A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 4°F(2°C) higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is 5°F(2.5°C) lower than a set temperature, the compressor will be
stopped.
* When the room temperature is between +4°F(+2°C) to -5°F(-2.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure1 based on the
fan speed mode and the outdoor temperature.
( Table1 : Compressor Frequency Range )
minimum
frequency
maximum
frequency
ASU9RLF22rps79rps
ASU12RLF18rps96rps
ASU15RLS15rps80rps
( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside airOutside air
temperaturetemperature
A zone79rps61rps52rps37rps
B zone79rps61rps52rps37rps
C zone79rps61rps52rps37rps
D zone52rps43rps37rps28rps
E zone64rps55rps49rps36rps
F zone64rps55rps49rps36rps
A zone
B zone
C zone
D zone
E zone
F zone
A zone
B zone
C zone
D zone
E zone
F zone
93.2°F
(34°C)
86°F
(30°C)
66.2°F
(19°C)
50°F
(10°C)
32°F
(0°C)
A zone
B zone
C zone
D zone
E zone
F zone
96.8°F
(36°C)
89.6°F
(32°C)
69.8°F
(21°C)
53.6°F
(12°C)
35.6°F
(2°C)
9RLF
12RLF
15RLS
HiMeLoQuiet
96rps61rps51rps33rps
96rps61rps51rps33rps
96rps61rps51rps33rps
57rps42rps36rps27rps
57rps42rps36rps27rps
57rps42rps36rps27rps
80rps45rps37rps29rps
80rps45rps37rps29rps
80rps45rps37rps29rps
47rps37rps31rps22rps
47rps37rps31rps22rps
47rps37rps31rps22rps
01-01
Page 5
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 6°F(3°C) than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 5°F(2.5°C) than a set temperatire, the compressor will be
stopped.
* When the room temperature is between +5°F(+2.5°C) to -6°F(-3°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
( Table2 : Compressor Frequency Range )
minimum
frequency
ASU9RLF22rps99rps
ASU12RLF18rps130rps
ASU15RLS15rps119rps
maximum
frequency
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table3.
However, after the compressor is driven, the indoor unit shall run at operation frequency of
64rps (9RLF), 61rps (12RLF), 51rps (15RLS), for a minute.
( Table3 : Compressor frequency )
Operating
frequency
9RLF
X zone
J zone
Y zone
37rps
28rps
0rps
12RLF
X zone
J zone
Y zone
( Fig.2 : Compressor Control based on Room Temperature )
RoomRoom
temperaturetemperature
Ts+3°F
(Ts+1.5°C)
Ts-1°F
(Ts-0.5°C)
Ts+1°F
(Ts+0.5°C)
Ts-3°F
(Ts-1.5°C)
X zone
J zone
Y zone
Operating
frequency
33rps
25rps
0rps
15RLS
X zone
J zone
Y zone
Operating
frequency
29rps
18rps
0rps
01-02
Page 6
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 64°F(18°C) and 88°F(30°C) in 2°F(1°C) steps.
Operation flow chart
START
Room temp.
>Ts+4°F(2°C)?
NO
YES
YES
or operation command other than
Room temp.
<Ts- 4°F(2°C)?
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
auto changeover operation?
NO
YES
NO
NO
YES
TS : Setting temperature
in OFF state for 6 minutes or
or operation command other than
auto changeover operation?
COOLING OPERATION
Thermostat remains
longer?
NO
System stops
NO
YES
YES
01-03
Page 7
5. INDOOR FAN CONTROL
1. Fan speed
( Table4 : Indoor Fan Speed )
Operation modeAir flow mode
Heating
Cooling/ Fan
Dry
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
Hi
Me+
Me
Lo
Quiet
Cool air prevention
S-Lo
Hi
Me
Lo
Quiet
Speed (rpm)
ASU9RLFASU12RLFASU15RLS
1330
1290
1160
980
710
600
480
1330
1160
930
680
X zone: 680
J zone: 660
1500
1360
1230
1050
770
600
480
1440
1230
1000
750
X zone: 750
J zone: 730
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure3.
On the other hand, if switched in [HIGH][QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH,as shown in Table4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
TR-Ts > 5°F
=
(2.5°C)
5°F > TR-Ts > 3°F
(2.5°C)(1.5°C)
3°F > TR-Ts
(1.5°C)
=
TR-Ts > 4°F
4°F > TR-Ts > 2°F
(2°C)(1°C)
2°F > TR-Ts
(1°C)
(2°C)
=
HIGH mode
MED mode
LOW mode
When the room
temperature drops
When the room
temperature rises
TR : Room temperature
Ts : Setting temperature
4. DRY OPERATION
Refer to th
During the d
eT
a
ble4.
ry mode operation, the fan speed sett
ing c
an not be
c
hange
d
.
01-04
Page 8
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure4.
On the other hand, if switched in [HIGH][QUIET], the indoor motor will run at a constant airflow
of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table4.
( Fig.4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > -2°F
=
(-1°C)
-2°F > TR-Ts > -4°F
(-1°C)(-2°C)
=
-4°F > TR-Ts
(-2°C)
When the room
temperature rises
LOW mode
MED mode
MED+ mode
When the room
temperature drops
TR-Ts > -3°F
=
-3°F > TR-Ts > -5°F
(-1.5°C)(-2.5°C)
-5°F > TR-Ts
(-2.5°C)
(-1.5°C)
=
TR : Room temperature
Ts : Setting temperature
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure5, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.5 : Cool Air Prevention Control)
Indoor heat exchanger
temperature
107.6°F (42°C)
102.2°F (39°C)
98.6°F (37°C)
86°F (30°C)
Hi
Me+
Lo
Cool air
prevention
S-Lo
Indoor heat exchanger
temperature
98.6°F (37°C)
93.2°F (34°C)
89.6°F (32°C)
75.2°F (24°C)
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow [AUTO] at cooling mode, and the indoor fan motor will run as shown in Figure6.
