Fujitsu AS*G18LFCA, AO*G18LFC Service Instruction

Page 1
SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
INVERTER
INSTRUCTION
Models Indoor unit Outdoor unit
AS*G18LFCA
type
AO*G18LFC
R410A
Page 2
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION................................................................................................
2. HEATING OPERATION.................................................................................................
3. DRY OPERATION.........................................................................................................
4. AUTO CHANGEOVER OPERATION............................................................................
5. INDOOR FAN CONTROL..............................................................................................
6. OUTDOOR FAN CONTROL..........................................................................................
7. LOUVER CONTROL.....................................................................................................
8. COMPRESSOR CONTROL..........................................................................................
9. TIMER OPERATION CONTROL...................................................................................
10. ELECTRONIC EXPANSION VALVE CONTROL........................................................
11. TEST OPERATION CONTROL...................................................................................
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST ).................................
13. FOUR-WAY VALVE EXTENSION SELECT................................................................
14. AUTO RESTART.........................................................................................................
15. MANUAL AUTO OPERATION ( Indoor unit body operation ).....................................
16. FORCED COOLING OPERATION..............................................................................
17. COMPRESSOR PREHEATING..................................................................................
18. 10°C HEAT OPERATION............................................................................................ 01-14
01-01 01-02 01-02 01-03 01-04 01-06 01-07 01-08 01-09 01-12 01-12 01-12 01-12 01-13 01-13 01-13 01-14
19. ECONOMY OPERATION............................................................................................
20.
DEFROST OPERATION CONTROL...........................................................................
21. OFF DEFROST OPERATION CONTROL...................................................................
22. VARIOUS PROTECTIONS.......................................................................................... 01-18
2. TROUBLE SHOOTING
2-1 ERROR DISPLAY.......................................................................................................
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY.....................
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION)....................................
2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE.....................................................
2-4 SERVICE PARTS INFORMATION.............................................................................. 02-28
3. APPENDING DATA
3-1 FUNCTION SETTING.................................................................................................
3-1-1 INDOOR UNIT....................................................................................................
01-14 01-15 01-17
02-01 02-01 02-02 02-03 02-23
03-01 03-01
3-1-2 Procedures to change the Function Setting for wireless RC..............................
3-2 Outdoor unit Pressure Value and Total Electric Current Curve................................... 03-05
3-3 Thermistor Resistance Values.....................................................................................
3-3-1 INDOOR UNIT....................................................................................................
3-3-2 OUTDOOR UNIT................................................................................................
03-03
03-07 03-07 03-07
Page 3
WALL MOUNTED type
R410A
INVERTER
1 . DESCRIPTION OF EACH CONTROL OPERATION
Page 4
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 2°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be stopped.
* When the room temperature is between +2°C to -2.5°C of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Fig.1 based on the fan speed mode and the outdoor temperature.
( Table 1 : Compressor Frequency Range )
minimum frequency
maximum frequency
maximum frequency
AO*G18LFC 18rps 70rps 113rps
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside air Outside air temperature temperature
A zone 113rps B zone C zone D zone E zone F zone
113rps 95rps 58rps 58rps 58rps
34°C
30°C
19°C
10°C
0°C
A zone
B zone
C zone
D zone
E zone
36°C
32°C
21°C
12°C
2°C
18LFC
Hi Me Lo Quiet
66rps 66rps 66rps 45rps 45rps 45rps
54rps 54rps 54rps 30rps 30rps 30rps
34rps 34rps 34rps 24rps 24rps 24rps
F zone
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
01-01
Page 5
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 3°C than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be stopped. * When the room temperature is between +2.5°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
( Table 2 : Compressor Frequency Range )
minimum frequency
AO*G18LFC 18rps 130rps
* The room temperature is controlled 2°C higher than the setting temperature for 60 minutes after starting the operation. After 60 minutes, it is controlled based on the normal setting temperature.
maximum frequency
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 3. However, after the compressor is driven, the indoor unit shall run at operation frequency of 58rps, for a minute.
( Table 3 : Compressor frequency )
Operating frequency
18LFC
X zone J zone Y zone
34rps 20rps
0rps
( Fig.2 : Compressor Control based on Room Temperature )
Room Room temperature temperature
Ts+1.5°C
Ts+0.5°C
Ts -1.5°C
X zone
Ts -0.5°C
J zone
Y zone
01-02
Page 6
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
Operation flow chart
START
Room temp.
>Ts+2°C ?
NO
YES
YES
or operation command other than
Room temp.
<Ts- 2°C ?
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
auto changeover operation?
NO
YES
NO
YES
TS : Setting temperature
in OFF state for 6 minutes or
or operation command other than
auto changeover operation?
COOLING OPERATION
Thermostat remains
longer?
NO
System stops
YES
YES
NO
NO
01-03
Page 7
5. INDOOR FAN CONTROL
1. Fan speed
( Table 4 : Indoor Fan Speed )
AS*G18LFCA
Operation mode Air flow mode Speed (rpm) Heating
Cooling
Dry
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs. When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
Hi Me+ Me Lo
Quiet
Cool air prevention
S-Lo Hi Me Lo
Quiet
1220 1120 1020
900 710 660
270 1220 1020
900
710
X zone: 710
J zone: 660
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 3. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH,as shown in Table 4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
°C
=
=
TR-Ts > 2 °C
2
°C > TR-Ts > 1 °C
=
1
°C > TR-Ts
HIGH mode
=
TR-Ts > 2.5
°C > TR-Ts > 1.5 °C
2.5
MED mode
1.5
°C > TR-Ts
LOW mode
When the room temperature drops
When the room temperature rises
TR : Room temperature Ts : Setting temperature
4. DRY OPERATION
Refer to the Table 4. During the dry mode operation, the fan speed setting can not be changed.
01-04
Page 8
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Fig.4.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 4.
