5-2-4 Outdoor Air Unit....................................................................................................
5-2-5 Vertical Air Handler...............................................................................................
6. DISASSEMBLY PROCESS
05-01
05-05
05-05
05-14
05-15
05-18
05-20
Page 5
1. TEST RUN
Page 6
Page 7
1. TEST RUN
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
Before execution
Execution zone decision
Confirmation of refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparations before execution
Execution
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Foundation work for products
Execution procedure and precautionsReason
Check the characteristics of the refrigerant used and grasp the
1
special features of the refrigerant. If refrigerant must be charged,
always charge the refrigerant specified for the product.
Confirm the product design pressure.
2
R410A 609psi (4.20MPa)
Use new refrigerant piping of the thickness specified by the
1
D&T manual.
Since R410A dedicated tools are necessary, prepare them
2
in advance.
Absolutely avoid use of existing piping. If use of existing
3
piping is unavoidable, the piping must be cleaned.
Always use a level and keep the indoor unit level.
If the equipment is tilted toward the drain port, install it so that the tilt is
within 10mm. Excessive tilt will cause water leakage.
When performing piping work, observe the following items so that the
inside of the piping is clean and air tight.
Use pipe that is not dirty inside.
1
When the pipe is left standing, protect it.
2
Finish flaring exactly.
3
Confirm the width across flats dimension and shape of flare nuts.
4
Always blow nitrogen while brazing.
5
Perform flushing before connecting the equipment.
6
Always make the downward slope of the drain pipe 1/100 or
1
greater and make the horizontal length within 66ft.(20m).
Use hard polyvinylchloride pipe as the drain pipe.
2
Support the drain pipe between
3
Use pipe of 1 rank up (VP30 or greater) as central piping.
4
Select the size of the heat insulating material according to the ambient
temperature and relative humidity of the refrigerant.
Use a heat insulating material having a heat conductivity of 0.043W/
.
(m
k) or less.
59-1/16 in(1.5m) to 6-3/4 in ( 2.0m).
Use of a refrigerant other than the
specified refrigerant will invite
equipment trouble.
Secure the necessary pressure
resistance.
Prevention of water leakage
Foreign matter, water, etc. in the
piping will cause faulty cooling and
compressor trouble.
Refrigerant leakage will cause low
performance and abnormal stopping.
Prevention of water leakage
Prevention of water leakage
Products installation work
*Refer to warning or caution in the attached
installation manual of each products
Refrigerant piping connection work
Air tightness test
Vacuum drying
When making flare connections always use a torque wrench and
tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure
and conduct a 24Hr air tightness test.
1
2
3
*
Refrigerant leakage will cause low
performance and abnormal stopping.
Refrigerant leakage will cause low
performance and abnormal stopping.
Install a vacuum pump with reverse flow check mechanism or a
reverse flow check adaptor to a conventional vacuum pump and
use.
Pump down sufficiently.
Approximately 1 hour or longer after
Allow to stand for approximately 1 hour after stopping the vacuum
pump and confirm that the needle does not return.
Air purging using refrigerant is strictly prohibited.
500 micron (-100.7kPa) reached.
Mixing in of vacuum pump oil by
reverse flow will cause equipment
trouble.
Prevents degradation of the oil by
completely removing water and air.
recommend the vacuuming
*
mode
Vacuuming mode
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vacuuming mode, the refrigerant address setting has to be finished.
When the [vacuuming mode] is set, <Push switch setting, F3:21>
EEV of connected all indoor units opens.
So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units, RB units
and outdoor unit, [vacuuming mode] is released.
01-01
Page 8
Execution
Addition refrigerant charging
Gas leak test
Pre-commisioning
"Before Power ON"
Pre-commisioning
"After Power ON"
Confirm the additional refrigerant amount with the installation
1
manual, etc.
Always take the R410A refrigerant from the cylinder liquid phase
2
and charge it using the gas phase.
(Do not lay a cylinder with siphon pipe on its side.)
3
Use an R410A dedicated gauge manifold and charging hose.
Use an R410A dedicated leak tester to check for gas leaks.
Power source installation inspection
1
Field setting and setting inspection
2
Transmission wire installation inspection
3
Piping installation inspection
4
Connect Service Tool
1
Power source inspection
2
Error indication inspection
3
Transmission wire connection inspection
4
Other Field setting with power ON state, and adjustment
If taken from the air phase, since the
composition of the refrigerant which is
charged will change, low performance
and abnormal stop will occur easily.
Prevent erroneous sealing in of
refrigerant.
A leak tester for other than R410A
cannot detect leaks.
Before starting the installed system,
the final inspection is necessary.
When you find out any incorrect install ation or wrong setting, revise it before
starting the system
When you see any abnormal things,
turn OFF the power supply first, and
revise it with power OFF state.
In case of "Auto Address setting"
Note :
Test run & adjustment
Handover & explanation of operation
Check operating condition by using service tool.
For the judgment of operating condition, refer to the operation check
sheet.
Perform the auto address setting of Signal amp. at first, and the next perform the auto address setting of indoor unit.
When you perform the autoaddress setting for RB unit, the indoor unit address setting
needs to be done at first.
When you see any abnormal things,
stop the system, and revise it with
power OFF state.
01-02
Page 9
1-2 Check Items Before Power ON
1-2-1 Power source Inspection sheet
Check ItemCheck contentsJudgement Present Status
Ref. circuit name: _________________
Power supply3 / 3W / (208-230V 10%) / 60Hz
Master (AJUA ___G) :_____(A)
For AJUA72G : 45A
For AJUA90G / 120G : 55A
Leakage current : 100mA, 0.1 sec or less
Check the breaker capacity vs. wire size
Example :
Slave-1(AJUA ___G) :_____(A)
Slave-2(AJUA ___G) :_____(A)
Yes / No
Master : ______ (AWG)
Slave-1: ______ (AWG)
Slave- 2: ______ (AWG)
Complied
Not complied
Power
Source
Outdoor
Unit
Circuit Breaker Size (A)
2
Power Line Wire Size (mm
)
Power line Wiring
Note: One Outdoor Unit must have
one individual Circuit Breaker
* Note: Regulation of wire size and circuit breaker differs from each locality, please refers in accordance with local rule
Check ItemCheck contentsJudgement Present Status
Ref. circuit name: _________________
Power
Source
Indoor
Unit &
RB Unit
Power supply
Circuit Breaker Size (A)
(Check, Leakage current vs.
number of IUs & RB units)
1
/ (208-230V 10%) / 60Hz
20A breaker for one circuit
Leakage current as follows:
No. of units vs. leakage current:
30mA for number of unit 44 units
100mA f or 45 numberr of units 128 units
(Units means Indoor unit + RB unit)
Note:
MCA for total connected units (IU + RB) less
Circuit num ber -1
Breaker capacity: _______ (A)
Nos. of Connected units: ______ (IU+RB)
Circuit num ber -2
Breaker capacity: ______ (A)
Nos. of connected units: _______ (IU+RB)
Circuit num ber -3
Breaker capacity: _______ (A)
Nos. of Connected units
than 15A for 20A breaker capacity
MCA means, minimum circuit ampere
Power line wire size
Power line wiring
1 2W
60Hz 230V
Circut breaker Circuit breaker
Earth lekage Over current
Check the breaker capacity vs. wire size
Example for one circuit
For (IU + RB units) 19 units
Complied
Not complied
: _______ (IU+RB)
________ (AWG)
* Note: Regulation of wire size and circuit breaker differs from each locality, please refers in accordance with local rule
01-03
Page 10
1-2-2 Outdoor unit field setting inspection sheet
Check ItemCheck contentsJudgement
No. of outdoor unit for one ref. circuit: ______, Ref. circuit name: _________________
AppearanceShall be no deformation
Serial No.Master:Slave -1:Slave -2 :
Outlook
Power source & transmission wiringConnection points & loosescrews check
Connection pipingIs it insulated properly without gap?
Step-1: Connect Service Tool PC to the VRF VR-II system.
Do scaning of refrigerant system which should be commissioned.
Step-2: Compare the number of installed units (OU, RB Group and IU) with the System List data obtained from the Service Tool.
Step-3: Operate all Indoor Units under Test Mode Cooling (Select Test mode either cool or heat based on ambient temperature.).
Step-3-1: During operation, check the RB unit SV status and IU thermistor value
Step-3-2: After 1-hour operation, check the Refrigerant System
Step-4: After 1-hour Test run operation (excluding special operation),
Step-4-1: Switching the operation mode of IU, in order of RB group number, from cool to heat.
- Check the RB unit SV status and IU thermistor value
Step-4-2: When all IUs run under heating, continue operation minimum 15min. And check the Refrigerant system
1-3-1 Power source check sheet
Check ItemCheck contentsJudgement Present Status
Ref. circuit name _______________________, Ref. address ________(00
Actual Power Supply (V)
Outdoor Unit
Between L1-L2 / L1-L3 / L2-L3
< 3N, 3Wire + ground, 60Hz >
AC (208 - 230V)
Incoming voltage per breaker
10%
Power
Source
Indoor Unit
&
RB Unit
Actual Power Supply (V)
< 1, 2Wire + ground, 60Hz >
AC (208 - 230V) 10%
Incoming voltage per breaker
1-3-2 Error indication check sheet 1/2
Check ContentsJudgementPresent Status
Ref. circuit name ________________________, Ref. address ________(00
Outdo or unit Check PCB- Lighting status
LE D1 01 (green li ght)
Judgment : mu st be ON
Note : LED102 (Red) must not be flash & must not be ON
7-SEG LED
Judgment : ‘Sn’ displayed
Indoor Unit
For Wall mounted, Universal, Celling & Small Cassette
Check IU operation LED & timer LED condition
Judgment : must be flashing alternately
For Large Cassette and Duct type IU
Check Wired RC (3- wire) display screen
Judgmen t : C lock dis pla y “ AM 12: 00” will ap pe a r
Check Wired RC (2-wire) display screen
Judgmen t : La n gu a ge selec tion sc ree n will a ppe a r
For each
refrigerant
system
Master
Slav e -1
Slav e -2
Indoor unit Check LED & RC display status
IU address _______ (RB a ddress ________ )
IU address _______ (RB a ddress ________ )
IU address _______ (RB a ddress ________ )
IU address _______ (RB a ddress ________ )
IU address _______ (RB address ________ )
IU address _______ (RB address ________ )
IU address _______ (RB address ________ )
IU address _______ (RB address ________ )
IU address _______ (RB a ddress ________ )
IU address _______ (RB address ________ )
IU address _______ (RB address ________ )
IU address _______ (RB address ________ )
99)
Master (V): R-S:_____ / S-T:____ / T-R:____
Slave -1 (V):R-S:_____ / S-T:____ / T-R:____
Slave -2 (V):R-S:_____ / S-T:____ / T-R:____
Breaker-1 (V):_______
Breaker-2 (V):_______
Breaker-3 (V):_______
_______
99)
LED101: Yes No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
7-S EG :
LED101: Yes No
7-S EG :
LED101: Yes No
7-S EG :
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
01-12
Page 19
1-3-2 Error indication check sheet 2/2
Check ContentsJudgementPresent Status
Ref. circuit name ________________________, Ref. address ________(00
RB unit & respectiv e IU address (Desig n Value)Check RB unit PCB-LED status
RB address _______ (IU address _____________)
LED1 (Green )
Judgment :
Note: LED2 (Red) of R B u n it must not be ON
For each
refrigerant
system
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
RB address _______ (IU address _____________)
1-3-3 Installed unit and their addresses check sheet
99)
mu st be ON
Yes / No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Check ContentsCheck itemsChecking methodJudgementPresent Status
Ref. circuit : Name _________________, Ref. address ________(select from 00 to 99)Design valueCheck status
Installed units
and
their addresses
check
Number of IU
IU address
Number of RB unit
RB unit address
Checked by
Service Tool
Number of units and their
address appeared in the
System List must be same
as the Actual Design value
Judgment:
(OK / Not OK)
Connected number of IU ______
Connected number of RB Gr. ___
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add
_____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
IU add _____ (RB a dd ____ )
OK
Not OK
OK
Not OK
01-13
Page 20
1-3-4 Transmission line connection check sheet
Note: The following check method by using test-run is necessary for checking of incorrect transmission wire connection.
Check Contents Check itemsChecking methodJudgementPresent Status
Ref. circuit : Name _________________, Ref. address ________(select from 00 to 99)
Judgment Point during
test - mode cooling :
Transmission line
connection
co nfirmation
check
Cooling status
Operate all Indoor
Units under Test-run
Cooling Mode by
using Commissioning
Function of Service
Tool
For In door Unit
- Thermist or v a lue
(TH21 - TH22)14.4 F 8
(Yes / No)
For RB Un it
-SV status
SVB1 & SVS mu st ON
(Yes / No)
Desi gn value
IU add _____ (RB add ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
IU add_____ (RB a dd ____)
Check sta tus
IURB
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Yes /NoYes /No
Check ContentsCheck itemsChecking methodJudgementPresent Status
Ref. circuit : Name _________________, Ref. address ________(select from 00 to 99)
Judgment Point after
switching IU mode from
cool to heat in order of
Transmission line
connection
co nfirmation
Heating status
Switching the operation of IU
from cool to hea t in order of RB
group number by using,
Control function of Service Tool
RB group number:
For Indoor Unit
- Thermist or v a lue
(TH24 > TH21)
(Yes / No)
IU add _____ (RB a dd ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
IU add _____ (RB add ____)
Desi gn value
Check status
IU
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
Ye s /No
01-14
Page 21
1-3-5 Operation check sheet
Check ContentsJudgementPresent Status
Refrigerant Circuit : Name _________________, Address ________(00
Degree of sub-cool at OU sub - cooler side should be,
9 F TSC 36 F(5 C Tsc 20 C) AND
Pulse value EEV3 should be,
EEV3 400P
Discharge refrigerant pressure should be,
Test-run operation
Cooling mode
363psi Pd 479psi(
2.5MPa Pd 3.3MPa)
Suction refrigerant pressure should be,
102psi Ps 174psi(
0.7MPa Ps 1.2MPa)
Discharge refrigerant temp. should be,
Td 212 F(100 C).And,
Discharge refrigerant superheat should be,
( Tshd >18 F(10 C)
Conducted by
Service Tool
IU refg. superheat should be,
(2 C Tshe 5 C).And,
(3.6 F Tshe 9 F)
RB group SV (SBS & SVB1) should be ON AND
Pulse value IU EEV should be, EEV 1000P
Ps between Master & Slave OUs should be,
( Ps 29psi(0.2Mpa))
Air temperature of each RB group IU should be,
Tair c ooling
14.4 F(8 C)
>
99)
Tsc
F( C)
EEV3 P
Pd Psi(MPa)
Ps Psi(MPa)
Td
Tshd
Tshe
SBS & SVB1 ON
F( C)
F( C)
F( C)
IU EEV P
Ps Psi(MPa)
Tair c ooling
F( C)
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
No water fall from IU
No abnormal noise from IU
Reference mark of Service tool
Tsc = Saturated liquid temperature of HPS - TH5
Tshd = TH1- Saturated liquid temperature of HPS
Tshe = TH24 - TH22
Tair c ooling = TH21 - Outlet Air temperature
Check ContentsJudgementPresent Status
Refrigerant Circuit : Name _________________, Address ________(00
Discharge refrigerant pressure should be,
363psi Pd 479psi (2.5MPa Pd 3.3MPa)
Suction refrigerant pressure should be,
Test-run operation
Heating mode
44psi Ps 174psi (0.3MPa Ps 1.2MPa)
Discharge refrigerant temperature should be,
Td 212 F (100 C) AND
Discharge refrigerant superheat should be,
Tshd > 18 F(10 C)
7.2 F 12.6 F
Conducted by
Service Tool
Degree of sub
(4
cool (at IU side) should be,
Tsc 7 ) AND
RB group SV (SBD1 & SVB2) should be ON
Refrigerant superheat (at OU side) should be,
3.6 F Tshe1& Tshe2 9 F(2 C Tshe1& Tshe2 5 C)
Td = TH1
99)
Tsc
Ye s / No
Pd = HPS
Ps = LPS
Pd Psi(MPa)
Ps Psi(MPa)
Td
Tshd
Tsc
SVD1 & SVB2 ON
Tshe
F( C)
F( C)
F( C)
F( C)
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Reference mark of Service tool
Tsc = Saturated liquid temperature of HPS - TH22
Tshd = TH1- Saturated liquid temperature of HPS
Tair heating = TH21 - Outlet Air temperature
Pd between Master & Slave OUs should be,
Ps 29psi (0.2MPa))
T
at each OU connected in series should be,
OUHE
TOUHE>9 F(5 C)
Air temperature of each RB group IU should be,
Tair heating > 27 F (15 C)
Tshe1 = TH7 - Saturated vapor temperature of LPS
Tshe2 = TH8 - Saturated vapor temperature of LPS
01-15
Ps Psi(MPa)
TOUHE
Tair heating
F( C)
F( C)
T = TH4 - TH9
OUHE 1
T = TH4 - TH10
OUHE 2
Yes / No
Yes / No
Page 22
1-4 Test Run Operation
1-4-1 Test Run From Outdoor unit PC Board
All the indoor units connected to the outdoor unit can be test-operated by push button setting. (Only for master unit)
SWITCH POSITION
POWER
MODE
ERROR
LED101
(GREEN)
LED102
(RED)
7 Segment
LED Lamp
LED105LED104
MODE
/EXIT
SELECT ENTER
Push button switch
Outdoor unit printed circuit board
SW107SW108SW109
TEST RUN SETTING
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
(5) Hold down the ENTER button ( SW109 ) for at least 3 seconds.
