Semi-standard Specifications
IP40 enclosure type
Type (FRN
C1J-U)
Applicable motor rating *1) 1/8
Enclosure (IEC 60529)
Cooling method
Weight / Mass
IP 40
Starting frequency: 0.0 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
Natural cooling Fan cooling Fan coolingNatural cooling
Rated capacity *2) 0.31
Rated current
0.7
Rated voltage *3)
Overload capability 150% of rated current for 1min, 200% of rated current for 0.5s
Rated frequency
Phases, voltage, frequency Three-phase, 200 to 240V, 50/60Hz Three-phase, 380 to 480V, 50/60Hz
Voltage/frequency variations
Required power supply capacity *7) 0.2
150
-
1.5(0.7)
Torque *8)
Torque *9)
DC injection braking
Applicable safety standards UL508C, C22.2No.14, EN50178:1997 or equivalent
Voltage: +10 to -15% (Voltage unbalance : 2% or less *10) ) Frequency: +5 to -5%
Momentary voltage dip capability *5)
Rated input current *6)
(with DCR)
(without DCR)
High carrier (4-15kHz)
Low carrier (-3kHz)
0.57
1.1
50, 60Hz
Three-phase, 200V/50Hz, 200, 220, 230V/60Hz Three-phase, 380, 400, 415V/50Hz, 380, 400, 440, 460V/60Hz
Input power source
FRNF12
C1J-2U
1/4
0.59
1.4
0.3
1.5(0.7)
0.93
1.8
FRNF25
C1J-2U
1/2
1.1
2.5
0.6
100
150
1.5(0.7)
1.6
3.1
FRNF50
C1J-2U
1
1.9
4.2
1.1
1.8(0.8)
3.0
5.3
FRN001
C1J-2U
2
3.1
7.0
2.0
50
4.8(1.8)
5.7
9.5
FRN002
C1J-2U
3
4.3
10.0
2.9
30
4.8(1.8)
8.3
13.2
FRN003
C1J-2U
FRN005
C1J-2U
FRNF50
C1J-2U
FRN001
C1J-2U
FRN002
C1J-2U
FRN003
C1J-2U
FRN005
C1J-2U
5
6.7
16.5
4.9
5.3(2.4)
14.0
22.2
1/2
1.1
1.5
0.6
100
150
2.6(1.2)
0.85
1.7
1
1.9
2.5
1.1
2.9(1.3)
1.6
3.1
2
2.9
3.7
2.0
50
4.0(1.8)
3.0
5.9
3
4.3
5.5
2.9
30
4.0(1.8)
4.4
8.2
5
7.1
9.0
0.8 1.5 3.0 5.0 8.0 11.0 17.0
4.9
5.3(2.4)
7.3
13.0
Three-phase 230V
Item Specifications
Three-phase 460V
Output ratingsInput ratings
Braking
When the input voltage is 165V or more, the inverter continues operation. If it
drops below 165V, the inverter operates for 15ms.
When the input voltage is 300V or more, the inverter
continues operation. If it drops below 300V, the inverter
%
A
A
%
%
lbs.(kg)
HP
kVA
kVA
V
Braking resistor built-in type
Type (FRN
C1S-U21)
Applicable motor rating *1) 235235
Enclosure (IEC 60529)
Cooling method
Weight / Mass
IP20, UL open type *11)
Fan cooling
Rated capacity *2) 3.1 4.3 6.7 2.9 4.3 7.1
Rated current *4)
8.0
(7.0)
11.0
(10.0)
17.0
(16.5)
3.7 5.5 9.0
Rated voltage *3)
Overload capability 150% of rated current for 1min, 200% of rated current for 0.5s
Rated frequency
Phases, voltage, frequency Three-phase, 200 to 240V, 50/60Hz Three-phase, 380 to 480V, 50/60Hz
Voltage/frequency variations
Required power supply capacity *7) 2.0 2.9
150 100 100 150 100 100
18 12 8 18 12 8
321.5321.5
4.9 2.0 2.9 4.9
4.0(1.8) 4.0(1.8) 5.5(2.5) 4.0(1.8) 4.0(1.8) 5.5(2.5)
Torque *8)
Braking time
Duty cycle
DC injection braking Starting frequency: 0.0 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
Voltage: +10 to -15% (Voltage unbalance *10) : 2% or less) Frequency: +5 to -5%
Momentary voltage dip capability *5)
Rated current *6)
(with DCR)
(without DCR)
5.7
9.5
8.3
13.2
14.0
22.2
3.0
5.9
4.4
8.2
7.3
13.0
50, 60Hz
Three-phase, 200V/50Hz, 200, 220, 230V/60Hz Three-phase, 380, 400, 415V/50Hz, 380, 400, 440, 460V/60Hz
Input power source
FRN002
C1S-2U21
FRN003
C1S-2U21
FRN005
C1S-2U21
FRN002
C1S-4U21
FRN003
C1S-4U21
FRN005
C1S-4U21
Three-phase 230V
Item Specifications
Three-phase 460V
Output ratingsInput ratings
Braking
When the input voltage is 165V or more, the inverter continues
operation. If it drops below 165V, the inverter operates for 15ms.
When the input voltage is 300V or more, the inverter continues
operation. If it drops below 300V, the inverter operates for 15ms.
A
s
A
%
%
lbs.(kg)
HP
kVA
kVA
V
*1) Standard 4-pole motor
*2) Rated capacity is calculated by regarding the output rated voltage as 220V for three-phase 230V
series, and as 440V for three-phase 460V series.
*3) Output voltage cannot exceed the power supply voltage.
*4) Use the inverter at the current given in ( ) or below when the carrier frequency setting is higher
than 4kHz ( : to ) or the ambient temperature is 40°C (104°F) or higher.
*5) Calculated under the standard overload conditions by JEMA committee (about 85% of overload
by the standard applicable motor.)
*6) Calculated under Fuji-specified conditions.
*7) Obtained when a DC reactor (DCR) is used.
*8) Average braking torque obtained with AVR control OFF (Varies with the efficiency of the motor.)
*9) Average braking torque obtained by use of external braking resistor (optional)
*10) Voltage unbalance [%] =
If this value is 2 to 3%, use AC reactor (option).
*11) NEMA1 kit (option) is required for the enclosure conforming to the UL standard TYPE1 (NEMA1).
Use the inverter in the ambient temperature range from -10 to +40°C (14 to 104°F).
Max voltage [V] - Min voltage [V]
Three-phase average voltage [V]
x 67 (Refer to IEC 61800-3.)
10