• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) /67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) /59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) /43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Provide sufficient installation space for product safety.
WALL MOUNTED
ASU18, 24RLF
Installation space requirement
- 4 -
Page 9
3. Wiring diagrams
3-1. Models: ASU18RLF and ASU24RLF
WALL MOUNTED
ASU18, 24RLF
- 5 -
Page 10
4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and
the indoor temperature, under given Airflow Rate (AFR):
WALL MOUNTED
ASU18, 24RLF
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
WALL MOUNTED
6-1. Noise level curve
ASU18, 24RLF
¢
Cooling
Model: ASU18RLF
Heating
Model: ASU24RLF
¢
Cooling
Heating
- 14 -
Page 19
6-2. Sound level check point
2 ft 7
-5/8
in (0.8 m)
3 ft 3
-3/8
in (1 m)
MicrophoneMicrophone
NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated
above.
WALL MOUNTED
ASU18, 24RLF
- 15 -
Page 20
7. Safety devices
WALL MOUNTED
ASU18, 24RLF
Circuit protectionCurrent fuse (PCB*)250 V, 3.15 A
Terminal protectionCurrent fuse250 V, 3 A
Fan motor protection
*PCB: Printed Circuit Board
Type of protectionProtection form
Thermistor protection
Power IC thermal
shutdown protection
Activate
Reset
Activate
Reset
Model
ASU18RLFASU24RLF
More than 185°F (85°C)
Fan motor speed down
Less than 185°F (85°C)
Fan motor speed recover
302±27°F (150±15°C)
Fan motor stop
Less than 275°F (135°C)
Fan motor restart
- 16 -
Page 21
8. External input and output
With using external input and output functions, this product can be operated inter-connectedly
with an external device.
ConnectorInputOutputRemarks
CN14Control input—
CN16—Operation status output
See external input/output
settings for details.
8-1. External input
With using external input function, some functions on this product can be controlled from an external device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
Control input (Operation/Stop or Forced stop)
¢
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
WALL MOUNTED
ASU18, 24RLF
Unit operationInitial setting after power is on
Operation modeAuto changeoverMode at previous operation
Set temperature76 °F (24 °C)Temperature at previous operation
Airflow modeAUTOMode at previous operation
Air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Starting mode other than initial
setting
- 17 -
Page 22
Circuit diagram example
Indoor unit
control PCB
Example: Switch
Locally purchased
Connected unit
1
3
Signal
Connector
*33 ft. (10 m)
Operation
Stop
On
Off
Input signal
Indoor unit
Remote controller
OnOnOn
Input signal
Indoor unit
Command
Remote control
operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
WALL MOUNTED
ASU18, 24RLF
• Contact capacity: DC 24 V or more, 10 mA or
more.
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Use non-polar relays and switches.
• When function setting is "Operation/Stop" mode
• When function setting is "Forced stop" mode
Optional part
Part nameModel nameExterior
External connect kitUTY-XWZX
External input wire
- 18 -
Page 23
8-2. External output
Locally purchased
Indoor unit
control PCB
Connected unit
Example: Display
Example: Relay unit
Relay
power supply
DC 24 V
1
2
Signal
V
Connector
*33 ft
(10 m)
On
Off
Operation
Stop
Indoor unit
Output signal
With using external output function, operating status of this product can be transmitted to the external device, and also, this product can be inter-connected with the external device.
Operation status output
¢
Air conditioner operation status signal can be output.
Circuit diagram example
WALL MOUNTED
ASU18, 24RLF
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
Optional part
Part nameModel nameExterior
External output wire
External connect kitUTY-XWZX
- 19 -
Page 24
9. Remote controller
o
p
j
k
l
n
m
b
d
e
a
f
i
g
h
c
q
r
s
t
u
v
w
x
WALL MOUNTED
9-1. Wireless remote controller
ASU18, 24RLF
¢
Display panel
Overview
a
FAN button
Selects the fan speed (AUTO, HIGH, MED, LOW, and
QUIET).
b START/STOP button
Starts and stops operation.
c SET button (vertical)
Adjusts the vertical airflow direction.
d SET button (horizontal)
Adjusts the horizontal airflow direction.
e SWING button
Sets the automatic swing operation and selects swing
mode (Up/down, Left/right, Up/down/left/right, and Stop
swing).
f RESET button
Used when replacing batteries.
g Timer set (- / +) button
Sets the current time and on-off time.
h TEST RUN button
Only used for the initial test in the unit installation.
i CLOCK ADJUST button
Used for adjusting the clock.
j TIMER MODE button
Selects the timer mode (off timer, on timer, program
timer, and timer reset).
k SLEEP button
Pressed to select sleep timer.
l ECONOMY button
m MIN. HEAT button
NOTE:
Functions may differ by type of the indoor unit. For details, refer to the operation manual.
n
SET TEMP. (temperature) (
• Sets desired temperature.
