FST DFX 2, DFX 4, DFX 7, DFX 9, DFX 11 Operating Instruction

...
Page 1
OPERATING INSTRUCTION
O11300G00169
Compressed Air-Dryer
DFX 2 A – DFX 85 A
Page 2
Type Code
07.2010 EN_2
Series
DFX
Type Code
Model Type no.
DFX 2 B10-230-xxx-01 1130 A DFX 4 B15-230-xxx-01 1131 A DFX 5 B15-230-xxx-01 1132 A DFX 7 B15-230-xxx-01 1133 A DFX 9 B15-230-xxx-01 1134 A DFX 11 B15-230-xxx-01 1135 A DFX 13 B25-230-xxx-01 1136 A DFX 15 B25-230-xxx-01 1137 A DFX 18 B32-230-xxx-01 1138 A DFX 23 B32-230-xxx-01 1139 A DFX 30 B32-230-xxx-01 1140 A DFX 36 B40-230-xxx-01 1141 A DFX 45 B40-230-xxx-01 1142 A DFX 55 B50-230-xxx-01 1143 A DFX 65 B50-230-xxx-01 1144 A DFX 75 B50-230-xxx-01 1145 A
Version air-cooled
DFX 85 B50-230-xxx-01 1146 A
Original instructions are in ENGLISH!
Technical modifications are subject to change without notice; errors not excluded.
FST GmbH Im Teelbruch 106 D-45219 Essen
Phone +49 (0) 2054 8735 0 Fax +49 (0) 2054 8735 100 e-mail: [email protected]
Page 3
Table of contents
EN_3 07.2010
Page Type code EN_2
Part 1 Important user information 1.1 General Notes EN_4
1.2 Legal requirements for the user EN_5
1.3 Safety regulations EN_6
1.4 Refrigerant handling EN_7
All safety notes in this operating instruction which may cause harm to personnel or equipment, when ignored, are marked by the following symbols:
General danger symbol
Electrical danger symbol
1.5 First Aid EN_8
1.6 Disposal EN_8 Part 2 Installation 2.1 Transportation EN_9
2.2 Requirements on the place of installation EN_9
2.3 Installation (Mounting) EN_9
2.4 Compressed air connection EN_10
2.5 Electric Connection EN_10
2.6 Connection condensate drain EN_11 Part 3 Description 3.1 Designation EN_12
3.2 Intended use EN_12
3.3 Unit layout EN_12
3.4 Electronic regulator EN_12
3.5 Nominal power of CA-Dryer EN_13
3.6 Principle of operation EN_13
3.7 Mode of operation EN_13
3.8 Condensate draining EN_14 Part 4 Operation 4.1 Commissioning EN_15
4.2 Starting EN_15
4.3 Operation EN_15
4.4 Stopping EN_16 Part 5 Maintenance 5.1 Maintenance EN_17
5.2 Troubleshooting EN_18
5.3 Spare parts list EN_24 Part 6 Technical data 6.1 Technical data EN_25 Part 7 Appendix legend 7.1 Appendix legend EN_26 Appendix Apx 1 Units layout
Apx 2 Spare parts view Apx 3 Wiring diagrams Apx 4 PI diagram Apx 5 Declaration EC-conformity
Page 4
Part 1 Important User Information
07.2010 EN_4
1.1 General notes
•
This compressed air-dryer is called CA-dryer in the following.
•
The Company does not accept responsibility if safety regulations are not met during handling, operation, maintenance and repair, even though these are not strictly stated in these operating instructions.
•
We recommend the notice of these operating instructions verified by the operating personnel in writing (personnel file).
•
We recommend translation of these operating instruction into native language of foreign workers.
•
The usability and the life cycle of the compressed air-dryer as well as the avoidance of premature repairs depends on proper operation, maintenance, care and competent repair under consideration of these operating instructions.
•
Hints to figures and locations are in brackets, e.g. (Fig.3/7).
•
Due to our position as suppliers of components we do not always know the final usage and total range of products’ application. We constantly improve our products to the latest state of science and technology and therefore, we assume that our product are free from defects in sense of product liability. However, it cannot be excluded that during faulty operation in critical areas of application especially at danger to life and limb of persons involved, additionally safety measures may be necessary. Therefore, we request the user of our components / units, to ensure in his own interest, to inform us about the application of our products in order to initiate additional safety measures, if necessary.
•
Keep this manual for future reference.
Page 5
Important User Information
Part 1
EN_5 07.2010
1.2 Legal requirements for the user
1.2.1 Classification EC regulation 97/23
• Due to classification into category 2 (type 1146A) according to EC-Pressure Equipment directive, the CA­Dryer are “systems to be monitored”.
1.2.2 Check of working materials
• Before starting the CA-Dryer, the user has to check the working materials and record this accordingly.
