Fuji Electric PYX Operating Manual

Instruction Manual
FUZZY CONTROLLER X
Type: PYX
PV
SV
SEL
OUT1
OUT2
ALM1
ALM2
Contents
I. PREPARING THE OPERATION ............................... 4
1. THE BASIC INSTALLATION PROCEDURE .................... 5
2. CHECK OF SPECIFICATIONS ........................................ 6
2.1 PYX4 MODEL CONFIGURATION ........................... 6
2.2 PYX5/9 MODEL CONFIGURATION ........................ 7
3. ACCESSORIES................................................................ 8
4. INSTALLATION ................................................................ 8
4.1 INSTALLATION PLACE ........................................... 8
4.2 INSTALLATION PROCEDURE ................................ 9
4.3 CAUTION ON SAFETY ............................................ 10
4.4 PANEL CUT DIMENSIONS ..................................... 18
5. WIRING ............................................................................ 19
5.1 PYX4 WIRING DIAGRAM [When the output 1 is relay (SPST) output,
SSR drive output or current output].......................... 19
5.2 PYX4 WIRING DIAGRAM
[When the output 1 is relay (SPDT) output].............. 21
5.3 PYX5/9 WIRING DIAGRAM
(NOT UNIVERSAL OUTPUT) .................................. 23
5.4 PYX5/9 WIRING DIAGRAM
(UNIVERSAL OUTPUT) ........................................... 26
5.5 NOTES ..................................................................... 28
II. FRONT PANEL LAYOUT .......................................... 30
1
III. OPERATION PROCEDURE ...................................... 33
1. OPERATION MODE/PARAMETER SETTING MODE ..... 33
2. VIEWING PARAMETERS ................................................ 33
3. CHANGING PARAMETERS............................................. 35
IV.SETTING INPUT AND OUTPUT TYPES .................. 37
Changing input ............................................................................. 37
Changing scale (voltage/current input) ......................................... 41
Changing output (universal output) .............................................. 42
V. FUNCTIONS .............................................................. 44
Lock .............................................................................................. 44
Auto-tuning ................................................................................... 47
Control function ............................................................................ 51
Alarm ............................................................................................ 55
Ramp soak ................................................................................... 60
Two set-points .............................................................................. 64
Analog output (AO) ....................................................................... 65
Digital output................................................................................. 67
Manual operation .......................................................................... 69
Remote SV ................................................................................... 71
Output monitoring ......................................................................... 72
VI.SET-UP PARAMETER .............................................. 73
Input filter ...................................................................................... 73
PV shift ......................................................................................... 74
Control type .................................................................................. 75
Output setting in input abnormal................................................... 76
Output limits.................................................................................. 77
Set point value limits..................................................................... 78
Output cycle time .......................................................................... 79
Direct/reverse control action......................................................... 81
2
Control processing cycle time....................................................... 82
APPENDIX...................................................................... 83
1. ERROR MESSAGES........................................................ 83
2. POWER FAILURE ............................................................ 83
3. SPECIFICATIONS............................................................ 84
4. TROUBLESHOOTING...................................................... 89
5. PARAMETER LIST........................................................... 91
3

I. PREPARING THE OPERATION

We thank you for the purchase of this PYX (Fuzzy Temperature Controller). Employing FUZZY LOGIC the PYX virtually eliminates system overshoot and effectively suppresses fluctuation of the process variable due to external disturbances. Please read this manual, when programed and operated within the guidelines setforth in this manual, your PYX controller will give you years of precise, reliable control.
PYX
The product conforms to the requirements of the Electromag­netic compatibility Directive 89/336/EEC as detailed within the technical construction file number TN510401. The applicable standards used to demonstrate compliance are :
EN50081-1 : 1992 Conducted and Radiated emissions EN50082-1 : 1992 Radiated immunity, ESD and FBT (The unit meets Class A limits for Conducted Emissions.)
The unit also complies with the part of Immunity standards.
IEC1000-4-2 : 1995 level 3, IEC1000-4-3 : 1995 level 3 IEC1000-4-4 : 1995 level 3, IEC1000-4-8 : 1993 level 4
* E.U. indicates Engineering Units.
4

1. THE BASIC INSTALLATION PROCEDURE

Is given here as to the basic flow from the installation to operate the PYX. For detailed description of each step, see the pages correspondent. See the section “Operation Procedure” on the pages 33 to 36 for calls and changes the specific parameter.
Installation of
Main Unit
Connection
Selecting Input
and Output Types
Selecting PID
or Fuzzy
Install the main unit on the panel, using the attached panel mounting bracket. (See page 8 to 18 for details.)
Connect the unit to power supply and input and output devices. (See page 19 to 29 for details)
Power up, then select and check input types (such as types of sensors), input temperature range, decimal point used or not used and so on. In case of the universal output type, set and check the output switch pins inside the main unit. (See page 37 to 43 for details.)
Either the conventional PID control mode or the fuzzy control mode, which is effective in minimizing overshoot rate and outer condition effects, can be selected. Select by setting the parameter , where the default set is PID. (See page 75 for details.)
Tuning
Ready
Normal
Operation
System power up then, execute auto-tuning to define the control parameters. (See page 47 to 50 for details.)
Basic preparations are completed. Carry on settings for the optional functions (alarm, two set points, transmission, ramp soak, analog output etc.), following this instruction.
See page 44, as setting values (SV) can be set in the same manner as the Lock parameter on page 44.
5

2. CHECK OF SPECIFICATIONS

Please make sure that specifications of this product is according with your request. The product specifications are provided on the main unit as model configuration following.

2.1 PYX4 MODEL CONFIGURATION

12345678 910111213 PYX
4 1-
T A
M
Y A B C D E F G H
Y A B C D
0 1 2 3 4
*
Note 1: Fuji Electric CC data line protocol Note 2: Modbus RTU protocol
R
Contents
Input type TC/PT input Voltage/Current input TC/PT/Voltage/Current multi input
Control output1 Without Relay (SPST) rev. act. Relay (SPST) dir. act. SSR drive rev. act. SSR drive dir. act. Current (DC 4~20mA) rev. act. Current (DC 4~20mA) dir. act. Relay (SPDT) rev. act. Relay (SPDT) dir. act.
Control output2 Without Relay (SPST) rev. act. Relay (SPST) dir. act. SSR drive rev. act. SSR dirve dir. act.
Alarm function Without 1pt. 2pts. HB alarm HB alarm + 1pt.
Input type code See Page 21.
Input range code
*
Y P Q R S M N A B C
J E F K
See Page 21. Additional function
Without 2 set points 4 ramp soak with start/reset RS-485 transmission RS-485 transmission RS-485 transmission RS-485 transmission + 4 ramp soak Auxiliary analog output Auxiliary analog output + 4 ramp soak Remote SV Front panel Japanese English (
°
C)
English (
°
F)
English (%)
+ 4 ramp soak
Note 1 Note 2
6

2.2 PYX5/9 MODEL CONFIGURATION

12345678 910111213 PYX
5 9
M
1-
Front panel dimensions: 48×96 mm 96×96 mm
Input type
T A
Y C D E F G H J K
Y C D E F G H
0 1 2 3 4
TC/Pt input Voltage/Current input TC/Pt/Voltage/Current multi-input
Control output 1 Without SSR/SSC drive rev. act. SSR/SSC drive dir. act. Current (DC4-20mA) rev. act. Current (DC4-20mA) dir. act. Relay rev. act. (SPDT) Relay dir. act. (SPDT) Universal output rev. act. Universal output dir. act.
Control output 2 Without SSR drive rev. act. SSR drive dir. act. Current (DC4-20mA) rev. act. Current (DC4-20mA) dir. act. Relay rev. act. (SPDT) Relay rev. dir. (SPDT)
Alarm function Without 1pt. 2pts. HB alarm HB alarm + 1pt.
Contents
*
*
Y P Q R S
Note 1: Fuji Electric CC data line protocol Note 2: Modbus RTU protocol
R
M N A B C
7
Input type code See Page 21.
Input range code See Page 21.
Additional functions Without 2 set points 4 ramp soak with start/reset RS-485 transmission RS-485 transmission + 4 ramp soak RS-485 transmission RS-485 transmission + 4 ramp soak Auxiliary analog output Auxiliary analog output + 4 ramp soak Remote SV
Front panel
J E F K
Japanese English ( English (°F) English (%)
°
C)
Note 1 Note 2

3. ACCESSORIES

In addition to the main unit, the following accessories are shipping in the same package.
Accessories Quat.
Instruction manual (this manual) (INP-TN1PYX-E)
Panel mounting bracket set
Current input resistance (250)
* Not delivered for TC/PT input type
* Suffix means revision control

4. INSTALLATION

4.1 INSTALLATION PLACE

Please verify if where the controller is mounted there is no: (1) splash of water, (2) mechanical vibration,
1
1
1
(3) extreme temperature (4) no corrosive gases, (5) dust or oil smoke, (6) electric noise.
8

4.2 INSTALLATION PROCEDURE

;
Panel mounting bracket (accessorie)
Panel
Panel
Clamping screw Main unit
Panel mounting bracket (accessorie)
Clamping screw
For PYX4
For PYX5/9
For PYX4 Slide the enclosed plastic panel mounting bracket (shipped with every PYX4) up the back of the controller until it makes contact with the back of the panel. Push the mounting bracket until the tabs seat themselves in the molded tab ridges, located on the front of the controllers outer case. Tighten the two screw on the mounting bracket for added pressure; do not use excessive force.
For PYX5/9 The mounting brackets tabs fit into the two holes on both the top and bottom of the controllers outer case. With an instrument screwdriver, turn the screw in the mounting bracket until the end of it touches the back of the panel. Do this to both brackets. Making sure that the face of the controller is flush and straight, tighten both mounting bracket screws. Your controller should now be firmly set. If the controller is still loose, tighten the mounting bracket screw a little more. Do not use excessive force.
9