< Pursuance completion >
LED105LED104
(6) Press the ENTER button ( SW109 ) or Time out ( 5 seconds)
< Return to mode select condition >
LED105LED104
(7) Press the MODE / EXIT button
[ Heating test run ]
LED105LED104
< Return to monitoring condition >
LED105LED104
[ Test run stop ]
LED105LED104
example,
Normal indicate : [ Cooling mode ]
[ Central control setting
Forced reset ]
LED105LED104
01-16
Page 23
1-4-2 Test Run From Remote Controller
1. Standard wired remote controller
Stop the indoor unit. Push the button and
button simultaneously for more than two seconds.
The air conditioner will start to conduct a test run and " " will display on
the remote controller display.
However, the , setting button does not have function,
but all other buttons, displays, and protection functions will operate.
Perform the test operation for 60 minutes.
To stop test run, push the START / STOP button of the standard wired remote
controller.
For the operation method, refer to the operating manual and perform operation
check.
Check that there are no abnormal sounds or vibration sounds during test run
operation.
UTY - RNK
SET TEMP.
TIMER MODE DAY
SET BACK
DAY OFF
CLOCK ADJUST
TIMER DELETE TIMER SET
START / STOP
FANMO DE
2. Standard wireless remote controller
Short two metal contacts under the battery compartment lid, while the air conditioner is running.
To stop test run operation, push button of the wireless
remote controller.
When the air conditioner is being test run, the OPERATION
and TIMER lamps of indoor unit flash slowly at the same time.
3. Simple remote controller
Stop the indoor and outdoor units. Push the remote controller
simultaneously for more than three seconds. The air conditioner will start to conduct a test
run and " " will display on the temperature display.
However the setting button does not have function but all other buttons,
displays and protection functions will operate.
button and
button
START/STOP button
Test run button
UTY - LNH
ON
OFF
ECONOMY
FILTER RESET
SET
TEMP.
SLEEP
TIMER
TIMER MODE
CLOCK
TEST
ADJUST
RUN
UTY - RSK
FANMODE
SET
SET
SWING
RESET
To stop test running press the button of the simple remote controller.
For the operation method refer to the operating manual and perform operation check.
Check that there are no abnormal sounds or vibration sounds during test run operation.
01-17
SET
Page 24
4. Touch panel controller
(1) Select the objective you want to test run.
Select the objective icon or list at the monitor screen. (Multiple selections is possible)
Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
(3) Switch to the <Detail setting screen > by pressing "Optional setting" on the setting screen,
(4) Press "Start" button and OK on the details setting screen.
Test run continues for 60 minutes.
To interrupt test run, select the device being the test run and excute an operation stop.
At the monitor screen, test run can cancel by selecting objective device and press OFF.
UTY - DTG
<Setting screen>
Operation Setting
Control Unit :
operation
On
On
Off
Off
Air Flow Direction
Economy
Anti Freeze
Filter Sign
Test Operation
Optional
Setting
Cancel
Cancel
Meeting Room
ModeSet Temp. Fan
Auto
24.0 C
Cool
Dry
Fan
Heat
Operation
Controlled
10/11.2008.Mar. 02:20 PM
R/C Prohibition
All
Auto
High
Med
Low
Quiet
On/Off
On
Mode
Temp.
Timer
Filter
Status: On
OK
OK
<Detail Setting screen>
5. Central remote controller
(1) Press " " button.
(2) Press "Set up Menue" and input password.
(3) Select "Indoor unit special setting" by presing or button.
(4) Select "Test operation by presing" or button
(5) Press the "Select ALL button" or "ldentify unit" button
[ Select All ]: All of R.C.Group (Indoor units)
[ Identify Unit ] : Specific R.C.Group (Indoor unit)
(6) Press the " Start " button
The test run continues for 60 minutes.
To interrupt test run before it is complet, return to the "Monitor Mode Screen",
and press ON/ OFF.
Indoor unit Special Setting
Test Operation
Indoor Unit
Set Temp. Range
05/31 03:59
Filter Sign
R.C. Prohibition
Test Operation
RCG_05
Operation Setting
SettingOptional
Air Flow Direction
Up
1
2
Swing
LeftRight
1
2
Swing
Cancel
05/31 03:59
3
Down
3
4
5
4
Group
Select
All
Identify
Unit
Clear
Unit
10/11.2008.Mar. 02:20 PM
Economy
Test
Special State
Anti Freeze
On
Off
Stand by (Defrost)
Stand by (Oil Recovery)
Test Operation
On
Off
Operation
UTY-DCG
Status: On
Filter Sign
Reset
Start
OK
01-18
Page 25
6. 2-wire type wired remote controller
(1) Press "Menu" on the monitor screen. the < Main Menu screen > is displayed.
(2) Press "Next Page" and press "Maintenance"
(3) Press "Next Page" and press "Test Run". the <Test run screen > is displayed.
(4) Press "OK"
The test run continues for 60 minutes.
To interrupt test run before it is complet, return to the "Monitor Mode Screen",
and press ON/ OFF.
< Monitor Mode Screen >
< Main Manu Screen >
UTY - RNR
< Test Run Screen >
< Maintenance Screen >
01-19
Page 26
1-5 TEST RUN CONTROL
1. When the test run signal is transmitted from standard wired, wireless remote controller,
simple remote controller, transmitted netwwork, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of
the temperature condition.
(2) Frost prevention operation has priority over item(1).
(3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a
test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ).
(4) After 60 minutes passes, the test run stops.
(5) Test running initialization is shown below.
* The temperature controlling on the test run operates regardless of setting temperature.
Operating Mode
Fan speedHiHiHiHi
Vertical Air Direction Panel
Swing
*EXAMPLE
1
2
3
4
EXCEPT FOR THE DUCT MODELDUCT TYPE
CoolingHeatingCoolingHeating
1
Position
4
1
2
3
Position
4
1
OFFOFF
2
3
4
COMPACT CASSETTE TYPE
CEILING TYPE
1
2
3
4
COMPACT WALL MOUNTED TYPE
01-20
Page 27
1-6 Field Setting And Monitor Mode List for Outdoor unit
Push switch on
outdoor unit PCB
Monitoring mode
[ F1 ]
Classification
Device and
system
Operation of
each part
Time guard20Accumulated current time
Refrigerant
cycle data 1
Refrigerant
cycle data 2
Refrigerant
cycle data 3
ITEM
CODE No.
Connected number of indoor unit
00
Software version of outdoor unit
01
02Software version of INV PCB
03Software version of communication PCB
10Rotational speed of outdoor unit fan motor
11Rotational speed of INV compressor
12Current value of INV compressorCurrent value of INV compressor is displayed
14Pulse of EEV1Pulse of EEV1 is displayed
15Pulse of EEV2Pulse of EEV2 is displayed
16Pulse of EEV3Pulse of EEV3 is displayed
21INV compressor accumulated time [ Cooling ]
INV compressor accumulated time [ Heating ]
22
30Information on Thermistor 1
( Discharge temperature sensor 1)
31Information on Thermistor 2
( Outdoor temperature sensor )
Information on Thermistor 3
32
( Suction temperature sensor )
Information on Thermistor 4
33
( Liquid temperature sensor 1)
34Information on Thermistor 5
(Liquid temperature sensor 2)
35Information on Thermistor 6
( Sub-cool H-Ex (outlet) sensor )
36Information on Thermistor 7
(Heat exchanger 1 gas sensor1)
37Information on Thermistor 8
(Heat exchanger 2 gas sensor2)
38Information on Thermistor 9
(Heat exchanger 1 liquid sensor)
39Information on Thermistor 10
(Heat exchanger 2 liquid sensor)
40Information on Thermistor 11
(Compressor temperature sensor)
50Information on pressure sensor 1
( High pressure sensor )
51Information on pressure sensor 2
( Low pressure sensor )
Setting Mode
Information contents
The number of the communicating unit is displayed
Software version :
[ ] [ ] [ ] [ ] [ ] displays by five items
It skips when there is no suffix
The rotational speed of the outdoor unit fan motor is displayed
[ 0 ~ 999 ] rpm
The rotational speed of the compressor is displayed
[ 0 ~ 999 ] rps
[ 0.00 ~99.99 ] A
[ 0 ~ 9999 ] pls
[ 0 ~ 9999 ] pls
[ 0 ~ 9999 ] pls
Accumulated current time is displayed
[ 0 ~ 9999 ]
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 0 ~ 9999 ]
Accumulated time is displayed in the heating operation of the
INV compressor
[ 0 ~ 9999 ]
The value of the Thermistor 1 is displayed
[ -99.9 ~ 999.9 ]
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 2 is displayed
[ -99.9 ~ 999.9 ] °C or °F
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 3 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 4 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 5 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 6 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 7 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 8 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 9 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 10 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the Thermistor 11 is displayed
[ -99.9 ~ 999.9 ] °C or °F
The value of the pressure sensor 1 is displayed
If unit is [MPa], it is displayed as [ 0.00 ~ 9.99 ]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
The value of the pressure sensor 2 is displayed
If unit is [MPa], it is displayed as [0.00 ~ 9.99]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
10hour
10hour
10hour
°C or °F
01-21
Page 28
Push switch on
outdoor unit PCB
Setting mode
[ F2 ]
Install
Correction
Change of
function 1
Change of
function 2
ITEM
CODE No.
Pipe length setting
00
10
Sequential start shift
11
Cooling capacity shift
Heating capacity shift
12
13,14,15 Forbidden
20Switching between batch stop or
emergency stop
22
Snow falling protection fan mode
23
Interval setting for snow falling
protection fan mode
24
High static pressure mode
25,26,27 Forbidden
Change of unit Temperature
28
Change of unit Pressure
29
30Energy saving level setting
32,33 Forbidden
Presence of heater selection
35
control using outdoor temperature *1
Outdoor temperature zone
36
boundary temperature A*1
37Outdoor temperature zone
boundary temperature B*1
Setting Mode
ITEM
CODE No.
131-213ft.(40-65m)
00
010-131ft.(0-40m)
02
213-295ft.(65-90m)
295-394ft.(90-120m)
03
394-492ft.(120-150m)
04
00
Normal
01
21sec. Delay
42sec. Delay
02
63sec. Delay
03
Normal mode
00
Save energy mode +4
01
High power mode 1 -4
02
High power mode 2 -7
03
Forbidden
04
00
Normal mode
01
Save energy mode -4
02
High power mode 1 +4
High power mode 2 +7
03
00
01
00
Batch stop
Emergency stop
01
Valid
00
01
Invalid
Standard (30min)
00
01
Short 1 (5min)
02
Short 2 (10min)
03
Short 3 (20min)
00
Standard
High static pressure 1 (equivalent to 0.12 in.WG /30Pa)
01
High static pressure 2 (equivalent to 0.32 in.WG /80Pa)
(Set the ones digit and tens digit of the No
of the electricity meter connected to CN135.)
71Electricity meter No. setting 2
(Set the hundreds digit of the No. of the
electricity meter connected to CN135.)
72Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135.)
73Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit
of the electricity meter pulse setting connected
to CN135.)
ITEM
CODE No.
00Off (quiet priority)
On (capacity priority)
01
Off (Normal)
On (Low noise mode operation is always done)
01
Level 1 (55dB)
00
Level 2 (50dB)
01
00*2
On
Off
01*3
00
On
Off
01
Setting FunctionDefaultClassification
00~99*4Setting number x00~x99
( Refer to Design & Technical Manual for details.)
00~02*4Setting number 0xx~2xx
( Refer to Design & Technical Manual for details.)
00~99*5Setting number xx00~xx99
( Refer to Design & Technical Manual for details.)
00~99*5Setting number 00xx~99xx
( Refer to Design & Technical Manual for details.)
*1 : Do not set this for outdoor units with Slave setting.
*2 : If one of compressor fails, backup operation will be performed by the remaining compressors.( For starting the system SET4-2 switching is required)
*3 : If one of compressor fails, all units will be abnormal stop.
*4 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*5 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
00
00
00
00
01-23
Page 30
Push switch on
outdoor unit PCB
Function mode
[ F3 ]
Classification
Forced
operation
Install and
maintenance 1
Install and
maintenance 2
ClearError history clear
ITEM
CODE No.
00
01
02
03,04
10
11
22
21
30
31
32
Setting ModeSetting Function
Cooling test run
Heating test runForced thermostat-ON in Heating
Test run stopTest run is stopped
Forbidden
Signal amplifier automatic address
Indoor unit automatic address
RB unit automatic address
Vacuuming mode
Forbidden
Current time clearAccumulated current time becomes [ 0 ]
Forced thermostat-ON in Cooling
Automatic address setting operates for signal amplifier
Automatic address setting operates for indoor unit of same
refrigerant circuit
Automatic address setting operates for RB unit of same
refrigerant circuit
Vacuuming mode operates
Refer to page 01-01 for the function
All the abnormal code histories are cleared
Push switch on
outdoor unit PCB
Error history mode
[ F9 ]
INV compressor accumulated time clear
33
Field setting all clearReturn to default the all set items
35
AbnormalAbnormal reset
Specialty
function
Error history
40
91
ITEM
CODE No.
