5-3-3 Saturation temperature and saturation pressure tables (R410A)........................
5-3-4 Temperature and pressure of refrigerant (Graph)...............................................
6. DISASSEMBLY PROCESS
05-02
05-02
05-18
05-19
05-19
05-20
05-21
05-22
1. TEST RUN
1. TEST RUN
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
Before execution
Location decision
Confirmation of Refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparation before execution
Execution 1/2
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Outdoor unit foundation work
Execution procedure and precautionsReason
Do not install the units in the place not recommended in the installation
manual.
Check the characteristics of the refrigerant used and grasp the
special features of the refrigerant. If refrigerant must be charged,
always charge the refrigerant specified for the product.
*Confirm the product design pressure. < R410A 4.20MPa >
Prepare the design for the system
Use new refrigerant piping of the thickness specified by the
1
D&T manual.
2
Since R410A dedicated tools are necessary, prepare them in
advance.
3
Absolutely avoid use of existing piping. If use of existing
piping is unavoidable, the piping must be cleaned.
Always use a level and keep the indoor unit level.
If the equipment is tilted toward the drain port, install it so that the tilt
is within 10mm. Excessive tilt will cause water leakage.
When performing piping work, observe the following items so that the
inside of the piping is clean and air tight.
1
Use pipe that is not dirty inside.
Confirm the design for the piping ( Diameter, Thickness )
2
3
When the pipe is left standing, protect it.
Confirm the angle of separation tube and header correctry.
4
Finish flaring exactly.
5
Confirm the width across flats dimension and shape of flare nuts.
6
Always blow nitrogen while brazing.
7
Perform flushing before connecting the equipment.
8
Always make the downward slope of the drain pipe 1/100 or
1
greater and make the horizontal length within 20m.
Use hard polyvinylchloride pipe as the drain pipe.
2
Support the drain pipe between 1.5 to 2.0m.
3
Use pipe of 1 rank up (VP30 or greater) as central piping.
4
Select the size of the heat insulating material according to the ambient
temperature and relative humidity of the refrigerant.
Use a heat insulating material having a heat conductivity of 0.043W/
(m.k) or less.
The performance may drop significantly
due to the protection controlling
Use of a refrigerant other than the
specified refrigerant will invite
equipment trouble
Secure the necessary pressure
resistance.
Prevention of water leakage
Foreign matter, water, etc. in the
piping will cause faulty cooling and
compressor trouble.
Incorrect pipe diameter will cause
faulty cooling
Incorrect angle of separation tube or
header will be cause poor cooling or
refrigerant noise problem
Refrigerant leakage will cause low
performance and abnormal stopping
Prevention of water leakage
Prevention of water leakage
Outdoor unit installation
Refrigerant piping connection work
Air tightness test
Vacuum drying
When making flare connections always use a torque wrench and
tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure
and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a
1
reverse flow check adaptor to a conventional vacuum pump and
use.
Pump down sufficiently.
2
Approximately 1 hour or longer after -0.10MPa reached.
Allow to stand for approximately 1 hour after stopping the vacuum
pump and confirm that the needle does not return.
Air purging using refrigerant is strictly prohibited.
3
Vaccuming mode
*
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vaccuming mode, the refrigerant address setting has to be finished.
Refrigerant leakage will cause low
performance and abnormal stopping.
Refrigerant leakage will cause low
performance and abnormal stopping.
Mixing in of vacuum pump oil by
reverse flow will cause equipment
trouble.
recommend the vacuuming mode
When the [vacuuming mode] is set, <Push switch setting, F3:21>
EEV of connected all indoor units opens.
So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units and
the outdoor unit, [vacuuming mode] is released.
01-01
Execution 2/2
Execution procedure and precautionsReason
Addition refrigerant charging
Gas leak test
Initial setting
Confirm the additional refrigerant amount with the installation
1
manual, etc.
Always take the R410A refrigerant from the cylinder liquid phase
2
and charge it using the gas phase.
(Do not lay a cylinder with siphon pipe on its side.)
3
Use an R410A dedicated gauge manifold and charging hose.
Charge refrigerant using the liquid pipe.
4
When the defined amount of refrigerant cannot charge using the
5
liquid pipe, charge refrigerant using the gas pipe while opearing
the cooling test run.
Charge refrigerant bit by bit with cautious operation of valve
for the liquid refrigerant back prevention.
