Fujitsu ABU36RSLX Service manual

Page 1
R410A
3 . CEILING TYPE :
ABU36RSLX
D2D_AB016E/03
2007.06.11
Page 2
3-1. FEATURE
MODELS : ABU36RSLX / AOU36RLX
FEATURES
CEILING TYPE ABU36R
Installation
OPEN SPACE CONCEALED
Wide air flow
WALL MOUNTED
(for high-ceilinged room)
Fresh-air intake
Slender shape
A slender shape with curves harmonizes
Wide air flow
perfectly with the room interior.
Long-life filter
High efficiency long-life filter that extends the cleaning cycle up to 2 times that of the current model is standard.
INDOOR
Slender
OUTDOOR
CEILING TYPE ABU36R
Filter
Double auto swing
VERTICAL HORIZONTAL
SWING
Others
Auto Restart Detachable and Washable Open Panel
SWING
- (03 - 01) -
Page 3
3-2. REMOTE CONTROLLER
3-2-1.
FEATURES
CEILING TYPE ABU36R
WIRELESS REMOTE CONTROLLER
Wireless remote controller is an accessory of all indoor units.
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
F
Built-in timers
Select from four different timer programs (On/Off/Program/Sleep).
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
Four kinds of timers. Easy operation.
Can be used jointly with Wired remote controllers.
Easy to change transmission code (4 patterns) by button operation.
CEILING TYPE ABU36R
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 1.8 °F set temperature can rise up to a maximum of
3.6 °F
(2°C).
60min.
(1°C) every hour. The
Timer setting
1.8 °F(1°C)
3.6 °F (2°C)
Heating operation
When the sleep timer is set, the set temperature automatically drops 1.8 °F The set temperature can drop to a maximum of
7.2 °F
(4°C).
1.8 °F(1°C)
30min.
60min.
90min.
(1°C) every 30 minutes.
3.6 °F(2°C)
5.4 °F
7.2 °F
(3°C)
(4°C)
Timer setting
Simple operation
After code change
Mixed-up
• Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
A B C D
A B
C
D
•Wide and precise transmitting range.
1. Press the MASTER CONTROL button for more than five seconds to start the code change.
2. Press the (+) or (-) button to select the desired code.
A B C D
3. Press the MASTER CONTROL button again to end the code change.
- (03 - 02) -
Page 4
CEILING TYPE ABU36R
FUNCTIONS
Display
3
2
9
10
1
1
5
START/STOP button
Pressed to start and stop operation
64
AM
F
7
2
Set temp./Set time buttons/Set remote controller custom code buttons
Sets the indoor temp./Sets the current time and on-off time /Set R.C. custom code
3
Master control button/
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). Start/end R.C. custom code change. (Max. 4 types)
4
Sleep timer button
Code change
Pressed to select sleep timer.
11
5
Signal transmitter
8
6
Timer button
CEILING TYPE ABU36R
Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET)
7
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
8
Battery compartment lid
Display panel
13
14
15
AM PM
9
Air flow direction button
TEST
RUN
12
Used to set the desired air flow direction & swing function.
10
Time adjust button
Sets the current time.
11
ACL button
Used when replacing batteries or change the code.
12
Test run button
Used when testing the air conditioner after installation.
13
Transmit indicator
14
Clock display
15
16
F
17
18
19
20
Master control display
16
Timer mode display
17
Fan speed display
18
Set temperature display
19
Timer set indicator
20
Temperature set indicator
SPECIFICATION
SIZE [H x W x D in.(mm)] 6 - 7 / 32 x 2 - 13 / 64 x 25 / 32 (158 x 56 x 20)
WEIGHT oz.( g ) 2 - 15 / 32 (70)
- (03 - 03) -
Page 5
3-3. SPECIFICATIONS
ABU36RSLX
AOU36RLX
Fin Pitch
FPI
Fin Pitch
FPI
9 - 7/16 × 65 - 11/32 × 27 - 9/16 (240 × 1660 × 700)
32 - 11/16 × 35 - 7/16 × 13 (830 × 900 × 330)
12 - 17/32 × 70 - 7/8 × 31 - 3/32 (318 × 1800 × 790)
38 - 3/16 × 41 - 11/32 × 17 - 17/32 (970 × 1050 × 445)
3/8 (9.52)
5/8 (15.88)
Outer diameter 25.6 (1)
SEER
HSPF
OUTDOOR
INDOOR
Rows x Stages
Rows x Stages
OUTPUT
WEIGHT
NET
lb. (kg)
REFRIGERANT TYPE
REFRIGERANT OIL
TYPE
OPERATION(OUTDOOR)
TYPE
MODEL NAME
INDOOR
OUTDOOR
POWER SOURCE
AVAILABLE VOLTAGE RANGE
CAPACITY
COOLING
RATED/MAX
HEATING
RATED/MAX
CFM(m3/h)
OUTDOOR
INPUT POWER
kW
CURRENT
A
STARTING CURRENT
MOISTURE REMOVAL
AIR CIRCULATION COOL/HEAT
INDOOR
FAN SPEED COOL/HEAT INDOOR
r.p.m
OUTDOOR
FAN TYPE x Q'ty
FAN MOTOR OUTPUT
W
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
INDOOR
dB(A)
OUTDOOR
COMPRESSOR
TYPE
STARTING METHOD
HEAT EXCHANGER TYPE
INDOOR
Coil
Fin
OUTDOOR
Coil
Fin
CASING COLOR
DIMENSIONS H × W × D
in.(mm)
PIPE
CONNECTION METHOD
SIZE
in.(mm)
MAX LENGTH
MAX HEIGHT
NET
°F(°C)
REMOTE CONTROLLER TYPE
DRAIN PIPE
MATERIAL
SIZE
mm
(Reference in.)