( Fig.6 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 5)
S-Lo
OFF
10306018060180601030
( Table5 : Indoor fan speed )
Dry
X zoneJ zone
ASU9/ 12RLF680rpm660rpm
ASU15RLS750rpm730rpm
Y zone
0 480rpm
0 480rpm
Cooling
480rpm
480rpm
(SEC)
01-05
Page 9
6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the type of the outdoor fan motor. The control method is different
between AC motor and DC motor.
( Table6 : Type of Motor )
AC MotorDC Motor
ASU9/ 12RLF,15RLS
2. Fan Speed
( Table7 : Outdoor fan speed )
Zone
CoolingHeating
(rpm)
Dry
Y
Z
860/ 780/ 760/ 470
860/ 470/ 330
ASU9RLF
F
G
ASU12RLF
Y
Z
F
G
Y
Z
850/ 750/ 670/ 500
850/ 500/ 350
1050/ 1010/ 870/ 720/ 530
870/ 530/ 300
ASU15RLS
F
G
300/ 250
250/ 200
Refer to Fig.7
( Fig.7 : Outside air temperature zone selection )
Outside air
temperature
69.8°F (21°C)
53.6°F (12°C)
35.6°F ( 2°C)
Y zone
Z zone
F zone
G zone
230
150
330
230
Outside air
temperature
66.2°F (19°C)
50°F (10°C)
32°F ( 0°C)
900/ 760/ 720/ 680/ 470
950/ 850/ 750/ 680/ 550/ 450
1100/ 850/ 780/ 590/ 480
760/ 470
760/ 470
530
The outdoor fan speed mentioned above depends on the compressor frequency.
*
(When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the
lower speed.)
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
*
as table8 without relating to the compressor frequency.
( Table8 : Outdoor fan speed after the defrost )
ASU9RLF900rpm
ASU12RLF950rpm
ASU15RLS1100rpm
01-06
Page 10
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow:
Types of Air flow Direction Setting:
,,,,, :DuringHeating/Cooling/Drymodes
Air Direction RangeFig.8 :
The Remote Controller's display does not change.
1
2
3
4
5
6
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode
Horizontal flow
Heating modeDownward flow
During AUTO mode operation, for the first a few minutes after beginning operation,
air-flow will be horizontal 1; the air direction cannot be adjusted during this period.
The air flow direction setting will temporarily become 1 when the temperature of the air -flow is
low at the start of the Heating mode.
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Table9 : Swinging Range)
Range
Cooling / Dry mode
Fan mode ()
Heating mode
Fan mode ()
The SWING operation may stop temporarily when the air conditioner’s fan is not operating,
or when operating at very low speeds.
01-07
Page 11
8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table10.
(Table10 : Compressor Operation Frequency Range)
CoolingHeating
MinMaxMinMaxMinMax
ASU9RLF
ASU12RLF
ASU15RLS15rps80rps15rps119rps18rps29rps
22rps79rps22rps99rps28rps37rps
18rps96rps18rps130rps25rps33rps
Dry
2. OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the Figure9.
(Fig.9 : Compressor Control at Start-up)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
(Frequency)
ASU9RLF
ASU12RLF
ASU15RLS
(Time)
ASU9RLF
ASU12RLF
ASU15RLS
Time
Frequency
70rps82rps92rps96rps96rps96rps
56rps74rps87rps97rps108rps119rps
40rps57rps72rps80rps101rps110rps
TimeTime
80sec140sec200sec380sec440sec440sec
80sec140sec200sec380sec440sec500sec
80sec110sec140sec200sec350sec410sec
TimeTimeTime
Frequency
FrequencyFrequency
TimeTimeTimeTime
Time
Frequency
Time
Frequency
01-08
Page 12
9. TIMER OPEARTION CONTROL
The table11 shows the available timer setting based on the product model.
(Table11 : Timer Setting)
ON TIMER / OFF TIMERPROGRAM TIMERSLEEP TIMER
ASU9/ 12RLF,15RLS
1. OPEARTION FREQUENCY RANGE
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Stop mode
Set time
Operation mode
Stop mode
Set timeSet timeSet time
Operation mode
Stop mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest
to the clock's current timer setting.
The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
01-09
Page 13
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically.
If the operation mode or the set temperature is change after the sleep timer is set, the operation is
continued according to the changed setting of the sleep timer from that time ON.
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 2°F(1°C).
It increases the setting temperature another 2°F(1°C) after 1 hour.
After that, the setting temperature is not changed and the operation is stopped at the time
of timer setting.
Set temperature rises
( Ts : Set temperature )
+4°F (2°C)
+2°F (1°C)
Ts
Stop of operation
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 2°F(1°C).
It decreases the setting temperature another 2°F(1°C) every 30 minutes.
Upon lowering 8°F(4°C) the setting temperature is not changed and the operation stops at
the time of timer setting.
Set temperature lowers
( Ts : Set temperature )
Ts
-2°F (-1°C)
-4°F (-2°C)
-6°F (-3°C)
-8°F (-4°C)
Set
30min
30min
Stop of operation
30min
01-10
Page 14
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the Table12.
The compressor frequency, the temperatures detected by the discharge temperature sensor, the
indoor heat exchanger sensor, the outdoor heat exchanger sensor,
and the outdoor temperature sensor.
Table12 : The pulse range of the electronic expansion valve control
Operation modePulse range
ASU9/ 12RLF
Cooling / Dry mode
Heating mode
Cooling / Dry mode
ASU15RLS
Heating mode
The expansion valve is set at 480 pulses after 110 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (528 pulses are input to the closing direction).
between 60 to 480 pulses.
between 60 to 480 pulses.
between 60 to 480 pulses.
between 45 to 480 pulses.
11. TEST OPERATION CONTROL
Under the condition where the air conditioner runs, press the test run button of the remote
control, and the test operation control mode will appear. During test running, the operation lamp
and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode,
and the compressor will continue to run regardless of whether the room temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is
stopped, even if any operation is given.
13. FOUR-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode, the
compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after
the compressor stopped.
14. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically started with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, since the timer operation time
is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF)
the indoor unit body timer lamp.
[Operation contents memorized when the power is interrupted]
Operation mode
Set temperature
Set air flow
Timer mode and timer time
Set air flow Direction
Swing
ECONOMY operation
MINIMUM HEAT operation
01-11
Page 15
15. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table13.
