01 11.19 3.73 15.42 11.70 3.78 35 12.24 10.07 3.86 12.47 10.15 3.88 12.79 10.21 3.91 13.28 10.82 3.97 13.50 10.80 4.00 13.94 10.73 4.05 14.35 11.28 4.11 40 10.96 7.61 4.10 11.44 8.51 4.20 11.80 9.31 4.28 12.49 10.15 4.36 12.79 10.41 4.38 13.32 10.86 4.45 14.37 11.02 4.48 46 10.31 7.51 4.56 10.80 8.46 4.69 11.17 9.09 4.77 11.86 9.90 4.88 11.90 10.20 4.89 12.70 10.61 4.96 13.67 11.16 4.99 50 8.89 7.41 4.83 9.63 8.08 4.98 9.94 8.53 5.10 10.62 9.26 5.22 10.52 9.53 5.21 11.36 10.03 5.30 12.27 10.86 5.30 52 8.28 7.35 4.96 9.15 7.93 5.12 9.42 8.28 5.25 10.10 8.97 5.37 9.89 9.22 5.36 10.78 9.75 5.45 11.66 10.75 5.44
Page 76
- 21 -
DUCT TYPE
ARGA30-60F
Model: ARGA60FHTA
AFR
m3/h
3350
Indoor temperature °CDB 18 21 23 25 27 29 32 °CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW kW 21 12.46 10.11 4.05 13.37 10.21 4.12 13.82 10.27 4.17 14.90 12.00 4.25 15.35 12.36 4.28 15.98 13.37 4.36 16.89 14.30 4.43 25 15.18 9.71 3.64 15.52 11.35 3.70 15.86 12.22 3.73 16.60 13.20 3.79 16.93 13.43 3.82 17.58 13.78 3.85 18.86 13.98 3.94 30 14.52 9.41 3.94 14.90 10.98 4.01 15.28 11.96 4.05 16.02 12.99 4.12 16.31 13.25 4.16 16.98 13.65 4.19 18.16 13.75 4.28 35 13.90 8.81 4.22 13.90 10.66 4.31 14.38 11.44 4.35 15.13 12.46 4.43 15.20 12.92 4.47 16.25 13.06 4.50 17.35 13.54 4.60 40 12.35 9.11 4.58 12.89 10.17 4.69 13.28 11.14 4.78 14.07 12.15 4.88 14.41 12.44 4.89 15.01 12.99 4.96 16.17 13.18 5.00 46 11.51 8.93 5.06 12.07 10.04 5.20 12.47 10.78 5.30 13.26 11.74 5.41 13.30 12.11 5.42 14.20 12.60 5.50 15.27 13.23 5.54 50 9.93 8.80 5.36 10.77 9.59 5.52 11.11 10.13 5.66 11.87 10.99 5.78 11.75 11.31 5.78 12.69 11.91 5.88 13.72 12.90 5.88 52 9.27 8.73 5.50 10.22 9.40 5.68 10.53 9.83 5.82 11.28 10.65 5.95 11.06 10.94 5.94 12.04 11.59 6.04 13.05 12.77 6.04
Page 77
- 22 -
DUCT TYPE
ARGA30-60F
7. Fan performance
7-1. Fan performance curve
Model: ARGA30FMTA
Factory setting is Mode 1.
