Fujitsu ASG18LFCA, ASG24LFCA, AOG18LFC, AOG24LFL, AOG30LFT Design & Technical Manual

...
Page 1
AIR CONDITIONER
Wall Mounted type
INDOOR
OUTDOOR
ASG18LFCA ASG24LFCA ASG30LFCA
AOG18LFC
AOG24LFL AOG30LFT
DESIGN & TECHNICAL MANUAL
Page 2
1. INDOOR UNIT
WALL MOUNTED TYPE :
ASG18LFCA ASG24LFCA ASG30LFCA
DTR_AS052E_01
2011.02.07
Page 3
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
CONTENTS
1. INDOOR UNIT
1. FEATURE
.................................................................................................................. 01 - 01
2. WIRELESS REMOTE CONTROLLER
............................................... 01 - 04
3. SPECIFICATIONS
.............................................................................................. 01 - 06
4. DIMENSIONS
........................................................................................................ 01 - 07
5. WIRING DIAGRAMS
........................................................................................ 01 - 09
6. CAPACITY TABLE
............................................................................................ 01 - 10
6-1. COOLING CAPACITY
...................................................................................... 01 - 10
6-2. HEATING CAPACITY
........................................................................................01 - 11
7. FAN PERFORMANCE
.................................................................................... 01 - 12
7-1. AIR VELOCITY DISTRIBUTION
..................................................................... 01 - 12
7-2. AIR FLOW
.......................................................................................................... 01 - 14
8. OPERATION NOISE
......................................................................................... 01 - 17
8-1. NOISE LEVEL CURVE
.................................................................................... 01 - 17
8-2. SOUND LEVEL CHECK POINT
..................................................................... 01 - 19
9. ELECTRIC CHARACTERISTICS
........................................................... 01 - 20
10. SAFETY DEVICES
............................................................................................ 01 - 21
11. EXTERNAL INPUT & OUTPUT
............................................................... 01 - 22
11-1. EXTERNAL INPUT
........................................................................................... 01 - 22
11-2. EXTERNAL OUTPUT
....................................................................................... 01 - 24
12. FUNCTION SETTING
...................................................................................... 01 - 25
12-1. INDOOR UNIT (Setting by remote controller)
........................................... 01 - 25
13. OPTIONAL PARTS
........................................................................................... 01 - 29
Page 4
- (01 - 01) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
FEATURE1.
MODEL
ASG18LFCA ASG24LFCA ASG30LFCA
FEATURES
ALL DC
z
Front view
a
b
Large air flow and quiet operation by new air flow path
High efficiency layout
Back view
New 3-row heat exchange system (24TYPE)
1
2
3
More compact compared with conventional model
b
DC
compressor
a
DC
fan motor
DC fan motor
Super quiet
z
Air ow mode can be set in 4 steps and more detailed air ow setting is possible.
Easy maintenance
z
Easy maintenance and always clean. Troublesome maintenance has been made easy.
Since the front panel is easy to remove, maintenance is also easy.
10°C HEAT Operation
z
The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied
Caution)
When the room temperature is higher than 10°C, “10°C HEAT” operation does not star t. Operation starts and maintains the room
temperature at 10°C when the temperature drops below 10°C.
10
°C
20
°C
“10°C HEAT”
Button ON
Indoor unit operation START
“10°C HEAT”
Button ON
AOG24LFL
AOG18LFC AOG30LFT
Page 5
- (01 - 02) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
Power diffuser
z
Adoption of large power diffuser
16
Outside air conditions:2
o
C 60%
( C)
Operation contents: Heating, Set temperature (Max set temp)
o
2933 32 31 30
30oC, Air flow Hi, Vertical flap : Downward Horizontal flap : Center
2.1
1
0
3 6 9 12
(m)
(m)
Power diffuser
(full open)
46
o
“Strong vertical air ow” provides powerful oor level heating.
“Healthy horizontal air ow” does not blow cool air directly at the occupants in the room.
Outside air conditions: 35 oC 40%
( C)
Operation contents: Cooling, Set temperature (Min set temp) 18
o
o
C, Air flow Hi,
1815 16 17
2.1
1
0
3 6 9 12
(m)
(m)
Vertical flap : Upward Horizontal flap : Center
Power diffuser
Low outdoor air temperature cooling and heating correspondence
z
Corresponds to cooling operation at -10°C and heating operation at -15°C outdoor air temperature
Cooling
-10°C
Heating
-15°C
Corresponds to maximum 50m long piping (30type)
z
Page 6
- (01 - 03) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
Air conditioner lter features
z
Organic coating fin used heat exchanger
Pre Filter Antibacterial deodorizing
pre-filter with special ceramic powder
Ion Deodorization Filter
Apple-catechin Filter
Apple­catechin Filter
Long-life Ion Deodorization Filter
Economy operation
z
Example : Cooling operation
Economy operation is energy saving, as the set temperature of indoor unit is shifted by 1°C and the maximum electric value of the outdoor unit is suppressed.
Temp.
Economy operation
Shift
setting
temp
Control maxmum current
Nomal operation
Time
Set temperature
Blue n heat exchanger (30type)
z
Corrosion-resistance of the heat exchanger even in coastal areas has been improved by blue n treatment of the outdoor unit heat exchanger.
Blue n heat exchanger
Cobalt Blue protection
Standard chromate protection
Aluminium bas e material
Hydrophilic coat ing
Page 7
- (01 - 04) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
WIRELESS REMOTE CONTROLLER2.
FEATURES
Built-in timers
z
Select from four different timer programs (On / Off / Program / Sleep).
Program timer
z
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
z
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
60min.
1°C
2°C
Timer setting
1°C
2°C
3°C
4°C
30min.
60min.
90min.