4.3 CAUTION ON SAFETY

First of all, read this "Caution on Safety" carefully,
and then use the instrument in the correct way.
The cautionary descriptions listed here contain important information about safety, so they should always be observed. Those safety precautions are classified in 2 ranks, WARNING and CAUTION.
The following shows the meaning of WARNING and CAUTION.
Wrong handling may cause a dangerous situation,
WARNING
CAUTION
1. WARNING
1.1 Caution on wiring
1) For the safe operation of the controller, where the temperature probe is to be installed into an environment where voltage exceed 50VDC, it is essen­tial that reinforced isolation or basic isolation and earth the maintained be­tween all connections to the rear of the temperature controller, and that supplementary isolation is required for the alarm outputs.
in which there is a possibility of death or heavy injury.
Wrong handling may cause a dangerous situation, in which there is a possibility of injury or physical damage.
The outputs from the controller are all less than 50VDC. When wiring the power supply terminal, use vinyl insulated 600 volt cable
or equivalent. A switch breaking both poles of the mains supply should be installed together with a fuse with a rating of 250 volt 1 Amp. The fuse should be installed between the mains switch and the controller.
The level of insulation provided by the temperature controller is:-
MAIN = BASIC HEATER = BASIC INPUTS = BASIC
10
Prior to operation of the installed system the wiring should be checked to ensure that the required levels of insulation have been provided.
2) When a fault in the instrument is likely to lead to a serious trouble, use a suitable protective circuit on the outside for protection against trouble.
3) This unit is not provided with power switch, fuse, etc. These parts can be installed separately, if required (fuse rating; 250V, 1A).
4) Use of Fuji's Z-Trap is recommended to protect the relay output from switch­ing surge and to ensure a long life.
Type: ENC241D - 05A (power voltage; 100V)
ENC471D - 05A (power voltage; 200V)
Mounting position: Connected to relay control output terminals
ex) PYZ4 Socket (ATX2PSB)
65 43
1.2 Operating condition
Operating temperature : -10 to 50°C Operating humidity : 90%RH or less (non condensing) Installation category : Pollution degree : 2
PYZ9
5
6
7
8
9
1.3 Power source
1) Use a power source of rated voltage to prevent damage or trouble.
2) Do not turn ON the power until the wiring is completed to prevent shock hazard or trouble.
11
1.4 Prohibition of use in gas
The instrument is not an intrinsic safety explosion - proof type. Do not use it in a place exposed to combustible or explosive gas.
1.5 Contact to unit
1) This unit must not be disassembled, modified or repaired to prevent mal­function, shock hazard or fire accident.
2) When the power is ON, do not touch the terminals to prevent shock hazard or malfunction.
1.6 Caution on maintenance
1) Before mounting or removing the module or unit, turn OFF the power in advance to prevent shock hazard, malfunction or trouble.
2) Periodical maintenance is recommended to ensure continuous and safe operation of the instrument. Some parts of the instrument are limited in life or are subject to secular change.
WARNING
It is essential that, when the controller is introduced into a system which uses or generates a hazardous voltage, the minimum creepage and clearances specified in the table below are maintained on the temperature probe. A hazardous voltage is one that exceeds 42.4V peak AC or 60V DC. If you have any doubt, seek advice from a
competent engineer before installing the controller into the host equipment.
The equipment must be installed such that with the exception of the connection to the mains, creepage and clearance distances shown in the table below are maintained between the temperature probe and any other assemblies which use or generate a voltage shown in the
12
table below. Failure to maintain these minimum distances would
Clearance (mm) Creepage (mm) Voltage used or generated
by the other assemblies
0.2 1.2 Up to 50V
rms or V DC
0.2 1.4 Up to 100Vrms or V DC
0.5 1.6 Up to 150Vrms or V DC
1.5 3.0 Up to 300Vrms or V DC Above 300Vrms or V DC
For a host or other assemblies fitted in the system, using or
generating voltages greater than 300V(rms or DC),advice from
a competent engineer must be obtained before installation of
the relevant equipment.
invalidate the EN61010 safety approval.
It is essential that following the installation of the system, and prior to powering the system up that it is tested to determine that the correct level of isolation is present to protect the user and other equipment against the hazards of electric shock and fire.
An explanation of creepage and clearance is given in the following diagram.
13
EXAMPLE INSTALLATION DIAGRAM
TO MAINTAIN SAFETY OF CONTROLLER
Example of how to install Controller into an environment where hazardous voltages may exist is shown below.
Make sure installed system has basic insulation around
Thermocouple, RTD, Voltage or Current
Make sure installed system has basic insulation
Heater Break Circuit
this connection
24V mains supply
Controller
Example Diagram To Explain The Meaning Of Creepage and Clearance Distances Is Shown Below
Communication card
X
X
Y
Y
Expansion card
Except for the edge connector which plugs into the host's expansion slot, clearance distance (X mm) and creepage distance (Y mm) as given in the table above, must be maintained between the controller and any other assemblies which use or generate a hazardous voltage.
14
2.
CAUTION
2.1 Caution on handling
1) Do not install the unit in any of the following places.
A place where the ambient temperature exceeds the range of -10 50°C
A place where the ambient humidity exceeds 90%RH
A place where temperature changes suddenly or dew condensation
occurs
A place exposed to corrosive gases (sulfuric gas, ammonia, etc.) or combustible gases
A place where vibration or shock is likely to be directly transmitted to the body.
A place exposed to water, oil, chemicals, vapor, steam, etc.
A place with much dust, salt or iron component
A place with much inductive disturbance, static electricity, magnetism
or noise
A place exposed to direct sunlight
A place where heat such as radiant heat stays
2) Mounting
PYX5/9 For mounting, attach the supplied mounting brackets (2 units) on top
and bottom and tighten with a screwdriver. Tightening torque is about 147N.cm (1.5kg.cm). (The case is made of plastic. Care should be taken not to tighten forcedly)
15
PYX4 Insert the supplied mounting frame from the rear side and push it in
until the main unit is secured firmly to the panel. If it has a slight play, tighten the 2 screws until the play is eliminated. (If the screws are tight­ened forcedly, the mounting frame may be slipped off the stopper)
3) When the unit is exposed to water, it may lead to a short-circuit or fire hazard. Contact your dealer for inspection.
2.2 Caution on cable connection
1) For thermocouple input, use a suitable compensating cable.
2) For resistance bulb input, use a cable with a small lead wire resistance and without resistance difference between 3 wires.
3) When external wiring has much noise, use the following step. When a conducted as load of digital output such as relay contact output or alarm output, connect a surge absorber to the conductor coil. (Example: ENC471D-05A for 200V AC)
4) When the power source has much noise, use an insulating transformer together with a noise filter. Noise filter should be mounted on a panel which has been earthed. The wiring between the noise filter output and the instru­ment power terminals should be as short as possible. Do not connect a fuse or switch to the noise filter output wiring, as it affects the performance of the filter.
5) Use of a twisted cable for the instrument power source provides better ef­fects (short twist pitch is effective for noise).
6) When a heater burnout alarm is provided, the heater power and controller power should be connected using the same power line.
7) Time for preparation of contact output is required at power ON. When the output signal is used for an external interlock circuit, etc., connect a delay relay to the circuit.
16
2.3 Other
When cleaning the instrument, do not use organic solvents such as alcohol, benzine, etc. Use neutral detergent.
3. Caution on key operation / trouble
(1) Alarm function should be set correctly. Otherwise, alarm output
cannot be obtained at the time of occurrence of trouble. Be sure to check the function prior to operation.
(2) Do not stop the device forcedly during auto - tuning, as it affects the
control action. When it needs to stop forcedly, be sure to turn OFF the power in advance.
(3) If the input cable is disconnected, the display shows UUUU or LLLL.
When replacing the sensor, be sure to turn OFF the power.
17

4.4 PANEL CUT DIMENSIONS

65 or more
100 or more
65 or more
45
+0.5
-0
+0.5
45
-0
For PYX4
92
+0.8
-0
+0.8
92
-0
For PYX9
When mounting one unit When mounting multiple n units (2
45
+0.8
-0
+0.8
a
-0
n ≤ 6)
115
or more
92
+0.8
-0
+0.8
92
-0
For PYX5
18
Unitsa2
933141418952376285
Units (mm)

5. WIRING

5.1 PYX4 WIRING DIAGRAM

[When the output 1 is relay (SPST) output, SSR drive output or current output]
Option
11 12
6
7
8
9
10
Control output 1
+
+
AC100-240V 50/60H
z
Alarm
1
2
3
4
5
Input
TC input Pt input Voltage input
N.C. N.C. N.C.
8
9
10
8
+
9
10
Pt
8
9
10
+
Pt
Input
Current input
8
9
250
10
+
NOTE: For current input (4-20mA), use the accessorie
resistance (250
).
Make sure that the setting pin is in the appropriate position according to page 40.
19
Control output 1
For relay output For SSR drive output For current output
Alarm
ALM2
ALM1
ALM-COM
Option
6
++
7
1
2
6
DC-V DC 4-20mA
7
6
7
NOTE: Only ALM 1 is available in the case of
3
the digital output type.
For control output 2
(relay output)
11
For current transformer input For RS485 transmission
11 12
12 11 12
For control output 2
(SSR drive output)
+
TRX– TRX+
11 12
For digital input
11 12
For remote SV input
+
11 12
For AO output
11 12
+
20

5.2 PYX4 WIRING DIAGRAM

[When the output 1 is relay (SPDT) output]
Option
11 12
Control output 1
AC100-240V 50/60H
z
1
2
Alarm
3
4
5
6
7
8
9
10
Control output 1
+
+
Input
TC input Pt input Voltage input
N.C. N.C. N.C.
8
9
10
8
+
9
10
Pt
10
8
9
+
Pt
Current input
8
9
250
10
Input
+
NOTE: For current input (4-20mA), use the accessorie
resistance (250
).
Make sure that the setting pin is in the appropriate position according to page 40.
21
Control output 1 Alarm
N.C. N.O.
1
2
Option
11 12
For control output 2
6
7
(relay output)
11
For digital input
12 11 12
1
ALM
ALM-COM
For control output 2
(SSR drive output)
For AO output
2
3
+
11 12
For current transformer input For RS485 transmission
TRX– TRX+
11 12
11 12
11 12
+
For remote SV input
+
11 12
22

