Fujitsu AB*F18LAT, AB*F14LAT, AB*F24LAT, AR* 9LUAB, AR*12LUAD Service Instruction

...
Models Indoor unit Outdoor unit
AB*14LBAJ AB*18LBAJ AB*24LBAJ AB*F14LAT AB*F18LAT AB*F24LAT
AR* 9LUAB AR*12LUAD AR*14LUAD AR*18LUAD AR*22LUAD AR*F09LALU AR*F12LALU AR*F14LALU AR*F18LALU AR*F22LALU
AO*18LMAK2 AO*24LMAM2 AO*30LMAW4
SERVICE
INSTRUCTION
R410A
AU*12LBAB AU*14LBAB AU*18LBAB AU*F09LAL AU*F12LAL AU*F14LAL AU*F18LAL
AS*18LBAJ AS*24LBAJ AS* 7LMACW AS* 9LMACW AS*12LMACW AS*A07LACM AS*A09LACM AS*A12LACM AS*A14LACM AS*A18LACM
AG*F09LAC AG*F12LAC AG*F14LAC
SPLIT TYPE ROOM AIR CONDITIONER
INVERTER MULTI
Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. CAPACITY CONTROL................................................................................................
3. INDOOR FAN CONTROL...........................................................................................
2. AUTO CHANGEOVER OPERATION..........................................................................
5. LOUVER CONTROL...................................................................................................
4. OUTDOOR FAN CONTROL.......................................................................................
7. TIMER OPERATION CONTROL................................................................................
6. COMPRESSOR CONTROL........................................................................................
9. TEST OPERATION CONTROL..................................................................................
8. ELECTRONIC EXPANSION VALVE CONTROL........................................................
11. 4-WAY VALVE EXTENSION SELECT.......................................................................
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )................................
13. MANUAL AUTO OPERATION...................................................................................
12. AUTO RESTART........................................................................................................
15. FRESH AIR CONTROL..............................................................................................
14. COMPRESSOR PREHEATING..................................................................................
18. DEFROST OPERATION CONTROL..........................................................................
16. EXTERNAL ELECTRICAL HEATER CONTROL........................................................
19. DRAIN PUMP OPERATION.......................................................................................
21. VARIOUS PROTECTIONS.........................................................................................
20. ENERGY SAVE FUNCTION.......................................................................................
01-01 01-01 01-02 01-11 01-12 01-21 01-22 01-26 01-26 01-26 01-26
01-27 01-27 01-27
01-28
01-29
17. COIL DRY OPERATION CONTROL........................................................................... 01-28
01-32 01-32 01-33
01-27
2-1-2 OUTDOOR UNIT DISPLAY................................................................................
2-1-1 INDOOR UNIT DISPLAY....................................................................................
2-1 ERROR DISPLAY......................................................................................................
2. TROUBLE SHOOTING
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
2-4 SERVICE PARTS INFORMATION............................................................................
02-01 02-01 02-06
2-1-3 WIRED REMOTE CONTROLLER DISPLAY......................................................
02-07
02-44
02-11
02-49
1-1-1 PARTS LAYOUT DRAWING...............................................................................
1-1-2 WIRING................................................................................................................
1-1-3 DISASSEMBLY PROCESS.................................................................................
1-1 For AO*18LMAK2/ 24LMAM2.................................................................................
1 REPLACEMENT PARTS ( For OUTDOOR UNIT ).......................................................
3. REPLACEMENT PARTS
03-01 03-01 03-01
03-04
03-03
1-2-1 PARTS LAYOUT DRAWING...............................................................................
1-2-2 WIRING................................................................................................................
1-2-3 DISASSEMBLY PROCESS.................................................................................
1-2-4 ASSEMBLY PROCESS of INVERTER UNIT......................................................
1-2 For AO*30LMAW4..................................................................................................
03-08 03-08
03-11
03-10
03-16
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
INVERTER (MULTI )
Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type
2. AUTO CHANGEOVER OPERATION
01-01
1. CAPACITY CONTROL
1-1 COOLING, HEATING, DRY CAPACITY CONTROL
Compressor frequency decides by capacity of an indoor unit, operation number of an indoor unit, set temperature, room temperature and outside temperature.
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING and MONITORING modes. During operation, the optimum mode is automatically swiched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1 degC steps.
When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo) After 1 minute, depends on the room temperature and outdoor unit's operarion mode, the operation mode is selected in accordance with the table below.
( Table 1-1 : Operation mode selection table )
1
Room temperature :TR
Operation mode
TR > Ts +2 degC
Ts +2 degC > TR
=
=
Ts +2 degC > TR > Ts-2 degC
Cooling
Monitoring
Heating
Ts : Setting temperature TR: Room temperature
( Table 1-2 : Operation mode selection table for AS*18/ 24LBAJ )
Room temperature :TR
Operation mode
TR > Ts +2.5 degC
Ts +2.5 degC > TR
=
=
Ts +2.5 degC > TR > Ts-2.5 degC
Cooling
Monitoring
Heating
Ts : Setting temperature TR: Room temperature
When COOLING was selected at , the same operation as COOLING OPERATION is performed.
When HEATING was selected at , the same operation as HEATING OPERATION is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at above, operation is switched to MONITORING and the operation mode is selected again.
1
2
3
1
4
1
3. INDOOR FAN CONTROL
1. Fan speed
( Table 2 : Indoor Fan Speed )
01-02
Operation mode Air flow mode Speed (rpm)
Hi 850
760 670
Me
Lo
Cooling
S-Lo
Heating
AB*14LBAJ
Operation mode Air flow mode Speed (rpm)
Hi 1030
890 770
250
Operation mode Air flow mode Speed (rpm)
Hi 1180
1040
900
Me
Lo
Cooling
S-Lo
Heating
AB*24LBAJ
300
250
Me
Lo
Cooling
S-Lo
Heating
Cooling Heating
Cooling Heating
Cooling Heating
Cooling Heating
AB*18LBAJ
Operation mode Air flow mode Speed (rpm)
Hi 955
870 800 650
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 750
680 610 550
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1000
860 720 570
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1040
890 750 595
Me
Lo
S-Lo
AR*9LUAB
AR*14LUAD
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1270
1050
800 595
Me
Lo
S-Lo
AR*22LUAD
AR*12LUAD
AR*18LUAD
Cooling Heating
Cooling Heating
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 850
800 740 670 300
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1040
950 800 740 300
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1230
1040
900 780 300
Me
Lo
Quiet
S-Lo
AB*F14LAT
AB*F24LAT
AB*F18LAT
01-03
Cooling Heating
Cooling Heating
AU*12/ 14LBAB
--- ---
AU*18LBAB
AU*F09LAL AU*F12LAL
Operation mode Air flow mode Speed (rpm)
Hi 730
670 590
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 800
700 600
Me
Lo
S-Lo
Cooling Heating
Cooling Heating
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1010
950 880 830 450
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 790
720 620 570 330
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 990
880 770 620 330
Me
Lo
Quiet
S-Lo
AR*F09LALU
AR*F14LALU
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1320
1100
980 780 450
Me
Lo
Quiet
S-Lo
AR*F22LALU
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1040
950 840 700 450
Me
Lo
Quiet
S-Lo
AR*F18LALU
AR*F12LALU
Operation mode Air flow mode
Speed (rpm)
Hi 660
580 520 460
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
650
580
Me+
620
520 460 460 300
Auto S- Lo
Cooling Fan
Heating
Operation mode Air flow mode
Speed (rpm)
Hi 590
540 490 440
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
590
540
Me+
570
490 440 460 300
Auto S- Lo
Cooling Fan
Heating
Operation mode Air flow mode
Speed (rpm)
Hi 730
630 540 460
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
740
670
Me+
700
600 480 460 300
Auto S- Lo
Cooling Fan
Heating
AU*F14LAL
Operation mode Air flow mode
Speed (rpm)
Hi 790
660 570 460
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
840
750
Me+
800
650 500 460 300
Auto S- Lo
Cooling Fan
Heating
AU*F18LAL
01-04
Cooling Heating
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1160
1000
830 780 550
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1290
1100
870 730 550
Me
Lo
Quiet
S-Lo
AS*18LBAJ AS*24LBAJ
Operation mode Air flow mode
Speed (rpm)
Louver position Louver position
Hi 1100
1050 1000
950
950 500
Me
Lo
Cooling Fan
Quiet
Quiet
Hi 1120
1070 1000
930 500
1100 1030
970
Me
Lo
Heating
AS*7LMACW
S- Lo
1
4
5
6
3
2
1
4
5
6
3
2
Operation mode Air flow mode
Speed (rpm)
Louver position Louver position
Hi 1200
1100 1000
940
940 500
Me
Lo
Cooling Fan
Quiet
Quiet
Hi 1200
1100 1000
900 500
1150 1050
960
Me
Lo
Heating
AS*9LMACW
S- Lo
1
4
5
6
3
2
Operation mode Air flow mode
Speed (rpm)
Louver position Louver position
Hi 1310
1260 1190 1100
970 500
Me
Lo
Cooling Fan
Quiet
Quiet
Hi 1310
1180 1030
970 500
1200 1100 1000
Me
Lo
Heating
AS*12LMACW
S- Lo
1
4
5
6
3
2
01-05
Operation mode Air flow mode
Speed (rpm)
Hi 1140
1000
880 700
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1140
1050
980 800 700 480
Auto S- Lo
Cooling Fan
Heating
AS*A07LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1220
1060
900 720
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1220 1110 1040
830 720 480
Auto S- Lo
Cooling Fan
Heating
AS*A09LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1280
1100
900 750
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1320 1180 1080
860 750 480
Auto S- Lo
Cooling Fan
Heating
AS*A12LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1480
1250 1050
850
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1480 1250 1100
950 850 480
Auto S- Lo
Cooling Fan
Heating
AS*A14LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1480
1250 1100
950
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1480 1250 1100
950 950 480
Auto S- Lo
Cooling Fan
Heating
AS*A18LACM
01-06
AG*F09LAC
Operation mode
Air flow mode
Speed (rpm)
Hi 1120/ 950 1230/ ---
960/ 820 1070/ ---
660/ 560 680/ ---
820/ 700 910/ --­ 660/ 560 750/ --­ 570/ 480 --- / --­1120/ 950 1230/ --­1000/ 850 1090/ --­ 860/ 730 940/ --­ 660/ 560 750/ ---
660/ 560
680/ ---
Me
Lo
Heating
Quiet
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
S-Lo
Cooling Fan
Upper& Lower air flow mode
Upper air flow mode
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower) (Upper/ Lower)
AG*F12LAC
Operation mode
Air flow mode
Speed (rpm)
Hi 1240/ 1050 1300/ ---
1050/ 890 1120/ ---
660/ 560 680/ ---
860/ 730 930/ --­ 660/ 560 750/ --­ 570/ 480 --- / --­1240/ 1050 1300/ --­1080/ 920 1140/ --­ 910/ 770 980/ --­ 660/ 560 750/ ---
660/ 560
680/ ---
Me
Lo
Heating
Quiet
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
S-Lo
Cooling Fan
Upper& Lower air flow mode
Upper air flow mode
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower) (Upper/ Lower)
AG*F14LAC
Operation mode
Air flow mode
Speed (rpm)
Hi 1330/ 1120 1370/ ---
1100/ 930 1160/ ---
660/ 560 680/ ---
890/ 750 960/ --­ 660/ 560 750/ --­ 570/ 480 --- / --­1330/ 1120 1370/ --­1140/ 970 1180/ --­ 940/ 800 1020/ --­ 660/ 560 750/ ---
660/ 560
680/ ---
Me
Lo
Heating
Quiet
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
S-Lo
Cooling Fan
Upper& Lower air flow mode
Upper air flow mode
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower) (Upper/ Lower)
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs.
