Fuji Electric PXV3 PXW Operating Manual

1
PXV3/PXW SERIES
Operation Manual
PID Autotune Controllers Featuring Fuzzy Logic
1-800-884-4967 U.S. & CANADA
802-863-0085 INT’L
802-863-1193 Fax
8:30 A.M.- 6:00 P.M. E.S.T.
V298.8
TABLE OF CONTENTS
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PXV3
Model Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Outer Dimensions and Panel Cutout Size . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Front Panel Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Front Panel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
PXW
Model Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Outer Dimensions and Panel Cutout Size . . . . . . . . . . . . . . . . . . . . . . 8
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Front Panel Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
System Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Front Panel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Autotuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Programming
Primary Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Secondary Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Factory Preset Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Appendix A: Autotuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Appendix B: Manual Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Appendix C: Heater Break Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Appendix D: Heat/Cool Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Quick Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
INTRODUCTION
Thank you for purchasing the Fuji Electric temperature/process controller. All of these controllers are PID Autotune controllers that employ Fuji Electric’s patented fuzzy logic algorithms.
It is a fully programmable temperature/process controller incor­porating many user-friendly features. The following easy-to-use instructions are intended to help you understand, set up, effectively operate, and achieve optimal performance from your controller. When programmed and operated within the guidelines set up for them in this manual, your controller will give you years of precise, reliable control. If needed, we will provide free technical support throughout the life of the controller.
The first section of this manual details the specifications and general description for the PXV3 controller. The second section will cover the PXW controller, followed by a detailed description of the programming parameters, which are common to both the controllers. Several appendices describe some of the controlling techniques. Finally, a Quick Reference guide gives a listing of all the parameters and their default values.
FEATURES
• Fuzzy Logic Control
• PID Autotune with manual override - heating or cooling
• Programmable control action - reverse or direct
• Programmable cycle time
• Programmable inputs - Thermocouple/ RTD, Current/ Voltage
• Sensor burn-out protection
• Input calibration by user
• Outputs: Relay, Solid-state relay drive, or 4-20mA DC (4-20mA not
available on PXV3)
• Secondary output for
cooling (optional)
• High/low alarm
outputs (optional)
• Heater break alarm (optional)
(only on PXW 5,7,9)
• Menu driven format
• Setting – touch keys on front panel
• Programmable 8-segment ramp/soak function
• Digital filtering (to suppress factory noise)
• Adjustable setpoint range
• Selectable °F/°C
• Offset adjustments
• Programmable decimal point
• Programmable lock feature
• Advanced security options to prevent unauthorized parameter
changes
• 4-digit, LED indication
• Output status indication
• Fault indication
• Non-volatile memory
• 1/32, 1/16, 1/8, 1/4 DIN and 72mm panel mount package
• NEMA 4X faceplate
• ABS plastic housing
• Termination— screw-down type (PXV3, PXW-5, 7, 9) or socket with
screw-down terminals (PXW-4)
• Metal mounting bracket; plastic bracket for PXV3/PXW-4
• 85 to 264V AC free voltage power supply
• 24V AC/DC power supply (optional)
• UL, C-UL, and CE approvals
• 3-year warranty
SAFETY PRECAUTIONS
Before using this product, the user is requested to read the follow­ing precautions carefully to ensure safety. The safety requirements are classified as either “warning” or “caution” according to the following explanations:
Warning
Wiring
1. If there is danger of serious accident resulting from a failure or defect in this unit, provide the unit with an appropriate external protective circuit to prevent an accident.
2. The unit is normally supplied without a power switch or a fuse. Use power switch and fuse as required (Rating of the fuse: 250V, 1A)
Power supply
1. Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure.
2. Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented.
General
1. Never attempt to disassemble, modify, or repair this unit.
Tampering with the unit may result in malfunction, electric shock, or fire.
2. Do not use the unit in combustible or explosive gaseous atmos-
pheres.
Caution
Installation
1. Avoid installing the unit in places where:
• the ambient temperature may reach beyond the range of -10 to 50°C (14 to 122°F) while in operation
• the ambient humidity may reach higher than 90% RH while in operation
• a change in the ambient temperature is so rapid as to cause condensation
• corrosive gases (sulfide and ammonia gas, in particular) or combustible gases are emitted
• the unit is subject to vibration or shock
• the unit is likely to come in contact with water, oil, chemicals, steam, or vapor
• the unit is exposed to dust, salt, or air containing iron particles
• the unit is subject to interference with static electricity, mag­netism, or noise
• the unit is exposed to direct sunlight
• heat may be accumulated due to radiation
Maintenance
1. Do not use organic solvents such as alcohol or benzene to wipe this unit. Use a neutral detergent.
2. Three-year warranty is guaranteed only if the unit is properly used.
Warning
Caution
suggesting that the user's mishandling can result in personal death or serious injury.
suggesting that the user's mishandling can result in personal injury or damage to the property.
3
PXV3 SPECIFICATIONS
INPUT RANGE TABLE:
________________________________________________________ Input Signal Input Range Input Range Remarks
(°C) (°F)
________________________________________________________
Thermocouple
J 0~800 32~1472 Cold Junction K 0~1200 32~2192 compensating R 0~1600 32~2912 function built-in B 0~1800 32~3272 S 0~1600 32~2912 T -199~200 -328~392 T -150~400 -238~752 E -199~800 -328~1472 N 0~1300 32~2372 PL2 0~1300 32~2372
________________________________________________________
RTD
Pt100 -150~850 -238~1562 Allowable wiring
resistance 10 ohms
max (per wire)
________________________________________________________
DC Voltage/ Current
1-5V Scaling Range: -1999 to 9999 For current input, 0-5V use the 250
Engineering Units resistor to obtain 4-20mA 1-5V or 0-5V DC 0-20mA input
________________________________________________________
CONTROL FUNCTION
(SINGLE OUTPUT)
________________________________________________________ Control action PID control with auto-tuning
Fuzzy control with auto-tuning
________________________________________________________ Proportional band (P) 0-999.9%, of full scale (FS), setting in 0.1% steps
________________________________________________________ Integral time (I) 0-3200 sec, setting in 1 sec steps
________________________________________________________ Differential time (D) 0-999.9 sec, setting in 0.1 sec steps
________________________________________________________ P,I,D = 0: 2-position action I,D = 0: Proportional action
________________________________________________________ Proportional cycle 1-150 sec, setting in 1 sec steps, for relay contact
output and SSR/SSC drive output only
________________________________________________________ Hysteresis width 0-50% FS, setting in 1 E.U. (Engineering Unit)
steps, 2-position action only
________________________________________________________ Anti-reset wind up 0-100% FS, setting in 1 E.U. steps, auto-setting
with auto-tuning
________________________________________________________ Input sampling cycle 0.5 sec
________________________________________________________ Control cycle 0.5 sec
________________________________________________________
CONTROL FUNCTION
(DUAL OUTPUT) (Heat/Cool Type)
________________________________________________________ Heating Proportional band P x 1/2 (P= 0-999.9%)
________________________________________________________ Cooling Proportional band Heating proportional band
x Cooling proportional band coefficient Cooling proportional band coefficient= 0-100 0: 2-position action
________________________________________________________ Integral time 0-3200 sec for heating and cooling
________________________________________________________ Differential time 0-999.9 sec for heating and cooling
________________________________________________________ ________________________________________________________
P,I,D= 0: 2-position action (without dead band) for heating and cooling I,D= 0: Proportional action
________________________________________________________ Proportional cycle 1-150 sec, for relay contact output and SSR/SSC
drive output only
________________________________________________________ Hysteresis width 2-position action for heating and cooling: 0.5% FS
2-position action for cooling: 0.5% FS
________________________________________________________ Anti-reset wind-up 0-100% FS, setting in 1 E.U. steps, auto setting
with auto-tuning
________________________________________________________ Overlap/dead band ±50% of heating proportional band
________________________________________________________ Input sampling cycle 0.5 sec
________________________________________________________ Control cycle 0.5 sec
________________________________________________________
OUTPUT
________________________________________________________ Relay contact output: SPST 220V AC/30V DC 2A (resistive load)
Mechanical life: 10
7
times (under no load)
Electrical life: 10
5
times (under the rated load)
________________________________________________________ SSR driver output: On-5V DC typ. (5.5V ±1V), 20mA max.
Off-0.5V or less
________________________________________________________ Alarm output/ SPST 220V AC/ 30V DC 2A (resistive load) 2nd control output:
________________________________________________________ Alarm: Configurable from the front panel keys as
Absolute, Deviation, Zone, or Combination alarms with or without the hold feature.
________________________________________________________
SETTING AND INDICATION
________________________________________________________ Accuracy: ± 0.5% of FS ± 1 digit ( ± 1°C for thermocouple)
R T/C: 0-400°C: ±1%FS ± 1 digit ± 1°C B T/C: 0-500°C: ±5%FS ± 1 digit ± 1°C
________________________________________________________
________________________________________________________ Setting method: 3-key operation
________________________________________________________ Indicator: 4 digit, 7-segment LED (green)
________________________________________________________
P X V 3
V
1
Type of Input Code
Thermocouple (°C) T Thermocouple (°F) R RTD/Pt100 (°C) N RTD/Pt100 (°F) S 4-20mA DC, 1-5V DC B 0-20mA DC, 0-5V DC A
Control Output 1 Code
Relay contact (reverse action) A Relay contact (direct action) B SSR/SSC driver (reverse action) C SSR/SSC driver (direct action) D
Control Output 2 Code
None Y Relay contact (reverse action) A Relay contact (direct action) B
Alarm Option Code
None 4 High/Low alarm (SPST)* 5 *Available with single output only
Power Supply Option Code
85-264 VAC ­24V AC/DC D
PXV3 MODEL CONFIGURATION
4
SELF-DIAGNOSIS
________________________________________________________ Method: Program error is monitored with a watchdog
timer.
________________________________________________________
PROTECTION FROM POWER FAILURE
________________________________________________________ Memory protection: Non-volatile memory. Parameter values
remain unchanged with disruption of power. Ramp/soak function has to be re-initiated.
________________________________________________________
OPERATING AND STORAGE CONDITIONS
________________________________________________________ Operating temperature: -10 to 50°C (14 to 122°F)
________________________________________________________ Operating humidity: 90% RH or less (non-condensing)
________________________________________________________ Storage temperature: -20 to 60°C (-4 to 140°F)
________________________________________________________ Installation category: II
________________________________________________________ Pollution degree: 2
________________________________________________________
GENERAL SPECIFICATIONS
________________________________________________________ Rated voltage: 85-264V AC or 24V AC/DC
________________________________________________________ Power consumption: 5VA or less (100V AC)
8VA or less (240V AC)
________________________________________________________ Insulation resistance: 20Mor more (500V DC)
________________________________________________________ Withstand voltage: Power source-Earth: 1500V AC, 1 min
Power source-input terminal: 1500V AC, 1 min Earth-relay output: 1500V AC, 1 min Earth-Alarm output: 1500V AC, 1 min Between other terminals: 500V AC, 1 min
________________________________________________________ ________________________________________________________ Input impedance: Thermocouple: 1Mor more
Voltage: 450Kor more Current: 250(external resistor)
________________________________________________________ Allowable signal Thermocouple: 100or less
source resistance: Voltage: 1Kor less
________________________________________________________ Allowable wiring RTD: 10or less per wire resistance:
________________________________________________________ Reference junction ± 1 °C (at 23°C) compensation accuracy:
________________________________________________________ Process variable offset: ±10% FS
________________________________________________________ Setpoint variable offset: ± 50% FS
________________________________________________________ Input filter: 0-900.0 sec, setting in 0.1 sec steps
(primary lagging filter)
________________________________________________________ Noise rejection ratio: Normal mode noise (50/60Hz): 50dB or more
Common mode noise (50/60Hz): 140dB or more
________________________________________________________
STRUCTURE
________________________________________________________ Mounting method: Panel mounting
________________________________________________________ Enclosure: Plastic housing
________________________________________________________ Protection: NEMA 4X/ IEC IP66 (front panel)
________________________________________________________ External terminal: Pluggable terminal w/screw connection
________________________________________________________ External dimensions: 48 (W) x 24.5 (H) x 99 (D) [mm]
________________________________________________________ Weight: Approx. 100 g
________________________________________________________ Finish color: Black (front panel)
________________________________________________________
DELIVERY
________________________________________________________ Controller, panel mounting bracket, waterproof gasket, 250precision resis­tor (when necessary), instruction manual.