Fan
speed
Item
Static pressure mode
Mode 1 Mode 2 Mode 3 Mode 4 Normal
High static pressure 1
High static
pressure 2
High static pressure 3
HIGH
Static
pressure
Pa 30 55 60 75 90 100 110 120
Airflow
m
3
/h
1820 1520 1600 1400 1530 1350 1400 1250
l/s 506 422 444 389 425 375 389 347
CFM 1071 894 941 824 900 794 824 735
MED
Static
pressure
Pa 23 45 50 63 73 82 90 100
Airflow
m
3
/h
1680 1400 1490 1310 1380 1240 1280 1150
l/s 467 389 414 364 383 344 356 319
CFM 988 824 876 771 812 729 753 676
LOW
Static
pressure
Pa 16 38 42 53 59 67 72 81
Airflow
m
3
/h
1540 1280 1360 1210 1270 1130 1170 1050
l/s 428 356 378 336 353 314 325 292
CFM 906 753 800 712 747 665 688 618
QUIET
Static
pressure
Pa 10 29 34 42 44 52 56 64
Airflow
m
3
/h
1370 1120 1210 1100 1110 980 1020 920
l/s 381 311 336 306 308 272 283 256
CFM 806 659 712 647 653 576 600 541
1800900
0
140 130 120 110 100
90 80 70 60 50 40 30 20 10
1000 1100 1200 1300 1400 1500 1600 1700 1900
Airflow [m3/h]
External Static Pressure [Pa]
Med
Med
Med
Low
Low
Low
Low
Quiet
Quiet
Quiet
Quiet
Med
Fan performance curve_1
Hi [High static pressure 3 (120Pa)]
Hi [High static pressure 2 (90Pa)]
Hi [Normal (30Pa)]
Hi [High static pressure 1 (60Pa)]
Page 78
- 23 -
DUCT TYPE
ARGA30-60F
NOTES:
• Setting of the external static pressure is switchable into 4-stage modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal mode".
Characteristics of air volume and capacity
Cooling
Fan performance curve_2
(For function setting by remote controller)
1800900
0
140 130 120 110 100
90 80 70 60 50 40 30 20 10
1000 1100 1200 1300 1400 1500 1600 1700 1900
Airflow [m3/h]
External Static Pressure [Pa]
Hi [High static pressure 3 (120Pa)]
Hi [High static pressure 2 (90Pa)]
Hi [Normal (30Pa)]
Hi [High static pressure 1 (60Pa)]
100
105
90
95
900 1300 1400 15001000 1100 1200 1600 1700 1800 1900
Airflow [m3/h]
Capacity [%]
Page 79
- 24 -
DUCT TYPE
ARGA30-60F
Model: ARGA36FMTA
Factory setting is Mode 2.
Fan
speed
Item
Static pressure mode
Mode 1 Mode 2 Mode 3 Mode 4
Low static
pressure
Normal
High static
pressure 1
High static pressure 2
HIGH
Static
pressure
Pa 30 45 60 75 90 105 115 120
Airflow
m
3
/h
2000 1780 2000 1790 2000 1680 1760 1700
l/s 556 494 556 497 556 467 489 472
CFM 1176 1047 1176 1053 1176 988 1035 1000
MED
Static
pressure
Pa 28 42 50 61 74 87 99 102
Airflow
m
3
/h
1920 1710 1850 1650 1810 1530 1630 1580
l/s 533 475 514 458 503 425 453 439
CFM 1129 1006 1088 971 1065 900 959 929
LOW
Static
pressure
Pa 24 35 38 47 63 74 83 86
Airflow
m
3
/h
1790 1610 1650 1440 1670 1420 1490 1450
l/s 497 447 458 400 464 394 414 403
CFM 1053 947 971 847 982 835 876 853
QUIET
Static
pressure
Pa 19 28 32 39 50 60 60 63
Airflow
m
3
/h
1610 1440 1510 1310 1490 1280 1280 1230
l/s 447 400 419 364 414 356 356 342
CFM 947 847 888 771 876 753 753 724
21001200
0
140 130 120 110 100
90 80 70 60 50 40 30 20 10
1300 1400 1500 1600 1700 1800 1900 2000
Airflow [m3/h]
External Static Pressure [Pa]
Med
Med
Med
Low
Low
Low
Low
Quiet
Quiet
Quiet
Quiet
Med
Fan performance curve_1
Hi [High static pressure 2 (120Pa)]
Hi [High static pressure 1 (90Pa)]
Hi [Normal (60Pa)]
Hi [Low static pressure (30Pa)]
Page 80
- 25 -
DUCT TYPE
ARGA30-60F
NOTES:
• Setting of the external static pressure is switchable into 4-stage modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal mode".