1.2.3 Periodical checks
• The user of the CA-Dryer has to find out the test periods of the complete unit and the unit parts on base of a safety related technical evaluation.
1.2.4 Instruction EN 378-1
• The user has to provide the instructions for the operators as well as their information of the used working media. A yearly instruction is mandatory.
1.2.5 Short Operating Instruction EN 378-2
• A „Short Operating Instruction“ must be prepared by the user and positioned next to the machine.
1.2.6 Documentation EN 378-4.3.1 EC regulation 842/2006
• The user is committed to create a unit record of the refrigerating plant when using more than 3 Kg refrigerant. A guideline can be provided by the service.
1.2.7 Maintenance EN 13 313
• Maintenance has to be provided by qualified personnel only.
Page 6
Part 1 Important User Information
07.2010 EN_6
1.3 Safety Regulations
Attention!
The operator has to observe the national working-, operating­and safety regulations. Also existing internal factory regulations must be met. Maintenance and repair work must only be carried out by specially trained personnel and, if necessary, under supervision of a person qualified for this work.
• Protective or safety devices must not be removed, modified or readjusted temporarily or permanently.
• User proper tools for maintenance and repair work only.
• Use original spare parts only.
Attention!
All maintenance and repair works must only be executed at stopped machine, disconnected power supply and pulled mains plug. Ensure that the CA-dryer cannot be switched on by mistake.
• Prior to dismounting a part under pressure disconnect the CA-dryer from all pressure sources and depressurize the CA­dryer.
• Do not use inflammable solvents for cleanings.
• Keep the environment absolutely clean during maintenance
and repair works. Keep free of dirt by covering the parts and free openings with clean cloth, paper or adhesive tape.
• Never weld at the pressure vessel or modify it in any way.
• Ensure that no tools, loose parts or similar are left in the
system.
• The casing of the CA-Dryer must not be stepped on.
• The CA-Dryer must not be used as deposit station.
• CA-Dryer must only be operated within the limits stated in the
nameplate.
• Condensate drain system access opening is intended to manage the drain only (display visibility and test button) : a deeper access inside the CA-Dryer may cause injuries due to refrigerant hot piping.
Page 7
Important User Information
Part 1
EN_7 07.2010
1.4 Refrigerant handling
•
Wear eye protection and protective gloves.
•
Avoid contact of liquid refrigerants with your skin (frostbite).
•
Do not inhale refrigerant vapours.
•
To avoid higher concentrations, all work rooms must be ventilated very well. The opening of windows and doors may not be sufficient, so an exhausting system must be used directly at the supply point or near the floor.
•
Do not smoke, because fire might decompose the refrigerant. The resulting substances are toxic and must not be inhaled.
•
Do not have refrigerants escaped during filling or repair work. Cover with tape.
•
Leave the room immediately and only enter after the room has been sufficiently ventilated when refrigerant concentrations (e.g. pipe line leakages) appear suddenly.
•
Execute welding and soldering works on refrigerating systems in well ventilated rooms only. Refrigerants will be decomposed in flames as well as in electrical arcs.
•
The resulting decomposition products are toxic.
•
Before welding and soldering at refrigerating systems, the refrigerant must be removed.
•
A stinking smell points to decomposition of refrigerant due to overheating:
- leave room immediately;
- ventilate room very well.
1.4.1 Refrigerant charging and discharging
•
refrigerant charging and discharging operations shall be made by qualified personnel only.
•
Do not throw out refrigerant in the environment during discharge operation. Use proper refrigerant recovery system.
•
In case of refrigerant charging requirement, use only refrigerant type and quantity as indicated in the CA-Dryer nameplate.
1.4.2 Refrigerant characteristics
Refrigerant Chemical formula TLV GWP
R134a – HFC CH2FCF3 1000 ppm 1300
R407C – HFC
R32/125/134a (23/25/52)
CHF2CF3/CH2F2/CH2FCF3
1000 ppm 1653
Page 8
Part 1 Important User Information
07.2010 EN_8
1.5 First aid
1.5.1 General notes:
•
Immediately bring casualty into the fresh air or into a well ventilated room.
•
Assistants must pay attention to self-protection!
•
Take off contaminated clothes.
•
Never leave the casualty unattended!
•
CALL THE DOCTOR and inform him that accident has been caused by refrigerants, as to be read on the name plate!
1.5.2
After inhaling:
•
Bring casualty into the fresh air, keep him warm, and let him relax.
•
At breathlessness: Oxygene therapie
•
At apnoea: Resuscitation
•
Mouth-to-nose resuscitation, mouth-to-mouth resuscitation or with equipment.
•
Medical treatment necessary
1.5.3
After skin contact:
•
At skin contact, clean with water and soap immediately.
•
After contact with the fluid, undercooled skin areas must be cooled with warm (not hot) water.
1.5.4
After eye contact:
•
Flush well opened eye with running water for at least 10 minutes.
•
Contact doctor.
