Fujitsu AS*G09KXCA Series, AO*G12KXCA Series, AS*G12KXCA Series, AO*G09KXCA Series Service Instruction

SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
type
Models Indoor unit Outdoor unit
AS*G09KXCA AS*G12KXCA
AO*G09KXCA AO*G12KXCA
SERVICE
INSTRUCTION
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION................................................................................................
3. DRY OPERATION.........................................................................................................
2. HEATING OPERATION.................................................................................................
5. INDOOR FAN CONTROL..............................................................................................
4. AUTO CHANGEOVER OPERATION............................................................................
7. LOUVER CONTROL.....................................................................................................
6. OUTDOOR FAN CONTROL..........................................................................................
10. TIMER OPERATION CONTROL.................................................................................
9. COMPRESSOR CONTROL..........................................................................................
12. TEST OPERATION CONTROL...................................................................................
11. ELECTRONIC EXPANSION VALVE CONTROL........................................................
14. FOUR-WAY VALVE EXTENSION SELECT................................................................
13. PREVENT TO RESTART (ST)...................................................................................
16. FORCED AUTO OPERATION....................................................................................
15. AUTO RESTART.........................................................................................................
17. FORCED COOLING OPERATION.............................................................................
19. 10°C HEAT OPERATION............................................................................................
18. COMPRESSOR PREHEATING..................................................................................
20. ECONOMY OPERATION............................................................................................
22. OFF DEFROST OPERATION CONTROL...................................................................
21.
DEFROST OPERATION CONTROL...........................................................................
01-01 01-02 01-02 01-03 01-05 01-07 01-08
01-10 01-11 01-13 01-13
01-14 01-14 01-14 01-14 01-15 01-15 01-15 01-16 01-18
01-13
2. TROUBLE SHOOTING
2-1 INDOOR UNIT ERROR DISPLAY...............................................................................
2-2 WIRELESS LAN ADAPTER ERROR DISPLAY..........................................................
2-3 MOBILE APP ERROR DISPLAY.................................................................................
02-01 02-02 02-03
2-4 MOBILE APP ERROR DISPLAY (In Wireless LAN Control system)........................... 02-04
23. VARIOUS PROTECTIONS.......................................................................................... 01-19
24. LOW NOISE OPERATION...........................................................................................01-21
26. POWERFUL OPERATION...........................................................................................
25. HUMAN SENSOR (Energy Saving).............................................................................
01-22
27. FILTER CLEAN............................................................................................................
01-22
01-21
8. DUAL FAN CONTROL.................................................................................................. 01-09
28. PLASMA CLEAN .........................................................................................................
01-22
29. WIRELESS LAN .........................................................................................................
01-23
2-5 TROUBLE SHOOTING WITH ERROR CODE.............................................................02-05
2-6 TROUBLE SHOOTING WITH NO ERROR CODE.......................................................
02-38
2-7 SERVICE PARTS INFORMATION..............................................................................
02-43
CONTENTS
3. APPENDING DATA
3-1 FUNCTION SETTING.................................................................................................
03-01
3-2 CUSTOM CODE SETTING FOR WIRELESS REMOTE CONTROLLER.................. 03-05
3-3 SWITCHING THE TEMPERATURE UNIT OF REMOTECONTROLLER.................. 03-06
4. WIRING DIAGRAMS....................................................................................................... 03-07
3. FUNCTION SETTING......................................................................................................
03-01
1 . DESCRIPTION OF EACH
CONTROL OPERATION
WALL MOUNTED type
INVERTER
( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 6.0°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
minimum frequency
maximum frequency
15rps 63rps
Outside air Outside air temperature drops temperature rises
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi Me Lo Quiet
( Table 1 : Compressor Frequency Range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +6.0°C to -1.0°C of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Figure1 based on the fan speed mode and the outdoor temperature.
* If the room temperature is 1.0°C lower than a set temperature, the compressor will be stopped.
A zone 63rps 32rps 26rps 17rps B zone 63rps 32rps 26rps 17rps C zone 52rps 32rps 26rps 17rps D zone 39rps 26rps 22rps 17rps E zone 39rps 26rps 17rps 15rps F zone 39rps 26rps 17rps 15rps
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 6.0°C than a set temperature, the compressor operation frequency will attain to maximum performance. * If the room temperature is 1.0°C higher than a set temperature, the compressor will be stopped. * When the room temperature is between +1.0°C to -6.0°C of the setting temperature, the compressor frequency is controlled within the range shown in Table2.