________________________________________________________
OUTER DIMENSIONS & PANEL CUTOUT SIZE
Outer Dimensions
Panel Cutout
When installing “n” number of units (NEMA4X/IP66-compatible)
INSTALLATION
,,,
,,,,
,,
NEMA 4X Integrity
The front side of this instrument conforms to NEMA 4X. To ensure the waterproofness between the instrument and the panel, use the gasket that is provided with the unit according to the installation procedure described below.
1. Install the gasket over the enclosure and insert the unit into the panel as shown in Figure 1.
2. Slide the mounting bracket and tighten the screws as shown in Figure 2.
Caution: After the mounting bracket is installed, check the gasket for
displacement and detachment as shown in Figure 3.
24.5(.97)
GASKET
( thickness=1mm )
48 (1.9)
PANEL
8 98 (3.86)
9.5
MOUNTING BRACKET
(.37)
Unit: mm (in.) Panel thickness: 1 to 8 mm (0.04 to 0.31)
MOUNTING BRACKET
22(.87)
48 (1.9)
34 or more
57 or more
–0
+0.3
22.2 +0.5 –0
45
Figure 1 Figure 2
Unit
Bezel Gasket Case
Panel Panel Mounting Bracket Screw
Figure 3
Gasket Gasket
Case Case
(Bad) (Good)
Unit
34.2(1.35)
5
WIRING INSTRUCTIONS
Terminal connection
Wiring material
1. For terminals 1, 2, 3, use 18 ~ 26 gauge wire.
2. For terminals 4 to 9, use 14 ~ 24 gauge wire.
Please refer to Page 9 for further instructions on wiring power, input and output to the controller.
Warning
Be sure to use the rated power supply voltage and polarity.
* For current input, install the 250Ω precision
resistor (accessory) before using the unit.
FRONT PANEL DESCRIPTION
Åõ
SV OUT ALM
SEL
1
8
7
6
54
3
2
NAME FUNCTION
1 Set value (SV) Comes on when a set value (SV)
indication lamp is displayed
2 Process value (PV)/ Process value (PV), Setpoint value (SV),
Set value (SV)/ or parameter symbols and codes are parameter display displayed.
3 Select key To be used when the first, second, or
third block parameters are selected
4 UP key Pressing the key once will increase the
value by one. By pressing it in succession, the value is continuously incremented.
5 DOWN key Pressing the key once will decrease the
value by one. By pressing it in succession, the value is continuously decremented.
6 Autotuning indication Blinks while the PID autotuning is being
lamp performed
7 Control output Comes on when the control output is ON
indication lamp
8 Alarm indication lamp Comes on when the alarm is activated.
Blinks while the alarm is being set.
FRONT PANEL OPERATION
The PXV3 controller programming menu consists of three blocks— PRIMARY (SETPOINT) MENU, SECONDARY (SYSTEM) MENU, and FACTORY PRESET MENU. At power up the controller will be in the operational mode, and process variable (PV) will be displayed. This is the variable that is being controlled, and it is not programmable. When setting the parameters, turn off the power to the load (operating equip­ment) to ensure safety. Since it takes 30 minutes for the unit to stabilize in terms of temperature, all measurements should be carried out at least 30 minutes after the power is turned on. Option-related features are displayed only when the options are provided.
Viewing and Setting Parameters
• The data is automatically registered in 3 seconds after the setting. It can also be registered by pressing the SEL key.
How to set Setpoint value (SV) Operation Display
1. Power on. – Process value (PV)
2. Press SEL key – SV value; SV lamp is lit
3. Press UP or DOWN key – SV value changes accordingly
4. Press SEL key to go back to – Process value (PV); SV lamp off the operational mode
PRIMARY (SETPOINT) MENU Operation Display
1. Operational Mode – Process value (PV)
2. Press SEL key for 3 seconds – ALM LED blinks; AH data (for
units with alarm option)
3. Press UP or DOWN key – AH data changes
4. Press SEL key to access the – AT 0, ......
next parameter
5. Press SEL key for 3 secs. – Operational mode
SECONDARY (SYSTEM) MENU Operation Display
1. Operational Mode – Process value
2. Press SEL key for 7 seconds – 3 seconds later, ALM LED blinks
7 seconds later, “P”
3. Release and press SEL key again – “P” data
4. Press UP or DOWN key – “P” data changes accordingly
5. Press SEL key once – “P”
6. Press DOWN key to scroll down – “i”, “d”, ..... “Mod”
the menu
7. Press SEL key for 3 secs. – Operational mode
FACTORY PRESET MENU Operation Display
1. Operational Mode – Process value
2. Press SEL key for 9 seconds – 3 seconds later, ALM LED blinks
7 seconds later, “P” 9 seconds later, “P-n1”
3. Release and press SEL key again – “P-n1” data
4. Press UP or DOWN key – “P-n1” data changed
5. Press SEL key – “P-n1”
6. Press DOWN key to scroll down – “P-dF”, ........ “dsp7”
the menu
7. Press SEL key for 3 secs. – Setpoint value
OUTPUT1 V. PULSE
INPUT POWER
123
456789
+
ALARM/
OUTPUT2
–+
BB A
–+
250
–+
Power supply
+
6
PXW MODEL CONFIGURATION
P X W
V
1
Front panel size Code 1/16 DIN 4 1/8 DIN 5 72mm 7 1/4 DIN 9
Type of input Code Thermocouple (°C) T Thermocouple (°F) R RTD/Pt100 (°C) N RTD/Pt100 (°F) S 4-20mA DC, 1-5V DC B 0-20mA DC, 0-5V DC A
Control Output 1 Code Relay contact (reverse action) A Relay contact (direct action) B SSR/SSC driver (reverse action) C SSR/SSC driver (direct action) D 4 to 20mA DC (reverse action) E 4 to 20mA DC (direct action) F
Control Output 2* Code None Y Relay contact (reverse action) A Relay contact (direct action) B SSR/SSC driver (reverse action) C SSR/SSC driver (direct action) D 4 to 20mA DC (reverse action) E 4 to 20mA DC (direct action) F *not available on PXW-4 type
Alarm Options Code Heater break alarm* 2 Process alarm & Heater break alarm* 3 None 4 Process alarm 5 *not available on PXW-4, or with 4-20mA output
Power Supply Option Code 24V AC/DC D
ACCESSORIES (Sockets: only for PXW4 and sold separately)
____________________________________________________ 8-pin sockets (for PXW-4 without H / L Alarm Option) ATX1NS Solder Type Socket PG-08 Screw-down type (terminals on back) ATX2PSB Screw-down type (terminals on back) (UL) TP28X Screw-down type (terminals on front) (UL)
11-pin sockets (for PXW-4 with H / L Alarm Option) PG-11 Screw-down type (terminals on back) TP311SB Screw-down type (terminals on back) (UL) TP311S Screw-down type (terminals on front) (UL)
Heater Break Current Sensing Transformer:
CTL-6-SF For heater current (1 to 30 amps) CTL-12-S36-8F For heater current (20 to 50 amps)
____________________________________________________
PXW SPECIFICATIONS
INPUT RANGE TABLE:
________________________________________________________ Input Signal Input Range Input Range Remarks
(°C) (°F)
________________________________________________________
Thermocouple
J 0~800 32~1472 Cold Junction K 0~1200 32~2192 compensating R 0~1600 32~2912 function built-in B 0~1800 32~3272 S 0~1600 32~2912 T -199~200 -328~392 T -150~400 -238~752 E -199~800 -328~1472 N 0~1300 32~2372 PL2 0~1300 32~2372
________________________________________________________
RTD
Pt100 -150~850 -238~1562 Allowable wiring
resistance 10 ohms max (per wire)
________________________________________________________
DC Voltage/ Current
1-5V Scaling Range: -1999 to 9999 For current input, use 0-5V Engineering Units the 250Ω resistor 4-20mA to obtain 1-5 V or 0-20mA 0-5V DC input
________________________________________________________
CONTROL FUNCTION
(SINGLE OUTPUT)
_________________________________________________________ Control action PID control with auto-tuning
Fuzzy control with auto-tuning
_________________________________________________________ Proportional band (P) 0-999.9%, of full scale (FS), setting in 0.1% steps
_________________________________________________________ Integral time (I) 0-3200 sec, setting in 1 sec steps
_________________________________________________________ Differential time (D) 0-999.9 sec, setting in 0.1 sec steps
_________________________________________________________ P,I,D = 0: 2-position action I,D = 0: Proportional action
_________________________________________________________ Proportional cycle 1-150 sec, setting in 1 sec steps, for relay contact
output and SSR/SSC drive output only
_________________________________________________________ Hysteresis width 0-50% FS, setting in 1 E.U. (Engineering Unit) steps,
2-position action only
_________________________________________________________ Anti-reset wind up 0-100% FS, setting in 1 E.U. steps, auto-setting
with auto-tuning
_________________________________________________________ Input sampling cycle 0.5 sec
_________________________________________________________ Control cycle 0.5 sec
_________________________________________________________
CONTROL FUNCTION
(DUAL OUTPUT) (Heat/Cool Type)
_________________________________________________________ Heating Proportional band P x 1/2 (P= 0-999.9%)
_________________________________________________________ Cooling Proportional band Heating proportional band
x Cooling proportional band coefficient Cooling proportional band coefficient= 0-100 0: 2-position action
_________________________________________________________ Integral time 0-3200 sec for heating and cooling
_________________________________________________________ Differential time 0-999.9 sec for heating and cooling
_________________________________________________________ _________________________________________________________
P,I,D= 0: 2-position action (without dead band) for heating and cooling I,D= 0: Proportional action
_________________________________________________________ Proportional cycle 1-150 sec, for relay contact output and SSR/SSC
drive output only
_________________________________________________________ Hysteresis width 2-position action for heating and cooling: 0.5% FS
2-position action for cooling: 0.5% FS
7
_________________________________________________________ Anti-reset wind-up 0-100% FS, setting in 1 E.U. steps, auto setting with
auto-tuning
_________________________________________________________ Overlap/dead band ±50% of heating proportional band
_________________________________________________________ Input sampling cycle 0.5 sec
_________________________________________________________ Control cycle 0.5 sec
_________________________________________________________
OUTPUT
(Single Output)
_________________________________________________________ Control output One of the following three types is selected:
(1) Relay contact (SPDT)
220V AC/30V DC, 3A (resistive load) Mechanical life: 10
7
times (under no load)
Electrical life: 10
5
times (under the rated load)
(2) SSR/SSC drive (voltage pulse):
15-30V DC at ON/0.5V DC or less at OFF. Current 60mA or less.
