Fujitsu 9318739183 Installation Manual

Page 1
En-1
Español
Français
English
AIR CONDITIONER INDOOR UNIT (Wall Mounted Type)
INSTALLATION MANUAL
1. SAFETY PRECAUTIONS .................................................................. 1
2. ABOUT THIS PRODUCT................................................................... 2
3. GENERAL SPECIFICATIONS ........................................................... 2
4. SELECTING THE INSTALLATION LOCATION .................................3
5. INSTALLATION WORK ..................................................................... 3
6. ELECTRICAL WIRING ..........................................................................5
7. FINISHING ........................................................................................ 6
8. FRONT PANEL REMOVAL AND INSTALLATION .............................7
9. REMOTE CONTROLLER INSTALLATION ........................................ 7
10. OPTIONAL KIT INSTALLATION ........................................................ 7
11. FUNCTION SETTING........................................................................ 9
12. TEST RUN ........................................................................................11
13. CUSTOMER GUIDANCE .................................................................11
14. ERROR CODES ...............................................................................11
PART No. 9318739183
1. SAFETY PRECAUTIONS
1.1. IMPORTANT! Please read before starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and effi ciently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state, and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury and the potential for product or prop­erty damage.
• Hazard alerting symbols
Electrical
Safety/alert
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certifi ed dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
1.2. Special precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYS­TEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wir­ing diagram and these instructions when wiring. Improper connections and inadequate earthing (grounding) can cause accidental injury or death.
• Earth (Ground) the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fi re hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fi ns on the air conditioner can cut your fi ngers.
When Installing...
...In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
...In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause drip­ping and water damage to walls and fl oors.
...In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffl e.
...In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow.
When Connecting Refrigerant Tubing
• Keep all tubing runs as short as possible.
• Use the fl are method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the fl are and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before opening the refrigerant valves.
When Servicing
• Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring.
• Keep your fi ngers and clothing away from any moving parts.
• Clean up the site after you fi nish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• After installation, explain correct operation to the customer, using the operating manual.
WARNING
Never touch electrical components immediately after the power supply has been turned off. Electric shock may occur. After turning off the power, always wait 5 minutes before touching electrical components.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a fl ame, it produces a toxic gas.
CAUTION
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by qualifi ed personnel with a capacity certifi cate for handling refrigerant fl uids. Refer to regulation and laws in use on installation place.
This unit is part of a set constituting an air conditioner. It must not be installed alone or with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 1/8 in. (3 mm) for this unit.
The unit must be correctly earthed (grounded) and the supply line must be equipped with a differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive atmosphere.
When moving, consult authorized service personnel for disconnection and installation of the unit.
Do not place any other electrical products or household belongings under indoor unit or outdoor unit. Dripping condensation from the unit might get them wet, and may cause damage or malfunction of your property.
All Fujitsu General products are manufactured to metric units and tolerances. United States customary units are provided for reference only. In cases where exact dimen­sions and tolerances are required, always refer to metric units.
For authorized service personnel only.
• Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.
Page 2
En-2
2.4. Accessories
The following installation accessories are supplied. Use them as required.
Name and Shape Q’ty Name and Shape Q’ty
Operating Manual
1
Drain hose insulation
1
Installation Manual (This manual)
1
Cloth tape
1
Wall hook bracket
1
Tapping screw (large) M4 × 25 mm
8
Remote controller
1
Tapping screw (small)
2
Battery
2
Air cleaning filter
2
Remote controller holder
1
Air cleaning filter frame
2
The following items are necessary to install this air conditioner. (The items are not includ­ed with the air conditioner and must be purchased separately.)
Name Q’ty Name Q’ty
Connection pipe assembly 1 Saddle 1 set Connection cable (4-conductor)
1 Drain hose 1 Wall pipe 1 Tapping screws 1 set Decorative tape 1 Sealant 1 Vinyl tape 1 M10 bolt, nut 4 set Wall cap 1
2.5. Additional materials required for installation
A. Refrigeration (armored) tape B. Insulated staples or clamps for connecting wire (See your local electrical codes.) C. Putty D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping
2.6. Optional parts
Refer to each installation manual for the method of installing optional parts.
Parts name Model No. Application
Wired Remote Controller UTY-RNNUM For air conditioner operation Wireless Remote Controller UTY-LNHUM For air conditioner operation Simple Remote Controlle UTY-RSNUM For air conditioner operation External connect kit UTY-XWZX For control input/output port
3. GENERAL SPECIFICATIONS
This INSTALLATION MANUAL briefl y outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
3.1. Type of copper pipe and insulation material
CAUTION
Refer to the installation manual for the outdoor unit for description of allowable pipe length and height difference.
Selecting pipe sizes
The diameters of the connection pipes according to the capacity of the indoor unit. Refer to the following table for the proper diameters of the connection pipes between the indoor unit and outdoor unit.