00
01
02
03
04
05
06
07
08
09
*
Forced Central control function forced release When the centralized control device failure, and the centralized
Meaning of Error History Number
1 time ago (Newest)When the error occurred, the error code is memorized up to
2 times ago
3 times ago
4 times ago
5 times ago
6 times ago
7 times ago
8 times ago
9 times ago
10 times ago (Oldest)
Accumulated time of the INV compressor becomes [ 0 ]
It was displayed when abnormality occurs, and abnormal
code is reset
This is a function that uses to clear abnormal display
after the repair is completed
Please operate the switch after power off or
power on the outdoor unit
control setting cannot be released, this function is used
All the limitations set with the centralized control device are
released
Information contentsClassification
10 on Main PCB.
If the memorized error code becomes over 10, the oldest one
will be erased.
Refer to Chapter TROUBLE SHOOTING
Error Code List of Outdoor unit
01-24
<< Error code which manual error release will be required >>
A5.1 Low pressure abnormal
84.1 Current sensor 1 error
93.1 Inverter compressor start up error
94.1 Trip detection
A1.1 Discharge temperature 1 abnormal
A3.1 Compressor 1 temperature abnormal
97.1 Outdoor unit fan motor lock error
97.5 Fan motor temperature abnormal
97.9 Fan motor driver abnormal
68.2 Rush current limiting resister temp rise protection
95.5 Compressor motor loss of synchronization
A6.3 Outdoor heat exchanger 1 gas temperature abnormal
A6.4 Outdoor heat exchanger 2 gas temperature abnormal
Page 31
1-7 Field Setting / Function Setting for Indoor unit
Indoor unitfield setting
setting by
remote controller
The Range of static pressure is
different from one model to other.
Static Pressure setting *2*3
- Duct (middle pressure) type -
The Range of static pressure is
different from one model to other.
Static Pressure setting *4*5
- Duct (high pressure) type -
The Range of static pressure is
different from one model to other.
*1: Please refer to FAN PERFORMANCE CURVE within Design and Technical manual for the features of each setting.
*2: If the Setting Number in ARUM30TLAV is configured to “12 to 14”, the operation is the same as that in “11 (SP mode 11)”.
*3: If the Setting Number in ARUM36TLAV is configured to “10 to 14”, the operation is the same as that in “09 (SP mode 09)”.
*4: If the Setting Number in ARUH96TLAV is configured to “30”, the operation is the same as that in “29 (SP mode 29)”.
*5: ARUH72TLAV : 04 (SP mode 04) - 27 (SP mode 27) and 31 (Normal SP)
ARUH96TLAV , ARUH72TLAV1 : 05 (SP mode 05) - 30 (SP mode 30) and 31 (Normal SP)
ITEM
CODE No.
0001Default
Longer
02Shorter
01Disable
02Display only on central remote control
00Default
01High ceiling
Indoor unit field setting
setting by
remote controller
Correction
Change of
function 1
Change of
function 2
ITEM
CODE No.
30
31
40
43
46
47
49
60
61
62
Setting Mode
Heat air temperature trigger00
Auto restart *100Enable
Cool air prevention00Super low
External control00
Error report target00
FAN Setting when cooling thermostat OFF *2
Switching functions for external
inputs and external outputs
terminals
Control switching of external
heaters
(Except Compact wall mounted
and Wall mounted )
Operating temperature switching of
external heaters
(Except Compact wall mounted
and Wall mounted )
ITEM
CODE No.
00Cool air temperature trigger
01
02
01
02
03
Default 0
Temperature overshoot setting +4°F(+2°C)
Temperature undershoot setting -4°F(-2°C)
Default 0°F(0°C)
Temperature undershoot setting -11°F(-6°C)
Temperature slightly unbdershoot setting -7°F(-4°C)
Temperature overshoot setting +7°F(+4°C)
Setting FunctionDefaultClassification
°F(0°C)
01Disable
01
Follow the setting on the remote controller
Start / Stop
01Emergency stop
02Forced stop (Start/Stop by RC is restricted)
All
01Display only for central remote control
00
Follow the setting on the remote controller
Forced stop
01
Mode 0
00
Mode 1
01
Mode 2
02
Mode 3
03
04
Mode 4
05
Mode 5
06
Mode 6
Mode 7
07
08
Mode 8
Auxiliary heater control 1
00
Auxiliary heater control 2
01
Heat pump prohibition control
02
03
Heater selection control using outdoor temperature 1
Heater selection control using outdoor temperature 2
04
Setting 0
00
01
Setting 1
02
Setting 2
03
Setting 3
04
Setting 4
Setting 5
05
*1: Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Fan Setting when cooling thermostat OFF, Connection of the wired remote controller (2-wire type or 3-wire type) and switching its thermistor are necessary.
01-26
Page 33
1-8 Field Setting / Function Setting for Outdoor air unit
Indoor unit field setting
setting by
remote controller
ITEM
CODE No.
AddressIndoor unit address 00~6300~63
00
Setting Mode
ITEM
CODE No.
02Refrigerant circuit address00~9900~99
Filter11Filter indicator Interval
13Filter sign display
Airflow
26
Static Pressure setting
- Outdoor air unit Only -
The Range of static pressure is
different from one model to other.
Change of
function 1
Change of
function 2
Model name
AAUA48TLAV
AAUA72TLAV
AAUA96TLAV
40Auto restart *100Enable
43Cool air prevention00Super low
46External control00Start / Stop
47
60,61,62
63
65Threshold temperature setting
Range of static
pressure
SP mode 05 to 19
(0.2 to 0.76 in.WG)
SP mode 05 to 20
(0.2 to 0.80 in.WG)
SP mode 05 to 22
(0.2 to 0.88 in.WG)
Error report target
Forbidden
Humidifier control *2
for cool / heat switch over*3
Normal static
pressure
0.74 in.WG
(185 Pa)
0.80 in.WG
(200 Pa)
0.80 in.WG
(200 Pa)
00Default
Longer
01
Shorter
02
00Enable
Disable
01
02Display only on central remote control
SP mode 05
05
SP mode 06 [ 0.24 in.WG ( 60 Pa) ]
06
SP mode 07 [ 0.28 in.WG ( 70 Pa) ]
07
SP mode 08 [ 0.32 in.WG ( 80 Pa) ]
08
SP mode 09 [ 0.36 in.WG ( 90 Pa) ]
09
SP mode 10 [ 0.40 in.WG ( 100 Pa) ]
10
SP mode 11 [ 0.44 in.WG ( 110 Pa) ]
11
SP mode 12 [ 0.48 in.WG ( 120 Pa) ]
12
SP mode 13 [ 0.52 in.WG ( 130 Pa) ]
13
SP mode 14 [ 0.56 in.WG ( 140 Pa) ]
14
SP mode 15 [ 0.60 in.WG ( 150 Pa) ]
15
SP mode 16 [ 0.64 in.WG ( 160 Pa) ]
16
SP mode 17 [ 0.68 in.WG ( 170 Pa) ]
17
SP mode 18 [ 0.72 in.WG ( 180 Pa) ]
18
SP mode 19 [ 0.76 in.WG ( 190 Pa) ]
19
SP mode 20 [ 0.80 in.WG ( 200 Pa) ]
20
SP mode 21 [ 0.84 in.WG ( 210 Pa) ]
21
SP mode 22 [ 0.88 in.WG ( 220 Pa) ]
22
Normal SP
31
01Disable
01Follow the setting on the remote controller
01Emergency stop
02Forced stop (Start/Stop by RC is restricted)
All
00
01Display only for central remote control
00
01
mode 00
00
01
mode 01
mode 02
02
mode 0 +
00
mode 1 +
01
02
mode 2 +
mode 3 +
03
mode 4 +
04
mode 5 +
05
mode 5 +
06
Setting FunctionDefaultClassification
[ 0.20 in.WG ( 50 Pa) ]
10°F (+5
-
4°F (+2
-
6°F (+3
-
8°F (+4
-
10°F (+5
-
12°F (+6
-
14°F (+7
-
°C)
°C)
°C)
°C)
°C)
°C)
°C)
-
-
-
-
-
-
00
00
*1: Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Select control conditions of external output.
"Mode 00" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
*3:
Threshold temperature setting for cool / heat mode under auto operation ; Set temperature +
*Cool / heat mode tends to be switched as the threshold temperature range gets smaller,
4°F (+2
°C) to +14°
-- - -
F (+7
°C)
and cool / heat mode becomes difficult to be switched as the threshold temperature range gets larger.
Set the proper value according to use conditions.
01-27
Page 34
2. OUTDOOR UNIT OPERATION CONTROL
Page 35
2. OUTDOOR UNIT
2-1 REFRIGERANT CIRCUIT
Outdoor unit
HPSW1
TH1
CMP1
(INV)
TH11
CMP
ACM
Indoor unit1
TH24
SV4
4WV 1
4WV 2
TH7
HEX1
TH8
HEX2
FP
FAN1
HPS
TH3
OS
SV2
SV3
SV1
LPS
ACM
: Capillary
TH21
HEX21
FAN21
TH22
EEV21
RB unit1
SVD1
SVB2
TH2
TH9
TH10
EEV1
EEV2
: Strainer
EEV3
RCV
SCHEX
TH4
TH6
FP
: Fusible plug
Operation temp. 165 F (75 C )
TH5
GAS LINE
(High pressure)
LIQUID LINE
GAS LINE
(Low
pressure)
No. Part nameFunction
1 Compressor temp. Sensor 1Detects the compressor temperature
2 Discharge temp. Sensor 1Detects the discharge temperature
High pressure SwitchDetects abnormal high pressure 609 psi (4.20 MPa)3
Measure range 0 to 5.0MPa (0 to 725psi)
Measure range 0 to 1.7MPa (0 to 247psi)
Measure range 10 to 130 (50 to 266 F)
Measure range -25 to 58 (-13 to 136 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range -35 to 70 (-31 to 158 F)
Measure range 10 to 130 (50 to 266 F)
Open 4.2MPa(609psi) / Short 3.2MPa(464psi)
Compressor 1 (Inverter)
Electric expansion valve 1 (HEX1)
Electric expansion valve 2 (HEX2)
Electric expansion valve 3 (SC - HEX)
Fan motor
ON (Error) / OFF (Normal)
ON (Operation) / OFF (Stop)
Control output: DC 0/12-24V, Max.30mA
Control output: DC 0/12-24V, Max.30mA
Display the information on operation, error and setting with single LED and
7 segment LED.
02-02
Page 38
2-3 Heat Recovery Operation controlling
2-3-1 Operation mode selection and controlling
Under Heat Recovery operation, the heat balance for the system is controlled based on the Target High pressure and the Target low pressure.
By changing compressor rotation speed or changing Heat exchange capacity, the system can maintain the good heat balance.
The target High pressure value and the target low pressure value in the target range are decided by the outdoor unit's operation mode (Cond ensor or Evaporator).
The outdoor unit's operation mode is decided by depending on the operation order from the connecting indoor unit at the first start up.
- Indoor unit's cooling demand is bigger than heating demand: Outdoor unit operates as Condensor
- Indoor unit's heating demand is bigger than cooling demand: Outdoor unit operates as Evaporator
After the mode was decided at the start up, the operation mode of outdoor unit will be selected by based on the target pressure.
Condensor capacity: UP
(Evaporator capacity: DOWN)
Targeted
(HP & LP)
Ex. When the refrigerant condensation is required
Compressor rps DOWN
Ex. When the refrigerant flow is not required
LP
P
P
Tar ge t: HP
Tar ge t: LP
H
HP
Tar ge t: HP
Target: LP
H
2-4-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same
refrigerant circuit is input, the compressor operates.
When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity",
is stopped.
But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation
Icing protection
Failure (Refer to chapter 4, TROUBLE SHOOTING )
Oil recovery
Under expansion valve initialization
At protective operation
Emergency stop
Defrost operation
Peak cut stop operation
02-03
the compressor
Page 39
2-4-2 Compressor speed control
(1) Speed range and controlling
- On operation range: 20 - 115 rps *
- Changing interval: 60 sec.
- When the multi connection outdoor unit has the same type of compressor, all of compressors rotational speed are controlled with the
same speed at the normal operating condition.
- All of the outdoor unit compressors must start at the start-up process.
- The Normal start process (Except the condition of Cold start)
The first target speed is decided by indoor unit capacity demand.
The upper limit speed at starting is made 60 rps and is raised in 30 rps to 90 rps after 60 seconds.
(The upper speed limit depends on the operating high pressure value)
- The lower limit speed at start-up changes depending on the outdoor temperature
[rps]
65cc (79cc) type compressor
74(60)
37(30)
24(20)
- 10
7
21
[ ]
Outdoor temperature
- Cold Start start process
Condition: Outdoor temperature below 21 (69.8 F) and the system stopped for more than 1 hour]
Control HP*: Change the rps so that high pressure does not reach to protection condition
[rps]
Process 1
Process 2
Process 3
1 min or Max.15 min.
Hold Control HP*
30 sec.10 sec.
Normal control starts
[sec]
02-04
Page 40
2-4-3 Capacity Control
(1) Capacity of compressor operation
The inverter compressor is able to control the amount of required refrigerant circulation in details.
By combining the operation of inverter compressors, the amount of required refrigerant circulation acceding to cooling and heating
load can be supplied from compressor efficiently.
Ex) Combnation of 65cc compressor / Heating (Heating main)
Total capacity
[rps]
[rps]
115
20
Total capacity
INV
[BTU]
[rps]
2 times 115
48
20
Total capacity
INV
INV
[BTU]
3 times 115
68
48
20
INV
INV
INV
[BTU]
Stand-alone
2 Outdoor units
3 Outdoor units
(2) Target low-pressure and high-pressure control
<Cooling>
In order to make the evaporation pressure of the indoor unit at the proper pressure on a variety of operations,
capacity of the compressor will be controlled by low-pressure sensor.
<Heating>
In order to make the condensation pressure of the indoor unit at the proper pressure on a variety of operations,
capacity of the compressor will be controlled by high-pressure sensor.
<Cooling main / Heating main>
In order to keep evaporation pressure / condensation pressure of the indoor unit at the proper pressure on a
variety of operations, capacity of the compressor and the capacity Heat exchange(incl. fan controll) will be
controlled by both of pressure sensor at the sametime
Target low-pressure and high pressure temperature depends on system capacity, capacity of compressor operation,
pipe length, and capacity shift switch settings.
02-05
Page 41
2-4-4 Compressor Sequence Operation
Make starting sequence and start and stop of the compressors in accordance with
the below sequence.
Starting sequence condition
Example)
Starting sequence : Compressor started first, compressor stopped last
Starting sequence : Compressor started 2nd, compressor stopped 2nd from the end
Starting sequence : Compressor started 3nd, compressor stopped 3nd from the end
Rotate the stating sequence under the following conditions:
(1) Defrosting
(2) Oil recovery
(3) When cooling discharge temperature is high
(4) After stopping from Heating operation / Heating main operation
Run command
Starting rotation
execution
Stop Compressor
Operation Compressor
INV
INV
INV
INV
INV
INVINV
INVINV
INVINV
INVINV
INVINV
Stop
Start
Start
Stop
Stop
INV
INV
INV
INV
INVINV
INV
INVINV
INVINV
Oil recovery
Starting rotation
INV
Stop
INV
Start
Start
INV
INVINV
INVINV
INVINV
INVINV
Start
INV
Stop
INV
Stop
Stop
(example)
Stop
execution
INV
INVINV
Stop
INV
INV
INV
Start
INV
INVINV
Stop
INV
INV
INV
Start
02-06
Page 42
2-5 HEAT EXCHANGER CAPACITY CONTROL
2-5-1 Operation mode selection and controlling
Under The heat exchanger capacity is controlled using the 4WV, fan, and EEV according to the target high and low pressures.
