Fuji Electric 9365388044 Installation Instructions Manual

OUTDOOR UNIT ACCESSORIES
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION SHEET
(PART NO. 9365388044)
WARNING
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
CAUTION
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant (R22) models. However, pay careful attention to the following points:
1 Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and
installation and service tools are special. (See the table below.) Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
2 Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with con-
ventional refrigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
3 Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
4 When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table 1. Never use copper pipes thinner than 0.8 mm (Nominal diameter is 3/8 in.), 1.0 mm (Nominal diameter is 5/8 in.) even when it is available on the market.
For authorized service personnel only.
WARNING
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts. This installa-
tion instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it
produces a toxic gas.
5 Do not use an extension cord.
6 Do not turn on the power until all installation work is complete.
••
••
Be careful not to scratch the air conditioner when handling it.
••
••
After installation, explain correct operation to the customer, using the operating manual.
••
••
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
SELECTING THE MOUNTING POSITION
- Continued on back -
Refrigerant
R410A
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm2) for high pressure. –0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm
2
) for low pressure. To increase pressure resistance, the hose material and base size were changed. A conventional vacuum pump can be used by installing a vacuum pump adapter. Special gas leakage detector for HFC refrigerant R410A.
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
For outdoor unit drain piping work [Heat & Cool model (Reverse cycle) only]
1
1
Drain pipe
Drain cap
Cassette Type
Table 1 Thicknesses of Annealed Copper Pipes
Nominal
diameter (inch)
3/8 5/8
Thickness (mm)
R410A [ref.] R22
0.80 0.80
1.00 1.00
Outer diameter
(mm)
9.52
15.88
WARNING
Install at a place that can withstand the weight of the in­door and outdoor units and install positively so that the units will not topple or fall.
CAUTION
1 Do not install where there is the danger of combustible
gas leakage.
2 Do not install near heat sources.
3 If children under 10 years old may approach the unit,
take preventive measures so that they cannot reach the unit.
Pipe
Pipe
Especially, the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the first installation. Decide the mounting position together with the customer as follows: The discharge direction can be selected as shown below.
Fig. 1
CAUTION
Since 2-way outlet as shown below causes performance problems, do not set it.
(4 directions)
(3 directions)
100 mm (4”) or more
Piping position
(2
directions
)
100 mm (4”) or more
100 mm (4”) or more
(2
directions
)
1,000 mm (39”) or more
INDOOR UNIT
(1) Install the indoor unit on a place having a sufficient strength so that it
withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstr ucted; the air should be
able to blow all over the room. (3) Leave the space required to service the air conditioner (Fig. 2). (4) The ceiling rear height as shown in Fig. 3. (5) A place from where the air can be distributed evenly throughout the
room by the unit. (6) A place from where drainage can be extracted outdoors easily. (7) Install the unit where noise and vibrations are not amplified.
Fig. 2
This mechanism enables the cassette body to move 35 mm down­ward and realizes installation to the space of 200 mm. No special works and option is needed.
Fig. 3
You can select 2-way setting
Obstruction
Strong and durable ceiling
2,300 mm (91”)
or more
1,000 mm (39”) or more
1,000 mm (39”)
or more
Floor
(B) Slender setting(A) Standard setting
200 mm (7-7/8”)
or more
235 mm (9-1/4”)
or more
OUTDOOR UNIT
WARNING
1 Install the unit where it will not be tilted by more than
5˚.
2 When installing the outdoor unit where it may exposed
to strong wind, fasten it securely.
(1) If possible, do not install the unit where it will exposed to direct sun-
light. (If necessary, install a blind that does not interfere with the air flow.)
(2) Install the outdoor unit in a place where it will be free from being dirty
or getting wet by rain as much as possible. (3) Install the unit when connection to the indoor unit is easy. (4) During heating operation, drain water flows from the outdoor unit.
Therefore, install the outdoor unit in a place where the drain water
flow will not be obstructed. (5) Do not place animals and plants in the path of the warm air. (6) Take the air conditioner weight into account and select a place where
noise and vibration are small. (7) Select a place so that the warm air and noise from the air conditioner
do not disturb neighbors. (8) Provide the space shown in Fig. 4 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides. (9) Do not set the unit directly on the ground because it will cause trou-
ble. (10) Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.