MODEL
Diameter
Liquid pipe Gas pipe
18, 24 1/4 in. (6.35 mm) 1/2 in. (12.70 mm) 30, 36 3/8 in. (9.52 mm) 5/8 in. (15.88 mm)
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
The basic installation work procedures are the same as conventional refrigerant (R22) models. However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and installation and service tools are special. (See the following table.) Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional piping and fl are nuts with the R410A piping and fl are nuts.
Models that use refrigerant R410A have a different charging port thread diameter to pre­vent erroneous charging with conventional refrigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2-20 UNF.]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases. And always charge from the liquid phase where refrigerant composition is stable.
2.2. Special tools for R410A
Tool name Contents of change
Gauge manifold
Pressure is high and cannot be measured with a conven­tional (R22) gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals -30 inHg to 768 psi (-0.1 to 5.3 MPa) for high pressure.
-30 inHg to 551 psi (-0.1 to 3.8 MPa) for low pressure.
Charge hose
To increase pressure resistance, the hose material and base size were changed.
Vacuum pump
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Gas leakage detector
Special gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 0.004 oz/100 ft. (40 mg/10 m). Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion value or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is nec­essary to choose adequate materials.
WARNING
Do not use the existing (for R22) piping and fl are nuts. If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause failure, injury, etc. (Use the special R410A materials.)
When installing and relocating the air conditioner, do not mix gases other than the specifi ed refrigerant (R410A) to enter the refrigerant cycle. If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause failure, injury, etc.
2.3. For authorized service personnel only.
WARNING
For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
Connect the indoor unit and outdoor unit with the air conditioner piping and cables available from your local distributor. This installation manual describes the correct con­nections using the installation set available from your local distributor.
Do not turn on the power until all installation work is complete.
CAUTION
This installation manual describes how to install the indoor unit only. To install the outdoor unit, refer to the installation manual included with the outdoor unit.
• Be careful not to scratch the air conditioner when handling it.
• After installation, explain correct operation to the customer, using the operating manual.
Page 3
En-3
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks. Use heat insulation with heat resistance above 248 °F (120 °C). Reverse cycle model only. In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 3/4 in. (15 mm) or thicker and if the expected humidity exceeds 80%, use heat insulation that is 13/16 in. (20 mm) or thicker. If heat insulation is used that is not as thick as specifi ed, condensation may form on the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m•K) or less (at [68 °F (20 °C)]).
3.2. Electrical requirement
The indoor unit is powered from the outdoor unit. Do not power indoor unit from separate power source.
WARNING
Refer to local codes for acceptable cable type.
4. SELECTING THE INSTALLATION LOCATION
Decide the mounting position with the customer as follows: (1) Install the indoor unit level on a strong wall which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed: the air should be able to blow all
over the room. (3) Install the unit a dedicated electrical branch circuit. (4) Do not install the unit where it will be exposed to direct sunlight. (5) Install the unit where connection to the outdoor unit is easy. (6) Install the unit where the drain pipe can be easily installed. (7) Take servicing, etc. into consideration and leave the spaces shown in [5.1. Installation
dimensions]. Also install the unit where the fi lter can be removed. Correct initial installation location is important because it is diffi cult to move unit after it is installed.
WARNING
Install the air conditioner in a location which can withstand a load of at least 3 times the weight of the main unit and which will not amplify sound or vibration. If the installation location is not strong enough, the indoor unit may fall and cause injuries.
Withstandable weight (Unit weight x 3*)
93 Lbs (42kg)
*In accordance with UL standards.
CAUTION
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts, caus­ing the parts to fail or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon fi bers or ammable dust, or volatile infl ammables such as paint thinner or gasoline.
• If gas leaks and settles around the unit, it can cause a fi re.
• Area where animals may urinate on the unit or ammonia may be generated.
• Do not use the unit for special purposes, such as storing food, raising animals, grow­ing plants, or preserving precision devices or art objects. It can degrade the quality of the preserved or stored objects.
• Do not install where there is the warning of combustible gas leakage.
• Do not install the unit near a source of heat, steam, or fl ammable gas.
• Install the unit where drainage does not cause any trouble.
• Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote control cable at least 40 in. (1m) away from a television or radio receivers. The purpose of this is to prevent TV reception interference or radio noise. (Even if they are installed more than 40 in. (1m) apart, you could still receive noise under some signal conditions.)
• If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
• Install the indoor unit on the wall where the height from the fl oors more than 70 in. (1.8 m).
5. INSTALLATION WORK
5.1. Installation dimensions
Remote controller
Remote controller holder
Tapping screw (small)
(Wall cap)
59-1/16 in. (1.5 m) or over
3-1/8 in. (80 mm) or over
3-1/8 in. (80 mm) or over
Wall hook bracket
4-3/4 in. (120 mm) or over
70 in. (1.8 m) or over
*
*
*
* Space from wall hook bracket.