The method for changing the capacity of the heat exchanger differs depending on the operation mode.
System demand Heat-Ex conditions Controling device Control target
Cooling Condensor Fan Motor + 4WV (ON/OFF) +EEV Target High pressure
Heating Evaporator Fan Motor (Max rpm) + 4WV (ON) +EEV Maximum control
Cooling main Condensor Fan Motor + 4WV (ON/OFF) + EEV Target High / Low pressure
Heating main Evaporator Fan Motor + 4WV (ON) + EEV Target High / Low pressure
2-5-2 Capacity control
The heat exchanger is operated at maximum efficiency by using each outdoor unit. (Max. 6 Heat exchanger can be used)
Masterr
HEX1
HEX2
Slave1rSlave2r
HEX1
HEX2
HEX1
HEX2
(1) Cooling (In case of 3 outdoor units connection)
Heat Exchanger condition: Condensor
- 4WV ON / OFF (Dpending on HEX capacity shift)
Fan speed Controlling range
- 0 to 500 rpm Only one HEX in use
- 300 to 500 rpm During HEX capacity shift
- Over 500 rpm Full of Heat-Ex capacity
Heat Exchanger capacity shift controlling
- Increas: Upper HEX has a priority in usage condition.
(No available Upper HEX, Lower HEX use)
- Decrease: Lower HEX has a priority in stop condition.
Fan Speed
(rpm)
880
(920)
500
(500)
300
(300)
0
( ) :L-Chassis
Number of Condensor
1 2 3 4 5 6
Target High pressure < Operating High Pressure
Target High pressure > Operating High Pressure
(2) Heating
Heat Exchanger condition: Evaporator
- 4WV ON state
Fan speed Controlling range
- Maximum speed
Heat Exchanger capacity shift controlling
- Use all of available HEXs (Maximum capacity)
Fan Speed
(rpm)
Maximum number of HEX available in use
Number of Evaporator
880 (920)
0
( ) :L-Chassis
(3) Cooling Main / Heating Main (In case of 3 outdoor units connection)
Heat Exchanger condition: Depending on the difference between operating pressure and the Target High pressure and the Target Low pressure.
Fan speed controlling: Depending on the condition of HEX (Condensor / Evaporator)
Heat Exchanger capacity shift controlling:
- Increas: Upper HEX has a priority in usage condition.
(No available Upper HEX, Lower HEX use)
- Decrease: Lower HEX has a priority in stop condition.
The fan speed is controlled to keep high pressure saturation temperature within the target range as follows
The high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
Fan speed (rpm)
(Conditions which raise the fan speed)
High-pressure saturation upper limit of target high-pressure saturation or heat sink temperature 176°F(80°C)
(Conditions which lower the fan speed)
High-pressure saturation low limit of target high-pressure saturation range and heat sink temperature 167°F(75°C)
High-pressure saturation temp.
129 F
(54.0 )
116 F
(46.6 )
107 F
(40.4 )
Upper limit of target high-pressure
saturation temp.
Target high-pressure
saturation temp.
Low limit of target high-pressure saturation temp.
95 F
(35.0 )
126 F
(52.0 )
Outdoor temperature
02-08
Page 44
Intermittent fan mode
When switched from normal fan step to intermittent fan step, always start from 300rpm/7sec.
When there was a change during intermittent step 1-6, switching is performed at the time the current speed
duration time reaches time-up.
The fan speed during all heating is constant with Fan step 16* regardless of the outdoor air temperature.
( rpm )
920
880
( )
-4 F 70 F
Heating Operating range
L-Chassis
S-Chassis
Fan step
16*
15
14
13
12
11
Fan speed (rpm)
S-ChassisL-Chassis
880
860
810
720
620
500
(-20 ) (21 )
(2) Heating main Operation
Operate at 500 rpm until all the heat exchangers are used up.
Then adjust the rpm up or down in accordance with the load.
Fan Speed
(rpm)
880 (920)
500 (500)
300 (300)
0
Number of Evaporator
1 2 3 4 5 6
920
870
820
720
620
500
( ): L-Chassis
02-09
Page 45
2-7 EXPANSION VALVE CONTROL
The EEV controls the flow of refrigerant
Operation mode
Contrl and detection
Control range
operation rangestop
Cooling
EEV 1
Cooling Main
EEV 2
Heating
Heating Main
Cooling
Cooling Main
EEV 3
Heating
Heating Main
Initialization conditions:
4WV 1
4WV 2
- Liquid Pressue control (TH4)
- HEX balance (TH9,TH10)
"TH9 TH10"
- SH control (TH7,TH8 - LPS )
"Target SH: 8 F (4 C)
"
- Protection (TH1) (LPS)
- SH control (TH6 - LPS )
"Target SH: 8 F (4 C)
"
- Protection (TH1)
- When power turned On. - When operation stopped.
TH7
HEX1
TH8
HEX2
TH9
TH10
EEV1
EEV2
RCV
TH4
52- 480 pulses
11 - 480 pulses
0- 500 pulses
SV4
EEV3
SCHEX
TH5
0 pulses
0 pulses
0 pulses
FP
FAN1
TH2
TH6
02-10
Page 46
2-8 SPECIAL OPERATION
2-8-1 Oil Recovery operation
(1) Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units
and the connection pipe with the refrigerant will become large as the operation time of compressor increases.
It is necessary to recover the oil back into the outdoor unit for a certain time interval
in order to prevent compressors from damaging due to lack of lubrication oil.
< Start condition >
Compressor accumulated operation time since last oil recovery operation exceeds 3 hours
(first time: 1 hour.)
< End condition >
3 minutes have elapsed since the compressor restart and Suction superheat "Suction temperature - Lowpressure
saturaion temperature" 10 F (5 C) at all Outdoor units
Or
6 minutes have elapsed since the start
< Operation >
Finishing processActuator
All compressor operation Stop
Keeps the operation mode
Stops
0 pls
Open
Compressor
Heat Ex(4WV)
FAN
Heat Ex EEV
SV1,SV2
Preparation processOn Oil recovery operatiom
All compressor operation Stop
Keeps the operation mode
Stops
0 pls
Open
All compressor start
Condensor (OFF)
Start (Target high pressure control)
480pls
Close
Others
During the oil recovery operation, the status can confirm:
- 2 wires WRC --- Press the Status button on the screen.
appears on the display - 3 wires WRC and Central remote controller ---
- Simple remote controller ---
- LED indication --- Operation LED (Green) flash slowly.
appears on the display
2-8-2 Pre-heat operation
This pre-heat operation protects the start up failure by preventing the refrigerant from soaking into the oil in compressor.
2 pcs of belt heater installed on the compressor
The crankcase heaters are controlled by the outdoor temperature
< Control condition >
Crankcase heater ON: 30 minutes elapsed since installed compressors stopped
OFF: Installed compressors operation
(However, ON when power turned on)
.
35W (1 pcs)
5
3
70W (2 pcs)
02-11
Page 47
2-8-3 Defrost Operation Control
< Defrosting start condition >
Accumulated heating operation time is 40 minutes or longer
(Accumulated heating operation time is reset at the end of cooling operation or defrosting operation.)
And
One of Heat-Ex satisfies condition or or below
Condition : Accumulated operating time is 150 minutes* or longer:
"Heat exchange liquid temperature (TH9 and TH10) 28.4°F ( -2°C)"
*75 minutes: when indoor unit connection capacity 90% at 1 outdoor unit connection.
Condition : Accumulated time 10 minutes:
"Heat exchange liquid temperature (TH9 and TH10) Defrosting Start Judgment Temperature*
And
"During heat exchange liquid temperature keeps droping "
*Defrosting Start Judgment Temperature(°F) = 0.8 x Outdoor temperature (°F) - 52.9
However, -17.7°F to 21.2°F
If the calculated result is lower than -17.7°F, the judgment temperature is defined as -17.7°F
If the calculated result is higher than 21.2°F, the judgment temperature is defined as 21.2°F
(Defrosting start judgment temperature are determined by the outdoor temperature.)
*Defrosting Start Judgment Temperature(°C) = 0.8 x Outdoor temperature (°C) - 11.6
However, -27.6°C to - 6°C
If the calculated result is lower than -27.6°C, the judgment temperature is defined as -27.6°C
If the calculated result is higher than -6°C, the judgment temperature is defined as -6°C
(Defrosting start judgment temperature are determined by the outdoor temperature.)
: Less than 10 minutes operation at outdoor temperature below 35.6°F (2°C) occured 20 times
Condition
< Defrosting end condition >
At all outdoor units, heat exchange liquid temperature Defrosting End Judgment Temp.* and 180sec elapsed,
and all of outdoor unit's Suction temperature - Low pressure saturation temperature 10°F (5°C)
or
When 15 minutes have elapsed from the start
*Defrosting End Judgment Temperature(°F)= 0.39 x outdoor temperature(°F) + 54.8
-However, 41.0°F to 53.6°F range
If the calculated result is lower than 41.0°F, the judgment temperature is defined as 41.0°F.
If the calculated result is higher than 53.6°F, the judgment temperature is defined as 53.6°F.
*Defrosting End Judgment Temperature(°C)= 0.39 x outdoor temperature(°C) + 12.7
-However, 5°C to 12°C range
If the calculated result is lower than 5°C, the judgment temperature is defined as 5°C.
If the calculated result is higher than 12°C, the judgment temperature is defined as 12°C
02-12
Page 48
< Operating state of each part during defrosting operation >
Actuator
Compressor
Heat Ex(4WV)
FAN
EEV1
EEV2
EEV3
SV1,SV2
Preparation processOn Defrost operatiom
All compressor operaiotn Stop
Change Condensor (OFF)
Stops
0 pls
0 pls
Open (Balancing)
[ STEP 1 ]
All compressors sart the operation in defrosting
Master
HEX1
EEV1: 300 pls
HEX2HEX2
EEV2: 480 pls
All compressor start
Cndensor (OFF)
Stops
EEV1: 300 -> 200 pls
EEV2: 480 -> 330 pls
100 - 500 pls
Close
Slave 1Slave 2
HEX1
EEV1: 300 plsEEV1: 300 pls
EEV2: 480 pls
EEV2: 480 pls
HEX1
HEX2
Finishing process
All compressor operaiotn Stop
Keeps the operation mode
Stops
0 pls
0 pls
Open
Compressor in operation
Stopped compressor
HEX in defrosting
DefrostingDefrostingDefrosting
HEX Defrost end
[ STEP 2 ]
When one of the heat exchanger reached to the End condition, the expansion valve open pls will be set as smaller pls to
make it easier for refrigerant distribution to another heat exchanger.
Slave 1Slave 2Master
HEX1HEX1
EEV1: 200 pls
HEX2HEX2
EEV2: 330 pls
Defrost end
EEV1: 300 pls
EEV2: 480 pls
Defrosting
EEV1: 200 pls
EEV2: 330 pls
Defrost end
HEX1
HEX2
[ STEP 3 ]
When the defrosting of all outdoor units ends, all outdoorunit stop.
The start rotation excution is done, and restarts
Slave 1Slave 2Master
HEX1HEX1HEX1
EEV1: 0 pls
HEX2HEX2HEX2
EEV2: 0 pls
Defrost end
EEV1: 0 pls
EEV2: 0 pls
Defrost end
EEV1: 0 pls
EEV2: 0 pls
Defrost end
02-13
Page 49
2-8-4 Low noise mode
When the low noise mode setting ON from Push SW or External input or System controller Input, the outdoor unit operates
in the low noise mode as follows.
Setting and corresponding operations
«
External Input (CN131)
on Master O.U
Low noise mode setting
or
(Push SW)
»
Capacity priority setting
(Push SW)
Low noise level setting
(Push SW)
Operation mode
LEVEL 1
LOW NOISE MODE
OFF
LEVEL 2
LOW NOISE MODE
ON
LEVEL 1
* Automatic switching
ON
LEVEL 2
Low noise mode and operation contents
«»
LOW NOISE MODE
LOW NOISE MODE
COOL
HEAT
COOL
HEAT
Fan upper limit speed
Upper limit compressor capacity
Fan upper limit speed
Upper limit compressor capacity
Fan upper limit speed
Upper limit compressor capacity
Fan upper limit speed
Upper limit compressor capacity
6 ton
620rpm620rpm
50rps
620rpm620rpm
50rps
500rpm500rpm
50rps
500rpm500rpm
50rps 52rps
8 ton
62rps
50rps
10 ton
620rpm
56rps
620rpm
56rps
500rpm
47rps
500rpm
53rps
54rps
* Automatic switching
The operating noise is reduced by limiting the rotational speed of compressor and fan motor
LOW NOISE MODE
LOW NOISE MODE
The operating sound lowers from about 3 to 5 dB more than the rated value
The operating sound lowers from about 3 to 5 dB more than the
LOW NOISE MODE
* Automatic switching
Operation in low noise mode
*Capacity shortage
Normal operation
* Automatic switching
Operation in low noise mode
*Capacity shortage
Operation in low noise mode
*Capacity shortage
Normal operation
Not switched for 30 minutes
after being once switched.
Capacity is enough even
when switched to low noise
mode
Not switched for 30 minutes
after being once switched.
Capacity is enough even
when switched to low noise
mode
Capacity is enough even
when switched to low noise
mode
*
Capacity shortage condition
- When the compressor capacity is not enough
(Compressor operates with upper limit capacity for long time.)
- When condensing capacity is not enough in cooling / cooling main operation
(When the following condition keeps for 5 minutes,
All of HEX in use and FAN spped can not increase and High pressure satu ration temperature 136.4 F (517.65psi) / 58 (3.57MPa))
- When evaporating capacity is not enough in heating / heating main operation
(When the following condition keeps for 5 minutes,
All of HEX in use and FAN spped can not increase and low pressure saturation temperature 32 F ( 0 C))
02-14
Page 50
2-8-5 Snow Falling Protection Fan mode - Default Setting -
The fan rotates compulsorily at the maximum speed when the outdoor temperature becomes 41 F(5 C) or less
The fan is rotated for 1 minute at the fan step upper limit at the interval set by PUSH SW.
This mode ends when the outdoor temperature becomes 44.6 F (7 C) or more or operation starts.