1.5.5
Notes for the doctor:
•
Inform doctor about the used refrigerant.
•
After inhalation, deep breathing of a corticoid emulsive dosing aerosol (e.g. Ventolair) as soon as possible.
•
Prohobition of using adrenergic drugs.
•
Prophylactic pulmonary edema after inhalation of decomposition products / fire gases
1.6 Disposal
•
When disposing of used devices, pay attention to oil and refrigerant in the hermetical sealed refrigerating circuit of CA-dryers. Therefore, before dismounting, these operation media must be disposed by a special company.
•
The used materials are listed on the recycling label inside the CA-dryer.
Attention!
Do not dispose waste oil into the environment. Do not mix with household rubbish and do not burn it unauthorized plants.
• The escape of refrigerant into the atmosphere must be prevented by appropriate measures.
Page 9
Installation
Part 2
EN_9 07.2010
2.1 Transportation Transportation has to be carried out in the normal operating
position of the CA-dryer. For a short time an inclined position of 45° is allowed. Handle with care. Heavy blows could cause irreparable damage.
2.2 Requirements on the place of installation
At the site of installation, the CA-dryer can be installed without anchorage or special foundation at the location desired. The CA-dryer is provided for an ambient temperature of 25 °C.
Attention!
To avoid corrosion on components of the CA-dryer the compressed and ambient air must be free of aggressive parts. The CA-dryer are provided for inside mounting. Deviating conditions require the consultation of the manufacturer.
To prevent the condensate from freezing the room temperature must not drop below +2 °C.
Attention!
At different ambient conditions pay attention to the layout data!
2.3 Installation (mounting)
The CA-dryer must be installed that accessibility to the front panel is ensured. Furthermore leave space for service purposes on both sides of the CA-dryer (fig.2.3a).
Wall mounting is possible with types 1130A-1137A (fig.2.3b).
Fig.
2.3a
Installation of CA-dryer
Page 10
Part 2 Installation
07.2010 EN_10
Fig.
2.3b
Preparation wall mounting
2.3.1 Version air cooled The cooling air is sucked in by the refrigerant condenser (Apx
1/3) and discharged at the right side (Apx 1/4). Both areas must be kept free and must non be obstructed.
2.4 Compressed air connection
The connection must be executed acc. to marking at the CA­dryer (Apx 1/1 + 1/2). For service purposes the installation of a bypass line in recommended (additional equipment).
Attention!
Before mounting the CA-dryer, welding residual, rust or other pollution must be removed from the pipelines to be connected. If pollution cannot be excluded, proper filter system must be installed. The compressed air pipes must be installed stress-free. Expansion joints are recommended in case of vibrations and pulsations. CA-dryer must only be operated within the temperature and pressure limits stated on the nameplate. Prior to use, the user must fit safety / pressure relief devices on the CA-system.
2.5 Electric connection The CA-dryers are completely equipped and wired. They
merely have to be connected to a power supply. The CA-dryer are to be protected by slow-blow fuses as defined in the wiring diagram. Operating voltage: according to name plate data.
Page 11
Installation
Part 2
EN_11 07.2010
2.6 Connection condensate drain
A hose already pre-mounted at the condensate drain leads the condensate out of the CA-dryer (Apx 1/5). A connection by the costumer has to be carried out corresponding to the local conditions.
The CA-dryers separates water as well as oil from the compressed air. The water/oil mixture must not be led into the sewage. Water and oil must be separated by suitable separators (additional equipment).
A minimum operating pressure of 2 bar is required for safe operation.
Attention!
Route outflow so that persons or objects will not be struck by condensate (condensate outlet at operating pressure)!
2.6.1 Connection condensate draining
The condensate drain pipe (fig.2.6/1) may be fixed to the wall with a rising slope of maximum 5m. thereby the minimum operating pressure increases for 0,1 bar per meter. The collecting pipe (fig.2.6/2) has to have at least the cross-section of the condensate outlet.
Fig.
2.6
Connection condensate draining
Page 12
Part 3 Description
07.2010 EN_12
3.1 Designation
Refrigerating compressed air-dryer (CA-dryer). Version see type code (page 2).
3.2 Intended use Only compressed air will be dehumidified by the CA-dryer.
3.3 Unit Layout
See Appendix Apx 1 for CA-dryer components which are accessible from outside.
Compressed air inlet
Compressed air outlet
Before maintenance works are to be executed at the CA­dryer, the unit must be disconnected from the power supply.
Risk of injury if the CA-dryer is not disconnected from the power supply because of a freely rotating fan blade.
