Thank you for purchasing Fuji Electric Programmable Controller MICREX-SX SPF Series.
This User’s Manual describes the hardware specications of the SPF series.
Read this manual carefully to ensure correct operation and also read the corresponding user’s manuals listed below.
TitleManual No. Contents
User’s Manual Instructions (Standard),
MICREX-SX series SPF
User’s Manual Instructions (Standard),
MICREX-SX series SPH
User’s Manual Instructions (Expert),
MICREX-SX series SPF
User’s Manual Instructions (Expert),
MICREX-SX series SPH
User’s Manual Analog Unit,
MICREX-SX series SPF
User’s Manual Built-in High-Speed Counter,
MICREX-SX series SPF
User’s Manual
General Purpose Communication,
MICREX-SX series SPF
User’s Manual Pulse Output Instructions,
MICREX-SX series SPF
User’s Manual SX-Programmer Standard
<Reference>, MICREX-SX series
User’s Manual SX-Programmer Expert
(D300win) <Reference>, MICREX-SX series
FEH524
FEH588
FEH525
FEH200
FEH527
FEH534
FEH528
FEH529
FEH598
FEH257
Describes the memory specications and instructions specic to
the SPF series (Standard).
Describes the memory, language and system denitions of the
MICREX-SX series SPH (Standard).
Describes the memory specications and instructions specic to
the SPF series (Expert).
Describes the memory, language and system denitions of the
MICREX-SX series SPH (Expert).
Describes the specications and operations of analog input/output
units of the MICREX-SX series SPF.
Describes the specications and operations of the high-speed
counter built in the main unit of the MICREX-SX series SPF.
Describes the specications of general purpose communication
(RS-232C/RS485) units/boards of the MICREX-SX series SPF
and how to create applications.
Describes the specications and operations of the high-speed
pulse output and high-speed positioning functions built in the main
unit of the MICREX-SX series SPF.
Describes the functions and the operations of SX-Programmer
Standard V3.
Describes the functions and the operations of SX-Programmer
Expert (D300win) V3.
* In addition to the above manuals, the following Fuji Electric Co.,Ltd.site offers various manuals and technical documents
associated with MICREX-SX series.
URL http://www.fujielectric.com
Notes
1. This manual may not be reproduced in whole or part in any form without prior written approval by the manufacturer.
2. The contents of this manual (including specifications) are subject to change without prior notice.
3. If you find any ambiguous or incorrect descriptions in this manual, please write them down (along with the manual No.
shown on the cover) and contact FUJI.
Safety Precautions
: Incorrect handling of the device may result in minor injury or physical damage.
Be sure to read the "Safety Precautions" thoroughly before using the module.
Here, the safety precautions items are classied into "Warning" and "Caution".
Warning
: Incorrect handling of the device may result in death or serious injury.
Caution
Even some items indicated by "Caution" may result in a serious accident.
Both safety instruction categories provide important information. Be sure to strictly observe these instructions.
Warning
Neve touch any part of charged circuits as terminals and exposed metal portion while the power is turned ON.
It may result in an electric shock to the operator.
Turn OFF the power before mounting, dismounting, wiring, maintaining or checking, otherwise, electric shock, erratic
operation or troubles might occur.
Place the emergency stop circuit, interlock circuit or the like for safety outside the PLC. A failure of the PLC might break
or cause problems to the machine.
When using an expansion right side unit, be sure to mount a healthy unit to stop the SPF system with a fatal fault if the
expansion right side unit is dropped. Unless a healthy unit is mounted, a dropout of the expansion right side unit is not
detected and the SPF system continues operation in the state where the expansion right side unit is dropped.
Safety Precautions
Caution
Do not use one found damaged or deformed when unpacked, otherwise, fire, failure or erratic operation might be caused.
Do not shock the product by dropping or tipping it over, otherwise, it might be damaged or troubled.
Follow the directions of the instruction manual and user’s manual when mounting the product.
If mounting is improper, the product might drop or develop problems or erratic operations.
Use the rated voltage and current mentioned in the instruction manual and user’s manual. Use beyond the rated values
might cause fire, erratic operation or failure.
Operate (keep) in the environment specified in the instruction manual and user’s manual. High temperature, high humidity,
condensation, dust, corrosive gases, oil, organic solvents, excessive vibration or shock, might cause electric shock, fire,
erratic operation or failure.
Select a wire size to suit the applied voltage and carrying current. Tighten the wire terminals to the specified torque.
Inappropriate wiring or tightening might cause fire, malfunction, failure or might cause the product to drop from its
mounting.
Contaminants, wiring chips, iron powder or other foreign matter must not enter the device when installing it, otherwise, fire,
accident, erratic operation or failure might occur.
Remove the dust-cover seals of modules after wiring, otherwise, fire, accident, erratic operation or failure might occur.
Connect the ground terminal to the ground, otherwise, electric shock or erratic operation might occur.
Periodically make sure the terminal screws and mounting screws are securely tightened.
Operation at a loosened status might cause fire or erratic operation.
Put the furnished connector covers on unused connectors, otherwise, erratic operation or failure might occur.
Sufficiently make sure of safety before program change, forced output, starting, stopping or anything else during a run.
Wrong operation might break or cause problems to the machine
Engage the loader connector in a correct orientation, otherwise, an erratic operation might occur.
Before touching the PLC, discharge any static electricity that may have been collected on your body. To discharge it, touch
a grounded metallic object. Static electricity might cause erratic operation or failure.
Be sure to install the electrical wiring correctly and securely, observing the directions of the instruction manual and user’s
manual. Wrong or loose wiring might cause fire, accident or failure.
When disengaging the plug from the outlet, do not pull the cord, otherwiase, break of cable might cause fire or failure.
Do not attempt to change system configurations (such as installing or removing expansion block) while the power is ON,
otherwise, failure or erratic operation might occur.
Do not attempt to repair the module by yourself, but contact your Fuji Electric agent, otherwise, fire, accident or failure
might occur.
To clean the module, turn power off and wipe the module with a cloth moistened with warm water. Do not use thinner or
other organic solvents, as the module surface might become deformed or discolored.
Do not remodel or disassemble the product, otherwise, failure might occur.
Follow the regulations of industrial wastes when the device is to be discarded.
The products covered in this user’s manual have not been designed or manufactured for use in equipment or systems
which, in the event of failure, can lead to loss of human life.
Do not use the products covered in this user’s manual for special applications, such as power plant, radiation facilities,
railroad, space/flight equipments, lifeline facilities, or medical equipments, where a great effect on human life, body,
society, major property or rights may be anticipated and high degree of safety is required.
Be sure to provide protective measures when using the products covered in this manual in equipment which, in the event
of failure, can lead to loss of human life or other grade results.
External power supply (such as 24 V DC power supply) which is connected to DC I/O should be strongly isolated from AC
power supply, otherwise, accident or failure might occur. (Use of EN60950 conforming power supply is recommended.)
Do not use the peoducts covered in this user’s manual in a residential environment.
Revision
* The manual No. is printed at the bottom right of the cover of this manual.
Oct. 2017FEH526c• The specications of new models were added.
(NA3LA-ET1, NA0LA-ET1, NA0FA-LC1)
• The description of a memory pack was added.
• The contents were revised.
Contents
Preface
Safety Precautions
Revision
Contents
Section 1 Overview
1-1 Features .............................................................................................................................................1-1
1-1-1 Overview of system conguration .................................................................................................................1-1
1-1-2 Function list ...................................................................................................................................................1-2
1-2 Type Code .......................................................................................................................................... 1-3
1-3 Product Type List ................................................................................................................................1-5
1-4-1 Program loader version .................................................................................................................................1-7
1-4-2 Main unit version ...........................................................................................................................................1-7
Section 2 System Conguration
2-1 System Conguration Specications ..................................................................................................2-1
2-1-2 Calculation of current consumption ...............................................................................................................2-3
2-2 System denition ................................................................................................................................2-7
2-3-1 Rules for assigning I/O addresses ................................................................................................................2-8
2-3-2 Example of address assignment ...................................................................................................................2-9
Section 3 Specications
3-1 General Specications .......................................................................................................................3-1
3-2 Main Unit Specications .....................................................................................................................3-2
3-3 Power supply specications ...............................................................................................................3-4
3-3-1 AC power supply type ...................................................................................................................................3-4
3-3-2 DC power supply type ...................................................................................................................................3-4
3-4-1 DC input specications..................................................................................................................................3-5
3-5-3 Output device protection and noise suppression in DO circuit......................................................................3-12
3-6 Analog Unit/Board Specications .......................................................................................................3-15
3-6-1 Analog input unit (NA0AX06-MR) .................................................................................................................3-15
3-6-2 Analog output unit (NA0AY02-MR) ...............................................................................................................3-16
3-6-3 Analog input/output unit (NA0AW06-MR) .....................................................................................................3-17
3-6-4 Analog output board (NA3AY02-MR) ............................................................................................................3-19
3-6-5 Analog input/output board (NA3AW03-MR) ..................................................................................................3-20
3-6-6 Thermocouple input unit (NA0AX02-TC/NA0AX06-TC/NA0AX16-TC) .........................................................3-21
3-6-7 Resistance thermometer element input unit (NA0AX06-PT).........................................................................3-24
3-7 Communication Unit/Board Specications .........................................................................................3-25
3-7-1 RS-232C/RS-485 general purpose communication board (NA3LA-RS1) .....................................................3-25
3-7-2 RS-232C general purpose communication unit (NA0LA-RS3) .....................................................................3-26
Contents
3-7-3 RS-485 general purpose communication unit (NA0LA-RS5) ........................................................................3-27
3-7-4 Ethernet communication board (NA3LA-ET1) / Ethernet communication unit (NA0LA-ET1) .......................3-28
3-8 Function Unit Specications ...............................................................................................................3-29
3-8-1 Load cell unit (NA0F-LC1).............................................................................................................................3-29
3-8-2 High-precision load cell unit (NA0FA-LC1)....................................................................................................3-31
3-9 Temperature derating of main unit .....................................................................................................3-32
3-10-1 Main unit .....................................................................................................................................................3-34
3-10-2 Expansion unit ............................................................................................................................................3-37
3-11 Names and Functions ......................................................................................................................3-39
3-11-1 Main unit .....................................................................................................................................................3-39
3-11-2 Expansion unit ............................................................................................................................................3-42
3-12-1 Main unit .....................................................................................................................................................3-44
3-12-2 Expansion unit ............................................................................................................................................3-46
3-13 Mass ................................................................................................................................................. 3-49
4-1-2 Before installation..........................................................................................................................................4-2
4-1-3 Control panel mounting (protection against noise)........................................................................................4-3
4-1-4 Environmental condition for mounting PLC on panel ....................................................................................4-5
4-2-1 Wiring and cables..........................................................................................................................................4-12
4-2-2 Wiring to power-supply, I/O and ground terminals ........................................................................................4-13
Section 5 Maintenance and Inspection
5-1 General Inspection Items ...................................................................................................................5-1
5-1-1 Inspection frequency .....................................................................................................................................5-1
5-1-2 Cautions on using the product ......................................................................................................................5-1
5-3-2 Free-of-charge warranty period and scope of warranty ................................................................................5-4
5-3-3 Service costs .................................................................................................................................................5-4
Appendix 1 Installing USB Driver ..............................................................................................App.1-1
Appendix 2 Automatic Update of System Software .................................................................App.2-1
Section 1 Overview
1-1 Features .................................................................................................... 1-1
1-1-1 Overview of system conguration ...............................................................1-1
1-1-2 Function list ................................................................................................1-2
1-2 Type Code ................................................................................................. 1-3
(1) Main unit ..................................................................................................... 1-3
(2) DIO expansion unit (expansion right side unit) ........................................... 1-3
(3) Analog unit (expansion right side unit) ....................................................... 1-3
(4) Function unit (expansion right side unit) ..................................................... 1-4
(5) Analog board .............................................................................................. 1-4
(6) Communication board ................................................................................ 1-4
(7) Communication unit (expansion left side unit) ............................................ 1-4
(8) Function unit (expansion left side unit) ....................................................... 1-4
(9) Expansion power supply unit ...................................................................... 1-4
1-3 Product Type List ..................................................................................... 1-5
1-4-1 Program loader version .............................................................................. 1-7
1-4-2 Main unit version ........................................................................................1-7
Section 1 Overview
• Expansion power supply unit
1-1 Features
1-1-1 Overview of system conguration
The SPF series units are small controllers equipped with excellent functions comparable to medium-sized controllers and
maximum ve communication ports.
Various types of expansion units are available. One unit can be connected on the front of or on the left side of the main unit and
six units on the right side. In addition, interface options such as RS-232C, RS-485, and Ethernet enable you to use peripheral
communication devices.
PORT4 (RS485)
+
G
TNN
PORT3 (RS485)
+
G
T
NA0LA-RS5
Front board
* Mounted on the front of the main unit.
• Communication board
• Analog board
Main unit
Expansion right side unitExpansion left side unit
X12X10
24V OUT
S/S
AC100~240V
C0
X0
X1 X3
PORT0
Y2
Y0
C2
max.
