Fuji Electric Fuji Electric PXF Temperature Controller Operations - 4.5 MB Manual

Page 1
MICRO-CONTROLLER X Type : PXF-2
Operation Manual
INP-TN5A2400-E
Page 2
Page 3
Please read the section “Safety Warnings” thoroughly before using. Safety precautions must be taken by every user to prevent accidents. Failure to co mply with the instructions contained in this manual may reduce the safety of the instrument. The safety requirements are classified into “Warning” and “Caution” according to the following interpretations:
WARNING
CAUTION
Mishandling may lead to serious injury or death.
Mishandling may result in personal injury or damage to the property.
1
Page 4
WARNING
Ambient temperature
-10 to 50°C
Operating humidity
90%RH or less (Non condensation)
Installation category:
II
Pollution degree:
2
Recommended fuse
250V AC, 0.1A T(Time-Lag) (AC100~240V) Usage environment
Indoor use
1) Over Voltage Category
II
2) Pollution Degree
2
BASIC INSULATION, SUPPLYMENTARY INSULATION, or REINFORCED INSULATION
4) Maximum Voltage line to neutral
300Vac rms or 300Vdc
Installation and wiring
This equipment is intended to be used under the following conditions.
400V DC/400V AC, 1A T(Time-Lag) (DC/AC24V)
If accessible Safety Extra Low Voltage (SELV) circuits are to be connected to Signal input terminal, SSR
drive output terminal, Current output terminal or Communication (RS485) terminal, ensure to provide a basic insulation between the SELV circuits and these terminals. For example, use transformer which has a basic insulation or higher degree of insulation.
If accessible Safety Extra Low Voltage (SELV) circuits are to be connected to Communication (RS-485)
terminal, be sure to provide a basic insulation between these terminals. For example, use a RS-485/232 converter which has a basic insulation. The basic insulation requires a clearance at least 1.5 mm and a creepage of at least 3.0 mm. Failure to maintain these minimum distances would invalidate the UL61010/EN61010 safety approval. For 24V DC/AC power supply model, if the equipment is connected to the Safety Extra Low Voltage (SELV)
circuit, a basic insulation must be provided between the SELV circuit and the power input terminals.
Otherwise, the power input terminals must be connect to Extra Low Voltage (ELV) circuit so as to prevent the
electric shock. For CT input, use Current Transfer which has specification as shown below in order to prevent the electric
shock and spread of fire.
According to IEC 61010-1
3) Required level of Insulating
2
Page 5
About safety standard
Please observe the following instructions to meet the requirements of safety standard. Failure to observe these instructions violates safety standards. (This product is not safety equipment.)
Install a recommended fuse, which is specified in the instruction manual, between the external main power (Mains Circuit) and this equipment.
Do not connect SELV directly to Signal input terminal, SSR Drive output terminal, Current output terminal, or Communication (RS-485) terminal. Otherwise, it may result in electrical shock.
If accessible Safety Extra Low Voltage (SELV) circuits are to be connected to Signal input terminal, SSR Drive
output terminal, Current output terminal or Communication (RS-485) terminal, ensure to provide a basic insulation between the SELV circuits and these terminals. For example, use transformer which has a basic insulation or higher degree of insulation.
If accessible Safety Extra Low Voltage (SELV) circuits are to be connected to Communication (RS-485) terminal, be
sure to provide a basic insulation between these terminals
For example, use a RS-485/232 convert e r which has a basic insulation. The basic insulation requires a clearance at least 1.5 mm and a creepage of at least 3.0 mm.
Be sure to install an appropriate external protective circuit to prevent excessive temperature rise etc.
When performing wiring work, be sure to turn the power off and to wear protection gloves or safety glasses, to
prevent an electric shock.
Set proper parameter input signals which correspond to each input to be connected.
Be careful not to confuse voltage input with current input, or vice versa.
Do not use this equipment for the measurement of circuits which falls under measurement categories II, III, or IV.
Do not use this equipment for measurement of signals to which a voltage over 30 Vr.m.s. or over 60 V DC is applied.
Be sure to use terminal covers. Before removing a terminal cover, turn off all the power.
For the above, if voltage exceeds 50Vdc ( called danger voltage), grounding and basic insulation for all
terminals of the equipment and auxiliary insulation for DO outputs are required. Note that the insulation class for this equipment is as follows. Before installing, please confirm that the insulation class for equipment meets usage req uirements.
Type PXF4
3
Page 6
Type PXF5/9
In cases where damage or problems with this equipment may lead to serious accidents, install appropriate external protective circuits.
As this equipment does not have a power switch or fuses, install them separately as necessary. If you install a fuse, be sure to place it between the main power switch and this equipment.
(Main power switch: 2-point Breaker, fuse rating: 250V 1A)
A power switch or a circuit breaker should be installed within the power supply facility.
A power switch or a circuit breaker should be properly installed within easy reach of an operator.
A power switch or a circuit breaker should be identified as the one for this product.
Electrical wiring must be made by the qualified personnel only and in accordance with your local and national standards.
For power supply wiring, use wire equal to 600V vinyl insulation or above.
To prevent damage and fa i lure of the equipment, provide the rated power voltage.
To prevent shock and equipment failure, do not turn the power ON until all wiring is complete.
Before feeding power, confirm that clearance space has been secured to prevent shock and fire with the equipment.
Do not touch the terminal while the machine is on. Doing so risks shock or equipment errors.
Never disassemble, convert , m odify or re pair t hi s equipm ent . Doing so ca rries the ris k of abnorm al opera tion, s hock a nd fire .
Output relays has limited-life. The contact of output relay may stay ON or OFF when it reaches the end of its service life.
Be sure to provide an external protective circuit for safety.
The factory default setting of this equipment is as follows. Change the setting as necessary so as the equipment to meet your application.
Please note that the improper settings may result in overheat or unexpected damage. For the details of operation, read
this manual.
Control output 1: heating control Control output 2 (optio na l): cooling control Digital input 1 to 5 (optional): no function
Symbols on the equipment
Please read this instruction manual thoroughly, and use the product accordingly.
Maintenance
When installing and removing the equipment, turn the power OFF. Failing to do so may cause shock operational errors or failures.
Periodic maintenance is recommended for continuous and safe use of this equipment.
Some components used on this equipment have a limited life and/or may deteriorate over time.
The warranty period for this unit (including accessories) is three year after the date of manufacture, if the product is used
properly.
4
Page 7
About EMC standard
or it may cause electric jamming. If you use this equipment in home environment, install appropriate measures on the
CAUTION
Cautions on installation
Avoid the following places for installation:
A place where the ambient temperature may reach beyond the range of from 0 to 50°C while in operation.
A place with rapid temperature changes, leading to dew condensation
A place where corrosive gases (sulfide gas and ammonia gas, in particular) or combustible gases are emitted.
A place with vibration or shock directly. (Vibration and shock may cause output relay malfunction.)
A place exposed to water, oil, chemicals, steam and/or vapor.
(If the equipment gets wet, there is a risk of electric shock or fire, so have it inspected by the distributor.)
A place where the unit is exposed to dust, salt air, or air containing iron particles.
A place where the unit is subject to interference with static electricity, magnetism, and noise.
A place where the unit is exposed to direct sunlight.
A place where the heat may be accumulated due to the radiation of heat.
Recommended site condition:
A plac e where the ambient hum idity during operation is between 45 to 85%RH.
This equipment is designed as Class A (for industrial environment). Do not use this equipment in home environment,
outside of the equipment.
Under the requirement of EMC standard, the maximum length of a sensor to be connected to this equipment is 30 m. Do not connect the sensor longer than 30 m.
Caution on installation on panel
Attach the included Fixtures (2 pieces) onto the top and bottom of PXF5/9 , and tighten them with a screwdriver. The clamp torque is approx. 0.15 N·m (1.5 kg·cm) The plastic fixture is designed such that over tightening will cause left/right cracking to the central area of the Fixtures and hence reduce the torque. Cracking to the central area will not cause any problems in terms of usability of the equipment as is.
(However, do exercise caution in not applying too much torque because the casing is made of plastic.)
The front of this equipment is waterproof in compliance with NEMA-4X standards (IP66-equivalent). However, regarding waterproofing between the equipment and the panel, use the included packing to ensure waterproofing and attach it according to the guidelines below. (Incorrect attachment may cause the equipment to lose its waterproof capabilities.)
(1)As shown in Fig. 1, insert the panel after attaching the packing to the equipment case. (2)As shown in Fig. 2, tighten the fixture screws so that no gaps can remain between the equipment face, the packing
and the panels. Once finished, confirm that there are no changes in shape such as displaced or improperly-fitted packing, etc. as shown in Fig. 3.
Please exercise caution if the panel strength is weak and gaps develop between the packing and the panel, as this will result in the loss of its waterproofing capabilities.
5
Page 8
PXF4
In order not to hamper heat radiation, do not block the sides of the equipment.
For PXF9, please attach the Fixtures to the attachment holes in the center of the main unit.
Mounting on vertical plane (in horizontal position)
PXF5/9
Mounting on vertical plane (in horizontal position)
Do not block the air vents on the upper part of the terminal.
Cautions on wiring
For thermocouple input, use the designated compensation lead; for resistance temperature sensors, use wires with small lead wire resistance and without any resistance difference among the three wires.
To avoid noise conductor effects, do not use input signal wires in close proximity with electric power lines or load lines.
Use the input signal lines and output signal lines that are separated from each other and are shielded.
If there is a lot of noise from the power source, adding an insulation transducer and using a noise filter is recommended.
(For example, noise filter: ZMB22R5-11 manufactured by TDK)
Always attach a noise filter to a panel that is grounded securely, and keep the wiring between the noise filter output side
and the measuring equipment power terminal wiring to a minimum length. Please do not attach fuses and switches, etc. to the noise filter output wiring since doing so will decrease the filter’s effectiveness.
Twisting the measuring instrument wiring is effective when connecting the wires. (The shorter the pitch of the twist, the more effective the connection is against noise.)
When the power is turned on, it takes some time before a contact output starts operation. If using it as a signal to an external interlock circuit, please couple it with a delayed relay.
Concerning the output relay, connecting the maximum rated load will shorten the relay’s life; so please attach an
auxiliary relay. If the output operation frequency is high, selecting a SSR/SSC drive output type is recommended.
[Proportional cycles] Relay output: 30 seconds or more, SSR/SSC drive output: 1 second or more
6
Page 9
Voltage
Nominal varistor voltage
100 V
240 V
200 V
470 V
PXF5/9 PXF4
When inductive loads such as magnetic opening/closing equipment, etc. as relay output equipment are connected, use of a serge absorber is recommended in order to protect the connection points against opening/closing surges and to ensure long-term use.
Recommended specification for surg e absorber
Key Operation Cautions/Error Operations
The alarm function does not work properly when an error takes place unless the settings are made correctly. Always verify its setting before operation.
If the input wiring breaks, the display will read "UUUU" or "LLLL". When replacing the sensor, always turn the power OFF.
Others
Do not wipe the equipment with organic solvents such as alcohol or benzene, etc. If wiping is necessary, use a neutral cleaning agent.
Do not use mobile phones near the instrument (within 50 cm). Otherwise malfunction may occur.
Trouble may occur if the equipment is used near a radio, TV, or wireless device.
Do not turn off the power right after you change the setting. If you turn off the power after setting change, be sure to wait
for a few seconds before turning it off, so that the changed values can be stored on the nonvolatile memory.
7
Page 10