( Fig.4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > - 1 °C
°C > TR-Ts > - 2 °C
- 1
°C > TR-Ts
- 2
TR : Room temperature Ts : Setting temperature
When the room temperature rises
=
=
LOW mode
MED mode
MED+ mode
When the room temperature drops
TR-Ts > - 1.5 °C
=
°C > TR-Ts > - 2.5 °C
- 1.5
- 2.5
°C > TR-Ts
=
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Fig.5, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
(Fig.5 : Cool Air Prevention Control)
Indoor heat exchanger temperature
42°C
39°C
37°C
30°C
Hi
Me+
Lo
Cool air prevention
S-Lo
Indoor heat exchanger temperature
37°C
34°C
32°C
28°C
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.6.
8. INDOOR UNIT FAN (ONTROL FOR ENERGY SAVING (Cooling mode)
It depends on the function setting "Indoor unit fan control for energy saving" at cooling mode, and the indoor fan motor will run as shown in Fig 6.
( Fig.6 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 5)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
( Table 5 : Indoor fan speed )
(SEC)
Dry
X zone J zone
AS*G18LFCA 710rpm 660rpm
Y zone
Cooling
0 270rpm 710rpm
01-05
Page 9
6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table 6 : Type of Motor )
AC Motor DC Motor
AO*G18LFC
2. Fan Speed
( Table 7 : Outdoor fan speed )
ZONE
AO*G18LFC 1050/ 920/ 870/ 720/ 530
Y Z F G
Cooling Dry Heating
870/ 530/ 300
300
250/ 200
530 300
250/ 200
1100/ 870/ 780/ 720/ 590/ 480
Refer to Fig.7.
( Fig.7 : Outside air temperature zone selection )
Outside air temperature
21°C
12°C
C
The outdoor fan speed mentioned avobe depends on the compressor frequency.
*
Y zone
Z zone
F zone
G zone
Outside air temperature
19°C
10°C
C
(When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequescy decreases, the outdoor fan speed also changes to the lower speed.)
(rpm)
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
*
as table 8 without relating to the compressor frequency.
( Table 8 : Outdoor fan speed after the defrost )
Min
AO*G18LFC
1100rpm
01-06
Page 10
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow:
Types of Airflow Direction Setting:
,,,,,
: During Heating/ Cooling/ Dry modes
The Remote Controller's display does not change.
1 2
3
4
5
6
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
During Cooling / Dry mode : Horizontal flow During Heating mode : Downward flow
During AUTO mode operation, for the first a few minutes after beginning operation, airflow will be horizontal ; the air direction cannot be adjusted during this period.
Direction Only the direction of the Airflow Direction Louver changes; the direction of the Power Diffuser does not change. The airflow direction setting will temporarily become when the temperature of
the airflow is low at the start of the Heating mode. After beginning of AUTO/HEAT mode operated and automatic defrosting operation time,
the air flow will be horizontal . However, the Airflow Direction cannot be adjusted at beginning AUTO operation mode.
2. HORIZONTAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follows.
Cooling / Heating / Dry mode / Fan mode
1
3
2
5
4
The Remote Controller's display does not change.
3. SWING OPERATION
To select Vertical Airflow Swing Operation
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
Cooling mode / Dry mode / Fan mode( ) : Heating mode / Fan mode( ) :
4
6
1 3
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted and it stops at either upper end or bottom end.
To select Horizontal Airflow Swing Operation
When the swing signal is received from the remote controller, the horizontal louver starts to swing.
(Swinging Range)
All mode :
1
5
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted and it stops at either upper end or bottom end.
To select Vertical and Horizontal Airflow Swing Operation
When the horizontal swing signal is input from remote control, the combination of the vertical and horizontal swing operation is performed.
1
4
36
01-07
Page 11
8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the table 9.
(Table 9 : Compressor Operation Frequency Range)
Cooling Heating
Min Max Min Max Min Max
AO*G18LFC
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the fig.8.
18rps 113rps 18rps 130rps 20rps 34rps
(Fig.8 : Compressor Control at Start-up)
Frequency
Frequency
Frequency Frequency
Frequency Frequency
Time
Time Time Time
Time
Dry
Time
(Frequency)
AO*G18LFC
(Time)
AO*G18LFC
Frequency
40rps 59rps 72rps 85rps 101rps 110rps
Time Time
120sec 180sec 220sec 270sec 350sec 410sec
Frequency
Frequency Frequency
Time Time Time Time
Frequency
Frequency
01-08
Page 12
9. TIMER OPEARTION CONTROL
9-1 WIRELESS REMOTE CONTROLLER
The table 10 shows the available timer setting based on the product model.
(Table 10 : Timer Setting)
ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER
AS*G18LFCA
1. OPEARTION FREQUENCY RANGE
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Stop mode
Set time
Operation mode
Stop mode
Set time Set time Set time
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
Stop mode
01-09
Page 13
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Set temperature rises
( Ts : Set temperature )
+2°C +1°C
Ts
Stop of operation
Set
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not changed and the operation stops at the time of timer setting.
Set temperature lowers
( Ts : Set temperature )
Ts
- 1°C
- 2°C
- 3°C
- 4°C
Set
30min
60min
30min
Stop of operation
30min
01-10
Page 14
9-2 WIRED REMOTE CONTROLLER (OPTION)
The table11 shows the available timer setting based on the product model.
( Table11 : Timer Setting )
ON TIMER / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
AS*G18LFCA
1. ON TIMER / OFF TIMER
Same to 9-1 1.ON TIMER / OFF TIMER and shown in those.
2. WEEKLY TIMER
This timer function can set operation times of the each day of the week. All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
ON OFF ON OFF ON OFF
Setting day Setting day Setting day
Set time Set time
3. TEMPERATURE SET BACK TIMER
This timer function can change setting temperature of setting operation times of the each day of the week. This can be together with other timer setting.
Set back tmp.
Normal tmp.
ON
Set time Set time
OFF
01-11
Page 15
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 60 to 480 pulses.
The expansion valve is set at 480 pulses after 110 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).
11. TEST OPERATION CONTROL
[ Wireless remote controller ]
Under the condition where the air conditioner runs, press the test run button of the remote control, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
[ Wired remote controller (Option) ]
If the operation lamp is on, press the Start/Stop button to turn it off. Press the Master Control and Fan Control buttons at the same time for more than two seconds to start the test operation. The operation lamp will light up and "o1" will be displayed on the set temperature display.