The refrigerant compressor of the refrigeration system heats up during operation, so a risk of burn injuries is given at maintenance works
3.3.1 Symbols
Condensate drain
3.4 Electronic regulator
The electronic regulator DDS5 is a controller specially designed for CA-dryers. It operates on the basis of the micro processors and performs three functions:
- Pressure dew point display
- Pressure dew point alarm
- Refrigerant condenser fan control (1130A-1138A)
P
Q
S
0
0
3
4
_
1
set
ON
7 1 8
5
6
4
3
2
1 10x Led green : Pressure dew point indication 2 Green area : Pressure dew point normal 3 Red area : Pressure dew point high 4 Led green : CA-dryer on 5 Led red : Alarm active (flashing) 6 Led yellow : refrigerant condenser fan on (1130A-1138A) 7 Set key
Fig.
3.4
Symbols electronic regulator
8 Up key
Page 13
Description
Part 3
EN_13 07.2010
3.5 Nominal power of CA-dryer
The nominal power of the CA-dryer mentioned in the technical data is related to a working pressure of 7 bar, a compressed air inlet temperature of 35 °C as well as an ambient te mperature of 25 °C acc. to ISO 7183. Lower working pressure, higher compressed air inlet temperature and/or higher ambient temperatures overload the compressor which causes to an increased pressure dewpoint and the compressor can be stopped by internal safety devices. At essentially deviating operating conditions, contact the deliverer of the CA-dryer for support.
3.6 Principle of operation
The CA-dryer includes a refrigerant system cooling the compressed air flow. The steam saturation limit is lowered causing condensate to fall out, which is removed by the condensate drain. The higher the cooling temperature difference of the compressed air, the higher the amount of condensate. The lower the cooling temperature of compressed air, the lower the moisture content. The lower limit of the compressed air cooling results from the working principle of the CA-dryer, which is based on the moisture separation in liquid form.
3.7 Mode of operation
3.7.1 Compressed air side
The compressed air precooled in the Aftercooler and saturated with moisture enters into the CA-dryer and is precooled in the first cooling stage, the air-to-air heat exchanger without additional energy. Cooling is carried out in counter flow to the already cooled air heated during this process. The cooling to the pressure dew point is performed in the second cooling stage, the refrigerant-to-air heat exchanger cooled by the refrigerant system installed. Subsequently, the cooled compressed air is reheated in the air-to-air heat exchanger as already described.
3.7.2 Refrigerant side The refrigerant is injected into the refrigerant-to-air heat
exchanger where it evaporates, thereby the compressed air is cooled. The hot gas by-pass valve regulates the cooling temperature and keeps the pressure dew point constant in nearly all capacity stages. The refrigerant compressed by the motor compressor is condensed within the condenser and is available for the evaporation again.
3.7.3 Pressure dew point control
Any compressed air dryer can be operated under partial load due to lower compressed air flow or lower compressed air inlet temperature in the range of 0 to 100% load in permanent operation.
Page 14
Part 3 Description
07.2010 EN_14
3.8 Condensate draining
The condensate drain (fig.3.8a) automatically drains the condensate. A minimum pressure of 2 bar is required for safe operation.
3.8.1 Condensate drain sensor-controlled
Once the container has filled with condensate, so that the capacitive level sensor emits a signal, the internal solenoid valve opens and the condensate is forced by the working pressure into the discharge pipe. The condensate drain electronic system ensures the closing of the outlet opening before any compressed air can escape.
Fig.
3.8a
Condensate drain General
Fig.
3.8b
Condensate drain Operation panel
Type 1130A-1144A
The power LED is lit up green when operating voltage is being applied.
- Ready for operation. Power On If the condensate discharge is not functioning properly, the valve will keep opening (about every 2 seconds) so as to clear the fault automatically, if possible.
- Test valve function (manual drainage). Press button for approx. 2 seconds. In response to longer pressing, the valve will keep opening. Do not use this function for continuous draining!
Type 1145A-1146A The operating states are indicated by two LED’s.
- Ready for operation. Power on.
- Malfunction / Alarm.
- Test of valve function and manual drainage: briefly press button.
- Press button for >1 minute to test the alarm function.
Page 15
Operation
Part 4
EN_15 07.2010
4.1 Commissioning
After installation the CA-dryer is supplied with power via the power cable or by operating the main switch (Apx 1/6).
Attention!
Before operating the operation switch (Apx 1/6), a waiting period of at least 6 hours is absolutely necessary.
4.2 Starting
The CA-dryer is switched on via operation switch (Apx 1/6). After approx. 5 minutes the compressed air admission is possible by connecting the compressed air compressor. The CA-dryer is designed for continuous operation and may remain switched on during periods of no load, as it adapts to the required performance automatically.
4.3 Operation Operation is indicated by the led “ON” of the electronic regulator (fig.4.3/4) The pressure dew point indication (fig.4.3/1) is showing the pressure dew point reached by the CA-dryer.
P
Q
S
0
0
3
4
_
1
set
ON
7
1
8
5
6
432
4.3.1
Electronic regulator
- Changing factory setting Fig.4.3
1. Press SET key (7) for 2 seconds to change from display into setup mode.
2. First data is ALARMON, shortly press SET key (7
) to go to
data FANON, shortly press SET key (7) to return to data ALARMON.