When the Snow Falling protection is not neccesary, change the Function setting F2 -22 "Invalid"
(Operation contents)
Interval setting
setting (standard)
setting
setting
setting
Fan step
Max
fan step
1 min1 min1 min1 min
Int
PUSH SW setting
( F2 - 23 )
00
01
02
03
IntInt
Interval time Int (min)
30
5
10
20
Time
02-15
Page 51
2-9 PROTECTIVE FUNCTION
2-9-1 Discharge temperature protection
Protective function
Discharge
temperature
protection 1
Discharge
temperature
protection 2
Discharge
temperature
protection 3
Discharge
temperature
protection 4
Detect deviceOperation
Discharge temp.
sensor <TH1>
Discharge temp.
sensor <TH1>
Discharge temp.
sensor <TH1>
Discharge temp.
sensor <TH1>
Cool Heat
Display
Starting conditions
Cooling/Cooling Main:
Discharge temperature
above 203
Heating/Heating Main:
Discharge temperature
above 216
Cooling/Cooling Main:
Discharge temperature
Above 225
Discharge temperature
Above 221
Discharge temperature
Above 194
(Heating/ Heating main)
°F(95°C)
°F(102°C)
°F(107°C)
°F(105°C)
°F(90°C)
Release conditions
Below 194°F
(90°C)
Below 207°F
(97°C)
Below 221°F
(105°F)
Below 212°F
(100°F)
Below 185
(85°C)
°F
EEV3 + 30pls/30 sec.
Outdoor unit rotation execution
* After rotation has been
executed once; it is executed
every 15 minutes.
Compressor speed decrease
- 6rps every 30 sec. until it
becomes the cancelation
condition.
EEV’s of operating indoor unit
in heating mode (incl. the
Thermo OFF indoor units)
gradually opens.
(Thermo OFF indoor unit;
max. 200 pls)
Discharge
temperature
protection 5
Discharge
temperature
protection stop
Discharge temp.
sensor <TH1>
Discharge temp.
sensor <TH1>
P1
EA11
Discharge temperature
Above 203
Pattern 1: Discharge
temperature
above 239
Pattern 2
Condition 1 generated
2 times within 40
minutes
°F(95°C)
°F(115°C)
Below 194°F
(90°C)
3 minutes have
elapsed and
Discharge
temperature
below 176
(80°C)
Error reset (push
button SW)
executed after
power reset
°F
EEV1 and EEV2 operating
outdoor unit +10pls / 30sec
Corresponding outdoor unit
stops
Corresponding outdoor unit
stops (Permanent stop) &
Error display
02-16
Page 52
Discharge temperature protection -Summary-
Protection controlling range in Cooling mode
R
R
S
R
R
176194203212 221225239 ( )
809095100 105107115 ( )
Note:
Target pressure controlling will be cancelled when the temperature is in the range color orange.
S
S
S
F
C
DTP COMP STOP: Error Indication
DTP2: Outdoor unit rotation excution
DTP3: limited Compressor speed
controlling
DTP1: EEV3 Liquid injection controlling
Protection controlling range in Heating mode
R
R
176
80
R
185
85
R
R
S
S
194203212 216221 239 ( )
9095 97100 102105 115 ( )
207
S
S
S
DTP COMP STOP: Error Indication
DTP3: limited Compressor speed
controlling
DTP1: EEV3 Liquid injection controlling
DTP5: EEV1,EEV2 opening controlling
DTP4: Indoor unit EEV opening
controlling
F
C
Note:
Target pressure controlling will be cancelled when the temperature is in the range of orange.
Pattern 2
Pattern 1 generated 2
times within 40 minutes
°F(115°C)
Heat Ex.1(2) gas temp. sensor
TH7 (TH8) for use as condenser
(4Way valve: Off, EEV: Open) is
detected abnormally-low to High
pressure saturated temp. for 4
minutes or more.
3 minutes have elapsed
and Discharge temp.
below 176
Error reset (push button
SW) executed after
power reset.
°F(80°C)
Error reset (push button
SW) executed after
power turned on
Operation
Corresponding outdoor
unit stops
Corresponding outdoor
unit stops (Permanent
stop) & Error display
System Stop and
Error indication
02-21
Page 57
2-9-7 Over current protection
Protective function
Overcurrecnt
protection stop
Detect deviceOperation
Inverter PCB
Embeded
Cool Heat
Display
E941
(permanent
stop)
E931
(permanent
stop)
Start conditionRelease condition
Over current protection
circuit detects (Abnormal
current) in 5 times during
compressor operatng.
Over current protection
circuit detects (Abnormal
current) at the compressor
start-up.
Error reset (push
button SW)
executed after
power turned on
Compressor stop and
Error indication
"Trip Detection"
Compressor stop and
Error indication
"Inverter Compressor
Start up Error"
2-9-8 Compressor Frequency Maximum setting protection
Protective functionDetect deviceOperation
Compressor
Frequency
Maximum
setting protection
Filter PCB
Current
transformer
Cool
Heat
Display
Start conditionRelease condition
Pattern 1
Current value more than :
28.7A ( 6ton, 8ton )
35.5A (10ton )
Pattern 2
Current value more than:
29.7A ( 6ton, 8ton)
36.5A (10ton)
Current value less than
the start condition
Current value less than
the start condition
Compressor speed
rise up prohibited
Compressor speed
lowered
2-9-9 Compressor compress ratio protection
( ) : L-Chassis
Protective function Detect deviceOperation
Compressor
compression
ratio protecion
High pressure sensor and
Low pressure sensor
Cool
Heat
Display
*1 Compress ratio:
Start conditionRelease condition
Compression ratio*
above 9 (8)
3 minutes elapsed,
and below 8 (7.5)
SV1 => ON
02-22
Page 58
2-9-10 Fan Motor, Motor Driver abnormal stop protection
Protective function
Fan Motor lock
protection stop
Fan Motor
temperature
protection stop
Fan Motor driver
protection stop
Detect
device
Embeded
device
Embeded
device
Embeded
device
Cool Heat
Display
E97. 1
E97. 5
E97. 9
Start conditionRelease condition
1. When the outdoor fan rotation speed is
less than 100rpm in 20seconds after
fan motor starts.
2. After the fan motor restarts, and when
the condition 1 is repeated consecutively
4 times.
1. When the FAN motor failed the operation
more than 470rpm.
2. After the fan motor restarts, and if the fan
motor cannot operate at 470rpm or more,
or the condition 1 is repeated
consecutively 3 times within 60 minutes.
When the Driver PCB detects the following
abnormalities,
Driver PCB defective, Fan motor defective
(short circuit), Main PCB defective (DC
output abnormal), lose connection, or
Disconnecting wire.
Error reset (push
button SW)
executed after
power turned on
Operation
Fan Motor and
Compressor Stop
Error indication
2-9-11 EEV Coil abnormal Stop
Protective function
Indoor unit EEV
coil abnormal
Stop
Outdoot unit
EEV coil 1,2,3
abnormal Stop
Detect device
Indoor unit
Controller
PCB EEV
drive Circuit
Outdoor unit
Controller
PCB EEV
drive Circuit
Cool Heat
Display
Error on IU.
LED blinks
Operation 5 times
Timer 2 times
Error on OU.
7-Seg display
E9A“X“
Coil No, “X“
Start conditionRelease condition
When the EEV
coil drive circuit
is open circuit
Drive circuit detects
normal condition
and Power reset
Operation
System Stop
Error indication
“I.U Coil 1 Error”
System Stop
Error indication
“CoiX1 Error”
Coil No, “X“
02-23
Page 59
3. INDOOR UNIT OPERATION
Page 60
Page 61
INDOOR UNIT OPERATION
3-1 FAN CONTROL
3-1-1 Fan Speed Setting
Fan speed setting
Press the FAN CONTROL button to set the fan speed.
AUTO
HIGHMEDLOW
3-1-2 "AUTO" Position
1. COOL OPERATION
The fan speed is determined automatically in accordance
with the condition "(TR(corrected room temperature) - TS
(corrected set temperature)" as shown on the right.
However, the fan speed zone is determined in the manner
as the room temperature increases for the following cases.
(1) When the TS is changed.
(2) When the operation mode is changed from other mode to "COOL".
(3) When the fan control is changed from other position to "AUTO".
2. HEAT OPERATION
Same as Cooling operation, fan speed is decided by the
difference between the room temperature and the set
temperature.
2°F(1°C)
- 4°F(-2°C)
T
TR-TS
TR-TS
R-TS
TR-TS
TR-TS
- 4°F(-2°C)
Fan speed zone
4°F(2°C)
4°F(2°C)
2°F(1°C)
When the room
temperature decreases
Fan speed zone
-5°F(-3°C)
Hi zone
Med zone
Low zone
Low zone
Med zone
TR-TS
4°F(2°C)
TR-TS
When the room
temperature increases
TR-TS
- 2°F(-1°C)
5°F(3°C)
TR-TS
4°F(2°C)
- 2°F(-1°C)
- 4°F(-2°C)
TR-TS
5°F(3°C)
TR-TS
-5°F(-3°C)
When the room
temperature decreases
Hi zone
TR-TS
When the room
temperature increases
- 4°F(-2°C)
3. DRY OPERATION
The indoor fan always rotates at "Lo" speed.
Expansion
valve
Indoor fan
motor
(1) The indoor fan starts operation 5 seconds after the electric expansion valve opens. However, when the indoor unit just
starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is not stopped,
the fan will rotate immediately without a delay time of 5 seconds.
(2) The indoor fan will stop in 30 seconds when the refrigerant circulation stops.
(3) The indoor fan will stop immediately when the indoor unit is stopped by pushing the stop button or by a setting of ON timer.
(4) When the refrigerant circulation is stopped due to a lower room temperature for more then 3 minutes, the fan will rotate
1 minutes at intervals of 3 minutes.
(5) When the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant
circulation is stopped, the fan will rotate for 1 minute and then it will operate according to the statement (4).
OPEN
CLOSE
ON
OFF
ON
ON
30s
ON
ONONON
5s
30s
2min30s
1min
3min
ON
ON
TIME -->
5s
4. FAN OPERATION
The indoor fan always rotates at "Lo" speed.
* The above explanation may differ from the actual operating condition when the compressor is controlled under protection function.
03-01
Page 62
3-2 MASTER CONTROL
3-2-1 Operation Mode Control
(1) Mode setting
Each possible operation mode in each connectable type is controlled as below.
RB : I.U = 1 : 1
RB : I.U = 1 : 2 8
(2) Cool, Dry and Heat Mode
Each operation mode is controlled as below.
CoolDry
Indoor fan motor
Operates according to the
AIRFLOW MODE setting.
RB : I.U = 0 : 1
See the fan control page.
Connectable type
Free Cool / Heat
Fix Cool / Heat
Only Cool
: Mode available
: Mode unavailable
X
: Mode available when the priority given to administrative indoor unit.
*1
: Mode available between Dry and Cool.
*2
Cool Dry Heat
X
Heat
Operates according to the
AIR FLOW-MODE setting, and
besides cold air prevention
operation
Operates according to the
AIR FLOW-MODE setting.
Auto
*1
*2
Custom Auto
Fan
Fan
*1
X
X
Drain pump
Electrical
expansion valve
Pulse controlled by the temp-
erature difference calculation
and freeze prevention control
(3) Stop mode
Indoor fan motor : OFF
Electric expansion valve
Drain pump
Turns ON-OFF by the drain pump control function
Pulse controlled by the
temperature difference
calculation and freeze
prevention function
Pulse controlled by the tempe-
rature difference.
: Stop pulse
: Turns ON-OFF by the drain pump control function
03-02
Stop pulse
Page 63
(4) Priority mode ( for connectable type )
The purpose of the priority mode is to restrict operation commands (heating, cooling, dry) from the
connected indoor units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority.
The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling, dry
Priority mode decision methods
Method 1. (Default value)
The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating
Priority when heating depending on which operation mode (cooling, heating) was input first.
After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there
was a Stop input from all the indoor units in the same RB Group.
Neutral
Cooling priority
Heating priority
Method 2. (Management by RB unit)
Operation mode management is made "Management by RB unit" by RB unit DIP-SW
(field setting).
The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the RB
unit regardless of the current mode.
Cooling priority
Heating priority
Method 3. (Management by indoor unit)
Operation mode management is made "Management by indoor unit" by RB unit DIP-SW
(field setting).
Then the master indoor unit is set by wired remote controller.
Thereupon the priority mode shifts to Cooling Priority or Heating Priority in accordance with input
from the master indoor unit regardless of the current priority mode.
The priority mode is fixed at either cooling or heating even if the master indoor unit stops
Cooling/Heating switching can be performed by the master indoor unit only.
Cooling priority
Heating priority
(5) Opposite operation mode ( for connectable type )
When the operation mode commanded from an indoor unit (remote controller) and the operation mode
allowed by the system (cooling and dry operation for cooling only type and operation mode allowed by
priority mode for heat pump type) do not match, it is indicated by blinking of an LED.
Timer lamp: 3 secs ON/1 sec OFF repeated
03-03
Page 64
3-2-1 Operation Mode Control for Outdoor air unit
(1) Mode setting
Each possible operation mode in each connectable type is controlled as below.
RB : I.U = 1 : 1
RB : I.U = 1 : 2 8
(2) Cool and Heat Mode
Each operation mode is controlled as below.
Cool
Outdoor air unit
fan motor
Drain pump
Electrical
expansion valve
Operates according to the
HIGH MODE setting.
Pulse controlled by the
temperature difference
calculation and
freeze prevention control
Connectable type
Free Cool / Heat
Fix Cool / Heat
Only Cool
: Mode available
: Mode unavailable
X
Cool Dry Heat
RB : I.U = 0 : 1
Heat
Operates according to the
HIGH MODE setting.
Operates according to the
HIGH MODE setting.
Fan
Turns ON-OFF by the drain pump control function
Pulse controlled by the
temperature difference.
Stop pulse
Fan
X
X
X
X
Solenoid valve
Closed at all times
(3) Stop mode
Outdoor air unit fan motor : OFF
Electric expansion valve
Drain pump
Solenoid valve: Closed
Opened at thermostat off
and compressor on.
Closed at other operation.
Closed at all times
: Stop pulse
: Turns ON-OFF by the drain pump control function
03-03
+1
Page 65
(4) Priority mode ( for connectable type )
The purpose of the priority mode is to restrict operation commands (heating, cooling) from the
connected outdoor air units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority.
The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling
Priority mode decision methods
Method 1. (Default value)
The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating
Priority when heating depending on which operation mode (cooling, heating) was input first.
After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there
was a Stop input from all the indoor units in the same RB Group.
Neutral
Cooling priority
Heating priority
Method 2. (Management by RB unit)
Operation mode management is made "Management by RB unit" by RB unit DIP-SW
(field setting).
The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the RB
unit regardless of the current mode.
Cooling priority
Heating priority
Method 3. (Management by indoor unit)
Operation mode management is made "Management by indoor unit" by RB unit DIP-SW
(field setting).
Then the master indoor unit is set by wired remote controller.
Thereupon the priority mode shifts to Cooling Priority or Heating Priority in accordance with input
from the master indoor unit regardless of the current priority mode.
The priority mode is fixed at either cooling or heating even if the master indoor unit stops
Cooling/Heating switching can be performed by the master indoor unit only.
Cooling priority
Heating priority
(5) Opposite operation mode ( for connectable type )
When the operation mode commanded from an indoor unit (remote controller) and the operation mode
allowed by the system (cooling and dry operation for cooling only type and operation mode allowed by
priority mode for heat pump type) do not match, it is indicated by blinking of an LED.
Timer lamp: 3 secs ON/1 sec OFF repeated
03-03
+2
Page 66
3-2-2 Auto Changeover Heating / Cooling Operation
[Function available Indoor unit(s)]
Connectable type : All Indoor units
Connectable type : Administrative indoor unit (Management Indoor unit) Refer to the setting Method
Setting Method
1. Switch operation mode management to "Management by indoor unit" by RB unit DIP-SW.
2. Set the master indoor unit by wired remote controller.
3. Judge cooling/heating by the difference between the master indoor unit's setting temperature and
the room temperature.