(3) 4-20mA DC:
Allowable load resistance – 600or less.
________________________________________________________
OUTPUT
(Dual Output)
_________________________________________________________ Control output For dual output type, one of the following three
types is selected on both heating and cooling types: (Not available on PXW-4 type) (1) Relay contact (SPDT):
220V AC/30V DC, 3A (resistive load)
(2) SSR/SSC drive (voltage pulse):
15-30V DC at ON/0.5V DC or less at OFF. Current: 60mA or less
(3) 4-20mA DC:
Allowable load resistance – 600or less
(Note: When SSR/SSC drive output for heating/ cooling side is selected, the total current should be less than 60mA)
_________________________________________________________
SETTING AND INDICATION
_________________________________________________________ Parameter setting method PXW: digital setting with three keys
_________________________________________________________ PV/SV display method PV/SV individual LED display,
4 digits each, PV=red, SV=green
_________________________________________________________ Status display Control output, alarm output, heater break alarm out-
put.
_________________________________________________________ Setting accuracy 0.1% FS
_________________________________________________________ Indication accuracy Thermocouple: ± 0.5% FS ± 1 digit ± 1°C
(at 23°C) R thermocouple: 0-400°C; ± 1% FS ± 1 digit ± 1°C
B thermocouple: 0-500°C; ± 5% FS ± 1 digit ± 1°C RTD, voltage, current: ± 0.5% FS ± 1 digit
_________________________________________________________
ALARM
_______________________________________________________ Alarm output Relay contact (SPST),
220V AC/30V DC, 1A (resistive load) PXW-4 type: 1 point Other types: 2 points
_______________________________________________________ Heater break Relay contact (SPST), alarm output 220V AC/30V DC, 1A (resistive load)
PXW-4 type: not available
_______________________________________________________
GENERAL SPECIFICATIONS
_______________________________________________________ Rated voltage 85-264V AC or 24V AC/DC
_______________________________________________________ Power consumption 10VA or less (100V AC)
15VA or less (240V AC)
_______________________________________________________ Insulation resistance 50Mor more (500V DC)
_______________________________________________________ Withstand voltage Power source-Earth: 1500V AC, 1 min
Power source-input terminal: 1500V AC, 1 min Earth-relay output: 1500V AC, 1 min Earth-Alarm output: 1500V AC, 1 min Between other terminals: 500V AC, 1 min
_______________________________________________________ Input impedance Thermocouple: 1Mor more
Voltage: 450Kor more Current: 250(external resistor)
_______________________________________________________ Allowable signal Thermocouple: 100or less
source resistance Voltage: 1Kor less
_______________________________________________________ Allowable wiring RTD: 10or less per wire resistance
_______________________________________________________ Reference junction ± 1 °C (at 23°C) compensation accuracy
_______________________________________________________ Process variable offset ±10% FS
_______________________________________________________ Setpoint variable offset ± 50% FS
_______________________________________________________ Input filter 0-900.0 sec, setting in 0.1 sec steps
(primary lagging filter)
_______________________________________________________ Noise rejection ratio Normal mode noise (50/60Hz): 50dB or more
Common mode noise (50/60Hz): 140dB or more
_______________________________________________________
POWER FAILURE PROTECTION
_______________________________________________________ Memory protection: Non-volatile memory. Parameter values
remain unchanged with disruption of power. Ramp/soak function has to be re-initiated.
_______________________________________________________
SELF-CHECK
_______________________________________________________ Method: Watchdog timer monitors program error.
_______________________________________________________
OPERATION AND STORAGE CONDITIONS
_______________________________________________________ Operating temperature -10 to 50°C (14 to 122°F)
_______________________________________________________ Operating humidity 90% RH or less (non-condensing)
_______________________________________________________ Storage temperature -20 to 60°C (-4 to 140°F)
_______________________________________________________ Installation category: II
_______________________________________________________ Pollution degree: 2
_______________________________________________________
OTHER FUNCTIONS
_______________________________________________________ Parameter mask function Parameter display is disabled by software
_______________________________________________________ Ramp soak function 4-ramp/4-soak
_______________________________________________________
8
STRUCTURE
_______________________________________________________ Mounting method Panel flush mounting or surface mounting
Surface mounting: PXW-4 type only
_______________________________________________________ External terminal PXW-4 type: 8-pin or 11-pin socket
Other types: screw terminal (M3.5 screw)
_______________________________________________________ Enclosure Black ABS plastic
_______________________________________________________ Dimensions PXW-4 48 x 48 x 85.7mm (1/16 DIN)
PXW-5 52.5 x 100.5 x 95.8mm (1/8 DIN) PXW-7 76.5 x 76.5 x 95.8mm (72 mm) PXW-9 100.5 x 100.5 x 95.8mm (1/4 DIN)
_______________________________________________________ Weight PXW-4 approx. 150g
PXW-5 approx. 300g PXW-7 approx. 300g PXW-9 approx. 400g
_______________________________________________________ Protective structure Front panel water-proof structure;
NEMA 4X (equivalent to IEC standards IP66) Rear case: IEC IP20
_______________________________________________________
DELIVERY
_______________________________________________________ PXW-4 type: controller, panel mounting bracket, socket (when specified), water proof gasket, 250precision resistor (when required), instruction manual. Other types: controller, panel mounting bracket, water-proof gasket, 250resistor (when required), instruction manual.
_______________________________________________________
OUTER DIMENSIONS & PANEL CUTOUT SIZE
48
48
7 71.5
85.7
44.8
57
48
F
C
SEL
HL
9.5
PV
SV
Panel
Gasket
Mounting Bracket
Unit: mm Panel thickness: 1 to 8 mm
Panel cutout size: when installing “n” number of units.
PXW4
PXW 5,7,9
Model PXW5 PXW7 PXW9
A
52.5
76.5
100.5
B
100.5
76.5
100.5
C
90.5 67
90.5
D
114.5 91
114.5
E
45 68 92
0.6
-0
0.7
-0
0.8
-0
F
92 68 92
0.8
-0
0.7
-0
0.8
-0
G
120min
96min
120min
H
92min 116min 140min
E
F
G
H
Unit: mm Panel thickness: 1 to 8 mm
Panel cutout size: when installing “n” number of units.
INSTALLATION
NEMA 4X Integrity
The front side of this instrument conforms to NEMA 4X. To ensure the waterproofness between the instrument and the panel, use the gasket that is provided with the unit according to the installation procedure described below.
How to install the unit
For PXW-5/7/9, install the two metal brackets, one on the top and the other on the bottom, and tighten the screws to a torque of about 14.7N­cm (1.5kg-cm). For PXW4, install the unit in the panel as shown below, and tighten the screws on the mounting bracket until the unit is secure. Make sure there is no space between the front side of the unit and the gasket, and between the gasket and the panel.
Figure 1 Figure 2
Unit
Front Gasket Case
Unit
Panel Panel Mounting bracket Screw
Caution: After the mounting bracket is installed, check the gasket for displacement and detachment as shown in Figure 3.
A
C1
C2 H HBL
PV
B
SV
SEL
16.2
F
Gasket
18.7
95.8
DC
Panel
63 or more
+0.5
-0
45
63 or more
+0.5
-0 45
Gasket Gasket
Case Case
(Bad) (Good)
Figure 3
9
* For current input, install the 250Ω precision
resistor (accessory) before using the unit.
WIRING INSTRUCTIONS
Power supply
– +
PXW4 socket type (with alarm)
1
2
3
4
5
6
7
8
9
10
11 ~
+
B B
A
+
Current output, SSR/SSC driving output
Contact output
*Voltage/
current
Alarm output
Power supply
When alarms are provided
(viewing from the back of instrument)
– +
RTD
Warning
Be sure to use the rated power supply voltage and polarity.
7
8
9
7
8
+
1
3
1 2 3
4 5 6
~
7 8 9
10 11 12
13 14 15
16 17 18
1012
+
RTD
Current output, SSR/SSC driving output
+
Control output 1
PXW7
B
B
A
*Voltage/
Current
input
T.C.
Alarm 1 (Upper limit alarm)
Alarm 2 (Lower limit alarm) Heater break
alarm output
Common
CT input
Control output 2(on the cooling side)
Current output, SSR/SSC driving output
Power supply
+
Power supply
+
Wiring Power to Controllers
• Be sure to use the rated power supply voltage and polarity for the unit to protect it against damage and to prevent the occurrence of failure.
• Keep the power off until all of the wiring is completed to prevent electric shock and abnormal operation.
• Keep the power supply wires separated from the input and output wires.
• Power connections should be made with 18-gauge or larger insulated wire. Stranded wire improves noise immunity. Noise filters and isolation transformers are recommended in case of noisy power lines.
• When the Heater Break option is selected, use the same power line for both the controller and the heater.
Wiring Inputs
There are two input categories available: Thermocouple/RTD or current/voltage. Make sure you have the right type before wiring the inputs. Refer to Table of Input Type Codes and set the parameter “P-n2” accordingly.
Note: In order to minimize the risk of high frequency noise induced by coils and windings in relays, solenoids, and transformers, use leads which have braided sheath and ground one end of the sheath. Keep your input leads separate from power and output leads. If you have to bring the input signal from a long distance, a signal transmitter might be needed to maintain an accurate reading; in this case, a unit that accepts current/voltage input would be necessary.
Thermocouple
• Connect thermocouples directly to the input terminals whenever possible.
• If using extension wires, make sure they are of the same thermocouple material and grade; any dissimilar metal junctions will lead to erroneous readings.
• Ungrounded thermocouples are recommended for optimal performance and to prevent ground loops.
• Make sure the polarity is correct.
RTD Pt100
• Use a 3-wire Pt100RTD whenever possible. All three wires must have low lead resistance (less than 10) and no resistance differentials among them.
• If using a 2-wire RTD, jumper the two B-legs with a wire of equal resis­tance.
• Make sure A and B leads are connected to the right terminals.
Current/Voltage
• The controller accepts 1-5V, 0-5V, 4-20mA, and 0-20mA DC signals. If wiring for a voltage input, feed the signal directly to the input terminals. For current inputs, first connect the 250precision resistor that comes with the unit.
• Make sure the polarity is correct.
Wiring Outputs
Before wiring the outputs, make sure the unit has the right kind of control output, and that all the load handling devices conform to the controller specifications. Note that it takes 5 seconds for the outputs to activate after the power is turned on.
+
4
3
2
1
Thermocouple input
(viewing from the back of instrument)
Contact output
5
6
7
~
8
– +
250
+
PXW4 socket type (standard)
Current output, SSR/SSC driving output
*Voltage/current
RTD
B
B
A
+
+
Thermocouple input
When no alarms are provided
PXW5, PXW9
*Voltage/
Current
input
1
Current output SSR/SSC driving output
2
Control output 1
T.C.
RTD
A
+
1
1
B
2
2
3
B
3
+
4 5
5
6 7
7
8
~
9
Current output, SSR/SSC driving output
10 11 12 13
Alarm 1 (upper limit alarm)
14
Alarm 2 (lower limit alarm)
15
Heater break alarm output
16
Common
17 18
CT input
+
10
Control output 2 (on the cooling side)
12
10
Refer to parameter “P-n1” and to the Table of Output Type Codes to choose the preferred type of control action– reverse acting or direct acting. If using two outputs in a heat/cool type control, please refer to Appendix D for more details.
