Fujitsu AU*A45LCLU, AO*A45LBTL, AO*A45LCTL, AU*A54LCLU, AO*A54LCTL Design & Technical Manual

DESIGN & TECHNICAL MANUAL
SINGLE INDOOR
OUTDOOR
AOA45LBTL
AUA45LCLU AUA54LCLU
AOA45-54LCTL
AIR CONDITIONER
Cassette type
1. INDOOR UNIT
D2D_AU041E/04
2011.03.01
CASSETTE TYPE :
AUA45LCLU AUA54LCLU
- (3) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
CONTENTS
1. INDOOR UNIT
1. FEATURE
............................................................................................................ 01 - 01
2. WIRED REMOTE CONTROLLER
................................................... 01 - 04
3. SPECIFICATIONS
........................................................................................ 01 - 06
4. DIMENSIONS
................................................................................................... 01 - 08
5. WIRING DIAGRAMS
.................................................................................. 01 - 10
6. CAPACITY TABLE
........................................................................................01 - 11
6-1. COOLING CAPACITY
.................................................................................01 - 11
6-2. HEATING CAPACITY
................................................................................. 01 - 13
7. FAN PERFORMANCE
.............................................................................. 01 - 15
7-1. AIR VELOCITY DISTRIBUTION
............................................................... 01 - 15
7-1-1. STANDARD MODE .................................................................................. 01 - 15
7-1-2. SPECIAL UPWARD MODE ..................................................................... 01 - 19
7-2. AIR FLOW
.................................................................................................... 01 - 20
7-2-1. 4-WAY OUTLET ....................................................................................... 01 - 20
7-2-2. 3-WAY OUTLET ....................................................................................... 01 - 21
7-3. FRESH AIR
................................................................................................... 01 - 22
7-4. DUCT CONNECTION
................................................................................. 01 - 23
8. OPERATION NOISE
................................................................................... 01 - 25
8-1. NOISE LEVEL CURVE
............................................................................... 01 - 25
8-2. SOUND LEVEL CHECK POINT
............................................................... 01 - 26
9. ELECTRIC CHARACTERISTICS
..................................................... 01 - 27
10. SAFETY DEVICES
....................................................................................... 01 - 28
11. EXTERNAL INPUT & OUTPUT
......................................................... 01 - 29
11-1. EXTERNAL INPUT
...................................................................................... 01 - 29
11-2. EXTERNAL OUTPUT
................................................................................. 01 - 30
12. FUNCTION SETTING
................................................................................ 01 - 32
12-1. INDOOR UNIT
.............................................................................................. 01 - 32
12-2. INDOOR UNIT (Setting by remote controller)
..................................... 01 - 34
12-3. WIRED REMOTE CONTROLLER
............................................................ 01 - 38
13. OPTIONAL PARTS
...................................................................................... 01 - 39
- (01 - 01) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
FEATURE1.
M O D E L S
AUA45LCLU / AOA45LBTL, AOA45LCTL AUA54LCLU / AOA54LCTL
FEATURES
Energy saving
z
All DC design • Heat exchange efciency increased and larger air ow by adoption of new type turbo fan
Advancement in comfort
z
Quiet operation was realized by adoption of new type turbo fan Improvement of air stream
Adoption of high efficiency turbo fan High efciency achieved by equaling the performance of the wing and air passing the heat
exchanger
Important of the flap Making space between the ceiling, the air ows far wide and ceiling does not get dirty.
500mm
Wind
velocity
Fast
Slow
3-dimensional wing
: Spin direction : Airflow direction
No airflow separation
Quiet
< Motor side >
Heat exchanger
Rear part
Front part
Ceiling
Round Flap
Much less temperature irregularity
happens by spreading air flow widely
Bottom view
AOA45LBTL AOA45LCTL
AOA54LCTL
- (01 - 02) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
High lift drain pump
z
850mm
Ceiling panel
Simplication of drain water check
z
Drain and contamination check are possible without removing the decoration panel.
Can be easily checked by removing the drain cover.
Easy installation
z
Easy setting by wired remote controller
Improvement of installation & maintenance
z
Adjustment of nut is possible after installation Mounting position of body can be ne adjusted after Decoration panel mounting.
Grille corner
Adjustment
can be done just taking off the corner part
1.5
3
7 5 3 73 5
Side view
Airflow range of 2m / s
120120
Wide & powerful airflow The wind is widely delivered by a high efciency fan and round ap.
[m]
DRAIN CAP
DRAIN COVER
- (01 - 03) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
FUNCTION SETTING
Other functions
z
Performs operation matched to the number of outlets when 4 directions are unnecessary and outlets are blocked when the ceiling cassette is installed in a corner, etc.
Ceiling switching function
z
Also delivers air to high ceilings by selecting the mode and raising the air ow according to the height of the ceiling.
Low ceiling (Mode 1)
4.2m
3.2m
2.7m
High ceiling (Mode 2) Standard ceiling (Standard)
Standard ...Operates at normal air ow. Mode 1 ...Air ow becomes smaller than normal. Mode 2 ...Air ow becomes greater than normal.
Filter sign
z
The indoor unit has sign to inform the user that it is time to clean the lter
Cooling room temperature correction
z
Heating room temperature correction
z
Auto restart
z
The units restart automatically when the current was returned even when there was a power interruption during operation.
Room temperature sensor switching
z
Switches from room temperature judgment by room temperature sensor attached to indoor unit body to room temperature judgment by room temperature sensor attached to wired remote controller.
Economy operation
z
The power consumption can be reduced.
Powerful mode ...Standard Soft mode ...Performs operation which reduces the power consumption
4-way direction 3-way direction
4-way direction mode: Set when there are 4 outlets
(shipped state).
3-way direction mode: Set when there are 3 outlets.
- (01 - 04) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
WIRED REMOTE CONTROLLER2.
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Economy operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the
temperature accurately with built-in thermo sensor.
Simple function setting
z
Setting of the air conditioner selection function is performed by remote controller.
High performance and compact size
z
Three functions are combined in one unit.
Built-in timers
z
Wired
remote
controller
Weekly
timer
Setback
timer
+ +
Weekly timer Setback timer
At "Weekly timer" + "Set back timer" setup
Easy-to-understand operation
z
[Variable timer control] The operation/display sections are zoned
according to time and operation, enabling variable programming to match application.
Simple installation
z
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is
needed.
European switch box
JIS box
SUMOTUWETH FR SA
7
3126 9
15 18 21
SUMOTUWETH FR SA
7
3126 9
15 18 21
SUMOTUWETH FR SA
3126 9
15 18 21
Possible to set ON/OFF time to operate twice each day of the week.
Setup scr een example (Set to Wednes day: 8:00 to 20:00.)
Screen after setup
Setup scr een example (Set from Sunday to Satu rday: 12:00 to 15:00, 28 °C.)
Possible to set temperature for two time spans and for each day of the week.
Easy-to-understand time bar display
24°C
0 3 6 9 12 15 18 21 Time
28°C
0 3 6 9 12 15 18 21 Time
28°C
24°C
0 3 6 9 12 15 18 21 Time
24°C 28°C 24°C
Timer area
Operation area
- (01 - 05) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
FUNCTIONS
Display panel
DIMENSION
SPECIFICATION
15
11
10
9
8
2
1
3
5
14
4
12
13
6 7
17
16
18
19
20
21
120
18
120
SIZE (H x W x D mm) 120 x 120 x 18
WEIGHT ( g ) 160
CABLE LENGTH ( m ) 10
POWER ( V ) 12
1
START/STOP button
Pressed to start and stop operation.
2
SET TEMP. button
Selects the setting temperature.
3
MODE button
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY).
4
FAN button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
5
ECONOMY (THERMO SENSOR) button
Turns the economy efcient mode on and off.
6
TIMER MODE (CLOCK ADJUST) button
Selects the timer mode (OFF TIM ER, ON TIMER, WEEKLY TIMER). Set the current time.
7
DAY (DAY OFF) button
Temporarily cancels of one day timer.
8
SET BACK buttonn
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
TIMER DELETE button
The schedule of a weekly timer is deleted.
11
TIMER SET button
Sets the date, hour, minute and on-of f time.
12
Vertical airow direction and swing button
Push for two seconds to change the swing mode.
13
Horizontal airow direction and swing button
Push for two seconds to change the swing mode.
14
FILTER RESET button
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
Operation mode display
18
Fan speed display
19
Operation lock display
20
Temperature display
21
Function display
Defrost display
Thermo sensor display
Economy display
Vertical swing display
Horizontal swing display
Filter display
Functions will be di fferent due to type of indoor unit. For detail s, pleas e see operation manual.
[ Unit : mm ]
Front View
- (01 - 06) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
SPECIFICATIONS3.