400mA
TX
RX
TX
RX
IN
X8
X4X2
X6
X5 X7
RXTX
Y4
Y3
C4 C6
X11 X13
X9
Y5
Y6Y1
SINK
Y8
SRCE
Y7
Y9
Y1Y2C2 C4C0
Y0
Y10Y8Y11 Y12 Y14
Y9C8C10 C12 Y13 Y15
Y3 Y4 Y6
Y5 Y7
• Communication unit
• High-accuracy load cell unit
• Advance main unit
(High-speed counter, positioning function)
2) PLS: Single pulse output mode, PWM: PWM output mode
3) The backup time is 10 years or more (ambient temperature: 55°C)
4) Notes on rewriting programs
When rewriting the program in the main unit from the loader while the PLC is running, the built-in RAM is changed,
however, the built-in ash memory is unchanged. As a result, the contents of the RAM does not match those of the ash
memory and the RUN/MEM LED blinks to prompt the user to transfer the contents of the RAM to the ash memory.
After rewriting the program, be sure to transfer the contents of the RAM to the ash memory. When the transfer is
completed normally, the RUN/MEM LED turns OFF.
<Method 1>
Perform transfer by using the loader.
<Method 2>
After rewriting the program, turn OFF the main unit and then ON again. When the power supply is turned ON, the contents
of the RAM is automatically transferred to the ash memory.
ZIP leBuilt-in ash memory
Data memoryBuilt-in RAM: Built-in lithium primary battery
NA0LA-RS3Communication unit, 2 ports RS-232C (Port 3 + Port 4)
NA0LA-RS5Communication unit, 2 ports RS-485 (Port 3 + Port 4)
NA0LA-ET1Ethernet communication unit, 1 channel
Analog output unit,
2 channels: 14-bit analog output (-10 to 10V, 0 to 10V, -20 to 20mA, 0 to 20mA)
Analog input/output unit
4 channels: 14-bit analog input (-10 to 10V, 0 to 10V, -20 to 20mA, 0 to 20mA) +
2 channels: 14-bit analog output (-10 to 10V, 0 to 10V, -20 to 20mA, 0 to 20mA)
Analog output board,
2 channels: 12-bit analog output (0 to 10V, 0 to 20mA)
Analog input/output board,
2 channels: 12-bit analog input (0 to 10V, 0 to 20mA) +
1 channel: 12-bit analog output (0 to 10V, 0 to 20mA)
High-precision load cell unit
(Expansion left side unit)
Expansion power supply unit
Healthy unit
(Terminating connector)
Memory packNA8PMF-20Memory for storing a project and data
Loader connecting cableNA0H-CUVRS-232C/USB conversion cable for loader connection port (Port 0), 1.8m (Note 1)
Personal computer loader
NA0FA-LC1High-precision load cell unit, 1 channel
NA0S-2
NA0S-4
NA8P-HEUnit for detecting a dropout/fault of expansion right side units
1) You need to install the USB driver into the personal computer.
See “Appendix 1 Installing USB Driver.”
1-6
Section 1 Overview
1-4 Supported Versions
1-4-1 Program loader version
1) Program loader versions that support the SPF series
• SX-Programmer Expert (D300win) : V3.6.11.* or later
• SX-Programmer Standard : V3.0.16.* or later
2) Program loader versions that support Ethernet communication board (Type: NA3LA-ET1), Ethernet communication unit
(Type: NA0LA-ET1) and High-precision load cell unit (Type: NA0FA-LC1)
• SX-Programmer Expert (D300win) : V3.6.12.* or later
• SX-Programmer Standard : V3.0.17.* or later
1-4-2 Main unit version
1) V03 or later software version of main units support analog boards that are connected on the front of them (Type: NA3AY02-MR,
NA3AW03-MR). Analog boards cannot be used with a main unit the software version of which is earlier than V03.
2) V04 or later software version of main units support Ethernet communication board (Type: NA3LA-ET1) and Ethernet
communication unit (Type: NA0LA-ET1). Ethernet communication board/unit cannot be used with a main unit the software
version of which is earlier than V04.
1-7
Section 2 System Conguration
2-1 System Conguration Specications .................................................... 2-1
2-3-1 Rules for assigning I/O addresses..............................................................2-8
2-3-2 Example of address assignment ................................................................2-9
Section 2 System Conguration
Expansion
left side unit
Front board
Max. 6 (Note 1)
2-1 System Conguration Specications
You can connect up to six expansion units on the right side, one expansion uint on the left side, and one front board on the front
of the SPF series main unit, respectively.
Max. 1
Expansion
right side unit
Y1Y2C2 C4C0
Y0
Y3 Y4 Y6
Y10Y8Y11 Y12 Y14
Y9C8C10 C12 Y13 Y15
Y5 Y7
O0+O1+
24V IN
AG O0-
I0+I1+ I2+I3+
I0-I1- I2-I3-
O1-
PORT4 (RS485)
+
G
TNN
PORT3 (RS485)
+
G
T
Main unit
X12X10
24V OUT
S/S
AC100~240V
C0
X0
X1 X3
PORT0
Y2
Y0
C2
max.
TX
RX
TX
RX
400mA
IN
X8
X4X2
X6
X5 X7
RXTX
Y4
Y3
C4 C6
X11 X13
X9
Y5
Y6Y1
SINK
Y8
SRCE
Y7
Y9
NA0LA-RS5
Max. 1
Notes:
1) The maximum number of connectable AIO units is 3.
An expansion power supply unit and healthy unit are excluded from the number of connectable units (Max. 6).
O0+O1+
24V IN
AG O0-
I0+I1+ I2+I3+
I0-I1- I2-I3-
O1-
2-1
Section 2 System Conguration
2-1-1 Expansion specications
The table below shows the connectable expansion units.
ClassicationProduct nameTypeSpecication
Expansion right side
unit
Expansion left side
unit
Front board
DIO expansion unit
(with power supply)
DIO expansion unit
(without power supply)
AIO expansion unit
(without power supply)
Expansion power supply
unit
Healthy unit
(Terminating connector)
Communication unit
Function unitNA0FA-LC1High-precision load cell unit, 1 channel (Note 2)
AIO board
Communication board
NA0E24R-34
NA0E24T-31Input 14 points, Tr sink output 10 points, AC power supply
NA0E08R-3Input 4 points, Ry output 4 points
NA0E08T-3
NA0E08X-3Input 8 points
NA0E08T-0
NA0E16R-0
NA0E16T-0Tr sink output 16 points
NA0AX06-MRAnalog input 6 channels
NA0AY02-MRAnalog output 2 channels
NA0AW06-MRAnalog input 4 channels, Analog output 2 channels
NA0AX02-TCThermocouple input 2 channels
NA0AX06-TCThermocouple input 6 channels
NA0AX16-TCThermocouple input 16 channels
NA0AX06-PTResistance thermometer element input 6 channels
NA0F-LC1Load cell unit, 1 channel
NA0S-2Input 100 to 240V AC
NA0S-4Input 24V DC
NA8P-HE
NA0LA-RS2RS-232c: 2 ports (Note 2)
NA0LA-RS5RS-485: 2 ports (Note 2)
NA0LA-ET1Ethernet 1 channel (Note 2)
NA3AY02-MRAnalog output 2 channels
NA3AW03-MRAnalog input 2 channels, Analog output 1 channel
NA3LA-RS1RS-232C: 1 port, RS-485: 1 port (Note 2)
NA3LA-ET1Ethernet 1 channel (Note 2)
Input 14 points, Ry output 10 points, DC power supply
Input 4 points, Tr sink output 4 points
Tr sink output 8 points
Ry output 16 points
Unit for detecting a dropout/fault of expansion right side
units (Note 1)
Notes:
1) A healthy unit is used to detect a dropout of expansion right side units.
Be sure to mount a healthy unit to stop the SPF system with a fatal fault when an expansion right side unit is dropped.
Unless a healthy unit is mounted, a dropout of the expansion right side unit is not detected and the SPF system continues
operation in the state where the expansion right side unit is dropped.
Connect a healthy unit to the expansion connector (OUT) of the rightmost expansion right side unit after removing the
cover.
When mounting a healthy unit, register it in the system denition.
A healthy unit is excluded from the number of connectable expansion right side units (Max. 6).
2) A dropout of the communication unit/board and high-precision load cell unit is not detected.
2-2
Section 2 System Conguration
2-1-2 Calculation of current consumption
(1) Suppliable current
TypeInternal 5V DCInternal 24V DCExternally supplied 24V DC
Main unitNA0P
Expansion unit with
power supply
Expansion power supply NA0S-2 / NA0S-4400mA250mA250mA
Notes:
1) When using an AC power supply type unit at a power supply voltage of 120V AC or less, the total of the internal 24V DC
and externally supplied 24V DC becomes 575mA.
oooo-oo
NA0E24T-31948mA350mA337mA
NA0E24R-34948mATotal 337mA
C1000mA400mA (Note 1)400mA (Note 1)
(2) Current consumption of main unit
TypeInternal 5V DCInternal 24V DC
NA0PB14R-34C360mA65mA60mA
Advance main unit
Basic main unit
NA0PB24R-34C435mA85mA105mA
NA0PB32R-34C520mA110mA138mA
NA0PB60R-34C555mA200mA210mA
NA0PA14T-34C360mA65mA60mA
NA0PA24T-ooC435mA85mA105mA
NA0PA32T-ooC520mA110mA138mA
Externally supplied 24V DC
(Note 2)
NA0PA40T-ooC530mA125mA156mA
NA0PA60T-ooC555mA200mA210mA
2-3
Section 2 System Conguration
(3) Current consumption of expansion unit
TypeInternal 5V DCInternal 24V DC
NA0E08R-330mA34mA18mA
NA0E08T-330mA34mA18mA
DIO expansion unit
AIO expansion unit
Load cell unitNA0F-LC132mA–48mA
AIO board
NA0E08X-330mA–36mA
NA0E08T-029mA68mA–
NA0E16R-040mA136mA–
NA0E16T-040mA136mA–
NA0AX06-MR25mA–53mA
NA0AY02-MR33mA–90mA
NA0AW06-MR35mA–103mA
NA0AX02-TC30mA–21mA
NA0AX06-TC30mA–29mA
NA0AX16-TC30mA–58mA
NA0AX06-PT32mA–16mA
NA3AY02-MR223––
NA3AW03-MR158––
Externally supplied 24V DC
(Note 2)
Communication board
Communication unit
High-precision load cell unit NA0FA-LC1120mA–48mA
Healthy unitNA8P-HE10mA––
Notes:
2) These values show consumed current when externally supplied 24V DC power supply is used for input/output power
supply. When not using externally supplied 24V DC power supply for input/output power supply, the current consumption
of externally supplied 24V DC becomes 0mA.
NA3LA-RS155mA––
NA3LA-ET1110mA––
NA0LA-RS318mA––
NA0LA-RS595mA––
NA0LA-ET1160mA––
2-4
Section 2 System Conguration
<Calculation example of current consumption>
Whether or not to use an expansion power supply is determined by the total current consumption of all the units. You need to
calculate the total current consumption and mount an expansion power supply unit if the current is insufcient.
Referring the tables on the previous page, calculate the current consumption.
Subtract the total current consumption of the main unit, additionally connected front board, expansion left side unit, and
expansion right side units from the current supplied from the main unit. When the result is minus, you need to mount an
expansion power supply. Thus mount an expansion power supply unit if the current is insufcient for the expansion units that are
connected on the right.
Expansion power supply units are excluded from the number of connectable expansion units.
● Main calculation formula
[Supplied current] - [Current consumption]
= [Current supplied from main unit] - [Current consumption of main unit]
- [Current consumption of front board]
- [Current consumption of expansion left side unit]
- [Total current consumption of expansion right side units]
>= 0
● Calculation formula for current consumption on the right of the expansion unit with power supply
(Expansion unit with power supply is referred to as “Exp_powunit” here.)
Exp_powunit receives the remaining current of the main unit on the left side and adds it to the current that Exp_powunit
supplies to supply expansion units connected on the right.
I_MainR + I_Exp_powunit - I_Exp >= 0
• I_MainR (Remaining current of main unit)
= [Current supplied from main unit] - [Current consumption of expansion left side unit]
- [Current consumption of expansion right side units]
- [Current consumption of front board]
• I_Exp_powunit (Current supplied from Exp_powunit)
• I_Exp (Total current consumption of expansion units that are connected on the right of Exp_powunit)
● Calculation formula when using an expansion power supply unit
Use the above calculation formula by replacing Exp_powunit with the expansion power supply unit.
<Calculation of current consumption by using the loader function>
When registering units in the system denition by using the loader, you can check the total current consumption of the units and
the supplied current value.
(Since externally supplied 24V DC is not calculated by the loader, you need to calculate it.)