2-2. For AB*F14L/ 18L/ 24L AR*F09L/ 12L/ 14L/ 18L/ 22L AU*F09L/ 12L/ 14L/ 18L AS*7L/ 9L/ 12L/ 18L/ 24L AS*A07L/ 09L/ 12L/ 14L/ 18L AG*F09L/ 12L/ 14L
The airflow can be switched in 4 steps such as AUTO, LOW, MED, HIGH, while the indoor fan only runs.
2-1. For AB*14L/ 18L/ 24L AR* 9L/ 12L/ 14L/ 18L/ 22L AU*12L/ 14L/ 18L
3. COOLING OPERATION
(Fig.1)
airflow change - over ( Cooling: AUTO )
When the room temperature rises
Lo mode
When the room temperature lowers
01-07
Hi mode
Me mode
TR : Room temperature Ts : Setting temperature
TR-Ts > 2 degC
=
1 degC > TR-Ts
2 degC > TR-Ts > 1 degC
=
TR-Ts > 3 degC
*(TR-Ts > 2.5 degC)
=
=
2 degC > TR-Ts
*(2 degC > TR-Ts)
3 degC > TR-Ts > 2 degC
*(2.5 degC > TR-Ts > 1.5 degC)
= =
*1
*1 : Contains a condition to the following
When the operation mode is set to AUTO mode at the start of operation. When the setting temperature was changed. When the operation mode was changed to COOLING mode. When the airflow mode was changed to AUTO mode.
4. HEATING OPERATION
When the airflow is set to [AUTO], the indoor fan motor operates [MED] mode. Then the indoor fan motor will run according to a room temperature, as shown in Figure 2.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 2.
47°C
41°C *(42°C)
Indoor heat exchanger temperature
( Fig.2 : Airflow change - over ( Heating : AUTO ) )
Hold
Go down one-step
Go up one-step
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 1. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH,as shown in Table 2.
*For AS*7/ 9/ 12LMACW
*For AS*A07/ 09/ 12/ 14/ 18LACM
*For AB*F/ AR*F/ AS*A/ AU*F/ AG*F Type
4-1. For AB/ AR/ AU/ AS Type
4-2. For AB*F/ AR*F/ AU*F/ AS*A/ AG*F Type
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 3.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 2.
( Fig.3 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > - 1.5 degC
=
- 2.5 degC > TR-Ts
- 1.5 degC > TR-Ts > - 2.5 degC =
TR-Ts > - 1 degC
=
- 2 degC > TR-Ts
- 1 degC > TR-Ts > - 2 degC =
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
Lo mode
Me mode
Hi mode *(Me+ mode)
01-08
5. COOL AIR PREVENTION CONTROL (Heating mode)
Setting Fan mode
Lo mode
S-Lo mode
33°C
30°C
30°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
The maximum value of the indoor fan speed is set as shown in Figure 4, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig.4 : Cool Air Prevention Control )
5-1. For AB/ AR/ AU Type
5-2. For AB*F/ AU*F Type
5-3. For AR*F Type
42°C
30°C
34°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 5, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.5 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me+
Lo
Cool air prevention
39°C
37°C
37°C
32°C
24°C
39°C
32°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
< The other of [Hi] setting >
< [Hi] setting >
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air prevention
37°C
30°C
34°C
24°C
Setting FAN mode
S-Lo
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 6, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.6 : Cool Air Prevention Control )
Setting Fan mode
Lo (Qu) mode
S-Lo mode
37°C
30°C
32°C
24°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
Hi mode
Lo mode
S-Lo mode
37°C
30°C
32°C
24°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
01-09
42°C
35°C
30°C
18°C
39°C
32°C
26°C
15°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
The maximum value of the indoor fan speed is set as shown in Figure 7-1,7-2, based on the fan speed mode and the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig.7-1 : Cool Air Prevention Control for AS*7/ 9/ 12LMACW )
5-4. For AS Type
E zone
D zone
C zone
B zone
A zone
AUTO HIGH MED LOW QUIET
E zone D zone C zone B zone A zone
Fan speed mode
ZONE
AUTO AUTO
S-Lo OFF OFF OFF OFF OFF
S-Lo S-Lo S-Lo S-Lo
Me
Lo Lo Lo
Setting Fan Speed
40°C
33°C
28°C
18°C
38°C
31°C
26°C
16°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
( Fig.7-2 : Cool Air Prevention Control for AS*18/ 24LBAJ )
E zone
D zone
C zone
B zone
A zone
AUTO HIGH MED LOW QUIET
E zone D zone C zone B zone A zone
Fan speed mode
ZONE
AUTO AUTO
S-Lo OFF OFF OFF OFF OFF
S-Lo S-Lo S-Lo S-Lo
Me
Lo Lo Lo
Setting Fan Speed
5-5. For AS*A Type
47°C
30°C
34°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.8 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me+
Lo
Cool air prevention
40°C
37°C
40°C
32°C
28°C
40°C
32°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air prevention
37°C
30°C
34°C
28°C
Setting FAN mode
S-Lo
[ AS*A07L: Cool air prevention 800rpm, S-Lo 480rpm ] [ AS*A09L: Cool air prevention 830rpm, S-Lo 480rpm ] [ AS*A12L: Cool air prevention 860rpm, S-Lo 480rpm ] [ AS*A14L/ 18L: Cool air prevention 850rpm, S-Lo 480rpm ]
01-10
5-6. For AG*F Type
42°C
30°C
31°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 9, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.9 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me
Lo
Cool air prevention
39°C
37°C
34°C
29°C
24°C
39°C
29°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air prevention
37°C
30°C
31°C
24°C
Setting FAN mode
S-Lo
During the dry mode operation, the fan speed setting can not be changed. ( S-Lo )
6. DRY OPERATION
01-11
4. OUTDOOR FAN CONTROL
Following table shows the fan speed of the outdoor unit.
1. Outdoor Fan Motor
*
For AO*18LMAK2/ 24LMAM2 When the outdoor heat exchanger tenperature is lower than 2°C, the fan speed switches to 780rpm on heating mode.
For AO*30LMAW4 It runs at 500rpm for 20 seconds after starting up the outdoor fan. When the outdoor heat exchanger tenperature is lower than 2°C, the fan speed switches to 780rpm on heating mode.
*
( Table 3 : Fan speed of the outdoor unit )
780/ 420 rpm
820/ 780/ 400/ 300/ 200 rpm
850/ 780/ 400/ 300/ 200 rpm
780/ 420 rpm
Cooling
Heating
AO*18LMAK2
AO*30LMAW4
AO*24LMAM2
5. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
(Swinging Range)
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-12
1
2
3
4
The indoor fan motor starts after the louver reaches to the setting position.
At the start of operation if the setting louver position is ,the setting position is set to after the louver moves from totally-enclosed position to . (Positioning Control)
( Stop mode means Operation stop.)
Airflow direction set Range of swing
to to to to
5-1 Compact Cassette (AU) type
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-13
The indoor fan motor starts after the louver reaches to the setting position.
At the start of operation if the setting louver position is or ,the setting position is set to or after the louver moves from totally-enclosed position to . (Positioning Control)
( Stop mode means Operation stop.)
1
4
5
6
7
3
2
1 2 3 4 5 6 7
1 2 3 4 5 6 7
1
2
1
3
1
2
3
6
4
5
3
4
5
6
7
1
7
1
1
2
2
3
(Swinging Range)
Airflow direction set
Range of swing
to to to to
1
4
5
7
7
7
to to to
5-2 Universal (AB) type
2. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The horizontal airflow direction is set automatically on after initialization.
(Function Range)
(Air Direction Range)
(Operation Range)
2-1. SWING OPERATION
When the swing signal is received from the remote controller, the horizontal louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-14
( Stop mode means Operation stop.)
1 2 3 4 5
1 2 334 5
1
3
4
5
2
1
2
1
3
1
2
5
5
3
4
3
4
5
(Swinging Range)
Airflow direction set
Range of swing
to to to to
1 5
to
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode
Use the air direction adjustments within the ranges shown above.
The remote control unit's display does not change.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal ; the air direction cannot be adjusted during this period.
Cooling mode / Dry mode / Fan mode ( ) ) Heating mode / Fan mode (
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-15
5-3 Wall Mounted (AS*7/ 9/ 12L) type
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode
Use the air direction adjustments within the ranges shown above.
The remote control unit's display does not change.
Direction Only the direction of the Moving Diffuser changes: the direction of the Air Direction Flaps does not change.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal ; the air direction cannot be adjusted during this period.
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
01-16
5-4 Wall Mounted (AS*18/ 24L) type
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
1
2
1
3
1
1
4
5
4
4
3
4
5
6
(Swinging Range)
Airflow direction set
Range of swing
to to to to
4
1
6
6
to to
01-17
2. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The horizontal airflow direction is set automatically on after initialization.
(Function Range)
(Air Direction Range)
(Operation Range)
2-1. SWING OPERATION
When the swing signal is received from the remote controller, the horizontal louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
1 2 3 4 5
1 2 334 5
1
3
4
5
2
1
2
1
3
1
2
5
5
3
4
3
4
5
(Swinging Range)
Airflow direction set
Range of swing
to to to to
1 5
to
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
range ( ) for long period of time, since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow Direction Louvers are left in the hating range for more than 30 minutes, they will automatically return to position .
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes , and it cannot be adjusted.
Cooling mode / Dry mode / Fan mode ( ) Heating mode / Fan mode ( )
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-18
5-5 Wall Mounted (AS*A) type
01-19
5-6 Compact Cassette (AU*F) type
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
1
2
3
4
( Stop mode means Operation stop.)
During Cooling/Dry mode/Fan mode : During Heating mode :
During AUTO mode operation, for the first minute after beginning operation, air-flow will be horizontal ; the air direction cannot be adjusted during this period.
(Swinging Range)
The type of operation
Cooling/Dry/Fan
Range of swing
to
Heating
to
01-20
5-7 Floor (AG*F) type
1. VERTICAL LOUVER CONTROL
1-2. SWING OPERATION
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes , and it cannot be adjusted.