If the remote control is lost or battery power dissipated, this function will work without the remote control.
(Table13)
Manual auto operation
OPERATION MODEAuto changeover
FAN CONT. MODEAuto
TIMER MODEContinuous
SETTING TEMP.75.2°F (24°C)
SETTING LOUVERStandard
SWING
ECONOMY
OFF
OFF
(No timer setting available)
Forced cooling operation
Cooling
Hi
Room Temp is not controlled
Horizontal
OFF
-
16. FORCED COOLING OPERATION
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more.
During the forced cooling operation, it operates regardless of room temperature sensor.
Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON
and 1 second OFF on both operation LED and timer LED (same as test operation).
Forced cooling operation is released after 60 minutes of starting operation.
The FORCED COOLING OPERATION will start as shown in Table13.
17. COMPRESSOR PREHEATING
When the outdoor temperature is lower than 68°F(20°C) and the heating operation has been
stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started and when the outdoor temperature rises to 77°F(25°C) or greater,
preheating is ended.
18. MINIMUM HEAT OPERATION
The MINIMUM HEAT operation functions by pressing MIN.HEAT button on the remote controller.
The MINIMUM HEAT operation is almost the same operation as below settings.
( Table14 )
ModeHeating
Setting temperature50°F (10°C)
Fan modeAUTO
19. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
The ECONOMY operation is almost the same operation as below settings.
Outdoor heat exchanger temp. < Outside air temp.- 12.6°F (7°C)
or Outdoor heat exchanger temp. < - 4°F (-20°C)
(at outside air temp. < 14°F (-10°C))
Less than 10 minutes
( For
intermittent operation )
OFF count of the compressor
40 times
=
=
=
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 17.
(Table 17 : Defrost Release Condition)
Release Condition
=
Outdoor heat exchanger temperature sensor value is higher than
+60.8°F (+16°C) or Compressor operation time has passed 15 minutes.
01-13
Page 17
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 10 minutes)
Normal defrost
Outside air temp. > 14°F
Outdoor HEX temp.
Below 1.4°F
(-17°C)
=
(-10°C)
Outside air temp. < 14°F
(-10°C)
Outdoor HEX temp.
- Outside air temp.
Below - 12.6°F(7°C)
or
Outdoor HEX temp.
Below - 4°F(-20°C)
Defrost start
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Integrating defrost
Intermittent operationContinuous operation
Compressor
OFF count :
40 times
Compressor
integrating
operation:
Over 240 minutes
Outdoor HEX temp.
Below 26.6°F(-3°C)
Outdoor fan : OFF
Compressor speed:0rps
EEV : 480pulse
4-way valve : OFF
Compressor speed : 90rps (09/ 12)
70rps (15)
Outdoor HEX temp.: Over 60.8°F(16°C)
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-14
Page 18
21. OFF DEFROST OPEARTION CONTROL
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit defrost lamp
lighting, the outdoor unit will allow the heat exchanger to defrost, and then stop.
1. OFF DEFROST OPERATION CONDITION
In heating operation, the outdoor heat exchanger temperature is less than 24.8°F (-4°C), and
compressor operation integrating time lasts for more than 30 minutes.
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 60.8°F (16°C)
or Compressor operation time has passed 15 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature:
Below 24.8°F(-4°C)
and
Compressor integrating operation:
Over 30 minutes
Defrost start
Defrost Indicater:
[Defrost lamp]
Lighting
Outdoor heat exchanger temperature:
Over 60.8°F (16°C) or
Compressor ON time: Over 15 minutes
Defrost end
01-15
Page 19
22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of the control of
the compressor frequency is released.
When the discharge temperature becomes higher than Temperature,the compressor is stopped
and the indoor unit LED starts blinking.
(Table18 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
213.8°F
(101°C)
ASU9/ 12RLF,15RLS
Temperature
219.2°F
(104°C)
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
Temperature
230°F
(110°C)
(Table19 : Current Release Operation Value / Release Value)
[ Heating ]
ASU9RLF
OT (Control / Release)
62.6°F(17°C)
53.6°F(12°C)
41°F(5°C)
OT : Outdoor Temperature
5.5A/ 5.0A
6.0A/ 5.5A
7.0A/ 6.5A
7.0A/ 6.5A
ASU12RLF
OT (Control / Release)
62.6°F(17°C)
53.6°F(12°C)
41°F(5°C)
OT : Outdoor Temperature
5.5A/ 5.0A
7.0A/ 6.5A
7.5A/ 7.0A
8.5A/ 8.0A
[ Cooling ]
ASU9RLF
OT (Control / Release)
114.8°F(46°C)
104°F(40°C)
OT : Outdoor Temperature
3.5A/ 3.0A
4.0A/ 3.5A
5.5A/ 5.0A
114.8°F(46°C)
ASU12RLF
OT (Control / Release)
4.0A/ 3.5A
104°F(40°C)
OT : Outdoor Temperature
5.0A/ 4.5A
6.0A/ 5.5A
ASU15RLS
OT (Control / Release)
62.6°F(17°C)
53.6°F(12°C)
41°F(5°C)
OT : Outdoor Temperature
OT (Control / Release)
114.8°F(46°C)
104°F(40°C)
OT : Outdoor Temperature
7.0A/ 6.5A
9.0A/ 8.5A
10.0A/ 9.0A
10.0A/ 9.5A
ASU15RLS
4.5A/ 3.0A
6.0A/ 5.5A
8.5A/ 8.0A
01-16
Page 20
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
*1. When the temperature rises.
*2. When the temperature drops.
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 152.6°F (67°C) or greater,
the compressor and the outdoor fan motor are stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
[ Control System ]
Indoor heat exchange
temperature
The compressor frequency is
decreased 3rps every 60seconds.
127.4°F
(53°C)
It returns to the normal operation
122°F
(50°C)
01-17
Page 21
WALL MOUNTED type
INVERTER
R410A
2 .TROUBLE SHOOTING
Page 22
2. TROUBLESHOOTING
2-1 ERROR DISPLAY
2-1-1 WIRED REMOTE CONTROLLER DISPLAY (OPTION)
1. SELF - DIAGNOSIS
When "Er" in Temperature Display is displayed, inspection of the air conditioning system is necessary.
