5-3-3 Saturation temperature and saturation pressure tables (R410A)........................
5-3-4 Temperature and pressure of refrigerant (Graph)...............................................
6. DISASSEMBLY PROCESS
05-02
05-02
05-18
05-19
05-19
05-20
05-21
05-22
Page 6
Page 7
1. TEST RUN
Page 8
Page 9
1. TEST RUN
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
Before execution
Location decision
Confirmation of Refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparation before execution
Execution 1/2
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Outdoor unit foundation work
Execution procedure and precautionsReason
Do not install the units in the place not recommended in the installation
manual.
Check the characteristics of the refrigerant used and grasp the
special features of the refrigerant. If refrigerant must be charged,
always charge the refrigerant specified for the product.
*Confirm the product design pressure. < R410A 4.20MPa >
Prepare the design for the system
Use new refrigerant piping of the thickness specified by the
1
D&T manual.
2
Since R410A dedicated tools are necessary, prepare them in
advance.
3
Absolutely avoid use of existing piping. If use of existing
piping is unavoidable, the piping must be cleaned.
Always use a level and keep the indoor unit level.
If the equipment is tilted toward the drain port, install it so that the tilt
is within 10mm. Excessive tilt will cause water leakage.
When performing piping work, observe the following items so that the
inside of the piping is clean and air tight.
1
Use pipe that is not dirty inside.
Confirm the design for the piping ( Diameter, Thickness )
2
3
When the pipe is left standing, protect it.
Confirm the angle of separation tube and header correctry.
4
Finish flaring exactly.
5
Confirm the width across flats dimension and shape of flare nuts.
6
Always blow nitrogen while brazing.
7
Perform flushing before connecting the equipment.
8
Always make the downward slope of the drain pipe 1/100 or
1
greater and make the horizontal length within 20m.
Use hard polyvinylchloride pipe as the drain pipe.
2
Support the drain pipe between 1.5 to 2.0m.
3
Use pipe of 1 rank up (VP30 or greater) as central piping.
4
Select the size of the heat insulating material according to the ambient
temperature and relative humidity of the refrigerant.
Use a heat insulating material having a heat conductivity of 0.043W/
(m.k) or less.
The performance may drop significantly
due to the protection controlling
Use of a refrigerant other than the
specified refrigerant will invite
equipment trouble
Secure the necessary pressure
resistance.
Prevention of water leakage
Foreign matter, water, etc. in the
piping will cause faulty cooling and
compressor trouble.
Incorrect pipe diameter will cause
faulty cooling
Incorrect angle of separation tube or
header will be cause poor cooling or
refrigerant noise problem
Refrigerant leakage will cause low
performance and abnormal stopping
Prevention of water leakage
Prevention of water leakage
Outdoor unit installation
Refrigerant piping connection work
Air tightness test
Vacuum drying
When making flare connections always use a torque wrench and
tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure
and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a
1
reverse flow check adaptor to a conventional vacuum pump and
use.
Pump down sufficiently.
2
Approximately 1 hour or longer after -0.10MPa reached.
Allow to stand for approximately 1 hour after stopping the vacuum
pump and confirm that the needle does not return.
Air purging using refrigerant is strictly prohibited.
3
Vaccuming mode
*
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vaccuming mode, the refrigerant address setting has to be finished.
Refrigerant leakage will cause low
performance and abnormal stopping.
Refrigerant leakage will cause low
performance and abnormal stopping.
Mixing in of vacuum pump oil by
reverse flow will cause equipment
trouble.
recommend the vacuuming mode
When the [vacuuming mode] is set, <Push switch setting, F3:21>
EEV of connected all indoor units opens.
So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units and
the outdoor unit, [vacuuming mode] is released.
01-01
Page 10
Execution 2/2
Execution procedure and precautionsReason
Addition refrigerant charging
Gas leak test
Initial setting
Confirm the additional refrigerant amount with the installation
1
manual, etc.
Always take the R410A refrigerant from the cylinder liquid phase
2
and charge it using the gas phase.
(Do not lay a cylinder with siphon pipe on its side.)
3
Use an R410A dedicated gauge manifold and charging hose.
Charge refrigerant using the liquid pipe.
4
When the defined amount of refrigerant cannot charge using the
5
liquid pipe, charge refrigerant using the gas pipe while opearing
the cooling test run.
Charge refrigerant bit by bit with cautious operation of valve
for the liquid refrigerant back prevention.
Use an R410A dedicated leak tester to check for gas leaks.
1
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
2
Confirm the DIP SW setting
SET 1: Factory setting, SET 2 : All OFF, SET 3 : All OFF,
SET 4: Factory setting
Confirm the Terminal resister setting
3
SET 5-4 OFF: Disable, ON: Enable
[Note] Perform in the power OFF state.
If taken from the air phase, since the
composition of the refrigerant which is
charged will change, low performance
and abnormal stop will occur easily.
Prevent erroneous sealing in of
refrigerant.
A leak tester for other than R410A
cannot detect leaks.
Dual address setting No. is not
allowed in one network.
If the DIP SW setting is wrong, the sys tem may not work correctly
If the Terminal resister setting is wrong,
the system may detect transmission
error
Piping length setting
Address setting for Signal Amp
- When using signal Amps -
Address setting for Indoor unit
Set according to the length of the connection piping.
Set to "Standard (40 to 65m)" at the factory.
Set using the push button SW on the outdoor unit main PCB.
< Refer to the Page 01-16 Setting mode F2-00 >
Set the pipe length to be the nearest indoor unit from the outdoor unit
When the setting is not same as the
real piping length, the system may
not work correctly.
If the pipe length is set as the farthest
indoor unit, the nearest operating
indoor unit may be stopped the
operation by the icing up protection
as by over cooling.
[Note] Perform in the power ON state after all indoor units have stopped operation
When setting the address of Signal amplifier, please refer to the
installation manual of the signal amplifier.
The address setting can be set by automatically from 1 outdoor unit
on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Dual address setting No. is not
allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Set the refrigerant circuit address and indoor unit address.
Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch
PCB) or from a remote controller or from a push button SW on the
outdoor unit Main PCB < Automatic address setting,
Refer to the Page 01-07 Setting mode F3-11>
Dual address setting No. is not
allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Indoor unit connection check
Test run & adjustment
Turnover & explanation of operation
Before starting the system, check on the number of indoor units and
the total capacity.
< Refer to the Page 01-08 Setting mode F3-12 >
Normal operation will not be possible
without performing the indoor unit
connection check.
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state
after all indoor units have stopped operation.
01-02
Page 11
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
Power
source
Outdoor
unit
Check contentsProcedure
Circuit breaker capacity
Type of power source
wiring
Supply power source
Wiring on terminal blocks
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Judgement standard
Outdoor unit: 32A ( AJ*A36,45,54LALH )
Indoor unit: 20A
Leakage current: 30mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit: 6mm
Indoor unit: 2.5mm2 2 wires + Ground
Outdoor unit side: AC 230V (220-240V)
Indoor unit side: AC 230V (220-240V)
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Check whether or not the heat insulation material is installed without a gap.
DIP SW SET1, SET4 : Factory setting, SET2,SET3, SET5-1,2,3: ALL OFF
Terminal resistor setting SET5 - 4 OFF: Disable, ON: Enable
Check the resistance value for each network segment
Refer to the installation manual 7.7
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
2
2 wires + Ground 4mm
2
Check
Indoor
unit
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned
and will lead to trouble.
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote controller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
There shall be no scratches, deformation, tilting, etc.
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit address (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
2
01-03
Page 12
1-2-2 Check Items After Power ON
[Note]
Cooling test run for each refrigerant circuit.
If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot
be detected.
Power ON
Outdoor unit Main
PCB push button
SW setting/check
Address
setting/
check
Indoor unit
connection check
Cooling
test run
Check contentsProcedure
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Judgement standard
Check
[Note] Turn on all indoor units power in the same refrigerant circuit address.
When the system operates with the indoor units remaining no power, it is cause of malfunction.
Function setting
Automatic address setting
Address read
Address record
Address hold check
Indoor unit connection check
Are the necessary functions set ?
< For the setting, Refer to the page 01-15 18 >
Addresses shall be assigned to all indoor units / Signal amps.
Check for unset or duplicated addresses.
< For the setting, Refer to the page 01-06, 07 >
All the indoor units and outdoor units of the same refrigerant circuit can be
checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool
after indoor/outdoor circuit breakers were turned OFF to ON.
Are the number of connecting indoor units correct ?
Is the total capacity of indoor units correct ?
< For the checking, Refer to the page 01-08 >
〜
[Note] Before connecting service tool, the address setting has to be completed.
Outdoor unit push button
SW operation
All the indoor units in the same refrigerant
state.
The outdoor units corresponding to the operation capacity of the indoor
units shall operate. < Test operation procedure, Refer to the page 01-09,10 >
circuit
shall enter the coolingtest run
All of the
indoor units
operation
(after 30 mins)
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
HPS: 2.7 MPa
LPS: 0.9 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/
abnormal vibration
There shall be no Error information on the 7-segment display on the Main PCB.
Between L - N AC230V (220-240V)
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound.
There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
01-04
Page 13
Indoor unit
individual
operation
Check contentsProcedure
Judgement standard
<Indoor unit service tool + actual measurement>
Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
Check
These are representative figures of AJYA54LALH at the standard condition. ( Indoor : 27
°C, Outdoor : 35°C )
If conditions are different from those above mentioned, the figures will be changed slightly.
It depends on following conditions.
Outdoor unit capacity
Indoor and outdoor temperature
Indoor unit capacity
Pipe length
etc
Trouble shooting on Test run operation
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and
check the description of the Error code.
< Refer to the Trouble shooting in the Service manual.>
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not
Evaporator Icing up protection, High discharge temperature protection,etc.
< Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit
Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc.
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
< Refer to the regulation of installation in the Installation manual>
01-05
Page 14
1-2-3 Automatic address setting for signal amplifiers When using signal amplifiers
SWITCH POSITION
Outdoor unit printed circuit board
When setting the address of the signal amplifier, please use the factory setting. (See the
installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB
to conÞ gure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment
LED Lamp
Push button switch
SELECT
SELECT
(When [F4] to [F9] are displayed, continue to press the "SELECT" button
until [ F3 ] is displayed)
ENTER
Automatic address setting for
signal ampliÞ ers
SELECT
ENTER
Press the “SELECT” button until "10" is displayed
Press the “ENTER” button for more than 3 seconds
End
*
ENTER
MODE/EXIT
* Setting is complete when the number of unit is displayed
01-06
Page 15
1-2-4 Automatic address setting for Indoor units
SWITCH POSITION
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit Main PCB is set to “00”.If it is not
set to “00”, it means the address of that device is not set. (Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the
main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment
LED Lamp
Push button switch
to configure settings according to the procedures below .
First 2 digits
SELECT
SELECT
ENTER
Last 2 digits
SELECT
ENTER
(When [F4] to [F9] are displayed,
continue to press the “SELECT”
button until [F3] is displayed.)
Automatic address setting
for indoor units
Press the “SELECT” button until
“11” is displayed.
Press the “ENTER” button for more
than 3 seconds.
It may take about 10 minutes for completing
the processing.
Found
End
Error
ENTER
The number of indoor units with normal settings will be displayed at the first 2 digits of
the 7 segment display. The number of indoor
units with error will be displayed at the last 2
digits.
NOTE) After the “ENTER” button is pressed, the
end processing will occur for about 30 seconds.
During this period, the 7 segment will blink.
01-07
Page 16
1-2-5 Indoor unit connection check
SWITCH POSITION
Outdoor unit printed circuit board
Please perform the indoor unit connection check according to following procedures.
Turn on the power •
of indoor unit and
outdoor unit.
LED105
LED104
MODE/EXIT
Set to Function mode [F3].
SELECT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment
LED Lamp
Push button switch
SELECT
continue to press the “SELECT”
button until [F3] is displayed.)
ENTER
(When [F4] to [F9] are displayed,
SELECT
Press the “SELECT” button until
“12” is displayed.
ENTER
Press the •
“ENTER”
button for
more than 3 seconds.
When indoor unit connection check
can not be performed
This will be displayed when the •
Indoor unit connection check
starts.
ENTER
(*1)
Confirm the number of connected indoor •
units and the volume ratio of the indoor
units connection.
SELECT
ENTER
When error occurs
(*1) The number of connected
indoor units
Ex.) When 8 units are connected
(*2)
(*2) Volume ratio of the indoor
units connection
Ex.) When the ratio is 120%
Exit indoor unit connection check •
mode.
01-08
Please refer to the following “Error code”
for details
ENTER
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
MODE/EXIT
When it finishes normally, nothing will be displayed on
7 segment display.
Page 17
1-2-6 Test Run From Outdoor Main PCB
All the indoor units connected to the outdoor unit can be test-operated by push button setting.
SWITCH POSITION
POWER
MODE
ERROR
LED101
(GREEN)
LED102
(RED)
7 Segment
LED Lamp
LED105LED104
Outdoor unit printed circuit board
MODE
/EXIT
SW107SW108SW109
SELECT ENTER
Push button switch
TEST RUN SETTING
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
< Monitoring condition >
LED105LED104
MODE / EXIT
Note
There are the following 2 methods of resetting test operation.