GROSS
GROSS
CEILING MODELS
INVERTER HEAT PUMP
208/230V 60Hz
187-253V 60Hz
--SIROCCO × 4
PROPELLER × 1
160
100
DC TWIN ROTARY (INVERTER)
1300
Inverter
Copper tube
Aluminium
3 × 12
18
9 - 29/32 × 53 - 5/32 × 1 - 9/16 (252 × 1350 × 39.9)
Copper tube
Aluminium
Beige (10YR7.5/1.0NN)
2 × 38
20
31 - 13/32 × 35 - 7/16 × 1 - 7/16 (798 × 900 × 36.38)
White (5Y9/0.5NN)
FLARE
R410A
WIRELESS (Option WIRED)
ABS
Inner diameter 22.0 (7/8)
4lb. 14oz. (2200)
POE
0 to 115 (-18 to 46)
14 to 75 (-10 to 24)
COOLING RATED/MAX 4.22/4.35
HEATING RATED/MAX 3.50/4.35
COOLING RATED/MAX 18.3/18.8
HEATING RATED/MAX 15.3/18.8
COOLING 14.0
HEATING 8.5
High 1089(1850) / 1089(1850)
CEILING TYPE ABU36R
Med 977(1660) / 883(1500)
Low 842(1430) / 748(1270)
Quiet -
High 2119 (3600) / 2237 (3800)
Low -
High 1100/1100
Med 1000/900
Low 850/750
Quiet
High 850/900
Low
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High 48.0/48.0
Med 45.0/43.0
Low 41.0/39.0
kW 10.0/10.5
BTU/h 34,100/36,000
kW 10.7/12.5
BTU/h 36,500/42,700
A 10.0
pints/h(l/h) 7.4(3.5)
CEILING TYPE ABU36R
54.0/55.0
W
Coil Dimensions
Coil Dimensions
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR 106(48)
OUTDOOR 141(64)
INDOOR 134(61)
OUTDOOR 154(70)
LIQUID
GAS
CHARGE lb. oz. (g)
COOLING
HEATING
in.(mm)
in. (mm)
ft. (m) 164 (50) [chargeless:49 (15)]
ft. (m) 98 (30)
Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80.6°F(27°C)DB/66.2°F(19°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75.2°F(24°C)WB. Heating : Indoor temperature of 68.0°F(20°C)DB/59.0°F(15°C)WB,and outdoor temperature of 44.6°F(7°C)DB/42.8°F(6°C)WB. Pipe length : 24ft. 7in.(7.5m),Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]
- (03 - 04) -
Page 6
3-4. DIMENSIONS
3-4-1. OUTDOOR UNIT
CEILING TYPE ABU36R
MODEL : AOU36R
32-11/16 (830)
Unit : in.(mm)
Top view
35-7/16 (900)
13/16 (21)
(9)
11/32
Front view
3-1/32 (77)
1-7/32
(31)
13 (330)
15-3/4 (400)
15/32
(12)
CEILING TYPE ABU36R
Side view
25-19/32 (650)
Air flow
14-7/8 (370)
MOUNTING POSITION
When there are obstacles at the back or front sides.
AIR
23-5/8 (600) or more
3-15/16 (100) or more
Bottom view
When there are obstacles at the back, side(s), and top.
3-15/16 (100) or more
AIR
(
9-27/
Ser
11-13/16 (300) or more
32 (
v
i
250)
c
e
s
pac
or
mor
e)
e
3-29/32 (99)
(196)
7-23/32
5-25/32 (147)
6-11/16 (170)
When there are obstacles at the back, side with the installation of more than one unit.