Timer setting
Cooling operation / dry operation
When the sleep timer is set, the set temperature automatically rises 1°C every hour. The set temperature can rise up to a maximum of 2°C.
Heating operation
When the sleep timer is set, the set temperature automatically drops 1°C every 30 minutes. The set temperature can drop to a maximum of 4°C.
Easy installation and operation
z
Code selector switch eliminates unit
• being wrongly switched. (Up to 4 codes can be set.)
*I.U.=Indoor unit
A B C D
A B
C
D
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Can be used jointly with wired remote controllers . Easy to change custom code (4 patterns).
Page 8
- (01 - 05) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
FUNCTIONS
MODE button1
Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. custom code change. (Max 4 types)
10°C2 HEAT button
SET TEMP. button ( ▲ / ▼ )3
Set remote controller custom code buttons Sets the indoor temp./ Sets R.C. custom code.
ECONOMY button4
SLEEP button5
Pressed to select sleep timer.
FAN button6
Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).
START/STOP button7
Pressed to start and stop operation.
SET button (Vertical)8
Air ow direction vertical set button.
SET button (Horizontal)9
Air ow direction horizontal set button.
SWING button10
Air ow direction swing button.
TIMER MODE button11
Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET)
TIMER SET ( / ) button12
Sets the current time and on-off time.
CLOCK ADJUST button13
Sets the current time.
RESET button14
Used when replacing batteries.
TEST RUN button15
Used when testing the air conditioner after installation.
Signal transmitter16
Temperature set display17
Operating mode display18
Sleep display19
Transmit indicator20
Fan speed display21
Swing display22
Timer mode display23
Clock display24
Display panel
Note: Functions will be different due to type of indoor unit.
For details, please see operation manual.
+
-
2
4
9
3
1
16
15
5
10
13
11
12
14
8
7
6
17
18
19
21
24
23
22
20
Page 9
- (01 - 06) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
SPECIFICATIONS3.
Typ e
WALL MOU NTED
INVERT ER HEAT PUM P Model na me ASG18LFCA ASG24LFCA ASG30LFCA Power source 230V~ 50 Hz Available voltage range 198-26 4V ~ 50Hz
Capacity
Cooling
Rated
kW 5.20 7.10 8.00
BTU/h 17,700 24,200 27, 3 00
Min.-Max.
kW 0.9~6.0 0.9 -8.0 2.9-9.0
BTU/h 3,100~20,500 3,100-27,300 9,900-30,700
Heating
Rated
kW 6.30 8.00 8.80
BTU/h 21,500 27, 30 0 30,000
Min.-Max.
kW 0.9~9.1 0.9-10.6 2. 2-11 .0
BTU/h 3,100~31,000 3,100-36, 200 7, 50 0 -3 7,6 00
Input power
Cooling
Rated
kW
1.52 2.20 2.49
Min.-Max. 0.09~2.07 0.30 -3.07 0.58-3.87
Heating
Rated 1.71 2.21 2.44 Min.-Max. 0.09~2.87 0.28-4.21 0.50-4.33
Current
Cooling
Rated
A
6.8 9.7 10.9
Max.* 9.0 13. 5 17. 0
Heating
Rated 7.6 9.7 10.7 Max.* 12.5 18 .5 19.0
EER Cooling
kW/kW
3.42 3.23 3.21
COP Heating 3.68 3.61 3.61 SENSIB LE CAPACIT Y Cooling kW 3.45 5.25 6.00
POWER FACTOR
Cooling
%
97 99 99
Heating 98 99 99
Moisture removal l/h (pints/ h) 2.6(4.6) 2.7(4. 8) 3.2(5 .6)
Fan
Airow rate
Cooling
High
m
3
/h
900 1100 110 0
Med 740 900 900 Low 620 74 0 74 0
Quiet 550 580 620
Heating
High 900 1120 115 0 Med 740 900 900 Low 620 74 0 74 0
Quiet 550 580 620 Type × Q'ty Cross ow fan × 1 Motor out put W 42 42 42
Sound pressure level
Cooling
High
dB(A)
43 47 48
Med 37 42 42 Low 33 37 37
Quiet 26 32 33
Heating
High 42 48 49 Med 37 42 42 Low 33 37 37
Quiet 25 32 33
Heat exchanger type
Dimensions (H × W × D)
mm
Main:378 x 832 x 26.6
Sub:84 x 382 x 13.3
Main : 378 × 832 × 2 6.6 Sub1 : 84 × 832 × 13.3,
Sub2 : 84 × 83 2 × 13.3 Fin pitch Main:1.2 Sub:1.4 Main : 1.2, Sub1 : 1.4, Sub2 : 1.4 Rows x Stag es Main:2 x 18 Sub:1 x 4 Main : 2 × 18, Sub1 : 1 × 4, Sub2 : 1 × 4 Pipe typ e Copper Fin type Aluminium
Enclosu re
Material Polystyrene
Colour
WHITE
Approximate colour of MUNSELL N 9. 25/ Dimensions ( H×W ×D )
Net
mm
320 × 998 × 2 38
Gross 329 × 1090 × 42 0
Weight
Net
kg(lbs.)
14 (30.8)
Gross 18 (39.6)
Connec tion pipe
Size
Liquid
mm
Ø6.35 (Ø1/4 in ) Ø6.35 (Ø1/4 in.) Ø9.52 (Ø3/ 8 in.)
Gas Ø12.7 (Ø1/2in ) Ø15.88 (Ø5/8 in.) Ø15.88 (Ø5/ 8 in.)