( Table 2 : Compressor Frequency Range )
01-02
minimum frequency
maximum frequency
15rps 128rps
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table3.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table3 : Compressor frequency )
( Fig.2 : Compressor Control based on Room Temperature )
Operating frequency
J zone Y zone
X zone 22rps
15rps
0rps
Room temperature drops
Room temperature rises
X zone
J zone
Y zone
4. AUTO CHANGEOVER OPERATION
01-03
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum mode from among the Heating, Cooling, and Monitoring mode. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1.0°C steps.
When operation starts, indoor main fan and outdoor fan are operated for around 1 minutes. Room temperature and outdoor temperature are sensed, and the operation mode is selected in accordance with the table below. <Monitoring mode>
( Table 4 : Operation mode selection table )
Room temperature (TR)
TR> Ts+2°C
Ts+2°C TR Ts -2°C
*Middle zone
TR < Ts -2°C Heating
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the Cooling or Heating mode was selected at above, operation is switched to Monitoring and the operation mode is selected again.
When the middle zone is selected on the predetermining of the operation mode, the operation mode before the changing to the monitor mode is selected.
1
2
3
1
( Fig.3 : Outdoor temperature zone selection )
Cooling
Operation mode
Temperature
25
°C and over
25
°C under
Heating
Cooling
Mode
*If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling and Heating mode, indoor unit will be operated according to the outdoor temperature as below.
TR : Room temperature Ts : Setting temperature
01-04
START
Room temp.
Ts+2
°C?
COOLING OPERATIONHEATING OPERATION
YES
Auto change over is
second or more?
NO
NO
YES
NO
NO
AUTO CHANGEOVER operation flow chart
TS : Setting temperature
Room temp.
Ts -2
°C?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
Middle zone
NO
NO
Operation mode of
outdoor unit : Cooling?
YES
NO
Operation mode of outdoor unit
: Heating?
YES
NO
YES
Outdoor temperature<
25°C?
NO
YES
YES
YES
NO
YES
YES
Operation mode
before the monitor mode is
cooling mode?
Monitor mode
(Fig.4 Flow chart)
5. INDOOR FAN CONTROL
The airflow setting by the remote controller can be switched in 5 steps such as AUTO, HIGH, MED, LOW, QUIET while the indoor main fan only runs.
When Fan mode is set at (Auto), it operates on (Me) Fan Speed.
01-05
1. Fan speed
2. FAN OPERATION
( Table5 : Indoor Fan Speed )
Operation mode Air flow mode
Speed (rpm)
Cooling/ Fan
Hi Me+ Me
Me
Lo Lo -
Lo
Quiet
Quiet
Dry
S-Lo
1570
Heating
Hi
Cool air prevention
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor main fan motor will run according to a room temperature, as shown in Fig. 6. On the other hand, if switched in [Hi] ~ [Quiet], the indoor main fan motor will run at a constant airflow of [COOL] operation modes Quiet -, Lo -, Me, Hi, as shown in Table5.
( Fig.6 : Airflow change - over ( Cooling : Auto ) )
TR : Room temperature Ts : Setting temperature
TR-Ts
1.5°C
0.5°C
2.5°C
1.5°C
Main Fan : Hi Dual Fan : Lo
4. DRY OPERATION
Refer to the Table5. During the dry mode operation, the fan speed setting can not be changed.
1490 1360 1300 1130 1130
980 830
610 1390 1310 1160 1100
960
1390
X zone : 960 J zone : 720
-
Main Fan
Air flow mode
Speed (rpm)
Hi Me
Lo Quiet
1290
Stop
1070
930 800 800 630 630 430
0
Dual Fan(Left Dual Fan)*
+
Lo
Cool air prevention
Quiet
+
TR-Ts
Main Fan : Lo Dual Fan : Quiet
Main Fan : Quiet Dual Fan : Quiet
Powerful
Powerful
Powerful
*Right Dual Fan is high +30rpm more than Left Dual Fan. (Resonance correspondence)
Lo - 1050
Quiet - 830
780Quiet -
Powerful
TR-Ts
1.5°C
0.5°C
2.5°C
1.5°C
Main Fan : Hi Dual Fan : Lo
TR-Ts
Main Fan : Lo Dual Fan : Quiet
Main Fan : Lo ­Dual Fan : Quiet
Dual Fan setting is ON Dual Fan setting is OFF
( Fig 5 : Dual Fan Speed )
The maximum value of the indoor main fan speed is set as shown in Fig.8, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
(Fig.8 : Cool Air Prevention Control)
01-06
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor main fan motor will run according to a room temperature, as shown in Fig. 7.