23-5/8 (600)
or more
AIR
9-27/32 (250) or more
11-13/16 (300)
9-27/32 (250) or more
or more
- (03 - 05) -
Page 7
3-4-2. INDOOR UNIT
CEILING TYPE ABU36R
MODEL : ABU36R
6
(150)
5-29/32
7-7/8 (200)
3-3/4 (95)1-5/16 (33)
6-5/16 (160)
4-17/32
3-15/16
(115)
(100)
Side view
1-3/16
3-15/32
(30)
(88)
3-7/32
(82)
4-21/32
(118)
6-1/2 (165)
5-5/16 (135)
6-5/16
(160)
63 (1600)
Rear view
Unit : in.(mm)
(300)
11-13/16
CEILING TYPE ABU36R
5-1/8
(130)
14-11/16
45
4-1/2 (114) 5-9/16 (141)
(373)
14-11/16
(373)
6-5/16
(160)
5-13/32 (137)
2-9/16 (65)
6-5/16 (160)
5-29/32 (150)
1 2 3
Bottom view
Suspension bolt pitch
1-3/16 (30) 1-3/16 (30)
INDOOR UNIT (TOP VIEW)
INDOOR UNIT
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection [Drain pipe : I.D. 22mm(7/8"), O.D. 25.6mm(1")]
4
Knock out hole for fresh air
63 (1600)
Dimensions (Space Required
for Installation)
13/32 (10) 6-3/32 (155)
11-13/16 (300)
Suspension bolt should extend outward 1-3/16 (30) to 2-15/16 (75).
[ 200mm(7-7/8")],
7-9/16 (192)
5
Knock out hole for refrigerant piping
6
Hole for lifting bolt (Use M10 screw bolt)
- (03 - 06) -
Page 8
MOUNTING POSITION
Ceiling
INDOOR UNIT
Unit : in.(mm)
CEILING TYPE ABU36R
3-5/32(80) or over 5-29/32(150) or over
Ceiling
96(2400) or over
13/32(10) or over
39-3/8(1000)
or over
Obstruction
Floor
Ceiling panel
INDOOR UNIT
CEILING TYPE ABU36R
3-5/32(80) or over 5-29/32(150) or over
Ceiling panel
96(2400) or over
13/32(10) or over
39-3/8(1000)
or over
Obstruction
Floor
- (03 - 07) -
Page 9
3-5. REFRIGERANT CIRCUIT
MODELS : ABU36R / AOU36R
CEILING TYPE ABU36R
OUTDOOR UNIT
Condenser
Strainer
Pressure Check Valve
High Pressure Switch
4-way
Muffler
Valve
Expansion Valve
c
Compressor
Strainer
Accumulator
INDOOR UNIT
Refrigerant Pipe
5/8"(15.88mm )
Charging Valve
Evaporator
CEILING TYPE ABU36R
Refrigerant Pipe
3/8"(9.52mm )
Charging Valve
: COOL
: HEAT
c
(COMPRESSOR TEMP.)
- (03 - 08) -
Page 10
3-6. WIRING DIAGRAMS
3-6-1. OUTDOOR UNIT
MODEL : AOU36R
CEILING TYPE ABU36R
TEMP.
TEMP.
TEMP.
TEMP.
TEMP.
CEILING TYPE ABU36R
POSISTOR
G
TO INDOOR UNIT
G
TO POWER SUPPLY
- (03 - 09) -
Page 11
3-6-2. INDOOR UNIT
MODEL : ABU36R
CEILING TYPE ABU36R
CEILING TYPE ABU36R
TO REMOTE CONTROL UNIT
(N)
TO OUTDOOR UNIT
- (03 - 10) -
Page 12
3-7. CAPACITY TABLE
Outdoor temperature
54°FWB
60°FWB
63°FWB
64°FDB
70°FDB
71°FWB
73°FWB
90°FDB
67°FWB
80°FDB
85°FDB
Indoor temperature
75°FDB
21.11°CDB
Outdoor temperature
29.44°CDB
23.89°CDB
21.67°CWB
15.56°CWB
17.72°CWB
19.44°CWB
Indoor temperature
17.78°CDB
12.22°CWB
32.22°CDB
22.78°CWB
26.67°CDB
MODELS : ABU36R / AOU36R
COOLING
AFR 1089
CEILING TYPE ABU36R
(°FDB)
AFR : Air flow rate(CFM) TC : Total capacity (kBTU)
AFR 30.8
(°CDB)
-17.78 7.81 6.67 1.36 8.81 6.71 1.38 9.30 7.35 1.39 9.97 7.69 1.41 10.63 7.94 1.43 10.96 8.80 1.43
-10.00 7.70 6.35 1.56 8.68 6.39 1.59 9.17 7.00 1.60 9.82 7.33 1.62 10.48 7.57 1.64 10.81 8.39 1.65
10.00 8.37 6.23 2.51 9.44 6.27 2.56 9.97 6.87 2.58 10.68 7.19 2.61 11.39 7.42 2.64 11.75 8.22 2.65
