FSP Technology FSP552PV-230H-48, HySpirit 5.5k User Manual

FSP HySpirit series User Manual www.fsp-group.com.tw
FSP HySpirit 5.5k
FSP552PV-230H-48
PVInverter User Manual
Version: 1.0
FSP HySpirit series User Manual www.fsp-group.com.tw
Table of Contents
1. Introduction ....................................................................................... 1
2. Important Safety Warning .................................................................. 2
3. Unpacking & Overview ....................................................................... 4
4. Installation .......................................................................................... 5
5. Surge Protection Device Installation .................................................. 6
6. Grid (Utility) Connection .................................................................... 8
7. PV Module (DC) Connection .............................................................. 8
8. Battery Connection .......................................................................... 11
9. Load (AC Output) Connection .......................................................... 12
10. Communication ................................................................................ 14
11. Application with Energy Meter ........................................................ 15
12. Commissioning ................................................................................. 16
13. Initial Setup ...................................................................................... 17
14. Operation ......................................................................................... 27
15. Charging Management ..................................................................... 38
16. Maintenance & Cleaning .................................................................. 40
17. Trouble Shooting .............................................................................. 41
18. Specifications..................................................................................... 44
FSP HySpirit series User Manual 1 http://www.fsp-group.com.tw/en/product/PVInverter.html
1. Introduction
This hybrid PV inverter can provide power to connected loads by utilizing PV power, utility power and battery power.
Figure 1 Basic hybrid PV System Overview
Depending on different power situations, this hybrid inverter is designed to generate continuous power from PV solar modules (solar panels), battery, and the utility. When MPP input voltage of PV modules is within acceptable range (see specification for the details), this inverter is able to generate power to feed the grid (utility) and charge battery. This inverter is only compatible with PV module types of single crystalline and poly crystalline. Do not connect any PV array types other than these two types of PV modules to the inverter. Do not connect the positive or negative terminal of the solar panel to the ground. See Figure 1 for a simple diagram of a typical solar system with this hybrid inverter.
Note: To conform to the EEG standard, every inverter sold to German area is not allowed to charge battery from Utility. The relevant function is automatically disabled via the software.
Hybrid inverter
PV module
Battery
Load
Distribution
Electric grids
FSP HySpirit series User Manual 2 http://www.fsp-group.com.tw/en/product/PVInverter.html
2. Important Safety Warning
Before using the inverter, please read all instructions and cautionary markings on the unit and this manual. Store the manual where it can be accessed easily.
This manual is for qualified personnel. The tasks described in this manual may be performed by qualified personnel only.
General Precaution-
WARNING! Before installing and using this inverter, read all instructions and cautionary markings on
the inverter and all appropriate sections of this guide.
WARNING! Normally grounded conductors may be ungrounded and energized when a ground fault is indicated.
WARNING! This inverter is so heavy that it should be lifted by at least two persons.
CAUTION! Before attempting any maintenance or cleaning or working on any circuits connected to
the inverter, disconnecting AC, DC and battery power from the inverter can reduce the risk of electric shock. Merely turning off controls will not reduce this risk because internal capacitors can remain charged for 5 minutes after disconnecting all sources of power.
CAUTION! Do not disassemble this inverter by yourself. It contains no user-serviceable parts. Attempt to service this inverter by yourself may cause electric shock or fire and will void the warranty from the manufacturer.
CAUTION! To avoid fire and electric shock, make sure that existing wiring is in good condition and that the wire is not undersized. Do not operate the damaged Inverter or substandard wiring.
Conventions used: WARNING! Warnings identify conditions or practices that could result in personal injury; CAUTION! Caution identify conditions or practices that could result in damage to the unit
or other equipment connected.
FSP HySpirit series User Manual 3 http://www.fsp-group.com.tw/en/product/PVInverter.html
CAUTION! In high temperature environment, the surface of this inverter could be hot enough to cause skin burns if accidentally touched. Ensure that this inverter is away from normal traffic areas.
CAUTION! Use only recommended accessories from installer. Otherwise, disqualified tools may cause fire, electric shock, or injury to persons.
CAUTION! To reduce risk of fire hazard, do not cover or obstruct the cooling fan.
CAUTION! Do not operate the Inverter if it has undergone a sharp blow, been dropped, or damaged
in any way. If the Inverter is damaged, please call for an RMA (Return Material Authorization) request.
CAUTION! AC breaker, DC switch and Battery circuit breaker are used as disconnect devices and these disconnect devices shall be easily accessible.
Symbols used in Equipment Markings
Refer to the operating instructions
Caution! Risk of danger
Caution! Risk of electric shock
Caution! Risk of electric shock. Energy storage timed discharge for 5 minutes.
Caution! Hot surface
Before working on this circuit
- Isolate inverter/Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all terminals including the
protective earth.