3. In order to adjust actual data, keep pressed SET key (7) and press UP key (8).
4. During the setup, led flashing will identify which data is displayed :
- led ON (4) and ALARM (5) flashing = ALARMON data
- led ON (4) and FAN (6) flashing = FANON data
5. Setup exit is automatic after 2 minutes or by pressing UP key (8).
Page 16
Part 4 Operation
07.2010 EN_16
4.3.2
Electronic regulator
- Data range
ALARMON RT1 temperature too high setpoint (ALARMON) is adjustable in the range +2 … 20 °C (factory setting 18°C), resolution 2°K, hysteresis -2°K. (ie : ALARMON = 18°C; Alarm is active with RT1 temperature ≥18°C for at least 5 minutes; Alarm condition resets immediately with RT1 temperature <16°C).
FANON RT2 temperature fan setpoint (FANON) is adjustable in the range +31 … 40 °C (factory setting 35°C), resolution 1 °K, hysteresis -5°K. (ie : FANON = 35°C; Fan start running with RT2 temperature ≥35°C; Fan stop running with RT2 temperature <30°C).
4.4 Stopping At standstill periods, the CA-dryer is switched off with the operation switch (Apx 1/6). For longer standstill periods or service works, the CA-dryer is switched off by pulling the power plug (Apx 1/8).
Page 17
Maintenance
Part 5
EN_17 07.2010
5.1 Maintenance
Attention!
Prior to any maintenance works all safety regulations for electrical systems and units must be observed (see also part 1).
Maintenance intervals highly depend on the model of operation and the ambient conditions on site, the intervals below are only to be understood as general recommendations.
5.1.1 Daily maintenance a) Check function of condensate drain.
Check, if water is drained. Test valve function (manual drainage): Press button for approx. 2 seconds. In response to longer pressing, the valve will keep opening. Do not use this function for continuous draining!
b) Monitor pressure dew point (fig.3.4/1). In case of
differences to normal operation (see 5.2.2, 5.2.3).
c) Verify the refrigerant condenser for cleanliness.
5.1.2 Weekly
maintenance
Inspection and cleaning of condensate draining system if necessary.
5.1.3 Yearly maintenance Condensate drain: replace service unit. For further information see separate drain instruction.
Leak tightness check : CA-Dryers mentioned in this manual have refrigerant charge ≤30 kg (refrigerant quantity as stated in the nameplate) : the maximum allowed leak rate of 2 % must not be exceeded.
5.1.4 Periodic checks at
pressure vessels
CA-Dryer type 1146A is included into the pressure vessel guideline category II, fluid group 2 and has a maximum pressure of 14 bar. Periodic checks must be done according to National legislations and the determinations of the user.
Attention!
Maintenance work must be performed at the depressurized condensate drain only. For this purpose, the installation of a bypass line is recommended.
Page 18
Part 5 Maintenance
07.2010 EN_18
5.2 Trouble shooting Symptom
Cause ⇒⇒⇒⇒ Remedy
5.2.1 No Function 1. Check and ensure power supply if necessary.
2. If the power supply is ok, contact service or send CA-dryer to the manufacturer.
5.2.2 Pressure dew point
too high
1. Temporary overload of the CA-dryer due to non-uniform compressed air consumption ⇒⇒⇒⇒ check CA-dryer’s capacity
(see 3.4).
2. Ambient temperature too high or the room aeration is insufficient ⇒⇒⇒⇒ reduce temperature and/or provide proper ventilation.
3. CA-dryer volume flow too high ⇒⇒⇒⇒ reduce volume flow; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
4. RT1 dew point sensor doesn’t detect the temperature properly ⇒⇒⇒⇒ ensure the sensor is pushed into the bottom of probe well or RT1 dew point sensor need to be replaced.
5. Refrigerant condenser fan is never running ⇒⇒⇒⇒ see 5.2.6.
6. Refrigerant condenser is polluted ⇒⇒⇒⇒ clean condenser.
7. Hot gas by-pass valve is out of setting ⇒⇒⇒⇒ contact service.
8. Leak in the refrigerating fluid circuit ⇒⇒⇒⇒ contact service.
5.2.3 Pressure dew point
too low
1. Ambient temperature is too low ⇒⇒⇒⇒ restore normal condition.
2. (type 1130A-1138A) Refrigerant condenser fan is always on and electronic regulator’s FAN led is flashing ⇒⇒⇒⇒ see
5.2.11.2.
3. (type 1139A-1146A) Refrigerant condenser fan is always on
⇒
⇒⇒
⇒ Fan control pressure switch SPV is defective ⇒⇒⇒⇒ contact
service.
4. Switch off CA-dryer and maintain compressed air flow. After approx. half an hour, the pressure dew point will return to normal value. Restart the unit. If the pressure dew point decrease again contact service.