15.00 8.96 6.49 2.10 10.11 6.53 2.14 10.68 7.16 2.16 11.44 7.49 2.18 12.21 7.74 2.21 12.59 8.57 2.22
19.44 8.45 6.27 2.32 9.53 6.31 2.36 10.07 6.91 2.38 10.79 7.23 2.40 11.51 7.47 2.43 11.87 8.28 2.44
25.00 8.86 6.45 3.11 9.99 6.49 3.17 10.56 7.11 3.19 11.31 7.44 3.23 12.07 7.68 3.27 12.44 8.52 3.28
30.56 8.08 6.10 3.39 9.12 6.14 3.45 9.63 6.73 3.48 10.32 7.04 3.52 11.01 7.27 3.55 11.35 8.06 3.57
35.00 8.26 6.17 4.19 9.32 6.20 4.27 9.84 6.80 4.30 10.50 7.11 4.35 11.25 7.34 4.40 11.60 8.14 4.42
40.00 6.63 5.58 3.37 7.48 5.61 3.43 7.90 6.15 3.46 8.46 6.43 3.50 9.03 6.64 3.54 9.31 7.36 3.56
46.11 4.61 4.72 2.46 5.20 4.75 2.50 5.50 5.20 2.52 5.89 5.44 2.55 6.28 5.62 2.58 6.48 6.23 2.59
AFR : Air flow rate(m3/min) TC : Total capacity (kW ) SHC : Sensible Heat capacity (kW) PI : Power Input (kW)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0 26.66 22.76 1.36 30.07 22.90 1.38 31.76 25.09 1.39 34.03 26.25 1.41 36.30 27.11 1.43 37.44 30.05 1.43
14 26.27 21.69 1.56 29.63 21.82 1.59 31.30 23.91 1.60 33.54 25.01 1.62 35.78 25.83 1.64 36.90 28.63 1.65
32 24.86 22.24 1.19 28.04 22.38 1.21 29.62 24.52 1.22 31.73 25.65 1.24 33.86 26.49 1.25 34.91 29.36 1.26
41 26.60 22.53 1.36 30.00 22.67 1.38 31.69 24.84 1.39 33.95 25.99 1.41 36.22 26.84 1.42 37.35 29.75 1.43
50 28.57 21.27 2.51 32.22 21.40 2.56 34.04 23.45 2.58 36.46 24.53 2.61 38.90 25.34 2.64 40.12 28.08 2.65
59 30.60 22.17 2.10 34.51 22.31 2.14 36.46 24.44 2.16 39.06 25.57 2.18 41.67 26.41 2.21 42.97 29.27 2.22
67 28.86 21.40 2.32 32.55 21.53 2.36 34.39 23.59 2.38 36.84 24.68 2.40 39.30 25.49 2.43 40.53 28.26 2.44
77 30.25 22.03 3.11 34.12 22.16 3.17 36.04 24.28 3.19 38.61 25.40 3.23 41.20 26.24 3.27 42.48 29.08 3.28
87 27.60 20.84 3.39 31.13 20.97 3.45 32.89 22.97 3.48 35.23 24.04 3.52 37.59 24.82 3.55 38.77 27.51 3.57
95 28.20 21.05 4.19 31.81 21.18 4.27 33.60 23.20 4.30 36.00 24.27 4.35 38.41 25.07 4.40 39.61 27.79 4.42
104 22.63 19.04 3.37 25.52 19.15 3.43 26.96 20.98 3.46 28.88 21.95 3.50 30.82 22.67 3.54 31.78 25.13 3.56
115 15.75 16.10 2.46 17.77 16.20 2.50 18.77 17.75 2.52 20.11 18.57 2.55 21.45 19.18 2.58 22.12 21.26 2.59
SHC : Sensible Heat capacity (kBTU) PI : Power Input (kW)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0.00 7.28 6.51 1.19 8.21 6.55 1.21 8.68 7.18 1.22 9.30 7.51 1.24 9.92 7.76 1.25 10.23 8.60 1.26
5.00 7.79 6.60 1.36 8.79 6.64 1.38 9.28 7.28 1.39 9.94 7.61 1.41 10.61 7.86 1.42 10.94 8.71 1.43
CEILING TYPE ABU36R
- (03 - 11) -
Page 13
HEATING
Outdoor temperature
60°FDB
65°FDB
Indoor temperature
70°FDB
75°FDB
78°FDB
25.56°CDB
21.11°CDB
23.89°CDB
15.56°CDB
18.33°CDB
Outdoor temperature
Indoor temperature
AFR 1089
CEILING TYPE ABU36R
(°FDB) (°FWB)
14 12 29.50 3.73 28.55 3.84 27.59 3.95 26.63 4.06 26.05 4.13
23 19 34.32 3.99 33.21 4.10 32.09 4.22 30.98 4.34 30.31 4.41
32 28 39.47 4.11 38.19 4.23 36.91 4.35 35.62 4.47 34.85 4.54
41 37 41.37 4.11 40.03 4.23 38.68 4.35 37.34 4.47 36.53 4.54
47 43 45.67 4.11 44.19 4.23 42.70 4.35 41.22 4.47 40.33 4.54