Please consult authoilzed service personnel.
Unit number (usually 0)
Error code
SUMOTUWETH FR
ex. Self-diagnosis check
SA
Error code
Error contents
Serial communication error
Remote controller communication error
Indoor unit main PCB error
Manual auto switch error
Room temperature sensor error
Indoor unit Heat Ex. sensor error
Indoor unit fan motor error
Outdoor unit main PCB error
PFC circuit error
IPM error
Discharge thermistor error
Outdoor unit Heat Ex. sensor error
Outdoor thermistor error
Current sensor error
Trip detection
Compressor motor control error
Outdoor unit fan motor error
4-way valve error
Discharge temperature error
Trouble
shooting
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
02-01
Page 23
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons,, [ON/OFF] simultaneously for 3 seconds
or more to start the self-diagnosis.
Error code
Error history number
SUMOTUWETH FR
3. Press the SET TEMPERATURE button to select the error history number.
SA
Lower
01234 567
FEdcbA98
Raise
ı
ı
4. Press the SET TEMPERATURE buttons,simultaneously for 3 seconds or more
or there is no key input for 60 seconds to stop the display.
2-1-2 OUTDOOR UNIT DISPLAY
1. ERROR DISPLAY
1-1. For ASU9/ 12RLF, 15RLS (AOU9/ 12RLFW, 15RLS)
Error contents
Discharge temperature error
IPM error
Current sensor error
Compressor motor control error
Outdoor unit sensor error
(Discharge or Outdoor or Heat EX.)
Outdoor unit fan motor error
LED Flashing Pattern
Continuously lighting
0.5sec ON / 0.5sec OFF
2sec ON / 2sec OFF
0.1sec ON / 2sec OFF
0.1sec ON / 0.1sec OFF
5sec ON / 5sec OFF
Trouble
shooting
19
10
14
16
11,12,13
17
02-02
Page 24
2-1-3 INDOOR UNIT DISPLAY
1. ERROR DISPLAY
Error contents
Serial communication error
Remote controller communication error
Indoor unit main PCB error
Manual auto switch error
Room temperature sensor error
Indoor unit Heat Ex. sensor error
Indoor unit fan motor error
Outdoor unit main PCB error
PFC circuit error
IPM error
Discharge thermistor error
Outdoor unit Heat Ex. sensor error
Outdoor thermistor error
Current sensor error
Trip detection
Compressor motor control error
Outdoor unit fan motor error
4-way valve error
Discharge temperature error
Operation lamp
(Green)
1 times flash
1 times flash
3 times flash
3 times flash
4 times flash
4 times flash
5 times flash
6 times flash
6 times flash
6 times flash
7 times flash
7 times flash3 times flash
7 times flash
8 times flash
9 times flash
9 times flash
9 times flash
9 times flash
10 times flash
Timer lamp
(Orange)
1 times flash
2 times flash
2 times flash
5 times flash
1 times flash
2 times flash
1 times flash
2 times flash
4 times flash
5 times flash
1 times flash
4 times flash
4 times flash
4 times flash
5 times flash
7 times flash
9 times flash
1 times flash
Economy lamp
(Green)
Continuous flash
Trouble
shooting
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
02-03
Page 25
2-2 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1-1
OUTDOOR UNIT Error Method:
Serial communication error
(Serial Reverse Transfer Error)
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit Fan motor
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 1 time Flash, Timer lamp: 1 time Flash
ERROR CODE : [E : 11]
Detective details:
When the indoor unit cannot receive the serial signal from Outdoor unit
more than 2minutes after power ON, or the indoor unit cannot receive
the serial signal more than 15seconds during normal operation.
Forecast of Cause:
1. Connection failure2. External cause3. Main PCB failure4. Outdoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of
Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Economy lamp: Continuous flash.
NO
Check Point 1-2: Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3.
>> If it is abnormal, Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB.
>> If Outdoor fan motor is normal, replace Main PCB.
BLACK
WHITE
RED
BLACK
WHITE
1
2
3
L1
L2
+
-
02-04
Page 26
Trouble shooting 1-2
INDOOR UNIT Error Method:
Serial communication error
(Serial Forward Transfer Error)
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 1 time Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 11]
Detective Actuators:
Indoor unit Controller PCB
Indoor unit Fan motor
Detective details:
When the outdoor unit cannot receive the serial signal from Indoor unit
more than 10seconds.
Forecast of Cause:
1. Connection failure2. External cause3. Controller PCB failure 4. Indoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of
Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
OK
NO
Check Point 1-2: Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit,
and check if there is a disconnection of the cable.
OKOK
Check Point 2 : Check Remote Control and Controller PCB
Check Voltage at CN305 (terminal 1-3) of UTY-XCBXZ1(Communication kit).
(Power supply to Remote Control)
>> If it is DC13V, Remote Control is failure. (Controller PCB is normal)>> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Upon correcting the removed connector or mis-wiring, reset the power.
02-06
Page 28
Trouble shooting 3
INDOOR UNIT Error Method:
Indoor unit main PCB error
Indicate or Display:
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 3 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 32]
Detective Actuators:
Indoor unit Controller PCB
Detective details:
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
Forecast of Cause:
1. External cause2. Defective connection of electric components3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YESYES
Check Point 2 :
Check Indoor unit electric components
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
NO
Check Point 1-2 :
Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 3 : Replace Controller PCB
Change Controller PCB.
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a nonvolatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
02-07
Page 29
Trouble shooting 4
INDOOR UNIT Error Method:
INDOOR UNIT
Manual auto switch error
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 3 times Flash, Timer lamp: 5 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 35]
Detective Actuators:
Indoor unit Controller PCB
Indicator PCB
Detective details:
When the Manual Auto Switch becomes ON for consecutive 60 or
more seconds.
Manual auto switch
Forecast of Cause :
1. Manual auto switch failure2.Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual auto switch
Check if Manual auto switch is kept pressed.
Check ON/OFF switching operation by using a meter.
>>If Manual Auto Switch is disabled (on/off switching), replace it.