(Function and Operation Range)
(Air Direction Range)
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrrupted and the louver stops at the memorized position.
01-21
6. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the table 4.
Cooling Heating
Min Max Min Max
AO*18LMAK2 15Hz 80Hz 15Hz 95Hz AO*24LMAM2 AO*30LMAW4
15Hz 80Hz 15Hz 95Hz 15Hz 90Hz 20Hz 95Hz
(Table 4 : Compressor Operation Frequency Range)
2. OPERATION FREQUENCY CONTROL AT START UP
2-1. For AO*18L/ 24L
The compressor frequency soon after the start-up is controlled as shown in Figure 10-1.
(Fig.10-1 : Compressor Control at Start-up)
56Hz
56Hz
40Hz
46sec 60sec 80sec 160sec
80Hz
Hold
2-2. For AO*30LMAW4
The compressor frequency soon after the start-up is controlled as shown in Figure 10-2.
(Fig.10-2 : Compressor Control at Start-up)
180sec
60sec
120sec
120sec
720sec
1
2
1 Discharge pipe temp. > 30°C 2 Discharge pipe temp. < 30°C
=
Hold
7. TIMER OPERATION CONTROL
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
01-22
7-1 Wireless Remote Controller ( For AB/ AU/ AU*F/ AS/ AS*A/ AB*F/ AG*F type )
ON / TIMER OFF / TIMER
PROGRAM TIMER
SLEEP TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
01-23
3. SLEEP TIMER
If the sleep timer is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers ( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1 degC. It increases the setting temperature another 1 degC after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1degC
+2degC
-2degC
-1degC
-4degC
-3degC
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1 degC. It decreases the setting temperature another 1 degC every 30 minutes. Upon lowering 4 degC, the setting temperature is not changed and the operation stops at the time of timer setting.
Set
30min
30min
30min
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The weekly timer allows up to two ON and OFF time to set up per day.
Use this timer function to set operating time for each day of the week.
Operation mode
The operating time can be set in 30 min increments only. The OFF time can be carried over to next day. The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
01-24
7-2 Wired Remote Controller ( For AR/ AR*F type )
ON / TIMER OFF / TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
01-25
The DAY OFF setting is only available for days for which weekly settings already exist.
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower.
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
Normal
Next day setting
If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
2-2. DAY OFF setting
3. TEMPERATURE SET BACK TIMER
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
Preceding day Next day
DAY OFF
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
DAY OFF
Setting day
Preceding day Next daySetting day
Case of SET BACK timer on the Cooling operation. ( Setting temperature :22°C, SET BACK temperature :26°C)
SET BACK setting
Operation temperature
Operation temperature
26°C
22°C
26°C
22°C
24°C
*1
ON OFF OFFON
*1: During the SET BACK function, the setting temperature is changed.
Chenge the setting temperature: 22°C 24°C
8. ELECTRONIC EXPANSION VALVE CONTROL
9. TEST OPERATION CONTROL
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
11. 4-WAY VALVE EXTENSION SELECT
01-26
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 30 to 480 pulses.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (1000 pulses are input to the closing direction).
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the 4-way valve is switched in 3 minutes later after the compressor stopped.
Under the condition where the air conditioner runs, short two metal contacts under the battery compartment lid, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller
Under the condition where the air conditioner stops, press the MASTER CONTROL button and the FAN CONTROL button simultaneously for 5 seconds or more, and the test operation control mode will appear. During test running, " " will display on the remote controller display. Set the test operation mode, and the compressor will continue to run regardless of whatever the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wired Remote Controller ( without TEST RUN button )
Under the condition where the air conditioner runs, press the TEST RUN button, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller ( with TEST RUN button )
13. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 5. If the remote control is lost or battery power dissipated, this function will work without the remote control.
(Table 5 : Manual auto operation)
14. COMPRESSOR PREHEATING
01-27
When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 6) and the heating operation has
been stopped for 3 hours, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to Release temperature or greater, preheating
is over.
(Table 6 : Preheating Operation / Release Temperature)
Before 24 hour After 24 hour
Operation temperature
Operation temperature
Release temperature
Release temperature
3°C 7°C 0°C 4°C
OPERATION MODE
Auto changeover
FAN CONT. MODE
Auto
TIMER MODE
Continuous (No timer setting available)
SETTING TEMP.
23°C or 24°C
SETTING LOUVER
Standard
SWING
OFF
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as shown in Figure 11.
15. FRESH AIR CONTROL (For AR type)
(Fig.11 : Fresh air control)
Operation
Stop
Operation
Stop
Fan motor (Indoor unit)
Fan motor (for Fresh Air)
12. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically resumed with the memorized operation contents. When the power is interrupted and recovered during timer operation, timer operation is canceled, but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature
Set air flow
Timer mode and timer time Air flow Direction
Swing Thermistor detected position (For AU*F model wih wired remote controller)
10°C HEAT (For AG*F model)
01-28
The external electrical heater is operated as shown in Figure 12.
16. EXTERNAL ELECTRICAL HEATER CONTROL (For AR type)
(Fig.12 : External electrical heater control)
When the room temperature rises
When the room temperature drops
Ts : Setting temperature
Heater : OFF
Heater : ON
Heater : OFF
Ts -10°C
Ts -1°C
Ts -3°C
Ts -12°C
When the compressor stop, External electrical heater is OFF.
17. COIL DRY OPERATION CONTROL (For AS*A/ AG*F type)
The coil-dry operation functions by pressing COIL DRY button on the remote controller. The coil-dry operation is consisted of 3 cycles of [Fan operation 3 minutes / Heating operation 2 minutes], and Fan operates for 3 minutes at last before ending the air conditioner operation. (It takes 18 minutes to complete the coil-dry operation.)
18. DEFROST OPERATION CONTROL
01-29
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 8-1.
(Table 8-1 : Defrost Release Condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 10°C or Compressor operation time has passed 15 minutes.
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 7-1.
(Table 7-1 : Condition of starting Defrost Operation)
Less than 6 min. *1 or 10min. *2
*2. Compressor stop time: Below 20min. Select 6min. Above 20min. Select 10min.
After 6 min. *1 or 10min. *2
Compressor integrating operation :Less than 40min.
Compressor integrating operation :40min and over
-8°C
Does not operate
*1. It means contiguous operation time.
1-1. For AO*18LMAK2/ 24LMAM2
2-1. For AO*18LMAK2/ 24LMAM2
Defrost operation is released when the conditions become as shown in Table 8-2.
(Table 8-2 : Defrost Release Condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 12°C or Compressor operation time has passed 15 minutes.
2-2. For AO*30LMAW4
1-2. For AO*30LMAW4
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 7-2.
(Table 7-2 : Condition of starting Defrost Operation)
Less than 6 min. *1 or 10min. *2
*3. Outdoor temp. > -1°C *4. Outdoor temp. < -1°C
*2. Compressor stop time: Below 20min. Select 6min. Above 20min. Select 10min.
After 6 min. *1 or 10min. *2
Compressor integrating operation :Less than 45min.
Compressor integrating operation :45min and over
-8°C *3
-10°C *4
Does not operate
=
*1. It means contiguous operation time.
3. Defrost Flow Chart
3-1. For AO*18LMAK2/ 24LMAM2
The defrosting shall proceed by the integrating operation time as follows.
(Not defrosted for 6 or 10 minutes)
3 sec later Compressor OFF 3 sec later Outdoor fan motor OFF 28 sec later 4-way valve OFF 34 sec later compressor ON (Frequency : 95 Hz)
Heating operation start : Compressor ON
Defrost Indicator: [Operation lamp] 9 sec ON / 1 sec OFF
Outdoor heat exchanger temperature: Over 10°C or Compressor ON time: Over 15 minutes
Defrost end
01-30
Compressor integrating operation: 40 minutes and over
Outdoor heat exchanger temperarure: Below -8°C
Defrost start
3-2. AO*30LMAW4
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger temperature as follows.
(Not defrosted for 6 or 10 minutes)
3 sec later Compressor OFF 3 sec later Outdoor fan motor OFF 28 sec later 4-way valve OFF 34 sec later compressor ON (Frequency : 92 Hz)
Heating operation start : Compressor ON
Defrost Indicator: [Operation lamp] 9 sec ON / 1 sec OFF
Outdoor heat exchanger temperature: Over 12°C or Compressor ON time: Over 15 minutes
Defrost end
01-31
Compressor integrating operation: 45 minutes and over
Outdoor heat exchanger temperarure: Below -10°C
Outdoor heat exchanger temperarure: Below -8°C
Outdoor temp. > -1°C
=
Outdoor temp. < -1°C
Defrost start
01-32
20. ENERGY SAVE FUNCTION (For AR type)
1. During Cooling / Dry operation:
The thermostat temperature setting increases by 1 degC as soon as the ENERGY SAVE button is pressed, and then increases by 1 degC after 1 hour later. Afterwards, energy consumption is saved by continuing to cool or dry at a thermostat temperature of 2 degC higher than setting temperature.
2. During Heating operation:
The thermostat temperature setting decreases by 1 degC as soon as the ENERGY SAVE button is pressed, and then decreases by another 1 degC every 30 minutes. Afterwards, energy consumption is saved by continuing to heat at a thermostat temperature of 4 degC lower than setting temperature.
1hour.
1 degC
2 degC
ENERGY SAVE ON
Setting temperature
1degC 2degC 3degC 4degC
30min.
1 hour.
1 hour 30 min.
ENERGY SAVE ON
Setting temperature
19. DRAIN PUMP OPERATION ( For AU type )
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Indoor heat exchanger de-icing function", the drain pump is turned off in 1 hour after the compressor stops.
4.When the water level in the drain pan rises up and then the float switch functions: The compressor, indoor and outdoor fan motor operation are stopped. Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
5. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
6. When the float switch turns OFF within 3 min., the unit starts cooling operation.
1 2
1.When the water level in the drain pan rises up and then the float switch functions: Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
1
During Cooling / Dry operation
During Heating / Fan / Stop operation
21. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
When the discharge temperature becomes higher than 110°C ,the compressor frequency is decreased 10 Hz, and it continues to decrease the frequency for 10 Hz every 120 seconds until
the temperature becomes lower than 110°C . When the discharge temperature becomes lower than 105°C ,the control of the compressor frequency is released.
When the discharge temperature becomes higher than 120°C ,the compressor stops. When the discharge temperature becomes lower than 80°C ,the compressor operates.
2. CURRENT RELEASE CONTROL
01-33
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit velue that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
3. ANTI-FREEZING CONTROL (Cooling mode)
The compressor frequency decreases on cooling mode when the indoor heat exchanger temperature sensor detects the temperature lower than 3°C. Then, the anti-freezing control is released when it becomes higher than 6°C.
(Fig 13 : Anti-freezing Protection Operation / Release Temperature)
Indoor heat exchange temperature
3°C
6°C
12°C
The compressor frequency is decreased 10Hz every 120 seconds.