5.3 PYX5/9 WIRING DIAGRAM

(Not universal output)
Control output 1
AC100~240V 50/60H
z
Output
Alarm
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
Option
Control output 2
Pt
+
+
Input
For TC input For Pt input For voltage input For current input
15
N.C. N.C. N.C.
+
16
18
15
16
18
Pt
15
16
18
15
16
+
250
18
NOTE: For current input (4-20mA), use the accessorie
resistance (250
).
In the case of multi-input, make sure that the setting pin is in the appropriate position according to page
40.
+
23
Control output 1
For relay output For SSR drive output For current output
N.O.
1
N.C.
2
1
++
DC-V DC 4-20mA
2
1
2
3
3
Control output 2
For relay output For SSR drive output For current output
N.O.
N.C.
12
+
13
14
12
+
13
DC-V DC 4-20mA
14
Alarm
3
12
13
14
ALM1
ALM2
ALM-COM
5
6
7
24
Option
For digital input
10
11
For AO output
+
For current transformer input For RS485 transmission
10 10
TRX+
10
11
For remote SV input
+
10
11
11
TRX–
11
25

5.4 PYX5/9 WIRING DIAGRAM

(universal output)
Control output 1
AC100~240V 50/60H
z
Input
Alarm
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
Option
Control output 1
Pt
+
+
Input
For TC input For Pt input For voltage input For current input
15
N.C. N.C. N.C.
+
16
18
15
16
18
Pt
15
16
18
15
16
+
250
18
NOTE: For current input (4-20mA), use the accessorie
resistance (250
).
In the case of multi-input, make sure that the setting
pin is in the appropriate position according to page
40.
+
26
Control output 1
For relay output For SSR drive output For current output
1
2
3
Alarm
Option
N.O.
N.C.
ALM1
ALM2
ALM-COM
12
+
13
DC-V DC 4-20mA
14
5
6
7
12
13
+
14
For digital input
10
11
For AO output
+
For current transformer input For RS485 transmission
10 10
11
11
TRX+
TRX–
10
11
For remote SV input
+
10
11
27

5.5 NOTES

Connection:
No power switch and fuse are provided on this product. Install them separately if necessary.
Use designated compensating wire in the case of thermo­couple input.
Use wire with line resistance lower that 10 thermoresistance input.
To avoid noise induction to input wires separate from the power and output wires also connected to your controller.
In case of model equipped with heater break alarms, the power supply used should be the same for the PYX and Heater.
for
Use shielded wires for input wires. Keep them away from output wires.
Noise: Take the following measures when there is serious noise induction in the external wiring:
When using a contactor as a load on digital output such as relay contact output and alarm output, supplement a serge absorber to the coil side of the contactor.
Z-Trap (ENB461D-14A for AC220V) manufactured by Fuji Electric
In the case of noise induction from the power supply, the use of an insulated transformer and a noise filter is recommended.
Noise Filter (ZMB22R5-11) manufactured by TDK
It is efficacious against noise induction to twist the power wires.
28
Connection of Load Circuit:
When the frequency of operation is rather high, in the case of proportional operation for instance, maximum load with respect to the capacity of the output relay will result in shorter life. Use an auxiliary relay in such a case. Type SSR is recommended.
electromagnetic switch: proportion cycle 20 sec. and above SSR: proportion cycle 2 sec. and above
(approximately)
contact output life: mechanical: 10 million times (no load)
electrical: 100 thousand times (nominal
load)
Relay contacts will be worn out with time. After certain period has passed, locking (a phenomenon in which a contact cannot be released once switched on) may happen. It is advisable to provide an external safety device to protect the system just in case locking happens.
29

II. FRONT PANEL LAYOUT

PV value display
Set point value display
PV
SV
SEL
OUT1
OUT2
ALM 1
ALM 2
Control output 1 monitor lamp
Control output 2 or remote operation monitor lamp
Alarm 1 lamp
Alarm 2 lamp
SELECT/Registration
DOWN key
UP key
➁ ➆
➆➇➈➉
CARRIAGE/Registration
PYX4
OUT1
OUT2 ALM 1 ALM 2 OUT1 OUT2 ALM 1 ALM 2
PV
SV
SEL
➈ ➇
PYX-5
➂➃➄➅
PV
SV
SEL
➆➇➈➉
PYX-9
PYX5
PYX9
30
PV value display PV Displays the measured value, as well as
the failure information. When more than one failure occurs simultaneously, the failure information of the highest priority alone will be displayed.
Set point value display
Display Priority
Main unit failure
Heater disconnected
Control loop failure
Meaning
High
Low
SV Displays the set point value.
(During auto-tuning or manual operation, the display of
or
and set point value alternate.)
Control output-1 monitor lamp Output 1(OUT1) Lights when Output 1 is ON. (it does not
Control output 2 or remote operation monitor lamp
light for the current output type.)
This lamp lights when Output 2 is ON or during remote operation. (it does not
light for the single output type.) Dual Control type Output 2(OUT2) Acts as the control output 2 monitor lamp.
Remote SV type REM Acts as the remote operation monitor lamp.
31
Alarm-1 monitor lamp ALM 1 Lights when the alarm-1 relay operates
Alarm 2 monitor lamp ALM 2 Lights when the alarm-2 relay operates
SELECT/Registration
Used to switch from the operation mode
SEL
to parameter setting mode, to select parameters, and to Registration set values.
Keeping pressing this key for about 3
DOWN key
UP key
sec switches between the operation mode and parameter setting mode.
Used to select parameters and to
decrease set values.
Continuing to press this key results in
auto-repeat.
Used to select parameters and to
increase set values.
Continuing to press this key results in
auto-repeat.
CARRIAGE/Registration
Used for preset value digit carrying or for
preset value Registration.
32

III. OPERATION PROCEDURE

1. OPERATION MODE/PARAMETER SETTING MODE

The operation of this device includes the Operation Mode where measured and set values are displayed and the Parameter Setting Mode where various parameters are set.
To switch between the operation and parameter setting modes,
SEL
continue to press the
key for about 3 sec.
Continue to press
Operation Mode Parameter Setting Mode
Displays measured and set point. Displays information on loop* break, heater break error, auto-tuning, and manual operation. Changes set point.
*
, main-unit
SEL
key for about 3 sec
Make no operation for 1 min
Displays and changes various parameters.
*
indicates an option.

2. VIEWING PARAMETERS

1. Enter the parameter setting mode. (continue to press
SEL
key for
about 3 sec)
SEL
2. Display the target parameter with the
, , or key.
NOTES: No parameter is displayed if its parameter lock setting is
illegal or if its corresponding option has been mounted in the system.
33
PV
SV
PV
* The numeric value shown in the
left-hand figure is only an example.
Continue to
press
SEL
key for about
3 sec
SEL
Parameter Setting Mode Operation Mode
SEL
SV
parameter
or
PV
SV
parameter
or
SEL
or
PV
SV
parameter
*Not displayed unless the transmission option is provided.
34

3. CHANGING PARAMETERS

1. Display the parameter to be set (to be changed) on the screen, as described in the Section 2. Viewing Parameter (page 33).
2. Select the digit to be set (to be changed ), with the
key (the
selected digit flickers).
3. Set (to be changed ) the data with the
SEL
4. Press the
key, or repeat pressing the key until it stops
and keys.
flickering (the set (changed) data is registered).
NOTES: If no operation is made for about one minute during data
setting (changing), control automatically returns to the operation mode. The data being changed (set) at this time is invalidated.
35
Example
<<Changing Lock from 1 to 2>>
PV
SV
Display the target
➀➁➂
Press
parameter.
PV
SV
The leftmost digit flickers, and data of that digit is changeable.
PV
SV
The center right digit
➃➄
flickers, and data of that digit is changeable.
PV
SV
The center left digit flickers, and data of that digit is changeable.
PV
SV
The rightmost digit flickers, and data of that digit is changeable.
PV
SV
Increment data by 1 to 2. Flickering stops, and is the
➅➆
SEL
or
PV
SV
registered.
36

IV. SETTING INPUT AND OUTPUT TYPES

After completing wiring, make sure that the measured value is of the right type before operating the device.
Parameter to be used