Method Flare
Operat ion rang e
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 30 or less
Remote co ntroller type Wireless
Drain pipe
Material PVC Size mm Outer diameter : 28 / I nner diameter : 16
Note : Specications are based on the following conditions. Cooling : Indoor temperature of 27°CD B/19°CWB. and outdoor temperature of 35°CDB/24°CWB. Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB. Pipe length : 5/7.5 m (*1), Height dif ference : 0 m. (Outdoor unit - Indoor unit) The maximum current is the maximum value when operated within the operation range(temperature) * The maximum current is the total current of indoor unit and outdoor unit. *1 18LFCA:5m, 24/30LFCA:7.5m
Page 10
- (01 - 07) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
DIMENSIONS4.
MODEL : ASG18LF, ASG24LF, ASG30LF
(Unit : mm)
ASG18LF ASG24LF ASG30LF
Refrigerant pipe are
connection
Liquid ø 6.35 mm (1/4 in.) ø 9.52 mm(3/8 in.)
Gas ø 12.7 mm(1/2 in.) ø 15.88 mm(5/8 in.)
Drain hose connection Drain hose
I.D. 12 mm , O.D. 16 mm
Drain hose : L=670mm
998
439
438
397
320: Unit size
269
20
37
26 x 11 hole
5 x 18: 14holes
21 x 5: 14holes
5 x 50: 3holes
13 x 5: 4holes
ø 80 hole
ø 5: 65holes
998: Unit size
Piping inlet
for tapping screw
18 x 11 hole
18 x 11 hole
122
172
75
387
170
16
400
Unit center
126
133
130
113
75
243
238
320
520
520
590
721
ø 80 hole
Piping inlet
30
30
149
197
272
44
12
13
26 x 11 hole
25
ø 32
ø 16
ø 12
Page 11
- (01 - 08) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
INSTALLATION PLACE
(Unit : mm)
63 or more
80 or more
53 or more
52 or more
80 or more
Outline of unit
120 or more
1500 or more
1800 or more
Page 12
- (01 - 09) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
WIRING DIAGRAMS5.
MODEL : ASG18LF, ASG24LF, ASG30LF
TO OUTDOOR UNIT
CONTROOL BOARD
TEST
CN13
CN14
2 1
CN16
EX.OUT (OPTION)
EX.IN (OPTION)
1
2
3
BLACK
WHITE
RED
REMOTE CONTROL
UNIT (OPTION)
3 2 1
Page 13
- (01 - 10) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
CAPACITY TABLE6.
COOLING CAPACITY6-1.
MODEL : ASG18LF
MODEL : ASG24LF
MODEL : ASG30LF
AFR : Air  ow rate (m3/min) TC : Total capaci ty (kW) SHC : Sens ible Hea t capaci ty (kW) IP : Input Pow er (kW)
AFR 15.0
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 4.62 3.14 1.03 5.15 3.15 1.05 5.33 3.43 1.05 5.68 3.44 1.06 5.85 3.71 1.07 6.20 3.70 1.08 6.56 3.94 1.09
25 4.63 3.14 1.17 5.16 3.16 1.19 5.34 3.43 1.20 5.69 3.45 1.21 5.86 3.72 1.22 6.21 3.71 1.23 6.57 3.95 1.24
30 4.38 2.97 1.32 4.88 2.99 1.34 5.04 3.25 1.35 5.38 3.26 1.36 5.54 3.52 1.37 5.87 3.50 1.38 6.21 3.73 1.39
35 4.11 2.91 1.47 4.58 2.93 1.49 4.73 3.18 1.50 5.04 3.19 1.51 5.20 3.45 1.52 5.51 3.44 1.54 5.82 3.66 1.55
40 3.56 2.41 1.35 3.96 2.43 1.38 4.10 2.64 1.38 4.37 2.65 1.40 4.50 2.86 1.40 4.78 2.85 1.42 5.05 3.03 1.43
46 3.08 2.09 1.65 3.43 2.10 1.68 3.55 2.28 1.68 3.78 2.29 1.70 3.90 2.48 1.71 4.13 2.47 1.73 4.37 2.63 1.74
AFR 18.3
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 5.72 4.53 1.17 6.37 4.56 1.19 6.59 4.96 1.19 7.02 4.97 1.20 7.24 5.37 1.21 7.67 5.35 1.22 8.11 5.70 1.23
25 6.41 4.90 1.84 7.15 4.93 1.87 7.39 5.36 1.88 7.88 5.38 1.90 8.12 5.81 1.91 8.61 5.79 1.93 9.09 6.16 1.95
30 6.19 4.71 2.02 6.90 4.74 2.05 7.13 5.15 2.06 7.60 5.17 2.08 7.84 5.58 2.09 8.31 5.56 2.11 8.78 5.92 2.13
35 5.61 4.43 2.09 6.25 4.46 2.13 6.46 4.85 2.14 6.89 4.86 2.16 7.10 5.25 2.21 7.53 5.23 2.19 7.95 5.57 2.21
40 5.08 4.11 2.08 5.66 4.13 2.12 5.85 4.50 2.13 6.24 4.51 2.15 6.43 4.87 2.16 6.82 4.85 2.18 7.20 5.17 2.20
46 4.62 3.88 2.24 5.15 3.91 2.27 5.32 4.25 2.29 5.68 4.26 2.31 5.85 4.60 2.32 6.20 4.58 2.34 6.55 4.88 2.37
AFR 18.3
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 6.31 5.01 1.29 7.03 5.04 1.31 7.27 5.48 1.32 7.75 5.50 1.33 7.99 5.94 1.34 8.47 5.92 1.35 8.95 6.30 1.37
25 6.99 5.45 2.03 7.79 5.48 2.06 8.05 5.96 2.07 8.58 5.98 2.09 8.85 6.46 2.10 9.38 6.43 2.12 9.91 6.85 2.14
30 6.66 5.23 2.26 7.42 5.26 2.29 7.67 5.72 2.30 8.18 5.74 2.33 8.43 6.20 2.34 8.94 6.18 2.36 9.44 6.58 2.39
35 6.32 5.06 2.40 7.04 5.09 2.44 7.28 5.54 2.45 7.76 5.56 2.48 8.00 6.00 2.49 8.48 5.98 2.51 8.96 6.37 2.54
40 5.68 4.63 2.68 6.33 4.66 2.72 6.54 5.07 2.74 6.97 5.08 2.77 7.19 5.49 2.78 7.62 5.47 2.81 8.05 5.82 2.84
46 5.17 4.22 2.89 5.76 4.25 2.93 5.96 4.62 2.95 6.35 4.63 2.98 6.55 5.00 2.99 6.94 4.98 3.02 7.34 5.31 3.05
Page 14
- (01 - 11) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
HEATING CAPACITY6-2.