Automatic reset when 60 minutes has elapsed.(1)
Reset when operation stop was performed.(2)
< Mode select condition >
[ Monitoring mode ][ Setting mode ]
SELECT
ENTER
LED105LED104LED105LED104LED105LED104LED105LED104
< Fuction select condition >
[ Cooling test run ]
LED105LED104
ENTER
SELECT
Press the ENTER button for at least 3 seconds.
[ Heating test run ]
L
ED
< Pursuance completion >
LED105LED104
SELECT
[ Function mode ]
SELECT
[ Error history mode ]
[ Central control setting
[ Test run stop ]
1
0
5
L
ED
1
0
4
SELECT
LED105LED104
SELECT
Forced reset ]
LED105LED104
ENTER
Press the "ENTER" button or Time out ( 5 seconds)
< Return to mode select condition >
LED105LED104
MODE / EXIT
< Return to monitoring condition >
LED105LED104
01-09
example, Normal indicate : [ Cooling mode ]
Page 18
1-2-7 Test Run From Remote Controller
1. Standard wired remote controller
Stop the indoor unit. Push the button and
button simultaneously for more than two seconds.
The air conditioner will start to conduct a test run and " " will display on
the remote controller display.
However, the , setting button does not have function,
but all other buttons, displays, and protection functions will operate.
Perform the test operation for 60 minutes.
To stop test run, push the START / STOP button of the standard wired remote
controller.
For the operation method, refer to the operating manual and perform operation
check.
Check that there are no abnormal sounds or vibration sounds during test run
operation.
UTY - RNK
SET TEMP.
TIMER MODE
CLOCK ADJUST
SET BACK
TIMER DELETE TIMER SET
DAY
DAY OFF
START / STOP
FANMODE
2. Standard wireless remote controller
Press the TEST RUN button on the remote controller, while the air conditioner is running.
To end test run operation, press the remote controller START / STOP button.
When the air conditioner is being test run, the OPERATION
and TIMER lamps of indoor unit flash slowly at the same time.
3. Simple remote controller
Stop the indoor and outdoor units. Push the remote controller
simultaneously for more than three seconds. The air conditioner will start to conduct a test
run and " " will display on the temperature display.
However the setting button does not have function but all other buttons,
displays and protection functions will operate.
button and
button
START / STOP button
TEST RUN button
UTY - LNH
START
STOP
ECONOMY
FILTER RESET
SET
TEMP.
SLEEP
TIMER
TIMER MODE
CLOCK
TEST
ADJUST
RUN
UTY - RSK
FANMODE
SET
SET
SWING
RESET
To stop test running press the button of the simple remote controller.
For the operation method refer to the operating manual and perform operation check.
Check that there are no abnormal sounds or vibration sounds during test run operation.
01-10
SET
Page 19
UTY-DCG
Monitor - All
On
Coll
℃
25.0
Setup Menu
Central Controller
Setting
05/31 03:59
05/31 03:59
Indoor unit
Special setting
Select
All
On
Off
Operation
Details
1
Monitor
Group
Setup
Menu
Help
2
Indoor unit Special Setting
Test Operation
Indoor Unit
Set Temp. Range
Test Operation
RCG_05
6)
05/31 03:59
Filter Sign
R.C. Prohibition
05/31 03:59
or
Group
Select
All
Identify
Unit
Clear
Unit
[ Select All (F2) ]: All of R.C.Group (Indoor units)
[ Identify Unit (F3) ] : Specific R.C.Group (Indoor unit)
(1) Select the objective you want to test run.
Select the objective icon or list at the monitor screen. (Multiple selections is possible)
Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
01-12
(1)
(2)
( * )
Page 21
<Setting screen>
Operation Setting
Control Unit :
operation
On
On
Off
Off
Air Flow Direction
Economy
Anti Freeze
Filter Sign
Test Operation
Optional
Setting
Cancel
Cancel
Meeting Room
ModeSet Temp. Fan
Auto
24.0 C
Cool
Dry
Fan
Heat
Operation
Controlled
10/11.2008.Mar. 02:20 PM
R/C Prohibition
All
Auto
High
Med
Low
Quiet
On/Off
On
Mode
Temp.
Timer
Filter
Status: On
OK
OK
(3) Switch to the <Details setting screen> by pressing "Optional Setting" on the setting screen.
<Details setting screen>
( * )
(3)
Operation Setting
10/11.2008.Mar. 02:20 PM
Status: On
SettingOptional
Air Flow Direction
Up
1
2
3
1
Down
2
3
Swing
4
4
Swing
LeftRight
Cancel
Economy
On
Off
Test
5
Special State
Stand by (Defrost)
Stand by (Oil Recovery)
Test Operation
Anti Freeze
Operation
On
Off
Filter Sign
Reset
Start
OK
(4)
(5)
(4) Send (start) test run by pressing "Start" and then pressing "OK" on the details setting screen. Test run continues for 60 minutes.
During sending, the slave screen shown below is displayed. When sending is completed, the sending slave screen and details setting
screen are closed.
To interrupt test run, select the device being test run and execute an
operation stop command.
(*) At the monitor screen, test run is reset by stopping operation
Transferring data.Please wait.
of the objective devices by pressing "OFF".
(*) Or test operation is reset by stopping operation of the objective
devices by pressing "Off" of Operation and then pressing "OK"
on the setting screen.
01-13
Page 22
1-3 TEST RUN CONTROL
1. When the test run signal is transmitted from standard wired, wireless remote controller,
simple remote controller, transmitted network, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of
the temperature condition.
(2) Frost prevention operation has priority over item(1).
(3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a
test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ).
(4) After 60 minutes passes, the test run stops.
(5) Test running initialization is shown below.
Operating Mode
Fan speedHiHi
Room Temperature Indication1830
Vertical Air Direction Panel
Swing
*EXAMPLE
1
2
3
4
EXCEPT FOR THE DUCT MODELDUCT TYPE
CoolingHeatingCoolingHeating
HiHi
1830
Position
4
1
OFFOFF
2
3
1
Position
4
1
2
3
4
COMPACT CASSETTE TYPE
CEILING TYPE
1
2
3
4
COMPACT WALL MOUNTED TYPE
01-14
Page 23
1-4 Field Setting And Monitor Mode List for Outdoor unit
Push switch onoutdoor
unit PCB
Monitor mode
[ F1 ]
Classification
Device and
system
Operation of
each part
Time guard20Accumulated current timeAccumulated current time is displayed
Refrigerant
cycle data 1
Refrigerant
cycle data 2
ITEM
CODE No.
00Connected number of indoor unitThe number of the communicating unit is displayed
Software version of outdoor unit
01
02Software version of INV PCB
03Software version of communication PCB
10Rotational speed of outdoor unit fan motorThe rotational speed of the outdoor unit fan motor is displayed
11Rotational speed of INV compressorThe rotational speed of the compressor is displayed
12Current value of INV compressorCurrent value of INV compressor is displayed
14Pulse of EEV1Pulse of EEV1 is displayed
Pulse of EEV2Pulse of EEV2 is displayed
15
21INV compressor accumulated time
[ Cooling ]
22INV compressor accumulated time
[ Heating ]
30Information on Thermistor 1
( INV compressor discharge temperature )
32
Information on Thermistor 3
( Outdoor temperature )
33Information on Thermistor 4
( Suction temperature )
34
Information on Thermistor 5
( Heat-exchanger temperature )
36
Information on Thermistor 7
( Liquid temperature 2 )
37
Information on Thermistor 8
( Sub-cool heat-exchanger inlet temperature )
38Information on Thermistor 9
( Sub-cool heat-exchanger outlet temperature )
39Information on Thermistor 10
( INV compressor temperature )
50
Information on pressure sensor 1
( High pressure sensor )
51
Information on pressure sensor 2
( Low pressure sensor )
Setting Mode
Information contents
Software version :
[ ] [ ] [ ] [ ] [ ] displays by five items
It skips when there is no suffix
[ rpm ]
[ rps ]
[ A ]
[ pls ]
[ pls ]
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 10 hour ]
Accumulated time is displayed in the heating operation of the
INV compressor
[ 10 hour ]
The value of the Thermistor 1 is displayed
[°C ] or [°F ]
The value of the Thermistor 3 is displayed
[°C ] or [°F ]
The value of the Thermistor 4 is displayed
[°C ] or [°F ]
The value of the Thermistor 5 is displayed
[°C ] or [°F ]
The value of the Thermistor 7 is displayed
[°C ] or [°F ]
The value of the Thermistor 8 is displayed
[°C ] or [°F ]
The value of the Thermistor 9 is displayed
[°C ] or [°F ]
The value of the Thermistor 10 is displayed
[°C ] or [°F ]
The value of the pressure sensor 1 is displayed
[ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed
[ MPa ] or [ psi ]
01-15
Page 24
Push switch
on outdoor unit PCB
Setting mode
[ F2 ]
Classification
ITEM
CODE No.
Setting Mode
ITEM
CODE No.
Install00Pipe length setting0040-65m
010-40m
0265-90m
0390-120m
Correction 10
Sequential start shift
Setting is forbidden
04
00
01
02
Setting is forbidden
Standard
03
Cooling capacity shift00Normal mode
11
01Save energy mode 1 (+2°C)
02High power mode 1 (-2°C)
03High power mode 2 (-4°C)
04High power mode 3 (-5°C)
Heating capacity shift
12
00Normal mode
01Save energy mode (-2°C)
02High power mode 1 (+2°C)
03High power mode 2 (+4°C)
13Defrost setting shift00End temperature:Normal
01End temperature:Higher
Change of
function 1
14Pressure equalization time shift
before defrosting start
20Switching between forced stop or00Forced stop
emergency stop
00No time shift
01Shift 1 ( 30 sec.)
02Shift 2 ( 60 sec.)
03
Shift 3 ( 90 sec.)
04
Shift 3 ( 120 sec.)
01Emergency stop
21Operation mode selecting method00Priority given to the first command
01Priority given to the external input of outdoor unit
02Priority given to the master indoor unit
22
Snow falling protection fan mode
Setting is forbidden
23
Interval setting for snow falling
protection fan mode
(Set the ones digit and tens digit of the No of
the electricity meter connected to CN135.)
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the
electricity meter connected to CN135.)
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135.)
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit
of the electricity meter pulse setting connected
to CN135.)
*4
*4
*3 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*4 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
Setting is forbidden: Any of problems caused by changing these setting is not covered by the warranty.
Only for solution :
*3
Only when the refrigerant noise during Defrosting was pointed out. It is the case that the
00Standard (47dB)
01
00Standard
01
00~99Setting number x00~x99
*3
( Refer to Design & Technical Manual for details.)
00~02Setting number 0xx~2xx00
( Refer to Design & Technical Manual for details.)
00~99Setting number xx00~xx9900
( Refer to Design & Technical Manual for details.)
00~99Setting number 00xx~99xx00
( Refer to Design & Technical Manual for details.)
compressor operating time in heating will be shorter.
01-16
Setting Function
Only for solution
Default
00
Page 25
Push switch on
outdoor unit PCB
Function mode
[ F3 ]
ITEM
CODE No.
Forced operation00Cooling test run
01Heating test runForced thermostat-ON in Heating.
Install and
maintenance 1
02Test run stopTest run is stopped.
10Signal amplifier automatic addressAutomatic address setting operates for signal amplifier.
11Indoor unit automatic address
Setting Mode
Setting Function
Forced thermostat-ON in Cooling.
Automatic address setting operates for indoor unit of same
refrigerant circuit.
12
Indoor unit connection check
Install and
maintenance 2
Clear 30Error history clearAll the abnormal code histories are cleared.
Reset40Abnormal reset It was displayed when abnormality occurs, and abnormal
Specialtyfunction91Foreced Central control function release
21Vacuuming modeVacuuming mode operatesRefer to page 01-01 for the function.
32Current time clearAccumulated current time becomes [ 0 ]
33INV compressor accumulated time clearAccumulated time of the INV compressor becomes [ 0 ]
34Constant Speed compressor accumulated
time clear
35Field setting all clearReturn to default the all set items.
36
Clear memorized information of "F3 - 12 "
( Indoor unit connection check )
*
Maximum memorized indoor unit number reset
41
90
Foreced Normal operation releaseNormal operation foreced release
The number of indoor units and the total capacity of indoor units
of same refrigerant circuit.
Not in Use on J-Series
The information of the number of indoor units and the total
capacity of indoor units are cleared.
code is reset.
This is a function that uses to clear abnormal display after the
repair is completed.
Please operate the switch after power off or power on
the outdoor unit.
Maximum memorized indoor unit number is reset.
"E14.5:Indoor unit number shortage" error is cleared.
When the centralized control device failure, and the centralized
control setting cannot be released, this function is used.
All the limitations set with the centralized control device are
released.
Push switch on
outdoor unit PCB
Error History Mode
[ F9 ]
Error history
ITEM
CODE No.
00
01
02
03
04
05
06
07
08
09
Meaning of Error History Number
1 time ago (Newest)
2 times ago
3 times ago
4 times ago
5 times ago
6 times ago
7 times ago
8 times ago
9 times ago
10 times ago (Oldest)
Information contents
When the error occurred, the error code is memorized up to
10 on Main PCB.
If the memorized error code becomes over 10, the oldest one
will be erased.