5.2. Indoor unit piping direction
The piping can be connected in the 7 directions indicated in the following. When the piping is connected in direction 2 , 3 , 4 or 5 , cut along the piping groove in the side of the front cover with a hacksaw.
1
Rear
outlet
2
Right outlet
3
Bottom outlet
4
Left bottom
outlet
5
Left
outlet
(Rear)
6
Center
outlet
7
Left rear
outlet
5.3. Cutting the hole in the wall for the connecting pipes
(1) Cut a 3-1/8 in. (80 mm) diameter hole in the wall at the position shown in the fi gure. (2) When cutting the wall hole at the inside of the wall hook bracket, cut the hole to a point
of intersection of center marks.
When cutting the wall hole at the outside of the wall hook bracket, cut the hole at a
point of 3/8 in. (10 mm) below.
(3)
Cut the hole so that the outside end is lower [3/16 to 3/8 in. (5 to 10 mm)] than the inside end. (4) Always align the center of the wall hole. If misaligned, water leakage will occur. (5) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap
with vinyl tape, and stick the pipe through the hole. (6) F
or left piping and right piping, cut the hole a little lower so that drain water will fl ow freely.
3/8 in. (10 mm) or more lower
3/8 in. (10 mm) or more lower
3-1/8 in. (80 mm) hole
Wall hook bracket
Centering marks
Fasten with vinyl tape
Wall cap*
Wall pipe*
(Inside)
Wall
(Outside)
*Locally purchased
3/16 to 3/8 in. (5 to 10 mm)
WARNING
If the wall pipe is not used, the cable interconnecting the indoor unit(s) and outdoor unit may touch metal and cause electric discharge.
Page 4
En-4
5.4. Installing the wall hook bracket
(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically.
If the wall hook bracket is tiled, water will drip to the fl oor.
(2)
Install the wall hook bracket so that it is strong enough to support the weight of the unit.
• Fasten the wall hook bracket to the wall with 6 or more screws through the holes near the outer edge of the bracket.
Check that there is no rattle at the wall hook bracket.
Wall hook bracket
Tapping screw (large) (Quantity: 8)
CAUTION
Install the wall hook bracket level, both horizontally and vertically.
5.5.
Forming the drain hose and pipe
[Rear piping, Right piping, Bottom piping]
• Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape.
• Install the piping so that the drain hose is at the bottom.
• Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.
[For Left rear piping, Left piping]
Interchange the drain cap and the drain hose.
CAUTION
• Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.
• When inserting, be sure not to attach any material besides water. If any other material is attached, it will cause deterioration and water leakage.
• After removing drain hose, be sure not to forget mounting drain cap.
• Be sure to fi x the drain hose with tape to the bottom of piping.
Prevent drain water freezing under low temperature environment. When installing indoor unit’s drain hose outdoors, necessary measure for frost protection should be taken to prevent drain water freezing. Under low temperature environment (when outdoor temperature under 32 °F (0 °C)), after cooling operation is executed, water in the drain hose could be frozen. Once drain water is frozen, the drain hose will be blocked and water leakage may result at the indoor unit.
Installation method of Drain cap
Right piping
Bind with vinyl tape
Indoor unit drain hose (bottom)
Pipe (top) Rear piping
Bottom
piping
Drain cap
Indoor unit drain hose
Remove the drain cap by pulling at the projection at the end of the cap with pli­ers, etc.
For left outlet piping, cut off the piping outlet cutting groove with a hacksaw.
CAUTION
Insert the drain hose and drain cap into the drain port, making sure that it comes in contact with the back of the drain port, and then mount it. If the drain hose is not connected properly, leaking will occur.
• Attach the Drain hose insulation to the drain hose.
Drain hose insulation
Drain hose
For left piping and left rear piping, align the marks on the wall hook bracket and shape the connection pipe.
• Bend the connection piping at a bend radius of 3-15/16 in. (100 mm) or more and install no more than 1-3/8 in. (35 mm) from the wall.
After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on the hooks at the top and bottom of the wall hook bracket.
[Installing the indoor unit]
• Hang the indoor unit from the hooks at the top of the wall hook bracket.
• Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate
the bottom of the indoor unit from the wall.
Indoor unit
Wall hook bracket
(Spacer)
Wall hook bracket
Alignment marks
Connection piping
Large piping
Top hooks
Indoor unit
(Fitting) Bottom hooks
Wall hook bracket
Small piping
After hooking the indoor unit to the top hook, hook the fi ttings of the indoor unit to the 2 bottom hooks while lowering the unit and pushing it against the wall.
5.6. Flare connection (Pipe connection)
CAUTION
Tighten the fl are nuts with a torque wrench using the specifi ed tightening method. Oth- erwise, the fl are nuts could break after a prolonged period, causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a fl ame.