[ Release ]
Perform the test operation for 60 minutes. Pressing the Start/Stop button will stop the test operation.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
13. FOUR-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 3 minutes later after the compressor stopped.
01-12
Page 16
14. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature Set air flow Timer mode and timer time Set air flow Direction Swing ECONOMY opeartion
15. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 12. If the remote control is lost or battery power dissipated, this function will work without the remote control.
(Table 12)
Manual auto operation OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous SETTING TEMP. 24°C SETTING LOUVER Standard SWING OFF
(No timer setting available)
16. FORCED COOLING OPERATION
If cooling operation is set, the operation is controlled as shown in Table13.
( Table13 )
Forced cooling operation OPERATION MODE FAN CONT. MODE TIMER MODE SETTING TEMP. SETTING LOUVER
SWING
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more. During the forced cooling operation, it operates regardless of room temperature sensor. Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON and 1 second OFF on both operation LED and timer LED (same as test operation). Forced cooling operation is released after 60 minutes of starting operation. The FORCED COOLING OPERATION will start as shown in Table13.
Cooling Hi
-
Room Temp is not controlled
Initial : Horizontal (It is changed follow as setting of remote controller)
OFF
01-13
Page 17
17. COMPRESSOR PREHEATING
When the outdoor heat exchanger temperature is lower than 5°C and the heating operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to 7°C or greater, preheating is ended.
( Fig.9 : Compressor Preheating )
OFF
7°C
5°C
ON
18. 10°C HEAT OPERATION
The 10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller. The 10°C HEAT operation is almost the same operation as below settings.
( Table14 )
Mode Heating Setting temperature 10°C Fan mode AUTO
19. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. The ECONOMY operation is almost the same operation as below settings.
( Table15 )
Mode Cooling/ Dry Heating Target temperature Setting temp.+1°C Setting temp.-1°C
01-14
Page 18
20. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects the temperature lower than the values shown in Table16.
( Table 16 : Condition of starting Defrost Operation )
Normal defrost
Tn10 : Temperature of continuous operation at 10minutes. Tnb : Back 5minutes temperature Ta : Outside air temperature
Integrating defrost (Constant monitoring)
*1 : If the compressor continuous operation time is less than 10 minutes and outdoor air temperature is less than 2°C once while operating the compressor, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
Compressor integrating operation time
Less than 25 min. More than 25min.
Does not operate
More than 240 min. (For long continuous operation)
- 3°C
Tn-Tn10< - 5deg, Tn < - 6°C Tn-Tnb < - 2deg, Tn < - 6°C Tn < - 17°C, Ta > - 10°C
=
Tn-Ta < - 7deg, Ta < - 10°C
=
Tn < - 20°C
=
Compressor integrating operation time
=
More than 213 min. (For long continuous operation)
= =
- 5°C
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table17.
Less than 10min.*1 (For intermittent operation)
OFF count of the compressor 40 times.
( Table17 : Defrost Release Condition )
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +16°C or Compressor operation time has passed 15 minutes.
01-15
Page 19
Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 10 minutes)
Tn-Tn10< -5deg Tn < -6°C
=
Tn-Tnb< -2deg Tn < -6°C
=
Tn < -17°C
=
Ta > -10°C
=
Normal defrost
Compressor integrating operation: Over 25 min.
Tn-Ta < -7deg
=
Ta < -10°C
Defrost start
Tn < -20°C
=
Integrating defrost
(Constant monitoring)
Compressor OFF count : 40 times (Less than 10min.)
Compressor integrating operation: Over 240 min.
Outdoor heat exchanger temperature: Below - 3°C
Compressor integrating operation: Over 213 min.
Outdoor heat exchanger temperature: Below - 5°C
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec O FF
Compressor OFF Outdoor fan motor OFF 50 sec later four - way valve OFF 55 sec later compressor ON
Outdoor heat exchanger temperature:
Over +16°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-16
Page 20
21. OFF DEFROST OPEARTION CONTROL
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
1. OFF DEFROST OPERATION CONDITION
In heating operation, the outdoor heat exchanger temperature is less than - 4°C, compressor continuous operation more than 10 minutes, and compressor operation integrating time lasts for more than 30 minutes.
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 16°C or Compressor operation time has passed 15 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature : Below - 4°C Compressor continuous operation : Over 10 minutes Compressor integrating operation : Over 30 minutes
Defrost start
Defrost Indicater: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 16°C or Compressor ON time: Over 15 minutes
Defrost end
01-17
Page 21
22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of the control of the compressor frequency is released.
When the discharge temperature becomes higher than Temperature , the compressor is stopped and the indoor unit LED starts blinking.
(Table 18 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Condition
Temperature
Temperature
104°C 101°C 110°C
AO*G18LFC
Ta' + 74°C Ta' + 71°C 110°C
Condition : - Cooling operation ­ Outdoor temperature Y, Z zone
or Outdoor temperaturee F, G zone and the compressor operation time is less than 20 minutes.
- Heating operation-
Temperature
Ta': Outdoor temperature
Condition : - Cooling operation ­ Outdoor temperaturee F, G zone and the compressor operation time is more than 20 minutes.
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit velue that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
(Table 19 : Current Release Operation Value / Release Value)
[ Heating ]
AO*G18LFC
OT (Control / Release)
7.0A/ 6.5A
17°C
9.0A/ 8.5A
12°C
10.5A/ 10.0A
5°C
12.0A/ 11.5A
OT : Outdoor Temperature
[ Cooling ]
AO*G18LFC
OT (Control / Release)
4.5A/ 4.0A
46°C
6.0A/ 5.5A
40°C
8.5A/ 8.0A
OT : Outdoor Temperature
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 20 : Anti-freezing Protection Operation / Release Temperature)
Outdoor temperature
Over than 10°C
*2
or 12°C *1
Less than 10°C *2
or 12°C
*1
Temperature Temperature
7°C
4°C
13°C
*1. When the temperature rises. *2. When the temperature drops.