Switch the airflow at cooling mode, and the indoor main fan motor will run as shown in Fig.9. It depends on the Function setting "Indoor unit fan control for energy saving."
On the other hand, if switched in [Hi ] ~ [Quiet ], the indoor main fan motor will run at a constant airflow of [HEAT] operation modes Quiet -, Lo -, Me, Hi , as shown in Table5.
6. COOL AIR PREVENTION CONTROL (Heating mode)
7. INDOOR UNIT FAN CONTROL FOR ENERGY SAVING (Cooling mode)
( Fig.7 : Airflow change - over ( Heating : Auto ) )
42°C
30°C
34°C
Indoor heat exchanger temperature
Indoor heat exchanger
temperature *Hi or setting Fan mode
*Me+ or setting Fan mode
*Lo or setting Fan mode
Cool air prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
( Fig.9 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 6)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(SEC)
( Table6 : Indoor Fan Speed )
X zone J zone
960rpm 720rpm
780rpm
Dry
Cooling
[Normal operation] [Powerful operation]
Indoor heat exchanger temperature
Indoor heat exchanger temperature
42°C
30°C
34°C
Powerful
Hi
Lo
Cool air prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
*Lower speed is selected
TR : Room temperature Ts : Setting temperature
TR-Ts
- 1°C
- 2°C
- 2°C
- 3°C
Main Fan : Quiet Dual Fan : Quiet
TR-Ts
Main Fan : Me Dual Fan : Lo
Main Fan : Hi Dual Fan : Lo
TR-Ts
- 1°C
- 2°C
- 2°C
- 3°C
Main Fan : Lo Dual Fan : Lo
TR-Ts
Main Fan : Me Dual Fan : Lo
Main Fan : Hi Dual Fan : Lo
Dual Fan setting is ON Dual Fan setting is OFF
6. OUTDOOR FAN CONTROL
*
The outdoor fan speed mentioned above depends on the compressor frequency. (When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequency decreases, the outdoor fan speed also changes to the lower speed.)
*
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table 7 without relating to the compressor frequency.
( Table 7 : Outdoor fan speed after the defrost )
1. Fan Speed
1070rpm
01-07
( Fig.10 : Outside air temperature zone selection )
12°C
0°C
Outside air temperature
Outside air temperature
F zone
enoz 2-D
G zone
2°C
10°C
21°C
enoz 1-D
19°C
Cooling Heating
D-2
D-1
F
Zone
1070/ 930/ 760/ 660/ 610/ 580/ 510/ 410
Refer to Fig. 10
(rpm)
200/ 180
G 200/ 170
Dry
840/ 820/ 740/ 660/ 620/ 450
740/ 620/ 450
200/ 180 200/ 170
840/ 820/ 500/ 450/ 410
7. LOUVER CONTROL
01-08
1. VERTICAL LOUVER CONTROL
Each time the Vertical SET button is pressed, the air direction will change as follow:
At the biginning of AUTO or HEAT mode, they may stay on position 1 for a while for adjustment. If the angle is set to position 5 - 8 for more than 30 minutes in COOL or DRY mode, the louver will autmatically
return to position 4. (*Keeping the position 5 - 8 during COOL or DRY mode may cause of condensation water drops.) After beginning of AUTO / HEAT mode operated and automatic defrosting operation time,
the air flow will be position 1. The airflow direction setting will temporarily become 1 when the temperature of the airflow is low at the start of
HEAT mode. At the beginning of AUTO mode, the position you cannot change the airflow direction.
(Function Range)
3. SWING OPERATION
2. HORIZONTAL LOUVER CONTROL
(Function Range)
Each time the Vertical SET button is pressed, the air direction will change as follow:
At the beginning of AUTO mode, the position you cannot change the airflow direction.
Set the automatic swing operation, Each time the SWING Button is pressd, the operation will change.
The Left/ Right swing operation will follow the direction as shown above. The Up/ Down Swing operation range will differ by mode as follows.