Refer to Chapter 4.TROUBLE SHOOTING
4-2-3 Error Code List of Outdoor unit
< Reset Error Item List By Abnormal Reset Setting >
*
Compressor Motor Loss of Synchronization
Compressor 1 Temperature Abnormal
Inverter Compressor Start Up Error
Discharge Temperature 1 Abnormal
Low Pressure Abnormal
Current Sensor 1 Error
Trip Detection
Rush Current Limiting Resistor Temp Rise Protection
Outdoor Unit FAN motor 1 Lock Error
Outdoor Unit FAN motor 2 Lock Error
01-17
Page 26
1-5 Field Setting / Function Setting for Indoor unit
23Vertical airflow direction00Default
02Right half
Correction
30
Cool air temperature trigger
00Default (0°C)
Indoor unit field setting
setting by
remote controller
Classification
Address
Filter11Filter indicator Interval00Default
Airflow20Ceiling airflow00Default
ITEM
CODE No.
01Indoor unit address 00~6300~6300
02Refrigerant circuit address00~99 00~9900
13Filter sign display00Enable
(Cassette type only)01High ceiling
24Horizontal swing airflow direction00Default
26
Static Pressure setting
Setting Mode
- Slim Duct Only -
The Range of static pressure is
different from one model to other.
31Heat air temperature trigger00Default (0°C)
32
Temperature correction in Auto
Change of40Auto restart00Enable
Function 1
43Cool air prevention00Enable
46External control00Start / Stop
47Error report target00All
ITEM
CODE No.
Longer
01
02Shorter
01Disable
02Display only on central remote control
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130
Operation current sensor
Pressure switch
Rotary SW & DIP-SW & Push SW
Input / output or kind of detailControl range
Measure range 10 to 130
Measure range -25 to 58
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Current transformer
Pressure switch
Address and function setting
Open 4.2MPa Short 3.2MPa
O
U
T
P
U
T
Communication
Input / Output
External
Input / Output
LED display
Compressor
Electronic expansion valve 1 (Main)EEV coilOperating voltage DC12V
Electronic expansion valve 2 (SC-Hex)EEV coilOperating voltage DC12V
Fan motor 1 (Upper)DC Brushless motor
Fan motor 2 (Lower)DC Brushless motor
4-way valve 4-way valve coilAC220-240V, 50/60Hz 6/5 W
Solenoid valve Comp pressure equalizing valveAC220-240V, 50Hz, 6W
Crank case heater For Inverter CompressorAC240V, 25W
ON (Error) / OFF (Normal)
ON (Operation) / OFF (Stop)
Display the information on operation, error and setting with single LED and
7 segment LED.
Operation coil AC220-240V, 50Hz
Control output: DC 0/12-24V, Max.30mA
Control output: DC 0/12-24V, Max.30mA
02-01
Page 30
2-2 COMPRESSOR OPERATION
2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same
refrigerant circuit is input, the compressor operates.
When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity",
is stopped.
But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation
Icing protection
Failure (Refer to chapter 4, TROUBLE SHOOTING )
Oil recovery
Under expansion valve initialization
At protective operation
Emergency stop
Defrost operation
Peak cut stop operation
the compressor
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to
cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of
required refrigerant circulation in details.
Total capacity
Capacity of
compressor operation
Inverter Compressor
02-02
Cooling/Heating load
Page 31
(2) Target low-pressure and high-pressure control
<Cooling>
In order to make the evaporation pressure of the indoor unit at the proper pressure on a variety of operations,
capacity of the compressor will be controlled by low-pressure sensor of the outdoor unit.
<Heating>
In order to make the condensation pressure of the indoor unit at the proper pressure on a variety of operations,
capacity of the compressor will be controlled by high-pressure sensor of the outdoor unit.
Target low-pressure and high pressure temperature depends on system capacity, capacity of compressor operation,
pipe length, and capacity shift switch settings.
2-2-3 Speed Range of Start, Stop, And Operation
On stop mode : 0 rps
On operating mode : 20 - 100 rps
(1) Cooling starting process
For cooling operation only, the upper limit speed at starting is made 50rps and is raised in
+10rps increments every 60 seconds.
The compressor operates at the upper limit speed if the target speed is higher than the upper limit speed.
The compressor operates at the target speed if the target speed is lower than the upper limit speed.
Speed
90rps
Target speed
80rps
70rps
60rps
50rps
10rps
10rps
10rps
60sec
60sec
60sec
60sec
0
60sec
120sec 180sec 240sec
02-03
Time
Page 32
(2) Heating starting process
At the start of heating, the compressor is started by the following process. Compressor start-up
to change the 4 way valve. Capacity control returns to normal control after the end of the starting process.
(target high-pressure control)
< Starting process >
Compressor operation speed
Normal control
Starting process
Starting process
Starting processStarting process
4rps/Min
32rps fixed
Cancel conditions
3 minutes elapsed from start of process
or
High-pressure 2.63MPa
20 minutes elapsed from start of process
or
High-pressure 2.63MPa
or
Discharge SH 10 and Discharge temperature 10
*However, when the following condition (A) or (B) are satisfied, starting process is not performed.
< Conditions under which starting process is not performed >
(A) The compressor temperature 32 , when the room temperature reached to the setting temperature
( Thermostat - OFF controlling )
(B) The compressor temperature 32 , when the system keeps heating mode with stop condition
< Operation >
Compressor operates based on the required capacity at the start up, after that the target high-pressure
control begins.
(3) Limits the upper limit speed of the INV compressor according to the present high-pressure value.
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
Outside air temperature
sensor detected value
TAOUT 10°C
10°C TAOUT 15°C
15°C TAOUT 20°C
20°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
(Condition which lowers the fan speed)
High-pressure 3.30MPa and heat sink temperature 80°C
(Condition which raises the fan speed)
High-pressure saturation 3.20MPa or heat sink temperature 85°C
Fan step
11
8
5
5
02-06
Page 35
2-3-3
Low noise mode
When the low noise mode setting ON from PUSH SW or EXTERNAL INPUT, the outdoor unit operates in
the low noise mode as follows.
«
Settings and corresponding operations
Capacity priority setting
( PUSH SW )( PUSH SW )
Low noise level setting
»
Operation mode
OFF
ON
«
Low noise mode and operation contents
COOL
Low Noise Mode
HEAT
Max Compressor Speed
Max Compressor Speed
ON
ON
»
Max FAN Step
Upper FAN
Lower FAN
Max FAN Step
Upper FAN
Lower FAN
LOW NOISE MODE
* Automatic switching
4HP
AJ*A36LALH
AJ*A45LALH
7
450
410
40
7
450
410
60
5HP
AJ*A54LALH
7
450
410
45
7
450
410
60
6HP
7
450
410
52
7
450
410
60
The operating noise is reduced by limiting the rotational speed of the compressor and fan motor
LOW NOISE MODE
The operating sound lowers from about 3 to 5 dB more than the rated value
* Automatic switching
Operation in low noise mode
Low
capacity
Normal operation
Not switched for 30 minutes
after being once switched.
Capacity does not become low
even when switched to low noise
mode
* Low capacity
Compressor capacity is low
or
High-pressure is high (high-pressure saturation 58°C) at cooling
or
Low-pressure is low (low-pressure saturation 0°C) at heating
02-07
Page 36
2-3-4 Other Control
To accurately detect the outside air temperature, the fan is operated while the outdoor unit is stopped.
2-4 EXPANSION VALVE CONTROL
Control range
Initialization
conditions
Operation mode
operationstop
Cooling
EEV 1
EEV 2
< Cooling mode >
500 pulses basically.
< Heating mode >
EEV is controlled so that the system reaches closer to the target discharge temperature that is calculated from
high and low pressure.
When power
turned on
When operation
stopped
Heating
Cooling
Heating
500 pulses
0 pulses
40 - 500 pulses
55 - 500 pulses0 pulses
02-08
Page 37
2-5 SPECIAL OPERATION
2-5-1 Oil Recovery Operation
Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units
and the connection pipe with the refrigerant will become large as the operation time of compressor increases.
It is necessary to recover the oil back into the outdoor unit for a certain time interval
in order to prevent compressors from damaging due to lack of lubrication oil.
1. Oil Recovery in Cooling operation
< Start condition >
Compressor accumulated operation time since last cooling oil recovery operation exceeds 3 hours (first time : 1hour)
< End condition >
30 seconds have elapsed since the start and "suction temperature - low pressure saturation temperature 5deg" or 6 minutes
have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode).
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
2. Oil Recovery in Heating operation
< Start condition >
Compressor accumulated operation time since the last heating oil recovery exceeds 8 hours (first time : 1hour)
< End condition >
After 4 minutes have elapsed
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit) : Controlled pulse (as normal operation mode)
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode)
Others
During the oil recovery operation, appears on the display of wired and central remote controller,
and appears on the simple remote controller.
The operation indicators (LED) of the indoor units flash slowly.
02-09
Page 38
2-5-2 Pre-heat Operation
This pre-heat operation protects the start up failure by preventing the refrigerant from soaking into the oil in compressor.
Crankcase heater ON: 30 minutes elapsed since installed compressors stopped
*It doesn't control according to the temperature.
OFF: Compressor starts
(However, ON when power turned on)
2-5-3 Defrost Operation Control
Defrost Operation Start Condition 1
Outdoor temperature <2 and Compressor stop count exceed 20 times at less than 10 minutes of accumulated
heating operation time
Defrost Operation Start Condition 2
Accumulated heating operation time is 40 minutes or longer
[Accumulated heating operation time is reset at the end of cooling operation or defrosting operation.]
and
an outdoor unit satisfies condition or below
Condition : "Heat exchange temperature -2°C" accumulated operating time is 180 minutes or longer
Condition : After the following all condition satisfied, "heat exchange temperature defrosting start judgment
temperature and during heat exchange liquid temperature drop" accumulated time:10minutes
(a) accumulated heating operation time 30 minutes
(b) 10 minutes have elapsed after outdoor unit starting
(c) 5 minutes have elapsed since oil recovery
* Defrosting start and end judgment temperature are determined by the outdoor temperature.
Defrosting start judgment temperature = 0.8 x outdoor temperature - 11.6 (However, -27.6°C to - 6°C)
If the calculated result is lower than -27.6 , the judgment temperature is defined as -27.6
If the calculated result is higher than -6 , the judgment temperature is defined as -6
Defrost Operation End Condition
At all outdoor units, heat exchange liquid temperature end judgment temperature
or
when 10 minutes have elapsed from the start
(When the indoor unit connection capacity is 90% or less, after 15 minutes have elapsed.)
Defrosting end judgment temperature = 0.39 x outdoor temperature + 12.7 (However, 5 to 12°C range)
If the calculated result is lower than 5 , the judgment temperature is defined as 5
If the calculated result is higher than 12 , the judgment temperature is defined as 12
02-10
Page 39
2-6 PROTECTIVE FUNCTION
2-6-1 Protective Function List
Protective Function
Discharge Temp
Protection 1
Discharge Temp
Protection 2
Discharge Temp
Protection 4
Discharge Temp
Protection 5
Discharge Temp
Protection Stop
Detect Parts
Discharge Temp
Thermistor
Discharge Temp
Thermistor
Discharge Temp
Thermistor
Discharge Temp
Thermistor
Discharge Temp
Thermistor
COOL HEAT
DISPLAY
P1
EA11
Operating Condition
<Starting conditions>
3 minutes have elapsed since the start of operation and
(discharge temperature 100°C or suction SH 10°C accumulated time
30 minutes)
<Reset conditions>
Discharge temperature 95°C and suctionSH 7°C
<Starting conditions>
Cooling: Discharge temperature 95°C
Heating: Discharge temperature 102°C
< starting condition>
Discharge temperature 105°C
<Starting conditions>
Discharge temperature 95°C and EEV1=500pls
<Reset conditions>
2 minutes have elapsed and
(discharge temperature 90°C or EEV1 400pls)
<Pattern starting condition>
Discharge temperature fixed value (115°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 80°C
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
<Reset conditions>
Discharge temperature 90°C
Discharge temperature 97°C
<Pattern reset condition>
Discharge temperature 100°C
Operation
EEV of operating indoor unit gradually opened
EEV2 + 30pls/30 secs
Compressor speed -6rps every 30 secs
Speed rise prohibited,
when discharge temperature becomes lower
than 105 , prohibit the rotational speed rise
of the compressor.
Expansion valve of stopped indoor unit gradually
opened
(upper limit 200pls)
<Reset conditions>
Fixed time has elapsed and Fixed time when SV2: ON 30 secs
COMP < 25 rps ---- HP 3.0 MPa
25 rps COMP < 30 rps ---- HP 3.2 MPa
30 rps COMP
<Starting conditions>
COMP 25 rps ---- HP 3.5 MPa
COMP < 25 rps ---- HP 3.3 MPa
<Reset conditions>
3 minutes have elapsed and high-pressure 2.80MPa
<Starting conditions>
Fixed time has elapsed and high-pressure 3.50MPa
(* Fixed time at start of operation: 10 secs, after operation execution: 20 secs)
<Pattern reset condition>
5 minutes have elapsed and high-pressure 3.50MPa
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and high-pressure 3.50MPa
<Pattern starting condition>
Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition>
5 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
<Starting conditions>
Low-pressure 0.20MPa
<Reset conditions>
5 minutes have elapsed and low-pressure 0.30MPa
Compressor stopped
Compressor stopped
Compressor stopped
Compressor stopped
Error display
SV2 ON
Operation
Low Pressure
Protection 2
Low Pressure
Protection 4
Abnormal Low
Pressure Protection
Control
Low Pressure
Protection Stop
Compressor Temp
Protection Stop
Low Pressure
Sensor
Low Pressure
Sensor
Low Pressure
Sensor
Low Pressure
Sensor
Compressor
Temp
Thermistor
P3
EA51
P4
<Starting conditions>
Low-pressure 0.10MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.17MPa
<Starting conditions>
3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.22MPa
<starting condition>
Low-pressure 0.16MPa
<Pattern starting condition>
Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition>
3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition>
Pattern generated 5 times within 180 minutes.