Changing input

Setting the Input type ( ) It refers to setting the input type (range), presence or absence of decimal-
°C/°
point, and units of display ( Setting procedure
F).
PV
SV
PV
SV
1. Turn the power of PYX (LEDs go on after a few sec).
SEL
2. Continue to press the key for about 3 sec (parameter is displayed).
At that time, if is displayed steps 3 and 4 need not be executed.
3. Press the key 4 times (the right most digit flickers).
37
PV
SV
PV
SV
PV
4. Change the lower display to with the
and keys, and stop flickering and
register the value with the and keys.
SEL
5. Repeat pressing the key until parameter is displayed.
SV
6. Set parameter to the desired specifications following.
Example: Setting of K thermocouple for 0.0-400.0 °C range
Display unit
0
°
C display
1
°
F display
Decimal-point display
0
No decimal point
0.1
1
°C/°
F display
Input type code
38
Input signal and measurement range
Input signal
Thermo­resistance JIS
Thermo­resistance old JIS
Thermo­couple
Pt100 Pt100 Pt100 Pt100 Pt100 Pt100 Pt100 Pt100
JPt100 JPt100 JPt100 JPt100 JPt100 JPt100 JPt100
J J K K K R B T T E E S N U WRe5-26 PL-II
Input type
code
00 01 02 03 04 05 06 07
10 11 12 13 14 15 16
20 21 22 23 24 25 26 27 28
29 2A 2B
2C 2D
2E 2F
Measurement
range (°C)
0~150°C 0~300°C 0~500°C 0~600°C
50~100°C
100~200°C150~600°C –150~850°C
0~150°C 0~300°C 0~500°C 0~600°C
50~100°C
100~200°C150~600°C
0~400°C 0~800°C 0~400°C
0~800°C 0~1200°C 0~1600°C 0~1800°C
199.9~200°C
150~400°C
0~800°C
–199.9~800°C
0~1600°C 0~1300°C
–199.9~400°C
0~2300°C 0~1300°C
Measurement
°
range (
238~1112°F
238~1562°F
238~1112°F
– –
328~1472°F
F)
32~302°F 32~572°F 32~932°F
32~1112°F
58~212°F
148~392°F
32~302°F 32~572°F 32~932°F
32~1112°F
58~212°F
148~392°F
32~752°F
32~1472°F
32~752°F 32~1472°F 32~2192°F 32~2912°F 32~3272°F 328~392°F 238~752°F 32~1472°F
32~2912°F 32~2372°F 328~752°F 32~4172°F 32~2372°F
0.1°C
display
Ο Ο Ο Ο Ο Ο Ο Ο
Ο Ο Ο Ο Ο Ο Ο
Ο Ο Ο Ο
× ×
× Ο Ο Ο Ο
×
× Ο
×
×
0.1°F
display
Ο Ο Ο
× Ο Ο
×
× Ο
Ο Ο
× Ο Ο
× Ο
× Ο
×
×
×
×
×
×
×
×
×
×
×
×
×
Power supply voltage
Power supply current
NOTES:
DC1-5V DC0-5V
40 41
–1999
(Possible scaling range)
to
9999
Ο: Enabled ×: Disabled
DC4-20mA
40*
* For current input, mount the
250 resistance on input
terminals, and apply the 1-5V
voltage input.
The 0.1°C/F display is impossible for all over the 1000°C/F span.
39
NOTES: Make sure to switch the input selection SW referencing the
following table when changing the type of input by changing the parameter
Switching from Pt or TC input
to voltage/current input Switching from voltage/current
input to Pt/TC input Other types of switching
Input selection SW
Lower
.
Re-position the input switch pin on "V" side.
Re-position the input switch pin on Pt/TC side.
Input pin re-positioning is not necessary.
V
J4
Input select SW
TC. Pt
ALM2 ALM1 OUT2 OUT1
Upper
Input selection SW
Lower
PYX-5
SEL
SV
PV
OUT1
OUT2 ALM1 ALM2
SEL
SV
PV
PYX4
Input selection SW
Lower
PYX-9
SEL
SV
PV
OUT1 OUT2 ALM1 ALM2
PYX5 PYX9
Upper
Upper
40
Parameter to be used

Changing scale (voltage/current input)

If it is used for voltage or current input, input scaling is possible. Input scaling
Engineering dimensions can be set to voltage or current input. Setting procedure
maximum value on scale
(
): Engineering value
equivalent to the 100% input is set (-1999 ~ 9999).
minimum value on scale
(
): Engineering value
equivalent to the 0% input is set (­1999 ~ 9999).
(decimal-point location):Decimal point location is set (see
below). (0 ~ 2)
(No decimal point)
0
1
2
NOTES: When setting the scale, set it so that the difference between
and (span) does not exceed 9999. The following condition must always be satisfied when setting is made:
is larger than .
41
Parameter to be used

Changing output (universal output) none

In case of the universal output type, the type of the control output 1 can be selected from the relay (SPDT) output, the SSR drive output and the current (4-20mA) output. Follow the table below when switching.
Desire type of control output 1 Switching
Relay (SPDT) output
SSR drive output
Current (4-20mA) output
Output selection SW
Upper
OUT1
OUT2 ALM1 ALM2
PV
SV
SEL
PYX-5
PYX5
Switch the pin J2 in the figure below to the RY position.
Switch the pin J2 in the figure below to the SSR position.
No swtching required.
Output selection SW
SSR
J2
RY
Lower
Output selection SW
Upper
OUT1 OUT2 ALM1 ALM2
PV
SV
SEL
PYX-9
Lower
PYX9
42
NOTES:
1. The output terminal for each output type is independent in the case of the universal output. Make sure that connections are properly made according to the page 27.
2. The current (4-20mA) output is made regardless of the position of the switching pin J2 in the case of the universal output. However, only one type of output can be concurrently used among the relay output, the SSR drive output and the current output.
43

V. FUNCTIONS

Parameter to be used

Lock

The lock function is to suppress display of those parameters which are not used frequently in normal operations, and thereby to prevent parameter miss-settings.
There are four lock levels: 0 to 3. Parameters corresponding to each lock level are displayed. Setting the lock level to 0 disables changing of all
parameters other than
.
<Parameters for each lock level>
PV
SV
Lock level
0
Lock level
1
Operation screen
Lock level
2
Lock level
3
44
45
NOTE: Some parameters may not be displayed, depending
upon the option composition.
Lock level Use
0
1
2
3
(Setting of no parameter allowed) Use this level to lock all parameters.
(Setting of only set point allowed) Use this level when no parameter other than the set point is changed.
(Setting of normally set parameters allowed) Use this when normal parameters are set or changed.
(Setting of all parameters allowed) Use this when the set-up parameters are set or changed.
46
Parameter to be used

Auto-tuning

Autotuning function
This is the function implemented by the controller itself to automatically perform ON/OFF control, identify the process, and determine control constants (P, I, D, Cool, Ar).
Operating procedure
(Autotuning Command)
Setting Operation
Provides normal control.
Perform auto-tuning while
(Standard
type)
targeting the present [set point value (SV)].
(Autotuning command) Setting
or in the autotuning command starts autotuning (during autotuning, value alternate in display on the run
Performs auto-tuning while
(Low PV
type)
targeting the present [set point value (SV) - 10%FS].
screen). Autotuning terminates automatically.
Supplementary descriptions
1. There are two types of auto-tuning (AT):
over-shoot) and
Type
is the system in which the measured value (PV) exceeds
Low PV type (suppressing overshoot).
and the set
Standard type (including
the set point value (SV) (overshoot) during autotuning. Use this type where overshoot is permitted.
Type
is the system in which ON-OFF control is provided by centering upon the value 10% (/full-scale) lower than the set point value (SV). Use this type where overshoot is to be suppressed.
47
For single output
Standard type (including overshoot)
AT started AT terminated
AT arithmetic being made
Set point value (SV)
PV (Measured value)
(PID determined)
ON 100%
ON ON
OFF 0%
(Control output)
Low PV type (suppressing overshoot)
AT started AT terminated
Set point value (SV)
OFF OFF
ON-OFF operation
(PID determined)
AT arithmetic being made
During AT, the ON-OFF operation (2-point operation) is provided where the measured value (PV) vibrates.
PID control
SV-10%FS
ON 100%
OFF 0%
(Control output)
PV (Measured value)
ON ON
OFF OFF
ON-OFF operation
48
During AT, the ON-OFF operation (2-point operation) is provided where the measured value (PV) vibrates.
PID control
For dual output
Standard type (including overshoot)
AT started AT terminated
AT arithmetic being made
Set point value
(SV)
PV (Measured value)
(Control output 1)
(Control output 2)
ON 100%
OFF 0%
ON 100%
ON ON
OFF OFF
OFF OFF
ON ON
(PID determined)
During AT, the ON-OFF operation (2-point operation) is provided where the measured value (PV) vibrates.
PID control
Low PV type (suppressing overshoot)
AT started AT terminated
AT arithmetic being made
Set point value
(SV)
PV (Measured value)
(Control output 1)
(Control output 2)
ON 100%
OFF 0%
ON 100%
ON ON
OFF OFF
OFF OFF
ON ON
(PID determined)
SV-10%FS
During AT, the ON-OFF operation (2-point operation) is provided where the measured value (PV) vibrates.
PID control
49
NOTES
1. Avoid applying the auto-tuning to the following processes. (a) The process must not be disturbed due to temporary ON-OFF
control output from PYX.
(b) Process featuring very quick response such as pressure/flow
rate process.
(c) Process where overshoot must not be generated
2. Auto-tuning cannot be executed under the following conditions. If the auto-tuning is already being executed, stop it.
(a) Manual operation (b) Measured value (PV) error occurring (c) When the set value (SV) has changed by more than 0.5%FS
per 0.5 second during auto-turning
(d) Auto-tuning not terminated within 12 hours
3. Do not execute auto-tuning when the ramp soak function is being used (i.e. when the parameter
is not ), since it
may result in incorrect tuning.
4. When the operation condition is changed, restart the auto-tuning
5. When the auto-tuning terminates abnormally, the PID value takes the value prior to auto-tuning, in such cases as abnormal termination of auto-tuning. The same applies when the auto-tuning command is switched to
50
during auto-tuning.