Swing operation may stop temporarily when the indoor unit fan is rotating at very low speed or is stopped. In FAN mode, the UP/ Down swing operation range of 1 5 or 5 8 is decided according the airflow direction previously set before starting the swing operation
(Function Range)
Up/ Down Left/ Right Up/ Down/ Left/ Right Stop swing
COOL or DRY mode HEAT mode
Horizontal air flow direction louver
COOL, DRY, or FAN mode
HEAT or FAN mode
*: Default setting
*: Default setting
8. DUAL FAN CONTROL
In COOL mode
1. DUAL FAN COMFORT
01-09
In HEAT mode
Cold airflow
Delivers airflow with a comfortable temperature.
Side airflow reduces warm air from rising up, warming from the floor level.
Warm air
The 2 types of airflow(cold/warm air from the main fan, and ambient temperature air from the dual fan) provide comfort through the room. This is recommended for those who do not like ordinary COOL/HEAT modes.
2. Operation
Dual FAN is OFF at the time of purchase. To activate the dual dan comfort, press the “DUAL FAN COMFORT” button. will be flashing on the remote controller display. To deactivate the dual fan comfort, press the “DUAL FAN COMFORT” button. again. will no longer be shown on the remote controller display. Dual fan operates with the recommended setting. (Refer to the Fig. 11) Dual fan does not operates in TEST operation by indoor unit button. Operation only with dual fan is not possible. In HEAT mode, there is no dual fan airflow with the following.
- When the room temperature is lower than the set temperature
- When the temperature of HEAT airflow is low
- During autmatic defrosting operation In AUTO mode, there is no dual fan airflow with the following.
- When the room temperatrure is under the monitoring in AUTO mode. (Fig. 11 )
3. Setting
The position of dual fan in COOL, DRY or FAN mode can change so that the airflows further. ( For the case that the opposite wall is far from the indoor unit, and the air agitation is required.)
1. Turn off the indoor unit by pressing the “Start/Stop ” button.
2. Press the “DUAL FAN COMFORT” button for at least 5 seconds until the current “DUAL FAN” status is displayed.
3. Press the “TEMP.” buttons to switch the setting. “1” (Standard) “2” (Far) *
4. Press the “Start/ Stop ”button to send the setting to the indoor unit. After the status is sent, the display will automatically return to the original screen. *If no buttons are pressed within 30 seconds after the “DUAL FAN” status is displayed, the system returns to the original clock display. In this case, start again from setp 1. If this still does not match the preferences. see the function setting.
Louver position
1 (Horizontal) 2 3 4 5 6 7 8 (Blow down)
Dual fan positoin COOL DRY HEAT FAN *
7 1 7 1 7 2 7
2 7 3 7 4 7 5 7 6
The dual fan position is controlled together with the louver position Up / Down. The fan speed is controlled with the fan speed of main fan and the louver position Right / Left. *The position 7: (Standard) is able to change to the postion 5: (Far) upward. Refer to the setting.
Remarks
Default setting COOL/ DRY/ FAN
The lowest down position in dew water protection (COOL/ DRY)
Default setting HEAT
9. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in Table 8.
Cooling
Min
Max
)egnaR ycneuqerF noitarepO rosserpmoC : 8 elbaT(
01-10
15rps 63rps
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Fig.12.
(Fig.12 : Compressor Control at Start-up)
Time
Time Time
Frequency
Frequency
Frequency
Time
Time Time
80sec 110sec 140sec
(Time)
29rps 53rps 65rps
(Frequency)
Frequency
Frequency
Frequency
Min
Max
15rps 128rps
Dry
Min
Max
15rps 22rps
Heating
Frequency
Frequency
Frequency
Time
Time Time
72rps 91rps 99rps
Frequency
Frequency
Frequency
Time
Time Time
200sec 350sec 410sec
10. TIMER OPERATION CONTROL
1. ON TIMER / OFF TIMER
The Table 9 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
( Table 9 : Timer setting )
2. PROGRAM TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time Set time Set time Set time
10-1 WIRELESS REMOTE CONTROLLER
01-11
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1°C
+2°C
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not changed and the operation stops at the time of timer setting.
Set
30min
30min
30min
-4°C
-3°C
-2°C
-1°C
01-12
11. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table10. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).
12. TEST OPERATION CONTROL
The compressor won't enter operation status for 140 sec. after the compressor is stopped, even if any operation is given.
13. PREVENT TO RESTART ( ST )
01-13
( Table10 : The pulse range of the electronic expansion valve control )
Cooling / Dry mode Heating mode
Operation mode Pulse range
between 32 to 480 pulses.
between 32 to 480 pulses.