Use an R410A dedicated leak tester to check for gas leaks.
1
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
2
Confirm the DIP SW setting
SET 1: Factory setting, SET 2 : All OFF, SET 3 : All OFF,
SET 4: Factory setting
Confirm the Terminal resister setting
3
SET 5-4 OFF: Disable, ON: Enable
[Note] Perform in the power OFF state.
If taken from the air phase, since the
composition of the refrigerant which is
charged will change, low performance
and abnormal stop will occur easily.
Prevent erroneous sealing in of
refrigerant.
A leak tester for other than R410A
cannot detect leaks.
Dual address setting No. is not
allowed in one network.
If the DIP SW setting is wrong, the sys tem may not work correctly
If the Terminal resister setting is wrong,
the system may detect transmission
error
Piping length setting
Address setting for Signal Amp
- When using signal Amps -
Address setting for Indoor unit
Set according to the length of the connection piping.
Set to "Standard (40 to 65m)" at the factory.
Set using the push button SW on the outdoor unit main PCB.
< Refer to the Page 01-16 Setting mode F2-00 >
Set the pipe length to be the nearest indoor unit from the outdoor unit
When the setting is not same as the
real piping length, the system may
not work correctly.
If the pipe length is set as the farthest
indoor unit, the nearest operating
indoor unit may be stopped the
operation by the icing up protection
as by over cooling.
[Note] Perform in the power ON state after all indoor units have stopped operation
When setting the address of Signal amplifier, please refer to the
installation manual of the signal amplifier.
The address setting can be set by automatically from 1 outdoor unit
on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Dual address setting No. is not
allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Set the refrigerant circuit address and indoor unit address.
Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch
PCB) or from a remote controller or from a push button SW on the
outdoor unit Main PCB < Automatic address setting,
Refer to the Page 01-07 Setting mode F3-11>
Dual address setting No. is not
allowed in one network.
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Indoor unit connection check
Test run & adjustment
Turnover & explanation of operation
Before starting the system, check on the number of indoor units and
the total capacity.
< Refer to the Page 01-08 Setting mode F3-12 >
Normal operation will not be possible
without performing the indoor unit
connection check.
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state
after all indoor units have stopped operation.
01-02
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
Power
source
Outdoor
unit
Check contentsProcedure
Circuit breaker capacity
Type of power source
wiring
Supply power source
Wiring on terminal blocks
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Judgement standard
Outdoor unit: 32A ( AJ*A36,45,54LALH )
Indoor unit: 20A
Leakage current: 30mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit: 6mm
Indoor unit: 2.5mm2 2 wires + Ground
Outdoor unit side: AC 230V (220-240V)
Indoor unit side: AC 230V (220-240V)
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Check whether or not the heat insulation material is installed without a gap.
DIP SW SET1, SET4 : Factory setting, SET2,SET3, SET5-1,2,3: ALL OFF
Terminal resistor setting SET5 - 4 OFF: Disable, ON: Enable
Check the resistance value for each network segment
Refer to the installation manual 7.7
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
2
2 wires + Ground 4mm
2
Check
Indoor
unit
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned
and will lead to trouble.
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote controller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
There shall be no scratches, deformation, tilting, etc.
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit address (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
2
01-03
1-2-2 Check Items After Power ON
[Note]
Cooling test run for each refrigerant circuit.
If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot
be detected.
Power ON
Outdoor unit Main
PCB push button
SW setting/check
Address
setting/
check
Indoor unit
connection check
Cooling
test run
Check contentsProcedure
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Judgement standard
Check
[Note] Turn on all indoor units power in the same refrigerant circuit address.
When the system operates with the indoor units remaining no power, it is cause of malfunction.
Function setting
Automatic address setting
Address read
Address record
Address hold check
Indoor unit connection check
Are the necessary functions set ?
< For the setting, Refer to the page 01-15 18 >
Addresses shall be assigned to all indoor units / Signal amps.
Check for unset or duplicated addresses.
< For the setting, Refer to the page 01-06, 07 >
All the indoor units and outdoor units of the same refrigerant circuit can be
checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool
after indoor/outdoor circuit breakers were turned OFF to ON.
Are the number of connecting indoor units correct ?
Is the total capacity of indoor units correct ?
< For the checking, Refer to the page 01-08 >
〜
[Note] Before connecting service tool, the address setting has to be completed.