2-5
Section 2 System Conguration
• Case 1
When the main unit can supply sufcient current
NA0L
A
-RS5
NA3L
A
-RS1
NA0P
A24T
-34C
NA0E
08R
-3
NA0E
16T
-0
Result
Internal 5V DC-95-55+565-30-40+345 (OK)
Internal 24V DC+315-34-136+145 (OK)
Externally supplied
24V DC
+295-18+277 (OK)
• Case 2
When the main unit cannot supply sufcient current
NA0L
A
-RS5
NA3L
A
-RS1
NA0P
A40T
-34C
NA0E
08R
-3
NA0E
16T
-0
NA0E
16T
-0
NA0A
X06
-MR
Result
Internal 5V DC-95-55+470-30-40-40-25+185 (OK)
Internal 24V DC+275-34-136-136-31 (overload)
Externally supplied
24V DC
+244-18-53+173 (OK)
• Case 3
When an expansion power supply unit is mounted in the case 2
When using SPF series, you need to register the actual unit conguration in a project.
<Example of system conguration>
Front board
Type: NA3LA-RS1
PORT4 (RS485)
+
G
TNN
PORT3 (RS485)
+
G
T
NA0LA-RS5
X0 X2 X4 X6 X8 X10X12 X14X16 X18
24V OUT
.
x
a
m
S/S
400mA
TX
RX
TX
RX
INAC100~240V
L N
X1 X3 X5 X7 X9 X11 X13X15 X17 X19
IN (X)
PWR/
BAT
RUN/
MEM
ALM
OUT (Y)
PORT0
Y1 Y2 Y4 Y5 Y6Y8 Y10
C0 Y0 C2 Y3 C4 C6 Y7 C8 Y9 Y11
Main unit
X20X22
0
4
A
P
A
N
Y14Y12
C12Y13 Y15
X21X23
-
0
T
3
1
C
Y1Y2C2 C4C0
Y0
Y10Y8Y11 Y12 Y14
Y9C8C10 C12 Y13 Y15
Expansion right side unit
Y5 Y7
Y3 Y4 Y6
NA0E16T-0
O0+O1+
24V IN
AG O0-
NA0AW06-MR
I0+I1+ I2+I3+
I0-I1- I2-I3-
<System conguration denition tree window>
The system conguration denition tree for the above system conguration is shown below.
O1-
<Rules for dening system conguration>
• For system denition, the unit on the right of the main unit is registered just below the main unit.
As for the unit station Nos. of units, the main unit is always assigned “0” (zero), and numbers beginning with 1 (one) are
assigned to expansion right side units, in their connected order.
• The front board is connected on the front of the main unit and registered below the expansion right side unit in the conguration
denition tree. The unit station No. is xed to “100.”
• The expansion left side unit is connected to the left of the main unit and registered at the lowermost location in the conguration
denition tree. The unit station No. is xed to “200.”
2-7
Section 2 System Conguration
{
Output:
<For Standard>
<For Expert (D300win)>
Y (bit), WY (word), DY (double-word)
2-3 I/O address assignment
2-3-1 Rules for assigning I/O addresses
In MICREX-SX series SPF, follow the rules below to assign I/O addresses.
Period
Prefix
Input:
{
Output:
Identifier
Input:
1) Unit No.
A number (1 to 6) is assigned to SPF expansion right side units, in their connected order. The number assigned to the main unit
is always “0” (zero). The front board is assigned “100” (xed) as an independent unit and the expansion left side unit with “200”
(xed).
To each SPF unit, words starting from the word 0 (zero) are assigned for the number of words that the unit occupies. No same
word is assigned to both input and output. Therefore, for main unit and expansion units with both inputs and outputs, words are
assigned rst to inputs and then to outputs. All types of main units (regardless of the No. of I/O points provided) occupy eight
words of the I/O area (input: four words, output: four words).
Main unit
Unit No. 0
Front board
Unit No. 100
Expansion
right side unit
Unit No. 1
Expansion
right side unit
Unit No. 2
Expansion
right side unit
Unit No. 3
2-8
Section 2 System Conguration
%QX0.4.0 to QX0.4.15 (Y0.40 to Y0.4F)
2-3-2 Example of address assignment
1) Example of a system consisting only of a main unit with 40 points
Main unit with 40 points
Unit No. 0
Input: 24 points
output: 16 points
(Word address)
%IW0.0 (WX0.0)
%IW0.1 (WX0.1)
%QW0.4 (WY0.4)
Input: 24 points
Output: 16 points
(Bit address)
0F
%IX0.0.0 to %IX0.0.15 (X0.00 to X0.0F)
%IX0.1.0 to %IX0.1.7 (X0.10 to X0.17)
2) Example of a system in which expansion units are connected to a main unit with 60 points
Main unit with 60 points
Unit No. 0
Input: 36 points
output: 24 points
(Word address)
%IW0.0 (WX0.0)
%IW0.1 (WX0.1)
%IW0.2 (WX0.2)
Expansion
right side unit
Unit No. 1
Input: 14 points
output: 10 points
Expansion
right side unit
Unit No. 2
Input: 4 points
output: 4 points
0F
Input: 36 points
Expansion
right side unit
Unit No. 3
Output: 16 points
(Bit address)
%IX0.0.0 to %IX0.0.15 (X0.00 to X0.0F)
%IX0.1.0 to %IX0.1.15 (X0.10 to X0.1F)
%IX0.2.0 to %IX0.2.3 (X0.20 to X0.23)
%QW0.4 (WY0.4)
%QW0.5 (WY0.5)
%IW1.0 (WX1.0)
%QW1.1 (WY1.1)
%IW2.0 (WX2.0)
%QW2.1 (WY2.1)
%QW3.0 (WY3.0)
Output: 24 points
Input: 14 points
Output: 10 points
Output: 16 points
%QX0.4.0 to %QX0.4.15 (Y0.40 to Y0.4F)
%QX0.5.0 to %QX0.5.7 (Y0.50 to Y0.57)
%IX1.0.0 to %IX1.0.13 (X1.00 to X1.0D)
%QX1.1.0 to %QX1.1.9 (Y1.10 to Y1.19)
Input:
4 points
Output:
4 points
%IX2.0.0 to %IX2.0.3 (X2.00 to X2.03)
%QX2.1.0 to %QX2.1.3 (Y2.10 to Y2.13)
%QX3.0.0 to %QX3.0.15 (Y3.00 to Y3.0F)
2-9
Section 2 System Conguration
3) Example of a system in which expansion units are connected to a main unit with 32 points
Main unit with 32 points
Unit No. 0
Input: 20 points
output: 12 points
(Word address)
%IW0.0 (WX0.0)
%IW0.1 (WX0.1)
%QW0.4 (WY0.4)
%IW1.0 (WX1.0)
%IW2.0 (WX2.0)
%IW2.1 (WX2.1)
%IW2.2 (WX2.2)
%IW2.3 (WX2.3)
%QW2.4 (WY2.4)
%QW2.5 (WY2.5)
Expansion
right side unit
Unit No. 1
Input: 8 points
Input: 20 points
Output: 12 points
Input: 8 points
Input: 4 words
Output: 2 words
Expansion
right side unit
Unit No. 2
Input: 4 words
output: 2 words
(Bit address)
0F
%IX0.0.0 to %IX0.0.15 (X0.00 to X0.0F)
%IX0.1.0 to %IX0.1.3 (X0.10 to X0.13)
%QX0.4.0 to %QX0.4.11 (Y0.40 to Y0.4B)
%IX1.0.0 to %IX1.0.7 (X1.00 to X1.07)
2-10
Section 3 Specications
3-1 General Specications ............................................................................ 3-1
3-2 Main Unit Specications ......................................................................... 3-2
Conforming to IEC61131-3
IL language (Instruction List)
ST language (Structured Text)
LD language (Ladder Diagram)
FBD language (Function Block Diagram)
SFC elements (Sequential Function Chart)
4608 words9216 words
5632 words11264 words
Default tasks (Cyclic scanning): 1
Fixed cycle tasks + Event tasks: 15 in total
1) You can freely increase or decrease the area sizes of the standard memory, retain memory, user FB memory, and system
FB memory. The above table shows the default values.
2) The initial value setting area of the standard memory and retain memory is included.
3-2
Section 3 Specications
3-2-2 Memory backup and internal battery specications
The primary battery built in the main unit cannot be replaced. When a voltage drop of the battery is detected, you need to
replace the main unit.
The battery connection switch is set to OFF at the factory shipment to save battery consumption. When you start using the main
unit, set the battery connection switch to ON to enable memory backup by the built-in battery.
For the details of the battery connection switch, see “3-11-1 Main unit” in “3-11 Names and Functions.”
Backup time10 years or moreAmbient temperature: 55°C
Battery voltage drop
detection function
Battery voltage read
function
Battery lifeLife of primary battery: 10 years
<Notes on battery connection switch>
When the battery connection switch is OFF, the battery voltage drop detection LED also blinks. Check the switch status.
Retain memory, retain attributed memory of
user FB and System FB instance memory,
RAS history, Calendar
Provided
(Updated approximately every 10 minutes
while the main power is ON.)
Provided
(Updated approximately every 10 minutes
while the main power is ON.)
Backup target parts: SRAM, RTC
• When a voltage drop of the battery is detected (*1), the
PWR/BAT LED blinks alternately in red and orange.
The battery error in the system memory is set ON.
• When detected that the battery voltage is normal (*2),
the PWR/BAT LED lights up in red. The battery error in
the system memory is set OFF.
*1 2.4V or less
(battery voltage A/D conversion value 492)
*2 2.4V or more
(battery voltage A/D conversion value 493)
• Battery voltage A/D conversion value is stored in the
special register “%MW1.61450 (WM61450).”
• Battery voltage
= Battery voltage A/D conversion value * 4.883 [mV]
* Battery voltage drop can be detected by an application.
<Notes on detection of battery voltage drop and primary battery life>
• The built-in graphite uoride lithium primary battery has a characteristic that its voltage is increased under a high ambient
temperature. Therefore, even if the battery voltage drop detection LED blinks at power-on of the main unit, it may turn OFF
as the temperature in the main unit rises while running.
• The remaining capacity of a graphite uoride lithium primary battery never recovers even if the ambient temperature is high.
If the ambient temperature is high and the battery remaining capacity is low, the battery voltage may rapidly drop as the
remaining capacity is consumed.
In addition, as a result of moisture absorption for a long period, self discharge of a graphite uoride lithium primary battery
may rapidly increase from some point to cause a rapid drop of the battery voltage.
• For the above reasons, if you conrm that the battery voltage drop detection LED blinks or when more than ten years have
passed since the date of shipment, promptly replace the main unit following the steps described in “5-2 Actions to be Taken
When Battery Voltage Drop is Detected” without turning off the power.
• If the battery voltage continues to decrease with the main power OFF, more and more data of the built-in SRAM can be
easily lost, which causes a memory backup error (retain memory loss) after the main power is turned ON. In addition, the
calendar may be stopped or delayed.
3-2-3 Calendar specications
ItemSpecicationRemark
Range
Precision±232 ppm (temperature: 25°C)±20 sec/day
Time setting/changeLoader, user application
Up to 31 Dec. 2069 23:59:59
3-3
Section 3 Specications
3-3 Power supply specications
3-3-1 AC power supply type
Specication
Item
Rated input voltage
(tolerance)
Rated frequency
(tolerance)
Dropout tolerance20ms or less
Power consumption36W, 65VA21W, 40VA
Inrush current20A at 264V AC
Built-in fuse specication2A, 250V AC (unreplaceable by users)
Power
supply
output
Insulation methodTransformer/photocoupler
Dielectric strength1500V AC, 1 minute
Insulation resistance10MΩ or more (500V DC megger)
Internal 5V DC5V DC ±5%, 1A (max.)5V DC ±5%, 948mA (max.)5V DC ±5%, 400mA (max.)
Internal 24V DC24V DC ±10%, 400mA (max.) 24V DC ±10%, 350mA (max.) 24V DC ±10%, 250mA (max.)
Externally supplied
24V DC
Main unit
NA0PAooT-31C
100 to 240V AC
(85 to 264V AC)
50/60Hz
(47 to 63Hz)
24V DC ±10%, 400mA (max.) 24V DC ±10%, 337mA (max.) 24V DC ±10%, 250mA (max.)
Expansion unit
with power supply
NA0E24T-31
Expansion power supply
NA0S-2
3-3-2 DC power supply type
Specication
Item
Rated input voltage
(tolerance)
Dropout tolerance10ms or less
Power consumption24W14W
Inrush current20A at 24V DC
Built-in fuse specication2.5A, 125V (unreplaceable by the user)
Internal 5V DC5V DC ±5%, 1A (max.)5V DC ±5%, 948mA (max.)5V DC ±5%, 400mA (max.)
Power
supply
output
Insulation methodTransformer/photocoupler
Dielectric strength500V DC, 1 minute
Insulation resistance10MΩ or more (500V DC megger)
Internal 24V DC24V DC ±10%, 400mA (max.)
Externally supplied
24V DC
Main unit
NA0P
oooo
24V DC
(20.4 to 28.8V DC)
24V DC ±10%, 400mA (max.)24V DC ±10%, 250mA (max.)
-34C
Expansion unit
with power supply
NA0E24R-34
24V DC ±10%,
337mA in total (max.)
Expansion power supply
NA0S-4
1.5A, 125V
(unreplaceable by users)
24V DC ±10%, 250mA (max.)
Notes:
The external 24V DC power supply output is not insulated from the internal 5V DC and the internal 24V DC.