AUTO CHANGEOVER operation
Operation flow chart
START
Room temp.
Ts+ 4°F(2°C) ?
NO
YES
YES
or operation command other than
Room temp.
Ts -4°F(-2°C)?
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
auto changeover operation?
NO
YES
NO
YES
TS : Setting temperature
in OFF state for 6 minutes or
or operation command other than
auto changeover operation?
COOLING OPERATION
Thermostat remains
longer?
NO
System stops
YES
YES
NO
NO
03-04
Page 67
3-2-2 Auto Changeover Heating / Cooling Operation for Outdoor air unit
[Function available Outdoor air unit(s)]
Connectable type : All Outdoor air units
Connectable type : Administrative outdoor air unit (Management Outdoor air unit).
Refer to the setting Method
Setting Method
1. Switch operation mode management to "Management by outdoor air unit" by RB unit DIP-SW.
2. Set the master outdoor air unit by wired remote controller.
3. Judge cooling/heating by the difference between the master outdoor air unit's setting temperature
and the suction airflow temperature
AUTO CHANGEOVER operation
Operation flow chart
START
YES
YES
Suction airflow temp.
Ts+9°F(+5°C) ?
NO
NO
Suction airflow temp.
Ts- 9°F(-5°C) ?
YES
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
System stops
or operation command other than
auto changeover operation?
YES
TS : Setting temperature
in OFF state for 6 minutes or
or operation command other than
COOLING OPERATION
Thermostat remains
longer?
NO
System stops
auto changeover operation?
YES
YES
NO
03-04
NO
+1
Page 68
3-2-3 Auto Changeover Cooling / Dry Operation
[Function available Indoor unit(s)]
Connectable type
Judge cooling/dry by the difference between the setting temperature and the room temperature.
In case of group connection of cooling only indoor unit, the room temperature sensor in wired remote controller
manages the operating mode.
AUTO CHANGEOVER operation (COOLING ONLY TYPE )
Operation flow chart
: Cooling Only indoor unit
START
TS : Setting temperature
Yes
Yes
Room temp.
Ts+4°F(2°C)?
Yes
COOLING OPERATION
Room temp.
Ts+2°F(1°C) ?
Room temp.
Ts+4°F(2°C)?
NO
Refrigerant
NO
circulation
circulation
stopped?
(due to temp.)
Yes
Refrigerant
started?
(due to temp.)
NO
DRY OPERATION
NO
NO
Yes
03-05
Page 69
3-2-4 Custom Auto Heating / Cooling Operation
[Function available in follwing conmditions]
- Remote controller type: UTY-RNRU
- Remote sensor in use
- Prohibit the central function from the Central controller *Reccomend
CUSTOM AUTO Operation
Operation flow chart
START
NO
T set.C - T set.H 6°F
YES
T set.C: Setting temp. in Cool
T set.H: Setting temp. in Heat
Room temp.
Room temp.
1/2 of DB + 3.0°F
NO
1/2 of DB - 3.0°F
YES
NO
YES
DB: Dead Band*
Room temp.
Room temp.
T set.C + 1.0°F
NO
T set.H - 1.0°F
YES
YES
NO
HEATING OPERATION
YES
YES
*Dead Band(DB) means between T set.C and T set.H, however the setting paramater of Dead Band always has a priolity.
Ex) T set. C: 82°F, T set. H : 78°F DB setting: 6°F => T set. C: 82°F, T set. H: 76°F (DB will be kept from Tset.C basis)
*When the outdoor unit(s) selected the operation mode at once, the selected operation mode will be kept for 12minutes minimum.
Thermostat remains
in OFF state for 6 minutes or
or operation command other than
auto changeover operation?
longer?
NO
System stops
NO
03-06
COOLING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
System stops
or operation command other than
auto changeover operation?
NO
YES
YES
Page 70
3-2-4 "COOL" Position
When using the cooling mode, set the temperature to a value lower than the current room temperature, otherwise
the indoor unit will not start the cooling operation and only the fan will rotate.
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
Ts +1°F(+0.5°C)
Temperature
Ts -1°F(-0.5°C)
Refrigerant
flow
Opening of
EEV
Indoor fan*1
Ts
3Min.
ON
OFF
100%
0%
ON
OFF
Ts : Corrected setting temperature
T
R : Corrected room temperature
*1 When Cooling Thermo-OFF(Fuction setting) activates, the Indoor fan stops under the temperature controlling.
(The room temperature detection in the wired remote controller has to be activated.)
3-2-5 "HEAT" Position
Ts +1°F(+0.5°C)
Ts -1°F(-0.5°C)
TR
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
(1) When using the heating mode, set the temperature to a value higher than the current room temperature, otherwise
the indoor unit will not start the heating operation.
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to
blow out warm air.
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation
(3)
will be temporarily interrupted.
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
Ts +1°F(+0.5°C)
Temperature
Ts -1°F(-0.5°C)
Refrigerant
flow
Opening of
EEV
Indoor fan*1
Ts
ON
OFF
100%
0%
ON
OFF
1Min.
4Min.
Ts : Corrected setting temperature
R : Corrected room temperature
T
: Duration of cold air prevention*2
1Min.
4Min.
Ts +1°F(+0.5°C)
Ts -1°F(-0.5°C)
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
4Min.
1Min.
R
T
*1 When the room temperature detection in the wired remote controlle activates, the Indoor fan stops at the thermo OFF condition.
*2 When the cold air prevention (Fuction setting) invaldiates, the Indoor fan keeps the operation by the setting.
03-06
Page 71
3-2-5 "COOL" Position for Outdoor air unit
When using the cooling mode, set the temperature to a value lower than the discharge airflow temperature, otherwise
the outdoor air unit will not start the cooling operation and only the fan will rotate.
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
Outdoor temp.
Discharge airflow
Temperature
Refrigerant
flow
Opening of
EEV
Outdoor air unit
fan
Ts
Ts - 9°F
(Ts - 5°C)
ON
OFF
100%
0%
ON
OFF
Excess capacity area
Thermistor ON
(6 minutes)
Ts : Corrected setting temperature
Thermistor OFF
(3 minutes)
Ts + 1°F (Ts + 0.5°C) : The thres hold temperature of start of refrigerant flow
Ts - 9°F (Ts - 5°C) : The thres hold temperature of stop of refrigerant flow
Thermistor ON
(6 minutes)
3-2-6 "HEAT" Position for Outdoor air unit
(1) When using the heating mode, set the temperature to a value higher than the discharge airflow temperature, otherwise
the outdoor air unit will not start the heating operation.
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation
(2)
will be temporarily interrupted.
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
Excess capacity area
Ts +9°F
(Ts +5°C)
Discharge airflow
Temperature
Outdoor temp.
Refrigerant
flow
Opening of
EEV
Ts
ON
OFF
100%
0%
Thermistor ON
(6 minutes)
Thermistor OFF
(3 minutes)
5 minutes has passed
at excess capacity area
Thermistor ON
(6 minutes)
5 minutes has passed
at excess capacity area
Outdoor air unit
fan
ON
OFF
Ts : Corrected setting temperature
Ts - 1°F (Ts - 0.5°C) : The thres hold temperature of start of refrigerant flow
Ts + 9°F (Ts + 5°C) for 5 minutes or more
: The thres hold temperature of stop of refrigerant flow
+1
03-07
Page 72
3-3 LOUVER CONTROL
(1) ADJUSTING THE DIRECTION OF AIR CIRCULATION
Instructions relating to heating ( ) are applicable only to heat pump type
outdoor unit.
Begin air conditioner operation before performing this procedure.
Vertical Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE",
"WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Press the VERTICAL AIR FLOW DIRECTION SET button.
Example : When set to vertical air direction.
Press the VERTICAL AIRFLOW DIRECTION button.
The temperature display will change to the vertical airflow direction setting display.
Press the VERTICAL AIRFLOW DIRECTION button to change the vertical louvre position.
The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4
Heating : 1 , 2 , 3 , 4
LARGE CEILING TYPE
1
2
3
4
UNIVERSAL FLOOR/CEILING TYPE
1
2
3
COMPACT WALL MOUNTED TYPE
1
2
3
4
WALL MOUNTED TYPE
4
CASSETTE TYPE
1
2
3
4
1
2
3
4
Adjustable Position (All Mode)
Position setting is available by only wiress remote controller
1 , 2 , 3 , 4 ,
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
During Cooling mode : Horizontal flow
During Heating mode : Downward flow
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal ,
1
(Large Wall mounted type: )
4
1
the air direction cannot be adjusted during this period.
03-07
Page 73
Horizontal Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR/CEILING TYPE" and "WALL MOUNTED TYPE".
Press the HORIZONTAL AIR FLOW DIRECTION SET button.
Press the HORIZONTAL AIRFLOW DIRECTION button. The temperature
display will change to the horizontal airflow direction setting display.
Press the HORIZONTAL AIRFLOW DIRECTION button to change the
horizontal louvre position. The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4 , 5
Heating : 1 , 2 , 3 , 4 , 5
Example : When set to horizontal air direction.
LARGE CEILING TYPE
1
5
2
4
3
WALL MOUNTED TYPE
UNIVERSAL FLOOR/CEILING TYPE
3
2
1
4
5
(2) SWING OPERATION
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE",
"WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Begin air conditioner operation before performing this procedure.
To select Vertical airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE",
"CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Press the VERTICAL SWING button for more than two seconds.
The remote controller's Vertical Swing Display will light up.
In this mode, the UP/DOWN air direction flaps will swing automatically to direct the air flow both up and down.
Example : When set to vertical swing.
To Stop Vertical airflow SWING Operation
Press the VERTICAL SWING button for more than two seconds
once and again.
The remote controller's Vertical Swing Display will go out.
Airflow direction will return to the setting before swing was begun.
03-08
Page 74
Instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE",
"WALL MOUNTED TYPE", and "COMPACT WALL MOUNTED TYPE".
About Vertical Airflow SWING Operation
The SWING operation may stop temporarily when the
air conditioner's fan is not operating, or when operating
at very low speeds.
The swing operation is not available depending on the model.
Please refer to the operating manual for the indoor unit.
To select Horizontal Airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE",
"UNIVERSAL FLOOR / CEILING TYPE", "WALL MOUNTED TYPE"
and "CEILING WALL TYPE".
Press the HORIZONTAL SWING button for more than two seconds.
The remote controller's Horizontal Swing Display will light up.
In this mode, the RIGHT/LEFT air direction louvers will swing
automatically to direct the airflow both right and left.
Air swing range
Air flow direction setRange of swing
1
2
3
4
1 to 4
(All range)
*Large Wall Mounted type
1 to 5
Example : When set to horizontal swing.
To stop Horizontal airflow SWING Operation
Press the HORIZONTAL SWING button for more than two seconds
once and again.
The remote controller's Horizontal Swing Display will go out.
Airflow direction will return to the setting before swing was begun.
About Horizontal Airflow Swing Operation
Left and right swing range can be changed in 3 steps by field setting.
The SWING operation may stop temporarily when the
air conditioner's fan is not operating, or when operating
at very low speeds.
The swing operation is not available depending on the model.
Please refer to the operating manual for the indoor unit.
Left and right swing range
Range of swing
1 to 5 (All range)
1 to 3
3 to 5
Function NumberSetting Value
24
( Factory setting)
00
01
02
03-09
Page 75
3-4 ELECTRONIC EXPANSION VALVE CONTROL
1. Initialization
When the power is turned ON.
When it has passed the limited time since the last initialization.
2. Operation Control
When indoor unit stopping by Thermo-OFF condition.
Outdoor unit Condition
OFF
Cooling
Heating
When starting up
(Cooling) Move to the cooling control base pulse in steps.
(Heating) Move to the heating control base pulse in steps.
Automatic operatic control
Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Room temperature control
The room temperature is controlled so that it reaches to the set-up temperature based on the difference
between the room temperature and the set-up temperature, and the change of indoor unit temperature.
Cooling operation: if the room temperature becomes 0.5 C lower than the set-up temperature, EEV is fully closed.
Heating operation: if the room temperature becomes 0.5 C Higher than the set-up temperature, EEV is slightly opened.
*In case of protection controlling, EEV keeps open position.
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously.
(2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped.
(3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention
operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost
prevention operation.
(4) When the water level in the drain pan rises up and then the float switch functions:
Microcomputer stops the refrigerant circulation and indoor fan motor operation.
1
2
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
(5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates.
(6) When the float switch turns OFF within 3 minutes, the unit starts cooling operation.
03-10
Page 76
3-4 ELECTRONIC EXPANSION VALVE CONTROL for Outdoor air unit
1. Initialization
When the power is turned ON.
When it has passed the limited time since the last initialization.
2. Operation Control
When indoor unit stopping by Thermo-OFF condition.
Outdoor unit Condition
OFF
Cooling
Heating
When starting up
(Cooling) Move to the cooling control base pulse in steps.
(Heating) Move to the heating control base pulse in steps.
Automatic operatic control
Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Discharge airflow temperature control
The discharge airflow temperature is controlled so that it reaches to the set-up temperature based on the difference
between the discharge airflow temperature and the set-up temperature.
Cooling operation: 1) If the discharge airflow temperature becomes 9°F (5°C) lower than the set-up temperature,
EEV is fully closed.
2) If the suction airflow temperature becomes 1°F (0.5°C) lower than the set-up temperature,
EEV is fully closed.
Heating operation: 1) If the discharge airflow temperature becomes 9°F (5°C) higher than the set-up temperature
for 5 minutes or more, EEV is fully closed.
2) If the suction airflow temperature becomes 1°F (0.5°C) higher than the set-up temperature,
EEV is fully closed.
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously.
(2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped.
(3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention
operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost
prevention operation.
(4) When the water level in the drain pan rises up and then the float switch functions:
Microcomputer stops the refrigerant circulation and indoor fan motor operation.
1
2
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
(5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates.
(6) When the float switch turns OFF within 3 minutes, the unit starts cooling operation.
03-11
+1
Page 77
3-6 FUNCTION
3-6-1 Auto Restart
The air conditioner restarts with the previous setting operation.
3-6-2 Freeze Prevention Control
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition
Compressor is operation more than 3 minutes.
When "Heat exchanger inlet temperature T
Compressor is operation more than 3 minutes.
When "Heat exchanger outlet temperature T
(2) Operation
EEV is closed.
Fan is at the setting amount.
(3) Completing Condition
Heat exchanger inlet and middle temperature T
After more than 5 minutes
A" continues *4 minutes or more.
A" continues 4 minutes or more.
B
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
*
TA
1°C
TB
7°C
3-6-3 Oil Recovery Operation / Defrost Operation
[Oil recovery operation / Defrost operation] :
It periodically returns the residual refrigerant ion oil in the indoor unit and the connection piping back to the outdoor unit ,
and prevents the compressor oil level from decreasing.
Indoor unit LED : Operation LED
6 sec ON 2 sec OFF Blinking
Indoor fan : Same operation before oil recovery operation in cooling operation or dry operation.(Heating operation: Stop)
Indoor EEV : Control pulse
During the above operation, a refrigerant noise might hear from the indoor unit.