01-18
Page 22
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C or greater, the compressor is stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
[ Control System ]
Indoor heat exchange temperature
Compressor is stopped
63°C
The compressor frequency is decreased 25rps every 120seconds.
55°C
The compressor frequency is decreased 4rps every 120seconds.
53°C
Stable zone
50°C
It returns to the normal operation
01-19
Page 23
WALL MOUNTED type
R410A
INVERTER
2 . TROUBLE SHOOTING
Page 24
2. TROUBLESHOOTING
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
Please refer the flashing pattern as follows. The OPERATION,TIMER,ECONOMY lamps operate as follows according to the error contents.
Error Contents
Serial Communication Error Wired Remote Controller
Communication Error Indoor Unit Model Information Error
EEPROM Access Abnormal Manual Auto Switch Error
Indoor Room Thermistor Error
Indoor Heat Ex. Thermistor Error
Indoor Unit Fan Motor Error
Outdoor Unit Main PCB Error
PFC Circuit Error
IPM Error
OPERATION (Green)
3 times
3 times
4 times
6 times
Indoor Unit Display
TIMER (Orange)
5 times
1 times
2 times6 times
4 times
5 times6 times
ECONOMY (Green)
Continuous1 times1 times
Continuous2 times1 times
Continuous2 times
Continuous
Continuous
Continuous4 times 2 times
Continuous1 times5 times
Continuous
Continuous
Continuous
Wired Remote Controller Display
11
12
32
35
41
42
51
62
64
65
Trouble shooting
1
2
3
4
5
6
7
8
9
10
Discharge Thermistor Error Heat Ex. Liquid Outlet
Thermistor Error Outdoor Thermistor Error
Current Sensor Error
Over Current Error
Compressor Control Error
Outdoor Unit Fan Motor Error
4 Way Valve Error
Discharge Temp. Error
7 times
7 times 3 times
7 times 4 times
9 times
9 times
9 times 9 times
1 times
4 times9 times
5 times
7 times
1 times10 times
Continuous
Continuous
Continuous
Continuous8 times 4 times
Continuous
Continuous
Continuous
Continuous
Continuous
71
73
74
84
94
95
97
99
A1
11
12
13
14
15
16
17
18
19
02-01
Page 25
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION)
1. SELF - DIAGNOSIS
When " Er " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel.
Unit number (usually 0)
Error code
SUMOTU WETH FR SA
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
Error code
Error history number
SU MO TU WETH FR SA
3. Press the SET TEMPERATURE button to select the error history number.
Lower
01234567
FEdcbA98
Raise
ı
ı
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
02-02
Page 26
2-2 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1-1
Indicate or Display:
OUTDOOR UNIT Error Method:
Serial Communication Error
Refer to error code table.
(Serial Reverse Transfer Error)
Detective Actuators:
Outdoor unit Main PCB Outdoor unit Fan motor
Detective details:
When the indoor unit cannot receive the serial signal from Outdoor unit more than 2minutes after power ON, or the indoor unit cannot receive the serial signal more than 15seconds during normal operation.
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB failure 4. Outdoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
NO
Check Point 1-2: Check external cause such as noise
Check the complete insulation of the grounding. Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V (AC220V -10%) - 264V (AC240V +10%) appears at Outdoor Unit Terminal L - N.
OK
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3. >> If it is abnormal, Check Outdoor unit fan motor. (PARTS INFORMATION 5) >> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB. >> If Outdoor fan motor is normal, replace Main PCB.
GREEN WHITE BLACK RED WHITE BLACK
N L 3 2
+
-
1
02-03
Page 27
Trouble shooting 1-2
INDOOR UNIT Error Method:
Serial Communication Error (Serial Forward Transfer Error)
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Indoor unit Fan motor
Detective details:
When the outdoor unit cannot receive the serial signal from Indoor unit more than 10seconds.
Forecast of Cause:
1. Connection failure 2. External cause 3. Controller PCB failure 4. Indoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
OK
NO
Check Point 1-2: Check external cause such as noise
Check the complete insulation of the grounding. Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V (AC220V -10%) - 264V (AC240V +10%) appears at Outdoor Unit Terminal L - N.
OK
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Forward Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 2 - 3. >> If it is abnormal, replace Controller PCB. >> If it is abnormal, Check Indoor unit fan motor. (PARTS INFORMATION 4) >> If Indoor unit fan motor is abnormal, replace Indoor unit fan motor and Controller PCB.
GREEN WHITE BLACK RED WHITE BLACK
N L 3
+
­2 1
02-04
Page 28
Trouble shooting 2 INDOOR UNIT Error Method:
Wired Remote Controller Communication Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Wired Remote Control
Detective details:
When the indoor unit cannot receive the signal from Wired Remote Control more than 1minute during normal operation.
Forecast of Cause:
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit, and check if there is a disconnection of the cable.
OKOK
Check Point 2 : Check Remote Control and Controller PCB
Check Voltage at CN6 (terminal 1-3). (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Upon correcting the removed connector or mis-wiring, reset the power.
02-05
Page 29
Trouble shooting 3
INDOOR UNIT Error Method:
Indoor Unit Model Information Error EEPROM Access Abnormal
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB
Detective details:
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
Forecast of Cause:
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Indoor unit electric components
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
NO
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 3 : Replace Controller PCB
Change Controller PCB.
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
02-06
Page 30
Trouble shooting 4 INDOOR UNIT Error Method:
INDOOR UNIT
Manual Auto Switch Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Indicator PCB
Detective details:
When the Manual Auto Switch becomes ON for consecutive 60 or more seconds.
Manual auto switch
Forecast of Cause :
1. Manual auto switch failure 2.Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual auto switch
Check if Manual auto switch is kept pressed. Check ON/OFF switching operation by using a meter.
>>If Manual Auto Switch is disabled (on/off switching), replace it.
OKOK
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB and Indicator PCB.
02-07
Page 31
Trouble shooting 5 INDOOR UNIT Error Method:
INDOOR UNIT
Indoor Room Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB
Detective details:
When Room Temperature Thermistor open or short-circuit is detected.