MODEL : ASG18LF
MODEL : ASG24LF
MODEL : ASG30LF
AFR: Air  ow rate (m3/min) TC : Total capaci ty (kW) IP : Input Pow er (kW)
AFR 15.0
Indoor t empera ture
16 18 20 22 24
Outdoo r temper ature
(°CD B) (°CWB) TC IP TC IP TC IP TC IP TC IP
-15 -16 5.09 2.16 4.96 2. 21 4.84 2. 26 4.72 2. 30 4.60 2. 35
-10 -11 6.04 2. 36 5.89 2 .42 5.75 2.47 5.61 2. 52 5.47 2. 57
-5 -7 6.81 2 .48 6.6 4 2.54 6.4 8 2 .59 6.3 2 2 .64 6.16 2. 69 0 -2 7.86 2 .65 7.67 2.72 7.48 2.7 7 7.29 2. 83 7.11 2.89 5 3 8.94 2.8 3 8.72 2.9 0 8.51 2.9 6 8.30 3. 01 8.09 3.08 7 6 9.56 2.75 9.33 2.82 9.10 2 .87 8.87 2 .92 8.6 5 2 .99
10 8 9.91 2 .75 9.66 2. 82 9.43 2.87 9 .19 2.92 8 .97 2.9 9 15 10 9. 59 2.38 9. 36 2.4 4 9.13 2.4 9 8 .90 2.5 4 8 .68 2.5 9
AFR 18.7
Indoor t empera ture
16 18 20 22 24
Outdoo r temper ature
(°CD B) (°CWB) TC IP TC IP TC IP TC IP TC IP
-15 -16 6.20 2.75 6.0 5 2 .80 5.9 0 2 .86 5.75 2.92 5.61 2. 97
-10 -11 7.06 2. 94 6.89 3. 00 6.72 3. 06 6.55 3 .12 6.38 3.18
-5 -7 8.2 3 3. 23 8.0 4 3 .29 7.84 3 .36 7.64 3 .43 7.45 3.49 0 -2 9. 05 3.20 8. 84 3.26 8 .62 3.33 8 .40 3.40 8.19 3.4 6 5 3 10.05 3.3 4 9.81 3 .41 9.57 3. 48 9.33 3. 55 9.09 3 .62 7 6 11.13 3. 38 10.87 3. 45 10.60 3 .52 10.3 4 3.59 10. 07 3.66
10 8 11.19 3 .38 10.93 3 .45 10.6 6 3.52 10. 39 3.59 10.13 3.66 15 10 10.71 2.90 10. 46 2.96 10 .20 3.0 2 9.95 3.0 8 9.69 3.13
AFR 19.2
Indoor t empera ture
16 18 20 22 24
Outdoo r temper ature
(°CD B) (°CWB) TC IP TC IP TC IP TC IP TC IP
-15 -16 7.75 4.07 7.56 4.16 7.38 4 .24 7.20 4.32 7. 01 4. 41
-10 -11 8.34 4.0 6 8 .14 4 .15 7.94 4. 23 7.74 4.31 7.54 4.4 0
-5 -7 9.61 4.08 9.38 4.17 9.15 4.2 5 8.92 4.3 4 8.69 4. 42 0 -2 10. 54 4.04 10. 29 4.13 10. 04 4.21 9.79 4.29 9.5 4 4.38 5 3 11.53 4.0 9 11.25 4.17 10.98 4.2 6 10.71 4. 35 10.43 4. 43 7 6 11.55 3.3 9 11.28 3. 46 11.00 3 .53 10.73 3 .60 10.4 5 3.67
10 8 11.90 3. 38 11.61 3 .45 11.33 3.52 11.05 3 .59 10.76 3 .66 15 10 11.48 2.95 11.20 3.01 10.9 3 3.07 10.6 6 3 .13 10.3 8 3.19
Page 15
- (01 - 12) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
FAN PERFORMANCE7.
AIR VELOCITY DISTRIBUTION7-1.
MODEL : ASG18LF
Note:
Fan speed : High
Operation mode : FAN
Voltage : 230V
2
1
0
1
2
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
3
2
1
0
1
2
3
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
3
2
1
0
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
3
2
1
0
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
Side view Vertic al ap : Dow n Horizo ntal ap : C enter
2.0
1.0
0.5
Side view Vertic al ap : Up Horizo ntal ap : C enter
2.0
1.0
0.5
Top view Vertic al ap : Up Horizo ntal ap : R ight & Lef t
1.0
1.0
0.5
0.5
2.0
Top view Vertic al ap : Up Horizo ntal ap : C enter
2.0 1.0 0.5
Page 16
- (01 - 13) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
MODEL : ASG24LF, ASG30LF
Note:
Fan speed : High
Operation mode : FAN
Voltage : 230V
2
1
0
1
2
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
3
2
1
0
1
2
3
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
3
2
1
0
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
3
2
1
0
(m)
(m)
Unit : m/s
0 1 2 3 4 5 6 7 8
Side view Vertic al ap : Dow n Horizo ntal ap : C enter
2.0
1.0
0.5
Side view Vertic al ap : Up Horizo ntal ap : C enter
2.0
1.0
0.5
Top view Vertic al ap : Up Horizo ntal ap : R ight & Lef t
1.0
1.0
0.5
0.5
2.0
Top view Vertic al ap : Up Horizo ntal ap : C enter
2.0 1.0 0.5
Page 17
- (01 - 14) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
AIR FLOW7-2.
