Fujitsu Airstage J-II Service Manual

Page 1
Small VRF system
for light commercial and home use
Page 2
Page 3
CONTENTS
1. TEST RUN
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS.............................
1-2 TEST RUN METHOD..................................................................................................
1-2-1 Check Items Before Power ON............................................................................
1-2-2 Check Items After Power ON...............................................................................
1-2-3 Automatic address setting procedure for Signal amplifiers.................................. 01-06
1-2-4 Automatic address setting procedure for indoor units..........................................
1-2-5 Indoor unit connection check procedure ............................................................. 01-08
1-2-6 Test run from the outdoor unit ............................................................................ 01-09
1-2-7 Test run from the Remote controller .................................................................... 01-09
1-3 TEST RUN CONTROL................................................................................................
1-4 Field Setting And Monitor Mode List....................................................................... 01-11
2. OUTDOOR UNIT OPERATION CONTROL
01-01 01-03 01-03 01-04
01-07
01-10
2-1 INPUT / OUTPUT LIST..............................................................................................
2-2 COMPRESSOR OPERATION....................................................................................
2-2-1 Operation / Stop Condition.................................................................................
2-2-2 Capacity Control.................................................................................................
2-2-3 Speed Range of Start,Stop,and Operation..........................................................
2-3 FAN CONTROL..........................................................................................................
2-3-1 Cooling Operation...............................................................................................
2-3-2 Heating Operation...............................................................................................
2-3-3 Low noise mode..................................................................................................
2-3-4 Other Control.......................................................................................................
2-4 EXPANSION VALVE CONTROL...............................................................................
2-5 SPECIAL OPERATION..............................................................................................
2-5-1 Oil Recovery Operation......................................................................................
2-5-2 Pre-Heat Operation............................................................................................
2-5-3 Defrost Operation Control..................................................................................
2-6 PROTECTIVE FUNCTION........................................................................................
2-6-1 Protective Function List......................................................................................
02-01 02-02
02-02
02-02 02-03
02-05 02-05 02-06
02-07
02-08
02-08
02-09 02-09 02-10
02-10
02-11 02-11
Page 4
3. INDOOR UNIT OPERATION
CONTENTS
3-1 FAN CONTROL..........................................................................................................
3-1-1 Fan Speed Setting...............................................................................................
3-1-2 "AUTO" Position...................................................................................................
3-2 MASTER CONTROL..................................................................................................
3-2-1 Operation Mode Control.......................................................................................
3-2-2 Auto Changeover.................................................................................................
3-2-3 "COOL" Position..................................................................................................
3-2-4 "HEAT" Position..................................................................................................
3-3 LOUVER CONTROL..................................................................................................
3-4 ELECTRONIC EXPANSION VALVE CONTROL......................................................
3-5 DRAIN PUMP OPERATION.......................................................................................
3-6 FUNCTION..................................................................................................................
3-6-1 Auto Restart.........................................................................................................
3-6-2 Icing Protection Control.......................................................................................
3-6-3 Oil Recovery Operation.......................................................................................
3-7 TIMER CONTROL......................................................................................................
3-7-1 Wireless Remote Controller................................................................................
03-01 03-01
03-01 03-02 03-02 03-04 03-05 03-05
03-06
03-09 03-09 03-10 03-10 03-10 03-10 03-11 03-11
3-7-2 Group Remote Controller..................................................................................... 03-13
3-7-3 Wired Remote Controller..................................................................................... 03-15
4. TROUBLE SHOOTING
4-1 NORMAL OPERATION..............................................................................................
4-1-1 Indoor Unit Display..............................................................................................
4-1-2 Outdoor Unit Display...........................................................................................
4-2 ABNORMAL OPERATION.........................................................................................
4-2-1 Indoor Unit Display..............................................................................................
4-2-2 Outdoor Unit Display...........................................................................................
4-2-3 Error Code List for Outdoor Unit..........................................................................
4-2-4 Remote Controller Display...................................................................................
4-2-5 Error Code List for Simple and Wired Remote Controller...................................
4-2-6 Error Code List for Group Remote Controller......................................................
4-2-7 Trouble Level of System.....................................................................................
4-2-8 Error History Mode..............................................................................................
4-3 TROUBLE SHOOTING.............................................................................. ...............
04-01 04-01
04-02
04-03 04-03 04-04 04-05 04-06
04-07
04-07
04-08 04-10
04-11
4-3-1 Trouble Shooting With Error Code (INDOOR UNIT)...........................................
4-3-2 Trouble Shooting With Error Code (OUTDOOR UNIT).......................................
4-3-3 Trouble Shooting for Optional Parts....................................................................
4-4 SERVICE PARTS INFORMATION............................................................................ 04-84
04-11 04-22 04-63
Page 5
CONTENTS
5. APPENDING DATA
5-1 REFRIGERANT CIRCUIT..........................................................................................
05-01
5-2 WIRING DIAGRAM....................................................................................................
5-2-1 Indoor Unit............................................................................................................
5-2-2 Outdoor Unit.........................................................................................................
5-3 CHARACTERISTICS OF SENSORS........................................................................
5-3-1 Pressure sensor..................................................................................................
5-3-2 Thermistor resistance..........................................................................................
5-3-3 Saturation temperature and saturation pressure tables (R410A)........................
5-3-4 Temperature and pressure of refrigerant (Graph)...............................................
6. DISASSEMBLY PROCESS
05-02
05-02
05-18
05-19
05-19
05-20 05-21 05-22
Page 6
Page 7
1. TEST RUN
Page 8
Page 9
1. TEST RUN
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
Before execution
Location decision
Confirmation of Refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparation before execution
Execution 1/2
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Outdoor unit foundation work
Execution procedure and precautions Reason
Do not install the units in the place not recommended in the installation manual.
Check the characteristics of the refrigerant used and grasp the special features of the refrigerant. If refrigerant must be charged, always charge the refrigerant specified for the product.
*Confirm the product design pressure. < R410A 4.20MPa >
Prepare the design for the system
Use new refrigerant piping of the thickness specified by the
1
D&T manual.
2
Since R410A dedicated tools are necessary, prepare them in advance.
3
Absolutely avoid use of existing piping. If use of existing piping is unavoidable, the piping must be cleaned.
Always use a level and keep the indoor unit level. If the equipment is tilted toward the drain port, install it so that the tilt is within 10mm. Excessive tilt will cause water leakage.
When performing piping work, observe the following items so that the inside of the piping is clean and air tight.
1
Use pipe that is not dirty inside. Confirm the design for the piping ( Diameter, Thickness )
2 3
When the pipe is left standing, protect it. Confirm the angle of separation tube and header correctry.
4
Finish flaring exactly.
5
Confirm the width across flats dimension and shape of flare nuts.
6
Always blow nitrogen while brazing.
7
Perform flushing before connecting the equipment.
8
Always make the downward slope of the drain pipe 1/100 or
1
greater and make the horizontal length within 20m. Use hard polyvinylchloride pipe as the drain pipe.
2
Support the drain pipe between 1.5 to 2.0m.
3
Use pipe of 1 rank up (VP30 or greater) as central piping.
4
Select the size of the heat insulating material according to the ambient temperature and relative humidity of the refrigerant. Use a heat insulating material having a heat conductivity of 0.043W/ (m.k) or less.
The performance may drop significantly due to the protection controlling
Use of a refrigerant other than the specified refrigerant will invite equipment trouble
Secure the necessary pressure resistance.
Prevention of water leakage
Foreign matter, water, etc. in the piping will cause faulty cooling and compressor trouble. Incorrect pipe diameter will cause faulty cooling Incorrect angle of separation tube or header will be cause poor cooling or refrigerant noise problem Refrigerant leakage will cause low performance and abnormal stopping
Prevention of water leakage
Prevention of water leakage
Outdoor unit installation
Refrigerant piping connection work
Air tightness test
Vacuum drying
When making flare connections always use a torque wrench and tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a
1
reverse flow check adaptor to a conventional vacuum pump and use. Pump down sufficiently.
2
Approximately 1 hour or longer after -0.10MPa reached. Allow to stand for approximately 1 hour after stopping the vacuum pump and confirm that the needle does not return. Air purging using refrigerant is strictly prohibited.
3
Vaccuming mode
*
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vaccuming mode, the refrigerant address setting has to be finished.
Refrigerant leakage will cause low performance and abnormal stopping.
Refrigerant leakage will cause low performance and abnormal stopping.
Mixing in of vacuum pump oil by reverse flow will cause equipment trouble. recommend the vacuuming mode
When the [vacuuming mode] is set, <Push switch setting, F3:21> EEV of connected all indoor units opens. So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units and the outdoor unit, [vacuuming mode] is released.
01-01
Page 10
Execution 2/2
Execution procedure and precautions Reason
Addition refrigerant charging
Gas leak test
Initial setting
Confirm the additional refrigerant amount with the installation
1
manual, etc. Always take the R410A refrigerant from the cylinder liquid phase
2
and charge it using the gas phase. (Do not lay a cylinder with siphon pipe on its side.)
3
Use an R410A dedicated gauge manifold and charging hose. Charge refrigerant using the liquid pipe.
4
When the defined amount of refrigerant cannot charge using the
5
liquid pipe, charge refrigerant using the gas pipe while opearing the cooling test run. Charge refrigerant bit by bit with cautious operation of valve for the liquid refrigerant back prevention.
Use an R410A dedicated leak tester to check for gas leaks.
1
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
2
Confirm the DIP SW setting SET 1: Factory setting, SET 2 : All OFF, SET 3 : All OFF, SET 4: Factory setting
Confirm the Terminal resister setting
3
SET 5-4 OFF: Disable, ON: Enable
[Note] Perform in the power OFF state.
If taken from the air phase, since the composition of the refrigerant which is charged will change, low performance and abnormal stop will occur easily. Prevent erroneous sealing in of refrigerant.
A leak tester for other than R410A cannot detect leaks.
Dual address setting No. is not allowed in one network.
If the DIP SW setting is wrong, the sys­ tem may not work correctly
If the Terminal resister setting is wrong, the system may detect transmission error
Piping length setting
Address setting for Signal Amp
- When using signal Amps -
Address setting for Indoor unit
Set according to the length of the connection piping. Set to "Standard (40 to 65m)" at the factory. Set using the push button SW on the outdoor unit main PCB. < Refer to the Page 01-16 Setting mode F2-00 > Set the pipe length to be the nearest indoor unit from the outdoor unit
When the setting is not same as the real piping length, the system may not work correctly.
If the pipe length is set as the farthest indoor unit, the nearest operating indoor unit may be stopped the operation by the icing up protection as by over cooling.
[Note] Perform in the power ON state after all indoor units have stopped operation
When setting the address of Signal amplifier, please refer to the installation manual of the signal amplifier. The address setting can be set by automatically from 1 outdoor unit on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Dual address setting No. is not allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Set the refrigerant circuit address and indoor unit address. Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch PCB) or from a remote controller or from a push button SW on the outdoor unit Main PCB < Automatic address setting, Refer to the Page 01-07 Setting mode F3-11>
Dual address setting No. is not allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Indoor unit connection check
Test run & adjustment
Turnover & explanation of operation
Before starting the system, check on the number of indoor units and the total capacity. < Refer to the Page 01-08 Setting mode F3-12 >
Normal operation will not be possible without performing the indoor unit connection check.
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state after all indoor units have stopped operation.
01-02
Page 11
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
Power
source
Outdoor
unit
Check contentsProcedure
Circuit breaker capacity
Type of power source wiring
Supply power source
Wiring on terminal blocks
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Judgement standard
Outdoor unit: 32A ( AJ*A36,45,54LALH )
Indoor unit: 20A
Leakage current: 30mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit: 6mm
Indoor unit: 2.5mm2 2 wires + Ground
Outdoor unit side: AC 230V (220-240V)
Indoor unit side: AC 230V (220-240V)
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Shall be checked and entered in the check sheet.
Shall be checked and entered in the check sheet.
Connection points check & loose terminal block screws check
0.33mm2, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
DIP SW SET1, SET4 : Factory setting, SET2,SET3, SET5-1,2,3: ALL OFF Terminal resistor setting SET5 - 4 OFF: Disable, ON: Enable Check the resistance value for each network segment
Refer to the installation manual 7.7
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
2
2 wires + Ground 4mm
2
Check
Indoor
unit
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned and will lead to trouble.
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote controller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
There shall be no scratches, deformation, tilting, etc.
Shall be checked and entered in the check sheet.
Shall be installed positively.
Connection points check & loose terminal panel screws check
0.33mm2, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
0.33mm
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit address (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
2
01-03
Page 12
1-2-2 Check Items After Power ON
[Note] Cooling test run for each refrigerant circuit. If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot be detected.
Power ON
Outdoor unit Main
PCB push button SW setting/check
Address
setting/
check
Indoor unit
connection check
Cooling
test run
Check contentsProcedure
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Judgement standard
Check
[Note] Turn on all indoor units power in the same refrigerant circuit address. When the system operates with the indoor units remaining no power, it is cause of malfunction.
Function setting
Automatic address setting
Address read
Address record
Address hold check
Indoor unit connection check
Are the necessary functions set ? < For the setting, Refer to the page 01-15 18 >
Addresses shall be assigned to all indoor units / Signal amps. Check for unset or duplicated addresses. < For the setting, Refer to the page 01-06, 07 >
All the indoor units and outdoor units of the same refrigerant circuit can be checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool after indoor/outdoor circuit breakers were turned OFF to ON.
Are the number of connecting indoor units correct ? Is the total capacity of indoor units correct ? < For the checking, Refer to the page 01-08 >
[Note] Before connecting service tool, the address setting has to be completed.
Outdoor unit push button
SW operation
All the indoor units in the same refrigerant state.
The outdoor units corresponding to the operation capacity of the indoor
units shall operate. < Test operation procedure, Refer to the page 01-09,10 >
circuit
shall enter the coolingtest run
All of the
indoor units
operation
(after 30 mins)
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
HPS: 2.7 MPa
LPS: 0.9 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/
abnormal vibration
There shall be no Error information on the 7-segment display on the Main PCB.
Between L - N AC230V (220-240V)
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound.
There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
01-04
Page 13
Indoor unit
individual
operation
Check contentsProcedure
Judgement standard
<Indoor unit service tool + actual measurement>
Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
Check
These are representative figures of AJYA54LALH at the standard condition. ( Indoor : 27
°C, Outdoor : 35°C ) If conditions are different from those above mentioned, the figures will be changed slightly. It depends on following conditions.