Risk of Voltage Backfeed
FSP HySpirit series User Manual 4 http://www.fsp-group.com.tw/en/product/PVInverter.html
3. Unpacking & Overview
3-1. Packing List
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should receive the following items inside of package:
Inverter unit PV connectors Software CD Manual USB cable RS-232 cable
Mounting
Surge protection device L-type plate Screws Magnets Cables screws
3-2. Product Overview
1) PV connectors
2) AC output connectors (Load connection)
3) Battery connectors
4) AC Grid connectors (Connect to SPD)
5) RS-232 communication port
6) USB communication port
7) Intelligent slot
8) DC Switch (option)
9) LCD display panel
10) LED indicators
11) Operation buttons
(Please check section 14 for details about LCD display, LED indicators and button operation)
FSP HySpirit series User Manual 5 http://www.fsp-group.com.tw/en/product/PVInverter.html
4. Installation
4-1. Selecting Mounting Location
Consider the following points to install the inverter:
Do not mount the inverter on flammable construction materials. Mount on a solid surface This inverter might make noises during operation which may be perceived as a nuisance in
a living area.
Install this inverter at eye level in order to allow the readability of LCD display at all times. For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side
and approx. 50 cm above and below the unit.
Dusty conditions on the unit may impair the performance of this inverter. The ambient temperature should be between 0°C and 40°C and relative humidity should
be between 5% and 85% to ensure optimal operation.
The recommended installation is vertical adherence. For proper operation of this inverter, please use appropriate cables for grid connection. The pollution degree of the inverter is PD2. Select an appropriate mounting location.
Install the solar inverter in a protected area that is dry, free of excessive dust and with adequate air flow. Do NOT operate it in the place where the temperature and humidity is beyond the specific limits. (Please check the specs for the limitations.)
The inverter should be installed in the position where the disconnection means is easily
accessible.
This inverter is designed with IP20 protection for indoor applications only. Regularly clean the fan filter.
4-2. Mounting Unit
Installation to the wall should be fixed with proper screws. After that, the device should be bolted on securely.
The inverter can only operate in a CLOSED ELECTRICAL OPERATING AREA. Only service personnel can enter this area.
Fix the unit with four screws.
WARNING!! Remember that this inverter is heavy so please be careful when removing it from the package.
WARNING!! FIRE HAZARD. SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
FSP HySpirit series User Manual 6 http://www.fsp-group.com.tw/en/product/PVInverter.html
5. Surge Protection Device Installation
CAUTION: Be sure to disconnect from AC power before installing surge protection device. Step 1: Install the SPD on the left hand side of the inverter with six magnets.
Step 2: To prevent surge protection device falling apart, use supplied L-type plate and fix it to
attach surge protection device tightly to the inverter.
Magnet x 6 pieces
FSP HySpirit series User Manual 7 http://www.fsp-group.com.tw/en/product/PVInverter.html
Step 3: Connect the OUTPUT of SPD to AC grid connectors of Hybrid Inverter. The INPUT of SPD is connected to AC utility.
Hybrid Inverter
Output of
SPD
AC Grid Input
FSP HySpirit series User Manual 8 http://www.fsp-group.com.tw/en/product/PVInverter.html
6. Grid (Utility) Connection
6-1. Preparation
Before connecting to AC utility, please install a separate AC circuit breaker between surge protection device (SPD) and AC utility. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input.
NOTE1: Although this inverter is equipped with 250Vac/40A fuse, it’s still necessary to install a separate circuit breaker for safety consideration. Please use 250Vac/40A circuit breaker between surge protection device (SPD) and AC utility. NOTE2: The overvoltage category of the AC input is III. It should be connected to the power distribution.
WARNING! For safety and efficiency, it's very important to use appropriate cables for grid (utility) connection. To reduce risk of injury, please use the proper cable size recommended below. Suggested cable requirement for AC wire
Model
5.5KW
Nominal Grid Voltage
230Vac
Conductor cross-section (mm2)
6
AWG no.
10
6-2. Connecting to the AC Utility Step 1: Check the grid voltage and frequency with an AC voltmeter to see if it’s same as the
“Vac” value on the product label.
Step 2: Turn off the circuit breaker.
Step 3: Remove insulation sleeve 10 mm from three
conductors and shorten phase L and neutral conductor N for 3 mm. Refer to chart 1.
Step 4: Connect wires according to the polarities indicating on terminal block. Be sure to connect PE protective conductor (G) first.
L→LINE (brown or black) N→Neutral (blue or white) G→Ground (yellow-green)
Step 5: Make sure the wires are securely connected. The reference tightening torque is 1.4~1.6N.m.
7. PV Module (DC) Connection
CAUTION: Before connecting to PV modules, please install separately DC circuit breakers
L
N
Chart 1
Chart 2
FSP HySpirit series User Manual 9 http://www.fsp-group.com.tw/en/product/PVInverter.html
between inverter and PV modules.
NOTE1: Please use 600Vdc/30A circuit breaker. NOTE2: The overvoltage category of the PV input is II.
Please follow the steps below to implement PV module connection:
Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 250Vdc-450Vdc (with rated load). This system is applied with two strings of PV array. Please make sure that the maximum current load of each PV input connector is 13A.
Step 2: Disconnect the circuit breaker and switch off the DC switch. Step 3: Assemble provided PV connectors with PV modules by the following steps. Components for PV connectors and Tools:
Female connector housing Female terminal
Male connector housing Male terminal
Crimping tool and spanner
Prepare the cable and follow the connector assembly process:
Strip one cable 8 mm on both end sides and be careful NOT to nick conductors.