5.6.1. Flaring
Use special pipe cutter and fl are tool exclusive for R410A. (1) Cut the connection pipe to the necessary length with a pipe cutter. (2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs. (3) Insert the fl are nut (always use the fl are nut attached to the indoor unit(s) and outdoor
unit respectively) onto the pipe and perform the fl are processing with a fl are tool. Use the special R410A fl are tool, or the conventional fl are tool. Leakage of refrigerant may result if other fl are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from en-
tering the pipes.
Die
A
Pipe
B
L
Check if [L] is flared uniformly and is not cracked or scratched.
Page 5
En-5
Pipe outside diameter
[in. (mm)]
Dimension A [in. (mm)]
Dimension B [in. (mm)]
Flare tool for R410A,
clutch type
1/4 (6.35)
0 to 0.020
(0 to 0.5)
3/8 (9.1)
3/8 (9.52)
1/2 (13.2)
1/2 (12.70)
5/8 (16.6)
5/8 (15.88)
3/4 (19.7)
3/4 (19.05)
15/16 (24.0)
When using conventional fl are tools to fl are R410A pipes, the dimension A should be approximately 0.020 in. (0.5 mm) more than indicated in the table (for fl aring with R410A flare tools) to achieve the specified flaring. Use a thickness gauge to measure the dimension A.
Width across
flats
flats
Pipe outside
diameter [in. (mm)]
Width across flats of
Flare nut [in. (mm)]
1/4 (6.35)
11/16 (17)
3/8 (9.52)
7/8 (22)
1/2 (12.70)
1 (26)
5/8 (15.88)
1-1/8 (29)
3/4 (19.05)
1-7/16 (36)
5.6.2. Bending pipes
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it diffi cult to bend or stretch them anymore.
• Do not bend or stretch the pipes more than 3 times.
CAUTION
• To prevent breaking of the pipe, avoid sharp bends.
• If the pipe is bent repeatedly at the same place, it will break.
5.6.3. Pipe connection
CAUTION
• Be sure to Install the pipe against the port on the indoor unit correctly. If the center­ing is improper, the fl are nut cannot tighten smoothly. If the fl are nut is forced to turn, the threads will be damaged.
• Do not remove the fl are nut from the indoor unit pipe until immediately before con- necting the connection pipe.
• Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to tighten the fl are nut correctly.
• Tighten the fl are nuts with a torque wrench using the specifi ed tightening method. Otherwise, the fl are nuts could break after a prolonged period, causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a fl ame.
CAUTION
• Connect the piping so that the control box cover can easily be removed for servic­ing when necessary.
• In order to prevent water from leaking into the control box, make sure that the pip­ing is well insulated.
When the flare nut is tightened properly by your hand, hold the body side coupling with a wrench, then tighten with a torque wrench. (See the table below for the flare nut tightening torques.)
Tighten with two wrenches.
Holding wrench
Flare nut
Connection pipe
Torque wrench
Indoor unit pipe (Body side)
Flare nut [in. (mm)] Tightening torque [lb·ft (N·m)]
1/4 (6.35) dia. 11.8 to 13.3 (16 to 18)
3/8 (9.52) dia. 23.6 to 31.0 (32 to 42) 1/2 (12.70) dia. 36.1 to 45.0 (49 to 61) 5/8 (15.88) dia. 46.5 to 55.3 (63 to 75) 3/4 (19.05) dia. 66.4 to 81.1 (90 to 110)
6. ELECTRICAL WIRING
Cable Cable size Remarks
Connection cable 14AWG UL 1505
3 cable+Earth (Ground),
1φ 208/230 V
Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 2% or more.
6.1.
Wiring system diagram
WARNING
Before connecting the wires, make sure the power supply is OFF.
Every wire must be connected fi rmly.
No wire should be allowed to touch refrigerant tubing, the compressor or any moving part.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fi re hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.
INDOOR UNIT SIDE
INDOOR UNIT
TERMINAL
DISCONNECT SWITCH (Locally purchased)
Power line
Control line
Earth
(ground) line
OUTDOOR UNIT
Connect it to the specifi ed terminal.
Disconnect switch - fi eld supplied if required by local code. Select the correct capacity of dis- connect switch according to the load.
Earth (Ground) screw
Disconnect switch
Indoor unit terminal block
Outdoor unit Connect it to
the specifi ed terminal.
• To connect the indoor unit wires to the terminal correctly, refer to the fi gure for proper length.
14AWG
Earth (Ground) wire
6-7/8 in. (175 mm)
7-1/2 in.
(190 mm)
Conduit holder
Conduit connector
Page 6
En-6
6.2. How to the install the indoor unit wire harness
1. Remove the screws, then remove the conduit holder.
2. Fasten the indoor unit wire harness to the conduit holder using the lock nut. IMPORTANT: Refer to fi gure of indoor unit wire length about the length of indoor unit wire harness.