Outdoor unit capacity Indoor and outdoor temperature Indoor unit capacity Pipe length etc
Trouble shooting on Test run operation
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and check the description of the Error code. < Refer to the Trouble shooting in the Service manual.> < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not Evaporator Icing up protection, High discharge temperature protection,etc. < Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc. < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1> < Refer to the regulation of installation in the Installation manual>
01-05
Page 14
1-2-3 Automatic address setting for signal amplifiers When using signal amplifiers
SWITCH POSITION
Outdoor unit printed circuit board
When setting the address of the signal amplifier, please use the factory setting. (See the installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units. Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB to conÞ gure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment LED Lamp
Push button switch
SELECT
SELECT
(When [F4] to [F9] are displayed, continue to press the "SELECT" button until [ F3 ] is displayed)
ENTER
Automatic address setting for
signal ampliÞ ers
SELECT
ENTER
Press the “SELECT” button until "10" is displayed
Press the “ENTER” button for more than 3 seconds
End
*
ENTER
MODE/EXIT
* Setting is complete when the number of unit is displayed
01-06
Page 15
1-2-4 Automatic address setting for Indoor units
SWITCH POSITION
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit Main PCB is set to “00”.If it is not set to “00”, it means the address of that device is not set. (Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment display. When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment LED Lamp
Push button switch
to configure settings according to the procedures below .
First 2 digits
SELECT
SELECT
ENTER
Last 2 digits
SELECT
ENTER
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
Automatic address setting for indoor units
Press the “SELECT” button until “11” is displayed.
Press the “ENTER” button for more than 3 seconds.
It may take about 10 minutes for completing the processing.
Found
End
Error
ENTER
The number of indoor units with normal set­tings will be displayed at the first 2 digits of the 7 segment display. The number of indoor units with error will be displayed at the last 2 digits.
NOTE) After the “ENTER” button is pressed, the end processing will occur for about 30 seconds. During this period, the 7 segment will blink.
01-07
Page 16
1-2-5 Indoor unit connection check
SWITCH POSITION
Outdoor unit printed circuit board
Please perform the indoor unit connection check according to following procedures.
Turn on the power • of indoor unit and outdoor unit.
LED105
LED104
MODE/EXIT
Set to Function mode [F3].
SELECT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment LED Lamp
Push button switch
SELECT
continue to press the “SELECT” button until [F3] is displayed.)
ENTER
(When [F4] to [F9] are displayed,
SELECT
Press the “SELECT” button until “12” is displayed.
ENTER
Press the
“ENTER”
button for
more than 3 seconds.
When indoor unit connection check can not be performed
This will be displayed when the • Indoor unit connection check starts.
ENTER
(*1)
Confirm the number of connected indoor • units and the volume ratio of the indoor units connection.
SELECT
ENTER
When error occurs
(*1) The number of connected
indoor units Ex.) When 8 units are connected
(*2)
(*2) Volume ratio of the indoor
units connection
Ex.) When the ratio is 120%
Exit indoor unit connection check • mode.
01-08
Please refer to the following “Error code” for details
ENTER
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
MODE/EXIT
When it finishes normally, nothing will be displayed on 7 segment display.
Page 17
1-2-6 Test Run From Outdoor Main PCB
All the indoor units connected to the outdoor unit can be test-operated by push button setting.
SWITCH POSITION
POWER
MODE
ERROR
LED101
(GREEN)
LED102
(RED)
7 Segment LED Lamp
LED105 LED104
Outdoor unit printed circuit board
MODE
/EXIT
SW107 SW108 SW109
SELECT ENTER
Push button switch
TEST RUN SETTING
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
< Monitoring condition >
LED105 LED104
MODE / EXIT
Note
There are the following 2 methods of resetting test operation.
Automatic reset when 60 minutes has elapsed.(1)
Reset when operation stop was performed.(2)
< Mode select condition >
[ Monitoring mode ] [ Setting mode ]
SELECT
ENTER
LED105 LED104LED105 LED104 LED105 LED104LED105 LED104
< Fuction select condition >
[ Cooling test run ]
LED105 LED104
ENTER
SELECT
Press the ENTER button for at least 3 seconds.
[ Heating test run ]
L
ED
< Pursuance completion >
LED105 LED104
SELECT
[ Function mode ]
SELECT
[ Error history mode ]
[ Central control setting
[ Test run stop ]
1
0
5
L
ED
1
0
4
SELECT
LED105 LED104
SELECT
Forced reset ]
LED105 LED104
ENTER
Press the "ENTER" button or Time out ( 5 seconds)
< Return to mode select condition >
LED105 LED104
MODE / EXIT
< Return to monitoring condition >
LED105 LED104
01-09
example, Normal indicate : [ Cooling mode ]
Page 18
1-2-7 Test Run From Remote Controller
1. Standard wired remote controller
Stop the indoor unit. Push the button and button simultaneously for more than two seconds. The air conditioner will start to conduct a test run and " " will display on the remote controller display. However, the , setting button does not have function, but all other buttons, displays, and protection functions will operate.
Perform the test operation for 60 minutes.
To stop test run, push the START / STOP button of the standard wired remote controller. For the operation method, refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
UTY - RNK
SET TEMP.
TIMER MODE
CLOCK ADJUST
SET BACK
TIMER DELETE TIMER SET
DAY
DAY OFF
START / STOP
FAN MODE
2. Standard wireless remote controller
Press the TEST RUN button on the remote controller, while the air conditioner is running. To end test run operation, press the remote controller START / STOP button.
When the air conditioner is being test run, the OPERATION and TIMER lamps of indoor unit flash slowly at the same time.
3. Simple remote controller
Stop the indoor and outdoor units. Push the remote controller simultaneously for more than three seconds. The air conditioner will start to conduct a test
run and " " will display on the temperature display. However the setting button does not have function but all other buttons, displays and protection functions will operate.
button and
button
START / STOP button
TEST RUN button
UTY - LNH
START
STOP
ECONOMY
FILTER RESET
SET
TEMP.
SLEEP
TIMER
TIMER MODE
CLOCK
TEST
ADJUST
RUN
UTY - RSK
FANMODE
SET
SET
SWING
RESET
To stop test running press the button of the simple remote controller. For the operation method refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
01-10
SET
Page 19
UTY-DCG
Monitor - All
On
Coll
25.0
Setup Menu
Central Controller Setting
05/31 03:59
05/31 03:59
Indoor unit Special setting
Select All
On
Off
Operation
Details
1
Monitor Group
Setup Menu
Help
2
Indoor unit Special Setting
Test Operation
Indoor Unit Set Temp. Range
Test Operation
RCG_05
6)
05/31 03:59
Filter Sign
R.C. Prohibition
05/31 03:59
or
Group
Select All
Identify Unit
Clear Unit
[ Select All (F2) ]: All of R.C.Group (Indoor units) [ Identify Unit (F3) ] : Specific R.C.Group (Indoor unit)
Page 20
5. Touch panel controller
Test run operating procedure
<Monitor screen (icon)>
UTY - DTG
Monitor Mode
All
Lange Group
Office A
On
Cool
21.5 C
Room
101
Off
Meeting 1
1
On
Heat
21.5 C
Conference
A
On
Heat
21.5 C
Group Error
Schedule Filter Sign
Op.Controlled Op.Restricted
<Monitor screen (list)>
Monitor Mode
All
Lange Group
Name
Office A
Expand
Top Up
Office B
On
Heat
21.0
Restrant
On
Auto
24.0 C
Meeting
2
Off
Conference B
On
Auto
22.0
Mode Set Temp.
Top Up
Status Mode
On
Heat
10/11.2008.Mar. 02:20 PM
Down
PC Room
On
C
Entrance
On
Meeting
3
On
Parking lot
Off
C
10/11.2008.Mar. 02:20 PM
Down
Set Temp
21.5 C
Fan
High
R/C Prohibit
List
Cool
26.0 C
Auto
24.0
Heat
21.0
List
Status: On
Setting
Schedule
(1)
C
Select All
C
Clear All
Operation
(1)
(2)
C
On
Off
( * )
Status: On
Setting
Schedule
(1)
Office B
PC Room
Mixed
On
Mixed Mixed Mixed
Auto
24.0 C
Low
Mixed
Select All
Clear All
Room 101
Restrant
Entrance
Meeting 1
Group Error
Schedule Filter Sign Op. Controlled Op. Restricted
Off
On
Off
Off
RC Prohibition All On/Off On
Cool
Mode Temp. Timer
26.0 C
Filter
Auto
Operation
On
Off
(1) Select the objective you want to test run. Select the objective icon or list at the monitor screen. (Multiple selections is possible) Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
01-12
(1)
(2)
( * )
Page 21
<Setting screen>
Operation Setting
Control Unit :
operation
On
On
Off
Off
Air Flow Direction Economy Anti Freeze Filter Sign Test Operation
Optional
Setting
Cancel
Cancel
Meeting Room
Mode Set Temp. Fan
Auto
24.0 C
Cool
Dry
Fan
Heat
Operation Controlled
10/11.2008.Mar. 02:20 PM
R/C Prohibition
All
Auto
High
Med
Low
Quiet
On/Off
On
Mode
Temp.
Timer
Filter
Status: On
OK
OK
(3) Switch to the <Details setting screen> by pressing "Optional Setting" on the setting screen.
<Details setting screen>
( * )
(3)
Operation Setting
10/11.2008.Mar. 02:20 PM
Status: On
SettingOptional
Air Flow Direction
Up
1
2
3
1
Down
2
3
Swing
4
4
Swing
Left Right
Cancel
Economy
On
Off
Test
5
Special State
Stand by (Defrost) Stand by (Oil Recovery) Test Operation
Anti Freeze
Operation
On
Off
Filter Sign
Reset
Start
OK
(4)
(5)
(4) Send (start) test run by pressing "Start" and then pressing "OK" on the details setting screen. Test run continues for 60 minutes. During sending, the slave screen shown below is displayed. When sending is completed, the sending slave screen and details setting screen are closed.
To interrupt test run, select the device being test run and execute an operation stop command.
(*) At the monitor screen, test run is reset by stopping operation
Transferring data. Please wait.
of the objective devices by pressing "OFF". (*) Or test operation is reset by stopping operation of the objective devices by pressing "Off" of Operation and then pressing "OK" on the setting screen.
01-13
Page 22
1-3 TEST RUN CONTROL
1. When the test run signal is transmitted from standard wired, wireless remote controller, simple remote controller, transmitted network, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of the temperature condition.
(2) Frost prevention operation has priority over item(1). (3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ). (4) After 60 minutes passes, the test run stops. (5) Test running initialization is shown below.
Operating Mode
Fan speed Hi Hi
Room Temperature Indication 18 30
Vertical Air Direction Panel
Swing
*EXAMPLE
1
2
3
4
EXCEPT FOR THE DUCT MODEL DUCT TYPE
Cooling Heating Cooling Heating
Hi Hi
18 30
Position
4
1
OFF OFF
2
3
1
Position
4
1
2
3
4
COMPACT CASSETTE TYPE
CEILING TYPE
1
2
3
4
COMPACT WALL MOUNTED TYPE
01-14
Page 23
1-4 Field Setting And Monitor Mode List for Outdoor unit
Push switch onoutdoor unit PCB
Monitor mode
[ F1 ]
Classification
Device and system
Operation of each part
Time guard 20 Accumulated current time Accumulated current time is displayed
Refrigerant cycle data 1
Refrigerant cycle data 2
ITEM CODE No.
00 Connected number of indoor unit The number of the communicating unit is displayed
Software version of outdoor unit
01
02 Software version of INV PCB
03 Software version of communication PCB
10 Rotational speed of outdoor unit fan motor The rotational speed of the outdoor unit fan motor is displayed
11 Rotational speed of INV compressor The rotational speed of the compressor is displayed
12 Current value of INV compressor Current value of INV compressor is displayed
14 Pulse of EEV1 Pulse of EEV1 is displayed
Pulse of EEV2 Pulse of EEV2 is displayed
15
21 INV compressor accumulated time
[ Cooling ]
22 INV compressor accumulated time
[ Heating ]
30 Information on Thermistor 1
( INV compressor discharge temperature )
32
Information on Thermistor 3
( Outdoor temperature )
33 Information on Thermistor 4
( Suction temperature )
34
Information on Thermistor 5
( Heat-exchanger temperature )
36
Information on Thermistor 7
( Liquid temperature 2 )
37
Information on Thermistor 8
( Sub-cool heat-exchanger inlet temperature )
38 Information on Thermistor 9
( Sub-cool heat-exchanger outlet temperature )
39 Information on Thermistor 10
( INV compressor temperature )
50
Information on pressure sensor 1
( High pressure sensor )
51
Information on pressure sensor 2
( Low pressure sensor )
Setting Mode
Information contents
Software version :
[ ] [ ] [ ] [ ] [ ] displays by five items
It skips when there is no suffix
[ rpm ]
[ rps ]
[ A ]
[ pls ]
[ pls ]
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the INV compressor [ 10 hour ] Accumulated time is displayed in the heating operation of the INV compressor [ 10 hour ]
The value of the Thermistor 1 is displayed
[°C ] or [°F ]
The value of the Thermistor 3 is displayed
[°C ] or [°F ]
The value of the Thermistor 4 is displayed
[°C ] or [°F ]
The value of the Thermistor 5 is displayed
[°C ] or [°F ]
The value of the Thermistor 7 is displayed
[°C ] or [°F ]
The value of the Thermistor 8 is displayed
[°C ] or [°F ]
The value of the Thermistor 9 is displayed
[°C ] or [°F ]
The value of the Thermistor 10 is displayed
[°C ] or [°F ]
The value of the pressure sensor 1 is displayed [ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed
[ MPa ] or [ psi ]
01-15
Page 24
Push switch on outdoor unit PCB
Setting mode
[ F2 ]
Classification
ITEM CODE No.
Setting Mode
ITEM CODE No.
Install 00 Pipe length setting 00 40-65m
01 0-40m 02 65-90m 03 90-120m
Correction 10
Sequential start shift
Setting is forbidden
04 00 01 02
Setting is forbidden
Standard
03
Cooling capacity shift 00 Normal mode
11
01 Save energy mode 1 (+2°C) 02 High power mode 1 (-2°C)
03 High power mode 2 (-4°C) 04 High power mode 3 (-5°C)
Heating capacity shift
12
00 Normal mode 01 Save energy mode (-2°C) 02 High power mode 1 (+2°C) 03 High power mode 2 (+4°C)
13 Defrost setting shift 00 End temperature:Normal
01 End temperature:Higher
Change of
function 1
14 Pressure equalization time shift
before defrosting start
20 Switching between forced stop or 00 Forced stop
emergency stop
00 No time shift
01 Shift 1 ( 30 sec.) 02 Shift 2 ( 60 sec.) 03
Shift 3 ( 90 sec.)
04
Shift 3 ( 120 sec.)
01 Emergency stop
21 Operation mode selecting method 00 Priority given to the first command
01 Priority given to the external input of outdoor unit 02 Priority given to the master indoor unit
22
Snow falling protection fan mode
Setting is forbidden
23
Interval setting for snow falling protection fan mode
Setting is forbidden
24
High static pressure mode
Setting is forbidden
Oil recovery
25
Setting is forbidden
00 Normal operation 01 00 Standard 01 02 03 00 Standard 01 02
Standard
00 01
02 03
Oil recovery Abnormal
26
low pressure protection control
Setting is forbidden
27 Error code Notification
00
00 01
Standard
01
Enable Disable
28 Change of unit (Temperature) 00 Celsius(°C)
01 Fahrenheit ( F)
29 Change of unit (Pressure) 00 MPa
01 psi Change of function 2
30 Energy saving level setting 00 Level 1 (stop)
01 Level 2 (operated at 40% capacity)
02 Level 3 (operated at 60% capacity)
03 Level 4 (operated at 80% capacity)
04 Level 5 (operated at 100% capacity)
31
Heating Starting prosess
Setting is forbidden
Low noise 40 Capacity priority setting 00 Off (quiet priority) setting 1
(in low noise mode)
41 Low noise mode setting
00
Standard
01
01 On (capacity priority)
00 Off (Normal)
01 On (Low noise mode operation is always done)
42
Change of function 3
Change of function 4
Low noise mode operation level
60
Setting is forbidden
Back up operation
Setting is forbidden
70
Electricity meter No. setting 1
(Set the ones digit and tens digit of the No of the electricity meter connected to CN135.)