Characteristics of air volume and capacity
Cooling
21001200
0
140 130 120 110 100
90 80 70 60 50 40 30 20 10
1300 1400 1500 1600 1700 1800 1900 2000
Airflow [m3/h]
External Static Pressure [Pa]
Fan performance curve_2
(For function setting by remote controller)
Hi [High static pressure 1 (90Pa)]
Hi [Normal (60Pa)]
Hi [High static pressure 2 (120Pa)]
Hi [Low static pressure (30Pa)]
100
105
90
95
21001200 1300 1400 1500 1600 1700 1800 1900 2000
Airflow [m3/h]
Capacity [%]
Page 81
- 26 -
DUCT TYPE
ARGA30-60F
Model: ARGA45FMTA
Factory setting is Mode 2.
Fan
speed
Item
Static pressure mode
Mode 1 Mode 2 Mode 3 Mode 4
Low static
pressure
Normal
High static
pressure 1
High static pressure 2
HIGH
Static
pressure
Pa 30 45 60 75 90 110 110 120
Airflow
m
3
/h
2500 2210 2500 2210 2380 2080 2100 1990
l/s 694 614 694 614 661 578 583 553
CFM 1471 1300 1471 1300 1400 1224 1235 1171
MED
Static
pressure
Pa 27 39 50 68 76 94 94 99
Airflow
m
3
/h
2340 2060 2380 2060 2200 1910 1910 1830
l/s 650 572 661 572 611 531 531 508
CFM 1376 1212 1400 1212 1294 1124 1124 1076
LOW
Static
pressure
Pa 23 33 44 58 65 78 78 83
Airflow
m
3
/h
2160 1910 2190 1900 2020 1740 1740 1670
l/s 600 531 608 528 561 483 483 464
CFM 1271 1124 1288 1118 1188 1024 1024 982
QUIET
Static
pressure
Pa 18 28 36 48 48 58 62 66
Airflow
m
3
/h
2000 1760 2000 1730 1730 1500 1550 1490
l/s 556 489 556 481 481 417 431 414
CFM 1176 1035 1176 1018 1018 882 912 876
26001400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
Airflow [m3/h]
0
140 130 120 110 100
90 80 70 60 50 40 30 20 10
External Static Pressure [Pa]
Med
Med
Med
Med
Low
Low
Low
Low
Quiet
Quiet
Quiet
Quiet
Fan performance curve_1
Hi [High static pressure 2 (120Pa)]
Hi [High static pressure 1 (90Pa)]
Hi [Normal (60Pa)]
Hi [Low static pressure (30Pa)]
Page 82
- 27 -
DUCT TYPE
ARGA30-60F
NOTES:
• Setting of the external static pressure is switchable into 4-stage modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal mode".
Characteristics of air volume and capacity
Cooling
26001400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
Airflow [m3/h]
0
140 130 120 110 100
90 80 70 60 50 40 30 20 10
External Static Pressure [Pa]
Fan performance curve_2
(For function setting by remote controller)
Hi: [High static pressure 2 (120Pa)]
Hi [High static pressure 1 (90Pa)]
Hi [Normal (60Pa)]
Hi [Low static pressure (30Pa)]
26001400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
Airflow [m3/h]
100
105
85
90
95
Capacity [%]
Page 83
- 28 -
DUCT TYPE
ARGA30-60F
Model: ARGA60FHTA
Factory setting is Mode 1.