• Sets remote controller custom code.
/ ) button
o MODE button
• Switches operation mode (AUTO, COOL, DRY, FAN,
and HEAT).
p
q Signal transmit indicator
r Fan speed indicator
s Swing indicator
t Timer mode indicator
u Clock indicator
v Sleep indicator
w Operating mode indicator
x Temperature indicator
To adjust the functions of this product according to the installation environment, various types of
WALL MOUNTED
ASU18, 24RLF
function settings are available.
NOTE:
10-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting procedure and the content of each function setting, select appropriate functions for your installation
environment.
NOTE: Incorrect settings can cause a product malfunction.
¢
The function number and the associated setting value are displayed on the LCD of the remote
controller. Follow the instructions written in the local setup procedure supplied with the remote
controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
Then, connect the power supply of indoor unit.
Incorrect settings can cause a product malfunction.
Setting procedure by using wireless remote controller
Entering function setting mode:
While pressing the FAN button and SET TEMP. () button simultaneously, press the RESET
button to enter the function setting mode.
STEP 1: Setting the remote controller custom code
Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a custom code if the air conditioner has not been set for the custom code.)
The custom codes that are set through this process are applicable only to the signal in the function setting.
For details on how to set the custom codes through the normal process, refer to "Custom code
setting for wireless remote controller" on page 28.
1. Press the SET TEMP. (
code between → → → . Match the code on the display to
the air conditioner custom code. (Initially set to
code does not need to be selected, press the MODE button, and
proceed to STEP 2.
2. Press the TIMER MODE button and check that the indoor unit can
receive signals at the displayed custom code.
3. Press the MODE button to accept the custom code, and proceed
to STEP 2.
4. After completing the function setting, be sure to disconnect the
power supply and then reconnect it.
) () buttons to change the custom
.) If the custom
NOTES:
•
The air conditioner custom code is set to “ ” prior to shipment.
•
The remote controller resets to custom code “ ” when the batteries on the remote controller
are replaced. If you use a custom code other than code “ ”, reset the custom code after re-
placing the batteries.
•
If you do not know the air conditioner custom code setting, try each of the custom codes ( →
→ → ) until you find the code that operates the air conditioner.
- 22 -
Page 27
STEP 2: Selecting the function number and setting value
Function number
Setting value
1. Press the SET TEMP. () () buttons to select the function
number. To switch between the left and right digits, press the
MODE button.
2. Press the FAN button to proceed the setting value. To return the
function number selection, press the FAN button again.
3. Press the SET TEMP. () () buttons to select the setting value.
To switch between the left and right digits, press the MODE button.
4. Press the TIMER MODE button, and START/STOP button, in the
order listed to confirm the settings.
5. Press the RESET button to cancel the function setting mode.
6. After completing the function setting, be sure to disconnect the
power supply and then reconnect it.
CAUTION
After disconnecting the power supply, wait 30 seconds or more before reconnecting it. The function setting will not become active unless the power supply is disconnected and then reconnected.
WALL MOUNTED
ASU18, 24RLF
- 23 -
Page 28
¢
Each function setting listed in this section is adjustable in accordance with the installation environment.
WALL MOUNTED
ASU18, 24RLF
NOTE:
1)Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Contents of function setting
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.Functions
1)11Filter sign
2)30/31Room temperature control for indoor unit sensor
3)40Auto restart
4)42Room temperature sensor switching
5)44Remote controller custom code
6)46External input control
7)48Room temperature sensor switching (Aux.)
8)92/93Room temperature control for wired remote controller sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufacturer’s recommended value).
*When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No
correction 0.0 °F (0.0 °C)" (01).
Enables or disables automatic restart after a power interruption.
Function numberSetting valueSetting descriptionFactory setting
00Enable♦
01Disable
NOTE:
40
Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.
4)Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function numberSetting valueSetting descriptionFactory setting
42
00Indoor unit♦
01Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
- 25 -
Page 30
5)Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
WALL MOUNTED
ASU18, 24RLF
6)External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
7)Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
Function numberSetting valueSetting descriptionFactory setting
00A♦
44
Function numberSetting valueSetting descriptionFactory setting
Function numberSetting valueSetting descriptionFactory setting
48
00Both♦
01Wired remote controller
- 26 -
Page 31
8)Room temperature control for wired remote controller sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to "Both" (01).
Ensure that the thermo sensor icon is displayed on the remote controller screen.