Contents

PLEASE READ FIRST ································································································· 1 Contents ······················································································································· 8 For Proper Use ············································································································· 9 Model Specifications ····································································································· 10
1 Part names and functions ············································································· 14
Digital characters ······························································································· 18 1-1
2 Basic Operation ···························································································· 19
Basic operation ·································································································· 19 2-1
Changing SV (set value) ···················································································· 20 2-2 Parameters List ································································································· 21 2-3
3 Parameter functions and setting procedure ·················································· 29
Operation mode ································································································· 29 3-1
CH1 PID (Control parameters) ·········································································· 41 3-2 CH2 PLT (PID palette parameters) ···································································· 57 3-3 CH3 PRG (Ramp soak parameters) ·································································· 70 3-4 CH4 MON (Monitor parameters) ······································································· 82 3-5 CH5 ALM (Alarm parameters) ··········································································· 100 3-6 CH6 SET (Setup parameters) ··········································································· 114 3-7 CH7 SYS (System parameters) ········································································· 141 3-8 CH8 MATH (Calculation parameters) ································································ 162 3-9
CH9 COM (Communication parameters)························································· 166 3-10
CH10 PFB (PFB parameter) ············································································ 175 3-11
CH11 DSP (Parameter mask) ·········································································· 181 3-12 CH12 CFG (Configuration parameters) ··························································· 182 3-13 CH13 PASS (Password parameters) ······························································· 194 3-14 TROUBLESHOOTING ···················································································· 196 3-15
8
Page 11
Confirmation of model code
Please confirm that the model delivered matches your order. "Model Specifications" (page 10)
Installation and Mounting
External dimensions
"3 Installation and Mounting" (instruction manual)
Wiring
Terminal connection diagram "4 Wiring" (instruction manual)
Power ON
Display and Operations
Changing set value
"3-2 CH1 PID (Control parameters) " (page 41)
Advanced Usage
Setting of input sensor and input range
"(4) Self tuning control (SELF) (3) Fuzzy control (FUZY)" (page 151)
Operation
Error Indications
Display during equipment error "3-15 TROUBLESHOOTING" (page 196)
minutes.

For Proper Use

•Panel cutout
• Panel mounting dimensions
Parameters List Functions of the Temperature Controller
Basic operations Parameters List Parameter setting "2-1 Basic operation" (page 19)
"2-2 Changing SV (set value)" (page 20)
Selecting control method Controlling through auto-tuning Parameter setting "3-7 CH6 SET (Setup parameters)" (page 114) "3-2 CH1 PID (Control parameters)" (page 41) "AT Auto tuning (005)" (page 33
Wait 30 minutes for the controller to be stabilized thermally. Operations such as measurements should be started after the equipment has been energized at least for 30
9
Page 12

Model Specifications

<PXF4>
10
Page 13
11
Page 14
<PXF5/9>
12
Page 15
13
Page 16
Operation keys
Indicators
USER key
assigned function. (No function is allocated at the
selection mode, or setup mode to return to PV/SV
ss this key once in PV/SV display to move to Press and hold this key in setup mode to move to Press this key once in channel selection mode to move
to move to Press this key once in parameter selection submode of Press this key once in parameter editing submode to
save the change and return to parameter selection
Use the this key to select the digit when changing
Use the this key to change SV value when in PV/SV During in operation control mode, channel selection
mode, or setup mode, this key allows you to change During in parameter setting mode, this key allows you
Shows set value. Shows parameter set point when in

1 Part names and functions

This section describes the names and functions of each part of the front panel. The front panel has the PV and SV displays, the status indicator lamps, and the setting keys, etc. Their functions are explained below. Please read and understand them before using the PXF. For details about the setting of parameter s, see Chapter 2.
PXF4>
• Pr ess this key once in PV/SV display to switch between SV display and MV display.
• Press and hold this key in PV/SV display to start the factory.)
• Press this key once in operation control mode, channel­display.
SEL key
• Pre operation control mode.
• channel selection mode.
• to setup mode.
• Press and hold this key in setup mode channel selection mode.
• setup mode to enter parameter editing submode.
• submode.
< key
• values.
˅˄ key
• screen.
• parameters to be displayed.
• to change parameter settings.
(1) Indicates process value (PV)
Shows parameter name when in parameter setting.
(2) Set point (SV)
parameter setting.
(3) Screen No.
Shows screen No. when in parameter setting.
(4) OUT1 indicator
Lights during control output 1 is ON.
(5) OUT2 indicator
Lights during control output 2 is ON.
(6) EV 1, EV 2, EV 3 indicators
Lights during digita l output 1 to 3 are ON.
(7) STBY indicator
Lights during standby .
(8) MANU indicator
Lights during manual mode.
(9) Lock indicator
Lights during key lock.
(10) No. indicator
Lights during a screen No . is displayed.
(11) RUN/HOLD/END indicators
Lights during ramp/soak operation.
(12) AT indicator
Lights during auto tuning.
(13) MV indicator
Lights during MV is displ a y ed on SV display.
(14)°C/˚F indicator
Shows the temperature unit under use.
14
Page 17
(The factory set function for this key is switching
(The factory set function for this key is switching between start/stop of auto-tuning.)
USER + ˄ key
• Press and hold this key in PV/SV display to start the assigned function.
between RUN and standby.)
USER + ˅ key
• Press and hold this key in PV/SV display to start the assigned function.
(15) A/%/kW/h indicator
Shows the unit under use for the values displayed on SV
display.
15
Page 18
Operation keys
Indicators
assigned function. (No function is allocated at the
e, or setup mode to return to PV/SV
Press this key once in PV/SV display to move to
Press this key once in parameter selection submode of Press this key once in parameter editing submode to save
Use the this key to change SV value when in PV/SV During in operation control mode, channel selection
mode, this key allows you to change
Shows set value. Shows parameter set point when in
Shows the temperature unit under use.
<PXF5/9>
USER key
• Pr ess this key once in PV/SV display to switch between SV display and MV display.
• Press and hold this key in PV/SV display to start the factory.)
• Press this key once in operation control mode, channel­selection mod display.
SEL key
• operation control mode.
• Press and hold this key in setup mode to move to channel selection mode.
• Press this key once in channel selection mode to move to setup mode.
• Press and hold this key in setup mode to move to channel selection mode.
• setup mode to enter parameter editing submode.
• the change and return to parameter selection submode.
< key
• Use the this key to select the digit when changing values.
˅˄ key
• screen.
• mode, or setup parameters to be displayed.
• Dur ing in parameter setting mode, this key allows you to change parameter settings.
(1) Indicates process value (PV)
Shows parameter name when in parameter setting.
(2) Set point (SV)
parameter setting.
(3) Screen No.
Shows screen No. when in parameter setting.
(4) OUT1 indicator
Lights during control output 1 is ON.
(5) OUT2 indicator
Lights during control output 2 is ON.
(6) EV 1, EV 2, EV 3 indicators
Lights during digita l output 1 to 3 are ON.
(7) STBY indicator
Lights during standby .
(8) MANU indicator
Lights during manual mode.
(9) Lock indicator
Lights during key lock.
(10) No. indicator
Lights during a screen No . is displayed.
(11) RUN/HOLD/END indicators
Lights during ramp/soak operation.
(12) AT indicator
Lights during auto tuning.
(13) MV indicator
Lights during MV is displa yed on SV display.
(14) °C/˚F indicator
16
Page 19
et function for this key is switching
(The factory set function for this key is switching between start/stop of auto-tuning.)
USER + ˄ key
• Press and hold this key in PV/SV display to start the assigned function.
(The factory s
between RUN and standby.)
USER + ˅ key
• Press and hold this key in PV/SV display to start the assigned function.
(15) A/%/kW/h indicator
Shows the unit under use for the values displayed on SV
display.
(16) Bar graph
Shows MV.
17
Page 20

Digital characters 1-1

The following tables provide correspondence between digital characters used for the display of the controller and alphanumerical characters. (See the following table for details.)
18
Page 21
Operation mode
You can check the output value (MV) and the amount of electric power by switching the screen.
Operation control mode
In this mode you can put the device to standby or change the alarm set value.
Channel selection mode
In this mode you can select the parameter channel to be displayed.
Setup mode
In this mode you can setup each parameter. This mode includes the parameter selection submode and the
˄˅
values by using ˄˅ keys.