Control function

Normal PID control
1. (Proportional band) Set the proportional band using the
Parameter to be used
ratio (%) with respect to the input full scale (0.0-999.9%).
Setting
to 0.0 provides the 2­point (ON-OFF) control. The 2-point control is not available in the fuzzy control mode. This parameter is automatically set with auto-tuning.
(Integral time) Set the integral time in sec units (0-
3200 sec).
Setting
to 0 provides no integral operation.This parameter is automatically set with auto-tuning.
(Derivative time) Set the derivative time in 0.1-sec
units (0.0-999.9 sec).
Setting
to 0.0 provides no derivative operation. This parameter is automatically set with auto-tuning.
51
(Anti-reset wind up) When control operation involves
integral operation, the initial over­integral causes overshoot to occur. Overshoot is prevented by limiting the integral range. Set setting value (SV) high and low limits with engineering units. (0~100%FS E.U.)
This parameter is automatically set
by executing auto-tuning.
PV
AR
SV
AR
Integral value truncated
Integral value truncated
(Manual resetting value) When control includes only the P
operation, it generates offset. To eliminate this, add the manual resetting value to the manipulated value (MV). (-100.0~100.0%)
SV
PV
PID arithmetic
52
MV
+
+
Manual resetting
Manipulated value (MV)
2. 2-POINT (ON-OFF) CONTROL When PID control is specified as the control type, setting P to 0.0
provides the 2-point (ON-OFF) control operation.
(2-point operation hysteresis)
Set the 2-point operation hysteresis
with engineering values. (0~100% FS D.E.U.)
HYS
Output ON
Output OFF
Set point
PV
3. FUZZY CONTROL Employing Fuzzy Logic control eliminates system overshoot and
effectively suppresses fluction of the process variable due to external disturbances. See the section describing control type setting (page75).
NOTES
1. The dual output type does not allow use of fuzzy control.
2. Though the fuzzy control also requires setting of parameters P, I,
and D, these values can be set to those being used in PID control. Auto tuning is also available.
4. DUAL CONTROL * This function is an option. If the process heats itself, cooling control is needed in addition to
heating control. The dual control is used for control of that process.
53
(Cooling-side proportional band coefficient )
Set the cooling-side proportion
band coefficient (0.1~10.0). This parameter is automatically set with auto-tuning.
= 50%
Heating side
Output
Cooling side
COOL=0.5
COOL=1.0
COOL=2.0
Offset (–) Offset (+)
Set point value (SV)
Heating-side
proportion band
Proportion band (P)
Cooling-side
proportion band
(Dead/overlap band) Used to separate (dead) and
overlap the heating and cooling side output as shown in the figure below (-50 ~ +50%)
Output
Heating side
Cooling side
Offset (–) Offset (+)
Overlap
band
Set point value
Dead
band
(SV)
54
Parameter to be used

Alarm

* This function is an
option.
This device provides the multi-alarm function (option) that allows simultaneous detection of a maximum of 4 types of alarming.
Multi-alarming
It allows a maximum of 4 types of alarm settings (among which, one is dedicated to loop/heater disconnection), detects those types of alarm individually, and makes logical OR before outputing it to the alarm relay.
(Multi-alarm)
Alarm setting 1 Alarm setting 2 Alarm setting 3
Alarm setting 4 (dedicated to loop/ heater break Alarms)
Operation procedure
(Alarm-1 type)
(Alarm-2 type)
Decision of Alarm 1 Decision of Alarm 2 Decision of Alarm 3
Decision of loop/ heater break Alarms
OR
Alarm relay
Setting 1Setting 2Setting 3Setting 4
Selection from B-group
* For the setting in the above figure, the result of ORing of the heater break alarm,
holding-featured low-limit deviation alarm, and high-limit absolute alarm is output.
Each one selected from A-group
55
Set one type code in each digit (settings 1 to 4). When a code that is not in the table is specified, it will be regarded as no alarm (code: 0)”.
(A-group alarm)
Code Type
0 1
2 9
3
4
A
5
6
B
7
C
8
D
No alarm
High limit absolute value
Low limit absolute value
Low limit absolute value with holding feature
High limit deviation
Low limit deviation
Low limit deviation with holding feature
High limit deviation (inverted)
Low limit deviation (inverted)
Low limit deviation (inverted) with holding feature
High/low limit deviation
High/low limit deviation with holding feature
High/low limit deviation (inverted)
High/low limit deviation (inverted) with holding
feature
No alarm used
PV
Alarm Set point
PV
Alarm Set point
Alarm Set point
PV
Set point
Alarm Set point
PV
Set point
Alarm Set point
PV
Set point
Alarm Set point
PV
Set point
Alarm Set point
PV
Set point
Alarm Set point
PV
E
SV high limit absolute value
SV low limit absolute value
F
Alarm Set point
SV
SV
Alarm Set point
NOTE: SV high limit absolute and SV low limit absolute alarms can be
set only in the remote SV type.
56
(B-group alarm)
Code Type
0
1
2
3
No alarm
Heater break detection
Loop break detection
Heater break detection + Loop break detection
NOTES: Any code setting does not result in heater break detection
unless the heater break option is provided.
(alarm 1 - set point 1) Sets the value for alarm. (alarm 1 - set point 2) (alarm 1 - set point 3) (alarm 2 - set point 1) (alarm 2 - set point 2) (alarm 2 - set point 3) (alarm 1-hysteresis 1) Sets the hysteresis for alarm. (alarm 1-hysteresis 2) (alarm 1-hysteresis 3) (alarm 2-hysteresis 1) (alarm 2-hysteresis 2) (alarm 2-hysteresis 3)
57
(loop break detection time)
The loop break detection time is set in
minutes and seconds. By setting 00.00, the alarm will turned ON only at an abnormal input (overrange/ underrange, burn-out etc.). (00.00 ~99.59)
(heater break detection current value)
The heater break detection current
value is set in the unit of ampere. (1~50A)
(heater current value)
Displays the current in the heater.
This parameter cannot be changed. (0~50A)
Supplementary descriptions
1. If during normal operation, the output (MV value) to switch to less 0% or
±
more 100%, and the input (PV value) not moved more than elapsed the time defined in
parameter, then the
3%FS
message will appear and loop break alarm turns ON.
2. This device provides the heater current monitor function (for only the heater break option-fitted type). The current value is displayed in parameter
. This can be used as reference when determining the heater break
detection current value.
3. The heater current measured value is read only when the control output-1 relay is on. When that relay is off, the value at the point immediately before the relay is set off is retained.
58
4. Detection of the heater current requires the following current transformer (to be purchased separately).
Heater current value
For 1~30A
For 20~50A
Types
CTL-6-SF
CTL-12-S36-8F
5. Heater break alarm is not available in the following cases.
1) Control output 1 is SSR drive output or current output.
2) Control output 1 is relay (1c contact) output and the heater is ON on the contact N.C. (normally close) side.
3) The output proportion cycle time of control output 1 is lower than 20 seconds.
59
Parameter to be used

Ramp soak

* This function is an option.
Ramp soak function
Function to automatically change the set point value (SV) with elapsing of time, in accordance with the preset pattern, as shown below. This device allows a maximum of 4 ramp soak programs. The first ramp starts at the value measured immediately before the program is executed (PV).
After the program ends, the manipulate value is output according to (
) setting. If you want to continue the control with the setting value (SV) immediately prior to the end of the program, set the parameter
to 0 (control continue). Note that, with this setting, the control will be continued even if abnormal input takes place.
Set point
Set point 3
Set point 2
Set point 1
Set point 4
PV
First ramp First soak
0
TM1R TM1S
Second ramp
TM2R
Second soak
TM2S
Third ramp
TM3R
Third soak
TM3S
Fourth ramp
TM4R
Fourth soak
Time
TM4S
Ramp···· Region in which the SP changes toward the target value. Soak····· Region in which the SP keeps unchanged at the target value.
Powering on can automatically trigger the program run (power-on start function). External contact signals (option) also run the program (start/ reset).
60
Operating procedure
(ramp soak command) Switches the program
(power-on start command) Set this to determine whether
(first-ramp target value) Sets the target value (SV)
operation modes.
Local operation
Program run
Program temporary halt
the power-on start should be made. (Yes/No)
during each ramp. (0~100%FS E.U.)
(second-ramp target value) (third-ramp target value) (fourth-ramp target value) (first ramp segment time) Sets the duration (in hours and
minutes) of each time segment
(first soak segment time) (second ramp segment time) (second soak segment time) (third ramp segment time)
61
(third soak segment time) (fourth ramp segment time) (fourth soak segment time) (time for rest of the program) The time for rest of the
program is displayed as follows. This parameter cannot be set.
When the time for rest is 100 hours or more: (example: for 100 hours)
When the time for rest is less than 100 hours: (example: for 99 hours and 59 min)
(present point of program) It displays the program run
status as shown in the following table. This parameter cannot be set.
Stop
First ramp running
First soak running
Second ramp running
Second soak running
Third ramp running
Third soak running
Fourth ramp running
Fourth soak running
Program end
62
When using the start/reset function, connect an external terminal with reference to the section 5. Wiring starting on the page 19. The operations will be as follows. External contact input takes place at the time when the contact status (ON/OFF) changes (edge detection).
External contact
(digital input DI)
ON OFF OFF ON
Program stops.
Program runs.
Operation
NOTE:
1. Do not use the auto-tuning function while the ramp soak function is ON (
2. The ramp soak command supply is switched
is not ).
will be set off, once the power
.
63
Parameter to be used

Two set-points

* This function is an option. Two set-points
Changes setpoint with external contact input (Digital Input). See “5. Wiring starting on the page 19 for connection of an external contact.
Main Set point
(SV)
Target point
Sub-Set point
( )
Operating procedure
(sub-set point) Set the sub-Set point in parameter
Target value
DI input
sub-Set point value while DI input is on and, while it is off, the main Set point value is the target value.
Main
Set point
OFF OFFON
Sub-Set point
DI input
. The target value is the
Main
Set point
64
Parameter to be used

Analog output (AO)

* This function is an option. AO output function
Function to externally output the PV, SV, or MV value with DC1~5V signals. AO output can be scaled.
Operating procedure
(AO output type) Set the parameter
the desired output signal type.
Measured Value
Setting Value
Manipulated Value
(scale high limit) (scale low limit) Set the parameters
and to the signal type values (%) corresponding to the 5V and 1V output respectively of AO. (Percentage against the input range is set when the signal type is
to
PV or SV, the % value with respect to the input range is set.)
65
Example: Input....K thermocouple, 0 ~ 800
°
C range
1~5V signals are to be output when PV values are at 200 -
°
600
Measured
value
800
(°C)
600
(°C)
C.
AO output
5(V)
AO signal type . . . PV value
600°C 75% of input range 200°C 25% of input range
(Setting)
200
(°C)
1(V)
0
• • •
• • •
• • •
75.0%
25.0%
NOTE:
1. must be greater than .
66
Parameter to be used