If you need an insulated I/O power supply, externally prepare 24V DC power supply.
3-4
Section 3 Specications
3-4 Input specications
3-4-1 DC input specications
(1) Specications
Function
Input signal
conditions
Input circuit
characteristic
High-speed
DC input
Rated voltage24V DC
Voltage (tolerance)26.4V DC
Ripple factor tolerance5%
Input typeSource, sink common (by external wiring)
Input current (at 24V DC) Approx. 9mAApprox. 6.5mAApprox. 4mA
Input impedanceApprox. 2.7k
Operating
voltage
Input typeDC type 1
Input delay
time
Maximum input frequency
/operating time
(Note 1)
OFF to ON18.5 to 26.4V19.5 to 26.4V20.5 to 26.4V
ON to OFF0 to 5V0 to 5V0 to 5V
Hardware1µs or less22µs or less0.55ms or less5.5ms or less
You can select any of the following values in the system
200kHz/2.5µs
(Advance main unit)
100kHz/5µs
(Basic main unit)
Ω
Medium-speed
DC input
Approx. 3.7k
20kHz/25µs0.83kHz/0.6ms–
Ω
Low-speed
DC input
Approx. 5.9k
Expansion
DC input
Ω
–
External wire connections
Input indicationLED indicator turns on when input is “ON” and turns off when input is “OFF”.
Isolation methodPhotocoupler
Dielectric strength1500V AC 1 minute (between input terminals and frame ground)
Insulation resistance10MΩ or more with 500V DC megger (between input terminals and frame ground)
Derating conditionSpecied (Note 2)None
NA0PA14T-34CX0, 1X2 to 7––
NA0PA24T-3oCX0, 1, 4, 5X2, 3, 6 to 13––
NA0PA32T-3oCX0, 1, 4, 5, 8, 9X2, 3, 6, 7, 10 to 15 X16 to 19–
NA0PA40T-3oCX0, 1, 4, 5, 8, 9X2, 3, 6, 7, 10 to 15 X16 to 23–
Corresponding
terminal No.
NA0PA60T-3oC
NA0PB14R-34CX0, 1X2 to 7––
NA0PB24R-34CX0, 1X2 to 13––
NA0PB32R-34CX0, 1X2 to 15X16 to 19–
NA0PB60R-34CX0, 1X2 to 15X16 to 35–
Expansion unit–––
Terminal block (M3 screw)
X0, 1, 4, 5, 8, 9, 12, 13X2, 3, 6, 7, 10, 11,
14, 15
X16 to 35–
All inputs
Notes:
1) In A/B-phase input mode, the maximum input frequency becomes half.
2) See “3-9 Temperature derating of main unit.”
3-5
Section 3 Specications
X0
X1
X3
External common line
Input device
External
power
supply
X2
X0
X3
X1X2
External common line
Input circuit
External
power
supply
(2) Input circuit conguration and external connection
The 24V DC digital input circuits are available for high, medium and low speed. They all have the similar circuit structures but
with different response speeds. When making the connection of external digital input devices, the one ends of all input devices
(e.g. buttons and switches) are connected together and called the external common wire, while the other ends of input circuits
are connected to the input terminals X0, X1, X2, etc., of SPF. Then nish it by connecting the external common wiring and
internal common terminal S/S to the 24VDC power. When connecting the internal common terminal S/S to 24V+ (positive) and
the external common wire to 24V- (negative), then the circuit serves as a sink input. On the contrary, while exchange the wiring
of the above internal and external common will serve as a source input. The above wiring schemes can illustrated below:
• Wiring of source input
24V DC
SPF
(Not available when using
an expansion unit without
power supply.)
• Wiring of sink input
24V DC
+24V
24V DC
NPN
sensor
-
S/S
Internal
common
terminal
R2
R1
R2
X1X2X0
R1
R2
R1
X3
R1
R2
PNP
sensor
SPF
+24V
-
24V DC
(Not available when using
an expansion unit without
power supply.)
Output indicationLED indicator turns on when input is “ON” and turns off when output is “OFF”.
Isolation methodPhotocoupler
Dielectric strength500V AC 1 minute (between output terminals and frame ground)
Insulation resistance10MΩ or more with 500V DC megger (between output terminals and frame ground)
Derating conditionSpecied (Note 5)None
NA0PA14T-34CY0 to 3Y4, 5––
NA0PA24T-3oCY0 to 3Y4 to 7Y8, 9–
Corresponding
terminal No.
Notes:
1) The total of all points is “0.1A x No. of output points” or less.
Example: In the case of a unit with 40 points (No. of output points: 16 points), the total is 1.6A or less.
2) 0.1A/point for an expansion unit with 24 points (NA0E24T-31)
3) 100kHz for A/B-phase output mode
4) 8kHz for A/B-phase output mode
5) See “3-9 Temperature derating of main unit.”
NA0PA32T-3oCY0 to 5Y6, 7Y8 to 11–
NA0PA40T-3oCY0 to 5Y6, 7Y8 to 15–
NA0PA60T-3oCY0 to 7–Y8 to 23–
Expansion unit–––All outputs
3-7
Section 3 Specications
2-point common output block4-point common output block
SPF
(2) Output circuit conguration and external connection
Transistor sink output
C2
1A
FUSE
Y2
Y3
C4
2A
FUSE
Y4
Y5
Y6
Y7
3-8
Section 3 Specications
R
SPF
R: Dummy load
(3) Speeding up transistor output circuits
With the sink structure in a transistor circuit, when the transistor switches from ON to OFF, the junction capacitor between
transistor CE electrodes should be charged to near the load voltage VDD before it can stop the current running through the
photocoupler inside the load, which increase the OFF time and decrease the response speed. This problem can be solved by
adding a Dummy load to accelerate charging rate and speed up the working frequency of transistor output. For the transistor
output, Dummy load that are added to the high and medium-speed transistor output and generate a load current of 20 to 50mA
is adequate. For low speed transistor where its driving capability (0.5A) but speed is concerned, adding a Dummy load only
decreases its driving capability without any signicant improvement and hence is not recommended. The following diagram
shows how to add a Dummy load to transistor sink output.
(2) Output circuit conguration and external connections
Each relay can provide current up to 2A. The maximum rated current in all output commons of SPF is 4A. Its mechanical lifetime
can reach up to 2 million times. The lifetime also varies depending on working voltage, load type (power factor cosψ) and
contact current. In the case of pure resistive load (cosψ=1.0) at 120VAC and 2A, the lifetime of contacts is about 250 thousand
times. While for high inductive or capacitive load with cosψ up to 0.2 and current within 1A, the lifetime decreases rapidly to
about 50 thousand times (AC200V) or 80 thousand times (AC120V).
AC/DC
power
supply
A4
Fuse
)
4
Operation (x10
AC/DC
power
supply
Life curve
Contact current (A)
A4
Fuse
resistive
resistive
3-11
Section 3 Specications
Surge current welds contacts.
PLC output
3-5-3 Output device protection and noise suppression in DO circuit
Since the digital output circuits are mainly used for the ON/OFF switching operation, the output components such as relays,
transistors and TRIAC can be deemed as kinds of switch components. Normally, surge currents or counter-electromotive force
voltages are generated during the ON/OFF operation of these switch components. The effect of surge currents or counterelectromotive force voltages is particularly serious when heavy capacitive or inductive loads are incorporated, which may cause
damage to the output components or generate noises in other electronic circuits and equipment. Special consideration should
be given to relays and transistors when they are used in high power applications or connected with capacitive or inductive loads
and are described in the following:
(1) Protection of relay contacts and noise suppression
Because the relay contacts are used to contact switch components having extremely low resistance, the surge current IR
generated instantly upon turning on the relay is normally pretty strong (even if the steady load current is very small). Under such
strong surge, the contact tends to melt and stick due to extreme temperature in such a way that the relay cannot trip when it is
disconnected. In addition, when the relay connections are OFF, large di/dt is generated because of the instantaneous change
from low resistance to open circuit (∞) soon after following the tripping of contact. As a result, an extremely strong counter-
electromotive force voltage is induced, which creates sparks between the electrodes of two relay contacts and results in poor
contact due to carbon deposits. Among those three output components, either in ON or OFF state, very serious interference can
be caused by the surge current or the counter-electromotive of the relay. The solutions to this problem are listed as follows:
1) Suppression of surge current
Connect a small resistor R in series to lower the surge current, but note that too large R will affect the driving capability or cause
too much voltage drop.
relay
Load
I s
Is
I r
Ir
Electric
circuits
R (note power dissipation P = Is2R and voltage drop V = IsR)
Ir max
Ir max of relay in SPF = 5A
C
VDD
R
V
R
VDD
3-12
Section 3 Specications
Suppress by a diode + Zener in DC power load (for high power and frequent ON/OFF)
2) Suppression of counter-electromotive force
For the inductive load, whether in AC or DC power, suppression devices must be connected in parallel to both its ends to protect
the relay contacts and lower noise interference. The schematic diagrams for AC and DC powers are shown below, respectively:
PLC Relay output
R
PLC Relay output
R
Suppress by a diode in DC power load (for low power)
PLC Relay output
R
Inductive load
RC
Scheme of AC power load
Inductive load
D
Inductive load
D
ZD
R: 100~120
C: 0.1 to 0.24uF
D: 1N4001 diode or
VDC
equivalent device
D: 1N4001 diode or
equivalent device
VDC
ZD: 9V Zener, 5W
(2) Contact transfer
Contact transfer refers to a phenomena in which one side of contact melts or evaporates and is transferred to the other side
because of on/off operation of the DC load. As the number of on/off times increases, the protruded portion on one contact grows
and the embossed portion on other contact becomes correspondingly large. Eventually the two contacts are locked as if contact
melting occurred. This phenomena may occur within the ratings of relay contacts. In particular, when a relay is used to turn on
and off a capacitive load, this phenomena may occur. In this case, use a resistor to suppress inrush current.
3-13
Section 3 Specications
Suppress by a diode + Zener (high power and frequent ON/OFF)
(3) Protection of transistor output and noise suppression
The transistor output in SPF already includes Zener diode for counter-electromotive force, which is sufcient for low power
inductive load and medium frequency of ON/OFF application. In conditions of high power or frequent ON/OFF, please construct
another suppression circuit to lower noise interference and prevent voltage from exceeding the limit or overheating that may
damage the transistor output circuit.
PLC Relay output
PLC Relay output
Inductive load
D
Suppress by a diode (for low power)
Inductive load
D
ZD
VDC
D: 1N4001 diode or
equivalent device
D: 1N4001 diode or
equivalent device
VDC
ZD: 9V Zener, 5W
3-14
Section 3 Specications
Terminal block
3-6 Analog Unit/Board Specications
3-6-1 Analog input unit (NA0AX06-MR)
(1) Specications
ItemSpecication
TypeNA0AX06-MR
No. of input channels6 channels
Input impedanceVoltage: 63.2 kW, Current: 250
Maximum allowable inputVoltage: ±15V, Current: 30mA
Input range
Resolution12 bits or 14 bits (Set for individual channels by the program loader.)
Overall accuracy±1% *1
A/D conversion valueINT type
Sampling periodSynchronized with the scan of the main unit.
Moving average1 to 16 times (Set for individual channels by the program loader.)
External wire connections8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire sizeAWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication5V power supply display, ON when normal (red)
Isolation methodNot isolated
Occupied words6 words
External power supply24V DC, 53mA *Wiring length: 10m or less
Internal current consumption5V DC, 25mA
Dimensions40 (W) x 90 (H) x 80 (D) (mm)
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
W
*1 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
(2) Names
<Signal assignment>
Expansion connector (IN)
Status indication LED
* For the detailed specications of and how to use the analog input unit (Type: NA0AX06-MR), refer to the user’s manual “Analog
Unit (FEH527).”
Expansion connector (OUT)
Terminal block
3-15
Section 3 Specications
Terminal block
3-6-2 Analog output unit (NA0AY02-MR)
(1) Specications
ItemSpecication
TypeNA0AY02-MR
No. of output channels2 channels
External load resistanceVoltage output: 500 W to 1 MW, Current output: 0 to 500 W or less
Analog output range
Resolution14 bits
Overall accuracy±1%
Data type of digital output value INT type
Output periodSynchronized with the scan of the main unit.
External wire connections8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire sizeAWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication5V power supply display, ON when normal (red)
Isolation methodNot isolated
Occupied words2 words
External power supply24V DC, 90mA *Wiring length: 10m or less
Internal current consumption5V DC, 33mA
Dimensions40 (W) x 90 (H) x 80 (D) (mm)
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
(2) Names
<Signal assignment>
Expansion connector (IN)
Status indication LED
* For the detailed specications of and how to use the analog output unit (Type: NA0AY02-MR), refer to the user’s manual “Analog
Unit (FEH527).”
NA0AY02-MR
Expansion connector (OUT)
Terminal block
3-16
㻺㻭㻜㻭㼅㻜㻞㻙㻹㻾
Section 3 Specications
3-6-3 Analog input/output unit (NA0AW06-MR)
(1) Specications
ItemSpecication
TypeNA0AW06-MR
No. of input channels4 channels
Input impedanceVoltage: 63.2 kW, Current: 250
Maximum allowable inputVoltage: ±15V, Current: 30mA
Input range
Resolution12 bits or 14 bits (Set for each channel by the program loader.)
