Fujitsu Airstage J-II Service Manual

Small VRF system
for light commercial and home use
CONTENTS
1. TEST RUN
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS.............................
1-2 TEST RUN METHOD..................................................................................................
1-2-1 Check Items Before Power ON............................................................................
1-2-2 Check Items After Power ON...............................................................................
1-2-3 Automatic address setting procedure for Signal amplifiers.................................. 01-06
1-2-4 Automatic address setting procedure for indoor units..........................................
1-2-5 Indoor unit connection check procedure ............................................................. 01-08
1-2-6 Test run from the outdoor unit ............................................................................ 01-09
1-2-7 Test run from the Remote controller .................................................................... 01-09
1-3 TEST RUN CONTROL................................................................................................
1-4 Field Setting And Monitor Mode List....................................................................... 01-11
2. OUTDOOR UNIT OPERATION CONTROL
01-01 01-03 01-03 01-04
01-07
01-10
2-1 INPUT / OUTPUT LIST..............................................................................................
2-2 COMPRESSOR OPERATION....................................................................................
2-2-1 Operation / Stop Condition.................................................................................
2-2-2 Capacity Control.................................................................................................
2-2-3 Speed Range of Start,Stop,and Operation..........................................................
2-3 FAN CONTROL..........................................................................................................
2-3-1 Cooling Operation...............................................................................................
2-3-2 Heating Operation...............................................................................................
2-3-3 Low noise mode..................................................................................................
2-3-4 Other Control.......................................................................................................
2-4 EXPANSION VALVE CONTROL...............................................................................
2-5 SPECIAL OPERATION..............................................................................................
2-5-1 Oil Recovery Operation......................................................................................
2-5-2 Pre-Heat Operation............................................................................................
2-5-3 Defrost Operation Control..................................................................................
2-6 PROTECTIVE FUNCTION........................................................................................
2-6-1 Protective Function List......................................................................................
02-01 02-02
02-02
02-02 02-03
02-05 02-05 02-06
02-07
02-08
02-08
02-09 02-09 02-10
02-10
02-11 02-11
3. INDOOR UNIT OPERATION
CONTENTS
3-1 FAN CONTROL..........................................................................................................
3-1-1 Fan Speed Setting...............................................................................................
3-1-2 "AUTO" Position...................................................................................................
3-2 MASTER CONTROL..................................................................................................
3-2-1 Operation Mode Control.......................................................................................
3-2-2 Auto Changeover.................................................................................................
3-2-3 "COOL" Position..................................................................................................
3-2-4 "HEAT" Position..................................................................................................
3-3 LOUVER CONTROL..................................................................................................
3-4 ELECTRONIC EXPANSION VALVE CONTROL......................................................
3-5 DRAIN PUMP OPERATION.......................................................................................
3-6 FUNCTION..................................................................................................................
3-6-1 Auto Restart.........................................................................................................
3-6-2 Icing Protection Control.......................................................................................
3-6-3 Oil Recovery Operation.......................................................................................
3-7 TIMER CONTROL......................................................................................................
3-7-1 Wireless Remote Controller................................................................................
03-01 03-01
03-01 03-02 03-02 03-04 03-05 03-05
03-06
03-09 03-09 03-10 03-10 03-10 03-10 03-11 03-11
3-7-2 Group Remote Controller..................................................................................... 03-13
3-7-3 Wired Remote Controller..................................................................................... 03-15
4. TROUBLE SHOOTING
4-1 NORMAL OPERATION..............................................................................................
4-1-1 Indoor Unit Display..............................................................................................
4-1-2 Outdoor Unit Display...........................................................................................
4-2 ABNORMAL OPERATION.........................................................................................
4-2-1 Indoor Unit Display..............................................................................................
4-2-2 Outdoor Unit Display...........................................................................................
4-2-3 Error Code List for Outdoor Unit..........................................................................
4-2-4 Remote Controller Display...................................................................................
4-2-5 Error Code List for Simple and Wired Remote Controller...................................
4-2-6 Error Code List for Group Remote Controller......................................................
4-2-7 Trouble Level of System.....................................................................................
4-2-8 Error History Mode..............................................................................................
4-3 TROUBLE SHOOTING.............................................................................. ...............
04-01 04-01
04-02
04-03 04-03 04-04 04-05 04-06
04-07
04-07
04-08 04-10
04-11
4-3-1 Trouble Shooting With Error Code (INDOOR UNIT)...........................................
4-3-2 Trouble Shooting With Error Code (OUTDOOR UNIT).......................................
4-3-3 Trouble Shooting for Optional Parts....................................................................
4-4 SERVICE PARTS INFORMATION............................................................................ 04-84
04-11 04-22 04-63
CONTENTS
5. APPENDING DATA
5-1 REFRIGERANT CIRCUIT..........................................................................................
05-01
5-2 WIRING DIAGRAM....................................................................................................
5-2-1 Indoor Unit............................................................................................................
5-2-2 Outdoor Unit.........................................................................................................
5-3 CHARACTERISTICS OF SENSORS........................................................................