03-11
Page 78
3-6-4 Outdoor temperature protected operation for Outdoor air unit
1. COOL OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
a) Operation mode management is made
"Management by indoor unit", and
outdoor air unit is master indoor unit.
b) Cases Other than (a)
Suction airflow
temperature rises
68°F
(20°C)
50°F
(10°C)
23°F
(-5°C)
Forced thermostat off
and Fan off
Suction airflow
temperature drops
Cooling operation
Fan operation
Heating operation
64°F
(18°C)
41°F
(5°C)
19°F
(-7°C)
Suction airflow
temperature rises
Cooling operation
68°F
(20°C)
50°F
(10°C)
Forced thermostat off
and Fan off
Suction airflow
temperature drops
Fan operation
2. HEAT OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
Suction airflow
temperature rises
70°F
(21°C)
23°F
(-5°C)
Forced thermostat off
and Fan off
Fan operation
Heating operation
Suction airflow
temperature drops
66°F
(19°C)
19°F
(-7°C)
64°F
(18°C)
41°F
(5°C)
3. FAN OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
a) Operation mode management is made
"Management by indoor unit", and
outdoor air unit is master indoor unit.
Suction airflow
temperature rises
50°F
(10°C)
23°F
(-5°C)
Forced thermostat off
and Fan off
Fan operation
Heating operation
Suction airflow
temperature drops
41°F
(5°C)
19°F
(-7°C)
03-12
+1
b) Cases Other than (a)
Suction airflow
temperature rises
Fan operation
50°F
(10°C)
Forced thermostat off
and Fan off
Suction airflow
temperature drops
41°F
(5°C)
Page 79
RB UNIT OPERATION
3-7 RB UNIT COMPORNENT
3-7-1 Position of Solenoid coil
Single type
UTP-RX01AHUTP-RX01BH
SV4
SV3SV2
SV1
Multi type
UTP-RX04BH
SV4
SV5
SV3SV2
SV1
SV4
SV5
SV3SV2
SV1
SV4
SV5
SV3SV2
SV4
SV5
SV3SV2
SV1
SV1
UTP-RX01CH
SV4
SV6
SV4
SV5
SV3SV2
SV5
SV3SV2
SV1
Color of Connector
SV1
SV1
SV2
SV3
SV4
SV5
SV6
Green
Blue
Black
White
Red
Yellow
3-7-2 Position of Solenoid valve
( ) : Indication on the Service Tool
Liquid Line
CP3
ST
High Pressure Gas Line
Low Pressure Gas Line
CV
CP1
SV3
(SVB1)
SV2
(SVB2)
SV1
(SVD1)
CP2
SV4
(SVS)
SV5
(SVS)
SV6
(SVS)
EEV
ST
Indoor unit Gas Pipe
Service Tool Display
SVS
*
SVB1
SVD1
SVB2
03-12
LP
*SV5, SV6 are not indicated on the Service tool
HP
Page 80
3-7-3 PCBs layout
Single type
DIP SW
SET 1
-Upper side-
SV connector
Multi type
Main PCB
Error indication LED
(Red)
Power supply indication
LED (Green)
Transmission PCB1
Transmission PCB2
- Upper side -
SV connector
DIP SW
SET 1
DIP SW
SET 2
3-7-4 PCB component
OU.
RB Unit
IU.
Transmission
PCB2
Main PCB: Pulse signal communication between Transmission PCB1 and Transmission PCB2
Transmission PCB1: Pulse signal communication between IU. and RB Main
Transmission PCB2: Pulse signal communication between OU. and RB Main
*The transmission PCB1 and The transmission PCB2 are the same part.
- Caution When the Main PCB is newly installed to the RB unit, the address setting is required.
The RBG Address number has to be set as the same address of connecting indoor unit.
(When a connection port of RB unit has a multi indoor unit connection, the younget address number of
indoor unit has to be given to the main PCB of RB.)
The preparation for mode changing takes a little time ( about 6 minutes).
By changing DIP-SW (SET4-3) to ON, the time for the mode selection
controlling will be shorter ( 3 minutes).
If the mode selection control time is short, the soud of refrigerant may
be loud during cool to heat selection control process.
03-14
Page 82
Page 83
4. TROUBLE SHOOTING
Page 84
Page 85
4. TROUBLESHOOTING
4-1 NORMAL OPERATION
4-1-1 Indoor Unit Display
Flashing PatternIndication LampIndication type
Operation
Continuous lighting
Operation LED
Continuous lighting(lowered light)Anti Freeze
Continuous lighting(lowered light)Timer LEDTimer
FilterFilter LEDContinuous lighting
1 sec1 sec
Operation LED
ON
OFF
Power Failure
1 sec
1 sec
6 sec2 sec
Defrosting
Oil Recovery
Timer LED
Operation LEDTest Operation
Timer LED
Operation LED
ON
OFF
ON
OFF
ON
OFF
1 sec
1 sec
Opposite Operation Mode
Maintenance Mode
Location Notification
Timer LED
Operation LED
Timer LED
Filter LED
Operation LED
Timer LED
Filter LED
3 sec1 sec
ON
OFF
ON
OFF
ON
OFF
This function is only available on the 2 wires remote controller.
Please refer to the installation manual of UTY-RNR*
1 sec1 sec
4 sec
1 sec
04-01
Page 86
4-1-2 OUTDOOR UNIT DISPLAY
Indication type7 Segment LED Pattern
Idling(stop)
Cooling Mode (Mainly Cooling)
Heating Mode (Mainly Heating)
Oil Recovery Operation
Defrost Operation
Discharge Temp. Protection is stopped
High Pressure Protection is stopped
Low Pressure Protection is stopped
Compressor Temperature Protection is stopped
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" ROTECT "4"
Description
Refer to Chapter 02.
(Outdoor unit operation control)
Refer to Chapter 02.
(Outdoor unit operation control)
<Starting condition>
Discharge temp fixed value 239°F(115°C)
<Release condition>
3 minutes have elapsed and discharge temperature 176°F(80°C)
<Starting condition>
High pressure 611psi(4.00MPa) or Pressure SW in operation
<Release condition>
5 minutes have elapsed and high pressure 509psi (3.50MPa) and
Pressure SW release
<Starting condition>
Low pressure 7psi (0.05MPa)
or low pressure 15psi (0.10MPa) continues for 10 mins
<Release condition>
3 minutes have elapsed and low pressure 25psi (0.17MPa)
<Starting condition>
Compressor temp fixed value 239°F(115°C)
<Release condition>
3 minutes have elapsed and discharge temperature 176°F(80°C)
Peak Cut Mode
Low Noise Mode
Snow Falling Protection Fan mode
Inverter Compressor Operation Indication
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
LED104
POWER
LED101
ERROR
LED102
"P" eak "C" ut
"L" OW "N" OISE
"SN" OW
Blinking
ON
OFF
ON
OFF
Refer to Chapter 02.
(Outdoor unit operation control)
Refer to Chapter 02.
(Outdoor unit operation control)
ON
1 sec1 sec
OFF
04-02
Page 87
4-2 ABNORMAL OPERATION
4-2-1 Error code Display
An Error code is represented by 3 digit characters.
The first 2 digit means the subsection Error code, and the last 1 digit means the specifics Error code.
Ex.) Indoor unit Network communication Error
1 4 . 3
Subsection Error Code
14 : Network communication Error
Specifics Error Code
3 : Indoor unit Network Communication Error
Each Error code section is shown by the following target
Subsection Error Code target
- Indoor unit (Operation / Timer / Filter) LED
- 2 / 3 Wires Remote controller
Subsection and Specifics Error code target
- Outdoor unit 7 segment Display
- Service Tool
- Simple Remote controller
- Group Remote controller
- Central Remote controller
- Touch - Panel Controller
When an Error occurs, each devices indicate own abnormal detecting condtion.
In order to confirm the actual error condition, the following procedure are required.
1) Confirm the Specific Error code on the Outdoor unit 7 segment display or the Service tool.
Ex.1.) When the wired remote controller shows " 9 U (Outdoor unit Error)".
Ex.2*.) When the wired remote controller shows " 4 2 (Indoor unit Heat-Ex Sensor Error)"
*The Specific Error code can be indicated by service tool.
2) Confirm each Error code on each devices in case of Network communication Error.
Ex.) When the Network cable of indoor unit 00 disconnected during operating.
Error code “ 14.2 ”
Outdoor unit
Error code “14.1 or 14.3”
Error indication pattern
"14.1": No communication between Outdoorunit and
Service tool.
"14.3": Communication Error on the Indoor unit.
Operation LED: 1 time blinking
Timer LED: 4 times blinking
"Network communication Error"
*Indoor unit detects the condition of Error code 14.3,
but it can only display the Subsection Error code.
" No communication between
indoor unit 00 "
Service
Tool
Error code “ 14 ”
RB
unit
Indoor unit 00
RB
unit
Indoor unit 01
Wired remote
controller
04-03
- DipSW 4-2:ON Default Setting -
Touch-panel Controller
Error code "14" “16”
Error indication pattern
"14": Error on the Outdoorunit (14.2)
"16": The Communication Error between Touch panel controller and Error indoor unit.
Note: About Service tool
- To change the connecting location of service tool
can be helpful for the trouble shooting.
- To check the system configuration, the Address
checker function can be helpful for trouble shooting.
Page 88
4-2-2 Indoor Unit Display
Error Indication Flashing Pattern
Example : Indoor Unit Main PCB Error (Operation LED : 3 times, Timer LED : 2 times)
1 cycle
ON
1.0s
Operation LED
Timer LED
Filter LED
OFF
ON
OFF
ON
OFF
0.5s 0.5s
0.1s / 0.1s
0.5s 0.5s 0.5s 0.5s
4.0s
1.0s
4-2-3 Outdoor Unit Display
3.0s
0.5s 0.5s
0.5s 0.5s
1.0s
4.0s
LED display
POWER
ERROR
MODE
LED101
(GREEN)
POWER MODE LED : on
ERROR LED : blink
LED102
(RED)
Operation button
MODE
ERROR transition
Short press : less than 3 seconds
Long press : more than 3 seconds
Type of errors
SELECTENTER
EXIT
SW108SW109
SW107
Annunciation
"Err." and quantity are alternately shown.
"ENTER" short press"ENTER" short press
ex : discharge thermistor 1 abnormal ex : indoor unit abnormal
"SELECT" short press
display change
POWER
LED101
ERROR
LED102
ON
OFF
0.1sec0.1sec
ON
OFF
If some error is newly occured or resolved
during transition, it is reflected after going
back to "Annunciation".
When there is more than one error, display is changed by "SELECT" short press.
"ENTER" long press
*
Address
"ENTER" short press
* Only in the case of "indoor unit abnormal
(E.5U.1)", indoor unit address is shown by
ENTER long press.
"SELECT" short press
display change
When more than one indoor unit is abnormal, display is changed by "SELECT" short press.
04-04
Page 89
4-2-4 Remote Controller Display
<< SIMPLE REMOTE CONTROLLER >>
ERROR CODE DISPLAY
If an error occurs, the following display will be shown.
““ will appear in the set room temperature display.)
(
“ is displayed, immediately contact authorized
“
If
service personnel.
<< WIRED REMOTE CONTROLLER 3 wire type>>
ERROR CODE DISPLAY
Error code
Faulty unit No.
(Remote controller address)
Ex. Error code display
If an error occurs, the following display will be shown.
““ will appear in the set room temperature display.)
(
“ is displayed, immediately contact authorized
“
If
service personnel.
<< WIRED REMOTE CONTROLLER 2 wire type>>
If an error occurred, an error icon appears on the Monitor mode screen.
Conference
Mode
Set Temp.
-Status
Fri 10:00AM
Fan
Menu
1. Touch the [Status] on the Monitor
mode screen.
-Status
Air Flow Direction
VT1
1
Economy
Off
Monitor
2. Touch the [Error Information] on
the Status screen.
Unit number (usually 0)Error code
Ex. Error code display
Hz
3
Anti Freeze
Next
Page
Page 1/3
Off
Error
Information
Error Information
Address
02-01
Error Code
12, 14
Back
2-digit numbers are corresponding to
the error code
Page 1/5
Next
Page
<< GROUP REMOTE CONTROLLER >>
ERROR CODE DISPLAY
The air conditioning system must be inspected if “ : “
(error code) appears on the timer and Clock Display, or the
operation lamp is flashing.
*1 ;
Model code
: Outdoor unit
: Indoor unit
: Group remote controller
: Convertor
04-05
Model code
*1
Error code
Ex. Error code display
Page 90
4-2-5 Trouble shooting index - Error code List 1/2 -
Display Target A
Simple Wired remote controller
2 / 3 wires Wired remote controller
Indoor unit LED brinking times,
Display Target B
Group Remote controller
Central Remote controller
Touch- Panel controller
: No Display A: LED 10 times BlinksJ: LED 13 times BlinksU: LED 15 times Blinks
*
Display
Target A
Display
Target B
7 4
Outdoor temp. Sensor Error
7 5
Suction gas temp. Sensor Error
Heat sink temp. Sensor Errorl
7 7
8 2
Sub cool HEX temp. Sensor Error
8 3
Liquid pipe temp. Sensor Error
Current Sensor Error
8 4
86
9U
J1
14
J116
*
*1: Master Outdoor unit : 9 U. 2 / Slave Outdoor unit and Service Tool indicate applicable Error code
Pressure Sensor Error
Compressor start up Error
93
94
Trip Detection
95
Compressor motor control Error
97
Outdoor unit FAN Motor 1 Error
9A
Outdoor unit coil (EEV) Error
Outdoor unit Abnormal
*1
Discharge temp. Abnormal
A1
Compressor temp. Abnormal
A3
Pressure abnormal 1
A4
Pressure abnormal 2
A5
Heat-Ex temp. Abnormal
A6
Ambient temp Abnormal
AC
RB Unit Error
Initial Setting Error
Error Contents
< Subsection >
Display
Target C
5U.1J1. 1
14. 114. 1
14. 214. 2
Display
Target D
7 4 . 1
7 5 . 1
7 7 . 1
8 2 . 2
8 3 . 1
8 3 . 2
8 4 . 1
86.1
86.3
86.4
93.1
94.1
95.5
97.1
97.5
97.9
9A.1
9A.2
9A.3
*1
A1.1
A3.1
A4.1
A4.2
A5.1
A6.3
A6.4
AC.4
14. 3
J1. 4
----
*
Outdoor temp. Sensor Error
Suction gas temp. Sensor Error
Heat sink temp. Sensor Error
Sub cool HEX gas outlet temp. Sensor Error
Liquid pipe temp. Sensor 1 Error
Liquid pipe temp. Sensor 2 Error
Current sensor 1 Error
Discharge pressure sensor Error
Suction pressure sensor Error
High pressure SW 1 Error
Inverter compressor Start up Error
Trip detection
Compressor motor loss of synchronization
Outdoor unit FAN Motor Lock Error
Outdoor unit FAN Motor temp. Abnormal
Outdoor unit FAN Motor Driver Abnormal
Coil 1 (EEV) Error
Coil 2 (EEV) Error
Coil 3 (EEV) Error
Slave out door unit Eror
Dischar
ge temp. 1 Abnormal
Compressor 1 Temperature Abnormal
High pressure Abnormal
High pressure protection 1
Low pressure Abnormal
Outdoor unit Heat-Ex 1 Gas temp. Abnormal
Outdoor unit Heat-Ex 2 Gas temp. Abnormal
Outdoor unit Heat Sink temp. Abnormal
RB Unit EEPROM Access Abnormal
RB Unit transmission PCB2 parallel
communication Error
Initial Setting Error
Error Contents
< Supecifics >
Wired remote controller "Internal Error" * These error codes will be shown only on the remote controller.