3. Use the screws to install the conduit holder provide with the indoor unit.
4. Remove the screws, then remove the cable clamp.
5. Connect indoor unit wire harness to the terminal. Refer to the wiring diagram.
6. Use the screws to install the cable clamp.
lock nut
CONDUIT HOLDER
SCREW
CONDUIT CON­NECTOR
Connection cable
Screw
Cable clamp
Connection
cable
Cable clamp
Screw
Square hole
Insert the tab into the square hole of the indoor unit and fas­ten with a screw.
Ta b
6.3. How to connect wiring to the terminals
Caution when wiring cable
When stripping off the insulation of a lead wire, always use a special tool such as a wire stripper. If there is no special tool available, carefully strip the insulation with a knife etc. (1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the wires using an appropriate tool so that the
wires do not come loose.
Strip : 3/8 in. (10 mm)
Ring terminal
Sleeve
(3) Use the specifi ed wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
Screw with special washer
Wire
Ring terminal
Terminal blocks
Wire
Screw with special washer
Ring terminal
(6) See the table below for the terminal screw tightening torques.
Tightening torque [lbf·in (N·m)]
M4 screw 11 to 16 (1.2 to 1.8)
CAUTION
• Attach the cable clamp fi rmly by holding the connection cable, and make sure that the clamp is fi xed securely. Incomplete attachment of the cable clamp might cause a malfunction of the open panel.
• Match the terminal block numbers and connection cable colors with those of the
outdoor unit.
Erroneous wiring may cause burning of the electric parts.
• Connect the connection cables fi rmly to the terminal block. Imperfect installation may
cause a fi re.
• Always fasten the outside covering of the connection cable with the cable clamp. (If the insulator is chafed, electric discharge may occur.)
• Always connect the ground wire.
• Do not use the earth screw of the indoor unit for the connection other than a specifi ed
outdoor unit.
7. FINISHING
(1) Insulate between pipes.
• Insulate suction and discharge pipes separately.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
• For left and left rear piping, butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
• For left and left rear piping, wrap the area which accommodates the rear piping housing section with cloth tape.
• For left and left rear piping, bind the connection cable to the top of the pipe with vinyl tape.
• For left and left rear piping, bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fi t into the rear piping housing section.
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water
does not enter.) (3) Fasten the connection pipe to the outside wall with a saddle, etc. (4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in. (5) Fasten the drain hose to the outside wall, etc.
*Locally purchased
Pipe
Saddle*
Outside wall cap*
Sealer putty*
(Outdoors)
Wall
Page 7
En-7
CAUTION
Install the Front panel and Intake grille securely. If installation is imperfect, the Front
panel or Intake grille may fall off and cause injury.
9. REMOTE CONTROLLER INSTALLATION
CAUTION
• Check that the indoor unit correctly receives the signal from the remote controller, then install the remote controller holder.
• Select the remote controller holder selection site by paying careful attention to the following: Avoid places in direct sunlight. Select a place that will not be affected by the heat from a stove, etc.
9.1. Remote controller holder installation
• Install the remote controller a maximum distance of 22 ft. (7 m) from the remote control receiver. However, when installing the remote controller, check that it operates correctly.
• I
nstall the remote controller holder to a wall, pillar, etc. with the tapping screw.
Remote controller holder fi xing
Remote controller holder
(1) Set
(2) Push
Remote controller
Tapping screw (small)
Remote controller mounting
10. OPTIONAL KIT INSTALLATION
This air conditioner can be connected with the following optional kits.
• Wired remote controller
• Simple remote controller
• External connect kit
10.1.
Before installing wired remote controller
• When you use wired remote controller, some functions may not be used.
Please use the recommended optional remote controller.
CAUTION
• Before installing, be sure to disconnect all power supply.
• Don’t touch the heat exchanger.
• During installing or removing operation, be sure not to have wire caught by parts or draw it hard. Or it may result troubles to the air-conditioner.
• Avoid place in direct sunlight.
• Select place that will not be affected by the heat from a stove, etc
• Before setting up the optional kit, please confi rm whether air-conditioner can receive the signal.
• Do not connect the wired remote controller to the terminal for power supply.
• When connecting the wired remote controller with the indoor unit, use the connecting cable (supplied with wired remote controller or simple remote controller).
• Recommended cable length of wired remote controller is 32 ft. (10 m). Make sure to do insulate of connecting part when extended the cable.
10.2.
Remote controller cable modifi cation
(1) Use a tool to cut off the terminal on the end of the remote controller cable, and then
remove the insulation from the cut end of the cable.
(2) Connect the remote controller cable and connecting cable.
(supplied with wired remote controller)
Important: Be sure to insulate the connection between the wires.
Connecting cable
White
Red
White
Red
Black
Black
Insulated connection
Remote controller cable
Remote controller cable
13/16 in.
(20 mm)
Overlap the insulation
Vinyl tape
Wrap with cloth tape
Cloth tape
Drain hose
Connection cable
Pipe
Drain hose
Check the following:
GOOD
Drain hose
Saddle
Lifted up
Wave
End in water
Drain hose
Connection pipe
Wall pipe Connection cable
Left piping For connection from the left rear
Pipe
Connection pipe (heat insulation)
Indoor unit pipe (heat insulation)
PROHIBITED
Bind the pipes together so that there is no gap.