2 Basic Operation

Basic operation 2-1

The below figure illustrates the mode transition and the key operations.
In this mode the normal operation is performed . The process value (PV) and the set value (SV) are displayed. The device starts in this mode when you turn on the power. You can change the set value (SV) in this mode.
parameter editing submode, which can be swit ched by SEL key. In the parameter selection submode, you can switch between parameters by using
keys. In the parameter editing submode, you can change parameter
19
Page 22

Changing SV (set value) 2-2

[Description] _______________________________________________________________
• The SV is a target value for control.
• SV must be within the range between SVL (lower limit) and SVH (upper limit) which belong to Pid parameter.
Related parameters: SVL (page 50), SVH (page 50)
[Setting example] Changing the SV from 250°C to 1195°C __________________________
Display Operating procedure
245
250
245
1195
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press
˅ key to change SV to “1195”.
○˄○
3. Press the SEL key to save the change.
(The change will be saved after three seconds, even if you do not press any key.)
20
Page 23

Parameters List 2-3

The following explains each channel p ar ameter.
• The range of the parameters in the shaded area indicat es the industrial values. When you change the PV input lower limit (Pvb), PV input upper limit (PvF), or decimal place position (Pvd), reconfigure all the industrial values.
• When the parameter that has [RESET] on its Remarks column is changed, turn off the power once, and then re-start the controller.
21
Page 24
22
Page 25
23
Page 26
24
Page 27
25
Page 28
26
Page 29
27
Page 30
28
Page 31
Display
Operating procedure
3 Parameter functions and setting
procedure

Operation mode 3-1

MAN Auto/manual switchover (001)
[Description] ________________________________________________________________
Manual control allows you to set the control output to any value.
• Range: oFF (auto) / on(manual)
• MANU indicator lights during manual operation.
• In this screen, only the switchover between auto/manual is available. Manual operation of contr ol output is available on PV/MV screen.
Note: This parameter is not displayed in default setting. To use this parameter, change the setting of "CH11 dSP".
[Setting example] Changing the mode from Auto to Manual __________________________
oN
PV
SV
PV
SV
SV
PV
245
250
MAN
oFF
MANU
MAN
SV
oN
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Press the SEL key to enter MAN mode.
(The lower part of the screen begins to blink.)
4. Use the
˅ keys to change oFF to oN.
○˄○
5. Press the SEL key to save the change.
The mode switches from the auto mode to the manual mode. (MANU indicator turns on.)
6. Press the key to return to the PV/SV display.
29
Page 32
Related parameters:
SbMd (page 133), Sbo1(page 132), Sbo2 (page 132)
Point:
• When "hold alarms" is on, the hold function activates when you switch the standby
will begin again when standby mode is turned off.
StbY RUN/Standby switchover (002)
[Description] _______________________________________________________________
Allows you to switch between operation mode and standby mode. The following items used during standby can be set beforehand.
• Control output (-5.0 to 105.0% )
• Alarm output (ON/OFF)
• Transfer output (ON/OFF)
You can set the detail of standby mode in "Standby mode".
setting from on to off.
• If the instrument is put into standby during auto tuning, the auto tuning is canceled. To complete auto-tuning, turn standby mode off and restart auto tuning.
• When the controller switches to standby mode, the ON delay timer will be reset. It
[Setting example] Switching to Standby mode ____________________________________
Display Operating procedure
245
250
MAN
oFF
StbY
oFF
STBY
StbY
PV
SV
PV
SV
PV
SV
PV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to StbY.
○˄○
4. Press the SEL key to enter StbY mode.
(The lower part of the screen begins to blink.)
5. Use the
˅ keys to change oFF to oN.
○˄○
6. Press the SEL key to save the change.
SV
oN
Now the controller is in the Standby Mode. (STBY indicator turns on.)
7. Press the key to return to the PV/SV display.
30
Page 33
REM Remote/local switc hover (003)
[Description] ________________________________________________________________
The following will switch you between lo cal SV and remote SV operation. In remote SV operation, SV is controlled by an external SV input (RSV).
Note: During remote operation, you cannot change the SV by using UP/DOWN keys on the front panel.
[Setting example] Switching to the remote SV mode ________________________________
Display Operating procedure
245
250
MAN
oFF
REM
LoCL
REM
REM
245
PV
SV
PV
SV
PV
SV
REM
PV
SV
PV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change “MAN” to “REM”.
○˄○
4. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
5. Use
˅ keys to change “LoCL” to “REM”..
○˄○
6. Press the SEL key to save the change. Remote SV mode starts
7. Press the key to return to the PV/SV display
“RSV” appears on the screen number indication area.
PSV 250
SV
31
Page 34
PRoG Ramp Soak control command (004)
[Description] _______________________________________________________________
Allows you to switch between Ramp/soak states. You can select among the following three state.
• oFF (stop): Ramp/soak is stopped.
• RUN (start): Ramp/soak starts.
• HLd (hold): Ramp/soak hold. To release the hold, select "RUN" again. The parameter information changes automatically depending on the ramp/soak state.
• GS (Guaranty soak ON): Guaranty soak is activated and PV is out of guaranty soak setting range.
ENd (end): Ramp/soak has finished.
During ramp soak operation, one of RUN, HOLD, or END indicators light according to the state of ramp soak. During ramp soak operation, on-going step No. and "r" (ramp) or "-" (soak) are displayed on the screen No. area of operation screen (PV/SV screen). For example, "2r" appears during step 2 ramp, and "2-" during step 2 soak. Related parameters: PRG (CH3) (page 70)
[Setting example] Ramp Soak command is carried out _____________________________
Display Operating procedure
245
250
MAN
oFF
PRoG
oFF
RUN
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to PRoG.
○˄○
4. Press the SEL key to enter PRoG mode.
(The lower part of the screen begins to blink.)
5. Use the
˅ keys to change oFF to RUN.
○˄○
6. Press the SEL key to save the change.
Ramp Soak command is carried out.
7. Press the key to return to the PV/SV display.
32
Page 35
oFF:
Stop/Finish
oN:
starts auto tuning (normal type)
L-oN:
starts auto tuning (low-PV type)
Low-PV type
Perfoms ON/OFF operation with SV-10% to
AT Auto tuning (005)
[Description] ________________________________________________________________
Running auto-tuning automatically sets the optimal PID.
• Setting range
There are the following two types in au to-tuning.
Normal type Performs ON/OFF operation with SV as the
baseline to calculate PID.
calculate PID. Use the this setting if you want to prevent overshoot.
• When auto tuning is normally completed, the auto matically set PID parameter value is maintained even if the power is turned off. If the power is turned off during auto tuning, the auto-tuning function is invalidated with PID parameters unchanged. In such a case, start again from the beginning.
• Since ON-OFF operation (2-position operation) is performed during auto tuning, PV may fluctuate greatly depending on the process. Do not perform auto tuning for the processes where large fluctuation of PV is not allowed. Do not perform auto tuning, either, for the processes where the response is qui ck, such as pressure control or flow rate control.