Relay
• Connecting a load to full capacity of the relay will shorten the relay life, especially if it is operated at a rapid rate. To protect the output relay, an external relay or a contactor should be used. If a higher current rating is required, a solid-state relay driver type output is recommended.
• Connect the load between the normally opened contacts of the relay.This way, if power to the controller is disrupted, the output cir­cuit would open, preventing the load from running out of control.
• Set the proportional time cycle parameter, “TC” to 30 secs. or more.
• Use of “Z-trap” (manufacturer: Fuji Electric Co.) is recommended to protect the relay against switching surges and to ensure the prod­uct’s long life. Connect it between the contacts of the relay as shown in the example below.
Part No.: ENC241D-05A (power supply voltage: 100V)
ENC471D-05A (power supply voltage: 200V)
SSR/SSC Driver (Pulsed DC Voltage)
• The non-isolated DC output is used to drive an external load-han­dling device such as Solid-State Relay(SSR) or Solid-State Contactor(SSC).
• The total current drawn, for both single and dual outputs, should be within the allowed value.
• Make sure the polarity is correct.
• Set the proportional time cycle parameter, “TC” to 1 sec. or more.
4 to 20mA DC
• The output is a non-isolated analog signal used to drive a variety of output devices such as SCRs and valve actuators.
• The load resistance must be less than 600Ω.
• Make sure the polarity is correct.
• The proportional time cycle parameter, “TC” is set to 0, and is not displayed on the programming menu.
Wiring Alarms
• Make sure the load does not exceed the rated capacity of the relay.
• Several types of alarm configurations can be programmed and does
not require a change in the wiring. Refer to parameters AL, AH, P­AH, P-AL, P-An.
• For details on Heater Break alarm, please refer to Appendix D and
the Heater Break Alarm Setpoint parameter “Hb” in the program­ming section.
SYSTEM WIRING DIAGRAMS
PXW4 (8-pin)
PXW9
PXV3
Z-Trap
Example 1:
Example 2:
FRONT PANEL DESCRIPTION
Name Function
1 Process Value (PV) display Displays the process value (PV). 2 Set value (SV) indication lamp Stays on while a set value is on the display. 3 Set value (SV) and Displays set value (SV), or parameter symbol or
parameter display code when setting various parameters.
4 SELECT key Key for switching between the parameter blocks
and for scrolling within the block.
5 UP key For incrementing the numerical value or scrolling
up the the menu. Numerical value changes contin­uously when held pressed.
6 DOWN key For decrementing the numerical value or scrolling
down the menu. Numerical value is decremented continuously when held pressed.
7 Auto-tuning indicator The indicator blinks while the PID auto-tuning is
being performed.
8 Control Output indication lamp C: (for PXW4) Stays on while control output is ON.
C1: Stays on while control output 1 is ON. C2: Stays on while control output 2 is ON.
9 Upper limit alarm Comes on when the upper limit alarm is activated.
indication lamp (optional) Blinks while the alarm value is being set.
10 Lower limit alarm Comes on when the lower limit alarm is activated.
indication lamp (optional) Blinks while the alarm value is being set.
11 Heater break alarm Comes on when the heater break alarm is output.
indication lamp
6543
5 6 7 8 9
123
456789
L
120V AC
N
INPUT
123
PXW4-RAY1-4V
PXV3-RCY1-5V
+
ALARM
/OUTPUT2
85 to 264 VAC
OUTPUT1 V. PULSE
+
456789
L
120V AC
N
Fuse
Heater (3A or less)
3
2
+
Thermocouple
Input
POWER 50/60Hz
4
1
Contact
Output
5
8
Fuse
Fuse
DC Input SSR
+
Alarm
Heater
Thermocouple
Fuse
6
7
Power
85 to 264 VAC
50/60Hz
11
10
8 8
1
3
2
Model : PXW4
9
10
8
9
C
C
HL
PV
SV
O
SEL
54
6
1 3
2
7
C
C1 C2 H L HB
PV
SV
SEL
4
Model : PXW5
7
6
5
8 8
C1
1
PV
3
2
Model : PXW7,9
C2 H HBL
SV
4
11
10
9
C
SEL
7
5 6
11
FRONT PANEL OPERATION
The PXW controller programming menu consists of three blocks— PRIMARY (SETPOINT) MENU, SECONDARY (SYSTEM) MENU, and FACTORY PRESET MENU. At power up the controller will be in the operational mode, and process variable (PV) and setpoint variable (SV) will be displayed. PV is the variable that is being controlled, and it is not programmable. When setting the parameters, turn off the power to the load (operating equipment) to ensure safety. Since it takes 30 minutes for the unit to stabilize in terms of temperature, all measure­ments should be carried out at least 30 minutes after the power is turned on. Option-related features are displayed only when the options are used.
Viewing and Setting Parameters
• The data is automatically registered in 3 seconds after the setting. It
can also be registered by pressing the SEL key.
How to set Setpoint value (SV) Operation Display
1. Power on. – Operational mode
2. Press UP or DOWN key – SV value changes accordingly
PRIMARY (SETPOINT) MENU Operation Display
1. Operational mode – PV, SV
2. Press SEL key for 3 seconds – ‘H’ LED blinks; AH data (for
units with alarm option)
3. Press UP or DOWN key – AH data changes
4. Press SEL key to access the – ‘L’ LED blinks, ....
next parameter
5. Press SEL key for 3 secs. – Operational mode
SECONDARY (SYSTEM) MENU Operation Display
1. Operational mode – PV, SV
2. Press SEL key for 7 seconds – 3 seconds later, “H” LED blinks
7 seconds later, “P”
3. Release and press SEL key again – “P” data
4. Press UP or DOWN key – “P” data changes accordingly
5. Press SEL key once – “P”
6. Press DOWN key to scroll down – “i”, “d”, ..... “Mod”
the menu
7. Press SEL key for 3 secs. – Operational mode
FACTORY PRESET MENU Operation Display
1. Operational mode – PV, SV
2. Press SEL key for 9 seconds – 3 seconds later, “H” LED blinks
7 seconds later, “P” 9 seconds later, “P-n1”
3. Release and press SEL key again – “P-n1” data
4. Press UP or DOWN key – “P-n1” data changed
5. Press SEL key once – “P-n1”
6. Press DOWN key to scroll down – “P-df”, ........ “dsp7”
the menu
7. Press SEL key for 3 secs. – Operational mode
AUTOTUNING
Before initiating the autotune function, first decide if you would like to autotune at setpoint or 10% of full scale below setpoint. Set the set­point (SV), alarms (AL, AH) and the cycle time (TC). Bring your process near setpoint before starting the autotune procedure.
Set the parameter AT to either “1” (to auto-tune at setpoint) or “2” (to auto-tune at 10% of full scale below setpoint) and press SEL key to start auto-tuning. The point indicator at lower right will then start blink­ing. When the auto-tuning is completed, the point indicator stops blink­ing and the parameter AT will automatically be set to “0.”
Duration of the autotune process varies with every application. The auto-tuning process may take between 1 and 30 minutes to complete. If it fails to complete, an abnormality may be suspected. In this case, recheck the wiring, control action, and input type code. Refer to page 12 and Appendix A for additional details.
The PID parameters calculated by autotuning will be retained even if the power is lost. However, if the power is turned off during the auto­tuning process, you must restart Autotuning. To abort the autotune procedure, set AT to “0.” Auto-tuning has to be repeated if there is a significant change in SV, P-SL or P-SU, or in the controlled process. Autotuning can also be performed while fuzzy control is selected.
PRIMARY (SETPOINT) MENU
PARAMETER DESCRIPTION
roFF - rhLd Ramp/Soak Command: The Ramp/Soak program auto-
matically changes the setpoint value with time according to a preset pattern. Setting: roFF : Normal operation is performed
rrUn : Ramp/Soak operation is performed
rhLd : Ramp/Soak operation is suspended
rEnd indicates that the operation is terminated.
AH High Alarm Setpoint: The High Alarm Setpoint is that
point of the process above which, the high alarm out­put relay is energized. If the alarm type, programmed in the secondary menu, includes an absolute value for the High Alarm Setpoint, enter the actual value you want the alarm to be activated at regardless of what the main setpoint is set for. If the alarm type includes a deviation value for the High Alarm Setpoint, enter the number of units above main setpoint in which you want the alarm to be activated at; the deviation alarm tracks main setpoint. Settable within the Input Range. Not indicated without the alarm option.
AL Low Alarm Setpoint: The Low Alarm Setpoint is that
point of the process below which, the low alarm output relay is energized. Absolute and deviation alarm con­figurations are programmable from within the sec­ondary menu. Settable within the Input Range. Not indicated without the alarm option, or in PXV3.
Blinking ‘H’ LED
Blinking ‘L’ LED
12
Hb Heater Break Alarm Setpoint: If the heater’s operating
current falls below this setpoint, the heater break alarm output relay is energized. This option is used in cases where the PXW is controlling a bank of heaters wired in parallel. A current transformer around the hot lead going to the heater bank and connected to the controller is tied with the controller’s output and sens­es the current used by the heater bank. If one or more of the zones burnout, resulting in cold spots, the cur­rent used by the defective heater bank is reduced. By determining what the optimal current and the optimal current minus one zone for the heater bank is, the Heater Break Alarm setpoint can be calculated and entered. Setting Range: 0.0 to 50.0 amps. Not indicated without the Heater Break Alarm option. Not available on PXW4, or with 4-20 mA DC outputs. Detection is made only on a single-phase heater. This function cannot be used when controlling a heater with SCR phase-angle control. Cycle Time, “TC,” must be set at 6 secs. or higher.
AT Autotuning: Autotuning is the automatic calculation
and entering of the control parameters (P, I and D) into memory. Autotuning will also automatically set anti­reset wind-up (Ar).There are two types of Autotuning that can be performed by the controller, Autotuning at main setpoint or Autotuning at 10% of full scale below main setpoint. The latter may yield slightly different val­ues, not as precise, but the process overshoot encoun­tered during the autotuning procedure would not be as much. Enter the value for the type of autotuning you would like to run on your particular application based on overshoot tolerances and the precision of the PID parameters needed. For more information on principles of Autotuning, refer to Appendix A. 0 - Autotuning off 1 - Autotuning performed at setpoint 2 - Autotuning performed at 10% of F.S. below setpoint
LoC Lock-out: This function enables or disables changing
the settings of parameters. Code: 0 - All parameter settings are changeable 1 - All parameter settings are locked; cannot be changed 2 - Only the main setpoint can be changed; all other parameter settings are locked and cannot be changed.
