A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 4°F(2°C) higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is 5°F(2.5°C) lower than a set temperature, the compressor will be
stopped.
* When the room temperature is between +4°F(+2°C) to -5°F(-2.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure1 based on the
fan speed mode and the outdoor temperature.
( Table1 : Compressor Frequency Range )
minimum
frequency
maximum
frequency
ASU9RLF22rps79rps
ASU12RLF18rps96rps
ASU15RLS15rps80rps
( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside airOutside air
temperaturetemperature
A zone79rps61rps52rps37rps
B zone79rps61rps52rps37rps
C zone79rps61rps52rps37rps
D zone52rps43rps37rps28rps
E zone64rps55rps49rps36rps
F zone64rps55rps49rps36rps
A zone
B zone
C zone
D zone
E zone
F zone
A zone
B zone
C zone
D zone
E zone
F zone
93.2°F
(34°C)
86°F
(30°C)
66.2°F
(19°C)
50°F
(10°C)
32°F
(0°C)
A zone
B zone
C zone
D zone
E zone
F zone
96.8°F
(36°C)
89.6°F
(32°C)
69.8°F
(21°C)
53.6°F
(12°C)
35.6°F
(2°C)
9RLF
12RLF
15RLS
HiMeLoQuiet
96rps61rps51rps33rps
96rps61rps51rps33rps
96rps61rps51rps33rps
57rps42rps36rps27rps
57rps42rps36rps27rps
57rps42rps36rps27rps
80rps45rps37rps29rps
80rps45rps37rps29rps
80rps45rps37rps29rps
47rps37rps31rps22rps
47rps37rps31rps22rps
47rps37rps31rps22rps
01-01
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 6°F(3°C) than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 5°F(2.5°C) than a set temperatire, the compressor will be
stopped.
* When the room temperature is between +5°F(+2.5°C) to -6°F(-3°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
( Table2 : Compressor Frequency Range )
minimum
frequency
ASU9RLF22rps99rps
ASU12RLF18rps130rps
ASU15RLS15rps119rps
maximum
frequency
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table3.
However, after the compressor is driven, the indoor unit shall run at operation frequency of
64rps (9RLF), 61rps (12RLF), 51rps (15RLS), for a minute.
( Table3 : Compressor frequency )
Operating
frequency
9RLF
X zone
J zone
Y zone
37rps
28rps
0rps
12RLF
X zone
J zone
Y zone
( Fig.2 : Compressor Control based on Room Temperature )
RoomRoom
temperaturetemperature
Ts+3°F
(Ts+1.5°C)
Ts-1°F
(Ts-0.5°C)
Ts+1°F
(Ts+0.5°C)
Ts-3°F
(Ts-1.5°C)
X zone
J zone
Y zone
Operating
frequency
33rps
25rps
0rps
15RLS
X zone
J zone
Y zone
Operating
frequency
29rps
18rps
0rps
01-02
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 64°F(18°C) and 88°F(30°C) in 2°F(1°C) steps.
Operation flow chart
START
Room temp.
>Ts+4°F(2°C)?
NO
YES
YES
or operation command other than
Room temp.
<Ts- 4°F(2°C)?
HEATING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
auto changeover operation?
NO
YES
NO
NO
YES
TS : Setting temperature
in OFF state for 6 minutes or
or operation command other than
auto changeover operation?
COOLING OPERATION
Thermostat remains
longer?
NO
System stops
NO
YES
YES
01-03
5. INDOOR FAN CONTROL
1. Fan speed
( Table4 : Indoor Fan Speed )
Operation modeAir flow mode
Heating
Cooling/ Fan
Dry
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
Hi
Me+
Me
Lo
Quiet
Cool air prevention
S-Lo
Hi
Me
Lo
Quiet
Speed (rpm)
ASU9RLFASU12RLFASU15RLS
1330
1290
1160
980
710
600
480
1330
1160
930
680
X zone: 680
J zone: 660
1500
1360
1230
1050
770
600
480
1440
1230
1000
750
X zone: 750
J zone: 730
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure3.