Room Temperature Thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
25°C 20°C15°C10°C5°C0°C-5°C-10°C
10.012.515.820.225.933.644.058.2Resistance Value (k )
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
40°C
5.36.58.0Resistance Value (k )
45°C35°C30°C
4.4
OK
Check Point 3 : Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK BLACK
THERMISTOR (ROOM TEMP.)
If the voltage does not appear, replace Controller PCB.
212
1
CN1
02-08
Page 32
Trouble shooting 6 INDOOR UNIT Error Method:
INDOOR UNIT
Indoor Heat Ex. Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB
Detective details:
When Heat Ex. Temperature Thermistor open or short-circuit is detected.
Heat Ex. temperature thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
20°C10°C5°C0°C-5°C-10°C-20°C-30°C
62.9103.3134.2176.0233.2312.3579. 1131.9Resistance Value (k )
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
50°C
17.125.639.6Resistance Value (k )
60°C
11.6
63°C40°C30°C
10.4
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR
3 2 1
(PIPE)
3 2 1
WHITE RED
212
1
CN3
BLACK BLACK
If the voltage does not appear, replace Controller PCB.
02-09
Page 33
Trouble shooting 7
INDOOR UNIT Error Method:
Indoor Unit Fan Motor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Indoor unit fan motor
Detective details:
When the condition that actual frequency of Indoor Fan is below 1/3 of target frequency is continued more than 56 seconds.
Forecast of Cause:
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
OK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
02-10
Page 34
Trouble shooting 8
OUTDOOR UNIT Error Method:
Outdoor Unit Main PCB Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Detective details:
Access to EEPROM failed due to some cause after outdoor unit started.
Forecast of Cause:
1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YESYES
Check Point 2 : Replace Main PCB
Change Main PCB.
NO
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
02-11
Page 35
Trouble shooting 9 OUTDOOR UNIT Error Method:
INDOOR UNIT
PFC Circuit Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When inverter output DC voltage is higher than 415V for over 3 seconds, the compressor stops. If the same operation is repeated 5 times, the compressor stops permanently.
Forecast of Cause :
1. External cause 2. Connector connection failure 3. Main PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit. Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit. Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
02-12
Page 36
Trouble shooting 10
OUTDOOR UNIT Error Method:
IPM Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Compressor
Detective details:
When more than normal operating current to IPM in Main PCB flows, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Compressor failure 5. Main PCB failure
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose. Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
OK
Check Point 3 : Check Outdoor Fan
Check Outdoor Fan Motor. (Refer to Trouble shooting 17)
>> If the Fan Motor is failure, replace it.
OKOK
Check Point 4 : Check Compressor
Check Compressor.
(PARTS INFORMATION 2)
OKOK
Check Point 5 : Replace Main PCB
If Check Point 1 4 do not improve the symptom, change Main PCB.
02-13
Page 37
Trouble shooting 11 OUTDOOR UNIT Error Method:
INDOOR UNIT
Discharge Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Discharge pipe temperature thermistor
Detective details:
When Discharge pipe temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
5°C0°C-5°C-10°C-20°C-30°C
20°C10°C
62.5100.9129.8168.6221.1292.9531.61013.1Resistance Value (k )
30°C
40.0
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
40°C
26.3
50°C
17.8
60°C
12.3
90°C80°C70°C
100°C
110°C
2.6
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK
BLACK BROWN BROWN
BLACK
BLACK
1
1
2
2
CN71
3
3
4
4
1
1
2
2
CN70
3
3
120°C
2.03.44.66.38.7Resistance Value (k )
If the voltage does not appear, replace Main PCB.
02-14
Page 38
Trouble shooting 12 OUTDOOR UNIT Error Method:
Heat Ex. Liquid Outlet Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Heat exchanger temperature thermistor
Detective details:
When Heat exchanger temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
-30°C
95.6
-20°C
50.3
-5°C-10°C
30°C20°C10°C5°C0°C
6.09.612.416.121.027.8Resistance Value (k )
3.8
Temperature
50°C40°C
80°C70°C60°C
0.60.81.21.72.5Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK
BLACK BROWN BROWN
BLACK
BLACK
1
1
2
2
CN71
3
3
4
4
1
1
2
2
CN70
3
3
If the voltage does not appear, replace Main PCB.
02-15
Page 39
Trouble shooting 13 OUTDOOR UNIT Error Method:
Outdoor Thermistor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Outdoor temperature thermistor
Detective details:
When Outdoor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
-30°C
224.3
-25°C
159.7
-15°C-20°C
10°C5°C0°C-5°C-10°C
26.935.246.662.384.2115.2Resistance Value (k )
20.7
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
20°C15°C
35°C
6.48.010.012.616.1Resistance Value (k )
40°C
5.2
45°C
4.2
50°C
3.5
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR (PIPE)
THERMISTOR (DISCHARGE)
THERMISTOR (OUTDOOR)
BLACK
BLACK BROWN BROWN
BLACK
BLACK
1
1
2
2
CN71
3
3
4
4
1
1
2
2
CN70
3
3
55°C30°C25°C
2.8
If the voltage does not appear, replace Main PCB.
02-16
Page 40
Trouble shooting 14
OUTDOOR UNIT Error Method:
Current Sensor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When Input Current Sensor has detected 0A, while Inverter Compressor is operating at higher than 56rps, after 1minute upon starting the Compressor. (Except during the defrost operation)
Forecast of Cause :
1. Defective connection of electric components 2. External cause 3. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
NO
YES
Check Point 2 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose. Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
02-17
Page 41
Trouble shooting 15
OUTDOOR UNIT Error Method: Over Current Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Compressor
Forecast of Cause :
1. Outdoor unit fan operation defective, foreign matter on hear exchanger,
Detective details:
"Protection stop by overcurrent generation after inverter compressor start processing completed'' generated consecutively 10 times. * The number of generations is reset if the start-up of the compressor succeeds.
excessive rise of ambient temperature
2. Inverter PCB failure
3. Inverter compressor failure (lock, winding short)
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
No obstructions in air passages? Heat exchange fins clogged Outdoor unit fan motor check Ambient temperature not raised by the effect of other heat sources? Discharged air not sucked in?