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the electricity meter connected to CN135.)
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of the electricity meter pulse setting connected to CN135.)
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135.)
*4
*4
*3 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective. Available setting number is "001" to "200" *4 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective. Available setting number is "0001" to "9999"
Setting is forbidden: Any of problems caused by changing these setting is not covered by the warranty.
Only for solution :
*3
Only when the refrigerant noise during Defrosting was pointed out. It is the case that the
00 Standard (47dB)
01
00 Standard
01
00~99 Setting number x00~x99
*3
( Refer to Design & Technical Manual for details.)
00~02 Setting number 0xx~2xx 00
( Refer to Design & Technical Manual for details.)
00~99 Setting number xx00~xx99 00
( Refer to Design & Technical Manual for details.)
00~99 Setting number 00xx~99xx 00
( Refer to Design & Technical Manual for details.)
compressor operating time in heating will be shorter.
01-16
Setting Function
Only for solution
Default
00
Page 25
Push switch on outdoor unit PCB
Function mode
[ F3 ]
ITEM CODE No.
Forced operation 00 Cooling test run
01 Heating test run Forced thermostat-ON in Heating.
Install and maintenance 1
02 Test run stop Test run is stopped.
10 Signal amplifier automatic address Automatic address setting operates for signal amplifier.
11 Indoor unit automatic address
Setting Mode
Setting Function
Forced thermostat-ON in Cooling.
Automatic address setting operates for indoor unit of same refrigerant circuit.
12
Indoor unit connection check
Install and maintenance 2
Clear 30 Error history clear All the abnormal code histories are cleared.
Reset 40 Abnormal reset It was displayed when abnormality occurs, and abnormal
Specialtyfunction 91 Foreced Central control function release
21 Vacuuming mode Vacuuming mode operatesRefer to page 01-01 for the function.
32 Current time clear Accumulated current time becomes [ 0 ]
33 INV compressor accumulated time clear Accumulated time of the INV compressor becomes [ 0 ]
34 Constant Speed compressor accumulated
time clear
35 Field setting all clear Return to default the all set items.
36
Clear memorized information of "F3 - 12 " ( Indoor unit connection check )
*
Maximum memorized indoor unit number reset
41
90
Foreced Normal operation release Normal operation foreced release
The number of indoor units and the total capacity of indoor units of same refrigerant circuit.
Not in Use on J-Series
The information of the number of indoor units and the total capacity of indoor units are cleared.
code is reset.
This is a function that uses to clear abnormal display after the repair is completed.
Please operate the switch after power off or power on the outdoor unit. Maximum memorized indoor unit number is reset.
"E14.5:Indoor unit number shortage" error is cleared.
When the centralized control device failure, and the centralized control setting cannot be released, this function is used.
All the limitations set with the centralized control device are released.
Push switch on outdoor unit PCB
Error History Mode
[ F9 ]
Error history
ITEM CODE No.
00
01
02
03
04
05
06
07
08
09
Meaning of Error History Number
1 time ago (Newest)
2 times ago
3 times ago
4 times ago
5 times ago
6 times ago
7 times ago
8 times ago
9 times ago
10 times ago (Oldest)
Information contents
When the error occurred, the error code is memorized up to 10 on Main PCB.
If the memorized error code becomes over 10, the oldest one will be erased.
Refer to Chapter 4.TROUBLE SHOOTING
4-2-3 Error Code List of Outdoor unit
< Reset Error Item List By Abnormal Reset Setting >
*
Compressor Motor Loss of Synchronization Compressor 1 Temperature Abnormal Inverter Compressor Start Up Error Discharge Temperature 1 Abnormal Low Pressure Abnormal Current Sensor 1 Error Trip Detection Rush Current Limiting Resistor Temp Rise Protection Outdoor Unit FAN motor 1 Lock Error Outdoor Unit FAN motor 2 Lock Error
01-17
Page 26
1-5 Field Setting / Function Setting for Indoor unit
23 Vertical airflow direction 00 Default
02 Right half
Correction
30
Cool air temperature trigger
00 Default (0°C)
Indoor unit field setting
setting by remote controller
Classification
Address
Filter 11 Filter indicator Interval 00 Default
Airflow 20 Ceiling airflow 00 Default
ITEM CODE No.
01 Indoor unit address 00~63 00~63 00 02 Refrigerant circuit address 00~99 00~99 00
13 Filter sign display 00 Enable
(Cassette type only) 01 High ceiling
24 Horizontal swing airflow direction 00 Default
26
Static Pressure setting
Setting Mode
- Slim Duct Only -
The Range of static pressure is different from one model to other.
31 Heat air temperature trigger 00 Default (0°C)
32
Temperature correction in Auto
Change of 40 Auto restart 00 Enable Function 1
43 Cool air prevention 00 Enable
46 External control 00 Start / Stop
47 Error report target 00 All
ITEM CODE No.
Longer
01 02 Shorter
01 Disable 02 Display only on central remote control
01 Raise
01 Left half
00
0 Pa
01
10 Pa
02
20 Pa
03
30 Pa
04
40 Pa
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
31
25 Pa
01 Temperature overshoot setting (+2 02 Temperature undershoot setting (-2
01 Temperature undershoot setting (-6 02 Temperature slightly undershoot setting (-4 03 Temperature overshoot setting (+4
00
Disable
01
Enable (Nonfunctional on J2 Series)
01 Disable
01 Disable (Ventilation mode)
01 Emergency stop
01 Display only for central remote control
Setting Function
Model name Range of static pressure AR XD 07L ATH AR XD 09 LATH AR XD12L ATH AR XD14L ATH AR XD18LAT H AR XD 24L ATH 0 to 50 Pa
0 to 90 Pa
°C)
°C)
°C)
°C)
°C)
Default
01-18
Page 27
2. OUTDOOR UNIT OPERATION CONTROL
Page 28
Page 29
2. OUTDOOR UNIT
2-1 INPUT / OUTPUT LIST
Discharge pressure sensor <HIGH> Pressure sensor Measure range 0.0 to 5.0MPa Suction pressure sensor <LOW> Pressure sensor Measure range 0.0 to 1.7MPa Discharge temperature sensor <TH1> Themistor <Blue> Outdoor temperature sensor <TH3> Themistor < - > Suction temperature sensor <TH4> Themistor <Red>
I
N
U
Heat exchanger temperature sensor <TH5> Themistor <Pink> Liquid temperature sensor <TH7> Themistor <Green>
P
Sub-cool heat exchanger (inlet) sensor <TH8> Themistor <White> Sub-cool heat exchanger (outlet) sensor<TH9> Themistor <Brown>
T
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130 Operation current sensor Pressure switch
Rotary SW & DIP-SW & Push SW
Input / output or kind of detail Control range
Measure range 10 to 130 Measure range -25 to 58 Measure range -35 to 70 Measure range -35 to 70 Measure range -35 to 70 Measure range -35 to 70 Measure range -35 to 70
Current transformer Pressure switch
Address and function setting
Open 4.2MPa Short 3.2MPa
O U T P U T
Communication Input / Output
External Input / Output
LED display
Compressor Electronic expansion valve 1 (Main) EEV coil Operating voltage DC12V
Electronic expansion valve 2 (SC-Hex) EEV coil Operating voltage DC12V Fan motor 1 (Upper) DC Brushless motor Fan motor 2 (Lower) DC Brushless motor 4-way valve 4-way valve coil AC220-240V, 50/60Hz 6/5 W Solenoid valve Comp pressure equalizing valve AC220-240V, 50Hz, 6W Crank case heater For Inverter Compressor AC240V, 25W
Base heater Field supply AC220-240V, 35W
LON WORKS Inverter communication
External input 1 (CN131) (Low noise mode operation) External input 2 (CN132) (Cooling / Heating priority) External input 3 (CN133) (Outdoor unit operation peak control) External input 4 (CN134) (Emergency stop operation)
External output 1 (CN136) (Error display) External output 2 (CN137) (Operation display)
Single LED 101 Single LED 102 7 Segment LED
Magnetic relay
Indoor unit Outdoor unit
Dry contact input
ON (Error) / OFF (Normal) ON (Operation) / OFF (Stop)
Display the information on operation, error and setting with single LED and 7 segment LED.
Operation coil AC220-240V, 50Hz
Control output: DC 0/12-24V, Max.30mA Control output: DC 0/12-24V, Max.30mA
02-01
Page 30
2-2 COMPRESSOR OPERATION
2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same refrigerant circuit is input, the compressor operates. When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity", is stopped. But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation Icing protection Failure (Refer to chapter 4, TROUBLE SHOOTING ) Oil recovery Under expansion valve initialization At protective operation
Emergency stop Defrost operation
Peak cut stop operation
the compressor
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of required refrigerant circulation in details.
Total capacity
Capacity of
compressor operation
Inverter Compressor
02-02
Cooling/Heating load
Page 31
(2) Target low-pressure and high-pressure control
<Cooling> In order to make the evaporation pressure of the indoor unit at the proper pressure on a variety of operations, capacity of the compressor will be controlled by low-pressure sensor of the outdoor unit.
<Heating> In order to make the condensation pressure of the indoor unit at the proper pressure on a variety of operations,
capacity of the compressor will be controlled by high-pressure sensor of the outdoor unit.
Target low-pressure and high pressure temperature depends on system capacity, capacity of compressor operation, pipe length, and capacity shift switch settings.
2-2-3 Speed Range of Start, Stop, And Operation
On stop mode : 0 rps
On operating mode : 20 - 100 rps
(1) Cooling starting process For cooling operation only, the upper limit speed at starting is made 50rps and is raised in +10rps increments every 60 seconds.
The compressor operates at the upper limit speed if the target speed is higher than the upper limit speed.
The compressor operates at the target speed if the target speed is lower than the upper limit speed.
Speed
90rps
Target speed 80rps 70rps 60rps 50rps
10rps
10rps
10rps
60sec
60sec
60sec
60sec
0
60sec
120sec 180sec 240sec
02-03
Time
Page 32
(2) Heating starting process
At the start of heating, the compressor is started by the following process. Compressor start-up to change the 4 way valve. Capacity control returns to normal control after the end of the starting process. (target high-pressure control)
< Starting process >
Compressor operation speed
Normal control
Starting process
Starting process
Starting process Starting process
4rps/Min
32rps fixed
Cancel conditions
3 minutes elapsed from start of process or High-pressure 2.63MPa
20 minutes elapsed from start of process or High-pressure 2.63MPa or Discharge SH 10 and Discharge temperature 10
*However, when the following condition (A) or (B) are satisfied, starting process is not performed.
< Conditions under which starting process is not performed >
(A) The compressor temperature 32 , when the room temperature reached to the setting temperature ( Thermostat - OFF controlling )
(B) The compressor temperature 32 , when the system keeps heating mode with stop condition
< Operation >
Compressor operates based on the required capacity at the start up, after that the target high-pressure control begins.
(3) Limits the upper limit speed of the INV compressor according to the present high-pressure value.
High Pressure
Maximum speed = 80rps
3.60MPa
Maximum speed = 90rps
3.30MPa
Maximum speed = 95rps
(Maximum) 3.00MPa
[ a ]
Maximum speed = 100rps
[ a ] = 1.25 Low pressure value 2.125
02-04
Page 33
2-3 FAN CONTROL
2-3-1 Cooling Operation
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
Fan speed (rpm)
AJ A36LALH AJ A45LALH AJ A54LALH
780 700 660 660 670 590 540 540 450 410 340 340 270 250 390 0 340 0 290 0 250 0 0 0
780 700 660 660 670 590 540 540 450 410 340 340 270 250 390 0 340 0 290 0 250 0 0 0
780 700 700 700 670 590 540 540 450 410 340 340 270 250 390 0 340 0 290 0 250 0 0 0
Step
Upper FAN Lower FAN
Switching conditions of step
The initial speed of the outdoor unit is detected by out door temperature sensor.
Outside air temperature sensor detected value
TAOUT 30°C
30°C TAOUT 20°C
20°C TAOUT 10°C
10°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
(Conditions which lower the fan speed) High-pressure saturation low limit of target high-pressure
saturation range and heat sink temperature 75°C
Fan step
7
5
2
0
The fan is controlled to keep high puressure saturation temperature within the target range as follows
High-pressure saturation temperature
54
46.6
40.4
Upper limit of target high-pressure saturation temp.
Low limit of target high-pressure saturation temp.
35 52
Target high-pressure saturation temp.
Outdoor temperature
(Conditions which raise the fan speed) High-pressure saturation upper limit of target high-pressure saturation or heat sink temperature 80°C
02-05
Page 34
2-3-2 Heating Operation
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
Fan speed (rpm)
AJ A36LALH AJ A45LALH AJ A54LALH
800 700 660 660 670 590 540 540 450 410 340 340 270 250 0 0 0 0 0 0 0 0 0 0
800 700 660 660 670 590 540 540 450 410 340 340 270 250 0 0 0 0 0 0 0 0 0 0
800 700 700 700 670 590 540 540 450 410 340 340 270 250 0 0 0 0 0 0 0 0 0 0
Switching conditions of step
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
Outside air temperature sensor detected value
TAOUT 10°C
10°C TAOUT 15°C
15°C TAOUT 20°C
20°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
(Condition which lowers the fan speed)
High-pressure 3.30MPa and heat sink temperature 80°C
(Condition which raises the fan speed) High-pressure saturation 3.20MPa or heat sink temperature 85°C
Fan step
11
8
5
5
02-06
Page 35
2-3-3
Low noise mode
When the low noise mode setting ON from PUSH SW or EXTERNAL INPUT, the outdoor unit operates in the low noise mode as follows.
«
Settings and corresponding operations
Capacity priority setting
( PUSH SW ) ( PUSH SW )
Low noise level setting
»
Operation mode
OFF
ON
«
Low noise mode and operation contents
COOL
Low Noise Mode
HEAT
Max Compressor Speed
Max Compressor Speed
ON
ON
»
Max FAN Step
Upper FAN Lower FAN
Max FAN Step
Upper FAN Lower FAN
LOW NOISE MODE
* Automatic switching
4HP
AJ*A36LALH
AJ*A45LALH
7
450 410
40
7
450 410
60
5HP
AJ*A54LALH
7
450 410
45
7
450 410
60
6HP
7
450 410
52
7
450 410
60
The operating noise is reduced by limiting the rotational speed of the compressor and fan motor
LOW NOISE MODE
The operating sound lowers from about 3 to 5 dB more than the rated value
* Automatic switching
Operation in low noise mode
Low capacity
Normal operation
Not switched for 30 minutes after being once switched.