• If auto tuning does not end after 4 hours, it means that tuning may not be completed successfully. Check input/output wiring and parameters such as control output (forward, reverse) and input sensor type.
• When you change SV or PV input type, or when operation does not work properly due to the change in operating conditions, perform auto tuning again.
• You can run auto-tuning when the control type is set to "fuzzy" or "PID2".
• You cannot run auto-tuning during manual mode.
• When you are using the PID selection function, the auto-tuning result for the selected PID group is stored.
• Auto tuning is forcibly terminated when SV is changed by the ramp soak function, remote SV function, or ramp SV.
Note: Since ON/OFF control is performed during auto-tuning, overshoot against the SV may occur. To reduce the overshoot, execute the auto-tuning with [L-on] (Low PV). Related parameters: CtRL (CH7) (page 153)
33
Page 36
[Setting example] Running Auto-tuning _________________________________________
Display Operating procedure
245
MAN
At
AT oN
250
oFF
oFF
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to At.
○˄○
4. Press the SEL key to enter At mode.
(The lower part of the screen begins to blink.)
5. Use the
˅ keys to change oFF to oN.
○˄○
6. Press the SEL key to save the change.
Auto tuning starts. AT indicator lamp blinks.
7. Press the key to return to the PV/SV display.
34
Page 37
oFF:
keeps the latch on
RSt:
releases latch
LACH Alarm output latch release (006)
[Description] ________________________________________________________________
Allows you to cancel the alarm Latch.
• Setting range
[Setting example] Releasing alarm output latch ____________________________________
Display Operating procedure
245
250
MAN
oFF
LACH
oFF
RSt
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to LACH.
○˄○
4. Press the SEL key to enter LACH mode.
(The lower part of the screen begins to blink.)
5. Use the
˅ keys to change oFF to RSt.
○˄○
6. Press the SEL key to save the change.
The alarm latch has been canceled.
7. Press the key to return to the PV/SV display.
35
Page 38
SVN SV selection (007)
[Description] _______________________________________________________________
Allows you to easily switch SV among the foll owing.
• Setting range: LoCL, SV1, SV2, SV3, SV4, SV5, SV6, SV7, di To use this function, you need to configure SVs (SV1 to SV7) in the PID palette parameters. It is recommended to activate the ramp SV before changing SV number so that control disorders can be reduced. Related parameters: RMP (CH7) (page 148)
Note: Changing the SV number will not change the control parameters (PID, etc). When changing the SV value with the front panel key, do not change the "Svn" parameter via communication. Otherwise, the changed SV may not be stored correctly.
[Setting example] Changing SV Number ________________________________________
Display Operating procedure
245
250
MAN
oFF
SVN
LoCL
SV3
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to SVN.
○˄○
4. Press the SEL key to enter SVN mode.
(The lower part of the screen begins to blink.)
5. Use the
˅ keys to change LoCL to SV3.
○˄○
6. Press the SEL key to save the change.
The SV used for control is now set to "SV3".
7. Press the key to return to the PV/SV display.
36
Page 39
PLN1 PID selection ( 008)
[Description] ________________________________________________________________
Allows you to easily switch PID No. among those you configured in the PID palette parameters. This allows you to change the PID according to the change of SV or control target.
• Range: LoCL, Pid1, Pid2, Pid3, Pid4, Pid5, Pid6, Pid7, di
[Setting example] Changing PID Number ________________________________________
Display Operating procedure
245
250
MAN
oFF
PLN1
LoCL
Pid1
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to PLN1.
○˄○
4. Press the SEL key to enter PLN1 mode.
(The lower part of the screen begins to blink.)
5. Use the
˅ keys to change LoCL to Pid1.
○˄○
6. Press the SEL key to save the change.
The PID calculation parameter used for control is now set to Pid1.
7. Press the key to return to the PV/SV display.
37
Page 40
AL1 A1-L A1-H Alarm settings (009 to 011) AL2 A2-L A2-H (012 to 014) AL3 A3-L A3-H (015 to 017) AL4 A4-L A4-H (018 to 020) AL5 A5-L A5-H (021 to 023)
[Description] _______________________________________________________________
Allows you to set the values for alarm 1 to alarm 5.
• Setting range: absolute value alarm: 0% to 100% FS deviation alarm: -100% to 100% FS
Related parameters: CH5 Alarm parameters ( page 100)
[Setting example] Setting alarms ______________________________________________
Display Operating procedure
245
250
MAN
oFF
AL1
0010
0020
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to AL1.
○˄○
4. Press the SEL key to enter AL1 mode.
(The first digit of the lower part of the screen begins to blink.)
5. Use the
○˂○˄○
˅ keys to change 10 to 20.
6. Press the SEL key to save the change.
The alarm value is now set to 20°C.
7. Press the key to return to the PV/SV display.
38
Page 41
oFF:
Stops calculation. (Calculated amount of electric power will be cleared.)
RUN:
Calculates the amount of electric energy.
HLd:
Suspend the calculation. (Calculated value of electric power will be retained.)
WCMd Elect ric power calculation command (027)
[Description] ________________________________________________________________
Allows you to switch the electric power calculation status among the following three modes.
Related parameters: CH6 Setup parame ters (page 114)
[Setting example] Switching electricity power calculation status _______________________
Display Operating procedure
245
250
MAN
oFF
WCMd
oFF
RUN
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to WCMd.
○˄○
4. Press the SEL key to enter WCMd mode.
(The lower part of the screen begins to blink.)
5. Use the
˅ keys to change oFF to RUN.
○˄○
6. Press the SEL key to save the change.
Calculates the amount of electric energy.
7. Press the key to return to the PV/SV display.
39
Page 42
oFF:
No lock
ALL:
All locked
PARA:
All but SV locked
LoC Key lock (028)
[Description] _______________________________________________________________
Prevents SV parameters from being changed. The following three settings are available:
The channel menu can be displayed even when key lock is active. Related parameters: Accidental operati on can also be prevented with a password. See CH13 Password parameters (page 194).
[Setting example] Setting Key Lock ____________________________________________
Display Operating procedure
245
250
MAN
oFF
LoC
oFF
ALL
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press the SEL key to move to operation mode.
3. Use the
˅ keys to change MAN to LoC.
○˄○
4. Press the SEL key to enter LoC mode.
(The first digit of the lower part of the screen begins to blink.)
5. Use the
˅ keys to change oFF to ALL.
○˄○
6. Press the SEL key to save the change.
Key Lock is now activated.
7. Press the key to return to the PV/SV display.
40
Page 43
P:
0.1 to 999.9%
I:
0 to 3200 seconds
D:
0.0 to 999.9 seconds
ON/OFF control
When the control method CtRL is set to oNoF, ON/OFF control is used. Use the controllability.
PID control
Use this function when you want to control with high controllability.
to optimally adjust P, I, and D before using this function.
PI control
When P ≠ 0, I ≠ 0, and D = 0, D control is turned off and PI control is used.
P control
When P ≠ 0 and I = 0, D = 0, I and D controls are turned off and P control is used. adjust the output convergence value “bAL”.