OKOK
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB and Indicator PCB.
02-08
Page 30
Trouble shooting 5
INDOOR UNIT Error Method:
INDOOR UNIT
Room Temperature Sensor Error
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 4 times Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 41]
Detective Actuators:
Indoor unit Controller PCB
Detective details:
When Room Temperature Thermistor open or short-circuit is detected.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
20°C10°C5°C0°C-5°C-10°C-20°C-30°C
62.9103.3134.2176.0233.2312.3579.61131.9Resistance Value (k )
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
50°C
17.125.639.6Resistance Value (k )
60°C
11.6
63°C40°C30°C
10.4
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR
BLACK
1
1
BLACK
2
2
CN4
If the voltage does not appear, replace Controller PCB.
BLACK
3
3
BLACK
4
4
(PIPE)
THERMISTOR
(ROOM TEMP.)
02-10
Page 32
Trouble shooting 7
INDOOR UNIT Error Method:
Indoor unit fan motor error
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 5 times Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 51]
Detective Actuators:
Indoor unit Controller PCB
Indoor unit fan motor
Detective details:
When the condition that actual frequency of Indoor Fan is
below 1/3 of target frequency is continued more than 56 seconds.
Forecast of Cause:
1. Fan rotation failure2. Fan motor winding open3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
OK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
02-11
Page 33
Trouble shooting 8
OUTDOOR UNIT Error Method:
Outdoor unit main PCB error
Indicate or Display:
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 6 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 62]
Detective Actuators:
Outdoor unit Main PCB
Detective details:
Access to EEPROM failed due to some cause after outdoor unit started.
Forecast of Cause:
1. External cause (Noise, temporary open, voltage drop)2. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YESYES
Check Point 2 : Replace Main PCB
Change Main PCB.
NO
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related
cables near the power line.
02-12
Page 34
Trouble shooting 9
OUTDOOR UNIT Error Method:
INDOOR UNIT
PFC circuit error
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 6 times Flash, Timer lamp: 4 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 64]
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When inverter output DC voltage is higher than 415V for over 3 seconds,
the compressor stops.
If the same operation is repeated 5 times, the compressor stops permanently.
Forecast of Cause :
1. External cause2. Connector connection failure3. Main PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
02-13
Page 35
Trouble shooting 10
OUTDOOR UNIT Error Method:
IPM error
Indicate or Display:
Outdoor Unit : LED 0.5sec ON/ 0.5sec OFF
Indoor Unit: Operation lamp: 6 times Flash, Timer lamp: 5 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 65]
Detective Actuators:
Outdoor unit Main PCB
Compressor
Detective details:
When more than normal operating current to IPM in Main PCB flows,
the compressor stops.
After the compressor restarts, if the same operation is repeated within 40sec,
the compressor stops again.
Ifandrepeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged4. Compressor failure5. Main PCB failure
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
OK
Check Point 3 : Check Outdoor Fan
Check Outdoor Fan Motor. (Refer to Trouble shooting 17)
>> If the Fan Motor is failure, replace it.
OKOK
Check Point 4 : Check Compressor
Check Compressor.
(PARTS INFORMATION 2)
OKOK
Check Point 5 : Replace Main PCB
If Check Point 14 do not improve the symptom, change Main PCB.
02-14
Page 36
Trouble shooting 11
OUTDOOR UNIT Error Method:
INDOOR UNIT
Discharge thermistor error
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
Indoor Unit: Operation lamp: 7 times Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 71]
Detective Actuators:
Outdoor unit Main PCB
Discharge pipe temperature thermistor
Detective details:
When Discharge pipe temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure2.Thermistor failure3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
5°C0°C-5°C-10°C-20°C-30°C
20°C10°C
30°C
62.6100.9134.2129.8221.1292.9531.61013.1Resistance Value (k )
40.0
Temperature
40°C
26.3
50°C
17.8
60°C
12.3
90°C80°C70°C
100°C
110°C
2.6
If Thermistor is either open or shorted, replace it and reset the power.
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
AOU9RLFW
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
1
1
2
2
CN61
3
3
4
4
1
1
2
2
CN62
3
3
If the voltage does not appear, replace Main PCB.
AOU12RLFW, 15RLS
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BROWN
BROWN
BLACK
BLACK
1
1
2
2
CN71
3
3
4
4
1
1
2
2
CN70
3
3
120°C
2.03.44.66.38.7Resistance Value (k )
02-15
Page 37
Trouble shooting 12
OUTDOOR UNIT Error Method:
Outdoor unit Heat Ex. sensor error
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
Indoor Unit: Operation lamp: 7 times Flash, Timer lamp: 3 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 73]
Detective Actuators:
Outdoor unit Main PCB
Heat exchanger temperature thermistor
Detective details:
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure2.Thermistor failure3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
-30°C
95.6
-20°C
50.3
-5°C-10°C
30°C20°C10°C5°C0°C
6.09.612.416.121.027.8Resistance Value (k )
3.8
Temperature
50°C40°C
80°C70°C60°C
0.60.81.21.72.5Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
AOU9RLFWAOU12RLFW, 15RLS
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
1
1
2
2
CN61
3
3
4
4
1
1
2
2
CN62
3
3
If the voltage does not appear, replace Main PCB.
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BROWN
BROWN
BLACK
BLACK
1
1
2
2
CN71
3
3
4
4
1
1
2
2
CN70
3
3
02-16
Page 38
Trouble shooting 13
OUTDOOR UNIT Error Method:
Outdoor thermistor error
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
Indoor Unit: Operation lamp: 7 times Flash, Timer lamp: 4 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 74]
Detective Actuators:
Outdoor unit Main PCB
Outdoor temperature thermistor
Detective details:
When Outdoor temperature thermistor open or short-circuit is
detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure2.Thermistor failure3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
-30°C
224.3
-25°C
159.7
-15°C-20°C
10°C5°C0°C-5°C-10°C
26.935.246.662.384.2115.2Resistance Value (k )
20.7
Temperature
20°C15°C
35°C
6.48.010.012.616.1Resistance Value (k )
40°C
5.2
45°C
4.2
50°C
3.5
If Thermistor is either open or shorted, replace it and reset the power.
