PERFECT FOR CONTROLLING RAPIDLY CHANGING PROCESSES LIKE PRESSURE AND FLOW
While most temperature control systems can be maintained sufficiently with the twice-per-second sampling rate found in other
controllers, the PYH reads the process variable ten times per second and makes control decisions at the same rate. That’s what
makes this controller well-suited to control pressure, flow rates, and temperature of low mass systems like a single metal filament.
With a fast sampling rate and full PID control, the PYH minimizes overshoot and oscillation around the setpoint which normally
would occur before most controllers would detect them.
The PYH can also handle slower responding processes and offers autotuning capability to optimize control parameters. For remote
operation and factory automation, up to 31 separate controllers can be monitored at the same time. Setpoint and other control
values can easily be reset at your command with free custom software.
The PYH offers another unique feature called position feedback. This capability lets you know and control the exact position of a
valve at any time. To initiate position feedback, the operator simply indicates two valve positions—fully open and fully closed. The
controller does the rest, keeping track of the valve position at all times. Knowing the precise position of the valve is critical in
boosting system performance and avoiding motor burnout where a controller without position feedback might try to open or close
a valve that’s already reached its limit.
• 100ms Sampling Rate
Handles fast responding processes like flow and pressure
• Dual Display
Shows process value, setpoint or % output simultaneously
• Offset Adjustments
Allows you to synchronize several controllers
• Auto/Manual Operation
Manual override allows you to take control of the process
at any time
• PID Autotuning
Automatically calculates PID control settings for you,
thereby optimizing system performance
• Inputs
J, K, R, T, S, B, E, W, 1 to 5 VDC, 0 to 10mV DC, 0 to 50mV
DC, 4 to 20mA, RTD
• Outputs
Relay, DC voltage pulse, 4 to 20mA, position feedback relay
• Password Protection
Prevent accidental or unauthorized changing of parameters
• Fault Indication
LEDs identify existing system problems
• Digital Filtering
Suppresses noise on input signal of fast-acting systems
• Sensor Break Protection
Protects your process if the input sensor fails
• User-Selectable Temperature Scale
Allows you to choose either °F or °C indication
• FREE Calibration
For the first three years you own your Fuji controller
• FREE Technical Support
From our team of factory-trained engineers
• Three-Year Warranty
Protects against manufacturing defects
Information subject to change without notice. Prices in USD.
PYH, CONTINUED
• Selectable Setpoints
• Remote Setpoint
• Digital Outputs
• Analog Retransmission
• Heater-Break Alarm
• Position Feedback
Compatible with systems using a slide wire to indicate valve position
• RS-485 Communications
Allows you to monitor and control your systems remotely
• Free Software
The Fuji PYH is available with an RS-485 communications option. When you buy this option, you get FREE software that enables
you to run 31 controllers per port from your PC. This software has been designed with the novice user in mind. It’s easy to
operate and install using a simple diskette and a standard twisted shielded pair type wiring. The source code for this software is
also provided, which allows you to rewrite your system easily and inexpensively. If you’ve considered automating your plant,
but don’t want to spend a fortune on distribution control software, this is an ideal solution.
PYH SPECIFICATIONS
GENERAL SPECIFICATIONS
POWER SUPPLY85 to 264 VAC
POWER CONSUMPTION15VA at 110 VAC or 30VA at 220 VAC
AUXILIARY OUTPUTOptional Retransmission of PV, SV, or MV
(ANALOG Output Signal: Linear 1 to 5 VDC
RETRANSMISSION)Impedance: 500KΩ or more
MEMORYNon-volatile (EEPROM)
INPUT SELECTION
INPUT SIGNAL
CONTROL FUNCTION
CONTROL MODE OUTPUT 1 Proportional Band: 0 to 3276% FS
CONTROL MODE OUTPUT 2 Proportional Band: 0 to 3276% FS
MANUAL CONTROLManual Mode: Local – A/M key on the front panel.
OUTPUT
RELAY3A at 220 VAC, SPDT (resistive load)
VOLTAGE (PULSED)10 to 27 VDC (DC drive for SSR)
CURRENTLinear 4 to 20mA DC resistive load
POSITION FEEDBACK3A, 220 VAC SPST(two relays)
Thermocouple: J, K, R, S, T, E, PR40/20, Tungsten
RTD: Pt100 IEC, Pt100 JIS
Voltage/Current: 4 to 20mA DC, 1 to 5 VDC,
0 to 10mV DC, 0 to 50mV DC
Integral Time: 0.1 to 3276 seconds
Derivative Time: 0 to 900 seconds
Cycle Time: 1 to 255 seconds (for relay,
voltage pulse)
Integral Time: 0.1 to 3276 seconds
Derivative Time: 0 to 900 seconds
Cycle Time: 1 to 255 seconds (for relay,
voltage pulse)
Remote – digital input
Manual Setting: -25 to 125% control output
ON: 10 to 27 VDC typical, 20mA DC max.