CH1 PID (Control parameters) 3-2

P Proportional band (050) Integration time (051) d Differential time (052)
[Description] ________________________________________________________________
Allows you to set PID (Proportional Band, Integration Time, Differential Time). Setting range
The following control methods are avail able with PID settings.
(2-position control)
Running auto-tuning automatically sets the optimal PID. See "AT Auto tuning (005) " (page 33) The PID settings configured by auto-tuning are generally considered to be optimal settings. If you want to change the responsiveness, adjust PID man ually. Generally, control becomes unstable when “P” is set too small. On the other hand, setting it too big makes the response slow. Set the hysteresis for the ON/OFF (2-position) control with the parameter “hyS”.
Note Do not perform auto tuning during ON/OFF control.
this function when you want to run simple control without worrying about the
P, I, and D should be adjusted to optimal values for the control target, although Pid can be activated with P ≠ 0, I ≠ 0, and D ≠ 0. In normal situations, run auto-tuning
In principle, P control generates offset and PV does not agree with SV. In this case,
41
Page 44
[Setting example] Setting P = 10.0%, I = 100sec., D = 20sec. ________________________
Display Operating procedure
PV
SV
PV
SV
PV
SV
SV
PV
245
250
CH
Pid
5.0
10.0
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
5. Use the
˅ keys to change 5.0 to 10.0.
○˄○
6. Press the SEL key to save the change.
7. Use the
˅ key to display i(integration time).
8. Press the SEL key.
d
SV
SV
PV
(The first digit of the lower part of the screen begins to blink.)
9. Use the
˅ keys to change 240 to 100.
○˄○
10. Press the SEL key to save the change.
11. Use the
˅ key to display d(differential time).
240
100
12. Press the SEL key.
60.0
20.0
SV
SV
(The first digit of the lower part of the screen begins to blink.)
13. Use the
˅ keys to change 60.0 to 20.0.
○˄○
14. Press the SEL key to save the change.
15. Press the key to return to the PV/SV display.
42
Page 45
• Frequency of output relays is high, so lifespan becomes short.
Large hysteresis
• Low-precision control
• Frequency of output relays is low, so lifespan is relatively long.
HYS ON/OFF contr ol hys t eresis (053)
[Description] ________________________________________________________________
Allows you to set the hysteresis for ON/OFF (2 position) control
• Setting range: 0.0 to 50.0% FS The controllability varies with the size of the hysteresis.
Small hysteresis • High-precision control
The relationship between SV and hyster esis in normal and reverse operation is shown below.
• During ON/OFF control, the i and d settings do not affect control.
• If the hysteresis width is narrow, and PV and SV are near ly equal, the output may frequently switch on and off. Note that it may affect the life of the contact.
[Setting example] Changing the hysteresis range from 25%FS to 30%FS ______________
Display Operating procedure
25
30
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
Pid
5.0
HYS
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to HYS.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 25 to 30.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
43
Page 46
Cooling proportional band = (Proportional band P/2) x Coefficient
CooL Cooling proportional band coefficient (054)
[Description] _______________________________________________________________
Allows you to set the proportional band coefficient for cooling.
• Setting range: 0.0 to 100.0 The relationship between heating control output and cooling control output is outlined below.
Cooling proportional band is set after the optimal value for heating proportional band is set.
The following example shows how the cooling proportional band is calculated. Example: Calculating the coefficient that will give a cooling proportional band of 10% when proportional band(P) = 50% with full scale cooling 10% = (50%/2) x Coefficient Coefficient = 0.4 To set cooling as a secondary operation, set " C ool" to 0.0. With two outputs set as P=0.0 and Cool=0.0, heating and cooling outputs become ON/OFF actions (3-position control). In this situation, the ON/OFF hysteresis is 0.5% FS (fixed) for heating and cooling outputs. The point of operation for the heating output can be shifted with the “HYS” parameter. The point of operation for the cooling output can be shifted with the “db” parameter. The relationship between SV and hyster esis in normal and reverse operation is shown below.
44
Page 47
[Setting example] Changing cooling proportional band coefficient from 1.0 to 2.5 _________
Display Operating procedure
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
Pid
5.0
CooL
1.0
2.5
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to Cool.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 1.0 to 2.5.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
45
Page 48
db Dead band (055)
[Description] _______________________________________________________________
Shifts the cooling proportional band against the set value as follows.
"db" is called dead band when the value is positive, and overlap band when the value is negative.
• Range: -50% to 50% "db" is measured as a percentage of MV and can be converted to a percentage deviation by the following
formula. DB [%] = deviation x 100/P [%] Example: Proportional Band (P) = 5.0%, with a desired dead band of 1% deviation from SV: DB [%] 1.0 ×100/5.0 = 20 [%] Dead band = 20 (%)
[Setting example] Setting Dead band to 1.5% ____________________________________
Display Operating procedure
PV
SV
PV
SV
PV
SV
PV
245
250
CH
Pid
5.0
db
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to db.
○˄○
5. Press the SEL key.
0.0
1.5
SV
SV
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 0.0 to 1.5.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
46
Page 49
Display
Operating procedure
bAL Output convergence value (056)
[Description] ________________________________________________________________
Output convergence value is a function that adds an offset to MV value.
• Setting range bAL: -100 to 100% By this function, the bAL offset is added to original MV which is the result of PID calculation determined by
PV and SV, and the total value is outputted as M V.
(The factory setting of bAL is 0% for single output, 50% for dual output.)
[Setting example] Changing Output convergence value from 0.0% to 3.0% ______________
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
Pid
5.0
bAL
0.0
3.0
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to bAL.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 0.0 to 3.0.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
47
Page 50
AR Anti-reset windup (057)
[Description] _______________________________________________________________
Anti-reset windup is a function that limits the range of valid integration to control overshooting. Setting range Ar: 0 to 100% FS
• The anti-reset windup function (“AR”) cuts integrat ion that falls outside of the Ar set range that is centered
around SV. It is automatically set to the optimum value when auto-tuning is activated
[Setting example] Changing the anti-reset windup to 500°C __________________________
Display Operating procedure
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
Pid
5.0
AR
100
500
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to AR.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 100 to 500.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
48
Page 51
RV_ _:
heat (reverse) / cool (none)
No_ _:
heat (normal) / cool (none)
RVNo:
heat (reverse) / cool (normal)
NoRV:
heat (normal) / cool (reverse)
RVRV:
heat (reverse) / cool (reverse)
NoNo:
heat (normal) / cool (normal)
REV Normal/reverse operation (058)
[Description] ________________________________________________________________
Specifies whether the control operations are normal or reverse.
• Setting range
Most temperature control is done with heating in reverse and cooling in normal.
[Setting example] Setting the heating control to reverse, cooling control to normal action ___
Display Operating procedure
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
Pid
5.0
REV
RV__
RVNo
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to REV.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change RV_ _ to RVNo.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
49
Page 52
8. Press the key to return to the PV/SV display.
SVL SV lower limit (059) SVH SV upper limit ( 060)
[Description] _______________________________________________________________
These parameters specify the setting range of the SV (Setting value). You can set any value within the measurement range.
• Setting range: 0 to 100% FS (Upper/Lower) The relationship between SV limits and the measurement range is as follows:
Note:
• Before setting SVH/SVL, be sure to set the following parameters in CH6 Setup parameters. PV lower limit (PVb)/PV uppe r limit (PVF)
• SVs set before setting the SV limits (Local SV, Palette SV, etc.) are affected by new SV limits.
• Make sure to set the value of SVh greater than SVL.
[Setting example] Setting the lower SV limit to 50°C _______________________________
Display Operating procedure
PV
SV
PV
SV
PV
SV
PV
245
250
CH
Pid
5.0
SVL
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to SVL.
○˄○
5. Press the SEL key.
SV
0
SV
50
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 0 to 50.
○˄○
7. Press the SEL key to save the change.
50
Page 53
Contact
The shorter the proportional cycle, the finer the control, however shorter proportional cycles
Approx.: 30 sec
SSR drive
Because there are no mechanical parts, use a short proportional cycle if the operating device
Approx.: 1 or 2 seconds
tC1 OUT1 proportional cycle (061) tC2 OUT2 proportional cycle (062)
[Description] ________________________________________________________________
When using contact output and SSR drive output with PV input inside the proportional band, output will switch between ON and OFF at regular intervals.
• These intervals are called proportional cycl es. OUT1 and OUT2 can be set separately. Setting range: 1 to 150
The following are the recommended settings for each control output.
output
output
Note:
• TC2 is only valid when there are dual outputs.
• t cannot be set for current output or voltage output. Approx.: 1 sec
also shorten the lifespan of the contact points and operating device. Keep a balance between controllability and controller lifespan when adjusting the proportional cycles.
is working properly.
51
Page 54
[Setting example] Setting OUT1 proportional cycle to 60 sec _________________________
Display Operating procedure
245
250
CH
Pid
5.0
tC1
PV
SV
PV
SV
PV
SV
PV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to tC1.
○˄○
5. Press the SEL key.
SV
30
SV
60
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 30 to 60.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
52
Page 55
Output
Lower limit
Upper limit
Setting range
OUT1
PLC1
PHC1
-5.0 to 105.0%
OUT2
PLC2
PHC2
-5.0 to 105.0%
PLC1 PHC1 OUT1 Upper/Lower Limits (063, 064) PLC2 PHC2 OUT2 Upper/Lower Limits (065, 066)
[Description] ________________________________________________________________
This parameter specifies the upper and lower limits for output control.
• Setting range
Related parameters: CH1 "Type of Ou tput Limiter" (page 54)
Note: Be sure to set the values so that PHC is greater than PLC.
[Setting example] Setting OUT1 lower limit to 5% __________________________________
Display Operating procedure
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
Pid
5.0
PLC1
-5.0
5.0
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to PLC1.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change -5.0 to 5.0.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
53
Page 56
Display
Operating procedure
PCUt Type of output limiter (067)
[Description] _______________________________________________________________
You can choose whether to apply the limit on the output value or let it exceed the limit. The output changes according to the limit, as follows.
Setting range
Setting Output 1 (OUT1) Output 2 (OUT2)
Lower limit Upper limit Lower limit Upper limit 0 -5% 105% -5% 105% 1 limit 105% -5% 105% 2 -5% limit -5% 105% 3 limit limit -5% 105% 4 5 limit 105% limit 105%
[Setting example] Setting to keep all the outputs within limits _________________________
6 -5% limit limit 105% 7 limit limit limit 105% 8 -5% 105% -5% limit 9 limit 105% -5% limit 10 -5% limit -5% limit 11 limit limit -5% limit 12 -5% 105% limit limit 13 limit 105% limit limit 14 -5% limit limit limit 15 limit limit limit limit
-5
105% limit 105%
0
15
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
Pid
5.0
PCUt
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to PCUt.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 0 to 15 (limit all).
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
54
Page 57
Result of control
bEtA
ALPA
Large overshoot
Increase BETA (β) by 20%
Decrease ALPA (α) by 10%
Small overshoot
Decrease BETA (β) by 20%
Increase ALPA (α) by 10%
ALPA
-300.0 to 300.0
bEtA
0.0 to 900.0
ALPA 2-degrees-of-freedom coefficient α (073) bEtA 2-degrees-of-freedom coefficient β (074)
[Description] ________________________________________________________________
These coefficients are used to suppress overshoot generated in PID control. The 2-degrees-of-freedom PID system of this inst r ument adopts set value (SV) filter method, which is effective in suppressing overshoot at the time of setting change or start-up. If ALPA (α) is set to 100.0%, and bEtA (β) to 0.0%, ordinary PID control (1 degree of freedom PID) is performed. Adjust ALPA (α) and bEtA (β) as follows. (1)Set ALPA (α) to 40.0%, and bEtA (β) to 100.0%. (Factory default setting) (2)Perform control and check responsiveness (overshoot volume). If overshoot cannot be improved in this stage, adjust ALPA (α) and bEtA (β), following the definition listed
in the following table. Generally, ALPA (α) does not require adjustment. Therefore, it is recommended to use the instrument with ALPA (α) set to 40.0%.
Setting range
[2 degrees of freedom PID block diagram]
Note: Changing ALPA (α) should be performed during manual mode. Before changing ALPA (α) setting, set bEtA (β) to 0.0%. First, change ALPA (α) setting, and then set bEtA (β) to desired value. Improper procedure may cause output (target value) to increase temporarily, thus posing danger. The purpose of this function is to suppress overshoot generated in ordinary PID control. Overshoot may not always be eliminated.
55
Page 58
[Setting example] Setting the 2-degrees-of-freedom coefficient α to 50.0% ______________
Display Operating procedure
245
CH
ALPA
250
Pid
5.0
40.0
50.0
PV
SV
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the SEL key to enter CH1 (PID parameters).
P is displayed.
4. Use the
˅ keys to change P to ALPA.
○˄○
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 40.0 to 50.0.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
56
Page 59
PID switching point 1 to 7