Outdoor unit push button
SW operation
All the indoor units in the same refrigerant
state.
The outdoor units corresponding to the operation capacity of the indoor
units shall operate. < Test operation procedure, Refer to the page 01-09,10 >
circuit
shall enter the coolingtest run
All of the
indoor units
operation
(after 30 mins)
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
HPS: 2.7 MPa
LPS: 0.9 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/
abnormal vibration
There shall be no Error information on the 7-segment display on the Main PCB.
Between L - N AC230V (220-240V)
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound.
There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
01-04
Indoor unit
individual
operation
Check contentsProcedure
Judgement standard
<Indoor unit service tool + actual measurement>
Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
Check
These are representative figures of AJYA54LALH at the standard condition. ( Indoor : 27
°C, Outdoor : 35°C )
If conditions are different from those above mentioned, the figures will be changed slightly.
It depends on following conditions.
Outdoor unit capacity
Indoor and outdoor temperature
Indoor unit capacity
Pipe length
etc
Trouble shooting on Test run operation
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and
check the description of the Error code.
< Refer to the Trouble shooting in the Service manual.>
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not
Evaporator Icing up protection, High discharge temperature protection,etc.
< Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit
Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc.
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
< Refer to the regulation of installation in the Installation manual>
01-05
1-2-3 Automatic address setting for signal amplifiers When using signal amplifiers
SWITCH POSITION
Outdoor unit printed circuit board
When setting the address of the signal amplifier, please use the factory setting. (See the
installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB
to conÞ gure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment
LED Lamp
Push button switch
SELECT
SELECT
(When [F4] to [F9] are displayed, continue to press the "SELECT" button
until [ F3 ] is displayed)
ENTER
Automatic address setting for
signal ampliÞ ers
SELECT
ENTER
Press the “SELECT” button until "10" is displayed
Press the “ENTER” button for more than 3 seconds
End
*
ENTER
MODE/EXIT
* Setting is complete when the number of unit is displayed
01-06
1-2-4 Automatic address setting for Indoor units
SWITCH POSITION
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit Main PCB is set to “00”.If it is not
set to “00”, it means the address of that device is not set. (Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the
main power is turned on)
MODE/EXIT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment
LED Lamp
Push button switch
to configure settings according to the procedures below .
First 2 digits
SELECT
SELECT
ENTER
Last 2 digits
SELECT
ENTER
(When [F4] to [F9] are displayed,
continue to press the “SELECT”
button until [F3] is displayed.)
Automatic address setting
for indoor units
Press the “SELECT” button until
“11” is displayed.
Press the “ENTER” button for more
than 3 seconds.
It may take about 10 minutes for completing
the processing.
Found
End
Error
ENTER
The number of indoor units with normal settings will be displayed at the first 2 digits of
the 7 segment display. The number of indoor
units with error will be displayed at the last 2
digits.
NOTE) After the “ENTER” button is pressed, the
end processing will occur for about 30 seconds.
During this period, the 7 segment will blink.
01-07
1-2-5 Indoor unit connection check
SWITCH POSITION
Outdoor unit printed circuit board
Please perform the indoor unit connection check according to following procedures.
Turn on the power •
of indoor unit and
outdoor unit.
LED105
LED104
MODE/EXIT
Set to Function mode [F3].
SELECT
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105LED104
MODE
SELECT ENTER
/EXIT
SW107 SW108 SW109
7 Segment
LED Lamp
Push button switch
SELECT
continue to press the “SELECT”
button until [F3] is displayed.)
ENTER
(When [F4] to [F9] are displayed,
SELECT
Press the “SELECT” button until
“12” is displayed.
ENTER
Press the •
“ENTER”
button for
more than 3 seconds.
When indoor unit connection check
can not be performed
This will be displayed when the •
Indoor unit connection check
starts.
ENTER
(*1)
Confirm the number of connected indoor •
units and the volume ratio of the indoor
units connection.
SELECT
ENTER
When error occurs
(*1) The number of connected
indoor units
Ex.) When 8 units are connected
(*2)
(*2) Volume ratio of the indoor
units connection
Ex.) When the ratio is 120%
Exit indoor unit connection check •
mode.
01-08
Please refer to the following “Error code”
for details
ENTER
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
MODE/EXIT
When it finishes normally, nothing will be displayed on
7 segment display.
