Fujitsu 18RLX, 24RLX, 42RLX, 36RLX Service Bulletin

Page 1
FUJITSU GENERAL AMERICA, INC
SERVICE BULLETIN
Number: 0006 Date: 9/22/09 Rev2
Em: ServiceHVAC@fujitsugeneral.com
Type: Field
Fresh Air Intake w/ Compressor Operation OnlyPROBLEM
Duct Fan ControlSOLUTION
Production: All CassettesMODEL :18/24/36/42RLX Systems
1. Outline
The circuit shown below provides a cost effective solution for wiring a current switch that monitors the compressor operation ON/OFF status and energizes the coil of a relay which in turn close the contacts and provide line voltage to the duct fan. The duct fan is required to introduce fresh (outside) air for ventilation.
2. Application
A third party current sensor switch with a built-in relay was used in this application. The current sensor may be installed around one of the compressor line voltage wires (Red, Black or White).
3. Wiring diagram
IPM
24V DC
115V AC
+ _
Current Sensor
N.O.
N.O.
N.O.
Built in Relay
Compressor
Duct fan booster
Page 2
4. Components utilized
Current sensor with built-in relay specifications: Split Core Fixed Threshold Current Status Sensor with Command Relay and Switching Power Supply.
FGAI Fresh Air Kit Part # KHRS940-25
5. Recommended Fan size.
Duct and Fan are field supply. A fan capable of generating 15 CFM at a static pressure of approximately .26 inches W.C.
Wiring
•Recommended wire size- 14 AWG.
10A Fuse
(Field Supply)
Page 3
Current Sensor Installation
• Install the current sensor around one of the compressor line voltage wires.
• Tuck sensor into the clearance behind the compressor wire molex plug.
• Secure the current sensor with a zip tie.
Page 4
Secure Current Sensor
1
3
2
4
1
3
2
4
• 4 zip ties are needed for correct installation.
• Secure the current sensor wires with all four zip ties according to the arrows. Do not tie around any of the copper lines.
•Cut the ends of the zip ties.
Page 5
CASSETTE
CEILING CASSETTE
OUTSIDE (FRESH) AIR INTAKE
58.8 Pa .24 in W.C.
15 CFM
4” Duct
Outside (Fresh)
Air Intake
Fan
2.75” x 4”
Field Supplied
Transition
Fan Static Pressure Requirements:
Static pressure required at Cassette = .24 in W.C. 25 ft. 4” duct + intake=45ft. TEL x .04/100 = .018 in W.C.
TOTAL =.258 in W.C.
Fan Selection:
Select fan to deliver 15 CFM @ approximately .26 in W.C. Static pressure requirements will vary with duct length and inlet conditions.
NOTE: Filter for outside air required. Add filter static pressure loss to static pressure requirements above.