Fan
speed
Item
Static pressure mode
Mode 1 Mode 2 Mode 3 Mode 4 Normal
High static pressure 1
High static
pressure 2
High static pressure 3
HIGH
Static
pressure
Pa 60 85 100 120 130 145 150 160
Airflow
m
3
/h
3350 2860 3060 2780 2900 2700 2760 2620
l/s 931 794 850 772 806 750 767 728
CFM 1971 1682 1800 1635 1706 1588 1624 1541
MED
Static
pressure
Pa 50 77 85 103 115 127 130 138
Airflow
m
3
/h
3170 2700 2820 2580 2720 2530 2550 2430
l/s 881 750 783 717 756 703 708 675
CFM 1865 1588 1659 1518 1600 1488 1500 1429
LOW
Static
pressure
Pa 45 70 67 86 97 110 115 123
Airflow
m
3
/h
2950 2550 2580 2370 2520 2370 2410 2300
l/s 819 708 717 658 700 658 669 639
CFM 1735 1500 1518 1394 1482 1394 1418 1353
QUIET
Static
pressure
Pa 37 55 57 67 85 96 95 101
Airflow
m
3
/h
2650 2270 2370 2130 2340 2210 2190 2100
l/s 736 631 658 592 650 614 608 583
CFM 1559 1335 1394 1253 1376 1300 1288 1235
2000 2200 2400 2600 2800 3000 3200 3400
External Static Pressure [Pa]
Fan performance curve_1
0
20
40
60
80
100
120
140
160
180
200
Hi [Normal (60Pa)]
Quiet
Airflow [m3/h]
Quiet
Quiet
Quiet
Low
Low
Low
Med
Med
Med
Hi [High static pressure 2 (130Pa)]
Hi [High static pressure 1 (100Pa)]
Hi [High static pressure 3 (160Pa)]
Low
Med
Page 84
- 29 -
DUCT TYPE
ARGA30-60F
NOTES:
• Setting of the external static pressure is switchable into 4-stage modes by using the remote controller.
• According to the resistance of the connecting duct, perform the setting of the external static pres­sure with referring “Fan performance curve_2” above.
• The default setting is set at "Normal mode".
Characteristics of air volume and capacity
Cooling
Fan performance curve_2
(For function setting of remote controller)
2000 2200 2400 2600 2800 3000 3200 3400
External Static Pressure [Pa]
0
20
40
60
80
100
120
140
160
180
200
Hi: [Normal (60Pa)]
Airflow [m3/h]
Hi: [High static pressure 2 (130Pa)]
Hi: [High static pressure 1 (100Pa)]
Hi: [High static pressure 3 (160Pa)]
Airflow [m3/h]
Capacity [%]
95
90
100
105
2000 2200 2400 2600 2800 3000 3200 3400
Page 85
- 30 -
DUCT TYPE
ARGA30-60F
8. Operation noise (sound pressure)
8-1. Noise level curve
Model: ARGA30FMTA
Cooling
Model: ARGA36FMTA
Cooling
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
HIGH
QUIET
Page 86
- 31 -
DUCT TYPE
ARGA30-60F
Model: ARGA45FMTA
Cooling
Model: ARGA60FHTA
Cooling
QUIET
HIGH
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000
8,000
HIGH
QUIET
Page 87
- 32 -
DUCT TYPE
ARGA30-60F
8-2. Sound level check point
Center
Front view
Microphone
Center
Side view
Product
Air
1.5 m
2 m 1 m
Microphone
Measuring duct (Set the static pressure as rating in this area.)
Measuring duct
Page 88
- 33 -
DUCT TYPE
ARGA30-60F
9. Safety devices
*: Printed Circuit Board
Protection form
Model
ARGA30FMTA ARGA36FMTA ARGA45FMTA
ARGA60FHTA
Circuit protection Current fuse (PCB*) 250 V, 5 A
Fan motor protection
Thermal protection program
Activate
115 ± 15 °C
Fan motor stop
Reset
70 °C
Fan motor restart
Current protection Activate
7.9 A
Fan motor stop
Page 89
- 34 -
DUCT TYPE
ARGA30-60F
10. External input and output
With using external input and output functions, this product can be operated inter-co nnectedly with an external device.