50 47 47.32 4.11 45.79 4.23 44.25 4.35 42.71 4.47 41.79 4.54
59 50 50.35 4.11 48.72 4.23 47.08 4.35 45.45 4.47 44.46 4.54
68 59 44.07 3.31 42.64 3.40 41.21 3.50 39.78 3.60 38.92 3.66
75 65 46.30 3.31 44.80 3.40 43.29 3.50 41.79 3.60 40.88 3.66
AFR : Air flow rate(CFM) TC : Total capacity (kBTU)
AFR 30.8
(°CDB) (°CW B)
-10.00 -11.11 8.64 3.73 8.36 3.84 8.08 3.95 7.80 4.06 7.63 4.13
-5.00 -7.22 10.05 3.99 9.73 4.10 9.40 4.22 9.07 4.34 8.88 4.41
0.00 -2.22 11.56 4.11 11.19 4.23 10.81 4.35 10.43 4.47 10.21 4.54
5.00 2.78 12.12 4.11 11.72 4.23 11.33 4.35 10.94 4.47 10.70 4.54
8.33 6.11 13.38 4.11 12.94 4.23 12.50 4.35 12.07 4.47 11.81 4.54
10.00 8.33 13.86 4.11 13.41 4.23 12.96 4.35 12.51 4.47 12.24 4.54
15.00 10.00 14.75 4.11 14.27 4.23 13.79 4.35 13.31 4.47 13.02 4.54
20.00 15.00 12.91 3.31 12.49 3.40 12.07 3.50 11.65 3.60 11.40 3.66
23.89 18.33 13.56 3.31 13.12 3.40 12.68 3.50 12.24 3.60 11.97 3.66
AFR : Air flow rate(m3/min) TC : Total capacity (kW ) PI : Power Input (kW )
TC PI TC PI TC PI TC PI TC PI
PI : Power Input (kW)
TC PI TC PI TC PI TC PI TC PI
CEILING TYPE ABU36R
- (03 - 12) -
Page 14
3-8. CAPACITY COMPENSATION FOR PIPE LENGTH
30m 98ft. - - - - 0.960 0.935 0.913
-5m -16ft. 0.992 0.992 0.981 0.975 0.952 0.928 0.906
COOLING
PIPE LENGTH
Outdoor unit
is bottom-side
HEIGHT DIFFERENCE
Outdoor unit
is up-side
30m 98ft. - - - - 0.906 0.885 0.872
-5m -16ft. 1.000 1.000 0.969 0.957 0.934 0.912 0.899
PIPE LENGTH
Outdoor unit
is bottom-side
Outdoor unit
is up-side
HEIGHT DIFFERENCE
HEATING
AND HEIGHT DIFFERENCE
MODELS : ABU36R / AOU36R
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
5 m 7.5 m 15 m 20 m 30 m 40 m 50 m
16 ft. 25 ft. 49 ft. 66 ft. 98 ft. 131 ft. 164 ft.
20m 66ft. - - - 0.983 0.960 0.935 0.913
10m 33ft. - - 0.989 0.983 0.960 0.935 0.913
CEILING TYPE ABU36R
7.5m 25ft. - 1.000 0.989 0.983 0.960 0.935 0.913
CEILING TYPE ABU36R
5m 16ft. 1.000 1.000 0.989 0.983 0.960 0.935 0.913
0m 0 ft. 1.000 1.000 0.989 0.983 0.960 0.935 0.913
-7.5m -25ft. - 0.988 0.977 0.971 0.948 0.924 0.902
-10m -33ft. - - 0.973 0.967 0.945 0.920 0.898
-20m -66ft. - - - 0.952 0.929 0.905 0.884
-30m -98ft. - - - - 0.914 0.890 0.869
5 m 7.5 m 15 m 20 m 30 m 40 m 50 m
16 ft. 25 ft. 49 ft. 66 ft. 98 ft. 131 ft. 164 ft.
20m 66ft. - - - 0.938 0.915 0.894 0.881
10m 33ft. - - 0.959 0.947 0.925 0.903 0.890
7.5m 25ft. - 0.993 0.962 0.950 0.927 0.905 0.892
5m 16ft. 0.995 0.995 0.964 0.952 0.929 0.907 0.895
0m 0 ft. 1.000 1.000 0.969 0.957 0.934 0.912 0.899
-7.5m -25ft. - 1.000 0.969 0.957 0.934 0.912 0.899
-10m -33ft. - - 0.969 0.957 0.934 0.912 0.899
-20m -66ft. - - - 0.957 0.934 0.912 0.899
-30m -98ft. - - - - 0.934 0.912 0.899
- (03 - 13) -
Page 15
3-9. ADDITIONAL CHARGE CALCULATION
49 66 98 131 164 (MAX)
15 20 30 40 50 (MAX)
ADDITIONAL CHARGE
PIPE LENGTH
0.43 oz./ft. 40g/m
4 lb. 14 oz. (2200)
R410A
MODELS : ABU36R / AOU36R
REFRIGERANT TYPE
REFRIGERANT AMOUNT lb. oz. (g)
REFRIGERANT CHARGE
ft.
m
lb. oz. 0 (Chargeless) 7.3 oz. 1 lb. 5.1 oz. 2 lb. 3.3 oz. 3 lb. 1.5 oz.
