Fujitsu 9370083002 Installation Instruction Sheet

Page 1
En-1
English
Cassette Type (VRF System)
Refrigerant
R407C&R22
INSTALLATION INSTRUCTION SHEET
(PART NO. 9370083002)
For authorized service personnel only.
WARNING!
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
CAUTION!
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
WARNING
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available from our stand-
ard parts. This installation instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel
only.
4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with
a flame, it produces a toxic gas.
5 Do not turn on the power until all installation work is complete.
6 When installing or moving the air conditioner, use care not to charge it with the wrong refrigerant (such as
R407C or R22).
CAUTION
Observe the following precautions when using R407C refrigerant.
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as this would reduce the lifetime of the unit.
Never use piping which has been used for previous installations. Only use parts that are delivered with the unit.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation instruction sheet because it is used when the air conditioner is
serviced or moved.
Page
CONTENTS .................................................................... 1
SAFTY PRECAUTIONS .................................................. 1
STANDARD PARTS ........................................................ 2
SELECTING THE MOUNTING POSITION ..................... 2
INSTALLATION PROCEDURE ....................................... 3
1. INDOOR UNIT INSTALLATION .................................. 3
2. INSTALLING DRAIN PIPE .......................................... 3
3. CONNECTION PIPE REQUIREMENT ....................... 4
Page
4. CONNECTING THE PIPING....................................... 4
5.
INSTALLING THE COUPLER HEAT INSULATION .........
5
6. ELECTRICAL REQUIREMENT................................... 6
7. ELCTRICAL WIRING .................................................. 6
8. CIRCUIT BOARD SETTING . ..................................... 8
9. GRILLE INSTALLATION ........................................... 10
10. TEST OPERATION ................................................. 13
11. AN ERROR DISPLAY .............................................. 14
Page 2
En-2
STANDARD PARTS
The following installation parts are supplied. Use them as required.
Name and Shape
Coupler heat insulation
Special nut A (large flange)
Special nut B (small flange)
Qty
2
4
4
Name and Shape
Bolt
Washer
Blower cover insulation
Qty
4
4
2
INDOOR UNIT ACCESSORIES GRILLE ACCESSORIES
Name and Shape
Template
Binder
Qty
1
2
SELECTING THE MOUNTING POSITION
Leave the space specified in Fig. 1 so that the air from the blower
will cover the entire room.
Install the indoor unit on a place having a sufficient strength so
that it withstands against the weight of the indoor unit.
A place from where drainage can be extracted outdoors easily.
Fig. 1
Strong and durable ceiling
250 mm (9-3/8”)
or more
1,000 mm (39”) or more
Obstruction
Service space 1,000 mm (39”) or more
WARNING
1 Never install in a room where there is the poten-
tial of leaking flammable gas. A spark could ig­nite the gas and cause an explosion or fire.
2 Avoid installing in a location with high tempera-
ture.
Fig. 2
100 mm (4”) or more
100 mm (4”) or more
100 mm (4”) or more
1,000 mm (39”) or more
(4 directions) (3 directions) (2 directions) (2 directions)
Pipe
The blower direction can be set for two directions or three di-
rections. When using two-direction or three-direction blower, fol­low Fig. 2 for the blower direction and space.
The method for changing the blower direction is shown in the
“9. GRILLE INSTALLATION” section of the “INSTALLATION PROCEDURE”.
Page 3
En-3
INSTALLATION PROCEDURE
Install the air conditioner as follows.
1. INDOOR UNIT INSTALLATION
(1) Make the holes for installing in the ceiling. (Fig. 4) (2) Install the hanging bolts (M10), refer to the position in Fig. 3. (3) Install special nut A, then special nut B onto the hanging bolt (Fig. 4). (4) Raise the body and mount its hooks onto the hanging bolt between the special nuts. (5) Turn special nut B to adjust the height of the body.