OKOK
Check Point 2: Replace Main PCB
If Check Point 1 do not improve the symptom, change Main PCB.
OKOK
Check Point 3: Replace Compressor
If Check Point 2 do not improve the symptom, change Compressor.
02-18
Page 42
Trouble shooting 16
OUTDOOR UNIT Error Method: Compressor Control Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Compressor
Detective details:
If the detected rotor location is out of phase with actual rotor location more than 105°(at start-up) and 120°(in operation), the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 2 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection. Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3: Replace Main PCB
If Check Point 1,2 do not improve the symptom, change Main PCB.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
02-19
Page 43
Trouble shooting 17
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Motor Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Outdoor unit fan motor
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated 3 times in a row, compressor and fan motor stops. If and repeats 5 times in a row, compressor and fan motor stops permanently.
Forecast of Cause:
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Outdoor unit fan motor
Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>>If Outdoor unit fan motor is abnormal, replace Outdoor unit fan motor.
OK
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
RED
1 2 3
CN800
If the voltage is not correct, replace Main PCB.
4 5 6 7
BLACK WHITE YELLOW BROWN
FAN MOTOR
FM
Read wire DC voltage
Red - Black
White - Black
240 - 400V
15 1.5V
02-20
Page 44
Trouble shooting 18 INDOOR UNIT Error Method:
4-Way Valve Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Heat Ex. temperature thermistor Room temperature thermistor 4-way valve
Detective details:
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops.
Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 20degC
Heating operation [Indoor heat exchanger temp.] - [room temp.] < - 20degC
If the same operation is repeated 5 times, the compressor stops permanently.
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Check each thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 5, 6), If defective, replace the thermistor
OKOK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN30 from PCB and check the resistance value of coil. Resistance value is 1.22k 1.49k (at 20°C).
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature, and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
OKOK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
02-21
Page 45
Trouble shooting 19 OUTDOOR UNIT Error Method:
INDOOR UNIT
Discharge Temp. Error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Outdoor unit Main PCB Discharge temperature thermistor
Forecast of Cause :
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
<Cooling operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV (EEV2, indoor unit EEV) open? Strainer clogging check (before and after EEV, ACM
oil return) Refer to "Service Parts Information 3".
"Protection stop by "discharge temperature 110degC during compressor operation"" generated 2 times within 24 hours.
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV (EEV1, EEV2) open? Strainer clogging check (before and after EEV, ACM
oil return) Refer to "Service Parts Information 3".
OK
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger Check if fan can be rotated by hand. Motor check (PARTS INFORMATION 5)
OK
Check Point 4 : Check the discharge thermistor
Discharger thermistor characteristics check. (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 11".
OK
Check Point 5 : Check the refrigerant amount
Leak check
OK
02-22
Page 46
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Trouble shooting 20
Forecast of Cause:
1. Power Supply failure 2. External cause
Indoor Unit - No Power
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
YESYES
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
02-23
Page 47
Trouble shooting 21
Outdoor Unit - No Power
Forecast of Cause:
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit. Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
YESYES
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
OK
If the symptom does not change by above Check 3, replace Main PCB.
02-24
Page 48
Trouble shooting 22
Forecast of Cause:
1. Setting/ Connection failure 2. External cause
No Operation (Power is ON)
3. Electrical Component defective
Check Point 1 : Check indoor and outdoor installation condition
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection. Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
OK
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit. Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components at Indoor and Outdoor
Check Voltage at CN6 (terminal 1-3). (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again)
>> Check Indoor unit fan motor. (PARTS INFORMATION 4)
If it is normal, replace Controller PCB.
If it is abnormal, replace Indoor unit fan motor and Controller PCB.
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
02-25
Page 49
Trouble shooting 23
No Cooling / No Heating
Forecast of Cause:
1. Indoor Unit error 2. Outdoor Unit error
3. Effect by Surrounding environment
4. Connection Pipe / Connection Wire failure 5. Refrigeration cycle failure
Check Point 1 : Check Indoor Unit
Does Indoor Unit FAN run on HIGH FAN?
Is Air Filter dirty? Is Heat Exchanger clogged?
Check if Energy save function is operated.
OKOK
Check Point 2 : Check Outdoor Unit Operation
Check if Outdoor Unit is operating Check any objects that obstruct the air flow route. Check clogged Heat Exchanger.
Is the Valve open?
OKOK
Check Point 3 : Check Site Condition
Is capacity of Indoor Unit fitted to Room size? Any windows open? Or direct sunlight ?
OKOK
Check Point 4 : Check Indoor/ Outdoor Installation Condition
Check connection pipe (specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
OKOK
MPa MPa
Check Point 5 : Check Refrigeration Cycle
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3) Check Compressor (PARTS INFORMATION 1,2)
Attention
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
02-26
Page 50
Trouble shooting 24
Forecast of Cause :
1. Abnormal installation (Indoor/ Outdoor)
Abnormal Noise
2. Fan failure (Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit. (Check and correct followings)
Abnormal noise is coming from Outdoor Unit. (Check and correct followings)
Is Main Unit installed in stable condition? Is the installation of Air suction grille and front panel normal?
OK
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Trouble shooting 25
Forecast of Cause:
Water Leaking
Is Main Unit installed in stable condition? Is Fan Guard installed normally?
OK
Is Fan broken or deformed? Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
OK
Check if vibration noise by loose bolt or contact noise of piping is happening.
OK
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water leak occurs
Is Main Unit installed in stable condition?
Is Main Unit broken or deformed at the time of
transportation or maintenance?
OKOK
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
OKOK
Is Fan rotating?
Diagnosis method when water is spitting out.
Is the filter clogged?
OKOK
Check Gas Pressure and correct it if there was a gas leak.
MPa MPa
02-27
Page 51
2-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 1
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check Main PCB, connection of
Compressor, and winding resistance.
(Refer to the next page).