Note : Speci cations are base d on the fol lowing c onditi ons. Coolin g : Indoor t emperat ure of 27 °CD B / 19 °CWB.a nd outdo or temper ature of 3 5 °CDB/ 24 °CWB. Heating : I ndoor te mperat ure of 20 °CD B / 15 °CWB.a nd outdoo r temper ature of 7 °C DB/6 °CW B. Pipe leng th : 7.5 m, Height di ffere nce : 0 m.(Out door uni t - Indoor u nit) The maxi mum cur rent is the m aximum v alue when o perate d within t he operat ion range (tempera ture)
Typ e
CASSE TTE MO DEL
INVER TER HE ATPUMP
Model na me
Indoor u nit AUA45LC LU
Outdoo r unit
AOA45LBTL
Power source 230V ~ 50 Hz
Availabl e voltag e range 198-2 64V ~ 50H z
Europea n energy l abel
Cooling A
Heating A
Capacity
Cooling
Rated
kW 12.5
BTU/h 42700
Min-Max
kW 4.0-14.0
BTU/h 13700-47800
Heating
Rated
kW 14.0
BTU/h 4780 0
Min-Max
kW 4.2-16.2
BTU/h 14300-55300
Input pow er
Cooling
Rated
kW
3.89
Max 4.56
Heating
Rated 3.77
Max 4.56
Current
Cooling
Rated
A
17.0
Max 20.0
Heating
Rated 16.5
Max 20.0
EER Cooling
kW/kW
3.21
COP Heating 3.71
Moistu re remova l l/h (pin ts/h) 4.5(7.9)
Fan
Airow rate
Cooling
High
m
3
/h
1900
Med 164 0
Low 14 60
Quiet 1250
Heating
High 19 00
Med 164 0
Low 14 60
Quiet 1250
Type × Q'ty Turbo × 1
Motor ou tput W 80
Sound pr essure l evel
Cooling
High
dB(A)
46
Med 42
Low 40
Quiet 36
Heating
High 46
Med 42
Low 40
Quiet 36
Heat excha nger t ype
Dimens ions (H × W × D)
mm
252×2021×13.3 252×2087×13.3 252×2153×13.3
Fin pitch 1.3
Rows x Sta ges 3 x 12
Pipe ty pe Copper
Fin type Aluminium
Enclos ure (Pane l)
Material Steel (HIPS)
Colour
WHITE
Approx imate co lour of M UNSEL L N 9.25/
Dimens ions ( H×W×D)
Net
Unit
mm
288×840×840
Panel 50×950×950
Gross
Unit 360×960×9 85
Panel 115×1120×100 0
Weight
Net
Unit
kg(lbs.)
27(6 0)
Panel 5. 5(12)
Gross
Unit 33( 73)
Panel 8.5 (19)
Connec tion pi pe
Size
Liquid
mm
Ø 9.52 (3/8 in .)
Gas Ø 15.88 (5/8 in .)
Method Flare
Operat ion ran ge
Cooling
°C 18 to 32
%RH 80 or les s
Heating °C 16 to 30
Remote co ntrol ler typ e Wired
Drain pi pe
Material PVC(V P25)
Size mm Outer dia meter : 32 .0 / Inner d iameter : 2 5.0
- (01 - 07) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
Note : Speci cations are base d on the fol lowing c onditi ons. Coolin g : Indoor t emperat ure of 27 °CD B / 19 °CWB.a nd outdo or temper ature of 3 5 °CDB/ 24 °CWB. Heating : I ndoor te mperat ure of 20 °CD B / 15 °CWB.a nd outdoo r temper ature of 7 °C DB/6 °CW B. Pipe leng th : 5 m, Heig ht diffe rence : 0 m. (Outdoor u nit - Indo or unit) The maxi mum cur rent is the m aximum v alue when o perate d within t he operat ion range(temper ature)
Typ e
CASSE TTE MO DEL
INVER TER HE ATPUMP
Model na me
Indoor u nit AUA45LC LU AUA54LC LU
Outdoo r unit
AOA45LC TL
AOA54LC TL
Power source 230V ~ 50 Hz
Availabl e voltag e range 198-2 64V ~ 50H z
Europea n energy l abel
Cooling A B
Heating A B
Capacity
Cooling
Rated
kW 12.5 13.3
BTU/h 42700 45400
Min-Max
kW 4.0-14.0 4.5-14.5
BTU/h 13700-47800 15400-49500
Heating
Rated
kW 14.0 16.0
BTU/h 4780 0 54600
Min-Max
kW 4.2-16.2 4.7-16.5
BTU/h 14300-55300 16000-56300
Input pow er
Cooling
Rated
kW
3.88 4.42
Max 4.70 4.94
Heating
Rated 3.77 4.69
Max 4.70 4.94
Current
Cooling
Rated
A
16.9 19 .3
Max 20.5 21.5
Heating
Rated 16.5 20.5
Max 20.5 21.5
EER Cooling
kW/kW
3.22 3.01
COP Heating 3.71 3.41
Moistu re remova l l/h (pin ts/h) 4.5 (7.9) 5.0 (8.8)
Fan
Airow rate
Cooling
High
m
3
/h
1900 2000
Med 1640 170 0
Low 14 60 153 0
Quiet 1250 13 00
Heating
High 19 00 2000
Med 1640 170 0
Low 14 60 153 0
Quiet 1250 13 00
Type × Q'ty Turbo × 1
Motor ou tput W 80
Sound pr essure l evel
Cooling
High
dB(A)
46 47
Med 42 43
Low 40 41
Quiet 36 37
Heating
High 46 47
Med 42 43
Low 40 41
Quiet 36 37
Heat excha nger t ype
Dimens ions (H × W × D)
mm
252×2021×13.3 252×2087×13.3 252×2153×13.3
Fin pitch 1.3
Rows x Sta ges 3 x 12
Pipe ty pe Copper
Fin type Aluminium
Enclos ure (Pane l)
Material Steel (HIPS)
Colour
WHITE
Approx imate co lour of M UNSEL L N 9.25/
Dimens ions ( H×W×D)
Net
Unit
mm
288×840×840
Panel 50×950×950
Gross
Unit 360×960×9 85
Panel 115×1120×100 0
Weight
Net
Unit
kg(lbs.)
27(6 0)
Panel 5. 5(12)
Gross
Unit 33( 73)
Panel 8.5 (19)
Connec tion pi pe
Size
Liquid
mm
φ9.52 (3/ 8 in.)
Gas φ15.88 (5/8 i n.)
Method Flare
Operat ion ran ge
Cooling
°C 18 to 32
%RH 80 or les s
Heating °C 16 to 30
Remote co ntrol ler typ e Wired
Drain pi pe
Material PVC(V P25)
Size mm Outer dia meter : 32 .0 / Inner d iameter : 2 5.0
- (01 - 08) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
DIMENSIONS4.
MODEL : AUA45LC, AUA54LC
Ceiling opening and hanging bolt pitch
z
(Unit : mm)
Refrigerant piping and drain piping positions
z
Airow split-ow duct and fresh air inlet positions
z
288
298
40
10
140 - 145
50 - 100
950 (Panel frame)
54 - 02 54 - 02
50
80
130
130
130
200
840 (Body frame)
795 (Hanging bolt pitch)
699 (Hanging bolt pitch)
860 - 910 (Ceiling opening)
950 (Panel frame)
54 - 02 54 - 02
840 (Body frame)
860 - 910 (Ceiling opening)
60278358
140
180
200
Drain pipe (Connect the attached drain hose)
88
70
2.5 hole
2.5 hole
250
352
100
8383
90
100
581 581
Airflow split-flow duct connecting port
Airflow split-flow duct connecting port
Airflow split-flow duct connecting port
Fresh air inlet position
Fresh air inlet position
Drain pipe
Refrigerant pipe
Detailed diagram of branched duct connecting port (4 sides)
Knockout hole pitch
Cut out
Cut out
Airflow split-flow duct connecting port
10
4
- (01 - 09) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
INSTALLATION PLACE
(Unit : mm)
3-way directions setting
z
To set “3-way directions”, the air outlet shutter plate (UTR-YDZC) sold separately must be installed and “outlet-direction” switched to “3-way” by remote controller.
1,500
or more
1,000 or more
1,800 or more
Obstruction
3,000 or more
Strong and durable ceiling
Floor
Ceiling mode “Low” : 2.7 m
Ceiling mode “Standard” : 3.2 m
Ceiling mode “High” : 4.2 m
100 or more
- (01 - 10) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
WIRING DIAGRAMS5.
MODEL : AUA45LC, AUA54LC
- (01 - 11) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
CAPACITY TABLE6.
COOLING CAPACITY6-1.
This table is created using the maximum capacity.