Overall accuracy±1% *1
A/D conversion valueINT type
Sampling periodSynchronized with the scan of the main unit.
Moving average1 to 16 times (Set for individual channels by the program loader.)
No. of output channels2 channels
External load resistanceVoltage output: 500 W to 1 MW, Current output: 0 to 500 W or less
Analog output range
Resolution14 bits
Overall accuracy±1%
Data type of digital output value INT type
Output periodSynchronized with the scan of the main unit.
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
W
External wire connections8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire sizeAWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication5V power supply display, ON when normal (red)
Isolation methodNot isolated
Occupied words6 words
External power supply24V DC, 103mA *Wiring length: 10m or less
Internal current consumption5V DC, 35mA
Dimensions40 (W) x 90 (H) x 80 (D) (mm)
*1 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
3-17
Section 3 Specications
Terminal block
(2) Names
<Signal assignment>
Expansion connector (IN)
Status indication LED
NA0AW06-MR
* For the detailed specications of and how to use the analog input/output unit (Type: NA0AW06-MR), refer to the user’s manual
“Analog Unit (FEH527).”
Expansion connector (OUT)
Terminal block
3-18
Section 3 Specications
<Signal assignment>
3-6-4 Analog output board (NA3AY02-MR)
(1) Specications
ItemSpecication
TypeNA3AY02-MR
No. of output channels2 channels
External load resistanceVoltage output: 1k W to 1MW, Current output: 0 to 500 W or less
Analog output range
Resolution12 bits
Overall accuracy±1%
Data type of digital output value INT type
Output periodSynchronized with the scan of the main unit.
Applicable wire sizeAWG#28-16 * Be sure to use shielded twisted pair cables.
Status indicationNone
Isolation methodNot isolated
Occupied words3 words
Internal current consumption5V DC, 158mA
*1 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
*2 Screw tightening torque for mounting the board on a main unit: 0.2 N·m
(2) Names
VI0+
IO0+
GND
II0+
VI1+
II1+
GND
* For the detailed specications of and how to use the analog input/output board (Type: NA3AW03-MR), refer to the user’s
manual “Analog Unit (FEH527).”
3-20
Section 3 Specications
3-6-6 Thermocouple input unit (NA0AX02-TC/NA0AX06-TC/NA0AX16-TC)
(1) Specications
ItemSpecication
TypeNA0AX02-TCNA0AX06-TCNA0AX16-TC
No. of input channels2 channels6 channels16 channels
Resolution0.1°C or 1°C *1
Thermocouple typeJ, K, R, S, E, T, B, N (Collectively set for all channels by the program loader)
Temperature measurement
range
Cold junction automatic
compensator
Overall accuracy
Data type of
A/D conversion value
Sampling period
Moving averageNo moving average / 2 / 4 / 8 times
External wire connections8-pole European-style terminal block (M2) x 2,
Applicable wire sizeAWG#28-16AWG#22-18
J: -200.0 to 1200.0°C -328.0 to 2192.0°F
K: -200.0 to 1200.0°C -328.0 to 2192.0°F
T: -190.0 to 380.0°C -310.0 to 716.0°F
E: -190.0 to 1000.0°C -310.0 to 1832.0°F
N: -200.0 to 1000.0°C -328.0 to 1832.0°F
B: 350.0 to 1800.0°C 622.0 to 3272.0°F
R: 0.0 to 1800.0°C 32.0 to 3272.0°F
S: 0.0 to 1700.0°C 32.0 to 3092.0°F
Built in the unit
± (1% + 1°C) *2
INT type
1 second (high speed) or
2 seconds (low speed)
(Collectively set [high speed or low speed] for all channels by the program loader.)
(Collectively set for all channels by the program loader.)
Tightening torque: 0.2 N·m
2 seconds (high speed) or
4 seconds (low speed)
3 seconds (high speed) or
6 seconds (low speed)
18-pole terminal block (M3) x 2,
Tightening torque:
0.59 to 0.78 N·m
Status indication5V power supply display, ON when normal (red)
Isolation methodTransformer (power supply) and photocoupler (signal)Not isolated
Occupied words2 words6 words16 words
External power supply
Internal current
consumption
Dimensions40 (W) x 90 (H) x 80 (D) (mm)90 (W) x 90 (H) x 80 (D) (mm)
*1 The resolution is determined by the setting of the “sampling period” in the parameter.
When the resolution is 1°C: Set to “high speed.”
When the resolution is 0.1°C: Set to “low speed.”
*2 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
24V DC, 21mA24V DC, 29mA24V DC, 58mA
*Wiring length: 10m or less
5V DC, 30mA
3-21
Section 3 Specications
Terminal block
Terminal block
(2) Names
1) NA0AX02-TC
<Signal assignment>
Expansion connector (IN)
Status indication LED
2) NA0AX06-TC
Expansion connector (IN)
Expansion connector (OUT)
Terminal block
<Signal assignment>
Expansion connector (OUT)
Status indication LED
Terminal block
3-22
Section 3 Specications
2) Terminal block
3) NA0AX16-TC
Expansion
connector (IN)
1) Status indication LED
Expansion
connector (OUT)
Nameplate
2) Terminal block
<Signal assignment>
* For the detailed specications of and how to use the thermocouple input unit (Type: NA0AX02-TC/NA0AX06-TC/NA0AX16-TC),
refer to the user’s manual “Analog Unit (FEH527).”
3-23
Section 3 Specications
2) Terminal block
3-6-7 Resistance thermometer element input unit (NA0AX06-PT)
(1) Specications
ItemSpecication
TypeNA0AX06-PT
No. of analog input channels6 channels
Resolution0.1°C or 1°C *1
Applicable resistance thermometer
element
Temperature measurement range
Overall accuracy±1% *2
Resistance of input wiring20Ω or less
Data type of A/D conversion valueINT type
Sampling period
Moving average
External wire connections8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire sizeAWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication5V power supply display, ON when normal (red)
Isolation methodNot isolated
Occupied words6 words
External power supply24V DC, 16mA *Wiring length: 10m or less
Internal current consumption5V DC, 32mA
Dimensions40 (W) x 90 (H) x 80 (D) (mm)
Pt100, Pt1000 (JIS or DIN)
Pt100: -200.0 to 850.0°C (-328.0 to 1562.0°F)
Pt1000: -200.0 to 600.0°C (-328.0 to 1112.0°F)
1 second (high speed) or 2 seconds (low speed)
(Collectively set for all channels by the program loader.)
No moving average / 2 / 4 / 8 times
(Collectively set for all channels by the program loader.)
*1 The resolution is determined by the setting of the “sampling period” in the parameter.
When the resolution is 1°C: Set to “high speed.”
When the resolution is 0.1°C: Set to “low speed.”
*2 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
(2) Names
<Signal assignment>
Expansion connector (IN)
1) Status indication LED
2) Terminal block
Expansion connector (OUT)
Nameplate
* For the detailed specications of and how to use the resistance thermometer element input unit (Type: NA0AX06-PT), refer to
the user’s manual “Analog Unit (FEH527).”
3-24
Section 3 Specications
Inch screw
9
6
G
3-7 Communication Unit/Board Specications
3-7-1 RS-232C/RS-485 general purpose communication board (NA3LA-RS1)
Max. number of simultaneous
communicable nodes
(number of communication ports)
Transmission codeBinary only
Internal current consumptionNA3LA-ET1: DC5V **mA, NA0LA-ET1: DC5V **mA
Occupied words0 word
(Server operation)
Loader communication
(Client operation)
Communication between the PLC and other nodes is performed by using TCP/IP
or UDP/IP protocol. Because of free data format, it is possible to communicate with
all kinds of nodes.
Communication with a POD or loader, host PC is performed by a loader command.
No communication program is required on the PLC side.
The data memory in the target device (another SPH or SPF) is read or written.
“R_READ” (for reading data) and “R_WRITE” (for writing data) FBs are used for
communication.
Start these FBs to send or receive a loader command from the self station to the
target device.
8 stations / physical port
Note: The maximum number of communication ports that one CPU can
simultaneously open is 16 when using both an Ethernet front board and a
left side unit.
However, responses of communication deteriorate as the number of
communication ports per CPU increases.
* Screw tightening torque for mounting the board on a main unit: 0.2 N·m
(2) Names
<NA3LA-ET1>
Ethernet status indication LED
Ethernet connector
* For the detailed specications of and how to use the Ethernet communication board (NA3LA-ET1) and Ethernet communication
unit (NA0LA-ET1), refer to the user’s manual “SPF Ethernet Communication (FEH630).”
3-28
Ethernet connector
Section 3 Specications
Terminal block
3-8 Function Unit Specications
3-8-1 Load cell unit (NA0F-LC1)
(1) Specications
ItemSpecication
No. of input channels1 channel
Input range
Resolution16 bits (including a sign bit)
Digital conversion value0 to 25,000 (INT type)
0 to 2mV/V, 0 to 5mV/V, 0 to 10mV/V, 0 to 20mV/V
(Set by the program loader.)
Load cell applied voltage5V DC, 100
Sampling period5/10/25/30/60/80Hz (Set by the program loader.)
Moving averageNo moving average / 2 / 4 / 8 times (Set by the program loader.)
Nonlinearity0.01% for full scale (at an ambient temperature of 25°C)
Accuracy
External wire connections8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Status indication5V power supply display, ON when normal (red)
Isolation methodTransformer (power supply) and photocoupler (signal)
Occupied words1 word
External power supply24V DC, 48mA
Internal current consumption5V DC, 32mA
Zero drift0.2µV/°C
Gain drift10ppm/°C
W
(2) Names
Expansion connector (IN)
Status indication LED
<Signal assignment>
Expansion connector (OUT)
Terminal block
3-29
Section 3 Specications
16
NA0F-LC1
(3) External connection
24V+
24V-
24V
-bit Da ta
24-Bit
Δ-Σ
A/D
+5V
+EXC
CH0+
CH0-
-EXC
+
-
R
R
Load Cell
R
R
3-30
Section 3 Specications
Status indication LED
Terminal block
3-8-2 High-precision load cell unit (NA0FA-LC1)
(1) Specications
ItemSpecication
No. of input channels1 channel
Resolution24 bits (including a sign bit)
Data type of digital conversion value INT type, DINT type
Load cell applied voltage5V DC, 350 Ω
Sampling period100 times/second
Max. measured voltage-1mV to 39mV
Input sensitivity, resolution0.15µV/d or more (d = minimum scale) 1/60000
External wire connections8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire sizeAWG#22-18 * Be sure to use shielded twisted pair cables.
5V power supply display, ON when normal (red)
Status indication
Isolation methodTransformer (power supply) and photocoupler (signal)
Parameter storage areaCalibration parameters and set values are saved in the internal EEPROM.
External power supply24V DC, 48mA *Wiring length: 10m or less
Internal current consumption5V DC, 120mA
(2) Names
<Signal assignment>
Expansion connector
Terminal block
* For the detailed specications of and how to use the high-precision load cell unit (Type: NA0FA-LC1), refer to the user’s
manual “High-precision Load Cell Unit (FEH530).”
3-31
Section 3 Specications
(No. of simultaneous
A
(AC power supply/
24V DC power supply,
transistor output [0.1A])
Main unit with 14 points
Main unit with 24 points
ON points)
(No. of simultaneous
ON points)
Basic main unit
(24V DC power supply,
relay output [1A])
(No. of simultaneous
A
(AC power supply/
24V DC power supply,
transistor output [0.1A])
Main unit with 32 points
Main unit with 40 points
ON points)
Basic main unit
(24V DC power supply,
relay output [1A])
3-9 Temperature derating of main unit
SPF main units have temperature derating limits for the No. of simultaneous ON points.
Expansion units have no temperature derating limits.