8. FRONT PANEL REMOVAL AND INSTALLATION
8.1. Intake grille removal
(1) Open the intake grille. (2) Pull down the knob. (3) Lift the intake grille upward, until the axle at the top of the intake grille is removed.
8.2. Intake grille installation
(1)
The fi xing axle of the intake grille is installed on the Panel.
(2) Lay down the intake grille.
8.3. Front panel removal
(1)
Remove intake grille (Reference the intake grille removal.) (2) Remove 6 screws. (3)
The thumb is hung on the lower part as shown in the fi gure, and it pulls to the front,
pushing [] mark , and bottom hooks (2 position) is removed from wall hook bracket. (4) The front panel is pulled to the front, raising the upper surface, and a front panel is
removed.
8.4. Front panel installation
(1) First, fi t the lower part of the front panel, and insert top and bottom hooks. (3 top
sides) (2) Attach the 6 screws. (3) Attach the intake grille.
Top holes (two sides)
Top hole (center)
Top hook (center)
Front panel
Indoor unit
Top hooks (2 sides)
Wall hook bracket
Front panel
Push
[] mark
Screws (6 position)
Push
Front panel
Front panel
Bearing
Mounting shaft
Intake grille
Intake grille
Knob
Page 8
En-8
10.3.
External input / output Wire modifi cation
(1)
Remove insulation from wire attached to wire kit connector.
Remove insulation from fi eld supplied cable. Use crimp type insulated butt connector to join fi eld cable and wire kit wire.
(2) Connect the wire and locally purchased wire.
(Supplied with external connect kit)
Important:
Be sure to solder wires to connect. Be sure to insulate the connection between the wires.
Option parts External input/output wire
Insulated connection
Cable (Locally purchased)
10.4. Front panel, control box cover and display case removal
(1) Refer to “FRONT PANEL REMOVAL AND INSTALLATION” to remove the front panel. (2) Remove the screw then remove the control box cover. (3) Remove the display case and connector.
control box cover
screw
display case
connector
10.5. Connecting cable to control board connector
(1) Pass the cable from the hole in the back of indoor unit. (2) Connect the cable to the control board connector. (3) Hook the cable to the rib.
connect the cable
rib
CN6
CN16
CN14
PCB
hole
Option type Connector No
Wired remote controller
Simple remote controller
CN6
External input CN14
External output CN16
(4) Use cable clamper and screw to fasten the cable of wired remote controller.
screw
cable clamper
cable of wired remote controller
original wire of control unit
conduit holder
cable clamper
screw
(5) Fix the binder clamp with the screw and bind the wire of external kit with the binder.
external connect wire
conduit holder
screw
binder clamp
original wire of control box
external connect wire
binder clamp
screw
binder
10.6.
Front panel, control box cover and display case installation
Install front panel, control box cover and display case by the reverse procedures as stated in 10.4. Front panel, control box cover and display case removal.
Page 9
En-9
11. FUNCTION SETTING
Perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
CAUTION
• Confi rm whether the wiring work for Outdoor unit or Branch box has been fi nished.
• Confi rm that the cover for the electrical enclosure on the outdoor unit is in place.
This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.
• After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
• Refer to the installation manual enclosed with the remote controller when the wired remote controller (option) is used.
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP. ( ) simultaneously, press the RESET button to enter the function setting mode.
STEP 1
Selecting the Remote Controller Custom Code
Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a signal if the air conditioner has not been set for the cus­tom code.) The custom codes that are set through this process are applicable only to the signals in the FUNCTION SETTING. For details on how to set the cus­tom codes through the normal process, refer to Remote controller custom code.
1
Press SET TEMP. ( ) ( ) button to change the custom code between A B C D. Match the code on the display to the air conditioner custom code. (initially set to A) (If the custom code does not need to be selected, press the MODE button and proceed to STEP 2.)
2
Press the TIMER MODE button and check that the indoor
unit can receive signals at the displayed custom code.
3
Press the MODE button to accept the custom code, and
proceed to STEP 2.
The air conditioner custom code is set to A prior to ship­ment. Contact your retailer to change the custom code.
The remote controller resets to custom code A when the batteries in the remote con­troller are replaced. If you use a custom code other than custom code A, reset the custom code after replacing the batteries. If you do not know the air conditioner custom code setting, try each of the custom codes (A
B C D) until you fi nd the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
1
Press the SET TEMP. (
) ( ) buttons to select the function number.
(Press the MODE button to switch between the left and right digits.)
2
Press the FAN button to proceed to setting the value.
(Press the FAN button again to return to the function number selection.)
3
Press the SET TEMP. (
) ( ) buttons to select the setting value.
(Press the MODE button to switch between the left and right digits.)