Heat insulation conditions differ according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load
changes.
"High insulation" (01) is when the heat insulation structure of the building is high and does not re-
quire system to rapidly respond to cooling or heating load changes.
When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 92, and 93) will reset to "No correction
0.0 °F (0.0 °C)".
Function numberSetting valueSetting descriptionFactory setting
95
00Standard insulation♦
01High insulation
NOTE:
When changing Function 95, perform this setting before other room-temperature control
settings (Function 30, 31, 92, and 93). If Function 95 is not set first, room-temperature
control settings (Function 30, 31, 92, and 93) will be reset and you must re-do them
again.
- 27 -
Page 32
¢
To interconnect the air conditioner and the wireless remote controller, assignment of the custom
code for the wireless remote controller is required.
WALL MOUNTED
ASU18, 24RLF
NOTE:
1.Press the START/STOP button until only the clock is displayed on the remote controller dis-
2.Press the MODE button for at least 5 seconds to display the current custom code. (Initially
Custom code setting for wireless remote controller
Air conditioner cannot receive a custom code if the air conditioner has not been set for
the custom code.
play.
set to
.)
Press the SET TEMP. (
3.
Match the code on the display to the air conditioner custom code.
4.Press the MODE button again to return to the clock indicator. The custom code will be
changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system returns to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to prior to shipment. To change the custom code,
contact your retailer.
• The remote controller resets to custom code when the batteries in the remote controller are
replaced. If you use a custom code other than code , reset the appropriate custom code af-
ter replacing the batteries. If you do not know the assigned code for the air conditioner, try
each of the custom code ( → → → ) until you find the code which operates the air condi-
tioner.
or ) button to change the custom code between → → → .
- 28 -
Page 33
11. Accessories
Part nameExteriorQ’tyPart nameExteriorQ’ty
Operating manual1Drain hose insulation1
Installation manual1Cloth tape1
WALL MOUNTED
ASU18, 24RLF
Wall hook bracket1
Remote controller1
Battery2Air cleaning filter2
Remote controller
holder
Tapping screw (large),
M4 × 25 mm
Tapping screw (small),
M3 × 12 mm
1Air cleaning filter frame2
8
2
- 29 -
Page 34
12. Optional parts
Mode
Menu
Cool
Monitor
Set temp.
Fan
High
°
F
80
Mo
10:00
AM
Icon check:
WALL MOUNTED
12-1. Controllers
ASU18, 24RLF
ExteriorPart nameModel nameSummary
Large and full-dot liquid crystal
Wired remote
controller
UTY-RVNUM
screen, wide and large keys easy to
press, user-intuitive arrow key.
Wire type: Polar 3-wire
Room temperature can be controlled
Wired remote
controller
UTY-RNNUM
by detecting the temperature
accurately with built-in thermo
sensor.
Wire type: Polar 3-wire
Compact remote controller
concentrates on the basic functions
Simple remote
controller
UTY-RSNUM
such as Start/Stop, fan control,
temperature setting, and operation
mode.
Wire type: Polar 3-wire
NOTE:
Available functions may differ by the remote controller. For details, refer to the operation
manual.
12-2. Others
ExteriorPart nameModel nameSummary
External
connect kit
UTY-XWZX
Use to connect with various
peripheral devices and air conditioner
PCB.