Fig. 4
Air
30 cm (1) or over
30 cm (1’) or over
30 cm (1’) or over
60 cm (2) or over
60 cm (2’) or over
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Coupler heat insulation
Special nut A (large flange)
Special nut B (small flange)
Template
Blower cover insulation
Hook wire
Binder (small)
Remote controller
Tapping screw (flush heads)
Remote controller cord
Q’ty
2
4
4
1
2
2
Application
For indoor side pipe joint
For installing indoor unit
For installing indoor unit
For ceiling hole cutting
For discharged air
For installing intake grille.
For fixing the remote controller cord
For installing the remote controller
For connecting the remote controller
1
1
2
1
1
INSTALLATION PROCEDURE
Install the air conditioner as follows:
INDOOR UNIT INSTALLATION
WARNING
Install the air conditioner in a location which can with­stand a load do at least five times the weight of the main unit and which will not amplify sound or vibra­tion. If the installation location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose. Please take care.
REMOVING THE INTAKE GRILLE
(1)Push the intake grille pushbuttons (two places). (2)Open the intake grille.
Fig. 5
OPEN
PUSH
(3)Remove the grille hinge wire.
Fig. 6
A
Pull up while pressing the B section (Fig. 7).
Fig. 7 Part A detail view Fig. 8 Part A section view
B
(4)Remove the intake grille.
REMOVING THE PANEL FRAME
Pull up the cor ner sections (A) of the panel frame as shown in Fig. 9 (4 locations).
Fig. 9 Part A detail view
Grille hinge wire
A
A
A
A
B
Pull up in the direction of the arrow while holding down the C section of Fig. 10 (4 locations).
Fig. 10 Part B detail view
Panel base
Fig. 11
C
Panel frame
CAUTION
Always remove the panel frame after removing the intake grille.
1. POSITION THE CEILING HOLE AND HANGING BOLTS
Fig. 12
940 mm ( 37”)
890 mm ( 35-3/64”)
750 mm (29-17/32”)
750 mm (29-17/32”)
Hanging bolt M10
Fig. 14
(A) Standard setting
Hole-in anchor Hole-in plug
Concrete Insert
Drain pipe (I.D. 32 mm)
60 mm
(2-3/8)
305.5 mm (12”)
298.5 mm (11-3/4”)
(2-3/4)
248.5 mm (9-25/32)
70 mm
(3-15/16)
(5)
100 mm
235 mm (9-1/4”)
127 mm
(B) Slender setting
Drain pipe (I.D. 32 mm)
60 mm
(2-3/8)
305.5 mm (12)
11-3/4 (298.5 mm)
248.5 mm (9-25/32)
70 mm
(2-3/4)
(3-15/16)
(3-5/8)
100 mm
92 mm
200 mm (7-7/8”)
3. BODY INSTALLATION
[The ceiling rear height is 235 mm (9-1/4") or more.] [Standard setting]
[The ceiling rear height is 200 mm (7-7/8") or more.] [Slender setting] (1) Install special nut A, then special nut B onto the hanging bolt (Fig. 15). (2) Raise the body and mount its hooks onto the hanging bolt between
the special nuts (Fig. 15). (3) Turn special nut B to adjust the height of the body (Fig. 15). (4) Leveling
Using a level, or vinyl hose filled with water, fine adjust so that the
body is level.
WARNING
Perform final tightening by tightening the double nut firmly.
Fig. 15
*Must fit tightly against ceiling
without any gap.
Special nut B
Hanging bolt
Special nut A
30 mm or more
Hook
Ceiling
After installing the body, tighten the nuts.
Fig. 16
* Allowable space between the unit and the ceiling 5 mm or less
INSTALLING THE PANEL FRAME
Fig. 17
Vinyl hose
* With slender setting, turn the panel frame 90° as shown in the dia-
gram above.
Grille setting method has been changed at the marked posi­tions on the panel frame and panel base.
Fig. 18
(A) Standard setting (B) Slender setting
Fig. 19 (Example)
Panel base
Panel frame
*90° Turn
Mark
Panel frame
No mark
2. HANGING PREPARATIONS
Firmly fasten the hanging bolts as shown in Fig. 13 or by another method.
Install the hanging bolts at a place where they would be capable of
holding a weight of at least 50 kgf per bolt.