Capacity does not become low even when switched to low noise mode
* Low capacity Compressor capacity is low or High-pressure is high (high-pressure saturation 58°C) at cooling or Low-pressure is low (low-pressure saturation 0°C) at heating
02-07
Page 36
2-3-4 Other Control
To accurately detect the outside air temperature, the fan is operated while the outdoor unit is stopped.
2-4 EXPANSION VALVE CONTROL
Control range
Initialization conditions
Operation mode
operation stop
Cooling
EEV 1
EEV 2
< Cooling mode > 500 pulses basically.
< Heating mode > EEV is controlled so that the system reaches closer to the target discharge temperature that is calculated from high and low pressure.
When power turned on When operation stopped
Heating
Cooling
Heating
500 pulses
0 pulses
40 - 500 pulses
55 - 500 pulses 0 pulses
02-08
Page 37
2-5 SPECIAL OPERATION
2-5-1 Oil Recovery Operation
Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units and the connection pipe with the refrigerant will become large as the operation time of compressor increases. It is necessary to recover the oil back into the outdoor unit for a certain time interval in order to prevent compressors from damaging due to lack of lubrication oil.
1. Oil Recovery in Cooling operation
< Start condition >
Compressor accumulated operation time since last cooling oil recovery operation exceeds 3 hours (first time : 1hour)
< End condition > 30 seconds have elapsed since the start and "suction temperature - low pressure saturation temperature 5deg" or 6 minutes
have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state. EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode). FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
2. Oil Recovery in Heating operation
< Start condition >
Compressor accumulated operation time since the last heating oil recovery exceeds 8 hours (first time : 1hour)
< End condition > After 4 minutes have elapsed
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state. EEV Opening (Indoor/Outdoor unit) : Controlled pulse (as normal operation mode) FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode)
Others
During the oil recovery operation, appears on the display of wired and central remote controller, and appears on the simple remote controller. The operation indicators (LED) of the indoor units flash slowly.
02-09
Page 38
2-5-2 Pre-heat Operation
This pre-heat operation protects the start up failure by preventing the refrigerant from soaking into the oil in compressor.
Crankcase heater ON: 30 minutes elapsed since installed compressors stopped
*It doesn't control according to the temperature.
OFF: Compressor starts
(However, ON when power turned on)
2-5-3 Defrost Operation Control
Defrost Operation Start Condition 1
Outdoor temperature <2 and Compressor stop count exceed 20 times at less than 10 minutes of accumulated heating operation time
Defrost Operation Start Condition 2
Accumulated heating operation time is 40 minutes or longer [Accumulated heating operation time is reset at the end of cooling operation or defrosting operation.] and an outdoor unit satisfies condition or below
Condition : "Heat exchange temperature -2°C" accumulated operating time is 180 minutes or longer
Condition : After the following all condition satisfied, "heat exchange temperature defrosting start judgment temperature and during heat exchange liquid temperature drop" accumulated time:10minutes
(a) accumulated heating operation time 30 minutes (b) 10 minutes have elapsed after outdoor unit starting (c) 5 minutes have elapsed since oil recovery
* Defrosting start and end judgment temperature are determined by the outdoor temperature.
Defrosting start judgment temperature = 0.8 x outdoor temperature - 11.6 (However, -27.6°C to - 6°C)
If the calculated result is lower than -27.6 , the judgment temperature is defined as -27.6 If the calculated result is higher than -6 , the judgment temperature is defined as -6
Defrost Operation End Condition
At all outdoor units, heat exchange liquid temperature end judgment temperature or when 10 minutes have elapsed from the start (When the indoor unit connection capacity is 90% or less, after 15 minutes have elapsed.)
Defrosting end judgment temperature = 0.39 x outdoor temperature + 12.7 (However, 5 to 12°C range)
If the calculated result is lower than 5 , the judgment temperature is defined as 5 If the calculated result is higher than 12 , the judgment temperature is defined as 12
02-10
Page 39
2-6 PROTECTIVE FUNCTION
2-6-1 Protective Function List
Protective Function
Discharge Temp Protection 1
Discharge Temp Protection 2
Discharge Temp Protection 4
Discharge Temp Protection 5
Discharge Temp Protection Stop
Detect Parts
Discharge Temp Thermistor
Discharge Temp Thermistor
Discharge Temp Thermistor
Discharge Temp Thermistor
Discharge Temp Thermistor
COOL HEAT
DISPLAY
P1
EA11
Operating Condition
<Starting conditions> 3 minutes have elapsed since the start of operation and (discharge temperature 100°C or suction SH 10°C accumulated time 30 minutes)
<Reset conditions> Discharge temperature 95°C and suctionSH 7°C
<Starting conditions> Cooling: Discharge temperature 95°C Heating: Discharge temperature 102°C
< starting condition> Discharge temperature 105°C
<Starting conditions> Discharge temperature 95°C and EEV1=500pls
<Reset conditions> 2 minutes have elapsed and (discharge temperature 90°C or EEV1 400pls)
<Pattern starting condition> Discharge temperature fixed value (115°C)
<Pattern reset condition> 3 minutes have elapsed and discharge temperature 80°C
<Pattern starting condition> Pattern generated 2 times within 40 minutes
<Pattern reset condition> Error reset (push button SW) executed after power turned on again
<Reset conditions> Discharge temperature 90°C Discharge temperature 97°C
<Pattern reset condition> Discharge temperature 100°C
Operation
EEV of operating indoor unit gradually opened
EEV2 + 30pls/30 secs
Compressor speed -6rps every 30 secs Speed rise prohibited, when discharge temperature becomes lower than 105 , prohibit the rotational speed rise of the compressor.
Expansion valve of stopped indoor unit gradually opened (upper limit 200pls)
Compressor stopped
Compressor stopped (permanent stop) Error display
High Pressure Protection 1
High Pressure Protection 2
High Pressure Protection 3
High Pressure Protection 4
High Pressure Protection 5
Abnormal High Pressure Protection Control
High Pressure Sensor
High Pressure Sensor
High Pressure Sensor
High Pressure Sensor
High Pressure Sensor
High Pressure Sensor
<Starting conditions> COMP < 25 rps ---- HP 3.3 MPa 25 rps COMP < 30 rps ---- HP 3.5 MPa 30 rps COMP
<Reset conditions> Fixed time has elapsed and Fixed time when SV2: ON 30 secs COMP < 25 rps ---- HP 3.0 MPa 25 rps COMP < 30 rps ---- HP 3.2 MPa 30 rps COMP
<Starting conditions> COMP 25 rps ---- HP 3.5 MPa COMP < 25 rps ---- HP 3.3 MPa
<Reset conditions> 3 minutes have elapsed and high-pressure 2.80MPa
<Starting conditions> Fixed time has elapsed and high-pressure 3.50MPa (* Fixed time at start of operation: 10 secs, after operation execution: 20 secs)
<Reset conditions> Operation (fan speed 1 step increase) complete
<Pattern starting condition> High-pressure 3.30MPa
<Pattern starting condition> High-pressure 3.50MPa
<Starting conditions> High-pressure 3.20MPa
<Pattern starting condition> COMP < 30 rps ---- HP 3.18 MPa COMP 30 rps ---- HP 3.68 MPa
<Pattern reset condition> After 25 seconds have elapsed and, COMP < 30 rps ---- HP 3.1 MPa COMP 30 rps ---- HP 3.6 MPa
<Pattern starting condition> COMP 30 rps ---- HP 3.3 MPa COMP 30 rps ---- HP 3.8 MPa
<Pattern reset condition> After 25 seconds have elapsed and, COMP 30 rps ---- HP 3.18 MPa COMP 30 rps ---- HP 3.68 MPa
---- HP 3.8 MPa
---- HP 3.5 MPa
<Pattern reset condition> High-pressure 3.2MPa
<Pattern reset condition> High-pressure 3.5MPa
<Reset conditions> High-pressure 3.20MPa
SV2 ON
SV2 ON
Fan speed 1 step increase
Fan speed lowered/every 30 secs
Fan lowest speed Upper 270 rpm Lower 250 rpm
Compressor capacity lowered/every 15 secs
Compressor capacity rise prohibited
Compressor capacity lowered every 30 secs
02-11
Page 40
Protective Function
High Pressure Protection Stop 1
High Pressure Protection Stop 2
Low Pressure Protection 1
Detect Parts
High Pressure Sensor
Pressure Switch
Low Pressure Sensor
COOL HEAT
DISPLAY
P2
EA41
P2
EA42
Operating Condition
<Pattern starting condition> High-pressure 4.00MPa
<Pattern reset condition> 5 minutes have elapsed and high-pressure 3.50MPa
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and high-pressure 3.50MPa
<Pattern starting condition> Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition> 5 minutes have elapsed and pressure SW operation reset (Reset by high-pressure 3.2MPa)
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and pressure SW operation reset (Reset by high-pressure 3.2MPa)
<Starting conditions> Low-pressure 0.20MPa
<Reset conditions> 5 minutes have elapsed and low-pressure 0.30MPa
Compressor stopped
Compressor stopped
Compressor stopped
Compressor stopped Error display
SV2 ON
Operation
Low Pressure Protection 2
Low Pressure Protection 4
Abnormal Low Pressure Protection Control
Low Pressure Protection Stop
Compressor Temp Protection Stop
Low Pressure Sensor
Low Pressure Sensor
Low Pressure Sensor
Low Pressure Sensor
Compressor Temp Thermistor
P3
EA51
P4
<Starting conditions> Low-pressure 0.10MPa
<Reset conditions> 3 minutes have elapsed and low-pressure 0.17MPa
<Starting conditions> 3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions> 3 minutes have elapsed and low-pressure 0.22MPa
<starting condition> Low-pressure 0.16MPa
<Pattern starting condition> Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition> 3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition> Pattern generated 5 times within 180 minutes.
<Pattern reset condition> Error reset (push button SW) executed after power turned on again.
<Pattern starting condition> Compressor temperature fixed value (110°C)
<Pattern reset condition> 3 minutes have elapsed and discharge temperature 80°C
<reset condition> 3 minutes have elapsed and low-pressure 0.18MPa
SV2 ON
EEV of stopped indoor unit opened quickly (450pls)
Compressor capacity lowered every 180 secs,
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise.
Compressor stopped
Compressor stopped (permanent stop) Error display
Compressor stopped
EA31
<Pattern starting condition> Pattern generated 2 times within 40 minutes
<Pattern reset condition> Error reset (push button SW) executed after power turned on again
02-12
Compressor stopped (permanent stop) Error display
Page 41
Protective Function
Overcurrent Break Stop (Compressor)
Detect Parts
Overcurrent Protection Circuit
COOL HEAT
DISPLAY
E941
(permanent stop)
Operating Condition
Compressor is stopped when the over currernt protectioncircuit in the inverter PCBoad detects an abnormal current duringthe operation. If it repeated 5 times, the compressor becomes permanentstop.
Operation
Compressor stopped
Heatsink Temp Protection Stop
Frequency Maximum Setting Protection (Compressor)
Heatsink Temp Thermistor
Current Detector Circuit
E931
(permanent stop)
EAC4
Compressor is stopped when the over current protection circuit in the inverter PC Board detects an abnormal current at the time of start up. Compressor becomes permanent stop if it repeated over the number of set time.
<Reset condition> Error reset (push button SW) executed after power turned on again.
<Pattern starting condition> Heat sink temperature 100°C
<Pattern reset condition> 3 minutes have elapsed and heat sink temperature 85°C
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and heat sink temperature 85°C
<Pattern starting condition> Current value Cooling: 22.5A / Heating: 23.5A
<Pattern reset condition> Current value Cooling: 22.5A / Heating: 23.5A
<Pattern starting condition> Current value Cooling: 23.0A / Heating: 24.0A
<Pattern reset condition> Current value Cooling: 23.0A / Heating: 24.0A
• Pattern and start current value changed by outside temperature
Compressor stopped
Compressor stopped Error display
Compressor speed rise prohibited
Compressor speed lowered
02-13
Page 42
Page 43
3. INDOOR UNIT OPERATION
Page 44
Page 45
3. INDOOR UNIT OPERATION
3-1 FAN CONTROL
3-1-1 Fan Speed Setting
Fan speed setting
Press the FAN CONTROL button to set the fan speed.
AUTO
HIGH MED LOW
3-1-2 "AUTO" Position
1. COOLING OPERATION
The fan speed is determined automatically in accordance with the condition "(TR(corrected room temperature) - TS (corrected set temperature)" as shown on the right. However, the fan speed zone is determined in the manner as the room temperature increases for the following cases.
(1) When the TS is changed. (2) When the operation mode is changed from other mode to "COOL". (3) When the fan control is changed from other position to "AUTO".
2. HEAT OPERATION
Same as Cooling operation, fan speed is decided by the difference between the room temperature and the set temperature.
-2
1
Fan speed zone
TR-TS
TR-TS
TR-TS
TR-TS
2
TR-TS
TR-TS
2
1
When the room temperature decreases
Fan speed zone
-2
-3
-3
When the room temperature decreases
Hi zone
Med zone
Low zone
Low zone
Med zone
Hi zone
TR-TS
2
TR-TS
When the room temperature increases
TR-TS
-1
TR-TS
When the room temperature increases
TR-TS
2
TR-TS
-2
3
3
-1
-2
3. DRY OPERATION
The indoor fan always rotates at "Lo" speed.
• Expansion
valve
• Indoor fan motor
(1) The indoor fan starts operation 5 seconds after the electric expansion valve opens. However, when the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is not stopped, the fan will rotate immediately without a delay time of 5 seconds. (2) The indoor fan will stop in 30 seconds when the refrigerant circulation stops. (3) The indoor fan will stop immediately when the indoor unit is stopped by pushing the stop button or by a setting of ON timer. (4) When the refrigerant circulation is stopped due to a lower room temperature for more then 3 minutes, the fan will rotate 2 minutes at intervals of 3 minutes. (5) When the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is stopped, the fan will rotate for 1 minute and then it will operate according to the statement (4).
OPEN CLOSE
ON OFF
ON
ON
30s
ON
ON ON ON
5s
30s
2min30s
2min
3min
ON
ON
TIME -->
5s
03-01
Page 46
3-2 MASTER CONTROL
3-2-1 Operation Mode Control
Each operation mode is controlled as below. (1) Stop mode
Indoor fan motor : OFF Electric expansion valve Drain pump
(2) Cool, Dry and Heat Mode
Indoor fan motor
: Stop pulse : Turns ON-OFF by the drain pump control function
Cool Dry
Operates according to
the AIR FLOW-MODE
setting.
See the fan control
page.
Heat
Operates according to
the AIR FLOW-MODE
setting, and besides
cold air prevention
operation
Drain pump
Electrical expansion valve
(3) Priority mode
Turns ON-OFF by the drain pump control function
Pulse controlled by
the temperature differ-
ence calculation and
frost prevent fuction
Pulse controlled by
the temperature dif-
ference calculation
and frost prevent
function
Pulse controlled by
the temperature dif-
ference.