Fig. 3
(Grille measurement)
650 mm (25-15/32”)
(Hanging bolt position)
400 mm (15-3/4”)
(Hanging bolt position)
606 mm (23-27/32
)
Fig. 4
131 mm (5-5/32
)
111 m m
(4-3/8”)
46 mm (1-27/32”)
86 mm (3-3/8”)
41 mm (1-9/16”)
250 mm (9-27/32
)
(Ceiling opening measurement)
(
600 mm ( 23-5/8”))
Drain pipe
40 mm (1-9/16”)
Ceiling
Special nut A
Hook
Special nut B
Hanging bolt
30 mm or more
15 mm (19/32”)
WARNING
1 Perform final tightening by tightening the double nut firmly. The product may fall if not installed properly.
2 Using a level, or vinyl hose filled with water, fine adjust so that the body is level.
Max. 400 mm (15”)
Rise
Trap
Supporter
1.5 to 2 m (5 to 6.5 ft)
Air bleeding
150 mm (6) or less
2. INSTALLING DRAIN PIPE
CAUTION
Install the drain pipe in accordance with the instructions in this installation instruction sheet and keep the area warm enough to prevent condensation. Problems with the piping may lead to water leaks.
Use general hard polyvinyl chloride pipe (VP25) [outside diam­eter 32 mm (1-1/4)] and connect it with adhesive (polyvinyl chlo­ride) so that there is no leakage. Always heat insulate the indoor side of the drain pipe.
Do not provide a rise, trap and air bleeding.
Provide a downward gradient (1/50 to 1/100).
Provide supports when long pipes are installed.
When desiring a high drain pipe height, raise it up to 400 mm
(15) or less from the ceiling within a range of 150 mm (6) from the body. A rise dimension over this range will cause leakage.
Gradient 1/50 to 1/100
Fig. 5
Page 4
En-4
3. CONNECTION PIPE REQUIREMENT
(1) Connected to outdoor unit
Table 1
unit : mm
Capacity of Suction Discharge
outdoor unit Gas Pipe Gas Pipe
Liquid Pipe
90 ø28.58 (1.2) ø19.05 (1.0) ø12.7 (0.8)
( ) : thickness
(2) Connected between two immediately adjacent refrigerant branch kits
Table 2
unit : mm
Total capacity Suction Discharge of indoor unit Gas Pipe Gas Pipe
Liquid Pipe
Less than 30 ø15.88 (1.0) ø12.7 (0.8) ø9.53 (0.8)
31 or more to 60 ø19.05 (1.0) ø15.88 (1.0) ø9.53 (0.8)
61 or more ø28.58 (1.2) ø19.05 (1.0) ø12.7 (0.8)
( ) : thickness
(3) Connected to indoor unit
Table 3
unit : mm
Capacity of
indoor unit
Gas Pipe Liquid Pipe
7, 9 ø9.53 (0.8) ø6.35 (0.8)
12, 14 ø12.7 (0.8) ø6.35 (0.8)
18, 20, 24, 25 ø15.88 (1.0) ø6.35 (0.8)
30 ø15.88 (1.0) ø9.53 (0.8)
36, 45, 54, 60 ø19.05 (1.0) ø9.53 (0.8)
( ) : thickness
* Capacity: The number displayed on the model name for the indoor and outdoor units.
Use pipe with water-resistant heat insulation.
The discharge gas pipe is only connected on heat recovery models.
4. CONNECTING THE PIPING
1. FLARE PROCESSING
(1) Cut the connection pipe with pipe cutters so that the pipe is
not deformed.
(2) Holding the pipe downwards so that cuttings cannot enter the
pipe and remove the burrs.
(3) Remove the flare nut from the indoor unit pipes and assemble
as shown in Table 4 and insert the flare nut onto the pipe, and flare with a flaring tool.
(4) Check if the flared part “L” (Fig. 6) is spread uniformly and that
there are no cracks.
Table 4
Pipe
Liquid pipe
(ø6.35 mm)
Gas pipe
(ø9.53 mm)
Gas pipe
(ø12.7 mm)
Gas pipe
(ø15.88 mm)
Width across flats
17 mm
22 mm
24 mm
24 mm
Fig. 6
Width across flats
L dimension
1.4 to 1.7 mm
1.8 to 2.0 mm
1.9 to 2.2 mm
2.2 to 2.4 mm
Page 5
En-5
2. CONNECTION PIPES
When the flare nut is tightened properly by your hand, hold the body side coupling with a separate spanner, then tighten with a torque wrench (Fig. 8, Table 5).