4
Press the TIMER
MODE button, and START/STOP button, in the order listed to confi rm the settings.
5
Press the RESET
button to cancel the function setting mode.
6
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The Function Setting does not become active unless the power is turned off then on again.
11.1.
Function details
Filter Sign
Select appropriate intervals for displaying the fi lter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select “No indication” (03).
(... Factory setting)
Function Number
Setting
Value
Setting Description
11
00 Standard (400 hours) 01 Long interval (1000 hours) 02 Short interval (200 hours) 03 No indication
Auto Restart
Enable or disable automatic restart after a power interruption.
(... Factory setting)
Function Number
Setting
Value
Setting Description
40
00 Enable 01 Disable
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or external device.
Room temperature sensor switching
(Only for Wired remote controller) When using the Wired remote controller temperature sensor, change the setting to “Both” (01).
(... Factory setting)
Function Number
Setting
Value
Setting Description
42
00 Indoor unit 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active. * Remote controller sensor must be turned on by using the remote controller
Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
(... Factory setting)
Function Number
Setting
Value
Setting Description
44
00 A 01 B 02 C 03 D
Function number
Setting value
Page 10
En-10
External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(... Factory setting)
Function Number
Setting
Value
Setting Description
46
00 Operation/Stop mode 01 (Setting prohibited) 02 Forced stop mode
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to “Wired remote controller” (01). This function will only work if the function setting 42 is set at “Both” (01)
(... Factory setting)
Function Number
Setting
Value
Setting Description
48
00 Both 01 Wired remote controller
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
(... Factory setting)
Function Number
Setting
Value
Setting Description
49
00 Disable 01 Enable
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
Setting record
Record any changes to the settings in the following table.
Setting Description Setting Value
Filter sign
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
11.2.
Temperature correction
NOTE:
When changing Function 95, perform this setting before other Room temp. control settings (Function 30, 31, 92, 93). If Function 95 is not set fi rst, Room temperature control settings (Function 30, 31, 92, 93) will be reset and you must re-do them again.
Heat Insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment. Standard insulation “00” allows system to rapidly respond to the cooling or heating load changes. High insulation “01” is when the heat insulation structure of the building is high and does not require system to rapidly respond to cooling or heating load changes. When High insulation “01” is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 92, 93) will reset to No correction [0.0°F (0.0°C)].
(... Factory setting)
Function Number
Setting
Value
Setting Description
95
00 Standard insulation 01 High insulation
Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting “00” (manufacturer’s recommended value). * When Function 95-01(High insulation) is set, the Standard setting “00” will be the same
as No correction “01” [0.0°F (0.0°C)].
(... Factory setting)
Function Number
Setting
Value
Setting Description
30
(For cooling)31(For heating)
00 Standard setting*
01 No correction 0.0°F (0.0°C)
02 -1°F (-0.5°C)
More
Cooling
Less
Heating
03 -2°F (-1.0°C)
04 -3°F (-1.5°C)
05 -4°F (-2.0°C)
06 -5°F (-2.5°C)
07 -6°F (-3.0°C)
08 -7°F (-3.5°C)
09 -8°F (-4.0°C)
10 +1°F (+0.5°C)
Less
Cooling
More
Heating
11 +2°F (+1.0°C)
12 +3°F (+1.5°C)
13 +4°F (+2.0°C)
14 +5°F (+2.5°C)
15 +6°F (+3.0°C)
16 +7°F (+3.5°C)
17 +8°F (+4.0°C)
Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(... Factory setting)
Function number
Setting
value
Setting description
92
(For cooling)93(For heating)
00 No correction 0.0°F (0.0°C)
01 No correction 0.0°F (0.0°C)
02 -1°F (-0.5°C)
More
Cooling
Less
Heating
03 -2°F (-1.0°C)
04 -3°F (-1.5°C)
05 -4°F (-2.0°C)
06 -5°F (-2.5°C)
07 -6°F (-3.0°C)
08 -7°F (-3.5°C)
09 -8°F (-4.0°C)
10 +1°F (+0.5°C)
Less
Cooling
More
Heating
11 +2°F (+1.0°C)
12 +3°F (+1.5°C)
13 +4°F (+2.0°C)
14 +5°F (+2.5°C)
15 +6°F (+3.0°C)
16 +7°F (+3.5°C)
17 +8°F (+4.0°C)
Setting record
• Record any changes to the settings in the following table.
Setting Setting Value
Heat Insulation condition (building insulation)
Room temperature control for indoor unit sensor
Cooling Heating
Room temperature control for wired remote controller sen­sor
Cooling Heating
After completing the Function Setting, be sure to turn off the power and turn it on again.
Page 11
En-11
Remote controller custom code setting
Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a signal if the air conditioner has not been set for the cus­tom code.)
(1) Press the START/STOP button until only the clock is displayed on the remote control-
ler display.
(2) Press the MODE button for at least 5 seconds to display the current custom code
(initially set to A).
