Fujitsu 12RGLXD, 30RGLXD, 36RGLXD, 48RGLXD, 18RGLXD Brochure

...
Page 1
MEDIUM STATIC PRESSURE DUCT MINI-SPLITS
ARU12RGLX / AOU12RLFC ARU18RGLX / AOU18RGLX ARU24RGLX / AOU24RGLX ARU30RGLX / AOU30RGLX ARU36RGLX / AOU36RGLX ARU42RGLX / AOU42RGLX ARU48RGLX / AOU48RGLX
Page 2
11-13/16”(300mm)
A GAME CHANGER
32-11/16 (830)
Fujitsu is proud to introduce the newest addition to our single-zone mini-split lineup – three new Medium Static Pressure Duct indoor units! These units use the same energy efficient inverter technology you expect from Fujitsu mini-split products, and they have enough static pressure to heat or cool a whole house. SEER ratings up to 21.3 and a compact size mean these indoor units can find a place in many applications.
SYSTEM 12RGLXD 18RGLXD 24RGLXD 30RGLXD 36RGLXD 42RGLXD 48RGLXD
Indoor Unit Outdoor Unit
ARU12RGLX ARU18RGLX ARU24GLX ARU30RGLX ARU36RGLX ARU42RGLX ARU48RGLX AOU12RLFC AOU18RGLX AOU24RGLX AOU30RGLX AOU36RGLX AOU42RGLX AOU48RGLX
SLIM & COMPACT DESIGN INDOOR UNIT & OUTDOOR UNIT
New ducted air conditioners are slim and compact in design in order to fit into most ceiling spaces, making them ideal for hidden installations.
The compact outdoor units can be installed below a window and in a narrow space. (18, 24, 30, 36,000 BTUh units)
AOU18/24/30/36RGLX
35-7/16 (900)15-3/4 (400)
36/42/48,000: 55-1/8”(1,400mm)
(unit : in. (mm))
18/24/30,000: 39-3/8”(1,000mm)
12,000: 27-9/16”(700mm)
27-9/16”(700mm)
2
Page 3
FEATURE HIGHLIGHTS
Long duct
Short duct
Energy efficient DC fan motor
Can be installed in applications that require static pressure up to 0.80” W.G. (12/18/24/30/36k models).
Max piping lengths of up to 246 feet (42/48RGLXD systems).
Medium Static Ducted units must be installed horizontally.
Heating operation rated down to -5˚F outdoor temperature.
Select two- or three-wire control via dipswitch on indoor unit.
AUTOMATIC AIRFLOW ADJUSTMENT FUNCTION
This unique and innovative function detects required airflow in each application case and automatically adjusts the flow.
0.12 in. W.G. (30Pa)
0.80 in. W.G. (200Pa)
BUILT-IN DRAIN PUMP
These units come standard with a built-in drain pump, up to 33.5” of vertical lift.
ENERGY EFFICIENT & QUIET OPERATION
The combination of the V-shaped heat exchanger, air stabilizer, and the energy efficient DC fan motor results in high efficiency and quiet operation.
The 12, 18 and 24,000 BTUh models are Energy Star qualified.
Noise Level
24dB(A)*
Air Stabilizer
V-shape heat exchanger
Lower power consumption
* 12,18, 24,000 BTUh models fan speed: Quiet
OPTIONAL PARTS
• Wired Remote Controller: UTY-RNRUZ2, UTY-RVNUM • Simple Remote Controller: UTY-RSRY, UTY-RHRY
• Thermostat Converter: UTY-TTRX • Wireless LAN Interface: UTY-TFSXZ2
• IR Receiver Unit: UTY-LBTUM • Remote Sensor Unit: UTY-XSZX
• External input & output PCB: UTY-XCSX • External input & output PCB Box: UTZ-GXNA
• External Connector Kit: UTY-XWZXZG, UTY-XWZXZ3
• Long Life Filter: UTD-LFNA (For 36/42/48k models), UTD-LFNB (For 18/24/30k models), UTD-LFNC (For 12k model)
3
Page 4
MULTI-ZONE MINI-SPLITS
8-9/16(217)
Top View
Side View (L) Side View (R)
A
B
24-13/16 (631)
27-9/16 (700)
D C
3-7/8(98)
Drain port
Drain port
Gas pipe
Liquid pipe
Front View
Air
Ø4-15/16 (125)
11-13/16 (300)
DIMENSIONS
Outdoor unit:
AOU12RLFC
3/4
(19) 31-1/8 (790)
2-5/8
11/16
(67)
(18) 11-7/16 (290)
7/8
(23)
Indoor units: ARU12/18/ 24/30/36/42/48RGLX
A 27-9/16 (700) 39-3/8 (1,000) 55-1/8 (1,400) B 18-3/16 (4 62) 30 (762) 45-3/4 (1,162) C 25 -9/16 (650) 35-1/4 (895) 51 (1,295) D 29 -1/8 (740) 40-15/16 (1,040) 56-11/16 (1,440)
Outdoor unit:
AOU18/ 24 /30/36RGLX
35-7/16 (900)
1-1/4
3-1/16
(31)
(77) 13 (330)
Outdoor unit:
AOU42/48RGLX
1/2
(12)
50-13/16 (1,290)
35-7/16 (900)
(Unit : in. (mm))
1-1/4
(31)
13 (330)
1/2
(12)
24- 7/16 (620)
13/16 (20)
3/8 (9)
13-7/8 (352)
Side viewFront view
32-11/16 (830)
13/16 (21)
3/8 (9)
15-3/4 (400)
Side viewFront view
SPECIFICATIONS
Model No.
