FuG Elektronik MCA Series, MCA 750, MCA 3000 Operating Instructions Manual

FuG Elektronik GmbH Am Eschengrund 11 D-83135 Schechen Tel.: +49(0)8039/40077-0 Fax: +49(0)8039/40077-99 info@fug-elektronik.de www.fug-elektronik.de
Medium Voltage Power Supplies MCA - Series
power classes up to 9000W
ISO 9001 : 2008
Operating Instructions
This instruction is only dedicated to electrical experts and people with a suitable technical education, which are familiar with electrical risks and can keep the risk for themselves and other people as low as possible. For the operation of this unit only a.m. persons are admitted.
MCA -Serie FuG Elektronik GmbH, Am Eschengrund 11, D - 83135 Schechen
File: MCA Rev_3 Englisch.docx Rev 3 2 von 16
Content:
1. Safety Instructions ............................................................................................................... 3
2. General ................................................................................................................................ 4
2.1 Setup Information ................................................................................................................ 5
2.2 Preparation for commissioning ............................................................................................ 5
3. Description ........................................................................................................................... 6
3.1 Front Panel, Controls ........................................................................................................... 6
3.2 Rear side, Connections........................................................................................................ 7
3.3 Assembly ............................................................................................................................. 7
3.4 Mode of operation ................................................................................................................ 8
4. Operation with local controls ................................................................................................ 9
5. Maintenance ...................................................................................................................... 10
6. Options .............................................................................................................................. 11
6.1 Analog Programming ......................................................................................................... 11
6.1.1 Directly Connected Analog Programming .......................................................................... 11
6.1.2 Floating Analog Programming (2kV) .................................................................................. 11
6.2 Digital Interface PROBUS V (Option)................................................................................. 14
7. Technical Data ................................................................................................ ................... 15
8. Calibration .......................................................................................................................... 16
9. Certificate of Conformity .................................................................................................... 16
10. Accessories ....................................................................................................................... 16
11. Warranty, Repairs .............................................................................................................. 16
12. Special Models, Modifications ............................................................................................ 16
MCA -Serie FuG Elektronik GmbH, Am Eschengrund 11, D - 83135 Schechen
File: MCA Rev_3 Englisch.docx Rev 3 3 von 16
Adhere strictly to the operating instructions before you either change switches, or connect sockets, marked with this symbol!
Symbol for high Voltage outputs
Symbol for cassis earth, potential safety earth
1. Safety Instructions
The units of the series MCA deliver dangerously High Voltages! Ensure that nothing, and nobody, will be endangered by this High Voltage before putting the unit into operation!
Attention ! The full dielectric strength of the high voltage connectors is only achieved if
fully mated together.
Before Commissioning Make sure that you have read and understood the operating instruction manual!
Ensure that you observe all the hints and warnings contained within it. In not following the operating instructions, you contravene the safety regulations for operating units of this type. FuG accepts no liability for consequences arising from the failure to follow these safety instructions.
Mains voltage Check whether the input voltage for your power supply, noted on the type label,
corresponds to your actual mains voltage.
Earth The unit is provided with a safety earth (German safety class I). For protection against
electric shocks, the unit must be connected to the mains via a suitable 3 or 5-pole cable with a non-fused earth conductor. For electrical potential equalization to the load, and to the center of the AC-supply, the earth stud must be used.
High leakage current! Labeled by a sticker on the rear. At a high leakage current is an earth connection to
the Earth stud mandatory.
Operating environment The units may only be operated in a clean, dry environment.
Please make sure that no objects or liquids can enter the casing through the ventilating apertures. Because of the risk of sparks, the unit must not be operated in the vicinity of flammable gases or fumes.
Cooling To ensure a adequate cooling, the ambient temperature must not exceed 40°C.
This unit is air cooled by convection or at units >800J/s by forced ventilation. Therefore , please ensure an adequate air-flow is available, and ensure that nothing is placed either above or below the unit which may impede this air-flow. Don’t operate table top units without the mounted legs. Do not expose the unit directly to solar radiation. If the unit is used as a plug-in component, sufficient air-flow must be provided, (1HU = 44,5 mm above and below clear).
Opening the unit Before opening, ensure that the unit is disconnected from the mains!
The unit may be opened by operating personnel only for the purpose of operating switches as described in the operating instructions, (e.g. baud rate switch of Probus V, which is inside).
Danger: The electronic boards inside the power supply are connected to one output
pole. During operation, the electronic boards lie on up to 2000V.
ATTENTION! The unit contains capacitors, which discharge only very slowly (typical
discharge time 5 min) or, in worst case, do not discharge at all.
For switch over use isolated tools only. Maintenance or repair of this unit should only be carried out by trained service
personnel who are aware of the inherent dangers of such equipment.