1-2-6 Test Run From Outdoor Main PCB
All the indoor units connected to the outdoor unit can be test-operated by push button setting.
SWITCH POSITION
POWER
MODE
ERROR
LED101
(GREEN)
LED102
(RED)
7 Segment
LED Lamp
LED105LED104
Outdoor unit printed circuit board
MODE
/EXIT
SW107SW108SW109
SELECT ENTER
Push button switch
TEST RUN SETTING
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
< Monitoring condition >
LED105LED104
MODE / EXIT
Note
There are the following 2 methods of resetting test operation.
Automatic reset when 60 minutes has elapsed.(1)
Reset when operation stop was performed.(2)
< Mode select condition >
[ Monitoring mode ][ Setting mode ]
SELECT
ENTER
LED105LED104LED105LED104LED105LED104LED105LED104
< Fuction select condition >
[ Cooling test run ]
LED105LED104
ENTER
SELECT
Press the ENTER button for at least 3 seconds.
[ Heating test run ]
L
ED
< Pursuance completion >
LED105LED104
SELECT
[ Function mode ]
SELECT
[ Error history mode ]
[ Central control setting
[ Test run stop ]
1
0
5
L
ED
1
0
4
SELECT
LED105LED104
SELECT
Forced reset ]
LED105LED104
ENTER
Press the "ENTER" button or Time out ( 5 seconds)
< Return to mode select condition >
LED105LED104
MODE / EXIT
< Return to monitoring condition >
LED105LED104
01-09
example, Normal indicate : [ Cooling mode ]
1-2-7 Test Run From Remote Controller
1. Standard wired remote controller
Stop the indoor unit. Push the button and
button simultaneously for more than two seconds.
The air conditioner will start to conduct a test run and " " will display on
the remote controller display.
However, the , setting button does not have function,
but all other buttons, displays, and protection functions will operate.
Perform the test operation for 60 minutes.
To stop test run, push the START / STOP button of the standard wired remote
controller.
For the operation method, refer to the operating manual and perform operation
check.
Check that there are no abnormal sounds or vibration sounds during test run
operation.
UTY - RNK
SET TEMP.
TIMER MODE
CLOCK ADJUST
SET BACK
TIMER DELETE TIMER SET
DAY
DAY OFF
START / STOP
FANMODE
2. Standard wireless remote controller
Press the TEST RUN button on the remote controller, while the air conditioner is running.
To end test run operation, press the remote controller START / STOP button.
When the air conditioner is being test run, the OPERATION
and TIMER lamps of indoor unit flash slowly at the same time.
3. Simple remote controller
Stop the indoor and outdoor units. Push the remote controller
simultaneously for more than three seconds. The air conditioner will start to conduct a test
run and " " will display on the temperature display.
However the setting button does not have function but all other buttons,
displays and protection functions will operate.
button and
button
START / STOP button
TEST RUN button
UTY - LNH
START
STOP
ECONOMY
FILTER RESET
SET
TEMP.
SLEEP
TIMER
TIMER MODE
CLOCK
TEST
ADJUST
RUN
UTY - RSK
FANMODE
SET
SET
SWING
RESET
To stop test running press the button of the simple remote controller.
For the operation method refer to the operating manual and perform operation check.
Check that there are no abnormal sounds or vibration sounds during test run operation.
01-10
SET
UTY-DCG
Monitor - All
On
Coll
℃
25.0
Setup Menu
Central Controller
Setting
05/31 03:59
05/31 03:59
Indoor unit
Special setting
Select
All
On
Off
Operation
Details
1
Monitor
Group
Setup
Menu
Help
2
Indoor unit Special Setting
Test Operation
Indoor Unit
Set Temp. Range
Test Operation
RCG_05
6)
05/31 03:59
Filter Sign
R.C. Prohibition
05/31 03:59
or
Group
Select
All
Identify
Unit
Clear
Unit
[ Select All (F2) ]: All of R.C.Group (Indoor units)
[ Identify Unit (F3) ] : Specific R.C.Group (Indoor unit)
(1) Select the objective you want to test run.