Digital output

* This function is an option. Digital transmission function
Using the RS-485 communication, this function allows remote control for parameter settings and process monitoring. This employs the multi­drop system, and allows connection of a maximum of 31 units. The communication protocol conforms to the Fuji Electric CC data line
R
protocol or Modbus
RTU (Radio Terminal Unit) protocol. Select model configuration when you order (See page 6 or 7). For details, refer to the Fuji Electric PYX Transmission Protocol Specifications (TN508165-E).
Operating procedure
(station No.) Set the station number (1~31).
Perform transmission in accordance with the PYX Transmission Protocol Specifications. In case of Fuji Electric CC data line protocol, the available commands are for polling (parameter read), selecting (parameter write) and control (parameter save). In case of Modbus
R
RTU (Radio Terminal Unit) protocol, they are for polling (parameter read) and selecting (parameter write, including parameter save <fix>). Communication settings are fixed as described below. Make sure that the host side has the same settings.
Transmission signal ..... RS-485
Transmission rate ........ 9600 bps
Parity ........................... Odd
Stop bit ........................ 1 bit
67
NOTES:
1. For the control (parameter save) operation, a maximum of 5 sec is required for the interval from receiving a command to completing the operation.
Before ending of that interval, never turn the power
for this device off (otherwise, the memory contents are destroyed
and disabled).
2. This unit requires a time length of 100 to 120mS as the interval from completing reception of a command from the host before returning the response. It also requires 20mS before it is able to receive the next command after completing a reply.
This device
100~120mS
Host Command
Response
20mS
Host Command
Time
Modbus R is a registered trademark of Gould Modicon.
68

Manual operation /Set Point value (MV)

Manual mode
Direct manipulation
Operating procedure
(control mode) Switches the control mode
Parameter to be used
Automatic control
Manual control
(During manual mode, the Set point
value and
alternate in
display on the Run screen.)
Set point value Set the manipulated variable to be
output in % units into the SP field of the operation screen. (-3.0-
103.0%)
Supplementary descriptions
1. The normal PID or fuzzy control status is called the auto mode ( manual mode (
), and manual operation status is referred to as the
).
69
NOTE:
1. For the dual control type, the manual control mode is not available.
2. Though the display of manual output can be set in 0.1% unit, the actual output resolution is 1%.
3. Autotuning cannot be executed in the manual mode.
4. Power supply is off during manual operation, the value of becomes 0.0%.
5. When the manipulated variable is changed during manual operation, the proportion cycle being output at that changing point is followed by the next proportion cycle which starts the actual output of changed MV.
Present cycle Next cycle
Output changed from 50%~20%
20% output started
70
Parameter to be used

Remote SV Set value

* This function is an option.
Remote SV function
This function is used to input a signal of 1 to 5 VDC externally, and changes and controls the set value (SV) according to the input voltage. This is useful for cascade control etc.
Operating procedure
Set value
(Select the control mode)
Sets the control mode
The set value (SV) by remote input is displayed during remote control. (The keys on the front panel are disabled during remote control.)
(Remote control set value)
The set value (SV) by remote input, regardless of the current mode. This parameter cannot be changed.
(Scale high limit)
The remote set values (SV) corresponding remote input 5V and 1V as the parameter
(Scale low limit)
(0 to 100% FS E.U.)
Enables automatic control. (See Page 69 for details.)
Enables manual control. (See Page 69 for details.)
Enables remote control.
to the
and respectively.
Supplementary descriptions
1. See Page 69 for and (automatic and manual modes).
2. When the mode is switched to
(the automatic mode) during (remote operation), the set value (SV) of the automati c mode will be the same as the set value of the remote control. (The set value will be switched by bumpless).
3. The set value will be the low limit when the remote input is disrupted.
4. Fuzzy control can be used for set value (SV) changes in steps.
NOTES:
1. must be greater than .
2. Caution is required when executing auto-tuning during remote operation, since auto-tuning will be disrupted if the set value (SV) changes by more than 0.5%FS per 0.5 second before the completion of auto-tuning.
71
Parameter to be used

Output monitoring

Output monitor function
Numerically displays the MV being output.
Operating procedure
(MV for output1) The currently output value of single-
output or dual-output heating-side MV is displayed in percent. (-3.0 to 103.0%)
(MV for output2) The currently output value of dual-
NOTES:
1. Neither
2.
output cooling-side MV is displayed in percent. (-3.0 to 103.0%)
nor can be set.
is not displayed with the single-output type.
72

VI. SET-UP PARAMETER

Parameter to be used

Input filter

Input filter
When a PV value becomes unstable due to effects of noise, the filter helps suppress the unstable status.
Setting procedure
(input filter constant) Set the filter time constant in sec
units (0.0 ~ 900.0 (sec)).
=0, input filter function is not active.
The filter effects increase as this setting becomes larger, and decrease as it becomes smaller.
Time constant LargerSmaller
Response SlowerFaster
Effect GreatLittle
73
Parameter to be used

PV shift

PV shift
Shifts the PV. Use this function when the PV is to be adjusted according to a recorder or an indication instrument, or when the sensor is not in the right position and therefore the PV must be adjusted.
Setting procedure
(PV shift value) Set the shift value to be added to
PV. (-50 ~ 50%FS E.U.)
+
PV Processor
+
74
Parameter to be used

Control type

Control type
In addition to PID control, this device is fitted with the fuzzy control suitable for suppressing overshoot. One of the two can be selected as the control type.
Setting procedure
(control type) Select the control type.
PID control
Fuzzy control
NOTES:
1. When control is made with the fuzzy, the PID parameter must be set as with PID control. However, it need not be tuned particularly for the fuzzy. (The values are allowed to be the same as those for PID control.)
2. The fuzzy control mode also allows use of the autotuning function.
3. Fuzzy control cannot be used in the dual output type.
4. The two-set-point function is not available in the fuzzy control mode.
5. Fuzzy control can only be used when the set values change in steps. Attention is required when the ramp soak function or remote SV function is used.
75
Parameter to be used

Output setting in input abnormal

Input abnormal-time output
In the event of an input PV error (e.g. thermocouple burn-out, sensor disconnection or short-circuit, over-input, under-input etc.), or after the ramp soak function (option) program ends, the value specified in advance as the parameter value.
Setting procedure
(input abnormal-time output selection code)
Code No. Control output 1
is out put as the manipulated
Set the code number (0 ~ 4) by
referencing the following table.
Control output 2
0
1
2
3
4
Going on control
-3%
103%
-3%
103%
Going on control
-3%
103%
103%
-3%
Supplement:
1. Set the parameter
to 0 when the control is desired to be continued after the ramp soak function (option) program terminates, with the set value prior to the program termination.
NOTES:
1. The parameter
specifies only one type of output for both cases of abnormal input and program end. In other words, the same operation will be made after an input error and after the program ends.
76
Parameter to be used

Output limits

Output limit
Function to limit the manipulated variable. Used to limit the output range to favor conditions of the process or operation terminal.
Setting procedure
(MV high limit) (MV low limit) Set the manipulated-variable high
and low limits (-3.0 ~ 103.0%).
Set point
Set point 3
Set point 2
Set point 1
Set point 4
PV
First ramp First soak
0
TM1R TM1S
Ramp···· Region in which the SP changes toward the target value. Soak····· Region in which the SP keeps unchanged at the target value.
Second ramp
TM2R
Second soak
TM2S
Third ramp
TM3R
Third soak
TM3S
Fourth ramp
TM4R
Fourth soak
Time
TM4S
NOTES 1: Setting must always be made to satisfy the condition of
> . 2: Limiting is not valid during manual operation. 3: Auto-tuning provides the 0-100% range output regardless
of limiting. 4: The limiter is not valid for the 2 point (ON/OFF) control. 5: The loop break detection cannot be performed when
exceeds 100.0% or does not reach 0.0%.
77
Parameter to be used

Set point vlaue limits

Set point limit
Function to limit the range in which Set point can be set.
Setting allowable range
Range
low limit
Range
high limit
Set point
Setting procedure
(Set point high limit) (Set point low limit) Set the Set point high and low limits
within the input scale 0 ~ 100% range. (0 ~ 100%FS E.U.)
NOTES: Setting must be made to satisfy the condition of >
.
78
Parameter to be used

Output cycle time

Output proportion cycle time
The relay/SSR drive output delivers the manipulated variable (0 ~ 100%) as the proportion of output-off time and output-on time. The sum of output-on time and output-off time lengths, that is the on/off cycle time is called the output proportion cycle time.
Output proportion cycle
OFF time ON time
Setting procedure
(Output 1 side proportion cycle time)
(Output 2 side proportion cycle time)
The output proportion cycle time is
set in sec units (1 ~ 120 sec).
Normally the following output
proportion cycle time values must be specified.
Relay output
SSR drive output
20 seconds
2 seconds
79
Supplement:
1. current output.
2.
and are not displayed in the case of
is not displayed in the case of single output type.
80
Parameter to be used

Direct/reverse control action

Selecting direct/reverse operation
Selects the direct operation mode (cooling control) or the reverse operation mode (heating control).
Setting
(operation on the control output 1 side)
Set the operation modes for control 1 and 2 as indicated below.
(operation on the control output 2 side)
NOTE:
1.
Reverse operation (heating control)
Direct operation (cooling control)
is not displayed in the case of single output type.
81
Parameter to be used

Control processing cycle time

Control processing cycle time
This function is not supported now. Please set 0.5 sec. to “dT” parameter.
Cf. Dellivery value of “dT” parameter is 0.5 sec..
82

APPENDIX

1. ERROR MESSAGES

Display Cause Control output
1. Thermocouple sensor burn out
2. Thermoresistance sensor disconnection
3. Input exceeding 105% of the input range
1. Thermoresistance sensor disconnection
2. Thermoresistance sensor short-circuit
3. Input under -5% of the input range
1. Heater disconnection
1. Control loop error (cause not specifically determined)
1. Memory data destroyed Going on control
The value preset in parameter is output. For details, see "Output setting in input abnormal" on page76.
Going on control
If display indicates an error, remove its cause as soon as possible.