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
AOU9RLFWAOU12RLFW, 15RLS
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
1
1
2
2
CN61
3
3
4
4
1
1
2
2
CN62
3
3
If the voltage does not appear, replace Main PCB.
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BROWN
BROWN
BLACK
BLACK
1
1
2
2
CN71
3
3
4
4
1
1
2
2
CN70
3
3
55°C30°C25°C
2.8
02-17
Page 39
Trouble shooting 14
OUTDOOR UNIT Error Method:
Current sensor error
Indicate or Display:
Outdoor Unit : LED 2sec ON/ 2sec OFF
Indoor Unit: Operation lamp: 8 times Flash, Timer lamp: 4 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 84]
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When Input Current Sensor has detected 0A, while Inverter Compressor is
operating at higher than 56rps, after 1minute upon starting the Compressor.
(Except during the defrost operation)
Forecast of Cause :
1. Defective connection of electric components2. External cause3. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
NO
YES
Check Point 2 :
Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring,
reset the power.
OK
Check Point 1-2 :
Check external cause at Indoor and Outdoor
(Voltage drop or Noise)
Instant drop : Check if there is a large load electric
apparatus in the same circuit.
Momentary power failure : Check if there is a defective
Noise : Check if there is any equipment causing harmonic
wave near electric line.(Neon bulb or electric
equipment that may cause harmonic wave)
Check the complete insulation of grounding.
contact or leak current in the
power supply circuit.
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
02-18
Page 40
Trouble shooting 15
OUTDOOR UNIT Error Method:
Trip detection
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 2sec OFF
Indoor Unit: Operation lamp: 9 times Flash, Timer lamp: 4 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 94]
Detective Actuators:
Outdoor unit Main PCB
Compressor
Forecast of Cause :
1. Outdoor unit fan operation defective, foreign matter on hear exchanger,
Detective details:
"Protection stop by overcurrent generation after inverter compressor start
processing completed'' generated consecutively 10 times.
* The number of generations is reset if the start-up of
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
OKOK
Check Point 2: Replace Main PCB
If Check Point 1 do not improve the symptom, change Main PCB.
OKOK
Check Point 3: Replace Compressor
If Check Point 2 do not improve the symptom, change Compressor.
02-19
Page 41
Trouble shooting 16
OUTDOOR UNIT Error Method:
Compressor motor control error
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 2sec OFF
Indoor Unit: Operation lamp: 9 times Flash, Timer lamp: 5 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 95]
Detective Actuators:
Outdoor unit Main PCB
Compressor
Detective details:
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 90°,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
Ifandrepeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components2. Main PCB failure3. Compressor failure
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 2 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3: Replace Main PCB
If Check Point 1,2 do not improve the symptom, change Main PCB.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
02-20
Page 42
Trouble shooting 17
OUTDOOR UNIT Error Method:
Outdoor unit fan motor error
Indicate or Display:
Outdoor Unit : LED 5sec ON/ 5sec OFF
Indoor Unit: Operation lamp: 9 times Flash, Timer lamp: 7 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 97]
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit fan motor
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
Ifandrepeats 5 times in a row, compressor and fan motor stops
permanently.
Forecast of Cause:
1. Fan rotation failure2. Motor protection by surrounding temperature rise3. Main PCB failure
4. Outdoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Outdoor unit fan motor
Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>>If Outdoor unit fan motor is abnormal, replace Outdoor unit fan motor.
OK
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
RED
1
2
3
4
5
6
7
BLACK
WHITE
YELLOW
BROWN
CN800
If the voltage is not correct, replace Main PCB.
FAN MOTOR
FM
Read wireDC voltage
Red - Black280V 10% (09/12RLFW)
240 - 400V (15RLS)
White - Black
15 1.5V
02-21
Page 43
Trouble shooting 18
INDOOR UNIT Error Method:
4-way valve error
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit: Operation lamp: 9 times Flash, Timer lamp: 9 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 99]
Detective Actuators:
Indoor unit Controller PCB
Heat Ex. temperature thermistor
Room temperature thermistor
4-way valve
Detective details:
When the indoor heat exchanger temperature is compared with
the room temperature, and either following condition is detected
continuously two times, the compressor stops.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Check each thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 5, 6),
If defective, replace the thermistor
OKOK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN501(09RL), CN30(12/ 15RL) from PCB and check the resistance value of coil.
Resistance value is 1.22k1.49k (at 20°C).
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
OKOK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
02-22
Page 44
Trouble shooting 19
OUTDOOR UNIT Error Method:
INDOOR UNIT
Discharge temperature error
Indicate or Display:
Outdoor Unit : Continuously lighting
Indoor Unit: Operation lamp: 10 times Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : A1]
Detective Actuators:
Outdoor unit Main PCB
Discharge pipe temperature thermistor
Detective details:
When the discharge temperature becomes higher than 230°F (110°C),
the compressor stops.
After the compressor restarts, if the same operation is repeated,
the compressor stops permanently.
Forecast of Cause :
1. Valve is close 2. EEV failure3. Gas Leak, less 4. Discharge Thermistor failure
5. Outdoor Fan Operation failure 6. Outdoor Heat Exchanger clogged
< Cooling mode >
Check Point 1 : Check if Gas Valve is open
If it is not open, open it and check the operation.
< Heating mode >
Check Point 1 : Check if LIquid Valve is open
If it is not open, open it and check the operation.
OKOK
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 3)
>>If EEV or Strainer is defective, replace it.
OK
MPa MPa
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 3)
>>If EEV or Strainer is defective, replace it.
OK
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>>If recharging refrigerant, make sure to perform
vacuuming and
recharge the specified amount.
OK
Check Point 4 : Check Discharge Thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 11),
If defective, replace the thermistor
OK
Check Point 5 : Check Outdoor FAN, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating? (Check by hand and if it is locked, replace the motor)
Check Outdoor Fan Motor.
>>If the Fan Motor is defective, replace it.
02-23
Page 45
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Trouble shooting 20
Indoor Unit - No Power
Forecast of Cause:
1. Power Supply failure2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC187 - 253V appears at Outdoor Unit Terminal L1 - L2.