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again.
<Pattern starting condition>
Compressor temperature fixed value (110°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 80°C
<reset condition>
3 minutes have elapsed and
low-pressure 0.18MPa
SV2 ON
EEV of stopped indoor unit opened quickly
(450pls)
Compressor capacity lowered every 180 secs,
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise.
Compressor stopped
Compressor stopped
(permanent stop)
Error display
Compressor stopped
EA31
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
02-12
Compressor stopped
(permanent stop)
Error display
Page 41
Protective Function
Overcurrent Break
Stop
(Compressor)
Detect Parts
Overcurrent
Protection Circuit
COOL HEAT
DISPLAY
E941
(permanent stop)
Operating Condition
Compressor is stopped when the over currernt protectioncircuit in the
inverter PCBoad detects an abnormal current duringthe operation.
If it repeated 5 times, the compressor becomes permanentstop.
Operation
Compressor stopped
Heatsink Temp
Protection Stop
Frequency Maximum
Setting Protection
(Compressor)
Heatsink Temp
Thermistor
Current Detector
Circuit
E931
(permanent stop)
EAC4
Compressor is stopped when the over current protection circuit in the
inverter PC Board detects an abnormal current at the time of start up.
Compressor becomes permanent stop if it repeated over the number
of set time.
<Reset condition>
Error reset (push button SW) executed after power turned on again.
<Pattern starting condition>
Heat sink temperature 100°C
<Pattern reset condition>
3 minutes have elapsed and heat sink temperature 85°C
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and heat sink temperature 85°C
<Pattern starting condition>
Current value Cooling: 22.5A / Heating: 23.5A
<Pattern reset condition>
Current value Cooling: 22.5A / Heating: 23.5A
<Pattern starting condition>
Current value Cooling: 23.0A / Heating: 24.0A
<Pattern reset condition>
Current value Cooling: 23.0A / Heating: 24.0A
• Pattern and start current value changed by outside
temperature
Compressor stopped
Compressor stopped
Error display
Compressor speed rise prohibited
Compressor speed lowered
02-13
Page 42
Page 43
3. INDOOR UNIT OPERATION
Page 44
Page 45
3. INDOOR UNIT OPERATION
3-1 FAN CONTROL
3-1-1 Fan Speed Setting
Fan speed setting
Press the FAN CONTROL button to set the fan speed.
AUTO
HIGHMEDLOW
3-1-2 "AUTO" Position
1. COOLING OPERATION
The fan speed is determined automatically in accordance
with the condition "(TR(corrected room temperature) - TS
(corrected set temperature)" as shown on the right.
However, the fan speed zone is determined in the manner
as the room temperature increases for the following cases.
(1) When the TS is changed.
(2) When the operation mode is changed from other mode to "COOL".
(3) When the fan control is changed from other position to "AUTO".
2. HEAT OPERATION
Same as Cooling operation, fan speed is decided by the
difference between the room temperature and the set
temperature.
-2
1
Fan speed zone
TR-TS
TR-TS
TR-TS
TR-TS
2
TR-TS
TR-TS
2
1
When the room
temperature decreases
Fan speed zone
-2
-3
-3
When the room
temperature decreases
Hi zone
Med zone
Low zone
Low zone
Med zone
Hi zone
TR-TS
2
TR-TS
When the room
temperature increases
TR-TS
-1
TR-TS
When the room
temperature increases
TR-TS
2
TR-TS
-2
3
3
-1
-2
3. DRY OPERATION
The indoor fan always rotates at "Lo" speed.
• Expansion
• valve
• Indoor fan
motor
(1) The indoor fan starts operation 5 seconds after the electric expansion valve opens. However, when the indoor unit just
starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is not stopped,
the fan will rotate immediately without a delay time of 5 seconds.
(2) The indoor fan will stop in 30 seconds when the refrigerant circulation stops.
(3) The indoor fan will stop immediately when the indoor unit is stopped by pushing the stop button or by a setting of ON timer.
(4) When the refrigerant circulation is stopped due to a lower room temperature for more then 3 minutes, the fan will rotate
2 minutes at intervals of 3 minutes.
(5) When the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant
circulation is stopped, the fan will rotate for 1 minute and then it will operate according to the statement (4).
OPEN
CLOSE
ON
OFF
ON
ON
30s
ON
ONONON
5s
30s
2min30s
2min
3min
ON
ON
TIME -->
5s
03-01
Page 46
3-2 MASTER CONTROL
3-2-1 Operation Mode Control
Each operation mode is controlled as below.
(1) Stop mode
Indoor fan motor : OFF
Electric expansion valve
Drain pump
(2) Cool, Dry and Heat Mode
Indoor fan motor
: Stop pulse
: Turns ON-OFF by the drain pump control function
CoolDry
Operates according to
the AIR FLOW-MODE
setting.
See the fan control
page.
Heat
Operates according to
the AIR FLOW-MODE
setting, and besides
cold air prevention
operation
Drain pump
Electrical
expansion valve
(3) Priority mode
Turns ON-OFF by the drain pump control function
Pulse controlled by
the temperature differ-
ence calculation and
frost prevent fuction
Pulse controlled by
the temperature dif-
ference calculation
and frost prevent
function
Pulse controlled by
the temperature dif-
ference.
The purpose of the priority mode is to restrict operation commands (heating, cooling, dry) from the
connected indoor units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority.
The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling, dry
1. Priority mode decision methods
Method 1. (Default value)
The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating
Priority when heating depending on which operation mode (cooling, heating) was input first.
After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there
was a Stop input from all the indoor units.
Neutral
Cooling priority
Heating priority
Method 2. (Management by outdoor unit)
Operation mode management is made "Management by outdoor unit" by outdoor unit PUSH-SW
(field setting).
The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the outdoor
unit regardless of the current mode.
Cooling priority
Heating priority
03-02
Page 47
Method 3. (Management by indoor unit)
Operation mode management is made "Management by indoor unit" by outdoor unit PUSH-SW
(field setting).
Then the master indoor unit is set by wired remote controller.
Thereupon the priority mode shifts to Cooling Priority or Heating Priority in accordance with input
from the master indoor unit regardless of the current priority mode.
The priority mode is fixed at either cooling or heating even if the master indoor unit stops
Cooling/heating switching can be performed by the master indoor unit only.
Cooling priority
Heating priority
(4) Opposite operation mode
When the operation mode commanded from an indoor unit (remote controller) and the operation mode
allowed by the system (cooling and dry operation for cooling only type and operation mode allowed by
priority mode for heat pump type) do not match, it is indicated by blinking of an LED.
Timer lamp: 3 secs ON/1 sec OFF repeated
03-03
Page 48
3-2-2 Auto Changeover
[Method]
1. Switch operation mode management to "Management by indoor unit" by outdoor unit DIP-SW.
2. Set the master indoor unit by wired remote controller.
3. Judge cooling/heating by the difference between the master indoor unit's setting temperature and
the room temperature.
AUTO CHANGEOVER operation
Operation flow chart
START
Room temp.
Ts+2°C ?
NO
YES
YES
or operation command other than
Room temp.
Ts- 2°C ?
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
auto changeover operation?
NO
YES
NO
YES
TS : Setting temperature
in OFF state for 6 minutes or
or operation command other than
auto changeover operation?
COOLING OPERATION
Thermostat remains
longer?
NO
System stops
YES
YES
NO
NO
03-04
Page 49
3-2-3 "COOL" Position
When using the cooling mode, set the temperature to a value lower than the current room temperature, otherwise
the indoor unit will not start the cooling operation and only the fan will rotate.
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
TR
• Temperature
• Refrigerant
flow
• Opening of
EEV
• Indoor fan
Ts + 0.5 C
Ts
Ts - 0.5 C
3Min.
ON
OFF
100%
0%
ON
OFF
Ts : Corrected setting temperature
TR : Corrected room temperature
Ts + 0.5 C
Ts - 0.5 C
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
3-2-4 "HEAT" Position
(1) When using the heating mode, set the temperature to a value higher than the current room temperature, otherwise
the indoor unit will not start the heating operation.
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to
blow out warm air.
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation
(3)
will be temporarily interrupted.
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
Ts + 0.5 C
• Temperature
• Refrigerant
flow
• Opening of
EEV
• Indoor fan
Ts
Ts - 0.5 C
ON
OFF
100%
0%
ON
OFF
1Min.
4Min.
Ts : Corrected setting temperature
TR : Corrected room temperature
: Duration of cold air prevention
4Min.
1Min.
Ts + 0.5 C
Ts - 0.5 C
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
4Min.
TR
1Min.
03-05
Page 50
3-3 LOUVER CONTROL
(1) ADJUSTING THE DIRECTION OF AIR CIRCULATION
Instructions relating to heating ( ) are applicable only to heat pump type
outdoor unit.
Begin air conditioner operation before performing this procedure.
Vertical Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE",
"WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Press the VERTICAL AIR FLOW DIRECTION SET button.
Example : When set to vertical air direction.
Press the VERTICAL AIRFLOW DIRECTION button.
The temperature display will change to the vertical airflow direction setting display.
Press the VERTICAL AIRFLOW DIRECTION button to change the vertical louvre position.
The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4
Heating : 1 , 2 , 3 , 4
LARGE CEILING TYPE
1
2
3
4
COMPACT WALL MOUNTED TYPE
1
2
UNIVERSAL FLOOR/CEILING TYPE
3
1
2
3
4
DANGER!
Never place fingers or foreign objects inside the
outlet ports, since the internal fan opertes at
high speed and could cause personal injury.
4
CASSETTE TYPE
WALL MOUNTED TYPE
4
Always use the remote control umit's
AIR FLOW DIRECTION button to adjust
the UP/DOWN air direction flaps or
1
2
3
4
RIGHT/LEFT air direction louvers. Attempting to move them manually
could result in improper operation; in
this case, stop operation and restart.
The louvers should begin to operate
1
2
3
4
properly again.
When used in a room with infants, children, elderly or sick persons, the air
direction and room temperature
should be considered carefully when
making settings.
Use the air direction adjustments within the ranges shown above.
1
2
3
The vertical airflow direction is set automatically as shown,
in accordance with the type of operation selected.
During Cooling mode : Horizontal flow
During Heating mode : Downward flow
1
4
During AUTO mode operation, for the first minute after beginning operation,
airflow will be horizontal ,
1
the air direction cannot be adjusted during this period.
03-06
Page 51
Horizontal Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR/CEILING TYPE" and "WALL MOUNTED TYPE".
Press the HORIZONTAL AIR FLOW DIRECTION SET button.
Press the HORIZONTAL AIRFLOW DIRECTION button. The temperature
display will change to the horizontal airflow direction setting display.
Press the HORIZONTAL AIRFLOW DIRECTION button to change the
horizontal louvre position. The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4 , 5
Heating : 1 , 2 , 3 , 4 , 5
Example : When set to horizontal air direction.
LARGE CEILING TYPE
1
5
2
4
3
WALL MOUNTED TYPE
1
2
3
4
5
UNIVERSAL FLOOR/CEILING TYPE
3
2
1
4
5
(2) SWING OPERATION
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE",
"WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Begin air conditioner operation before performing this procedure.
To select Vertical airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE",
"CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Press the VERTICAL SWING button for more than two seconds.
The remote controller's Vertical Swing Display will light up.
In this mode, the UP/DOWN air direction flaps will swing automatically to direct the air flow both up and down.
Example : When set to vertical swing.
To Stop Vertical airflow SWING Operation
Press the VERTICAL SWING button for more than two seconds
once and again.
The remote controller's Vertical Swing Display will go out.
Airflow direction will return to the setting before swing was begun.
03-07
Page 52
Instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE",
"WALL MOUNTED TYPE", and "COMPACT WALL MOUNTED TYPE".
About Vertical Airflow SWING Operation
The SWING operation may stop temporarily when the
air conditioner's fan is not operating, or when operating
at very low speeds.
The swing operation is not available depending on the model.
Please refer to the operating manual for the indoor unit.
To select Horizontal Airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR / CEILING TYPE", "WALL MOUNTED TYPE".
Press the HORIZONTAL SWING button for more than two seconds.
The remote controller's Horizontal Swing Display will light up.
In this mode, the RIGHT/LEFT air direction louvers will swing
automatically to direct the airflow both right and left.
Air swing range
Air flow direction set
1
2
3
4
Range of swing
1 to 4
(All range)
Example : When set to horizontal swing.
To stop Horizontal airflow SWING Operation
Press the HORIZONTAL SWING button for more than two seconds
once and again.
The remote controller's Horizontal Swing Display will go out.
Airflow direction will return to the setting before swing was begun.
About Horizontal Airflow Swing Operation
Left and right swing range can be changed in 3 steps by field setting.
The SWING operation may stop temporarily when the
air conditioner's fan is not operating, or when operating
at very low speeds.
The swing operation is not available depending on the model.
Please refer to the operating manual for the indoor unit.
Left and right swing range
Range of swing
1 to 5 (All range)
1 to 3
3 to 5
Function Number
24
( Factory setting)
Setting Value
00
01
02
03-08
Page 53
3-4 ELECTRONIC EXPANSION VALVE CONTROL
1. Initialization
When the power is turned ON.