Operation method Before starting the test run, wait for 1 minute after connecting the power supply. By the wireless remote controller
• To start the test run, press the “Start/Stop ” “ button, the “TEST RUN” button on the remote controller with a by using the tip of a ballpoint pen or other small object. By the indoor unit button
• To start the test run, keep on pressing the “INDOOR UNIT” button of the indoor unit for more than 10 sec.
• To end test operation, press the remote controller “Start/Stop ” button.
(When the air conditioner is running by pressing the “TEST RUN” button, the “OPERATION” indicator and “TIMER” indicator blink simultaneously.)
16. FORCED AUTO OPERATION
If the Indoor unit button is pressed 3 to 10 sec. the operation is controlled as shown in Table 11. (If the remote controller is lost, this function can use.) The Operation indicator and the Timer indicator blinks for 1 sec, ON, and 1 sec. OFF. The forced auto operation is released after 60 min. after starting the operation. By pressing the Indoor unit button for 3sec., the operation stops.
OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous (No timer setting available) SETTING TEMP. 24°C SETTING LOUVER Standard / Momorized position
(Table11)
01-14
17. FORCED COOLING OPERATION
Manual auto operation
If the Indoor unit button is pressed over 10 sec., the operation is controlled as shown in Table 12. (If the remote controller is lost, this function can use.) The Operation indicator and the Timer indicator blinks for 1 sec, ON, and 1 sec. OFF. The forced auto operation is released after 60 min. after starting the operation. By pressing Indoor unit button for 3 sec., the operation stops.
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking slowly (6 sec ON/2 sec OFF) the indoor unit body timer indicator.
[ Operation contents memorized when the power is interrupted ]
Operation mode Set temperature Set air flow Timer mode and timer time Set air flow Direction
S
Human sensor setting Low noise operation
wing ECONOMY operation 10°C HEAT operation
15. AUTO RESTART
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 140 sec. later aftter the compressor Stopped.
14. FOUR-WAY VALVE EXTENSION SELECT
DUAL FAN HUMAN SENSOR ECONOMY SWING
OFF OFF OFF OFF
OPERATION MODE COOL FAN CONT. MODE Hi TIMER MODE Continuous (No timer setting available) SETTING TEMP. 24°C SETTING LOUVER Standard
Manual auto operation
DUAL FAN HUMAN SENSOR ECONOMY SWING
OFF OFF OFF OFF
(Table12)
At the time when the compressor stopped during heating mode, the four-way valve position changes to the cooling position with certain period as follows.
- When the compressor is stopped by the operation STOP: after 140 sec.
- When the compressor is stopped by other than above: after 1800 sec.
01-15
When the time erapsed 30 min, after compressor stopped, and whren the outdoor heat exchanger temperature sensor detects lower temperature, the preheating starts. When the operation starts, the preheating stops. The preheating does not oeprate when the system is stopped with Error of permanent stop.
18. COMPRESSOR PREHEATING
) gnitaeherP rosserpmoC : 31.giF (
7°C
5°C
19. 10°C HEAT OPERATION
The 10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller. The 10°C HEAT operation is almost the same operation as below settings.
Mode Heating Setting temperature 10°C Fan mode Lo (AUTO)
( Table13 )
20. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating Target temperature Setting temp.+1°C Setting temp.-1°C
( Table14)
0°C
C°2-
-2°C C°4-
OFF OFF ON ON
14°C
C°21
0°C
C°2-
-2°C C°4-
OFF ON ON ON
JUMPER (J600) removed
When the 10°C HEAT operation is operating, the ECONMY indicator turns ON.
21. DEFROST OPERATION CONTROL
01-16
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects the temperature lower than the values shown in Table15.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table16.
( Table16 : Defrost Release Condition )
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +16°C
or Compressor operation time has passed 15min.
( Table 15 : Condition of starting Defrost Operation )
Defrosting (Normal) starting operation
Compressor integrating operation time
Compressor integrating operation time
Less than 40min. More than 40min.
Does not operate
Integrating defrost (Constant monitoring)
More than 240min. (For long continuous operation)
Less than 10min.*1 (For intermittent operation)
- 3°C
More than 215min. (For long continuous operation)
- 5°C
OFF count of the compressor 40 times.