The purpose of the priority mode is to restrict operation commands (heating, cooling, dry) from the connected indoor units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority. The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling, dry
1. Priority mode decision methods Method 1. (Default value) The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating Priority when heating depending on which operation mode (cooling, heating) was input first. After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there was a Stop input from all the indoor units.
Neutral
Cooling priority
Heating priority
Method 2. (Management by outdoor unit) Operation mode management is made "Management by outdoor unit" by outdoor unit PUSH-SW (field setting). The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the outdoor unit regardless of the current mode.
Cooling priority
Heating priority
03-02
Page 47
Method 3. (Management by indoor unit) Operation mode management is made "Management by indoor unit" by outdoor unit PUSH-SW (field setting). Then the master indoor unit is set by wired remote controller. Thereupon the priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the master indoor unit regardless of the current priority mode. The priority mode is fixed at either cooling or heating even if the master indoor unit stops Cooling/heating switching can be performed by the master indoor unit only.
Cooling priority
Heating priority
(4) Opposite operation mode When the operation mode commanded from an indoor unit (remote controller) and the operation mode allowed by the system (cooling and dry operation for cooling only type and operation mode allowed by priority mode for heat pump type) do not match, it is indicated by blinking of an LED.
Timer lamp: 3 secs ON/1 sec OFF repeated
03-03
Page 48
3-2-2 Auto Changeover
[Method]
1. Switch operation mode management to "Management by indoor unit" by outdoor unit DIP-SW.
2. Set the master indoor unit by wired remote controller.
3. Judge cooling/heating by the difference between the master indoor unit's setting temperature and the room temperature.
AUTO CHANGEOVER operation
Operation flow chart
START
Room temp.
Ts+2°C ?
NO
YES
YES
or operation command other than
Room temp.
Ts- 2°C ?
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
auto changeover operation?
NO
YES
NO
YES
TS : Setting temperature
in OFF state for 6 minutes or
or operation command other than
auto changeover operation?
COOLING OPERATION
Thermostat remains
longer?
NO
System stops
YES
YES
NO
NO
03-04
Page 49
3-2-3 "COOL" Position
When using the cooling mode, set the temperature to a value lower than the current room temperature, otherwise
the indoor unit will not start the cooling operation and only the fan will rotate.
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
TR
• Temperature
• Refrigerant flow
• Opening of EEV
• Indoor fan
Ts + 0.5 C
Ts
Ts - 0.5 C
3Min.
ON OFF
100% 0%
ON OFF
Ts : Corrected setting temperature
TR : Corrected room temperature
Ts + 0.5 C Ts - 0.5 C
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
3-2-4 "HEAT" Position
(1) When using the heating mode, set the temperature to a value higher than the current room temperature, otherwise
the indoor unit will not start the heating operation.
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to blow out warm air.
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation
(3)
will be temporarily interrupted.
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
Ts + 0.5 C
• Temperature
• Refrigerant flow
• Opening of EEV
• Indoor fan
Ts
Ts - 0.5 C
ON OFF
100% 0%
ON OFF
1Min.
4Min.
Ts : Corrected setting temperature TR : Corrected room temperature
: Duration of cold air prevention
4Min.
1Min.
Ts + 0.5 C Ts - 0.5 C
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
4Min.
TR
1Min.
03-05
Page 50
3-3 LOUVER CONTROL
(1) ADJUSTING THE DIRECTION OF AIR CIRCULATION
Instructions relating to heating ( ) are applicable only to heat pump type outdoor unit.
Begin air conditioner operation before performing this procedure.
Vertical Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Press the VERTICAL AIR FLOW DIRECTION SET button.
Example : When set to vertical air direction.
Press the VERTICAL AIRFLOW DIRECTION button. The temperature display will change to the vertical airflow direction setting display.
Press the VERTICAL AIRFLOW DIRECTION button to change the vertical louvre position. The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4
Heating : 1 , 2 , 3 , 4
LARGE CEILING TYPE
1
2
3
4
COMPACT WALL MOUNTED TYPE
1
2
UNIVERSAL FLOOR/CEILING TYPE
3
1
2
3
4
DANGER!
Never place fingers or foreign objects inside the outlet ports, since the internal fan opertes at high speed and could cause personal injury.
4
CASSETTE TYPE
WALL MOUNTED TYPE
4
Always use the remote control umit's AIR FLOW DIRECTION button to adjust the UP/DOWN air direction flaps or
1
2
3
4
RIGHT/LEFT air direction louvers. At­tempting to move them manually could result in improper operation; in this case, stop operation and restart. The louvers should begin to operate
1
2
3
4
properly again. When used in a room with infants, chil­dren, elderly or sick persons, the air direction and room temperature should be considered carefully when making settings.
Use the air direction adjustments within the ranges shown above.
1
2
3
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
During Cooling mode : Horizontal flow During Heating mode : Downward flow
1
4
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal ,
1
the air direction cannot be adjusted during this period.
03-06
Page 51
Horizontal Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE" and "WALL MOUNTED TYPE".
Press the HORIZONTAL AIR FLOW DIRECTION SET button.
Press the HORIZONTAL AIRFLOW DIRECTION button. The temperature display will change to the horizontal airflow direction setting display.
Press the HORIZONTAL AIRFLOW DIRECTION button to change the horizontal louvre position. The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4 , 5
Heating : 1 , 2 , 3 , 4 , 5
Example : When set to horizontal air direction.
LARGE CEILING TYPE
1
5
2
4
3
WALL MOUNTED TYPE
1
2
3
4
5
UNIVERSAL FLOOR/CEILING TYPE
3
2
1
4
5
(2) SWING OPERATION
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Begin air conditioner operation before performing this procedure.
To select Vertical airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Press the VERTICAL SWING button for more than two seconds.
The remote controller's Vertical Swing Display will light up. In this mode, the UP/DOWN air direction flaps will swing automat­ically to direct the air flow both up and down.
Example : When set to vertical swing.
To Stop Vertical airflow SWING Operation
Press the VERTICAL SWING button for more than two seconds once and again.
The remote controller's Vertical Swing Display will go out. Airflow direction will return to the setting before swing was begun.
03-07
Page 52
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE", and "COMPACT WALL MOUNTED TYPE".
About Vertical Airflow SWING Operation
The SWING operation may stop temporarily when the air conditioner's fan is not operating, or when operating at very low speeds.
The swing operation is not available depending on the model. Please refer to the operating manual for the indoor unit.
To select Horizontal Airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "WALL MOUNTED TYPE".
Press the HORIZONTAL SWING button for more than two seconds.
The remote controller's Horizontal Swing Display will light up. In this mode, the RIGHT/LEFT air direction louvers will swing automatically to direct the airflow both right and left.
Air swing range
Air flow direction set
1 2 3 4
Range of swing
1 to 4 (All range)
Example : When set to horizontal swing.
To stop Horizontal airflow SWING Operation
Press the HORIZONTAL SWING button for more than two seconds once and again.
The remote controller's Horizontal Swing Display will go out. Airflow direction will return to the setting before swing was begun.
About Horizontal Airflow Swing Operation
Left and right swing range can be changed in 3 steps by field setting.
The SWING operation may stop temporarily when the air conditioner's fan is not operating, or when operating at very low speeds.
The swing operation is not available depending on the model. Please refer to the operating manual for the indoor unit.
Left and right swing range
Range of swing
1 to 5 (All range)
1 to 3 3 to 5
Function Number
24
( Factory setting)
Setting Value
00 01 02
03-08
Page 53
3-4 ELECTRONIC EXPANSION VALVE CONTROL
1. Initialization
When the power is turned ON. When it has passed the limited time since the last initialization.
2. Operation Control
When indoor unit stopping
Outdoor unit Condition
OFF
Cooling
Heating
When starting up
(Cooling) Move to the cooling control base pulse in steps. (Heating) Move to the heating control base pulse in steps.
Automatic operatic control
Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Room temperature control
The room temperature is controlled so that it reaches to the set-up temperature based on the difference between the room temperature and the set-up temperature, and the change of indoor unit temperature. if the room temperature becomes 0.5 C lower than the set-up temperature, EEV is fully closed.
EEV Condition
Fully closed
Fully closed
Slightly open
3. Special Control
Oil recovery operation : Controlled pulse. Test run operation : Controlled pulse. Icing protection control : Fully closed. Pump down operation : Fully open. Defrost operation : Controlled pulse
3-5 DRAIN PUMP OPERATION
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously. (2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped. (3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost prevention operation. (4) When the water level in the drain pan rises up and then the float switch functions:
Microcomputer stops the refrigerant circulation and indoor fan motor operation.
1
Drain pump operates continuously for 3 minutes after the float switch is turned off.
2
(Almost condensing water may be drained) (5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates. (6) When the float switch turns OFF within 3 minutes, the unit starts cooling operation.
03-09
Page 54
3-6 FUNCTION
3-6-1 Auto Restart
The air conditioner restarts with the previous setting operation.
3-6-2 Icing Protection Control
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition Compressor is operation more than 3 minutes. When "Heat exchanger inlet temperature TA" continues *4 minutes or more. Compressor is operation more than 3 minutes. When "Heat exchanger outlet temperature TA" continues 4 minutes or more.
(2) Operation EEV is closed. Fan is at the setting amount.
(3) Completing Condition Heat exchanger inlet and middle temperature TB After more than 5 minutes
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
*
TA
1°C
TB
7°C
3-6-3 Oil Recovery Operation
[Oil recovery operation] : It periodically returns the residual refrigerant ion oil in the indoor unit and the connection piping back to the outdoor unit , and prevents the compressor oil level from decreasing.
Indoor unit LED : Operation LED
6 sec ON 2 sec OFF Blinking
Indoor fan : Same operation before oil recovery operation.
Indoor EEV : Control pulse
During the above operation, a refrigerant noise may be from the indoor unit.
03-10
Page 55
3-7 TIMER CONTROL
3-7-1 Wireless Remote Controller
UTY - LNH
There are following 4 kinds of timer modes are available.
ON Timer OFF Timer PROGRAM Timer SLEEP Timer
1. ON / OFF TIMER
The timer functions cannot be used when this controller is used together with the remote controller (Wired type). A beeping sound is made when a signal is received.
To set the ON / OFF timer
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
Press the TIMER MODE button to select
1
2. PROGRAM TIMER
To set the PROGRAM timer
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
1
"OFF TIMER" or "ON TIMER"
CANCEL OFF TIMER ON TIMER
PROGRAM TIMER (OFF ON, OFF ON)
Select "OFF TIMER" Adjust the OFF time. Select "ON TIMER"
2
2
3
Adjust the OFF or ON time.
(About 5 seconds later, the entire display will reappear.)
Adjust the ON time.
(About 5 seconds later, the entire display.
4 5
will reappear.)
To cancel the TIMER
Select "CANCEL".
The air conditioner will return to normal op­eration.
*To change operating conditions
If you wish to change the operating conditions (ON/OFF,Mode, Fan Speed, Temperature Setting), after making the time set­ting, wait until the entire display reappears, then press the ap­propriate buttons to change to the desired operating condition.
Select "PROGRAM TIMER"
(Either OFF ON or OFF ON will display.) (If the ON timer has been se­ lected to operate first, the unit will stop operating at this point.)
* Even ON/OFF and Sleep timer are valid.
3. SLEEP TIMER
To set the SLEEP timer
Unlike other timer functions, the SLEEP timer is designed to set the duration of time in which the unit does not operate. The SLEEP timer can be set regardless of whether the indoor unit is operating or stopped.
(Both the indoor unit's OPERATION indi-
1
To change the timer settings
cator lamp (green) and the TIMER indi­ cator lamp (orange) will light.)
1 2
Press the SLEEP button once again.
Set the time using the TIMER SET buttons.
2
*To cancel the TIMER
Select "CANCEL".
The air conditioner will re­turn to normal operation.
Adjust the OFF time.
(About 5 seconds later,the entire display will reappear.)
*To stop air conditioner operation during timer operating
03-11
* Even ON/OFF and Program timer are valid.
Page 56
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sieeping.
Cooling operation / dry operation Heating operation
When the sleep timer is set, the set temperature automatically rises 1°C every hour.The set temperature can rise up to a maximum of 2°C
When the sleep timer is set, the set temperature sutomatically drops 1°C every 30 minutes. The set temperature can drop to a maximum of 4°C
60min.
Timer setting
1°C
2°C
30min.
60min.
1 C
2 C
90min.
Timer setting
3 C
4 C
03-12
Page 57
3-7-2 Group Remote Controller
UTY - CGG
WEEKLY TIMER
Different schedules can be set for each day of the week.
Four timers can be set for each day
1. WEEKLY TIMER
The timer function is not available depending on the initial setting.
Different schedules can be set for each day of the week. Four timers can be set for each day. Operation on/off time, operation mode, and temperature can be specified for each timer.
To start / cancel the WEEKLY timer operation
The timer does not start if the time is not set.
Press the ALL TIMER button to start or cancel the WEEKLY timers for all indoor units.
If any of the indoor units are in the timer mode, pressing this button cancels the timers for all indoor units. If none of the indoor units are in the timer mode, pressing this button starts the timers for all indoor units.
Press the Select button to select the indoor unit.
Press the Timer Mode (DELETE) button to start or cancel the WEEKLY timers.
Note: When a time is not set, the weekly timer cannot be started.
To set the WEEKLY timer
1
Press the PROGRAM (CLOCK AD­JUST) button.
3
Press the DAY button to select the day of the week.
* For ALL, all of the days can be set together when a appears around each day.
4

* Do not press this button for two sec­ onds or more, otherwise you will en­ ter the time setting mode.
Day of the week setting

Timer setting
Decrement Increment
2
Press the Select button to select the indoor unit.
* If all indoor units are selected, the times for all of the registered indoor unit timers are set at once.
ALL
Press the Set Time buttons to set the time in 10-minute increments. * Hold down a Set Time button to adjust the time quickly.
S M T W T F S
SUN MON TUE WED THU FRI SAT
All indoor units
* The time already set at another timer is skipped at the relevant indoor unit.
03-13
Page 58
5
Operating setting
Press the Start/Stop button or the Mode button or the Set Temperature button to set the operation.
* For the operations that can be set, refer to "Operation mode setting", "Room tem­ perature setting", and "To start /stop operation" , in "OPERATION". * Only the current operation settings are displayed.
Raise
Lower
Setting the next timer for the same day:
AM
ex.TIMER-1 will start operation at 8:00 on COOL.
6
TIMER-1 TIMER-2 TIMER-3 TIMER-4
Then press the ENTER button to proceed to the time setting, and repeat steps from to .
Repeat steps to to set the timer for another day of the week.
Be careful for pressing the ENTER button without any operation setting because the time that is set will be cancelled.
Setting the timer for the other indoor units:
3 5
7
Before setting the timer for other indoor units, press the ENTER button to confirm the settings. * The display switches to the next timer.
Repeat steps to to set the timer for other indoor units.
2 6
4 5
8
1. Press the ENTER button to confirm the set timer.
2. Press again the PROGRAM (CLOCK ADJUST) button to complete the weekly timer setting.
* flashes for two seconds.