5-3-1 Pressure sensor..................................................................................................
5-3-2 Thermistor resistance..........................................................................................
5-3-3 Saturation temperature and saturation pressure tables (R410A)........................
5-3-4 Temperature and pressure of refrigerant (Graph)...............................................
6. DISASSEMBLY PROCESS
05-02
05-02
05-18
05-19
05-19
05-20 05-21 05-22
1. TEST RUN
1. TEST RUN
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
Before execution
Location decision
Confirmation of Refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparation before execution
Execution 1/2
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Outdoor unit foundation work
Execution procedure and precautions Reason
Do not install the units in the place not recommended in the installation manual.
Check the characteristics of the refrigerant used and grasp the special features of the refrigerant. If refrigerant must be charged, always charge the refrigerant specified for the product.
*Confirm the product design pressure. < R410A 4.20MPa >
Prepare the design for the system
Use new refrigerant piping of the thickness specified by the
1
D&T manual.
2
Since R410A dedicated tools are necessary, prepare them in advance.
3
Absolutely avoid use of existing piping. If use of existing piping is unavoidable, the piping must be cleaned.
Always use a level and keep the indoor unit level. If the equipment is tilted toward the drain port, install it so that the tilt is within 10mm. Excessive tilt will cause water leakage.
When performing piping work, observe the following items so that the inside of the piping is clean and air tight.
1
Use pipe that is not dirty inside. Confirm the design for the piping ( Diameter, Thickness )
2 3
When the pipe is left standing, protect it. Confirm the angle of separation tube and header correctry.
4
Finish flaring exactly.
5
Confirm the width across flats dimension and shape of flare nuts.
6
Always blow nitrogen while brazing.
7
Perform flushing before connecting the equipment.
8
Always make the downward slope of the drain pipe 1/100 or
1
greater and make the horizontal length within 20m. Use hard polyvinylchloride pipe as the drain pipe.
2
Support the drain pipe between 1.5 to 2.0m.
3
Use pipe of 1 rank up (VP30 or greater) as central piping.
4
Select the size of the heat insulating material according to the ambient temperature and relative humidity of the refrigerant. Use a heat insulating material having a heat conductivity of 0.043W/ (m.k) or less.
The performance may drop significantly due to the protection controlling
Use of a refrigerant other than the specified refrigerant will invite equipment trouble
Secure the necessary pressure resistance.
Prevention of water leakage
Foreign matter, water, etc. in the piping will cause faulty cooling and compressor trouble. Incorrect pipe diameter will cause faulty cooling Incorrect angle of separation tube or header will be cause poor cooling or refrigerant noise problem Refrigerant leakage will cause low performance and abnormal stopping
Prevention of water leakage
Prevention of water leakage
Outdoor unit installation
Refrigerant piping connection work
Air tightness test
Vacuum drying
When making flare connections always use a torque wrench and tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a
1
reverse flow check adaptor to a conventional vacuum pump and use. Pump down sufficiently.
2
Approximately 1 hour or longer after -0.10MPa reached. Allow to stand for approximately 1 hour after stopping the vacuum pump and confirm that the needle does not return. Air purging using refrigerant is strictly prohibited.
3
Vaccuming mode
*
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vaccuming mode, the refrigerant address setting has to be finished.
Refrigerant leakage will cause low performance and abnormal stopping.
Refrigerant leakage will cause low performance and abnormal stopping.
Mixing in of vacuum pump oil by reverse flow will cause equipment trouble. recommend the vacuuming mode
When the [vacuuming mode] is set, <Push switch setting, F3:21> EEV of connected all indoor units opens. So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units and the outdoor unit, [vacuuming mode] is released.
01-01
Execution 2/2
Execution procedure and precautions Reason
Addition refrigerant charging
Gas leak test
Initial setting
Confirm the additional refrigerant amount with the installation
1
manual, etc. Always take the R410A refrigerant from the cylinder liquid phase
2
and charge it using the gas phase. (Do not lay a cylinder with siphon pipe on its side.)
3
Use an R410A dedicated gauge manifold and charging hose. Charge refrigerant using the liquid pipe.
4
When the defined amount of refrigerant cannot charge using the
5
liquid pipe, charge refrigerant using the gas pipe while opearing the cooling test run. Charge refrigerant bit by bit with cautious operation of valve for the liquid refrigerant back prevention.
Use an R410A dedicated leak tester to check for gas leaks.
1
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
2
Confirm the DIP SW setting SET 1: Factory setting, SET 2 : All OFF, SET 3 : All OFF, SET 4: Factory setting
Confirm the Terminal resister setting
3
SET 5-4 OFF: Disable, ON: Enable
[Note] Perform in the power OFF state.
If taken from the air phase, since the composition of the refrigerant which is charged will change, low performance and abnormal stop will occur easily. Prevent erroneous sealing in of refrigerant.
A leak tester for other than R410A cannot detect leaks.
Dual address setting No. is not allowed in one network.