2. POWER FAILURE

a) Operation of this device is not affected in case of instantaneous
power failure with a duration of 20ms or less.
b) In case of power failure with a duration of 20ms or more, operation
is made in the same manner as when re-powering on is made.
83

3. SPECIFICATIONS

Input block
Indication accuracy Thermocouple input
±
0.5%FS±1digit±1 (at 23°C)
°
* B thermocouple 0 ~ 400
C ±5%
R thermocouple 0 ~ 500
Thermoresistance input
±
0.5%FS±1digit (at 23°C)
Voltage input, current input (externally mounted resistance use)
±
0.5%FS±1digit (at 23°C) Temperature drift Reference contact temperature compensation adjustment
Input sampling cycle time 500msec Input impedance Thermocouple: 1M
Allowable signal source resistance
±
0.3%FS/10°C
±
1.0°C
Current input: externally mounted
Voltage input: 1MΩ or above
Thermocouple: 250Ω or below
°
C ±1%
or above
resistance of 250
Voltage input: 1k
Allowable wiring resistance Thermoresistance: 10
(for one wire)
or below
or below
84
Output block Control output • Relay contact output
Proportion cycle time: 20 ~ 120sec Contact structure: SPST, SPDT Contact capacity: AC220V/DC30V 3A
(Standard load)
(resistance load) AC220V/DC30V 1A
(inductive load) Minimum switching current Mechanical life: 20 million cycles or more Electrical life: 100 thousand cycles or
Voltage pulse output (SSR/SSC drive output) Proportion cycle time: 1 ~ 120sec ON voltage: DC9V ~ 24V OFF voltage: DC0.5V or below Maximum current: DC20mA Load resistance: 600
Current output (DC4 ~ 20mA) Ensured output range: DC3.52mA ~ 20.48mA
Accuracy: Linearity:
: 100mA (DC24V)
more (Standard load)
or above
(-3 ~ 103%)
±
5%FS
±
2%FS Resolution: 1.0%FS Follow-up speed: 2 sec or below Load resistance: 600
Display block Display system 7-segment, 4-digit
Power supply block
Power supply voltage AC100 ~ 240V, Free power supply Power supply voltage variation Power supply frequency 50/60Hz ( Power consumption AC100V: 10VA or below
within -15% ~ +10%
AC240V: 18VA or below
×
2-stage, red, green
±
5%)
or below
85
External dimensions: (W × H × D) mm: 48
×
48×120.5 (PYX4)
48
×
96×112 (PYX5)
96
×
96×112 (PYX9)
Weight: Approx. 200g (PYX4) Approx. 300g (PYX5) Approx. 400g (PYX9)
Mounting method: Panel-installed type
External terminals: screw terminals M3.5
Ambient temperature -10 ~ 50
Ambient humidity 90%RH or below (no condensation)
Warm up 2 hours or above
Insulation resistance DC500V, 20M
Control function (PID or fuzzy control selectable)
Basic PID type (Position type)
Proportional band (P): 0.0 ~ 999.9%, P=0 ON/OFF control
Integration time (I): 0 ~ 3200 sec, I=0 integration off
Derivative time (D): 0 ~ 999.9 sec, D=0 derivative off
Fuzzy control
Digital filter First-order time-lag filter
0.0 ~ 900.0 sec, Set resolution 0.1 sec (0:
OFF)
PV input compensation PV shift (
Over-range, under-range Outside the range of -5 ~ 105%
°
C
±
or above
50%FS)
86
Alarm output (ALM1, ALM2 option)
Output update cycle time: 500msec
Relay contact output
Contact capacity: AC220V/DC30V 1A (Standard load) (resistance load)
Minimum switching current: 100mA (DC24V) Mechanical life: 12 million cycles (200
Electrical life: 100 thousand cycles
Loop break alarm output (Option)
Output update cycle time: 500msec
Alarm setting range: 0.0 ~ 99 min 59 sec
Relay contact output: Alarm relay also used for
×
2-pts SPST contact
AC220V/DC30V 0.3A (inductive load)
times/min.) (Standard load, 20 times/
min.)
Heater break alarm input signal (option) 1 ~ 30A: CT (CTL-6-SF) 20 ~ 50A: CT (CTL-12-S36-8F) used *However, the output proportion cycle time must be 20
sec or above.
Heater break alarm output (option)
Output update cycle time: 500msec
Alarm setting range: 1 ~ 50A
The alarm output relay is also used for this output.
Ramp/soak function (option)
Program pattern count: 1 pattern Number of ramps/soaks per pattern: Maximum of 4 Time indication range: 0 hour 0 min - 799 hours
this
Memory backup: EEP-ROM OFF/run by digital input possible (only when start/reset option is provided)
87
Auxiliary analog output (option)
Number of channels: 1
Output type: DC1 ~ 5V
Ensured output range: DC0.88V ~ 5.12V (-3 ~
103%) Accuracy: Ripple voltage: P-P 1.0%FS or below
Temperature drift: Load resistance: 500k
Attached function: scaling function
Output update cycle time: 500msec
Digital input (Input by contact)
DC15V~21V 5mA
Transmission function (option) RS-485 (2-wire system)
Transmission system: Half-duplex, bit serial
Synchronous system: start-stop synchronization
Coding: data length 8-bit
±
0.5%FS
(50Hz or below)
±
0.3%FS/10°C
or above
Parity odd
Transmission rate: 9600BPS
Number of units connectible
Transmission distance: 500m
Remote SV function (option)
Instruction setting accuracy
Input filter: Digital filter (First-order
Sampling cycle time: 500msec
Temperature drift:
Input impedance: 1M
Allowable signal: 1K
source resistance
Attached function: Scaling function
: 31 units
:±0.5%FS±1digit (at 23°C)
time-lag filter) time constant 1 second
±
0.3%FS/10°C
or above
or below
88

4. TROUBLESHOOTING

Phenomenon Possible cause User response
Required parameter not displayed
Set point not changed
Setting of alarm not displayed
display flickering
Wrong lock level is specified.
Set point limits not correct
Ramp/soak command set to other
than (for the type with the ramp/soak function)
Alarm type set to "No alarm" (Code: 0)
Input error
Heater break
Control loop illegally connected
Set the right lock level. (See Page
44~46.)
Set the correct Set point limits. (See Page78.)
Set the ramp/soak command to
. (See Page 60~63.)
Set the alarm type to be set. (See Page 55~59.)
Check the input or sensor connection and input switch pin setting (for multi-input type). (See Page 19~29, 40.)
Replace the heater.
Set the correct control loop.
“ ” display
flickering
or display output
---- displayed Input value incapable of being
EEP-ROM data destroyed
Input error
Input switch pin illegally set (for
multi-input type)
displayed in four digits
Replace the main unit.
Check the input or sensor
connection. (See Page 19~29.)
Set the input switch pin correctly. (See Page 40.)
Make sure the input is appropriate.
89
Phenomenon Possible cause User response
Autotuning not available
" " Set point not raised (for the type fitted with heater break alarming)
Input error
Ramp/soak command set to other
than " "
Manual run being performed
Set point changed during
autotuning
Because of the too slow process, autotuning is not terminated within 12 hours.
The control output relay has been switched on not long enough.
Output proportion cycle time too short
Check the input or sensor connec­tion. (See page 19~29.)
Check the input switch pin correctly. (See page 40.)
Set the ramp/soak command to
" " during autotuning. (See
page 60~63.)
Switch the manual run mode to the automatic run mode. (See page 69.)
Do not change the Set point value during autotuning.
Autotuning is not available. Perform
manual tuning. (See page 51~54.)
If the control output relay does not get triggered at least 1 sec after powering on, the correct heater current value cannot be detected. (See page 58.)
Set the output proportion cycle time of " " to 20 sec or more. (See page 79.)
Loop break detection not available
Digital transmission not properly performed
Output limit setting is illegal Loop break detection is not
Host-side setting is wrong.
Station number is wrong.
Polarity of transmission
connection is wrong.
available when " " is smaller than 100.0 or " " is larger than 0.0. (See page 77.)
Give the right transmission setting to the host. (See page 67~68.)
Set the right station number. (See page 67~68.)
Check if the transmission connection are all right. (See pages 19~29.)
90