On the other hand, if switched in [HIGH][QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH,as shown in Table4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
TR-Ts > 5°F
=
(2.5°C)
5°F > TR-Ts > 3°F
(2.5°C)(1.5°C)
3°F > TR-Ts
(1.5°C)
=
TR-Ts > 4°F
4°F > TR-Ts > 2°F
(2°C)(1°C)
2°F > TR-Ts
(1°C)
(2°C)
=
HIGH mode
MED mode
LOW mode
When the room
temperature drops
When the room
temperature rises
TR : Room temperature
Ts : Setting temperature
4. DRY OPERATION
Refer to th
During the d
eT
a
ble4.
ry mode operation, the fan speed sett
ing c
an not be
c
hange
d
.
01-04
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure4.
On the other hand, if switched in [HIGH][QUIET], the indoor motor will run at a constant airflow
of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table4.
( Fig.4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > -2°F
=
(-1°C)
-2°F > TR-Ts > -4°F
(-1°C)(-2°C)
=
-4°F > TR-Ts
(-2°C)
When the room
temperature rises
LOW mode
MED mode
MED+ mode
When the room
temperature drops
TR-Ts > -3°F
=
-3°F > TR-Ts > -5°F
(-1.5°C)(-2.5°C)
-5°F > TR-Ts
(-2.5°C)
(-1.5°C)
=
TR : Room temperature
Ts : Setting temperature
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure5, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.5 : Cool Air Prevention Control)
Indoor heat exchanger
temperature
107.6°F (42°C)
102.2°F (39°C)
98.6°F (37°C)
86°F (30°C)
Hi
Me+
Lo
Cool air
prevention
S-Lo
Indoor heat exchanger
temperature
98.6°F (37°C)
93.2°F (34°C)
89.6°F (32°C)
75.2°F (24°C)
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow [AUTO] at cooling mode, and the indoor fan motor will run as shown in Figure6.
( Fig.6 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 5)
S-Lo
OFF
10306018060180601030
( Table5 : Indoor fan speed )
Dry
X zoneJ zone
ASU9/ 12RLF680rpm660rpm
ASU15RLS750rpm730rpm
Y zone
0 480rpm
0 480rpm
Cooling
480rpm
480rpm
(SEC)
01-05
6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the type of the outdoor fan motor. The control method is different
between AC motor and DC motor.
( Table6 : Type of Motor )
AC MotorDC Motor
ASU9/ 12RLF,15RLS
2. Fan Speed
( Table7 : Outdoor fan speed )
Zone
CoolingHeating
(rpm)
Dry
Y
Z
860/ 780/ 760/ 470
860/ 470/ 330
ASU9RLF
F
G
ASU12RLF
Y
Z
F
G
Y
Z
850/ 750/ 670/ 500
850/ 500/ 350
1050/ 1010/ 870/ 720/ 530
870/ 530/ 300
ASU15RLS
F
G
300/ 250
250/ 200
Refer to Fig.7
( Fig.7 : Outside air temperature zone selection )
Outside air
temperature
69.8°F (21°C)
53.6°F (12°C)
35.6°F ( 2°C)
Y zone
Z zone
F zone
G zone
230
150
330
230
Outside air
temperature
66.2°F (19°C)
50°F (10°C)
32°F ( 0°C)
900/ 760/ 720/ 680/ 470
950/ 850/ 750/ 680/ 550/ 450
1100/ 850/ 780/ 590/ 480
760/ 470
760/ 470
530
The outdoor fan speed mentioned above depends on the compressor frequency.
*
(When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the
lower speed.)
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
*
as table8 without relating to the compressor frequency.
( Table8 : Outdoor fan speed after the defrost )
ASU9RLF900rpm
ASU12RLF950rpm
ASU15RLS1100rpm
01-06
7. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range will change as follow:
Types of Air flow Direction Setting:
,,,,, :DuringHeating/Cooling/Drymodes
Air Direction RangeFig.8 :
The Remote Controller's display does not change.