If the DIP SW setting is wrong, the sys­ tem may not work correctly
If the Terminal resister setting is wrong, the system may detect transmission error
Piping length setting
Address setting for Signal Amp
- When using signal Amps -
Address setting for Indoor unit
Set according to the length of the connection piping. Set to "Standard (40 to 65m)" at the factory. Set using the push button SW on the outdoor unit main PCB. < Refer to the Page 01-16 Setting mode F2-00 > Set the pipe length to be the nearest indoor unit from the outdoor unit
When the setting is not same as the real piping length, the system may not work correctly.
If the pipe length is set as the farthest indoor unit, the nearest operating indoor unit may be stopped the operation by the icing up protection as by over cooling.
[Note] Perform in the power ON state after all indoor units have stopped operation
When setting the address of Signal amplifier, please refer to the installation manual of the signal amplifier. The address setting can be set by automatically from 1 outdoor unit on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Dual address setting No. is not allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Set the refrigerant circuit address and indoor unit address. Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch PCB) or from a remote controller or from a push button SW on the outdoor unit Main PCB < Automatic address setting, Refer to the Page 01-07 Setting mode F3-11>
Dual address setting No. is not allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Indoor unit connection check
Test run & adjustment
Turnover & explanation of operation
Before starting the system, check on the number of indoor units and the total capacity. < Refer to the Page 01-08 Setting mode F3-12 >
Normal operation will not be possible without performing the indoor unit connection check.
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state after all indoor units have stopped operation.
01-02
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
Power
source
Outdoor
unit
Check contentsProcedure
Circuit breaker capacity
Type of power source wiring
Supply power source
Wiring on terminal blocks
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Judgement standard
Outdoor unit: 32A ( AJ*A36,45,54LALH )
Indoor unit: 20A
Leakage current: 30mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit: 6mm
Indoor unit: 2.5mm2 2 wires + Ground
Outdoor unit side: AC 230V (220-240V)
Indoor unit side: AC 230V (220-240V)
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Shall be checked and entered in the check sheet.
Shall be checked and entered in the check sheet.
Connection points check & loose terminal block screws check
0.33mm2, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
DIP SW SET1, SET4 : Factory setting, SET2,SET3, SET5-1,2,3: ALL OFF Terminal resistor setting SET5 - 4 OFF: Disable, ON: Enable Check the resistance value for each network segment
Refer to the installation manual 7.7
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
2
2 wires + Ground 4mm
2
Check
Indoor
unit
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned and will lead to trouble.
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote controller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
There shall be no scratches, deformation, tilting, etc.
Shall be checked and entered in the check sheet.
Shall be installed positively.
Connection points check & loose terminal panel screws check
0.33mm2, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
0.33mm
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit address (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
2
01-03
1-2-2 Check Items After Power ON
[Note] Cooling test run for each refrigerant circuit. If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot be detected.
Power ON
Outdoor unit Main
PCB push button SW setting/check
Address
setting/
check
Indoor unit
connection check
Cooling
test run
Check contentsProcedure
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Judgement standard
Check
[Note] Turn on all indoor units power in the same refrigerant circuit address. When the system operates with the indoor units remaining no power, it is cause of malfunction.
Function setting
Automatic address setting
Address read
Address record
Address hold check
Indoor unit connection check
Are the necessary functions set ? < For the setting, Refer to the page 01-15 18 >
Addresses shall be assigned to all indoor units / Signal amps. Check for unset or duplicated addresses. < For the setting, Refer to the page 01-06, 07 >
All the indoor units and outdoor units of the same refrigerant circuit can be checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool after indoor/outdoor circuit breakers were turned OFF to ON.
Are the number of connecting indoor units correct ? Is the total capacity of indoor units correct ? < For the checking, Refer to the page 01-08 >
[Note] Before connecting service tool, the address setting has to be completed.
Outdoor unit push button
SW operation
All the indoor units in the same refrigerant state.
The outdoor units corresponding to the operation capacity of the indoor
units shall operate. < Test operation procedure, Refer to the page 01-09,10 >
circuit
shall enter the coolingtest run
All of the
indoor units
operation
(after 30 mins)
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
HPS: 2.7 MPa
LPS: 0.9 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/
abnormal vibration
There shall be no Error information on the 7-segment display on the Main PCB.
Between L - N AC230V (220-240V)
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound.
There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
01-04
Indoor unit
individual
operation
Check contentsProcedure
Judgement standard
<Indoor unit service tool + actual measurement>
Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
Check
These are representative figures of AJYA54LALH at the standard condition. ( Indoor : 27
°C, Outdoor : 35°C ) If conditions are different from those above mentioned, the figures will be changed slightly. It depends on following conditions.