Models: ARGA30FMTA, ARGA36FMTA, and ARGA45FMTA
Model: ARGA60FHTA
*: Any one of the output functions can be selected by function setting No.60.
10-1. Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit. Unit operation is started at the following contents by adding the contact input of a commercial on/
off switch to a connector on the external control PCB and turning it on.
Circuit diagram example
• When function setting is in "Operation/Stop" mode
Connector Input Output Remarks
CN102 Control input
See external input/output
settings for details.
CN103 Operation status output
CN6 Fresh-air control output
Connector Input Output Remarks
CN46 Control input
See external input/output
settings for details.
* CN47
Operation status output — Error status output — Fresh-air control output
Unit operation Initial setting after power is on
Starting mode other than initial
setting
Operation mode Auto changeover Mode at previous operation Set temperature 24 °C Temperature at previous operation
Airflow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit within 10 m.
• Use non-polar relays and switches.
Indoor unit
control PCB
Connected unit
Example: Switch
Connector
1 3
Signal
Locally purchased
*10 m
24 V
Page 90
- 35 -
DUCT TYPE
ARGA30-60F
• When function setting is in "Forced stop" mode
Optional part
Model name Exterior
UTD-ECS5A
External input wire
Remote controller
On On On
Input signal
On Off
Indoor unit
Operation
Stop
Remote controller
On On On
Input signal
Indoor unit
Command
Remote control operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
Page 91
- 36 -
DUCT TYPE
ARGA30-60F
10-2. External output
With using external output function, operating status of this product can be transmitted to the external device, and also, this product can be inter-connected with the external device.
Operation status output
Circuit diagram example
• *: Make the distance from the PCB to the connected unit within 10 m.
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
Optional part
Model name Exterior
UTD-ECS5A
External output wire
For 30,36,45 models
For 60 model
Locally purchased
Example: Display
Indoor unit
control PCB
Connected unit
Example:
Relay unit
1
2
Signal
Relay power supply
V
Connector
*10 m
DC 24 V
On
Off
Operation
Stop
Indoor unit
Output signal
Page 92
- 37 -
DUCT TYPE
ARGA30-60F
Error status output
Circuit diagram example
*: Make the distance from the PCB to the connected unit within 10 m. Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
Optional part
Fresh-air control output
Signal linked to the indoor unit fan on can be output. NOTE: In cold-air prevention control operation, the signal becomes off.
Circuit diagram example
• *: Make the distance from the PCB to the connected unit within 10 m.
• Relay spec: Rated DC 12 V, 50 mA or less.
Model name Exterior
UTD-ECS5A
External output wire
Locally purchased
Example: Display
Indoor unit
control PCB
Connected unit
Example:
Relay unit
1
2
Signal
Relay power supply
V
Connector
*10 m
DC 24 V
On
Off
Operation
Stop
Indoor unit
Output signal
Locally purchased
Indoor unit
control PCB
Connector
1
12 V
on/off
2
Signal
Relay power supply
Example: Fan
Connected unit
Example: Relay unit
*10 m
Page 93
- 38 -
DUCT TYPE
ARGA30-60F
Optional part
Model name Exterior
UTD-ECS5A
Fresh-air output wire
On
Off
Operation
Stop
Indoor unit
Output signal
Page 94
- 39 -
DUCT TYPE
ARGA30-60F
11. Function settings
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE: Incorrect settings can cause a product malfunction.
11-1. Function settings on indoor unit
By using some components on the PCB, you can change the function settings.
Models: ARGA30FMTA, ARGA36FMTA, and ARGA45FMTA
By using some components on the PCB, you can change the function settings.
Related components on the PCB and the applicable settings
Component location
Components on the indoor unit main PCB used for the function settings are located as shown in the following figure.
Component Setting content
DIP switch
1
Remote controller address setting
2 3 4
Jumper wire
JM1 Setting change prohibited JM2 Setting change prohibited JM3 Setting change prohibited
Indoor unit main PCB
Page 95
- 40 -
DUCT TYPE
ARGA30-60F
DIP switch setting
Remote controller address setting
When operating a number of indoor units by using a wired remote controller, DIP switch se tting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00.