Fig. 13
2
INSTALLING DRAIN PIPE
CAUTION
Install the drain pipe in accordance with the instructions in this installation instruction sheet and keep the area warm enough to prevent condensation. Problems with the pip­ing may lead to water leaks.
NOTE: Install the drain pipe.
••
••
Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.
••
••
Use general hard polyvinyl chloride pipe (VP25) [outside diameter
32 mm (1-1/4)] and connect it with adhesive (polyvinyl chloride) so that there is no leakage.
••
••
When the pipe is long, install supporters.
••
••
Do not perform air bleeding.
••
••
Always heat insulate the indoor side of the drain pipe.
••
••
When desiring a high drain pipe height, raise it up to 800 mm (31) or
less from the ceiling within a range of 150 mm (6) from the body. A rise dimension over this range will cause leakage.
Fig. 20
Max. 800 mm (31”)
Rise
Trap
Supporter
1.5 to 2.0 m (5 to 6.5 ft)
Air bleeding
150 mm (6) or less
3
OUTDOOR UNIT INSTALLATION
1. OUTDOOR UNIT PROCESSING
When the outdoor unit will be exposed to strong wind, fasten it with bolts at the four places indicated by the arrows (Fig. 21).
Fig. 21
Drain pipe
2. OUTDOOR UNIT CONNECTION CORD AND PIPE CONNECTION PREPARATIONS
(1) Remove outdoor unit terminal cover.
Fig. 22
(2) Connect the piping, connection cord and power supply cord.
CAUTION
If this product is used in an area where the temperature falls below freezing for long periods of time, do not con­nect the drain pipe. Instead, allow the water to drain into a drain pan.
Bottom
Drain pipe mounting hole
Drain cap
Air flow
Drain pipe mounting hole
Bottom plate
Terminal cover
CONNECTION PIPE REQUIREMENT
Table 2
Diameter
Large
15.88 mm (5/8”)
Maximum
length
25 m (82 ft)
Maximum Height (between indoor
and outdoor)
15 m (50 ft)
Small
9.52 mm (3/8”)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks. Use heat insulation with heat resistance above 120 °C. (Re­verse cycle model only) In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insulation around the refrigerant piping. If the ex­pected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker. If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 20 °C).
ELECTRICAL REQUIREMENT
••
••
Electric wire size and fuse/breaker capacity:
Table 3
••
••
Always use H07RN-F or equivalent to the connection cord.
••
••
Install the disconnect device with a contact gap of at least 3 mm nearby
the units (both indoor unit and outdoor unit).
••
••
Use pipe with water-resistant heat insulation.
Power supply cord (mm2)
Connection cord (mm2)
Fuse/Breaker capacity (A)
MAX.
MIN.
MAX.
MIN.
4.0
3.5
2.5
1.5
30
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter. (2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor
and outdoor units respectively) onto the pipe and perform the flare processing with a flare tool. Use the special R410A flare tool, or the conventional (for R22) flare tool. When using the conventional flare tool, always use an allowance ad­justment gauge and secure the A dimension shown in table 4.
Fig. 23
CONNECTING THE PIPING
WARNING
Do not use the existing (for R22) piping and flare nuts.
If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc. (Use the special R410A materials.)
CAUTION
1 Do not use mineral oil on flared part.
Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
2 While welding the pipes, be sure to blow dry nitrogen
gas through them.
3 The maximum lengths of this product are shown in ta-
ble 2. If the units are further apart than this, correct operation can not be guaranteed.
4
Check if [L] is flared uniformly and is not cracked or scratched.
Die
A
Pipe
Table 4 Pipe outside diameter
Pipe outside
diameter
9.52 mm (3/8 in.)
15.88 mm (5/8 in.)
A (mm)
Conventional (R22) flare tool Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
Flare tool for
R410A, clutch type
0 to 0.5 0 to 0.5
L
Extend the pipe by unwinding it.
Cut line
Pipe
Heat insulating pipe
Cutter
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 24
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the heat insulating pipe with a sharp cutter as shown in Fig. 25, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insulating pipe back on the pipe, and secure it with tape.
Fig. 25
CAUTION
1 To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or over.
2 If the pipe is bent repeatedly at the same place, it will
break.
3. CONNECTION PIPES
(1) Indoor unit side
Fig. 26
CAUTION
1 Be sure to apply the pipe against the port on the in-
door unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
2 Do not remove the flare nut from the indoor unit pipe
until immediately before connecting the connection pipe.