1
2
3
4
5
6
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode
Horizontal flow
Heating modeDownward flow
During AUTO mode operation, for the first a few minutes after beginning operation,
air-flow will be horizontal 1; the air direction cannot be adjusted during this period.
The air flow direction setting will temporarily become 1 when the temperature of the air -flow is
low at the start of the Heating mode.
2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Table9 : Swinging Range)
Range
Cooling / Dry mode
Fan mode ()
Heating mode
Fan mode ()
The SWING operation may stop temporarily when the air conditioner’s fan is not operating,
or when operating at very low speeds.
01-07
8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table10.
(Table10 : Compressor Operation Frequency Range)
CoolingHeating
MinMaxMinMaxMinMax
ASU9RLF
ASU12RLF
ASU15RLS15rps80rps15rps119rps18rps29rps
22rps79rps22rps99rps28rps37rps
18rps96rps18rps130rps25rps33rps
Dry
2. OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the Figure9.
(Fig.9 : Compressor Control at Start-up)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
(Frequency)
ASU9RLF
ASU12RLF
ASU15RLS
(Time)
ASU9RLF
ASU12RLF
ASU15RLS
Time
Frequency
70rps82rps92rps96rps96rps96rps
56rps74rps87rps97rps108rps119rps
40rps57rps72rps80rps101rps110rps
TimeTime
80sec140sec200sec380sec440sec440sec
80sec140sec200sec380sec440sec500sec
80sec110sec140sec200sec350sec410sec
TimeTimeTime
Frequency
FrequencyFrequency
TimeTimeTimeTime
Time
Frequency
Time
Frequency
01-08
9. TIMER OPEARTION CONTROL
The table11 shows the available timer setting based on the product model.
(Table11 : Timer Setting)
ON TIMER / OFF TIMERPROGRAM TIMERSLEEP TIMER
ASU9/ 12RLF,15RLS
1. OPEARTION FREQUENCY RANGE
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Stop mode
Set time
Operation mode
Stop mode
Set timeSet timeSet time
Operation mode
Stop mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest
to the clock's current timer setting.
The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
01-09
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically.
If the operation mode or the set temperature is change after the sleep timer is set, the operation is
continued according to the changed setting of the sleep timer from that time ON.
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 2°F(1°C).
It increases the setting temperature another 2°F(1°C) after 1 hour.
After that, the setting temperature is not changed and the operation is stopped at the time
of timer setting.
Set temperature rises
( Ts : Set temperature )
+4°F (2°C)
+2°F (1°C)
Ts
Stop of operation
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 2°F(1°C).
It decreases the setting temperature another 2°F(1°C) every 30 minutes.
Upon lowering 8°F(4°C) the setting temperature is not changed and the operation stops at
the time of timer setting.
Set temperature lowers
( Ts : Set temperature )
Ts
-2°F (-1°C)
-4°F (-2°C)
-6°F (-3°C)
-8°F (-4°C)
Set
30min
30min
Stop of operation
30min
01-10
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the Table12.
The compressor frequency, the temperatures detected by the discharge temperature sensor, the
indoor heat exchanger sensor, the outdoor heat exchanger sensor,
and the outdoor temperature sensor.
Table12 : The pulse range of the electronic expansion valve control
Operation modePulse range
ASU9/ 12RLF
Cooling / Dry mode
Heating mode
Cooling / Dry mode
ASU15RLS
Heating mode
The expansion valve is set at 480 pulses after 110 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (528 pulses are input to the closing direction).
between 60 to 480 pulses.
between 60 to 480 pulses.
between 60 to 480 pulses.
between 45 to 480 pulses.
11. TEST OPERATION CONTROL
Under the condition where the air conditioner runs, press the test run button of the remote
control, and the test operation control mode will appear. During test running, the operation lamp
and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode,
and the compressor will continue to run regardless of whether the room temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is
stopped, even if any operation is given.