(1) Main unit with 14/24 points
dvance main unit
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
No limit
50%
(7 points)
No limit
50%
(7 points)
Simultaneous
ON rate
100%
(14 points)
(No. of simultaneous
ON points)
Simultaneous
ON rate
100%
(14 points)
(No. of simultaneous
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
50%
(12 points)
No limit
50%
(12 points)
16 points
100%
(24 points)
ON points)
100%
(24 points)
°C
51
Simultaneous
ON rate
Simultaneous
ON rate
(2) Main unit with 32/40 points
dvance main unit
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
(16 points)
(16 points)
50%
50%
16 points
(32 points)
(32 points)
°C
46
Simultaneous
ON rate
100%
(No. of simultaneous
ON points)
30 points
°C
54
Simultaneous
ON rate
100%
(No. of simultaneous
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
(20 points)
16 points
50%
100%
(40 points)
°C
43
Simultaneous
ON rate
ON points)
3-32
Section 3 Specications
(No. of simultaneous
A
(AC power supply/
24V DC power supply,
transistor output [0.1A])
Main unit with 60 points
Basic main unit
(24V DC power supply,
relay output [1A])
(No. of simultaneous
ON points)
(3) Main unit with 60 points
dvance main unit
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
60°C
50°C
40°C
temperature
Ambient operating
30°C
20°C
0%
(0 point)
15 points
50%
(30 points)
50%
(30 points)
100%
(60 points)
36 points
100%
(60 points)
°C
42
Simultaneous
ON rate
ON points)
°C
45
Simultaneous
ON rate
3-33
Section 3 Specications
C0Y0C2Y3C4
C0Y0C2Y3C4
C6Y7Y9
X12
X8
C0Y0C2Y3C4
C6Y7Y9
3-10 Terminal Arrangement
3-10-1 Main unit
(1) Main unit with 14 points (8 points input / common, 2 points output / common x 3 circuits)
1) DC power supply type (NA0PA14T-34C, NA0PB14R-34C)
400mA
IN24VDC
S/S
24V OUT
.
x
a
m
X0X2X4X6
X1X3X5X7
Y1Y2Y4Y5
(2) Main unit with 24 points
(14 points input / common, 2 points output / common x 3 circuits, 4 points output / common)
1) AC power supply type (NA0PA24T-31C)
400mA
INAC100~240V
LN
S/S
24V OUT
.
x
a
m
2) DC power supply type (NA0PA24T-34C, NA0PB24R-34C)
X0X2X4X6
X1X3X5X7
Y1Y2Y4Y5
X10
X9X11X13
Y6Y8
400mA
IN24VDC
S/S
24V OUT
.
x
a
m
X0X2X4X6
X1X3X5X7
Y1Y2Y4Y5
X8
X10
X9X11X13
Y6Y8
X12
Note: “•” indicates an NC terminal, which cannot be wired to maintain necessary safety standards and prevent damage to the
unit.
3-34
Section 3 Specications
X0X2X4X6X8X10X12X14X16X18
24V OUT
C0Y0C2Y3C4C6Y7C8Y9Y11
X0X2X4X6X8X10X12X14X16X18
24V OUT
C0Y0C2Y3C4C6Y7C8Y9Y11
X0X2X4X6X8X10X12X14X16X18
24V OUT
C0Y0C2Y3C4C6Y7C8Y9Y11
C12Y13
Y15
X20X22
X0X2X4X6X8X10X12X14X16X18
24V OUT
C0Y0C2Y3C4C6Y7C8Y9Y11
Y15
X20X22
(3) Main unit with 32 points
(20 points input / common, 2 points output / common x 4 circuits, 4 points output / common)
1) AC power supply type (NA0PA32T-31C)
.
x
a
m
400mA
S/S
X1X3X5X7X9X11X13X15X17X19
INAC100~240V
N
L
Y1Y2Y4Y5Y6Y8Y10
2) DC power supply type (NA0PA32T-34C, NA0PB32R-34C)
.
x
a
m
400mA
IN24VDC
+-
S/S
X1X3X5
Y1Y2Y4Y5Y6Y8Y10
X7X9
X11
X13
X15X17X19
(4) Main unit with 40 points
(24 points input / common, 2 points output / common x 4 circuits, 4 points output / common x 2 circuits)
1) AC power supply type (NA0PA40T-31C)
.
x
a
m
400mA
S/S
X1X3X5X7X9X11
X13
X15X17
X19
X21X23
INAC100~240V
L
N
Y1Y2
2) DC power supply type (NA0PA40T-34C)
.
x
a
m
400mA
IN24VDC
+
S/S
-
X1X3X5X7X9X11X13X15X17X19
Y1
Y2Y4Y5Y6Y8Y10
Y4Y5Y6Y8Y10
C12Y13
Y14Y12
X21X23
Y14Y12
3-35
Section 3 Specications
24V OUT
X0
X2X4X6X8X10X12 X14X16 X18
X20X22
X24X26 X28X30 X32
X34
C0Y0C2Y3
C4
C6Y7C8Y9Y11C12 Y13Y15 C16
Y17
Y19
C20Y21
Y23
24V OUT
X0
X2X4X6X8X10X12 X14X16 X18
X20X22
X24X26 X28X30 X32
X34
C0Y0C2Y3
C4
C6Y7C8Y9Y11C12 Y13Y15 C16
Y17
Y19
C20Y21
Y23
(5) Main unit with 60 points
(36 points input / common, 2 points output / common x 4 circuits, 4 points output / common x 4 circuits)
1) AC power supply type (NA0PA60T-31C)
.
x
a
m
400mA
INAC100~240V
S/S
L
N
2) DC power supply type (NA0PA60T-34C, NP0PB60R-34C)
.
x
a
m
400mA
IN24VDC
S/S
+-
X1X3X5X7X9X11X13 X15X17 X19
Y1
X1X3X5X7X9X11X13 X15X17 X19
Y1
Y4Y5
Y2
Y4Y5
Y2
Y6Y8Y10Y14Y12Y16 Y18Y20 Y22
Y6Y8Y10Y14Y12Y16 Y18Y20 Y22
X21X23
X21X23
X25X27 X29X31 X33X35
X25X27 X29X31 X33X35
3-36
Section 3 Specications
Y9C8C10C12Y13Y15
S/S
X0
X2
C0
C2Y3
S/S
X5X7
C6C4Y7
3-10-2 Expansion unit
(1) Expansion unit with 8 points (4 points input / common, 2 points output / common x 2 circuits)
1) No power supply type (NA0E08R-3, NA0E08T-3)
X1X3
Y2
Y1Y0
(2) Expansion unit with input 8 points (8 points input / common)
1) No power supply type (NA0E08X-3)
X0
X2
X1X3
X4X6
(3) Expansion unit with output 8 points (2 points output / common x 4 circuits)
1) No power supply type (NA0E08T-0)
C0C2
Y0Y3Y1Y2
Y5Y4Y6
(4) Expansion unit with output 16 points
(2 points output / common x 4 circuits, 4 points output / common x 2 circuits)
1) No power supply type (NA0E16R-0, NA0E16T-0)
Y1
Y0
Y2
C2C4C0
Y3Y4Y6
Y5Y7
Y8Y11
Y10
Y12Y14
3-37
Section 3 Specications
Y0
C0
Y0
C2Y3C4
C6Y7Y9
(5) Expansion unit with 24 points
(14 points input / common, 2 points output / common x 3 circuits, 4 points output / common)
1) AC power supply type (NA0E24T-31)
m
400mA
INAC100~240V
S/S
24V OUT
.
x
a
LN
C0
X0X2X4
X1X3X5X7
Y1Y2Y4
C2Y3C4
2) DC power supply type (NA0E24R-34)
m
400mA
S/S
24V OUT
.
x
a
IN24VDC
+
-
X0X2X4
X1X3X5X7
Y1Y2Y4
(6) Expansion power supply unit
1) AC power supply type (NA0S-2)
X6
X8X10X12
X9X11X13
Y5
Y6Y8
C6Y7Y9
X6
X8X10X12
X9X11X13
Y5
Y6Y8
24V OUT
.
x
a
m
250mA
INAC100䡚240V
LN
2) DC power supply type (NA0S-4)
24V OUT
.
x
a
m
250mA
IN24VDC
+-
䠇䠉
3-38
Section 3 Specications
When the cover plate is mounted
3) I/O terminal block
3-11 Names and Functions
3-11-1 Main unit
The following gure describes the names and functions of the main unit using a main unit with 24 points (Type: NA0PA24T-31C)
as an example.
(1) Names
Mounting hole (φ4.5 x 2)
1) Status indication LED
Cover plate
Nameplate (on the right side)
2) Built-in loader port
Front board connector
Expansion connector (left side)
Front board fixing screw hole
4) Battery connection switch
3) I/O terminal block
DIN rail tab
When the cover plate is removed
5) Memory pack connector
Expansion connector (right side)
3-39
Section 3 Specications
.
(2) Functions
1) Status indication LED
Input status indication (red)
* The left gure shows the status indication LED
of the main unit with 24 points.
Output status indication (red)
PWR/BAT
(red/orange)
ON (red)ONOFFThe CPU is running normally.
ON (red)OFFOFFThe CPU is stopped normally.
ON (red)BlinksOFF
ON (red)ONBlinksThe CPU is running in a nonfatal fault condition.
ON (red)BlinksBlinks
ON (red)BlinksBlinks
ON (red)OFFBlinksThe CPU is stopped in a fatal or nonfatal fault condition.
Blinks alternately
in red and orange
ON (red)OFFBlinks at high speed
2) Built-in loader port (PORT 0)
The built-in loader port is used to connect a personal computer loader.
Use a dedicated cable (Type: NA0H-CUV [1.8m]) to connect a personal computer loader.
RUN/MEM
(green)
––Battery voltage is low or the battery connection switch is OFF
ALM
(red)
Status
A program is being downloaded.
(A program is being downloaded while the PLC is stopped or
being rewritten while the PLC is running)
A program is being rewritten while the PLC is running when
the CPU is running in a nonfatal fault condition.
A program is being downloaded when the CPU is stopped in a
fatal fault condition.
A unit fault has occurred.
(system ROM or system RAM error)
3) I/O terminal block
Upper side: Terminals for external power supply (24V DC, 400mA) and input terminals
Lower side: Terminals for power supply to control the unit and output terminals
* The tightening torque: 0.59 to 0.78N·m.
* For the details of the signal assignment and wiring method, see “3-10 Terminal Arrangement.”
* The terminal blocks of advance main units (NA0PA***) are detachable.
The terminal blocks of basic main units (NA0PB***) are not detachable.
4) Battery connection switch
ON (upper side) : The battery is internally connected to the PLC.
OFF (lower side): The battery is internally disconnected from the PLC (factory default setting)
* When you start using the main unit, set the battery connection switch to ON.
For details, see “3-2-2 Memory backup and internal battery specications”.
3-40
Section 3 Specications
Protect switch
(Right side face when mounted)
ON (upper side): Write protected
5) Memory pack connector
A memory pack for user ROM operation and data storage is connected.
• Memory pack (Type: NA8PMF-20)
OFF (lower side): Write enabled
• Operation when a memory pack is mounted
ItemProtect switch OFFProtect switch ON
When the main unit is powered on
Execution of project downloading
Execution of resource initialization
Data writing to the memory packData can be written.Data can be written.
• How to perform operation with a project in the memory pack (user ROM operation)
1) Power off the main unit.
2) Turn off the protect switch of the memory pack and mount it on the main unit.
3) Power on the main unit and download a project from the loader.
4) Power off the main unit.
5) Remove the memory pack from the main unit, turn on the protect switch, and then mount it on the main unit again.
6) Power on the main unit.
(Operation starts with the project in the memory pack.)
Operation is performed with the
project in the built-in ash memory
The project is also stored in the
memory pack.
The project in the memory pack is
also cleared.
Operation is performed with the
project in the memory pack
Not possible
(CPU memory access error)
Not possible
(Clearing failed.)
3-41
Section 3 Specications
2) I/O terminal block
3-11-2 Expansion unit
(1) Names
1) Status indication LED
Expansion connector (IN)
Expansion connector (IN)
Expansion connector (OUT)
Nameplate (on the right side)
2) I/O terminal block
DIN rail tab
2) I/O terminal block
1) Status indication LED
Expansion connector (OUT)
Nameplate (on the right side)
2) I/O terminal block
Expansion connector (IN)
DIN rail tab
2) I/O terminal block
1) Status indication LED
Expansion connector (OUT)
Nameplate (on the right side)
2) I/O terminal block
DIN rail tab
3-42
Section 3 Specications
(2) Functions
1) Status indication LED
Input status indication (red)
* The left gure shows the status indication LED
of the expansion unit with 24 points.
Output status indication (red)
PWR (red)Status
ON (red)Power is being supplied normally.
OFF
3) I/O terminal block
* The tightening torque: 0.59 to 0.78N·m.
* For the details of the signal assignment and wiring method, see to “3-10 Terminal Arrangement.”
* The terminal blocks of expansion units are not detachable.
Unit with power supply: The power supply of the main unit is OFF or the expansion cable is disconnected.
Unit without power supply: The power supply is OFF.
3-43
Section 3 Specications
4
Unit: mm
4
Unit: mm
3-12 Dimensions
3-12-1 Main unit
(1) Main unit with 14/24 points
The main unit with 14 points and the main unit with 24 points have the same dimensions.
Target type : NA0PA14T-34C, NA0PB14R-34C
: NA0PA24T-34C, NA0PA24T-31C, NA0PB24R-34C
4
2×Φ4.5
(20)(25)
4
903
34.5
21
90
4
(2) Main unit with 32/40 points
The main unit with 32 points and the main unit with 40 points have the same dimensions.
Target type : NA0PA32T-34C, NA0PA32T-31C, NA0PB32R-34C
: NA0PA40T-34C, NA0PA40T-31C
4
2×Φ4.5
(20)(25)
4
(97)
80
7.5
90
30.3212127.4
130
4
3-44
(97)
80
7.5
3
Section 3 Specications
4
903
Unit: mm
(2) Main unit with 60 points
Target type : NA0PA60T-34C, NA0PA60T-31C, NA0PB60R-34C
4
2×Φ4.5
(20)(25)
4
2140.32152.4
175
4
80
(97)
7.5
3-45
Section 3 Specications
3.8
Unit: mm
4
Unit: mm
3-12-2 Expansion unit
(1) Expansion unit with 8 points, AIO expansion unit, Load cell unit, Expansion power supply unit,
High-precision load cell unit
Target type : NA0E08R-3, NA0E08T-3, NA0E08X-3, NA0E08T-0,
(2) Wiring to terminal ...................................................................................... 4-14
(3) Emergency stop circuit and interlock circuit ............................................. 4-15
Section 4 Installation and Wiring
4-1 Installation Precautions
This section describes the precautions related to installation and wiring that must be observed in order to ensure high reliability
and performance of this system. Those calling for special attention are indicated below.
