Fronius Type verification test sheet G99 Fronius Tauro 50-3-P [UK] Certificate [EN]

ENA Engineering Recommendation G99
This form should be used by the Manufacturer to demonstrate and declare compliance with the requirements of EREC G99. The form can be used in a variety of ways as detailed below:
1. To obtain Fully Type Tested status (50kW) The Manufacturer can use this form to obtain Fully Type Tested status for a Power
Generating Module by registering this completed form with the Energy Networks Association (ENA) Type Test Verification Report Register. Tests 1 – 15 must all be completed and compliant for the Power Generating Module to be classified as Fully Type Tested.
2. To obtain Type Tested status for a product This form can be used by the Manufacturer to obtain Type Tested status for a product which is used in a Power Generating Module by registering this form with the relevant parts completed with the Energy Networks Association (ENA) Type Test Verification Report Register. Where the Manufacturer is seeking to obtain Type Tested status for an Interface Protection device the appropriate section of Form A2-4 should be used.
3. One-off Installation This form can be used by the Manufacturer or Installer to confirm that the Power Generating Module has been tested to satisfy all or part of the requirements of this EREC G99. This form shall be submitted to the DNO as part of the application.
A combination of (2) and (3) can be used as required, together with Form A2-4 where compliance of the Interface Protection is to be demonstrated on site.
Note: Within this Form A2-3 the term Power Park Module will be used but its meaning can be interpreted within Form A2-3 to mean Power Park Module, Generating Unit or Inverter as appropriate for the context. However, note that compliance must be demonstrated at the Power Park Module level.
If the Power Generating Module is Fully Type Tested and registered with the Energy Networks Association (ENA) Type Test Verification Report Register, the Installation Document (Form A3) should include the Manufacturer’s reference number (the Product ID), and this form does not need to be submitted.
Where the Power Generating Module is not registered with the ENA Type Test Verification Report Register or is not Fully Type Tested this form (all or in parts as applicable) needs to be completed and provided to the DNO, to confirm that the Power Generating Module has been tested to satisfy all or part of the requirements of this EREC G99.
Manufacturer´s reference number
Tauro 50-3-P
PGM technology
IGBT power modules, transformerless
Manufacturer name
Fronius International GmbH
Adress
Guenter Fronius Str.1 4600 Wels-Thalheim, Austria
Tel
+43-7242-241-0
Fax
+43-7242-241-224
Issue 1 – Amendment 8 2021
R&D - TESTING TR31969 page 1 of 14
FORM A2-3 Compliance Verification Report for Type A Inverter
Connected Power Generating Modules
@BCL@40080E81.doc Backup: Tauro General
ENA Engineering Recommendation G99
E:mail
pv@fronius.com
Web site
www.fronius.com
Registered Capacity
50 kW
Manufacturer compliance declaration. - I certify that all products supplied by the company with the above Type Tested Manufacturer’s reference number will be manufactured and tested to ensure that they perform as stated in this document, prior to shipment to site and that no site Modifications are required to ensure that the product meets all the requirements of EREC G99.
Signed
On behalf of
Fronius International GmbH
Note that testing can be done by the Manufacturer of an individual component or by an external test house.
Where parts of the testing are carried out by persons or organisations other than the Manufacturer then that person or organisation shall keep copies of all test records and results supplied to them to verify that the testing has been carried out by people with sufficient technical competency to carry out the tests.
Issue 1 – Amendment 8 2021
R&D - TESTING TR31969 page 2 of 14
@BCL@40080E81.doc Backup: Tauro General
ENA Engineering Recommendation G99
1. Operating Range: Tests should be carried with the Power Generating Module operating at
Registered Capacity and connected to a suitable test supply or grid simulation set. The power
supplied by the primary source shall be kept stable within ± 5 % of the apparent power value set for the entire duration of each test sequence.
Frequency, voltage and Active Power measurements at the output terminals of the Power Generating Module shall be recorded every second. The tests will verify that the Power Generating Module can operate within the required ranges for the specified period of time.
The Interface Protection shall be disabled during the tests. In case of a PV Power Park Module the PV primary source may be replaced by a DC source.
In case of a full converter Power Park Module (eg wind) the primary source and the prime mover Inverter/rectifier may be replaced by a DC source. Pass or failure of the test should be indicated in the fields below (right hand side), for example with the statement “Pass”, “No disconnection occurs”, etc. Graphical evidence is preferred.
Note that the value of voltage stated in brackets assumes a LV connection. This should be adjusted for HV as required.
Test 1 Voltage = 85% of nominal (195.5 V),
Frequency = 47.0 Hz, Power factor = 1, Period of test 20 s
Test 2 Voltage = 85% of nominal (195.5 V),
Frequency = 47.5 Hz, Power factor = 1, Period of test 90 minutes
Issue 1 – Amendment 8 2021
R&D - TESTING TR31969 page 3 of 14
@BCL@40080E81.doc Backup: Tauro General
ENA Engineering Recommendation G99
Test 3 Voltage = 110% of nominal (253 V),
Frequency = 51.5 Hz, Power factor = 1, Period of test 90 minutes
Test 4 Voltage = 110% of nominal (253 V),
Frequency = 52.0 Hz, Power factor = 1, Period of test 15 minutes
Test 5 Voltage = 100% of nominal (230 V),
Frequency = 50.0 Hz, Power factor = 1, Period of test 90 minutes
Issue 1 – Amendment 8 2021
R&D - TESTING TR31969 page 4 of 14
@BCL@40080E81.doc Backup: Tauro General
ENA Engineering Recommendation G99
Test 6 RoCoF withstand Confirm that the Power Generating Module is
capable of staying connected to the Distribution Network and operate at rates of change of frequency up to 1 Hzs-1 as measured over a period of 500 ms. Note that this is not expected to be demonstrated on site.
Measurement before jump (50Hz)
Measurement jump (51Hz)
Remark: During the tests 1, 2, 3, 4,5 and 6 the unit does not disconnect, tests have been passed.
Issue 1 – Amendment 8 2021
R&D - TESTING TR31969 page 5 of 14
@BCL@40080E81.doc Backup: Tauro General
Loading...
+ 9 hidden pages