MODEL : AUA45LC / AOA45LB
MODEL : AUA45LC / AOA45LC
AFR : Air  ow rate (m3/min) TC : Total capaci ty (kW ) SHC : Sens ible Hea t capaci ty (kW ) IP : Input Pow er (kW)
AFR 31.7
Indoor t empera ture
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoo r temper ature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SH C IP TC SHC IP TC SHC IP TC SHC IP
-15 11.00 8 .83 1.99 12. 26 8. 88 2.03 12.6 8 9.65 2.04 13.51 9.68 2.06 13. 93 10.46 2 .07 14.76 10.42 2.0 9 15.60 11.10 2.11
-10 10.95 8.78 1.99 12.19 8.8 3 2.03 12.61 9.60 2.04 13.4 4 9.6 3 2.06 13.8 6 10.40 2.07 14.69 10.36 2.09 15 .52 11.04 2.11
0 10.88 8.51 2.00 12.11 8.5 6 2.04 12.53 9.31 2.05 13. 35 9.3 4 2.07 13.77 10.0 8 2.0 8 14.59 10.04 2.10 15.42 10.70 2.1 2
5 10.83 8.61 2.05 12.0 6 8.6 6 2.08 12.47 9.41 2.09 13. 30 9. 44 2.11 13.71 10.20 2 .12 14.53 10.16 2 .15 15.3 5 10.82 2.17
10 10.81 8 .73 2.1 2 12.05 8.79 2.16 12. 46 9. 55 2.17 13.28 9.5 8 2.19 13.69 10.35 2.20 14.51 10.31 2. 22 15. 33 10.98 2. 25
15 10.75 8.71 2.23 11.97 8.76 2.26 12.38 9. 53 2.27 13.2 0 9.5 6 2.29 13.61 10.32 2.31 14.42 10.28 2. 33 15. 24 10.95 2. 35
20 11.01 8.69 2.74 12.26 8.74 2.78 12.6 8 9.5 0 2.79 13.51 9.53 2.82 13. 93 10.29 2. 84 14.7 7 10.25 2. 87 15.6 0 10.92 2.8 9
25 11.09 8.8 0 3.18 12.35 8.85 3.23 12 .77 9. 62 3.25 13.6 2 9.65 3.28 14.04 10.42 3.30 14.88 10.38 3. 33 15.7 2 11.06 3.36
30 11.36 8.84 4.30 12.66 8. 89 4.36 13.0 9 9.67 4.38 13.95 9.70 4.43 14. 38 10.47 4. 45 15. 24 10.43 4. 50 16.11 11.11 4.5 4
35 11.06 8.98 4.29 12.32 9. 03 4.35 12.74 9.82 4.38 13.58 9. 85 4.42 14.0 0 10.64 4.4 4 14.8 4 10.60 4.4 9 15.6 8 11.29 4.5 3
40 8.64 7.7 1 3.59 9.63 7.75 3.65 9.96 8.43 3.67 10. 61 8.46 3.71 10.9 4 9 .13 3.72 11.60 9.10 3.76 12. 26 9.6 9 3.80
46 5.97 6.37 2.71 6.65 6.41 2.76 6.88 6.97 2.77 7. 33 6.99 2.80 7.56 7.55 2.81 8.01 7.52 2.84 8.47 8.01 2.87
AFR 31.7
Indoor t empera ture
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoo r temper ature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SH C IP TC SHC IP TC SHC IP TC SHC IP
-15 11.34 8.71 2.56 12.6 3 8.76 2.6 0 13.06 9.52 2.62 13. 92 9. 55 2.64 14.3 5 10.32 2.6 6 15. 21 10.28 2.6 8 16.07 10.9 5 2.71
-10 11.44 8.70 2.46 12.74 8.75 2.50 13.17 9.51 2.51 14.0 4 9.5 5 2.54 14.48 10.31 2.55 15.35 10.27 2. 58 16. 21 10.94 2.6 0
0 11.55 8.77 2.23 12. 87 8.8 3 2.26 13.31 9.60 2.28 14.18 9.6 3 2.30 14.62 10.4 0 2. 31 15.50 10.35 2.33 16.38 11.03 2. 36
5 11.37 8.78 2.30 12.6 7 8.8 4 2.34 13.10 9.61 2.35 13. 96 9. 64 2.37 14.4 0 10.41 2.39 15.2 6 10.37 2. 41 16.12 11.04 2.43
10 11.11 8 .78 2.49 12.37 8.83 2.53 12.79 9. 60 2.54 13.6 4 9.6 3 2.57 14.06 10.40 2.58 14.90 10.36 2 .61 15.74 11.04 2.6 3
15 10.84 8 .68 2.69 12. 07 8 .74 2.73 12.48 9.50 2.74 13.31 9. 53 2.77 13.72 10.2 9 2.78 14.54 10.25 2.81 15.37 10.92 2. 84
20 11.22 8.69 3.15 12.49 8.74 3.20 12.9 2 9.5 0 3.22 13.77 9.53 3.25 14. 20 10.29 3. 27 15.0 5 10.25 3. 30 15.9 0 10.92 3.3 3
25 11.10 8.78 3.36 12.36 8 .83 3.41 12.79 9.6 0 3.43 13.63 9.63 3.46 14.05 10.40 3. 48 14.8 9 10.36 3.51 15 .74 11.03 3.5 5
30 11.34 8.84 4.27 12.63 8. 89 4.34 13.0 6 9.67 4.36 13.92 9.70 4.41 14.3 5 10.48 4.4 3 15. 21 10.43 4.4 3 16.07 11.11 4.43
35 11.06 8.82 4.53 12.32 8 .87 4.60 12.74 9.64 4.62 13.58 9.68 4.67 14.0 0 10.45 4.6 9 14.8 4 10.41 4.6 9 15.6 8 11.09 4.6 9
40 8.79 7.66 3.92 9.79 7.83 3.98 10.13 8.52 4.00 10. 80 8. 54 4.04 11.13 9.23 4.06 11.80 9.1 9 4.0 6 12.47 9.79 4.06
46 6.69 6.63 3.24 7.45 6.87 3.29 7.7 1 7.47 3.31 8.22 7.49 3.34 8.47 8.09 3.36 8.98 8.06 3.36 9.49 8.58 3.36
- (01 - 12) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
This table is created using the maximum capacity.
MODEL : AUA54LC
AFR : Air  ow rate (m3/min) TC : Total capaci ty (kW ) SHC : Sens ible Hea t capaci ty (kW ) IP : Input Pow er (kW)
AFR 33.3
Indoor t empera ture
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoo r temper ature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SH C IP TC SHC IP TC SHC IP TC SHC IP
-15 11.73 9.03 2.69 13.07 9.08 2.73 13.52 9 .87 2.75 14.41 9.9 0 2.78 14.85 10.69 2.79 15.74 10.65 2. 82 16.6 4 11.35 2. 85
-10 11.72 9 .04 2.59 13. 06 9.10 2.63 13.50 9.89 2.64 14.39 9. 92 2.67 14.8 4 10.71 2.6 8 15.73 10.67 2.71 16.62 11.37 2.73
0 11.84 9 .12 2. 33 13.19 9 .17 2.36 13.64 9.97 2.37 14.5 4 10.01 2. 40 14.9 9 10.81 2 .41 15.8 9 10.76 2.4 3 16.78 11.46 2.46
5 11.60 8 .96 2.42 12. 92 9. 02 2.46 13.37 9.80 2.47 14.25 9. 83 2.50 14.6 9 10.62 2 .51 15.5 7 10.58 2.5 4 16.45 11.27 2.56
10 11.44 8. 90 2.54 12.74 8.95 2.58 13.18 9.73 2.59 14.04 9.76 2.62 14.48 10.54 2.63 15. 35 10.50 2. 66 16.2 2 11.18 2.6 8
15 11.22 8. 99 2.80 12.5 0 9.0 4 2.85 12.92 9.83 2.86 13.77 9.8 6 2.89 14.2 0 10.65 2.91 15.05 10.61 2.93 15. 90 11.30 2. 96
20 12.0 6 9.5 5 3.73 13.43 9.61 3.79 13. 89 10.45 3.81 14. 81 10.48 3.8 5 15.2 6 11.32 3.8 7 16 .18 11.27 3.9 0 17.10 12.01 3. 94
25 11.82 9 .10 4.31 13.17 9 .15 4. 38 13. 62 9.9 5 4.40 14.52 9.98 4.45 14.97 10.78 4.47 15.8 6 10.73 4. 51 16.76 11.43 4.56
30 11.62 8.98 4.52 12.95 9.0 4 4.59 13.3 9 9.8 2 4.61 14.27 9.86 4.66 14.71 10.64 4.6 8 15.5 9 10.60 4.6 8 16.48 11.29 4.68
35 11.46 8.89 4.75 12.76 8. 95 4.82 13.2 0 9.73 4.8 5 14.07 9.76 4.90 14. 50 10.54 4 .92 15. 37 10.50 4. 92 16. 24 11.18 4.9 2
40 9.11 8.03 3.94 10.15 8.21 4.00 10.49 8. 93 4.02 11.18 8.9 6 4.06 11.53 9.67 4.08 12. 22 9.6 3 4.08 12.91 10.2 6 4.08
46 6.94 6.91 3.26 7.73 7.16 3.31 7.99 7.78 3.33 8.52 7.81 3.36 8.78 8.43 3.38 9.31 8.40 3.38 9.83 8.94 3.38
- (01 - 13) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
HEATING CAPACITY6-2.
This table is created using the maximum capacity.
MODEL : AUA45LC / AOA45LB
MODEL : AUA45LC / AOA45LC
AFR : Air o w rate (m3/min) TC : Total capaci ty (kW) IP : Input Pow er (kW)
AFR 31.7
Indoor temperature
°CDB 16 18 20 22 24
Outdoo r temper ature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 11.43 4.49 11.16 4.58 10.89 4.67 10.62 4.77 10.35 4.86
-10 -11 12.38 4.49 12.08 4.58 11.79 4.67 11.49 4.77 11. 20 4.86
-5 -7 13 .18 4.48 12.87 4.57 12.55 4.67 12. 24 4.76 11.93 4.85
0 -2 14.10 4.48 13.77 4.58 13.4 3 4.67 13.09 4.76 12.76 4.86
5 3 16.02 4.49 15.64 4.58 15.25 4.67 14.87 4.77 14.49 4.86
7 6 17.01 4.49 16.61 4.58 16.20 4.67 15.80 4.77 15. 39 4.86
10 8 17.19 4.35 16.78 4.44 16. 37 4.53 15.96 4.62 15. 55 4.71
15 10 1 7.3 2 4.10 16.91 4.19 16.50 4.28 16.09 4.36 15.67 4.43
20 15 17. 46 3.06 17. 05 3.12 16.63 3.19 16.22 3.25 15.80 3.30
24 18 17. 51 3.00 1 7.10 3.0 6 16.68 3.12 16.26 3.19 15.84 3.24
AFR 31.7
Indoor temperature
°CDB 16 18 20 22 24
Outdoo r temper ature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 10.90 4.14 10.6 4 4. 22 10.38 4.31 10.12 4.40 9.86 4.48
-10 -11 11.86 4.29 11.57 4.38 11. 29 4.47 11.01 4.56 10.73 4.65
-5 -7 12.96 4.25 12. 65 4.3 4 12.34 4.43 12.03 4.43 11.73 4.43
0 -2 14.01 4.25 13.68 4.34 13.35 4.43 13.01 4.43 12.68 4.43
5 3 15.51 4.25 15.1 4 4.34 14.77 4.43 14.40 4.43 14.03 4.43
7 6 17.01 4.25 16.61 4.3 4 16.20 4.43 15.80 4.43 15.39 4.43
10 8 17.29 4.25 16.88 4.34 16.46 4.43 16.05 4.43 15.64 4.43
15 10 16.80 3.80 16 .40 3.88 16.00 3.96 15.60 3.96 15.20 3.96
20 15 16.27 3.80 15.88 3.88 15.49 3.96 15.10 3.96 14.72 3.96
24 18 16.79 3.26 16.39 3.33 15.99 3.40 15.60 3.40 15.20 3.40
- (01 - 14) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
This table is created using the maximum capacity.