MODEL : ASG18LF
Cooling / Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 1220
900 m
3
/h
250 l/s
530 CFM
MED 1020
740 m
3
/h
206 l/s
435 CFM
LOW 900
620 m
3
/h
172 l/s
365 CFM
QUIET 710
550 m
3
/h
153 l/s
324
CFM
Page 18
- (01 - 15) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
MODEL : ASG24LF
Cooling
z
Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 1430
110 0 m
3
/h
306 l/s
647 CFM
MED 1220
900 m
3
/h
250 l/s
530 CFM
LOW 1020
740 m
3
/h
206 l/s
435 CFM
QUIET 860
580 m
3
/h
161 l/s
341 CFM
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 1480
112 0 m
3
/h
311 l/s
659 CFM
MED 1220
900 m
3
/h
250 l/s
530 CFM
LOW 1020
740 m
3
/h
206 l/s
435 CFM
QUIET 860
580 m
3
/h
161 l/s
341 CFM
Page 19
- (01 - 16) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
MODEL : ASG30LF
Cooling
z
Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 1430
1100 m
3
/h
306 l/s
647 CFM
MED 1220
900 m
3
/h
250 l/s
530 CFM
LOW 1020
740 m
3
/h
206 l/s
435 CFM
QUIET 900
620 m
3
/h
172 l/s
365 CFM
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 1530
1150 m
3
/h
319 l/s
677 CFM
MED 1220
900 m
3
/h
250 l/s
530 CFM
LOW 1020
740 m
3
/h
206 l/s
435 CFM
QUIET 900
620 m
3
/h
172 l/s
365 CFM
Page 20
- (01 - 17) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL : ASG18LF
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
High
Quiet
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
MODEL : ASG24LF
Cooling
z
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
High
Quiet
High
Quiet
High
Quiet
Cooling
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
Page 21
- (01 - 18) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
MODEL : ASG30LF
High
Quiet
High
Quiet
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Cooling
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 22
- (01 - 19) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
SOUND LEVEL CHECK POINT8-2.
Page 23
- (01 - 20) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
ELECTRIC CHARACTERISTICS9.
Model name ASG18LF ASG24LF ASG30LF
Power supply
Volt ag e V 230 ~ Frequency Hz 50
Max. operating current A 0.3
*1)Wiring Spec.
Connection cable mm
2
1.5 - 2.5
Limited wiring length m 26 31 51
*1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
Page 24
- (01 - 21) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
SAFETY DEVICES10.
Protection form
Model
ASG18LF, ASG24LF, ASG30LF
Circuit protection Current fuse (PCB) 3.15A 250V
Terminal protection Current (thermal) fuse 3A 250V
Fan motor protection Thermal protector program
100
+15
-10
°C OFF
95+5
-10
°C ON
Page 25
- (01 - 22) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
EXTERNAL INPUT & OUTPUT11.
Connector INPUT OUTPUT REMARKS
CN14 Control input - See external
input/output settings
for details.
CN16 - Operation status output
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit. Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Initial starting after power turned on Starting other than at the left
Operation mode Auto changeover Mode at previous operation Set temperature 24°C Temperature at previous operation
Air ow mode AUTO Mode at previous operation Up-down air direction (swing) Standard air direction (swing OFF) Air direction at previous operation Left-right air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
z
Indoor
control PC board Connected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m. Contact capacity : 24VDC or more, 10mA or more. Please use the non-polar relays and switches.
*10 m
When function setting is "Operation/Stop" mode
z
Operation
Stop
ON
OFF
Input signal
Indoor unit
Page 26
- (01 - 23) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
When function setting is "Forced stop" mode
Remote controller
On On On
Input signal
On Off
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control operation invalidity
Parts (Optional)
z
Parts name
Model name
External connect kit UT Y-X WZ X
Wire (External input) : UTY-XWZX
Page 27
- (01 - 24) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
EXTERNAL OUTPUT11-2.
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
z
Field supply
Ex.)Display
Indoor
control PC board
Connected unit
Ex.)Relay unit
1
2
Signal
Relay power supply
V
Connector
* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Max.24VDC, 10mA to less than 500mA.
*10 m
24V DC
ON
OFF
Operation
Stop
Indoor unit
Output signal
Parts (Optional)
z
Parts name
Model name
External connect kit UT Y-X WZ X
Wire (External input) : UTY-XWZX
Page 28
- (01 - 25) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
FUNCTION SETTING12.
INDOOR UNIT (Setting by remote controller)12-1.
The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP. (
) simultaneously, press the RESET button to enter the function
setting mode.
STEP 1 Setting the Remote controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) The signal codes that are set through this process are applicable only to the signals in the FUNCTION SETTING. For details on how to set the signal codes through the normal process, refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE.
Press the SET TEMP. (1.
) ( ) button to change the signal code between →
→ Match the code on the display to the air conditioner signal code. (initially
set to
)
(If the signal code does not need to be selected, press the MODE button and proceed to STEP 2.)
Press the TIMER MODE button and check that the indoor unit can receive signals 2. at the displayed signal code.
Press the MODE button to accept the signal code, and proceed to STEP 2.3.
The air conditioner signal code is set to A prior to shipment.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes (
→ → → ) until you
nd the code which operates the air conditioner.
STEP 2 Selecting the Function Number and Setting Value
Press the SET TEMP. (1.
) ( ) buttons to select the function
numbe r. (Press the MODE button to switch between the left and right digits.)
Press the FAN button to proceed to setting the value. 2. Press the FAN button again to return to the function number selection.)