Indoor unit
Small pipe
Large pipe
Holding spanner
Body side
Torque wrench
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 27, in order to tighten the flare nut correctly.
To prevent gas leakage, coat the flare surface with alkylbenzene oil (HAB). Do not use mineral oil.
Table 5 Flare nut tightening torque
Do not remove the cap from the connection pipe before connecting the pipe.
CAUTION
Be sure to connect the large pipe after connecting the small pipe completely.
(2) Outdoor unit side
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the same as that as at the indoor side.
Fig. 28
Flare nut
9.52 mm (3/8 in.) dia.
15.88 mm (5/8 in.) dia.
Tightening torque
33 to 42 N·m (330 to 420 kgf·cm)
63 to 77 N·m (630 to 770 kgf·cm)
(Large pipe)
(Small pipe)
Connection pipe
Flare nut
3-Way valve
2-Way valve
When the flare nut is tightened properly by your hand, hold the body side coupling with a separate spanner, then tighten with a torque wrench (Fig. 27).
Fig. 27
(Hanging bolt position)
(Grille measurement)
(Hanging bolt position)
(Ceiling opening measurement)
* Appearance of slender setting
603 mm
343 mm
*After removing the screws,
remove terminal cover.
7
GRILLE INSTALLATION
BLOWER COVER INSULATION
Install the blower cover insulation only when the outlet direction is not specified. Two blower cover insulations are packed with the indoor unit. Install the blower cover insulation at the diffuser position shown in Fig. 38. At this time, use the piping position as the criteria.
Fig. 38
A-A Section view
A
A
INSTALLING THE INTAKE GRILLE
(1)Mount the grille hinge wire to the hook shaft as shown in Fig. 39.
Fig. 39
A
Latch the grille hinge wire to the hook shaft, and fasten.
Fig. 40 Part A detail view Fig. 41 Part A section view
Grille hinge wire
(2)Install the hook wire.
Pass the hook wire through the panel base from the rear side as shown in Fig. 42, and fasten to the reinforced metal fitting of the intake grille using a screw.
Fig. 42
Screw
Fig. 43 Section view
2 direction example
(Piping direction)
Blower cover insulation
Panel base
Drain pan
Hook shaft
Hook wire
RFM (grille)
(3)Loosen the screw, put the loop of the hook wire over it, and tighten
the screw again.
CAUTION
Install the intake grille hook wire to the grille assem­bly. If it falls, it may cause injuries.
(4)Bring up the intake grille by pushing it up at an angle as shown in
Figs. 44, 45, and fasten.
Fig. 44
Fig. 45
Hook wire
(1) Remove the control box cover and cover (wire) B and install the con-
nection cord.
Fig. 33
Remote controller cord
Terminal board (Indoor unit)
Ceiling height
(m)
Normal
High ceiling 1
High ceiling 2
Low ceiling
1
2.5 - 3.0
3.0 - 3.5
More than 3.5
Less than 2.5
2
OFF
ON
OFF
ON
3
OFF
OFF
ON
ON
DIP-SW4
Gas
Liquid
5
VACUUM PROCESS
CAUTION
1 Do not purge the air with refrigerants but use a vacuum
pump to vacuum the installation! There is no extra re­frigerant in the outdoor unit for air purging!
2 Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may dam­age the vacuum pump or the unit.
1. VACUUM
(1) Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the pressure
gauge indicates –0.1 MPa (–76 cmHg).
(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump
for at least 15 minutes.
(4) Disconnect the service hoses and fit the cap to the charging valve to
the specified torque.
(5) Remove the blank caps, and fully open the spindles of the 2-way and
3-way valves with a hexagon wrench (Torque : 6 to 7 N · m (60 to 70 kgf·cm).
(6) Tighten the blank caps of the 2-way valve and 3-way valve to the
specified torque.
Table 6
Fig. 29
Connecting pipe
Blank cap
Hexagon wrench
3-way valve
Charging port
Cap
Service hose with valve core
Outdoor unit
CAUTION
Use a clean gauge mani­fold and charging hose for R410A exclusively.
t
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor unit at the factory. When the piping is longer than 7.5 m, additional charging is necessary. For the additional amount, see the table below.