4-1-1 Installation Environment
Handle with care.
Caution
1) Do not drop or bring down the product.
2) Do not install the unit in locations which are subject to
excessive vibration.
Do not install or use the product as shown below.
Doing so may cause damage, malfunction, or failure of the product.
PLC
PLC
5) Do not use the unit in places with high temperature and
high humidity or with temperature too low.
(Locations where condensation may occur because of
rapid temperature changes.)
Operating temperature: 0 to 55°C
Operating humidity: 20 to 95%RH (without condensation)
PLC
PLC
3) Do not install the unit in locations where corrosive gas is
present.
PLC
4) Do not install the unit in locations where there is a lot of
dust, conductive particles such as steel particles or oil
mist, or high salinity.
PLC
6) Do not mount the unit on a panel in which high-voltage
devices (3000V, 6000V or higher) are mounted.
7) Do not use the same power supply which supplies the
power to a noise generating device.
PLC
High-voltage device
Noise generating device
8) Do not install the unit in locations where a strong electric
or magnetic field is generated.
PLC
+
4-1
-
Section 4 Installation and Wiring
Ladder representation
Program
4-1-2 Before installation
(1) Check the product
When you unpack the product, check to see
1) That the product is as ordered, and
2) That the product is not damaged, and
3) That accessories are included as specied.
(2) Operation check of the main unit
This check is performed to see that the product you received operates normally before it is installed in the control panel.
The purpose of this check is to detect as early as possible any defects that might have occurred in the product during
transportation. Therefore, it is recommended that you perform this check for sure.
1) Wiring the power terminals
2) Checking PLC operation using a test program
Load the following program into PLC internal memory and test PLC operation. If the PLC operates normally, proceed to the next
step (installing the PLC in a control panel). If the PLC does not operate normally, ensure the power supply connection, power
voltage, and the program are correct.
%IX0.0.0%QX0.4.0
Notes:
Specify addresses that conform to the user’s PLC.
4-2
Section 4 Installation and Wiring
4-1-3 Control panel mounting (protection against noise)
The SPF series products are especially immure to noise pickup. However, it is always recommended to take the following
measures to further enhance system reliability.
erusaemretnuoCesion fo esuaC.oN
1Noise via power-supply terminals
• Lightning surge
• Internal surge (switching surge)
1) An isolation transformer should be used.
PLC
Electrostatic shielding
(to reduce the stray capacitance
between the primary and
secondary coils)
2) An isolation transformer should be used.
Device
Other device
Other device
PLC
Surge absorber
(FUJI Z-trap)
Cabinet
.desu eb dluohs retlif esion A esion ycneuqerf-hgiH2
Twisted pair wires should be used between the noise
filter and power-supply terminals of the PLC.
Type D (Class 3) grounding
(ground resistance of
100Ω or less)
4Noise via ground of the secondary coils of a transformer• The secondary side of the isolation transformer should
not be grounded as shown in the above ltem 1.
4-3
Section 4 Installation and Wiring
5When inductive load current is interrupted by a switch,
high voltage is induced between the two ends of the load,
which may affect the PLC.
Interrupting current
Arc discharge
1) A diode, varistor or RC should be connected to the
DC load.
2) A RC should be connected to the AC load.
(Example)
erusaemretnuoCesion fo esuaC.oN
Switch
Low voltage
Surge voltage
(10 to 20 times the load voltage)
6Malfunction due to external I/O signal lines bound
together with or installed near a high-voltage cable or
power cable
(Electromagnetic inducation, electrostatic induction)
7Transmission cable malfunction or damage caused by
lightning surge
Uphill
station
Mountain
Lightning
Transmission cable
Downhill
station
Power supply
Load
I/O lines should be separated from other cables and
should not be wired in the same panel or pit.
Duct, independent cable pipe or metal pipe (as shown
below) should be used for isolation.
Transmission cables should run through underground
metal pipes or in an electrical duct. The metal pipes
should be grounded.
RS-232C, RS-485, etc
Type D (Class 3) grounding
(ground resistance of 100Ω or less)
Metal pipe
8Malfunction of PLC located near device that
generates a switching arc
Magnetic
contactor
PLC
L
When the control panel door closed, if the distance
L between the PLC front panel and magnetic
contactor is 50mm or less, the PLC malfunctions
due to the switching arc generated by the magnetic contactor.
The device layout should be changed or a shielding
panel should be installed.
(Example)
Door
Magnetic
contactor
Shielding panel
PLC
4-4
Section 4 Installation and Wiring
4-1-4 Environmental condition for mounting PLC on panel
Caution
Use this PLC in the environment described below.
High temperature, high humidity, condensation, dust, corrosive gases, oil, organic solvents, excessive vibration or shock
might cause electric shock, fire, erratic operation or failure.
Keep an open space around the PLC as shown below to obtain sufficient ventilation, otherwise, abnormal temperature
rise or failure occurs.
FUJI PLCs are reliable because they provide excellent resistance against environmental conditions. Note that system reliability
and operational safety can be further improved by observing the following precautions.
ItemSpecicationsRemarks
Temperature
• The PLC must be operated in the environment from
0 to 55°C according to specication of components.
• The PLC should not be installed where it will be
exposed to direct sunlight.
• To maintain the ambient temperature within the
specied range, a fan or air-conditioner must be
introduced in case of excessively high ambient
temperature or a heater must be installed in the
panel in case of excessively low ambient temperature.
Humidity • The relative humidity must be from 20 to 95%.
• Condensation due to sudden temperature changes
must be avoided.
• In winter, condensation may be caused by
temperature change when a room-heater is turned
ON and OFF. This condition must be avoided by
leaving the room-heater on even during the night or
by other measures.
Vibration
Shock
Atmosphere
2
• 19.6 m/s
• 98 m/s
(screw mounting)
2
(rail mounting)
• Corrosive gases must be prevented.
• In case of excessive vibration, secure the panel with
vibration-absorbing rubber or reduce vibration by
improving the building structure and oor strength.
• If there are harmful gases, air-purging inside the
panel must be introduced. (air-lteration)
PLC layout1) Keep all units at least 100mm apart vertically. Otherwise, excessive temperature rise may occur.
2) Keep units at least 50mm away from other devices and the building structure to ensure appropriate
ventilation.
3) Heat-generating devices (heaters, transformers and resistors) must not be installed directly under the PLC.
4) The PLC must be isolated (shielded) from high-voltage devices, high-voltage cables and power equipment
as far as possible. PLC I/O cables must not be run parallel with the cables for those devices.
5) The PLC must be installed in a vertical position. Installing the PLC on a level (as shown in illustration below)
will cause adverse thermal affects on the device.
Front viewSide view
2)
Expansion
unit
Other
device
Other
100mm50mm
1)
4)
High
voltage
device
device
Floor surface
5) PLC
PLC
Main unit
Other
device
Other device
2) 50mm
3) Heat generating
device
4-5
PLC
2)
50mm
5) PLC
Section 4 Installation and Wiring
1)
4-1-5 Mounting methods
There are two methods for mounting the unit in the panel: screw mounting and rail mounting. Be careful to note that, as
compared with screw mounting, rail mounting is, on the one hand, advantageous in ease of mounting and removal, but on the
other hand has the disadvantage of being vulnerable to vibration or shock.
(1) Mounting with a DIN rail
You can use a DIN rail to mount a unit in locations not to subject to a vibration of 0.5G or more. As shown in the gure below,
use DIN EN50022 DIN rail.
Mounting a unita
1mm
7.5mm
Hold the unit facing its front, press it down with a 15 degree tilt onto the DIN RAIL. Swing it down until the
upper edge of DIN RAIL groove on the unit back touches the upper tab of DIN RAIL. Then use this lockedin point as a pivot to press the unit forward on the bottom and lock it in position. The procedure is illustrated
below:
Make sure the tab is pressed in, or
it cannot be locked into position.
35mm
1)
Dismounting a unit
2)
2)
Use a long screwdriver to reach in the hole on the DIN RAIL tab. Pull out the tab to “pulled out” position
a
to remove the unit, as shown in the gure below.
Tab in “pulled out” position
4-6
Section 4 Installation and Wiring
2 × M3 to M4
4
82
2 × M3 to M4
4
82
2 × M3 to M4
482
(2) Mounting with screws
In locations subject to larger vibration (more than 0.5G), the unit must be secured by M3 or M4 screws. The positions and sizes
of the screw holes of each SPF unit are illustrated below.
Expansion units connected to the main unit can be mounted without gaps.
PORT4 (RS485)
+
G
TNN
PORT3 (RS485)
+
G
T
m
400mA
TX
RX
TX
RX
INAC100~240V
L N
X0 X2 X4 X6 X8 X10X12 X14X16 X18
24V OUT
.
x
a
S/S
X1 X3 X5 X7 X9 X11 X13X15 X17 X19
IN (X)
PWR/
BAT
RUN/
MEM
ALM
OUT (Y)
PORT0
Y1 Y2 Y4 Y5 Y6Y8 Y10
C0 Y0 C2 Y3 C4 C6 Y7 C8 Y9 Y11
X20X22
0
4
A
P
A
N
Y14Y12
C12Y13 Y15
X21X23
-
3
0
T
O0+O1+
Y1Y2C2 C4C0
Y0
1
C
Y10Y8Y11 Y12 Y14
Y9C8C10 C12 Y13 Y15
Y5 Y7
Y3 Y4 Y6
NA0E16T-0
24V IN
AG O0-
NA0AW06-MR
I0+I1+ I2+I3+
I0-I1- I2-I3-
O1-
O0+O1+
24V IN
AG O0-
NA0AW06-MR
I0+I1+ I2+I3+
I0-I1- I2-I3-
O1-
NA0LA-RS5
<How to connect an expansion right side unit>
1) Remove the connector cover of the expansion connector (right side) of the main unit or that of the expansion connector (OUT)
of the expansion unit that is mounted on the left of the expansion right side unit to be connected.
2) Connect the expansion cable connector equipped with the expansion right side unit to be connected to the expansion
connector described in the step 1).
3) After the connector is connected, store the remaining cable inside the connector housing of the unit on the left side.
4) Attach the connector cover removed in the step 1).
X6 X8 X10 X12
X5X9 X11X7X12
2
0
3
I
4
65
7
II
I0
8
9
I2 I3
IN (X)
PWR/
BAT
RUN/
MEM
ALM
OUT (Y)
2
0
3
I
5
4
7
6
9
8
Y4 Y5 Y6 Y8
Y7 Y9C4 C4
Expansion
connector
Store the remaining
expansion cable here.
O0+ O1+
24V IN
AG O0-
I0+ I1+ I2+ I3+
I0- I1- I2- I3-
O1-
Expansion cable
<How to connect a healthy unit>
1) Remove the connector cover of the expansion connector (OUT) of the rightmost expansion right side unit.
2) Mount a healthy unit to the expansion connector described in the step 1).
(The connector cover removed in the step 1) is not used.)
4-9
Section 4 Installation and Wiring
the expansion cable inlet.
Expansion left side unit
<How to connect an expansion left side unit>
1) To connect an expansion left side unit, break the plastic part of the expansion cable inlet of the main unit.
• Remove the cover plate on the front of the main unit.
• If a front board is already mounted, remove it once.
• Break the plastic part of the expansion cable inlet on the side of the main unit.
2) Connect the expansion cable connector equipped with the expansion left side unit to the expansion connector (left side) of
the main unit.
3) After the connector is connected, store the remaining cable inside the connector housing of the expansion left side unit.
4) If the front board has been removed, reattach it.
5) Attach the cover plate removed in the step 1).
PORT4 (RS485)
+
TX
G
RX
TNN
PORT3 (RS485)
+
TX
G
RX
T
NA0LA-RS5
Expansion cable
connector
Break the plastic part of
<How to mount a front board>
1) Remove the cover plate on the front of the main unit.
2) Mount a front board and x it with the supplied screws (Tightening torque: 0.2 N·m)
3) Attach the cover for the front board.
4-10
Section 4 Installation and Wiring
4-2 Wiring
When performing wiring, observe the following points:
1) Warning for wiring
Warning
Never touch any part of charged circuits as terminals and exposed metal portion while the power is turned ON.
It may result in an electric shock to the operator.
Turn OFF the power before mounting, dismounting, wiring, maintaining or checking, otherwise, electric shock, erratic
operation or troubles might occur.
Place the emergency stop circuit, interlock circuit or the like for safety outside the PLC. A failure of PLC might break or
cause problems to the machine.
2) Cautions for wiring and mounting
Caution
Follow the directions of the operating instructions when mounting the product. If mounting is improper, the product might
drop or develop problems or erratic operations.