Compressor OFF : Hold Compressor ON : Release of protection
Hold
Release of protection
01-34
4. COOLING PRESSURE OVER RISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 70.5°C or greater, the compressor is stopped and error display is indicated.
Indoor heat exchange temperature
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
(Fig 14 : Heating Overload Protection Control)
63°C
54°C 50°C
56°C 52°C
Temperature
AO*18LMAK2 AO*24LMAM2 AO*30LMAW4
Temperature
Compressor is OFF
The compressor frequency is decreased 10Hz every 60 seconds.
Compressor OFF : Release of protection Compressor ON : The compressor frequency is increased 10Hz every 60seconds.
Hold
Temperature
Temperature
2 . TROUBLE SHOOTING
R410A
INVERTER (MULTI )
Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type
2. TROUBLESHOOTING
02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT DISPLAY
1. ERROR DISPLAY Please refer the blinking pattern as follows.
2-way valve temperature thermistor error
Forced auto switch error
Power supply frequency detection error
Connected indoor unit error
Room temperature thermistor error
Indoor heat exchanger temperature thermistor error
Outdoor heat exchanger temperature thermistor error
Outdoor discharge pipe temperature thermistor error
IPM error
Compressor rotor location cannot detect
(permanent stop)
Compressor temperature thermistor error
Outdoor temperature thermistor error
3-way valve temperature thermistor error
Communication error (Serial reverse transfer error)
Outdoor communication signal error (Forward transfer signal error)
When an error occurs, "Large division indication" is indicated first. Secondly, "Small division indication" is indicated by pushing "Test run" button of remote controller.
Error contents Error contents
Thermistor error (indoor unit)
Thermistor error (outdoor unit)
(2 times)
Red lamp Green lamp
Red lamp Green lamp
Red lamp Green lamp
Red lamp Green lamp
Red lamp Green lamp
Red lamp Green lamp
Red lamp Green lamp
Red lamp
Green lamp
(2 times)
Red lamp
Green lamp
(3 times)
Red lamp
Green lamp (2 times)
Red lamp
Green lamp (4 times)
Red lamp
Green lamp (2 times)
Red lamp
Green lamp (3 times)
Red lamp
Green lamp (2 times)
Red lamp
Green lamp (3 times)
Red lamp
Green lamp
(2 times)
Red lamp
Green lamp
(4 times)
Red lamp
Green lamp
(6 times)
Red lamp
Green lamp
(8 times)
Red lamp
Green lamp
(9 times)
Red lamp
Green lamp
(10 times)
Red lamp
Green lamp
(2 times)
Red lamp
Green lamp
(2 times)
(3 times)
Red lamp
Green lamp
(2 times)
Red lamp
Green lamp
(5 times)
Control unit error (indoor unit)
Control unit error (outdoor unit)
Pressure switch error
Inverter error
Serial error
(4 times)
Fan motor error (indoor unit)
(5 times)
Indoor fan motor lock error
(6 times)
(2 times)
(3 times)
Red lamp Green lamp (4 times)
(5 times)
Indoor fan motor speed error
Pressure switch error
Red lamp Green lamp
Red lamp
Green lam
(2 times)
Indoor EEPROM abnormal error
Indoor EEPROM abnormal (Model No.)
Outdoor unit fan motor error
Red lamp
Green lamp
LED indication LED indication
Small division indicationLarge division indication
3
4
25
26
2
11
10
8
5
7
12
21
22
13
23
18
17
9
14
Trouble shooting
For AS*7/ 9/ 12LMACW
: Fast flashing : Slow flashing
Operation lamp : Red lamp Timer lamp : Green lamp
02-02
The OPERATION, TIMER and SWING lamps operate as follows according to the error contents.
Error display
OPERARION TIMER SWING
(RED) (GREEN) (ORANGE)
Error contents
2 times
2 times
3 times
3 times
5 times
6 times
5 times
8 times
9 times
IPM error 10 times
13 times
14 times
5 times
3 times
4 times
5 times
3 times
2 times
4 times
:
Fast flashing
:
Slow flashing
:
Off
2-way valve temperature thermistor error
Connected indoor unit error
Indoor heat exchanger temperature thermistor error (Opened) Indoor heat exchanger temperature thermistor error (Short circuited)
Outdoor heat exchanger temperature thermistor error
Outdoor discharge pipe temperature thermistor error
Compressor rotor location cannot detect
(permanent stop)
Compressor temperature thermistor error
Outdoor temperature thermistor error
3-way valve temperature thermistor error
Communication error (Serial reverse transfer error)
Outdoor communication signal error (Forward transfer signal error)
Indoor fan error
Pressure switch error
Indoor EEPROM abnormal
(Model No.)
Outdoor unit fan motor error
Trouble shooting
Room temperature thermistor error (Opened) Room temperature thermistor error (Short circuited)
Main CPU-Sub CPU communication error
9
3
4
2
11
10
4 times
Water drain abnormal
6
12
13
21
22
23
14
17
18
24
5
7
8
For AS*18/ 24LBAJ For AB*14L - 24L / AU*12L - 18L
02-03
Forced auto switch error
Power supply frequency detection error
VDD permanence stop protection (Electric air clean)
Reverse-VDD permanence stop protection (Electric air clean power supply circuit abnormal)
The OPERATION, TIMER, AIR CLEAN and COIL DRY lamps operate as follows according to the error contents.
Error display
OPERATION
TIMER
COIL DRY
(RED) (GREEN) (GREEN)
(ORANGE)
Error contents
:
0.5s ON / 0.5s OFF (Flash)
:
OFF
2-way valve temperature thermistor error
Indoor heat exchanger temperature thermistor (middle) error
Outdoor heat exchanger temperature thermistor error
Outdoor discharge pipe temperature thermistor error
Compressor temperature thermistor error
Outdoor temperature thermistor error
Heat sink temperature thermistor error
Communication error (Serial reverse transfer error)
Outdoor communication signal error (Forward transfer signal error)
Trouble shooting
Room temperature thermistor error
2
1
3
11
19
4
12
13
21
22
25
26
34
35
15
30
16
9
23
14
17
18
24
10
5
7
8
For AS*A07 - 18LACM
Discharge temperature error
Indoor fan motor abnormal
Outdoor unit fan motor error
Pressure switch error
CT error
IPM error
Compressor rotor location cannot detect
(permanent stop)
8 times
Communication error
(indoor unit remote control)
2 times
3-way valve temperature thermistor error
2 times 3 times
2 times 3 times
4 times 5 times
2 times
2 times
3 times
3 times
2 times
3 times
3 times
3 times
4 times
3 times
7 times
3 times
8 times
4 times
2 times
4 times
4 times
4 times
7 times
4 times
8 times
5 times
2 times
5 times
3 times
5 times
5 times
5 times
6 times
5 times
7 times
5 times
6 times
8 times
7 times
2 times
7 times
5 times
2 times 3 times
8 times
3 times 2 times
3 times 3 times
Connected indoor unit error
Main CPU-Sub CPU communication error
AIR CLEAN or QUIET
Indoor EEPROM abnormal (Model No.)
Active filter module (AFM) error
Continuous blink
Continuous blink
Continuous blink
Continuous blink
02-04
For AG*F09 - 14LAC
Forced auto switch error
The OPERATION, TIMER and 10°C HEAT lamps operate as follows according to the error contents.
Error display
OPERATION
TIMER
(GREEN) (ORANGE) (GREEN)
Error contents
:
0.5s ON / 0.5s OFF (Flash)
:
OFF
Indoor heat exchanger temperature thermistor (middle) error
Outdoor heat exchanger temperature thermistor error
Outdoor discharge pipe temperature thermistor error
Outdoor temperature thermistor error
Communication error (Serial reverse transfer error)
Outdoor communication signal error (Forward transfer signal error)
Trouble shooting
Room temperature thermistor error
2
3
1
11
4
14
25
38
15
17
18
10
39
40
30
9
5
7
8
Discharge temperature error
Indoor fan lock error
Indoor UPPER fan speed error
Indoor LOWER fan lock error
Indoor LOWER fan speed error
Outdoor unit fan motor error
CT error
IPM error
Compressor rotor location cannot detect
(permanent stop)
Damper error
(UPPER & LOWER air flow)
Damper error
(UPPER air flow)
Damper error
8 times
Communication error
(indoor unit remote control)
2 times
2 times 3 times
4 times 5 times
2 times
2 times
3 times
3 times
2 times
3 times
3 times
3 times
4 times
4 times
2 times
4 times
3 times
5 times
2 times
5 times
3 times
5 times
5 times
5 times
5 times
6 times
6 times
2 times
6 times
3 times
6 times
6 times
2 times
3 times
6 times
4 times
6 times
6 times
5 times
7 times
2 times
10°C HEAT
Indoor EEPROM abnormal (Model No.)
Continuous blink
Continuous blink
Continuous blink
Main relay welded
02-05
The OPERATION, TIMER and FILTER lamps operate as follows according to the error contents.