When it has passed the limited time since the last initialization.
2. Operation Control
When indoor unit stopping
Outdoor unit Condition
OFF
Cooling
Heating
When starting up
(Cooling) Move to the cooling control base pulse in steps.
(Heating) Move to the heating control base pulse in steps.
Automatic operatic control
Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Room temperature control
The room temperature is controlled so that it reaches to the set-up temperature based on the difference
between the room temperature and the set-up temperature, and the change of indoor unit temperature.
if the room temperature becomes 0.5 C lower than the set-up temperature, EEV is fully closed.
EEV Condition
Fully closed
Fully closed
Slightly open
3. Special Control
Oil recovery operation : Controlled pulse.
Test run operation : Controlled pulse.
Icing protection control : Fully closed.
Pump down operation : Fully open.
Defrost operation : Controlled pulse
3-5 DRAIN PUMP OPERATION
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously.
(2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped.
(3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention
operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost
prevention operation.
(4) When the water level in the drain pan rises up and then the float switch functions:
Microcomputer stops the refrigerant circulation and indoor fan motor operation.
1
Drain pump operates continuously for 3 minutes after the float switch is turned off.
2
(Almost condensing water may be drained)
(5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates.
(6) When the float switch turns OFF within 3 minutes, the unit starts cooling operation.
03-09
Page 54
3-6 FUNCTION
3-6-1 Auto Restart
The air conditioner restarts with the previous setting operation.
3-6-2 Icing Protection Control
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition
Compressor is operation more than 3 minutes.
When "Heat exchanger inlet temperature TA" continues *4 minutes or more.
Compressor is operation more than 3 minutes.
When "Heat exchanger outlet temperature TA" continues 4 minutes or more.
(2) Operation
EEV is closed.
Fan is at the setting amount.
(3) Completing Condition
Heat exchanger inlet and middle temperature TB
After more than 5 minutes
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
*
TA
1°C
TB
7°C
3-6-3 Oil Recovery Operation
[Oil recovery operation] : It periodically returns the residual refrigerant ion oil in the indoor unit and the connection
piping back to the outdoor unit , and prevents the compressor oil level from decreasing.
Indoor unit LED : Operation LED
6 sec ON 2 sec OFF Blinking
Indoor fan : Same operation before oil recovery operation.
Indoor EEV : Control pulse
During the above operation, a refrigerant noise may be from the indoor unit.
03-10
Page 55
3-7 TIMER CONTROL
3-7-1 Wireless Remote Controller
UTY - LNH
There are following 4 kinds of timer modes are available.
ON Timer
OFF Timer
PROGRAM Timer
SLEEP Timer
1. ON / OFF TIMER
The timer functions cannot be used when this controller is used together with the remote controller (Wired type).
A beeping sound is made when a signal is received.
To set the ON / OFF timer
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
Press the TIMER MODE button to select
1
2. PROGRAM TIMER
To set the PROGRAM timer
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
1
"OFF TIMER" or "ON TIMER"
CANCEL OFF TIMER ON TIMER
PROGRAM TIMER (OFF ON, OFF ON)
Select "OFF TIMER" Adjust the OFF time.Select "ON TIMER"
2
2
3
Adjust the OFF or ON time.
(About 5 seconds later, the
entire display will reappear.)
Adjust the ON time.
(About 5 seconds later, the entire display.
4 5
will reappear.)
To cancel the TIMER
Select "CANCEL".
The air conditioner will return to normal operation.
*To change operating conditions
If you wish to change the operating conditions (ON/OFF,Mode,
Fan Speed, Temperature Setting), after making the time setting, wait until the entire display reappears, then press the appropriate buttons to change to the desired operating condition.
Select "PROGRAM TIMER"
(Either OFF ON or OFF ON
will display.)
(If the ON timer has been se lected to operate first, the unit
will stop operating at this point.)
* Even ON/OFF and Sleep timer are valid.
3. SLEEP TIMER
To set the SLEEP timer
Unlike other timer functions, the SLEEP timer is designed to set the duration of time in which the unit does not operate.
The SLEEP timer can be set regardless of whether the indoor unit is operating or stopped.
(Both the indoor unit's OPERATION indi-
1
To change the timer settings
cator lamp (green) and the TIMER indi cator lamp (orange) will light.)
1 2
Press the SLEEP button
once again.
Set the time using the
TIMER SET buttons.
2
*To cancel the TIMER
Select "CANCEL".
The air conditioner will return to normal operation.
Adjust the OFF time.
(About 5 seconds later,the
entire display will reappear.)
*To stop air conditioner
operation during
timer operating
03-11
* Even ON/OFF and Program timer are valid.
Page 56
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to
the time setting to prevent excessive cooling and heating while sieeping.
When the sleep timer is set, the set temperature
automatically rises 1°C every hour.The set
temperature can rise up to a maximum of 2°C
When the sleep timer is set, the set temperature
sutomatically drops 1°C every 30 minutes. The
set temperature can drop to a maximum of 4°C
60min.
Timer setting
1°C
2°C
30min.
60min.
1 C
2 C
90min.
Timer setting
3 C
4 C
03-12
Page 57
3-7-2 Group Remote Controller
UTY - CGG
WEEKLY TIMER
Different schedules can be set for each day of the week.
Four timers can be set for each day
1. WEEKLY TIMER
The timer function is not available depending on the initial setting.
Different schedules can be set for each day of the week.
Four timers can be set for each day.
Operation on/off time, operation mode, and temperature can be specified for each timer.
To start / cancel the WEEKLY timer operation
The timer does not start if the time is not set.
Press the ALL TIMER button to start or cancel the WEEKLY timers for all indoor units.
If any of the indoor units are in the timer mode, pressing this
button cancels the timers for all indoor units.
If none of the indoor units are in the timer mode, pressing
this button starts the timers for all indoor units.
Press the Select button to select the indoor unit.
Press the Timer Mode (DELETE) button to start or cancel the WEEKLY timers.
Note: When a time is not set, the weekly timer cannot be started.
To set the WEEKLY timer
1
Press the PROGRAM (CLOCK ADJUST) button.
3
Press the DAY button to select the day of the week.
* For ALL, all of the days can be set together when a appears around
each day.
4
* Do not press this button for two sec onds or more, otherwise you will en ter the time setting mode.
Day of the week setting
Timer setting
Decrement Increment
2
Press the Select button to select the indoor unit.
* If all indoor units are selected, the times for all of the registered indoor unit
timers are set at once.
ALL
Press the Set Time buttons to set the time in 10-minute increments.
* Hold down a Set Time button to adjust the time quickly.
S M T W T F S
SUNMONTUEWEDTHUFRISAT
All indoor units
* The time already set at another timer is skipped at the relevant indoor unit.
03-13
Page 58
5
Operating setting
Press the Start/Stop button or the Mode button or the Set Temperature button to set
the operation.
* For the operations that can be set, refer to "Operation mode setting", "Room tem perature setting", and "To start /stop operation" , in "OPERATION".
* Only the current operation settings are displayed.
Raise
Lower
Setting the next timer for the same day:
AM
ex.TIMER-1 will start operation at 8:00 on COOL.
6
TIMER-1TIMER-2TIMER-3TIMER-4
Then press the ENTER button to proceed to the time setting, and repeat steps from to .
Repeat steps to to set the timer for another day of the week.
Be careful for pressing the ENTER button without any operation setting because the time that is set will be
cancelled.
Setting the timer for the other indoor units:
35
7
Before setting the timer for other indoor units, press the ENTER button to confirm the
settings.
* The display switches to the next timer.
Repeat steps to to set the timer for other indoor units.
26
45
8
1. Press the ENTER button to confirm the set timer.
2. Press again the PROGRAM (CLOCK ADJUST)
button to complete the weekly timer setting.
* flashes for two seconds.
To delete the operating time
NOTES
(1) The WEEKLY timer does not operate when the HEAT timer is set if a HEAT PUMP MODEL in the air conditioning system
is operating in the cooling mode. In addition, the WEEKLY timer does not operate when the COOL or DRY timer is set if
a HEAT PUMP MODEL in the air conditioning system is operating in the heating mode.
(2) Even if the timer operation is set, the timer lamp of the indoor unit does not light up. (The timer lamp is used for
wireless remote controller only.)
(3) If the same time is set in Timer-1 to Timer-4 of an indoor unit, the timer setting of the smallest number will be effective.
1. If the Timer Mode (DELETE) button is pressed during steps to , the operat ing time for the selected day will be deleted.
* If all the days are selected, the operating times for all of the days of the se lected timer will be deleted.
2. Press the ENTER button to confirm the deletion.
When the operating time is set, the mark appears.
ex. TIMER-1 will start operation at 8:00 on COOL with a set ting of 20 C
37
03-14
Page 59
3-7-3 Wired Remote Controller
UTY - RNK
ON / OFF TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
The timer function is not available depending on the model.
To set the ON/OFF timer
1
No display
NON
STOP
To cancel
Press the timer mode button to select the ON timer or OFF timer.
It is switched every time as shown
in the below diagram when the
button is pressed.
OFF
TIMER
Press the DELETE button to cancel the timer mode.
The timer mode can also be canceled by changing the timer mode using the timer mode button.
ON
TIMER
WEEKLY
TIMER
SUMOTUWETH FR
SA
2
From 1 to 24 hours
Press the set time buttons to set the time.
After the time is set, the timer will start automatically.
The amount of time until the OFF timer operates that is
displayed on the timer display decreases as time passes.
ex. OFF timer set for 6 hours
03-15
Page 60
2. WEEKLY TIMER
The timer function is not available depending on the model.
Weekly timer setting
1
Press the timer mode button to select the weekly timer.
Day of the week setting
3
1
Press the DAY button to select the day of the week, and then press the
TIMER SET button to confirm the setting.
For ALL, all of the days can be set together when a
each day.
Time setting (ON / OFF timer)
2
SUMOTUWETH FR
369
ALL SU MO TU WE TH FR SA
SA
12 15 18 21
appears around
4
1
2
2
Press the SET button for 2 seconds or more.
SUMOTUWETH FR
369
When the operating time is set, the
mark appears.
SA
12 15 18 21
ON-1OFF-1ON-2OFF-2
ex. The timer is set for 7:00-18:00.
Press the SET TIME buttons to set the ON time in 30-minute increments, then press the TIMER SET button to proceed to
the OFF time setting. Set the OFF time in the same way.
If necessary, set the second weekly timer settings in the same way.
Time setting (Independent OFF timer)
Switching from ON/OFF timer to independent OFF timer
The independent timer
will flash on the display.
1
ON-2OFF-2OFF-2OFF-3
Press the TIMER MODE button to change to the independent OFF timer setting.
* The time setting process is the same as the ON/OFF timer.
Press the TIMER MODE button to return to the ON/OFF timer setting.
To delete the operating time
5
6
Repeat steps and to set
the weekly timer for another
day of the week.
34
Press the TIMER SET button
for 2 seconds or more to
complete the weekly timer
settings.
03-16
If the TIMER DELETE button is pressed during steps or
, the operating time for the selected day will be deleted.
If all the days are selected, the operating times for all of the
days will be deleted.
3
4
Page 61
To start /cancel the WEEKLY timer operation
To start
The independent timer
will flash on the display.
369
ex.Operating time 7:00-18:00
Indpnd. OFF time 21:00
When the weekly timer is selected,
the timer starts automatically.
The operating time for the current
day is displayed.
NOTES
(1) PRECAUTIONS DURING WEEKLY TIMER SETUP
Setup is not possible in the following cases, so amend
the time.
Be sure to set the ON time first, then the OFF time. If
either the ON time or the OFF time is not set cor
rectly, the timer will not operate properly.
The WEEKLY 2 settings cannot be set earlier than the
WEEKLY 1 settings.
The WEEKLY 1 and WEEKLY 2 time spans cannot
overlap.
To cancel
12 15 18 21
(2) The earliest OFF time you can set is 30 minutes after the
ON time.
(3) The OFF time can be carried over to the next day.
(4) The earliest independent OFF time you can set is 30 min utes after the last OFF time.
(5) An independent OFF time can be set up to 0:00 hours of
the next day.
(6) Even if the timer operation is set, the timer indicator lamp
of the indoor unit does not light up. (The timer indicator
lamp is used for wireless remote controllers only.)
Press the TIMER DELETE button to
cancel the timer mode.
The timer mode can also be canceled
by changing the timer mode using
the TIMER MODE button.
To set the DAY OFF (for a holiday)
1
During the weekly timer,
press the TIMER SET
button for 2 seconds or
more to set the day.
SUMOTUWETH FR
234
Select the day to set the
DAY OFF.
SA
SUMOTUWETH FR
Press the DAY (DAY OFF)
button for 2 seconds or
more to set the DAY OFF.
SA
Flashing mark:
indicates the DAY OFF.
Press the TIMER SET
button for 2 seconds or
more to complete the
DAY OFF setting.
To cancel
369
12 15 18 21
ex. The DAY OFF is set for Monday.
369
12 15 18 21
Follow the same procedures as those
for setup.
NOTES
The DAY OFF setting is only available for days for which weekly settings already exist.
If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as
shown below.
NormalNext day setting
DAY OFF
DAY OFF
ONOFFONOFF
WEEKLYWEEKLY
Setting dayPreceding day Next daySetting dayPreceding day Next day
The DAY OFF setting can only be set one time.