g 0 (Chargeless) 200 600 1000 1400
CEILING TYPE ABU36R
CEILING TYPE ABU36R
- (03 - 14) -
Page 16
3-10. OPERATION RANGE
Cooling
Dry
64 to 88°F
(18 to 31°C)
0 to 115°F
(-18 to 46°C)
60 to 86°F
(16 to 31°C)
14 to 75°F
(-10 to 24°C)
ABU36R
AOU36R
Model
Mode
Operation Range
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
About 80% or less
CEILING TYPE ABU36R
Heating
-
CEILING TYPE ABU36R
- (03 - 15) -
Page 17
3-11. FAN PERFORMANCE AND AIR FLOW
3-11-1. AIR VELOCITY DISTRIBUTION
MODEL : ABU36R
CEILING TYPE ABU36R
Unit : ft./s(m/s)
13/16(0.25)
14 10
10 14
(m)(ft.)
4 3 2
7
1
3
7(2)
0
0
1
3
2
7
3(1)
2(0.5)
3 4
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 0 7 14 20 26 32 39 45 52 59
TOP VIEW VERTICAL FLAP : UP HORIZONTAL FLAP : CENTER
Unit : ft./s(m/s)
13/16(0.25)
13/16(0.25)
14 10
10 14
(m)(ft.)
4 3 2
7
1
3
7(2)
0
0
1
3
2
7
3(1)
3(1)
2(0.5)
2(0.5)
3 4
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 0 7 14 20 26 32 39 45 52 59
TOP VIEW VERTICAL FLAP : UP HORIZONTAL FLAP : RIGHT AND LEFT
Unit : ft./s(m/s)
13/16(0.25)
10
(m)(ft.)
3
7(2)
2
7
3(1)
2(0.5)
(m) (ft.)
(m) (ft.)
Note :
Condition
Fan speed : High Operation mode :FAN
(m)(ft.)
3
10
7(2)
2
7
1
3
0
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
3(1)
2(0.5)
Unit : ft./s(m/s)
13/16(0.25)
0 7 14 20 26 32 39 45
SIDE VIEW VERTICAL FLAP : CENTER HORIZONTAL FLAP : CENTER
(m)(ft.)
3
10
7
(2)
2
7
3
0
3
(1)
1
0
2
13/16(0.25)
(0.5)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Unit : ft./s(m/s)
0 7 14 20 26 32 39 45
SIDE VIEW VERTICAL FLAP : DOWN HORIZONTAL FLAP : CENTER
CEILING TYPE ABU36R
(m) (ft.)
(m) (ft.)
1
3
0
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 0 7 14 20 26 32 39 45 52 59
SIDE VIEW VERTICAL FLAP : UP HORIZONTAL FLAP : CENTER
(m) (ft.)
- (03 - 16) -
Page 18
3-11-2. AIR FLOW
m3/h
1850
m3/h
1660
m3/h
1430
m3/h
3600
1100
1000
850
850
Indoor unit
Outdoor unit
HIGH
MED
LOW
HIGH
FAN SPEED
NUMBER OF
ROTATIONS
(r.p.m)
AIR FLOW
MODELS : ABU36R / AOU36R
CEILING TYPE ABU36R
l/s 514
CFM 1089
l/s 461
CEILING TYPE ABU36R
CFM 977
l/s 397
CFM 842
l/s 1000
CFM 2119
- (03 - 17) -
Page 19
3-11-3. FRESH AIR
FRESH AIR CHARACTERISTIC
CEILING TYPE ABU36R
0.39
0.2
(Pa)
98
49
10
8
6
4
2
13/32
5/16
1/4
5/32
3/32
(in.WG) (mmAq) (in.Ag)
INTAKE DUCT STATIC PRESSURE
CEILING TYPE ABU36R
3
(m /min)
3
(ft /min)
0 1 2 3 4 5 6 7
35 71 106 141 177 212 247
FRESH AIR FLOW (m /min)
3
0
0
- (03 - 18) -
Page 20
3-12. NOISE LEVEL CURVE
3-12-1. OUTDOOR UNIT
CEILING TYPE ABU36R
COOLING
MODEL : AOU36R
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
MODEL : AOU36R
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
CEILING TYPE ABU36R
0
63 1 25 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
0
63 1 25 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
- (03 - 19) -
Page 21
SOUND LEVEL CHECK POINT
CEILING TYPE ABU36R
3ft. 3-3/8in. (1m)
CEILING TYPE ABU36R
- (03 - 20) -
Page 22
3-12-2. INDOOR UNIT
HIGH
LOW
HIGH
LOW
CEILING TYPE ABU36R
COOLING
MODEL : ABU36R
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
MODEL : ABU36R
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
CEILING TYPE ABU36R
0
63 1 25 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
0
63 1 25 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
- (03 - 21) -
Page 23
SOUND LEVEL CHECK POINT
UNDER CEILING
3ft. 3-3/8in.(1m)
3ft. 3-3/8in. (1m)
MIC
CEILING TYPE ABU36R
CEILING TYPE ABU36R
- (03 - 22) -
Page 24
3-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current
60
ABU36R
AOU36R
10
Rated Value
Mode
*1) Wiring Spec.