Fig. 7
Indoor unit
Liquid pipe
Gas pipe
Holding spanner
Body side
Torque wrench
Fig. 8
Table 5: Flare nut tightening torque
Tightening Torque
150 to 220 kgf·cm (14.7 to 19.6 N·m)
310 to 350 kgf·cm (30.4 to 34.3 N·m)
500 to 550 kgf·cm (49.0 to 53.3 N·m)
750 to 800 kgf·cm (73.5 to 78.4 N·m)
Flare nut
Liquid pipe (ø6.35 mm)
Gas pipe (ø9.53 mm)
Gas pipe (ø12.7 mm)
Gas pipe (ø15.88 mm)
CAUTION
1 Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper, the flare
nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
2 Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection
pipe.
3 Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 8, in order to
tighten the flare nut correctly.
5.
INSTALLING THE COUPLER HEAT INSULATION
After checking for gas leaks, insulate by the coupler heat insulation around the gas pipe and liquid pipe of the indoor unit.
Fig. 9
CAUTION
Must fit tightly against body without any gap.
Body
Coupler heat insulation
Be sure to overlap the insulation
No gap
Coupler heat insulation
Page 6
En-6
6. ELECTRICAL REQUIREMENT
Table 6
Power supply
Maximum 2.5
cord (mm
2
)
Minimum 1.5
Transmission
Maximum 1.25
cord (mm
2
)
Minimum 0.75
Remote control
Maximum 1.25
cord (mm
2
)
Minimum 0.75
Fuse capacity (A) 20
Shield cord
(LONWORKS
compatible part)
H07RN-F or equivalent
Sheathed vinyl cord or
cable
7. ELECTRICAL WIRING
WARNING
1 Before starting work, check that power is not being supplied to the indoor unit.
2 Connect the connection cord firmly to the terminal board. Imperfect installation may cause a fire.
3 Always fasten the outside covering of the connection cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
4 Always connect the ground wire.
Remove the control box cover and install the connection cord (Figs. 10 and 11).
Fig. 10
TRANS MISSION
POWER SUPPLY
TO REMORTE CONTROL UNIT
When the two wires are attached.
Screw with special washer
Round terminal
Terminal board
Wire
Terminal block
(For solid wire only)
(Solid wire)
Strip 25 mm
(15/16”)
Insulation
Loop
(Strand wire) Round terminal
Strip 10 mm
(3/8”)
Clamp
Remote
control cord
Cord clamp
Transmission
cord
RB unit cord (Heat recovery model only)
Power supply cord
Clamp
Clamp
Control box cover
different diameter connect to one side
Befor attaching the wire to terminal block.
Binder
Binder
Page 7
En-7
Fig. 11
RB unit cord (Heat recovery model only)
Power supply cord
Transmission
cord
Remote
control cord
380-415 V 3ø 50 Hz
220-240 V 1ø 50 Hz
Remote controller
Terminal board
Note that the arrangement of the terminal board may vary from model to model.
Indoor unit
Outdoor unit
Refrigerant branch unit (Heat recovery model only)
Remote
controller
WARNING
1 The rated voltage of this product is 220-240 V A.C. 50 Hz.
Before turning on verify that the voltage is within the 198 V to 264 V range.
2 Always use a special branch circuit and install a special receptacle to supply power to the air conditioner.
3 Use a circuit breaker and receptacle matched to the capacity of the air conditioner.
4
Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
5 Install a leakage circuit breaker in accordance with the related laws and regulations and electric company
standards.
6 Never connect other electrical equipment to the power supply for this system.
CAUTION
1 Use care to wire properly. (Miss-wiring will result in damage.)
2 Never bundle the power supply cord, transmission cord and remote controller cord together. Bundling
these cords together will cause misoperation.