5. PARAMETER LIST

Lock
Display Name
level
Description
Initial value
during
shipment
Remarks
LOCK
CAS
OUT1
OUT2
MOD
AT
Lock level
Remote set
0
3
value
Control output 1 output value
3
Control output 2 output value
3
Control mode
Autotuning
2
1
command
Parameter locking
2
(setting range: 0 ~ 3) Displays the set value (SV) by
remote input. (Displayed range: 0 to 100% FS E.U.)
Displays the output value of Copntrol
Output 1. (display range: –3.0 ~ 103.0%)
Displays the output value of Copntrol
Output 2. (display range: –3.0 ~ 103.0%)
Setting
Setting
Mode
Auto
Manual
Remote
Autotuning
Stop
Not displayed when the remote SV function is disabled.
No setting
No setting Not displayed unless control output 2 is provided.
not displayed when the remote SV function is disabled.
Low-PV type autotuning
D-SV
Sub-Set point
2-setting function sub-set point
2
(setting range: 0 ~ 100%FS E.U.)
STAT
Ramp/soak present point
Ramp/soak proceeding status is
1
displayed with a symbol. No setting (display: OFF/1-RP/1-SK/2-RP/2­SK/3-RP/3-SK/4-RP/4-SK/END)
TIME
Ramp/soak remaining­operation time
The ramp/soak proceeding status is
1
displayed with the time for remaining operation. When the time for remaining operation exceeds 100 hours, the hours display of "xxxh" is made. When the time is under 100 hours, the hour/min display of "xx.xx" is made. No setting.
* See page 44~46 for lock level.
Normal autotuning
0%FS
E.U.
Not displayed unless the 2-setting function is provided.
Not displayed unless the ramp/soak function is provided.
* E.U.: Engineering Units * D.E.U. : Deviation engineering Units
91
Display Name
PROG
Ramp/soak command
Lock
level
1
Description
Setting Operation
Function OFF
Run
Temporary stop
Initial value
during
shipment
Remarks
SV-1
TM1R
TM1S
SV-2
TM2R
TM2S
SV-3
TM3R
First target value
First ramp time
First soak time
Second target value
Second ramp time
Second soak time
Third target value
Third ramp time
1
First-ramp target value (setting range:0~100%FS E.U.)
1
First-ramp segment time (hour/min) (setting range:00.00~99.59)
1
First-soak segment time (hour/min) (setting range:00.00~99.59)
1
Second-ramp target value (setting range:0~100%FS E.U.)
1
Second-ramp segment time (hour/min) (setting range:00.00~99.59)
1
Second-soak segment time (hour/min) (setting range:00.00~99.59)
1
Third-ramp target value (setting range:0~100%FS E.U.)
1
Third-ramp segment time (hour/min) (setting range:00.00~99.59)
0%FS
E.U.
00.00
00.00
0%FS
E.U.
00.00
00.00
0%FS
E.U.
00.00
Not displayed unless the ramp/soak function is provided.
TM3S
SV-4
TM4R
TM4S
P-ON
P
Third soak time
Fourth target value
Fourth ramp time
Fourth soak time
Power-on start
Proportional band
1
Third soak segment time (hour/min) (setting range:00.00~99.59)
1
Fourth-ramp target value (setting range:0~100%FS E.U.)
1
Fourth-ramp segment time (hour/min) (setting range:00.00~99.59)
1
Fourth-soak segment time (hour/min) (setting range:00.00~99.59)
2
Ramp/soak power-on start command (setting range:NO/YES)
2
setting range:0.0~999.9%
92
00.00
0%FS
E.U.
00.00
00.00
NO
5.0
'0' for ON-OFF control
Display Name
Lock level
Description
Initial
value
during
shipment
Remarks
HYS
I
D
COOL
DB
AR
MAN
2-point operation hysteresis
Integration time
Derivative time
Control output 2 proportional band coefficient
Dead band
Anti­resetting wind up
Manual resetting value
2
(setting range:0~100%FS D.E.U.)
2
(setting range:0~3200sec)
2
(setting range:0.0~999.9sec)
2
Control output 2 proportional band coefficiency. 0 for 2-point operation (setting range: 0.0~10.0)
3
Control output 2 shift value (setting range:–50~50%)
3
The integration range is set (setting range: 0.0~100.0% D.E.U.)
3
MV shift (setting range:–100.0~100.0%)
0.5%FS D.E.U.
240
60.0
1.0
0.0
100
%
FS
(D.E.U.)
0.0
Not displayed except when P = 0.
At '0', integration operation turns off.
At 0, derivative operation turns off.
Not displayed unless control output 2 is provided.
AL1T
AL11
A11H
Types of alarm-1
Alarm 1-1 Set point
Alarm 1-1 hysteresis
2
Dedicated to loop/heater disconnection
2
Set point of Alarm 1-1 (setting range: 0~100%FS E.U.)
3
Hysteresis for alarm 1-1 (setting range: 0~100%FS D.E.U.)
1-3
type
1-2
type
1-1
type
Not displayed
0003
1000 for
the HB
10 °C/°F.
(0%FS
E.U. for the
HB-fitted)
0.5%FS (D.E.U.)
unless alarm 1 is provided.
fitted
Not displayed when alarm 1 is not provided, and when setting is not made for alarm 1-1.
93
Display Name
Lock level
Description
Initial value
during
shipment
Remarks
AL12
A12H
AL13
AL13H
AL2T
Alarm 1-2 Set point
Alarm 1-2 hysteresis
Alarm 1-3 Set point
Alarm 1-3 hysteresis
Type of alarm 2
Alarm 1-2 Set point
2
(setting range: 0~100%FS E.U.)
Alarm 1-2 hysteresis
3
(setting range: 0~100%FS D.E.U.)
Alarm 1-3 Set point
2
(setting range: 0~100%FS E.U.)
Alarm 1-3 hysteresis
3
(setting range: 0~100% FS D.E.U.)
2
Dedicated to loop/heater disconnection
2-3
type
2-2
type
2-1
type
0%FS
0.5%FS (D.E.U.)
0%FS
0.5%FS (D.E.U.)
0004
1000 for the
HB-fitted
E.U.
E.U.
Not displayed when alarm 1 is not provided, or when setting is not made for alarm 1-2.
Not displayed when alarm 1 is not provided, or when setting is not made for alarm 1-3.
Not displayed unless alarm 2 is provided.
AL21
A21H
AL22
A22H
Alarm 2-1 Set point
Alarm 2-1 hysteresis
Alarm 2-2 Set point
Alarm 2-2 hysteresis
Set point of alarm 2-1
2
(setting range: 0~100%FS E.U.)
Hysteresis for alarm 2-1
3
(setting range: 0~100%FS D.E.U.)
Alarm 2-2 Set point
2
(setting range: 0~100%FS E.U.)
Alarm 2-2 hysteresis
3
(setting range: 0~100%FS D.E.U.)
10 °C/°F.
(0%FS
E.U. for the
HB-fitted)
0.5%FS (D.E.U.)
0%FS
0.5%FS (D.E.U.)
E.U.
Not displayed when alarm 2 is not provided, and when setting is not made for alarm 2-1 and alarm 2.
Not displayed when alarm 2 is not provided, or when setting is not made for alarm 2-2.
94
Display Name
Lock
level
Description
Initial value
during
shipment
Remarks
AL23
AL23H
Loop
HB-A
CT
PVT
Alarm 2-3 Set point
Alarm 2-3 hysteresis
Loop break alarm
Set
point
Heater break alarm
Set point
Heater current
PV type
Alarm 2-3 Set point
2
(setting range: 0~100FS E.U.)
Alarm 2-3 hysteresis
3
(setting range: 0~100FS D.E.U.)
Loop break alarm detection time
2
(min/sec) (setting range: 00.00~99.59)
Heater break alarm detection current
2
(setting range: 1~50A)
Heater current monitor
2
No setting (display range: 0~50A)
Input type, presence or absence of
3
decimal point, and°C/°F specified
Input
type
Presence or absence of decimal point
°C/°F
0%FS
E.U.
Not displayed when alarm 2 is not provided,
0.5%FS (D.E.U.)
00.00
50A
or when setting is not made for alarm 2-3.
Not displayed unless alarming is provided.
Not displayed unless heater break alarming is provided.
2200
unless
otherwise
specified
(K
thermo-
couple, 0
- 400 °C)
PVF
PVB
PVD
TF
Full scale
Base scale
Scaling decimal-point location
Input filter
Scaling full scale
3
(setting range:–1999~9999)
Scaling base scale
3
(setting range:–1999~9999)
Scaling decimal-point location
3
"2" "1" "0":none
Input filter time constant
3
Setting 0.0 turns the filter off. (setting range: 0.0~900.0sec)
95
1000
0
1
5.0
Displayed only in the voltage or current input mode.
Display Name
SFT
PV shift
Lock level
PV shift value
3
(setting range:–50~50%FS D.E.U.)
Description
Initial value
during
shipment
0%FS
(D.
E.U.)
Remarks
SV-H
SV-L
REMF
REMB
CTRL
DT
REV1
Set point high limit
Set point low limit
Remote scaling full scale
Remote scaling base scale
Control operation
system
Control operation
cycle time
Control output 1
direct/reverse
operation selection
Set point high limit
3
(setting range:0~100%FS E.U.)
Set point low limit
3
(setting range:0~100%FS E.U.)
The full scale for remote input scaling
3
(Set range: 0 to 100% FS E.U.)
The base scale for remote input scaling
3
(Set range: 0 to 100% FS E.U.)
Control operation algorithm selected
2
(setting range: PID/FUZY)
3
(Setting range: REV/NORM)
3
100%FS
0%FS
E.U.
100% FS industrial
value
0% FS
industrial
value
PID
0.5 sec
Not displayed when the remote SV function is disabled
REV2
TC-1
TC-2
Control output 2
direct/reverse
operation selection
Control output 1
output proportion
cycle time
Control output 2
output proportion
cycle time
(Setting range: REV/NORM)
3
(Setting range: 1~120 sec)
3
(Setting range: 1~120 sec)
3
Relay
output: 20
sec, SSR
drive: 2 sec
Relay
output: 20
sec, SSR
drive: 2 sec
Not displayed when control output 2 is not provided.
Not displayed when output 1 is 4 - 20mA.
Not displayed when 4 - 20mA output or without control output 2.
96
Display Name
Lock level
Description
Initial value
during
shipment
Remarks
MV-H
MV-L
BURN
A0T
A0-H
MV high limit
MV low limit
Output setting in
input abnormal
AO output type
AO scaling full
scale
(setting range: –3.0~103.0%)
3
(setting range: –3.0~103.0%)
3
3
3
3
Setting Output 1
Going on control
–3.0%
103.0%
–3.0%
103.0%
Setting AO source
AO output scaling full scale (setting range: 0.0~100.0%)
Output 2
Going on control
–3.0%
103.0%
103.0%
–3.0%
PV
SV
MV
100.0
0.0
1
Not displayed unless AO is provided
100.0
A0-L
STNO
AO scaling base
scale
Station No.
AO output scaling base scale
3
(setting range: 0.0~100.0%)
Transmission originating station number
2
(setting range: 1~31)
0.0
1
Not displayed unless transmission is provided.
97
Loading...