CH2 PLT (PID palette parameters) 3-3

PID palette parameters are used to register SVs, P I Ds, and other control parameters. Up to seven sets of SVs and PIDs can be stored, and you can toggle among them by simply selecting their numbers. This is very useful when operating conditions change frequently. The palette menu (CH2) consists of the following function blocks:
To change the SV No. or PID No., refer to "S V selection" (page 36), "PID selection" (pag e 37).
57
Page 60
SV1 to SV7 Set Value (100 to 160)
[Description] _______________________________________________________________
Up to seven SVs (SV1-SV7) can be recorded. Recorded SVs can be invoked by the SV selection ("Svn") parameter in the operation menu. Setting range: SV lower limit (SVL) to SV upper limit (SVH) %FS It is recommended to activate the ramp SV b ef ore changing SV number, so that control diso rders can be
reduced.
Related parameters: "SV selection" (page 36)
[Setting example] Setting SV1 to 300°C _________________________________________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
300
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 0 to 300.
○˄○
7. Press the SEL key to save the change.
8. To set SV2 to SV7, press the
steps 5 to 7.
˅ key in the step 4 and then repeat
9. Press the key to return to the PV/SV display.
58
Page 61
Proportional band (P):
0.0 to 999.9%
Integration time (I):
0 to 3200 seconds
Differential time (D):
0.0 to 999.9 seconds
P1 to P7 Proportional band (101 to 161) i1 to i7 Integration time (102 to 162) d1 to d7 Differential time (103 to 163)
[Description] ________________________________________________________________
These parameters allows you to configure PID. Up to seven types of PID (palettes 1 to 7) can be recorded. Recorded PIDs can be called from selected PID number ("PLN1") in the operation menu CH1.
• Setting range
Related parameters: "Proportional Band, Integration Time, Differential Time (CH1)" (page 41) When a PID No. is changed, the following parameters change to match it.
• ON/OFF control hysteresis
• Cooling proportional band
• Dead band
• Output convergence value
• Anti-reset windup
• Normal/reverse operation Running auto-tuning will automatically set to the PID No. selected in the PID selection parameter.
Note:
• For safety, make sure to turn off the power before switching the normal/reverse operations by using the PID selection function. (Do not switch between normal and reverse while operation.)
If "(PID No. +1, SV No. +1(increment))" function is executed under the "PID No. ≠ SV No.", PID No. and SV No. is automatically set to the same value.
• PID is switched per palette. You cannot combine the values of PID among palettes.
59
Page 62
[Setting example] Setting P = 10.0%, I = 100 sec., D = 20 sec. _______________________
Display Operating procedure
245
250
CH
PLt
SV1
10.0
0
P1
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to P1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
PV
i1
100
d1
20
SV
PV
SV
7. Use the
˅ keys to change 5.0 to 10.0.
○˄○
8. Press the SEL key to save the change.
9. Use the
˅ key to change 100 to 20.
10. Repeat the same steps to set Pid2 to Pid7.
11. Press the key to return to the PV/SV display.
60
Page 63
HYS1 to HYS7 ON/OFF control hysteresis (104 to 164)
[Description] ________________________________________________________________
This parameter allows you to set the hysteresis width for the ON/OFF control. Up to seven types of hysteresis (for palettes 1 to 7) can be recorded. Recorded hysteresis can be called by PID selection ("PLN1") in the operation mode.
• Setting range: 0 to 50% FS
Related parameters: "ON/OFF control hysteresis" (page 43)
[Setting example] Setting the ON/OFF control hysteresis 1 to 3°C _____________________
Display Operating procedure
0
1
3
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
HYS1
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to HYS1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 1 to 3.
○˄○
8. Press the SEL key to save the change.
9. Repeat the same steps to set HYS2 to HYS7.
10. Press the key to return to the PV/SV display.
61
Page 64
CoL1 to CoL7 Cooling Proportional Band (105 to 165)
[Description] _______________________________________________________________
Allows you to set the cooling proportional band when dual outputs are selected. Up to seven types of cooling proportional band (for palettes 1 to 7) can be recorded. Recorded cooling proportional band can be called from PID selection (“PL1N”) in the operation mode.
• Setting range: 0.0% to 100.0% Related parameters: "Cooling Proportional Band Coefficient" (p. 45)
[Setting example] Setting the Cooling proportional band 1 to 5.0% ____________________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
CoL1
1.0
5.0
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to CoL1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 1.0 to 5.0.
○˄○
8. Press the SEL key to save the change.
9. Repeat the same steps to set CoL2 to CoL7.
10. Press the key to return to the PV/SV display.
62
Page 65
db1 to db7 Dead band (106 to 166)
[Description] ________________________________________________________________
Allows you to set the dead band when dual outputs are selected. Up to seven types of dead band (for palettes 1 to 7) can be recorded. Recorded dead band can be called from PID selection (“PLN1”) in the operation mode.
• Setting range: -50.0% to 50.0%
Related parameters: "Dead Band" (page 46)
[Setting example] Setting Dead band 1 to 7.0% ____________________________________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
db1
0.0
7.0
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to db1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 0.0 to 7.0.
○˄○
8. Press the SEL key to save the change.
9. Repeat the same steps to set db2 to db7.
10. Press the key to return to the PV/SV display.
63
Page 66
bAL1 to bAL7 Output convergence value (107 to 167)
[Description] _______________________________________________________________
Allows you to set the output convergence value. Up to seven types of output convergence value (for palettes 1 to
7) can be recorded. Recorded output convergence value can be called from PID selection (“PLN1”) in the operation mode.
• Setting range: -100.0% to 100.0% Related parameters: "Output Convergence Value" (page 47)
[Setting example] Setting Output convergence value 1 to -5.5% ______________________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
bAL1
0.0
-5.5
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to bAL1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 0.0 to -5.5.
○˄○
8. Press the SEL key to save the change.
9. Repeat the same steps to set bAL2 to bAL7.
10. Press the key to return to the PV/SV display.
64
Page 67
AR1 to AR7 Anti-reset windup (108 to 168)
[Description] ________________________________________________________________
Allows you to set the anti-reset windup. Up to seven types of anti-reset windup (for palettes 1 to 7) can be recorded. Recorded anti-reset windup can be called f r om PID selection (“PLN1”) in the operation mode.
• Setting range: 0.0% to 100.0%
Related parameters: "Anti-reset windup" (page 48)
[Setting example] Setting the anti-reset windup 1 to 50 FS ___________________________
Display Operating procedure
0
50
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
AR1
100
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to AR1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 100 to 50.
○˄○
8. Press the SEL key to save the change.
9. Repeat the same steps to set bAL2 to bAL7.
10. Press the key to return to the PV/SV display.
65
Page 68
Range
Control operation
RV_ _
heat (reverse) / cool (none)
No_ _
heat (normal) / cool (none)
RVNo
heat (reverse) / cool (normal)
NoRV
heat (normal) / cool (reverse)
RVRV
heat (reverse) / cool (reverse)
NoNo
heat (normal) / cool (normal)
REV1 to REV7 Normal/reverse (109 to 169)
[Description] _______________________________________________________________
Allows you to set the normal/reverse setting. Up to seven types of normal/reverse settings (for palettes 1 to 7) can be recorded. Recorded normal/reverse settings can be called from PID selection (“PLN1”) in the operation mode.
Related parameters: "Normal/Reverse" (C H1) (page 49)
[Setting example] Setting the normal/reverse 1 to heat (reverse)/ cool (normal) __________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
REV1
RV__
RVNo
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to REV1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change "RV" to "RVNo".
○˄○
8. Press the SEL key to save the change.
9. Repeat the same steps to set REV2 to REV7.
10. Press the key to return to the PV/SV display.
66
Page 69
REF1 to REF7 PID palette switching point (170 to 176)
[Description] ________________________________________________________________
This parameter allows you to set threshold value at which the controller automatically switches among PID palettes.
• Setting range: 0 to 100% FS
Related parameters: PID palette switchin g method (CH 7) (page 161)
[Setting example] Setting the PID palette switching point 1 to 30% FS __________________
Display Operating procedure
0
0
30
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
REF1
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to REF1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 0 to 30.
○˄○
8. Press the SEL key to save the change.
9. Repeat the same steps to set REF2 to REF7.
10. Press the key to return to the PV/SV display.
67
Page 70
SVMX Max SV selecti on num ber (177)
[Description] _______________________________________________________________
Allows you to set the maximum SV number that can be selected via the USER key.
• Setting range: SV1 to SV7, LoCL, di Related parameters: "User key assignment" (CH 7 ) (page 141)
[Setting example] Setting the max. SV selection number to SV4 ______________________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
SVMX
SV7
SV4
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to SVMX.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change SV7 to SV4.
○˄○
8. Press the SEL key to save the change.
9. Press the key to return to the PV/SV display.
68
Page 71
PL1M Max PID selection number (178)
[Description] ________________________________________________________________
Allows you to set the maximum PID number that can be selected via the USER key.
• Setting range: Pid1 to Pid7, LoCL, di
Related parameters: "User key assignment" (CH 7 ) (page 141)
[Setting example] Setting the max. PID selection number to PID6 _____________________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PLt
SV1
PL1M
Pid7
Pid6
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH2 (PID palette parameters).
4. Press the SEL key to enter CH2 (PID palette parameters).
SV1 (set value) is displayed.
5. Use the
˅ keys to change SV1 to PL1M.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change "Pid7" to "Pid6".
○˄○
8. Press the SEL key to save the change.
9. Press the key to return to the PV/SV display.
69
Page 72