MODEL : AUA54LC
AFR : Air o w rate (m3/min) TC : Total capaci ty (kW) IP : Input Pow er (kW)
AFR 33.3
Indoor temperature
°CDB 16 18 20 22 24
Outdoo r temper ature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 11.00 4.16 10.73 4.24 10.47 4.33 10. 21 4.42 9.95 4.50
-10 -11 12.08 4.31 11.79 4.40 11.50 4.49 11.22 4.58 10.93 4.67
-5 -7 13.30 4.49 12.99 4.59 12.67 4.68 12.35 4.68 12.04 4.68
0 -2 14.44 4.49 14.10 4.59 13.75 4.68 13.41 4.68 13.07 4.68
5 3 16.01 4.49 15.62 4.59 15.24 4.68 14.86 4.68 14.48 4.68
7 6 17. 33 4.49 16. 91 4.59 16.50 4.68 16.09 4.68 15.68 4.68
10 8 17.61 4.49 17.19 4.59 16.77 4.68 16.35 4.68 15.93 4.68
15 10 16.97 3.82 16.57 3.90 16.16 3.98 15 .76 3.98 15.35 3.98
20 15 16.43 3.37 16.04 3.44 15.65 3.51 15.25 3.51 14.86 3.51
24 18 16.96 3.37 16. 56 3.44 16.15 3.51 15 .75 3.51 15.35 3.51
- (01 - 15) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
FAN PERFORMANCE7.
AIR VELOCITY DISTRIBUTION7-1.
STANDARD MODE7-1-1.
MODEL : AUA45LC
4-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
5
4
3
2
1
0
1
2
3
4
5
Unit : m/s(m)
(m)
TOP VIEW VERTICA L LOUVER : Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L LOUVER : Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L LOUVER : D ownward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
0.25 0.25
11
0.5 0.5
2 2
0.25 0.25
1 1
0.5 0.5
2 2
0.25
0.25
0.5
0.5
1
1
10.5 0.51
2
2 2
2
- (01 - 16) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
3-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
5
4
3
2
1
0
1
2
3
4
5
Unit : m/s(m)
(m)
TOP VIEW VERTICA L LOUVER : Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L LOUVER : Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L LOUVER : D ownward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
0.25 1
0.5
0.25
0.5
2
1
2
0.25
1 1
0.5
0.25
0.5
2 2
0.25
0.25
1
1
0.5
0.5
2
2
0.251 0.52
- (01 - 17) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
MODEL : AUA54LC
4-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L FLAP : D ownward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L FLAP : Upward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
5
4
3
2
1
0
1
2
3
4
5
Unit : m/s(m)
(m)
TOP VIEW VERTICA L FLAP : Upward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
- (01 - 18) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
3-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L FLAP : D ownward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W
VERTICA L FLAP : Upward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
5
4
3
2
1
0
1
2
3
4
5
Unit : m/s(m)
(m)
TOP VIEW VERTICA L FLAP : Upward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
- (01 - 19) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
SPECIAL UPWARD MODE7-1-2.
MODEL : AUA45LC
4-way air outlet
z
MODEL : AUA54LC
4-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
(m)
SIDE VIE W
VERTICA L LOUVER : Speci al upward
Unit : m/s(m)
3.2
2
1
0
0.25
1
0.5
2
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
(m)
SIDE VIE W
VERTICA L FLAP : Speci al upward
Unit : m/s(m)
3.2
2
1
0
- (01 - 20) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
AIR FLOW7-2.
4-WAY OUTLET7-2-1.
MODEL : AUA45LC
Cooling / Heating
z
MODEL : AUA54LC
Cooling / Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 690
m
3
/h 1900
l/s 528
CFM 1118
MED 610
m
3
/h 1640
l/s 456
CFM 965
LOW 550
m
3
/h 1460
l/s 406
CFM 859
QUIET 470
m
3
/h 1250
l/s 347
CFM 736
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 720
m3/h
2000
l/s
556
CFM
1177
MED 630
m3/h
1700
l/s
472
CFM
1000
LOW 570
m3/h
1530
l/s
425
CFM
900
QUIET 480
m3/h
1300
l/s
361
CFM
765
- (01 - 21) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
3-WAY OUTLET7-2-2.
MODEL : AUA45LC
Cooling / Heating
z
MODEL : AUA54LC
Cooling / Heating
z
*Air ow can be changed according to the direction in which the outlet is blocked.
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 720
m
3
/h 1690
l/s 469
CFM 995
MED 640
m
3
/h 1490
l/s 414
CFM 877
LOW 580
m
3
/h 1340
l/s 372
CFM 789
QUIET 500
m
3
/h 114 0
l/s 317
CFM 671
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 740
m
3
/h 1740
l/s 483
CFM 1024
MED 650
m
3
/h 1520
l/s 422
CFM 895
LOW 590
m
3
/h 1360
l/s 378
CFM 800
QUIET 500
m
3
/h 1140
l/s 317
CFM 671
- (01 - 22) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
FRESH AIR7-3.
MODEL : AUA45LC, AUA54LC
Installation
z
250 mm
185 mm
2.5 mm hole4
70 mm
62 mm
62 mm
Refrigerant pipe
Fresh air inlet position(A)
Fresh air inlet position
View(A)
Drain pipe
Duct frange *2
Flexible duct *2
Fan *2
Flexible duct *2
Insulation *1
*1 : In case of fresh air intake, please remove the insulation.
*2 : Locally procured parts
Fresh air Inlet position
Duct
(Inside Dia. ø70mm)
Static pressure required to take in fresh air
Duct Fan
98
49
0
10
8
6
4
2
0
0 0.1 0.2 0. 3 0.4 0.5 0.6 0.7
Air ow (m3/min)
Duct static pressure (Pa)
Duct static pressure (mmAq)
- (01 - 23) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
DUCT CONNECTION7-4.
Outlet air
z
L
Duct (Inside size. 350mm×100mm)
Duct static pressure (mmAq)
L=10m
L=5m
L=1m
Fan Speed Quiet 2-way
Fan Speed Quiet 1-way
Fan Speed High 1-way
Fan Speed High 2-way
98
49
0
10
9
8
7
6
5
4
3
2
1
0
0 2 4 6 8 10 12 14
Air ow (m3/min)
Duct static pressure (Pa)
L=10m
L=5m L=1m
Fan Speed Quiet 2-way
Fan Speed Quiet 1-way
Fan Speed High 1-way
Fan Speed High 2-way
98
49
0
10
9
8
7
6
5
4
3
2
1
0
0 120 240 360 480 600 720 8 40
AUA54LC
Air ow (m
3
/h)
Duct static pressure (Pa)
Duct static pressure (mmAq)
AUA45LC
- (01 - 24) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
PRECAUTIONS WHILE CONNECTING AIR OUTLET DUCT
z
Connect the air outlet duct at up to two locations among the four duct connection locations. (Do not connect ducts at three or more locations.)
z
Blow-off pattern when a branch duct is installed Bi-directional branching, main unit bi-directional branching
z
Once the location where the duct is to be connected is decided, always be sure to close the outlets in the same direction.
A
B
C
D
Close Close
Branch
Branch
Close
Close
Branch
Branch
DUCT (Locally procured parts)
Close the outlet here.
* Use only af ter closing the outlet of the cassette on the
side on which the duct is used, using the “Air outlet shutter plate (UTR-YDZC)”.
- (01 - 25) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL : AUA45LC
Condition
Ceiling mode : Standard
Air outlet : 4-way air outlet
MODEL : AUA54LC
Condition
Ceiling mode : Standard
Air outlet : 4-way air outlet
QUIET
HIGH
Heating
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
QUIET
HIGH
Cooling
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
HIGH
QUIET
Heating
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
HIGH
QUIET
Cooling
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
- (01 - 26) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
SOUND LEVEL CHECK POINT8-2.
Microphone
Microphone
CENTER
1.5m
- (01 - 27) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
ELECTRIC CHARACTERISTICS9.
Model name
AUA45LC AUA54LC
Power supply
Voltage V 230 ~
Frequency Hz 50
Max. operating current (Indoor unit) A 1.2
Wiring spec. (Indoor unit to outdoor unit)
Connection cable mm
2
1.5 - 2.5
Limited wiring length m 50
- (01 - 28) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
SAFETY DEVICES10.