To delete the operating time
NOTES
(1) The WEEKLY timer does not operate when the HEAT timer is set if a HEAT PUMP MODEL in the air conditioning system is operating in the cooling mode. In addition, the WEEKLY timer does not operate when the COOL or DRY timer is set if a HEAT PUMP MODEL in the air conditioning system is operating in the heating mode. (2) Even if the timer operation is set, the timer lamp of the indoor unit does not light up. (The timer lamp is used for wireless remote controller only.) (3) If the same time is set in Timer-1 to Timer-4 of an indoor unit, the timer setting of the smallest number will be effective.

1. If the Timer Mode (DELETE) button is pressed during steps to , the operat­ ing time for the selected day will be deleted. * If all the days are selected, the operating times for all of the days of the se­ lected timer will be deleted.
2. Press the ENTER button to confirm the deletion.
When the operating time is set, the mark appears.
ex. TIMER-1 will start operation at 8:00 on COOL with a set­ ting of 20 C
3 7
03-14
Page 59
3-7-3 Wired Remote Controller
UTY - RNK
ON / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
The timer function is not available depending on the model.
To set the ON/OFF timer
1
No display
NON STOP
To cancel
Press the timer mode button to se­lect the ON timer or OFF timer.
It is switched every time as shown in the below diagram when the button is pressed.
OFF TIMER
Press the DELETE button to cancel the timer mode. The timer mode can also be canceled by changing the timer mode using the timer mode button.
ON TIMER
WEEKLY TIMER
SUMOTUWETH FR
SA
2
From 1 to 24 hours
Press the set time buttons to set the time. After the time is set, the timer will start automatically. The amount of time until the OFF timer operates that is displayed on the timer display decreases as time passes.
ex. OFF timer set for 6 hours
03-15
Page 60
2. WEEKLY TIMER
The timer function is not available depending on the model.
Weekly timer setting
1
Press the timer mode button to select the weekly timer.
Day of the week setting
3
1
Press the DAY button to select the day of the week, and then press the TIMER SET button to confirm the setting.
For ALL, all of the days can be set together when a each day.
Time setting (ON / OFF timer)
2
SUMOTUWETH FR
369
ALL SU MO TU WE TH FR SA
SA
12 15 18 21
appears around
4
1
2
2
Press the SET button for 2 sec­onds or more.
SUMOTUWETH FR
369
When the operating time is set, the
mark appears.
SA
12 15 18 21
ON-1 OFF-1 ON-2 OFF-2
ex. The timer is set for 7:00-18:00.
Press the SET TIME buttons to set the ON time in 30-minute increments, then press the TIMER SET button to proceed to the OFF time setting. Set the OFF time in the same way. If necessary, set the second weekly timer settings in the same way.
Time setting (Independent OFF timer)
Switching from ON/OFF timer to independent OFF timer
The independent timer will flash on the display.
1
ON-2 OFF-2 OFF-2 OFF-3
Press the TIMER MODE button to change to the independent OFF timer setting. * The time setting process is the same as the ON/OFF timer. Press the TIMER MODE button to return to the ON/OFF timer setting.
To delete the operating time
5
6
Repeat steps and to set the weekly timer for another day of the week.
3 4
Press the TIMER SET button for 2 seconds or more to complete the weekly timer settings.
03-16
If the TIMER DELETE button is pressed during steps or , the operating time for the selected day will be deleted. If all the days are selected, the operating times for all of the days will be deleted.
3
4
Page 61
To start /cancel the WEEKLY timer operation
To start
The independent timer will flash on the display.
369
ex.Operating time 7:00-18:00 Indpnd. OFF time 21:00
When the weekly timer is selected, the timer starts automatically.
The operating time for the current day is displayed.
NOTES
(1) PRECAUTIONS DURING WEEKLY TIMER SETUP Setup is not possible in the following cases, so amend the time. Be sure to set the ON time first, then the OFF time. If either the ON time or the OFF time is not set cor rectly, the timer will not operate properly. The WEEKLY 2 settings cannot be set earlier than the WEEKLY 1 settings. The WEEKLY 1 and WEEKLY 2 time spans cannot overlap.
To cancel
12 15 18 21
(2) The earliest OFF time you can set is 30 minutes after the ON time. (3) The OFF time can be carried over to the next day. (4) The earliest independent OFF time you can set is 30 min­ utes after the last OFF time. (5) An independent OFF time can be set up to 0:00 hours of the next day. (6) Even if the timer operation is set, the timer indicator lamp of the indoor unit does not light up. (The timer indicator lamp is used for wireless remote controllers only.)
Press the TIMER DELETE button to cancel the timer mode. The timer mode can also be canceled by changing the timer mode using the TIMER MODE button.
To set the DAY OFF (for a holiday)
1
During the weekly timer, press the TIMER SET button for 2 seconds or more to set the day.
SUMOTUWETH FR
2 3 4
Select the day to set the DAY OFF.
SA
SUMOTUWETH FR
Press the DAY (DAY OFF) button for 2 seconds or more to set the DAY OFF.
SA
Flashing mark: indicates the DAY OFF.
Press the TIMER SET button for 2 seconds or more to complete the DAY OFF setting.
To cancel
369
12 15 18 21
ex. The DAY OFF is set for Monday.
369
12 15 18 21
Follow the same procedures as those for setup.
NOTES
The DAY OFF setting is only available for days for which weekly settings already exist. If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
Normal Next day setting
DAY OFF
DAY OFF
ON OFF ON OFF
WEEKLY WEEKLY
Setting dayPreceding day Next day Setting dayPreceding day Next day
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
ON
WEEKLY
03-17
OFF
ON
WEEKLY
OFF
Page 62
3. TEMPERATURE SET BACK TIMER
The timer function is not available depending on the model.
Temperature SET BACK timer setting
SET BACK
SUMOTUWETH FR
1
369
Press the SET BACK button to change to the SET BACK con­firmation display. The SET BACK operating time and the set temperature will be displayed.
Day setting Operating time setting
3
1
Follow step and in "To set the WEEKLY timer". The DELETE button is also used as described in the procedures for the weekly timer.
3 4
Temperature setting
2
4
SA
12 15 18 21
3
Press the set temperature buttons to set the temperature. (The temperature setting range is the same as the range for the operation mode.)
SUMOTUWETH FR
SA
If there is no existing SET BACK tempera­ture setting, " - - " will be displayed for the temperature.
4
2
Press the SET button for 2 seconds or more.
SUMOTUWETH FR
369
ex. When setting all days together
SA
12 15 18 21
5
369
12 15 18 21
ex. Operating time 15:00 - 22:00
ON OFF
SET BACK temperature
Normal temperature
To start /cancel the temperature SET BACK timer operation
To start
SET BACK
24°C
SUMOTUWETH FR
28°C
24°C
SA
Repeat steps and . Press the SET button for 2 sec­onds or more to complete the temperature SET BACK timer settings.
To cancel
3 4
1
ex. Display during SET BACK timer operation (The operating time will not be displayed.)
Press the SET BACK button. The SET BACK confirmation display appears for 5 seconds, and then the timer starts automatically.
NOTES
The SET BACK timer only changes the set temperature, it cannot be used to start or stop air conditioner operation. The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used. The SET BACK timer can be used together with the ON, OFF, and weekly timer functions. The SET BACK operating time is displayed only in the SET BACK confirmation display. (Refer to step 1 for the SET BACK confirmation display. )
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower. Room temperatures as low as 10, 12, and 14°C cannot be set depending on the model.
Press the SET BACK button, and then press the DELETE button while the SET BACK confirmation display is dis­played. Even if the SET BACK button is pressed again, the SET BACK timer will be cancelled.
2
03-18
Page 63
4. TROUBLE SHOOTING
Page 64
4. TROUBLESHOOTING
4-1 NORMAL OPERATION
4-1-1 Indoor Unit Display
Flashing PatternIndication LampIndication type
Operation
Continuous lighting
Operation LED
Continuous lighting(lowered light)Anti Freeze
Continuous lighting(lowered light)Timer LEDTimer
Filter Filter LED Continuous lighting
1 sec 1 sec
Operation LED
ON
OFF
Power Failure
1 sec
1 sec
6 sec 2 sec
Defrosting
Oil Recovery
Timer LED
Operation LEDTest Operation
Timer LED
Operation LED
ON
OFF
ON
OFF
ON
OFF
1 sec
1 sec
Opposite Operation Mode
Maintenance Mode
Timer LED
Operation LED
Timer LED
Filter LED
ON
OFF
ON
OFF
3 sec 1 sec
1 sec 1 sec
04-01
Page 65
4-1-2 OUTDOOR UNIT DISPLAY
Indication type 7 Segment LED Pattern
Idling(stop)
Cooling Mode
Heating Mode
Oil Recovery Operation
Defrost Operation
System stooped with Discharge Temp. Protection
System stopped with High Pressure Protection
System stopped with Low Pressure Protection
System stopped with compressor Temperature Protection
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" ROTECT "4"
Description
Refer to 02-10 page for operation.
Refer to 02-11 page for operation.
<Starting condition> Discharge temp fixed value: 115°C <Release condition> 3 minutes have elapsed and discharge temperature 80°C
<Starting condition> High pressure 4.00MPa <Release condition> 5 minutes have elapsed and high pressure 3.50MPa
<Starting condition> Low pressure 0.05MPa or low pressure 0.10MPa continues for 10 minutes <Release condition> 3 minutes have elapsed and low pressure 0.17MPa
<Starting condition> Compressor temp fixed value :110°C <Release condition> 3 minutes have elapsed and discharge temperature 80°C
Peak Cut Mode
Low Noise Mode
Inverter Compressor Operation Indication
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
LED104
POWER LED101
ERROR LED102
"P" eak "C" ut
"L" OW "N" OISE
Blinking
ON
OFF
ON
OFF
Refer to 02-08 page for operation.
ON
1 sec 1 sec
OFF
04-02
Page 66
4-2 ABNORMAL OPERATION
4-2-1 Indoor Unit Display
Please refer the flashing pattern as follows.
Error Contents
Remote Controller Communication Error
Network Communication Error
Indoor Unit Parallel Communication Error
Indoor Unit Power Frequency Abnormal
Indoor Unit Main PCB Error
Room Temperature Sensor Error
Indoor Unit Heat Ex. Sensor Error
Indoor Unit Fan Motor Error
Water Drain Abnormal
Outdoor Unit Error
1 times flash
1 times flash
4 times flash
4 times flash
5 times flash
5 times flash
9 times flash
4 times flash
6 times flash
3 times flash
15 times flash
Filter LEDTimer LEDOperation LED
Continuous flash2 times flash1 times flash
Continuous flash
Continuous flash
Continuous flash1 times flash3 times flash
Continuous flash 2 times flash3 times flash
Continuous flash1 times flash
Continuous flash2 times flash
Continuous flash1 times flash
Continuous flash
Continuous flash
Trouble shooting
9
11
10
2
1,3
4
5,6
8
7
12 ~ 48
Depending on contents of Outdoor unit, it may not indicate. (Refer to "TROUBLE LEVEL OF SYSTEM")
Error Indication Flashing Pattern
Example : Indoor Unit Main PCB Error (Operation LED : 3 times, Timer LED : 2 times)
1 cycle
ON
1.0s
Operation LED
Timer LED
Filter LED
OFF
ON
OFF
ON
OFF
0.5s 0.5s
0.1s / 0.1s
0.5s 0.5s 0.5s 0.5s
4.0s
1.0s
3.0s
0.5s 0.5s
0.5s 0.5s
1.0s
4.0s
04-03
Page 67
4-2-2 Outdoor Unit Display
LED display
POWER
ERROR
MODE
POWER MODE LED : on ERROR LED : blink
LED101
LED102
(GREEN)
(RED)
Operation button
MODE
SW107
EXIT
SELECT
SW108 SW109
ERROR transition
Short press : less than 3 seconds Long press : more than 3 seconds
POWER
ON
LED101
OFF
0.1sec 0.1sec
ON
ERROR LED102
OFF
ENTER
Annunciation
"Err." and quantity are alternately shown.
"ENTER" short press"ENTER" short press
Type of errors
ex : discharge thermistor 1 abnormal ex : indoor unit abnormal
"SELECT" short press display change
When there is more than one error, display is changed by "SELECT" short press.
"ENTER" short press"ENTER" long press
*
If some error is newly occured or resolved during transition, it is reflected after going back to "Annunciation".
Address
"SELECT" short press display change
When more than one indoor unit is abnormal, display is changed by "SELECT" short press.
04-04
* Only in the case of "indoor unit abnormal (E.5U.1)", indoor unit address is shown by ENTER long press.
Page 68
4-2-3 Error Code List for Outdoor Unit
Error
Code
- - - -
1 4 . 2
1 4 . 5
2 8 . 1
2 8 . 4
5 U . 1
6 2 . 3
6 2 . 6
6 2 . 8
6 3 . 1
6 7 . 2
6 9 . 1
7 1 . 1
7 2 . 1
7 3 . 3
Error Contents
Initial Setting Error
Outdoor unit Network communication abnormal 2
The number of Indoor unit shortage
Auto Address Setting Error
Signal Amplifier Auto Address Setting Error
Indoor Unit Error
Outdoor Unit EEPROM Access Error
Inverter Communication Error
EEPROM Data corrupted Error
Inverter Error
Inverter PCB short intereuption detection
Outdoor Unit transmission PCB Parallel Communication Error
Discharge Temp. Sensor Error < TH1 >
Compressor Temp. Sensor Error < TH10 >
Heat Ex. Liquid pipe Temp. Sensor Error < TH5 >
Trouble
shooting
12
14
48
46
47
1 - 11
15
16
17
18
19
20
21
22
23
Error Code
9 3 . 1
9 4 . 1
9 5 . 5
9 7 . 1
9 7 . 4
9 7 . 5
9 8 . 5
A 1 . 1
A 3 . 1
A 4 . 1
A 4 . 2
A 5 . 1 Low Pressure Abnormal
Inverter Compressor Start Up Error
Trip Detection
Compressor Motor Loss of Synchronization
Outdoor Unit Fan Motor Lock Error (Start up Error)
Outdoor unit FAN motor under voltage (Lack of DC Voltage)
Outdoor Unit Fan Motor 1 Temperature Abnormal 39
Outdoor Unit Fan Motor Lock Error (Start up Error)
Outdoor Unit Fan Motor 2 Temperature Abnormal 39
Coil ( Expansion Valve 1 ) Error 409 A . 1
Coil ( Expansion Valve 2 ) Error 409 A . 2
Discharge Temperature Abnormal
Compressor Temperature Abnormal
High Pressure Abnormal
High Pressure Protection 1
Error Contents
Trouble
shooting
34
35
36
37
38
379 8 . 1
41
42
43
44
45
7 4 . 1
7 5 . 1
7 7 . 1
8 2 . 1
8 2 . 2
8 3 . 2
8 4 . 1
8 6 . 1
8 6 . 3
8 6 . 4
Outdoor Temp. Sensor Error < TH3 >
Suction Gas Temp. Sensor Error < TH4 >
Heat Sink Temp. Sensor Error < IPM built in >
SC HE. Gas Inlet Temp. Sensor Error < TH8 >
SC HE. Gas Outlet Temp. Sensor Error < TH9 >
SC HE. Liquid Outlet Temp Sensor Error < TH7 >
Current Sensor Error
Discharge Pressure Sensor Error
Suction Pressure Sensor Error
High Pressure Switch Error
24
25
26
27
28
29
30
31
32
33
04-05
Page 69
4-2-4 Remote Controller Display
<< SIMPLE REMOTE CONTROLLER >>
ERROR CODE DISPLAY
If an error occurs, the following display will be shown. ( will appear in the set room temperature display.)
is displayed, immediately contact authorized
If service personnel.