Outdoor unit capacity Indoor and outdoor temperature Indoor unit capacity Pipe length etc
Trouble shooting on Test run operation
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and check the description of the Error code. < Refer to the Trouble shooting in the Service manual.> < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not Evaporator Icing up protection, High discharge temperature protection,etc. < Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc. < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1> < Refer to the regulation of installation in the Installation manual>
01-05
1-2-3 Automatic address setting for signal amplifiers When using signal amplifiers
SWITCH POSITION
Outdoor unit printed circuit board
When setting the address of the signal amplifier, please use the factory setting. (See the installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units. Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB to conÞ gure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment LED Lamp
Push button switch
SELECT
SELECT
(When [F4] to [F9] are displayed, continue to press the "SELECT" button until [ F3 ] is displayed)
ENTER
Automatic address setting for
signal ampliÞ ers
SELECT
ENTER
Press the “SELECT” button until "10" is displayed
Press the “ENTER” button for more than 3 seconds
End
*
ENTER
MODE/EXIT
* Setting is complete when the number of unit is displayed
01-06
1-2-4 Automatic address setting for Indoor units
SWITCH POSITION
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit Main PCB is set to “00”.If it is not set to “00”, it means the address of that device is not set. (Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment display. When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment LED Lamp
Push button switch
to configure settings according to the procedures below .
First 2 digits
SELECT
SELECT
ENTER
Last 2 digits
SELECT
ENTER
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
Automatic address setting for indoor units
Press the “SELECT” button until “11” is displayed.
Press the “ENTER” button for more than 3 seconds.
It may take about 10 minutes for completing the processing.
Found
End
Error
ENTER
The number of indoor units with normal set­tings will be displayed at the first 2 digits of the 7 segment display. The number of indoor units with error will be displayed at the last 2 digits.
NOTE) After the “ENTER” button is pressed, the end processing will occur for about 30 seconds. During this period, the 7 segment will blink.
01-07
1-2-5 Indoor unit connection check
SWITCH POSITION
Outdoor unit printed circuit board
Please perform the indoor unit connection check according to following procedures.
Turn on the power • of indoor unit and outdoor unit.
LED105
LED104
MODE/EXIT
Set to Function mode [F3].
SELECT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105 LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment LED Lamp
Push button switch
SELECT
continue to press the “SELECT” button until [F3] is displayed.)
ENTER
(When [F4] to [F9] are displayed,
SELECT
Press the “SELECT” button until “12” is displayed.
ENTER
Press the
“ENTER”
button for
more than 3 seconds.
When indoor unit connection check can not be performed
This will be displayed when the • Indoor unit connection check starts.
ENTER
(*1)
Confirm the number of connected indoor • units and the volume ratio of the indoor units connection.
SELECT
ENTER
When error occurs
(*1) The number of connected
indoor units Ex.) When 8 units are connected
(*2)
(*2) Volume ratio of the indoor
units connection
Ex.) When the ratio is 120%
Exit indoor unit connection check • mode.
01-08
Please refer to the following “Error code” for details
ENTER
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
MODE/EXIT
When it finishes normally, nothing will be displayed on 7 segment display.
1-2-6 Test Run From Outdoor Main PCB
All the indoor units connected to the outdoor unit can be test-operated by push button setting.
SWITCH POSITION
POWER
MODE
ERROR
LED101
(GREEN)
LED102
(RED)
7 Segment LED Lamp
LED105 LED104
Outdoor unit printed circuit board
MODE
/EXIT
SW107 SW108 SW109
SELECT ENTER
Push button switch
TEST RUN SETTING
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
< Monitoring condition >
LED105 LED104
MODE / EXIT
Note
There are the following 2 methods of resetting test operation.
Automatic reset when 60 minutes has elapsed.(1)
Reset when operation stop was performed.(2)
< Mode select condition >
[ Monitoring mode ] [ Setting mode ]
SELECT
ENTER
LED105 LED104LED105 LED104 LED105 LED104LED105 LED104
< Fuction select condition >
[ Cooling test run ]
LED105 LED104
ENTER
SELECT
Press the ENTER button for at least 3 seconds.
[ Heating test run ]
L
ED
< Pursuance completion >
LED105 LED104
SELECT
[ Function mode ]
SELECT
[ Error history mode ]
[ Central control setting
[ Test run stop ]
1
0
5
L
ED
1
0
4
SELECT
LED105 LED104
SELECT
Forced reset ]
LED105 LED104
ENTER
Press the "ENTER" button or Time out ( 5 seconds)
< Return to mode select condition >
LED105 LED104
MODE / EXIT
< Return to monitoring condition >
LED105 LED104
01-09
example, Normal indicate : [ Cooling mode ]
1-2-7 Test Run From Remote Controller
1. Standard wired remote controller
Stop the indoor unit. Push the button and button simultaneously for more than two seconds. The air conditioner will start to conduct a test run and " " will display on the remote controller display. However, the , setting button does not have function, but all other buttons, displays, and protection functions will operate.
Perform the test operation for 60 minutes.
To stop test run, push the START / STOP button of the standard wired remote controller. For the operation method, refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
UTY - RNK
SET TEMP.
TIMER MODE
CLOCK ADJUST
SET BACK
TIMER DELETE TIMER SET
DAY
DAY OFF
START / STOP
FAN MODE
2. Standard wireless remote controller
Press the TEST RUN button on the remote controller, while the air conditioner is running. To end test run operation, press the remote controller START / STOP button.