The DAY OFF setting is cancelled automatically after the set day has passed.
ON
WEEKLY
03-17
OFF
ON
WEEKLY
OFF
Page 62
3. TEMPERATURE SET BACK TIMER
The timer function is not available depending on the model.
Temperature SET BACK timer setting
SET BACK
SUMOTUWETH FR
1
369
Press the SET BACK button to change to the SET BACK confirmation display.
The SET BACK operating time and the set temperature will
be displayed.
Day setting Operating time setting
3
1
Follow step and in "To set the WEEKLY timer". The DELETE button is also used as described in the
procedures for the weekly timer.
34
Temperature setting
2
4
SA
12 15 18 21
3
Press the set temperature buttons to set
the temperature. (The temperature setting
range is the same as the range for the
operation mode.)
SUMOTUWETH FR
SA
If there is no existing
SET BACK temperature setting, " - - " will
be displayed for the
temperature.
4
2
Press the SET button for 2
seconds or more.
SUMOTUWETH FR
369
ex. When setting all days together
SA
12 15 18 21
5
369
12 15 18 21
ex. Operating time 15:00 - 22:00
ONOFF
SET BACK temperature
Normal temperature
To start /cancel the temperature SET BACK timer operation
To start
SET BACK
24°C
SUMOTUWETH FR
28°C
24°C
SA
Repeat steps and .
Press the SET button for 2 seconds or more to complete the
temperature SET BACK timer
settings.
To cancel
34
1
ex. Display during SET BACK timer operation
(The operating time will not be displayed.)
Press the SET BACK button. The SET BACK confirmation display appears
for 5 seconds, and then the timer starts automatically.
NOTES
The SET BACK timer only changes the set temperature, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
The SET BACK timer can be used together with the ON, OFF, and weekly timer functions.
The SET BACK operating time is displayed only in the SET BACK confirmation display.
(Refer to step 1 for the SET BACK confirmation display. )
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature
is set to 17°C or lower.
Room temperatures as low as 10, 12, and 14°C cannot be set depending on the model.
Press the SET BACK button, and then
press the DELETE button while the
SET BACK confirmation display is displayed. Even if the SET BACK button
is pressed again, the SET BACK timer
will be cancelled.
2
03-18
Page 63
4. TROUBLE SHOOTING
Page 64
4. TROUBLESHOOTING
4-1 NORMAL OPERATION
4-1-1 Indoor Unit Display
Flashing PatternIndication LampIndication type
Operation
Continuous lighting
Operation LED
Continuous lighting(lowered light)Anti Freeze
Continuous lighting(lowered light)Timer LEDTimer
FilterFilter LEDContinuous lighting
1 sec1 sec
Operation LED
ON
OFF
Power Failure
1 sec
1 sec
6 sec2 sec
Defrosting
Oil Recovery
Timer LED
Operation LEDTest Operation
Timer LED
Operation LED
ON
OFF
ON
OFF
ON
OFF
1 sec
1 sec
Opposite Operation Mode
Maintenance Mode
Timer LED
Operation LED
Timer LED
Filter LED
ON
OFF
ON
OFF
3 sec1 sec
1 sec1 sec
04-01
Page 65
4-1-2 OUTDOOR UNIT DISPLAY
Indication type7 Segment LED Pattern
Idling(stop)
Cooling Mode
Heating Mode
Oil Recovery Operation
Defrost Operation
System stooped with Discharge Temp.
Protection
System stopped with High Pressure
Protection
System stopped with Low Pressure
Protection
System stopped with compressor Temperature
Protection
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" ROTECT "4"
Description
Refer to 02-10 page for operation.
Refer to 02-11 page for operation.
<Starting condition>
Discharge temp fixed value: 115°C
<Release condition>
3 minutes have elapsed and discharge temperature 80°C
<Starting condition>
High pressure 4.00MPa
<Release condition>
5 minutes have elapsed and high pressure 3.50MPa
<Starting condition>
Low pressure 0.05MPa
or low pressure 0.10MPa continues for 10 minutes
<Release condition>
3 minutes have elapsed and low pressure 0.17MPa
<Starting condition>
Compressor temp fixed value :110°C
<Release condition>
3 minutes have elapsed and discharge temperature 80°C
Peak Cut Mode
Low Noise Mode
Inverter Compressor Operation Indication
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
LED104
POWER
LED101
ERROR
LED102
"P" eak "C" ut
"L" OW "N" OISE
Blinking
ON
OFF
ON
OFF
Refer to 02-08 page for operation.
ON
1 sec1 sec
OFF
04-02
Page 66
4-2 ABNORMAL OPERATION
4-2-1 Indoor Unit Display
Please refer the flashing pattern as follows.
Error Contents
Remote Controller
Communication Error
Network Communication Error
Indoor Unit Parallel
Communication Error
Indoor Unit Power
Frequency Abnormal
Indoor Unit Main PCB Error
Room Temperature Sensor Error
Indoor Unit Heat Ex. Sensor Error
Indoor Unit Fan Motor Error
Water Drain Abnormal
Outdoor Unit Error
1 times flash
1 times flash
4 times flash
4 times flash
5 times flash
5 times flash
9 times flash
4 times flash
6 times flash
3 times flash
15 times flash
Filter LEDTimer LEDOperation LED
Continuous flash2 times flash1 times flash
Continuous flash
Continuous flash
Continuous flash1 times flash3 times flash
Continuous flash 2 times flash3 times flash
Continuous flash1 times flash
Continuous flash2 times flash
Continuous flash1 times flash
Continuous flash
Continuous flash
Trouble
shooting
9
11
10
2
1,3
4
5,6
8
7
12 ~ 48
Depending on contents of Outdoor unit, it may not indicate. (Refer to "TROUBLE LEVEL OF SYSTEM")
Error Indication Flashing Pattern
Example : Indoor Unit Main PCB Error (Operation LED : 3 times, Timer LED : 2 times)
1 cycle
ON
1.0s
Operation LED
Timer LED
Filter LED
OFF
ON
OFF
ON
OFF
0.5s 0.5s
0.1s / 0.1s
0.5s 0.5s 0.5s 0.5s
4.0s
1.0s
3.0s
0.5s 0.5s
0.5s 0.5s
1.0s
4.0s
04-03
Page 67
4-2-2 Outdoor Unit Display
LED display
POWER
ERROR
MODE
POWER MODE LED : on
ERROR LED : blink
LED101
LED102
(GREEN)
(RED)
Operation button
MODE
SW107
EXIT
SELECT
SW108SW109
ERROR transition
Short press : less than 3 seconds
Long press : more than 3 seconds
POWER
ON
LED101
OFF
0.1sec0.1sec
ON
ERROR
LED102
OFF
ENTER
Annunciation
"Err." and quantity are alternately shown.
"ENTER" short press"ENTER" short press
Type of errors
ex : discharge thermistor 1 abnormal ex : indoor unit abnormal
"SELECT" short press
display change
When there is more than one error, display is changed by "SELECT" short press.
"ENTER" short press"ENTER" long press
*
If some error is newly occured or resolved
during transition, it is reflected after going
back to "Annunciation".
Address
"SELECT" short press
display change
When more than one indoor unit is abnormal, display is changed by "SELECT" short press.
04-04
* Only in the case of "indoor unit abnormal
(E.5U.1)", indoor unit address is shown by
ENTER long press.
Page 68
4-2-3 Error Code List for Outdoor Unit
Error
Code
- - - -
1 4 . 2
1 4 . 5
2 8 . 1
2 8 . 4
5 U . 1
6 2 . 3
6 2 . 6
6 2 . 8
6 3 . 1
6 7 . 2
6 9 . 1
7 1 . 1
7 2 . 1
7 3 . 3
Error Contents
Initial Setting Error
Outdoor unit Network communication abnormal 2
The number of Indoor unit shortage
Auto Address Setting Error
Signal Amplifier Auto Address Setting Error
Indoor Unit Error
Outdoor Unit EEPROM Access Error
Inverter Communication Error
EEPROM Data corrupted Error
Inverter Error
Inverter PCB short intereuption detection
Outdoor Unit transmission PCB
Parallel Communication Error
Discharge Temp. Sensor Error < TH1 >
Compressor Temp. Sensor Error < TH10 >
Heat Ex. Liquid pipe Temp. Sensor Error < TH5 >
Trouble
shooting
12
14
48
46
47
1 - 11
15
16
17
18
19
20
21
22
23
Error
Code
9 3 . 1
9 4 . 1
9 5 . 5
9 7 . 1
9 7 . 4
9 7 . 5
9 8 . 5
A 1 . 1
A 3 . 1
A 4 . 1
A 4 . 2
A 5 . 1Low Pressure Abnormal
Inverter Compressor Start Up Error
Trip Detection
Compressor Motor Loss of Synchronization
Outdoor Unit Fan Motor Lock Error
(Start up Error)
Outdoor unit FAN motor under voltage
(Lack of DC Voltage)
Outdoor Unit Fan Motor 1 Temperature Abnormal39
Outdoor Unit Fan Motor Lock Error
(Start up Error)
Outdoor Unit Fan Motor 2 Temperature Abnormal39
Coil ( Expansion Valve 1 ) Error 409 A . 1
Coil ( Expansion Valve 2 ) Error 409 A . 2
Discharge Temperature Abnormal
Compressor Temperature Abnormal
High Pressure Abnormal
High Pressure Protection 1
Error Contents
Trouble
shooting
34
35
36
37
38
379 8 . 1
41
42
43
44
45
7 4 . 1
7 5 . 1
7 7 . 1
8 2 . 1
8 2 . 2
8 3 . 2
8 4 . 1
8 6 . 1
8 6 . 3
8 6 . 4
Outdoor Temp. Sensor Error < TH3 >
Suction Gas Temp. Sensor Error < TH4 >
Heat Sink Temp. Sensor Error < IPM built in >
SC HE. Gas Inlet Temp. Sensor Error < TH8 >
SC HE. Gas Outlet Temp. Sensor Error < TH9 >
SC HE. Liquid Outlet Temp Sensor Error < TH7 >
Current Sensor Error
Discharge Pressure Sensor Error
Suction Pressure Sensor Error
High Pressure Switch Error
24
25
26
27
28
29
30
31
32
33
04-05
Page 69
4-2-4 Remote Controller Display
<< SIMPLE REMOTE CONTROLLER >>
ERROR CODE DISPLAY
If an error occurs, the following display will be shown.
(““ will appear in the set room temperature display.)
“ is displayed, immediately contact authorized
If “
service personnel.
<< WIRED REMOTE CONTROLLER >>
Error code
Faulty unit No.
(Remote controller address)
Ex. Error code display
ERROR CODE DISPLAY
If an error occurs, the following display will be shown.
(““ will appear in the set room temperature display.)
“ is displayed, immediately contact authorized
If “
service personnel.
<< GROUP REMOTE CONTROLLER >>
ERROR CODE DISPLAY
The air conditioning system must be inspected if “ : “
(error code) appears on the timer and Clock Display, or the
operation lamp is flashing.
*1 ;
Model code
: Outdoor unit
: Indoor unit
: Group remote controller
: Convertor
Unit number (usually 0)Error code
Ex. Error code display
Model code
Error code
Ex. Error code display
*1
04-06
Page 70
4-2-5 Error Code List for Simple and Wired Remote Controller
Error
Code
1 2
1 4
1 5
1 6
3 1
3 2
Error Contents
Remote Controller
Communication Error
Network Communication Error
Scan Error
Indoor Unit Parallel Communication Error
Indoor Unit Power Frequency Abnormal
Indoor Unit Main PCB Error
Trouble
shooting
9, 82
11
83
10
2
1, 3
Error
Code
4 1
4 2
5 1
5 3
9 U
4-2-6 Error Code List for Group Remote Controller
Error
Code
- -
1 2
1 4
1 5
1 6
Error Contents
Initial Setting Error
Remote Controller
Communication Error
Network Communication Error
Scan Error
Indoor Unit Parallel Communication Error
Trouble
shooting
12
9,10,71,77
11,13,14,80
83
10
Error
Code
8 2
8 3
8 4
8 6
9 3
Error Contents
Room Temperature Sensor Error
Indoor Unit Heat Ex. Sensor Error
Inddor Unit Fan Motor Error
Water Drain Abnormal
Outdoor Unit Error
Error Contents
Sub-cool Heat Ex. Gas Temperature Sensor Error
Liquid Pipe Temperature Sensor Error
Current Sensor Error
Pressure Sensor Error
Compressor Start Up Error
Trouble
shooting
4
5, 6
8
7
12 48
Trouble
shooting
27,28
29
30
31 33
34
2 6
2 8
3 1
3 2
4 1
4 2
5 1
5 3
6 2
6 3
6 7
6 9
7 1
7 2
7 3
7 4
7 5
Address Setting Error
Other Setting Error
Indoor Unit Power Frequency Abnormal
Indoor Unit Main PCB Error
Room Temperature Sensor Error
Indoor Unit Heat Ex. Sensor Error
Indoor Unit Fan Motor Error
Water Drain Abnormal
Outdoor Unit Main PCB Error
Inverter Error
Inverter PCB short interruption detection
Outdoor Unit transmission PCB Error
Discharge Temperature Sensor Error
Compressor Temperature Sensor Error
Heat Ex. liquid pipe Temperature Sensor Error
Outdoor Temperature Sensor Error
Suction Gas Temperature Sensor Error
78
46, 47
2
1, 3
4
5, 6
8
7
15 17
18
19
20
21
22
23
24
25
9 4
9 5
9 7
9 8
9 A
A 1
A 3
A 4
A 5Low Pressure Abnormal
C 4PCB Error76
C ASoftware Error67, 74
C 1PCB Error 165, 70
Trip Detection
Compressor Motor loss of Synchronization
Outdoor Unit Fan Motor 1 Error
Outdoor Unit Fan Motor 2 Error
Coil ( Expansion Valve ) Error
Discharge Temperature Abnormal
Compressor Temperature Abnormal
High Pressure Abnormal
35
36
37 39
37 39
40
41
42
43, 44
45
7 7Heat Sink Temperature Sensor Error
26
04-07
Page 71
4-2-7 TROUBLE LEVEL OF SYSTEM
<< System Condition when Outdoor Unit Error is occurred >>
12
System Condition
Outdoor unit Condition
>Abnormal
>LED indication
>Outdoor unit does not stop
(1)
Not indicated on Indoor Unit.