5.2.4 Water in compressed air system
1. Condensate drain is not drained sufficiently ⇒⇒⇒⇒ see 5.2.12.
2. CA-operating pressure too low ⇒⇒⇒⇒ increase operating pressure; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
3. Temporary overload of the CA-dryer due to non-uniform compressed air consumption ⇒⇒⇒⇒ check CA-dryer’s capacity
(see 3.4).
4. CA-dryer volume flow too high ⇒⇒⇒⇒ reduce volume flow; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
5. CA-inlet temperature too high ⇒⇒⇒⇒ restore normal conditions.
6. (Only with installed bypass line) Bypass valve is open ⇒⇒⇒⇒ close bypass valve.
7. (Only with installed bypass line) Bypass valve is leaking
⇒
⇒⇒
⇒ seal or replace bypass valve.
Page 19
Maintenance
Part 5
EN_19 07.2010
5.2.5 Stopping CA-dryer during operation
1. Compressor’s internal overload protection (klixon) is tripped
⇒
⇒⇒
⇒ eliminate cause of trouble (see 3.4) or contact service.
CA-dryer will restart automatically after compressor has cooled down.
Note: the immediate restarting of the unit is not possible because the compressor’s overload protection requires a minimum time to cool down to an acceptable operating temperature.
2. Compressor or starting device is defective ⇒⇒⇒⇒ contact service.
3. CA-dryer volume flow too high ⇒⇒⇒⇒ reduce volume flow; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
4. CA-inlet temperature too high ⇒⇒⇒⇒ restore normal conditions.
5. Ambient temperature too high or the room aeration is insufficient ⇒⇒⇒⇒ Reduce temperature or provide proper ventilation.
6. Refrigerant condenser fan is never running ⇒⇒⇒⇒ see 5.2.6.
7. Refrigerant condenser is polluted ⇒⇒⇒⇒ clean condenser.
8. CA-operating pressure too low ⇒⇒⇒⇒ increase operating pressure; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
9. (type 1142A-1146A) Safety thermo-switch FTS is tripped ⇒⇒⇒⇒ see 5.2.8.
10. (type 1143A-1146A) Safety high pressure-switch FPA is tripped ⇒⇒⇒⇒ see 5.2.9.
5.2.6 Refrigerant condenser fan is never running
1. Check and ensure electric wiring.
2. Fan’s internal overload protection is tripped ⇒⇒⇒⇒ eliminate cause of trouble (see 3.4) or contact service. Fan will restart automatically after it has cooled down.
3. (type 1130A-1138A) Electronic regulator is defective ⇒⇒⇒⇒ contact service.
4. (type 1139A-1146A) Fan control pressure switch SPV is defective ⇒⇒⇒⇒ contact service.
5. Leak in the refrigerating fluid circuit ⇒⇒⇒⇒ contact service.
5.2.7 High differential
pressure at CA-side
1. CA-dryer volume flow too high ⇒⇒⇒⇒ reduce volume flow; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
2. CA-operating pressure too low ⇒⇒⇒⇒ increase operating pressure; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly
selected, increase CA-dryer’s capacity.
3. Pressure dew point too low ⇒⇒⇒⇒ see 5.2.3.
4. Condensate drain is not drained sufficiently ⇒⇒⇒⇒ see 5.2.12.
5. Heat exchanger polluted ⇒⇒⇒⇒ contact service.
Page 20
Part 5 Maintenance
07.2010 EN_20
5.2.8
Safety thermo-switch FTS is tripped (type 1142A-1146A)
1. CA-dryer volume flow too high ⇒⇒⇒⇒ reduce volume flow; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
2. CA-inlet temperature too high ⇒⇒⇒⇒ restore normal conditions.
3. Ambient temperature too high or the room aeration is insufficient ⇒⇒⇒⇒ reduce temperature and/or provide proper ventilation.
4. Refrigerant condenser fan is never running ⇒⇒⇒⇒ see 5.2.6.
5. Refrigerant condenser is polluted ⇒⇒⇒⇒ clean condenser.
6. CA-operating pressure too low ⇒⇒⇒⇒ increase operating pressure; ⇒⇒⇒⇒ check whether CA-dryer’s capacity is properly selected, increase CA-dryer’s capacity.
7. Leak in the refrigerating fluid circuit ⇒⇒⇒⇒ contact service.
8. Safety thermo-switch FTS is defective ⇒⇒⇒⇒ contact service.
Note: Safety thermo-switch FTS require a reset : press reset button (fig.5.2.8).
Fig.
5.2.8
Safety thermo-switch FTS reset button
Page 21
Maintenance
Part 5
EN_21 07.2010
5.2.9 Safety high pressure-switch FPA is tripped (type 1143A­1146A)
1. Ambient temperature too high or the room aeration is insufficient ⇒⇒⇒⇒ reduce temperature and/or provide proper ventilation.
