Steps
Swing: Cooling , Dry and Fan mode
Swing: Heating and Fan mode
Up and Down Swing
1
2
5
4
3
7 steps selectable
6
7
M O D E L
G18 LV
CEILING TYPE
AB
ABG18LVTB / AOG18LALL
FEATUR ES
Energy saving
z
High energy saving was realized by making the indoor unit and outdoor unit fan motor and
compressor all DC and optimal design of the refrigerant cycle. Class A was achieved in European
energy classications.
Flexible installation
z
Example for oor installation Example for ceiling installation
G18 LV
CEILING TYPE
AB
Easy installation
z
Main work settings can be done easily from the remote controller at installation
Main work settings
High ceiling setting ●
Auto restart ●
Temperature adjustment when cooling / heating ●
Double auto swing
z
A combination of right/left and up/down directional swing allows 3-dimensional air direction control
- (01 - 01) -
Page 5
G18 LV
10
°C
20
°C
“10°C HEAT”
Button ON
Indoor unit
operation START
CEILING TYPE
AB
10°C HEAT Operation
z
*Only available with Wireless RC.
G18 LV
CEILING TYPE
AB
The room temperature can be set to go no lower than 10°C,
thus ensuring that the room does not get too cold when not occupied
Caution)
• When the room temperature is higher than 10°C, “10°C HEAT” operation does not star t. Operation starts and maintains the room
temperature at 10°C when the temperature drops below 10°C.
• When “10°C HEAT” operation stops, the room set temperature quickly returns to the preset temperature.
Economy operation
z
The power consumption can be reduced.
Powerful mode ...Standard
Soft mode ...Performs operation which reduces the power consumption
- (01 - 02) -
Page 6
WIRELESS REMOTE CONTROLLER2.
ABCD
AB
C
D
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
60min.
1 °C
2 °C
Timer setting
1 °C
30min.
60min.
90min.
2 °C
3 °C
4 °C
Timer setting
FEATUR ES
G18 LV
CEILING TYPE
AB
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are
¾
possible.
Four kinds of timers. Easy operation.
¾
Easy to change transmission code (4 patterns) by button operation.
¾
Built-in timers
z
Select from four different timer programs (ON / OFF / PROGRAM / SLEEP).
Program timer
z
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
z
The sleep timer function automatically corrects the temperature thermostat setting according to
the time setting to prevent excessive cooling and heating while sleeping.
G18 LV
CEILING TYPE
AB
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 1°C every hour. The set
temperature can rise up to a maximum of 2°C.
Simple function setting
z
Heating operation
When the sleep timer is set, the set temperature
automatically drops 1°C every 30 minutes. The set
temperature can drop to a maximum of 4°C.
Setting of the air conditioner selection function is performed by remote controller.
Switching remote controller signal code
z
Code selector switch eliminates unit
•
being wrongly switched.
(Up to 4 codes can be set.)
*I.U.=Indoor unit
- (01 - 03) -
Page 7
G18 LV
2
4
9
3
1
16
15
5
10
13
11
12
14
8
7
6
17
18
19
21
24
23
22
20
CEILING TYPE
AB
FUNCTIONS
MODE button1
Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT).
/Start / end R.C. signal code change. (Max 4 types)
G18 LV
CEILING TYPE
AB
10°C2 HEAT button
SET TEMP. button ( ▲ / ▼ )3
Sets the indoor temp./ Sets R.C. signal code.
ECONOMY button4
SLEEP button5
Pressed to select sleep timer.
FAN button6
Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).
START/STOP button7
Pressed to start and stop operation.
SET button (Vertical)8
Air ow direction vertical set button.
SET button (Horizontal)9
Air ow direction horizontal set button.
SWING button10
Air ow direction swing button.
TIMER MODE button11
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)
TIMER SET ( 12 / ) button
Sets the current time and on-off time.
CLOCK ADJUST button13
Sets the current time.
RESET button14
Used when replacing batteries.
TEST RUN button15
Used when testing the air conditioner after installation.
Display panel
Signal transmitter16
Temperature set display17
Operating mode display18
Sleep display19
Transmit indicator20
Fan speed display21
Swing display22
Timer mode display23
Clock display24
SPECIFICATION
Note: Functions will be different due to type of indoor unit.