3 For transmission cord, only ground one side of the ground wire.
4 The total length of the transmission cord should not exceed 500 meters. Note that the total length of the
transmission cord can be extended to 2,000 meters if the optional signal amplifier is used.
5 The power source capacity must be the sum of the air conditioner current and the current of other electrical
appliances. When the current contracted capacity is insufficient, change the contracted capacity.
6 When the voltage is low and the air conditioner is difficult to start, contact the power company the voltage
raised.
Page 8
En-8
8. CIRCUIT BOARD SETTING
Set the switch on the circuit board. (1) Indoor unit addresses
Rotary switch (SW5) - - - Factory setting “0” When connecting multiple indoor units to one refrigerant system, set the address at SW5 in sequence from 0.
(2) Refrigerant circuit address
Rotary switch (SW7) - - - Factory setting “0” Rotary switch (SW8) - - - Factory setting “0” In the case of multiple refrigerant systems, set SW7 and SW8 as shown in the Table 7 for each refrigerant system. Set to the same refrigerant circuit address as the outdoor unit.
Example: When SW8 is set to 1 and SW7 is set to 14, the refrigerant circuit address will be 30.
Table 7
Refrigerant Rotary Refrigerant Rotary Refrigerant Rotary Refrigerant Rotary Refrigerant Rotary
circuit
Switch Setting
circuit
Switch Setting
circuit
Switch Setting
circuit
Switch Setting
circuit
Switch Setting
address
INDOOR UNIT
address
INDOOR UNIT
address
INDOOR UNIT
address
INDOOR UNIT
address
INDOOR UNIT
SW8 SW7 SW8 SW7 SW8 SW7 SW8 SW7 SW8 SW7
0 0020144028603128050
1 0121154129613138151
2 02221642210623148252
3 03231743211633158353
4 0 4 24 1 8 44 2 12 64 4 0 84 5 4
5 0 5 25 1 9 45 2 13 65 4 1 85 5 5
6 0 6 26 1 10 46 2 14 66 4 2 86 5 6
7 0727111472156743 8757
8 0 8 28 1 12 48 3 0 68 4 4 88 5 8
9 0 9 29 1 13 49 3 1 69 4 5 89 5 9
10 0 10 30 1 14 50 3 2 70 4 6 90 5 10
11 0 11 31 1 15 51 3 3 71 4 7 91 5 11
12012322052347248 92512
13013332153357349 93513
14 0 14 34 2 2 54 3 6 74 4 10 94 5 14
15015352355377541195515
16 1 0 36 2 4 56 3 8 76 4 12 96 6 0
17 1 1 37 2 5 57 3 9 77 4 13 97 6 1
18 1 2 38 2 6 58 3 10 78 4 14 98 6 2
19 1 3 39 2 7 59 3 11 79 4 15 99 6 3
Page 9
En-9
(3) Remote controller address
Rotary switch (SW9) - - - Factory setting “0” When connecting multiple indoor units to one standard wired remote controller, set the address at SW9 in sequence from 0.
Fig. 12
Example If 4 indoor units are connected.
Remote controller
(4) Model select switch
SW4 should be checked.
Table 8
Capacity 18 14 12 9 7
SW4-1 OFF ON OFF ON OFF
SW4-2 OFF ON ON OFF OFF
SW4-3 ON OFF OFF OFF OFF
SW4-4 OFF OFF OFF OFF OFF
CAUTION
Do not set any switches other than those specified in this sheet. The air conditioner may not operate correctly if any switches other than those specified are changed.
R-SW9
0
R-SW9
1
R-SW9
2
R-SW9
3
Indoor unit Indoor unit Indoor unitIndoor unit
Page 10
En-10
A
A
9. GRILLE INSTALLATION
1. INSTALLING BLOWER COVER INSULATION (IN CASE OF 2 OR 3 OUTLET DIRECTION)
Install the blower cover insulation only when the outlet direction
is changed to 2 or 3 direction.
Two blower cover insulations are packed with the grille assem-
bly.
Install the blower cover insulation at the diffuser position shown
in Fig. 13. At this time, use pipe side as the criteria.