<< WIRED REMOTE CONTROLLER >>
Error code
Faulty unit No. (Remote controller address)
Ex. Error code display
ERROR CODE DISPLAY
If an error occurs, the following display will be shown. ( will appear in the set room temperature display.)
is displayed, immediately contact authorized
If service personnel.
<< GROUP REMOTE CONTROLLER >>
ERROR CODE DISPLAY
The air conditioning system must be inspected if “ : “ (error code) appears on the timer and Clock Display, or the
operation lamp is flashing.
*1 ;
Model code
: Outdoor unit : Indoor unit : Group remote controller : Convertor
Unit number (usually 0) Error code
Ex. Error code display
Model code
Error code
Ex. Error code display
*1
04-06
Page 70
4-2-5 Error Code List for Simple and Wired Remote Controller
Error Code
1 2
1 4
1 5
1 6
3 1
3 2
Error Contents
Remote Controller Communication Error
Network Communication Error
Scan Error
Indoor Unit Parallel Communication Error
Indoor Unit Power Frequency Abnormal
Indoor Unit Main PCB Error
Trouble
shooting
9, 82
11
83
10
2
1, 3
Error Code
4 1
4 2
5 1
5 3
9 U
4-2-6 Error Code List for Group Remote Controller
Error Code
- -
1 2
1 4
1 5
1 6
Error Contents
Initial Setting Error
Remote Controller Communication Error
Network Communication Error
Scan Error
Indoor Unit Parallel Communication Error
Trouble
shooting
12
9,10,71,77
11,13,14,80
83
10
Error Code
8 2
8 3
8 4
8 6
9 3
Error Contents
Room Temperature Sensor Error
Indoor Unit Heat Ex. Sensor Error
Inddor Unit Fan Motor Error
Water Drain Abnormal
Outdoor Unit Error
Error Contents
Sub-cool Heat Ex. Gas Temperature Sensor Error
Liquid Pipe Temperature Sensor Error
Current Sensor Error
Pressure Sensor Error
Compressor Start Up Error
Trouble
shooting
4
5, 6
8
7
12 48
Trouble
shooting
27,28
29
30
31 33
34
2 6
2 8
3 1
3 2
4 1
4 2
5 1
5 3
6 2
6 3
6 7
6 9
7 1
7 2
7 3
7 4
7 5
Address Setting Error
Other Setting Error
Indoor Unit Power Frequency Abnormal
Indoor Unit Main PCB Error
Room Temperature Sensor Error
Indoor Unit Heat Ex. Sensor Error
Indoor Unit Fan Motor Error
Water Drain Abnormal
Outdoor Unit Main PCB Error
Inverter Error
Inverter PCB short interruption detection
Outdoor Unit transmission PCB Error
Discharge Temperature Sensor Error
Compressor Temperature Sensor Error
Heat Ex. liquid pipe Temperature Sensor Error
Outdoor Temperature Sensor Error
Suction Gas Temperature Sensor Error
78
46, 47
2
1, 3
4
5, 6
8
7
15 17
18
19
20
21
22
23
24
25
9 4
9 5
9 7
9 8
9 A
A 1
A 3
A 4
A 5 Low Pressure Abnormal
C 4 PCB Error 76
C A Software Error 67, 74
C 1 PCB Error 1 65, 70
Trip Detection
Compressor Motor loss of Synchronization
Outdoor Unit Fan Motor 1 Error
Outdoor Unit Fan Motor 2 Error
Coil ( Expansion Valve ) Error
Discharge Temperature Abnormal
Compressor Temperature Abnormal
High Pressure Abnormal
35
36
37 39
37 39
40
41
42
43, 44
45
7 7 Heat Sink Temperature Sensor Error
26
04-07
Page 71
4-2-7 TROUBLE LEVEL OF SYSTEM
<< System Condition when Outdoor Unit Error is occurred >>
1 2
System Condition
Outdoor unit Condition
>Abnormal >LED indication >Outdoor unit does not stop
(1) Not indicated on Indoor Unit. Not indicated on Peripheral Unit. Indicated on Service Tool.
(Not available)
Trouble Level
(2) Indicated on Indoor Unit. Indicated on Peripheral. Indicated on Service Tool.
> Suction gas Temp sensor error > Outdoor Temp sensor error > Sub-cool heat Ex. gas inlet Temp sensor error > Sub-cool heat Ex. gas outlet Temp sensor error
System is not stopped compulsorily
>Abnormal >LED indication >Outdoor unit does not stop
>Temporary blackout detection protection (Inverter compressor stop)
> Discharge temperature abnormal (Inverter compressor stops) > Compressor temperature abnormal (Inverter compressor stops) > High pressure switch error (Inverter compressor stops) > High pressure switch error (Constant speed compressor stops) > Discharge Temp sensor error (Inverter compressor stops) > Compressor Temp sensor error (Inverter compressor stop) > Heat sink Temp sensor error (Inverter compressor stop) > Current sensor error (Inverter compressor stop) > High pressure switch error (Inverter compressor stop) > Inverter error (Inverter compressor stop) > Heat sink temperature abnormal (Inverter compressor stop) > Inverter compressor start up error (Inverter compressor stop) > Trip detection (Inverter compressor stops) > Rush current limiting resister Temp rise protection (Inverter compressor stop) > Comp. motor loss of synchronization (Inverter compressor stop) > Inverter communication error (Inverter compressor stop) > Outdoor unit EEPROM access error > Outdoor unit EEPROM data corrupted
> Indoor unit number shortage
This will not be displayed on indoor unit which Error Report Target(function setting 47 of indoor unit) is set "for administrator".
04-08
Page 72
System Condition
System is compulsorily stopped.
Outdoor unit Condition
>Abnormal >LED indication >Outdoor unit stops >Need to repair >secondary accident is possible.
Trouble Level
1 2
(1) Not indicated on Indoor Unit. Not indicated on Peripheral Unit. Indicated on Service Tool.
(Not available) >High pressure abnormal
(2) Indicated on Indoor Unit. Indicated on Peripheral. Indicated on Service Tool.
>Low pressure abnormal >Fan motor 1 lock error >Fan motor 2 lock error >Fan motor 1 temp. abnormal >Fan motor 2 temp. abnormal >Heat Ex. liquid Temp sensor error >Discharge pressure sensor error >Suction pressure sensor error >Outdoor unit communication PCB parallel communication error >Outdoor unit network communication 2 error >Lack of DC Voltage >Indoor unit number shortage >SC HE. Liquid Outlet Temp Sensor Error
<Important>
Even if power is reset, the following Error cannot release.
- Discharge temperature abnormal
- Compressor temperature abnormal
- Current sensor error
- Inverter compressor start up error
- Trip detection
- Rush current limiting resister Temp rise protection
- Comp. motor loss of synchronization
- Low pressure abnormal
- Fan motor 1 lock error
- Fan motor 2 lock error
These errors can not be judged without operating the system, and the serviceman would not be able to check it if the system power is turned off before visiting the site for repair. In Error release, you need to operate push switch and apply "Error reset" (F3-40) after power restart.
04-09
Page 73
Page 74
4-3 TROUBLE SHOOTING
4-3-1 Trouble shooting with error code (INDOOR UNIT)
Trouble shooting 1 INDOOR UNIT Error Method:
Model Information Error (Indoor Unit Main PCB Error)
Indicate or Display: Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Error Code : 3 2
Detective details:
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause : 1. Outside cause 2. Connection failure of electric components 3. Controller PCB defective
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
3 continuous failure of read test of EEPROM at Power ON, or Apparent Model information error from EEPROM. Also, Error on Model information upon model information test of EEPROM, or Model information of EEPROM not possible to recover.
NO
YES
Check Point 2 : Check Indoor Unit electric components
Check all connectors (loose connector or incorrect wiring) Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
04-11
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
Page 75
Trouble shooting 2 INDOOR UNIT Error Method:
Power Frequency Abnormal
Indicate or Display: Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 3 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash.
Error Code : 3 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause : 1. Outside cause 2. Installation failure 3. Defective connection of electric components
4. Controller PCB defective
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
Detective details:
When 5 continuous failures occurred at Power frequency test.
NO
YES
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Check Point 2 : Check Installation condition
Check Cable/Breaker Check loose or removed connection
>> If Installation defect is found, correct it by referring
to Installation Manual.
OK
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Wrong power supply installation ----- Check if the power supply frequency is stable or not.
Check Point 3 : Check connection of electric components
Check power supply voltage (AC230V between Indoor unit terminal 1 and 2) Check connection of Connector (any lose connector or incorrect wiring) Check any shortage or corrosion on PCB.
AC
OK
Check Point 4 : Replace Controller PCB
Change Controller PCB and set up the original address.
04-12
Page 76
Trouble shooting 3 INDOOR UNIT Error Method:
EEPROM Access Abnormal (Indoor Unit Main PCB Error)
Indicate or Display: Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause :
1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Detective details:
When 3 continuous failure occurred on read test of EEPROM.
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
YES
Check Point 2 : Check Indoor Unit electric components
Check all connectors (loose connector or incorrect wiring) Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
NO
Check Point 1-2 :­Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
04-13
Page 77
Trouble shooting 4 INDOOR UNIT Error Method:
Room Temperature Sensor Error
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash.
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit Indoor Temperature Thermistor
Forecast of Cause :
1. Connector defective connection 2. Thermistor defective 3. Controller PCB defective
Detective details:
When Indoor thermistor open or shortage is detected at power ON.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
2520151050
10.012.515.820.125.233.6Resistance Value ( )
Temperature (°C)
504540
30
8.0
35
6.5
3.54.35.3Resistance Value ( )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN20 Wire:Black)
H/E Outlet Thermistor (CN20 Wire:Gray)
Room Temp. Thermistor (CN19 Wire:Black)
Cassette Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN9 Wire:Black)
H/E Outlet Thermistor (CN9 Wire:Gray)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
Wall mount Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN17 Wire:Black)
H/E Outlet Thermistor (CN17Wire:Gray)
DC
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
Room Temp. Thermistor
(CN10 Wire:Black)
Room Temp. Thermistor (CN8 Wire:Black)
If the voltage does not appear, replace Controller PCB and set up the original address.
Room Temp. Thermistor (CN16 Wire:Black)
04-14
Page 78
Trouble shooting 5 INDOOR UNIT Error Method:
Heat Exchanger Inlet Sensor Error
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash. Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB Circuit Heat Exchanger Inlet Thermistor
Forecast of Cause :
1. Connector defective connection 2. Thermistor defective 3. Controller PCB defective
Detective details:
When open or shorted Heat Exchanger Inlet Thermistor is detected at Power ON.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
Resistance Value ( )
2520151050
49.862.579.1100.9129.8168.6
30
40.0
35
32.4
Temperature (°C)
Resistance Value ( )
If Thermistor is either open or shorted, replace it and reset the power.
504540
17.821.226.3
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN20 Wire:Black)
H/E Outlet Thermistor (CN20 Wire:Gray)
Room Temp. Thermistor (CN19 Wire:Black)
Cassette Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN9 Wire:Black)
H/E Outlet Thermistor (CN9 Wire:Gray)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
Wall mount Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN17 Wire:Black)
H/E Outlet Thermistor (CN17 Wire:Gray)
DC
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
Room Temp. Thermistor
(CN10 Wire:Black)
Room Temp. Thermistor (CN8 Wire:Black)
If the voltage does not appear, replace Controller PCB and set up the original address.
Room Temp. Thermistor (CN16 Wire:Black)
04-15
Page 79
Trouble shooting 6 INDOOR UNIT Error Method:
Heat Exchanger Outlet Sensor Error
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash. Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB Circuit Heat Exchanger Outlet Thermistor
Forecast of Cause : 1. Connector defective connection 2.Thermistor defective 3.Controller PCB defective
Detective details:
When open or shorted Heat Exchanger outlet Thermistor is detected at Power ON.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
Resistance Value ( )
Temperature (°C)
2520151050
49.862.579.1100.9129.8168.6
30
40.0
504540
35
32.4
Resistance Value ( )
If Thermistor is either open or shorted, replace it and reset the power.
17.821.226.3
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN20 Wire:Black)
H/E Outlet Thermistor (CN20 Wire:Gray)
Room Temp. Thermistor (CN19 Wire:Black)
Cassette Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN9 Wire:Black)
H/E Outlet Thermistor (CN9 Wire:Gray)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
Wall mount Schematic Diagram (Connector connection)
H/E Inlet Thermistor (CN17 Wire:Black)
H/E Outlet Thermistor (CN17 Wire:Gray)
DC
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
Room Temp. Thermistor
(CN10 Wire:Black)
Room Temp. Thermistor (CN8 Wire:Black)
If the voltage does not appear, replace Controller PCB and set up the original address
Room Temp. Thermistor (CN16 Wire:Black)
04-16
Page 80
Trouble shooting 7 INDOOR UNIT Error Method:
Water Drain Abnormal
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 5 times Flash, Timer LED 3 Times Flash, Filter LED Continuous Flash.
Error Code : 5 3
Detective Actuators:
Indoor Unit Controller PCB Circuit Float Switch
Forecast of Cause : 1. Float switch defective 2. Shorted connector/wire 3. Controller PCB defective 4. Drain pump defective
Detective details:
When Float switch is ON for more than 3 minutes.
Check Point 1 : Check Float Switch
Check operation of float switch. (any blocking by dust, etc.) Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is defective, replace it.
ON OFF
OK
Check Point 2 : Check Connector (CN 1) / Wire
Check loose contact of CN1 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
OK
Check Point 3 : Check Controller PCB
If Check Point 1 & 2 do not improve the symptom, change
Controller PCB and set up the original address.
Attention!!
Small size wall mount type does not have a float switch. In this case, replace Controller PCB and set up the original address. Please refer to.
04-17
Page 81
Trouble shooting 8 INDOOR UNIT Error Method:
Indoor Unit Fan Motor Error
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 5 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash. Error Code : 5 1
Detective details:
Detective Actuators:
Indoor Unit Controller PCB Circuit Indoor Fan Motor
Forecast of Cause : 1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temp. increase
4. Capacitor failure 5. Control PCB failure
When Indoor fan control is either phase control or DC control and rotation feed back control is ON, the feed back rotation value becomes 0 and lasts for more than 1 minute at motor operation condition. Or, the feed back rotation value continues at 1/3 of target value for more than 1 minute.
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check Motor winding
Check Indoor Fan motor
>>If Fan motor is abnormal, replace it.
OK
Check Point 3 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation..
OK
Check Point 4 : Check Motor Capacitor
Check continuity of motor capacitor
>>If it is shorted, replace the capacitor.
OK
Check Point 5 : Replace Controller PCB
Change Controller PCB and set up the original address.
Attention!!