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas Pipe Valve open? (Low Pressure is too low)
MPa MPa
Check if Refrigerant is leaking. (Recharge Refrigerant)
Abnormal noise
Check if vibration noise by loose bolt or contact noise of piping is happening.
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Replace Compressor
Check if Strainer is clogged. (PARTS INFORMATION 3)
Check Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.)
02-28
Replace Compressor
Page 52
SERVICE PARTS INFORMATION 2
Inverter Compressor
Check Point 1 : Check Connection
Check terminal connection of Compressor
(loose or incorrect wiring)
Terminal cover opened
S(W)
(WHITE)
C(T)
(BLACK)
R
(RED)
Check Point 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
C
Resistance Value :
0.477 at 25°C
R
S
Check Point 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
02-29
Page 53
SERVICE PARTS INFORMATION 3
Outdoor unit Electronic Expansion Valve ( EEV )
Check Point 1 : Check Connections
Check connection of connector (CN40) ( Loose connector or open cable )
EXPANSION VALVE COIL
EV
CN40
1 2 3 4 5
RED BLUE ORANGE YELLOW WHITE
Check Point 2 : Check Coil of EEV
Remove connector, check each winding resistance of Coil.
Read wire
Resistance value White - Red Yellow - Red Orange - Red
46 4
at 20°C
Blue - Red
Check Point 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
If Resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed, it has a temp. difference between Inlet and Outlet.
CLOSE Example : Hot Gas
Pipe (In)
If it is open, it has no temp. difference between Inlet and Outlet.
OPEN Example : Hot Gas
Hi TEMP.
DC
Pipe (In)
Hi TEMP.
Pipe (Out)
Normal TEMP.
Pipe (Out)
Hi TEMP.
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In) Pipe (Out)
02-30
Pipe (In) Pipe (Out)
Page 54
SERVICE PARTS INFORMATION 4
Indoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Indoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
Pin number (wire color)
1 (Blue) 2 (Yellow) 3 (White) 4 (Black) 5 6 (Red)
Terminal function (symbol)
Feed back (FG) Speed command (Vsp) Control voltage (Vcc) Earth terminal (GND) No function DC voltage (Vm)
SERVICE PARTS INFORMATION 5
Outdoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Outdoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number (wire color)
1 (Red) 2 3 4 (Black) 5 (White) 6 (Yellow) 7 (Brown)
Terminal function (symbol)
DC voltage (Vm) No function No function Earth terminal (GND) Control voltage (Vcc) Speed command (Vsp) Feed back (FG)
02-31
Page 55
WALL MOUNTED type
R410A
INVERTER
3 . APPENDING DATA
Page 56
3-1. FUNCTION SETTING
3-1-1 INDOOR UNIT
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
1-1. Setting the Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the filter sign to be displayed, select the setting value for "No indication".
( Factory setting)
Setting Description Standard (400 hours) Long interval (1000 hours) Short interval ( 200 hours) No indication
1-2. Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
Setting Description Standard Slightly lower control Lower control Warmer control
Function Number Setting Value
11
( Factory setting)
Function Number Setting Value
30
00 01 02 03
00 01 02 03
1-3. Setting the Heater Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
( Factory setting)
Setting Description Standard Lower control Slightly warmer control Warmer control
Function Number Setting Value
31
03-01
00 01 02 03
Page 57
1-4. Setting the Auto Restart
Enable or disable automatic system restart after a power outage.
( Factory setting)
Setting Description
Yes No
Function Number Setting Value
00
40
01
1-5. Setting the Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
( Factory setting)
Setting Description
No Yes
* If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor. * If setting value is "01" : Room temperature is controlled by either indoor unit temperature sensor or
remote controller unit sensor.
Function Number Setting Value
00
42
01
1-6. Setting the Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
( Factory setting)
Setting Description
A B C D
Function Number Setting Value
00
44
01 02 03
1-7. Setting the External input control
"Operation/Stop" mode or "Forced stop" mode can be elected.
( Factory setting)
Setting Description
Operation/Stop mode (Setting forbidden) Forced stop mode
Function Number Setting Value
00
46
01 02
1-8. Indoor unit fan control for energy saving (Only cooling mode)
Enable or disable indoor unit fan control when the outdoor unit is stopped.
( Factory setting)
Setting Description
Function Number Setting Value No Yes
* If setting value is "00" : When the outdoor unit is stopped, the indoor unit fan operates following the setting on the remote controller continuously.
* If setting value is "01" : When the outdoor unit is stopped, the indoor unit fan operates at very low speed intermittently.
49
03-02
00 01
Page 58
3-1-2 Procedures to change the Function Setting for wireless RC
This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the "FUNCTION SETTING" according to the installation conditions using the remote controller.
Settings will not be changed if invalid numbers or setting values are selected.
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP.( ) simultaneously, press the RESET button to enter the function setting mode.
Selecting the Function Number and Setting Value
10°C HEAT
(1) Press the MODE button, and proceed to Fanction Number and Setting Value. (There is no necessity for setting remote control signal code. Because signal code is setting by Fanction Number and Setting Value.)
(2) Press the SET TEMP. ( ) ( ) buttons to select the Function Number. (Press the MODE button to switch between the left and right digits.)
(3) Press the FAN button to proceed to Setting Value. (Press the FAN button again to return to the Function Number selection.)
(4) Press the SET TEMP. ( ) ( ) buttons to select the Setting Value. (Press the MODE button to switch between the left and right digits.)
(5) Press the TIMER MODE button. It makes a signal to indoor unit. (Indoor unit recognize the setting.)
(6) Press the START/STOP button. It makes a signal to indoor unit. (Indoor unit run the setting.)
Function Number
1 0
° C
H E
A T
10°C HEAT
Setting Value
10°C HEAT
(7) Press the RESET button to cancel the function setting mode. (8) After completing the FUNCTION SETTING, be sure to turn of the
power and turn it on again.
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The FUNCTION SETTING doesn't become effective if it doesn't do so.
03-03
10°C HEAT
Page 59
Custom code setting for remote controller
(1) Press the MODE button for more then 5 seconds.