Error display
OPERATION TIMER
FILTER
(GREEN) (ORANGE)
(RED)
Error contents
:
0.5s ON / 0.5s OFF (Flash)
:
OFF
2-way valve temperature thermistor error
Indoor heat exchanger temperature thermistor (middle) error
Indoor heat exchanger temperature thermistor (inlet) error
Outdoor heat exchanger temperature thermistor error
Outdoor discharge pipe temperature thermistor error
Compressor temperature thermistor error
Outdoor temperature thermistor error
Heat sink temperature thermistor error
Communication error (Serial reverse transfer error)
Outdoor communication signal error (Forward transfer signal error)
Trouble shooting
Room temperature thermistor error
2
3
1
11
27
28
19
4
12
13
21
22
25
15
23
14
17
18
24
10
30
32
5
7
8
For AU*F09 - 18LAL AB*F14 - 24LAT
Discharge temperature error
Indoor fan motor abnormal
Outdoor unit fan motor error
Pressure switch error
CT error
Communication error
(Main PCB Display PCB)
Communication error
(Main PCB Display PCB)
IPM error
Compressor rotor location cannot detect
(permanent stop)
4-way valve error
Forced auto switch error
8 times
Communication error
(indoor unit remote control)
6 times
2 times
2 times
3 times
2 times
4 times
2 times
2 times
3 times
3 times
3 times
4 times3 times
7 times
3 times
2 times
4 times
2 times
5 times
3 times5 times
5 times5 times
6 times5 times
7 times5 times
8 times5 times
2 times7 times
4 times7 times
5 times7 times
6 times
8 times
3 times
2 times
3 times
3-way valve temperature thermistor error
3 times3 times
7 times
2 times 3 times
2 times 3 times
4 times 5 times
Connected indoor unit error
Main CPU-Sub CPU communication error
02-06
Operation
0.5sec 0.5sec 2sec
ON
OFF
1. ERROR DISPLAY
3. NORMAL OPERATION DISPLAY
2. ERROR DISPLAY METHOD
Outdoor LED Blink (1 to 18 times) 0.5sec ON / 0.5sec OFF blinking
2-1-2 OUTDOOR UNIT DISPLAY
LEDA LEDB LEDC LEDD
OFFOFF OFF
2-way valve temperature thermistor A error
2-way valve temperature thermistor B error
2-way valve temperature thermistor C error
2-way valve temperature thermistor D error
3-way valve temperature thermistor A error
3-way valve temperature thermistor B error
3-way valve temperature thermistor C error
3-way valve temperature thermistor D error
Outdoor heat exchanger temperature thermistor error
Outdoor temperature thermistor error
Outdoor discharge pipe temperature thermistor error
8
11
Error Contents
1 times blink
1 times blink
1 times blink
1 times blink
2 times blink
OFF
OFF OFF
OFF OFF
OFFOFF
OFF
OFF
OFF
OFF
OFF
OFFOFF
OFF
5
3 times blink
OFFOFF
OFF
7
4 times blink
OFFOFF
OFF
5 times blink
OFFOFF
OFF
5 times blink
5 times blink
5 times blink
OFFOFF
OFF
OFFOFFOFF
6 times blink
OFF
OFF
OFF
6 times blink
OFFOFFOFF
12
7 times blink
OFF
OFF
19
8 times blink
OFF
OFF
13
9 times blink
OFF
OFF
10 times blink
OFF
OFF
23
11 times blink
OFF
OFF
14
12 times blink
OFF
OFF
17
13 times blink
OFF
OFF
20
14 times blink
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
18
15 times blink
OFFOFF
OFF
24
17 times blink
OFFOFF
OFF
21
6 times blink
OFFOFFOFF
OFF
OFF
OFF
22
6 times blink
OFFOFFOFF
Trouble shooting
LED
A B C D
Outdoor communication signal error (Forward transfer signal error)
Connected indoor unit error
Main CPU - sub CPU communication error
Outdoor unit fan motor error
IPM error
Compressor rotor location cannot detect
(permanent stop)
Compressor temperature thermistor error
Heat sink temperature thermistor error
Pressure switch 1 error
Pressure switch 2 error
Compressor Start-up error
(permanent stop)
Normal operation
Continuously lighting
5sec ON / 1sec OFF
Protected operation
02-07
Run [Self-Diagnosis] if [E:EE] flashes on the clock display of the remote controller.
When the error indication "E:EE" is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel.
Ex. Self-diagnosis
Error code
SUMOTUWETH FR
SA
Display
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons and simultaneously for 5 seconds or more to start the self-diagnosis.
3. Press the SET TEMPERATURE buttons and simultaneously for 5 seconds or more or there is no key input for 20 seconds to stop the self-diagnosis.
2-1-3 WIRED REMOTE CONTROLLER DISPLAY (For AR*9L - 22L)
1. SELF - DIAGNOSIS
Error code
Error contents
Trouble shooting
Communication error (Serial reverse transfer error)
Room temperature thermistor open
Room temperature thermistor short-circuited
Indoor heat exchanger temperature thermistor open
Indoor heat exchanger temperature thermistor short-circuited
Outdoor heat exchanger temperature thermistor error
Outdoor heat exchanger temperature thermistor short-circuited
Outdoor temperature thermistor open
Outdoor temperature thermistor short-circuited
Outdoor discharge pipe temperature thermistor open
Outdoor discharge pipe temperature thermistor short-circuited
Indoor EEPROM abnormal (Model No.)
Indoor fan motor abnormal
Outdoor unit fan motor error
Outdoor communication signal error (Forward transfer signal error)
Pressure switch error
CT error
Active Filter Module (AFM) error
Communication error (indoor unit remote control)
IPM error
Compressor rotor location cannot detect
Compressor temperature thermistor error
1 2
5
7
8
9
26
19
10
11 12 13 14 15 16
17 18 24 21
22 23
3
4
2-way valve temperature thermistor error
Power supply frequency detection error
Connected indoor unit error
Main CPU - sub CPU communication error
3-way valve temperature thermistor error
Heat sink temperature thermistor error
DAY OFF
DELETE SET
ENERGY
SAVE
SET BACK
DAY
CLOCK ADJUST
SET
THERMO SENSOR
DAY OFF
DELETE SET
ENERGY
SAVE
SET BACK
DAY
CLOCK ADJUST
SUMOTUWETH FR
SA
02-08
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , and the START/STOP button simultaneously for 5 seconds or more to start the self-diagnosis.
5. Press the SET TEMPERATURE buttons , and START/STOP button simultaneously for 5 seconds or more or there is no key input for 20 seconds to stop the display.
DAY
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
4. Press the SET TEMPERATURE button to select the error history number.
SUMOTUWETH FR
SA
Error code
Error history number
Lower
3. Press the START/STOP button.
0 1 2 3 4 5 6 7
F E d c b A 9 8
SUMOTUWETH FR
SA
DAY
DAY
Raise
02-09
When "EE" in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel.
Error code
Error contents
Trouble shooting
Communication error (Serial reverse transfer error)
Room temperature sensor error
Indoor heat exchanger temperature sensor error
Outdoor heat exchanger temperature sensor(outlet) error
Water drain abnormal
Outdoor temperature sensor error
Outdoor discharge pipe temperature sensor error
Discharge temperature error
Indoor fan motor abnormal
Outdoor unit fan motor error
Outdoor communication signal error (Forward transfer signal error)
2-1-4 WIRED REMOTE CONTROLLER DISPLAY (For AR*F09 - 22L)
Pressure switch error
Communication error (indoor unit remote control)
Communication error (Main PCB Display PCB)
Communication error (Main PCB Display PCB)
IPM error
CT error
Compressor rotor location cannot detect (permanent stop)
Compressor temperature sensor error
1. SELF - DIAGNOSIS
1 2
5 6 7
8
10
11 12 13
14 15
17 18
25
31 27
28
Indoor manual auto switch error
Exessive high pressure protection on cooling
3 4
SU MOTUWETH FR SA
Unit number (usually 0)
Error code
ex. Self-diagnosis check
30
If “CO” appears in the unit number display, there is a remote controller error. Refer to the installation instruction sheet included with the remote controller.
32
4-way valve error
21
2-way valve temperature thermistor error
22
3-way valve temperature thermistor error
24
Main CPU - sub CPU communication error
23
Connected indoor unit error
02-10
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
3. Press the SET TEMPERATURE button to select the error history number.
SU MOTU WETH FR SA
Error code
Error history number
0 1 2 3 4 5 6 7
F E d c b A 9 8
Lower
Raise
Trouble shooting 1 INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check Remote Control and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Indicate or Display:
Communication Error (Indoor unit Remote control)
Indoor unit controller PCB circuit Wired Remote Control
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit, and check if there is a disconnection of the cable.
Upon correcting the removed connector or mis-wiring, reset the power.
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
When the indoor unit cannot receive the signal from Wired Remote more than 10seconds after power ON, or the indoor unit cannot receive the signal more than 1minute during normal operation.
02-11
2-2 TROUBLE SHOOTING WITH ERROR CODE
Refer to error code table.
Trouble shooting 2
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Communication Error (Serial Reverse Transfer Error)
Outdoor Unit Main PCB Circuit Active Filter Module
1. Connection failure 2. External cause 3. Main PCB failure 4. Active Filter Module failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection between Outdoor Unit Main PCB and Filter PCB. (If there is loose connector or open cable)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal N - 3.
>> If it is abnormal, Check Active Filter Module. (PARTS INFORMATION 3)
When the indoor unit cannot receive the serial signal from Outdoor unit more than 10seconds.
>>If Active Filter Module is abnormal, replace it.
>>If Active Filter Module is normal, replace Main PCB.
02-12
N
L
3
WHITE
BLACK
+
-
Trouble shooting 3
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 1 : Check connection of Connector
Check Point 3 : Check Point 3 : Check voltage of Controller PCB (DC5.0V)
6.51
35°C
8.04
30°C
10.012.515.820.225.933.6Resistance Value (k )
25°C20°C15°C10°C5°C0°C
Temperature
OK
OK
3.594.355.30Resistance Value (k )
50°C45°C40°C
Temperature
Room Temperature Thermistor Error
Indoor Unit Controller PCB Circuit Room Temperature Thermistor
When Room Temperature Thermistor open or short-circuit is detected at power ON.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-13
Refer to error code table.
Trouble shooting 4
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
31.7
35°C
39.6
30°C
49.762.980.3103134176Resistance Value (k )
25°C20°C15°C10°C5°C0°CTemperature
OKOK
OK
17.120.825.6Resistance Value (k )
50°C45°C40°CTemperature
Indoor Heat Exchanger Temperature Thermistor Error
Indoor Unit Controller PCB Circuit Heat Exchanger Temperature Thermistor
When Heat Exchanger Temperature Thermistor open or short-circuit is detected at power ON.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-14
Refer to error code table.
Trouble shooting 5 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
4.77
25°C
5.98
20°C
7.569.6312.416.121.027.8Resistance Value (k )
15°C10°C5°C0°C-5°C-10°CTemperature
OKOK
OKOK
DC
3.84
30°C
Outdoor Heat Exchanger Temperature Thermistor Error
Outdoor Unit Main PCB Circuit Heat Exchanger Temperature Thermistor
When Heat Exchanger Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-15
Refer to error code table.
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN23 CN22 CN21
1 21 21 21 2
Check Point 2 : Check Point 2 : Check Connector (CN15) / Wire
Check Point 1 : Check Float Switch
Check Point 3 : Replace Controller PCB
ONON OFFOFF
OKOK
OKOK
Trouble shooting 6
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Water Drain Abnormal
Indoor Unit Controller PCB Circuit Float Switch
When Float Switch is ON for more than 3 minutes.
1. Float Switch failure 2. Shorted connector/ wire 3. Controller PCB failure
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation by using a meter.
>>If Float switch is detective, replace it.
Check loose contact of CN15 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
02-16
Refer to error code table.
Trouble shooting 7
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
30°C
12.620.726.935.246.662.3115Resistance Value (k )
20°C
16.1
15°C10°C5°C0°C-20°C -10°C -5°CTemperature
3.45 2.36 1.65Resistance Value (k )
50°C 60°C 70°C
5.187.97
40°CTemperature
Outdoor Temperature Thermistor Error
Outdoor Unit Main PCB Circuit Outdoor Temperature Thermistor
When Outdoor Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-17
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN23 CN22 CN21
1 21 21 21 2
Refer to error code table.
Trouble shooting 8
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
17.826.3
20°C
40.062.579.1101130169Resistance Value (k )
15°C10°C5°C0°CTemperature
OKOK
OKOK
12.3
30°C
50°C40°C
60°C
0.52
180°C
0.79
160°C
1.222.003.434.606.278.69Resistance Value (k )
140°C120°C100°C
90°C80°C70°CTemperature
Outdoor Discharge Pipe Temperature Thermistor Error
Outdoor Unit Main PCB Circuit Discharge Pipe Temperature Thermistor
When Discharge Pipe Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-18
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN23 CN22 CN21
1 21 21 21 2
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 : Check Indoor Unit electric components
YESYES
NO
Trouble shooting 9
INDOOR UNIT Error Method:
Indicate or Display:
Indicate or Display:
Indoor EEPROM abnormal (Model No.)