Table 7
Between 7.5 m and 25 m, when using a connection pipe other than that in the table, charge additional refrigerant with 40 g (1.4 oz)/1 m (3.3 ft) (Reverse cycle model), 20 g (0.71 oz)/1 m (3.3 ft) (Cooling model) as the criteria.
CAUTION
1 When moving and installing the air conditioner, do not
mix gas other than the specified refrigerant (R410A) inside the refrigerant cycle.
2 When charging the refrigerant R410A, always use an
electronic balance for refrigerant charging (to meas­ure the refrigerant by weight).
3 When charging the refrigerant, take
into account the slight change in the composition of the gas and liq­uid phases, and always charge from the liquid phase side whose com­position is stable.
4 Add refrigerant from the charging valve after the com-
pletion of the work.
5 If the units are further apart than the maximum pipe
length, correct operation can not be guaranteed.
GAS LEAKAGE INSPECTION
CAUTION
After connecting the piping, check the joints for gas leak­age with gas leak detector.
Blank cap (2-way valve)
Blank cap (3-way valve)
Charging port cap
Tightening torque
20 to 25 N·m (200 to 250 kgf·cm)
30 to 35 N·m (300 to 350 kgf·cm)
10 to 12 N·m (100 to 120 kgf·cm)
Use a 4 mm hexagon wrench.
Gauge manifold
Vacuum pump
Service hose
R410A
Cooling
model
7.5 m (25 ft)
None
None
Pipe length
10 m (33 ft)
100 g
(3.5 oz)
50 g
(1.8 oz)
15 m (49 ft)
300 g
(10.6 oz)
150 g
(5.3 oz)
20 m (66 ft)
500 g
(17.6 oz)
250 g
(8.8 oz)
Additional refrigerant
Heat & Cool
(Reverse cycle)
25 m (82 ft)
700 g
(24.7 oz)
350 g
(12.3 oz)
LO
HI
6
8
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 25 mm (15/16”) of expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using pliers, bend the solid wire to form a loop suitable for the
terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 10 mm (3/8”) of expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using a round terminal fastener or pliers, securely clamp a round
terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the ter-
minal screw using a screwdriver.
Fig. 31
A. Solid wire
Strip 25 mm (15/16”)
Insulation
Loop
B. Strand wire
Strip 10 mm (3/8”)
Round terminal
Wire
Screw with special washer
Round terminal
Terminal board
Wire
Screw with special washer
Round terminal
HOW TO FIXED CONNECTION CORD AND POWER CORD AT THE CORD CLAMP
After passing the connection cord and power cord through the insula­tion tube, fasten it with the cord clamp.
Fig. 32
Insulation tube
Insulation tube Cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
1. INDOOR UNIT SIDE
WARNING
1 Before starting work, check that power is not being sup-
plied to the indoor unit and outdoor unit.
2 Match the terminal board numbers and connection cord
colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.
3 Connect the connection cord firmly to the terminal
board. Imperfect installation may cause a fire.
4 Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)
5 Always connect the ground wire.
Body
Be sure to overlap the insulation
Coupler heat insulation
No gap
Coupler heat insulation
INSTALLING THE COUPLER
HEAT INSULATION
After checking for gas leaks, insulate by wrapping insulation around the two parts (large and small) of the indoor unit coupling, using the coupler heat insulation. After installing the coupler heat insulation, wrap both ends with vinyl tape so that there is no gap.
Fig. 30
CAUTION
Must fit tightly against body without any gap.
(2) After wiring is complete, clamp the remote controller cord and con-
nection cord with the cord clamp.
(3) Install the control box cover and cover (wire) B.
Fig. 34
Cover (wire) B
Control box cover
Cord clamp
Connection cord (To the outdoor unit)
Fig. 35
Red
White
Black
Ceiling height setting
Set the DIP switch for the ceiling height according to the table below.
Table 8
CAUTION
1 If the setting for a low ceiling is selected, the capacity
of the air conditioner decreases slightly.
2 Do not set any switches other than those specified in
this sheet. The air conditioner may not operate correctly if any switches other than those specified are changed.
Remote controller
Terminal board
OUTDOOR UNIT
Connection cord
2. OUTDOOR UNIT SIDE
WARNING
1 Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.
2 Match the terminal board numbers and connection cord
colors with those of the indoor unit side. Erroneous wiring may cause burning of the electric parts.
3 Connect the connection cords and the power supply
cord firmly to the terminal board. Imperfect installation may cause a fire.
