ERROR
CONTENTS
CAUSE
COUNTERMEASURE 
Outdoor 
thermistor error
1. Check if the connector of outdoor 
  temperature thermistor THH0 loosens
  or comes off. 
2. Check the resistance of outdoor 
  temperature thermistor THH0. If it's  
  abnormal, replace thermistor.
1. Connector contact is faulty.
2. Outdoor temperature 
  thermistor THH0 is faulty.
10
Suction 
thermistor error
11 Heat exchanger
inlet 
thermistor 1 
error
1. Check if the connector of heat 
  exchanger inlet thermistor THHI1  
  loosens or comes off.
2. Check the resistance of heat 
  exchanger inlet thermistor THHI1. If it's
  abnormal, replace thermistor.
1. Connector contact is faulty.
2. Heat exchanger inlet 
  thermistor THHI1 is faulty.
Heat exchanger 
inlet 
thermistor 2 
error
1. Connector contact is faulty.
2. Heat exchanger inlet 
  thermistor THHI2 is faulty.
Heat exchanger 
inlet 
thermistor 3 
error
1. Connector contact is faulty.
2. Heat exchanger inlet 
  thermistor THHI3 is faulty.
Heat exchanger 
outlet 
thermistor 1 
error
1. Error occurrence condition 
  Each thermistor condition, 
  which is short or open, 
  is detected.
2. Relevant operation
1) All Compressors are 
  stopped. 
 *For suction temperature 
  thermistor error, 
  compressors are not stopped.
2) Error is displayed on LED of 
  outdoor unit and output to 
  communication bus line. 
 *For suction temperature 
  thermistor error, error is only 
  displayed on LED of outdoor 
  unit. 
3. Clearance 
  Thermistor detection is 
  other than short or open. 
1. Connector contact is faulty.
2. Heat exchanger outlet  
  thermistor THHO1 is faulty.
1. Connector contact is faulty.
2. Heat exchanger outlet  
  thermistor THHO2 is faulty.
1. Connector contact is faulty.
2. Heat exchanger outlet  
  thermistor THHO3 is faulty.
1. Connector contact is faulty.
2. Suction temperature 
  thermistor THS is faulty.
12
13
14
15
16
17
Heat exchanger 
outlet 
thermistor 2 
error  
Heat exchanger 
outlet 
thermistor 3 
error
1. Check if the connector of heat 
  exchanger inlet thermistor THHI2  
  loosens or comes off.
2. Check the resistance of heat 
  exchanger inlet thermistor THHI2. If it's
  abnormal, replace thermistor.
2. Check the resistance of heat 
  exchanger inlet thermistor THHI3. If it's
  abnormal, replace thermistor.
1. Check if the connector of heat 
  exchanger thermistor THHI3  
  loosens or comes off.
1. Check if the connector of heat 
  exchanger outlet thermistor THHO1  
  loosens or comes off.
2. Check the resistance of heat 
  exchanger thermistor THHO1. If it's
  abnormal, replace thermistor.
1. Check if the connector of heat 
  exchanger outlet thermistor THHO2  
  loosens or comes off.
2. Check the resistance of heat 
  exchanger outlet thermistor THHO2. 
  If it's abnormal, replace thermistor.
1. Check if the connector of heat 
  exchanger outlet thermistor THHO3  
  loosens or comes off.
2. Check the resistance of heat 
  exchanger outlet thermistor THHO3. 
  If it's abnormal, replace thermistor.
1. Check if the connector of suction 
  temperature thermistor THS  
  loosens or comes off.
2. Check the resistance of suction 
  temperature thermistor THS. 
  If it's abnormal, replace thermistor.
ERROR 
 CODE
05-19