Power supply V /Ø/Hz 208/230 V ~ single phase ~ 60Hz
Capacity
Input power kW 0.89 1.38 1.90 2.83 3.60 3.65 4.75
Cooling
Heating
Fan
EER
SEER Btu/hW 21.3 19.0 17.5 16.5 16.7 17.8 16.6
Sound pressure
Capacity
Input power kW 1.20 1.50 2.06 2.48 2.88 3.67 4.45
COP
HSPF Btu/hW 11.7 10.9 10.8 10.4 11.3 10.5 10.3
Sound pressure
Air Flow Rate (Hi/Me/Lo/Qu)
Indoor ARU12RGLX ARU18RGLX ARU24RGLX ARU30RGLX ARU36RGLX ARU42RGLX ARU48RGLX
Outdoor AOU12RLFC AOU18RGLX AOU24RGLX AOU30RGLX AOU36RGLX AOU42RGLX AOU48RGLX
Rated Btu/h 12,000 18,000 24,000 30,000 36,000 42,000 48,000 Min-Max Btu/h 3,100 - 13,600 5,400 - 21,500 5,400 - 29,000 9,600 - 35,000 9,600 - 39,000 17,100 - 45,000 17,100 - 50,000
kW/kW 3.93 3.81 3.69 3.11 2.93 3.37 2.96
Btu/hW 13.4 13.0 12.6 10.6 10.0 11.5 10.1
Indoor (Hi/Me/Lo/Qu) Outdoor 49 47 53 53 54 55 57 Rated Btu/h 16,000 21,000 27,000 32,000 36,000 47,000 53,000 Min-Max Btu/h 3,100 - 19,400 5,400 - 25,600 5,400 - 32,400 9,200 - 39,000 9,200 - 48,000 18,000 - 51,000 18,000 - 55,000
Indoor (Hi/Me/Lo/Qu) Outdoor 50 50 55 55 56 57 59
35 / 30 / 27 / 24 31 / 28 / 25 / 24 34 / 29 / 26 / 24 37 / 34 / 30 / 29 37 / 33 / 30 / 26 40 / 35 / 33 / 29 40 / 35 / 33 / 29
dB(A)
kW/kW 3.90 4.10 3.84 3.78 3.66 3.75 3.49
Btu/hW 13.3 14.0 13.1 12.9 12.5 12.8 11.9
35 / 30 / 27 / 24 31 / 28 / 25 / 24 34 / 29 / 26 / 24 37 / 34 / 30 / 29 35 / 33 / 30 / 26 40 / 35 / 33 / 29 40 / 35 / 33 / 29
dB(A)
500 / 400 / 347 /
CFM
(m3/h)
(850 / 680 / 590 /
300
510)
618 / 565 / 530 /
459
(1,050 / 960 / 900
/ 780)
800 / 636 / 518 /
400
(1,360 / 1,080 /
880 / 680)
1,001 / 800 / 700 / 630 (1,700 / 1,360 / 1,190
/ 1,070)
1,207 / 965 / 783 / 630 (2,050 / 1,640 / 1,330
/ 1,070)
3/8 (9) 13/16 (21)
1,501 / 1,201 / 971 /
842
(2,550 / 2,040 / 1,650
/ 1,430)
15-3/4 (400)
Side viewFront view
1,501 / 1,201 / 971 /
842
(2,550 / 2,040 / 1,650 /
1,430)
Static Pressure
Dimensions
Piping
Operation range
Refrigerant R410A Note: Specifications are based on the following conditions: Cooling: Indoor temperature of 80°F (26.7°C) DB/67°F (19.4°C)WB, and outdoor temperature of 95°F(35°C) DB/75°F(23.9°C)WB. Heating: Indoor temperature of 70°F (21.1°C) DB/60°F (15.6°C)WB, and outdoor temperature of 47°F(8.3°C) DB/43°F(6.1°C)WB. Pipe Length: 25ft. (7.5m), Height difference: 0ft. (0m) (Outdoor unit - indoor unit). Voltage: 230[V].
Printed in the USA 12/2018
Static Pressure Range
Indoor
Outdoor
Connection Pipe Diameter Max pipe length Pre charge pipe length 49 (15) 65 (20) 98 (30) Max height difference 49 (15) 98 (30)
Cooling °F (°C)
Heating °F (°C) -5 to 75 (-20 to 24)
Min.-Max.
H×W×D in. (mm)
Weight lbs. (kg) 60 (27) 79 (36) 101 (46)
H×W×D in. (mm)
Weight lbs. (kg) 84 (38) 134 (61) 209 (95)
Liquid / Gas in. (mm)
in. W.G
ft. (m)
(Pa)
11-13/16×27­9/16×27-9/16
(300×700×700)
24-7/16×31­1/8×11-7/16
(620×790×290)
1/4 / 3/8 (6.35 /
14 to 115 (-10 to
Part # 6-26-FG2100
0.12 to 0.80 (30 to 200) 0.12 to 0.72 (30 to 180)
11-13/16×39-3/8×27-9/16 (300×1,000×700) 11-13/16×55-1/8×27-9/16 (300×1,400×700)
32-11/16×35-7/16×13(830×900×330) 50-13/16×35-7/16×13 (1,290×900×330)
9.52)
65 (20) 164 (50) 246 (75)
46)
1/4 / 1/2 (6.35 /
12.7)
3/8 / 5/8 (9.52 / 15.88)
-5 to 115 (-20 to 46)
FUJITSU GENERAL AMERICA, INC.
353 Route 46 West • Fairfield, NJ 07004
www.fujitsugeneral.com
Loading...