When the air conditioner is being test run, the OPERATION and TIMER lamps of indoor unit flash slowly at the same time.
3. Simple remote controller
Stop the indoor and outdoor units. Push the remote controller simultaneously for more than three seconds. The air conditioner will start to conduct a test
run and " " will display on the temperature display. However the setting button does not have function but all other buttons, displays and protection functions will operate.
button and
button
START / STOP button
TEST RUN button
UTY - LNH
START
STOP
ECONOMY
FILTER RESET
SET
TEMP.
SLEEP
TIMER
TIMER MODE
CLOCK
TEST
ADJUST
RUN
UTY - RSK
FANMODE
SET
SET
SWING
RESET
To stop test running press the button of the simple remote controller. For the operation method refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
01-10
SET
UTY-DCG
Monitor - All
On
Coll
25.0
Setup Menu
Central Controller Setting
05/31 03:59
05/31 03:59
Indoor unit Special setting
Select All
On
Off
Operation
Details
1
Monitor Group
Setup Menu
Help
2
Indoor unit Special Setting
Test Operation
Indoor Unit Set Temp. Range
Test Operation
RCG_05
6)
05/31 03:59
Filter Sign
R.C. Prohibition
05/31 03:59
or
Group
Select All
Identify Unit
Clear Unit
[ Select All (F2) ]: All of R.C.Group (Indoor units) [ Identify Unit (F3) ] : Specific R.C.Group (Indoor unit)
5. Touch panel controller
Test run operating procedure
<Monitor screen (icon)>
UTY - DTG
Monitor Mode
All
Lange Group
Office A
On
Cool
21.5 C
Room
101
Off
Meeting 1
1
On
Heat
21.5 C
Conference
A
On
Heat
21.5 C
Group Error
Schedule Filter Sign
Op.Controlled Op.Restricted
<Monitor screen (list)>
Monitor Mode
All
Lange Group
Name
Office A
Expand
Top Up
Office B
On
Heat
21.0
Restrant
On
Auto
24.0 C
Meeting
2
Off
Conference B
On
Auto
22.0
Mode Set Temp.
Top Up
Status Mode
On
Heat
10/11.2008.Mar. 02:20 PM
Down
PC Room
On
C
Entrance
On
Meeting
3
On
Parking lot
Off
C
10/11.2008.Mar. 02:20 PM
Down
Set Temp
21.5 C
Fan
High
R/C Prohibit
List
Cool
26.0 C
Auto
24.0
Heat
21.0
List
Status: On
Setting
Schedule
(1)
C
Select All
C
Clear All
Operation
(1)
(2)
C
On
Off
( * )
Status: On
Setting
Schedule
(1)
Office B
PC Room
Mixed
On
Mixed Mixed Mixed
Auto
24.0 C
Low
Mixed
Select All
Clear All
Room 101
Restrant
Entrance
Meeting 1
Group Error
Schedule Filter Sign Op. Controlled Op. Restricted
Off
On
Off
Off
RC Prohibition All On/Off On
Cool
Mode Temp. Timer
26.0 C
Filter
Auto
Operation
On
Off
(1) Select the objective you want to test run. Select the objective icon or list at the monitor screen. (Multiple selections is possible) Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
01-12
(1)
(2)
( * )
<Setting screen>
Operation Setting
Control Unit :
operation
On
On
Off
Off
Air Flow Direction Economy Anti Freeze Filter Sign Test Operation
Optional
Setting
Cancel
Cancel
Meeting Room
Mode Set Temp. Fan
Auto
24.0 C
Cool
Dry
Fan
Heat
Operation Controlled
10/11.2008.Mar. 02:20 PM
R/C Prohibition
All
Auto
High
Med
Low
Quiet
On/Off
On
Mode
Temp.
Timer
Filter
Status: On
OK
OK
(3) Switch to the <Details setting screen> by pressing "Optional Setting" on the setting screen.
<Details setting screen>
( * )
(3)
Operation Setting
10/11.2008.Mar. 02:20 PM
Status: On
SettingOptional
Air Flow Direction
Up
1
2
3
1
Down
2
3
Swing
4
4
Swing
Left Right
Cancel
Economy
On
Off
Test
5
Special State
Stand by (Defrost) Stand by (Oil Recovery) Test Operation
Anti Freeze
Operation
On
Off
Filter Sign
Reset
Start
OK
(4)
(5)
(4) Send (start) test run by pressing "Start" and then pressing "OK" on the details setting screen. Test run continues for 60 minutes. During sending, the slave screen shown below is displayed. When sending is completed, the sending slave screen and details setting screen are closed.
To interrupt test run, select the device being test run and execute an operation stop command.
(*) At the monitor screen, test run is reset by stopping operation
Transferring data. Please wait.
of the objective devices by pressing "OFF". (*) Or test operation is reset by stopping operation of the objective devices by pressing "Off" of Operation and then pressing "OK" on the setting screen.
01-13
1-3 TEST RUN CONTROL
1. When the test run signal is transmitted from standard wired, wireless remote controller, simple remote controller, transmitted network, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of the temperature condition.