Jumper wire setting
JM1: Setting change prohibited
JM2: Setting change prohibited
JM3: Setting change prohibited
Remote
controller
address
DIP switch number
Factory setting
1 2 3 4
00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14OFFONONON 15 ON ON ON ON
00 01 02
Remote controller address
Indoor unit
Remote controller
Page 96
- 41 -
DUCT TYPE
ARGA30-60F
Model: ARGA60FHTA
By using some components on the PCB, you can change the function settings.
Related components on the PCB and the applicable settings
Component location
Components on the indoor unit main PCB used for the function settings are located as shown in the following figure.
DIP switch setting
Remote controller address setting (SW100) When operating a number of indoor units by using a wired remote controller, DIP switch setting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00.
Remote
controller
address
DIP switch number
Factory
setting
1 2 3 4
00 OFFOFFOFFOFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF O FF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON
11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON
SW100
1234
SW101
123
Page 97
- 42 -
DUCT TYPE
ARGA30-60F
Switch 1: Setting change prohibited (SW101)
Switch 2: Setting change prohibited (SW101)
Switch 3: Setting change prohibited (SW101)
00 01 02
Remote controller address
Indoor unit
Remote controller
Page 98
- 43 -
DUCT TYPE
ARGA30-60F
11-2. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce­dure and the content of each function setting, select appropriate functions for your installation envi­ronment.
NOTE: Incorrect settings can cause a product malfunction.
Setting procedure by using wired remote controller
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before turning on the power of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
1. Turn on the power.
2. Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously for more than 5 seconds to enter the function setting mode.
3. Press the SET BACK button to select the indoor unit number when you set the remote controller address setting.
4. Press the set time buttons to select the function number.
5. Press the SET TEMP. buttons ( ) ( ) to select the setting value. The display flashes during setting value selection.
6. Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops flashing. If the setting value display changes or if “- -” is displayed when the flashing stops, the setting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.)
SU
MO
TU
WE
TH FR
SA
SET BACK
SUMOTUWETH FR
SA
Unit number of indoor unit
SUMOTUWETH FR
SA
Function number
SUMOTUWETH FR
SA
Setting value
Page 99
- 44 -
DUCT TYPE
ARGA30-60F
7. Repeat steps 3 to 6 to perform additional settings. Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1 minute if no oper­ation is performed.
8. After completing the function setting, be sure to turn off the power and turn it on again.
!
CAUTION
After turning off the power, wait 30 seconds or more before turning on the power again. The function setting will not become active unless the power is turned off then on again.
Page 100
- 45 -
DUCT TYPE
ARGA30-60F
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
For 30 model
For 36, 45 model
For 60 model
Function no. Functions
1)
11
Filter sign
2)
21
Static pressure
3)
30
Room temperature sensor control for cooling
4)
40
Auto restart
5)
42
Room temperature sensor switching
6)
46
External input control
7)
48
Room temperature sensor switching (Aux.)
8)
60
Switching functions for external output terminal
Function number Setting value Setting description Factory setting
11
00 Standard (2,500 hours) 01 Long interval (4,400 hours) 02 Short interval (1,250 hours) 03 No indication
Function number Setting value Setting description Factory setting
21
00 Normal (30 Pa) 01 High static pressure 1 (60 Pa) 02 High static pressure 2 (90 Pa) 03 High static pressure 3 (120 Pa)
Function number Setting value Setting description Factory setting
21
00 Normal (60 Pa) 01 Low static pressure (30 Pa) 02 High static pressure 1 (90 Pa) 03 High static pressure 2 (120 Pa)
Function number Setting value Setting description Factory setting
21
00 Normal (60P a) 02 High static pressure 1 (100 Pa) 03 High static pressure 2 (130 Pa) 04 High static pressure 3 (160 Pa)
Loading...