Fig. 13
2. INSTALLING GRILLE ASSEMBLY TO BODY
Hang the grille assembly on the wires attached to the indoor unit as shown in Fig. 14.
Fig. 14
3 direction
Fit the blower cover insulation.
Blower cover insulation
A-A Section view
Wire
Wire hook
Motor cover assembly
Wire
Wire hook
Example
Wire hook
CAUTION
Do not install the blower cover insulation at the diffuser position on pipe side.
Do not set the 2-way outlet as shown in the figure to the right. Setting in this
manner will cause performance problems.
Pipe
Pipe side
Pipe side
Do not install here.
Pipe
Main body
Page 11
En-11
Installing the grille assembly to the body
Install the grille assembly to the body with the four bolts and washers.
(1) Lightly tighten the bolts shown in “B” of Fig. 15. Hang the panel. (2) Tighten the other bolts. (3) Tighten all bolts securely. (4) Connect the connector in accordance with part A detail view. (Fig. 16)
Fig. 15 Fig. 16
Part A detail view
No gap between ceiling and grille around entire periphery.
3. INSTALLING/REMOVING THE INTAKE GRILLE
INSTALLING THE INTAKE GRILLE
(1) Fully insert the intake grille hooks into the rectangular holes in the panel. (Fig. 17) (2) Close the intake grille, then slide the two grille stoppers outward. (Fig. 18)
Fig. 17 Fig. 18
Washer
Bolt
Display PCB wire harness
Wire (Louver)
Display PCB wire harness
Joint wire (Louver)
Panel
Rectangular hole
A
B
Intake grille
Grille hook
Grille stopper
Page 12
En-12
REMOVING THE INTAKE GRILLE
(1) Slide the two grille stoppers inward, then open the intake grille. (2) Remove the grille hook screws, then open the intake grille. (Fig. 19) (3) Open the intake grille so that it is at an angle of 20° to 40°, then remove the grille.
Fig. 19
Grille hook
CAUTION
1 The louver angle cannot be changed if the power is not on, (If moved by hand, it may be damaged.)
2 The grille assembly is directional relative to the air conditioner body.
3 Install so that there is no gap between the grille assembly and the air conditioner body.
Page 13
En-13
When EE : EE blinks at the current time display, there is an error inside the air conditioner. If the SET TIME button ( ) and SET
TEMP./DAY button (
) are pressed simultaneously for more than three seconds, the self diagnosis check will start and the error contents will be displayed at the current time display. In addition, the remote controller address will be displayed below. When the operation lamp lights, press the START/STOP button and after operation lamp goes off, perform the same operation (Fig. 21).
Fig. 21
10. TEST OPERATION
Supply power to the crankcase heater for 12 hours prior to the start of operation in the winter. The following is the procedure for the test operation.
1. TEST OPERATION USING CIRCUIT BOARD (OUTDOOR UNIT)
Refer to the Installation Instruction Sheet for the outdoor unit if the circuit board for the outdoor unit is to be used for the test operation.
2. TEST OPERATION USING REMOTE CONTROLLER
(1) Standard wired remote controller
For test running, when the remote controller FAN CONTROL button and MASTER CONTROL button are pressed simulta­neously for more than three seconds when the air conditioner is not running, the air conditioner starts and TEST is displayed on the remote controller display. However, the SET TEMP./DAY setting button does not function, but all other buttons, displays, and protection functions operate (Fig. 20).
Fig. 20
To stop test running, press the START/STOP button.
For the operation method, refer to the operating manual and perform operation check.
Check that there are no abnormal sounds or vibration sounds during test running.