CC.1
C2.1
15.4
Sensor Error
Transmission PCB Error
*
Data acquisition Error
Replace the remote controller, If the error appears on the remote controller.
*
*
Service Tool
Trouble
shooting No.
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
4-2-6Trouble shooting index - No Error code -
Error condition
Indoor Unit - No Power (Except W all Mounted )
Indoor Unit -No Power( Wall Mounted)
Outdoor unit - No Power
RB Unit - No Power
No operation ( Power is ON )
No Cooling / No Heating
Abnormal Noise
Water leaking
Indoor Unit - No Power (Outdoor air unit)
No E rror Code
System Abnormal
Indoor Unit - No Power (Except Wall M ounted )
Indoor unit - No Power ( Wall Mounted)
Outdoor unit - No Power
RB Unit - No Power
No operation (Power is ON )
No Cooling
Abnoemal Noise
Water leaking
Indoor Unit - No Power(Outdoor air unit)
04-07
Error Contents
Trouble
shooting
72
73
74
75
76
77
78
79
80
Page 92
4-2-7 TROUBLE LEVEL OF SYSTEM
<< System Condition when Outdoor Unit Error is occurred >>
Trouble Level
12
System Condition
System is not
stopped compulsorily
Operation continues
System is
compulsorily stopped
(*4)
System is
compulsorily stopped
(*1) This will not be displayed on indoor unit which Error Report Target (function setting 47 of indoor unit) is set "for administrator".
(*2) The System condition can change to (Trouble Level 1) by changing DIP SW (SET 4-1:OFF)
(*3) Even if power is reset, this Error cannot release. In Error release, you need to solving the problem and operate the push switch and a and apply
"Error reset" (F3-40) after power restart.
When one of outdoor unit on the multi connection detects these Error, the backup operation can activate by using of remaining outdoorunit(s)
(*4)
Please check each trouble shooting, and read the caution before using the backup operation.
Outdoor unit Condition
Abnormal LED indication
Outdoor unit does not stop
Abnormal LED indication
Outdoor unit stop
Abnormal LED indication
Outdoor unit stop
Not indicated on Indoor Unit and
Peripheral unit.
Indicated on Service Tool.
- 14.1 Outdoor unit network
communication 1 error
- 67.2 Inverter PCB short
interruptation detection
Indicated on Indoor Unit (*1)
and Peripheral unit.
Indicated on Service Tool.
- 62.3 Outdoorunit EEPROM acccess error
- 62.8 EEPROM data corrupted error
- 73.5 Heat Ex.1 liquid temp. sensor error
- 73.7 Heat Ex.2 liquid temp. sensor error
- 75.1 Suction gas temp sensor error
- 82.2 Sub-cool Heat Ex. gas outlet temp. sensor error
- 83.1 Liquid pipe temp. sensor 1 error
- 83.2 Liquid pipe temp. sensor 2 error
- 62.6 Inverter communication error
- 63.1 Inverter error
- 68.2 Rush current limiting resister temp. rise protection (*3)
- 71.1 Discharge Temp sensor 1 error
- 72.1 Compressor Temp sensor 1 error
- 73.4 Heat Ex. 1 gas temp sensor error
- 73.6 Heat Ex. 2 gas temp sensor error
- 74.1 Outdoor Temp sensor error
- 77.1 Heat sink Temp sensor error
- 84.1 Current sensor 1 error (*3)
- 86.1 Discharge pressure sensor error
- 86.3 Suction pressure sensor error
- 86.4 High pressure switch 1 error
- 93.1 Inverter compressor start up error (*3)
- 94.1 Trip detection (*3)
- 95.5 Comp. motor loss of synchronization (*3)
- 97.1 Outdoor unit fan motor lock error (*3)
- 97.5 Fan motor temperature abnormal (*3)
- 97.9 Fan motor driver abnormal (*3)
- A1.1 Discharge temperature 1 abnormal (*3)
- A3.1 Compressor1 temperature abnormal (*3)
- A4.1 High pressure abnormal
- A4.2 High pressure protection1
- A6.3 Outdoor Heat Ex. 1 gas temp. abnormal (*3)
- A6.4 Outdoor Heat Ex. 2 gas temp. abnormal (*3)
- AC.4 Heat sink temperature abnormal
- 13.1 Communication error between outdoor unit
- 14.2 Outdoor unit network communication 2 error
- 14.5 The number of indoor unit shortage (*2)
- 61.5 Outdoor unit reverse phase, missing phase wire error
- 69.1 Outdoor unit transmission PCB parallel communication error
- 9A.1 Coil1 (Expansion valve1) error
- 9A.2 Coil2 (Expansion valve2) error
- 9A.3 Coil3 (Expansion valve3) error
- A5.1 Low pressure abnormal (*3)
<< Error code which manual error release will be required >>
A5.1 Low pressure abnormal
84.1 Current sensor 1 error
93.1 Inverter compressor start up error
94.1 Trip detection
A1.1 Discharge temperature 1 abnormal
A3.1 Compressor 1 temperature abnormal
97.1 Outdoor unit fan motor lock error
97.5 Fan motor temperature abnormal
97.9 Fan motor driver abnormal
68.2 Rush current limiting resister temp rise protection
95.5 Compressor motor loss of synchronization
A6.3 Outdoor heat exchanger 1 gas temperature abnormal
A6.4 Outdoor heat exchanger 2 gas temperature abnormal
04-08
Page 93
4-2-8 ERROR HISTORY MODE
When the abnormality occurred, the Outdoor unit memorizes the history of error codes up to 10
and it can be displayed on 7 segments LED.
It is an effective means to examine abnormality that occurred in the past.
*The error history can be cleared by setting to F3-30.
Refer to the following for the procedure.
1
Mode Selection Display
Select the
Error History Number
4
Monitor Mode
1
Change to the Error History Mode from the Mode Selection Display
POWER
ERROR
LED105
MODE
LED101
(GREEN)
LED102
(RED)
LED104
"ENTER" button
short press
Mode selection displayThe newest History Number and
2
Select the Error History Number
LED105
POWER
MODE
LED101
(GREEN)
ERROR
LED102
(RED)
LED104
It changes if the
"SELECT" buttonis
short pressed
[Forward]
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
Error Code are displayed by the 2 digits
Error History Number : [00]Error Code : [71]
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
LED105
LED104
LED104
2
"SELECT" button
short press
[Forward]
ERROR HISTORY MODE
3
Display details
of the
Error History
: Light off
: Flashing
: Lighting
(Newest)
00010209
The History Number changes sequentially
from "00" to "09" by the "SELECT" button
(Oldest)
3
Check the detail of the Error History
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
Select the History Number
"ENTER" button
short press
LED104
It changes if the
"SELECT" button
is short pressed
LED105
Detail of Error Code is displayed by the 3 digits
example) Error Code : E711
[Forward]
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
Error History Number : [01]
Error Code : [- -]
There is no Error History yet,
in the object History Number
4
End of the Error History mode
POWER
ERROR
MODE
LED101
LED102
(RED)
(GREEN)
LED105
LED104
"MODE/ EXIT" button
short press
LED104
"ENTER" button
short press
LED105
If there is no Error History,
detail of Error Code is displayed as above
LED105
POWER
MODE
LED101
(GREEN)
POWER
MODE
LED101
(GREEN)
POWER
MODE
LED101
(GREEN)
ERROR
LED102
(RED)
ERROR
LED102
(RED)
ERROR
LED102
(RED)
LED104
LED104
LED104
Select the History Number Return to the Monitor Mode
example) Normal display (Cooling operation)
04-09
Page 94
4-2-9 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1 E12.1
INDOOR UNIT Error Method:
Wired Remote Controller
Communication Error
Detective Actuators:
Indoor unit controller PCB circuit
Wired Remote Control (3 wire / 2 Wire type)
Forecast of Cause : 1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash. < 1 2 >
Error Code : 1 2
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor
unit, but the same signal has not been received more than 1 minute (3 Wire
type). 2.5 minute (2 Wire type)
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of controller PCB Connector CNC01. (Power supply for Remote)
If DC12V, Remote Control failure (C
If DC0V, Controller PCB failure (Remote is OK) >>> Replace Controller PCB
wiring, turn on the power again.
-In case of re-installation is done due to removed connector or incorrect
ontroller PCB is OK) >>> Replace Remote controller
DC
04-10
Page 95
Trouble shooting 2 E12.2
INDOOR UNIT Error Method:
Wired Remote Controller signal Error
Indicate or Display:
Outdoor Unit : E.5 U.1,
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Remote Controller : 1 2
Detective Actuators:
Indoor unit Controller PCB circuit
Wired Remote Control (3 wire type)
Forecast of Cause : 1. Terminal connection abnormal 2. Mis-setting 3. Wired Remote Control failure 4. Controller PCB failure
Detective details:
More than 1 time of Token (Communication between wired remote controllers)
is received, but it was not received more than 1 minute.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of Controller PCB Connector CNC01. (Power supply for Remote)
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote
lIf DC0V, Controller PCB failure (Remote is OK) >>> Replace Conroller PCB
In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
DC
04-11
Page 96
Trouble shooting 3 E12.3
INDOOR UNIT Error Method:
Number excess of device in Wired
remote contorller system (2 Wires RC)
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Forecast of Cause : 1. Wrong wiring of RCgroup 2. Indoor unit controller PCB failure
Detective details:
When the number of connecting Indoor unit and Remote controller in one
RCgroup exceeds more than 32 units.
Check Point 1 : Wire installation Wrong RCgroup setting
Wrong wire connection in RCgroup (Please refer to the installation manual)
The number of connecting indoor unit and Remote controller in one RCgroup were less than 32 units.
Check Point 2 : Check Indoor unit controller PCB
Check if controller PCB damage
Change controller PCB and check the Error after setting remote controller address
04-12
Page 97
Trouble shooting 4 E1 3. 1
OUTDOOR UNIT Error Method:
Communication Error Between
Outdoor unit
Indicate or Display:
Outdoor Unit : E. 1 3. 1
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code : 9 U / 1 3
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop 2. Power supply defective
3. The number setting mistake of outdoor unit
4. Connection of communication lines between outdoor units defective 5. Main PCB defective
Detective details:
Master unit: State in which "number of connected slave units" by Dip-SW and
the number of slave units which can be recognized by
communication did not match continued for 10 seconds or more
after the start of control.
Slave unit: State in which communication from the master unit was not
received continued for 10 seconds or more after the start of control.
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the power supply
Main power ON/OFF state check
Power cable connection, open check
OK
Check Point 3 : Check the number setting of outdoor units
Check the number setting of outdoor units.
Number of outdoor unit
1 unit
2 units
3 units
DIP-SW
SET 5-1
OFF
OFF
ON
DIP-SW
SET 5-2
OFF
ON
OFF
OK
Check Point 4 : Check the connection of communication lines
between outdoor units
Turn off the power and check.
Connection and open check of communication lines between outdoor units.
OK
Check Point 5 : Replace Main PCB
Change Main PCB and set up the original address.
04-13
Page 98
Trouble shooting 5 E14.1
OUTDOOR UNIT Error Method:
Outdoor Unit Network
Communication 1 Error
* Indoor unit indicates No display or 1 4
Peripheral device indicates 1 4 or 16.
Indicate or Display:
Outdoor Unit : E. 1 4. 1
Indoor Unit : No display /
Operation LED 1 times Flash, Timer LED 4 Times Flash,
Filter LED Continuous Flash.
Error Code : 1 4 / 1 6 / 1 4. 1 / 1 4. 3 *
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop 2. Indoor unit or RB unit power off
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Controller PCB defective
Detective details:
DIP-SW SET4-1 is OFF.
No communication for 180 seconds or more from an indoor unit which received
communication once and no Outdoor unit network communication 2 error.
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit or RB unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
Refer to SERVICE INFORMATION Network communication Abnormal
OK
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
OK
Check Point 5 : Check the communication PCB (outdoor unit/ indoor unit/ RB unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit/ indoor unit/ RB unit)
Change Main PCB and set up the original address.
04-14
Page 99
Trouble shooting 6 E14. 2
OUTDOOR UNIT Error Method ::
Outdoor Unit Network
Communication 2 Error
* Indoor unit indicates 9 U or 1 4
Peripheral device indicates 1 4 or 1 6
Indicate or Display:
Outdoor Unit : E. 1 4. 2
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash. /
Operation LED 1 times Flash, Timer LED 4 Times Flash,
Filter LED Continuous Flash. *
1. Noise, momentary open, voltage drop 2. Indoor unit or RB unit power off
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Control PCB defective
Detective details:
[DIP-SW SET4-1 : ON] (Factory setting)
No communication for 180 seconds or more from an indoor unit which
received communication once.
[DIP-SW SET4-1 : OFF]
No communication for 180 seconds or more from all indoor units that once
received communication.
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit or RB unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
Refer to SERVICE INFORMATION Network communication Abnormal
OK
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
OK
Check Point 5 : Check the communication PCB (outdoor unit/ indoor unit/ RB unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit/ indoor unit/ RB unit)
Change Main PCB and set up the original address.
04-15
Page 100
Trouble shooting 7 E14. 3
INDOOR UNIT Error Method:
Indoor unit Network communication
Error
* Outdoor unit indicates 1 4.1 or 1 4.2 (No communication from 14.3 Error Indoor unit)
Peripheral device indicates 1 4 or 1 6
Indicate or Display:
Outdoor Unit : E.1 4. 1 / 1 4. 2 *
Indoor Unit : Operation LED 1 times Flash, Timer LED 4 Times Flash,
Filter LED Continuous Flash.
Error Code : 1 4 / 1 6 / 9 U / 14.1 / 14.2 / 14.3 *
Detective Actuators:
Indoor unit Controller PCB circuit
Indoor unit Communication PCB
Detective details:
When the cut-off of network communication is detected (more than 90 seconds
passed since the last receipt of Outdoor unit signal).
Forecast of Cause : 1. Outside cause 2.Connection failure 3. Communication PCB failure 4. Controller PCB failure
Check Point 1 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit.
Momentary power failure ----- Check contact failure or leak current in power supply circuit
>>Check power supply for RB unit and Outdoor Unit as well.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which
causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
Check Point 2 : Check the connection
After turning off the power, check and correct followings.
Is Indoor Communication PCB loose?
Check loose or removed connection of communication line Indoor unit => RB unit => Outdoor unit.
Refer to SERVICE INFORMATION Network communication Abnormal
Check the Error indication of RB unit.
Refer to SERVICE INFORMATION RB Unit Abnormal
When the signal amplifier is connected , Check the error indication of signal amplifier. ( Refer to the installation manual)
OK
Check Point 3 : Check Communication PCB
Replace Communication PCB of the Indoor units that have the error.
If still the error is there, replace the communication PCB of the RB unit which corresponds to the error indicating Indoor unit.
OK
Check Point 4 : Check Controller PCB
Replace controller PCB of the Indoor units that have the error.
If still the error is there, replace the controller PCB of the RB unit which corresponds to the error indicating Indoor unit.
04-16
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.