SECONDARY (SYSTEM) MENU
P Proportional Band: The proportional band is that area
around main setpoint where the control output is nei­ther fully on nor fully off. Setting range: 0.0 to 999.9% of full scale For On/Off control, set to “0”
I Integral Time (reset): The Integral Time is the speed at
which a corrective increase or decrease in output is made to compensate for offset which usually accom­panies proportional only processes. The more Integral Time entered, the slower the action. The less Integral Time entered, the faster the action. Enter a value that would eliminate offset without overcompensating, leading to process oscillation. Setting Range: 0 to 3200 secs
d Derivative Time (Rate): The Derivative Time is that time
used in calculating rate of change and thermal lag in helping eliminate overshoot which results in response to process upsets. This overshoot usually accompanies proportional only and proportional-integral processes. The derivative action dampens proportional and inte­gral action as it anticipates where the process should be. The more Derivative Time entered, the more damp­ing action. The less Derivative Time entered, the less damping action. Enter as much Derivative Time as nec­essary to eliminate overshoot without over-damping the process resulting in process oscillation. Setting Range: 0.0 to 999.9 secs
TC Cycle Time (Output #1): The Cycle Time for output #1 is
that time where the output is on for a percentage of that time and off for a percentage of that time, creating a proportioning effect. The Cycle Time is only used when P, PI, PD, or PID control action is used, and when the output is time proportional as with the relay or SSR driver outputs. The shorter the Cycle Time, the higher the proportioning resolution is, and better is the con­trol, but there will be an increased strain on the output device. Enter a value that is based on the limitations of your controller’s output type. Setting range: 1 to 150 secs. For relay output: Set to 30 secs. or more. For SSR/SSC driver output: Set to 1 sec or more. For current output: Set to 0 (normally not indicated)
Start of AT End of AT
AT in operation
Set value (SV)
100%
0%
ON-OFF action
PV
ON
OFFONOFF
(Measured value)
PID control
Start of AT End of AT
AT in operation
Set value (SV)
100%
0%
ON-OFF action
PV
ON
OFF
ON
OFF
PID control
SV-10%FS
(Control output)
(Control output)
(Measured value)
Standard type (AT=1)
Low PV type (AT=2)
TEMP
Setpoint
Proportional
Action
Integral
Action
Derivative
Action
TIME
30 sec. Cycle Time
25% Output
ON OFF
30 sec. Cycle Time
75% Output
ON OFF
Blinking ‘HB’ LED
Optimal Current of
Heater Bank
minus
Optimal Current of
Heater Bank
less One Zone
Optimal Current of
+
Heater Bank
less One Zone
2
=
Heater
Break Alarm
Setpoint
13
HYS Hysteresis: Hysteresis is that area around the main
setpoint where the output does not change condition. That area or deadband is intended to eliminate relay chatter at setpoint for On/Off control applications. The wider the Hysteresis, the longer it takes for the con­troller to change output condition. The narrower the Hysteresis, the less time the controller takes to change output condition. When the Hysteresis is narrow, the On/Off control is more accurate but the wear on the output relay is increased. Enter a value which is small enough to meet the control tolerance of the application but large enough to eliminate relay chatter. Setting range: 0 to 50% of FS, set in E.U. for output #1. Hysteresis for On/Off action for dual outputs (heating and cooling) is fixed at 0.5% of FS.
TC2 Cycle Time (Output #2) The Cycle Time for output #2 is
similar in function to Cycle Time for output #1. Output #2 is the cooling side of a heat/cool PXW controller. Enter a value that is based on the limitations of your controller’s output type. Setting Range: 1 to 150 secs. Not indicated without the control output #2 option For current output: Set to 0 (normally not indicated)
Cool Proportional Band Coefficient for Cooling: The
Proportional Band Coefficient for Cooling is a multiplier for the proportional band on the cooling side of a heat/cool controller. It varies the width of the propor­tional band on the cooling side. A large value would establish a larger proportional band for more powerful cooling loads. A small value would establish a smaller proportional band for less powerful cooling loads. Enter a value based on the power of your cooling load.
Setting Range: 0.0 to 100.0 Not indicated without control output #2 option. Set to “0” for On/Off control.
db Deadband/Overlap: The Deadband/Overlap is that per-
centage of the heating side of the proportional band where the heating (output #1) and the cooling (output #2) outputs are separated by a Deadband or where they Overlap on a heat/cool controller. A value greater than zero establishes a Deadband area where neither the heating nor cooling outputs are energized, for more powerful heating and cooling loads. A value less than zero establishes an Overlap area where both the heat-
ing and cooling outputs are energized at the same time, for less powerful heating and cooling loads. Enter a value based on the power of your heating and cool­ing loads as well as the application’s efficiency in maintaining tight heat/cool control. Setting range: -50.0 to 50.0% of the heating proportion­al band. Not indicated without control output #2 option
bAL Balance: Balance is used to pre-position the propor-
tional band with respect to setpoint. With Balance (MV Offset) set at 50% the proportional band will be cen­tered around setpoint. To move the band left or right, decrease or increase the balance setting respectively. Setting range: 0-100%
Ar Anti-Reset Wind-up: Anti-Reset is used to limit the
range where integration occurs. This helps in stabiliz­ing a system. With Anti-Reset at 100%, integration will occur throughout the proportional band. With Anti­Reset set to 90%, integration will occur at 90% of the band above the setpoint and 90% of the band below the setpoint. Autotuning automatically sets Ar. Setting range: 0-100% of full scale, set in E.U.
P-n2 Input type: The Input Type is the type of sensor to be
used with the controller in sensing the process vari­able. The Input Type must be correctly programmed into the controller in order for the controller to perform with the selected sensor type. Depending on the type of sensor to be used, the controller comes in two mod­els. One model accepts J, K, R, B, S, T, E, N thermo­couples and RTDs (Pt100). The other model accepts 1­5/0-5V DC and 4-20/0-20mA DC signals. The current/voltage model comes with a 250Ω preci-
Deadband/Overlap
Output OFF
Wide
Hystersis
Output ON
Hystersis
Output OFF
Output ON
Setpoints
Narrow
Prop. Band for Heating X Input Range
100%
Prop. Band for Cooling X Input Range
100%
Deadband/Overlap X Input Range
100%
Input Range= ( minus )
Heating Side
100%
OUTPUT
0%
2
Setpoint TEMP
Setpoint TEMP
Setpoint TEMP
100%
OUTPUT
0%
100%
OUTPUT
0%
Heating Side
Heating Side
# of units in the = Proportional Band for Heating
# of units in the = Proportional Band for Cooling
# of units in the = Deadband/Overlap
Coolng Side
Coolng Side
Coolng Side
<1 =1
>1
Deadband
Overlap
Prop. Band for Heating X Input Range =
Prop. Band for Cooling X Input Range =
Deadband/Overlap X Input Range =
2
2
200%
X
X
14
sion resistor. Wired directly to the controller, it would convert a current signal into a voltage signal. There is no need to use the resistor if a voltage signal is applied directly. After the appropriate physical changes have been made, the controller still needs the correct code for the Input Type to be used. Enter the appropriate code from the Table of Input Type Codes.
P-SL Lower Limit of Input Range: The Lower Limit of Input
Range is that value which establishes the desired low limit for the type of input used. The value must be greater than or equal to the input type’s lowest limit. Setpoint settings are restricted to values greater than the low limit. Parameters which are calculated as a percentage of full scale are affected by this setting. An underscale error message is indicated on the process variable display when the process variable goes below the Lower Limit of Input Range setting by 5% of full scale. The primary purpose of the Lower Limit of Input Range when used with a thermocouple or RTD sensor input is to limit setpoint settings. Making the input range smaller does not increase the accuracy. The primary purpose of the Lower Limit of Input range when used with 1-5/0-5V DC or 4-20/0­20mA DC signal input is to scale the range so that 1/0V DC on a 1-5/0-5V DC signal and 4/0mA DC on a 4-20/0­20mA DC signal equals the low limit of the engineering unit range used. The engineering unit range could be %, PSI, GPM, PH, or any range which can be scaled between -1999 and 9999 units. Enter a value to set Lower Limit of Input range based on the type of input used.
P-SU Upper Limit of Input Range: The Upper Limit of Input
Range is that value which establishes the desired high limit for the type of input used. The value must be less than or equal to the input type’s highest limit. Setpoint settings are restricted to values less than the high limit. Parameters which are calculated as a percent­age of full scale are affected by this setting. An over­scale error message is indicated on the process vari­able display when the process variable goes above
the Upper Limit of Input Range setting by 5% of full scale. The primary purpose of the upper limit when used with a thermocouple or RTD input is to limit set­point settings. Making the input range smaller does not increase the accuracy. The primary purpose of the Upper Limit of Input range when used with 1-5/0-5V DC or 4-20/0-20mA DC signal input is to scale the range so that 5V DC on a 1-5/0-5VDC signal and 20mA DC on a 4-20/0-20mA DC signal equals the high limit of the engineering unit range used. The engineering unit range could be %, PSI, PH, or any range which can be scaled between -1999 and 9999 units.
Enter a value to set Upper Limit of Input range based on the type of input used.
P-dP Decimal Point Position (Resolution): The Decimal
Point
Position is the resolution at which the controller displays the process variable and other parameter val­ues. The display can indicate integers, tenths or hun­dredths of a unit. The Decimal Point Position does not increase the accuracy of the controller, it only increases the resolution. For a thermocouple, integers are usually sufficient due to the accuracy rating and the pro­grammed input range. For a RTD (Pt100), integers or tenths of a degree may be entered, because of the increased accuracy of these sensors, depending on the programmed input range. For a 1-5/0-5V DC or 4-20/0­20mA DC signal, integers, tenths or hundredths of a unit may be entered depending on the programmed input range. Setting: 0 -None 1- Tenths of a unit 2 - Hundredths of a unit
RTD (IEC)
Thermocouple
DC current/ voltage
Pt100 Pt100 Pt100 Pt100 Pt100 Pt100 Pt100 Pt100
J J K K K R B S T T E E N
PL-I I
0-20mA/ 0-5V 4-20mA/ 1-5V
0 to 150 0 to 300 0 to 500 0 to 600
-50 to 100
-100 to 200
-150 to 600
-150 to 850 0 to 400
0 to 800 0 to 400 0 to 800
0 to 1200 0 to 1600 0 to 1800 0 to 1600
-199 to 200
-150 to 400
-0 to 800
-199 to 800
0 to 1300 0 to 1300
Range of
measurement
(°C)
32 to 302 32 to 572 32 to 932
32 to 1112
-58 to 212
-148 to 392
-238 to 1112
-238 to 1562 32 to 752
32 to 1472
32 to 752
32 to 1472 32 to 2192 32 to 2912 32 to 3272 32 to 2912
-328 to 392
-238 to 752 32 to 1472
-328 to 1472
-32 to 2372 32 to 2372
Range of
measurement
(°F)
O O O O O O O X
O O O O X X X X O O O O X
X
With
decimal
point (°C)
O O O X O O X X
O X O X X X X X X X X X X
X
With
decimal
point (°F)
-1999 to 9999
(Scaling is possible)
X =Disabled
O= Enabled
1
2 2 3 3 3 4 5 6 7 7 8 8
12 13
1 1 1 1 1 1 1
15 16
Input Signal
Code
Table of Input Type Codes
SCALING THERMOCOUPLE AND RTD(Pt100) INPUT RANGES
Example:
Program a J thermocouple for 50 to 500°F
Input Type
J Thermocouple
Program to 50 to 500
Full Range = (500-50) = 450 F
27.5 50 500 522.5 5% 5%
Minimum/Maximum Range
32 . . . . . . . . . . . . .1472 °F
Setpoint Range
Indicating Range
SCALING DC CURRENT/VOLTAGE INPUT RANGES
Program a 4-20mA DC signal for 0 to 100 E.U.