MASTER
CONTROL
FAN
CONTROL
TIMER MODE
TEMP./DAY
SET TIME
CLOCK ADJUST
START/STOP
SET
DAY OFF
ZONE
ENERGY SAVE
COOL
FAN
DRY
HEAT
AUTOAUTO
CLOCK
OFF
OFF
ON
ON
C F
NEXT DAY
DAY
TIMER
NON STOP OFFON
TIMER WEEKLY
ANTI FREEZE
CENTRAL
DAY OFF
DEFROST
TEST
12
Stop operation
MASTER
CONTROL
FAN
CONTROL
TIMER MODE
TEMP./DAY
SET TIME
CLOCK ADJUST
START/STOP
SET
DAY OFF
ZONE
ENERGY SAVE
COOL
FAN
DRY
HEAT
AUTOAUTO
CLOCK
OFF
OFF
ON
ON
C F
NEXT DAY
DAY
TIMER
NON STOP OFFON TIMER WEEKLY
ANTI FREEZE
CENTRAL
DAY OFF
DEFROST
TEST
12
MASTER
CONTROL
FAN
CONTROL
TIMER MODE
TEMP./DAY
SET TIME
CLOCK ADJUST
START/STOP
SET
DAY OFF
ZONE
ENERGY SAVE
COOL
FAN
DRY
HEAT
AUTOAUTO
CLOCK
OFF
OFF
ON
ON
C F
NEXT DAY
DAY
TIMER
NON STOP OFFON TIMER WEEKLY
ANTI FREEZE
CENTRAL
DAY OFF
DEFROST
TEST
12
Error code Error contents
Blower temperature thermistor error
Drain abnormal
Room temperature abnormal
Indoor unit fan error
Transmission error
Node setting error
Parallel communication error
Outdoor unit error
Table 9
Error code Error contents
No error
Model information abnormal
Power supply frequency abnormal
EEPROM access error
EEPROM deletion error
Room temperature thermistor error
Indoor unit heat exchanger thermistor (middle) error
Indoor unit heat exchanger thermistor (inlet) error
Indoor unit heat exchanger thermistor (outlet) error
Page 14
En-14
(2) Standard wireless remote controller
Press the remote control unit test run button while the air condi­tioner is running.
At the end of test running, press the remote control unit start­stop button (Fig. 22).
Operation can be checked by lighting and flashing of the display section OPERATION and TIMER lamps. Perform judgement in accordance with the following.
TEST RUN button
START
STOP
ABCD
START/STOP button
Fig. 22
11. AN ERROR DISPLAY
(1) Run the air conditioner in accordance with the operating manual. (2) Operation can be checked by lighting and flashing of the grille display section OPERATION and TIMER lamps. (3) Perform judgment in accordance with the following.
Test running
When the air conditioner is run by pressing the remote controller test run button, the OPERATION and TIMER lamps flash slowly at the same time.
Error
The OPERATION and TIMER lamps operate as follows (Table 10) according to the error contents.
Fig. 23
SWING TIMER OPERATION
MANUAL
AUTO
OPERATION LAMP (Red)
SWING LAMP (Orange)
TIMER LAMP (Green)
Page 15
En-15
Table 10
OPERATION
lamp
Blinks
Blinks
Pulses 2times
Pulses 3times
Pulses 3times
Pulses 3times
Pulses 4times
Pulses 5times
Pulses 5times
Pulses 6times
Pulses 7times
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Error contents
Model information abnormal
Power supply frequency abnormal
Room temperature thermistor error
Indoor unit heat exchanger thermistor (inlet) error
Indoor unit heat exchanger thermistor (middle) error
Indoor unit heat exchanger thermistor (outlet) error
Drain abnormal
Communication error (Indoor unit remote controller)
Microcomputer error
Indoor unit fan error
Blower temperature thermistor error
Outdoor unit error
EEPOM access error
EEPROM deletion error
Transmission error
Node setting error
Parallel communication error
Room temperature abnormal
Error display
TIMER
lamp
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Pulses 3times
Pulses 4times
Pulses 4times
Pulses 5times
Pulses 5times
Pulses 6times
Pulses 7times
VERTICAL
SWING lamp
Goes off
Blinks
Goes off
Pulses 1time
Pulses 2times
Pulses 3times
Goes off
Pulses 1time
Pulses 2times
Goes off
Goes off
Pulses 3times
Pulses 1time
Pulses 2times
Pulses 1time
Pulses 2times
Goes off
Goes off
Loading...