OFF: 0.5 VDC max.
Impedance: 600Ω or less
AUXILIARY INPUT
REMOTE SETPOINT (OPT)1 to 5 VDC. Input Resistance:1MΩ or greater
SELECTABLE SETPOINT PYH9–up to 7 setpoint settings, PYH5–up to
(OPTIONAL)3 setpoint settings
REMOTE AUTO/MANUALDigital switching
VALVE POSITION For position feedback control 100 to 1000Ω
POTENTIOMETER3-wire potentiometer. Zero and span adjustment
programmable
ALARMS
SETTING TYPEDeviation and absolute value
ALARM TYPEHigh, Low, Low with hold on start-up, High/Low,
High/Low with hold on start-up
OUTPUT2 SPDT relays: 1A, 220 VAC resistive load
HEATER BREAK ALARM Input: 0 to 30A or 20 to 50A 50/60Hz for current
(OPTIONAL)sensing transformer
Output: Relay: 1A, 220 VAC, SPST (resistive load)
Setting: Voltage and current trip point
(programmable)
FAULT ALARMLLLL: Under-range condition
UUUU: Over-range condition
EEPROM: Error
COMMUNICATIONS (OPTIONAL)
INTERFACERS-485
SYSTEMHalf duplex
SYNCHRONIZINGStart-stop
DATA LENGTH8 bits
PARITYNone, odd, or even (programmable)
STOP BIT1 or 2 bits (programmable)
BAUD RATE9600 or 19200 (programmable)
DISTANCE1km max.
ADDRESS31 addressable units max.
Information subject to change without notice. Prices in USD.
PYH, CONTINUED
OPERATION AND DISPLAY SECTION
MAIN DISPLAYSProcess (PV), Setpoint (SV), % Output (MV) PV is
displayed on the top by a red, 4-digit, 7-segment
LED. SV or MV are displayed on the bottom, one
at a time, by a green, 4-digit, 7-segment LED
STATUS INDICATORSControl outputs, alarm outputs, heater break alarm,
fault alarm, auto/manual, remote setpoint
(Programmable to indicate status of other
alarm conditions.)
TEMPERATURE STABILITY5µ V/°C
REPEATABILITY.83°C
SAMPLING TIME0.1 to 3276 seconds (programmable)
STRUCTURE
MOUNTINGPanel mount
TERMINATIONCompression type terminal (IEC IP00)
FRONT PANELDrip and dust proof plastic(IEC IP55)
OPERATING AND STORAGE CONDITIONS
AMBIENT TEMPERATURE10 to 50°C
STORAGE TEMPERATURE-10 to 70°C
AMBIENT HUMIDITY0 to 90% relative humidity non-condensing
DIGITAL OUTPUT OPTION
DIGITAL OUTPUTSOptional alarms
SETTING TYPEDeviation and absolute value
ALARM TYPEHigh, Low, High/High, Low/Low, change in PV,
change in MV
OUTPUT TYPEPYH9 up to three 1A, 30 VDC relays (open
collectors), PYH5 up to one 1A, 30 VDC
(open collector)
PYH ORDERING INFORMATION
PYAHBCD2HIEFG
To create a part number fill in the boxes above with the appropriate number and/or letter from the corresponding box below.
Box A: Front Panel Size
5 = 1/8 DIN $ 529
9 = 1/4 DIN549
Box B: Control Functions
A = Single output controlN/C
B = Single output control w/ selectable setpoints$ 125
C = Inverter control w/ selectable setpoints 275
(PYH 9 only)
D = Position feedback control75
E = Position feedback control w/ selectable setpoints 200
F = Dual output control60
G = Dual output control w/ selectable setpoints200
Box C: Control Output 1
1 = Relay (SPDT; 3A @ 220 VAC)N/C
2 = Voltage pulse (10–27 VDC for N/C
triggering SSR, SCR)
3 = 4–20mA DCN/C
4 = Position feedback output for motor drive valvesN/C
(2 Relays 3A @ 220 VAC)
Box E: Additional Specifications 1
0 = NoneN/C
1 = With heater break alarm $ 75
(available with relay outputs only)
Heater break option requires current transformers.
Please specify part # (see Accessories).
Box F: Digital Communications Function
Y = NoneN/C
R = With RS-485*$ 100
* RS485 to RS232 converter, part no. RSFC24
recommended for direct link to PC.
Box G: Additional Specifications 2
Y = NoneN/C
A = With remote setpoint$ 150
(not available with selectable setpoints)
B = With re-transmission output200
C = With remote setpoint & re-transmission output325
Box H: Input Specifications
A = Thermocouple/RTD/mVN/C
B = 4–20mA DC, 1–5 VDCN/C