(3) Press the SET TEMP. () () button to change the custom code between
ABCD. Match the code on the display to the air conditioner custom code.
(4) Press the MODE button again to return to the clock display. The custom code will be
changed.
If no buttons are pressed within 30 seconds after the custom code is displayed, the system returns to the original clock display. In this case, start again from step 1
The air conditioner custom code is set to A prior to shipment.
The remote controller resets to custom code A when the batteries in the remote control­ler are replaced. If you use a custom code other than custom code A, reset the custom code after replacing the batteries. If you do not know the air conditioner custom code setting, try each of the custom codes (ABCD.) until you find the code which operates the air conditioner.
12. TEST RUN
WARNING
Do not turn on the power until all installation work is complete.
CAUTION
Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection.
Check items
(1) Is operation of each button on the remote control unit normal? (2) Does each lamp light normally? (3) Do air fl ow direction louvers operate normally? (4) Is the drain normal? (5) Do not have an abnormal noise and vibration during operation?
• Do not operate the air conditioner in test run for a long time.
[Operation method]
• For the operation method, refer to the operating manual.
• The outdoor unit may not operate depending on the room temperature. In this case, press the test run button on the remote controller while the air conditioner is
running. (Point the transmitter section of the remote controller toward the air conditioner and press the test run button with the tip of a ballpoint pen, etc.)
Transmitter section
TEST RUN button
• To end test operation, press the remote controller START/STOP button. (When the air conditioner is running by pressing the TEST RUN button, the OPERA­TION Lamp and TIMER Lamp will simultaneously fl ash slowly.)
[Using the wired remote control] (Option)
For the operation method, refer to the operating manual. (1) Stop the air conditioner operation. (2) Press the MODE button and the FAN button simultaneously for 2 seconds or more to
start the test run.
Test run display
(3) Press the START/STOP button to stop the test run.
13. CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual: (1) Starting and stopping method, operation switching, temperature adjustment, timer, air
ow switching, and other remote control unit operations. (2) Air fi lter removal and cleaning, and how to use the air louvers. (3) Give the operating manual to the customer.
14. ERROR CODES
If you use a wireless remote controller, the lamp on the photo detector unit will output error codes by way of blinking patterns. If you use a wired remote controller, error codes will ap­pear on the remote control display. See the lamp blinking patterns and error codes in the table. An error display is displayed only during operation.
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp
(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
(1)
(1)
Serial communication error
(1)
(2)
Wired remote controller communication error
(1)
(5)
Check run unfinished
(2)
(1)
Unit number or Refrigerant circuit address setting error [Simultaneous Multi]
(2)
(2)
Indoor unit capacity error
(2)
(3)
Combination error
(2)
(4)
• Connection unit number error (indoor secondary unit)
[Simultaneous Multi]
• Connection unit number error (indoor unit or branch unit) [Flexible Multi]
(2)
(7)
Primary unit, secondary unit set­up error [Simultaneous Multi]
(3)
(2)
Indoor unit PCB model information error
(3)
(5)
Manual auto switch error
(4)
(1)
Room temp. sensor error
(4)
(2)
Indoor unit Heat Ex. Middle temp. sensor error
(5)
(1)
Indoor unit fan motor error
(5)
(3)
Drain pump error
(5)
(7)
Damper error
(5)
(8)
Intake grille error
(5)
(15)
Indoor unit error
(6)
(2)
Outdoor unit main PCB model information error or communication error
(6)
(3)
Inverter error
(6)
(4)
Active filter error, PFC circuit er­ror
(6)
(5)
Trip terminal L error
Page 12
En-12
(6)
(10)
Display PCB microcomputers communication error
(7)
(1)
Discharge temp. sensor error
(7)
(2)
Compressor temp. sensor error
(7)
(3)
Outdoor unit Heat Ex. liquid temp. sensor error
(7)
(4)
Outdoor temp. sensor error
(7)
(5)
Suction Gas temp. sensor error
(7)
(6)
• 2-way valve temp. sensor error
• 3-way valve temp. sensor error
(7)
(7)
Heat sink temp. sensor error
(8)
(2)
• Sub-cool Heat Ex. gas inlet temp. sensor error
• Sub-cool Heat Ex. gas outlet temp. sensor error
(8)
(3)
Liquid pipe temp. sensor error
(8)
(4)
Current sensor error
(8)
(6)
• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
(9)
(4)
Trip detection
(9)
(5)
Compressor rotor position detection error
(9)
(7)
Outdoor unit fan motor error
(9)
(9)
4-way valve error
(10)
(1)
Discharge temp. error
(10)
(3)
Compressor temp. error
(10)
(4)
High pressure error
(10)
(5)
Low pressure error
(13)
(2)
Branch boxes error [Flexible Multi]
Display mode
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
[Troubleshooting with the Wired Remote Controller Display (Option)]
If an error occurs, the following display will be shown. (“Er” will appear in the set room temperature display.)
Error code
Loading...