CH3 PRG (Ramp soak parameters) 3-4

This function automatically runs according to SVs and the times for the SV changes configured previously. You can choose up to 64 steps for SV setting and 14 types of operation patterns.
• Ramp: Changing SV towards a target SV
• Soak: Maintains a SV The ramp/soak parameters (CH3) consists of the following function blocks.
70
Page 73
0
steps 1 to 8
8
steps 1 to 16
1
steps 9 to 16
9
steps 17 to 32
2
steps 17 to 24
10
steps 33 to 48
3
steps 25 to 32
11
steps 49 to 64
4
steps 33 to 40
12
steps 1 to 32
5
steps 41 to 48
13
steps 33 to 64
6
steps 49 to 56
14
steps 1 to 64
7
steps 57 to 64
di
depending on di
PtN Ramp/soak operation pattern (Step No.) (200)
[Description] ________________________________________________________________
The 64-step ramp/soak patterns are divided into 15 segments. You can choose any one to use.
• Setting range
Note: Do not change this parameter during the ramp soak operation. Be sure to set “PRG” = “OFF” before changing the parameter.
[Setting example] Setting the Ramp/Soak Activation Pattern to steps 1 to 8 ______________
Display Operating procedure
14
0
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PRG
PtN
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
6. Use the
˅ keys to change 14 to 0.
○˄○
7. Press the SEL key to save the change.
8. Press the key to return to the PV/SV display.
71
Page 74
tiMU Ramp/soak time units (201)
[Description] _______________________________________________________________
Allows you to set the time units for Ramp/soak operation.
• Setting range: HH : MM(hour:min) MM : SS(min:sec)
Note: Time units can not be set separately for each step. All steps use the same unit of time.
[Setting example] Setting the time unit to MM:SS __________________________________
Display Operating procedure
14
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PRG
PtN
tiMU
HH:MM
MM:SS
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Use the
˅ keys to change PtN to tiMU.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Press the
˅ keys to change HH:MM to MM:SS.
○˄○
8. Press the SEL key to save the change.
9. Press the key to return to the PV/SV display.
72
Page 75
SV
SV lower limit (SVL) to SV upper limit (SVH) %FS
Ramp time
00:00 to 99:59 (hour:min/min:sec)
Soak time
00:00 to 99:59 (hour:min/min:sec)
SV-1:50
SV-2:200
SV-3:100
TM1r:0.10
TM2r:0.00
TM3r:1.00
TM1S:0.05
TM2S:0.00
TM3S:0.75
SV-1 to SV64 Ramp soak seg1 SV1 to seg64 SV64 (202 to 391) tM1R to t64R Ramp soak seg1 ramp time to seg64 ramp time (203 to 392) tM1S to t64S Ramp soak seg1 soak time to seg64 ramp time (204 to 393)
[Description] ________________________________________________________________
Sets the ramp soak SV, ramp time and soak time. Setting range:
• The segment that both ramp time and soak time are set to 0.00 will be skipped.
(Example)
• The SV limit function (SV-h, SV-L) is in effect while ramp/soak is running.
The set value (SV-n) does not change, but the value is limited during ramp/soak. For the above reason, the
value may not change at the set times and t he ramp soak runs with the following pattern.
73
Page 76
[Setting example] Setting SV1, ramp time, and soak time for step1 ____________________
Display Operating procedure
14
0
50
0
0
PV
SV
PV
SV
PV
SV
PV
SV
SV
PV
SV
SV
PV
SV
SV
245
250
CH
PRG
PtN
SV-1
tM1R
0.10
tM1S
0.05
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Use the
˅ keys to change PtN to SV-1.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 0 to 50.
○˄○
8. Press the SEL key to save the change.
9. Use the
˅ keys to change SV-1 to tM1R.
○˄○
10. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
11. Use the
˅ keys to change 0 to 0.10.
○˄○
12. Press the SEL key to save the change.
13. Use the
˅ keys to change tM1R to tM1S.
○˄○
14. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
15. Use the
˅ keys to change 0 to 0.05.
○˄○
16. Press the SEL key to save the change.
17. Repeat the same steps for step 2 to step 64.
18. Press the key to return to the PV/SV display.
74
Page 77
Power-on start
Starts ramp/soak with the current PV when the main unit is turned on.
END time output
Maintains the same state as at the end o f ra mp/soak when ramp/soak is complete.
oFF time output
Switches to the OFF state when ramp/soak is complete.
Repeat operation
Repeats ramp/soak from step 1 when the last step finishes.
MOD
Power-on start
Ending output
OFF output
Repeat behavior 0
none
Maintain control
Maintain control
none
1
none
Maintain control
Maintain control
on 2 none
Maintain control
Standby Mode
none
3
none
Maintain control
Standby Mode
on 4 none
Standby Mode
Maintain control
none
5
none
Standby Mode
Maintain control
on 6 none
Standby Mode
Standby Mode
none
7
none
Standby Mode
Standby Mode
on 8 on
Maintain control
Maintain control
none
9
on
Maintain control
Maintain control
on
10
on
Maintain control
Standby Mode
none
11
on
Maintain control
Standby Mode
on
12
on
Standby Mode
Maintain control
none
13
on
Standby Mode
Maintain control
on
14
on
Standby Mode
Standby Mode
none
15
on
Standby Mode
Standby Mode
on
Mod Ramp soak mode (394)
[Description] ________________________________________________________________
Allows you to set the method of ramp/soak operation. The following items can be set.
• You can choose from the following 16 modes.
• When not in repeat operation, the last SV value is held when ramp/soak finishes.
75
Page 78
[Setting example] Setting the ramp soak mode to 1 ________________________________
Display Operating procedure
245
250
CH
PRG
PtN
Mod
14
0
1
PV
SV
PV
SV
PV
SV
PV
SV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Use the
˅ keys to change PtN to Mod.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 0 to 1.
○˄○
8. Press the SEL key to save the change.
9. Press the key to return to the PV/SV display.
76
Page 79
on/off
Guarantee soak upper limit
0 to 50% FS
Guarantee soak lower limit
0 to 50% FS
GSoK Guarant ee soak ( 395) GS-L Guarantee soak band (lower) (396) GS-H Guarantee soak band (upper) (397)
[Description] ________________________________________________________________
This function guarantees the soak ti me. Soak time is counted down only when PV is in the certain temperature range. As seen in the figure below, only the sum of the shaded areas is counted as soak time. The operation moves onto the next step when the total soak time has reached the specified soak time.
Setting range:
Guarantee soak
77
Page 80
[Setting example] Setting guaranty soak to ON and upper/lower limits to 5°C ____________
Display Operating procedure
14
oN
0
5
PV
SV
PV
SV
PV
SV
PV
SV
SV
PV
SV
SV
PV
245
250
CH
PRG
PtN
GSoK
oFF
GS-L
GS-H
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Use the
˅ keys to change PtN to GSo K.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use
˅ keys to change "oFF" to "oN".
○˄○
8. Press the SEL key to save the change.
9. Use
˅ keys to change GSoK to GS-L.
○˄○
10. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
11. Use the
˅ keys to change 0 to 5.
○˄○
12. Press the SEL key to save the change.
SV
0
SV
5
13. Use
14. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
15. Use the
˅ keys to change GS-L to GS-H.
○˄○
˅ keys to change 0 to 5.
○˄○
16. Press the SEL key to save the change.
17. Press the key to return to the PV/SV display.
78
Page 81
PVSt PV start ( 398)
[Description] ________________________________________________________________
When the ramp soak starts (RUN), this function searches the first point where the measurement value (PV) and the program pattern match, and starts operation at that point.
If the measurement value does not match the pattern as with (3), the normal operation starts.
Setting range: oN (PV start on), oFF (PV start off)
[Setting example] Setting PV start to ON _________________________________________
Display Operating procedure
14
oN
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PRG
PtN
PVSt
oFF
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Use the
˅ keys to change PtN to PVSt.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use
˅ keys to change "oFF" to "oN".
○˄○
8. Press the SEL key to save the change.
9. Press the key to return to the PV/SV display.
79
Page 82
RES:
Does not operate ramp soak.
CoN:
Resumes the operation from the status of the time at which power is turned off. (It can restore the state to five minutes before maximum. )
iNi:
Starts the Ramp/Soak from the first step again.
CoNt Restore m ode (399)
[Description] _______________________________________________________________
This parameter specifies the ramp soak operat ion when the power is restored after being interrupted due to power outage or other reasons. Setting range
Note: Do not change this parameter during the ramp soak operation. Be sure to set “PRG” = “oFF” before changing the parameter.
[Setting example] Setting the restore mode so that the device resumes the operation _____
Display Operating procedure
14
PV
SV
PV
SV
PV
SV
PV
SV
SV
245
250
CH
PRG
PtN
CoNt
RES
CoNt
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Use the
˅ keys to change PtN to CoNt.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use
˅ keys to change "RES" to "CoNt".
○˄○
8. Press the SEL key to save the change.
9. Press the key to return to the PV/SV display.
80
Page 83
PtNM Max pattern selection (400) PMiN Min patter n s elect ion ( 401)
[Description] ________________________________________________________________
Sets the max./min. pattern number that can be selected when proceeding the Ramp/so ak activation pattern with USER keys.
• Setting range: 0 to 14
• Related parameters: Ramp soak operation pattern (CH 3) (page 71)
User key assignment (CH 7) (page 141)
Note: Do not set a value for Min pattern selection that is larger than the value for Max pattern selection.
[Setting example] Setting the min. number to 2 and max. number to 4 _________________
Display Operating procedure
14
14
4
0
2
PV
SV
PV
SV
PV
SV
PV
SV
SV
PV
SV
SV
245
250
CH
PRG
PtN
PtNM
PMiN
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH3 (Ramp soak p ar ameters).
4. Press the SEL key to enter CH3 (Ramp soak parameters).
PtN (Ramp soak operation pattern) is displayed.
5. Use the
˅ keys to change PtN to PtNM.
○˄○
6. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
7. Use the
˅ keys to change 14 to 4.
○˄○
8. Press the SEL key to save the change.
9. Use the
˅ keys to change PtNM to PMiN.
○˄○
10. Press the SEL key.
(The first digit of the lower part of the screen begins to blink.)
11. Use the
˅ keys to change 0 to 2.
○˄○
12. Press the SEL key to save the change.
13. Press the key to return to the PV/SV display.
81
Page 84
Display
Status
oFF
Ramp soak is stopped
1-RP
Step 1 ramp
1-St
Step 1 soak
2-RP
Step 2 ramp
2-St
64RP
Step 2 soak
Step 64 ramp
64St
Step 64 soak
ENd
Ramp soak is finished