Indoor Unit Controller PCB circuit
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When the model information being read from EEPROM has an apparent error.
02-19
Refer to error code table.
Trouble shooting 10
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
Indoor Fan Motor abnormal
Indoor Unit Controller PCB Circuit Indoor Fan Motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Control PCB failure
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is below 1/3 of target frequency is continued more than 56 seconds. Or the condition of fan speed is 0rpm is continued more than 56 seconds.
02-20
Indicate or Display:
Check Point 3 : Replace Controller PCB
If Check Point 1,2 do not improve the symptom, change Controller PCB.
Refer to error code table.
Trouble shooting 11
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check Connection
OK
Indicate or Display:Indicate or Display:
Check Point 3 : Check the voltage of power supply
Check Point 1-1 : Reset the power
YESYES
NO
Check Point 1-2:
OK
Check Point 4 : Check Serial Signal (Forward Transfer Signal)
Check Serial Signal (Forward Transfer Signal)
Outdoor Communication Signal Error (Forward Transfer Signal Error)
Indoor Unit Controller PCB Circuit
1. Connection failure 2. External cause 3. Controller PCB failure
Does Error indication reappear?
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check the voltage of power supply
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal N - 3.
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection between Indoor Unit Controller PCB and Filter PCB. (If there is loose connector or open cable)
>> If it is abnormal, Controller PCB is failure. >> Replace Controller PCB
02-21
When the outdoor unit cannot receive the serial signal from Indoor unit more than 10seconds.
N
L
3
WHITE
BLACK
+
-
Refer to error code table.
Trouble shooting 12 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
Compressor Temperature Thermistor Error
Outdoor Unit Main PCB Circuit Compressor Temperature Thermistor
When Compressor Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-22
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(COMPRESSOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
BROWN
CN25 CN26 CN23 CN22 CN21
1 21 21 21 21 2
Refer to error code table.
17.826.3
20°C
40.062.579.1101130169Resistance Value (k )
15°C10°C5°C0°CTemperature
12.3
30°C
50°C40°C
60°C
0.52
180°C
0.79
160°C
1.222.003.434.606.278.69Resistance Value (k )
140°C120°C100°C
90°C80°C70°CTemperature
For AO*30LMAW4
Trouble shooting 13
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Point 2 : Check voltage of Main PCB (DC5.0V)
PRESSURE SWITCH 1
RED RED
CN37
1 2
PRESSURE SWITCH 2 (For AO*30LMAW4)
RED RED
CN36
1 2
Check Point 1 : Reset Power Supply and operate
Check Point 3 : Check Pressure Switch
YESYES
NONO
Pressure Switch Error
Outdoor Unit Main PCB Circuit Pressure Switch
1. Connector connection failure 2. Pressure Switch failure 3. Main PCB failure
When pressure switch open is detected in 10 seconds after the power is turned on.
Does abnormal LED indication show again?
Make sure circuit diagram of outdoor unit and check terminal voltage at Pressure Switch. (DC5.0V)
If the voltage does not appear, replace Main PCB.
Check if connector is loose or cable is open.
>> If no abnormal connection is found, replace Pressure Switch.
After replacing Pressure Switch, check operating condition and pressure in operation.
02-23
Refer to error code table.
OK
Trouble shooting 14
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Compressor
OK
OK
(PARTS INFORMATION 2)
Indicate or Display:
Check Point 4 : Replace Main PCB
OKOK
Check Point 1 : Check connections of Outdoor Unit Electrical Components
IPM error
Outdoor Unit Main PCB Circuit Compressor
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Compressor failure 5. Main PCB failure
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating by hand when operation is off ?
Check Outdoor Fan Motor. (Refer to Trouble shooting 18)
>> If the Fan Motor is locked, replace it.
>> If the Fan Motor is failure, replace it.
Check Compressor.
If Check Point 1, 2, 3 do not improve the symptom, change Main PCB.
When more than normal operating current to IPM in Main PCB flows, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
02-24
Refer to error code table.
Trouble shooting 15
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Filter PCB and Main PCB
Check Point 4 : Replace Main PCB
YES
NO
OK
Indicate or Display:
CT error
Outdoor Unit Main PCB Circuit Outdoor Unit Filter PCB Circuit (Input current sensor unit)
Check Point 2 : Check connections of Outdoor Unit Electrical Components
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
1. Defective connection of electric components 2. External cause 3. Filter PCB failure 4. Main PCB failure
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
When Input Current Sensor has detected lower than 0.5A while Inverter Compressor is operating at higher than 56Hz, after 1minute upon starting the Compressor. (Except during the defrost operation)
02-25
Check DC voltage of CN1 (between 2 (Brown) and 3 (Red)) on Filter PCB.
>> After 40seconds upon starting the Compressor, If it is higher than 0.2V, Main PCB is failure. (Filter PCB is normal) >> Replace Main PCB >> If it is lower than 0.2V, Filter PCB is failure. >> Replace Filter PCB
If it does not improve the symptom, change Main PCB.
AO*18L/ 24L
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Refer to error code table.
Trouble shooting 16
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Active Filter Module
OKOK
OKOK
OKOK
Active Filter Module (AFM) error
Outdoor Unit Main PCB Circuit Active Filter Module
1. External cause 2. Connector connection failure 3. Active Filter Module failure 4. Main PCB failure
Check Point 2 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Active Filter Module. (PARTS INFORMATION 3) >>If Active Filter Module is abnormal, replace it.
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
02-26
When inverter input DC voltage is higher than 467V or lower than 237V. When a momentary power cut off occurred on low voltage.
Refer to error code table.
Trouble shooting 17
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 1 : Check connection of around the Compressor components
OKOK
Indicate or Display:
Check Point 2 : Replace Main PCB
Outdoor Unit Main PCB Circuit
Compressor rotor location cannot detect (Permanent Stop)
1. Defective connection of electric components 2. Main PCB failure
If Check Point 1 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of phase with actual rotor location more than 90 degrees, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
02-27
Refer to error code table.
Trouble shooting 18
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check ambient temp. around motor
OK
OK
Indicate or Display:
Outdoor Unit Fan Motor Error
Outdoor Unit Main PCB Circuit Outdoor Fan Motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Check Point 3 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated 3 times in a row, compressor and fan motor stops. If and repeats 5 times in a row, compressor and fan motor stops permanently.
Read wire DC voltage
Red - Black
White - Black
300 400V
15 1.5V
02-28
CN800
1 2 3 4 5 6 7
BLACK WHITE YELLOW BROWN
RED
FM
FAN MOTOR
Refer to error code table.
For AO*30LMAW4
Trouble shooting 19 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
Heat Sink Temperature Thermistor Error
Outdoor Unit Main PCB Circuit Heat Sink Temperature Thermistor
When Heat Sink Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-29
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE)
THERMISTOR
(OUTDOOR)
THERMISTOR
(HEAT SINK)
BROWN
BLACK
BLACK
BLUE
CN25 CN23 CN22 CN21
1 21 21 21 2
Refer to error code table.
30°C
6.109.7312.416.1
Resistance Value (k )
20°C
7.67
15°C10°C5°C0°C
Temperature
1.79
1.25 0.89
Resistance Value (k )
50°C
60°C 70°C
0.65
80°C
0.48
90°C
0.36
100°C
0.21
12.3 8.69 6.27 4.60 3.43 2.00
120°C
2.623.95
62.5101130169 79.1
17.826.340.0
40°C
Temperature
AO*18L/ 24L
AO*30L
AO*18L/ 24L
AO*30L
Trouble shooting 20
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Indicate or Display:
Compressor Start-up error (Permanent Stop)
On start-up the compressor, when detected rotor position is out of phase with actual rotor position more than 90 degrees,the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Outdoor Unit Main PCB Circuit
1. Defective connection of electric components 2. Main PCB failure
Check Point 1 : Check connection of around the Compressor components
OKOK
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB.
Check if connector is removed.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
02-30
Refer to error code table.
Trouble shooting 21 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
30°C
103176233312Resistance Value (k )
20°C
134
15°C10°C5°C0°C-10°C -5°CTemperature
39.6
25.6 17.1Resistance Value (k )
50°C
60°C 70°C
11.6
80°C
8.12
90°C
5.78
100°C
4.19 3.09
62.980.3
40°C
Temperature
2-way valve Temperature Thermistor Error
Outdoor Unit Main PCB Circuit 2-way valve Temperature Thermistor
When 2-way valve Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-31
BLACK RED RED RED RED RED RED RED
GRAY
BROWN
BLACK
BLUE
YELLOW
RED
BLACK WHITE WHITE WHITE WHITE WHITE WHITE WHITE
RED
WHITE
1 2 3 4 5 6 7 8
1
2
3 4
5
6 7 8
1
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9
1
4 5 6
7 8 9
CN40
CN39
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
2-WAY VALVE C
3-WAY VALVE C
ORANGE
GREEN
2-WAY VALVE D
3-WAY VALVE D
VALVE THERMISTOR C, D (For AO*30LMAW4)
Refer to error code table.
Trouble shooting 22 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OKOK
OKOK
30°C
103176233312Resistance Value (k )
20°C
134
15°C10°C5°C0°C-10°C -5°C
Temperature
39.6
25.6 17.1Resistance Value (k )
50°C
60°C 70°C
11.6
80°C
8.12
90°C
5.78
100°C
4.19 3.09
62.980.3
40°C
Temperature
3-way valve Temperature Thermistor Error
Outdoor Unit Main PCB Circuit 3-way valve Temperature Thermistor
When 3-way valve Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-32
BLACK
RED RED RED RED
RED
RED
RED
GRAY
BROWN
BLACK
BLUE
YELLOW
RED
BLACK WHITE
WHITE
WHITE WHITE
WHITE
WHITE
WHITE
RED
WHITE
1 2 3 4 5 6
7
8
1
2
3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9
1
4 5 6 7 8 9
CN40
CN39
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
2-WAY VALVE C
3-WAY VALVE C
ORANGE
GREEN
2-WAY VALVE C
3-WAY VALVE C
Refer to error code table.
VALVE THERMISTOR C, D (For AO*30LMAW4)
Trouble shooting 23
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
Connected Indoor unit error
Outdoor Unit Main PCB Circuit
When the total capacity of the connected indoor units exceed the connectable range of the total capacity.
1. The selection of connected indoor unit is incorrect 2.Main PCB failure
Check Point 1 : Check the total capacity of indoor unit
Check the total capacity of the connected indoor units.
02-33
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, change Main PCB.
Trouble shooting 24
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Main CPU - Sub CPU communication error
Outdoor Unit Main PCB Circuit
When it cannot receive an effective signal for 10sec between the Main CPU and Sub CPU in outdoor unit.