2. Refrigerant condenser fan is never running ⇒⇒⇒⇒ see 5.2.6.
3. Refrigerant condenser is polluted ⇒⇒⇒⇒ clean condenser.
Note: Safety high pressure-switch FPA require a reset : press reset button (fig.5.2.9).
Fig.
5.2.9
Safety high pressure-switch FPA reset button
Page 22
Part 5 Maintenance
07.2010 EN_22
5.2.11
Electronic regulator DDS5
Symptom
Cause ⇒⇒⇒⇒ Remedy
5.2.11.1
Alarm led and display 1st (left) and 10th (right) led are flashing
P
Q
S
0
0
3
4
_
2
set
ON
RT1 dew point sensor is defective ⇒⇒⇒⇒ replace it.
5.2.11.2
Alarm led and Fan led are flashing
(type 1130A-1138A)
P
Q
S
0
0
3
4
_
3
set
ON
RT2 fan control sensor is defective ⇒⇒⇒⇒ replace it.
Note: refrigerant condenser fan is always running.
5.2.11.3
Alarm led is flashing and display led is lighted
P
Q
S
0
0
3
4
_
4
set
ON
Pressure dew point alarm (higher than ALARMON setpoint ⇒⇒⇒⇒ see 5.2.2 and 4.3.
Note: alarm become active 5 minutes later with dewpoint temperature continuously higher than ALARMON setpoint
5.2.11.4
Alarm led and display 1st (left) led are flashing
set
P
Q
S
0
0
3
4
_
5
ON
Pressure dew point too low (lower than -1°C) ⇒⇒⇒⇒ see 5.2.3.
5.2.11.5
Display 10th (right) led is flashing
set
P
Q
S
0
0
3
4
_
6
ON
Pressure dew point too high (higher than 24°C) ⇒⇒⇒⇒ see 5.2.2.
Note: Alarm led could be lighted or not (alarm become active 5 minutes later with dewpoint temperature continuously higher than ALARMON setpoint)
Page 23
Maintenance
Part 5
EN_23 07.2010
5.2.12 Condensate drain
Symptom
Cause ⇒⇒⇒⇒ Remedy
5.2.12.1
LED not lighting up
Power supply faulty. Power supply board defective.
- Check voltage on type plate.
- Check connections.
- Check of the circuit boards for possible damage to be carried
out by qualified personnel only.
5.2.12.2
Pressing of test button, but no condensate discharge
Feed and / or outlet line shut off or blocked. Worn parts (seals, valve core, diaphragm). Power supply board defective. Service unit defective. Dropping below necessary minimum pressure. Maximum pressure exceeded.
- Check feed line and outlet line
- Check if valve opens audibly (press test button several times).
- Check of the circuit board for possible damage to be carried
out by qualified personnel only.
- Check operating pressure.
5.2.12.3
Condensate discharge only when test button is being pressed
Feed line with insufficient slope; cross-section too small. Excessive condensate quantities. Service unit extremely dirty.
- Lay feed line with adequate slope
- Replace service unit.
5.2.12.4
Device keeps blowing off air
Service unit defective or dirty.
- Replace service unit.
Page 24
Part 5 Maintenance
07.2010 EN_24
Page 25
Technical Data
Part 6
EN_25 07.2010
Page 26
Part 7 Legend Appendix
07.2010 EN_26
APX 1
1 2 3 4 5
Compressed air inlet Compressed air outlet Cooling air inlet Cooling air outlet Condensate drain
6 7
8 E100 EICA
Electric connection Service access Fixing holes Operation switch Electronic regulator
APX 2 & APX 4
W100 W10L
W10K
B100
W110 TSAH PSAH
PS00 V100
V400 W200 M200 M201 M203
F100
X500
EIC3
Heat exchanger complete Heat exchanger air/air Heat exchanger refrigerant/air Condensate separator Heat exchanger insulation shell Safety thermo-switch Refrigerant high pres.-switch Refrigerant pres.-switch Fan Refrigerant compressor Hot gas by-pass regulator Refrigerant condenser Fan (motor) Fan blade Fan grid Filter drier Capillary tube DewPoint sensor
EIC4 V710 EICA A100 E100
51 52 53 54 55 56 58 60 66
81 A160 X100