10
30
Max Operating Current
Starting Current
0.59
0.14
0.63
Model Name
Outdoor Fan Motor
0.13
95
Indoor Fan Motor
Power Supply
230
Indoor unit
Outdoor unit
MODELS : ABU36R / AOU36R
Voltage V
Frequency Hz
Current A 18.3 15.3
Input kW 4.22 3.50
Cooling Heating
A 18.8 18.8
CEILING TYPE ABU36R
A
A
Power Cable AWG
*2)Limited wiring length ft.
Input kW
Full Load Amp. A
Input kW
Full Load Amp. A
*1) Wiring Spec. : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
CEILING TYPE ABU36R
- (03 - 23) -
Page 25
3-14. SAFETY DEVICE
PROTECTION FORM
OFF : 609±15 psi
ON : 464±22 psi
OFF : 4.2±0.1MPa ON : 3.2±0.15MPa
OFF : 248±9°F
ON : 176±9°F
OFF : 120±5°C
ON : 80±5°C
OFF : 266±9°F
ON : 176±9°F
OFF : 130±5°C
ON : 80±5°C
5A 250V
AOU36R
3.15A 250V
FUSE ON MAIN PCB
CURRENT FUSE
PROTECTION FORM
ABU36R
3.15A 250V
OUTDOOR UNIT
CEILING TYPE ABU36R
FAN MOTOR PROTECTION THERMAL PROTECTOR
HIGH PRESSURE PROTECTION PRESSURE SWITCH
DISCHARGE THERMISTOR THERMAL PROTECTOR
COMPRESSOR THERMISTOR THERMAL PROTECTOR
212
+27
-18
°F
100 °C
INDOOR UNIT
PCB FUSE CURRENT FUSE
FAN MOTOR PROTECTION THERMAL PROTECTOR 248±9°F 120±5°C
+15
-10
CEILING TYPE ABU36R
- (03 - 24) -
Page 26
3-15. FUNCTION SETTING
Auto restart validity/invalidity
Room temperature correct coefficient
Room temperature correct coefficient
Forbidden
Indoor unit number setting
Forbidden
Remote control unit signal code
Ceiling height setting
INDOOR UNIT
DIP SW
3
1
JM3
Jumper Wire
2
3
JM1
JM2
Rotary SW
SW 2
SW 1
SW 4
1
2
3-15-1. INDOOR UNIT
CEILING TYPE ABU36R
CEILING TYPE ABU36R
SWITCH POSITION
Indoor unit control circuit board
- (03 - 25) -
Page 27
3-15-2. SWITCH FUNCTION (INDOOR UNIT)
SW 1-1
SW state
OFF
Invalidity
ON
Validity
0 degF
0 degF
0 degF
cooling
-3.6degF
SW 1-2
SW 1-3
0 degF
heating
dry
-3.6degF
-3.6degF
ONONON
OFF
OFF
+3.6degF
-3.6degF
OFF
SW state
-3.6degF
OFF
ON
0 degF
+7.2degF
3
OFF
-
ON
Normal
High ceiling 1
High ceiling 2
Low ceiling
-ONON-OFF
-
ON
OFF
OFF
Ceiling height ft.(m)
DIP - SW4
1
2
DIP SWITCH SETTING
SW1-1. Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
( Factory setting)
CEILING TYPE ABU36R
SW1-2, 1-3. Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient value of heating.
TEMPERATURE CORRECTION
( Factory setting)
When used for Floor console type
SW4-1. REMOTE CONTROLLER SETTING
( Factory setting)
SW 4-1
OFF
ON
Wireless Remote Controller
Wired Remote Controller (option)
SW state
CEILING TYPE ABU36R
SW4-2, 4-3. Ceiling height setting
8ft. 2-7/16in. to 9ft. 10-1/8in. (2.5 to 3.0)
9ft. 10-1/8in. to 11ft. 5-25/32in. (3.0 to 3.5)
More than 11ft. 5-25/32in. (3.5)
Less than 8ft. 2-7/16in. (2.5)
If the setting for a low ceiling is selected, the capacity of the air conditioner decreases slightly.
- (03 - 26) -
( Factory setting)
Page 28
BCD
Disconnect
Disconnect
Disconnect
Disconnect
connect
connect
JM3
Remote control unit
signal code
connect
connect
A
JM2
Jumper wire
ROTARY SWITCH SETTING
0
Single
1 - 15
Indoor unit address
SW 2
SW state
(This function operates only when optional wired remote controller is used.)
This switch can be used when group control system. Set the indoor unit address in the 0,1,-,15 order.
( Factory setting)
CEILING TYPE ABU36R
JUMPER WIRE SETTING
JM 1, 2, 3 setting
( Factory setting)
CEILING TYPE ABU36R
- (03 - 27) -
Page 29
3-16. OPTIONAL PARTS
3-16-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
CEILING TYPE ABU36R
SUMOTUWETH FR SA
AM
7
3126 9
F
15 18 21
High performance and compact size
Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.)