CH4 MON (Monitor parameters) 3-5

StAt Ramp soak pr ogress (420)
[Description] _______________________________________________________________
Displays the progress of the ramp soak. The ramp soak status are indicated as follows.
Related parameters: Ramp soak parameters (CH 3) ( page 70)
[Setting example] Checking ramp soak progress __________________________________
Display Operating procedure
245
CH
StAt
250
MoN
oFF
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Press the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is displayed.
5. Press the key to return to the PV/SV display.
82
Page 85
MV1, MV2 Control output (MV1, MV2) (421, 422)
[Description] ________________________________________________________________
Displays the output values (OUT1/OUT2).
[Setting example] Checking the output value (OUT1) _______________________________
Display Operating procedure
245
250
CH
MoN
StAt
oFF
MV1
58.4
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The output value of OUT1 is displayed.
˅ keys to change StAt to MV1.
○˄○
6. Repeat the same steps to check the output value of OUT2.
7. Press the key to return to the PV/SV display.
83
Page 86
PFb PFB input value ( 423)
[Description] _______________________________________________________________
Motorized valve opening will be displayed when using position feedback (PFB) as the control.
[Setting example] Checking the PFB input value __________________________________
Display Operating procedure
245
250
CH
MoN
StAt
oFF
PFb
19.5
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
for PFB is displayed.
˅ keys to change “StAt” to “PFb”. The input value
○˄○
6. Press the key to return to the PV/SV display.
84
Page 87
RSV Remote SV (424)
[Description] ________________________________________________________________
Displays the remote SV input value.
[Setting example] Checking the remote SV input value ______________________________
Display Operating procedure
245
250
CH
MoN
StAt
oFF
RSV
17.5
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is show n.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
for remote SV is displayed.
˅ keys to change “StAt” to “RSV”. The input value
○˄○
6. Press the key to return to the PV/SV display.
85
Page 88
Ct1 Heater cur r ent (425)
[Description] _______________________________________________________________
Display the Heater current value. (The current value measured during the control output 1 is ON is indicated.)
[Setting example] Checking the heater current value _______________________________
Display Operating procedure
245
250
CH
MoN
StAt
oFF
Ct1
25.5
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
for heater current is displayed.
˅ keys to change “StAt” to “Ct1”. The input value
○˄○
6. Press the key to return to the PV/SV display.
86
Page 89
LC1 Leak current ( 427)
[Description] ________________________________________________________________
Display the Leak current value. (The current value measured during the control output 1 is OFF is indicated.)
[Setting example] Checking the leak current value _________________________________
Display Operating procedure
245
250
CH
MoN
StAt
oFF
LC1
0.0
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
value is displayed.
˅ keys to change “StAt” to “LC1”. The leak current
○˄○
6. Press the key to return to the PV/SV display.
87
Page 90
tM1 to tM5 Remaining time on timer (429 to 433)
[Description] _______________________________________________________________
Displays the remaining time on timer. Related parameters: ALM hysteresis, AL M delay, ALM delay time units (CH 5) (page 100)
[Setting example] Checking the remaining time on the timer 1 ________________________
Display Operating procedure
8
PV
SV
PV
SV
PV
SV
PV
SV
245
250
CH
MoN
StAt
oFF
tM1
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The remaining time on the timer 1 is displayed.
˅ keys to change StAt to tM1.
○˄○
6. Repeat the same steps to check the remaining times of the timer2
and the timer 3.
7. Press the key to return to the PV/SV display.
88
Page 91
Display
Operating procedure
CoMM Comm unicat ion status (435)
[Description] ________________________________________________________________
Counts the number of communication times. If the counter has reached 9999, it restarts counting from zero.
[Setting example] Checking the count ___________________________________________
245
250
CH
MoN
StAt
oFF
CoMM
0
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
Communication count is displayed.
˅ keys to change StAt to CoMM.
○˄○
6. Press the key to return to the PV/SV display.
89
Page 92
Display
Operating procedure
CUR1 Current ( 436)
[Description] _______________________________________________________________
Displays the electric current value meas ured with CT. (The value is independent of the control output 1.)
[Setting example] Checking the leak current value _________________________________
245
250
CH
MoN
StAt
oFF
CUR1
0.0
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The current value is displayed.
˅ keys to change “StAt” to “CUR1”.
○˄○
6. Press the key to return to the PV/SV display.
90
Page 93
Display
Operating procedure
PoW Electric power ( 438)
[Description] ________________________________________________________________
Displays the calculated amount of electric power (kW).
[Setting example] Checking the electric power ____________________________________
245
250
CH
MoN
StAt
oFF
PoW
0.0
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The electric power is displayed.
˅ keys to change “StAt” to “PoW”.
○˄○
6. Press the key to return to the PV/SV display.
91
Page 94
KWH Power (439)
[Description] _______________________________________________________________
Displays the calculated amount of electric power.
[Setting example] Checking the amount of electric power ___________________________
Display Operating procedure
245
250
CH
MoN
StAt
oFF
KWH
1.2
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The amount of electric power is displayed.
˅ keys to change StAt to KWH.
○˄○
6. Press the key to return to the PV/SV display.
92
Page 95
RCN1, RCN2 Number of operating times (440, 441)
[Description] ________________________________________________________________
Displays the number of times that control output relay 1 or 2 has operated. The number is displayed in increments of 1000. (For example, when 1 is displayed, it means the relay has operated 1000 times.)
[Setting example] Checking the number of operating times (control relay 1) ______________
Display Operating procedure
0
PV
SV
PV
SV
PV
SV
PV
SV
245
250
CH
MoN
StAt
oFF
RCN1
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is displayed.
5. Use the
The number of times that control output relay 1 has operated is displayed.
˅ keys to change StAt to RCN1.
○˄○
6. Repeat the same steps to check the number of operating times of
control output relay 2.
7. Press the key to return to the PV/SV display.
93
Page 96
Display
Operating procedure
RUNt Operating days ( 442)
[Description] _______________________________________________________________
Displays the number of days that the temperatu r e controller has been operated.
[Setting example] Checking the number of days the controller has operated _____________
245
250
CH
MoN
StAt
oFF
RCN1
10
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The number of days that the controller has operated is displayed.
˅ keys to change StAt to RUNt.
○˄○
6. Press the key to return to the PV/SV display.
94
Page 97
0 bit
PV input underflow (LLLL)
1 bit
2 bit
PV under range
3 bit
4 bit
RSV under range
5 bit
6 bit
Range setting error
8 bit
9 bit
RSV input circuit error
10 bit
11 bit
PFB input underrange
12 bit
FALt Error source (443)
[Description] ________________________________________________________________
Displays the source of an error. (with hexadecimal number)
PV input overflow (UUUU)
PV over range
RSV over range
PV input circuit error
CT & PFB input circuit error
PFB input overrange
[Setting example] Checking the error source ______________________________________
Display Operating procedure
245
250
CH
MoN
StAt
oFF
FALt
0000
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The error source is displayed. (with hexadecimal number)
˅ keys to change StAt to FALt.
○˄○
6. Press the key to return to the PV/SV display.
95
Page 98
0 bit
DI 1
1 bit
2 bit
DI 3
3 bit
4 bit
DI 5
Display
Operating procedure
Di DI input state ( 444)
[Description] _______________________________________________________________
Displays the state of DI (with hexadecimal number).
DI 2
DI 4
[Setting example] Checking the DI input state ____________________________________
245
250
CH
MoN
StAt
oFF
di
0000
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The DI input state is displayed in hexadecimal.
˅ keys to change “StAt” to “di”.
○˄○
6. Press the key to return to the PV/SV display.
96
Page 99
Display
Operating procedure
ERSt Comm unicat ion error station number (445)
[Description] ________________________________________________________________
Shows the station number under error and the detail of error during cooperative communication or programless communication.
[Setting example] Checking the station number under communication error _____________
245
250
CH
MoN
StAt
oFF
ERSt
0
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The station number under communication error is displayed.
˅ keys to change “StAt” to “ERSt”.
○˄○
6. Press the key to return to the PV/SV display.
97
Page 100
Display
Operating procedure
PLNo Current PI D No. ( 446)
[Description] _______________________________________________________________
Displays the PID palette No. currently selected.
[Setting example] Checking the PID number currently selected ______________________
245
250
CH
MoN
StAt
oFF
PLNo
LoCL
PV
SV
PV
SV
PV
SV
PV
SV
1. Check that the PV/SV display is shown.
2. Press and hold the SEL key to display CH1 (PID parameters).
3. Use the
˅ key to access CH4 (Monitor parameters).
4. Press the SEL key to enter CH4 (Monitor parameters).
StAt (Ramp soak progress) is display ed.
5. Use the
The PID number currently selected is displayed.
˅ keys to change “StAt” to “PLNo”.
○˄○
6. Press the key to return to the PV/SV display.
98
Loading...