Symbols
MCA -Serie FuG Elektronik GmbH, Am Eschengrund 11, D - 83135 Schechen
File: MCA Rev_3 Englisch.docx Rev 3 4 von 16
2. General
The units of the series MCA (Medium Voltage Chopper Autoranging Power Supplies) are high stable DC- power supplies..
High Voltage Output ATTENTION The units supply dangerously HIGH VOLTAGE! Polarity At units up to 1500V nominal voltage the output is floating. Either the positive or the
negative output pole may be connected to earth. Units with 3000V nominal voltage will be delivered with positive or negative polarity. The polarity has been fixed in the factory and cannot be changed. One output terminal carries high voltage, the other pole „0V“ is intern connected to earth via a wire link.
Output Isolation At units up to 400V nominal voltage each output terminal may float up to max. ±500V,
Load and “0V” Terminal at 750V nominal voltage up to max ± 1000V
and at 1500V up to max. ±2000V with respect to earth.
Short-circuit Protection All units are short-circuit proof. The maximum current can be supplied for all output
voltages, even into a short-circuit.
ATTENTION! During short-circuit or flash over, the internal filter-capacitors will be discharged very fast. The output current is only limited by internal safety resistors, and can reach 500 x the nominal value.
Load Types The type of load is not critical. All passive bipolar loads can be connected. Power Limitation The maximum of supplied power is limited 750W / 1500W / 3000W. Series Connection A series connection is possible, paying attention to the stated output isolation. That
means, at a series connection of power supplies the sum voltage of both power supplies may not exceed the mentioned value.
Parallel Connection Parallel connection of power supplies with same output voltage is supported. Type Number From the type number you can see both the power class and the maximum output
voltage of the unit. Example: MCA 750 - 3 000 = Power class 750W / Nominal voltage 3 000V Modified types with differing electrical or mechanical data are indicated by "MOD"
within the type number on the label at the rear panel.
(In this case pay attention to the description in section 8) Serial Number The label on the rear of the unit, the technical manual and the circuit diagrams show
the serial number.
It has the following content:
IMPORTANT Please indicate on all further enquiries for warranty, service or spare parts
orders the serial number and the model number of the unit.
internal order number Item number Consecutive number out of this item
Serial No.:
AAAAA-PP-NN YYYY/MM
Delivery Year / Month
MCA -Serie FuG Elektronik GmbH, Am Eschengrund 11, D - 83135 Schechen
File: MCA Rev_3 Englisch.docx Rev 3 5 von 16
2.1 Setup Information
Operating position The units may only be operated in horizontal position. Class of pollution The units are designed for the pollution class 1 (normal, not conductive pollution). EMC The units are built according to current standards. When length of signal- and control
lines <3m. Transport If the power supply is equipped with lifting appliances or handles, the weight of the unit
must be shared to these points.
2.2 Preparation for commissioning
Mains Voltage Check whether the input voltage for your power supply, noted on the type label,
corresponds to your actual mains voltage. Use only the enclosed delivered mains
cable. Earth, Safety Conductor The unit is provided with a safety earth (German safety class I). For protection against
electric shocks, the unit must be connected to the mains via a cable with a non-fused
earth conductor.
For electrical potential equalization to the load, and to the center of the AC-supply, the
earth stud must be used.
High leakage current! When this sticker is placed on the rear side of the unit or the text “High leakage
current” is engraved , the unit must be grounded properly by using the appropriate
grounding bolt with a cable of at least 10 mm ² cross section.
Fuses Internal: See type label.
External: On mains side next higher size, characteristics delay-action or if
automatic cut-out is used, characteristics "C" or "K".
Return Current Flow The return current must not flow via the mains earth!
The screen of a HV-cable is always connected to earth. Only in some cases it may be
used for the return current.
Load and "0V“ Terminal At units up to 400V nominal voltage each output terminal may float up to max. ±500V,
at 750V nominal voltage up to max ± 1000V and at 1500V up to max. ±2000V with
respect to earth. Attention At units with 3000V nominal voltage one pole lies on the HV terminal, the other one on
the „0V“ terminal and is intern connected to earth by a wire link. In this operation mode
the screen of the HV-cable may be used for the return current.
Earthy Operation The link between „0V“ and earth may be disconnected by the customer.
Open the unit, you will find this wire link inside between the „0V“ and the earth
terminal. Pay attention to the safety instructions!
Attention The „0V"-terminal than is earthy and may float up to max. ±300 V. For the return
current a separate isolated line back to the „0V“ terminal has to be used, the screen of
the HV-cable in this case must not be used, it always lies on earth.
In this operation mode the „0V“ terminal is protected against overvoltage by an
overvoltage arrestor with 350 V, which must not be stressed for a longer time.
Therefore it should be put on a fixed potential between 0 and 300 V. Danger! On load side a suitable overvoltage arrestor (or earthing) must be provided to assure,
that due to a inadvertent opened 0V back connection on the power supply, the voltage
does not exceed the a.m. values with respect to earth.
Use only safety connectors according to IEC 1010-1 or VDE 0110.