*1 : If the compressor continuous operation time is less than 10 min, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
Tn-Tn10 < - 5deg Tn-Tnb < - 2deg However, Tn < - 6°C
=
Tn10 : Temperature of continuous operation at 10minutes. Tnb : Back 5minutes temperature
Tn < - 17°C
=
01-17
Compressor OFF Outdoor fan motor OFF 50sec. later four - way valve OFF 55sec. later compressor ON
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.
(Not defrosted for 10min.)
Heating operation start : Compressor ON
Outdoor heat exchanger temperature:
Over +16°C
or
Compressor ON time: Maximum 15min.
Defrost end
Integrating defrost
(Constant monitoring)
Defrost Indicator: [Operation indicator] 6sec. ON / 2sec. OFF
Defrost start
Compressor OFF count : 40 times (Less than 10min.)
Normal defrost
Compressor integrating operation: Over 240min.
Outdoor heat exchanger temperature: Below - 3°C
Compressor integrating operation: Over 215min.
Outdoor heat exchanger temperature: Below - 5°C
Compressor integrating operation: Over 40min.
Tn-Tn10 < - 5deg Tn-Tnb < - 2deg However, Tn < - 6 °C
=
Tn < - 17°C
=
22. OFF DEFROST OPEARTION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation indicator flashes slowly (6 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than -4°C, compressor continuous operation more than 10 minutes, and compressor operation integrating time lasts for more than 30 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature : Below -4°C Compressor continuous operation : Over 10 minutes Compressor integrating operation : Over 30 minutes
Defrost start
Defrost Indicater: [Operation indicator] 6 sec ON / 2 sec OFF
Outdoor heat exchanger temperature :
Over +16°C
or
Compressor ON time : Maximum 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +16°C or Compressor operation time has passed 15 minutes.
01-18
23. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until
the temperature becoms lower than Temperature . When the discharge temperature becomes lower than Temperature , the control of the control of the compressor frequency is released. When the discharge temperature becomes higher than Temperature , the compressor is stopped and the indoor unit indicator starts blinking.
104°C 101°C 110°C
( Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature )
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
( Table 18 : Current Release Operation Value / Release Value)
01-19
[ Heating ]
[ Cooling ]
TO (Control / Release)
4.5A / 4.0A
6.0A / 5.5A
7.0A / 6.5A
46°C 40°C
TO (Control / Release)
8.5A / 8.0A
10.5A / 10.0A
12.5A / 12.0A
17°C 12°C
[ Heating ]
TO : Outdoor Temperature
[ Cooling ]
TO (Control / Release)
5.0A / 4.5A
6.5A / 6.0A
7.5A / 7.0A
46°C 40°C
TO (Control / Release)
10.5A / 10.0A
12.5A / 12.0A
14.5A / 14.0A
17°C 12°C
Model 09
Model 12
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
( Table 19 : Anti-freezing Protection Operation / Release Temperature )
Outdoor temperature
Over than 10°C *1
or 12°C *2
Less than 10°C *1
or 12°C *2
*1. When the temperature rises. *2. When the temperature drops.
4°C
7°C
13°C
Temperature
Temperature
01-20
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 65°C or greater the compressor is stopped.The compressor restarst after the 140 sec, erapsed (ST). and the temperature detection starts 60 sec. erapsed after compressor started.
5. HIGH TEMPERATURE AND HIGH PRESSURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
Indoor heat exchange temperature rises
Indoor heat exchange temperature drops
[ Control System ]
It returns to the normal operation
Compressor is stopped
53°C
55°C
63°C
50°C
The compressor frequency is decreased 4rps every 120seconds.
The compressor frequency is decreased 25rps every 120seconds.
6. HIGH PRESSURE PROTECTION
When the pressure switch becomes OFF (Open : higher than 4.2 MPa), the compressor is stopped. It is released when the pressure switch becomes ON (Close : lower than 3.2 MPa) after 140sec. of compressor stop.
Stable zone
7. 4 way valve protection
The 4 way valve protection operates with the following conditions.
1. When the compresspr operates for more than 20 minutes.
2. Tn (Indoor unit HEX temp) -Tb (Room temp) > 10 deg in COOL and DRY
3. Tn (Indoor unit HEX temp) -Tb (Room temp) < -10 deg in HEAT When the above condition 1&2 or 1&3 repeat 2 times for 2 min, the compressor stops. When the same condition repeats 5 times, the system indicates the Error code.
8. Dew water protection (Operating in COOL, DRY)
When the vertical louver is set the position 5 ~ 8, and when the operating time erapsed 30 minutes, the louver position changes automatically to the position 4.