- 30 -
Page 35
Part 2. OUTDOOR UNIT
SINGLE TYPE:
AOU18RLXFWH
AOU24RLXFWH
Page 36
1. Specifications
TypeInverter heat pump
Model nameAOU18RLXFWHAOU24RLXFWH
Power supply208/230 V ~ 60 Hz
Available voltage range187—253 V
Starting currentA8.010.5
Fan
Sound pressure level *1
OUTDOOR UNIT
AOU18, 24RLXFWH
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions
(H × W × D)
Weight
Connection pipe
Operation range
Drain hose
Airflow rate
Type × Q'tyPropeller fan × 1
Motor outputW100
Type × Q'tyHermetic motor compressor × 1
Motor outputW2,100
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Cooling
Heating1,489 (2,530)2,119 (3,600)
Cooling
Heating5055
Dimensions
(H × W × D)
Fin pitchFPI20
Rows × Stages2 × 38
Pipe typeCopper
Fin type
TypeR410A
Charge
TypePOE (RB68)
Amount
MaterialSteel sheet
Color
Liquid
GasØ 5/8 (Ø 15.88)
Cooling
Heating-15 to 75 (-26 to 24)
MaterialLDPE
SizemmØ 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
CFM (m3/h)
dB (A)
in31-7/16 × 35-7/16 × 1-7/16
mm798 × 900 × 36.4
Type (Material)Corrugate (Aluminum)
Surface treatmentCorrosion resistance (Blue fin)
lb oz4 lb 10.1 oz
g2,100
in3 (cm3)
in32-11/16 × 35-7/16 × 13
mm830 × 900 × 330
in39-3/8 × 41-5/16 × 17-1/2
mm1,000 × 1,050 × 445
lb (kg)
in (mm)
ft (m)
°F (°C)
1,489 (2,530)2,001 (3,400)
4754
48.8 (800)
Beige
Approximate color of MUNSELL 10YR7.5/1.0
135 (61)
Ø 3/8 (Ø 9.52)
66 (20)
-5 to 115 (-20 to 46)
- 32 -
Page 37
2. Dimensions
Unit: in (mm)
Top view
Front view
Side view
Bottom view
3(77)
35-3/8 (900)
32-3/4 (830)
17-3/8 (440)
7/8 (21)
15-3/4 (400)
13 (330)
7-3/4 (196)
5-3/4 (147)
6-3/4 (170)
14-5/8 (370)
25-5/8 (650)
Airflow
1-1/4
(31)
1/2
(12)
3-7/8
(99)
3/8
(9)
2-1. Models: AOU18RLXFWH and AOU24RLXFWH
OUTDOOR UNIT
AOU18, 24RLXFWH
- 33 -
Page 38
3. Installation space
4 (100) or more
10 (250)
or more
12 (300)
or more
4 (100)
or more
24 (600)
or more
24 (600)
or more
4 (100)
or more
12 (300)
or more
Max. 19
(500)
24 (600)
or more
40 (1,000)
or more
4 (100)
or more
10 (250)
or more
20 (500)
or more
Max. 19
(500)
3-1. Models: AOU18RLXFWH and AOU24RLXFWH
¢
Provide sufficient installation space for product safety.
Single outdoor unit installation
OUTDOOR UNIT
AOU18, 24RLXFWH
Space requirement
• When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only.When there are obstacles at the rear and
sides.
When there are obstacles at the front only.When there are obstacles at the front and
rear.
• When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear
and above.
When there are obstacles at the rear, sides,
and above.
- 34 -
Page 39
Multiple outdoor unit installation
12 (300)
10 (250)
or more
or more
60 (1,500)
or more
10 (250) or more
20 (500)
or more
60 (1,500)
or more
10 (250) or more
60 (1,500) or more
20 (500) or more
10 (250)
or more
10 (250)
or more
Max. 11
(300)
60 (1,500)
or more
• When the upper space is open:
When there are obstacles at the rear only.When there are obstacles at the front only.
When there are obstacles at the front and
rear.
Unit: in (mm)
OUTDOOR UNIT
AOU18, 24RLXFWH
• When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
- 35 -
Page 40
Outdoor unit installation in multi-row
6 (150) or more
24 (600) or more
40 (1,000) or more
79 (2,000) or more
20 (500) or more
24 (600) or more
60 (1,500) or more
10 (250) or more
119 (3,000) or more
10 (250) or more
60 (1,500) or more
20 (500) or more
10 (250) or more
OUTDOOR UNIT
AOU18, 24RLXFWH
Unit: in (mm)
Single parallel unit arrangementMultiple parallel unit arrangement
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no
obstacle.
• Height above the floor level should be 2 in (50 mm) or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the
drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 32 °F (0 °C) or less, do not use the accessory drain pipe
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may
freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it
might become difficult to get warm, and it is likely to cause product malfunction. Construct a
canopy and a pedestal, or place the unit on a high stand that is locally installed.
- 36 -
Page 41
4. Refrigerant circuit
3-way valve
(small)
3-way valve
(large)
Muffler
Pressure
switch
4-way valve
Strainer
Expansion valve
Strainer
Heat exchanger
(INDOOR)
Heat exchanger
(OUTDOOR)
Sub-accumulator
Compressor
Cooling
Heating
4-1. Models: AOU18RLXFWH and AOU24RLXFWH
OUTDOOR UNIT
AOU18, 24RLXFWH
- 37 -
Page 42
5. Wiring diagrams
5-1. Model: AOU18RLXFWH
OUTDOOR UNIT
AOU18, 24RLXFWH
- 38 -
Page 43
5-2. Model: AOU24RLXFWH
OUTDOOR UNIT
AOU18, 24RLXFWH
- 39 -
Page 44
6. Capacity compensation rate for pipe length and height
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
difference
OUTDOOR UNIT
AOU18, 24RLXFWH
6-1. Models: AOU18RLXFWH and AOU24RLXFWH
NOTE: Values mentioned in the table are calculated based on the maximum capacity.