Example:
Input Type
4-20mA DC
Program to 0 to 100
Full Range = (100-0) = 100 Engineering Units
-5 0 100 105 5% 5%
Minimum/Maximum Range
-1999 . . . 9999 Enginerring Units
Setpoint Range
Indicating Range
15
P-AH Alarm Type 1: P-AL Alarm Type 2: These functions set the control action
for the optional alarm output relays. They can be pro­grammed for absolute, deviation, combination, or zone alarm configuration. The high and low alarm setpoints are set with primary menu parameters AH and AL (AL is not applicable in the case of PXV3). The absolute alarm configurations are independent of main setpoint. The alarm output relays are energized when the process variable exceeds the alarm setpoint, an absolute value. The deviation alarm configuration is main setpoint tracking. The alarm output relays are energized when the process variable exceeds the main setpoint by a deviation value set by AL or AH. The combination alarm configurations are a mixture of both the deviation and absolute value settings for the high and low alarms. With zone alarm configurations the alarm output is energized between the range set by AL and AH. One of the alarm types is Alarm with Hold. In this case the alarm is not turned on the first time the measured value is in the alarm band. Instead it turns on only when the measured value goes out of the band and enters it again. This type is useful when using devia­tion alarm with step type input. Enter the code for P-AH and P-AL from the Table of Alarm Action Type Codes. See Figues below. P-AL is not applicable in the case of PXV3. Note 1: A change of alarm action type can cause the alarm set value to change, but this is not a malfunction. Note 2: After the alarm type is changed, turn off the power to the unit once.
PVOF Process Variable Offset: The Process variable Offset
is the amount by which the indicated process variable is shifted in a positive or negative direction. Both the indicated as well as the measured process variable will be changed. This parameter can be used to cor­rect for differences in sensors, sensor placement, and standardization problems. Enter a value which is the difference between the measured process value and the actual process value of the system. Setting range: -10 – 10% of full scale, set in Eng. units.
SVOF Setpoint Variable Offset: The Setpoint Variable Offset
is that amount of offset which shifts the measured set­point variable in a positive or negative direction. The measured setpoint variable is changed but the indicat­ed setpoint variable remains unchanged. Be careful when using this variable because what you see as the setpoint variable may be very different from the actual setpoint variable. Setting range: -50 – 50% of full scale, set in Eng. units. Indicated Setpoint Variable is Unchanged Measured Setpoint Variable is Changed
P-F C/F Selection: The C/F Selection allows choosing
either the Celsius or the Fahrenheit scale. If using the controller to control a process other than temperature using the current/voltage input model, the C/F Selection is not important because the scaling is done using the lower limit of the input range and upper limit of input range parameters. If using the thermocouple/RTD (Pt100) input model, however, the C/F Selection is important in scaling the controller’s parameters. Setting: °C or °F
Table of Alarm Action Type Codes—PXW
Table of Alarm Action Type Codes—PXV3
ALM1
Absolute
value alarm
Deviation
alarm
Zone alarm
( )
0
1
2
3
4
5
6
7
8
9
10
11
ALM2
( )
Alarm type Action diagram
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
No alarm
High alarm
Low alarm
High alarm (with hold)
Low alarm (with hold)
High alarm
Low alarm
High/Low alarm
High alarm (with hold)
Low alarm (with hold)
High/Low alarm
(with hold)
High/Low deviation
alarm
(ALM 1/2 independent action)
High/Low
absolute alarm
High/Low
deviation alarm
High absolute/
Low deviation alarm
High deviation/
Low absolute alarm
AH AL
SV
AH AL
SV
AL
AL
Code
( )
Absolute
value alarm
Deviation
alarm
10
Range alarm
11
PV
AH AL
AH AL
AH AL
AH AL
AH AL
AH ALAHAL
SV
AH AL
AH ALAHAL
SV
AH ALAHAL
SV
AHAL
SV
SV
AH
SV
PV
PV
PV
PV
PV
PV
SV
PV
PV
PV
SV
PV
PV
PV
AHAL
PV
PV
AH
PV
Alarm type Action diagram
0
1
2
3
4
5
6
7
8
9
No alarm
Absolute upper limit
Absolute lower limit
Absolute upper limit
(with hold)
Absolute lower limit
(with hold)
Upper limit deviation
Lower limit deviation
Upper and lower
limit deviation
Upper limit deviation
(with hold)
Lower limit deviation
(with hold)
Upper and lower
limit deviation (with hold) Deviation from upper and
lower limit of a range
PV
AH
AH
AH
AH
AH
SV
AH
AHAH
SV
AH
SV
AH
AHAH
SV
AHAH
SV
PV
PV
PV
PV
PV
PV
SV
PV
PV
PV
SV
PV
PV
16
STAT Ramp/Soak Status: The Ramp/Soak program automati-
cally changes the setpoint value with time in accordance with a preset pattern, as shown in the fig­ure. This device allows a maximum of four ramp and four soak segments. Ramp is the region in which SV changes toward the target value. Soak is the region in which the target value is maintained. STAT displays the current ramp/soak status. No setting can be made. oFF: Not in operation 1-rP – 4-rP: Executing 1st – 4th ramp 1-St – 4-St: Executing 1st – 4th soak End: End of program
SV-1 Ramp Target Value: Sets the target value for each ramp
to to segment.
SV-4 Setting range: 0-100% of full scale
TM1r Ramp Segment Time: Sets the duration of each ramp
to to segment.
TM4r Setting range: 00.00 to 99hrs 59mins.
TM1S Soak Segment Time: Sets the duration of each soak
to to segment.
TM4S Setting range: 00.00 to 99hrs 59mins.
Mod Ramp/Soak Mode: Up to 16 different modes of
ramp/soak operations are possible. Choose the appro­priate code from the Table of Ramp/Soak Modes Setting: 0-15
FACTORY PRESET MENU
P-n1 Control Action & Sensor Burn-out Protection: The
Control Action is the direction of the output relative to the process variable. The controller can be pro­grammed for either reverse or direct control action. In a reverse acting controller, the output decreases as the process variable increases. A heating application would require reverse acting control. In a direct acting controller, the output increases as the process vari­able increases. A cooling application would require direct acting control. Enter the code from the Table of Output Type Codes which establishes either a reverse or direct control action.
The Sensor Burn-out Protection is the intended direc­tion of the output in the event of a thermocouple or RTD sensor break, or a break in the analog input. The controller can be programmed with either upper-limit or lower-limit burn-out direction. With Upper-limit Burn-out, a 100% output will be delivered in the event of a sensor burn-out. With Lower-limit Burn-out, 0% output will be delivered in the event of a sensor burn­out. Enter the appropriate code from the Table of Output Type Codes.
Refer to Error Messages for more details.
Time
Fourth Soak
Fourth
Ramp
Third
soak
Second soak
First soak
First ramp
Second
ramp
Third ramp
TM1R TM1S TM2R TM2S TM3R TM3S TM4R TM4S
Set Value
SV3
SV2
SV1
SV4
PV
Ramp: Region in which the setpoint changes toward the target value. Soak: Region in which the setpoint stays unchanged at the target value.
Note 1: SV cannot be changed while the operation is running or suspended. Note 2: The use of fuzzy control is inhibited while Ramp-Soak operation is being performed.
1. Power on Start: Program starts from the current PV value.
2. Output on END: Output condition at the end of the program (rEnd)
3. Output on OFF: Output condition when program is terminated (roFF)
4. Repeat function: Ramp-soak program operates repeatedly. If the repeat function is off, the SV value on the last step is maintained.
Stand-by mode: Output -3%, Alarm off. Going on Control: When program ends (rEnd), control is at the SV value
on the last step. When program is terminated (roFF), control is at the main SV value.
MOD Power on start Output on END Output on OFF Repeat function
0 No Going on control Going on control No 1 No Going on control Going on control Yes 2 No Going on control Stand-by mode No 3 No Going on control Stand-by mode Yes 4 No Stand-by mode Going on control No 5 No Stand-by mode Going on control Yes 6 No Stand-by mode Stand-by mode No 7 No Stand-by mode Stand-by mode Yes 8 Yes Going on control Going on control No
9 Yes Going on control Going on control Yes 10 Yes Going on control Stand-by mode No 11 Yes Going on control Stand-by mode Yes 12 Yes Stand-by mode Going on control No 13 Yes Stand-by mode Going on control Yes 14 Yes Stand-by mode Stand-by mode No 15 Yes Stand-by mode Stand-by mode Yes
Table of Ramp/Soak Modes
17
P-dF Input Filter Constant: The Input Filter is used to filter
out the quick changes that occur to the process vari­able in a dynamic or quick responding application which causes erratic control. By slowing down the response time, the PXW controller averages out the peaks and valleys of a dynamic system which, in turn, stabilizes the control. The digital filter also aids in con­trolling processes where the electrical noise is affect­ing the input signal. The larger the value entered, the more filter added and the slower the controller reacts to process variable changes. The smaller the value entered, the less filter added and the quicker the con­troller reacts to process variable changes. Enter as small a value as possible that provides accurate and stable control. Setting range: 0.0-900.0 secs
P-An Alarm Hysteresis: The Alarm Hysteresis is that area on
one side of the alarm setpoint where the output does not change condition. That area or deadband is intend­ed to eliminate relay chatter at alarm setpoint with less wear on the relay. With a wide Alarm Hysteresis, the controller takes a longer time to change output condi­tion. With a narrow Alarm Hysteresis, the controller takes a short time to change output condition. Enter a value which is just large enough to eliminate relay chatter. Setting Range: 0 to 50% of full scale, set in E.U.
FUZY Fuzzy Logic Control: Employing Fuzzy Logic Control in
addition to PID control eliminates system overshoot and effectively suppresses fluctuation of the process variable due to external disturbances. This function may be enabled even during auto-tuning. Note that fuzzy control is not effective in units with dual outputs, due to the complexity of the process. Fuzzy control is also inhibited while the Ramp/Soak function is in oper­ation.
ADJ0 Input Calibration: This function is used for input cali-
bra-
ADJS tion by the user in a simple manner. Calibration is
effected by first applying the appropriate signal for zero and span points of the input range being used and then by correcting the errors. The user calibration function is an independent function and the instrument can easily be reset to conditions prior to delivery.
Example:
Input range 0-400°C Indication at 0°C : -1°C Indication at 400°C: 402°C Change ADJ0 to 1 and ADJS to -2 to correct the error. The instrument can be set back to factory values by setting ADJ0 and ADJS to 0.
dSP1 Parameter Mask function: This function is used to indi-
to to vidually mask the display of parameters that are not
dSP7 used for your application, or parameters that are not
to be accessed by the operator. To mask or unmask a parameter, appropriate values should be selected from the DSP Assignment table.
Example 1:
To mask parameter P
1) Determine the dSP value for P from Quick Reference P = dSP1 – 128
2) Add 128 to the existing dSP1 value.
Example 2:
To display/unmask the parameter P-F
1) Determine the dSP value for P-F from Quick Reference P-F = dSP4 – 2
2) Subtract 2 from the existing dSP4 value.