For details, please see operation manual.
SIZE (H × W × D mm)170 × 56 × 19
WEIGHT (g)85 (w/o batteries)
ACCESSORYHolder
- (01 - 04) -
Page 8
SPECIFICATIONS3.
G18 LV
CEILING TYPE
AB
Type
Model name
Power source230V
Available voltage range198 - 264V
Speci catio ns are bas ed on the fol lowing c onditi ons.
Coolin g : Indoor t emperat ure of 27˚C DB / 19˚CWB.a nd outdo or temper ature of 35˚C DB / 24˚CWB.
Heatin g : Indoor te mperat ure of 20˚CD B / 15˚CWB.and o utdoor te mperat ure of 7˚CD B / 6˚CWB.
Pipe leng th : 7.5 m, Height di ffere nce : 0 m. (Out door unit - I ndoor un it)
The max imum cur rent is the m aximum va lue when o perated w ithin th e operat ion range (t emperat ure)
The prote ctive fu nction m ight wor k when usin g outsid e the oper ation ra nge.
Octave band sound pressure level, dB:(0 dB= 0.00 02µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0 dB= 0.00 02µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
G18 LV
CEILING TYPE
AB
0
63 125 250 5 00 1,000 2 ,000 4, 000 8,000
Octave band center frequ ency,Hz
0
63 125 250 5 00 1,000 2 ,000 4, 000 8,000
Octave band center frequ ency,Hz
- (01 - 14) -
Page 18
G18 LV
Microphone
1m
Microphone
1 m
1 m
Microphone
CEN TER
Microphone
1 m
0.8 m
CEILING TYPE
AB
SOUND LEVEL CHECK POINT8-2.
Floor console
z
Under ceiling
z
G18 LV
CEILING TYPE
AB
- (01 - 15) -
Page 19
ELECTRIC CHARACTERISTICS9.
G18 LV
CEILING TYPE
AB
Model nameAB¾G18LV
G18 LV
CEILING TYPE
AB
VoltageV230 ~
Power supply
FrequencyHz50
Max. operating currentA0.45
Connection cablemm
2
1.5
*1) Wiring Spec.
Limited wiring lengthm26
*1) Wiring Spec.
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
- (01 - 16) -
Page 20
SAFETY DEVICES10.
G18 LV
CEILING TYPE
AB
Protection form
Model
G18 LV
CEILING TYPE
AB
AB¾G18LV
Circuit protectionCurrent fuse (PCB)250V 3.15A
Fan motor protection
Thermal protection
program
138 ± 15 °C OFF
115 ± 15 °C ON
- (01 - 17) -
Page 21
EXTERNAL INPUT & OUTPUT11.
Indoor
control PC boardConnected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m.
*10 m
Contact capacity : 24VDC or more, 10mA or more.
Please use the non-polar relays and switches.
Operation
Stop
ON
OFF
Input signal
Indoor unit
Remote controller
OnOnOn
Input signal
On
Off
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control
operation invalidity
G18 LV
CEILING TYPE
AB
ConnectorINPUTOUTPUTREMARKS
CN102Control input—
CN103—Operation status output
See external
input/output settings for
details.
G18 LV
CEILING TYPE
AB
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operationInitial starting after turned power onOther than initial starting
Operation modeAuto changeoverMode at previous operation
Set temperature24°CTemperature at previous operation
Air ow modeAUTOMode at previous operation
Up-down air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Left-right air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Circuit diagram example
z
When function setting is "Operation/Stop" mode ●
When function setting is "Forced stop" mode ●
Model name
UT Y-XWZ X
Parts (Optional)
z
Wire (External input)
- (01 - 18) -
Page 22
G18 LV
Field supply
Ex.)Display
Indoor
control PC board
Connected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Max.24VDC, 10mA to less than 1A.
*10 m
24V DC
ON
OFF
Operation
Stop
Indoor unit
Output signal
CEILING TYPE
AB
OPERATION STATUS OUTPUT
EXTERNAL OUTPUT11-2.
G18 LV
CEILING TYPE
AB
An air conditioner operation status signal can be output.
Circuit diagram example
z
Parts (Optional)
z
Wire (External output)
Model name
UT Y-XWZ X
- (01 - 19) -
Page 23
FUNCTION SETTING12.