Protection form
Model
AUA45LC AUA54LC
Circuit protection Current fuse (PCB) 3.15A 250V
Fan motor protection
Thermal protection program
110±15°C OFF
105±15°C ON
- (01 - 29) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
EXTERNAL INPUT & OUTPUT11.
Connector INPUT OUTPUT REMARKS
CN102
Control input
(Operation/Stop)
See external
input/output settings for
details.
CN103 Operation status output
CN6 Fresh air control output
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop)
The air conditioner can be remotely operated by means of the following on-site work. Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Initial starting after power turned on Starting other than at the left
Operation mode Auto changeover Mode at previous operation Set temperature 24°C Temperature at previous operation
Air ow mode AUTO Mode at previous operation Up-down air direction (swing) Standard air direction (swing OFF) Air direction at previous operation Left-right air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
z
Indoor
control PC board Connected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m. Contact capacity : 12VDC or more, 15mA or more. Please use the non-polar relays and switches.
*10 m
Operation
Stop
ON
OFF
Input signal
Indoor unit
Parts (Optional)
z
Model name
UT Y-XWZ X
Wire (External input)
- (01 - 30) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
EXTERNAL OUTPUT11-2.
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
z
Field supply
Ex.)Display
Indoor
control PC board
Connected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Max.24VDC, 10mA to less than 500mA.
*10 m
24V DC
ON
OFF
Operation
Stop
Indoor unit
Output signal
Parts (Optional)
z
Model name
UT Y-XWZ X
Wire (External output)
- (01 - 31) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
FRESH AIR CONTROL OUTPUT
A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation.
Circuit diagram example
z
Field supply
Indoor
control PC board
Connector
1
12 V
on/off
2
Signal
Relay
power
supply
* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Rated 12VDC, 50mA or less.
Ex.) Fan
Connected unit
Ex.) Relay unit
*10 m
ON
OFF
Operation
Stop
Indoor fan
Output signal
Parts (Optional)
z
Model name
UTZ-VXGA *1
Wire (Fresh air output)
Note *1: Please prepare External control set (UTD-ESC5A) when using it excluding Fresh air intake kit (UTZ-VXGA).
- (01 - 32) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
FUNCTION SETTING12.
INDOOR UNIT12-1.
SWITCH POSITION
DIP-SW SETTING
Indoor unit address setting
z
A number of indoor units can be operated at the same time using a wired remote controller. Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board. (See the following table.) The DIP switches are normally set to make the unit number 00.
(. . .Factory setting)
Indoor unit address
DIP switch No.
1 2 3 4
00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON
INDOOR UNIT
DIP SW
1
Indoor unit address setting
2
3
4
Jumper Wire
JM1
Remote controller signal code
JM2
JM3 Setting forbidden
JM3
JM2
JM1
Indoor unit Printed circuit board
MAIN PCB
- (01 - 33) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
JUMPER WIRE SETTING
Remote control unit signal code
Indoor unit setting
(

Factory setting)
Jumper wire
Remote control unit
signal code
JM 1 JM 2
Connect Connect A
Disconnect Connect B
Connect Disconnect C
Disconnect Disconnect D
- (01 - 34) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
INDOOR UNIT (Setting by remote controller)12-2.
The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
PREPARATION
Turn on the power.
* By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have
been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wired remote controller)
Setting method
z
(1) Press the set temperature buttons ( ) ( ) and fan control button simultaneously for more than 5 seconds to enter the function
setting mode.
SU
MO
TU
WE
TH FR
SA
(2) Press the SET BACK button to select the indoor unit number.
SET BACK
SUMOTUWETH FR
SA
Unit number of INDOOR UNIT
(3) Press the set time buttons to select the function number.
Function number
SUMOTUWETH FR
SA
(4) Press the set temperature buttons ( ) ( ) to select the setting value. The display ashes as shown to the right during setting value
selection.
- (01 - 35) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
(5) Press the TIMER SET button to conrm the setting. Press the TIMER SET button for a few seconds until the setting value stops
ashing. If the setting value display changes or if “- -” is displayed when the ashing stops, the setting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.)
Settin g value
SUMOTUWETH FR
SA
(6) Repeat steps 2 to 5 to perform additional settings. Press the set temperature buttons ( ) ( ) and fan control button simultaneously
again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1 minute if no operation is performed.
(7) After completing the FUNCTION SET TING, be sure to turn off the power and turn it on again.
!
CAUTION
• After turning off the power, wait 30 seconds or more before turning on it again. The FUNCTION SETTING doesn’t become effective if it doesn’t do so.
- (01 - 36) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
CONTENTS OF FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
1-1 Filter sign 1-2 Ceiling height 1-3 Outlet directions 1-4 Vertical wind direction adjustment range 1-5 Cooler room temperature correction 1-6 Heater room temperature correction 1-7 Auto Restart 1-8 Indoor Room Temperature Sensor Switching Function
1-1. Setting the lter sign
The indoor unit has a sign to inform the user that it is time to clean the lter. Select the time setting for the lter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the lter sign to be displayed, select the setting value for "No indication".
(. . .Factory setting)
Setting Description Function Number Setting Value
"Standard
(2,500 hours)"
11
00
"Long interval (4,400 hours)"
01
"Short interval
(1,250 hours)"
02
No indication 03
1-2. Setting the ceiling height
Select the setting values in the table below according to the height of the ceiling.
(. . .Factory setting)
Setting Description Function Number Setting Value
Standard
3.2m
20
00
Low ceiling
2.7m
01
High ceiling
4.2m
02
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet mode.
1-3. Setting the outlet directions
Select the setting values in the table below for using a 3-way outlet.
(. . .Factory setting)
Setting Description Function Number Setting Value
4-way
22
00
3-way 01
- (01 - 37) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
1-4. Setting the vertical wind direction adjustment range
•The use of “upward” is recommended if you wish to prevent draft. (The unit is factory-set to “00”)
•Note that the ceiling may become dirty depending on your usage condition.When this happens,
we recommend the use of the optional “PANEL SPACER KIT”.
(. . .Factory setting)
Setting Description Function Number Setting Value
Standard
23
00
upward 01
•We recommend the use of “upward” when using “High ceiling mode”.
upward
1-5. Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
(. . .Factory setting)
Setting Description Function Number Setting Value
Standard
30
00
Lower control 01
1-6. Setting the Heater Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as shown in the table below.
(. . .Factory setting)
Setting Description Function Number Setting Value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
1-7. Auto Restart
The following settings are also possible, depending on the operating conditions.
(. . .Factory setting)
Setting Description Function Number Setting Value
Yes
40
00
No 01
1-8. Indoor Room Temperature Sensor Switching Function
(Only for Wired remote controller) The following settings are needed when use the control by Wired remote controller temperature
sensor.
(. . .Factory setting)
Setting Description Function Number Setting Value
No
42
00
Yes 01
If setting value is “00”,
room temperature is controlled by the indoor unit temperature sensor. If setting value is “01”,
room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
- (01 - 38) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
WIRED REMOTE CONTROLLER12-3.
SWITCH POSITION
DIP SWITCH SETTING
1. Dual remote controller setting
Set the remote controller DIP switch No.2 according to the following table.
2. Memory backup setting
Set to ON to use batteries for the memory backup. If batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
DIP SW
1 Can not be used. (Do not change)
2 Dual remote controller setting
3 Can not be used. (Do not change)
4 Can not be used. (Do not change)
5 Can not be used. (Do not change)
6 Memory backup setting
ON
ON
OFF
1 2 3 4 5 6
Front case (back side)
Do not use this DIP Switch
DIP Switch
(

Factory setting)
Number
of remote
controller
Master unit Slave unit
DIP-SW No.2 DIP-SW No.2
1 (Normal) OFF
2 (Dual) OFF ON
(

Factory setting)
DIP-SW
No.6
Memory backup
OFF Invalidity
ON Validity
- (01 - 39) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
OPTIONAL PARTS13.
Exterior Parts name Model No. Summary
Air outlet
shutter plate
UTR-YDZC
Air outlet shutter plate is installed at the air outlet when 3-way direction is performed.
Wide panel UTG-AGYA-W
Wide panel hides the gap between the ceiling hole and the Decoration panel.
Panel spacer UTG-BGYA-W
Installation in a space of 256mm or greater is possible by using panel spacer when the height behind the ceiling is low. (Normal behind the ceiling installation height is 298mm.)
IR Receiver kit UTY-LRHA1
Unit control is performed by wireless remote controller
Wired remote
controller
UTB-UD
Unit control is performed by wired remote controller
Insulation kit
for high
humidity
UTZ-KXGA
Install when the under roof condition is expected to be the humidity of over 80% and the temperature of over 30 °C
External
connect kit
UTY-XWZX
Use to connect with various peripheral devices and air conditioner PC board.
( x 1 ) ( x 2 )
( x 1 ) ( x 2 )
External
control set
UTD-ECS5A
Use to connect with various peripheral devices and air conditioner PC board. (Set of 6)
- (01 - 40) -
CASSETTE TYPE
AU
A45-54LC
CASSETTE TYPE
AU
A45-54LC
Exterior Parts name Model No. Summary
Fresh air intake
kit
UT Z-V XGA
It can be taken in fresh air of up to 10% of “high” air volume of the indoor unit by attaching Fresh Air Intake Kit to cassette type indoor unit.