Table of Output Type Codes
Code
0 1 2 3
Output type
Single
Control action
Output 1
Output 2
Reverse action
Direct
action 4 5 6
Reverse
action 7 8
10 11 12 13 14 15 16 17 18
9
Dual
Direct action
Reverse
action
Reverse action
Direct action
19
---
Direct action
Burn-out direction
Output 1
Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit
Output 2
---
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Alarm ON
Low Alarm
Setpoint
Alarm OFF Alarm OFF
Low Alarm
Hysteresis
Main
Setpoint
High Alarm
Hysteresis
Alarm ON
High Alarm
Setpoint
18
APPENDIX A
Autotuning
By autotuning, the controller selects what it calculates to be the opti­mal PID control parameters for a particular process and then stores them in EEPROM memory for future use. The PID parameters are stored so that when the controller is powered up after being shut down, the controller does not need to be autotuned again. The con­troller uses the same autotuned PID parameters until the Autotune function is again initiated. The Autotune parameters are only good for the process the Autotune function was used on. If the setpoint is sig­nificantly changed, the input sensor is changed, the load or output device is changed or relocated, or any other disturbances occur which might change the dynamics of the system, the Autotune func­tion should be performed again. The autotuned control parameters are not always perfect for every application but almost always give the operator a good starting point from which further refinement of the control parameters can be performed manually.
The autotuning algorithm used here is particularly suited for tempera­ture control applications and may not always autotune effectively for other processes. Here are cases where the Autotune function does not perform well or does not perform at all:
1. The system is affected by process disturbances external to the con­trol loop. Adjacent heater zones, changing material levels, exother­mic reactions are examples of process disturbances which are external to the control loop. The controller would never be able to autotune such an unstable process.
2. The system is very dynamic. The process variable changes very quickly. Certain pressure and flow applications would be charac­terized as very dynamic. Because of how the Autotune function is performed, a very dynamic system would create very large over­shoots which could damage the process.
3. The system is very insulated and cannot cool down in a timely man­ner. With such heating systems the autotuning function would take a long time to complete, with questionable results.
During autotuning test signals are sent to the process. The test sig­nals are 100% output and 0% output at the Autotune point. The Autotune point can either be at setpoint or 10% of full scale below setpoint. The controller performs as an On/Off controller. See diagram below.
ERROR MESSAGES
Error Indication Cause Control Output
1. Thermocouple burnt out. When the burn-out
2. RTD (A) leg burnt out. control output is set for
3. PV value exceeds P-SU lower limit (standard): by 5% FS. OFF, or 4mA or less.
1. When RTD (B or C) is When the burn-out burnt out. control output is set for
2. When RTD (between upper limit: ON, or 20mA A and B, or between or less. A and C) is shorted.
3. When PV value is below P-SL by 5% FS.
4. When analog input wiring is open or short.
When PV value goes below Control is continued until
-1999. the value reaches -5% FS
or less, after which burn­out condition will occur.
HB lamp ON Heater break condition Normal control output for
heating is continued.
When the setting of OFF, or, 4mA or less. P-SL/P-SU is improper
Fault in the unit Undefined. Stop use
immediately.
Autotune
Point
Process Variable
100%
ON ON ONOFF OFF
Output
0%
Autotune Period
Time
Time
19
The controller then reads the reaction of these test signals on the process. Keep in mind that every process is different and therefore every reaction to the test signals is different. This is why PID parame­ters are not the same for all processes. The amplitude (L) or lag time which is the overshoot and undershoot of the system when autotun­ing, and the time constant (T) which is the time the process takes to go through one On/Off cycle are measured. See diagram below.
The measurements are then used with the Autotune algorithm for cal­culation of the proper PID parameters for the system, as shown below, where K is the proportionality constant and S is the Laplace operator.
K
e
-LS
(1+TS)
APPENDIX B
Manual Tuning
Tune the controller if any of the following occurs:
The controller is installed in a new system
The controller is used as a replacement in an existing system
The input sensor is relocated or changed
The output device is relocated or changed
The setpoint is significantly changed
Any other condition that will alter the dynamics of the system
Proportional Band
The proportional band is a band around the setpoint of the PXW where the output is between 0% and 100%. The percentage of output is pro­portional to the amount of error between the setpoint variable (SV) and the process variable (PV). Outside of the proportional band the output is either 0% or 100% The proportional band on PXV3/PXW is equidistant from the main set­point as illustrated below.
An example of proportioning would be a vehicle approaching a stop sign at an intersection. If the driver were traveling at 50mph and only applied his brakes once at the intersection, his car would skid through the intersection before coming to a full stop. This illustrates how On/Off control acts. If, however, the driver started slowing down some distance before the stop sign and continued slowing down at some rate, he could conceivably come to a full stop at the stop sign. This illustrates how proportional control acts. The distance where the speed of the car goes from 50 to 0 MPH illustrates the proportional band. As you can see, as the car travels closer to the stop sign, the speed is reduced accordingly. In other words, as the error or distance between the car and the stop sign becomes smaller, the output or speed of the car is proportionally diminished. Figuring out when the vehicle should start slowing down depends on many variables such as speed, weight, tire tread, and braking power of the car, road condi­tions, and weather much like figuring out the proportional band of a control process with its many variables.
The width of the proportional band depends on the dynamics of the system. The first question to ask is, how strong must my output be to eliminate the error between the setpoint variable and process vari­able? The larger the proportional band (low gain), the less reactive the process. A proportional band too large, however, can lead to process wandering or sluggishness. The smaller the proportional band (high gain), the more reactive the output becomes. A proportion­al band too small, however, can lead to over-responsiveness leading to process oscillation.
A proportional band which is correct in width approaches main set­point as fast as possible while minimizing overshoot. If a faster approach to setpoint is desired and process overshoot is not a prob­lem, a smaller or narrower proportional band may be used. This would establish an over-damped system or one where the output would change greatly, proportional to the error. If process overshoot cannot be tolerated and the approach to setpoint does not have to be quick, a larger or wider proportional band may be used. This would establish an under-damped system or one where the output would change little, proportional to the error.
To Calculate Proportional Band:
Proportional Band Proportional Band (as a percentage) =
____________________
X 100%
Input Range
Example:
30°C
3% =
__________
X 100%
100°C
Proportional Band
(as a percentage)
Proportional Band Range =
____________________
X 1000°C
100%
Example:
3%
30°C =
__________
X 1000°C
100%
Time Constant
Overshoot
Amplitude
Undershoot
Time
OFF
Time
ON
100%
Output
0%
Reverse Action
PB
PV
Main Setpoint
100%
Output
0%
Direct Action
PB
PV
Main Setpoint
Time
PV
Proportional Band
with Correct Width
Time
PV
Proportional Band
Too Small
Time
PV
Proportional Band
Too Large
20
Integral Time
With the proportional band alone, the process tends to reach equilib­rium at some point away from the main setpoint. This offset is due to the difference between the output needed to maintain setpoint and the output of the proportional band at setpoint. SInce the proportional band is equidistant from the main setpoint, the output is around 50%. If anything more or less than 50% output is required to maintain set­point, an offset error will occur. Integral action eliminates this offset. See the diagrams below.
Integral action eliminates offset by adding to or subtracting from the output of the proportional action alone. This increase or decrease in output corrects for offset error within the proportional band in estab­lishing steady-state performance at setpoint. It is not intended to cor­rect for process disturbances. See the following diagram.
Integral Time is the speed at which the controller corrects for offset. A short integral time means the controller corrects for offset quickly. If the integral time is too short, the controller would react before the effects of previous output shifts–due to lead or lag time– could be sensed, causing oscillation. A long Integral time means the control corrects for offset over a long time. If the integral time is too long, the offset will remain for some time causing a slow responding or slug­gish control. See the diagram below.
Derivative Time
In the case of a process upset, proportional only or proportional-inte­gral action cannot react fast enough in returning a process back to setpoint without overshoot. The derivative action corrects for distur­bances providing sudden shifts in output which oppose the diver­gence of the process from setpoint. See the diagram below.
The derivative action changes the rate of reset or integration propor­tional to the rate of change and lag time of the system. By calculating the rate of change of the process and multiplying it by the lag time which is the time it takes the controller to sense an output change, the controller can anticipate where the process should be and change the output accordingly. This anticipatory action speeds up and slows down the effect of proportional only and proportional-integral actions to return a process to setpoint as quickly as possible with minimum overshoot. See the diagram below.
Derivative time is the amount of anticipatory action needed to return a process back to setpoint. A short derivative time means little deriva­tive action. If the derivative time is too short, the controller would not react quickly to process disturbances. A long derivative time means more derivative action. If the derivative time is too large, the con­troller would react too dramatically to process disturbances creating rapid process oscillation. A process which is very dynamic such as pressure and flow applications is more efficiently controlled if the derivative action is turned off because of the oscillation problem which would result.
Tuning
Tuning, as with any PID loop, requires tuning each parameter sepa­rately and in sequence. To achieve good PID control manually, you can use the trial and error method explained below.
Tune the Proportional Band
Set Integral Time = 0 (off)
Set Derivative Time = 0 (off) Start with a large Proportional Band value which gives very sluggish control with noticeable offset and tighten by decreasing the value in half. Analyze the process variable. If the control is still sluggish, tight­en by decreasing the value in half again. Continue with the same pro­cedure until the process starts to oscillate at a constant rate. Widen the Proportional Band by 50%, or multiply the setting 1.5 times. From a cold start, test and verify that the Proportional Band allows maximum rise to setpoint while maintaining minimum overshoot and offset. If not completely satisfied, fine-tune the value, up or down, as needed and test until correct. The Proportional Band is now tuned.
Add Integral Time
Start with a large Integral Time value which gives very sluggish response to process offset and tighten by decreasing the value in half. Analyze the process variable. If the response to process offset is still sluggish, tighten by decreasing the value in half again. Continue with the same procedure until the process starts to oscillate at a con­stant rate. Increase the Integral Time value by 50%, or multiply the setting 1.5 times. From a cold start, test and verify that the Integral Time allows maximum elimination of offset with minimum overshoot. If not completely satisfied, fine-tune the value, up or down, as needed and test until correct. The Integral Time is now tuned.
Rate of Change X Lag Time= Anticipated Process Variable
0%
Main Setpoint
PV
100%
Output
Setpoint
PV
Short Integral Time
Output
Proportional Action Only
Offset
Time
Long Integral Time
Time
PV
Time
21
Add Derivative Time
Do not add Derivative Time if the system is too dynamic. Start with a small Derivative Time value which gives sluggish response to process upsets and double the value. Analyze the process variable. If the response to process upsets is still sluggish, double the value again. Continue with the same procedure until the process starts to oscillate at a quick constant rate. Decrease the Derivative Time value by 25%. From a cold start, test and verify that the Derivative Time value allows maximum response to process disturbances with minimum overshoot. If not completely satisfied, fine-tune the value, up or down, as needed and test until correct. Note that the Derivative Time value is usually somewhere around 25% of the Integral Time value. The derivative Time is now tuned.
Another tuning method is the closed-loop cycling or Zeigler-Nichols method. According to J.G. Zeigler and N.B. Nichols, optimal tuning is achieved when the controller responds to a difference between set­point and the process variable with a 1/4 wave decay ratio. That is to say that the amplitude of each successive overshoot is reduced by 3/4 until stabilizing at setpoint. The procedure is explained below.
1. Integral Time=0 Derivative Time=0
2. Decrease the Proportional Band to the point where a constant rate of oscillation is obtained. This is the response frequency of the system. The frequency is different for each process.
3. Measure the Time Constant which is the time to complete one cycle of the response frequency. The Time Constant will be defined as
“T” when calculating Integral and Derivative Times.
4. Widen the Proportional Band until only slightly unstable. This is the Proportional Band’s Ultimate Sensitivity. The Proportional Band’s Ultimate Sensitivity width will be defined as “P” when calculating the actual Proportional Band.
5. Use the following coefficients in determining the correct PID set-
tings
for your particular application.