Press the SET TEMP. (3.
) ( ) buttons to select the setting value. (Press the MODE button to switch between the left and right digits.)
Press the TIMER MODE button, and START/STOP button, 4. in the order listed to conrm the settings.
Press the RESET button to cancel the function setting 5. mode.
After completing the FUNCTION SETTING, be sure to turn 6. off the power and turn it on again.
Function number
Setting value
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The FUNCTION SETTING doesn’t become effective if it doesn’t do so.
Page 29
- (01 - 26) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
FUNCTION DETAILS
Functions Wall mounted
1) Filter sign
z
2) Cooler room temperature correction
z
3) Heater room temperature correction
z
4) Auto restart
z
5)
Indoor room temperature sensor switching function
z
6) Remote controller signal code
z
7) External input control
z
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the lter. Select the time setting for the lter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the lter sign to be displayed, select the setting value for "No indication".
(... Factory setting)
Setting description Function number Setting value
Standard
11
00
Long interval 01 Short interval 02
No indication 03
The lter sign interval time is different according to Indoor unit type as follows.
Setting description Wall mounted
Standard 400 hours Long interval 1000 hours Short interval 200 hours
2) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
30
00
Slightly lower control 01
Lower control 02
Warmer control 03
3) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
Page 30
- (01 - 27) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
4) Auto restart
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting description Function number Setting value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
(... Factory setting)
Setting description Function number Setting value
No
42
00
Yes 01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
6) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(... Factory setting)
Setting description Function number Setting value
A
44
00 B 01 C 02 D 03
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(... Factory setting)
Setting description Function number Setting value
Operation/Stop mode
46
00
(Setting forbidden) 01 Forced stop mode 02
Page 31
- (01 - 28) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
REMOTE CONTROLLER SIGNAL CODE SETTING
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has
not been set for the signal code.)
Press the START/STOP button until only the clock is displayed on the remote 1. controller display.
Press the MODE button for at least ve seconds to display the current signal code 2. (initially set to
).
Press the SET TEMP. (3.
) ( ) button to change the signal code between →
→ .
Match the code on the display to the air conditioner signal code.
Press the MODE button again to return to the clock display. The signal code will 4. be changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original clock display. In this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment. Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes (
→ → → ) until you nd the code which
operates the air conditioner.
Page 32
- (01 - 29) -
WALL MOUNTED TYPE
AS
G18-30LF
WALL MOUNTED TYPE
AS
G18-30LF
OPTIONAL PARTS13.
Exterior Parts name Model No. Summary
SUMOTUWETH FR
SA
AM PM
3 6 9
12 15 18 21
Wired remote
controller
UTY- RNNY M
Unit control is performed by wired remote controller.
Apple-catechin
lter
UTR- FA13 -1
Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the lter by static electricity, and further growth is inhibited and deactivated by the polyphenol ingredient extracted from apples.
Ion
deodorisation
lter
UTR- FA13 -2
The lter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra ne-particle ceramic.
External
connect kit
UTY-X W ZX
Use to connect with various peripheral devices and air conditioner PC board.
Page 33
2. OUTDOOR UNIT
SINGLE TYPE :
AOG18LFC
AOG24LFL
AOG30LFT
DTR_AO080E_01
2011.02.07
Page 34
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
CONTENTS
2. OUTDOOR UNIT
1. SPECIFICATIONS
.............................................................................................. 02 - 01
2. DIMENSIONS
........................................................................................................ 02 - 02
3. REFRIGERANT CIRCUIT
............................................................................ 02 - 05
4. WIRING DIAGRAMS
........................................................................................ 02 - 08
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
......................................................................02 - 11
6. ADDITIONAL CHARGE CALCULATION
......................................... 02 - 14
7. AIR FLOW
................................................................................................................ 02 - 15
8. OPERATION NOISE
......................................................................................... 02 - 17
8-1. NOISE LEVEL CURVE
.................................................................................... 02 - 17
8-2. SOUND LEVEL CHECK POINT
..................................................................... 02 - 19
9. ELECTRIC CHARACTERISTICS
........................................................... 02 - 20
10. SAFETY DEVICES
............................................................................................ 02 - 21
Page 35
- (02 - 01) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
SPECIFICATIONS1.
Typ e INVERTER HEAT PUMP Model name AOG18LFC AOG24LFL AOG30LFT Power source 230V~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current A 7. 6 9.7 10.9
Fan
Airow rate
Cooling
m
3
/h
2,150 2,340 3,600
Heating 2,070 2,570 3,600 Type × Q'ty Propeller fan×1 Motor output W 40 11 5 100
Sound pressure level
Cooling
dB(A)
50 53 53
Heating 51 56 55
Heat exchanger type
Dimensions
(H × W × D)
mm
588 × 881 × 36.4
Main : 546 × 866 × 36.4
Sub : 504 × 589 × 18.2
798×900×36.4
Fin pitch 1.3 Main:1.4, Sub:1.4 1.3
Rows x Stages 2 × 28 Main:2 × 26, Sub:1 × 24 2×38
Pipe type Copper
Fin
Type(Material) Corrugate (Aluminum) Surface treat­ment
Corrosion resistance
Corrosion resistance
(Blue n)
Compressor
Type × Q'ty Rotary ×1 Motor output W 900 1,000 2,10 0
Refrigerant
Typ e R410A
Charge g 1,200 1,650 2 ,10 0
Refrigerant oil Typ e FREOLα68SZ POE (RB68)
Enclosure
Material Steel
Colour
BEIGE
Approximate colour of MUNSELL 10YR7.5/1.0
Dimensions ( H×W×D)
Net
mm
620 × 790 × 290 578×790×315 830×900×330
Gross 712 × 935 × 400 648×910×380 970×1050×445
Weight
Net
kg(lbs.)