Not indicated on Peripheral Unit.
Indicated on Service Tool.
(Not available)
Trouble Level
(2)
Indicated on Indoor Unit.
Indicated on Peripheral.
Indicated on Service Tool.
> Suction gas Temp sensor error
> Outdoor Temp sensor error
> Sub-cool heat Ex. gas inlet Temp
sensor error
> Sub-cool heat Ex. gas outlet Temp
sensor error
System is not
stopped compulsorily
>Abnormal
>LED indication
>Outdoor unit does not stop
> Discharge temperature abnormal
(Inverter compressor stops)
> Compressor temperature abnormal
(Inverter compressor stops)
> High pressure switch error
(Inverter compressor stops)
> High pressure switch error
(Constant speed compressor stops)
> Discharge Temp sensor error
(Inverter compressor stops)
> Compressor Temp sensor error
(Inverter compressor stop)
> Heat sink Temp sensor error
(Inverter compressor stop)
> Current sensor error
(Inverter compressor stop)
> High pressure switch error
(Inverter compressor stop)
> Inverter error
(Inverter compressor stop)
> Heat sink temperature abnormal
(Inverter compressor stop)
> Inverter compressor start up error
(Inverter compressor stop)
> Trip detection
(Inverter compressor stops)
> Rush current limiting resister Temp
rise protection
(Inverter compressor stop)
> Comp. motor loss of synchronization
(Inverter compressor stop)
> Inverter communication error
(Inverter compressor stop)
> Outdoor unit EEPROM access error
> Outdoor unit EEPROM data corrupted
> Indoor unit number shortage
This will not be displayed on indoor unit which Error Report Target(function setting 47 of indoor unit) is set "for administrator".
04-08
Page 72
System Condition
System is
compulsorily stopped.
Outdoor unit Condition
>Abnormal
>LED indication
>Outdoor unit stops
>Need to repair
>secondary accident
is possible.
Trouble Level
12
(1)
Not indicated on Indoor Unit.
Not indicated on Peripheral Unit.
Indicated on Service Tool.
(Not available)>High pressure abnormal
(2)
Indicated on Indoor Unit.
Indicated on Peripheral.
Indicated on Service Tool.
>Low pressure abnormal
>Fan motor 1 lock error
>Fan motor 2 lock error
>Fan motor 1 temp. abnormal
>Fan motor 2 temp. abnormal
>Heat Ex. liquid Temp sensor error
>Discharge pressure sensor error
>Suction pressure sensor error
>Outdoor unit communication PCB
parallel communication error
>Outdoor unit network
communication 2 error
>Lack of DC Voltage
>Indoor unit number shortage
>SC HE. Liquid Outlet Temp
Sensor Error
<Important>
Even if power is reset, the following Error cannot release.
- Discharge temperature abnormal
- Compressor temperature abnormal
- Current sensor error
- Inverter compressor start up error
- Trip detection
- Rush current limiting resister Temp rise protection
-Comp. motor loss of synchronization
- Low pressure abnormal
- Fan motor 1 lock error
- Fan motor 2 lock error
These errors can not be judged without operating the system, and the serviceman
would not be able to check it if the system power is turned off before visiting the site for repair.
In Error release, you need to operate push switch and apply "Error reset" (F3-40) after power restart.
04-09
Page 73
Page 74
4-3 TROUBLE SHOOTING
4-3-1 Trouble shooting with error code (INDOOR UNIT)
Trouble shooting 1
INDOOR UNIT Error Method:
Model Information Error
(Indoor Unit Main PCB Error)
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Error Code : 3 2
Detective details:
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause : 1. Outside cause 2. Connection failure of electric components 3. Controller PCB defective
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
3 continuous failure of read test of EEPROM at Power ON, or Apparent Model
information error from EEPROM. Also, Error on Model information upon model
information test of EEPROM, or Model information of EEPROM not possible to
recover.
NO
YES
Check Point 2 :
Check Indoor Unit electric components
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-2 :
Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure ----- Check if there is a defective
contact or leak current in the
power supply circuit.
Noise ----- Check if there is any equipment causing harmonic
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.
04-11
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a nonvolatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
Page 75
Trouble shooting 2
INDOOR UNIT Error Method:
Power Frequency Abnormal
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 3 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
Error Code : 3 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause : 1. Outside cause 2. Installation failure 3. Defective connection of electric components
4. Controller PCB defective
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
Detective details:
When 5 continuous failures occurred at Power frequency test.
NO
YES
Check Point 1-2 :
Check outside cause (Voltage drop or noise, etc.)
Check Point 2 : Check Installation condition
Check Cable/Breaker
Check loose or removed connection
>> If Installation defect is found, correct it by referring
to Installation Manual.
OK
Instant drop ----- Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure ----- Check if there is a defective
contact or leak current in the
power supply circuit.
Noise ----- Check if there is any equipment causing harmonic
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.
Wrong power supply installation ----- Check if the power supply
frequency is stable or not.
Check Point 3 : Check connection of electric components
Check power supply voltage (AC230V between Indoor
unit terminal 1 and 2)
Check connection of Connector (any lose connector or
incorrect wiring)
Check any shortage or corrosion on PCB.
AC
OK
Check Point 4 : Replace Controller PCB
Change Controller PCB and set up the original address.
04-12
Page 76
Trouble shooting 3
INDOOR UNIT Error Method:
EEPROM Access Abnormal
(Indoor Unit Main PCB Error)
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause :
1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Detective details:
When 3 continuous failure occurred on read test of EEPROM.
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
YES
Check Point 2 :
Check Indoor Unit electric components
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
NO
Check Point 1-2 :Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure ----- Check if there is a defective
contact or leak current in the
power supply circuit.
Noise ----- Check if there is any equipment causing harmonic
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.
04-13
Page 77
Trouble shooting 4
INDOOR UNIT Error Method:
Room Temperature Sensor Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Temperature Thermistor
When Indoor thermistor open or shortage is detected at power ON.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
2520151050
10.012.515.820.125.233.6Resistance Value ( )
Temperature (°C)
504540
30
8.0
35
6.5
3.54.35.3Resistance Value ( )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN20 Wire:Black)
H/E Outlet Thermistor
(CN20 Wire:Gray)
Room Temp. Thermistor
(CN19 Wire:Black)
Cassette Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN9 Wire:Black)
H/E Outlet Thermistor
(CN9 Wire:Gray)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
Wall mount Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN17 Wire:Black)
H/E Outlet Thermistor
(CN17Wire:Gray)
DC
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
Room Temp. Thermistor
(CN10 Wire:Black)
Room Temp. Thermistor
(CN8 Wire:Black)
If the voltage does not appear, replace Controller PCB and set up the original address.
Room Temp. Thermistor
(CN16 Wire:Black)
04-14
Page 78
Trouble shooting 5
INDOOR UNIT Error Method:
Heat Exchanger Inlet Sensor Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Heat Exchanger Inlet Thermistor
When open or shorted Heat Exchanger Inlet Thermistor is detected
at Power ON.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
Resistance Value ( )
2520151050
49.862.579.1100.9129.8168.6
30
40.0
35
32.4
Temperature (°C)
Resistance Value ( )
If Thermistor is either open or shorted, replace it and reset the power.
504540
17.821.226.3
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN20 Wire:Black)
H/E Outlet Thermistor
(CN20 Wire:Gray)
Room Temp. Thermistor
(CN19 Wire:Black)
Cassette Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN9 Wire:Black)
H/E Outlet Thermistor
(CN9 Wire:Gray)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
Wall mount Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN17 Wire:Black)
H/E Outlet Thermistor
(CN17 Wire:Gray)
DC
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
Room Temp. Thermistor
(CN10 Wire:Black)
Room Temp. Thermistor
(CN8 Wire:Black)
If the voltage does not appear, replace Controller PCB and set up the original address.
Room Temp. Thermistor
(CN16 Wire:Black)
04-15
Page 79
Trouble shooting 6
INDOOR UNIT Error Method:
Heat Exchanger Outlet Sensor Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Heat Exchanger Outlet Thermistor
Forecast of Cause : 1. Connector defective connection 2.Thermistor defective 3.Controller PCB defective
Detective details:
When open or shorted Heat Exchanger outlet Thermistor is detected at Power
ON.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
Resistance Value ( )
Temperature (°C)
2520151050
49.862.579.1100.9129.8168.6
30
40.0
504540
35
32.4
Resistance Value ( )
If Thermistor is either open or shorted, replace it and reset the power.
17.821.226.3
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Duct Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN20 Wire:Black)
H/E Outlet Thermistor
(CN20 Wire:Gray)
Room Temp. Thermistor
(CN19 Wire:Black)
Cassette Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN9 Wire:Black)
H/E Outlet Thermistor
(CN9 Wire:Gray)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
Wall mount Schematic Diagram (Connector connection)
H/E Inlet Thermistor
(CN17 Wire:Black)
H/E Outlet Thermistor
(CN17 Wire:Gray)
DC
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
Room Temp. Thermistor
(CN10 Wire:Black)
Room Temp. Thermistor
(CN8 Wire:Black)
If the voltage does not appear, replace Controller PCB and set up the original address
Room Temp. Thermistor
(CN16 Wire:Black)
04-16
Page 80
Trouble shooting 7
INDOOR UNIT Error Method:
Water Drain Abnormal
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 5 times Flash, Timer LED 3 Times Flash,
Filter LED Continuous Flash.
Error Code : 5 3
Detective Actuators:
Indoor Unit Controller PCB Circuit
Float Switch
Forecast of Cause : 1. Float switch defective 2. Shorted connector/wire 3. Controller PCB defective 4. Drain pump defective
Detective details:
When Float switch is ON for more than 3 minutes.
Check Point 1 : Check Float Switch
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is defective, replace it.
ONOFF
OK
Check Point 2 : Check Connector (CN 1) / Wire
Check loose contact of CN1 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
OK
Check Point 3 : Check Controller PCB
If Check Point 1 & 2 do not improve the symptom, change
Controller PCB and set up the original address.
Attention!!
Small size wall mount type does not have a
float switch. In this case, replace Controller PCB
and set up the original address. Please refer to.
04-17
Page 81
Trouble shooting 8
INDOOR UNIT Error Method:
Indoor Unit Fan Motor Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 5 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
Error Code : 5 1
Detective details:
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Fan Motor
Forecast of Cause : 1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temp. increase
4. Capacitor failure 5. Control PCB failure
When Indoor fan control is either phase control or DC control and rotation feed
back control is ON, the feed back rotation value becomes 0 and lasts for more
than 1 minute at motor operation condition. Or, the feed back rotation value
continues at 1/3 of target value for more than 1 minute.
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check Motor winding
Check Indoor Fan motor
>>If Fan motor is abnormal, replace it.
OK
Check Point 3 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation..
OK
Check Point 4 : Check Motor Capacitor
Check continuity of motor capacitor
>>If it is shorted, replace the capacitor.
OK
Check Point 5 : Replace Controller PCB
Change Controller PCB and set up the original address.
Attention!!
In case of Duct type, replace Controller PCB
and set up the original address, since it is a
tapping control.
04-18
Page 82
Trouble shooting 9
INDOOR UNIT Error Method:
Wired Remote Controller
Communication Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Error Code : 1 2
Detective Actuators:
Indoor unit controller PCB circuit
Wired Remote Control
Forecast of Cause : 1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor
unit, but the same signal has not been received more than 1 minute.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of controller PCB Connector. (Power supply for Remote)
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote
If DC0V, Controller PCB failure (Remote is OK) >>> Replace Controller PCB
wiring, turn on the power again.
-In case of re-installation is done due to removed connector or incorrect
DC
Trouble shooting 9
INDOOR UNIT Error Method:
Wired Remote Controller Token Error
Detective Actuators:
Indoor unit Controller PCB circuit
Wired Remote Control
Forecast of Cause : 1. Terminal connection abnormal 2. Mis-setting 3. Wired Remote Control failure 4. Controller PCB failure
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1, Error LED Continuous Flash.
Remote Controller : 1 2
Detective details:
More than 1 time of Token (Communication between wired remote controllers)
is received, but it was not received more than 1 minute.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of Controller PCB Connector. (Power supply for Remote)
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote
lIf DC0V, Controller PCB failure (Remote is OK) >>> Replace Conroller PCB
In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
DC
04-19
Page 83
Trouble shooting 10
INDOOR UNIT Error Method:
Indoor Unit Parallel Communication
Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 1 times Flash, Timer LED 6 Times Flash,
Filter LED Continuous Flash.