4 Always fasten the outside covering of the connection
cord and the power supply cord with cord clamps. (If the insulator is chafed, electric leakage may occur.)
5 Always connect the ground wire.
(1) Remove the terminal cover of the outdoor unit, and insert the end of
the connection cord and the power supply cord into the terminal board.
(2) Fasten the connection cord and the power supply cord with the cord
clamp, and install the terminal cover.
Fig. 37
Power supply
Remote controller
Black
White
Red
Outdoor unit side terminal
Indoor unit side terminal
Power line
Control line
EARTH
NL32
(N)
1
Connection cord
Terminal board
Cord clamp
Power supply cord
Insulation tube
Connection cord
Power supply cord
Cord clamp
Insulation tube
L N 3
1
3
2
(N)
2
(N)
1
3 2 1
EARTH
Terminal cover
45 mm
45 mm
CAUTION
When routing the ground wires, leave slack as shown in the illustrations.
9
10
POWER
WARNING
1 The rated voltage of this product is 230 V A.C. 50 Hz.
2 Before turning on verify that the voltage is within the
198 V to 264 V range.
3 Always use a special branch circuit and install a spe-
cial receptacle to supply power to the air conditioner.
4 Use a special branch circuit breaker and receptacle
matched to the capacity of the air conditioner. (Install in accordance with standard.)
5 Perform wiring work in accordance with standards so
that the air conditioner can be operated safely and posi­tively.
6 Install a leakage special branch circuit breaker in ac-
cordance with the related laws and regulations and elec­tric company standards.
CAUTION
1 The power source capacity must be the sum of the air
conditioner current and the current of other electrical appliances. When the current contracted capacity is in­sufficient, change the contracted capacity.
2 When the voltage is low and the air conditioner is diffi-
cult to start, contact the power company the voltage raised.
3 This air conditioner must be connected to a power
source that has an electrical impedance of 0.159 or less or has a supply current of 100 A or greater. If the power supply does not meet the specifications, con­tact the power company.
ONONOFF
1 2 3 4 5 6
1. INSTALLING THE REMOTE CONTROLLER
(1) Open the operation panel on the front of the remote controller, re-
move the two screws indicated in the following figure, and then re­move the front case of the remote controller.
Fig. 46
Front case (back side)
Rear case
Connector
Remote controller wires
Rear case
Connector
Front case
1. Red
2. White
3. Black
Binder
3. SETTING THE DIP SWITCHES
When using a battery (memory backup)
Fig. 49
Change the DIP switch setting to use batteries. (The DIP switch is not set to use batteries at the factory.) Change DIP switch No. 6 from OFF to ON. If batteries are not used, all of the settings stored in memory will be de­leted if there is a power failure.
DIP Switch
Screws
2. ROUTING THE REMOTE CONTROLLER WIRES
(1) Install the remote controller wires to the terminals on the top of the
rear case as shown in the following figure. (2) Fasten the wires with the binder. (3) If the remote controller wires run through the room, use a tool to cut
away the thin area on the upper center of the front case.
Fig. 48 (Example)
11
REMOTE CONTROLLER
SETTING
CAUTION
1 In order to detect the room temperature
correctly when using the temperature sensor of the remote controller, do not install the remote controller in a place where it will be exposed to direct sun­light or directly below the air outlet of the indoor unit.
2 When installing the remote controller and cord near a
source of electromagnetic waves, separate the remote controller from the source of the electromagnetic waves and use shielded cord.
3 Do not touch the remote controller PC board and PC
board parts directly with your hands.
Temperature sensor
When installing the remote controller, remove the connector from the front case. The wires may break if the connector is not removed and the front case hangs down. When installing the front case, connect the connector to the front case.
(2) Install the rear case to the wall, etc. with the two tapping screws.
Refer to the following information to install the remote controller wires.
Fig. 47
SUMOTUWETH FR
SA
4. SETTING THE ROOM TEMPERATURE DETEC­TION LOCATION
The detection location of the room temperature can be selected from the following three examples. Choose the detection location that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor.
A
B. Remote controller setting
The room temperature is detected by the remote controller temperature sensor.
B
C
Indoor unit
(1) When the THERMO SENSOR button is pressed, the lock display
flashes because the function is locked at the factory.
Fig. 50
(1) Press the THERMO SENSOR button for 5
seconds or more to unlock the function. The thermo sensor display flashes and then dis­appears when the function is unlocked.