P Only 2P * *
PI 2.2P .83T *
PID 1.67P .5T .125T
APPENDIX C
Heater Break Option
The Heater Break Option is used to detect heater break conditions and to energize an alarm relay when such conditions exist. In most cases, the option is used to detect the failure of one or more zones in a multi­zoned heater where all individual resistive heater zones are wired in parallel. Failed heater zones would create cold spots in a system which could hamper the process and even ruin the product. If cold spots in a system are a problem, the Heater Break option is an effective way of alerting the operator of a heater break condition, a cause of cold spots.
The PXW controller is able to detect a heater problem by analyzing the current used by the heater. The actual sensing is done by a current sensing transformer, sold separately, which is placed around the hot lead going to the heater and connected to the controller. The signal sent by the current sensing transformer is timed with the output of the PXW. When the output is energized the signal sent from the current sensing transformer is analyzed. When the output is de-energized the signal sent from the current sensing transformer is not analyzed. This eliminates the alarm condition turning on and off due to the output con­dition of the controller. If the signal sent when the output is energized indicates that the current level is below what the Heater Break alarm is set for, the alarm is energized. The alarm is non-latching.
Notes:
1. The Heater Break Option is available on the PXW-5, 7, and 9 controllers only.
2. The Heater Break Option cannot be used on the PXW controller with a 4-20mA DC output. The current sensing transformer would pick up current changes due to fluctuating power output, between 0% and 100%, which would result in a heater break alarm condition even though no such condition existed.
3. The Cycle Time must be set at 6 secs. or higher in order for the controller to correctly analyze the signal sent by the current sensing transformer.
4. The power supply used should be the same for the PXW and heater to eliminate current fluctuations due to power differences between different power supplies.
Wiring and Setting:
1. Choose the correct current sensing transformer based on the maxi­mum current usage of the heater. 0 - 30 Amps (part # CTL-6-SF) 20 - 50 Amps (part # CTL-12-S36-8F)
2. Thread the hot lead going to the heater through the donut of the cur­rent sensing transformer. Connect the wires of the current sensing trans former to the current sensing transformer input terminals in the back of the controller.
Connection to PXW (Polarity not important)
Hot lead to Heater
Control P I D
Action Setting Setting Setting
Time
Constant
PV
Time
22
3. Set Heater Break alarm setpoint parameter, “Hb”. With the current sensing transformer connected and the heater in operation (output energized), change the Heater Break Alarm set­ting from the maximum current setting for the particular current sensing transformer being used to a lower value. Allow 3 secs. or more between setting changes. Continue lowering the setting until the relay is energized and the “HB” status indicator is lit. This is the maximum current usage of the heater. Using the same proce­dure, find the maximum current usage of the heater minus one zone. Set the setpoint in between the two current readings. In this way, the opera­tor knows if one or more zones fail because the current sensed will only be below the Heater Break Alarm setting if one or more zones fail.
db Deadband/Overlap: Deadband is that area where neither
outputs are energized. Overlap is that area when both out­puts are energized. This function lets you decide where you want the heating action to stop and the cooling action to begin.
Notes:
1. The Heat/Cool Option is available on the PXW-5, 7, and 9 con­trollers only. Output #2 type can be the same or different than Output #1 type (Relay, SSR driver, or 4-20mA DC)
2. Integral and Derivative Times are the same for both the heating and cooling sides of a process with PID control because the response frequency or time constant of the system does not change at main setpoint when cooling is added.
3. The Proportional Band for heating and cooling are almost always different. Rarely does the same amount of cooling output remove the same percentage of process error as the heating output does. The Cooling Proportional Band must be manually and separately tuned.
4. If the heating side is set for On/Off control, the cooling side will be set for On/Off control also. Regardless of what the COOL parame­ter is set for, if the Proportional Band is set to zero, the Heating Proportional Band and the Cooling Proportional Band will always be zero or On/Off.
5. If the cycle times of one or both outputs are long and the process dynamic, there is a good chance that both outputs will be cycling on and off at the same time around main setpoint. This is evident if one or both outputs are relays.
6. Autotune is not effective on the cooling side of Heat/Cool control.
Autotune the controller for heat only and then manually tune the cooling parameters.
Wiring and Setting
1. Make sure that your PXW has the correct output type installed for Output #2. Verify that the TC2, COOL, and DB parameters are indi­cated in the primary (setpoint) menu.
2. Wire your cooling load to the Output #2 terminals located on the back of your PXW controller.
3. In the secondary (system) menu, program the correct code for Heat/Cool action. See Table of Output Type Codes.
4. In the primary (setpoint) menu, program TC2, the cycle time for Output #2. The table below is a general guide to TC2 settings.
5. Autotune or manually tune the PID parameters of your PXW con­troller. Autotune will work for the heating PID parameters but not on the cooling parameters. You must manually tune the cooling para­meters.
6. With the heat side tuned, manually set the COOL parameter or Proportional Band Coefficient for Cooling. If the cooling output is
APPENDIX D
Heat/Cool Option
With the Heat/Cool Option, the PXW can control a temperature applica­tion with one input at one main setpoint using two outputs, a heating output and a cooling output. By using a heating and cooling output, a process is able to quickly bring the temperature to setpoint in both directions and to limit the amount of overshoot. The larger the deviation from setpoint, the more output applied to the system on both the heat­ing and cooling sides. Heat/Cool control is a very effective way of con­trolling exothermic processes, processes that generate their own heat, or processes where ambient temperature is not adequate or fast enough in returning a process back to setpoint.
The two outputs on the PXW are independent and sent to two different output devices. The PXW can be equipped with two of the same or two different output types. Output #2 can be relay, SSR driver, or 4-20mA DC, regardless of what Output #1 is. Both output types must be speci­fied when ordering.
The PXW controls the cooling side with three additional parameters, TC-2, COOL, and DB as explained in the programming section.
TC2 Cycle Time (Output #2): Because Output #2 is not nec-
essarily the same as Output #1, the cycle time may be different.
CooL Proportional Band Coefficient for Cooling:
Because the cooling power may not necessarily be the same as the heating power, the cooling proportional band may be different from that of the heating proportional band.
Relay 30
SSR Driver (pulsed DC) 2
4-20mA DC Not indicated or 0
Output#2 Type Setting(Secs)
Power Supply
Main
Output
8 9
5 7
17
4
15
Alarm Output
16
+
18
1
2
Current Sensing Transformer
Input Sensor
Heater
23
less powerful than the heating output, the Cooling Proportional Band must be narrower than the Heating Proportional Band; the COOL parameter would be less than “1”. If the cooling output is more powerful than the heating output, the Cooling Proportional Band must be wider than the Heating Proportional Band; the COOL parameter would be more than “1”. See the programming section for more details.
7. Finally, you can add a Deadband/Overlap. The programmed Deadband/
Overlap parameter can be within -50% to +50% of the Heating Proportional band. To establish a Deadband, parameter “db” is set somewhere between 0% and 50% of the Heating Proportional band. To establish an Overlap, db is set somewhere between -50% and 0% of the Heating Proportional Band.
8. Manually fine-tune the parameters, CooL and db, until just the right amount of cooling is achieved. Refer to the programming section for more details on these parameters.
Heating Side Cooling SIde
Heating Proportional Band Cooling Proportional Band
[P/2] [P/2 COOL]
I I (same as for heating)
D D (same as for heating)
Heating Side Cooling Side
24
Parameter Range Description Default DSP
settings settings
roFF - rHLd roFF/rrUn/rHLd Ramp/soak command roFF dSP1-1
AH 0 - 100%FS High Alarm Setpoint 10 dSP1-2
* AL* 0 - 100%FS Low Alarm Setpoint 10 dSP1-4
Hb 0.0 - 50.0A Heater break alarm S.P. 0.0 dSP1-8 AT 0 - 2 Auto-tuning 0 dSP1-16 LoC 0 - 2 Lock-out 0 dSP1-32
Secondary Menu
P 0.0 - 999.9%FS Proportional band 5.0 dSP1-128 I 0 - 3200sec Integral time 240 dSP2-1 D 0.0 - 999.9sec Derivative time 60 dSP2-2 TC 1 - 150sec Cycle Time (output #1) dSP2-4 HYS 0 - 50%FS Hysteresis 1 dSP2-8 TC2 1 - 150sec Cycle Time (output #2) dSP2-16 CooL 0.0 - 100.0 Proportional band 1.0 dSP2-32
coefficient for cooling db -50.0 - 50.0%FS Deadband/Overlap 0.0 dSP2-64 bAL 0 - 100% Balance 0.0/50.0 dSP2-128 Ar 0 - 100%FS Anti-reset wind-up 100%FS dSP3-1 P-n2 0 - 16 Input type code dSP3-2 P-SL -1999 - 9999 Lower range of input 0%FS dSP3-4
P-SU -1999 - 9999 Upper range of input 100%FS dSP3-8 P-dP 0 - 2 Decimal point position 0 dSP3-16 P-AH 0 - 11 Alarm Type 1 code 5 dSP3-32
* P-AL* 0 - 15 Alarm Type 2 code 9 dSP3-64
PVOF -10 - 10%FS PV offset 0 dSP3-128 SVOF -50 - 50%FS SV offset 0 dSP4-1 P-F °C/°F °C/°F selection dSP4-2 STAT -- Ramp/soak status oFF dSP4-4 SV-1 0 - 100%FS 1st S.P. 0%FS dSP4-8 TM1r 0 - 99hr 59min 1st ramping time 0.00 dSP4-16 TM1S 0 - 99hr 59min 1st soaking time 0.00 dSP4-32 SV-2 0 - 100%FS 2nd S.P. 0%FS dSP4-64 TM2r 0 - 99hr 59min 2nd ramping time 0.00 dSP4-128 TM2S 0 - 99hr 59min 2nd soaking time 0.00 dSP5-1 SV-3 0 - 100%FS 3rd S.P. 0%FS dSP5-2 TM3r 0 - 99hr 59min 3rd ramping time 0.00 dSP5-4 TM3S 0 - 99hr 59min 3rd soaking time 0.00 dSP5-8 SV-4 0 - 100%FS 4th S.P. 0%FS dSP5-16 TM4r 0 - 99hr 59min 4th ramping time 0.00 dSP5-32 TM4S 0 - 99hr 59min 4th soaking time 0.00 dSP5-64 MOD 0 -15
Ramp/soak Mode code 0 dSP5-128
PXW/PXV3 QUICK REFERENCE
Primary Menu
* Not applicable to PXV3 † Based on the model
Factory Preset Menu
Parameter Range Description Default DSP
settings settings
P-n1 0 -19 Control Action code dSP6-2 P-dF 0.0 - 900.0sec Input Filter Constant 5.0 dSP6-4 P-An 0 - 50%FS Alarm Hysteresis 1 dSP6-8 rCJ - N/A ON dSP6-16 PLC1 - N/A -3.0 dSP6-32 PHC1 - N/A 103.0 dSP6-64 PLC2 - N/A -3.0 dSP6-128 PHC2 - N/A 103.0 dSP7-1 PCUT - N/A 0 dSP7-2 FUZY OFF/ON Fuzzy control OFF dSP7-4 GAIN - N/A 1 dSP7-8 ADJ0 - Zero calibration 0 dSP7-16 ADJS - Span calibration 0 dSP7-32 OUT - N/A -3.0 dSP7-64
dSP1-7 0-255 Parameter mask -
HB
H
L
Loading...