D2D_AO052E/01
2009.04.30
SINGLE TYPE :
AOA45LBTL
2. OUTDOOR UNIT
CONTENTS
2. OUTDOOR UNIT
2-1. SPECIFICATIONS
.......................................................................................... 02-01
2-2. DIMENSIONS
..................................................................................................... 02-02
2-3. REFRIGERANT CIRCUIT
......................................................................... 02-03
2-4. WIRING DIAGRAMS
.................................................................................... 02-04
2-5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
................................................................. 02-05
2-6. ADDITIONAL CHARGE CALCULATION
..................................... 02-06
2-7. AIR FLOW
............................................................................................................02-07
2-8. OPERATION NOISE
..................................................................................... 02-08
2-8-1. NOISE LEVEL CURVE
................................................................................. 02-08
2-8-2. SOUND LEVEL CHECK POINT
.................................................................02-09
2-9. ELECTRIC CHARACTERISTICS
....................................................... 02-10
2-10. SAFETY DEVICES
......................................................................................... 02-11
- (02 - 01) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
SPECIFICATIONS2-1.
Note :
Specicati ons are based on the f ollowing conditions. Coolin g : Indoor temperature of 27 ˚CD B / 19 ˚CWB.an d outdoo r temper ature of 35 ˚CDB / 24 ˚CWB. Heating : Indoor temperature of 20 ˚CD B / 15 ˚CWB.and outdoor temperature of 7 ˚CD B / 6 ˚CWB. Pipe leng th : 7.5 m, Height differe nce : 0 m.(Out door uni t - Indoor unit)
Type INVERTER HEATPUMP
Model name AOA45LBTL
Power source 230V ~ 50Hz
Available voltage range 198-264V ~ 50Hz
Starting current A 15.0
Fan
Airow rate
Cooling
m3/h
6600
Heating 6600
Type × Q'ty Propeller × 2
Motor output W 103 × 2
Sound pressure level
Cooling
dB(A)
55
Heating 56
Heat exchanger type
Dimensions (H × W × D)
mm
1260 × 900 × 36.4
Fin pitch 1.30
Rows x Stages 2 × 60
Pipe type Copper
Fin type Aluminium
Compressor
Type × Q'ty Twin Rotary × 1
Motor output W 3750
Refrigerant
Type R410A
Charge g 3350
Refrigerant oil Type POE
Enclosure
Material Steel sheet
Colour
BEIGE
( Approximate colour of MUNSELL 10 YR 7.5 / 1.0 )
Dimensions ( H×W×D)
Net
mm
1290 × 900 × 330
Gross 1430 × 1050 × 445
Weight
Net
kg (lb.)
98 ( 216 )
Gross 107 ( 236 )
Connection
pipe
Size
Liquid
mm
Ø 9.52 (Ø 3/8 in.)
Gas Ø 15.88 (Ø 5/8 in.)
Method Flare
Max. length
m
50(chargeless:20)
Max. height difference 30
Operation range
Cooling
˚C
-15 to 46
Heating -15 to 24
- (02 - 02) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
DIMENSIONS2-2.
MODEL : AOA45L
(Unit : mm)
MOUNTING POSITION
900
1290
77 31
21
370
9
400
650
151
99
196
170
4-Ø12mm hole
12330
Air flow
Drain cap mounting places
Top view
Side view
Bottom view
Front view
When there are obstacles at the back or front side.
When there are obstacles at the back and front sides.
When there are obstacles at the back, side(s), and
top.
When there are obstacles at the back side with the installation of more than one unit.
100 mm or more
600 mm or more
250 mm or more
250 mm or more
300 mm or more
250 mm or more
(Service space)
300 mm or more
100 mm or more
100 to 300 mm *
600 to 1000 mm
* If the spac e is larg er than th at is stated, the co nditio n will be the same as t hat there are no obstacles.
- (02 - 03) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
REFRIGERANT CIRCUIT2-3.
MODEL : AOA45L
- (02 - 04) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
WIRING DIAGRAMS2-4.
MODEL : AOA45L
- (02 - 05) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 2-5. AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL : AOA45L
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
30 0.893 0.890 0.870
20 0.919 0.908 0.905 0.885
10 0.979 0.934 0.923 0.920 0.899
7.5 0.988 0.983 0.938 0.927 0.924 0.903
5 1.001 0.992 0.987 0.942 0.931 0.927 0.907
0 1.009 1.000 0.995 0.949 0.938 0.935 0.914
2
Indoor unit is under
than outdoor unit
-5 1.009 1.000 0.995 0.949 0.938 0.935 0.914
-7.5 1.000 0.995 0.949 0.938 0.935 0.914
-10 0.995 0.949 0.938 0.935 0.914
-20 0.949 0.938 0.935 0.914
-30 0.938 0.935 0.914
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
30 0.971 0.950 0.927
20 0.985 0.971 0.950 0.927
10 1.016 0.985 0.971 0.950 0.927
7.5 1.000 1.016 0.985 0.971 0.950 0.927
5 0.978 1.000 1.016 0.985 0.971 0.950 0.927
0 0.978 1.000 1.016 0.985 0.971 0.950 0.927
2
Indoor unit is under
than outdoor unit
-5
0.973 0.995
1.011
0.980 0.966
0.945 0.923
-7.5
0.993
1.009
0.978 0.963
0.943 0.920
-10 1.006 0.975 0.961 0.940 0.918
-20 0.966 0.951 0.931 0.909
-30 0.942 0.921 0.899
Outdoor unit
Indoor unit
Connec tion pipe
2 Indoor unit is under than outdoor unit.
H
Indoor unit
Outdoor unit
Connec tion pipe
1 Indoor unit is upper than outdoor unit.
H
Height difference H
- (02 - 06) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
ADDITIONAL CHARGE CALCULATION2-6.
MODEL : AO
A45L
Refrigerant charge
z
Refrigerant type R410A
Refrigerant amount g 3350
Pipe length m ~ 20 30 40 50
50g/m
Additional charge g 0 (Chargeless) +500 +1000 +1500
- (02 - 07) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
AIR FLOW2-7.
MODEL : AOA45L
Cooling
z
Heating
z
Number of
rotations
(r.p.m)
Air ow
Upper fan 850
m
3
/h 6600
l/s 1833
Lower fan 750
CFM 3884
Number of
rotations
(r.p.m)
Air ow
Upper fan 850
m
3
/h 6600
l/s 1833
Lower fan 750
CFM 3884
- (02 - 08) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
OPERATION NOISE2-8.
2-8-1. NOISE LEVEL CURVE
MODEL : AOA45L
Heating
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Cooling
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
- (02 - 09) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
2-8-2. SOUND LEVEL CHECK POINT
Microphone
Microphone
Air Fiow
1m
- (02 - 10) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
ELECTRIC CHARACTERISTICS2-9.
*1) Wiring Spec. :
Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length :
This is the wiring length in case voltage descent is less than 2%. When the wiring length becomes long, please select the wiring of a more larger diameter.
Model Name AOA45L
Power Supply
Voltage V 230 ~
Frequency Hz 50
Max. Operating Current A 20.0
Starting Current A 15.0
*1) Wiring Spec.
Main Fuse (Circuit breaker) Current A 30
Power Cable mm
2
5.3 - 6.0
*2)Limited wiring length m 17
- (02 - 11) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
SAFETY DEVICES2-10.
Protection form
Model
AOA45L
Circuit protection
Current fuse (NEAR THE TERMINAL) 25A 250V
Current fuse (NEAR THE TERMINAL) 10A 250V
Current fuse (MAIN PRINTED CIRCUIT BOARD) 5A 250V
Current fuse (MAIN PRINTED CIRCUIT BOARD) 3.15A 250V
Fan motor protection Thermal protection program
OFF : 130±20°C
ON : 100±20°C
High Pressure Protection High Pressure Switch
OFF : 4.2±0.1MPa ON : 3.2±0.15MPa
Compressor protection
Thermal protection program (COMPRESSOR TEMP.)
OFF : 110°C
ON : 80°C
Thermal protection program (DISCHARGE TEMP.)
OFF : 115°C
ON : After 7 minutes
DTR_AO081E_01
2011.03.01
SINGLE TYPE :
AOA45LCTL
AOA54LCTL
2. OUTDOOR UNIT
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
2. OUTDOOR UNIT
CONTENTS
1. SPECIFICATIONS
······························································································ 02 - 01
2. DIMENSIONS
········································································································ 02 - 02
3. INSTALLATION PLACE
················································································ 02 - 03
3-1. SINGLE OUTDOOR UNIT INSTALLATION
················································· 02 - 03
3-2. MULTIPLE OUTDOOR UNIT INSTALLATION
············································ 02 - 04
3-3. OUTDOOR UNIT INSTALLATION IN MULTI ROW
··································· 02 - 04
4. REFRIGERANT CIRCUIT
············································································ 02 - 05
5. WIRING DIAGRAMS
······················································································· 02 - 06
6. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
····································································· 02 - 07
7. ADDITIONAL CHARGE CALCULATION
········································ 02 - 09
8. AIR FLOW
················································································································ 02 - 10
9. OPERATION NOISE
·························································································02 - 11
9-1. NOISE LEVEL CURVE
························································································02 - 11
9-2. SOUND LEVEL CHECK POINT
········································································02 - 12
10. ELECTRIC CHARACTERISTICS
···························································02 - 13
11. SAFETY DEVICES
·····························································································02 - 14
12. EXTERNAL INPUT & OUTPUT
·······························································02 - 15
12-1. EXTERNAL INPUT
································································································02 - 15
12-2. EXTERNAL OUTPUT
···························································································02 - 17
13. FUNCTION SETTING
······················································································ 02 - 19
13-1. FIELD SETTING SWITCHES
············································································ 02 - 19
13-2. SETTING METHOD
····························································································· 02 - 20
13-2-1. LOW NOISE MODE ······················································································· 02 - 20
13-2-2. PEAK CUT MODE ························································································· 02 - 21
14. OPTIONAL PARTS
··························································································· 02 - 22
- (02 - 01) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
SPECIFICATIONS1.