In case of Duct type, replace Controller PCB and set up the original address, since it is a tapping control.
04-18
Page 82
Trouble shooting 9 INDOOR UNIT Error Method:
Wired Remote Controller Communication Error
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash. Error Code : 1 2
Detective Actuators:
Indoor unit controller PCB circuit Wired Remote Control
Forecast of Cause : 1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor unit, but the same signal has not been received more than 1 minute.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of controller PCB Connector. (Power supply for Remote)
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote If DC0V, Controller PCB failure (Remote is OK) >>> Replace Controller PCB
wiring, turn on the power again.
-In case of re-installation is done due to removed connector or incorrect
DC
Trouble shooting 9 INDOOR UNIT Error Method:
Wired Remote Controller Token Error
Detective Actuators:
Indoor unit Controller PCB circuit Wired Remote Control
Forecast of Cause : 1. Terminal connection abnormal 2. Mis-setting 3. Wired Remote Control failure 4. Controller PCB failure
Indicate or Display: Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash. Outdoor Unit : E.5 U.1, Error LED Continuous Flash. Remote Controller : 1 2
Detective details:
More than 1 time of Token (Communication between wired remote controllers) is received, but it was not received more than 1 minute.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of Controller PCB Connector. (Power supply for Remote)
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote lIf DC0V, Controller PCB failure (Remote is OK) >>> Replace Conroller PCB
In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
DC
04-19
Page 83
Trouble shooting 10 INDOOR UNIT Error Method:
Indoor Unit Parallel Communication Error
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 1 times Flash, Timer LED 6 Times Flash, Filter LED Continuous Flash. Error Code : 1 6
Detective Actuators:
Indoor unit Controller PCB circuit Indoor unit Communication PCB
Forecast of Cause : 1. Connection failure 2. Outside cause 3. Communication PCB failure 4. Controller PCB failure
Check Point 1-1 : Reset the power
Does LED error indication reappear?
Detective details:
When Parallel communication error (Communication reset occurs continuously more than specified times) is detected.
NO
YES
Check Point 2 : Check Connection
Check if Indoor Communication PCB is removed.
OK
Check Point 1-2 : Check outside cause such as noise
Check the complete insulation of the grounding. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 3 : Replace Communication PCB
Replace Communication PCB (If the symptom does not change, replace Controller PCB and set up the original address.
04-20
Page 84
Trouble shooting 11 INDOOR UNIT Error Method:
Network Communication Error
Indicate or Display: Outdoor Unit : E.5 U.1 Indoor Unit : Operation LED 1 times Flash, Timer LED 4 Times Flash, Filter LED Continuous Flash. Error Code : 1 4
Detective Actuators:
Indoor unit Controller PCB circuit Indoor unit Communication PCB
Detective details:
When the cut-off of network communication is detected (more than 90 seconds passed since the last receipt of Outdoor unit signal).
Forecast of Cause : 1. Connection failure 2. Outside cause 3. Communication PCB failure 4. Controller PCB failure
Check Point 1 : Check the connection
After turning off the power, check and correct followings.
Is Indoor Communication PCB loose? Check loose or removed connection of communication line between Indoor
and Outdoor unit.
When the signal amplifier is connected , is it failure of signal amplifier? (Refer to "TROUBLE SHOOTING FOR OPTIONAL PARTS")
OK
Check Point 2 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit. Momentary power failure ----- Check contact failure or leak current in power supply circuit
>>Check Outdoor Unit as well.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which
causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
OK
Check Point 3 : Check Communication PCB and Controller PCB
If some of Indoor units have errors, replace Communication PCB of the Indoor units that have the error.
>>If the symptom does not change, replace Indoor unit Controller PCB.
If all the Indoor units have error, check if the Outdoor Unit Communication PCB has a loose connection.
>>If the symptom does not change, replace Outdoor unit Communication PCB (Replace Controller PCB if it does not change).
04-21
Page 85
4-3-2 Trouble Shooring With Error Code (OUTDOOR UNIT)
3. Main PCB defective
Trouble shooting 12 OUTDOOR UNIT Error Method:
Initial Setting Error
Detective Actuators:
Outdoor unit main PCB
Forecast of Cause :
1. Wrong DIP SW setting
2. Power supply defective
Indicate or Display: Outdoor Unit : - - - - ( Flashing 0.5 sec. ON and OFF ) Indoor Unit : No Display Error Code : No Display
Detective details:
When the DIP SW setting was wrong, after turned on the power supply
Check Point 1 : Check the power supply
Main power ON/OFF state check Power cable connection, open check
OK
Check Point 2 : Check the outdoor unit address/number of connected slave units setting
Setting check of outdoor unit address of each outdoor unit
Outdoor unit address
SET 3-1 SET 3-2
Master
OFF OFF
OK
Check Point 3 : Replace Main PCB
Change Main PCB and set up the original address.
04-22
Page 86
Trouble shooting 13
OUTDOOR UNIT Error Method:
Outdoor Unit Network Communication 1 Error
Indicate or Display:
Outdoor Unit : E. 14. 1 Indoor Unit : No display
Error Code : 14
Detective Actuators:
Outdoor unit Main PCB Outdoor unit communication PCB
1. Noise, momentary open, voltage drop 2. Indoor unit power off
Forecast of Cause :
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Main PCB defective
Detective details:
No communication for 180 seconds or more from an indoor unit which received communication once and no outdoor network communication error 2.
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
OK
Check Point 4 : Check the Terminal resistor setting
erminal resistor setting check
T
OK
Check Point 5 : Check the communication PCB (outdoor unit/indoor unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit / indoor unit)
Change Main PCB and set up the original address.
04-23
Page 87
Change Main PCB and set up the original address.
Trouble shooting 14 OUTDOOR UNIT Error Method ::
Outdoor Unit Network Communication 2 Error
Indicate or Display:
Outdoor Unit : E. 14. 2 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 14
Detective Actuators:
Outdoor unit Main PCB Outdoor unit communication PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop 2. Indoor unit power off
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Main PCB defective
Detective details:
No communication for 180 seconds or more from all indoor units that once received communication
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
OK
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
OK
Check Point 5 : Check the communication PCB (outdoor unit/indoor unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit / in door unit)
04-24
Page 88
Trouble shooting 15
OUTDOOR UNIT Error Method:
Outdoor Unit EEPROM Access Error
Indicate or Display:
Outdoor Unit : E. 62. 3 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 62
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
Check Point 1-1 : Turn the power
1. Noise, momentary open, voltage drop 2. Main PCB defective
on agaun.
NO
Error displayed again?
YES
Check Point 2 : Replace Main PCB
Change Main PCB and set up the original address.
Detective details:
Access to EEPROM failed due to some cause after outdoor unit started.
Check Point 1-2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the
power line.
04-25
Page 89
Trouble shooting 16 OUTDOOR UNIT Error Method:
Inverter Communication Error
Indicate or Display:
Outdoor Unit : E. 62. 6 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash. Error Code : 62
Detective Actuators:
Outdoor unit Main PCB Outdoor unit Inverter PCB
Forecast of Cause :
1. Noise 2. Main to Inverter PCBs wiring connection defective
3. Main PCB defective 4. Inverter PCB defective
Check Point 1-1 : Turn the power
Detective details:
on again.
NO
Error displayed again?
YES
Check Point 2 : Check the main to Inverter PCB wiring
Connector connection state check
Cable open check
Communication not received from Inverter PCB for 10 seconds or more
Check Point 1-2 : Noise
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 3 : Check Main PCB
Chack Main PCB. (Refer to "Sarvise Parts Information )
OK
Check Point 4 : Replace Inverter PCB
Replace Inverter PCB.
04-26
Page 90
Trouble shooting 17
OUTDOOR UNIT Error Method:
EEPROM Data corrupted Error
Indicate or Display:
Outdoor Unit : E. 62. 8 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 62
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop 2. Main PCB defective
Detective details:
Set contents sum value memorized in EEPROM and sum value calculated based on the set contents read from EEPROM do not match Regarding the sum value, only the contents set in the push button SW
*
setting mode (F2) shall be the objective.
Check Point 1-1 : Turn the power on again.
Error generated again after Field setting all clear (push button SW F3 (function mode) -35 execution) and the power was turned back on?
YES NO
Check Point 1-2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Replace Main PCB
Change Main PCB and set up the original address.
Reset the setting of F2 (setting mode) by push button SW. * To clear the setting of F2 by Field setting all clear.
04-27
Page 91
Trouble shooting 18
OUTDOOR UNIT Error Method:
Inverter Error
Indicate or Display:
Outdoor Unit : E. 63. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 63
Detective Actuators:
Inverter PCB Filter PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop. 2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open 3. Filter PCB ( INV) defective 4. Inverter PCB defective
Check Point 1-1 : Turn the power on again.
Error displayed again?
NO
Detective details:
Error information received from Inverter PCB
Check Point 1-2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the
power line.
YES
Check Point 2 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
Connector and wiring connection state check Cable open check
OK
Check Point 3 : Check Filter PCB (INV) and Inverter PCB
Check Filter PCB (INV) and Inverter PCB.
04-28
Page 92
Trouble shooting 19 OUTDOOR UNIT Error Method:
Inverter PCB short interruption detection
Indicate or Display:
Outdoor Unit : E. 67. 2 Indoor Unit : No Display
Error Code : 67
Detective Actuators:
Inverter PCB
Forecast of Cause :
1. Noise, momentary power failure, voltage drop
2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
3. Main PCB defective 4. Inverter PCB defective
Detective details:
''Momentary power failure" received from Inverter PCB
Check Point 1 : Noise, momentary power failure, voltage drop
Check if temporary voltage drop was not generated. Check if momentary power failure was not generated. Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
Connector and wiring connection state check Cable open check
OK
Check Point 3 : Check Main PCB
Check Main PCB Power supply
OK
Check Point 4 : Replace Inverter PCB
Replace Inverter PCB.
04-29
Page 93
Trouble shooting 20
OUTDOOR UNIT Error Method: Outdoor Unit transmission PCB
Parallel Communication Error
Indicate or Display:
Outdoor Unit : E. 69. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 69
Detective Actuators:
Outdoor unit Main PCB Communication PCB
Forecast of Cause :
1. Noise 2. Communication PCB connection defective
3. Communication PCB defective 4. Main PCB defective
Detective details:
Parallel communication (communication between main CPU and communication PCB ) failed 5 times.
Check Point 1-1 : Turn the power on again.
Check Point 1-2 : Noise
NO
Error displayed again?
Check if ground is connection correctly or there are no related cables near the power line.
YES
Check Point 2 : Check the communication PCB connection
Communication PCB connection check
OK
Check Point 3 : Check the communication PCB
Communication PCB check
OK
Check Point 4 : Replace Main PCB
Change Main PCB and set up the original address.
04-30
Page 94
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Trouble shooting 21 OUTDOOR UNIT Error Method:
Discharge Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 71. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 71
Detective Actuators:
Detective details:
Discharge temperature thermistor 1 short detected
Discharge temperature thermistor 1
Discharge thermistor 1 open detected after compressor 1 operated continuously for 5 minutes or more
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN141:1-2) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(DIS.TEMP )
< TH1 >
K
K
C
C
BLACK
BLA
BLA 1 2 3 4 5 6
1 2 3 4 5 6
THERMISTOR
(COMP SHELL )
< TH10 >
BLACK
CN141
Discharge temperature sensor 1 (CN141:1-2)
If the voltage does not appear, replace Main PCB and set up orignal address.
DC
04-31
Page 95
Check Point 3 : Check voltage of Main PCB (DC5.0V)
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 22
OUTDOOR UNIT Error Method:
Compressor Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 72. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 72
Detective Actuators:
Compressor temperature thermistor 1
Detective details:
Compressor temperature thermistor 1 short detected Compressor thermistor 1 open detected after compressor 1 operated continuously for 5 minutes or more
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN141:5-6) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(COMP SHELL1)
THERMISTOR
(DIS.TEMP.1)
<TH1>
K C
BLA
BLACK
BLACK 1 2 3 4 5 6
1 2 3 4 5 6
<TH10>
K C
BLA
CN141
Compressor temperature sensor 1 (CN141:5-6)
DC
04-32
Page 96
Check Point 3 : Check voltage of Main PCB (DC5.0V)
If the voltage does not appear, replace Main PCB and set up orignal address.
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 23 OUTDOOR UNIT Error Method:
Outdoor Unit Heat Ex. Liquid Temp. Sensor Error
Indicate or Display:
Outdoor Unit : E. 73. 3 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 73
Detective Actuators:
Heat exchanger liquid temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Detective details:
Heat exchanger liquid temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN143:3-4) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
(SUC. TEMP.)
< TH4 >
(HEX. EXIT.)
THERMISTOR
BLACK
BLACK 1 2 3 4
1 2 3 4
< TH5 >
THERMISTOR
K C
BLACK
BLA
CN143
Heat exchanger liquid temperature sensor (CN143:3-4)
DC
04-33
Page 97
Check Point 3 : Check voltage of Main PCB (DC5.0V)
If the voltage does not appear, replace Main PCB and set up orignal address.
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 24 OUTDOOR UNIT Error Method:
Outdoor Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 74. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 74
Detective Actuators:
Outdoor temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Detective details:
Outdoor temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check Cable open check
OK
Check Point 2: Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information ".
OK
Main PCB (CN144:1-3) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
(OUT TEMP.)
< TH3 >
THERMISTOR
K
CK
C
LA B
BLA
1 2 3 1 2 3
CN144
Outdoor temperature sensor (CN144:1-3)
DC
04-34
Page 98
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 25
OUTDOOR UNIT Error Method:
Suction Gas Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 75. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 75
Detective Actuators:
Suction gas temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
Detective details:
Suction gas temperature thermistor short or open detected
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN143:1-2) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(SUC. TEMP)
< TH4 >
THERMISTOR
(HEX. EXT)
< TH5 >
K C
BLACK
BLACK
BLA
BLACK
1 2 3 4 1 2 3 4
CN143
Suction gas temperature sensor (CN143:1-2)
DC
04-35
Page 99
Trouble shooting 26 OUTDOOR UNIT Error Method:
Heat Sink Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 77. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 77
Detective Actuators:
Inverter PCB
Forecast of Cause :
Detective details:
Heat sink temperature thermistor ( Inside IPM ) open/short circuit detected
1. Inverter PCB failure
If this error is displayed, replace Inverter PCB
04-36
Page 100
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Trouble shooting 27
OUTDOOR UNIT Error Method: Sub-cool Heat EX. Gas Inlet
Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 82. 1 Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Error Code : 82
Detective Actuators:
Sub-cooling heat exchanger gas inlet temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
Detective details:
Sub-cooling heat exchanger gas inlet temperature thermistor short or open detected
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN142:5-6) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
THERMISTOR
(SC.EXT.LIQ)
K
K
CK
C
C
A
A
L
L
BLACKBLA
B
B
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
THERMISTOR
(SC.INT.GAS)
< TH 8 >
(SC.EXT.GAS)
K
K
C
C
A
A
L
L
B
B
CN142
Sub-cooling heat exchanger gas inlet temperature sensor (CN142:5-6)
DC
04-37
Loading...