Select the objective icon or list at the monitor screen. (Multiple selections is possible)
Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
01-12
(1)
(2)
( * )
<Setting screen>
Operation Setting
Control Unit :
operation
On
On
Off
Off
Air Flow Direction
Economy
Anti Freeze
Filter Sign
Test Operation
Optional
Setting
Cancel
Cancel
Meeting Room
ModeSet Temp. Fan
Auto
24.0 C
Cool
Dry
Fan
Heat
Operation
Controlled
10/11.2008.Mar. 02:20 PM
R/C Prohibition
All
Auto
High
Med
Low
Quiet
On/Off
On
Mode
Temp.
Timer
Filter
Status: On
OK
OK
(3) Switch to the <Details setting screen> by pressing "Optional Setting" on the setting screen.
<Details setting screen>
( * )
(3)
Operation Setting
10/11.2008.Mar. 02:20 PM
Status: On
SettingOptional
Air Flow Direction
Up
1
2
3
1
Down
2
3
Swing
4
4
Swing
LeftRight
Cancel
Economy
On
Off
Test
5
Special State
Stand by (Defrost)
Stand by (Oil Recovery)
Test Operation
Anti Freeze
Operation
On
Off
Filter Sign
Reset
Start
OK
(4)
(5)
(4) Send (start) test run by pressing "Start" and then pressing "OK" on the details setting screen. Test run continues for 60 minutes.
During sending, the slave screen shown below is displayed. When sending is completed, the sending slave screen and details setting
screen are closed.
To interrupt test run, select the device being test run and execute an
operation stop command.
(*) At the monitor screen, test run is reset by stopping operation
Transferring data.Please wait.
of the objective devices by pressing "OFF".
(*) Or test operation is reset by stopping operation of the objective
devices by pressing "Off" of Operation and then pressing "OK"
on the setting screen.
01-13
1-3 TEST RUN CONTROL
1. When the test run signal is transmitted from standard wired, wireless remote controller,
simple remote controller, transmitted network, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of
the temperature condition.
(2) Frost prevention operation has priority over item(1).
(3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a
test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ).
(4) After 60 minutes passes, the test run stops.
(5) Test running initialization is shown below.
Operating Mode
Fan speedHiHi
Room Temperature Indication1830
Vertical Air Direction Panel
Swing
*EXAMPLE
1
2
3
4
EXCEPT FOR THE DUCT MODELDUCT TYPE
CoolingHeatingCoolingHeating
HiHi
1830
Position
4
1
OFFOFF
2
3
1
Position
4
1
2
3
4
COMPACT CASSETTE TYPE
CEILING TYPE
1
2
3
4
COMPACT WALL MOUNTED TYPE
01-14
1-4 Field Setting And Monitor Mode List for Outdoor unit
Push switch onoutdoor
unit PCB
Monitor mode
[ F1 ]
Classification
Device and
system
Operation of
each part
Time guard20Accumulated current timeAccumulated current time is displayed
Refrigerant
cycle data 1
Refrigerant
cycle data 2
ITEM
CODE No.
00Connected number of indoor unitThe number of the communicating unit is displayed
Software version of outdoor unit
01
02Software version of INV PCB
03Software version of communication PCB
10Rotational speed of outdoor unit fan motorThe rotational speed of the outdoor unit fan motor is displayed
11Rotational speed of INV compressorThe rotational speed of the compressor is displayed
12Current value of INV compressorCurrent value of INV compressor is displayed
14Pulse of EEV1Pulse of EEV1 is displayed
Pulse of EEV2Pulse of EEV2 is displayed
15
21INV compressor accumulated time
[ Cooling ]
22INV compressor accumulated time
[ Heating ]
30Information on Thermistor 1
( INV compressor discharge temperature )
32
Information on Thermistor 3
( Outdoor temperature )
33Information on Thermistor 4
( Suction temperature )
34
Information on Thermistor 5
( Heat-exchanger temperature )
36
Information on Thermistor 7
( Liquid temperature 2 )
37
Information on Thermistor 8
( Sub-cool heat-exchanger inlet temperature )
38Information on Thermistor 9
( Sub-cool heat-exchanger outlet temperature )
39Information on Thermistor 10
( INV compressor temperature )
50
Information on pressure sensor 1
( High pressure sensor )
51
Information on pressure sensor 2
( Low pressure sensor )
Setting Mode
Information contents
Software version :
[ ] [ ] [ ] [ ] [ ] displays by five items
It skips when there is no suffix
[ rpm ]
[ rps ]
[ A ]
[ pls ]
[ pls ]
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 10 hour ]
Accumulated time is displayed in the heating operation of the
INV compressor
[ 10 hour ]
The value of the Thermistor 1 is displayed
[°C ] or [°F ]
The value of the Thermistor 3 is displayed
[°C ] or [°F ]
The value of the Thermistor 4 is displayed
[°C ] or [°F ]
The value of the Thermistor 5 is displayed
[°C ] or [°F ]
The value of the Thermistor 7 is displayed
[°C ] or [°F ]
The value of the Thermistor 8 is displayed
[°C ] or [°F ]
The value of the Thermistor 9 is displayed
[°C ] or [°F ]
The value of the Thermistor 10 is displayed
[°C ] or [°F ]
The value of the pressure sensor 1 is displayed
[ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed
[ MPa ] or [ psi ]
01-15
Push switch
on outdoor unit PCB
Setting mode
[ F2 ]
Classification
ITEM
CODE No.