Be sure to install the electrical wiring correctly and securely, observing the operating instructions and manual.
Wrong or loose wiring might cause fire, accidents, or failure.
Select a wire size to suit the applied voltage and carrying current, and carry out wiring according to the operating
instructions and manual. Poor wiring might cause fire, erratic operation or failure.
Periodically make sure the terminal screws and mounting screws are securely tightened. Operation at a loosened status
might cause fire or erratic operation.
Before touching the PLC, touch any metallic object which is connected to the ground to discharge static electricity.
Excessive static electricity may cause malfunction or fault.
3) Cautions for checking wiring
Caution
Sufficiently make sure of safety before program change, forced output, starting, stopping or anything else during a run.
Engage the loader connector in a correct orientation, otherwise, an erratic operation might occur.
4) Cautions after wiring
Caution
Remove the dust-cover seals of modules after wiring, otherwise, fire, accidents, failure or fault might occur.
4-11
Section 4 Installation and Wiring
(100‰ or less)
200 mm or more
4-2-1 Wiring and cables
Use the following cables for systems incorporating SPF series products.
Power cable
Main unit
1) Communication cables
For signal line of the communication units/boards
2) Low-power cables
For signal line of the analog units
3) Control cables
4) Power cables
Expansion
unit
Separate general control cables
from power cables.
1)
1)
2)
300 mm or more
3)
300 mm or more
4)
Metal cable rack
or
2)
Type D (Class 3) grounding
(100‰ or less)
3)
4)
Metal cable rack
(steel)
Type D (Class 3) grounding
Cable types
ItemSpecicationsRemarks
Power supply cable for main and expansion unit
Twisted cables 1.25mm
Input device connection cable for main and expansion unit0.5 to 1.25mm
Output device connection cable for main and expansion unit
0.75 to 1.25mm
2
2
2
* For the details of the communication unit/board, refer to the user’s manual “General Purpose Communication (FEH528)”.
* For the details of the analog unit, refer to the user’s manual “Analog Unit (FEH527)”.
4-12
Section 4 Installation and Wiring
Main power supply
Coil terminal
4-2-2 Wiring to power-supply, I/O and ground terminals
(1) Precautions
• If the power supply to be used for the processor module has voltage uctuations that exceed the specied range, a voltage
stabilizer must be used.
Power
supply
Voltage
stabilizer
PLC
• The power supply must not generate excessive noise between power lines or between lines and ground. For details on
countermeasures against excessive noise, see “4-1-3 Control panel mounting (protection against noise).”
• The power supply wiring to the processor module must be separate from wiring for I/O devices and for power equipment.
PLC power supply
I/O device power supply
Main control power supply
To coil
Isolation
transformer
PLC
CR
• The distance between the isolation transformer and the processor must be as short possible and the wire size must be
twisted. To minimize voltage drops, the wire size must be as large as possible (1.25mm2)
• If I/O wiring cannot be separated from the main circuit cables or power cables, bound shielded cables must be used for each
I/O unit and the shield must be grounded at the PLC end.
• The 24V DC I/O cables must be separated from 100V AC and 200V AC cables.
CAUTION
Be careful of the following items when you connect the external power supply (service power) cable of the main unit
(AC power supply specification).
1) Make sure that output current is below the level specified.
Voltage is cut off if the output is short-circuited (overloaded) during operation, and restored when the error is corrected.
2)
(The PLC does not detect the error and continues to run, but externally supplied voltage is lost, resulting in a system error.)
3)
In the short-circuited (overloaded) condition, the PLC won’t start even when the power supply is turned on.
4)
The power supply is a switching regulator. When you connect a high-sensitivity sensor or the like, be sure to check for
any influence from switching noise.
4-13
Section 4 Installation and Wiring
(2) Wiring to terminal
When wiring to PLC terminal, pay attention to the following items.
1) When performing wiring of SPF series PLCs, comply with national and local laws and regulations about installation.
2) Use AWG24 to AWG12 copper wire for the SPF series I/O wire. According to the current loads, select a proper wire.
3) Shorter wires are preferred. It is recommended that the length of I/O wiring does not exceed 100m (10m for high-speed input).
4) Input wiring must be separated from output or power wiring (at least 30 to 50mm apart). In case separation is not possible,
adopt vertical crossing, no parallel wiring is allow.
5) The pitch of an SPF series terminal block is 7.62mm. The torque for screws and recommended terminals are shown below:
7.62 mm
terminal block
< 6mm
M3
< 6mm
M3
Torque: 0.59 to 0.78N·m
4-14
Section 4 Installation and Wiring
MC
(3) Emergency stop circuit and interlock circuit
• To improve operational safety, it is necessary to include an emergency stop circuit which can stop the system operation in an
emergency or at fault occurrence.
The emergency stop circuit should be implemented in a PLC external circuit.
a) Emergency stop circuit
• Congure it in an external circuit.
A normal emergency stop circuit is built into an interlock circuit that detaches an I/O control power at failure.
b) Interlock circuit
• An interlock relay (MC) opens to interrupt the power supply in an emergency or at fault occurrence.
For the interlock circuit, contacts of a relay which works only during normal operation of PLC are inserted into a maintained
circuit.
It is necessary to create PLC application software to turn the contacts of the relay off when a fault is detected.
An emergency stop circuit varies depending on the conguration of the PLC used or controlled object. The example circuit is
shown below.
Transformer
Prepare to
operate
Emergency
stop
MC
MC
AUX
Use output
unit
PLC
AUX
4-15
Section 5 Maintenance and Inspection
5-1 General Inspection Items ........................................................................ 5-1
5-1-1 Inspection frequency .................................................................................. 5-1
5-1-2 Cautions on using the product .................................................................... 5-1
5-3-2 Free-of-charge warranty period and scope of warranty.............................. 5-4
5-3-3 Service costs .............................................................................................. 5-4
Section 5 Maintenance and Inspection
5-1 General Inspection Items
For use of the SPF under the best operating conditions, periodic inspection must be performed.
5-1-1 Inspection frequency
The SPF is a highly-reliable programmable controller, consisting mainly of semiconductor devices. However, because
deterioration of devices may occur due to environmental conditions, periodic inspection is recommended. The standard
inspection should be done once or twice a year; however, it can be shorter, depending on environmental conditions. If any
inspection result does not match the rated value, check the operating conditions to make sure they are appropriate.
5-1-2 Cautions on using the product
Caution
Select a wire size to suit the applied voltage and carrying current, and carry out wiring according to the operating
instructions and manual. Poor wiring might cause fire.
Operate (keep) in the environment specified in the operating instructions and manual. High temperature, high humidity,
condensation, dust, corrosive gases, oil, organic solvents, excessive vibration or shock might cause electric shock, fire,
erratic operation or failure.
Contaminants, wiring chips, iron powder or other foreign matter must not enter the device when installing it, otherwise,
erratic operation or failure might occur.
Periodically make sure the terminal screws and mounting screws are securely tightened.
Before touching the PLC, discharge any static electricity that may have been collected on your body. To discharge it, touch
a grounded metallic object. Static electricity might cause erratic operation or failure of the module.
5-1
Section 5 Maintenance and Inspection
5-1-3 Inspection items
When inspecting the equipment, use the following inspection table.
Is the voltage within the normal range when
measured at a terminal block ?
Are there frequent momentary power failures or
abrupt voltage rises or drops ?
Is the temperature within the specied range ?
(temperature in the panel when installed inside the
panel)
Is there condensation or extreme discoloration or
corrosion ?
Is there any vibration ?
Is there any dirt or other foreign matter ?
Are all modules mounted securely ?No loosenessVisual inspection
Are there any loose screws on the external wiring
terminals ?
Are cable connectors inserted securely ?No looseness
LED must not be
blinking.
AC:
100V: 85 to 132V
240V: 170 to 264V
DC:
24V: 20.4 to 28.8V
Voltage uctuations
must be within the
above range.
0 to +55°CMax./min.
20 to 95%RH
There must be no
vibration.
There should be no
dirt or other matter.
No loosenessScrewdriver
Visual inspection
Voltmeter
Oscilloscope
thermometer
Visual inspection,
hygrometer
Check by touching
Visual inspection
Visual inspection,
Screwdriver
Are any external wiring cables damaged ?
Spare parts
Program
Notes:
1) If a fault occurs, replace the entire faulty unit or board. For this replacement, a minimum amount of space components
should be provided.
2) For spare main units and expansion units, power on once every six months.
(To prevent discharging of aluminum electrolytic capacitor in the power supply module)
Is the designated quantity available ?
Are storage conditions appropriate ?
Were any errors detected through verication ?
Is the source program stored appropriately?
No abnormal
appearance
See the inspection
records.
There must be no
errors.
Visual inspection
Program verication
5-2
Section 5 Maintenance and Inspection
5-2 Actions to be Taken When Battery Voltage Drop is Detected
The primary battery built in the main unit cannot be replaced. When a voltage drop of the battery is detected, you need to
replace the main unit.
If you conrm that the “PWR/BAT” LED of the main unit blinks alternately in red and orange, promptly replace the main unit with
a new one.
Main unit replacement procedure
n
(1) Stop the SPF system and save necessary user data (such as retain memory and user FB / system FB instance memory) in a
backup le in the personal computer with the backup function of the SX control utility of the loader.
(2) Turn OFF the power supply of the SPF system, and then replace the main unit.
(3) Turn ON the power supply of the SPF system. After stopping the main unit, download the backup le to the new main unit
with the SX control utility.
(3) Reset the main unit. Then, the main unit starts up.
5-3
Section 5 Maintenance and Inspection
5-3 Maintenance Services
5-3-1 Ordering notes
When ordering electrical and control equipment (or requesting price estimates), the following general notes are to be observed,
unless otherwise specied in the estimation paper, contract paper, catalogs, or specications.
When the product is delivered, check the contents of the package as soon as possible. Even before inspection, use caution on
storing and using the product safely.
5-3-2 Free-of-charge warranty period and scope of warranty
[Free-of-charge warranty period]
(1) This product is covered by a warranty for a period of one year from the date of purchase or 18 months from the date of
manufacture described in the nameplate, whichever comes earlier.
(2) This warranty period may not be applied if the operating environment, operating condition, operating frequency, or number of
operations affects the operating life of the product.
(3) The warranty period for the product section repaired by Fuji Electric service sector is six (6) months from the date of
completion of repair.
[Warranty period]
(1) If a failure judged to be the responsibility of Fuji Electric occurs during the warranty period, please contact the Fuji sales
agent. By sending back the failed product, it is repaired or the replacement product is delivered on a free-of-charge basis.
However, the following failures are not covered by this warranty.
1) Failures occurring through inappropriate condition, environment, operation, or use not described in the catalog,
operating manual, or specication.
2) Failures occurring through cause other than the purchased product or delivered product.
3) Failures occurring through customer’s equipment or software design, or cause other than products from Fuji Electric.
4) Failures occurring through programs not developed by Fuji Electric as for programmable products
5) Failures occurring through modication or repair not performed by Fuji Electric
6) Failures occurring through failure to perform correctly maintenance or replacement of the consumables described in the
operating manual or catalog
7) Failures occurring through cause which cannot be forecasted by science and technologies practically used at the time of
purchase or delivery
8) Failures occurring through use of the product which is not intended by Fuji Electric
9) Failures occurring through natural calamities, disasters, or other cause judged not to be the responsibility of Fuji Electric
(2) The warranty is limited only to a single purchased product and a single delivered product.
(3) The upper limit of the warranty period is (1). Any damages caused by failures of the purchased product and delivered product
(damages to or loss of machinery and equipment, or passive damages) are not covered by this warranty.
[Failure diagnosis]
Temporary failure diagnosis is intended to be performed by the customer. However, upon request from the customer, Fuji
Electric or Fuji Electric service network offers surrogate services on a fee basis. The fee is borne by the customer according to
the fee code of Fuji Electric.
[Exclusion of responsibility of warranty such as opportunity loss]
Regardless of the free-of-charge warranty period, damages judged not to be the responsibility of Fuji Electric, opportunity
loss on the customer side caused by failure of products from Fuji Electric, passive damages, damages caused by exceptional
circumstances regardless of forecast by Fuji Electric, secondary damages, accident compensation, damages to products not
from Fuji Electric, and damages to other business are not covered by this warranty.
[Repair period after production stoppage and supply period of spare parts (maintenance period)]
As for retired models (products), Fuji Electric performs repair work within seven (7) years from the date of retirement. As for
major spare parts for repair, Fuji Electric also performs repair work within seven (7) years from the date of retirement.
With electronic parts, however, difculty in procurement or production may be anticipated because of short life cycles and
therefore repair or spare parts supply may be difcult even during the warranty period. For details, please contact Fuji
Electric sales ofce or service sector.
5-3-3 Service costs
The price of the product does not include maintenance and servicing costs, such as the cost of dispatching an engineer to the
customer. The customer will be charged for actual expenses in the following cases.
(1) Guidance for installation and adjustment, and attendance at a test operation
(2) Maintenance, inspection, adjustment, and repair
(3) Technical guidance and technical education
5-4
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.