1. Main PCB failure
Check Point 1 : Replace Main PCB
Change Main PCB.
Refer to error code table.
Refer to error code table.
Trouble shooting 25
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
Forced auto switch error
Indoor Unit Controller PCB Circuit Forced auto switch
When the Forced auto switch becomes ON for 10 consecutive seconds.
When the Forced auto switch becomes ON for 30 consecutive seconds.
1. Forced auto switch failure 2.Controller PCB failure
Check Point 1 : Check the Forced auto switch
Check if Forced auto switch is kept pressed.
02-34
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB.
Check ON/OFF switching operation by using a meter.
>>If Forced auto switch is detective, replace it.
Refer to error code table.
For AB*F/ AU*F/ AG*F
02-35
Check Point 4 : Replace Controller PCB
If Check Point 1 3 do not improve the symptom, change Controller PCB.
Trouble shooting 26
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Power supply frequency detection error
Indoor Unit Controller PCB Circuit
The power supply frequency cannot be recognized after 4sec of power ON.
OK
YESYES
NO
OK
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection between Outdoor Unit Main PCB and Filter PCB. (If there is loose connector or open cable)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
1. Connection failure 2. External cause 3. Controller PCB failure
Refer to error code table.
Trouble shooting 27
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:Indicate or Display:
YESYES
NO
Communication Error (Main PCB ---> Display PCB)
Indoor Unit Main PCB Circuit Display PCB
1. Connection failure 2. External cause 3. Display PCB failure 4. Main PCB failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check connection between Main PCB and Display PCB. (If there is loose connector or open cable)
Check Point 3 : Replace Display PCB
>> If Check Point 1, 2 do not improve the symptom, change Display PCB. (If the symptom does not change, replace Main PCB.)
When the Display PCB cannot receive the signal from the Main PCB.
02-36
Refer to error code table.
Trouble shooting 28
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:Indicate or Display:
YESYES
NO
Communication Error (Main PCB <--- Display PCB)
Indoor Unit Main PCB Circuit Display PCB
1. Connection failure 2. External cause 3. Display PCB failure 4. Main PCB failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check connection between Main PCB and Display PCB. (If there is loose connector or open cable)
Check Point 3 : Replace Display PCB
>> If Check Point 1, 2 do not improve the symptom, change Display PCB. (If the symptom does not change, replace Main PCB.)
When the Main PCB cannot receive the signal from the Display PCB.
02-37
Refer to error code table.
Trouble shooting 30
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Discharge temperature error
Outdoor Unit Main PCB Circuit Discharge Pipe Temperature Thermistor
02-38
When the discharge temperature becomes higher than 110°C, the compressor stops.
Check Point 1 : Check if Gas Valve is open
If it is not open, open it and check the operation.
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>>If recharging refrigerant, make sure to perform vacuuming and recharge the specified amount.
Check Point 5 : Check Outdoor FAN, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating? (Check by hand and if it is locked, replace the motor) Check Outdoor Fan Motor.
>>If the Fan Motor is defective, replace it.
Check Point 4 : Check Discharge Thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 8), If defective, replace the thermistor
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
OK OK
OK
OK
OK
OK
MPa MPa
1. Valve is close 2. EEV failure 3. Gas Leak, less 4. Discharge Thermistor failure
5. Outdoor Fan Operation failure 6. Outdoor Heat Exchanger clogged
< Cooling mode >
< Heating mode >
Check Point 1 : Check if LIquid Valve is open
If it is not open, open it and check the operation.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
Refer to error code table.
Trouble shooting 32 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
4-way valve error
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
Remove CN30 from PCB and check the resistance value of coil. Resistance value is about 1.4k
>>If it is Open or abnormal resistance value, replace Solenoid Coil.
02-39
[ Solenoid coil ]
Check each piping temperature, and the location of the valve by the temperature difference.
>>If the value location is not proper, replace 4-way valve.
[ 4-way valve ]
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1- 3 do not improve the symptom, replace Main PCB.
Check Point 2 : Check thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor, If defective, replace the thermistor
Refer to error code table.
Indoor Unit Controller PCB Circuit Heat Exchanger Temperature Thermistor Room Temperature Thermistor 4-way valve
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops.
Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 10degC
Heating operation [indoor heat exchanger temp.] - [Room temp.] < -10degC
If the same operation is repeated 5 times, the compressor stops permanently.
Trouble shooting 34
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
VDD permanence stop protection (Electric air clean)
Electric air clean unit Indoor Unit Controller PCB Circuit
When the air cleanness monitor trial protection operates 4 times.
1. Electric air clean unit failure 2. Controller PCB failure
Check Point 1 : Check the Electric air clean unit
Check the Micro switch in Electric air clean unit. (Check ON/OFF switching operation by using a meter.)
Check the front panel is closed.
02-40
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB.
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB.
Trouble shooting 35
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
Reverse-VDD permanence stop protection (Electric air clean power supply circuit abnormal)
Electric air clean unit Indoor Unit Controller PCB Circuit
The air clean operation signal was detected for 1 minute at the time of air clean mode OFF.
1. Electric air clean unit failure 2. Controller PCB failure
Check Point 1 : Replace Electric air clean unit
Change Electric air clean unit.
>>If Micro switch is detective, replace Electric air clean unit.
Refer to error code table.
Refer to error code table.
Trouble shooting 38
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Main relay welded error
Outdoor Unit Main PCB Circuit Main relay
When the signal from the outdoor unit is input after 2min.20sec. from the time of operation stop under the Main relay is OFF condition.
1. Main relay 2. Main PCB failure
02-41
Check Point 1 : Replace Main PCB
Change Main PCB.
Refer to error code table.
02-42
Trouble shooting 39
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Damper error
(Upper & Lower air flow) (Upper air flow)
Indoor unit Controller PCB Circuit Limit switch Damper
When damper opening recovery operation repeats 6 times.
1. Limit switch failure 2. Shorted connector/ wire 3. Damper faulure
4. Controller PCB failure
Refer to error code table.
Check Point 2 : Check Point 2 : Check Connector (CN18) / Wire
Check Point 1 : Check Limit switch
Check Point 4 : Replace Controller PCB
OKOK
OKOK
Check operation of limit switch. (any blocking by dust, etc.) Remove Limit switch and check ON/OFF switching operation by using a meter.
>>If Limit switch is detective, replace it.
Check loose contact of CN18 /shorted wire (pinched wire).
>>Replace Limit switch if the wire is abnormal
Check Point 2 : Check Point 3 : Check Damper
OKOK
>>Replace Damper if the damper is abnormal
If Check Point 1 3 do not improve the symptom, change Controller PCB.
Check the obstruction of damper movement. Check the damper movement.
02-43
Trouble shooting 40
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Damper error
Indoor unit Controller PCB Circuit Limit switch
When close detecting sw and open detecting sw operates simultaneously.
1. Limit switch failure 2. Shorted connector/ wire 3. Controller PCB failure
Refer to error code table.
Check Point 2 : Check Point 2 : Check Connector (CN18) / Wire
Check Point 1 : Check Limit switch
Check Point 3 : Replace Controller PCB
OKOK
Check operation of limit switch. (any blocking by dust, etc.) Remove Limit switch and check ON/OFF switching operation by using a meter.
>>If Limit switch is detective, replace it.
Check loose contact of CN18 /shorted wire (pinched wire).
>>Replace Limit switch if the wire is abnormal
OKOK
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
Trouble shooting 41
Forecast of Cause:
YESYES
NO
OKOK
OKOK
OKOK
Indoor Unit - No Power
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Point 3 : Check Electrical Components
Check Voltage of power supply.
>> Check AC198 - 264V appears at Indoor Unit Terminal L - N (Power Supply).
Check Fuse (F101) in Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB is loose, and replace Fuse.
Check Varistor (VA101, VA102) in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor.
If the symptom does not change by above Check3, replace Filter PCB.
02-44
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Trouble shooting 42
Forecast of Cause:
Check Point 3 : Check Electrical Components
OKOK
OKOK
YESYES
OK
NO
Check Point 1 : Check Installation Condition
Outdoor Unit - No Power
1. Power Supply failure 2. External cause
3. Electrical Components defective
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
YESYES
Check Fuse (F2, F4) in Main PCB.
>> If Fuse is open, check loose terminal or removed connector (CN1) , and replace Fuse.
Check Varistor in Main PCB (VA103).
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
If the symptom does not change by above Check 3, replace Main PCB.
Check Active Filter Module. (PARTS INFORMATION 3) >>If Active Filter Module is abnormal, replace it.
02-45
Trouble shooting 43
Forecast of Cause:
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check Electrical Components at Indoor and Outdoor
OK
OK
OKOK
No Operation (Power is ON)
1. Setting/ Connection failure 2. External cause
3. Electrical Component defective
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control, or terminals between Indoor Units. Or, check if there is an open cable connection. Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and Data & Technical Manual.
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
02-46
Attention
Trouble shooting 44
Forecast of Cause:
Check Point 2 : Check Outdoor Unit Operation
Check Point 1 : Check Indoor Unit
Check Point 3 : Check Site Condition
Check Point 5 : Check Refrigeration Cycle
Check Point 4 : Check Indoor/ Outdoor Installation Condition
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
OKOK
OKOK
OKOK
OKOK
MPa MPa
No Cooling / No Heating
1. Indoor Unit error 2. Outdoor Unit error
3. Effect by Surrounding environment
4. Connection Pipe / Connection Wire failure 5. Refrigeration cycle failure
Does Indoor Unit FAN run on HIGH FAN?
Is Air Filter dirty? Is Heat Exchanger clogged?
Check if Energy save function is operated.
Check if Outdoor Unit is operating (If not, refer to Trouble shooting 30)
Check any objects that obstruct the air flow route.
Check clogged Heat Exchanger.
Is the Valve open?
Is capacity of Indoor Unit fitted to Room size?
Any windows open? Or direct sunlight ?
Check connection pipe (specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 4)
Check Compressor (PARTS INFORMATION 1,2)
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-47
Trouble shooting 45
Forecast of Cause :
Trouble shooting 46
Forecast of Cause:
OK
OK
OK
OK
OKOK
OKOK
OKOK
Abnormal Noise
1. Abnormal installation(Indoor/ Outdoor) 2. Fan failure(Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit. (Check and correct followings)
Abnormal noise is coming from Outdoor Unit. (Check and correct followings)
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is Main Unit installed in stable condition? Is the installation of Air suction grille and front panel normal?
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is Main Unit installed in stable condition? Is Fan Guard installed normally?
Check if vibration noise by loose bolt or contact noise of piping is happening.
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
Water Leaking
Diagnosis method when water is spitting out.
Is the filter clogged?
Check Gas Pressure and correct it if there was a gas leak.
Diagnosis method when water leak occurs
Is Drain Hose connection loose? Is there a trap in Drain Hose?
Is Drain Hose clogged?