Setting Mode
ITEM
CODE No.
Install00Pipe length setting0040-65m
010-40m
0265-90m
0390-120m
Correction 10
Sequential start shift
Setting is forbidden
04
00
01
02
Setting is forbidden
Standard
03
Cooling capacity shift00Normal mode
11
01Save energy mode 1 (+2°C)
02High power mode 1 (-2°C)
03High power mode 2 (-4°C)
04High power mode 3 (-5°C)
Heating capacity shift
12
00Normal mode
01Save energy mode (-2°C)
02High power mode 1 (+2°C)
03High power mode 2 (+4°C)
13Defrost setting shift00End temperature:Normal
01End temperature:Higher
Change of
function 1
14Pressure equalization time shift
before defrosting start
20Switching between forced stop or00Forced stop
emergency stop
00No time shift
01Shift 1 ( 30 sec.)
02Shift 2 ( 60 sec.)
03
Shift 3 ( 90 sec.)
04
Shift 3 ( 120 sec.)
01Emergency stop
21Operation mode selecting method00Priority given to the first command
01Priority given to the external input of outdoor unit
02Priority given to the master indoor unit
22
Snow falling protection fan mode
Setting is forbidden
23
Interval setting for snow falling
protection fan mode
(Set the ones digit and tens digit of the No of
the electricity meter connected to CN135.)
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the
electricity meter connected to CN135.)
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135.)
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit
of the electricity meter pulse setting connected
to CN135.)
*4
*4
*3 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*4 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
Setting is forbidden: Any of problems caused by changing these setting is not covered by the warranty.
Only for solution :
*3
Only when the refrigerant noise during Defrosting was pointed out. It is the case that the
00Standard (47dB)
01
00Standard
01
00~99Setting number x00~x99
*3
( Refer to Design & Technical Manual for details.)
00~02Setting number 0xx~2xx00
( Refer to Design & Technical Manual for details.)
00~99Setting number xx00~xx9900
( Refer to Design & Technical Manual for details.)
00~99Setting number 00xx~99xx00
( Refer to Design & Technical Manual for details.)
compressor operating time in heating will be shorter.
01-16
Setting Function
Only for solution
Default
00
Push switch on
outdoor unit PCB
Function mode
[ F3 ]
ITEM
CODE No.
Forced operation00Cooling test run
01Heating test runForced thermostat-ON in Heating.
Install and
maintenance 1
02Test run stopTest run is stopped.
10Signal amplifier automatic addressAutomatic address setting operates for signal amplifier.
11Indoor unit automatic address
Setting Mode
Setting Function
Forced thermostat-ON in Cooling.
Automatic address setting operates for indoor unit of same
refrigerant circuit.
12
Indoor unit connection check
Install and
maintenance 2
Clear 30Error history clearAll the abnormal code histories are cleared.
Reset40Abnormal reset It was displayed when abnormality occurs, and abnormal
Specialtyfunction91Foreced Central control function release
21Vacuuming modeVacuuming mode operatesRefer to page 01-01 for the function.
32Current time clearAccumulated current time becomes [ 0 ]
33INV compressor accumulated time clearAccumulated time of the INV compressor becomes [ 0 ]
34Constant Speed compressor accumulated
time clear
35Field setting all clearReturn to default the all set items.
36
Clear memorized information of "F3 - 12 "
( Indoor unit connection check )
*
Maximum memorized indoor unit number reset
41
90
Foreced Normal operation releaseNormal operation foreced release
The number of indoor units and the total capacity of indoor units
of same refrigerant circuit.