9. EEV shutoff protection (Operating in HEAT)
The EEV shutoff protection operates with the following conditions.
1. When the compresspr operates for more than 20 minutes.
2. Tn (Indoor unit HEX temp) -Tb (Room temp) < 4 deg
When the above condition 1 and 2 repeat 2 times in 2 min, the compressor stops.
After the ST (Restart protection), the compressor starts.
01-21
24. LOW NOISE OPERATION
Operating mode
COOL, DRY
HEAT
Outdoor fan speed
[rpm]
Compressor speed
[rps]
The compressor speed and the outdoor unit fan speed are limited to reduce the operation noise by presssing “LOW NOISE” button on the remote controller. However, during the DEFROST OPERATION, the compressor operates by the speed for DEFROST OPERATION.
660 660
32 32
*The performance drops when operating in the LOW NOISE OPERATION.
25. HUMAN SENSOR (Energy Saving)
• Details about detection with the human sensor
• The human sensor detects whether there are people in the room
by looking for movement by people in the room.
About the ENERGY SAVING Operation
If no one enters the room for approximately 20 minutes, the set temperature will be automatically controlled. (When someone comes back into the room, the human sensor will detect this, and automatically revert to the original settings.)
Operation mode
About the HUMAN SENSOR
Cool / Dry
Heat
Auto
Operation details
(if there is no one in the room for a while) The set temperature will be increased by
a maximum of approximately 2
°C.
Application range is follows. Vertical angle 90
°(Side view)
ENERGY SAVING function may not work when the room temperature is very different from the temperature defined in temperature setting, such as when immediately after starting the operation
Horizontal angle 100
°(Top view)
The set temperature will be decreased by a maximum of approximately 4
°C.
This runs the ENERGY SAVING function automatically for the selected mode (Cooling/ Heating/ Drying)
* High limit : 30°C
* Low limit : 16°C
* When using together with the SLEEP time, the SLEEP timer will be prioritized. * During 10°C HEAT operation, if there is no one in the room the set temperature will not be changed.
01-22
26. POWERFUL OPERATION
The Powerful operation functions by pressing POWERFUL button on the remote controller. The indoor unit & outdoor unit will operate at maximum power as shown in Table 20.
Release Condition is as follows. [Cooling / Dry]
- Room tenperature < Setting temperature - 0.5°C or Operation time has passed 20 min..
COMPRESSOR FREQUENCY Maximum FAN CONT. MODE Powerful SETTING LOUVER Cooling/ Dry : 4, Heating : 7
(Table 20)
Powerful operation
=
=
[Heating]
- Room tenperature > Setting temperature +0.5°C or Operation time has passed 20 min..
27. FILTER CLEAN
The Filter clean function operates with the following conditions.
1. Auto filter clean When the air conditioner operating time reached 40 hours*. *Filter clean operation interval time can change by the function setting.
2. Manual filter clean When the Filter Clean button on the remote controller is pressed. The filter cleaning time is approximately 13 min.. The indoor unit “FILTER CLEAN” indicator lights up during filter cleaning. When the FILTER CLEAN indicator blinks slowly, this indicates that it is time to clean the dust box. (After approximately 10,000 hours of air conditioner operation have elapsed.) After cleaning the dust box, press Indoor unit button less than 3 sec.. By pressing the indoor unit button, the accumulated operation time is reset. When the indicator brinks as follows, check filter installing (refer to the operation manual.)
28. PLASMA CLEAN
The plasma clean function operates with the following conditions.
- When the plasma air clean button on the remote controller is pressed.
- When the Indoor unit main fan is rotating at very low speed or is stopped. The indoor unit “PLASMA AIR CLEAN” indicator lights up during the functioning. When the PLASMA AIR CLEAN indicator blinks slowly, this indicates that it is time to clean the plasma air clean unit. (After approximately 1,100 hours of plasma air clean operation have elapsed.) After cleaning the plazma clean unit (refer to the operation manual), press Indoor unit button less than 3 sec.. By pressing the indoor unit button, the accumulated operation time is reset. When the PLASMA AIR CLEAN indicator blinks, this indicates that the plasma clean unit is wet, dirty or the intake grille is opened. In this case, stop the air conditioner and then check intake grille or clean the plasma clean unit and dry it completely.
01-23
29. WIRELESS LAN
The operation with the wireless LAN is possible by using the wireless LAN adaptor (packaged with the manuals), and by performing the network setting.