Note :
Speci cations are base d on the fol lowing c onditi ons. Coolin g : Indoor t emperat ure of 27 °CD B / 19 °CWB.a nd outdo or temper ature of 3 5 °CDB/ 24 °CWB. Heating : I ndoor te mperat ure of 20 °CD B / 15 °CWB.a nd outdoo r temper ature of 7 °C DB/6 °CW B. Pipe leng th : 5 m, Heig ht diffe rence : 0 m. (Outdoor u nit - Indo or unit)
Model na me AOA45LCTL AOA54LC TL Power source 230V~ 50 Hz Available voltage r ange 198 -264V~ 50Hz Starting cur rent A 18.9 20.9
Fan
Airow rate
Cooling
(m
3
/h)
6,750 6,750
Heating 6,200 6,850 Type × Q'ty P ropeller × 2 Motor out put W 10 4 104
Sound pressure level
Cooling
dB(A)
55 55
Heating 55 57
Heat exchanger ty pe
Dimensions (H × W × D)
mm
1260 × 900 × 36.4
Fin pitch 1.30
Rows x Stag es 2 × 60
Pipe typ e Copper
Fin type
Type (Material) C orrugate (Alu minium) Surfa ce treatment Cor rosion resist ance (Blue n)
Compressor
Type × Q'ty Twin Rotar y × 1 Motor out put W 2100
Refrigerant
Typ e R410 A
Charge g 3350
Refrigerant oil Ty pe RB68
Enclosu re
Material Steel she et
Colour
BEIGE
( Approximate colour of MU NSELL 10YR 7.5 / 1.0 )
Dimensions ( H×W×D)
Net
mm
1290 × 90 0 × 330
Gross 1430 × 1050 × 4 45
Weight
Net
kg(lbs.)
86 (190)
Gross 94 (208)
Connec tion pipe
Size
(Standard)
Liquid
mm
Ø 9.52 (Ø 3/8 in.)
Gas Ø 15.88 (Ø 5/8 in.) Method Flare Pre- charge length
m
20
Max. length 50 Max. height dif ferenc e 30
Operat ion range
Cooling
°C
-15 to 46
Heating -15 to 24
- (02 - 02) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
DIMENSIONS2.
MODEL : AOA45LC, AOA54LC
(Unit : mm)
45
66
(
370
)
38
(Liquid)
46
(
Gas
)
40
650 11 9132
1290
900
21
9
Ø28
(Cable port)
Pipe port
87
131
25
543
(
Gas valve
)
540
(Liquid valve)
Ø28
(Cable port)
3-way valve
(
Gas
)
3-way valve
(
Liquid
)
Terminal blocks
21
50
330
31
12
Ø28
(Cable port)
21
55
50
156
112
Ø28
(Cable port)
Pipe port
A
188
265
302
400
51.5 440
625
330
31
89
95
120
50
95
167
21
67
Ø28
(Cable port)
Ø28 (Cable port)
Pipe port
Front view
Bottom view
Side view Rear view
Detail A
1446
1654
Pipe & cable port
Top view
- (02 - 03) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
INSTALLATION PLACE3.
SINGLE OUTDOOR UNIT INSTALLATION3-1.
WHEN THE UPWARD AREA IS OPEN
(Unit : mm)
Obstacles at rear only
Obstacles at rear and sides only
Obstacles at front only
150
200
200
300
1000 or more
Obstacles at front and rear only
1000 or more
150
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA
(Unit : mm)
Obstacles at rear and above only
Obstacles at rear, sides, and above only
Max. 500
300
1000
Max. 500
500
250
250
1500
- (02 - 04) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
MULTIPLE OUTDOOR UNIT INSTALLATION3-2.
WHEN THE UPWARD AREA IS OPEN
(Unit : mm)
Obstacles at rear only Obstacles at front only Obstacles at front and rear
only
300
1500 or more
500
1500 or more
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA
(Unit : mm)
Obstacles at rear and above only
1500
1500
500
Max. 300
OUTDOOR UNIT INSTALLATION IN MULTI ROW3-3.
(Unit : mm)
Single parallel unit arrangement Multiple parallel unit arrangement
1000
2000 or more
600
150
3000 or more
600
1500
500
- (02 - 05) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
REFRIGERANT CIRCUIT4.
MODEL : AOA45LC, AOA54LC
- (02 - 06) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
WIRING DIAGRAMS5.
MODEL : AOA45LC, AOA54LC
- (02 - 07) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 6.
AND HEIGHT DIFFERENCE
MODEL : AOA45LC
Height difference H
HH
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Outdoor unit
Outdoor unit
Connection pipe
Indoor unit
Indoor unit
Connection pipe
HEATING
Pipe length (m)
5 7. 5 10 20 30 40 50
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
30 - - - - 0.978 0.968 0.958
20 - - - 0.988 0.978 0.968 0.958
10 - - 0.998 0.988 0.978 0.968 0.958
7. 5 - 1.000 0.998 0.988 0.978 0.968 0.958
5 1.000 1.000 0.998 0.988 0.978 0.968 0.958
0 1.000 1.000 0.998 0.988 0.978 0.968 0.958
Û
2
Indoor unit is
under than
outdoor unit.
-5 0.998 0.995 0.993 0.983 0.973 0.963 0.953
-7. 5 - 0.993 0.991 0.9 81 0.971 0.9 61 0.951
-10 - - 0.988 0.978 0.968 0.958 0.948
-20 - - - 0.968 0.958 0.949 0.939
-30 - - - - 0.949 0.939 0.929
COOLING
Pipe length (m)
5 7. 5 10 20 30 40 50
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
30 - - - - 0.879 0.846 0.814
20 - - - 0.926 0.893 0.861 0.828
10 - - 0.975 0.942 0.908 0.875 0 . 8 41
7. 5 - 0.988 0.979 0.946 0.912 0.878 0.845
5 0.992 0.992 0.983 0.949 0.916 0.882 0.848
0 1.000 1.000 0.991 0.957 0.923 0.889 0.855
Û
2
Indoor unit is
under than
outdoor unit.
-5 1.000 1.000 0.991 0.957 0.923 0.889 0.855
-7. 5 - 1.000 0.991 0.957 0.923 0.889 0.855
-10 - - 0.991 0.957 0.923 0.889 0.855
-20 - - - 0.957 0.923 0.889 0.855
-30 - - - - 0.923 0.889 0.855
- (02 - 08) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
MODEL : AOA54LC
Height difference H
HH
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Outdoor unit
Outdoor unit
Connection pipe
Indoor unit
Indoor unit
Connection pipe
HEATING
Pipe length (m)
5 7. 5 10 20 30 40 50
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
30 - - - - 0.978 0.968 0.958
20 - - - 0.988 0.978 0.968 0.958
10 - - 0.998 0.988 0.978 0.968 0.958
7. 5 - 1.000 0.998 0.988 0.978 0.968 0.958
5 1.000 1.000 0.998 0.988 0.978 0.968 0.958
0 1.000 1.000 0.998 0.988 0.978 0.968 0.958
Û
2
Indoor unit is
under than
outdoor unit.
-5 0.998 0.995 0.993 0.983 0.973 0.963 0.953
-7. 5 - 0.993 0.991 0.981 0.971 0.961 0.9 51
-10 - - 0.988 0.978 0.968 0.958 0.948
-20 - - - 0.968 0.958 0.949 0.939
-30 - - - - 0.949 0.939 0.929
COOLING
Pipe length (m)
5 7. 5 10 20 30 40 50
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
30 - - - - 0.871 0.837 0.803
20 - - - 0.921 0.886 0. 851 0.816
10 - - 0.971 0.936 0.900 0.865 0.830
7. 5 - 0.988 0.975 0.940 0.904 0.868 0.833
5 0.992 0.992 0.979 0.943 0.908 0.872 0.836
0 1.000 1.000 0.987 0.951 0.915 0.879 0.843
Û
2
Indoor unit is
under than
outdoor unit.
-5 1.000 1.000 0.987 0.951 0.915 0.879 0.843
-7. 5 - 1.000 0.987 0.951 0.915 0.879 0.843
-10 - - 0.987 0. 9 51 0.915 0.879 0.843
-20 - - - 0.951 0.915 0.879 0.843
-30 - - - - 0.915 0.879 0.843
- (02 - 09) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
ADDITIONAL CHARGE CALCULATION7.
MODEL : AOA45LC, AOA54LC
REFRIGERANT CHARGE
z
Refrigerant type R 410A
Refrigerant amount g 3,350
Total pipe length m 20 or less 30 40 50 (MAX)
40g/m
Additional charge g 0 400 800 1200
- (02 - 10) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
AIR FLOW8.
MODEL : AOA45LC, AOA54LC
Cooling
z
Heating
z
MODEL
Number of
rotations
(r.p.m.)
Air ow
AOA45LC
Upper fan 850
m
3
/h 6750
l/s 1875
Lower fan 800
CFM 3974
AOA54LC
Upper fan 850
m
3
/h 6750
l/s 1875
Lower fan 800
CFM 3974
MODEL
Number of
rotations
(r.p.m.)
Air ow
AOA45LC
Upper fan 780
m
3
/h 6200
l/s 172 2
Lower fan 750
CFM 3650
AOA54LC
Upper fan
850
m3/h
6850
l/s
1903
Lower fan
830
CFM
4033
- (02 - 11) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
OPERATION NOISE9.