Not in Use on J-Series
The information of the number of indoor units and the total
capacity of indoor units are cleared.
code is reset.
This is a function that uses to clear abnormal display after the
repair is completed.
Please operate the switch after power off or power on
the outdoor unit.
Maximum memorized indoor unit number is reset.
"E14.5:Indoor unit number shortage" error is cleared.
When the centralized control device failure, and the centralized
control setting cannot be released, this function is used.
All the limitations set with the centralized control device are
released.
Push switch on
outdoor unit PCB
Error History Mode
[ F9 ]
Error history
ITEM
CODE No.
00
01
02
03
04
05
06
07
08
09
Meaning of Error History Number
1 time ago (Newest)
2 times ago
3 times ago
4 times ago
5 times ago
6 times ago
7 times ago
8 times ago
9 times ago
10 times ago (Oldest)
Information contents
When the error occurred, the error code is memorized up to
10 on Main PCB.
If the memorized error code becomes over 10, the oldest one
will be erased.
Refer to Chapter 4.TROUBLE SHOOTING
4-2-3 Error Code List of Outdoor unit
< Reset Error Item List By Abnormal Reset Setting >
*
Compressor Motor Loss of Synchronization
Compressor 1 Temperature Abnormal
Inverter Compressor Start Up Error
Discharge Temperature 1 Abnormal
Low Pressure Abnormal
Current Sensor 1 Error
Trip Detection
Rush Current Limiting Resistor Temp Rise Protection
Outdoor Unit FAN motor 1 Lock Error
Outdoor Unit FAN motor 2 Lock Error
01-17
1-5 Field Setting / Function Setting for Indoor unit
23Vertical airflow direction00Default
02Right half
Correction
30
Cool air temperature trigger
00Default (0°C)
Indoor unit field setting
setting by
remote controller
Classification
Address
Filter11Filter indicator Interval00Default
Airflow20Ceiling airflow00Default
ITEM
CODE No.
01Indoor unit address 00~6300~6300
02Refrigerant circuit address00~99 00~9900
13Filter sign display00Enable
(Cassette type only)01High ceiling
24Horizontal swing airflow direction00Default
26
Static Pressure setting
Setting Mode
- Slim Duct Only -
The Range of static pressure is
different from one model to other.
31Heat air temperature trigger00Default (0°C)
32
Temperature correction in Auto
Change of40Auto restart00Enable
Function 1
43Cool air prevention00Enable
46External control00Start / Stop
47Error report target00All
ITEM
CODE No.
Longer
01
02Shorter
01Disable
02Display only on central remote control
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130
Operation current sensor
Pressure switch
Rotary SW & DIP-SW & Push SW
Input / output or kind of detailControl range
Measure range 10 to 130
Measure range -25 to 58
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Measure range -35 to 70
Current transformer
Pressure switch
Address and function setting
Open 4.2MPa Short 3.2MPa
O
U
T
P
U
T
Communication
Input / Output
External
Input / Output
LED display
Compressor
Electronic expansion valve 1 (Main)EEV coilOperating voltage DC12V
Electronic expansion valve 2 (SC-Hex)EEV coilOperating voltage DC12V
Fan motor 1 (Upper)DC Brushless motor
Fan motor 2 (Lower)DC Brushless motor
4-way valve 4-way valve coilAC220-240V, 50/60Hz 6/5 W
Solenoid valve Comp pressure equalizing valveAC220-240V, 50Hz, 6W
Crank case heater For Inverter CompressorAC240V, 25W
ON (Error) / OFF (Normal)
ON (Operation) / OFF (Stop)
Display the information on operation, error and setting with single LED and
7 segment LED.
Operation coil AC220-240V, 50Hz
Control output: DC 0/12-24V, Max.30mA
Control output: DC 0/12-24V, Max.30mA
02-01
2-2 COMPRESSOR OPERATION
2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same
refrigerant circuit is input, the compressor operates.
When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity",
is stopped.
But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation
Icing protection
Failure (Refer to chapter 4, TROUBLE SHOOTING )
Oil recovery
Under expansion valve initialization
At protective operation
Emergency stop
Defrost operation
Peak cut stop operation
the compressor
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to
cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of
required refrigerant circulation in details.
Total capacity
Capacity of
compressor operation
Inverter Compressor
02-02
Cooling/Heating load
Loading...
+ 179 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.