(2) Frost prevention operation has priority over item(1). (3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ). (4) After 60 minutes passes, the test run stops. (5) Test running initialization is shown below.
Operating Mode
Fan speed Hi Hi
Room Temperature Indication 18 30
Vertical Air Direction Panel
Swing
*EXAMPLE
1
2
3
4
EXCEPT FOR THE DUCT MODEL DUCT TYPE
Cooling Heating Cooling Heating
Hi Hi
18 30
Position
4
1
OFF OFF
2
3
1
Position
4
1
2
3
4
COMPACT CASSETTE TYPE
CEILING TYPE
1
2
3
4
COMPACT WALL MOUNTED TYPE
01-14
1-4 Field Setting And Monitor Mode List for Outdoor unit
Push switch onoutdoor unit PCB
Monitor mode
[ F1 ]
Classification
Device and system
Operation of each part
Time guard 20 Accumulated current time Accumulated current time is displayed
Refrigerant cycle data 1
Refrigerant cycle data 2
ITEM CODE No.
00 Connected number of indoor unit The number of the communicating unit is displayed
Software version of outdoor unit
01
02 Software version of INV PCB
03 Software version of communication PCB
10 Rotational speed of outdoor unit fan motor The rotational speed of the outdoor unit fan motor is displayed
11 Rotational speed of INV compressor The rotational speed of the compressor is displayed
12 Current value of INV compressor Current value of INV compressor is displayed
14 Pulse of EEV1 Pulse of EEV1 is displayed
Pulse of EEV2 Pulse of EEV2 is displayed
15
21 INV compressor accumulated time
[ Cooling ]
22 INV compressor accumulated time
[ Heating ]
30 Information on Thermistor 1
( INV compressor discharge temperature )
32
Information on Thermistor 3
( Outdoor temperature )
33 Information on Thermistor 4
( Suction temperature )
34
Information on Thermistor 5
( Heat-exchanger temperature )
36
Information on Thermistor 7
( Liquid temperature 2 )
37
Information on Thermistor 8
( Sub-cool heat-exchanger inlet temperature )
38 Information on Thermistor 9
( Sub-cool heat-exchanger outlet temperature )
39 Information on Thermistor 10
( INV compressor temperature )
50
Information on pressure sensor 1
( High pressure sensor )
51
Information on pressure sensor 2
( Low pressure sensor )
Setting Mode
Information contents
Software version :
[ ] [ ] [ ] [ ] [ ] displays by five items
It skips when there is no suffix
[ rpm ]
[ rps ]
[ A ]
[ pls ]
[ pls ]
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the INV compressor [ 10 hour ] Accumulated time is displayed in the heating operation of the INV compressor [ 10 hour ]
The value of the Thermistor 1 is displayed
[°C ] or [°F ]
The value of the Thermistor 3 is displayed
[°C ] or [°F ]
The value of the Thermistor 4 is displayed
[°C ] or [°F ]
The value of the Thermistor 5 is displayed
[°C ] or [°F ]
The value of the Thermistor 7 is displayed
[°C ] or [°F ]
The value of the Thermistor 8 is displayed
[°C ] or [°F ]
The value of the Thermistor 9 is displayed
[°C ] or [°F ]
The value of the Thermistor 10 is displayed
[°C ] or [°F ]
The value of the pressure sensor 1 is displayed [ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed
[ MPa ] or [ psi ]
01-15
Push switch on outdoor unit PCB
Setting mode
[ F2 ]
Classification
ITEM CODE No.
Setting Mode
ITEM CODE No.
Install 00 Pipe length setting 00 40-65m
01 0-40m 02 65-90m 03 90-120m
Correction 10
Sequential start shift
Setting is forbidden
04 00 01 02
Setting is forbidden
Standard
03
Cooling capacity shift 00 Normal mode
11
01 Save energy mode 1 (+2°C) 02 High power mode 1 (-2°C)
03 High power mode 2 (-4°C) 04 High power mode 3 (-5°C)
Heating capacity shift
12
00 Normal mode 01 Save energy mode (-2°C) 02 High power mode 1 (+2°C) 03 High power mode 2 (+4°C)
13 Defrost setting shift 00 End temperature:Normal
01 End temperature:Higher
Change of
function 1
14 Pressure equalization time shift
before defrosting start
20 Switching between forced stop or 00 Forced stop
emergency stop
00 No time shift
01 Shift 1 ( 30 sec.) 02 Shift 2 ( 60 sec.) 03
Shift 3 ( 90 sec.)
04
Shift 3 ( 120 sec.)