Is Main Unit installed in stable condition? Is Main Unit broken or deformed at the time of transportation or maintenance?
Is Fan rotating?
>> Check Fan Motor (PARTS INFORMATION 5)
02-48
OKOK
MPa MPa
Is Float Switch defective?
>> Check Float Switch (Refer to Trouble Shooting 6)
1. Erroneous installation 2. Drain hose failure 3. Float Switch failure
SERVICE PARTS INFORMATION 1
MPa
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check Filter PCB, Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
Check Filter PCB, Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas Pipe Valve open? (Low Pressure is too low)
Check if Refrigerant is leaking. (Recharge Refrigerant)
Check if Strainer is clogged. (PARTS INFORMATION 4)
>> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.)
Abnormal noise
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Check if vibration noise by loose bolt or contact noise of piping is happening.
02-49
2-4 SERVICE PARTS INFORMATION
MPa
SERVICE PARTS INFORMATION 2
Check Point 1 : Check Connection
UU(RED)(RED)
V V (WHITE)(WHITE)WW
(BLACK)(BLACK)
Terminal cover opened
Check Point 2 : Check Winding Resistance
Check Point 3 : Replace Main PCB
U
V
W
Inverter Compressor
Check terminal connection of Compressor (loose or incorrect wiring)
Check connection of Main PCB (Loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If the symptom does not change with above Check 1, 2, replace Main PCB.
Resistance Value : 1.41 ( at 20°C )
Resistance Value : 0.88 ( at 20°C )
02-50
MAIN PCB
W304
W305 W303
RED
WHITE
BLACK
Compressor
For AO*18LMAK2/ 24LMAM2
For AO*30LMAW4
SERVICE PARTS INFORMATION 3
Active Filter Module
02-51
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Check Point 2 : Check the Output DC voltage (between P and N1)
L2L1
P
N2
N1
Power factor control
D1
(+)
( )
Io
Check the Output DC voltage (between P and N1) of compressor stopping and operating.
If it is abnormal,replace ACTIVE FILTER MODULE
Remove connector, check the open or short-circuit and the diode in the module
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping, Active Filter Module is detective. >> Replace Active Filter Module
Terminal
Resistance value
L2
L1
L1,L2
P
P
Control Box
N1
N1
(+)
(+)
( )
( )
Tester(+) Tester(-)
Check the open or short-circuit
L2
P
P
N2
L2
L2
Check the diode
0
360k
720k
1.65M /
20%
+
-
360k
20%
+
-
20%
+
-
(Ref. value 1)
1.14M
(Ref. value 2)
1.01M /
(Ref. value 1)
761k
(Ref. value 2)
Terminal
Resistance value
Tester(+) Tester(-)
1.32M /
(Ref. value 1)
663k
(Ref. value 2)
1.01M /
(Ref. value 1)
762k
(Ref. value 2)
Ref. value 1 Specifications for Multimeter Manufacturer : FLUKE Model name : FLUKE11 Power source : DC9V.
Ref. value 2 Specifications for Multimeter Manufacturer : Sanwa Model name : PM3 Power source : DC3V.
SERVICE PARTS INFORMATION 4
Check Point 2 : Check Coil of EEV
Yellow - Brown
Orange - Red
Blue - Brown
White - Red
Read wire
46 4
Resistance value
Check Point 1 : Check Connections
Check Point 3 : Check Voltage from Main PCB.
Check Point 4 : Check Noise at start up
DC
at 20°C
Outdoor unit Electronic Expansion Valve ( EEV )
Check connection of connector ( Loose connector or open cable )
Remove connector, check each winding resistance of Coil.
If Resistance value is abnormal, replace EEV.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
02-52
EXPANSION VALVE COIL A
EXPANSION VALVE COIL B
CN27
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
1 2 3 4 5 6
E V
CN27
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
1 2 3 4 5 6
E V
EXPANSION VALVE COIL A
EXPANSION VALVE COIL B
EXPANSION VALVE COIL C
EXPANSION VALVE COIL D
CN27
CN50
CN51
RED
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
BLACK WHITE WHITE WHITE WHITE WHITE
BROWN BLUE
ORANGE YELLOW WHITE
WHITE
GREEN
BLACK
GREEN GREEN GREEN GREEN
RED BROWN BLUE ORANGE YELLOW WHITE
GREEN
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
2
1
1 3
4 5 6 7
4 5 6
7
E V
E V
E V
CN52
GREEN
BLACK
GREEN GREEN GREEN GREEN
RED BROWN BLUE ORANGE YELLOW WHITE
GREEN
1 2 3 4 5 6
1 2 3 4 5 6
1 3 4 5 6
7
E V
For AO*18LMAK2 / AO*24LMAM2 For AO*30LMAW4
Check Point 5 : Check Opening and Closing Operation of Valve
Pipe (In)
Pipe (Out)
Hi TEMP.
Pipe (In)
Hi TEMP.
Normal TEMP.
CLOSE Example : Hot Gas
OPEN Example : Hot Gas
Pipe (Out)
Hi TEMP.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
Check Point 6 : Check Strainer
When Valve is closed, it has a temp. difference between Inlet and Outlet.
If it is open, it has no temp. difference between Inlet and Outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-53
SERVICE PARTS INFORMATION 5
Check Point : AB*14/ 18/ 24LBAJ
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
445 8%
346 8%
124 8%
80.0 8%
80.0 8%
Resistance value
(AC)
Thermal protector
Pr
VIOLET
BLUE
PINK
RED
BLACK
WHITE
140°C
at 20°C
Indoor Unit Fan Motor
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
02-54
AB*14LBAJ
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
222 8%
175 8%
279 8%
63.5 8%
63.5 8%
Resistance value
at 20°C
AB*24LBAJ
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
291 8%
204 8%
182 8%
78.5 8%
78.5 8%
Resistance value
at 20°C
AB*18LBAJ
Check Point : AR*9LUAB/ 12/ 14/ 18/ 22LUAD
(AC)
Thermal protector
Pr
VIOLET
BLUE
PINK
RED
BLACK
WHITE
150°C
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
90.3 8%
152 8%
222 8%
42.9 8%
42.9 8%
Resistance value
at 20°C
AR*12/ 14/ 18/ 22LUAD
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
367 8%
145 8%
160 8%
62.6 8%
62.6 8%
Resistance value
at 20°C
AR*9LUAB
Check Point : AU*12/ 14/ 18LBAB
(AC)
VIOLET
BLUE
YELLOW
PINK
RED
BLACK
WHITE
Thermal protector
140°C
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
02-55
Red Pink
Pink Violet
Violet Blue
Blue Black
White Red
Read Wire
431 8%
10.7 8%
55.5 8%
55.5 8%
35.7 8%
Resistance value
at 20°C
AU*18LBAB
Red Pink
Pink Violet
Violet Blue
Blue Black
White Red
Read Wire
427 8%
191 8%
191 8%
92.8 8%
92.8 8%
Resistance value
at 20°C
AU*12/ 14LBAB
Pr
Check Point : AS*18/ 24LBAJ
(AC)
BLUE
YELLOW
RED
BLACK
WHITE
Thermal protector
140°C
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Blue Red
Blue Black
White Red
Read Wire
129 8%
21.0 8%
277 8%
Resistance value
at 20°C
Pr
Check Point : AS*7/ 9/ 12LMACW
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
White Yellow
Black Yellow
Read Wire
138 8%
136 8%
Resistance value
at 20°C
(AC)
Thermal protector
WHITE
YELLOW
BLACK
Pr
SERVICE PARTS INFORMATION 6
Check Point : AO*18LMAK2/ 24LMAM2
Red - Blue
Red - Black
White - Red
Read Wire
8%
96.3
54.7
8%
185 8%
Resistance value
(AC)
Thermal protector
Pr
BLUE
RED
BLACK
WHITE
150°C
at 20°C
Outdoor Unit Fan Motor
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
02-56
3 . REPLACEMENT PARTS
R410A
INVERTER (MULTI )
Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type
Compressor
PTC Thermistor
Thermistor (Discharge temp.)
Thermistor (2-way valve temp.)
Thermistor (3-way valve temp.)
1. REPLACEMENT PARTS (For OUTDOOR UNIT)
1-1 For AO*18LMAK2/ 24LMAM2
1-1-1 PARTS LAYOUT DRAWING
03-01
Fan motor
Fan
Heat Exchanger
Coil (Expansion valve)& Expansion valve
Solenoid
Main PCB
Active Filter Module
Pressure SW
Accumulator
4-way valve
Thermistor (Heat exchanger temp.)
2-way valve (Liquid)
3-way valve (Gas)
03-02
Thermo Holder& Thermistor (Outdoor Temp.)
BIND (Thermistor (Heat exchanger temp.)) (Thermistor (Outdoor temp.))
BIND (Thermistor (Outdoor temp.))
1-1-2 WIRING (For AO*18LMAK2/ 24LMAM2)
03-03
CLAMP Solenoid wire Fan motor wire Fan capacitor wire
Compressor wire
BIND Thermistor (Discharge temp.) Thermistor (2/3-way valve temp.) Thermistor (Heat exchanger temp.) Thermistor (Outdoor temp.) PTC Thermistor Coil (Expansion valve)X2 Pressure SW
1. TOP PANEL removal
Remove the 5 mounting screws. Remove the TOP PANEL upward.
2. CONTROL BOX COVER removal
Remove the 3 mounting screws. Remove the CONTROL BOX COVER and TERMINAL COVER.
REAR VIEW
1-1-3 DISASSEMBLY PROCESS (For AO*18LMAK2/ 24LMAM2)
03-04
TOP PANEL
CONTROL BOX COVER
TERMINAL COVER
3. MAIN PCB removal
Remove the 4 mounting screws. Remove the connectors and cords. (Refer to VIEW -A,-B) Remove the MAIN PCB.
03-05
VIEW - A
C
DETAIL C
VIEW - B
A
B
Thermistor (Discharge temp.) (Yellow)
Thermistor (2/3-way valve temp.) (White)
Thermistor (Heat EX temp.) (Red)
Thermistor (Heat sink) (Black)
Thermistor (Outdoor temp.) (Blue)
Pressure SW (Red)
PTC Thermistor (Green)
Coil(Expansion valve) (Red)
Coil(Expansion valve) (White)
Solenoid (White)
Fan motor
SCREW
Compressor
Red
White
Black
Twist 3 times or more
Active Filter Module
" TM104 " (Yellow)
" TM105 " (Blue)
From CN407
" + " (Red) " - " (Black)
" P " (White) " N1 " (Purple)
" L2 " (White)
" L1 " (White)
UNIT A
POWER
UNIT B
1 1
2(N) 2(N)
L
N
3 3
LABEL Wire UNIT A: 1 W4(Black) UNIT A: 2 W5(White) UNIT A: 3 W8(Red) UNIT B: 1 W6(Black) UNIT B: 2 W7(White) UNIT B: 3 W9(Yellow) POWER: L Fuse holder (Black) POWER: N W2(White)
Loading...