Easy installation with a slim shape with no boldge in the back.
Built in room temperature sensor.
CEILING TYPE ABU36R
Three functions are combined in one unit.
Wired
remote
controller
Built-in timers
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
PM
3126 9
15 18 21
Setup screen example [Set to Wednesday: AM8:00 to PM8:00,75 °F(24 °C)]
0 3 6 9 12 15 18 21
time O'clock time O'clock
12 3 6 9 12 3 6 9
At "Weekly timer" + "Set back timer" setup
Easy-to-understand time bar display
SUMOTUWETH FR SA
AM
7
3126 9
F
15 18 21
75°F (24°C)
AM PM
75°F 82°F 75°F
(24°C 28°C 24°C)
Weekly
timer
Setback
timer
Setback timerWeekly timer
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
Screen after setup
Setup screen example [Set from Sunday to Saturday: PM12:00 to PM3:00, 82°F(28 °C)]
0 3 6 9 12 15 18 21
12 3 6 9 12 3 6 9
75°F (24°C)
0 3 6 9 12 15 18 21
time O'clock
12 3 6 9 12 3 6 9
AM PM
PM
3126 9
15 18 21
82°F (28°C)
AM PM
82°F (28°C)
F
Easy-to-understand operation Simple installation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
Timer area
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
Operation area
European switch box
- (03 - 28) -
JIS box
Page 30
CEILING TYPE ABU36R
FUNCTIONS
Display
2 7 8
9
10
11
12
Display panel
SET BACK
16
SUMOTUWETH FR
AM PM
369
SUMOTUWETH FR
AM PM
369
CLOCK ADJUST
DELETE SET
12 15 18 21
12 15 18 21
DAY
DAY OFF
1
START/STOP button
Pressed to start and stop operation.
2
Set Temperature button
SA
F
15
1 3
ENERGY
SAVE
THERMO
SENSOR
4 6 5
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
13
14
6
Thermo sensor button
Selects whether the room temperature is detected at the
CEILING TYPE ABU36R
indoor unit (remote sensor) or the remote controller.
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
17
1819 20
SA
F
9
Set back button
pressed select the set back timer.
10
Set time button
Pessed to select the set back timer.
Delete button
2122 2324 25
11
The schedule of a weekly timer is deleted.
12
Set button
Sets the date, hour, minute and on-off time.
13
Horizontal air flow direction and swing button
Push for two seconds to change the swing mode.
14
Vertical air flow direction and swing button
Push for two seconds to change the swing mode
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
Operation mode display
18
Fan speed display
Central control display
19
20
Temperature display
21
Stand by display Indicates during defrosting operation.
22
Vertical swing display
23
Horizontal swing display
24
Energy save display
25
SPECIFICATION
Thermo sensor display
SIZE [(H x W x D in.) mm] 4-23/32 x 4-23/32 x 43/64 (120 x 120 x 17)
WEIGHT oz.( g ) 5-21/32 (160)
CABLE LENGTH ft.( m )
POWER ( V )
33 (10)
12
- (03 - 29) -
Page 31
3-16-2. WIRED REMOTE CONTROLLER CIRCUIT BOARD
Wired remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
CEILING TYPE ABU36R
SWITCH POSITION
Wired remote controller
Front case (back side)
DIP Switch
OFF
CEILING TYPE ABU36R
ON
1 2 3 4 5 6
ON
- (03 - 30) -
Page 32
3-16-3. WIRED REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
( Factory setting)
Number of remote controller
1 (Normal)
2 (Dual)
CEILING TYPE ABU36R
1-2 Group control setting
Number of indoor unit connection (One/Multiple) This is switched according to the number of connected indoor units.
DIP-SW No.3
OFF
Master unit Slave unit
DIP-SW No.1
DIP-SW No.2
ON
OFF
( Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW No.1
ON ON
DIP-SW No.2
CEILING TYPE ABU36R
ON Multiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( Factory setting)
DIP-SW No.4
OFF
ON Cooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
( Factory setting)
DIP-SW No.5
OFF
ON Validity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.If batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
( Factory setting)
DIP-SW No.6
OFF
ON Validity
Memory backup
Invalidity
- (03 - 31) -
Page 33
3-16-4. OPTIONAL PARTS
Drain water riser kit (UTR-DPB241)
Optional drain lift-up mechanism allows more flexible installation.
ROUND FLANGE (UTD - RF204)
CEILING TYPE ABU36R
Round flange is used when the fresh air duct is installed.
Ø8-1/16(205)
Ø7-11/16(195)
CEILING TYPE ABU36R
UNIT : in.(mm)
)
5
3
2
(
4
/
1
-
9
Ø
Ø
8
-
2
7
/
3
2
(
2
2
5
)
Ø3-11/32
(85)
Round flange
- (03 - 32) -