(2) Press the THERMO SENSOR button. The thermo sensor display ap-
pears.
(3) Press the THERMO SENSOR button again for 5 seconds or more to
lock the function. The thermo sensor display flashes and then remains on when the function is locked.
(4) Make sure that the function is locked.
C.Indoor unit/remote controller setting
(room temperature sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect the room temperature.
12
TEST RUN
CAUTION
Supply power to the crankcase heater for at least 12 hours before the start of operation in winter.
(1) Stop the air conditioner operation. (2) Press the master control button and the fan control button simultane-
ously for 2 seconds or more to start the test run.
Fig. 53
Unit number (usually 0)
Error code
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication “E:EE” is displayed, follow the following items to perform the self-diagnosis. E:EE indicates an error has occurred.
1. REMOTE CONTROLLER DISPLAY
(1) Stop the air conditioner operation.
(2) Press the set temperature buttons simultaneously for 5 sec-
onds or more to start the self-diagnosis. Refer to the following tables for the description of each error code.
Fig. 54
Test run display
(3) Press the set temperature buttons simultaneously for 5 sec-
onds or more to stop the self-diagnosis.
Table 9
Ex. Self-diagnosis
Error code Error contents
Communication error (indoor unit
remote controller) Communication error (indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short­circuited Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor short­circuited Power source connection error
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor short-circuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor short-circuited
00 01 02
03 04 05 06
07 08 09 0A 0b 0c 0d
Indoor unit No. 0 Indoor unit No. 1 Indoor unit No. 2 Indoor unit No. 3
Remote controller wire
Remote controller
(2) Rotary switch setting (indoor unit)
Set the unit number of each indoor unit using the rotary switch on the indoor unit circuit board. The rotary switch is normally set to 0.
(3) DIP switch setting (remote controller)
Change DIP switch No. 3 on the remote controller from OFF to ON.
Indoor unit
Rotary Switch
Remote controller
DIP Switch
2. DUAL REMOTE CONTROLLERS (OPTIONAL)
Two separate remote controllers can be used to operate the indoor units.
(1) Wiring method (indoor unit to remote controller)
Fig. 59
(2) DIP switch setting (remote controller)
Set the remote controller DIP switch Nos. 1 and 2 according to the following table.
Number of remote controllers
Master unit
1 (Normal)
2 (Dual)ONOFF
OFF
OFF
DIP-SW No. 1 DIP-SW No. 2
Remote controller
DIP Switch
Number of remote controllers
Slave unit
1 (Normal)
2 (Dual)–ON–ON
DIP-SW No. 1 DIP-SW No. 2
SW3
Table 11
Table 12
Fig. 60
2. OUTDOOR UNIT LEDS
Heat & Cool model (reverse cycle) only
When a malfunction occurs in the outdoor unit, the LEDs on the circuit board light to indicate the error. Refer to the following table for the descrip­tion of each error according to the LEDs.
Table 10
When the fault is cleared, the LED lamp goes off. However, for discharge pipe temperature abnormal and high pressure abnormal, the LED lamp lights continuously for 24 hours, as long as the power is not turned off.
Quick flash continued Quick flash continued
Model abnormal or EEPROM abnormal
1 quick flash repeated Lighting continued
Power source connection error
2 quick flash repeated Lighting continued
Discharge tempera­ture sensor error
3 quick flash repeated Lighting continued
Outdoor heat exchanger tempera­ture sensor error
4 quick flash repeated Lighting continued Outdoor temperature
sensor error
5 quick flash repeated Lighting continued
Communication signal error 6 quick flash repeated Lighting continued Indoor unit error 7 quick flash repeated Lighting continued Discharge temperature
abnormal 8 quick flash repeated Lighting continued
High pressure abnormal
Error display
LED1 LED2 Error contents
Error code Error contents
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
0E 0F 11 12 13
14
0.1 sec.
OFF
ON
0.1 sec.
OFF
ON
0.5 sec.
2 sec.
OFF
ON
OFF
ON
0.5 sec.
2 sec.
OFF
ON
OFF
ON
0.5 sec.
2 sec.
OFF
ON
OFF
ON
1 2 3
1 2 3
1 2 3
ONOFF
1 2 3 4 5 6
ON
1 2 3 1 2 3 1 2 3
1 2 3
1 2 3
ONOFF
1 2 3 4 5 6
NO.