Fan sensor Condensate drain service valve Electronic regulator Condensate drain – complete Main switch Front panel Rear panel Right lateral panel Left lateral panel Cover panel Base plate Support beam Control panel Cover control panel Flow diagram sticker Condensate drain – service unit Schrader valve
APX 3
S1
K
KT KR CS CR
V KV CV
Main switch Refrigerant compressor Compressor thermal protection Compressor starting relay Compressor starting capacitor Compressor run capacitor Condenser fan Fan thermal protection Fan starting capacitor
TSAH
PSAH
PS00
A2 EIC3 EIC4
B1
Safety thermo-switch Refrigerant high pres.-switch Refrigerant pres.-switch Fan DDS Electronic regulator DewPoint sensor Fan sensor Condensate drainer
Page 27
APPENDIX
Page 28
07.2010
Apx 1.1 1130 A – 1137 A
Apx 1.2 1138 A – 1142 A
Page 29
07.2010
Apx 1.3 1143 A – 1145 A
Apx 1.4 1146 A
Page 30
07.2010
Apx 2.1 1130 A
Apx 2.2 1131 A – 1132 A
Page 31
07.2010
Apx 2.3 1133 A – 1137 A
Apx 2.4 1138 A
Page 32
07.2010
Apx 2.5 1139 A – 1141 A
Apx 2.6 1142 A
Page 33
07.2010
Apx 2.7 1143 A – 1145 A
Apx 2.8 1146 A
Page 34
Page 35
Page 36
Page 37
Page 38
Page 39
EG-Konformitätserklärung
EC declaration of conformity
Déclaration “CE” de conformité
EG-verklaring van overeenstemming
EU-konformitetsforklaring
FSN002003 Rev.03
DE - EN - FR
NL - DA
Hiermit enklären wir, dass die: Kälte-Drucklufttrockner Herewith we declare that: Compressed air refrigeration dryer Par la présente, nous déclarons, que la type de: Sécheur par réfrigération Hiermde verklaren wij, dat de handel gebrachte machine: Perslucht koeldrogers Hermed erklæres at produkttypen: Trykluft-køletørrer
Baureihe / Series / Série / Serie Typ / Type Artikel-Nr.:/Serial-No.:/ 97/23/EG – Kat. / Cat. No Série/Serienummer:
DFX2 B10-230-xxx-01 1130A 1C Y 1130 B 0x 00 9 Art. 3 (3) DFX4 B15-230-xxx-01 1131A 1C Y 1131 B 0x 00 9 Art. 3 (3) DFX5 B15-230-xxx-01 1132A 1C Y 1132 B 0x 00 9 Art. 3 (3) DFX7 B15-230-xxx-01 1133A 1C Y 1133 B 0x 00 9 Art. 3 (3) DFX9 B15-230-xxx-01 1134A 1C Y 1134 B 0x 00 9 Art. 3 (3) DFX11 B15-230-xxx-01 1135A 1C Y 1135 B 0x 00 9 Art. 3 (3) DFX13 B25-230-xxx-01 1136A 1C Y 1136 B 0x 00 9 Art. 3 (3) DFX15 B25-230-xxx-01 1137A 1C Y 1137 B 0x 00 9 Art. 3 (3) DFX18 B32-230-xxx-01 1138A 1C Y 1138 B 0x 00 7 Art. 3 (3) DFX23 B32-230-xxx-01 1139A 1C Y 1139 B 0x 00 7 Art. 3 (3) DFX30 B32-230-xxx-01 1140A 1C Y 1140 B 0x 00 7 Art. 3 (3) DFX36 B40-230-xxx-01 1141A 1C Y 1141 B 0x 00 7 I DFX45 B40-230-xxx-01 1142A 1C Y 1142 B 0x 00 7 I DFX55 B50-230-xxx-01 1143A 1C Y 1143 B 0x 00 7 I DFX65 B50-230-xxx-01 1144A 1C Y 1144 B 0x 00 7 I DFX75 B50-230-xxx-01 1145A 1C Y 1145 B 0x 00 7 I DFX85 B50-230-xxx-01 1146A 1C Y 1146 B 0x 00 7 II
folgenden weiteren Richtlinien entspricht: 97/23/EG conform with the following directives: 2004/108/EG correspond aux disposition suivantes: 2006/95/EG komt overeen met de volgende verdere richtlijnen: 2006/42/EG videre retningslinier som anvendtes:
Angewendete harmonisierte Normen, insbesondere: ASME VIII Div.1 ; EN378-2 ; EN953 ; Applied harmonized standards in particular: EN954-1 ; EN1050 EN1088 ; Normes harmonisée utilisées, notamment: EN10028-3 ; EN12100-1 ; Gebruike geharmoniseerde normen, in het bijzonder: EN12100-2 ; EN12451 ; EN50081-2 ; Harmoniserade normen som anvendtes, i særdeleshed: EN50082-2 ; EN60204-1
Referenz Qualität Dokument: Fd – FSN002002 Rev.01 Reference quality document: Référence Document de qualité: Referentie kwaliteit document: Reference kvalitet dokument:
Essen, 15.07.2010
Datum / Date / Datum / Dato Underschrift / Signature / Handtekening / Underskrift
(Bevollmächtigter / Authorized person / Fondé de pouvoir / Gevolmagtiegde / Fuldmægtig)
FST GmbH
Im Teelbruch 106, D-45219 Essen
Page 40
Loading...