Error Code : 1 6
Detective Actuators:
Indoor unit Controller PCB circuit
Indoor unit Communication PCB
Forecast of Cause : 1. Connection failure 2. Outside cause 3. Communication PCB failure 4. Controller PCB failure
Check Point 1-1 : Reset the power
Does LED error indication reappear?
Detective details:
When Parallel communication error (Communication reset occurs continuously
more than specified times) is detected.
NO
YES
Check Point 2 : Check Connection
Check if Indoor Communication PCB is removed.
OK
Check Point 1-2 : Check outside cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near
the power cable (Neon light bulb or any electronic equipment which
causes harmonic wave).
Check Point 3 : Replace Communication PCB
Replace Communication PCB (If the symptom does not
change, replace Controller PCB and set up the original
address.
04-20
Page 84
Trouble shooting 11
INDOOR UNIT Error Method:
Network Communication Error
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 1 times Flash, Timer LED 4 Times Flash,
Filter LED Continuous Flash.
Error Code : 1 4
Detective Actuators:
Indoor unit Controller PCB circuit
Indoor unit Communication PCB
Detective details:
When the cut-off of network communication is detected (more than 90 seconds
passed since the last receipt of Outdoor unit signal).
Forecast of Cause : 1. Connection failure 2. Outside cause 3. Communication PCB failure 4. Controller PCB failure
Check Point 1 : Check the connection
After turning off the power, check and correct followings.
Is Indoor Communication PCB loose?
Check loose or removed connection of communication line between Indoor
and Outdoor unit.
When the signal amplifier is connected , is it failure of signal amplifier?
(Refer to "TROUBLE SHOOTING FOR OPTIONAL PARTS")
OK
Check Point 2 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit.
Momentary power failure ----- Check contact failure or leak current in power supply circuit
>>Check Outdoor Unit as well.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which
causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
OK
Check Point 3 : Check Communication PCB and Controller PCB
If some of Indoor units have errors, replace Communication PCB of the Indoor units that have the error.
>>If the symptom does not change, replace Indoor unit Controller PCB.
If all the Indoor units have error, check if the Outdoor Unit Communication PCB has a loose connection.
>>If the symptom does not change, replace Outdoor unit Communication PCB (Replace Controller PCB if it does not change).
04-21
Page 85
4-3-2 Trouble Shooring With Error Code (OUTDOOR UNIT)
3. Main PCB defective
Trouble shooting 12
OUTDOOR UNIT Error Method:
Initial Setting Error
Detective Actuators:
Outdoor unit main PCB
Forecast of Cause :
1. Wrong DIP SW setting
2. Power supply defective
Indicate or Display:
Outdoor Unit : - - - - ( Flashing 0.5 sec. ON and OFF )
Indoor Unit : No Display
Error Code : No Display
Detective details:
When the DIP SW setting was wrong, after turned on the power supply
Check Point 1 : Check the power supply
Main power ON/OFF state check
Power cable connection, open check
OK
Check Point 2 : Check the outdoor unit address/number of
connected slave units setting
Setting check of outdoor unit address of each outdoor unit
Outdoor unit address
SET 3-1SET 3-2
Master
OFFOFF
OK
Check Point 3 : Replace Main PCB
Change Main PCB and set up the original address.
04-22
Page 86
Trouble shooting 13
OUTDOOR UNIT Error Method:
Outdoor Unit Network
Communication 1 Error
Indicate or Display:
Outdoor Unit : E. 14. 1
Indoor Unit : No display
Error Code : 14
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit communication PCB
1. Noise, momentary open, voltage drop 2. Indoor unit power off
Forecast of Cause :
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Main PCB defective
Detective details:
No communication for 180 seconds or more from an indoor unit which
received communication once and no outdoor network communication error 2.
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
OK
Check Point 4 : Check the Terminal resistor setting
erminal resistor setting check
T
OK
Check Point 5 : Check the communication PCB (outdoor unit/indoor unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit / indoor unit)
Change Main PCB and set up the original address.
04-23
Page 87
Change Main PCB and set up the original address.
Trouble shooting 14
OUTDOOR UNIT Error Method ::
Outdoor Unit Network
Communication 2 Error
Indicate or Display:
Outdoor Unit : E. 14. 2
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 14
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit communication PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop 2. Indoor unit power off
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Main PCB defective
Detective details:
No communication for 180 seconds or more from all indoor units that once
received communication
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
OK
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
OK
Check Point 5 : Check the communication PCB (outdoor unit/indoor unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit / in door unit)
04-24
Page 88
Trouble shooting 15
OUTDOOR UNIT Error Method:
Outdoor Unit EEPROM Access Error
Indicate or Display:
Outdoor Unit : E. 62. 3
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 62
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
Check Point 1-1 : Turn the power
1. Noise, momentary open, voltage drop 2. Main PCB defective
on agaun.
NO
Error displayed again?
YES
Check Point 2 : Replace Main PCB
Change Main PCB and set up the original address.
Detective details:
Access to EEPROM failed due to some cause after outdoor unit started.
Check Point 1-2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the
power line.
04-25
Page 89
Trouble shooting 16
OUTDOOR UNIT Error Method:
Inverter Communication Error
Indicate or Display:
Outdoor Unit : E. 62. 6
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 62
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit Inverter PCB
Forecast of Cause :
1. Noise 2. Main to Inverter PCBs wiring connection defective
3. Main PCB defective 4. Inverter PCB defective
Check Point 1-1 : Turn the power
Detective details:
on again.
NO
Error displayed again?
YES
Check Point 2 : Check the main to Inverter PCB wiring
Connector connection state check
Cable open check
Communication not received from Inverter PCB for 10 seconds or more
Check Point 1-2 : Noise
Check if ground is connection correctly or there are no related cables near the
power line.
OK
Check Point 3 : Check Main PCB
Chack Main PCB. (Refer to "Sarvise Parts Information )
OK
Check Point 4 : Replace Inverter PCB
Replace Inverter PCB.
04-26
Page 90
Trouble shooting 17
OUTDOOR UNIT Error Method:
EEPROM Data corrupted Error
Indicate or Display:
Outdoor Unit : E. 62. 8
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 62
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop 2. Main PCB defective
Detective details:
Set contents sum value memorized in EEPROM and sum value calculated
based on the set contents read from EEPROM do not match
Regarding the sum value, only the contents set in the push button SW
*
setting mode (F2) shall be the objective.
Check Point 1-1 : Turn the power on again.
Error generated again after Field setting all clear (push button SW F3
(function mode) -35 execution) and the power was turned back on?
YESNO
Check Point 1-2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Replace Main PCB
Change Main PCB and set up the original address.
Reset the setting of F2 (setting mode) by push button SW.
* To clear the setting of F2 by Field setting all clear.
04-27
Page 91
Trouble shooting 18
OUTDOOR UNIT Error Method:
Inverter Error
Indicate or Display:
Outdoor Unit : E. 63. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 63
Detective Actuators:
Inverter PCB
Filter PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop. 2. Power supply to Filter PCB (INV) to Inverter PCB
wiring disconnection, open 3. Filter PCB ( INV) defective 4. Inverter PCB defective
Check Point 1-1 : Turn the power
on again.
Error displayed again?
NO
Detective details:
Error information received from Inverter PCB
Check Point 1-2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the
power line.
YES
Check Point 2 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
Connector and wiring connection state check
Cable open check
OK
Check Point 3 : Check Filter PCB (INV) and Inverter PCB
Check Filter PCB (INV) and Inverter PCB.
04-28
Page 92
Trouble shooting 19
OUTDOOR UNIT Error Method:
Inverter PCB short interruption
detection
Indicate or Display:
Outdoor Unit : E. 67. 2
Indoor Unit : No Display
Error Code : 67
Detective Actuators:
Inverter PCB
Forecast of Cause :
1. Noise, momentary power failure, voltage drop
2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
3. Main PCB defective 4. Inverter PCB defective
Detective details:
''Momentary power failure" received from Inverter PCB
Check Point 1 : Noise, momentary power failure, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary power failure was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the wiring (Power supply to Filter PCB (INV) to
Inverter PCB)
Connector and wiring connection state check
Cable open check
OK
Check Point 3 : Check Main PCB
Check Main PCB Power supply
OK
Check Point 4 : Replace Inverter PCB
Replace Inverter PCB.
04-29
Page 93
Trouble shooting 20
OUTDOOR UNIT Error Method:
Outdoor Unit transmission PCB
Parallel Communication Error
Indicate or Display:
Outdoor Unit : E. 69. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 69
Detective Actuators:
Outdoor unit Main PCB
Communication PCB
Forecast of Cause :
1. Noise 2. Communication PCB connection defective
3. Communication PCB defective 4. Main PCB defective
Detective details:
Parallel communication (communication between main CPU and
communication PCB ) failed 5 times.
Check Point 1-1 : Turn the power
on again.
Check Point 1-2 : Noise
NO
Error displayed again?
Check if ground is connection correctly or there are
no related cables near the power line.
YES
Check Point 2 : Check the communication PCB connection
Communication PCB connection check
OK
Check Point 3 : Check the communication PCB
Communication PCB check
OK
Check Point 4 : Replace Main PCB
Change Main PCB and set up the original address.
04-30
Page 94
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Trouble shooting 21
OUTDOOR UNIT Error Method:
Discharge Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 71. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 71
Detective Actuators:
Detective details:
Discharge temperature thermistor 1 short detected
Discharge temperature thermistor 1
Discharge thermistor 1 open detected after compressor 1 operated
continuously for 5 minutes or more
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN141:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(DIS.TEMP )
< TH1 >
K
K
C
C
BLACK
BLA
BLA
1 2 3 4 5 6
1 2 3 4 5 6
THERMISTOR
(COMP SHELL )
< TH10 >
BLACK
CN141
Discharge temperature sensor 1 (CN141:1-2)
If the voltage does not appear, replace Main PCB and set up orignal address.
DC
04-31
Page 95
Check Point 3 : Check voltage of Main PCB (DC5.0V)
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 22
OUTDOOR UNIT Error Method:
Compressor Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 72. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 72
Detective Actuators:
Compressor temperature thermistor 1
Detective details:
Compressor temperature thermistor 1 short detected
Compressor thermistor 1 open detected after compressor 1 operated
continuously for 5 minutes or more
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN141:5-6) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(COMP SHELL1)
THERMISTOR
(DIS.TEMP.1)
<TH1>
K
C
BLA
BLACK
BLACK
1 2 3 4 5 6
1 2 3 4 5 6
<TH10>
K
C
BLA
CN141
Compressor temperature sensor 1 (CN141:5-6)
DC
04-32
Page 96
Check Point 3 : Check voltage of Main PCB (DC5.0V)
If the voltage does not appear, replace Main PCB and set up orignal address.
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 23
OUTDOOR UNIT Error Method:
Outdoor Unit Heat Ex. Liquid Temp.
Sensor Error
Indicate or Display:
Outdoor Unit : E. 73. 3
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 73
Detective Actuators:
Heat exchanger liquid temperature
thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Detective details:
Heat exchanger liquid temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN143:3-4) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
(SUC. TEMP.)
< TH4 >
(HEX. EXIT.)
THERMISTOR
BLACK
BLACK
1 2 3 4
1 2 3 4
< TH5 >
THERMISTOR
K
C
BLACK
BLA
CN143
Heat exchanger liquid temperature sensor (CN143:3-4)
DC
04-33
Page 97
Check Point 3 : Check voltage of Main PCB (DC5.0V)
If the voltage does not appear, replace Main PCB and set up orignal address.
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 24
OUTDOOR UNIT Error Method:
Outdoor Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 74. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 74
Detective Actuators:
Outdoor temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Detective details:
Outdoor temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2: Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information ".
OK
Main PCB (CN144:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
(OUT TEMP.)
< TH3 >
THERMISTOR
K
CK
C
LA
B
BLA
1 2 3
1 2 3
CN144
Outdoor temperature sensor (CN144:1-3)
DC
04-34
Page 98
If the voltage does not appear, replace Main PCB and set up orignal address.
Trouble shooting 25
OUTDOOR UNIT Error Method:
Suction Gas Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 75. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 75
Detective Actuators:
Suction gas temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
Detective details:
Suction gas temperature thermistor short or open detected
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN143:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
(SUC. TEMP)
< TH4 >
THERMISTOR
(HEX. EXT)
< TH5 >
K
C
BLACK
BLACK
BLA
BLACK
1 2 3 4
1 2 3 4
CN143
Suction gas temperature sensor (CN143:1-2)
DC
04-35
Page 99
Trouble shooting 26
OUTDOOR UNIT Error Method:
Heat Sink Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 77. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Trouble shooting 27
OUTDOOR UNIT Error Method:
Sub-cool Heat EX. Gas Inlet
Temp Sensor Error
Indicate or Display:
Outdoor Unit : E. 82. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 82
Detective Actuators:
Sub-cooling heat exchanger gas inlet
temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
Detective details:
Sub-cooling heat exchanger gas inlet temperature thermistor short or
open detected
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Main PCB (CN142:5-6) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
THERMISTOR
THERMISTOR
(SC.EXT.LIQ)
K
K
CK
C
C
A
A
L
L
BLACKBLA
B
B
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
THERMISTOR
(SC.INT.GAS)
< TH 8 >
(SC.EXT.GAS)
K
K
C
C
A
A
L
L
B
B
CN142
Sub-cooling heat exchanger gas inlet temperature sensor (CN142:5-6)
DC
04-37
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.