13. FOUR-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode, the
compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after
the compressor stopped.
14. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically started with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, since the timer operation time
is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF)
the indoor unit body timer lamp.
[Operation contents memorized when the power is interrupted]
Operation mode
Set temperature
Set air flow
Timer mode and timer time
Set air flow Direction
Swing
ECONOMY operation
MINIMUM HEAT operation
01-11
15. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table13.
If the remote control is lost or battery power dissipated, this function will work without the remote control.
(Table13)
Manual auto operation
OPERATION MODEAuto changeover
FAN CONT. MODEAuto
TIMER MODEContinuous
SETTING TEMP.75.2°F (24°C)
SETTING LOUVERStandard
SWING
ECONOMY
OFF
OFF
(No timer setting available)
Forced cooling operation
Cooling
Hi
Room Temp is not controlled
Horizontal
OFF
-
16. FORCED COOLING OPERATION
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more.
During the forced cooling operation, it operates regardless of room temperature sensor.
Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON
and 1 second OFF on both operation LED and timer LED (same as test operation).
Forced cooling operation is released after 60 minutes of starting operation.
The FORCED COOLING OPERATION will start as shown in Table13.
17. COMPRESSOR PREHEATING
When the outdoor temperature is lower than 68°F(20°C) and the heating operation has been
stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started and when the outdoor temperature rises to 77°F(25°C) or greater,
preheating is ended.
18. MINIMUM HEAT OPERATION
The MINIMUM HEAT operation functions by pressing MIN.HEAT button on the remote controller.
The MINIMUM HEAT operation is almost the same operation as below settings.
( Table14 )
ModeHeating
Setting temperature50°F (10°C)
Fan modeAUTO
19. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
The ECONOMY operation is almost the same operation as below settings.
Outdoor heat exchanger temp. < Outside air temp.- 12.6°F (7°C)
or Outdoor heat exchanger temp. < - 4°F (-20°C)
(at outside air temp. < 14°F (-10°C))
Less than 10 minutes
( For
intermittent operation )
OFF count of the compressor
40 times
=
=
=
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 17.
(Table 17 : Defrost Release Condition)
Release Condition
=
Outdoor heat exchanger temperature sensor value is higher than
+60.8°F (+16°C) or Compressor operation time has passed 15 minutes.
01-13
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 10 minutes)
Normal defrost
Outside air temp. > 14°F
Outdoor HEX temp.
Below 1.4°F
(-17°C)
=
(-10°C)
Outside air temp. < 14°F
(-10°C)
Outdoor HEX temp.
- Outside air temp.
Below - 12.6°F(7°C)
or
Outdoor HEX temp.
Below - 4°F(-20°C)
Defrost start
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Integrating defrost
Intermittent operationContinuous operation
Compressor
OFF count :
40 times
Compressor
integrating
operation:
Over 240 minutes
Outdoor HEX temp.
Below 26.6°F(-3°C)
Outdoor fan : OFF
Compressor speed:0rps
EEV : 480pulse
4-way valve : OFF
Compressor speed : 90rps (09/ 12)
70rps (15)
Outdoor HEX temp.: Over 60.8°F(16°C)
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-14
21. OFF DEFROST OPEARTION CONTROL
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit defrost lamp
lighting, the outdoor unit will allow the heat exchanger to defrost, and then stop.
1. OFF DEFROST OPERATION CONDITION
In heating operation, the outdoor heat exchanger temperature is less than 24.8°F (-4°C), and
compressor operation integrating time lasts for more than 30 minutes.
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 60.8°F (16°C)
or Compressor operation time has passed 15 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature:
Below 24.8°F(-4°C)
and
Compressor integrating operation:
Over 30 minutes
Defrost start
Defrost Indicater:
[Defrost lamp]
Lighting
Outdoor heat exchanger temperature:
Over 60.8°F (16°C) or
Compressor ON time: Over 15 minutes
Defrost end
01-15