JM3
JM2
JM1
1
OFF
234
G18 LV
CEILING TYPE
AB
INDOOR UNIT12-1.
INDOOR UNIT
G18 LV
CEILING TYPE
AB
1
2
DIP SW
indoor unit address setting
3
4
JM1
Jumper Wire
Setting forbiddenJM2
JM3
SWITCH POSITION
MAIN PCB
Indoor unit Printed circuit board
DIP-SW SETTING
Indoor unit address setting
z
A number of indoor units can be operated at the same time using a wired remote controller.
Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board.
(See the following table.)
The DIP switches are normally set to make the unit number 00.
The function settings of the control of the indoor unit can be changed by this procedure according •
G18 LV
CEILING TYPE
AB
to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation •
conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. •
Settings will not be changed if invalid numbers or setting values are selected. •
PREPARATION
Turn on the power. •
* By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have
been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP. (
•
setting mode.
STEP 1
Setting the Remote controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note
that the air conditioner cannot receive a signal code if the air conditioner has not
been set for the signal code.) The signal codes that are set through this process are
applicable only to the signals in the FUNCTION SETTING. For details on how to set
the signal codes through the normal process, refer to SELECTING THE REMOTE
CONTROLLER SIGNAL CODE.
Press the SET TEMP. (1.
→
→ Match the code on the display to the air conditioner signal code. (initially
set to
(If the signal code does not need to be selected, press the MODE button and
proceed to STEP 2.)
Press the TIMER MODE button and check that the indoor unit can receive signals 2.
at the displayed signal code.
Press the MODE button to accept the signal code, and proceed to STEP 2.3.
)
) ( ) button to change the signal code between →
) simultaneously, press the RESET button to enter the function
The air conditioner signal code is set to A prior to shipment.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a
signal code other than signal code A, reset the signal code after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes (
nd the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
Press the SET TEMP. (1.
number.
(Press the MODE button to switch between the left and right
digits.)
Press the FAN button to proceed to setting the value. 2.
Press the FAN button again to return to the function number
selection.)
Press the SET TEMP. (3.
(Press the MODE button to switch between the left and right
digits.)
Press the TIMER MODE button, and START/STOP button, in the 4.
order listed to conrm the settings.
Press the RESET button to cancel the function setting mode.5.
After completing the FUNCTION SETTING, be sure to turn off 6.
the power and turn it on again.
After turning off the power, wait 10 seconds or more before turning on it again.
The FUNCTION SETTING doesn’t become effective if it doesn’t do so.
) ( ) buttons to select the function
) ( ) buttons to select the setting value.
CAUTION
→ → → ) until you
- (01 - 21) -
Page 25
G18 LV
CEILING TYPE
AB
CONTENTS OF FUNCTION SETTING
G18 LV
CEILING TYPE
AB
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in •
accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value. •
Settings will not be changed if invalid numbers or setting values are selected. •
1-1Filter sign
1-2Ceiling height
1-3Cooler room temperature correction
1-4Heater room temperature correction
1-5Auto restart
1-6Indoor room temperature sensor switching function
1-7Remote controller signal code
1-8External input control
1-1. Filter sign
The indoor unit has a sign to inform the user that it is time to clean the lter. Select the time setting
for the lter sign display interval in the table below according to the amount of dust or debris in the
room. If you do not wish the lter sign to be displayed, select the setting value for "No indication".
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
"Standard
(400 hours)"
"Long interval
(1,000 hours)"
"Short interval
(200 hours)"
No indication03
11
00
01
02
1-2. Ceiling height
Select the setting values in the table below according to the height of the ceiling.
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
Standard
High ceiling01
20
00
1-3. Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
Standard
Lower control01
Lower control02
Warmer control03
30
00
When using oor console installation, change the setting value to "1".
- (01 - 22) -
Page 26
G18 LV
CEILING TYPE
AB
1-4. Heater room temperature correction
G18 LV
CEILING TYPE
AB
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
Standard
Lower control01
Slightly warmer control02
Warmer control03
31
00
When using oor console installation, change the setting value to "1".
1-5. Auto restart
The following settings are also possible, depending on the operating conditions.
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
Yes
No01
40
00
1-6. Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature
sensor.