1) Wireless LAN adaptor
2) Wireless LAN router
3) Internet
4) Mobile device and Mobile app
CLOUD
1) Wireless LAN adaptor The adaptor is packaged with the manuals. The SSID is in the label with the wireless LAN adaptor. For the installing and setting, refer to the installation manual and the setting manual. The wireless adaptor has the LED indicator, and it indicates the status. In case of trouble, refer to the troubleshooting or setting manual.
2) Wireless LAN router Loacl purchase (use the user’s product) PIN code or WPS (serting) is required for linking with the wireless LAN adaptor. The internet connection is required.
3) Internet The operation and the status indication are performed via the Internet.
4) Moble device and Mobile app Mobile app (application software) “ FGLair” has to be installed to the user’s mobile device. (For installing the app, the user registeration is required. Refer to the setting manual.) The function available on the mobile device may differ from the finction on the remote controller. (Refer to the operation manual of mobile app)
2 . TROUBLESHOOTING
WALL MOUNTED type
INVERTER
2-1 INDOOR UNIT ERROR DISPLAY
Please refer the flashing pattern as follows. The OPERATION, TIMER and ECONOMY indicators operate as follows according to the error contents.
Room Temperature Thermistor Error
Error Contents
Trouble shooting
(Orange) (Green)
Serial Communication Error
Indoor unit Heat Ex. Thermistor Error
OPERATION, TIMER indicator : 0.5s ON / 0.5s OFF (Flash) ECONOMY indicator: 0.1s ON / 0.1s OFF (Flash continuous)
Outdoor unit Discharge Thermistor Error Outdoor unit Heat Ex. Thermistor Error Outdoor Temperature Thermistor Error
Indoor Fan Motor Error
Compressor start up Error Outdoor Unit Fan Motor Error
Side Fan ( Left ) Motor Error Side Fan ( Right ) Motor Error
Over current Error
CT Error
Manual Auto Switch Error
Indoor Unit Display
4 Way Valve Error Discharge Temperature Error
Power Supply Frequecy Detection Error
02-01
OPERATION TIMER ECONOMY
Indoor unit Model Information Error
Plasma air clean unit Vdd Error Filter set abnormal
Combination Error
Outdoor unit Model Information Error Trip terminal L Error
High pressure SW Error
1 time 1 time 2 time 3 times 3 times 3 times 4 times 4 times 5 times 5 times 5 times 5 times 5 times 6 times 6 times 7 times 7 times 7 times 8 times 8 times 9 times 9 times 9 times 9 times 10 times
1 time 8 times 3 times 1 time 2 times 5 times 1 time 2 times 1 time 4 times 5 times 9 times 10 times 2 times 5 times 1 time 3 times 4 times 4 times 6 times 4 times 5 times 7 times 9 times 1 time
1, 2 26,29,30 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
External Communication Error
INDOOR UNIT LED INDICATOR
(Green)
Continuous Continuous Continuous
Continuous Continuous Continuous Continuous
Continuous Continuous Continuous Continuous
Continuous Continuous Continuous Continuous Continuous
Continuous
Continuous
Continuous
Continuous Continuous Continuous Continuous Continuous
Continuous
Flashing Fast : Repeating 0.5 seconds ON / 0.5 seconds OFF
Wireless LAN addapter Error
Communication Error (”Troubleshooting 26” and “Troubleshooting 28” are simultaneous Error)
Trouble
shooting
26
27
28
Error Contents
Wireless LAN adapter Indicator
LED 1 LED2
Network Communication Error (Communication Error of between Wireless LAN router to Wireless LAN adapter)
External Communication Error (Communucation Error of between Indoor unit to wireless LAN adapter)
ON
LED 1 (Green) LED 2 (Orange)
WIRELESS LAN ADAPTER INDICATOR
Please refer the flashing pattern as follows. LED 1 (green) and LED 2 (orange) operate as follow according to the error contents.
Flashing Fast
ON
29
Wireless LAN adapter Non-Energized
OFF OFF
30
02-02
2-2 WIRELESS LAN ADAPTER ERROR DISPLAY
*The status LED1(Green) ON: The communication between the Indoor unit and the adaptor is normal.
(Green) (Orange)
Flashing Fast
Flashing Fast
Flashing Fast
Flashing Fast
Flashing Fast
Error code
18
No Error
No Error
18
18
Wireless LAN adapter Sleep mode
OFF OFF
31
No Error
Loading...
+ 80 hidden pages