NOISE LEVEL CURVE9-1.
MODEL : AOA45LC
Cooling
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,00 0 4,00 0 8,000
MODEL : AOA54LC
Cooling
z
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
- (02 - 12) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
SOUND LEVEL CHECK POINT9-2.
Microphone
1m
Microphone
Air Flow
- (02 - 13) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
ELECTRIC CHARACTERISTICS10.
Model name AOA45LC AOA54LC
Power supply
Voltage V 230 ~ Frequency Hz 50
*1) Max. operating current A 22.5 23.5
*2) Wiring spec.
Main fuse (Circuit breaker) Current
A 30
Power cable mm
2
6.0
*1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring spec. : Selected sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
- (02 - 14) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
SAFETY DEVICES11.
Protection form
Model
AOA45LC AOA54LC
Circuit protection
Current fuse (Filter printed circuit board)
10A 250V, 3.15A 250V
Current fuse (Main printed circuit board)
3.15A 250V
Fan motor protector Thermal protector
OFF : 150±15°C
ON : 120±15°C
Compressor protection
Thermal protection program (Compressor temp.)
OFF : 108°C
ON : 80°C
Thermal protection program (Discharge temp.)
OFF : 110°C
ON : After 7 minutes
High pressure protection Pressure switch
OFF : 4.2±0.1MPa ON : 3.2±0.15MPa
Low pressure protection Pressure sensor
OFF : 0.12MPa
ON : 0.15MPa
- (02 - 15) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
EXTERNAL INPUT & OUTPUT12.
EXTERNAL INPUT12-1.
ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specied by external signal.
LOW NOISE MODE
The following reduces the operating sound of the outdoor unit from the normal sound. • The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial timer or ON/OFF switch to a connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature condition, etc.
Circuit diagram example
z
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*10m
Connected unit
Ex.) Switch
Contact capacity : 24VDC or more, 10mA or more.
* Make the distance from the PC board to the connected unit within 10m.
Use the following parts and construct a circuit as shown above. Input Signal∙∙∙ON : Low noise mode, Input Signal∙∙∙OFF : Normal operation
* Set the "Low noise mode" level, refer to "13.FUNCTION SETTING".
ON
OFF
ON
OFF
Input Signal
Low noise mode
Parts (Optional)
z
Parts name External connect kit
Model name UT Y-XW Z XZ3
Input Output Connector Remarks
Low noise mode CN10
See external
input/output settings
for details.
Peak cut mode CN11
Error status CN12
Compressor status CN13
- (02 - 16) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on- site work. The air conditioner is set to the Peak cut mode when closing the contact input of a commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
z
Contact capacity : 24VDC or more, 10mA or more.
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*10m
Connected unit
Ex.) Switch
* Make the distance from the PC board to the connected unit within 10m.
Use the following parts and construct a circuit as shown above. Input Signal∙∙∙ON : Peak cut mode, Input Signal∙∙∙OFF : Normal operation
*Set the "Peak cut mode" level, refer to "13.FUNCTION SETTING".
ON
OFF
ON
OFF
Input Signal
Peak cut mode
Parts (Optional)
z
Parts name External connect kit
Model name UT Y-XW Z XZ3
- (02 - 17) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
EXTERNAL OUTPUT12-2.
ERROR STATUS OUTPUT
An air conditioner error status signal is produced when a malfunction occurs.
Circuit diagram example
z
1) Power supply
●Voltage (Chart sign=Vcc) : DC 24V or less
2) Load
● Load : DC 500mA or less is recommended
Signal
Outdoor unit
control PC board
Connected unit
Connector
1
2
Field supply
*10m
Vcc
+
+
-
Load
Vcc
Power supply
* Make the distance from the PC board to the connected unit within 10m.
Error
Normal
ON
OFF
Error status
Output signal
Parts (Optional)
z
Parts name External connect kit
Model name UT Y-XW Z XZ3
- (02 - 18) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
COMPRESSOR STATUS OUTPUT
Compressor operation status signal is produced when the compressor is running.
Circuit diagram example
z
1) Power supply
●Voltage (Chart sign=Vcc) : DC 24V or less
2) Load
● Load : DC 500mA or less is rec ommended
Signal
Outdoor unit
control PC board
Connected unit
Connector
1
2
Field supply
*10m
Vcc
+
+
-
Load
Vcc
Power supply
* Make the distance from the PC board to the connected unit within 10m.
ON
OFF
Operation
Stop
Compressor
Output signal
status
Parts (Optional)
z
Parts name External connect kit
Model name UT Y-XW Z XZ3
- (02 - 19) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
FUNCTION SETTING13.
FIELD SETTING SWITCHES13-1.
The positions of the switches on the outdoor unit control board are shown in the gure below.
FUNCTIONS
Caution
Discharge the static electricity from your body before setting up the push buttons.
Never touch the terminals or the patterns on the parts that are mounted on the board.
Terminal blocks
Push buttons
LED lamps
Display lamp Function or operation method
(1) POWER / MODE Green
Lights on while power on. Local set ting in outdoor unit or error code is displayed with blink.
(2) ERROR Red Blinks during abnormal operation.
(3) PUMP DOWN (L1) Orange
Lights on during pump down operation.
(4) LOW NOISE MODE
(L2,L3)
Orange
Lights on during “Low noise” mode when local setting is activated. (Lighting pattern of L2 and L3 indicates low noise level)
(5) PEAK CUT MODE
(L4,L5,L6)
Orange
Lights on during “Peak cut” mode when local setting is activated. (Lighting pattern of L4, L5 and L6 indicates peak cut level)
Button Function or operation method
SW1 MODE
To switch between “Local setting” and “Error code display”.
SW2 SELECT
To switch between the individual “Local settings” and the “ Error c ode displays”.
SW3 ENTER
To x between the individual “Local settings” and the “Error code displays”.
SW4 EXIT
To return to “Operation status display”.
SW5
PUMP
DOWN
To start the pump down operation.
SW1
SW2
SW3 SW4 SW5
(1)
(2)
(3)
(4)
(5)
LED lamp
- (02 - 20) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
SETTING METHOD13-2.
Stop the operation of air conditioner before this setting.
LOW NOISE MODE13-2-1.
SW1
SW2
SW3 SW4 SW5
LED lamp part
(1) Switch to “Local setting mode” by pressing [MODE] button (SW1) for 3 seconds or more.
(2) Conrm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW3).
POWER
MODE
ERROR
(L1) (L2) (L3) (L4) (L5) (L6)
PUMP
DOWN
LOW NOISE PEAK CUT
Blinks (9 times)
Sign “ ” : Lights off
(3) Press [SELECT] button (SW2), and adjust LED lamp as shown below. (Current setting is displayed)
(L2)
(L3)
LOW NOISE
Blink
LOW NOISE
MODE
(4) Press [ENTER] button (SW3).
(L2) (L3)
LOW NOISE
LOW NOISE
MODE
Sign “ ” : Lights on
(5) Press [SELECT] button (SW2), and adjust LED lamp as shown in below gure.
PEAK CUT
MODE 1
MODE 2
Blink
Blink
(L4) (L5) (L6)
The noise of MODE2 is lower than one of MODE1.
(6) Press [ENTER] button (SW3) and x it.
PEAK CUT
MODE 1
MODE 2
(L4) (L5) (L6)
(7) Return to “Operating status display (Normal operation)” by pressing [EXIT] button (SW4).
• In case of missing how many times [SELECT] and [ENTER] button are pressed, restart from the beginning of operation procedure after returning to “Operation status display (normal operation)” by pressing the [EXIT] button once.
- (02 - 21) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
PEAK CUT MODE13-2-2.
SW1
SW2
SW3 SW4 SW5
LED lamp part
(1) Switch to “Local setting mode” by pressing [MODE] button (SW1) for 3 seconds or more.
(2) Conrm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW3).
POWER
MODE
ERROR
(L1) (L2) (L3) (L4) (L5) (L6)
PUMP
DOWN
LOW NOISE PEAK CUT
Blinks (9 times)
Sign “ ” : Lights off
(3) Press [SELECT] button (SW2), and adjust LED lamp as shown below. (Current setting is displayed)
(L2)
(L3)
LOW NOISE
Blink
PEAK CUT
MODE
(4) Press [ENTER] button (SW3).
(L2) (L3)
LOW NOISE
PEAK CUT
MODE
Sign “ ” : Lights on
(5) Press [SELECT] button (SW2), and adjust LED lamp as shown in below gure.
100% of rated input ratio
75% of rated input ratio
50% of rated input ratio
0% of rated input ratio
Blink
Blink Blink
Blink
Blink
PEAK CUT
(L4) (L5) (L6)
(6) Press [ENTER] button (SW3) and x it.
100% of rated input ratio
75% of rated input ratio
50% of rated input ratio
0% of rated input ratio
PEAK CUT
(L4) (L5) (L6)
(7) Return to “Operating status display (Normal operation)” by pressing [EXIT] button (SW4).
• When pressed number is lost during operation, restart from the beginning of operation procedure after returning
to “Operation status display (normal operation)” by pressing the [EXIT] button once.
- (02 - 22) -
OUTDOOR UNIT
AO
A45-54LC
OUTDOOR UNIT
AO
A45-54LC
OPTIONAL PARTS14.
Exterior Parts name Model No. Summary
External connect
kit
UTY-XWZXZ3
Use to operate the External input and output function of Outdoor unit.
Loading...