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
No
Yes 01
42
00
If setting value is “00”,
•
room temperature is controlled by the indoor unit temperature sensor.
If setting value is “01”,
•
room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
1-7. Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
A
B01
C02
D03
44
00
1-8. External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(. . .Factory setting)
Setting DescriptionFunction NumberSetting Value
Operation/Stop mode
(Setting forbidden)01
Forced stop mode02
46
00
- (01 - 23) -
Page 27
G18 LV
CEILING TYPE
AB
REMOTE CONTROLLER SIGNAL CODE SETTING
Use the following steps to select the signal code of the remote controller.
(Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
1. Press the START/STOP button until only the clock is displayed on the remote controller display.
2. Press the MODE button for at least ve seconds to display the current signal code (initially set to
3. Press the SET TEMP. (
Match the code on the display to the air conditioner signal code.
4. Press the MODE button again to return to the clock display. The signal code will be changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original clock
display. In this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment. Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a
signal code other than signal code A, reset the signal code after replacing the batteries.
If you do not know the air conditioner signal code setting,try each of the signal codes (
nd the code which operates the air conditioner.
) ( ) button to change the signal code between → → → .
→ → → .) until you
).
G18 LV
CEILING TYPE
AB
- (01 - 24) -
Page 28
OPTIONAL PARTS13.
G18 LV
CEILING TYPE
AB
ExteriorParts nameModel No.Summary
Wired remote
controller
External
connect kit
UTY-RNN¾M
UTY-XWZX
Unit control is performed by
wired remote controller
Use to connect with various
peripheral devices and air
conditioner PC board.
TypeINVERTER HEAT PUMP
Model nameAOG12L ALLAOG14L ALLAOG18L ALL
Power sourse230V ~ 50Hz
Available voltage range198 - 264V ~ 50Hz
Starting currentA5.16.17.4
Airow rate
Fan
G12-18LA
OUTDOOR UNIT
AO
Sound pressure level
Type × Q'tyPropeller × 1
Motor outputW54
Cooling
Heating1630174 01910
Cooling
Heating484950
3
m
/h
dB (A)
Dimensions
Heat exchanger type
(H × W × D)
Fin pitch1.30
Rows × Stages2 × 26
mm
Pipe typeCopper
Fin TypeAluminium
Compressor
Refrigerant
Type × Q'tyTwin Rotary × 1
Motor outputW110 0
TypeR410A
Chargeg115 0 1250
Refrigerant oilTy pePOE
Enclosure
Dimensions
(H × W × D)
Weight
Connenction pipe
Net
Gross648 × 910 × 380
Net
Gross44 (97)
Size
MethodFlare
Pre-charge length
Max. length25
MaterialSteel sheet
ColourBeige (10YR7.5 / 1.0NN)
mm
kg
Liquid
GasØ9.52 (Ø3/8 in.)Ø12.70 (Ø1/2 in.)
mm
m
Max. height difference15
Operation range
Cooling
Heating-15 to 24
°C
178019102000
474950
546 × 876 × 18.2
546 × 842 × 18.2
578 × 790 ×300
40 (88)
Ø6.35 (Ø1/4 in.)
15
-10 to 46
G12-18LA
OUTDOOR UNIT
AO
Note :
Specications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB / 24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB / 6 °CWB.
Pipe length : 7.5 m, Height dif ferenc e : 0 m. (Outdoor unit - Indoor unit)
The maximum current is the maximum value when the operated within the operation range (temperature).
The protective function might work when using it outside the operation range.
- (02 - 01) -
Page 32
DIMENSIONS2.
600 mm
or more
100 mm
or more
600 mm or more
300 mm
or more
100 mm
or more
300 mm or more
(Service space)
300 mm
or more
300 mm
or more
300 mm
or more
Air flow
Top view
Front view
Side view
Bottom view
MODEL : AOG12LA, AOG14LA, AOG18LA
(Unit : mm)
G12-18LA
OUTDOOR UNIT
AO
G12-18LA
OUTDOOR UNIT
AO
INSTALLATION PLACE
When there are obstacles at
the back or front sides.
When there are obstacles at
the back, side(s), and top.
When there are obstacles at the
back, side with the installation of
more than one unit.