41 (90) 43 (95) 61 (135)
Gross 45 (99) 47 (104) 68 (150)
Connection pipe
Size
Liquid
mm
Ø6.35 (Ø1/4 in.) Ø9.52 (Ø3/8 in.)
Gas Ø12.7 (Ø1/2 in.) Ø15.88 (Ø5/8 in.) Method Flare Pre-charge length
m
15 15
20 Max. length 25 30 50 Max. height difference 20 20 30
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Note :
Specications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB /24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CW B.and outdoor temperature of 7 °CDB/6 °CWB. Pipe length : 5/7.5 m (*1), Height dif ference : 0 m.(Outdoor unit - Indo or unit) *1 18LFC : 5m, 24 /30LFT : 7.5m
Page 36
- (02 - 02) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
DIMENSIONS2.
MODEL : AOG18LF
(Unit : mm)
INSTALLATION PLACE
(Unit : mm)
If the space is larger that is stated, the condition will be the same as that are no obstacles.
600 or more
100 or more
200 or more
100 or more
250 or more
(Service space)
Pitch of bolts for installation
353
45.4
320
395
540
125
Drain port Ø20
20
790
620
20
62
290
Page 37
- (02 - 03) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG24LF
(Unit : mm)
INSTALLATION PLACE
600 mm or more
100 mm or more
600 mm or more
300 mm
or more
100 mm or more
300 mm or more
(Service space)
300 mm or more
300 mm or more
300 mm or more
When there are obstacles at the back or front sides.
When there are obstacles at the back, side(s), and top.
When there are obstacles at the back, side with the installation of more than one unit.
Air flow
Top view
Front view
Side view
Bottom view
Page 38
- (02 - 04) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG30LF
(Unit : mm)
INSTALLATION PLACE
600 mm or more
100 mm or more
600 mm or more
300 mm
or more
100 mm or more
250 mm or more
(Service space)
250 mm or more
250 mm or more
300 mm or more
When there are obstacles at the back or front sides.
When there are obstacles at the back, side(s), and top.
When there are obstacles at the back, side with the installation of more than one unit.
Air flow
900
650
830
370
99
196
21
9
77
31 330
400
170
147
12
Top view
Front view
Side view
Bottom view
Page 39
- (02 - 05) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
REFRIGERANT CIRCUIT3.
MODEL : AOG18LF
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 1/2" (12.7 mm)
Page 40
- (02 - 06) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG24LF
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Sub-accumulator
Compressor
Cooling Heating
Muffler
Muffler
Pressure switch
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 5/8" (15.88 mm)
Page 41
- (02 - 07) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG30LF
3-Way valve (Small)
3-Way valve (Large)
Strainer
Strainer
Muffler
Pressure switch
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Sub-accumulator
Compressor
Cooling Heating
Refrigerant pipe diameter Liquid : 3/8" (9.52 mm) Gas : 5/8" (15.88 mm)
Page 42
- (02 - 08) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
WIRING DIAGRAMS4.
MODEL : AOG18LF
Page 43
- (02 - 09) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG24LF
Page 44
- (02 - 10) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG30LF
Page 45
- (02 - 11) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
MODEL : AOG18LF
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5 10 15 20 25
Height difference H
(m)
Û
1
Indoor unit is upper
than outdoor unit.
20 - - - 0.901 0.879
10 - 0.989 0.927 0.901 0.879
5 1.000 0.989 0.927 0.901 0.879
0 1.000 0.989 0.927 0.901 0.879
Û
2
Indoor unit is under
than outdoor unit
-5 0.995 0.984 0.922 0.896 0. 874
-10 - 0.979 0. 917 0.892 0.869
-20 - - - 0.876 0.853
COOLING
Pipe length (m)
5 10 15 20 25
Height difference H
(m)
Û
1
Indoor unit is upper
than outdoor unit.
20 - - - 0.869 0.867
10 - 0.973 0.911 0.885 0.883
5 0.992 0.981 0.919 0.893 0.891
0 1.000 0.989 0.927 0.901 0.899
Û
2
Indoor unit is under
than outdoor unit
-5 1.000 0.989 0.927 0.901 0.899
-10 - 0.989 0.927 0.901 0.899
-20 - - - 0.901 0.899
Page 46
- (02 - 12) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG24LF
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5 7. 5 10 15 20 25 30
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
20 - - - - 0.954 0.932 0.908
10 - - 0.998 0.975 0.954 0.932 0.908
7. 5 - 1.000 0.998 0.975 0.954 0.932 0.908
5 0.989 1.000 0.998 0.975 0.954 0.932 0.908
0 0.989 1.000 0.998 0.975 0.954 0.932 0.908
Û
2
Indoor unit is
under than
outdoor unit
-5 0.984 0.995 0.993 0.970 0.950 0.927 0.903
-7. 5 - 0.993 0.991 0.968 0.947 0.925 0.901
-10 - - 0.988 0.965 0.945 0.923 0.899
-20 - - - - 0.935 0.914 0.890
COOLING
Pipe length (m)
5 7. 5 10 15 20 25 30
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
20 - - - - 0.952 0.951 0.951
10 - - 0.980 0.966 0.968 0.967 0.966
7. 5 - 0.988 0.984 0.970 0.972 0.971 0.970
5 0.995 0.992 0.988 0 .974 0.976 0.975 0. 974
0 1.003 1.000 0.996 0.982 0.983 0.983 0.982