01 Emergency stop
21 Operation mode selecting method 00 Priority given to the first command
01 Priority given to the external input of outdoor unit 02 Priority given to the master indoor unit
22
Snow falling protection fan mode
Setting is forbidden
23
Interval setting for snow falling protection fan mode
Setting is forbidden
24
High static pressure mode
Setting is forbidden
Oil recovery
25
Setting is forbidden
00 Normal operation 01 00 Standard 01 02 03 00 Standard 01 02
Standard
00 01
02 03
Oil recovery Abnormal
26
low pressure protection control
Setting is forbidden
27 Error code Notification
00
00 01
Standard
01
Enable Disable
28 Change of unit (Temperature) 00 Celsius(°C)
01 Fahrenheit ( F)
29 Change of unit (Pressure) 00 MPa
01 psi Change of function 2
30 Energy saving level setting 00 Level 1 (stop)
01 Level 2 (operated at 40% capacity)
02 Level 3 (operated at 60% capacity)
03 Level 4 (operated at 80% capacity)
04 Level 5 (operated at 100% capacity)
31
Heating Starting prosess
Setting is forbidden
Low noise 40 Capacity priority setting 00 Off (quiet priority) setting 1
(in low noise mode)
41 Low noise mode setting
00
Standard
01
01 On (capacity priority)
00 Off (Normal)
01 On (Low noise mode operation is always done)
42
Change of function 3
Change of function 4
Low noise mode operation level
60
Setting is forbidden
Back up operation
Setting is forbidden
70
Electricity meter No. setting 1
(Set the ones digit and tens digit of the No of the electricity meter connected to CN135.)
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the electricity meter connected to CN135.)
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of the electricity meter pulse setting connected to CN135.)
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135.)
*4
*4
*3 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective. Available setting number is "001" to "200" *4 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective. Available setting number is "0001" to "9999"
Setting is forbidden: Any of problems caused by changing these setting is not covered by the warranty.
Only for solution :
*3
Only when the refrigerant noise during Defrosting was pointed out. It is the case that the
00 Standard (47dB)
01
00 Standard
01
00~99 Setting number x00~x99
*3
( Refer to Design & Technical Manual for details.)
00~02 Setting number 0xx~2xx 00
( Refer to Design & Technical Manual for details.)
00~99 Setting number xx00~xx99 00
( Refer to Design & Technical Manual for details.)
00~99 Setting number 00xx~99xx 00
( Refer to Design & Technical Manual for details.)
compressor operating time in heating will be shorter.
01-16
Setting Function
Only for solution
Default
00
Push switch on outdoor unit PCB
Function mode
[ F3 ]
ITEM CODE No.
Forced operation 00 Cooling test run
01 Heating test run Forced thermostat-ON in Heating.
Install and maintenance 1
02 Test run stop Test run is stopped.
10 Signal amplifier automatic address Automatic address setting operates for signal amplifier.
11 Indoor unit automatic address
Setting Mode
Setting Function
Forced thermostat-ON in Cooling.
Automatic address setting operates for indoor unit of same refrigerant circuit.
12
Indoor unit connection check
Install and maintenance 2
Clear 30 Error history clear All the abnormal code histories are cleared.
Reset 40 Abnormal reset It was displayed when abnormality occurs, and abnormal
Specialtyfunction 91 Foreced Central control function release
21 Vacuuming mode Vacuuming mode operatesRefer to page 01-01 for the function.
32 Current time clear Accumulated current time becomes [ 0 ]
33 INV compressor accumulated time clear Accumulated time of the INV compressor becomes [ 0 ]
34 Constant Speed compressor accumulated
time clear
35 Field setting all clear Return to default the all set items.
36
Clear memorized information of "F3 - 12 " ( Indoor unit connection check )
*
Maximum memorized indoor unit number reset
41
90
Foreced Normal operation release Normal operation foreced release
The number of indoor units and the total capacity of indoor units of same refrigerant circuit.
Not in Use on J-Series
The information of the number of indoor units and the total capacity of indoor units are cleared.
code is reset.
This is a function that uses to clear abnormal display after the repair is completed.
Please operate the switch after power off or power on the outdoor unit. Maximum memorized indoor unit number is reset.
"E14.5:Indoor unit number shortage" error is cleared.
When the centralized control device failure, and the centralized control setting cannot be released, this function is used.
All the limitations set with the centralized control device are released.
Push switch on outdoor unit PCB
Error History Mode
[ F9 ]
Error history
ITEM CODE No.
00
01
02
03
04
05
06
07
08
09
Meaning of Error History Number
1 time ago (Newest)
2 times ago
3 times ago
4 times ago
5 times ago
6 times ago
7 times ago
8 times ago
9 times ago
10 times ago (Oldest)
Information contents
When the error occurred, the error code is memorized up to 10 on Main PCB.
If the memorized error code becomes over 10, the oldest one will be erased.
Refer to Chapter 4.TROUBLE SHOOTING
4-2-3 Error Code List of Outdoor unit
< Reset Error Item List By Abnormal Reset Setting >
*
Compressor Motor Loss of Synchronization Compressor 1 Temperature Abnormal Inverter Compressor Start Up Error Discharge Temperature 1 Abnormal Low Pressure Abnormal Current Sensor 1 Error Trip Detection Rush Current Limiting Resistor Temp Rise Protection Outdoor Unit FAN motor 1 Lock Error Outdoor Unit FAN motor 2 Lock Error
01-17
1-5 Field Setting / Function Setting for Indoor unit
23 Vertical airflow direction 00 Default
02 Right half
Correction
30
Cool air temperature trigger
00 Default (0°C)
Indoor unit field setting
setting by remote controller
Classification
Address
Filter 11 Filter indicator Interval 00 Default
Airflow 20 Ceiling airflow 00 Default
ITEM CODE No.