SW state
Detail
OFF ON
1 Dual remote controller
2 setting
3
One unit
Multiple unit Group control setting
4
Heat & Cool model
Cooling only model
Model setting
5 Invalidity Validity ✽ Auto changeover setting
6 InvalidityValidity Memory backup setting
NO.
SW state
Detail
OFF ON
1 Invalidity Validity ✽ Auto restart setting
2 ——✽ Temperature correction
3 ——✽ setting for heating
1 ——Remote controller setting
2
Air flow setting
3
DIP-Switch 1
Indoor unit
Table 13
Remote controller
Table 14
[DIP-SWITCH SETTING]
DIP-Switch 4
DIP-Switch
: Factory setting
OPENING THE DUCT CONNECTION HOLE
Fig. 62
Distribution duct
Distribution duct
Fresh air
CAUTION
1 When performing hole opening work, be careful not to
damage the drain pan.
2 When connecting the distribution duct, to make the air
flow easily, block the outlet port with the blower cover insulation as shown by the hatched lines in Fig. 62. For the blocking direction, refer to Fig. 38.
1. DIMENSION
Screw position and connection hole which are fresh air duct and distribu­tion duct.
Fig. 63
P. D 120
160
4
5°
4
5°
ø100
ø70
113
334.2
P. D 88
97
Unit: mm
12-ø3.3 self tapping screw holes (for 4 mm)
2. DISTRIBUTION DUCT AND FRESH AIR DUCT HOLE PROCESSING
Use the distribution duct hole and fresh air duct hole by removing the insulation material as shown below.
Fig. 64
Cut
Cut
Cabinet
Cut off the part (Cabinet) indicated by the arrow in the Fig. 64 with
nippers, needle nose pliers, etc.
Fig. 65
PART NO. 9365388044
Fig. 51
NOTES
If the function to change the temperature sensor is used as shown in examples A and B (other than example C), be sure to lock the detection location. If the function is locked, the lock display will flash when the THERMO SENSOR button is pressed.
(1) Press the THERMO SENSOR button for 5 seconds or more to unlock
the function. The thermo sensor display flashes and then disappears when the function is unlocked.
(2) Press the THERMO SENSOR button to select the temperature sen-
sor of the indoor unit or the remote controller.
Fig. 52
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using a single remote controller.
(1) Wiring method (indoor unit to remote controller)
Fig. 56
Cabinet
Knife
Insulation (Inner box)
14
123
O
F
F
SW 4
123
O
F
F
SW 1
Indoor unit PC board
Dip switch (SW4)
Indoor unit PC board
Fig. 36
DAY OFF
DELETE SET
ENERGY
SAVE
THERMO SENSOR
SET BACK
DAY
CLOCK ADJUST
3. AUTO RESTART
When the air conditioner power was temporarily turned off by a power failure etc., it restarts automatically after the power recovers. (Operated by setting before the power failure)
The auto restart function can be canceled.
(1) DIP switch setting (indoor unit)
Change the DIP switch (SW1-1) on the indoor unit circuit board from ON to OFF. The auto restart function will be canceled.
Indoor unit
OFF
123
OFF
SW1
OFF
123
SW4
DIP Switch
Fig. 61
3. CHECKING DRAINAGE
To check the drain, remove the water cover and fill with 2 to 3rof water as shown in Fig. 55. The drain pump operates when operating in the cooling mode.
Fig. 55
Water cover
Drain pipe
Watering pot
13
SPECIAL INSTALLATION
METHODS
CAUTION
1 When setting the rotary switch and DIP switches, do
not touch any other parts on the circuit board directly with your bare hands.
2 Be sure to turn off the main power.
Indoor unit
Indoor unit
Remote controller wire
Fig. 57 Fig. 58
Indoor unit
Master
unit
Slave
unit
Open the holes and cut the insulation with a knife. * Be careful not to damage the internal parts. * Be careful not to cut yourself on the cutout in the metal plate. * Please remove the insulation (inner box) left over after cutting.
Connect the distribution duct. * When mounting the duct, block the gap so that there is no cold air leakage. *Insulate the duct and cut connection.
CAUTION
The air conditioner cannot take in fresh air by itself. When connecting a fresh air duct, always use a duct fan.
Remote controller
Loading...