Insert striped cable into female terminal and crimp female terminal as shown below.
Insert assembled cable into female connector housing as shown below.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.
WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single crystalline and poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding. CAUTION: It’s requested to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules.
FSP HySpirit series User Manual 10 http://www.fsp-group.com.tw/en/product/PVInverter.html
Insert striped cable into male terminal and crimp male terminal as shown below.
Insert assembled cable into male connector housing as shown below.
Then, use spanner to screw pressure dome tightly to female connector and male connector as shown below.
Step 4: Check the correctness of the polarity of connection cable on PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
WARNING! For safety and efficiency, it's very important to use appropriate cables for PV module connection. To reduce risk of injury, please use the proper cable size as recommended below.
Conductor cross-section (mm2)
AWG no.
4~6
10~12
CAUTION: Never directly touch the terminals of inverter. It might cause lethal electric shock.
FSP HySpirit series User Manual 11 http://www.fsp-group.com.tw/en/product/PVInverter.html
Recommended Panel Configuration
Solar Panel Spec. (reference)
- 260Wp
- Vmp: 30.7Vdc
- Imp: 9.18A
- Voc: 38.9Vdc
- Isc: 8.56A
- Cells: 60
SOLAR INPUT 1
SOLAR INPUT 2
Q'ty of panels
Total Input
Power
(Min in serial: 6pcs;
Max. in serial: 12pcs)
6pcs in serial
x
6pcs
1,560W
x
6pcs in serial
6pcs
1,560W
8pcs in serial
x
8pcs
2,080W
x
8pcs in serial
8pcs
2,080W
6pcs in serial
6pcs in serial
12pcs
3,120W
7pcs in serial
7pcs in serial
14pcs
3,640W
8pcs in serial
8pcs in serial
16pcs
4,160W
10pcs in serial
10pcs in serial
20pcs
5,200W
12pcs in serial
12pcs in serial
24pcs
6,240W
8. Battery Connection
CAUTION: Before connecting to batteries, please separately install a DC circuit breaker between inverter and batteries. NOTE1: Please only use sealed lead acid battery, vented and Gel battery. Please check its maximum charging voltage and current when first using this inverter. If using Lithium iron or Nicd
battery, please consult with installer for the details.
NOTE2: Please use 80Vdc/200A circuit breaker. NOTE3: The overvoltage category of the battery input is II.
Please follow the steps below to implement battery connection: Step 1: Check the nominal voltage of batteries. The nominal input voltage for inverter is 48Vdc. Step 2: Use two battery cables. Remove insulation sleeve 12 mm and insert conductor into cable ring terminal. Refer to the right diagram. Step 3: Remove the cover of battery and follow the polarity of battery printed near the battery terminal! Place the external battery cable ring terminal over the battery terminal.
RED cable to the positive terminal (+); BLACK cable to the negative terminal (-).
CAUTION: Do NOT touch the inverter to avoid electric shock. When PV modules are exposed to sunlight, it may generate DC voltage in the inverter.
FSP HySpirit series User Manual 12 http://www.fsp-group.com.tw/en/product/PVInverter.html
WARNING! Wrong connections may damage the unit permanently. Step 4: Make sure the wires are securely connected. The reference tightening torque is 2.04 N.m. WARNING! For safety and efficiency, it's very important to use appropriate cables for battery
connection. To reduce risk of injury, please use the proper cable size recommended as below.
Conductor cross-section (mm2)
38
AWG no.
2
9. Load (AC Output) Connection
CAUTION: To prevent extra supply to the load via the inverter during any mode of operation, an additional disconnection device should be placed on in the building wiring installation. WARNING! For safety and efficiency, it's very important to use appropriate cable for AC connection. To reduce risk of injury, please use the proper cable size recommended as below.
Model
5.5KW
Nominal Grid Voltage
230Vac
Conductor cross-section (mm2)
6
AWG no.
10
Step 1: Remove insulation sleeve 8 mm for three conductors. And shorten phase L and neutral conductor N 3 mm. Refer to Diagram 3. Step 2: Connect wires according to the polarities indicated on terminal block. Be sure to connect PE
protective conductor ( ) first. Refer to Diagram 4.
L
N
Diagram 3
FSP HySpirit series User Manual 13 http://www.fsp-group.com.tw/en/product/PVInverter.html
L→LINE (brown or black)
→Ground (yellow-green)
N→Neutral (blue or white)
Step 3: Make sure the wires are securely connected. The
reference tightening torque is 1.4~1.6N.m.
CAUTION: It’s only allowed to connect load to “AC Output Connector”. Do NOT connect the utility to “AC Output Connector”. CAUTION: Be sure to connect L terminal of load to L terminal of “AC Output Connector” and N terminal of load to N terminal of “AC Output Connector”. The G terminal of “AC Output Connector” is connected to grounding of the load. Do NOT mis-connect.
CAUTION: This inverter is not allowed to operate in parallel. Please do NOT connect more than one unit in parallel in AC output connector. Otherwise, it will damage this inverter.
Diagram 4