01 Indoor unit address 00~63 00~63 00 02 Refrigerant circuit address 00~99 00~99 00
13 Filter sign display 00 Enable
(Cassette type only) 01 High ceiling
24 Horizontal swing airflow direction 00 Default
26
Static Pressure setting
Setting Mode
- Slim Duct Only -
The Range of static pressure is different from one model to other.
31 Heat air temperature trigger 00 Default (0°C)
32
Temperature correction in Auto
Change of 40 Auto restart 00 Enable Function 1
43 Cool air prevention 00 Enable
46 External control 00 Start / Stop
47 Error report target 00 All
ITEM CODE No.
Longer
01 02 Shorter
01 Disable 02 Display only on central remote control
01 Raise
01 Left half
00
0 Pa
01
10 Pa
02
20 Pa
03
30 Pa
04
40 Pa
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
31
25 Pa
01 Temperature overshoot setting (+2 02 Temperature undershoot setting (-2
01 Temperature undershoot setting (-6 02 Temperature slightly undershoot setting (-4 03 Temperature overshoot setting (+4
00
Disable
01
Enable (Nonfunctional on J2 Series)
01 Disable
01 Disable (Ventilation mode)
01 Emergency stop
01 Display only for central remote control
Setting Function
Model name Range of static pressure AR XD 07L ATH AR XD 09 LATH AR XD12L ATH AR XD14L ATH AR XD18LAT H AR XD 24L ATH 0 to 50 Pa
0 to 90 Pa
°C)
°C)
°C)
°C)
°C)
Default
01-18
2. OUTDOOR UNIT OPERATION CONTROL
2. OUTDOOR UNIT
2-1 INPUT / OUTPUT LIST
Discharge pressure sensor <HIGH> Pressure sensor Measure range 0.0 to 5.0MPa Suction pressure sensor <LOW> Pressure sensor Measure range 0.0 to 1.7MPa Discharge temperature sensor <TH1> Themistor <Blue> Outdoor temperature sensor <TH3> Themistor < - > Suction temperature sensor <TH4> Themistor <Red>
I
N
U
Heat exchanger temperature sensor <TH5> Themistor <Pink> Liquid temperature sensor <TH7> Themistor <Green>
P
Sub-cool heat exchanger (inlet) sensor <TH8> Themistor <White> Sub-cool heat exchanger (outlet) sensor<TH9> Themistor <Brown>
T
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130 Operation current sensor Pressure switch
Rotary SW & DIP-SW & Push SW
Input / output or kind of detail Control range
Measure range 10 to 130 Measure range -25 to 58 Measure range -35 to 70 Measure range -35 to 70 Measure range -35 to 70 Measure range -35 to 70 Measure range -35 to 70
Current transformer Pressure switch
Address and function setting
Open 4.2MPa Short 3.2MPa
O U T P U T
Communication Input / Output
External Input / Output
LED display
Compressor Electronic expansion valve 1 (Main) EEV coil Operating voltage DC12V
Electronic expansion valve 2 (SC-Hex) EEV coil Operating voltage DC12V Fan motor 1 (Upper) DC Brushless motor Fan motor 2 (Lower) DC Brushless motor 4-way valve 4-way valve coil AC220-240V, 50/60Hz 6/5 W Solenoid valve Comp pressure equalizing valve AC220-240V, 50Hz, 6W Crank case heater For Inverter Compressor AC240V, 25W
Base heater Field supply AC220-240V, 35W
LON WORKS Inverter communication
External input 1 (CN131) (Low noise mode operation) External input 2 (CN132) (Cooling / Heating priority) External input 3 (CN133) (Outdoor unit operation peak control) External input 4 (CN134) (Emergency stop operation)
External output 1 (CN136) (Error display) External output 2 (CN137) (Operation display)
Single LED 101 Single LED 102 7 Segment LED
Magnetic relay
Indoor unit Outdoor unit
Dry contact input
ON (Error) / OFF (Normal) ON (Operation) / OFF (Stop)
Display the information on operation, error and setting with single LED and 7 segment LED.
Operation coil AC220-240V, 50Hz
Control output: DC 0/12-24V, Max.30mA Control output: DC 0/12-24V, Max.30mA
02-01
2-2 COMPRESSOR OPERATION
2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same refrigerant circuit is input, the compressor operates. When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity", is stopped. But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation Icing protection Failure (Refer to chapter 4, TROUBLE SHOOTING ) Oil recovery Under expansion valve initialization At protective operation
Emergency stop Defrost operation
Peak cut stop operation
the compressor
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of required refrigerant circulation in details.
Total capacity
Capacity of
compressor operation
Inverter Compressor
02-02
Cooling/Heating load
Loading...
+ 179 hidden pages