Û
2
Indoor unit is
under than
outdoor unit
-5 1.0 03 1.000 0.996 0.982 0.983 0.983 0.982
-7. 5 - 1.000 0.996 0.982 0.983 0.983 0.982
-10 - - 0.996 0.982 0.983 0.983 0.982
-20 - - - - 0.983 0.983 0.982
Page 47
- (02 - 13) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG30LF
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5 7. 5 10 20 30 40 50
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
30 - - - - 0.816 0.756 0.686
20 - - - 0.872 0.816 0.756 0.686
10 - - 0.991 0.872 0.816 0.756 0.686
7. 5 - 1.000 0.991 0.872 0.816 0.756 0.686
5 0.986 1.000 0.991 0.872 0.816 0.756 0.686
0 0.986 1.000 0.991 0.872 0.816 0.756 0.686
Û
2
Indoor unit is
under than
outdoor unit
-5 0.981 0.995 0.986 0.868 0. 812 0.752 0.683
-7. 5 - 0.993 0.983 0.866 0.810 0.750 0.681
-10 - - 0.981 0.864 0.808 0 .748 0.679
-20 - - - 0.855 0.799 0.74 0 0.672
-30 - - - - 0.791 0.733 0.665
COOLING
Pipe length (m)
5 7. 5 10 20 30 40 50
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
30 - - - - 0.932 0.929 0.924
20 - - - 0.945 0.947 0.945 0.940
10 - - 0.984 0.9 61 0.963 0.960 0.956
7. 5 - 0.988 0.988 0.965 0.967 0.964 0.959
5 0.990 0.992 0.992 0.968 0.971 0.968 0.963
0 0.998 1.000 1.000 0.976 0.979 0.976 0. 971
Û
2
Indoor unit is
under than
outdoor unit
-5 0.998 1.000 1.000 0.976 0.979 0.976 0. 971
-7. 5 - 1.000 1.000 0.976 0.979 0.976 0.971
-10 - - 1.000 0.976 0.979 0.976 0.971
-20 - - - 0.976 0.979 0.976 0.971
-30 - - - - 0.979 0.976 0.971
Page 48
- (02 - 14) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
ADDITIONAL CHARGE CALCULATION6.
MODEL : AOG18LF
Refrigerant charge
z
MODEL : AOG24LF
Refrigerant charge
z
MODEL : AOG30LF
Refrigerant charge
z
Refrigerant type R410A
Refrigerant amount g 1200
Total pipe length m 15 or less 20 25(MAX)
20g/m
Additional charge g 0 100 200
Refrigerant type R410A
Refrigerant amount g 1650
Total pipe length m 15 or less 20 25 30(MAX)
20g/m
Additional charge g 0 100 200 300
Refrigerant type R410A
Refrigerant amount g 2100
Total pipe length m 20 or less 30 40 50(MAX)
40g/m
Additional charge g 0 400 800 1200
Page 49
- (02 - 15) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
AIR FLOW7.
MODEL : AOG18LF
Cooling
z
Heating
z
MODEL : AOG24LF
Cooling
z
Heating
z
Number of
rotations
(r.p.m.)
Air ow
920
2150 m
3
/h
597 l/s
1265 CFM
Number of
rotations
(r.p.m.)
Air ow
870
2070 m
3
/h
575 l/s
1218 CFM
Number of
rotations
(r.p.m.)
Air ow
1050
2470 m
3
/h
686 l/s
145 4 CFM
Number of
rotations
(r.p.m.)
Air ow
110 0
2570 m
3
/h
714 l/s
1512 CFM
Page 50
- (02 - 16) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG30LF
Cooling
z
Heating
z
Number of
rotations
(r.p.m.)
Air ow
850
3600 m
3
/h
1000 l/s
2119 CFM
Number of
rotations
(r.p.m.)
Air ow
850
3600 m
3
/h
1000 l/s
2119 CFM
Page 51
- (02 - 17) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL : AOG18LF
Cooling
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
MODEL : AOG24LF
Cooling
z
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 52
- (02 - 18) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
MODEL : AOG30LF
Cooling
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd sound p ressur e level, dB:(0 dB= 0.0002µbar)
Octave ba nd cente r freque ncy,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,00 0 2,0 00 4,00 0 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Page 53
- (02 - 19) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
SOUND LEVEL CHECK POINT8-2.
Page 54
- (02 - 20) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
ELECTRIC CHARACTERISTICS9.
Model name AOG18LF AOG24LF AOG30LF
Power supply
Voltage V 230V ~ Frequency Hz 50
*1) Max operating current A
12.5 18.5
19.0
Starting Current A 7. 6 9.7 10.9
*2) Wiring spec.
Main Fuse (Circuit breaker) Current
A
20
30
Power Cable mm
2
3.5-4.0
3.5-4.5
*3) Limited wiring length m 20
*1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring Spec. Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*3) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Page 55
- (02 - 21) -
OUTDOOR UNIT
AO
G18-30LF
OUTDOOR UNIT
AO
G18-30LF
SAFETY DEVICES10.
Protection form
Model
AOG18LF AOG24LF AOG30LF
Circuit protection
Current fuse (NEAR THE TERMINAL)
20A 250V 20A 250V 20A 250V
5A 250V 10A 250V 5A 250V
Current fuse (MAIN PRINTED CIRCUIT BOARD)
15A 250V
3.15A 250V
15A 250V
3.15A 250V 3.15A 250V
Fan motor protection
Thermal protection program
OFF : 100±10°C
ON : 95±10°C
OFF : 100±10°C
ON : 95±10°C
OFF : 130±20°C
ON : 100±20°C
Compressor protection
Thermal protection program (COMPRESSOR TEMP.)
OFF : 110°C
ON : After 40
minutes
OFF : 108°C
ON : After 40
minutes
Thermal protection program (DISCHARGE TEMP.)
OFF:110 °C
ON: After 7 minutes
OFF:110 °C
ON: After 7 minutes
OFF:110 °C
ON: After 7 minutes
High Pressure Protection
Pressure Switch
OFF : 4.2±0.1MPa ON : 3.2±0.15MPa
OFF : 4.2±0.1MPa
ON : 3.2±0.15MPa