(2) Press the SET TEMP. ( ) ( ) buttons to change the signal code between . Match the code on the display to the air conditioner signal code. (initially set to )
(3) Press the MODE button. (Return to normal display)
CAUTION
If you change the setting of Fanction Number and Setting Value after setting custom code in remote controller, please set custom code in remote controller again. The remote control unit resets to signal code A when the batteries in the remote control unit are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes ( ) until you find the code which operates the air conditioner.
03-04
Page 60
ethod
3-2. Outdoor unit Pressure Value and Total Electric Current Curve
Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AS*G18LFCA
[Condition] Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
Standard amount
amount
Piping
5.0m (Height difference 1m)
length
Power
50Hz - 230V
voltage
Operation
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
condition
Measuring
m
Caution
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*G18LFCA
1.3
1.2
1.1
RH70% RH60% RH50%
1.0
0.9
0.8
Low-pressure of outdoor unit [MPa
0.7 16 18 20 22 24 26 28 30 32
In/Outdoor ambient temperature [ C]
[50Hz-230V]
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*G18LFCA
7.0
6.5
6.0
5.5
5.0
4.5
4.0
Outdoor total electric current [A]
3.5
3.0
16 18 20 22 24 26 28 30 32
RH70% RH60% RH50%
In/Outdoor ambient temperature [ C]
[50Hz-230V]
03-05
Page 61
Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
e
diti
Model Name : AS*G18LFCA
[Condition] Ambient
temperatur
Refrigerant
amount
Piping 5.0m (Height difference 1m)
length
Power
voltage
Operation
con
Measuring
method
Indoor 15, 20, 23 °C / Outdoor 2, 7, 12 °C Standard amount
50Hz - 230V
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
on
outdoor unit overall current with the current clamp meter at Power Cable.
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*G18LFCA
23 C
3.1
2.9
2.7
2.5
2.3
High-pressure of outdoor unit [MPa]
2.1 02468101214
Indoor ambient
20 C
temperature[ C]
15 C
Outdoor ambient temperature [ C]
[50Hz-230V]
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*G18LFCA
23 C
Indoor ambient
8.0
7.6
7.2
6.8
6.4
Outdoor total electric current [A]
6.0
20 C
temperature[ C]
15 C
02468101214
Outdoor ambient temperature [ C]
[50Hz-230V]
03-06
Page 62
3-3. Thermistor Resistance Values
3-3-1 INDOOR UNIT
Room temperature thermistor
Temp (°C) Temp (°C)
Resistance(k )
Voltage(V)
-10.0 58.2 0.73
Indoor heat exchanger thermistor
Resistance(k )
-30.0 1131.9 0.21
-5.0 44.0 0.93 -25.0 804.5 0.29
0.0 33.6 1.15 -20.0 579.6 0.40
5.0 25.9 1.39 -15.0 422.9 0.53
10.0 20.2 1.66 -10.0 312.3 0.69
15.0 15.8 1.94 -5.0 233.2 0.88
20.0 12.5 2.22 0.0 176.0 1.10
25.0 10.0 2.50 5.0 134.2 1.36
30.0 8.0 2.77 10.0 103.3 1.63
35.0 6.5 3.03 15.0 80.3 1.92
40.0 5.3 3.27 20.0 62.9 2.21
45.0 4.4 3.49 25.0 49.7 2.51
30.0 39.6 2.79
35.0 31.7 3.06
40.0 25.6 3.30
45.0 20.8 3.53
50.0 17.1 3.73
55.0 14.1 3.90
60.0 11.6 4.05
63.0 10.4 4.14
3-3-2 OUTDOOR UNIT
Voltage(V)
Discharge thermistor
Temp (°C) Temp (°C) Temp (°C)
Resistance(k )
Voltage(V)
-30.0 1013.1 0.06
-25.0 729.1 0.09
-20.0 531.6 0.12
-15.0 392.3 0.16
-10.0 292.9 0.21
-5.0 221.1 0.28
0.0 168.6 0.36
5.0 129.8 0.46
10.0 100.9 0.57
15.0 79.1 0.71
20.0 62.5 0.86
25.0 49.8 1.03
30.0 40.0 1.23
35.0 32.4 1.43
40.0 26.3 1.65
45.0 21.6 1.88
50.0 17.8 2.11
55.0 14.8 2.34
60.0 12.3 2.57
65.0 10.3 2.79
70.0 8.7 3.00
75.0 7.4 3.19
80.0 6.3 3.37
Outdoor heat exchanger thermistor
Resistance(k )
Voltage(V)
-30.0 95.6 0.24
-25.0 68.9 0.32
-20.0 50.3 0.43
-15.0 37.2 0.57
-10.0 27.8 0.73
-5.0 21.0 0.92
0.0 16.1 1.14
5.0 12.4 1.39
10.0 9.6 1.65
15.0 7.6 1.93
20.0 6.0 2.21
25.0 4.8 2.49
30.0 3.8 2.77
35.0 3.1 3.02
40.0 2.5 3.26
45.0 2.1 3.48
50.0 1.7 3.68
55.0 1.4 3.85
60.0 1.2 4.00
65.0 1.0 4.13
70.0 0.8 4.25
75.0 0.7 4.35
80.0 0.6 4.43
Outdoor temperature thermistor
-30.0 224.3 0.73
-25.0 159.7 0.97
-20.0 115.2 1.25
-15.0 84.2 1.56
-10.0 62.3 1.90
-5.0 46.6 2.26
0.0 35.2 2.61
5.0 26.9 2.94
10.0 20.7 3.25
15.0 16.1 3.52
20.0 12.6 3.76
25.0 10.0 3.97
30.0 8.0 4.14
35.0 6.4 4.28
40.0 5.2 4.41
45.0 4.2 4.51
50.0 3.5 4.59
55.0 2.8 4.65
85.0 5.4 3.54
90.0 4.6 3.69
95.0 4.0 3.83
100.0 3.4 3.96
105.0 3.0 4.07
110.0 2.6 4.17
115.0 2.3 4.26
120.0 2.0 4.33
Resistance(k )
Voltage(V)
03-07
Page 63
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
Sep. 2011 Printed in Japan
Loading...