YESYES
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB
is loose, and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
Upon checking the normal power supply, replace Varistor.
OK
If the symptom does not change by above Check 3, replace Main PCB.
NO
02-24
Page 46
Trouble shooting 21
Outdoor Unit - No Power
Forecast of Cause:
1. Power Supply failure2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC187 - 253V appears at Outdoor Unit Terminal L1 - L2.
YESYES
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose,
and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
Upon checking the normal power supply, replace Varistor.
OK
If the symptom does not change by above Check 3, replace Main PCB.
NO
02-25
Page 47
Trouble shooting 22
Forecast of Cause:
1. Setting/ Connection failure 2. External cause
No Operation (Power is ON)
3. Electrical Component defective
Check Point 1 : Check indoor and outdoor installation condition
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control.
Or, check if there is an open cable connection.
Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
OK
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components at Indoor and Outdoor
Check Voltage at CN305 (terminal 1-3) of UTY-XCBXZ1(Communication kit).
(Power supply to Remote Control)
>> If it is DC13V, Remote Control is failure. (Controller PCB is normal)>> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data & Technical
Manual.
OKOK
MPa MPa
Check Point 5 : Check Refrigeration Cycle
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3)
Check Compressor (PARTS INFORMATION 1,2)
Attention
Strainer normally does not have temperature difference
between inlet and outlet as shown in, but if there is a
difference like shown in, there is a possibility of inside
clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
Pipe (In)Pipe (Out)
02-27
Page 49
Trouble shooting 24
Forecast of Cause :
1. Abnormal installation (Indoor/ Outdoor)
Abnormal Noise
2. Fan failure (Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit.
(Check and correct followings)
Abnormal noise is coming from Outdoor Unit.
(Check and correct followings)
Is Main Unit installed in stable condition?
Is the installation of Air suction grille and
front panel normal?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Trouble shooting 25
Forecast of Cause:
Water Leaking
Diagnosis method when water leak occurs
Is Main Unit installed in stable condition?
Is Fan Guard installed normally?
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
OK
Check if vibration noise by loose bolt or contact noise
of piping is happening.
OK
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water is spitting out.
Is Main Unit installed in stable condition?
Is Main Unit broken or deformed at the time of
transportation or maintenance?
OKOK
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
OKOK
Is Fan rotating?
02-28
Is the filter clogged?
OKOK
Check Gas Pressure and correct it
if there was a gas leak.
MPa MPa
Page 50
2-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 1
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection
cable?
Check Main PCB, connection of
Compressor, and winding resistance.
(Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection
cable?
Is Gas Pipe Valve open?
(Low Pressure is too low)
MPa MPa
Check if Refrigerant is leaking.
(Recharge Refrigerant)
Abnormal noise
Check if vibration noise by
loose bolt or contact noise
of piping is happening.
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Replace Compressor
Check if Strainer is clogged.
(PARTS INFORMATION 3)
Check Main PCB, connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
Replace Compressor
02-29
Page 51
SERVICE PARTS INFORMATION 2
Inverter Compressor
Check Point 1 : Check Connection
Check terminal connection of Compressor
(loose or incorrect wiring)
Terminal cover opened
C(W)
(BLACK)
R(U)
(WHITE)
S(V)
(RED)
Terminal cover opened
C(W)
(BLACK)
S(V)
(WHITE)
AOU9RLFW
Check Point 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0or infinite, replace Compressor.
C
R
S
AOU9RLFW
Resistance Value :
AOU12RLFW
Resistance Value :
AOU15RLS
Resistance Value :
AOU12RLFW
2.7 at 20°C
0.7 at 20°C
1.4 at 25°C
R(U)
(RED)
Terminal cover opened
C(T)
(BLACK)
R
(RED)
AOU15RLS
S(W)
(WHITE)
Check Point 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
02-30
Page 52
SERVICE PARTS INFORMATION 3
Outdoor unit Electronic Expansion Valve
( EEV )
Check Point 1 : Check Connections
Check connection of connector (CN40)
( Loose connector or open cable )
RED
1
2
BLUE
3
4
5
6
ORANGE
YELLOW
WHITE
CN40
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Read wire
White - Red
Yellow - Red
Orange - Red
Blue - Red
EXPANSION
VALVE COIL
EV
Resistance value
46
at 20°C
Check Point 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
4
Turn on Power and check operation noise.
If an abnormal noise does not show,
replace Main PCB.
If Resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot Gas
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot Gas
DC
Pipe (In)
Hi TEMP.
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in,
but if there is a difference as shown in, there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In)Pipe (Out)
Pipe (Out)
Normal TEMP.
Pipe (In)
Hi TEMP.
Pipe (Out)
Hi TEMP.
Pipe (In)Pipe (Out)
02-31
Page 53
SERVICE PARTS INFORMATION 4
Indoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Indoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
Pin number
(wire color)
1 (Blue)
2 (Yellow)
3 (White)
4 (Black)
5
6 (Red)
Terminal function
(symbol)
Feed back (FG)
Speed command (Vsp)
Control voltage (Vcc)
Earth terminal (GND)
No function
DC voltage (Vm)
SERVICE PARTS INFORMATION 5
Outdoor unit fan motor
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Outdoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number
(wire color)
1 (Red)
2
3
4 (Black)
5 (White)
6 (Yellow)
7 (Brown)
Terminal function
(symbol)
DC voltage (Vm)
No function
No function
Earth terminal (GND)
Control voltage (Vcc)
Speed command (Vsp)
Feed back (FG)
02-32
Page 54
WALL MOUNTED type
INVERTER
R410A
3 .APPENDING DATA
Page 55
3-1. FUNCTION SETTING
3-1-1 INDOOR UNIT
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
1-1. Setting the Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the filter.
Select the time setting for the filter sign display interval in the table
below according to the amount of dust or debris in the room.
If you do not wish the filter sign to be displayed, select the setting value for "No indication".
(Factory setting)
Setting Description
Function NumberSetting Value
Standard (400 hours)
Long interval (1000 hours)
Short interval ( 200 hours)
No indication
1-2. Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
Setting Description
Standard
Slightly lower control
Lower control
Warmer control
1-3. Setting the Heater Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
Function NumberSetting Value
11
(Factory setting)
30
00
01
02
03
00
01
02
03
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
(Factory setting)
Function NumberSetting Value
00
31
03-01
01
02
03
Page 56
1-4. Setting the Auto Restart
Enable or disable automatic system restart after a power outage.
(Factory setting)
Setting Description
Function NumberSetting Value
Yes
No
40
00
01
1-5. Setting the Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by
Wired remote controller temperature sensor.
(Factory setting)
Setting Description
No
Yes
* If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is "01" : Room temperature is controlled by remote controller unit sensor.
Function NumberSetting Value
00
42
01
1-6. Setting the Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(Factory setting)
Setting DescriptionFunction NumberSetting Value
A
B
44
C
D
00
01
02
03
1-7. Setting the External input control
"Operation/Stop" mode or "Forced stop" mode can be elected.
Setting Description
Operation/Stop mode
(Setting forbidden)
Forced stop mode
(Factory setting)
Function NumberSetting Value
00
46
01
02
03-02
Page 57
3-1-2 Procedures to change the Function Setting for wireless RC
This procedure changes to the function settings used to control the indoor unit according to
the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the "FUNCTION SETTING" according to the installation
conditions using the remote controller.
Settings will not be changed if invalid numbers or setting values are selected.
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP.() simultaneously,
press the RESET button to enter the function setting mode.
Selecting the Function Number and Setting Value
MIN.HEAT
(1) Press the MODE button, and proceed to Fanction Number
and Setting Value.
(There is no necessity for setting remote control signal code. Because
signal code is setting by Fanction Number and Setting Value.)
(2) Press the SET TEMP. () () buttons to select the Function Number.
(Press the MODE button to switch between the left and right digits.)
(3) Press the FAN button to proceed to Setting Value.
(Press the FAN button again to return to the Function Number selection.)
(4) Press the SET TEMP. () () buttons to select the Setting Value.
(Press the MODE button to switch between the left and right digits.)
(5) Press the TIMER MODE button. It makes a signal to indoor unit.
(Indoor unit recognize the setting.)
(6) Press the START/STOP button. It makes a signal to indoor unit.
(Indoor unit run the setting.)
Function Number
M
I
N
.
H
E
A
T
MIN.HEAT
Setting Value
MIN.HEAT
(7) Press the RESET button to cancel the function setting mode.
(8) After completing the FUNCTION SETTING, be sure to turn of the
power and turn it on again.
CAUTION
After turning off the power, wait 10 seconds or more
before turning on it again.
The FUNCTION SETTING doesn't become effective
if it doesn't do so.
MIN.HEAT
03-03
Page 58
Custom code setting for remote controller
(1) Press the MODE button for more then 5 seconds.
(2) Press the SET TEMP. () () buttons to change the signal code between.
Match the code on the display to the air conditioner signal code. (initially set to)
(3) Press the MODE button. (Return to normal display)
CAUTION
If you change the setting of Fanction Number and Setting Value
after setting custom code in remote controller, please set custom
code in remote controller again.
The remote control unit resets to signal code A when the batteries in
the remote control unit are replaced. If you use a signal code other
than signal code A, reset the signal code after replacing the
batteries.
If you do not know the air conditioner signal code setting, try each
of the signal codes () until you find the code which
operates the air conditioner.
03-04
Page 59
3-2. Thermistor Resistance Values
3-2-1 INDOOR UNIT
Room temperature thermistor
Temp ( C)
Resistance(k )
Voltage(V)
-10.058.20.73
Indoor heat exchanger thermistor
Temp ( C)
Resistance(k )
-30.01131.90.21
-5.044.00.93-25.0804.50.29
0.033.61.15-20.0579.60.40
5.025.91.39-15.0422.90.53
10.020.21.66-10.0312.30.69
15.015.81.94-5.0233.20.88
20.012.52.220.0176.01.10
25.010.02.505.0134.21.36
30.08.02.7710.0103.31.63
35.06.53.0315.080.31.92
40.05.33.2720.062.92.21
45.04.43.4925.049.72.51
30.039.62.79
35.031.73.06
40.025.63.30
45.020.83.53
50.017.13.73
55.014.13.90
60.011.64.05
63.010.44.14
3-2-2 OUTDOOR UNIT
Voltage(V)
Discharge thermistor
Temp ( C)
Resistance(k )
Voltage(V)
-30.01013.10.06
-25.0729.10.09
-20.0531.60.12
-15.0392.30.16
-10.0292.90.21
-5.0221.10.28
0.0129.80.46
5.0134.21.36
10.0100.90.57
15.079.10.71
20.062.60.86
25.049.81.03
30.040.01.23
35.032.41.43
40.026.31.65
45.021.61.88
50.017.82.11
55.014.82.34
60.012.32.57
65.010.32.79
70.08.73.00
75.07.43.19
80.06.33.37
85.05.43.54
90.04.63.69
95.04.03.83
100.03.43.96
105.03.04.07
110.02.64.17
115.02.34.26
120.02.04.33
Outdoor heat exchanger thermistor
Temp ( C)
Resistance(k )
Voltage(V)
-30.095.60.24
-25.068.90.32
-20.050.30.43
-15.037.20.57
-10.027.80.73
-5.021.00.92
0.016.11.14
5.012.41.39
10.09.61.65
15.07.61.93
20.06.02.21
25.04.82.49
30.03.82.77
35.03.13.02
40.02.53.26
45.02.13.48
50.01.73.68
55.01.43.85
60.01.24.00
65.01.04.13
70.00.84.25
75.00.74.35
80.00.64.43
Outdoor temperature thermistor
Temp ( C)
Resistance(k )
Voltage(V)
-30.0224.30.73
-25.0159.70.97
-20.0115.21.25
-15.084.21.56
-10.062.31.90
-5.046.62.26
0.035.22.61
5.026.92.94
10.020.73.25
15.016.13.52
20.012.63.76
25.010.03.97
30.08.04.14
35.06.44.28
40.05.24.41
45.04.24.51
50.03.54.59
55.02.84.65
03-05
Page 60
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
Sep. 2010 Printed in Japan